dlO-diesel lOcOMOtiVe cable

advertisement
dlO-diesel lOcOMOtiVe cable
90°c 2000 VOlt dlO, ul rHH/rHw 600 VOlt,
csa r90 1000 VOlt
APPLICATIonS
Suitable for use as follows:
• Diesel electric locomotives
• Telecom power supply
• Oil and gas drilling rigs
• Mining and earth-moving equipment
• Shipyards
• Motor leads
• Where flexible power leads must be installed in conduit or raceways
STAndARdS
&
REFEREnCES
• UL Listed
• Accepted for listing by MSHA
• CSA R90
• RoHS Compliant
ConSTRUCTIon
• Conductor:
10 AWG through 777.7 MCM stranded tinned annealed copper per AAR 589
90°c temperature
Rating
• Insulation:
excellent impact and
abrasion resistance
• Jacket:
resists oils, acids,
Alkalies, Heat, Flame
• Sample Jacket Marking:
flexible tinned
Copper Stranding
ft4 upon request
Premium-grade 90°C EP
VIPER™ CPE, black
SIZES 10 THROUGH 1 AWG – SOUTHWIRE VIPER™ (SIZE) (STRANDING) 90°C DLO
2000 VOLTS P-7K-123040 MSHA CSA R90 1000V (UL) RHH or RHW 600 VOLTS
SIZES 1/0 THROUGH 646.4 – SOUTHWIRE VIPER™ (SIZE) 90°C DLO
2000 VOLTS P-7K-123040 MSHA CSA R90 1000V (-40°C) FT-1 – (UL) RHH or RHW
600 VOLTS SUNLIGHT RESISTANT FOR CT USE
NOTE: (535.3 AND 646.4 MCM printed (UL) RHH OR RHW 2000 VOLTS)
SIZE 777.7 MCM ONLY – SOUTHWIRE VIPER™ C(UL) TYPE RHW-2 2KV VW-1 FOR CT
USE TYPE DLO 2000V 90°C P-102 MSHA
PACKAGInG
• Lengths cut to order
• Some constructions subject to minimum order quantity
WEIG H T S ,
ME A S U R E M E N T S
Nominal Insulation
Thickness
A ND
P ACK A GI N G
NOMINAL Overall
diameter
CURRENT
AMPS*
inches
mm
inches
mm
1
2
APPROX.
NET weight
lbs/m'**
27/24
0.045
1.14
0.26
6.60
40
55
60
8
37/24
0.060
1.52
0.34
8.64
55
80
95
6
61/24
0.060
1.52
0.40
10.16
75
105
145
4
105/24
0.060
1.52
0.46
11.68
95
140
205
2
154/24
0.060
1.52
0.52
13.21
130
190
295
AWG
or mcm
CONDUCTOR
STRAND
10
1
224/24
0.080
2.03
0.65
16.51
150
220
440
1/0
280/24
0.080
2.03
0.69
17.53
170
260
515
2/0
329/24
0.080
2.03
0.73
18.54
195
300
580
3/0
456/24
0.080
2.03
0.81
20.57
225
350
770
930
4/0
551/24
0.080
2.03
0.87
22.10
260
405
262.6
646/24
0.095
2.41
1.00
25.40
296
467
1130
313.3
777/24
0.095
2.41
1.06
26.92
326
522
1295
373.7
925/24
0.095
2.41
1.10
27.94
362
591
1545
1820
444.4
1110/24
0.095
2.41
1.23
31.24
400
652
535.3
1332/24
0.120
3.05
1.34
34.04
445
728
2195
646.4
1600/24
0.120
3.05
1.45
36.83
493
815
2560
777.7
1924/24
0.120
3.05
1.50
38.10
910
904
3050
* (1) A
mpacities based on 90°C Conductor and 30°C Ambient temperature based on Table 310.16 in the
National Electrical Code® for not more than three current-carrying conductors in raceway, cable or earth.
(2) Ampacities based on single-conductor in free air, in accordance with National Electrical Code® Table 310.17.
** Actual shipping weight may vary.
dlo-Diesel Locomotive Cable 90°C 2000 Volt DLO, UL RHH/RHW 600 Volt, CSA R90 1000 Volt
I ND U S T R I A L
CORD
Download