E LECTRICAL
ELECTRICAL
Cables
April 24, 2007
CONDUMEX INCORPORATED
WIRE & CABLE PRODUCT INDEX
BUILDING WIRE
! MTW/THHN/THWN 600 VOLTS COPPER 14 AWG SOLID 750 MCM
STRANDED UL 83
! XHHW-2 600 VOLTS COPPER 14 AWG 1000 MCM STRANDED UL 44
! RHH-RHW-USE 600 VOLTS COPPER (XLP) 6 AWG 1000 MCM STRANDED UL 44
POWER CABLE
!
!
!
!
!
PRIMARY URD CABLES, 15 KV 35 KV, 100% & 133% INSULATION
LEVELS, COPPER OR ALUMINUM CONDUCTOR, EPR OR TR-XLP
INSULATION, CONCENTRIC COPPER WIRE NEUTRAL, WITH OR WITHOUT
ENCAPSULATING JACKET OVERALL
SPECIFICATIONS: ICEA S-94-649 & AEIC CS8
TYPE MV-90 & MV-105 (EPR INSULATION ONLY FOR MV-105) POWER CABLE, 5 KV - 35
KV, 100% & 133% INSULATION LEVELS, COPPER CONDUCTOR, EPR OR XLP
INSULATION, COPPER DRAIN WIRE OR COPPER TAPE METALLIC SHIELD, BLACK PVC
SUNLIGHT RESISTANT JACKET. SINGLE CONDUCTOR CONSTRUCTION.
LISTED UL 1072; SPECIFICATIONS: ICEA S-93-639 & AEIC CS8
TYPE MC ARMORED CABLES, 600 VOLTS, 5 KV - 15 KV, MULTI-CONDUCTOR
STRANDED COPPER, EPR OR XLP INSULATION, ALUMINUM OR GALVANIZED STEEL
INTERLOCKED ARMOR, PVC SUNLIGHT RESISTANT JACKET OVERALL. UL 1569
HIGH VOLTAGE POWER CABLES UP TO 138 KV, COPPER OR ALIMINUM CONDUCTOR,
XLP UNSULATION, METALLIC SHIELD,PVC JACKET.SPECIFICATION: AEIC Cs7
BARE OVERHEAD CONDUCTORS, TYPES AAC AND ACSR, PER ASTM B230 & B232
TRAY CABLE
! TYPE TC/THHN 600 VOLTS COPPER 14 AWG STRANDED 750 MCM
STRANDED, 3 AND/OR 4 CONDUCTOR, WITH OR WITHOUT BARE
GROUND WIRE (SIZES 8 AWG AND LARGER), UP TO 16 CONDUCTOR
FOR SIZES 14, 12 AND 10 AWG UL 1277
! TYPE TC/XHHW-2 600 VOLTS COPPER 14 AWG STRANDED 750 MCM
STRANDED, 3 AND/OR 4 CONDUCTOR, WITH OR WITHOUT BARE
GROUND WIRE (SIZES 8 AWG AND LARGER), UP TO 16 CONDUCTOR
FOR SIZES 14, 12 AND 10 AWG UL 1277
SPECIAL PURPOSE CABLES
! TYPE RHH-RHW 2000 VOLTS, (DLO), SINGLE CONDUCTOR TINNED COPPER, ROPE-LAY
STRANDED, EPR INSULATION, SEPARATOR, BLACK CSPE JACKET. CONDUCTOR SIZES
4 AWG 1 AWG UL LISTED AS VW-1; SIZES 1/0 AWG 929.2 MCM UL LISTED FOR “CT
USE”, CSA LISTED AS FT4. SIZE 1111 MCM IS PER ICEA S-68-516.
TYPE THHN OR THWN 600 VOLTS
DESCRIPTION
1) Annealed bare solid (14-10 AWG),
annealed bare stranded class C
concentric round (14-2 AWG),
compressed stranding class B
(1 AWG - 1000 MCM) copper conductor.
2) Polyvinyl chloride (PVC insulation)
3) Nylon overall protective jacket.
APPLICATION
General use in commercial and industrial
construction, and installations where
resistance against oils and gasoline is
required. May be used for power and
control circuits in recognized raceways, in
wet or dry locations, and in presence of
gases, gasoline and chemicals. Also
suitable as machine tool and switchboard
wiring.
MAXIMUM OPERATING VOLTAGE
600 volts
MAXIMUM CONDUCTOR TEMPERATURE
Dry locations (THHN)
Dry and wet locations (THWN)
In oil (Oil resistant II)
90° C
75° C
75° C
FEATURES
1) Good resistance to moisture, heat, oil,
gasoline, chemicals and grease.
2) Suitable for installation where thermal
overload exists.
3) Strict quality control during
manufacturing process.
4) Flame retardant, UL listed as VW-1.
5) Smooth nylon jacket aids in easier
pulling.
