LV power air circuit breakers and switch-disconnectors Catalogue Masterpact NT and NW Merlin Gerin We do more with electricity 000000000 © yyyy Schneider Electric - All right reserved Schneider Electric Industries SA 5, rue Nadar 92506 Rueil-Malmaison Cedex France Tel : +33 (0)1 41 29 82 00 Fax : +33 (0)1 47 51 80 20 As standards, specifications and designs change from time to time, please ask for confirmation of the information given iin this publication ce document a étéhas imprimé This document been printed on ecological paper sur du papier écologique. http://www.schneiderelectric.com Design: Schneider Electric - AMEG Photos: Schneider Electric Printed: BTP207E mm-yy E58856 Things never be same E58880 will the The original Masterpact has set a new standard for power circuit breakers around the world. Over the years, other major manufacturers have tried to keep up by developing products incorporating Masterpact’s most innovative features, including the breaking principle, modular design and the use of composite materials. Today, Schneider Electric continues to innovate with the new Merlin Gerin Masterpact NT and NW ranges. In addition to the traditional features of power circuit breakers (withdrawability, discrimination and low maintenance), Masterpact now offers built-in communications and metering functions, all in optimised frame sizes. Masterpact NT and NW incorporate the latest technology to enhance both performance and safety. Easy to install, with user-friendly, intuitive operation and environment-friendly design, they are, quite simply, circuit breakers of their time. 1 Masterpact Schneider Electric E58873 The ultimate power in power distribution New Masterpact, new levels of performance Five performance levels 025855 029693 N1 - for standard applications with low short-circuit levels. H1 - for industrial sites with high short-circuit levels or installations with two parallel-connected transformers. H2 - high-performance for heavy industry where very high short-circuits can occur. H3 - for incoming devices supplying critical applications requiring both high performance and a high level of discrimination. L1 - for high current-limiting capability and a discrimination level (37 kA) as yet unequalled by any other circuit breaker of its type; intended for the protection of cable-type feeders or to raise the performance level of a switchboard when the transformer power rating is increased. E58868 Integration in a communications network Masterpact can be integrated in a general supervision system to optimise installation operation and maintenance. The communication architecture is open, and may be upgraded for interfacing with any protocol. Switch-disconnector versions E58865 The switch-disconnectors are derived directly from the circuit breakers and offer the same features and performance levels. They are available in HA, NA and HF versions, depending on the models. The HF version includes instantaneous protection to prevent closing on a short-circuit. Once closed, the switch-disconnectors are unprotected and behave like ordinary switches. They are often used for busbar coupling. 1000 V and 400 Hz distribution systems The Masterpact range can be used on 1000 V installations (mining industry) and 400 Hz systems (aeronautics, computer centres). 2 Masterpact Schneider Electric E58882 Thing will be never the same 3 frame sizes, 2 families The new range of power circuit breakers includes two families: c Masterpact NT, the world’s smallest true power circuit breaker, with ratings from 800 to 1600 A; c Masterpact NW, in two frame sizes, one from 800 to 4000 A and the other from 4000 A to 6300 A. Masterpact NT 056477 E58891 800 to 1600 A Masterpact NW 056473 De 4000 à 6300 A E58893 056472 E58892 800 to 4000 A 3 Masterpact Schneider Electric E58869 No other offer can put us in the shade Optimised volumes E58879 The smallest circuit breaker in the world Masterpact NT innovates by offering all the performance of a power circuit breaker in an extremely small volume. The 70 mm pole pitch means a three-pole drawout circuit breaker can be installed in a switchboard section 400 mm wide and 400 mm deep. E58880 Practical installation solutions E58881 The new range improves upon all the installation solutions which have already made Masterpact a success. It has been designed to standardise switchboards, optimise volumes and simplify installation: c incoming connection to top or bottom terminals; c no safety clearance required; c connection: v horizontal or vertical rear connection; v front connection with minimum extra space; v mixed front and rear connections; c 115 mm pole pitch on all versions; c no derating up to 55° C and 4000A. Optimised volumes Up to 4000 A, Masterpact NW circuit breakers are all the same size, the same as the old M08 to 32 range. From 4000 A to 6300 A, there is just one size, much smaller than before. Retrofit solutions Special connections are available to replace a fixed or drawout Masterpact M08 to 32 with a Masterpact NW, without modifying the busbars or the door cut-out. 4 Masterpact Schneider Electric E58867 A perfect fit E58871 Ease of installation E58879 With optimised sizes, the Masterpact NT and NW ranges simplify the design of switchboards and standardise the installation of devices: c a single connection layout for Masterpact NT; c three connection layouts for Masterpact NW: v one from 800 to 3200 A; v one for 4000 A; v one up to 6300 A; c identical connection terminals from 800 to 6300 A (Masterpact NW); c front connection requires little space because the connectors to not increase the depth of the device; c rear connection to vertical or horizontal busbars simply by turning the connectors 90°. E58870 E58872 Vertical front connection of a fixed Masterpact NW. Vertical and horizontal rear connection of a fixed Masterpact NW. Connection to busbars. 5 Masterpact Schneider Electric E58878 The shortest distance between two points Innovation E58875 Greater dependability… Filtered breaking The patented new design of the arc chutes includes stainless-steel filters. The chutes absorb the energy released during breaking, thus limiting the stresses exerted on the installation. They filter and cool the gases produced, reducing effects perceptible from the outside. Automatic unlatching The automatic unlatching of the circuit breaker operating mechanism for high short-circuits extends performance up to 150kA. It produces ultrafast tripping for all short-circuits higher than 37 kA (L1) and 65 kA (H3). For lower short-circuits, the system does not react so that the control unit can provide total discrimination with downstream devices. Filtered breaking More intelligent trip units… Today, with the high speed of calculation, the small size of memories and advances in miniaturisation, trip units have become circuit breaker control units offering increasingly powerful functions. They accurately measure system parameters, instantly calculate values, store data, log events, signal alarms, communicate, take action, etc. The new Masterpact ranges, equipped with Micrologic control units, constitute both an extremely reliable protective device and an accurate measurement instrument. E58874 User friendly… Intuitive use… Micrologic control units are equipped with a digital LCD display used in conjunction with simple navigation buttons. Users can directly access parameters and settings. Navigation between screens is intuitive and the immediate display of values greatly simplifies settings. Text is displayed in the desired language. … backed by incomparable security Protection functions are separate from the measurement functions and are managed by an ASIC electronic component. This independence guarantees immunity from conducted or radiated disturbances and ensures a high degree of reliability. A patented “double setting” system for protection functions establishes: * a maximum threshold set using the control-unit dials; * fine adjustments via the keypad or remotely. The fine adjustments for thresholds (to within one ampere) and tripping delays (to within a fraction of a second) are displayed directly on the screen. The control unit cover can be lead-sealed to prevent uncontrolled access to the dials and protect the settings. Navigation buttons on a Micrologic P control unit. 6 Masterpact Schneider Electric E58876 How many green circuit breakers do you know? Ready for the future Compliance with environmental requirements Schneider Electric fully takes into account environmental requirements, starting right from the design phase of every product through to the end of its service life: c the materials used for Masterpact are not potentially dangerous to the environment; c the production facilities are non-polluting in compliance with the ISO 14001 standard; c filtered breaking eliminates pollution in the switchboard; c the energy dissipated per pole is low, making energy losses insignificant; c the materials are marked to facilitate sorting for recycling at the end of product service life. Simple upgrading of installations Installations change, power levels increase, new equipment is required and switchboards must be extended. Masterpact is designed to adapt to these changes: c all control units are interchangeable; c communication with a supervision system is an option that may be added at any time; c a reserve chassis can be pre-addressed so that system parameters do not have to be modified when a drawout device is installed at a later date; c any future changes to the products will be designed to ensure continuity with the current ranges, thus simplifying installation upgrades. 7 Masterpact Schneider Electric Masterpact NT and NW 10 years already… 056409 The original Masterpact has set a new standard for power circuit breakers around the world. Over the years, other major manufacturers have tried to keep up by developing products incorporating Masterpact’s most innovative features, including the breaking principle, modular design and the use of composite materials. Today, Schneider Electric continues to innovate with the new Merlin Gerin Masterpact NT and NW ranges. In addition to the traditional features of power circuit breakers (withdrawability, discrimination and low maintenance), Masterpact now offers built-in communications and metering functions, all in optimised frame sizes. Masterpact NT and NW incorporate the latest technology to enhance both performance and safety. Easy to install, with user-friendly, intuitive operation and environment-friendly design, they are, quite simply, circuit breakers of their time. Setting the standard, once again 1 Masterpact Schneider Electric Loup ultimate in The power power distribution 2 Masterpact Schneider Electric 5 levels of performance… 044587 026160 Masterpact NT and NW offer 5 levels of performance to cover a wide range of applications. Special applications E58868 053598 N1 - for standard applications with low short-circuit levels. H1 - for industrial sites with high short-circuit levels or installations with two parallel-connected transformers. H2 - high-performance for heavy industry where very high short-circuits can occur. H3 - for incoming devices supplying critical applications requiring both high performance and a high level of discrimination. L1 - for high current-limiting capability and a discrimination level (37 kA) as yet unequalled by any other circuit breaker of its type; intended for the protection of cable-type feeders or to raise the performance level of a switchboard when the transformer power rating is increased. Switch-disconnectors The switch-disconnectors are derived directly from the circuit breakers. They are available in a number of versions: c for Masterpact NT: HA (equivalent to H1). c for Masterpact NW: v NA and HA (equivalent to N1 and H1) v HF, a high-performance switch-disconnector including instantaneous protection to prevent closing on a shortcircuit. Once closed, the switch-disconnector is unprotected and behaves like an ordinary switch. It is often used for busbar coupling. 029693 1000 V and 400 Hz distribution systems The Masterpact range can be used on 1000 V installations (mining industry) and 400 Hz systems (aeronautics, computer centres). 3 Masterpact Schneider Electric Tournesol Things will the never be same 4 Masterpact Schneider Electric 3 frame sizes, 2 families The new range of power circuit breakers includes two families: c Masterpact NT, the world’s smallest true power circuit breaker, with ratings from 800 to 1600 A; c Masterpact NW, in two frame sizes, one from 800 to 4000 A and the other from 4000 A to 6300 A. 056477 800 to 1600 A E58891 Masterpact NT 056473 4000 to 6300 A E58893 056472 800 to 4000 A E58892 Masterpact NW 5 Masterpact Schneider Electric Cypres No other offer can put us in the shade 6 Masterpact Schneider Electric E58879 Optimised volumes The smallest circuit breaker in the world Masterpact NT innovates by offering all the performance of a power circuit breaker in an extremely small volume. The 70 mm pole pitch means a three-pole drawout circuit breaker can be installed in a switchboard section 400 mm wide and 400 mm deep. E58881 E58880 Practical installation solutions: The new range improves upon all the installation solutions which have already made Masterpact a success. It has been designed to standardise switchboards, optimise volumes and simplify installation: c incoming connection to top or bottom terminals c no safety clearance required c connection: v horizontal or vertical rear connection v front connection with minimum extra space v mixed front and rear connections c 115 mm pole pitch on all versions c no derating up to 55° C and 4000A. Optimised volumes Up to 4000 A, Masterpact NW circuit breakers are all the same size, the same as the old M08 to 32 range. The dimensions of a 3-pole Masterpact NW40 drawout circuit breaker are therefore 440 mm x 440 mm x 400 mm (H x W x D). From 4000 A to 6300 A, there is just one size, much smaller than before. The dimensions of a 3-pole Masterpact NW63 drawout circuit breaker are therefore 480 mm x 730 mm x 440 mm (H x W x D). Retrofit solutions Special connections are available to replace a fixed or drawout Masterpact M08 to 32 with a Masterpact NW, without modifying the busbars or the door cut-out. 7 Masterpact Schneider Electric Abeilles A fit perfect 8 Masterpact Schneider Electric E58871 Ease of installation With optimised sizes, the Masterpact NT and NW ranges simplify the design of switchboards and standardise the installation of devices: c a single connection layout for Masterpact NT c three connection layouts for Masterpact NW: v one from 800 to 3200 A v one for 4000 A v one up to 6300 A c identical connection terminals from 800 to 6300 A (Masterpact NW) c front connection requires little space because the connectors to not increase the depth of the device c rear connection to vertical or horizontal busbars simply by turning the connectors 90°. E58870 E58872 Vertical front connection of a fixed Masterpact NW Connection to busbars. Vertical and horizontal rear connection of a fixed Masterpact NW. 9 Masterpact Schneider Electric Girafe The shortest distance between two points Giraffe hoto iraffe” p e the “G n replac gic Microlo You ca by… hoto. logic” p o r ic M “ the 10 Masterpact Schneider Electric Innovation E58875 Greater dependability… Filtered breaking The patented new design of the arc chutes includes stainless-steel filters. The chutes absorb the energy released during breaking, thus limiting the stresses exerted on the installation. They filter and cool the gases produced, reducing effects perceptible from the outside. Automatic unlatching Filtered breaking. The automatic unlatching of the circuit breaker operating mechanism for high short-circuits extends performance up to 150kA. It produces ultrafast tripping for all short-circuits higher than 37 kA (L1) and 65 kA (H3). For lower short-circuits, the system does not react so that the control unit can provide total discrimination with downstream devices. E58874 Greater intelligence… Today, with the high speed of calculation, the small size of memories and advances in miniaturisation, trip units have become circuit breaker control units offering increasingly powerful functions. They accurately measure system parameters, instantly calculate values, store data, log events, signal alarms, communicate, take action, etc. The new Masterpact ranges, equipped with Micrologic control units, constitute both an extremely reliable protective device and an accurate measurement instrument. User friendly… Intuitive use… Navigation buttons on a Micrologic P control unit. Micrologic control units are equipped with a digital LCD display used in conjunction with simple navigation buttons. Users can directly access parameters and settings. Navigation between screens is intuitive and the immediate display of values greatly simplifies settings. Text is displayed in the desired language. … backed by incomparable security Protection functions are separate from the measurement functions. They are managed by an ASIC electronic component common to all the control units to guarantee immunity from conducted or radiated disturbances and ensure a high degree of reliability. A patented «double setting» system for protection functions establishes a maximum threshold set using the control-unit dials and fine adjustments via the keypad or remotely. The fine adjustments for thresholds (to within one ampere) and tripping delays (to within a fraction of a second) are displayed directly on the screen. The control unit cover can be lead-sealed to prevent uncontrolled access to the dials and protect the settings. 11 Masterpact Schneider Electric Oiseaux How many green circuit breakers do you know? 12 Masterpact Schneider Electric Ready for the future Compliance with environmental requirements Schneider Electric fully takes into account environmental requirements, starting right from the design phase of every product through to the end of its service life: c the materials used for Masterpact are not potentially dangerous to the environment c the production facilities are non-polluting in compliance with the ISO 14001 standard c filtered breaking eliminates pollution in the switchboard and the energy dissipated per pole is low, making energy losses insignificant c the materials are marked to facilitate sorting for recycling at the end of product service life. Integration in a communications network Masterpact can be integrated in a general supervision system to optimise installation operation and maintenance. The communication architecture is open, and may be upgraded for interfacing with any protocol. Simple upgrading of installations Installations change, power levels increase, new equipment is required and switchboards must be extended. Masterpact is designed to adapt to these changes: c all control units are interchangeable c communication with a supervision system is an option that may be added at any time c a reserve chassis can be pre-addressed so that system parameters do not have to be modified when a drawout device is installed at a later date c any future changes to the products will be designed to ensure continuity with the current ranges, thus simplifying installation upgrades. 