IEEE 45/1580 & UL 1309/1072 IEEE 45/1580 & UL 1309/1072 Installation Recommendations Cable type Minimum bending radius Armored Cable 8D Unarmored Cable 6D , D:cable’s diameter(mm) 2. Cable pulling-in force Care should be taken to prevent damage to insulation or distortion of cable during installation. The pulling force in Newtons should not exceed 0.036 times the circular mil area of the copper cross-sectional area times the number of conductors in the cable when pulling on the conductors utilizing pulling eyes and bolts. Pulling force for multicore cables when utilizing eyes or bolts should not include drain or ground conductors in the copper cross-sectional area. When pulling with a basket weave grip, maximum pulling tension (per grip) should not exceed 4.5kN, or the value calculated for eyes or bolts, whichever is greater. The sidewall pressure should not exceed a maximum of 7.3kN per meter of the inside radius of the bend. Cables should not be pulled in freezing conditions. If conditions are below 0 , consult the manufacturer. a) Single-conductor ac cables should not be located closer than 76mm from parallel magnetic material. b) Single-conductor ac cable should be supported on insulators. Armor, if used, should be grounded only at approximately the midpoint of the cable run. c) Where single-conductor ac cables penetrate the bulkhead, conductors of each phase of the same circuit should pass through a common nonferrous bulkhead plate to prevent heating of the bulkhead. d) Single-conductor cables in-groups should be arranged to minimize their inductive effect. This may be accomplished by the transposition of cables in groups of three (one each phase) to give the effect of triplexed cable. This transposition should be made at intervals of not over 15m and need not be made in cable runs of less than 30m. 4. Cable continuity and grounding All cable should be continuous between terminations, however, splicing is permitted under certain conditions. For cable provided with armor, the armor should be electrically continuous between terminations and should be grounded at each end (multiconductor cables only); except that for final subcircuits, the armor may be grounded at the supply end only. 5. Cable locations Cable installation should avoid spaces where excessive heat and gases may be encountered such as galleys, boiler rooms and pump rooms, and spaces where cables may be exposed to damage such as cargo spaces and exposed sides of deck houses. Cables should not be located in cargo tanks, ballast tanks, fuel tanks, or water tanks except to supply equipment If it is necessary to pull in these conditions, cables shoulld be stored at a temperature above 10 for 24 h prior to installation, if the cable has been previously stored in an area under 0 . Low Voltage Control cable Closed magnetic circuits around single-conductor ac cable should be avoided, and no magnetic material should be permitted between cables of different phases of a circuit. Low Voltage Signal cable 1. Minimum bending radius To avoid an undesirable inductive effect in ac installlations, the following precautions should be observed. and instrumentaion specifically designed for such locations and whose functions require it to be installed on the tank. Such High Voltage Distribution The following installation recommendations are in accordance with IEEE 2002 Low Voltage