TYPE:

CATALOG #:

NOTES:

RS

Series

6 and 12 Volt Decorator Recessed

Emergency Lighting

Features

• Each unit comes with two (2) 6 or 12V-9W high-intensity incandescent

EF-9 lamp heads (standard). EF-10, EF-18, and EF-150 lamp heads are optional

• Constructed of 20-gauge steel with an off-white baked enamel finish

• Available with sealed, maintenance-free Nickel-Cadmium, or Lead-Calcium batteries

• PulsePlus Charger circuitry offers 120/277V input 60 Hz., 0.3/0.15A (other inputs available), fused output circuit(s), dual diagnostic indicator lights, temperature compensated charger, sealed relay, low voltage battery disconnect, brownout protection and lock out (automatic battery connect)

• Fully-recessed assembly for ceiling or wall mount. Includes adjustable bar hangers for grid ceilings. Can be framed into studs/joists

• UL924 Listed

• 3-year limited warranty

Detailed warranty terms located at: www.emergi-lite.com/usa/files/EL_Warranty.pdf

Optional Features

DESCRIPTION

New York City (EF-18 12 Watt Lamps)

ACCESSORIES

Wire Guard (Units with EF-9, EF-10 or EF-18, EF-150 Heads)

Remote Test Switch (metal face plate)

Remote Test Switch (plastic face plate)

-NYC

WG6-E

RTS

RTS-1

SUFFIX

Electrical

Power Requirements: 120/277 Vac, 60 Hz., 0.3/0.15 Amp (other inputs available). Output: 6 or 12 volt fused outputcircuit. Transfer: dust-tight relay automatically and instantly energizes lamp load upon failure of

AC supply. LVD: low voltage battery disconnect circuit automatically disconnects the lamp load and circuitry when battery reaches 871/2% discharge to protect the battery from deep discharge and permanent damage. Lockout: labor saving electronic circuit automatically connects battery when the AC circuit is activated. Brownout: close tolerance electronic circuit activates emergency unit when utility power dips below

80-85% of nominal voltage. Charger: The pulse plus charging circuit utilizes an integrated circuit chip which samples the battery in relation to its temperature, state of charge and input voltage fluctuations.

The charger is current limited, temperature compensated, shortcircuit proof and reverse polarity protected. Charger regulation ±1%. The equipment is capable of full recharge in compliance with Underwriters

924 specification. Transformer: 120/277 volt. Controls: test switch and dual diagnostic LED indicator lights, Hi-charge and AC pilot.

Suggested Specification

Supply and install

RSC

Emergi-Lite ® Series RSM RSE , or

in 6 or 12V, with electrically compatible remote fixtures or exit signs as indicated on the plans. The emergency lighting unit shall be an architecturally designed, self-contained fixture including sealed, maintenance-free battery:

TYPE RSM to be supplied with Lead-Calcium battery.

TYPE RSE to be supplied with long life Pure Lead battery.

TYPE RSC to be supplied with long life Nickel-Cadmium battery.

The unit charger shall utilize an integrated circuit which samples the battery in relation to its temperature, state of charge and input voltage fluctuations. The charger shall be current limited, temperature compensated, short-circuit protected and reverse polarity protected.

The unit shall be furnished with an electronic lockout circuit which will connect the battery when the AC circuit is activated, and an electronic brownout circuit which will activate the unit when utility power dips below 80-85% of nominal voltage.

A low voltage battery protection circuit shall be provided and will disconnect the load and circuitry from the fused output circuit when battery reaches 871/2% of its nominal voltage. The unit shall be capable of full recharge in compliance with UL924 specifications. The unit shall be furnished with a sealed, dusttight relay, a test switch and dual diagnostic LED indicator lights (Hi-charge and AC pilot). The unit shall be designed for fully recessed installation in walls or ceilings, including grid type suspended ceilings. Unit shall be constructed of 20 gauge steel with a off-white baked enamel mounting plate. Unit will be furnished with two (2) lampheads as follows:

TYPE EF-9 decorator heads; 6V, 12V: 9W lamp per head.

TYPE EF-18 decorator heads; 6V, 12V:W lamp per head.

Fused output terminals shall be provided for ease of remote lamp connections. All 6 and 12 volt RS Series shall be fully warranted for three years, subject to proper installation and maintenance.

The unit shall be Emergi-Lite ® model: .