13 Masterpact Schneider Electric 8 Masterpact Schneider Electric Masterpact Functions and characteristics Presentation 1 General overview Detailed contents 10 Circuit breakers and switch-disconnectors NT06 to NT16 NW08 to NW63 12 14 Micrologic control units Overview of functions Micrologic A «ammeter» Micrologic P «power meter» Micrologic H «harmonic meter» Accessories and test equipment 16 18 20 24 26 Communication COM option in Masterpact Overview of functions Masterpact in a communication network 28 29 30 Connections Overview of solutions Optional accessories 32 33 Locking On the device On the chassis 36 37 Indication contacts Remote operation 38 Remote ON/OFF Remote tripping 40 43 Accessories Source-changeover systems 44 Presentation Mechanical interlocking Electrical interlocking Associated automatic controllers 46 47 48 49 Display modules 50 Dimensions and connection Electrical diagrams Installation recommendations Additional characteristics References 9 Masterpact 53 81 91 115 121 Schneider Electric Functions and characteristics General overview Detailed contents This chapter describes all the functions offered by Masterpact NT and NW devices. The two product families have identical functions implemented using the same or different components depending on the case. Circuit breakers and switch-disconnectors page 12 056402 c ratings: v Masterpact NT 630 to 1600 A v Masterpact NW 800 to 6300 A c circuit breakers type N1, H1, H2, H3, L1 c switch-disconnectors type NA, HA, HF c 3 or 4 poles c fixed or drawout versions c option with neutral on the right c protection derating page 16 E46256 E46253 Micrologic control units Ammeter A 2.0 basic protection 5.0 selective protection 6.0 selective + earth-fault protection 7.0 selective + earth-leakage protection Power meter P 5.0 selective protection 6.0 selective + earth-fault protection 7.0 selective + earth-leakage protection Harmonic meter H 5.0 selective protection 6.0 selective + earth-fault protection 7.0 selective + earth-leakage protection c external sensor for earth-fault protection c rectangular sensor for earth-leakage protection c setting options (long-time rating plug): v low setting 0.4 to 0.8 x Ir v high setting 0.8 to 1 x Ir v without long-time protection c external power-supply module c battery module 100 % 40 % menu Communication page 28 c COM option in Masterpact c Masterpact in a communication network E46427 E46428 E46431 056403 page 32 E46426 Connections c rear connection (horizontal or vertical) c front connection c mixed connections c optional accessories v bare-cable connectors and connector shields v terminal shields v vertical-connection adapters v cable-lug adapters v interphase barriers v spreaders v disconnectable front-connection adapter v safety shutters, shutter locking blocks, shutter position indication and locking 10 Masterpact Schneider Electric 056405 page 36 E47481 E47482 Locking c pushbutton locking by padlockable transparent cover c OFF-position locking by padlock or keylock c chassis locking in disconnected position by keylock c chassis locking in connected, disconnected and test positions c door interlock (inhibits door opening with breaker in connected position) c racking interlock (inhibits racking with door open) c racking interlock between crank and OFF pushbutton c automatic spring discharge before breaker removal c mismatch protection page 38 E47301 E47302 056428 Indication contacts c standard or low-level contacts: v ON/OFF indication (OF) v «fault trip» indication (SDE) v carriage switches for connected (CE), disconnected (CD) and test (CT) positions c programmable contacts: v 2 contacts (M2C) v 6 contacts (M6C). OF contact M2C contact E47303 page 40 E47304 Gear motor MX, XF and MN voltage releases Accessories c auxiliary terminal shield c operation counter c escutcheon c transparent cover for escutcheon c escutcheon blanking plate 11 Masterpact page 44 E47483 056407 Remote operation c remote ON/OFF: v gear motor v XF closing or MX opening voltage releases v PF ready-to-close contact v options: RAR automatic or Res electrical remote reset - BPFE electrical closing pushbutton c remote tripping function: v MN voltage release - standard - adjustable or non-adjustable delay v or second MX voltage release 0039 9 Schneider Electric 056408 Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 common characteristics number of poles rated insulation voltage (V) impulse withstand voltage (kV) rated operational voltage (V AC 50/60 Hz) suitability for isolation degree of pollution Ui Uimp Ue IEC 60947-2 IEC 60664-1 3/4 1000/1250 12 690 / 1000V 3 circuit-breaker characteristics as per IEC 60947-2 rated current (A) rating of 4th pole (A) sensor ratings (A) type of circuit breaker ultimate breaking capacity (kA rms) V AC 50/60 Hz rated service breaking capacity (kA rms) rated short-time withstand current (kA rms) V AC 50/60 Hz integrated instantaneous protection (kA peak ±10%) rated making capacity (kA peak) V AC 50/60 H In at 40°C / 50°C** Icu 220/415 V 440 V 525 V 690 V 1000 V % Icu 0.5 s 3s Ics Icw Icm 220/415 V 440 V 525 V 690 V 1000 V break time (ms) closing time (ms) circuit-breaker characteristics as per NEMA AB1 breaking capacity (kA) V AC 50/60 Hz 240 V 480 V 600 V switch-disconnector characteristics as per IEC 60947-3 type of switch-disconnector rated making capacity (kA peak) V AC 50/60 Hz Icm rated short-time withstand current (kA rms) V AC 50/60 Hz ultimate breaking capacity (Icu) with external protection relay, maximum delay 350 ms 220/415 V 440 V 500/690 V 1000 V 0.5 s 3s Icw installation, connection and maintenance service life C/O cycles x 1000 mechanical electrical with maintenance without maintenance without maintenance 440 V 690 V 1000 V 690 V FC RC FC RC 3P 4P 3P 4P 3P/4P 3P/4P motor control (AC3-947-4) connection drawout fixed dimensions (mm) HxWxD drawout fixed weight (kg) (approximate) drawout fixed * see the current-limiting curve in the «additional characteristics» section ** 50°C: rear vertical connected. Refer to temperature derating tables for other connection types. (1) SELLIM system 12 Masterpact Schneider Electric NT06 NT08 NT10 NT12 NT16 630 630 400 to 630 800 800 400 to 800 1000 1000 400 to 1000 1250 1250 630 to 1250 1600 1600 800 to 1600 H1 42 42 42 42 100 % 42 20 88 88 88 88 25 < 50 L1* 150 130 100 25 - H10 20 10 1(1) 330 286 220 52 9 20 42 25 42 42 42 150 100 25 HA 75 75 75 42 20 42 H1 42 42 42 42 100 % 42 20 88 88 88 88 25 < 50 H10 20 - 42 42 42 - HA10 42 20 20 HA 75 75 75 42 20 42 HA10 42 20 20 25 12.5 6 (NT16: 3) 2 (NT16: 1) 2 (NT16: 1) c c c c 25 12.5 0.5 c c - 25 25 25 12.5 12.5 12.5 6 3 3 2 0.5 3 2 c c c c c c c c c c 322 x 288 x 280 322 x 358 x 280 301 x 274 x 211 301 x 344 x 211 30/39 14/18 20 42 25 sensor selection sensor rating (A) Ir threshold setting (A) 400 160 to 400 630 250 to 630 13 800 320 to 800 Masterpact 1000 400 to 1000 1250 500 to 1250 1600 640 to 1600 Schneider Electric 056409 Functions and characteristics Circuit breakers and switch-disconnectors NW08 to NW63 common characteristics number of poles rated insulation voltage (V) impulse withstand voltage (kV) rated operational voltage (V AC 50/60 Hz) suitability for isolation degree of pollution Ui Uimp Ue IEC 60947-2 IEC 60664-1 3/4 1000/1250 12 690/1150 4 circuit-breaker characteristics as per IEC 60947-2 056410 rated current (A) rating of 4th pole (A) sensor ratings (A) type of circuit breaker ultimate breaking capacity (kA rms) V AC 50/60 Hz rated service breaking capacity (kA rms) rated short-time withstand current (kA rms) V AC 50/60 Hz integrated instantaneous protection (kA peak ± 10%) rated making capacity (kA peak) V AC 50/60 Hz In at 40°C / 50°C** Icu 220/415 V 440 V 525 V 690 V 1150 V % Icu 1s 3s Ics Icw Icm 220/415 V 440 V 525 V 690 V 1150 V break time (ms) closing time (ms) circuit-breaker characteristics as per NEMA AB1 breaking capacity (kA) V AC 50/60 Hz 240 V 480 V 600 V switch-disconnector characteristics as per IEC 60947-3 type of switch-disconnector rated making capacity (kA peak) V AC 50/60 Hz Icm rated short-time withstand current (kA rms) V AC 50/60 Hz ultimate breaking capacity (Icu) with external protection relay, maximum delay 350 ms 220/415 V 440 V 500/690 V 1150 V 1s 3s Icw installation, connection and maintenance service life C/O cycles x 1000 mechanical electrical with maintenance without maintenance without maintenance 440 V 690 V 1150 V 690 V FC RC FC RC 3P 4P 3P 4P 3P/4P 3P/4P motor control (AC3-947-4) connection drawout fixed dimensions (mm) HxWxD drawout fixed weight (kg) (approximate) drawout fixed * see the current-limiting curve in the «additional characteristics» section ** 50°C: rear vertical connected. Refer to temperature derating tables for other connection types. (1) except 4000 A 14 Masterpact Schneider Electric NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63 800 800 400 to 800 2500 2500 1250 to 2500 4000 4000 2000 to 4000 4000 4000 2000 to 4000 H3 150 150 130 100 - H10 50 65 65 150 330 330 286 220 25 50 50 without 105 25 H1 H2 100 150 100 150 100 130 100 100 100 % 100 100 100 100 without270 220 330 220 330 220 286 220 220 25 25 < 80 150 150 100 - 100 100 100 HA10 105 50 50 50 HA 187 187 187 85 85 85 1000 1000 400 to 1000 N1 H1 H2 42 65 100 42 65 100 42 65 85 42 65 85 100 % 42 65 85 22 36 50 without without 190 88 143 220 88 143 220 88 143 187 88 143 187 25 25 25 < 70 42 42 42 65 65 65 100 100 85 NA 88 88 88 42 42 HA 105 105 105 50 36 50 HF 187 187 187 85 75 85 25 12.5 10 10 10 10 10 10 10 10 10 c c c c c c c c c c c c 439 x 441 x 395 439 x 556 x 395 352 x 422x 297 352 x 537x 297 90/120 60/80 1250 1250 630 to 1250 1600 1600 800 to 1600 2000 2000 1000 to 2000 L1* 150 150 130 100 - H10 50 30 30 80 330 330 286 220 10 50 50 without 105 25 150 150 100 - 65 65 65 100 100 85 HA10 105 50 50 50 HA 105 105 105 50 36 50 HF 187 187 187 85 75 85 0.5 c c - 20 10 8 6 6 c c c c 3 3 c c - H1 H2 65 100 65 100 65 85 65 85 100 % 65 85 36 75 without 190 143 220 143 220 143 187 143 187 25 25 < 70 8 6 6 c c c c 3200 3200 1600 to 3200 H3 150 150 130 100 - L1* 150 150 130 100 - H10 50 65 65 150 330 330 286 220 25 30 30 80 330 330 286 220 10 50 50 without 105 25 150 150 100 150 150 100 - 65 65 65 100 100 85 HA10 105 50 50 50 HA 121 121 121 55 55 55 HF 187 187 187 85 75 85 0.5 c c - 20 10 5 2.5 2.5 c c c (1) c 2 2 6 c c - 3 3 c c - H1 H2 65 100 65 100 65 85 65 85 100 % 65 85 65 75 without 190 143 220 143 220 143 187 143 187 25 25 < 70 5 2.5 2.5 c c c (1) c 1.25 1.25 2.5 c c - 5000 5000 2500 to 5000 6300 6300 3200 to 6300 150 150 100 10 5 1.5 1.5 1.5 1.5 c c c c 479 x 786 x 395 479 x 1016 x 395 352 x 767x 297 352 x 997x 297 225/300 120/160 0.5 c c - sensor selection sensor rating (A) Ir threshold setting (A) 400 160 to 400 630 250 to 630 800 320 to 800 1000 400 to 1000 15 1250 500 to 1250 1600 630 to 1600 Masterpact 2000 800 to 2000 2500 1000 to 2500 3200 1250 to 3200 4000 1600 to 4000 5000 2000 to 5000 6300 2500 to 6300 Schneider Electric Functions and characteristics Micrologic control units Overview of functions All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site. Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications. Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management. Dependability Integration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances. On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor. Micrologic name codes Current protection Micrologic 2: basic protection Z X: type of protection c 2 for basic protection c 5 for selective protection c 6 for selective + earth-fault protection c 7 for selective + earth-leakage protection Y: control-unit generation Identification of the control-unit generation. “0” signifies the first generation. Z: type of measurement c A for “ammeter” c P for “power meter” c H for “harmonic meter”. E46019 X Y t Protection: 0 Ir Isd I long time + instantaneous Micrologic 5: selective protection E46020 2.0 A t Protection: 056411 0 Ir Isd Ii long time + short time + instantaneous I t E46033 E46020 Micrologic 6: selective + earth-fault protection t Protection: 0 Ir Isd Ii 0 I Ig I long time + short time + instantaneous + earth fault t E46034 E46020 Micrologic 7: selective + earth-leakage protection t Protection: 0 16 Ir Isd Ii Masterpact I 0 I∆n I long time + short time + instantaneous + earth leakage Schneider Electric Measurements and programmable protection A: ammeter c I1, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these measurements c fault indications c settings in amperes and in seconds P: A + power meter + programmable protection c measurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, Vpeak, Apeak, power factor and maximeters and minimeters c IDMTL long-time protection, minimum and maximum voltage and frequency, voltage and current imbalance, phase sequence, reverse power c load shedding and reconnection depending on power or current c measurements of interrupted currents, differentiated fault indications, maintenance indications, event histories and time-stamping, etc. H: P + harmonics 2.0 A E46251 c power quality: fundamentals, distortion, amplitude and phase of harmonics up to the 51st order c waveform capture after fault, alarm or on request c enhanced alarm programming: thresholds and actions 100 % 40 % E46256 E46255 6.0 H 7.0 H E46256 7.0 P E46255 6.0 P 5.0 H E46256 5.0 P E46256 5.0 A E46252 menu 100 % 40 % 6.0 A E46253 menu 100 % 40 % 7.0 A E46253 menu 100 % 40 % menu 17 Masterpact Schneider Electric Control units Micrologic A “ammeter” Micrologic A control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection, version 7 provides earth-leakage protection. Protection settings ........................................................ E46028 Functions and characteristics Micrologic 6.0 A 9 10 ∆t= I∆n= tsd= tr= Isd= Ii= Ir= Ig= tg= MAX s kA 11 100 % 12 40 % Protection thresholds and delays are set using the adjustment dials. The selected values are momentarily displayed in amperes and in seconds. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I2t type (ON or OFF) for short-time delay. Earth fault protection Residual or source ground return. Selection of I2t type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. d Protected against nuisance tripping. k DC-component withstand class A up to 10 A. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3t), neutral protection at 0.5 In (4P 3t + N/2), neutral protection at In (4P 4t). Zone selective interlocking (ZSI) A ZSI terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping. “Ammeter” measurements ........................................... 13 menu long time Ir 1 .7 .6 .5 .4 alarm tr 8 (s) 4 .9 12 16 .95 2 .98 1 20 24 1 .5 .8 x In 3 tsd (s) 5 D C B A E .3 .2 .1 on .2 .1 0 I t off 2 delay tg F G H J Ii .4 .4 .3 setting Ig Communication option 7 In conjunction with the COM communication option, the control unit transmits the following: c setting values c all “ammeter” measurements c tripping causes c maximeter reset. instantaneous short time (s) on .2 .1 2 I t 6 8 10 12 15 off 2 x In test .4 .4 .3 .3 .2 .1 4 3 Micrologic A control units measure the true rms value of currents. A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I1, I2, I3, IN, Ig, I∆n, stored-current (maximeter) and setting values by successively pressing the navigation button. The optional external power supply makes it possible to display currents < 20% In. 2 @ 6 Ir Isd 4 5 3 2.5 6 2 8 1.5 10 x Ir menu 4 6 8 0 off ground fault 1 2 3 4 5 6 7 8 9 10 11 12 13 long-time current setting and tripping delay overload signal (LED) short-time pick-up and tripping delay instantaneous pick-up earth-leakage or earth-fault pick-up and tripping delay earth-leakage or earth-fault test button long-time rating plug screw test connector lamp test, reset and battery test indication of tripping cause digital display three-phase bargraph and ammeter navigation buttons Note. Micrologic A control units come with a transparent leadseal cover as standard. 18 Masterpact Schneider Electric Micrologic 2.0 A long time current setting (A) Ir = In x … tripping between 1.05 and 1.20 x Ir time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 %) thermal memory Isd = Ir x … 1.5 8 10 2 2.5 3 4 5 6 Ir tr Isd I menu I2 I3 IN I1 no auxiliary source (where I > 20 % In) I1 max I2 max I3 max IN max tr at 1.5 x Ir tr at 6 x Ir tr at 7.2 x Ir Micrologic 5.0 / 6.0 / 7.0 A 0.4 0.5 0.6 0.7 0.8 0.9 0.95 other ranges or disable by changing rating plug 12.5 25 50 100 200 300 400 0.5 1 2 4 8 12 16 0.34 0.69 1.38 2.7 5.5 8.3 11 20 minutes before and after tripping 0.98 1 500 20 13.8 600 24 16.6 8 10 E46023 Micrologic 5.0 / 6.0 / 7.0 A long time current setting (A) Ir = In x … tripping between 1.05 and 1.20 x Ir time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % thermal memory time delay (ms) at In or 1200 A 600 24 16.6 Micrologic 2.0 A Protection t Ir tr Isd tsd Isd = Ir x … 1.5 2 2.5 3 4 Off I2t On tsd (max resettable time) tsd (max break time) 0 20 80 0.1 0.1 80 140 0.2 0.2 140 200 0.3 0.3 230 320 0.4 0.4 350 500 Ii = In x … 2 3 4 6 8 10 12 15 off Ig = In x … In i 400 A 400 A < In i 1200 A In > 1200 A settings I2t Off I2t On tg (max resettable time) tg (max break time) Micrologic 6.0 A A B C 0.3 0.3 0.4 0.2 0.3 0.4 500 640 720 0 0.1 0.2 0.1 0.2 20 80 140 80 140 200 D 0.5 0.5 800 0.3 0.3 230 320 E 0.6 0.6 880 0.4 0.4 350 500 F 0.7 0.7 960 G 0.8 0.8 1040 H 0.9 0.9 1120 J 1 1 1200 Micrologic 7.0 A 0.5 1 2 3 5 7 60 80 140 350 350 500 800 800 1000 settings I2t residual earth leakage (Vigi) sensitivity (A) I∆n accuracy: 0 to -20 % time delay (ms.) settings t∆n (max resettable time) t∆n (max break time) Ammeter continuous current measurements measurements from 20 to 200 % of In accuract: 1.5 % (including sensors) maximeters 140 140 200 230 230 320 5 6 Ii 0 E46024 earth fault pick up (A) accuracy: ±10 % 500 20 13.8 t 0 continuous current measurements measurements from 20 to 200 % de In accuracy: 1.5% (including sensors) maximeters instantaneous pick-up (A) accuracy: ±10 % 1 fixed: 20 ms Ammeter short time pick-up (A) accuracy: ±10 % time delay (ms) at 10 Ir 0.98 I t 2 I t on Ig 2 tg I t off 0 Micrologic 5.0 / 6.0 / 7.0 A 10 20 30 E46243A instantaneous pick-up (A) accuracy: ±10 % time delay tr at 1.5 x Ir tr at 6 x Ir tr at 7.2 x Ir 0.4 0.5 0.6 0.7 0.8 0.9 0.95 other ranges or disable by changing rating plug 12.5 25 50 100 200 300 400 0.5 1 2 4 8 12 16 0.34 0.69 1.38 2.7 5.5 8.3 11 20 minutes before and after tripping E46022 Protection t I I∆n t∆n 0 I menu I2 I3 IN Ig I∆n I1 no auxiliary source (where I > 20 % In) I1 max I2 max I3 max IN max Ig max I∆n max Note. All current-based protection functions require no auxiliary source. The test / reset button resets maximeters, clears the tripping indication and tests the battery. 19 Masterpact Schneider Electric Control units Micrologic P “power” Micrologic P control units include all the functions offered by Micrologic A. In addition, they measure voltages and calculate power and energy values. They also offer new protection functions based on currents, voltages, frequency and power reinforce load protection. Protection settings ........................................................ E46017 Functions and characteristics Micrologic 6.0 P 9 10 I (A) Trip 2000A 11 24s 20 kA 0.4s Programmable alarms and other protection ...................... Off 13 14 12 15 2 long time .7 .6 .5 .4 alarm tr 8 (s) 4 .9 12 16 .95 2 .98 1 20 24 1 .5 .8 x In 7 @ 6 Ir instantaneous short time 3 Isd 4 5 3 2.5 6 2 8 1.5 10 x Ir 16 tsd .4 .4 .3 .2 .3 .1 .2 .1 2 0 D C B A E on I t off delay tg F G H J Ii (s) setting Ig 5 Depending on the thresholds and time delays set using the keypad or remotely using the COM option, the Micrologic P control unit monitors currents and voltage, power, frequency and the phase sequence. Each threshold overrun is signalled remotely via the COM option. Each threshold overrun may be combined with tripping (protection) or an indication carried out by an optional M2C or M6C programmable contact (alarm), or both (protection and alarm). Load shedding and reconnection ........................................ Ir 1 + The adjustable protection functions are identical to those of Micrologic A (overloads, short-circuits, earth-fault and earth-leakage protection). Double setting Within the range determined by the adjustment dial, fine adjustment of thresholds (to within one ampere) and time delays (to within one second) is possible on the keypad or remotely using the COM option. IDMTL setting Coordination with fuse-type or medium-voltage protection systems is optimised by adjusting the slope of the overload-protection curve. This setting also ensures better operation of this protection function with certain loads. Neutral protection On three-pole circuit breakers, neutral protection may be set using the keypad or remotely using the COM option, to one of four positions: neutral unprotected (4P 3t), neutral protection at 0.5 In (4P 3t + N/2), neutral protection at In (4P 4t) and neutral protection at 2 In (4P 3t + 2N). Neutral protection at 2 In is used when the neutral conductor is twice the size of the phase conductors (major load imbalance, high level of third order harmonics). On four-pole circuit breakers, neutral protection may be set using a three-position switch or the keypad: neutral unprotected (4P 3t), neutral protection at 0.5 In (4P 3t + N/2), neutral protection at In (4P 4t). Neutral protection produces no effect if the long-time curve is set to one of the IDMTL protection settings. (s) on .2 .1 2 I t 6 8 10 12 15 off 2 x In test .4 .4 .3 .3 .2 .1 4 3 4 6 8 0 off ground fault Load shedding and reconnection parameters may be set according to the power or the current flowing through the circuit breaker. Load shedding is carried out by a supervisor via the COM option or by an M2C or M6C programmable contact. Measurements ....................................................................... The Micrologic P control unit calculates in real time all the electrical values (V, A, W, VAR, VA, Wh, VARh, VAh, Hz), power factors and crest factors. The Micrologic P control unit also calculates demand current and demand power over an adjustable time period. Each measurement is associated with a minimeter and a maximeter. In the event of tripping on a fault, the interrupted current is stored. The optional external power supply makes it possible to display the value with the circuit breaker open or not supplied. Histories and maintenance indicators ................................ The last ten trips and alarms are recorded in two separate history files. Maintenance indications (contact wear, operation cycles, etc.) are recorded for local access. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 long-time current setting and tripping delay overload signal (LED) short-time pick-up and tripping delay instantaneous pick-up earth-leakage or earth-fault pick-up and tripping delay earth-leakage or earth-fault test button long-time rating plug screw test connector lamp + battery test and indications reset indication of tripping cause high-resolution screen measurement display maintenance indicators protection settings navigation buttons hole for settings lockout pin on transparent cover Indication option via programmable contacts The M2C (two contacts) and M6C (six contacts) auxiliary contacts may be used to signal threshold overruns or status changes. They can be programmed using the keypad on the Micrologic P control unit or remotely using the COM option. Communication option (COM) The communication option may be used to: c remotely read and set parameters for the protection functions c transmit all the calculated indicators and measurements c signal the causes of tripping and alarms c consult the history files and the maintenance-indicator register. An event log and a maintenance register, stored in control-unit memory but not available locally, may be accessed in addition via the COM option. Note. Micrologic P control units come with a non-transparent lead-seal cover as standard. 