Distribution 3. Single-conductor ac cables equipment may include submerged cargo pumps and associated control devices, cargo monitoring, and underwater When installing low smoke cables, additional consideration should be given to handling and lubrication due to their possible lower tear strength and higher coefficient of friction than other marine cable. Unless unavoidable, cables should not be located behind or embedded in structural heat insulation. Where cables are installed behind paneling, all connections should be readily accessible and the location of concealed connection boxes should be indicated. Cables should preferably not be run through refrigerated cargo spaces. For more guidance concerning this subject, refer to IEEE Std 576-2001 Cables should not be located below the faceplate of the vessel s main bottom structural members or within .6m above any double bottom tanktop. Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 Information Data navigation systems. IEEE 45/1580 & UL 1309/1072 IEEE 45/1580 & UL 1309/1072 1. Construction and resistance of conductor protected by removable metal coverings, angle irons, or other equivalent means. (1) Temperature correction factors for annealed high conductivity copper Where cables pass through insulation, they should be protected by a continuous pipe. For wiring entering Values of the correction factor (Kc) and reciprocal of factor (Kr) are given in following table for a normal range of refrigerated compartments, the pipe should be of heat-insulating material (fiber or phenolic tubing) joined to temperatures in accordance with IEC Pub. 60228. the bulkhead-stuffing tube, or a section of such material should be inserted between the bulkhead-stuffing tube The values are based on the following formula : and the metallic pipe. Kc = Where cables are installed in pipes, the space factor (ratio of the sum of the cross-sectional areas corresponding to the external diameter of the cables to the internal cross-sectional areas of the pipe) shall not be greater than 0.41, except for two cables, where the space factor shall not exceed 0.31, Pipes shall be so 1 1+ 0.00393 (t 20) Temperature arranged or designed to prevent the accumulation of internal condensation. ( Note) Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 254.5 234.5+t Correction factor ) , Kr = 1/Kc Reciprocal of factor Temperature Correction factor Reciprocal of factor (Kr) (Kr) ( ) (Kr) (Kr) 5 1.063 0.941 36 0.940 1.063 6 1.058 0.945 37 0.936 1.067 7 1.054 0.949 38 0.933 1.071 8 1.050 0.953 39 0.930 1.075 9 1.045 0.957 40 0.927 1.079 10 1.041 0.961 41 0.923 1.082 11 1.037 0.965 42 0.920 1.086 12 1.033 0.969 43 0.917 1.090 13 1.028 0.972 44 0.914 1.094 14 1.024 0.976 45 0.910 1.098 15 1.020 0.980 46 0.907 1.102 16 1.016 0.984 47 0.904 1.106 17 1.012 0.988 48 0.901 1.110 18 1.008 0.992 49 0.898 1.114 19 1.004 0.966 50 0.894 1.118 20 1.000 1.000 51 0.891 1.122 21 0.996 1.004 52 0.888 1.126 22 0.992 1.008 53 0.885 1.130 23 0.988 1.012 54 0.882 1.134 24 0.985 1.016 55 0.879 1.138 25 0.981 1.020 56 0.876 1.142 26 0.977 1.024 57 0.873 1.146 27 0.973 1.028 58 0.870 1.149 28 0.970 1.031 59 0.867 1.153 29 0.966 1.035 60 0.864 1.157 30 0.962 1.039 65 0.850 1.177 31 0.958 1.043 70 0.836 1.197 32 0.955 1.047 75 0.822 1.216 33 0.951 1.051 80 0.809 1.235 34 0.947 1.055 85 0.797 1.256 35 0.944 1.059 90 0.784 1.275 /1000ft = 0.3048 /km = 3.281 Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 = /km /1000ft Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 Low Voltage Signal cable such as locations in way of cargo ports, hatches, tank tops, and where passing through decks, should be High Voltage Distribution against chafing or displacement due to vibration. Cables in bunkers, and where particularly liable to damage, Information Data Cables should be adequately protected where exposed to mechanical damage. Cables should be secured Low Voltage Control cable Low Voltage Distribution Electrical Data 6. Cable protection IEEE 45/1580 & UL 1309/1072 IEEE 45/1580 & UL 1309/1072 Nominal dc Resistance at 25 Single conductors ( Multi conductors /km) ( /km) Pair conductors ( /km) Conductor Size Stranding No. & size each wire in strand EA (mm) (mm) (mm) (mm) 22 7 9.6 0.244 0.0288 0.732 16.7 54.81 55.90 57.00 20 7 12.1 0.307 0.036 0.922 10.6 34.79 35.48 36.18 18 7 15.2 0.386 0.046 1.158 7.05 23.14 23.60 24.06 16 7 19.2 0.488 0.058 1.463 4.44 14.57 14.86 15.15 14 7 24.2 0.615 0.073 1.844 2.73 8.96 9.14 9.32 12 7 30.5 0.775 0.092 2.324 1.72 5.64 5.76 5.87 10 7 38.5 0.978 0.116 2.946 1.08 3.54 3.62 3.69 8 7 48.6 1.234 0.146 3.708 0.679 2.228 2.273 2.318 7 7 54.5 1.384 0.164 4.166 0.539 1.769 1.804 1.840 6 7 61.2 1.554 0.184 4.674 0.427 1.401 1.429 1.457 5 7 68.8 1.748 0.206 5.232 0.339 1.113 1.135 1.157 4 7 77.2 1.961 0.232 5.893 0.269 0.883 0.901 0.918 3 7 86.7 2.202 0.260 6.604 0.213 0.699 0.713 - 2 7 97.4 2.474 0.292 7.417 0.169 0.555 0.566 - 1 19 66.4 1.687 0.332 8.433 0.134 0.440 0.449 - 1/0* 275/24 1/0 19 74.5 1.892 0.373 9.474 0.106 0.348 0.355 - 2/0* 325/24 2/0 19 83.7 2.126 0.418 10.643 0.0843 0.2767 0.2822 - 3/0 19 94.0 2.388 0.470 11.938 0.0669 0.2196 0.2240 - 4/0 19 105.5 2.680 0.528 13.411 0.0525 0.1723 0.1757 250MCM 37 82.2 2.088 0.573 14.605 0.0449 0.1474 300MCM 37 90.0 2.286 0.630 16.002 0.0374 0.1227 350MCM 37 97.3 2.471 0.681 17.297 0.0320 400MCM 37 104.0 2.642 0.728 18.491 500MCM 37 116.2 2.951 0.813 600MCM 61 99.2 2.520 750MCM 61 110.9 1000MCM 61 128.0 (inch) (inch) (mm) Maximum dc Resistance at 25 Maximum ac Resistance at 20 ( /1000ft) ( /km) 22 19/34 1 19 0.030 0.031(0.787) 16.01 51.51 20 19/32 1 19 0.039 0.039(0.991) 9.91 31.89 18 19/30 1 19 0.048 0.052(1.321) 6.34 20.40 16 19/29 1 19 0.054 0.062(1.575) 4.92 15.83 14 19/27 1 19 0.068 0.074(1.880) 3.11 10.01 12 19/25 1 19 0.086 0.094(2.388) 1.96 6.31 10 27/24 1 27 0.120 0.128(3.251) 1.125* 3.62 8 37/24 1 37 0.142 0.147(3.734) 0.7899 2.542 6* 61/24 1 61 0.198 0.207(5.258) 0.483 1.554 5* 91/24 7 13 0.235 0.244(6.198) 0.330 1.062 4* 105/24 7 15 0.261 0.264(6.706) 0.287 0.923 3* 125/24 7 18 0.286 0.288(7.315) 0.236 0.759 2* 150/24 7 21 0.318 0.325(8.255) 0.203 0.653 1* 225/24 7 32 0.381 0.390(9.906) 0.135 0.434 (7 15+12 14) 0.433 0.440(11.176) 0.110 0.354 19 17 0.450 0.477(12.116) 0.094 0.302 0.555 0.565(14.351) 0.068 0.219 19 15 19 24 (7 23+12 24) - 4/0* 550/24 (7 28+12 29) 0.605 0.620(15.748) 0.055 0.177 0.1503 - 262*MCM 650/24 19 34 0.654 0.660(16.764) 0.047 0.151 0.1252 - 313*MCM 775/24 19 41 0.720 0.725(18.415) 0.0393 0.1265 0.1050 0.1071 - 373*MCM 925/24 37 25 0.790 0.795(20.193) 0.0326 0.1049 0.0278 0.0912 0.0931 - 444*MCM 1100/24 37 30 0.860 0.870(22.098) 0.0273 0.0878 20.650 0.0222 0.0729 0.0743 - 535*MCM 1325/24 37 36 0.940 0.970(24.638) 0.0227 0.0730 0.893 22.682 0.0187 0.0614 0.0626 - 