6) Superior abrasion and mechanical
properties.
7) Sizes 1/0 and larger are marked "For
CT use", and are approved for installation
in cable trays. Sunlight resistant in
Accordance with NEC Article 318.
3
Size
AWG/
kcmil
2
1
Overall
Jacket
Number Conductor Conductor Insulation
Diameter Thickness Thickness Diameter
Area
of
inch
mils
mils
mils
kcmil
Strands
Net
Weight
lb/mft
4.1
0.06
15
5
0.10
16
1 Solid
6.5
0.08
15
5
0.12
23
1 Solid
10.3
0.10
20
5
0.15
37
14
19
4.1
0.07
15
5
0.12
17
12
19
6.5
0.09
15
5
0.14
26
10
19
10.3
0.11
20
5
0.17
40
8
19
16.5
0.15
30
5
0.23
65
6
19
26.2
0.18
30
6
0.26
99
4
19
41.7
0.23
40
6
0.34
157
3
19
52.6
0.26
40
7
0.36
197
2
19
66.3
0.29
40
7
0.39
241
1
19
83.7
0.32
50
7
0.45
306
1/0
19
106
0.37
50
8
0.50
380
2/0
19
133
0.41
50
8
0.54
472
3/0
19
168
0.47
50
8
0.59
587
211
14
1 Solid
12
10
4/0
19
0.52
50
8
0.65
729
250
37
0.57
60
9
0.72
870
300
37
0.62
60
9
0.78
1033
350
37
0.67
60
9
0.83
1196
400
37
0.72
60
9
0.87
1359
500
37
0.80
60
9
0.96
1685
600
61
0.88
70
10
1.06
2023
SPECIFICATIONS
750
61
0.98
70
10
1.15
2454
UL-83
1000
61
1.14
70
10
1.27
3347
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
HOW TO ORDER
VINANEL® Nylon, solid or stranded type
THHN or THWN, 600 volts, size, color and length
NATIONAL ELECTRICAL CODE REFERENCE
Ampacities
Article 3 10-15
Conduit fill tables
Switchboard wiring
Article 384
Chapter 9
Condumex Wire and Cable
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
02-06
1
POWER CABLE TYPE TC
THHN/THWN 600 VOLTS
DESCRIPTION
1) Annealed bare Class C concentric
strand copper conductors.
2) Polyvinyl Chloride (PVC) thermoplastic
insulation.
3) Nylon protective covering.
4) Binder tape over core.
5) Overall flame retardant PVC jacket.
APPLICATION
Condumex Type TC cable may be used for power,
lighting, control, signal and communcation circuits,
in raceways, direct burial in earth, or in
messenger. Type TC cable may be used in wet or
dry locations and in the presence of oil and most
chemicals in accordance with the National
Electrical Code
Size
AWG
14
MAXIMUM OPERATING VOLTAGE
600 volts
Number
of
Strands
19
3
2
1
Number
of
Conductors
Jacket
Thickness
mils
Overall
Diameter
inches
Net
Weight
lb/Mft
2
45
0.34
68
3
45
0.36
87
4
45
0.40
109
5
45
0.43
130
7
45
0.46
167
9
60
0.56
234
MAXIMUM CONDUCTOR TEMPERATURE
12
60
0.63
285
Wet or Dry
Dry
16
60
0.67
335
2
45
0.38
90
3
45
0.40
119
4
45
0.43
154
5
45
0.46
173
7
60
0.55
247
75° C
90° C
FEATURES
1) UL listed for direct burial.
2) Flame retardant, (passes UL 1277, 70,000
BTU flame test.
3) Sunlight resistant; can be installed outdoors.
4) UL listed as Type TC for power and control
tray cable used in accordance with the National
Electrical Code.
O
5) PVC jacket is UL rated 90 C and listed Oil
Resistant I.
6) Acceptable for Class I, Division 2, Hazardous
Location Applications. Type TX offers
substantial cost savings over the previously
required metallic sheathed cables.
7) Circuit identification; color coded per ICEA
S-73-532 (table E-2 or Method S/B 4.)
7a) Other color coding methods are available,
based on ICEA S-73-532
12
10
SPECIFICATIONS
UL 1277 and UL 83
HOW TO ORDER
Condumex Tray Cable Type TC/THHN,
600 volts, number and size of conductors.
Condumex Wire and Cable
03-06
2
4
5
19
19
9
60
0.64
326
12
60
0.71
400
16
60
0.76
485
2
45
0.45
139
3
45
0.47
180
4
60
0.55
247
5
60
0.60
178
7
60
0.65
367
9
60
0.75
480
12
80
0.89
637
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
POWER CABLE TYPE TC
THHN/THWN 600 VOLTS
DESCRIPTION
1) Annealed bare Class C (8-2 AWG)
compressed stranded Class B (1/0 AWG750 kcmil) copper conductors.