20 Masterpact Schneider Electric Micrologic 5.0 / 6.0 / 7.0 P long time (rms) current setting (A) Ir = In x … tripping between 1.05 and 1.20 x Ir time delay (s) accuracy: 0 to -30 % accuracy: 0 to -20 % accuracy: 0 to -20 % IDMTL setting curve slope thermal memory time delay (ms.) at 10 x Ir Ir tr Isd IDMTL 2 2.5 3 4 Off I2t On tsd (max resettable time) tsd (max break time) 0 20 80 0.1 0.1 80 140 0.2 0.2 140 200 0.3 0.3 230 320 0.4 0.4 350 500 Ii = In x … 2 3 4 6 Ig = In x … In i 400 A 400 A < In i 1200 A In > 1200 A settings I2t Off I2t On tg (max resettable time) tg (max break time) Micrologic 6.0 P A B C 0.3 0.3 0.4 0.2 0.3 0.4 500 640 720 0 0.1 0.2 0.1 0.2 20 80 140 80 140 200 settings I2t 5 6 8 10 tsd 8 10 12 15 OFF D 0.5 0.5 800 0.3 0.3 230 320 E 0.6 0.6 880 0.4 0.4 350 500 F 0.7 0.7 960 G 0.8 0.8 1040 H 0.9 0.9 1120 J 1 1 1200 Micrologic 7.0 P 0.5 1 2 3 5 10 60 60 140 350 350 500 800 800 1000 140 140 200 230 230 320 I 0 E46024 1.5 Alarms and other protection t 2 I t on Ig 2 I t off tg 0 7 20 30 t I I∆n t∆n 0 I Micrologic 5.0 / 6.0 / 7.0 P current current imbalance maximum demand current Iimbalance Imax demand: I1, I2, I3, IN, Ig threshold 0.05 to 0.6 Imax 0.4 In at short-time pick-up time delay 1 to 40 s. 0 to 1500 s. voltage voltage imbalance minimum voltage maximum voltage Uimbalance Umin Umax 0.02 to 0.3 Uaverage 60 to 690 V between phases 100 to 930 V between phases 1 to 40 s. 0.2 to 5 s. 0.2 to 5 s. power reserve power rP 5 to 500 kW 0.2 to 20 s. frequency minimum frequency maximum frequency Fmin Fmax 45 to 400 Hz 45 to 540 Hz 0.2 to 5 s. 0.2 to 5 s. t threshold threshold delay ∆Ø Ø1/2/3 or Ø1/3/2 Load shedding and reconnection measured value current power 600 24 16.6 t Ii Isd = Ir x … residual earth leakage (Vigi) sensitivity (A) I∆n accuracy: 0 to -20 % time delay (ms.) settings t∆n (max resettable time) t∆n (max break time) phase sequence sequence 500 20 13.8 E46243 earth fault pick-up (A) accuracy: ±10 % 1 E46015 instantaneous pick-up (A) accuracy: ±10 % 0.98 I P delay 0 I/U/P/F instantaneous Micrologic 5.0 / 6.0 / 7.0 P threshold 0.5 to 1 Ir per phases 200 kW to 10 MW time delay 20% tr to 80% tr. 10 to 3600 s. E46016 short time (rms) pick-up (A) accuracy: ±10 % time delay (ms.) at 10 x Ir tr at 1.5 x Ir tr at 6 x Ir tr at 7.2 x Ir + Micrologic 5.0 / 6.0 / 7.0 P 0.4 0.5 0.6 0.7 0.8 0.9 0.95 other ranges or disable by changing rating plug 12.5 25 50 100 200 300 400 0.5 1 2 4 8 12 16 0.34 0.69 1.38 2.7 5.5 8.3 11 SIT VIT EIT HVFuse DT 20 minutes before and after tripping E46021 Protection t threshold threshold delay delay 0 I/P Note. All current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker. 21 Masterpact Schneider Electric Control units Micrologic P “power” 3850A E46261 E46258 Functions and characteristics Imax instant. N 1 2 3 100 I1 I2 = = 4800A 4600A I3 = 4000A IN = = 200A 13A I 50 Reset ( + / - ) Navigation from one display to another is intuitive. The six buttons on the keypad provide access to the menus and easy selection of values. When the setting cover is closed, the keypad may no longer be used to access the protection settings, but still provides access to the displays for measurements, histories, indicators, etc. Measurements ....................................................................... Instantaneous values The value displayed on the screen is refreshed every second. Minimum and maximum values of measurements are stored in memory (minimeters and maximeters). 0 currents Default display Display of a maximum current I rms U inst. U12 = U23 = U31 = U1N = U2N = U3N = E46263 E46262 I max rms 400V 404V 401V 230V 229V 233V Pinst. P (kW) +2180 Q (kVAR) -650 S (kVA) +2280 A A A A 1 2 e-fault 1 2 e-fault 3 N e-leakage 3 N différentiel V V V % 12 23 31 1N 2N 3N (U12 + U23 + U31) / 3 voltages U rms V rms U average rms U imbalance power, energy P active, Q reactive, S apparent E active, E reactive, E apparent W, Var, VA Wh, VARh, VAh power factory PF totals totals consumed - supplied totals consumed totals supplied total frequencies F (Hz) Display of a power E46265 E47305 Display of a voltage P Pdemand demande PActive P (kW) 2180 kW +2180 QRéactive (kVAR) Q - 650 kVAR -650 60.0 S (kVA) Apparente+2280 S 2280 kVA Display of a frequency Display of a demand power F Hz Demand metering The demand is calculated over a fixed or sliding time window that may be programmed from 5 to 60 minutes. According to the contract signed with the power supplier, an indicator associated with a load shedding function makes it possible to avoid or minimise the costs of overrunning the subscribed power. Maximum demand values are systematically stored and time stamped (maximeter). currents I demand I max demand A A A A 1 2 e-fault 1 2 e-fault 3 N e-leakage 3 N e-leakage power P, Q, S demand P, Q, S max demand W, Var, VA W, Var, VA totals totals Minimeters and maximeters Only the current and power maximeters may be displayed on the screen. Trip history Ir 03/08/1999 Isd 27/07/1999 Umax 30/06/1999 Display of a tripping history E46260 E46259 Histories ................................................................................. Trip 03/08/1999 12:02:36 Ir = 1000A I1 = 1200A I2 = I3 = 1430A 1060A IN = 53A Display after tripping The last ten trips and alarms are recorded in two separate history files that may be displayed on the screen. c tripping history: v type of fault v date and time v values measured at the time of tripping (interrupted current, etc.). c alarm history: v type of fault v date and time v values measured at the time of the alarm.. Maintenance indicators ........................................................ A number of maintenance indicators may be called up on the screen: c contact wear c operation counter: v cumulative total v total since last reset 22 Masterpact Schneider Electric E47070 POWERLOGIC System Manager Demo Edit View Setup Control Display Reports File Time 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 Ready 5 seconds Event 08:49:06 08:49:01 08:48:38 08:48:30 08:46:16 08:39:19 08:39:06 08:39:06 08:38:57 08:30:44 08:24:31 08:24:30 08:24:15 08:18:07 07:54:05 07:53:55 07:53:54 07:51:46 07:51:33 07:51:29 07:50:17 07:50:17 07:49:13 07:48:57 07:48:38 07:48:22 07:46:54 07:44:59 07:44:59 With the communication option Tools Window Help Sampling Mode : MANUAL Module Net Server Shutdown User Log Out DB Table Change DB Table Change DB Table Change User Log In Security Check Net Server Started User Log In Net Server Shutdown Security Check Net server Started User Log IN IPC Error DB Table Change DB Table Change DB Table Change DB Table Change DB Table Change DB Table Change DB Table Change DB Table Change Setup: Device Name Change Setup: Device Added Setup: Device Name Change Setup: Device Added User Log In Security Check Net Server Started User : master User : master User : master User : master User : master User : master Key Status : Key Found User : master PowerLogic Network… SMS-3000 Client Alarm Setup Alarm Setup Alarm Setup SMS-3000 Client PowerLogic Network… Level : 1 PowerLogic Network… Event/Alarm/Network… User : master Level : 1 PowerLogic Network… Key Status : Key Found PowerLogic Network… User : master Level : 1 PowerLogic Network… Event/Alarm/Network… User : NA Err : 109 SMS-3000 Client User : -1 Logger Template Devices Logger Setup User : -1 Logger Template Topics Logger Setup User : -1 Logger Templates Logger Setup User : master Analog Levels Assigned Alarm Setup User : master Analog Levels Template Alarm Setup User : master Functions Alarm Setup User : master Digital Levels Assigned Alarm Setup User : master Analog Levels Assigned Alarm Setup Device : MicroLogic Breaker User :master Device Setup Device : MicroLogic Breaker User :master Device Setup Device : Transformer Temp User : master Device Setup Device : Transformer Temp User :master Device Setup User : master User Level : 1 SMS-3000 Client Key Status : Key Found PowerLogic Network… User :master Level : 1 PowerLogic Network… ONLINE: DEMO Level : 1 User level : 1 TOD Event Tasks Tasks TOD Events User level : 1 No working system Display of an event log on a supervisor 9:30 Additional measurements, maximeters and minimeters Certain measured or calculated values are only accessible with the COM communication option: c I peak / r, (I1 + I2 + I3)/3, I imbalance c load level in % Ir c total power factor The maximeters and minimeters are available only via the COM option for use with a supervisor. Event log All events are time stamped. c trips c beginning and end of alarms c modifications to settings and parameters c counter resets c system faults: v fallback position v thermal self-protection c loss of time c overrun of wear indicators c test-kit connections c etc. Maintenance register Used as an aid in troubleshooting and to better plan for device maintenance operations. c highest current measured c operation counter c number of test-kit connections c number of trips in operating mode and in test mode c contact-wear indicator. Additional technical characteristics Setting the display language System messages may be displayed in six different languages. The desired language is selected via the keypad. Protection functions All current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker. Measurement functions Measurement functions are independent of the protection functions. The high-accuracy measurement module operates independently of the protection module, while remaining synchronised with protection events. Measurement-calculation mode c measurement functions implement the new “zero blind time” concept which consists in continuously measuring signals at a high sampling rate. The traditional “blind window” used to process samples no longer exists. This method ensures accurate energy calculations even for highly variable loads (welding machines, robots, etc.). c energies are calculated on the basis of the instantaneous power values, in two manners: v the traditional mode where only positive (consumed) energies are considered v the signed mode where the positive (consumed) and negative (supplied) energies are considered separately. Accuracy of measurements (including sensors) cvoltage (V) 1% c current (A) 1.5% c frequency (Hz) 0.1 Hz c power (W) and energy (Wh) 2.5% Stored information The fine setting adjustments, the last 100 events and the maintenance register remain in the control-unit memory even when power is lost. Time-stamping Time-stamping is activated only if an external power supply module is present (max. drift of 1 hour per year). Reset An individual reset, via the keypad or remotely, acts on alarms, minimum and maximum data, peak values, the counters and the indicators. 23 Masterpact Schneider Electric Control units Micrologic H “harmonics” Micrologic H control units include all the functions offered by Micrologic P. Integrating significantly enhanced calculation and memory functions, the Micrologic H control unit offers in-depth analysis of power quality and detailed event diagnostics. It is intended for operation with a supervisor. In addition to the Micrologic P functions, the Micrologic H control unit offers: c in-depth analysis of power quality including calculation of harmonics and the fundamentals c diagnostics aid and event analysis through waveform capture c enhanced alarm programming to analyse and track down a disturbance on the AC power system E46257 Functions and characteristics Measurements ....................................................................... (A) The Micrologic H control unit offers all the measurements carried out by Micrologic P, with in addition: c phase by phase measurements of: v power, energy v power factors c calculation of: v current and voltage total harmonic distortion (THD) v current, voltage and power fundamentals (50 Hz) v current and voltage harmonics up to the 51st order. Instantaneous values displayed on the screen (V) I rms Micrologic 7.0 H I U P E currents (kW) I max rms (kWh) A A A A 1 2 e-fault 1 2 e-fault 3 N e-leakage 3 N e-leakage V V V % 12 23 31 1N 2N 3N (U12 + U23 + U31) / 3 voltages U rms V rms U average rms U imbalance Harmonics power, energy P active, Q reactive, S apparent E active, E reactive, E apparent W, Var, VA Wh, VARh, VAh power factor PF totals 1 2 3 totals consumed - supplied totals consumed totals supplied total 1 2 3 frequencies F long time Ir .7 .6 .5 .4 x In power-quality indicators instantaneous short time setting I∆n (A) 3 2 1 .5 5 total fundamentals THD U and I harmonics @ 6 Ir Isd 4 5 3 2.5 6 2 8 1.5 10 x Ir tsd (s) .4 .4 .3 .2 .1 0 I t off .3 .2 .1 2 on delay ∆t (ms) 230 10 140 20 30 60 7 Hz alarm tr 8 (s) 4 .9 12 16 .95 2 .98 1 20 24 1 .5 .8 Ii 6 8 10 4 12 3 15 off 2 x In U I U I 3 5 % amplitude P Q S 7 9 11 13 Harmonics 3, 5, 7, 9, 11 and 13, monitored by electrical utilities, are displayed on the screen. Demand measurements Similar to the Micrologic P control unit, the demand values are calculated over a fixed or sliding time window that may be set from 5 to 60 minutes. test 350 currents 800 I demand earth leakage I max demand A A A A 1 2 e-fault 1 2 e-fault 3 N e-leakage 3 N e-leakage puissances P, Q, S demand P, Q, S max demand W, Var, VA W, Var, VA totals totals Maximeters Only the current maximeters may be displayed on the screen. Histories and maintenance indicators These functions are identical to those of the Micrologic P. Note. Micrologic H control units come with a non-transparent lead-seal cover as standard. 24 Masterpact Schneider Electric E47071 POWERLOGIC System Manager Demo File Edit View Setup Control Display Reports Time With the communication option Tools Window Help Sampling Mode : MANUAL 5 seconds Event Module Phase A-N Voltage - Harmonics Analysis Phase 1-N 1,20 Harmonics(RMS) Fundamental: 1,00 RMS: RMS-H: % Fundamental 0,80 Peak: CF: THD: H1: 118.09 H2: 0.01 H3: 0.45 H4: 0.03 H5: 0.45 H6: 0.04 H7: 1.27 H8: 0.05 H9: 0.42 H10: 0.01 H11: 1.03 H12: 0.07 0,60 OK 0,40 0,20 0,00 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 Harmonics ONLINE: DEMO Ready No working system 9:30 E47072 Display of harmonics up to 12th order. POWERLOGIC System Manager Demo Edit View Setup Control Display Reports File Tools Window Help 5 seconds Sampling Mode : MANUAL Phase A-N Voltage Phase A Current 167 642 83 321 0 0 17 -83 33 50 66 17 -321 33 50 66 Your Specific Device - Phase A-N Voltage -167 -642 Harmonics(RMS) Fundamental: Phase B-N Voltage 118.08 RMS: 118.11 RMS-H: 167 2.38 Peak: 83 166.86 CF: 1.41 0 17 -83 33 50 THD: 2.02 -167 H1: 118.09 H2: 0.01 H3: 0.45 H4: 0.03 H5: 0.45 H6: 0.04 H7: 1.27 H8: 0.05 H9: 0.42 H10: 0.01 H11: 1.03 H12: 0.07 Additional measurements, maximeters and minimeters Certain measured or calculated values are only accessible with the COM communication option: c I peak / r, (I1 + I2 + I3)/3, I imbalance c load level in % Ir c power factor (total and per phase) c voltage and current THD c K factors of currents and average K factor c crest factors of currents and voltages c all the fundamentals per phase c fundamental current and voltage phase displacement c distortion power and distortion factor phase by phase c amplitude and displacement of current and voltage harmonics 3 to 51. The maximeters and minimeters are available only via the COM option for use with a supervisor. Waveform capture The Micrologic H control unit stores the last 12 cycles of each instantaneous current or voltage measurement. On request or automatically on programmed events, the control unit stores the waveforms. The waveforms may be displayed in the form of oscillograms by a supervisor via the COM option. Enhanced alarm programming Each instantaneous value can be compared to user-set high and low thresholds. Overrun of a threshold generates an alarm. An alarm or combinations of alarms can be linked to programmable actions, including circuit-breaker opening, activation of a M2C or M6C contact, selective recording of measurements in a log, waveform capture, etc. Event log and maintenance registers The Micrologic H offers the same event log and maintenance register functions as the Micrologic P. OK ONLINE: DEMO Ready No working system 9:30 E47070 Waveform capture POWERLOGIC System Manager Demo Edit View Setup Control Display Reports File Additional technical characteristics Tools Window Help Sampling Mode : MANUAL Time 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 04/21/98 Ready Log 5 seconds Event 08:49:06 08:49:01 08:48:38 08:48:30 08:46:16 08:39:19 08:39:06 08:39:06 08:38:57 08:30:44 08:24:31 08:24:30 08:24:15 08:18:07 07:54:05 07:53:55 07:53:54 07:51:46 07:51:33 07:51:29 07:50:17 07:50:17 07:49:13 07:48:57 07:48:38 07:48:22 07:46:54 07:44:59 07:44:59 Module Net Server Shutdown User Log Out DB Table Change DB Table Change DB Table Change User Log In Security Check Net Server Started User Log In Net Server Shutdown Security Check Net server Started User Log IN IPC Error DB Table Change DB Table Change DB Table Change DB Table Change DB Table Change DB Table Change DB Table Change DB Table Change Setup: Device Name Change Setup: Device Added Setup: Device Name Change Setup: Device Added User Log In Security Check Net Server Started User : master User : master User : master User : master User : master User : master Key Status : Key Found User : master PowerLogic Network… SMS-3000 Client Alarm Setup Alarm Setup Alarm Setup SMS-3000 Client PowerLogic Network… Level : 1 PowerLogic Network… Event/Alarm/Network… User : master Level : 1 PowerLogic Network… Key Status : Key Found PowerLogic Network… User : master Level : 1 PowerLogic Network… Event/Alarm/Network… User : NA Err : 109 SMS-3000 Client User : -1 Logger Template Devices Logger Setup User : -1 Logger Template Topics Logger Setup User : -1 Logger Templates Logger Setup User : master Analog Levels Assigned Alarm Setup User : master Analog Levels Template Alarm Setup User : master Functions Alarm Setup User : master Digital Levels Assigned Alarm Setup User : master Analog Levels Assigned Alarm Setup Device : MicroLogic Breaker User :master Device Setup Device : MicroLogic Breaker User :master Device Setup Device : Transformer Temp User : master Device Setup Device : Transformer Temp User :master Device Setup User : master User Level : 1 SMS-3000 Client Key Status : Key Found PowerLogic Network… User :master Level : 1 PowerLogic Network… ONLINE: DEMO Level : 1 User level : 1 TOD Event Tasks Tasks TOD Events User level : 1 No working system 9:30 Setting the display language System messages may be displayed in six different languages. The desired language is selected via the keypad. Protection functions All current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker. Measurement functions Measurement functions are independent of the protection functions. The high-accuracy measurement module operates independently of the protection module, while remaining synchronised with protection events. Measurement-calculation mode An analogue calculation function dedicated to measurements enhances the accuracy of harmonic calculations and the power-quality indicators. The Micrologic H control unit calculates electrical magnitudes using 1.5 x In dynamics (20 x In for Micrologic P). Measurement functions implement the new “zero blind time” concept Energies are calculated on the basis of the instantaneous power values, in the traditional and signed modes. Harmonic components are calculated using the discrete Fourier transform (DFT). Accuracy of measurements (including sensors) cvoltage (V) 1% c current (A) 1.5% c frequency (Hz) 0.1 Hz c power (W) and energy (Wh) 2.5% c total harmonic distortion 1% Stored information The fine-setting adjustments, the last 100 events and the maintenance register remain in the control-unit memory even when power is lost. Time-stamping Time-stamping is activated only if an external power supply module is present (max. drift of 1 hour per year). Reset An individual reset, via the keypad or remotely, acts on alarms, minimum and maximum data, peak values, the counters and the indicators. 