Diagnostic/Self Test Feature

(Optional)

Advanced Diagnostics (audible and non audible versions) Our

Advanced Diagnostic circuitry is designed to continuously monitor every critical function of the unit, attached remote lighting heads and exit signs. Operational status is indicated by colored LED lamps. A high-pitch audible alarm and an LED status indicator alert maintenance personnel to a unit malfunction. This option saves the time spent on testing and trouble shooting by maintenance personnel. This new generation of Emergi-Lite diagnostics is perfect for any application.

The self test will test the unit for a minimum 30 seconds every 30 days,

30 minutes every six months and 90 minutes annually. Self-testing in accordance with NFPA 101, Life Safety Code. Unit tests itself every thirty days for one minute, thirty minutes on the sixth month and ninety minutes annually.

13

Dimensions

Dimensions are approximate and subject to change.

Back Box EF18 EF9 & EF10

Unit Warranty*

Entire unit (excluding lamps and fuses) carries a 3-year Full Warranty.

Battery Warranty*

Unit batteries are warranted as follows:

Sealed Nickel-Cadmium: RSC – 12-year life expectancy, 5-year Full

Warranty, plus 5-year pro rata warranty.

Sealed Long Life Lead: RSE – 10-year life expectancy, 5-year Full

Warranty, plus 5-year pro rata warranty.

Sealed Lead Calcium: RSM – 8-year life expectancy, 3-year Full

Warranty, plus 3-year pro rata warranty.

*Subject to proper installation and maintenance.

Unit Rating

EF-9 lamp heads: 6 or 12 volt 9 watt High Intensity Incandescent lamps.

Sealed Maintenance-Free Battery Types

Nickel-Cadmium

Lead-Calcium

Nickel-Cadmium

Lead-Calcium

6

6

6

12

12

6

6

12

UNIT EQUIPMENT – NO REMOTE CAPABILITY

Model Number

D.C.

Voltage

EF-150 Deco EF-9 Lamp Heads

RSC18-2150 RSC18-2

RSM18-2150 RSM18-2

UNIT EQUIPMENT – WITH REMOTE CAPABILITY

RSC25-2150 RSC25-2

12RSC36-2150

12RSC50-2150

12RSC36-2

12RSC50-2

RSM27-2150

RSM36-2150

12RSM36-2150

RSM27-2

RSM36-2

12RSM36-2

* National Electrical Code Specification

25

36

50

27

36

36

Watts to 87-1/2% of rated battery voltage*

4 hrs

18

18

1 1⁄2 hrs

12

12

2 hrs

10

9

3 hrs

How to Order

COLOR

Blank = Factory white

B = Black enclosure

SERIES/BATTERY TYPE

RSC18 = 6V-18W Ni-Cd*

RSC25 = 6V-25W Ni-Cd*

RSM18 = 6V-18W Lead-Calcium

RSM27 = 6V-27W Lead-Calcium

RSM36 = 6V-36W Lead-Calcium

12RSC36 = 12V-36W Ni-Cd*

12RSC50 = 12V-50W Ni-Cd*

12RSM36 = 12V-36W

Lead-Calcium

WATTS

-0 = No head

-1 = One head

-2 = Two heads

HEADS

Blank = EF9 Mini PAR

18 style

10 = EF10 Mini plastic MR16

18 = EF18 (PAR 36 plastic)

150 = EF150 Deco heads MR16

LAMP TYPE

Blank = 6V-9W or 12V-9W Inc. wedge base

LA = 6V-4W, MR16 LED*

LG = 12V-4W, MR16 LED*

LI = 12V-5W, MR16 LED*

LJ = 12V-6W, MR16 LED*

H_ = Halogen bi-pin

I_ = Inc. DC-bayonet

U_ = Inc. sealed-beam**

X_ = Halogen sealed-beam**

Z_ = Inc. wedge

M_ = Halogen MR16*

NOTE: For a complete list of available lamp types, please refer to the lamp data on pages

140-141

18

21

36

18

25

25

12

15

25

14

20

20

OPTIONS

Blan k= No options

-AD = Advanced Diagnostics

(audible)

-ADNA = Advanced Diagnostics

(non-audible)

-V = Voltmeter*

-A = Ammeter*

-D1 = Time Delay (5 minutes)

-D2 = Time Delay (10 minutes)

-D3 = Time Delay (15 minutes)

9

12

18

10

14

14

* Not Available with sealed beams.

Example: BRSC18-210LA-AD

* Available with EF10 and EF150 lamp heads only

** Available with the EF18 lamp head only

* Voltmeter & Ammeter are not available with -AD & -ADNA

All information and specifications contained in this specsheet are subject to change due to engineer design, errors and omissions.

15

Illustrations and diagrams within this specsheet may vary from actual products.

2016© Thomas & Betts Limited. All rights reserved.