2) Polyvinyl Chloride thermoplastic insulation
3) Nylon protective covering.
4) Fillers
5) Binder tape over core
6) Overall flame retardant PVC jacket.
APPLICATION
Condumex Type TC cable may be used for
power, lighting, control, signal and
communication circuits, in raceways, direct
cable may be used in wet or dry locations
and in the presence of oil and most chemicals
in accordance with the National Electrical Code.
MAXIMUM OPERATING VOLTAGE
600 volts
MAXIMUM CONDUCTOR TEMPERATURE
Wet or Dry
Dry
75° C
90° C
FEATURES
1) UL listed for direct burial.
2) Flame retardant, (passes UL 1277, 70,000
BTU flame test.)
3) Sunlight resistant; can be installed outdoors.
4) UL listed as Type TC for power and control
tray cable use in accordance with the National
Electrical Code.
5) PVC jacket is UL rated 90° C and listed Oil
Resistant I.
6) Acceptable for Class I, Division 2, Hazardous
Location Applications. Type TC offers
substantial cost savings over the previously
required metallic sheathed cables.
7) Circuit identification; color coded per ICEA
S-73-532 (table E-2 or Method S/B 4.)
7a) Other color coding methods are available,
based on ICEA S-73-532
5
6
Size
AWG/kcmil
Number
of
Conductors
4
3
Ground
Insulation
Jacket
Conductor Thickness Thickness
AWG
mils
mils
2
1
Overall
Diameter
inch
Net
Weight
lb/Mft
8
3
10
30/5
60
0.638
338
6
3
8
30/5
60
0.698
448
4
3
6
40/7
80
0.884
693
2
3
6
40/7
80
1.015
1012
1/0
3
6
50/8
80
1.223
1495
2/0
3
6
50/8
80
1.320
1858
3/0
3
4
50/8
80
1.428
2297
4/0
3
4
50/8
80
1.549
2791
250
3
4
60/9
80
1.760
3374
350
3
3
60/9
110
1.980
4526
500
3
2
60/9
110
2.260
6230
750
3
1
70/10
110
2.967
8845
1/0
4
6
50/8
80
1.350
1913
2/0
4
6
50/8
80
1.457
2311
4/0
4
4
50/8
110
1.773
3597
350
4
3
60/9
110
2.188
5754
500
4
2
60/9
110
2.502
8018
750
4
1
70/10
140
3.057
11716
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
SPECIFICATIONS
UL 1277 and UL 83
HOW TO ORDER
Condumex Tray Cable Type TC/THHN,
600 volts, number and size of conductors.
Condumex Wire and Cable
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
03-06
3
VULCANEL® MEDIUM VOLTAGE
XLPE OR EPR NON-SHIELDED
WET OR DRY POWER CABLE 5 KV
DESCRIPTION
1) Annealed bare stranded class B compact
copper conductor.
2) Extruded semiconducting strand shield.
3) Ethylene propylene (EPR) or cross-linked
polyethylene (XLPE) insulation.
4) Polyvinyl chloride (PVC) protective jacket.
APPLICATION
VULCANEL® 5kv Non-shielded power cables
are ideally suited for use in industrial and
utility applications where shields cannot be
adequate for proper termination of the shielding.
MAXIMUM CONDUCTOR TEMPERATURE
Normal Operation
105° C
Emergency Overload
130° C
Short Circuit
250° C
FEATURES
1) Simultaneous extrusion of strand shield,
insulation and insulation shield (triple
extrusion) results in a virtually perfect
cable core.
2) XLPE insulation offers:
- Low moisture absorption.
- Good resistance to chemicals.
- Very low dielectric loss
EPR insulation offers:
- Excellent heat, moisture and corona
resistance.
- Electrical stability under stress
- Low dielectric loss
- Chemical resistance
3) Easy-stripping insulation shield
4) The external PVC jacket is resistant to
abrasion, ozone and moisture.
5) UL listed as MV-105, sunlight resistant,
direct burial. Optional marking "For CT
use" available on single conductor in
accordance with the National Electrical
Code.
4
3
2
Size Number Conductor Insulation Insulation Jacket
Overall
AWG/
of
Diameter Thickness Diameter Thickness Diameter
kcmil Strands
inch
inch
inch
mils
Inch
1
Net Weight
Lb/Mft
XLPE
EPR
5kV 133% Insulation Level, 115 mils Insulation Thickness
8
7
0.14
125
0.43
80
0.60
190
201
6
7
0.17
125
0.47
80
0.64
234
245
4
7
0.22
125
0.52
80
0.68
298
310
2
7
0.27
125
0.57
80
0.74
394
409
1/0
19
0.34
125
0.64
80
0.80
539
557
2/0
19
0.38
125
0.68
80
0.85
639
658
3/0
19
0.43
125
0.73
95
0.92
788
808
4/0
19
0.48
125
0.78
95
0.97
944
966
250
37
0.52
140
0.87
110
1.09
1143
1171
350
37
0.62
140
0.96
110
1.19
1496
1527
500
37
0.74
140
1.08
110
1.31
2014
2030
750
61
0.91
155
1.29
125
1.55
2950
2998
1000
61
1.06
155
1.44
125
1.70
3799
3854
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
SPECIFICATIONS
ICEA S-68-516, AEIC CS-6-87 (EPR)
ICEA S-66-524, AEIC CS-S (XLP)
UL 1072
HOW TO ORDER
VULCANEL® EPR/XLPE Non-Shielded power
cable, voltage and insulation level, conductor
size and type, length and reel dimensions.