25 Masterpact Schneider Electric E47477 External sensor (CT) 056467 Functions and characteristics Rectangular sensor for source return protection Micrologic control units Accessories and test equipment External sensors External sensor for earth-fault and neutral protection The sensors, used with the 3P circuit breakers, are installed on the neutral conductor for: c neutral protection (with Micrologic P and H) c residual type earth-fault protection (with Micrologic A, P and H).. The rating of the sensor (CT) must be compatible with the rating of the circuit breaker: c NT06 à NT16: TC 400/1600 c NW08 à NW20: TC 400/2000 c NW25 à NW40: TC 1000/4000 c NW40b à NW63: TC 2000/6300. For double neutral protection (2 IN,) the sensor rating must be compatible with the measurement range: 2 x IN. Rectangular sensor for earth-leakage protection The sensor is installed around the busbars (phases + neutral) to detect the zerophase sequence current required for the earth-leakage protection. Rectangular sensors are available in two sizes. Inside dimensions (mm) c 280 x 115 up to 1600 A for Masterpact NT c 470 x 160 up to 4000 A for Masterpact NW. External sensor for source ground return protection The sensor is installed around the connection of the transformer neutral point to earth and connects to the Micrologic 6.0 control unit via an MDGF module to provide the source ground return (SGR) protection. Voltage measurement inputs Voltage measurement inputs are required for power measurements and for earthleakage protection. As standard, the control unit is supplied by internal voltage measurement inputs placed downstream of the pole for voltages between 100 and 690 V AC. On request, it is possible to replace the internal voltage measurement inputs by an external connector which enables the control unit to draw power directly from the distribution system upstream of the circuit breaker. 056412 Long-time rating plug Four interchangeable plugs may be used to limit the long-time threshold setting range for higher accuracy. As standard, control units are equipped with the 0.4 to 1 plug. Setting ranges 025171 025173 standard Ir = In x… Low-setting option Ir = In x… high-setting option Ir = In x… off plug 0,4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 0.4 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8 0.80 0.82 0.85 0.88 0.90 0.92 0.95 0.98 1 no long-time protection External power-supply module The external power-supply module makes it possible to use the display even if the circuit breaker is open or not supplied (for the exact conditions of use, see the “electrical diagrams” part of this catalogue). This module powers both the control unit and the M2C and M6C programmable contacts. With the Micrologic A control unit, this module makes it possible to display currents of less than 20% of In. With the Micrologic P and H, it can be used to display fault currents after tripping and to time-stamp events (alarms and trips). Characteristics c power supply: v 110/130, 200/240, 380/415 V AC (+ 10% - 15%), consumption 10 VA v 24/30, 48/60, 100/125 V DC (+20% -20%), consumption 10 W c output voltage: 24 V DC; power delivered: 5 W / 5 VA c ripple < 5% c class 2 isolation. Battery module The battery module makes it possible to use the display even if the power supply to the Micrologic control unit is interrupted. Characteristics: c battery run-time: 12 hours (approximately) c mounted on vertical backplate or symmetrical rail 26 Masterpact Schneider Electric 056429 Spare parts Lead-seal covers A lead-seal cover controls access to the adjustment dials. When the cover is closed: c it is impossible to modify settings using the keypad unless the settings lockout pin on the cover is removed. c the test connector remains accessible. c the test button for the earth-fault and earth-leakage protection function remains accessible. Characteristics c transparent cover for basic Micrologic and Micrologic A control units c non-transparent cover for Micrologic P and H control units. Spare battery A battery supplies power to the LEDs identifying the tripping causes. Battery service life is approximately ten years. A test button on the front of the control unit is used to check the battery condition. The battery may be replaced on site when discharged. Lead-seal cover 056413 M2C, M6C programmable contacts 056430 These contacts are optional equipment for the Micrologic P and H control units. They are described with the indication contacts for the circuit breakers. characteristics minimum load breaking capacity (A) p.f.: 0.7 M2C M2C/M6C V AC V DC M6C 240 380 24 48 125 250 10mA/24V 5 3 1.8 1.5 0.4 0.15 M2C: 24 V DC power supplied by control unit (consumption 100 mA). M6C: external 24 V DC power supply required (consumption 100 mA). 056466 Test equipment Portable test kit Mini test kit The autonomous hand-held mini test kit may be used to: c check operation of the control unit and the tripping and pole-opening system by sending a signal simulating a short-circuit c supply power to the control units for settings via the keypad when the circuitbreaker is open (Micrologic P and H control units). Power source: standard LR6-AA battery. Portable test kit The portable test kit is available in two versions: c the autonomous version with built-in keypad and display c the complete version controlled by a PC. The autonomous version may be used to check: c the mechanical operation of the circuit breaker c the electrical continuity of the connection between the circuit breaker and the control unit c operation of the control unit: v display of settings v operating tests on the ASIC electronic component v automatic and manual tests on protection functions v test on the zone-selective interlocking (ZSI) function v inhibition of the earth-fault protection v inhibition of the thermal memory. The complete version controlled by a PC offers in addition: c comparison of the real tripping curve with the catalogue curves available on the PC c reset of the M2C / M6C contacts and indications c reading and modification of settings and counters c reading of histories and logs c waveform capture c analysis of harmonics. 27 Masterpact Schneider Electric Communication COM option in Masterpact The COM option is required for integration of the circuit breaker or switch-disconnector in a supervision system. Masterpact uses the Digipact or Modbus communications protocol for full compatibility with the SMS PowerLogic electrical-installation management systems. An external gateway is available for communication on other networks: c Profibus c Ethernet… For fixed devices, the COM option is made up of: c a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE ,PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases. For drawout devices, the COM option is made up of: c a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE, PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases c a "craddle" communication module supplied separately with its set of sensors (CE, CD and CT contacts). Status indication by the COM option is independent of the device indication contacts. These contacts remain available for conventional uses. Digipact or Modbus «Device» communication module This module is independent of the control unit. It receives and transmits information on the communication network. An infra-red link transmits data between the control unit and the communication module. Consumption: 30 mA, 24 V. Digipact or Modbus «craddle» communication module This module is independent of the control unit. With Modbus "craddle" communication module, this module makes it possible to address the craddle and to maintain the address when the circuit breaker is in the disconnected position. Consumption: 30 mA, 24 V. XF and MX communicating voltage releases The XF and MX communicating voltage releases are equipped for connection to the "device" communication module. The remote-tripping function (second MX or MN) are independent of the communication option. They are not equipped for connection to the "device" communication module. Digipact «device» communication module. communication Bus ++ CCM CT 2 modb us CE E47073 Digipact «craddle» communication module CD 056431 056401 Functions and characteristics + CE C 056431 CT C OF SDE PF CH Modbus «device» communication module CD C MX XF 4 5 1 E45183 3 Modbus «craddle» communication module 1 2 3 4 5 «Device» communication module «Craddle» communication module OF, SDE, PF and CH «device» sensors CE, CD and CT «craddle» sensors MX and XF release : hard wire : communication bus Note: eco COM The eco COM Modbus is intended to fit the circuit breaker with module display (DMB300, DMC300…). 28 Masterpact Schneider Electric POWERLOGIC System Manager Demo Edit View Setup Control Display Reports File Time The Masterpact switch-disconnectors are compatible only with the Digipact COM option. Tools Window Help 5 seconds Sampling Mode : MANUAL Event Module Phase A-N Voltage - Harmonics Analysis Phase 1-N 1,20 Harmonics(RMS) Fundamental: 1,00 RMS: RMS-H: 0,80 % Fundamental E47071 Overview of functions Peak: CF: THD: H1: 118.09 H2: 0.01 H3: 0.45 H4: 0.03 H5: 0.45 H6: 0.04 H7: 1.27 H8: 0.05 H9: 0.42 H10: 0.01 H11: 1.03 H12: 0.07 0,60 OK 0,40 0,20 0,00 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 The Masterpact circuit breakers are compatible with the Digipact or Modbus COM option. The COM option may be used with all types of control units to: c identify the device c indicate status conditions c control the device. Depending on the different types of Micrologic (A, P, H) control units, the COM option also offers: c setting of the protection and alarms functions c analysis of the AC-power parameters for operating-assistance and maintenance purposes H12 Harmonics Ready ONLINE: DEMO No working system 9:30 switch-disconnector with circuit breaker with communication bus communication bus Digipact Modbus Digipact Modbus c - - A A P P H H A A A A P P H H c c c c - A A A A A P P P P P c - - A A device identification address calibre type of device type of control unit type of long-time rating plug A A P P P P P H H H H H H H H H H A A A A A P P P P P H H H H H P H A P H P H A P P H H P H H P P P H H H H P P H H status indications ON/OFF OF spring charged CH ready to close PF fault-trip SDE connected/disconnected/test position CE/CD/CT commandes opening / closing MX/XF spring charging reset of the mechanical indicator protections and alarms settings reading of protections settings writing of fine settings in the range imposed by the adjustment dials reading/writing of alarms (délestage, relestage, M2C…) reading/writing of alarms personnalisables operating and maintenance aids measurement current voltages, frequency, power, etc. power quality: fundamental, harmonics programming of demand metering fault readings type of fault interrupted current waveform capture on faults on demand or programmed histories and logs trip history alarm history event logs indicators counter operation contact wear maintenance register A P P H H A A H H A P H A P P P H H H P P P H H H Note. See the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators. 29 Masterpact Schneider Electric Communication Masterpact in a communication network E67968 Functions and characteristics Software Communication interface RS 232C,Ethernet RS 485 Communication Bus IN LIN GER MERSV JBus pulsar BBus com error com 24V Data concentrator DC150 OK error 1 3 N°1 N°1 Device OF24 MN Com CD3 CE6 CD2 CE5 UC1 UC2 UC3 UC4 M2C UC2 SDE2 CE3 CE2 MX1 XF PF CD3 CD1 CD2 814 824 812 834 822 811 832 821 831 MCH OC24 OF23 OC23 OF22 OC22 OF21 OC21 CE1 CD1 CE4 CE1 CE2 314 CE3 324 312 SDE1 334 322 311 332 K2 84 321 82 UC4 M2C/M6C Q3 184/ 331 UC3 V3 484/ 474/ Q2 182 K1 81 UC2 2+ V2 Q1 181/ M3 F UC1 Com 6 Z5 M1 M2 3 T4 VN - V1 471/ E5 E 4 Z3 Z4 T T1 T2 F1 E3 E E2 Z1 Z2 E1 MCHB PF 2 XF 254 B3 MX1 A2 252 MN/MX2 12 C2 B1 A3 251 D2/ C 13 C3 A1 /C C1 D1/ C11 OF14 OC14 OF13 OC13 OF12 OF11 OC12 OF24 CT1 CT2 914 CT3 924 912 OF1 934 922 OF2 911 14 932 OF3 921 24 12 OF4 931 OF11114 44 34 32 22 11 OF12124 21 42 OF13134 31 112 OF14144 41 122 OF21214 111 132 OF22224 121 142 OF23234 131 212 OF24244 141 222 211 232 221 242 231 241 Reset push push 70 Ig Isd I ∆n Ii Ap CD2 CE5 NX 32 ON Ics = UC3 UC4 M2C UC2 SDE2 CE3 CE2 MX1 XF PF CD1 CD2 814 824 812 834 822 811 832 821 831 MCH OC24 OF23 OC23 OF22 OC22 OF21 OC21 CE1 CE1 CE2 314 CE3 324 312 SDE1 334 322 311 332 K2 84 321 82 UC4 M2C/M6C Q3 184/ 331 UC3 V3 484/ 474/ Q2 182 K1 81 UC2 2+ V2 Q1 181/ M3 F UC1 Com 6 Z5 M1 M2 3 T4 VN - V1 471/ E5 E 4 Z3 Z4 T T1 T2 F1 E3 E E2 Z1 Z2 E1 MCHB PF 2 XF 254 B3 MX1 A2 252 MN/MX2 12 C2 B1 A3 251 D2/ C 13 C3 A1 /C C1 D1/ C11 Reset Icu (kA) 100 100 85 OF14 OC14 OF13 OC13 OF12 OF11 OC12 CT1 CT2 914 CT3 924 912 OF1 934 922 OF2 911 14 932 OF3 921 24 12 OF4 931 OF11114 44 34 32 22 11 OF12124 21 42 OF13134 31 112 OF14144 41 122 OF21214 111 132 OF22224 121 142 OF23234 131 212 OF24244 141 222 211 232 221 242 231 241 100% push push 70 NX 32 ON Icu Ir Ig Isd I ∆n Ii Ap reset Ics = 0 Icu (kA) 100 100 85 100% Icu 50/60Hz O OFF 947-2 AS NEMA IEC UNE EN 60947-2 BS CEI UTE Icw 85kA/1s cat.B ed discharg 50/60Hz O OFF H2 Ue (V) 220/440 525 690 OFF Micrologic Icw 85kA/1s cat.B ed discharg UC2 H2 Ue (V) 220/440 525 690 OFF reset UC1 CD1 CE4 CD3 Micrologic Ir MN Com CD3 CE6 947-2 AS NEMA IEC UNE EN 60947-2 BS CEI VDE UTE 3 125 0 VDE 3 125 Digipact Bus ModBUS Bus volets shutters volets shutters Test Test Masterpact Masterpact Devices Circuit breakers equipped with Micrologic control units may be connected to either a Digipact or Modbus communication bus. The information made available depends on the type of Micrologic control unit (A, P or H) and on the type of communication bus (Digipact or Modbus). Switch-disconnectors may be connected exclusively to the Digipact communication bus. Communication bus Digipact The Digipact bus is the internal bus of the low-voltage switchboard in which the Digipact communicating devices are installed (Masterpact with Digipact COM, PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data concentrator (see the Powerlogic System catalogue). Addresses Addressing is carried out by the DC150 data concentrator. Number of devices The maximum number of devices that may be connected to the Digipact bus is calculated in terms of “communication points”. These points correspond to the amount of traffic the bus can handle. The total number of points for the various devices connected to a single bus must not exceed 100. If the required devices represent more than 100 points, add a second Digipact internal bus. Communicating device DC150 data concentrator Micrologic + Digipact COM PM150 SC150 UA150 Number of points 4 4 4 4 4 Length of bus The maximum recommended length for the Digipact internal bus is 200 meters. Bus power source Power is supplied by the DC150 data concentrator (24 V).. 30 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating Modbus devices (Masterpact with Modbus COM, PM300, Sepam, Vigilohm, etc.) are installed. All types of PLCs and microcomputers may be connected to the bus. Addresses The software layer of the Modbus protocol can manage up to 255 addresses (1 to 255). The “device” communication module comprises three addresses linked to: b circuit-breaker manager; b measurement manager; b protection manager. The “craddle” communication module comprises one address linked to: b the craddle manager. The division of the system into four managers secures data exchange with the supervision system and the circuit-breaker actuators. The manager addresses are automatically derived from the circuit-breaker address @xx entered via the Micrologic control unit (the default address is 47). logic addresses @xx @xx + 50 @xx + 200 @xx + 100 Circuit-breaker manager Craddle manager Measurement managers Protection manager (1 to 47) (51 to 97) (201 to 247) (101 to 147) Number of devices The maximum number of devices that may be connected to the Modbus bus depends on the type of device (Masterpact with Modbus COM, PM300, Sepam, Vigilohm, etc.), the baud rate (19200 is recommended), the volume of data exchanged and the desired response time. The RS485 physical layer offers up to 32 connection points on the bus (1 master, 31 slaves). A fixed device requires only one connection point (communication module on the device). A drawout device uses two connection points (communication modules on the device and on the craddle). The number must never exceed 31 fixed devices or 15 drawout devices. Length of bus The maximum recommended length for the Modbus bus is 1200 meters. Bus power source A 24 V DC power supply is required (less than 20% ripple, insulation class II). Communication interface The Modbus bus may be connected to the central processing device in any of three manners: b direct link to a PLC. The communication interface is not required if the PLC is equipped with a Modbus port; b direct link to a computer. The Modbus (RS485) / Serial port (RS232) communication interface is required; b connection to a TCP/IP (Ethernet) network. The Modbus (RS485) / TCP/IP (Ethernet) communication interface is required. Software To make use of the information provided by the communicating devices, software with a Modbus driver must be used. Micrologic utilities This is a set of Modbus drivers that may be used with a PC to: b display the variables (I, U, P, E, etc.) with the DDS (Data Display Software) application; b read/write the settings with the RSS (Remote Setting Software) application; b remotely control (ON / OFF) the device with the CSS (Control Command Software) application. These softwares are available upon request. SMS (System Manager Software) SMS is a software to monitor LV and/or MV electrical energy. The SMS family includes a software range depending on the application and function, from single product monitoring to the management of a multiple building: c Power Meter and Circuit Monitor units c LV devices c Sepam units. 31 Masterpact Schneider Electric Connections Overview of solutions Functions and characteristics Rear connection vertical 056432 056433 horizontal Simply turn a horizontal rear connector 90° to make it a vertical connector. 056434 Front connection 056436 056435 Mixed connection 056437 Three types of connection are available: c vertical or horizontal rear connection c front connection c mixed connection. The solutions presented are similar in principle for all Masterpact NT and NW fixed and drawout devices.. Note. Masterpact circuit breakers can be connected indifferently with bare-copper, tinnedcopper and tinned-aluminium conductors, requiring no particular treatment. 32 Masterpact Schneider Electric Optional accessories Masterpact NT06 to NT16 fixed rear connection fixed front connection rear connection front connection drawout rear connection front connection rear connection E47064 front connection E46427 E46428 E79058 Interphase barriers E46428 Cable lug adapters E46426 E46426 Vertical connection adapters E46427 Bare-cable connectors and connector shield Masterpact NW08 to NW63 drawout E46428 Type of accessory max. 4000 A E46431 E46431 Spreaders E46889 Disconnectable front-connection adapter E47068 E47067 E47066 Safety shutters with padlocking Arc chute screen E70745 Shutter position indication and locking Masterpact M replacement kit A set of connection parts is available to allow replacement of a Masterpact M08 to M32 circuit breaker by a Masterpact NW without modifying the busbars (please consult us). Mounting on a switchboard backplate using special brackets Masterpact NT and NW fixed front-connected circuit breakers can be installed on a backplate without any additional accessories. Masterpact NW circuit breakers require a set of special brackets. 33 Masterpact Schneider Electric 056438 Functions and characteristics Connections Optional accessories Bare-cable connectors and connector shield The connectors can be mounted on fixed front-connected devices to allow connection using bare cables. They are supplied with a connector shield. They are designed to connect four 240 mm2 cables each. 056440 Vertical-connection adapters 056441 Mounted on front-connected devices or craddle, the adapters facilitate connection to a set of vertical busbars. Cable-lug adapters Cable-lug adapters are used in conjunction with vertical rear connectors or with vertical-connection adapters. They can be used to connect a number of cables fitted with lugs. To ensure adequate mechanical strength, the connectors must be secured together via spacers. 056415 Interphase barriers These barriers are flexible insulated partitions used to reinforce isolation of connection points in installations with busbars, whether insulated or not. For Masterpact NT/NW devices, they are installed vertically between rear connection terminals. 056442 Spreaders E70746 Mounted on the front or rear connectors, spreaders are used to increase the distance between bars in certain installation configurations. Arc chute screen For Masterpact NT fixed, front connected and using vertical-connection adapters front oriented, it is mandatory to install arc chute screen in order to comply with the safety perimeter. I O push push ON OFF rged discha O OFF 34 Masterpact Schneider Electric 056443 Disconnectable front-connection adapter 056445 Mounted on a fixed front-connected device, the adapter simplifies replacement of a fixed device by enabling fast disconnection from the front. Safety shutters E47476 Mounted on the craddle, the safety shutters automatically block access to the disconnecting contact cluster when the device is in the disconnected or test positions (degree of protection IP 20) When the device is removed from its craddle, no live parts are accessible. The shutter-locking system is made up of a moving block that can be padlocked (padlock not supplied). The block: * prevents connection of the device * locks the shutters in the closed position For Masterpact NW08 to NW63 A support at the back of the craddle is used to store the blocks when they are not used. * 2 blocks for NW08 to NW40 * 4 blocks for NW40b to NW63. Shutter position indication and locking on front face This option located on the craddle front plate indicates that the shutters are closed. It is possible to independently or separately padlock the two shutters using one to three padlocks (not supplied). 