646*MCM 1600/24 37 43 1.040 1.060(26.924) 0.0188 0.0605 2.817 0.998 25.349 0.0148 0.0486 0.0495 - 777*MCM 1925/24 37 52 1.128 1.130(28.702) 0.0156 0.0502 3.251 1.152 29.261 0.0111 0.0364 0.0372 - 1111*MCM 2750/24 61 45 1.338 1.340(34.036) 0.0110 0.0354 K1(0.98073) /1000ft to K1 ; Converts 25 Maximum Diameter 450/24 /km at 20 . K2(1.02) K3(1.02 or 1.04) Ro ; Norminal conductor resistance in Ko ; Converts Nominal Diameter 3/0* /km) were calculated from the ICEA formula and converted to R=Ro Ko(3.281) Suggested construction AWG/MCM AWG/MCM Note) Resistance( ( /1000ft) Maximum dc Resistane at 20 /1000ft @ 25 19 29 * Rope lay stranded Note) The number of strands are nominal and may vary so as to comply with both the d.c resistance and maximum diameter requirements. Resistance( /km) were calculated from the ICEA formula and converted to /km (Ko=3.281) values to 20 , ICEA S 61 402 Table 6 1 (K1=0.98073) R=Ro Ko(3.281) Ro ; Norminal conductor resistance in K3 ; Converts single conductor resistance to multiple conductor resistance Ko ; Converts /1000ft to K1 ; Converts 25 /1000ft @ 25 /km (Ko=3.281) values to 20 , ICEA S 61 402 Table 6 1 (K1=0.98073) K3 = 1.04 for pair or other precabled units Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 . K1(0.98073) K2 ; Converts nominal resistance to maximum, ICEA S 61 402 Table 2 3 (K2=1.02) K3 = 1.02 for multiple conductor /km at 20 Low Voltage Distribution Conductor diameter Low Voltage Control cable Diameter of wires Low Voltage Signal cable Number of wires High Voltage Distribution Conductor Size (3) Construction and resistances of flexible stranded conductors. Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 Information Data (2) Construction and resistances of standard class B concentric conductors. IEEE 45/1580 & UL 1309/1072 IEEE 45/1580 & UL 1309/1072 (IEEE 45-1998, Type P @ 45 Temperature ambient) Single Conductor Cable Conductor Correction Factors for Tye P(X110) or Type E Insulated Cables AWG/MCM mm2 Citcular mils Two Conductor Cable Three Conductor Cable Maximum conductor temperature : 100 5 41 0.75 0.098 10 50 0.83 0.29 20 0.6 1022 12 10 9 15.5 60 1.00 1.00 18 1.0 1624 16 14 12 20 68 1.20 2.5 16 1.2 2583 23 19 16 25 77 1.57 6.6 14 2.1 4110 37 31 25 30 86 2.10 16.5 12 3.3 6530 45 40 31 3. Minimum insulation resistance and high-voltage ac test potentials (1) Type P(X110) Insulated Cables Insulation Resistance Conductor Size ( Test Potentials 1000ft at 15.5 ) 10 5.3 10400 58 49 41 8 8.4 16500 72 64 52 7 10.6 20800 84 78 63 6 13.3 26300 96 85 70 5 16.8 33100 109 101 82 4 21.1 41700 128 110 92 3 26.7 52600 146 132 108 2 33.6 66400 169 149 122 1 42.4 83700 194 174 143 1/0 53.5 106000 227 199 164 2/0 67.4 133000 262 242 188 3/0 85.0 168000 300 265 218 AWG/kcmil 0 ~ 2000V 0 ~ 600V 601 ~ 2000V 22 ~ 16 3,000 1,500 - 4/0 107.2 212000 351 307 252 14 ~ 9 1,600 3,500 5,500 250MCM 127 250000 389 344 282 8~2 1,200 5,500 7,000 262MCM 133.1 262600 407 358 294 1 ~ 4/0 800 7,000 8,000 300MCM 152 300000 449 385 316 250 ~ 525 650 8,000 9,500 313MCM 158.7 313100 455 391 321 526 and larger 550 10,000 11,500 350MCM 177 350000 485 421 344 373MCM 189.4 373700 516 442 361 400MCM 203 400000 533 455 371 444MCM 225.2 444400 588 504 411 500MCM 253 500000 609 520 428 535MCM 271.3 535000 662 566 465 600MCM 304 600000 678 585 478 646MCM 327.6 646000 731 632 516 750MCM 380 750000 786 656 537 777MCM 394.2 777000 