National Electrical Code References:
Ampacities
Cable Trays
Type MV
310-15
318
326
Page 1 of 2
Condumex Wire and Cable
07-04
4
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
VULCANEL® MEDIUM VOLTAGE
XLPE OR EPR NON-SHIELDED
WET OR DRY POWER CABLE 5 KV
Size Number Conductor Insulation Insulation Jacket
Overall
AWG/
of
Diameter Thickness Diameter Thickness Diameter
kcmil Strands
inch
inch
inch
mils
Inch
Net Weight
lb/Mft
XLPE
EPR
15kV 133% Insulation Level, 220 mils Insulation Thickness
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
7
19
19
19
19
37
37
37
61
61
0.14
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.06
125
125
125
125
125
125
125
125
140
140
140
155
155
0.43
0.47
0.52
0.57
0.64
0.68
0.73
0.78
0.87
0.96
1.08
1.29
1.44
80
80
80
80
80
80
95
95
110
110
110
125
125
0.60
0.64
0.68
0.74
0.80
0.85
0.92
0.97
1.09
1.19
1.31
1.55
1.70
190
234
298
394
539
639
788
944
1143
1496
2014
2950
3799
201
245
310
409
557
658
808
966
1171
1527
2030
2998
3854
0.60
0.64
0.68
0.74
0.80
0.85
0.92
0.97
1.09
1.19
1.31
1.55
1.70
190
234
298
394
539
639
788
944
1143
1496
2014
2950
3799
201
245
310
409
557
658
808
966
1171
1527
2030
2998
3854
0.60
0.64
0.68
0.74
0.80
0.85
0.92
0.97
1.09
1.19
1.31
1.55
1.70
190
234
298
394
539
639
788
944
1143
1496
2014
2950
3799
201
245
310
409
557
658
808
966
1171
1527
2030
2998
3854
25kV 100% Insulation Level, 260 mils Insulation Thickness
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
7
19
19
19
19
37
37
37
61
61
0.14
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.06
125
125
125
125
125
125
125
125
140
140
140
155
155
0.43
0.47
0.52
0.57
0.64
0.68
0.73
0.78
0.87
0.96
1.08
1.29
1.44
80
80
80
80
80
80
95
95
110
110
110
125
125
35kV 100% Insulation Level, 345 mils Insulation Thickness
8
6
4
2
1/0
2/0
3/0
4/0
250
350
500
750
1000
7
7
7
7
19
19
19
19
37
37
37
61
61
0.14
0.17
0.22
0.27
0.34
0.38
0.43
0.48
0.52
0.62
0.74
0.91
1.06
125
125
125
125
125
125
125
125
140
140
140
155
155
0.43
0.47
0.52
0.57
0.64
0.68
0.73
0.78
0.87
0.96
1.08
1.29
1.44
80
80
80
80
80
80
95
95
110
110
110
125
125
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
Page 2 of 2
Condumex Wire and Cable
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
07-04
5
1
VULCANEL® MEDIUM VOLTAGE EPR
SHIELDED POWER CABLES 5, 15, 25, 35 KV
DESCRIPTION
1) Annealed bare stranded class B compact
copper conductor.
2) Extruded semiconducting strand shield.
3) Ethylene propylene rubber (EPR) insulation.
4) Extruded semiconducting insulation shield.
5) Annealed copper tape shield (25% overlap
minimum).
6) Polyvinyl chloride (PVC) protective jacket.
5
6
4
3
2
1
APPLICATION
Three-phase electrical distribution systems.
Suitable for use in overhead installations,
recognized raceways, direct burial or cable
trays.
MAXIMUM CONDUCTOR TEMPERATURE
Normal Operation
105 °C
Emergency Overload
130 °C
Short Circuit
250 °C
FEATURES
1) Simultaneous extrusion of strand shield,
insulation and insulation shield (triple
extrusion) results in a virtually perfect
cable core.
2) EPR insulation offers:
- Excellent heat, moisture and corona
resistance.
- Electrical stability under stress
- Low dielectric loss
- Chemical resistance
3) Easy-stripping insulation shield
4) Tape shield provides high short circuit
capabilities and uniform shield impedance.
5) The external PVC jacket is resistant to
abrasion, ozone and moisture.