35 Masterpact Schneider Electric Locking On the device E47062 Functions and characteristics 3 NW 1 H1 1250 12kV 0V Ui 100 8kV Uimp Uimp Ue (V) 220/240 480/690 gic Microlo Ir Icu (kA) 100 85 70 Ig Isd I ∆n Ii Ap t rese I O push push OFF disc 2 ON harg 4 5 6 ed O OFF 7 Ics = IEC Icu 100% 947-2 UTE VDE 012 BS CEI UNE NEMA 1 reset button for mechanical trip indication 2 OFF pushbutton 3 OFF position lock 4 electrical closing pushbutton 5 ON pushbutton 6 springs charged indication 7 pushbutton locking 8 contact position indication 9 operation counter 8 53 056448 056446 056447 9 Access to pushbuttons protected by transparent cover Pushbutton locking using a padlock OFF position locking using a padlock Pushbutton locking The transparent cover blocks access to the pushbuttons used to open and close the device. It is possible to independently lock the opening button and the closing button. The locking device is often combined with a remote operating mechanism. The pushbuttons may be locked using either: c three padlocks (not supplied) c lead seal c two screws. Device locking in the OFF position The circuit breaker is locked in the OFF position by physically maintaining the opening pushbutton pressed down: c using padlocks (one to three padlocks, not supplied) c using keylocks (one or two different keylocks, supplied). Keys may be removed only when locking is effective (Profalux or Ronis type locks). The keylocks are available in any of the following configurations: c one keylock c one keylock mounted on the device + one identical keylock supplied separately for interlocking with another device c two different key locks for double locking. Profalux and Ronis keylocks are compatible with each other. A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell). Accessory-compatibility For Masterpact NT: 3 padlocks or 1 keylock For Masterpact NW: 3 padlocks and/or 2 keylocks 056449 Cable-type door interlock OFF position locking using a keylock This option prevents door opening when the circuit breaker is closed and prevents circuit breaker closing when the door is open. For this, a special plate associated with a lock and a cable is mounted on the right side of the circuit breaker. With this interlock installed, the source changeover function cannot be implemented. 36 Masterpact Schneider Electric E47063 On the craddle 3 4 5 6 7 8 9 1 1 2 3 4 5 6 7 mismatch protection door interlock racking interlock keylock locking padlock locking position indicator craddle front plate (accessible with cubicle door closed) 8 racking-handle entry 9 reset button 10 racking-handle storage 10 056451 056450 2 «Disconnected» position locking Mounted on the craddle and accessible with the door closed, these devices lock the circuit breaker in the «disconnected» position in two manners: c using padlocks (standard), up to three padlocks (not supplied) c using keylocks (optional), one or two different keylocks are available. Profalux and Ronis keylocks are available in different options: c one keylock c two different keylocks for double locking c one (or two) keylocks mounted on the device + one (or two) identical keylocks supplied separately for interlocking with another device. A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell). 056417 «Disconnected» position locking by padlocks «Disconnected» position locking by keylocks Door interlock «Connected», «disconnected» and «test» position locking The «connected», «disconnected» and «test» positions are shown by an indicator. The exact position is obtained when the racking handle blocks. A release button is used to free it. On request, the «disconnected» position locking system may be modified to lock the circuit breaker in any of the three positions, «connected», «disconnected» and «test». Door interlock catch Mounted on the right or left-hand side of the craddle, this device inhibits opening of the cubicle door when the circuit breaker is in «connected» or «test» position. It the breaker is put in the «connected» position with the door open, the door may be closed without having to disconnect the circuit breaker. 056452 Racking interlock Racking interlock This device prevents insertion of the racking handle when the cubicle door is open. Cable-type door interlock This option is identical for fixed and drawout versions. Racking interlock between crank and OFF pushbutton 056453 This option makes it necessary to press the OFF pushbutton in order to insert the racking handle and holds the device open until the handle is removed. Mismatch protection Automatic spring discharge before breaker removal This option discharges the springs before the breaker is removed from the craddle. Mismatch protection Mismatch protection ensures that a circuit breaker is installed only in a craddle with compatible characteristics. It is made up of two parts (one on the craddle and one on the circuit breaker) offering twenty different combinations that the user may select. 37 Masterpact Schneider Electric 056418 Functions and characteristics Indication contacts Indication contacts are available: c in the standard version for relay applications c in a low-level version for control of PLCs and electronic circuits. M2C and M6C contacts may be programmed via the Micrologic P and H control units. ON/OFF indication contacts (OF) Two types of contacts indicate the ON or OFF position of the circuit breaker: c microswitch type changeover contacts for Masterpact NT c rotary type changeover contacts directly driven by the mechanism for Masterpact NW. These contacts trip when the minimum isolation distance between the main circuit-breaker contacts is reached. OF NT supplied as standard maximum number breaking capacity (A) p.f.: 0.3 AC12/DC12 standard V AC 240/380 480 690 V DC 24/48 125 250 ON/OFF indication contacts (OF) (microswitch type) low-level V AC 24/48 240 380 V DC 24/48 125 250 * standard contacts: 10 A; optional contacts: 6 A. NW 4 4 4 12 minimum load: 100mA/24V 6 10/6* 6 10/6* 6 6 2.5 10/6* 0.5 10/6* 0.3 3 minimum load: 2mA/15V DC 5 6 5 6 5 3 5/2.5 6 0.5 6 0.3 3 «Fault-trip» indication contacts (SDE) 056462 056419 Circuit-breaker tripping due to a fault is signalled by: c a red mechanical fault indicator (reset) c one changeover contact (SDE). Following tripping, the mechanical indicator must be reset before the circuit breaker may be closed. ON/OFF indication contacts (OF) (rotary type) SDE NT/NW supplied as standard maximum number breaking capacity (A) p.f.: 0.3 AC12/DC12 standard V AC 240/380 480 690 V DC 24/48 125 250 low-level Additional «fault-trip» indication contacts (SDE) V AC 24/48 240 380 V DC 24/48 125 250 1 2 minimum load: 100mA/24V 5 5 3 3 0.3 0.15 minimum load: 2mA/15V DC 3 3 3 3 0.3 0.15 Combined «connected/closed» contacts (EF) The contact combines the «device connected» and the «device closed» information to produce the «circuit closed» information. Supplied as an option for Masterpact NW, it is mounted in place of the connector of an additional OF contact. 056455 EF Combined contacts NW maximum number breaking capacity (A) p.f.: 0.3 AC12/DC12 standard V AC 240/380 480 690 V DC 24/48 125 250 low-level V AC 24/48 240 380 V DC 24/48 125 250 38 Masterpact 8 minimum load: 100mA/24V 6 6 6 2.5 0.8 0.3 minimum load: 2mA/15V DC 5 5 5 2.5 0.8 0.3 Schneider Electric 056456 CE, CD and CT «connected/ disconnected/test» position carriage switches «Connected», «disconnected» and «test» position carriage switches 056413 Three series of optional auxiliary contacts are available for the craddle: c changeover contacts to indicate the «connected» position (CE) c changeover contacts to indicate the «disconnected» position (CD). This position is indicated when the required clearance for isolation of the power and auxiliary circuits is reached. c changeover contacts to indicate the «test» position (CT). In this position, the power circuits are disconnected and the auxiliary circuits are connected. Additional actuators A set of additional actuators may be installed on the craddle to change the functions of the carriage switches. M2C programmable contacts: circuit-breaker internal relay with two contacts NT contacts maximum number standard V AC 240 380 480 690 V DC 24/48 125 250 M6C programmable contacts: circuit-breaker external relay with six independent changeover contacts controlled from the circuit breaker via a threewire connection. low-level V AC 24/48 240 380 V DC 24/48 125 250 M2C / M6C programmable contacts These contacts, used with the Micrologic P and H control units, may be programmed via the control unit keypad or via a supervisory station with the COM communication option. They require an external power supply module. They indicate: c the type of fault c instantaneous or delayed threshold overruns. They may be programmed: c with instantaneous return to the initial state c without return to the initial state c with return to the initial state following a delay. characteristics M2C/M6C V AC V DC M2C: 24 V DC power supplied by control unit (consumption 100 mA). 100mA/24V 5 3 1.8 1.5 0.4 0.15 240 380 24 48 125 250 M6C: external 24 V DC power supply required (consumption 100 mA). E59470 484 474 minimum load breaking capacity (A) p.f.: 0.7 E59469 1 3 S1 7 9 S2 6 4 S3 12 10 18 16 24 22 S4 S6 S5 S1 S2 5 11 2 8 14 20 471 056430 CE/CD/CT 3 3 3 9 0 0 6 3 0 6 0 3 minimum load: 100mA/24V 8 8 8 8 8 8 6 6 2.5 2.5 0.8 0.8 0.3 0.3 minimum load: 2mA/15V DC 5 5 5 5 5 5 2.5 2.5 0.8 0.8 0.3 0.3 standard with additional actuators breaking capacity (A) p.f.: 0.3 AC12/DC12 NW CE/CD/CT 3 2 1 39 Masterpact Schneider Electric Remote operation Remote ON / OFF Two solutions are available for remote operation of Masterpact devices: c a point-to-point solution c a bus solution with the COM communication option. The remote ON / OFF function is used to remotely open and close the circuit breaker. It is made up of: c an electric motor (MCH) equipped with a «springs charged» limit switch contact (CH) c two voltage releases: v a closing release (XF) v an opening release (MX). Optionally, other functions may be added: c a «ready to close» contact (PF) c an electrical closing pushbutton (BPFE) c remote reset following a fault. A remote-operation function is generally combined with: c device ON / OFF indication (OF) c «fault-trip» indication (SDE). 056407 Functions and characteristics E46041 Wiring diagram of a point-to-point remote ON / OFF function spring charged B3 opening order closing order B2 C2 ready to close A2 252 fault 254 82 open 84 closed 12 14 MCH PF MX OF1 SDE XF CH B1 C1 A1 251 81 11 E46042 Wiring diagram of a bus-type remote ON / OFF function spring charged B3 opening order B2 C2 closing order A2 C3 A3 MCH MXcom XFcom CH Note: An opening order always takes priority over a closing order. If opening and closing orders occur simultaneously, the mechanism discharges without any movement of the main contacts. The circuit breaker remains in the open position (OFF). In the event of maintained opening and closing orders, the standard mechanism provides an anti-pumping function by blocking the main contacts in open position. Anti-pumping function. After fault tripping or intentional opening using the manual or electrical controls, the closing order must first be discontinued, then reactivated to close the circuit breaker. When the automatic reset after fault trip (RAR) option is installed, to avoid pumping following a fault trip, the automatic control system must take into account the information supplied by the circuit breaker before issuing a new closing order or blocking the circuit breaker in the open position (information on the type of fault, e.g. overload, short-time fault, earth fault, earth leakage, short-circuit, etc.). B1 C1 A1 COM OF supervisor PF SDE CH 40 Masterpact Schneider Electric 056420 056468 Electric motor (MCH) The electric motor automatically charges and recharges the spring mechanism when the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible following opening. The spring-mechanism charging handle is used only as a backup if auxiliary power is absent. The electric motor (MCH) is equipped as standard with a limit switch contact (CH) that signals the “charged” position of the mechanism (springs charged). characteristics power supplyV AC 50/60 Hz V DC operating threshold consumption (VA or W) motor overcurrent charging time operating frequency CH contact 48/60 - 100/130 - 200/240 - 277- 380/415 - 400/440 - 480 24/30 - 48/60 - 100/125 - 200/250 0.85 to 1.1 Un 180 2 to 3 In for 0.1 second maximum 3 seconds for Masterpact NT maximum 4 seconds for Masterpact NW maximum 3 cycles per minute 10 A at 240 V Voltage releases (XF and MX) 056421 Electric motor (MCH) for Masterpact NT Electric motor (MCH) for Masterpact NW XF and MX voltage releases Closing release (XF) The XF release remotely closes the circuit breaker if the spring mechanism is charged. Opening release (MX) The MX release instantaneously opens the circuit breaker when energised. The supply can be maintained or automatically disconnected. characteristics power supplyV AC 50/60 Hz V DC operating threshold consumption (VA or W) 056457 circuit-breaker response time at Un “Ready to close” contacts (PF) XF MX 24 - 48 - 100/130 - 200/250 - 277 - 380/480 12 - 24/30 - 48/60 - 100/130 - 200/250 0.85 to 1.1 Un 0.7 to 1.1 Un hold: 4.5 hold: 4.5 pick-up: 200 pick-up: 200 55 ms ± 10 (Masterpact NT) 50 ms ± 10 70 ms ± 10 (NW i 4000A) 80 ms ± 10 (NW > 4000A) “Ready to close” contact (PF) The “ready to close” position of the circuit breaker is indicated by a mechanical indicator and a PF changeover contact. This signal indicates that all the following are valid: c the circuit breaker is in the OFF position c the spring mechanism is charged c a maintained opening order is not present: v MX energised v fault trip v remote tripping (second MX or MN) v device not completely racked in v device locked in OFF position v device interlocked with a second device. characteristics supplied as standard maximum number breaking capacity p.f.: 0.3 AC12/DC12 NT/NW standard V AC 240/380 480 690 V DC 24/48 125 250 low-level V AC 24/48 240 380 V DC 24/48 125 250 41 Masterpact 1 1 minimum load: 100mA/24V 5 5 3 3 0.3 0.15 minimum load: 2mA/15V DC 3 3 3 3 0.3 0.15 Schneider Electric Remote operation Remote ON / OFF (cont.) Functions and characteristics 056469 Electrical closing pushbutton (BPFE) E46044 Located on the front panel, this pushbutton carries out electrical closing of the circuit breaker. It is generally associated with the transparent cover that protects access to the closing pushbutton. Electrical closing via the BPFE pushbutton takes into account all the safety functions that are part of the control/monitoring system of the installation. The BPFE connects to the closing release (XF) in place of the COM module. remote closing order Electrical closing pushbutton (BPFE). A2 BPFE A3 XF com A1 Remote reset after fault trip E46045 Electrical reset after fault trip (Res) Following tripping, this function resets the “fault trip” indication contacts (SDE) and the mechanical indicator and enables circuit breaker closing. Power supply: 110 / 130 V AC and 200 / 240 V AC reset order K2 SDE2 K1 Automatic reset after fault trip (RAR) Following tripping, a reset of the mechanical indicator (reset button) is no longer required to enable circuit-breaker closing. The mechanical (reset button) and electrical (SDE) indications remain in fault position until the reset button is pressed. 42 Masterpact Schneider Electric 056458 Remote tripping This function opens the circuit breaker via an electrical order. It is made up of: c a shunt release (second MX) c or an undervoltage release (MN) c or a delayed undervoltage release (MN + delay unit). The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain instantaneous opening of the circuit breaker. E46554 E46553 E46043 Wiring diagram for the remote-tripping function opening order delayed opening order opening order 10 12 3 6 056421 time delay unit MX or MN voltage release C12 D2 instantaneous opening order MN MN MX2 C11 D2 D1 D1 Voltage releases (second MX) When energised, the MX voltage release instantaneously opens the circuit breaker. A continuous supply of power to the second MX locks the circuit breaker in the OFF position. characteristics power supplyV AC 50/60Hz V DC operating threshold permanent locking function consumption (VA or W) circuit-breaker response time at Un 24 - 48 - 100/130 - 200/250 - 277- 380/480 12 - 24/30 - 48/60 - 100/130 - 200/250 0.7 to 1.1 Un 0.85 to 1.1 Un pick-up: 200 hold: 4.5 50 ms ± 10 Instantaneous voltage releases (MN) The MN release instantaneously opens the circuit breaker when its supply voltage drops to a value between 35% and 70% of its rated voltage. If there is no supply on the release, it is impossible to close the circuit breaker, either manually or electrically. Any attempt to close the circuit breaker has no effect on the main contacts. Circuit-breaker closing is enabled again when the supply voltage of the release returns to 85% of its rated value. characteristics power supplyV AC 50/60 Hz V DC operating opening threshold closing consumption (VA or W) circuit-breaker response time at Un 24 - 48 - 100/130 - 200/250 - 380/480 24/30 - 48/60 - 100/130 - 200/250 0.35 to 0.7 Un 0.85 Un pick-up: 200 hold: 4.5 40 ms ± 5 pour NT 90 ms ± 5 pour NW MN delay units To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of the MN release can be delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions are available, adjustable and non-adjustable. characteristics power supply V AC 50-60 Hz /DC operating threshold consumption (VA or W) circuit-breaker response time at Un 43 Masterpact non-adjustable adjustable opening closing non-adjustable adjustable 100/130 - 200/250 48/60 - 100/130 - 200/250 - 380/480 0.35 to 0.7 Un 0.85 Un pick-up: 200 hold: 4.5 0.25 s 0.5 s - 0.9 s - 1.5 s - 3 s Schneider Electric Functions and characteristics Accessories 056463 Auxiliary terminal shield (CB) Optional equipment mounted on the craddle, the shield prevents access to the terminal block of the electrical auxiliaries. 056464 Operation counter (CDM) E47535 The operation counter sums the number of operating cycles and is visible on the front panel. It is compatible with manual and electrical control functions. Escutcheon (CDP) Optional equipment mounted on the door of the cubicle, the escutcheon increases the degree of protection to IP 40 (circuit breaker installed free standing: IP30) . It is available in fixed and drawout versions. Blanking plate (OP) for escutcheon Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and drawout devices. Transparent cover (CP) for escutcheon Optional equipment mounted on the escutcheon, the cover is hinged and secured by a screw. It increases the degree of protection to IP 54, IK10. It adapts to both fixed and drawout devices. 016819 Escutcheon (CDP) with blanking plate Transparent cover (CP) for Escutcheon 44 Masterpact Schneider Electric 45 Masterpact Schneider Electric Functions and characteristics Source-changeover systems Presentation 87921 Remote-operated source-changeover systems This is the most commonly employed system. No intervention by human operators is required. The switch from the normal to the replacement source is controlled electrically. A remote-operated source-changeover system is made up of two or three circuit breakers or switch-disconnectors linked by an electrical interlocking system implemented in a number of manners. Device control is backed up by a mechanical interlocking system that protects against the consequences of an electrical malfunction and inhibits incorrect manual operation. Automatic source-changeover systems 029693 Service sector: c hospital operating rooms c safety systems for tall buildings c computer rooms (banks, insurance companies, etc.) c lighting systems in shopping centres. When a remote-operated source-changeover system is combined with an automatic controller, the sources can be controlled automatically according to a number of programmed operating modes. This solution provides optimal energy management: c switching to a replacement source depending on any external conditions; c management of power sources; c regulation; c emergency source replacement, etc. A communications function for dialogue with a supervisor is available for the automatic controller. IMG0021 Industry: c assembly lines c propulsion systems on ships c essential auxiliaries in thermal power stations. Infrastructure: c port and railway installations c runway lighting systems c control systems for military installations. 