822 684 562 854 701 (2) Type E Insulated cables for 5~15kv shielded conductors Voltage rating of cable(phase-tophase circuit voltage) Size of conductor Insulation resistance constart K (based on 1000 feet, 15.6 ) 100% Insulation level (grounded neutral) a.c. 133% Insulation level (grounded neutral) d.c. a.c. d.c. AWG-kcmil - kV kV kV kV 5kV 8-1000(1111) 20,000 13 N/A 13 N/A 1000MCM 507 1000000 939 8kV 6-1000(1111) 20,000 18 45 22 45 1111MCM 563.1 1111000 1025 15kV 2-1000(1111) 20,000 27 70 33 80 1250MCM 633 1250000 1072 Note) Based on a conductor kilometer : K=6100(see, table 12.6 of UL 1072) Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 1500MCM 706 1500000 1195 2000MCM 1013 2000000 1400 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 Low Voltage Control cable Distribution, control and signal cables-single banked maximum ampacity in air Low Voltage Signal cable by the correction factors given in High Voltage Distribution The insulation resistance shall be measured at room temperature and corrected to 15.5 the following table Low Voltage Distribution 4. Maximum current-carrying capacity Information Data 2. Temperature correction factors for insulation resistance IEEE 45/1580 & UL 1309/1072 IEEE 45/1580 & UL 1309/1072 Single Conductor Cable Conductor mm2 14 2.1 12 10 Citcular mils Three Conductor Cable Conductor Maximum conductor temperature : 110 MC MCM Single Conductor Cable AWG MM 2 Three Conductor Cable Maximum conductor temperature : 90 4410 39 33 27 16,500 17 8 8.4 68 48 3.3 6530 49 41 33 20,800 21 7 10.6 77 59 5.3 10400 61 52 43 26,230 26 6 13.3 88 65 8 8.4 16900 77 68 55 33,100 33 5 16.8 100 75 7 10.6 20800 88 82 67 41,700 42 4 21.1 118 83 6 13.3 26300 100 90 74 52,600 53 3 26.7 134 99 5 16.8 33100 114 105 85 66,400 66 2 33.6 156 111 4 21.1 41700 134 115 95 83,700 84 1 42.4 180 131 3 26.7 52600 153 138 113 106,000 106 1/0 53.5 207 150 2 33.6 66400 178 156 126 133,000 133 2/0 67.4 240 173 1 42.4 83700 205 183 149 168,000 168 3/0 85.0 278 201 1/0 53.5 106000 236 208 171 212,000 212 4/0 107.2 324 232 2/0 67.4 133000 274 265 197 250,000 250 127.0 359 259 3/0 168000 317 279 229 262,000 262 133.1 378 273 4/0 107 85.0 212000 369 323 264 300,000 300 152.0 412 290 250MCM 127 250000 409 360 295 313,000 313 158.7 423 298 300MCM 152 300000 470 403 330 350,000 350 177.0 446 317 350MCM 177 350000 508 441 361 373,000 373 189.4 474 332 400MCM 203 400000 557 494 390 400,000 400 203.0 489 342 500MCM 253 500000 638 546 448 444,000 444 225.2 546 382 535MCM 271 535000 660 565 464 500,000 500 253.0 560 393 600MCM 304 600000 710 614 502 535,000 535 271.3 615 432 646MCM 327 646000 - - - 600,000 600 304.0 623 440 750MCM 380 750000 824 686 536 646,000 646 327.6 671 474 777MCM 394 777000 - 750,000 750 380.0 723 494 1000MCM 507 1000000 988 777,000 777 394.2 755 516 1111MCM 562 1111000 - 1,000,000 1000 507.0 867 1250MCM 633 1250000 1128 1,111,000 1111 563.1 942 1500MCM 706 1500000 1254 2000MCM 1013 2000000 1473 644 Notes: 1) Current ratings are for ac or dc. 2) Current-carrying capacity of four conductor cables where one conductor is neutral, is the same as three conductor cables. the values shown above should be multiplied by the following factors: 3) If ambient temperatures differ from 45 Ambient temperature Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 40 50 60 Type E insulated cables 1.05 0.94 0.82 - Type P(X110) insulated