6) UL listed as MV-105, sunlight resistant,
direct burial. Optional marking "For CT
use" available on single conductor in
accordance with the National Electrical
Code.
SPECIFICATIONS
ICEA S-68-516, AEIC CS6-87
UL 1072
HOW TO ORDER
VULCANEL® EPR shielded power cable,
voltage and insulation level, conductor
size and type, length and reel dimensions.
National Electrical Code References:
Ampacities
310-15
Cable Trays
318
Type MV
326
Size
AWG/kcmil
Number
of
Strands
Conductor Insulation Insul. Shld. Jacket
Overall
Net
Diameter Thickness Diameter Thickness Diameter Weight
Inch
inch
inch
mils
Inch
lb/Mft
5kV 133% Insulation Level, 115 mils Insulation Thickness
6
7
0.17
0.45
0.53
60
0.67
290
4
7
0.22
0.49
0.57
60
0.71
357
2
7
0.27
0.55
0.63
60
0.74
478
1/0
19
0.34
0.62
0.70
80
0.85
668
2/0
19
0.38
0.66
0.74
80
0.92
775
3/0
19
0.43
0.71
0.79
80
0.97
933
4/0
19
0.48
0.76
0.84
80
1.02
1071
250
37
0.52
0.81
0.90
80
1.07
1226
350
37
0.62
0.91
0.99
80
1.17
1560
500
37
0.74
1.03
1.13
80
1.32
2150
750
61
0.91
1.21
1.32
80
1.50
3027
1000
61
1.11
1.36
1.46
80
1.64
3845
5kV 100% Insulation Level, 175 mils Insulation Thickness
2
7
0.27
0.67
0.75
80
0.93
570
1/0
19
0.34
0.74
0.82
80
1.00
736
2/0
19
0.38
0.78
0.86
80
1.04
849
3/0
19
0.43
0.83
0.91
80
1.09
1010
4/0
19
0.48
0.88
0.96
80
1.14
1190
250
37
0.52
0.94
1.02
80
1.20
1330
350
37
0.62
1.03
1.14
80
1.32
1753
500
37
0.74
1.16
1.26
80
1.44
2280
750
61
0.91
1.34
1.44
80
1.62
3142
1000
61
1.11
1.36
1.59
110
1.83
5794
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
Page 1 of 2
Condumex Wire and Cable
07-04
6
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
VULCANEL® MEDIUM VOLTAGE EPR
SHIELDED POWER CABLES 5, 15, 25, 35 KV
Size
AWG/kcmil
Number
of
Strands
Conductor Insulation Insul. Shld. Jacket
Overall
Net
Diameter Thickness Diameter Thickness Diameter Weight
Inch
inch
inch
mils
Inch
lb/Mft
15kV 133% Insulation Level, 220 mils Insulation Thickness
6
7
0.17
0.45
0.53
60
0.67
290
4
7
0.22
0.49
0.57
60
0.71
357
2
7
0.27
0.55
0.63
60
0.74
478
1/0
19
0.34
0.62
0.70
80
0.85
668
2/0
19
0.38
0.66
0.74
80
0.92
775
3/0
19
0.43
0.71
0.79
80
0.97
933
4/0
19
0.48
0.76
0.84
80
1.02
1071
250
37
0.52
0.81
0.90
80
1.07
1226
350
37
0.62
0.91
0.99
80
1.17
1560
500
37
0.74
1.03
1.13
80
1.32
2150
750
61
0.91
1.21
1.32
80
1.50
3027
1000
61
1.11
1.36
1.46
80
1.64
3845
25kV 100% Insulation Level, 260 mils Insulation Thickness
1/0
19
0.34
0.92
1.00
80
1.18
894
2/0
19
0.38
0.96
1.04
80
1.22
1009
3/0
19
0.43
1.00
1.11
80
1.29
1181
4/0
19
0.48
1.06
1.16
80
1.34
1394
250
37
0.52
1.11
1.22
80
1.40
1537
350
37
0.62
1.21
1.31
80
1.49
1936
500
37
0.74
1.33
1.43
80
1.61
2516
750
61
0.91
1.51
1.61
110
1.85
3620
1000
61
1.11
1.66
1.80
110
2.04
4543
35kV 100% Insulation Level, 345 mils Insulation Thickness
1.09
1.19
80
1.37
1041
0.38
113
1.23
80
1.41
1226
0.43
1.18
1.28
80
1.46
1380
1/0
19
0.34
2/0
19
3/0
19
4/0
19
0.48
1.23
1.33
80
1.51
1569
250
37
0.52
1.29
1.39
80
1.57
1750
350
37
0.62
1.38
1.49
80
1.67
2163
500
37
0.74
1.50
1.61
110
1.85
2893
750
61
0.91
1.68
1.83
110
2.07
3900
2.21
110
1.97
1.83
1.11
61
1000
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
4807
Page 2 of 2
Condumex Wire and Cable
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
07-04
5-05
1
7
MINING CABLE EPR TYPE SHD-GC
THREE CONDUCTOR 5000 VOLTS
18.SHD-GC.01
DESCRIPTION
1) Three flexible annealed tinned copper
rope-lay stranded conductors.