46 Masterpact Schneider Electric Mechanical interlocking 056427 Electrical interlocking of two or three devices is used to create a remoteoperated source-changeover system. A basic mechanical interlocking system enhances the reliability of system operation. To ensure a continuous supply of power, certain electrical installations are connected to two power sources: c a normal source N; c a replacement source R which supplies the installation when source N is not available. A source-changeover system switches between the two sources. The system may include an automatic controller which manages switching according to external conditions. A source-changeover system may comprise two or three circuit breakers or switch-disconnectors. Interlocking of two devices using connecting rods The two devices must be stack mounted. This function requires: c an adaptation fixture on the right side of each device; c a set of connecting rods with no-slip adjustments. The complete interlock kit is supplied for assembly by the customer. Maximum vertical distance between the fixing planes: 900 mm Combinations of Masterpact Normal and Replacement devices Masterpact NT and NW devices may not be used together in a source-changeover system. The two devices must both be fixed devices or drawout devices to maintain correct alignment of the mechanisms. Interlocking of two or three devices using cables Using cables, the devices may be stack mounted or installed side-by-side. Interlocking of two devices (Masterpact NT or NW) This function requires: c an adaptation fixture on the right side of each device; c a set of cables with no-slip adjustments. Maximum distance between the fixing planes (vertical or horizontal): 2000 mm Interlocking of three devices (only Masterpact NW) This function requires: c an adaptation fixture (different for each type of interlocking) on the right side of each device; c two or three sets of cables with no-slip adjustments. Maximum distance between the fixing planes (vertical or horizontal): 1000 mm Installation The complete interlock kit is supplied for assembly by the customer. Combinations of Masterpact Normal and Replacement devices All combinations of Masterpact NT and NW devices may be used together in a sourcechangeover system. Interlocked devices may be fixed or drawout, three or four pole, with different ratings and sizes. 47 Masterpact Schneider Electric Functions and characteristics Source-changeover systems Electrical interlocking Electrical interlocking is used with the mechanical interlocking system. It controls switching between sources. An automatic controller may be added to take into account information from the distribution system. Electrical interlocking requires an electrical control device. This function can be implemented in one of two ways: c using the IVE electrical interlocking unit c by an electrician using the electrical systems presented in the diagrams in the “Source-changeover systems” section of this catalogue. Characteristics of the IVE unit c external connection terminal block: v inputs: control of devices v outputs: status of the SDE contacts on the Normal and Replacement devices. c connector to the two Normal and Replacement devices: v inputs: - status of the OF contacts on each device (ON or OFF) - status of the SDE contacts on the Normal and Replacement devices v outputs: power supply for motor mechanisms. c control voltage: v 24 to 250 V DC v 48 to 415 V 50/60 Hz v 440 V 60 Hz. The control voltage for the IVE electrical interlocking unit must be identical to that of the operating mechanism. Necessary equipment Each device must be equipped with: c a remote-operation system made up of: v MCH gear motor v MX or MN opening release v XF closing release v PF “ready to close” contact c an available OF contact c a CE connected-position carriage switch on drawout devices. types of mechanical interlocking possible combinations standard configurations ref. (presented in section “Source-changeover systems”) E30736 2 devices Q1 Q2 Q1 0 Q2 0 electrical interlocking 51156903 automatic controller with permanent replacement source 51156904 automatic controller with engine generator set 51156905 0 1 1 0 Q1 0 1 0 1 0 Q2 0 0 0 1 1 Q3 0 0 1 0 0 automatic controller with permanent replacement source: without lockout after fault 51156906 with lockout after fault 51156907 automatic controller with engine generator set: without lockout after fault 51156908 with lockout after fault 51156909 Q1 0 1 0 0 Q2 0 0 1 0 Q3 0 0 0 1 electrical interlocking: without lockout after fault with lockout after fault 51156910 51156911 Q1 0 1 0 0 1 0 1 Q2 0 0 1 0 1 1 0 Q3 0 0 0 1 0 1 1 electrical interlocking: without lockout after fault with lockout after fault automatic controller 51156912 51156913 51156914 E30737 3 devices: 2 Normal sources and 1 Replacement source Q1 Q2 Q3 E30738 3 devices: 3 sources, only 1 device closed Q1 Q2 Q3 E30739 3 devices: 2 sources and 1 coupling Q1 Q2 Q3 Lockout after fault option: this option makes it necessary to manually reset the device following fault tripping. 48 Masterpact Schneider Electric Associated automatic controllers By combining a remote-operated sourcechangeover system with an integrated BA or UA automatic controller, it is possible to automatically control source transfer according to user-selected sequences. These controllers can be used on sourcechangeover systems comprising 2 circuit breakers. For source-changeover systems comprising 3 circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams provided in the “electrical diagrams” section of this catalogue. controller BA compatible circuit breakers 4-position switch Automatic operation Forced operation on “Normal” source Forced operation on “Replacement” source Stop (both “Normal” and “Replacement” sources off) c c c c c c c c c c automatic operation Monitoring of the “Normal” source and automatic changeover Generator set startup control Generator set shutdown control Load shedding and reconnection of non-priority circuits Changeover to the “Replacement” source if one of the phases of the “Normal” phase is absent c c c c test By opening the P25M circuit breaker supplying the controller By pressing the test button on the front of the controller 053058R UA All Compact NS and Masterpact circuit breakers c c indications Circuit breaker status indication on the front of the controller: on, off, fault trip Automatic mode indicating contact c c c c Selection of type of “Normal” source (single-phase or three-phase) Voluntary transfer to “Replacement” source c (e.g. energy management commands) During peak-tariff periods (energy management commands), forced operation on “Normal” source if “Replacement” source not operational Additional contact (not part of controller). c Transfer to “Replacement” source only if contact is closed. (e.g. used to test the frequency of UR). Setting of maximum startup time for the replacement source c other functions BA controller c c c c options communication option c 053058 power supply control voltages (1) 220 to 240 V 50/60 Hz 380 to 415 V 50/60 Hz 440 V 60 Hz c c c c c c 0.35 Un i voltage i 0.7 Un 0.5 Un i voltage i 0.7 Un voltage u 0.85 Un c c c c operating thresholds undervoltage phase failure voltage presence c characteristics of output contacts rated thermal current (A) minimum load UA controller 8 10 mA at 12 V utilisation category (IEC 947-5-1) operational current (A) 24 V 48 V 110 V 220/240 V 250 V 380/415 V 440 V 660/690 V AC12 8 8 8 8 5 4 - AC AC13 7 7 6 6 - AC14 5 5 4 4 - AC15 6 5 4 3 - DC12 8 2 0.6 0.4 - DC DC13 2 - (1) The controller is powered by the ACP auxiliaries control plate. The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, then the “Normal” and “Replacement” sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used. 49 Masterpact Schneider Electric Display modules Perfectly integrated in the Compact and Masterpact ranges, Display modules are designed for use with Micrologic control units to provide instant and highly intuitive access to all the information provided by the circuit breakers, including device status, current, voltage and power values, etc. DMB300 and DMC300 display modules use the power and communications capabilities of the Micrologic control units to centralise the display of electrical values, status conditions and alarms of one or more Compact or Masterpact circuit breakers. The mounting and cabling system for the display modules ensures fast, easy and reliable installation. Start-up is immediate with no configuration or programming required. Digipact display modules are high-performance devices combining: c simple and easy-to-read dials c powerful and accurate digital processing. Their small size and extensive communications capabilities make for easy and flexible installation and operation. 057454 Functions and characteristics Display modules DMB300 DMC300 Associated circuit breakers Type Compact or Masterpact equipped with Micrologic control units 1 to 4 1 to 16 Number Display Screen type Screen size Entry DMB300 display module: basic and harmonic measurements Black and white 240 x 64 pixels 5 buttons Colour, touch screen 5“, 320 x 240 pixels Touch screen A A A A A A Information displayed E79078 Currents (per phase) Currents I1, I2, I3, IN Maximum current Earth-fault and earth-leakage currents Demand current Maximum demand current Total harmonic distortion (THD) Maximum total harmonic distortion Amplitudes of individual harmonics Waveform capture P P P P P H H H H H H H P P P P P P H H H H H H H H H Power Active (P), reactive (Q) and apparent (S) power Power factor and cos Maximum power (P, Q, S) Demand power (P, Q, S) Maximum demand power (P, Q, S) P P P P P Metering Active, reactive and apparent energy P Voltages Phase-to-phase voltages (U1-2, U2-3, U3-1) Minimum/maximum phase-to-phase voltages Phase-to-neutral voltages (V1-N, V2-N, V3-N) Minimum/maximum phase-to-neutral voltages Frequency Voltage imbalance (% per phase) Total harmonic distortion (% per phase) Maximum total harmonic distortion (% per phase) Amplitudes of individual harmonics DMC300 display module: measurements, harmonic analysis, diagnosis P P P P P H H H H H H H H H P P P H H H P P H H H H H H H H H H P P P P P H H H H H H P H On-line help On-line help is available for each type of information supplied by the module Circuit-breaker diagnostics Identification of control units Reading of protections Circuit-breaker status Type of trip Current alarms Maintenance indicator Installation diagnosis Indication of faulty devices Fault log Associated Micrologic control unit A = Micrologic A P = Micrologic P H = Micrologic H A A A A P P P P P H H H H H A A A A P P P P P P H H H H H H A A P P H H Installation and start-up Mounting Connection 50 Masterpact Mounted through door, without tools, using 6 spring-clips supplied with the mod. Prefabricated wiring systems Schneider Electric 24 V DC power E59178 Connection of DMB300 display module Wiring system The wiring system is designed for low-voltage power switchboards. Installation requires no tools or special skills. The prefabricated wiring ensures both data transmission (ModBus protocol) and 24V DC power distribution for the display module and the communications modules on the Micrologic control units. 1 2 E59081A ON ON ON n° 4n° 4 4 ON n° n° 3n°° 3 n° 4 n° 2n° 2 n° 3 n° 3 n° 1n° 1 n° 2 n° 2 OUTOUT n° 1 IN IN T IN ON OU 1 2 3 Reset push push 70 NX 32 ON Ir Ig Isd I ∆n Ii Ap reset Icu (kA) 100 100 85 Icw 85kA/1s cat.B d Ics = discharge CDM 303: Connection cable between display module and junction block H2 Ue (V) 220/440 525 690 OFF Micrologic 100% Icu 50/60Hz O OFF 947-2 AS NEMA IEC UNE EN 60947-2 BS CEI UTE 012 VDE 53 com DMB300 Digipact volets shutters Test 1 2 I 3 U P ? select E59180A 4 NW 1251 12kV Icu (kA) 100 85 Ue (V) 220/240 480/690 70 2 H1 Uimp Ui 1000V 8kV Uimp Micrologic Ir Ig Isd I ∆n Ii Ap reset I ON OOFF push push discharged O OFF Ics = IEC 100% Icu 947-2 UTE VDE 012 BS CEI ON NEMA UNE 53 IN NW 1251 n° 2 n° 3 n° 4 ON H1 Uimp Ui 1000V 8kV Uimp 12kV Icu (kA) 100 85 Ue (V) 220/240 480/690 70 n° 1 OUT Micrologic Ir Ig Isd I ∆n Ii Ap reset I ON OOFF push push discharged O OFF Ics = IEC 100% 947-2 UTE VDE Icu BS CEI CJB 306 junction block NEMA UNE 53 E59179 012 3 Masterpact circuit breakers equipped with Micrologic control units and the ModBus eco COM option CCP 303: Connection cable between Masterpact or Compact and junction block Connection of DMC300 display module Maximum distance between module and circuit breaker: 1200 m 5 4 E59082A E59176A 4 2 2 2 1 NW 1251 H1 Uimp Ui 1000V 8kV Uimp NW 12kV Ir Ap reset Ir I ON OOFF Ig Isd I ∆n Ii Ap I ON OOFF discharged O OFF Ics = IEC 100% NX 32 ON d discharge Icu (kA) 100 100 85 Icw 85kA/1s cat.B Ics = 012 H2 Ue (V) 220/440 25 525 690 OFF reset 100% Icu 50/60Hz O OFF 947-2 AS NEMA IEC UNE EN 60947-2 BS CEI UTE 3 VDE Ics = BS CEI UNE NEMA IEC 012 NW 1251 H1 Uimp Ui 1000V 8kV Uimp NW 12kV Ap Ir I ON OOFF Ig Isd I ∆n Ii Ap I ON OOFF discharged Ics = IEC push push NX 32 ON 100% d discharge O OFF BS CEI UNE NEMA IEC 100% 947-2 UTE VDE 012 BS CEI UNE NEMA 53 5 Icu (kA) 100 100 85 100% Icu NW 50/60Hz 1251 70 NW 12kV Ig Isd I ∆n Ii H1 Uimp 12kV Icu (kA) 100 85 Ue (V) 220/240 480/690 70 Micrologic Ir 1251 Ui 1000V 8kV Uimp Icu (kA) 100 85 Ue (V) 220/240 480/690 VDE H1 Uimp Ui 1000V 8kV Uimp 947-2 AS NEMA IEC UNE EN 60947-2 BS CEI UTE Ics = 947-2 53 Icu Icw 85kA/1s cat.B Ics = Icu H2 Ue (V) 220/440 525 690 OFF reset push push O OFF UTE VDE 012 Ap 12kV Icu (kA) 100 85 reset push discharged 70 CCR 301: Roll of RS485 cable (2 RS485 wires + 2 power supply wires) H1 Uimp Ue (V) 220/240 480/690 70 reset push Ig Isd I ∆n Ii NEMA Micrologic Ig Isd I ∆n Ii O OFF Reset UNE 1251 Ui 1000V 8kV Uimp Icu (kA) 100 85 Ue (V) 220/240 480/690 70 Ir Ir Icu BS CEI 53 3 Micrologic Micrologic 100% 947-2 UTE VDE 53 3 E59177A Ap Icu 947-2 UTE VDE push push 70 Ig Isd I ∆n Ii push push discharged Reset 12kV Icu (kA) 100 85 reset push push Ir H1 Uimp Ue (V) 220/240 480/690 70 Micrologic Ig Isd I ∆n Ii O OFF Micrologic 1251 Ui 1000V 8kV Uimp Icu (kA) 100 85 Ue (V) 220/240 480/690 70 Micrologic Micrologic Ap reset Ir I ON OOFF Ig Isd I ∆n Ii Ap reset I ON push OOFF push discharged O OFF Ics = IEC 100% 947-2 UTE VDE 012 push push discharged O OFF Icu BS CEI Ics = UNE NEMA IEC 100% 947-2 UTE VDE 53 012 Icu BS CEI UNE NEMA 53 CSD 309: SubD 9-pin connector for colour-coded connection of wires to screw terminals Masterpact circuit breakers equipped with Micrologic control units and the ModBus eco COM option 51 Masterpact Schneider Electric 52 Masterpact Schneider Electric Dimensions and connection Masterpact Presentation Functions and characteristics 1 9 Masterpact NT06 to NT16 Fixed 3/4-pole device Drawout 3/4-pole device 54 58 Masterpact NW08 to NW32 Fixed 3/4-pole device Drawout 3/4-pole device 62 64 Masterpact NW40 Fixed 3/4-pole device Drawout 3/4-pole device 66 68 Masterpact NW40b to NW63 Fixed 3/4-pole device Drawout 3/4-pole device 70 72 NT/NW accessories NT/NW external modules 74 76 Electrical diagrams Installation recommendations Additional characteristics References 53 Masterpact 81 91 115 121 Schneider Electric NT06 to NT16 circuit breakers Fixed 3/4-pole device Dimensions and connection Dimensions E47191B 105 (3P) 175 (4P) 105 188 94 E47190B Y 178 136 105 210 X X 123 6,5 39 15 125 (3P) 195 (4P) 3 13 150,5 125 13 F Rear mounting detail (on upright or backplate) E47194B Bottom mounting (on base plate or rails) E47193A Y X Y E47192B 6 Ø6,5 4 Ø6,5 25 100 X 39 100 18 mini 39 maxi 136,5 B 194 mini (3P) 264 mini (4P) 125 Rear panel cutouts E47197A A (*) E47196A E47195A E59443A Door cutout B 77 125 125 (3P) 195 (4P) Safety clearances 154 F 125 (3P) 195 (4P) F A (*) 125 62,5 194 mini Y Y 62 44 X 40 130 108 (1) 133 (2) F 194 (1) 244 (2) A B Insulated parts Metal parts Energised parts 0 0 0 0 100 60 F : Datum. X 216 (1) 266 (2) 100 (3P) 170 (4P) 62 106 100 97 (1) 122 (2) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 50 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block. 54 Masterpact Schneider Electric E47210A Connections E47200A Detail 43,5 E47199A E47198A Horizontal rear connection 70 70 70 15 123 67,5 N Y X 67,5 44 E47201B 123 25 15 9,5 12,5 60 167,5 12,5 F 2 Ø11 Detail E47204A 43,5 E47203A E47202A Vertical rear connection 70 70 70 15 View A 97 N X Y E47205B 97 60 12,5 9,5 12,5 167,5 F 44 25 2 Ø11 View A detail 12 E47208A Detail E47207B 150 View A 70 N 326 X 44 25 70 70 Y Top connection E47209B E47206A Front connection Bottom connection 2 Ø11 9,5 13 150 13 2 Ø11 25 44 9,5 View A detail 164 F Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 55 Masterpact Schneider Electric NT06 to NT16 circuit breakers Fixed 3/4-pole device Dimensions and connection Connection E47213A E47212A E47211A Front connection with spreaders 95 95 70 View A 70 15 202 Y 434 95 E47214A X 95 70 95 70 70 12,5 202 View A 12,5 15 N Y 179 F 98 95 E47221A E47219A E47220A Rear connection with spreaders 95 70 70 123 15 X 15 82,5 52,5 Y E47222A 123 95 95 70 95 70 70 219,5 12,5 234,5 12,5 F N Y Spreader detail 25 = 38,5 13,5 = 25 = 13,5 = 15 5 Ø11 = 13,5 = 38,5 = 13,5 = 30 30 82 52 15 77 25 30 82 52 15 5 Ø11 82 52 15 5 Ø11 5 Ø11 25 25 52 38,5 25 30 82 52 77 Left or right spreader for 3P E47294A 77 Left or right spreader for 4P E47293A 77 38,5 Middle spreader for 3P E47292A E47234A Middle left or middle right spreader for 4P 25 25 52 52 52 View A detail F : Datum Note: X and Y are the symmetry planes for a 3-pole device. 56 Masterpact Schneider Electric E47210A Connections E47216A 116,5 E47217A E47215A Front connection via vertical connection adapters 70 70 70 15 View A 21 221 N E47218A 472 X 89 = = 25 12,5 15 21 (1) 101 221 21 Y 21 3 Ø11 15 20 View A detail 190,5 253 F 15 E47232A 221 E47233A E47231A Front connection via vertical connection adapters fitted with bare cable connectors. 70 70 70 15 50 View A 271 21 221 572 X E47230A N Y 184 17 50 50 21 50 50 80 221 271 15 5 Ø13 5 Ø11 View A detail 50 15 340,5 357,5 F Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer (1) 2 connection possibilities on vertical connection adapters (21 mm between centres) 57 Masterpact Schneider Electric NT06 to NT16 circuit breakers Drawout 3/4-pole device Dimensions and connection E47172A Dimensions E47171C 210 mini 127,5 (3P) 197,5 (4P) 160,5 188 94 Y 46 (*) 199 X X 123 5 45,5 60 mini 90 (3P) 160 (4P) 231 90 F (*) disconnected position Bottom mounting (on base plate or rails) Rear mounting detail (on upright or backplate) E47175B Y X E47173B E47174B Y 4 Ø6,5 6 Ø6,5 X 25 24 150 50 25 100 100 216 231 F 90 (3P) 160 (4P) 109 (3P) 179 (4P) B B C C 170 mini (3P) 240 mini (4P) 109 Rear panel cutout E47178A Door cutout E47177B A E47176B E59444A Safety clearances F 90 230 mini Y X Y X 259 (1) 303 (2) 234 117 40 180 F A B C 109 (1) 130,8 (2) 161 (1) 183 (2) Insulated parts Metal parts Energised parts 0 10 0 0 10 0 30 60 30 102,5 (3P) 172,5 (4P) 102,5 259 (1) 307 (2) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. F : Datum. 58 Masterpact Schneider Electric E47189A Connections E47181A Detail E47180A E47179A Horizontal rear connection 49 70 70 70 15 67,5 228 X N E47201B 67,5 114 Y 44 25 9,5 12,5 15 267,5 F 60 12,5 2 Ø11 Detail 70 E47183A E47182A Vertical rear connection 70 70 15 49 97 E47184A View A X N E47205B 97 Y 60 12,5 9,5 12,5 267,5 F 44 25 2 Ø11 View A detail Detail 15 12,5 70 E47187A E47186B 70 View A 70 171 N X Top connection 9,5 12,5 Bottom connection 44 140 235 Y 336 25 37,9 26 83 F 131 52 26 37,9 9,5 100 2 Ø11 25 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 9,5 2 Ø11 E47188B E47185A Front connection 44 9,5 View A detail 59 Masterpact Schneider Electric NT06 to NT16 circuit breakers Drawout 3/4-pole device Dimensions and connection Connection E47225A E47224A E47223A Front connection with spreaders 95 95 70 View A 70 238 223 Y E47226A X 207 95 95 70 95 70 70 View A 192 12,5 12,5 250 F N Y Rear connection with spreaders 25 = 38,5 13,5 = 25 = 13,5 = 15 5 Ø11 = 13,5 = 38,5 = 13,5 = 30 30 82 52 15 77 25 30 82 52 15 5 Ø11 82 52 15 5 Ø11 5 Ø11 25 25 52 38,5 25 30 82 52 77 Left or right spreader for 3P E47294A 77 Left or right spreader for 4P E47293A 77 38,5 Middle spreader for 3P E47292A E47234A Middle left or middle right spreader for 4P 25 25 52 52 52 View A detail Note: X and Y are the symmetry planes for a 3-pole device. F : Datum 60 Masterpact Schneider Electric E47189A Connections E47227A E47228A 15 E47229A Front connection via vertical connection adapters fitted with bare cable connectors. 70 70 70 View A 15 50 71 292 21 N 583 X E472230A 171 Y 15 184 17 50 50 50 140 21 50 80 261 5 Ø13 71 5 Ø11 View A detail 50 15 193,5 F Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 61 Masterpact Schneider Electric NW08 to NW32 circuit breakers Fixed 3/4-pole device Dimensions and connection E46050A Dimensions 189 (3P) 304 (4P) 189 308 154 E46055A Y 191 150 260 X X 161 11 7 57 233 200 (3P) 315 (4P) 11 11 Mounting detail Y E46052A E46051A Mounting on base plate or rails 200 X Ø9,5 25 72 15 mini 60 maxi 38 162 F 218,5 200 (3P) 315 (4P) F B E46054A A (*) 200 Ø9,5 Door cutout A (*) B E46053A Safety clearances E59445A 124 162 295 mini (3P) 410 mini (4P) 295 mini Y 270 (1) 316 (2) 135 (1) 158 (2) X 15 205 F 325 (1) 364 (2) A B Insulated parts Metal parts Energised parts 0 0 0 0 100 60 F : Datum. 162,5 (1) 182 (2) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block. 62 Masterpact Schneider Electric E46004A NX 08 HA1012kV Uimp Ui 1000V Ue (V) 690 s 50kA/1 50/60Hz AS UNE IEC 947-2 BS CEI EN 60947-2 VDE UTE maste rpact NBMA II N GERIN MERLI Connections Horizontal rear connection Détail 20 E46056A E46086A E46351A 27 115 115 115 20 150 N 76 E46057A X 93 Y 13 38 161 = = 25 12,5 20 47 233,5 3 Ø11,5 F Detail E46058A 27 E46089A E46087A Vertical rear connection 14,5 115 115 115 20 View A 68 N X E46059A 141 Y 47 14,5 12,5 13 = 233,5 = F 3 Ø11,5 76 38 25 View A detail E46090A 20 12,5 E46060A Detail E46088A Front connection 115 115 N 230,5 E46061B 475 View A Y Top connection X 115 Bottom connection 76 25 25 13 12,5 219,5 3 Ø11,5 3 Ø11,5 12,5 12,5 219 View A detail F 25 25 13 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 63 Masterpact Schneider Electric NW08 to NW32 circuit breakers Drawout 3/4-pole device Dimensions and connection E46352A Dimensions E46506A 400 mini 220,5 (3P) 335,5 (4P) 220,5 308 154 Y 56 (*) 238,5 X X 200,5 128 11 383,5 200 60 mini 400 (*) Disconnected position Mounting detail Y E46353B E46354A Mounting on base plate or rails X 2 Ø11,5 x 22 Ø11,5 10 175 110 103 Ø10,5 175 283 F F 167,5 (3P) 282,5 (4P) Door cutout A A B E59446A E46356A B E46355A Safety clearances 162,5 300 mini (3P) 415 mini (4P) 300 mini Y 270 (1) 379 (2) X 135 (1) 222 (2) 153,3 (1) 100 225 F A B 325 (1) 364 (2) Insulated parts Metal parts Energised parts 0 0 0 0 0 60 F : Datum. 