513-2.1: Westinghouse Circuit Breaker Ratings

advertisement
c
tn
w
ALLEN-BRADLEY
Westinghouse Circuit Breaker Ratings
Instantaneous Trip Motor Circuit
Protectors HMCP used in Circuit
Breaker Type Combination Starters
Product Data
150AHMCP
Circuit
Breaker
Bulletin
513 Combination
Starter
withCircuit
Breaker
(HMCP)
Trip
Setting
File Name: AB_CombinationStarter_513_spec_D792
Description
MotorCircuit
Protector
The Westinghouse line of Motor Circuit Protectors (HMCP) are
instantaneous (magnetic only) trip current limiting type circuit breakers.
They may be supplied by Allen-Bradley in Bulletin 500 Line NEMA Sizes 0
through 5 combination starters. The particular circuit breaker (trip range)
supplied with a combination starter depends on the horsepower and voltage
that was specified when the device was ordered. Table 1 lists the various
combinations of circuit breakers and starter sizes. When using the table, be
sure to refer to the line that applies to your equipment.
For Bulletin 500 Line
Applications
Table 1
Horsepower Rating and (Catalog Number)
Frame
Size
Continuous
Current
Rating
(Amps)
Size
3
o-1
7
o-1
15
0
1
30
150A
HMCP
250A
HMCP
400A
HMCPO
Starter
50
200 Volts
38OVolts
HP
Catalog
Suffix
Number
HP
Catalog
Suffix
Number
O-y4
(34)
o-1
(35)
o-1
(35)
(35)
l-2
(37)
lj$3
(38)
lJ$-3
(38)
1x-3
lJ$3
3
3-5
3-5
[ii;
5
5-7J4
(39)
(40)
5
5-7J$
(39)
(40)
(41)
1;
[ii;
1:
20-25
-
(44)
-
20-25
3;
Suffix
Number
HP
Catalog
Suffix
Number
0%
(32)
0-s
(32)
M-1
(35)
M-1
(38)
(38)
lpj-3
lJ$-3
1
HP
5
-
(39)
5-7%
(40)
7J4-10
2
1
2
3
v4
10
-
(40)
(41)
-
1;
-
(41)
15-20
-
-
I
575Volts
460 Volts
Catalog
Suffix
Number
Catalog
HP
-
-
-
-
-
(ii)
-
(41)
(42)
(44)
(45)
100
2
3
4
15-25
-
(44)
-
15
20-25
-
(42)
(44)
-
t;
-
;::I
-
30-50
-
(47)
-
40-50
60
$i3/
150
4
3
30
(45)
40
30
;:i;
ii
;;;
60-75
-
(49)
75-100
-
(50)
250
4
-
75
(49)
250
5
4
40
(46)
(50)
(47)
-
-
250
5
50-60
(48)
60-75
(49)
-
-
400
5
75
(49)
100
(50)
-
-
-
0
0
0
Circuit Breaker
Adjustment Considerations
2
230 Volts
-
-
100
125-150
200
-
-
(50)
125
ii
(52)
125-150
-
(54)
-
(54)
-
Less line and load lugs recommended by Allen-Bradley.
Includes line and load lugs recommended by Allen-Bradley.
Not for use in UNILOCK” Enclosure.
The assigned horsepower ratings for the combination starters specified in the
table are related to the motor full load currents as specified in the National
Electrical Code and the Canadian Electrical Code. The circuit breaker is
shipped with the adjustment pointer set on the lowest setting.
I
lnsta ,aneou Trip Setting ( mps)
III
A
B
C
1 21 1 28 1 35
18
21 1 24
27 1 30
HMCPOO3AOC
1
25102-258-01 1
ELC3003R
1
25107-101-10
42
49 1 56
63 1 70
HMCPOO7COC
1
25102-258-02 1
ELC3007R
1
25107-101-11 1
105
120
135
240
270
350
400
700
800
600
I
I
1 750
G
H
I
I
150
HMCPOl5EOC
25102-258-03
ELC3015R
25107-101-12
300
HMCP030HlC
25102-258-04
ELC3030R
25107-101-13
450
500
HMCP050K2C
900
1000
HMCPlOOR3C
1500
HMCPlSOT4C
1315 1410 1500 HMCP250G5WO
1 750 1 840 1 935
1 875 1 980 I1090
1090
I
Allen-Bradley
Part Number
E
210
F
Westinghouse
Catalog
Number
D
180
1 450
Allen-Bradley Part
Number
Westinghouse
Catalog Number
ELC Current Limiter Attachment
I
I
HMCP25OJ5WO
I
I
HMCP4OOXSW
1310 1420 1530 1640 1750
1 1250 1 1405 I1560
1560 1720 1875 I2030 2185 I2340 2500 HMCP250W5WO
p 2000 I2250
2250 I2500
2500 2750 3000 3250 3500 3750 4000
Current Limiter Attachment
I
25102-258-05
I
25102-258-07
I
1 40021-934-390 1
I
40021-934-30
0
40021-935-23
0
ELC3150R
-
I
25107-101-14
I
25107-101-15
I
25107-101-16
I
-
I
I
I
I
1 40021-934-330 1
I
I
ELC3lOOR
25102-258-06
I
ELC3050R
I
I
I
I
I
I
The ELC current limiter is an attachment that bolts to the load end of the
HMCP to provide increased interrupting capability. It is available for NEMA
sizes 0 through 4. The current limiter is coordinated with the HMCP so that
normal short circuits will be cleared automatically by the HMCP, opening all
3 poles.