2) Extruded semi-conducting conductor shield
and ethylene propylene rubber (EPR) insulation.
3) Color coded cotton/copper braid shield
applied over semi-conducting tape.
4) Two annealed tinned copper rope-lay stranded
5
7
6
3
4
2
1
grounding conductors.
5) Annealed tinned copper rope-lay stranded
ground check conductor, yellow EPR insulation
and covered with a yellow cotton braid.
6) Rubberized cotton binder tape.
Overall
Ground
Ground
Size Number of Conductor Insulation
7) Nylon web reinforced extra-heavy-duty
Check Size Diameter
Size
Diameter Thickness
AWG/ Strands
chlorosulfonated polyethylene (CSPE) jacket.
inch
AWG
AWG
mils
inch
/AWG
kcmil
Net
Weight
lb/mft
APPLICATION
6
7x30/29
0.20
110
10
8
1.56
1675
4
7x47/29
0.25
110
8
8
1.68
1888
2
7x74/29
0.31
110
6
8
1.87
2322
1
7x37/25
0.35
110
5
8
1.95
2653
1/0
7x47/25
0.39
110
4
8
2.08
3068
2/0
7x60/25
0.45
110
3
8
2.20
3504
MAXIMUM OPERATING VOLTAGE
5,000 volts
3/0
7x75/25
0.50
110
2
8
2.36
4206
4/0
19x35/25
0.59
110
1
8
2.50
5023
MAXIMUM CONDUCTOR TEMPERATURE
Normal continuous
90° C
130° C
Overload
Short circuit
250° C
300
19x49/25
0.69
120
1/0
8
2.81
6371
350
19x58/25
0.76
120
2/0
8
2.95
7654
Trailing cable on ac mining equipment
where service conditions are severe and
maximum safety is mandatory, such as
power shovels and draglines in open-pit
mines, quarries, gantry cranes and slag
reclaiming. Also used for medium voltage
distribution in underground mines where
frequent relocation is necessary.
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
FEATURES
1) Special tinned copper stranded conductors
designed for flexibility and resistance to
fatigue resulting from bending and flexing.
2) Ground check conductor facilitates fail-safe
ground monitoring for maximum safety.
3) EPR insulation offers excellent heat and moisture
resistance, outstanding corona resistance,
high dielectric strength and chemical resistance.
4) Prevulcanized thermosetting non-wicking fillers
are used if necessary to obtain a substantially
round configuration.
5) PLCV-Cured extra-heavy-duty CSPE, reinforced
with a nylon webbing, provides a tough, defense
mechanical resistant jacket.
6) Acceptance No. P-218-1-MSHA by Mines Safety
and Health Administration Approval No. P-218-1-MSHA
by the Pennsylvania Department of Environmental
Resources. Meets MSHA flame test requirements.
SPECIFICATIONS
ICEA-S-68-516
HOW TO ORDER
Condumex Mining Cable EPR type SHD-GC
three conductor cable, voltage size and
length.
Condumex Wire and Cable
07-04
8
1
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
POWER CABLE TYPE TC
XHHW 600 VOLTS
DESCRIPTION
1) Annealed bare stranded compressed
Class B copper conductors.
2) Cross-Linked polyethylene, thermosetting
XLPW insulation.
3) Fillers (if required)
4) Binder tape over core.
5) Overall flame retardant PVC jacket.
APPLICATION
Condumex Type TC cable may be used for power,
lighting, control, signal and communication circuits,
in cable trays, raceways, direct burial, or on
messenger. Type TC cable may be used in wet
or dry locations and in the presence of oil and
most chemicals in accordance with the
National Electrical Code.
MAXIMUM OPERATING VOLTAGE
600 volts
MAXIMUM CONDUCTOR TEMPERATURE
O
Normal
90 C
Overload
130O C
FEATURES
1) UL listed for direct burial.
2) Flame retardant, (passes UL 1277 70,000
BTU flame test.)
3) Sunlight resistant; can be installed outdoors.
4) UL listed as Type TC for power and control
tray cable, use in accordance with the
National Electrical Code.
5) PVC jacket is UL rated 90O C and listed Oil
Resistant I.
6) Acceptable for Class 1, Division 2, Hazardous
Locations applications.
SPECIFICATIONS
UL 1277
HOW TO ORDER
Condumex Tray Cable Type TC/XHHW, 600
Volts number and size of conductors, with or
without grounding conductor.