162,5 (1) 182 (2) 47 (1) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. 64 Masterpact Schneider Electric E46005A NX 08 HA10 12kV Uimp Ui 1000V Ue (V) 690 50kA/1s 50/60Hz UNE IEC 947-2 BS CEI EN 60947-2 VDE UTE AS NBMA act II masterp GERIN MERLIN Connections Detail E46363A E46360A E46357A Horizontal rear connection 115 115 115 27 20 N 20 76 E46057A X 296 93 Y 13 38 = = 25 12,5 184 47 20 3 Ø11,5 14,5 298,5 F Detail E46364A E46361A E46358A Vertical rear connection 115 115 115 20 View A 27 N X 141 E46059A 68 Y 47 14,5 12,5 13 = = 298,5 3 Ø11,5 76 38 25 F View A detail 20 12,5 E46365A Detail E46362A E46359A Front connection 115 N 151 E46819B 400 View A 115 Y Top connection X 115 Bottom connection 76 25 25 224 13 12,5 3 Ø11,5 3 Ø11,5 12,5 284 12,5 F View A detail 25 25 13 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 65 Masterpact Schneider Electric NW40 circuit breakers Fixed 3/4-pole device Dimensions and connection E46050A Dimensions 189 (3P) 304 (4P) 189 308 154 E46055A Y 191 150 260 X X 161 11 7 57 200 (3P) 315 (4P) 11 233 11 Mounting detail E46052A E46051A Mounting on base plate or rails 200 X Y Ø9,5 25 72 15 mini 60 maxi 124 162 38 162 F 218,5 200 (3P) 315 (4P) F A (*) B A (*) B 295 mini (3P) 410 mini (4P) E46054A E59445A Ø9,5 Door cutout E46053A Safety clearances 200 295 mini Y 270 (1) 316 (2) 135 (1) 158 (2) X 15 205 F 325 (1) 364 (2) A B Insulated parts Metal parts Energised parts 0 0 0 0 100 60 F : Datum. 162,5 (1) 182 (2) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block. 66 Masterpact Schneider Electric E46484A NX 08 HA1012kV Uimp Ui 1000V Ue (V) 690 s 50kA/1 50/60Hz UNE IEC 947-2 BS CEI EN 60947-2 VDE UTE maste rpact AS NBMA II N GERIN MERLI Connections Horizontal rear connection E46485A E46351A 27 20 20 150 X 93 161 20 233,5 F 150 150 115 52,5 E46490A E46489B Detail 150 115 115 12,5 14,5 25 25 25 52,5 17,5 17,5 135 12,5 47 E46550A 4 Ø11,5 N 332,5 (4P) 100 12,5 12,5 25 25 25 14,5 217,5 Y 47 27 E46488A E46486A Vertical rear connection 117,5 X 190,5 233,5 F 115 115 115 20 E46491A E46058A Detail 47 14,5 12,5 View A 12,5 25 N 25 Y 20 25 125 25 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 5 Ø11,5 67 Masterpact Schneider Electric NW40 circuit breakers Drawout 3/4-pole device Dimensions and connection E46506A Dimensions 220,5 (3P) 335,5 (4P) E46352A 400 mini 220,5 308 154 Y 56 (*) 238,5 X X 200,5 128 11 383,5 200 400 60 mini (*) Disconnected position Mounting on base plate or rails Mounting detail E46353B E46354A Y X 2 Ø11,5 x 22 Ø11,5 10 175 Ø10,5 110 103 175 F 283 F 167,5 (3P) 282,5 (4P) Door cutout A A B E59446A E46356A B E46355A Safety clearances 162,5 300 mini (3P) 415 mini (4P) 300 mini Y 270 (1) 379 (2) X 135 (1) 222 (2) 153,3 (1) 100 225 F A B 325 (1) 364 (2) Insulated parts Metal parts Energised parts 0 0 0 0 0 60 F : Datum. 162,5 (1) 182 (2) 47 (1) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. The safety clearances take into account the space required to remove the arc chutes. 68 Masterpact Schneider Electric E46005A NX 08 HA10 12kV Uimp Ui 1000V Ue (V) 690 50kA/1s 50/60Hz UNE IEC 947-2 BS CEI EN 60947-2 VDE UTE AS NBMA act II masterp GERIN MERLIN Connections E46492A E46360A Horizontal rear connection 27 20 20 X 296 93 184 20 298,5 F 150 150 115 E46490A E46496B Detail 150 115 115 52,5 135 12,5 12,5 14,5 25 25 25 52,5 17,5 17,5 47 N Y 332,5 E46550A 4 Ø11,5 217,5 100 12,5 12,5 25 25 25 14,5 47 E46491A E46493A E46495A Vertical rear connection 47 14,5 12,5 27 12,5 25 25 117,5 20 25 125 25 X 5 Ø11,5 190,5 View A detail 298,5 F E46364A Detail 115 115 115 20 View A Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer N 69 Y Masterpact Schneider Electric NW40b to NW63 circuit breakers Fixed 3/4-pole device Dimensions and connection Dimensions E46282A 534 3P) 764 (4P) 189 308 154 E46055A Y 191 150 260 X X 161 7 57 545 (3P) 775 (4P) 11 233 11 Mounting detail Y E46283A E46284A Mounting on base plate or rails 200 X Ø9,5 25 72 124 162 38 15 mini 60 maxi 162 F 218,5 545 (6P) 775 (8P) F Safety clearances A (*) Ø9,5 Door cutout A (*) B 639 mini (3P) 839 mini (4P) B E46286A 295 mini Y E46285A E59445A 200 270 (1) 316 (2) 135 (1) 158 (2) X 15 205 F 325 (1) 364 (2) A B Insulated parts Metal parts Energised parts 0 0 0 0 100 60 F : Datum 162,5 (1) 182 (2) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block. 70 Masterpact Schneider Electric E46281A NX 63 HA Uimp 12kV Ui 1000V Ue (V) 690 Icw 85kA/1s 50/60Hz AS 947-2 UNE IEC BS CEI EN 60947-2 VDE UTE pact master NBMA II GERIN MERLIN Connections E46551A Horizontal rear connection (NW40b - NW50) E46287A 20 X E46289A 47 230 115 230 115 115 115 230 115 115 115 20 150 20 93 N 161 Y E46057A 76 13 38 253,5 25 = = 12,5 F 47 3 Ø11,5 E46290A Détail E46552A E46288A Prises arrière verticales (NW40b - NW50) 14,5 47 230 115 230 115 115 115 230 115 115 115 68 20 View A X 141 N Y 47 14,5 12,5 13 E46059A 253 253,5 F = 76 = 3 Ø11,5 38 25 View A detail Vertical rear connection (NW63) Detail 47 230 230 115 115 115 230 115 115 115 20 E46290A E59536A E59535A 115 117,5 View A X N 190,5 Y 47 14,5 12,5 253 253,5 E46491A F 12,5 25 25 20 25 125 25 5 Ø11,5 Note: Recommended connection screws: M10 s/s class A4 80 Tightening torque: 50 Nm with contact washer. View A detail 71 Masterpact Schneider Electric NW40b to NW63 circuit breakers Drawout 3/4-pole device Dimensions and connection 565,5 (3P) 795,5 (4P) E46498A E46487A Dimensions 400 mini 220,5 308 154 Y 56 (*) 238,5 X X 200,5 128 40 60 mini 11 383,5 200 400 (*) Disconnected position Mounting detail E46508A Mounting on base plate or rails Y E46499A X 250 53 250 333 23 F 6 Ø11 x 34 325 (3P) 450 (4P) Safety clearances F 151 (3P) 162,5 (4P) 174 (3P) 287,5 (4P) Door cutout A A B 646 mini (3P) 876 mini (4P) 300 mini Y E46500A E59446A E46501A B 270 (1) 379 (2) X 135 (1) 222 (2) 153,3 (1) 150 275 F A B 47 (1) Insulated parts Metal parts Energised parts 0 0 0 0 0 60 F : Datum. 325 (1) 364 (2) 162,5 (1) 182 (2) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. 72 Masterpact Schneider Electric E46497A NX 08 HA10 12kV Uimp Ui 1000V Ue (V) 690 50kA/1s 50/60Hz AS UNE IEC 947-2 BS CEI EN 60947-2 VDE UTE NBMA t II masterpac GERIN MERLIN Connections Detail E46507A Horizontal rear connection (NW40b - NW50) 115 X 20 115 115 115 N 291 93 115 115 E46504A 20 Y 76 E46057A E46502A 27 115 179 13 38 = = 25 12,5 20 47 3 Ø11,5 14,5 348,5 F Detail E46494A E46505A Vertical rear connection (NW40b - NW50) 115 115 115 115 115 115 115 20 E46503A 27 View A 68 N Y E46059A X 141 47 14,5 12,5 13 = = 348,5 F 3 Ø11,5 76 38 25 View A detail Detail E59533A E46505A E59534A Vertical rear connection (NW63) 115 115 115 115 115 115 115 20 27 View A 117,5 190,5 E46491A N X Y 47 14,5 12,5 12,5 25 25 348,5 20 F 25 125 25 5 Ø11,5 View A detail Note: Recommended connection screws: M10 s/s class A4 80 Tightening torque: 50 Nm with contact washer 73 Masterpact Schneider Electric NT/NW accessories Dimensions and connection Mounting on backplate with special brackets (Masterpact NW08 to NW32 fixed). E46805A 429 (3P) 544 (4P) E46806A Y 4 Ø12 X X 159 96 113 218,5 4,5 203,5 11 125 11 407 (3P) 522 (4P) F Disconnectable front-connection adapter (Masterpact NW08 to NW32 fixed) Detail 67 115 E46812A E46807A E46809A Horizontal rear connection 20 115 N 183 Y 76 E46057A X 115 13 38 25 = = 12,5 172 47 3 Ø11,5 14,5 20 253,5 F Detail E46810A 67 E46811A E46808A Vertical rear connection 115 115 115 20 View A 231 E46059A N X Y 47 14,5 12,5 13 220 = 76 = 3 Ø11,5 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 253,5 38 25 View A detail F F Datum 74 Masterpact Schneider Electric Rear panel cutout (drawout devices) E46271A NW08 to NW40 E46272A Y X 302 X 187 264 200,5 (3P) 315,5 (4P) 200,5 401 (3P) 516 (4P) F E46273A E46274A NW40b to NW63 Y X 297 X 182 314 478,5 (3P) 708,5 (4P) 200,5 679 (3P) 909 (4P) F Escutcheon Masterpact NT Fixed device Drawout device Y E59887A E59885A Y X X 275 313 27 27 27 27 13 27 317 253 Masterpact NW Fixed device Drawout device Y E59890A E59889A Y X X 324 25 387 18 45 25 372 25 F Datum 25 372 75 Masterpact Schneider Electric NT/NW external modules Dimensions and connection E47684A E47683A Connection of auxiliary wiring to terminal block S : 0,6 mm2 S : 2,5 mm2 2 1 8 Ø3,5 One conductor only per connection point M6C relay module 1 3 11 9 7 5 15 13 17 23 25 81 S1 S2 S3 S4 S5 S6 M6c 1 9 5 7 3 S1 S3 2 4 11 24V 25 21 23 17 19 . com 0V 46 E47689A E47688A 99 21 19 1 S2 S6 S5 22 24 S4 18 20 14 16 10 12 6 8 3 13 15 17 19 M6c 1 25 21 23 17 19 . com 0V 24V S6 S5 24 20 22 16 18 14 10 12 6 8 9 5 7 3 11 21 23 25 S1 S2 S3 S4 S5 S6 S2 S1 S4 99 66 11 9 7 5 S3 2 4 46 External power supply module (AD) E47690A 60 L4 L3 AD 22 t Inpu C 24VD 2 Ø6 60 73 + ut Outp C 24VD G2 0A 112 E47691A G1 75 L4 L3 t Inpu C 24VD ut Outp C 24VD 0A AD 22 + G2 G1 Battery module (BAT) Mounting E47692A 60 2 Ø6 60 H4 H3 24V BAT t Inpu C 24VD + + 73 ut Outp C 24VD H1 112 75 E47693A H2 H4 H3 24V BAT t Inpu C 24VD + + ut Outp C 24VD H1 H2 76 Masterpact Schneider Electric Delay unit for MN release MNR E47694A 57 1 2 3 4 5 6 81 S 3 6 0.5 10 12 3 73,5 73 E47695A 2 66 42 1 1.5 3 MN r de R UV dateu Retardelay for Time MN UVR 30 V 100/1C AC/D 1 2 Ø4,2 1 2 3 4 5 6 72 S 3 6 0.5 30 V 100/1C AC/D 1 2 1 1.5 3 MN r de R UV dateu Retardelay for Time MN UVR 10 12 3 46 “Craddle” communication module BatiBUS E47686A E47685A ModBUS 90 Fault Com. CE CD CT ss Addre . sync 58 45 Breaker us modb CCM Disjoncteur Réseau shield B’ B’ A’ A’ B B A A Network ++ + 54 External sensor for source ground return (SGR) protection “MGDF summer” module E58561 E47687A Sensor 200 90 130 45 F MDG 45 76 150 58 77 Masterpact 106 Schneider Electric NT/NW external modules Dimensions and connection External sensor for external neutral Dimensions 400/1600 A (NT06 to NT16) 400/2000 A (NW08 to NW20) 4 Ø14 E47700 E47699 GND VN VC H1 H2 H1 4 Ø14 H2 SG1 SG2 X1 X2 GND VN VC 35 76 X2 X1 SG2 SG1 177 44 102 208 174 206 2000/6300 A (NW40b to NW63) 8 Ø14 H1 H2 SG1 SG2 X1 X2 GND VN VC 44 174 E47702 E47701 1000/4000 A (NW025 to NW40) 16 Ø14 H1 H2 SG1 SG2 X1 X2 GND VN VC 44 127 127 44 H1 44 H2 SG1 SG2 X1 X2 GND VN VC 295 44 174 70 44 127 44 295 Installation 400/2000 A (NW08 to NW20) E47696A E47696 400/1600 A (NT06 to NT16) 2000/6300 A (NW40b to NW63) E67969 E47697A 1000/4000 A (NW25 to NW40) 2 identical external sensor shipped as loosed part 78 Masterpact Schneider Electric Rectangular sensor for earth leakage protection (Vigi) 280 x 115 mm window E47703A E47704B 4 Ø9 115 2 M3 M1 M 197 215 M1 M2 M3 70 280 362 380 470 x 160 mm window E47717A E47718B 8 Ø9 146 2 M1 M 242 160 260 M3 M1 M2 M3 70 456 470 552 570 Busbars window (mm) weight (kg) I i 1600 A I i 3200 A 280 x 115 14 470 x 160 18 Busbars path 470 x 160 window Busbars spaced 115 mm centre-to-centr E47708 E47707 280 x 115 window Busbars spaced 70 mm centre-to-centre M1 M2 M3 M1 M2 M3 2 bars 50 x 10 E67971 E67970 4 bars 100 x 5 M1 M2 M3 M1 M2 M3 2 bars 100 x 5 4 bars 125 x 5 79 Masterpact Schneider Electric 80 Masterpact Schneider Electric Electrical diagrams Masterpact Presentation Functions and characteristics Dimensions and connection 1 9 53 Masterpact NT06 to NT16 Masterpact NW08 to NW63 Masterpact NT and NW 82 84 86 Installation recommendations Additional characteristics References 81 Masterpact 91 115 121 Schneider Electric Masterpact NT06 to NT16 Fixed and drawout devices Electrical diagrams The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position. readyto-close fault fault Z5 Z4 Z3 Z1 downstream cb Z5 Z4 L3 Z3 L2 Z2 L1 Z1 N Remote operation upstream cb AT charged Control unit power Z2 Power BPF M6C MCH Q SDE1 MN Res H UC2 B1 251 E46138A A1 D1 E46135A 81 181 E46139A or or E46133 471 E46132A F2+ F1 T4 T3 X2 T2 X1 T1 SG2 M3 SG1 M2 M1 E46555B P Com UC1 CH 24 V DC Remote operation Control unit Terminal block marking PF E46137A M6C or K1 M2C XF MX1 E46136A U MX2 C1 SDE2 S1 S2 Micrologic C11 I A B2 B3 254 A3 252 A2 C3 C2 C12 D2 84 82 K2 184 182 Q3 Q2 Q1 484 474 Z5 Z4 Z3 Z2 Z1 V3 V2 V1 VN BPO UC3 UC4 / M2C / M6C SDE2 / Res E5 E6 Z5 M1 M2 M3 F2+ V3 / 484 / Q3 184 E3 E4 Z3 Z4 T3 T4 VN V2 / 474 / Q2 182 E1 E2 Z1 Z2 T1 T2 F1 – V1 / 471 / Q1 181 Control unit / K2 SDE1 84 MN / MX2 D2 / C12 82 / K1 81 D1 / C11 MX1 XF PF MCH C2 A2 254 B2 C3 A3 252 B3 C1 A1 251 B1 Remote operation c c c Com: E1-E6 communication c c c UC1 : Z1-Z5 zone selective interlocking; Z1 = ZSI OUT SOURCE Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) SDE2: Fault-trip indication contact or Res : Remote reset SDE1: Fault-trip indication contact (supplied as standard) MN : Undervoltage release or MX2 : Shunt release c c c c c c c c c UC2 : T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7) MX1 : Shunt release (standard or communicating) XF : Closing release (standard or communicating) c c c PF : Ready-to-close contact c c UC3 : F2+, F1– external 24 DC power supply VN external voltage connector (optional) c c UC4 : optional external voltage connector c c M2C : 2 programmable contacts (internal relay); ext. 24V DC power supply required or c c M6C : 6 programmable contacts (external relay); ext. 24V DC power supply required. MCH: electric motor or Note: When communicating MX or XF releases are used, the third wire (C3,A3) must be connected even if the communication module is not installed. A : Digital ammeter P: A + power meter + additional protection H: P + harmonics 82 Masterpact Schneider Electric Craddle contacts OF4 OF3 OF2 OF1 CD2 44 34 24 14 42 32 22 12 41 31 21 11 Indication contacts OF4 / OF3 / OF2 / OF1 : ON/OFF indication contacts 914 912 314 312 324 E47074A 311 911 CE1 321 CE2 CD1 CE3 CE2 CE1 CT1 824 814 334 324 314 914 822 812 332 322 312 912 821 811 331 321 311 911 Craddle contacts CD2: Disconnected CD1 position contacts (*) Spring charging motor 440/480 V AC (380 V motor + additional resistor) CE3: Connected CE2 position CE1 contacts CT1: Test position contacts - 440/480 V 9 “spring charged“ light 440/480 V 322 332 814 CE3 E46134A 821 E47075A 11 21 31 41 E46141A 812 824 12 822 CT1 CD1 Indication contacts CN1 Test OF1 CD2 E47484 connected 331 OF2 14 22 OF3 disconnected 811 OF4 24 32 closed 34 44 42 open Craddle contacts 334 Indication contacts 11 R B3 B2 MCH 380V CH B1 CN2 key: - 440/480 V Drawout device only XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard Interconnected connections (only one wire per connection point) 83 Masterpact Schneider Electric Masterpact NW08 to NW63 Fixed and drawout devices Electrical diagrams The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position. readyto-close fault fault Z5 Z4 Z1 downstream cb Z5 Z4 L3 Z3 upstream cb L2 Z2 L1 Z1 N Z3 power Remote operation AT charged Control unit Z2 Power BPF M6C Q B2 B3 254 A3 252 A2 C3 C2 C12 D2 84 82 K2 184 182 Q3 Q2 Q1 484 474 Z5 Z4 Z3 Z2 Z1 V3 V2 V1 VN BPO MCH I SDE1 MN SDE2 S1 S2 Micrologic U MX2 XF MX1 PF CH Res E46139A B1 251 E46138A A1 E46137A E46136A C1 D1 81 181 E46135A E46133 471 E46132A F2+ T4 F1 T3 X2 T2 X1 M3 T1 SG2 24 V DC E46555B SG1 M2 M1 or or C11 M6C ou K1 M2C Remote operation Control unit Terminal block marking A c c P c c H Com UC1 UC2 UC3 UC4 M2C / M6C SDE2 / Res E5 E6 Z5 M1 M2 M3 F2+ V3 484 / Q3 184 E3 E4 Z3 Z4 T3 T4 VN V2 474 / Q2 182 E1 E2 Z1 Z2 T1 T2 F1 – V1 471 / Q1 181 Control unit / K2 SDE1 84 MN / MX2 D2 / C12 82 / K1 81 D1 / C11 MX1 XF PF MCH C2 A2 254 B2 C3 A3 252 B3 C1 A1 251 B1 Remote operation c Com: E1-E6 communication c UC1 : Z1-Z5 zone selective interlocking; Z1 = ZSI OUT SOURCE Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) c c c c c c c c c UC2 : T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7) c c c c c UC3 : F2+, F1– external 24 DC power supply VN external voltage connector (optional) c c UC4 : V1, V2, V3 optional external voltage connector c c M2C : 2 programmable contacts (internal relay); ext. 24V DC power supply required or c c M6C : 6 programmable contacts (to be connected to the external module M6C); ext. 24V DC power supply required SDE2: Fault-trip indication contact or Res : Remote reset SDE1: Fault-trip indication contact (supplied as standard) MN : Undervoltage release or MX2 : Shunt release MX1 : Shunt release (standard or communicating) XF : Closing release (standard or communicating) PF : Ready-to-close contact MCH: electric motor Note: When communicating MX or XF releases are used, the third wire (C3,A3) must be connected even if the communication module is not installed. A : Digital ammeter P: A + power meter + additional protection H: P + harmonics 84 Masterpact Schneider Electric Indication contacts 914 912 924 922 934 932 314 312 Test 324 814 332 812 824 822 834 832 ..6 322 connected disconnected 334 connected and closed ..8 ..4 ..2 12 14 22 24 32 not connected or connected and open closed closed 34 42 44 open Craddle contacts EF . . OF4 OF3 OF2 OF . . OF1 OF CT3 CD3 CD2 CD1 CE3 CE2 CT2 CT1 CE1 or Indication contacts 911 921 931 E46142A 311 321 331 E46134A 811 CD3 CD2 CD1 114 834 824 814 334 324 314 934 924 914 122 112 832 822 812 332 322 312 932 922 912 131 121 111 831 821 811 331 321 311 931 921 911 or or or OF3 OF2 OF1 44 34 24 14 244 234 224 214 144 134 124 42 32 22 12 242 232 222 212 142 132 41 31 21 11 241 231 221 211 141 or or or or or EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CE3 CE2 CE1 CT3 or CE6 CE5 CT2 CT1 or CE4 CE9 CE8 CE7 248 238 228 218 148 138 128 118 364 354 344 394 384 374 246 236 226 216 146 136 126 116 362 352 342 392 382 372 245 235 225 215 145 135 125 115 361 351 341 391 381 371 Indication contacts : ON/OFF indication contacts 821 Craddle contacts OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OF4 OF4 OF3 OF2 OF1 831 E46131A ..5 ..1 11 21 31 41 E46141A E46140 CE Craddle contacts OF24 or EF24 : ON/OFF indication contacts Combined “connected-deconnected” indication contacts OF23 or EF23 OF22 or EF22 CD3: Disconnected CE3: Connected CD2 position CE2 position CD1 contacts CE1 contacts CT3: Test CT2 position CT1 contacts or or CE6: Connected CE5 position CE4 contacts CE9:Connected CE8 position CE7 contacts OF21 or EF21 or OF14 or EF14 CD6:Disconnected CD5 position CD4 contacts key: OF13 or EF13 Drawout device only OF12 or EF12 XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard Interconnected connections (only one wire per connection point) OF11 or EF11 85 Masterpact Schneider Electric Masterpact NT and NW Communications option 24 VDC external power supply Electrical diagrams E47593 Connection of the communications option 914 L3 812 314 912 812 312 SDE MX1 com 911 PF CT + CD CE Modbus COM craddle CE BB BB B' A' B A E6 E5 E4 E3 E2 E1 F2+ F1 T4 T3 T2 T1 M3 M2 CD Digipact COM craddle + (2) CCP 303 M1 311 811 CT + + B' A' B A device communication module U 911 CCP 303 5 H1 H2 BB BB com Q Micrologic 311 XF CH I 811 shield Z5 Z4 Z3 Z2 Z1 V3 microswitch built into COM module OF V2 L2 V1 L1 VN N 4 BAT module 2 (1) H3 H4 1 (2) L3 L4 110/240 V AC 24/125 V DC blue white yellow brown black red E1 E2 E3 E4 + A B + / / E3 / E4 E5 / E6 Digipact junction block 0 G1 G2 AD module Modbus junction block CJB306 3 E5 E6 A' B' Modbus BB BB + Digipact twisted pair twisted pair 24 V 0V 0V 24 VDC 1A communication power supply 24 V 24 VDC DC 150 None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power-supply (AD module) is required for certain operating configurations as indicated in the table below. circuit breaker voltage measurement inputs M2C, M6C programmable contacts option Protection function Display function Time-stamping function Circuit-breaker status indications and control via communications bus Identification, settings, operation and maintenance aids via communications bus (1) draw-out device equipped with Modbus craddle COM. (2) draw-out device equipped with Digipact craddle COM. (3) except for Micrologic A control units (if current < 20% In). (4) except for Micrologic A control units. (5) time setting is manual and can be carried out automatically by the supervisor via the communications bus. closed powered open powered not powered yes no no (3) no no yes no no (4) no no yes no yes yes (5) no no (3) no (4) yes The communications bus requires its own 24 V DC power source (E1, E2). This source is not the same as the 24 V DC external power-supply module (F1-, F2+). In case of using the 24 VDC external power supply (AD module), maximum cable length between 24 VDC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters. The BAT battery module, mounted in series upstream of the AD module, ensures an uninterrupted supply of power if the AD module power supply fails. The voltage measurement inputs are standard equipment on the downstream connectors of the circuit breaker. External connections are possible using the PTE external voltage measurement input option. With this option, the internal voltage measurement inputs are disconnected and terminals VN, V1 and V2 are connected only to the control unit (Micrologic P and H only). The PTE option is required for voltages less than 100 V and greater than 690 V (in which case a voltage transformer is compulsory). For three-pole devices, the system is supplied with terminal VN connected only to the control unit (Micrologic P and H). When the PTE option is implemented, the voltage measurement input must be protected against short-circuits. Installed as close as possible to the busbars, this protection function is ensured by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117). This voltage measurement input is reserved exclusively for the control unit and must not ever be used to supply other circuits outside the switchboard. 