cables 1.04 0.95 0.85 0.74 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 70 Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 Information Data AWG/MCM Two Conductor Cable ambient) Low Voltage Control cable (IEEE 45-1998, Type E @ 45 ambient) Low Voltage Signal cable Distribution, Power cables - single banked maximum ampacity in air (IEEE 45-1995, Type X110 @ 45 High Voltage Distribution Distribution, control and signal cables - single banked maximum ampacity in air Low Voltage Distribution Maximum current-carrying capacity IEEE 45/1580 & UL 1309/1072 IEEE 45/1580 & UL 1309/1072 4) The above current-carrying capacities are for marine installations with cables arranged in a single bank per hanger and are 85% of the ICEA calculated values. Double banking of distribution-type cables should be avoided. For those instances where cable must be double banked, the current-carrying capacities in the above table should be multiplied Technical information Short circuit current ratings by 0.8. 5) The ICEA calculated current capacities of these cables are based on cables installed in free air, that is, at least one cable diameter spacing between adjacent cables. (1) The following short current ratings are for cable normally operating at a maximum conductor temperature of 100 (2) The theoretical temperature that arises in the conductor during a short circuit, which is used as a basis of the 6) Ampacity adjustment factors for more than 3 conductors in a cable with no load diversity: calculation, is 250 in accordance with IEC 60724. (3) EPR and XLPE insulation are capable of withstanding of short term temperature up to 250 Number of conductors Percent of values in the above table for three conductor cable as adjusted for ambient temperature, if necessary (4) The short circuit current ratings for copper conductors given in the table are values for one second for other duration the current may be calculated from the following formula; 4 through 6 80 7 through 9 70 10 through 20 50 l1 lt = t lt = short circuit current for t second (kA) 21 through 30 45 l1 = short circuit current for one second (kA) 31 through 40 40 t = short circuit duration (second) 41 through 60 35 (5) The duration of the short circuit based on these assumptions should be between 0.2 sec. and 5 sec. AWG or Kcmil Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297 Short circuit current (A) Short circuit duration (second) - 0.1 0.2 0.5 1 2 22 159 112 71 50 35 20 259 183 16 82 58 18 401 283 179 127 90 16 551 390 246 174 123 14 868 614 388 275 194 12 1,373 971 614 434 307 10 2,183 1,543 976 690 488 8 3,159 2,234 1,413 999 706 6 5,213 3,686 2,331 1,648 1,166 4 8,810 6,230 3,940 2,786 1,970 2 13,985 9,889 6,254 4,423 3,127 1 17,858 12,628 7,987 5,647 3,993 1/0 22,725 16,069 10,163 7,186 5,081 2/0 29,219 20,661 13,067 9,240 6,533 3/0 35,713 25,253 15,971 11,293 7,986 4/0 45,454 32,141 20,327 14,374 10,164 262 55,195 39,028 24,684 17,454 12,342 313 66,384 46,940 29,688 20,992 14,844 373 79,029 55,882 35,343 24,991 17,672 444 94,834 67,058 42,411 29,989 21,206 535 113,803 80,471 50,894 35,988 25,447 646 135,931 96,118 60,790 42,985 30,395 777 164,382 116,235 73,514 51,982 36,757 111 234,526 165,835 104,883 74,164 52,442 Head Office Tel:82-43-530-2000 Fax:82-43-530-2140 Sales Office Tel:82-2-2140-3042 Fax:82-2-2140-3098 Pusan Office Tel:82-51-817-0295 Fax:82-51-817-0297