Condumex Wire and Cable
5
Size
AWG/kcmil
4
Number
of
Conductors
3
2
Ground
Insulation
Jacket
Conductor Thickness Thickness
AWG
mils
mils
1
Overall
Diameter
inch
Net
Weight
lb/Mft
8
3
10
45
60
0.66
336
6
3
8
45
60
0.74
474
4
3
8
45
80
0.88
691
2
3
6
45
80
1.03
1015
1/0
3
6
55
80
1.21
1501
2/0
3
4
55
80
1.31
1861
3/0
3
4
55
80
1.42
2255
4/0
3
4
55
80
1.54
2735
250
3
4
65
110
1.75
3298
350
3
3
65
110
1.96
4437
500
3
2
65
110
2.25
6120
8
4
10
45
60
0.73
418
6
4
8
45
80
0.87
630
4
4
8
45
80
0.97
867
2
4
6
45
80
1.12
1276
1/0
4
6
55
80
1.34
1900
350
4
3
65
110
2.17
5681
500
4
2
65
110
2.49
7870
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
07-04
19
VULCANEL® XLPE CABLE
TYPE XHHW-2 600 VOLTS
DESCRIPTION
1) Annealed bare stranded class B
concentric round (14-8 AWG)
compressed (6 AWG-1000 MCM)
copper conductor.
2) Cross-linked polyethylene (XLPE)
insulation.
APPLICATION
Power or control circuits in recognized
raceways, in wet or dry location and in
presence of oil. Also suitable as
switchboard wiring.
MAXIMUM OPERATING VOLTAGE
600 volts
MAXIMUM CONDUCTOR TEMPERATURE
Dry locations
90° C
Wet locations
75° C
Overload
130° C
250° C
Short Circuit
FEATURES
1) Smaller overall diameter for easier
pulling and greater conduit fill.
2) Good moisture resistance.
3) Good resistance to most oils and
chemicals.
4) Suitable for installation in sub-zero
temperatures.
5) Optical "For CT use" marking, for use in
cable trays. Sunlight resistant in
accordance with NEC Article 318.
6) Available in VW-1 and non VW-1
designs.
SPECIFICATIONS
UL-44
1
2
Size
AWG/kcmil
Number
of
Strands
14
7
12
10
Conductor Conductor Insulations Overall
Area
Diameter Thickness Diameter
kcmil
inch
Mils
inch
Net
Weight
lb/Mft
4.1
0.07
30
0.13
19
7
6.5
0.09
30
0.15
48
7
10.3
0.11
30
0.17
42
8
7
16.5
0.15
45
0.24
71
6
7
26.2
0.18
45
0.27
98
4
7
41.7
0.23
45
0.32
153
2
7
66.3
0.29
45
0.38
241
1/0
19
106.0
0.37
55
0.48
378
2/0
19
133.0
0.41
55
0.52
446
3/0
19
168.0
0.47
55
0.58
556
211.0
4/0
19
0.52
55
0.63
697
250
37
0.57
65
0.70
851
300
37
0.62
65
0.75
997
350
37
0.67
65
0.80
1180
400
37
0.72
65
0.85
1306
500
37
0.80
65
0.93
1662
600
61
0.88
80
1.04
1974
750
61
0.98
80
1.15
2450
1000
61
1.14
80
1.30
3240
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
HOW TO ORDER
®
VULCANEL XLPE cable, type XHHW-2,
600 volts, size and length.
National Electrical Code References:
Ampacities
Switchboard wiring
Conduit fill tables
Article 310
Article 384
Chapter 9
* Dupont trade mark
Condumex Wire and Cable
07-04
10
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
TYPE RHH-RHW-USE-2
COPPER XLPE 600 VOLTS
DESCRIPTION
1) Annealed bare stranded class B
conductor
2) Flame-retardant cross-linked
polyethylene (XLPE) insualtion.
APPLICATION
May be installed in free air, all raceways or
use in direct burial in industrial and
commercial application. May be used as
underground service entrance cable.
MAXIMUM OPERATING VOLTAGE
600 volts
MAXIMUM CONDUCTOR TEMPERATURE
Type RHH
Type RHW or
USE
90° C Dry and
damp locations
75° C Dry and
wet locatinons
Size
AWG/kcmil
Number
of
Strands
Conductor Conductor Insulations Overall
Area
Diameter Thickness Diameter
kcmil
inch
mils
inch
Net
Weight
lb/Mft
8
7
16.5
0.15
60
0.27
73
6
7
26.2
0.18
60
0.31
108
4
7
41.7
0.22
60
0.35
161
2
7
66.3
0.28
60
0.41
245
1/0
19
106
0.36
80
0.53
392
2/0
19
133
0.41
80
0.58
485
3/0
19
168
0.46
80
0.63
600
211
746
4/0
19
0.51
80
0.69
FEATURES
250
37
0.56
95
0.76
887
1) Flame retardant, moisture and heat
resistant insulation.