The current limiter will only clear the very high level faults at approximately
50 or more times the continuous rating of the HMCP. At the same time a
sufficient level of current let-through will magnetically trip the HMCP to
prevent single-phasing.
Each pole of the current limiter is equipped with a spring loaded indicator to
quickly identify the phase(s) on which the fault has occurred. Circuit
problems must be corrected before attempting to restore service.
3
UL Listed Short Circuit
Current Ratin s for
Combination J tarters Bulletin Numbers 507,
507X, 513 and 1233X o
Table 2
Enclosure Type
Bolted
3R,7&9
1,4and 12
I
I
4x
UNILOCK
Bolted
3R,7&9
Pump Panels
3R
0
Q
Push-To-Trip Mechanism
4
Maximum Available
Amperes RMS
Symmetrical
NEMA Sizes
I
I
o-2
o-5
I
I
65,000
25,OOOQ
o-3
5,000
4-5
10,000
o-3
5,000
4-5
10,000
o-2
l-3
4-5
I
I
5,000
5,000
10,000
Maximum Voltage
I
I
600V
I
I
480/6OOV
Consult the Sales Department at Milwaukee for combination starters not listed in the table.
Maximum Available Amperes is 10,000 when using a 250 Amp HMCP for NEMA Size 4.
A push-to-trip mechanism is used to trip the HMCP. Depress the red button
located on the circuit breaker cover. This mechanical pressure causes a
plunger to engage the trip bar which then rotates and results in the HMCP
contacts opening.
Circuit Breaker Trip Settings
Field adjustment on the trip setting of the HMCP is dependent upon the
motor full load current. Allen-Bradley recommends the selection of trip
settings that are approximately 10 times the motor nameplate’s full load
current. The trip setting is adjusted by rotating a cam lever to the appropriate
position. The positions are labeled A through H for 150A frame and A
through I for 250A and 400A frames. The procedure for setting the HMCP
is:
1. Place the circuit breaker operator in the “OFF” position.
2. To select setting, use a screwdriver to depress the adjustment pointer and
mm in the direction indicated by the curved arrow.
3. Verify that the circuit breaker will not trip during motor starting. If the
circuit breaker trips on starting, turn the pointer clockwise to
successively higher positions until the circuit breaker does not trip on
starting.
NOTE: The trip setting of the circuit breaker must never exceed 13 times the
motor full load current. Refer to the National Electrical Code and the
Canadian Electrical Code for information.
At0
ATTENTION:
The horsepower ratings and corresponding trip settings for
each circuit breaker in the table are only valid when the motor
running overcurrent protective device (overload relay) in the
combination starter is an Allen-Bradley Bulletin 592 or
Bulletin 593 overload relay with properly selected heater
elements.
When correctly selected, this combination of equipment will
permit coordinated overcurrent protection in the motor branch
circuit for motors rated for continuous duty and can provide
protection against damage due to short circuits and ground
faults as defined in the National Electrical Code and Canadian
Electrical Code.
The tripping of the circuit breaker indicates the interruption of
a high fault current. In order to maintain protection against
fire and/or shock hazard, the current carrying parts of the
combination starter should be examined and replaced if
damaged. (Refer to NEMA Standards Publication ICS 2.2
titled: “Maintenance of Motor Controllers After a Fault
Condition” - also published as NEMA Standard Publication
No. ICS 2, Part ICS 2-3022
5
m
w
L ALLEN-BRADLEY
A ROCKWELL INTERNATIONAL COMPANY
A subsidiary
ofRockwell
International,
oneoftheworld’s
largest
technology
companies,
Allen-Bradley
meetstoday’s
automation
challenges
withover85 years ofpractical
plant
floor
experience.
Morethan11,000
employees
throughout
theworlddesign,
manufacture
and
apply
a widerangeofcontrol
and automation
products
and supporting
services
tohelpour
customers
continuously
improve
quality,
productivity
andtimetomarket,
Theseproducts
and
services
notonlycontrol
individual
machines,
butalsointegrate
themanufacturing
process
while
providing
accesstovital
plant
floor
datathat
canbe usedtosupport
decision-making
throughout
theenterprise.
With offices in major cities worldwide.
WORLD HEADQUARTERS
Allen-Bradley
1201 South Second Street
Milwaukee, WI 53204 USA
Tel:(414) 362-2000
Telex:43
11 016
FAX:(414)382-4444
EUROPE/MIDDLE EAST/
AFRICA HEADQUARTERS
Allen-Bradley EuropeB.V.
Amsterdamseweg
15
1422AC Uithoorn
The Netherlands
Tel:(31)
2975/43500
Telex:(844)
18042
FAX:(31)
2975/60222
Publication 513-2.1 July, 1992
Supwsedes Publicahm 51 Z-2.1 Dated September 1987
ASIA/PACIFIC HEADQUARTERS
CANADAHEADQUARTERS
CanadaLimited
Allen-Bradley
(HongKong)Limited Allen-Bradley
Room 1006,BlockB,Sea ViewEstate 135DundasStreet
Cambridge,
Ontario
NlR 5X1
2-8WatsonRoad
Canada
Hong Kong
Tel:(519)623-1810
Tel:(852)887-4788
FAX:(519)623-8930
Telex:(780)
64347
FAX:(852)51
O-9436
0 1992 Allen-BradIcy
Company
LATIN AMERICA
HEADQUARTERS
Allen-Bradley
1201SouthSecondStreet
Milwaukee,
WI 53204USA
Tel:(414)382-2000
Telex:43
11016
FAX:(414)382-2400
PRINTED IN USA
Download