2) UL listed as types RHH or RHW or USE for
use in accordance with the National
Electrical Code.
3) UL approved as VW-1 (RHH or RHW)
4) Good resistance to most oils and
chemicals.
5) Suitable for installation in sub-zero
temperatures.
6) Stable electrical propoerties.
7) Extremely tough.
300
37
0.61
95
0.82
1052
350
37
0.66
95
0.87
1216
400
37
0.71
95
0.92
1380
500
37
0.79
95
0.99
1708
600
61
0.87
110
1.11
2055
750
61
0.97
110
1.20
2542
1000
61
1.12
110
1.36
3353
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
SPECIFICATIONS
UL-44
Standard for Rubber-Insulated
Wires and Cables.
ICEA S-66-524 Standard for Cross-Linked
Polyethylene Insualted Wire and Cable.
National Electrical Code References:
Article 310, Table 310-13
Product
Ampacities
Article 310-15
HOW TO ORDER
CONDUMEX type RHH-RHW-USE-2
XLPE 600 volts, size, length, quantity,
packaging.
Condumex Wire and Cable
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
07-04
11
11
1
BARE ACSR CABLE
ALUMINUM CONDUCTOR STEEL REINFORCED
26.ACSR.01
DESCRIPTION
CONDUCTORS
Aluminum 1350 wire concentrically laid over
a solid or stranded galvanized steel core.
APPLICATION
Overhead transmission, subtransmission
and distribution systems. Static wires to protect
overhead lines. Messenger cables to support
overhead electrical cables. Messenger and
power support conductor in catenary systems
for railroad electrification.
MAXIMUM CONDUCTOR TEMPERATURE
Normal Operation
75 °C
FEATURES
1) Ideal combination of conductivity and
strength to permit the longest possible
spans.
2) Minimum sag between supports with
fewer towers required.
3) High resistance to mechanical strength.
4) Wide variety of sizes available in long
lengths to suit both electrical and
Mechanical design requirements.
5) Good corrosion resistance.
SPECIFICATIONS
ASTM B232 Conductor overall
ASTM B230 Aluminum wires
ASTM B498 Galvanized steel class A
CODE
WORD
SIZE
STRAND OVERALL DIAMETER
AWG or MCM AL/Steel
Inch
mm
NET WEIGHT
RUPTURE STRENGTH
Lbs./mft kg/km
lbs
Turkey
6
6/1
0.198
5.03
36
54
1,190.3
Swan
4
6/1
0.250
6.35
58
86
1,860.8
Swallow
3
6/1
0.281
7.14
73
108
2,304.0
Sparrow
2
6/1
0.316
8.03
91
136
2,857.5
Robin
1
6/1
0.355
9.02
115
171
3,555.0
Raven
1/0
6/1
0.398
10.11
145
216
4,387.5
Quail
2/0
6/1
0.447
11.35
183
273
5,310.0
Pigeon
3/0
6/1
0.502
12.75
231
344
6,682.5
Penguin
4/0
6/1
0.563
14.30
291
433
8,430.8
Partridge
266.8
26/7
0.642
16.31
366
544
11,317.5
Linnet
336.4
26/7
0.721
18.31
162
688
14,107.5
Oriole
336.4
30/7
0.741
18.82
525
782
17,325.0
Ibis
397.5
26/7
0.783
19.89
545
811
16,312.5
Lark
397.5
30/7
0.806
20.47
619
921
20,317.5
Hawk
477.0
26/7
0.858
21.79
654
973
19,507.5
Hen
477.0
30/7
0.883
22.43
743
1106
23,850.0
Heron
500.0
30/7
0.904
22.96
781
1162
24,750.0
HOW TO ORDER
Dove
556.5
26/7
0.927
23.55
765
1138
22,725.0
ACSR cable, size, Aluminum Association
Code Word, quantity required in weight.
Eagle
556.5
30/7
0.953
24.21
869
1293
27,900.0
Duck
605.0
54/7
0.953
24.21
779
1159
23,400.0
Grosbeak
636.0
26/7
0.990
25.15
872
1298
25,200.0
Starling
715.5
26/7
1.051
26.70
986
1467
28,350.0
Crow
715.5
54/7
1.035
26.29
918
1366
26,100.0
Drake
795.0
26/7
1.108
28.14
1095
1629
31,500.0
Condor
795.0
54/7
1.093
27.76
1021
1520
28,125.0
Canary
900.0
54/7
1.162
29.51
1160
1726
32,337.0
Rail
954.0
45/7
1.165
29.59
1076
1601
25,875.0
Bluejay
1113.0
45/7
1.259
31.98
1256
1869
30,987.0
Dimension and weights shown are nominal, unless otherwise indicated, and subject to
manufacturing tolerances.
Condumex Wire and Cable
07-04
12
1
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
NOTES:
Condumex Wire and Cable
5-05
2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-9473
Grand Prairie, Texas
800-925-9473