86 Masterpact Schneider Electric Examples using the COM communications option Switchboard display unit CDM303 + CSD309 E47976 This architecture provides remote display of the variables managed by Micrologic control units equipped with the eco COM Modbus module. c I (Micrologic A) c I, U, P, E (Micrologic P) c I, U, P, E, THD (Micrologic H) No programming is required. For Micrologic A control unit (if current < 20% In), it is recommended to use the 24 VDC external power supply (AD module). d < 1 km DMB300 4 2 3 4 CCP303 5 1 I U P 3 ? 2 switchboard display unit 1 0 24 V 0V Modbus junction block CJB 306 24 VDC 1A power circuit breaker Communicating switchboard E47977 This configuration provides remote display and control of Masterpacts equipped with the Modbus or Digipact COM module. The Digipact bus can be combined with the Modbus bus. Software PC running PC running Micrologic utilities SMS Micrologic utilities SMS PLC PLC TCP/IP Communication interface RS 232C Ethernet RS 485 RS 485 Bus Modbus communication Bus Data concentrator Bus Modbus DC150 Device UA150 source change-ower SC150 contraf interface PM150 measure Masterpact COM Digipact Masterpact COM Modbus Digipact Bus PM300 measure Sepam Vigilohm Altivar Modbus Bus 87 Masterpact Schneider Electric Masterpact NT and NW Earth-fault and earth-leakage protection Neutral protection Zone selective interlocking Electrical diagrams External sensor (CT) for residual earth-fault protection Z4 Z5 Z3 T4 Z2 T3 Z1 V3 L3 V2 L2 VN L1 V1 N E47591B Q I Micrologic 6 F2+ F1 T2 T1 M3 M2 U M1 Connection of current-transformer secondary circuit for external neutral Masterpact equipped with a Micrologic 6 A/P/H: c shielded cable with 2 twisted pairs c SG1 twisted with SG2 c X1 twisted with X2 c shielding connected to GND on one end only c maximum length 5 meters c cable cross-sectional area 0.4 to 1.5 mm2 c recommended cable: Belden 9552 or equivalent. If supply is via the top, follow the shematics. If supply is via the bottom, control wiring is identical; for the power wiring, H1 is connected to the source side, H2 to the load side. For four-pole versions, for residual earth-fault protection, the current transformer for the external neutral is not necessary. If the 2000/6300 current transformer is used: c signals SG1 and SG2 must be wired in series c signals X1 and X2 must be wired in parallel. Connection for signal VN is required only for power measurements (3 Ø, 4 wires, 4CTs). VN H2 SG1 SG2 X1 X2 H1 GND Z4 T4 Z5 Z3 T3 Z2 Z1 V3 V2 VN Connection of the secondary circuit Masterpact equipped with a Micrologic 6 A/P/H: c unshielded cable with 1 twisted pair c maximum length 150 meters c cable cross-sectional area 0.4 to 1.5 mm2 c terminals 5 and 6 may not be used at the same time c use terminal 5 for NW08 to 40 c use terminal 6 for NW40b to 63 c recommended cable: Belden 9409 or equivalent. V1 External transformer for source ground return (SGR) earth-fault protection Q I Micrologic 6 F2+ 7 F1 T1 6 T2 M3 M2 M1 U or E47592 H1 88 H2 X1 12 5 1 3 X2 MDGF module 13 14 10 11 9 8 PE Masterpact Schneider Electric Earth-leakage protection Z4 Z5 Z3 T4 Z2 T3 Z1 V3 L3 V2 L2 VN L1 V1 N E47974B Connection of the rectangular-sensor secondary circuit Masterpact equipped with a Micrologic 7 A/P/H: c unshielded cable with 3 twisted conductors: v M1, M2, M3 twisted together c maximum length 4 metres c cable cross-sectional area 0.4 to 1.5 mm2 c recommended cable: Belden 9493 or equivalent. Q I Micrologic 7 F2+ F1 T2 T1 M3 M2 M1 U M1 M2 M3 Neutral protection c Three pole breaker: v Masterpact equipped with Micrologic P or H v the current transformer for external neutral is necessary (the wiring diagram is identical to the one used for the residual earth-fault protection). c Four pole breaker: v Masterpact equipped with Micrologic A, P or H v the current transformer for external neutral is not necessary. A pilot wire interconnects a number of circuit breakers equipped with Micrologic A/P/H control units, as illustrated in the diagram above. The control unit detecting a fault sends a signal upstream and checks for a signal arriving from downstream. If there is a signal from downstream, the circuit breaker remains closed for the full duration of its tripping delay. If there is no signal from downstream, the circuit breaker opens immediately, whatever the tripping-delay setting. Fault 1. Only circuit breaker A detects the fault. Because it receives no signal from downstream, it immediately opens in spite of its tripping delay set to 0.3. Fault 2. Circuit breakers A and B detect the fault. Circuit breaker A receives a signal from B and remains closed for the full duration of its tripping delay set to 0.3. Circuit breaker B does not receive a signal from downstream and opens immediately, in spite of its tripping delay set to 0.2. E47975B Zone selective interlocking upstream circuit breaker A Z1 Z2 Z3 Z4 Z5 tsd = 0,3 fault 1 B Z1 Z2 Z3 Z4 Z5 tsd = 0,2 fault 2 Z1 Z2 Z3 Z4 Z5 Note: the maximum permissible distance between two devices is 3000 m and the maximum number of devices is 100. 89 Masterpact downstream circuit breaker Z1 Z2 Z3 Z4 Z5 Schneider Electric 90 Masterpact Schneider Electric Installation recommendations Masterpact Presentation Functions and characteristics Dimensions and connection Electrical diagrams 1 9 53 81 Operating conditions Installation in switchboard Door interlock catch Cable-type door interlock Connection of MN, MX and XF voltage releases Power connection Recommended busbars drilling Busbar sizing Temperature derating Power dissipation and input/output resistance Derating in switchboards Substitution kit Additional characteristics References 91 Masterpact 92 94 96 97 97 98 100 102 104 104 105 112 115 121 Schneider Electric Operating conditions Installation recommendations E51260B Ambient temperature Masterpact devices can operate under the following temperature conditions: c the electrical and mechanical characteristics are stipulated for an ambient temperature of -5° C to +70° C; c circuit-breaker closing is guaranteed down to -35° C; Storage conditions are as follows: c -40 to +85°C for a Masterpact device without its control unit c -25°C to +85°C for the control unit. E51261B Test Extreme atmospheric conditions Masterpact devices have successfully passed the tests defined by the following standards for extreme atmospheric conditions: c IEC 68-2-1: dry cold at -55° C; c IEC 68-2-2: dry heat at +85° C; c IEC 68-2-30: damp heat (temperature +55° C, relative humidity 95%); c IEC 68-2-52 level 2: salt mist. Masterpact devices can operate in the industrial environments defined by standard IEC 947 (pollution degree up to 4). It is nonetheless advised to check that the devices are installed in suitably cooled switchboards without excessive dust. Test Vibrations E51262B Masterpact devices are guaranteed against electromagnetic or mechanical vibrations. Tests are carried out in compliance with standard IEC 68-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyd’s, etc.): c 2 to 13.2 Hz: amplitude ±1 mm; c 13.2 to 100 Hz: constant acceleration 0.7 g. Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts. Test 92 Masterpact Schneider Electric E51263B Altitude 2000 m At altitudes higher than 2000 metres, the modifications in the ambient air (electrical resistance, cooling capacity) lower the following characteristics as follows: E51264B Test Altitude (m) Dielectric resistance voltage (V) Average insulation level (V) Maximum utilisation voltage (V) Average thermal current (A) at 40 °C 2000 3500 3000 3150 4000 2500 5000 2100 1000 900 700 600 690 590 520 460 1 x In 0.99 x In 0.96 x In 0.94 x In Electromagnetic disturbances Test Masterpact devices are protected against: c overvoltages caused by devices that generate electromagnetic disturbances; c overvoltages caused by atmospheric disturbances or by a distribution-system outage (e.g. failure of a lighting system); c devices emitting radio waves (radios, walkie-talkies, radar, etc.); c electrostatic discharges produced by users. Masterpact devices have successfully passed the electromagnetic-compatibility tests (EMC) defined by the following international standards: c IEC 60947-2, appendix F; c IEC 60947-2, appendix B (trip units with earth-leakage function). The above tests guarantee that: c no nuisance tripping occurs; c tripping times are respected. 93 Masterpact Schneider Electric Installation in switchboard Installation recommendations E47652A E47651A E47650A Possible positions Power supply E47653A Masterpact devices can be supplied either from the top or from the bottom without reduction in performance, in order to facilitate connection when installed in a switchboard. Mounting the circuit-breaker E47656A E47657A It is important to distribute the weight of the device uniformily over a rigid mounting surface such as rails or a base plate. This mounting plane should be perfectly flat (tolerance on support flatness: 2 mm). This eliminates any risk of deformation which could interfere with correct operation of the circuit breaker. Masterpact devices can also be mounted on a vertical plane using the special brackets. E47658A Mounting on rails. Mounting with vertical brackets. 94 Masterpact Schneider Electric E47659A Partitions Sufficient openings must be provided in partitions to ensure good air circulation around the circuit breaker; For high currents, of 2500 A and upwards, the metal supports or barriers in the immediate vicinity of a conductor must be made of non-magnetic material A; Metal barriers through which a conductor passes must not form a magnetic loop. a A a E47661A E47660A A : non magnetic material Busbars non magnetic material E47662B The mechanical connection must be exclude the possibility of formation of a magnetic loop around a conductor. E47663A Increases the length of the tracking path between phases; Reduces the risk of short circuits being caused by objects falling from above onto circuit breaker connections. E47664 Interphase barrier 351 (NT) 453 (NW) F Dimensions and weights Main dimensions in mm (H x W x D) Masterpact drawout fixed 3P 4P 3P 4P NT06/12 322 x 288 x 280 322 x 358 x 280 301 x 276 x 211 301 x 346 x 211 NW08/40 439 x 441 x 395 439 x 556 x 395 352 x 422 x 297 352 x 537 x 297 NW40b/63 479 x 786 x 395 479 x 1016 x 395 352 x 767 x 297 352 x 997 x 297 3P 4P 3P 4P NT06/12 30 39 14 18 NW08/40 90 120 60 80 NW40b/63 225 300 120 160 Weight (kg) Masterpact drawout fixed 95 Masterpact Schneider Electric Door interlock catch Mounted on the right or left-hand side of the craddle, this device inhibits opening of the cubicle door when the circuit breaker is in «connected» or «test» position. It the breaker is put in the «connected» position with the door open, the door may be closed without having to disconnect the circuit breaker. E47669B Installation recommendations Y X 15 (1) 8 (2) Catch not supplied 17 5 Dimensions (mm) Type NT08-16 (3P) NT08-16 (4P) NW08-40 (3P) NW08-40 (4P) NW40b-63 (3P) NW40b-63 (4P) (1) 135 205 215 330 660 775 (2) 168 168 215 215 215 215 Breaker in “connected” or “test” position E47670A Door cannot be opened door Dimensions (mm) F (1) (2) Type NT NW (1) 5 83 (2) 23 103 Breaker in “disconnected” position E47671A Door can be opened Note: The door interlock can either be mounted on the right side or the left side of the breaker. F Datum. 96 Masterpact Schneider Electric Cable-type door interlock Connection of MN, MX and XF voltage releases NT/NW Cable-type door interlock E59115A E59113A This option prevents door opening when the circuit breaker is closed and prevents circuit breaker closing when the door is open. For this, a special plate associated with a lock and a cable is mounted on the right side of the circuit breaker. With this interlock installed, the source changeover function cannot be implemented. E59114B 46 121 165 10 79 84 52 Wiring of voltage releases During pick-up, the power consumed is approximately 150 to 200 VA. For low control voltages (12, 24, 48 V), maximum cable lengths are imposed by the voltage and the cross-sectional area of cables. Recommanded maximum cable lengths (meter) 12 V 2,5 mm2 MN U source 100 % – U source 85 % – MX-XF U source 100 % 21 U source 85 % 10 24 V 1,5 mm2 – – 12 6 2,5 mm2 58 16 115 75 48 V 1,5 mm2 35 10 70 44 2,5 mm2 280 75 550 350 1,5 mm2 165 45 330 210 Note: the indicated length is that of each of the two wires 97 Masterpact Schneider Electric E47676A B C aa If cables are used for the power connections, make sure that they do not apply excessive mechanical forces to the circuit breaker terminals. For this, make the connections as follows: c extend the circuit breaker terminals using short bars designed and installed according to the recommendations for bar-type power connections: v for a single cable, use solution B opposite v for multiple cables, use solution C opposite. c in all cases, follow the general rules for connections to busbars: v position the cable lugs before inserting the bolts v the cables should firmly secured to the framework of the switchboard. E47675A Cables connections a Power connection Installation recommendations B C E47673A E47677A E47672A The busbars should be suitably adjusted to ensure that the connection points are positioned on the terminals before the bolts are inserted B The connections are held by the support which is solidly fixed to the framework of the switchboard, such that the circuit breaker terminals do not have to support its weight C. (This support should be placed close to the terminals). A E47674A Busbars connections E E B Electrodynamic stresses The first busbar support or spacer shall be situated within a maximum distance from the connection point of the breaker (see table below). This distance must be respected so that the connection can withstand the electrodynamic stresses between phases in the event of a short circuit. Maximum distance A between busbar to circuit breaker connection and the first busbar support or spacer with respect to the value of the prospective short-circuit current. Isc (kA) 30 50 65 80 100 150 distance A (mm) 350 300 250 150 150 150 98 Masterpact Schneider Electric 2 3 4 Clamping Correct clamping of busbars depends amongst other things, on the tightening torques used for the nuts and bolts. Over-tightening may have the same consequences as under-tightening. For connecting busbars (Cu ETP-NFA51-100) to the circuit breaker, the tightening torques to be used are shown in the table below. These values are for use with copper busbars and steel nuts and bolts, class 8.8. The same torques can be used with AGS-T52 quality aluminium bars (French standard NFA 02-104 or American National Standard H-35-1). 5 E47665 E47667B E47668 Examples 6 1 terminal screw factory-tightened to 16 Nm (NW), 13 Nm (NT) 2 breaker terminal 3 busbar 4 bolt 5 washer 6 nut Tightening torques Ø Ø nominal (mm) drilling (mm) 10 11 tightening torque (Nm) with grower or flat washers with contact or corrugatec washers 37.5 50 E47331A E47330A E47329A Busbar drilling Examples E47680A Isolation distance X Dimensions (mm) Ui 600 V 1000 V X min 8 mm 14 mm Busbar bending When bending busbars maintain the radius indicated below(a smaller radius would cause cracks). E47679A E47678A 1 r e Dimensions (mm) e 5 10 99 radius of curvature r min recommended 5 15 7.5 18 to 20 Masterpact Schneider Electric Recommended busbars drilling Masterpact NT06 to NT16 Installation recommendations 12,5 12,5 25 38,5 25 9,5 12,5 = 13,5 25 25 12,5 38,5 = 25 13,5 82 52 38,5 = 25 13,5 5 Ø11 15 5 Ø11 5 Ø11 25 25 13,5 = 30 82 52 15 2 Ø11 25 25 52 52 38,5 = 25 30 82 52 15 77 = 30 82 52 15 5 Ø11 Left or right spreader for 3P 77 = 30 60 12,5 12,5 Left or right spreader for 4P 77 = 15 Ø12 maxi Middle spreader for 3P E59326A E59325A E59324A 25 77 80 15 12,5 Ø12 maxi 12,5 Middle left or middle right spreader for 4P 44 E59310A 25,5 12,5 Ø12 maxi 25 63 E59328A 25 50 E59327A 12,5 Ø12 maxi E59309A 50 12,5 Rear connection with spreaders E59308A E59308A Rear connection 52 52 Ø12 maxi 25 E59329A 12,5 Ø12 maxi 25 12,5 50 12,5 Ø12 maxi 25 12,5 12,5 E59315 A 40 E59314A 32 E59313A E59312A E59311A Vertical rear connection 63 Ø12 maxi 25 12,5 80 Ø12 maxi 25 12,5 12,5 12,5 12,5 60 12,5 9,5 12,5 25 44 2 Ø11 12,5 12,5 Ø12 maxi 25 12,5 25 Bottom connection 25 9,5 E59331A 44 25 12,5 Ø12 maxi 12,5 Top connection E59330A 50 2 Ø11 89 = = 63 25,5 80 15 15 12,5 Ø12 maxi 25 12,5 E59310A 50 E59309A E59308A Front connection via vertical connection adapters E59332A E59308A Front connection 12,5 Ø12 maxi 25 25 12,5 12,5 15 21 13 101 21 3 Ø11 13 2 Ø11 15 25 44 20 9,5 100 Masterpact Schneider Electric Masterpact NW08 to NW63 12,5 12,5 Ø12 maxi E59333A 25 25,5 80 15 15 12,5 Ø12 maxi 12,5 25 25 25 12,5 100 28 22 Ø12 maxi 12,5 25 25 E59323A 13 = = 25 28 Ø12 maxi 76 38 100 22 E59317A 63 NW40b to NW50 E59316A 50 E59310A E59309A E59308A Horizontal rear connection NW08 to NW38 Ø12 maxi 25 25 12,5 12,5 115 115 115 115 115 39 39 39 39 39 12,5 47 3 Ø11,5 14,5 Y 25 12,5 Ø12 maxi 25 12,5 12,5 12,5 12,5 100 25 25 Ø12 maxi 25 12,5 80 E59322A 63 25 25 Ø12 maxi 25 E59334A 50 E59321A E59319A E59318A 40 E59320A Vertical rear connection NW08 to NW32, NW40b to NW50 Ø12 maxi 25 12,5 12,5 Ø12 maxi 25 12,5 12,5 47 14,5 12,5 13 = 76 = 3 Ø11,5 38 25 50 12,5 12,5 Ø12 maxi 25 12,5 80 15 15 12,5 Ø12 maxi 25 Ø12 maxi 25 25 12,5 12,5 Bottom connection 76 25 25 13 12,5 E59336A E59335A 63 25,5 Top connection E59310A E59309A E59308A Front connection NW08 to NW32 3 Ø11,5 3 Ø11,5 12,5 25 25 13 101 Masterpact Schneider Electric Busbar sizing Installation recommendations Basis of tables: c maximum permissible busbars temperature: 100 °C c Ti: temperature around the circuit breaker and its connection c busbar material is unpainted copper. E47681A Front or rear horizontal connection maximum service current Ti : 40 °C no. of 5 mm thick bars NT06 NT06 NT08 or NW08 NT10 or NW10 NT12 or NW12 400 630 800 1000 1250 NT16 or NW16 NT16 or NW16 NW20 NW20 NW25 NW25 NW32 NW32 NW32 NW40 NW40 NW50 NW50 1400 1600 1800 2000 2200 2500 2800 3000 3200 3800 4000 4500 5000 2b.30 x 5 2b.40 x 5 2b.50 x 5 3b.50 x 5 3b.50 x 5 2b.80 x 5 3b.50 x 5 3b.63 x 5 3b.80 x 5 3b.100 x 5 3b.100 x 5 4b.100 x 5 4b.100 x 5 5b.100 x 5 6b.100 x 5 Masterpact no. of 10 mm thick bars 1b.30 x 10 1b.40 x 10 1b.50 x 10 1b.63 x 10 2b.40 x 10 2b.40 x 10 2b.40 x 10 2b.50 x 10 2b.63 x 10 2b.80 x 10 2b.80 x 10 2b.100 x 10 3b.80 x 10 3b.80 x 10 3b.100 x 10 4b.100 x 10 5b.100 x 10 6b.100 x 10 7b.100 x 10 Ti : 50 °C no. of 5 mm thick bars 2b.30 x 5 2b.40 x 5 2b.50 x 5 3b.50 x 5 3b.50 x 5 2b.80 x 5 2b.80 x 5 3b.80 x 5 3b.80 x 5 3b.100 x 5 3b.100 x 5 4b.100 x 5 4b.100 x 5 6b.100 x 5 8b.100 x 5 no. of 10 mm thick bars Ti : 60 °C no. of 5 mm thick bars no. of 10 mm thick bars 1b.30 x 10 1b.40 x 10 1b.50 x 10 2b.50 x 10 2b.50 x 10 2b.30 x 5 2b.40 x 5 2b.50 x 5 3b.63 x 5 3b.63 x 5 1b.30 x 10 1b.40 x 10 1b.63 x 10 2b.50 x 10 2b.50 x 10 2b.50 x 10 2b.63 x 10 2b.63 x 10 2b.80 x 10 2b.80 x 10 2b.100 x 10 3b.80 x 10 3b.100 x 10 3b.100 x 10 5b.100 x 10 5b.100 x 10 6b.100 x 10 7b.100 x 10 3b.80 x 5 3b.80 x 5 3b.100 x 5 3b.100 x 5 4b.80 x 5 4b.100 x 5 5b.100 x 5 8b.100 x 5 2b.63 x 10 3b.50 x 10 2b.80 x 10 3b.63 x 10 2b.100 x 10 3b.80 x 10 3b.100 x 10 4b.80 x 10 4b.100 x 10 5b.100 x 10 6b.100 x 10 7b.100 x 10 With Masterpact NT, it is recommanded to use 50 mm wideness bars (see "Recommended busbars drilling") Example Conditions: c drawout version c horizontal busbars c Ti: 50 °C c service current: 1800 A. Solution: For Ti = 50 °C, use an NW20 which can be connected with three 80x5 mm bars or two mm 63x10 bars. Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 102 Masterpact Schneider Electric Basis of tables: c maximum permissible busbars temperature: 100 °C c Ti: temperature around the circuit breaker and its connection c busbar material is unpainted copper. E47682A Rear vertical connection Masterpact NT06 NT06 NT08 or NT10 or NT12 or NT16 or NT16 or NW08 NW10 NW12 NW16 NW16 NW20 NW20 NW25 NW25 NW32 NW32 NW32 NW40 NW40 NW50 NW50 NW63 NW63 Maximum service current Ti: 40 °C no. of 5 mm thick bars 400 630 800 1000 1250 1400 1600 1800 2000 2200 2500 2800 3000 3200 3800 4000 4500 5000 5700 6300 2b.30 x 5 2b.40 x 5 2b.50 x 5 2b.50 x 5 2b.63 x 5 2b.63 x 5 2b.80 x 5 2b.80 x 5 2b.100 x 5 2b.100 x 5 4b.80 x 5 4b.100 x 5 5b.100 x 5 6b.100 x 5 no. of 10 mm thick bars 1b.30 x 10 1b.40 x 10 1b.50 x 10 1b.50 x 10 1b.63 x 10 1b.63 x 10 1b.80 x 10 1b.80 x 10 2b.63 x 10 2b.63 x 10 2b.80 x 10 2b.100 x 10 3b.80 x 10 3b.100 x 10 4b.100 x 10 4b.100 x 10 5b.100 x 10 5b.100 x 10 7b.100 x 10 8b.100 x 10 Ti: 50 °C no. of 5 mm thick bars 2b.30 x 5 2b.40 x 5 2b.50 x 5 2b.50 x 5 2b.63 x 5 2b.63 x 5 2b.80 x 5 2b.80 x 5 2b.100 x 5 2b.100 x 5 4b.80 x 5 4b.100 x 5 6b.100 x 5 6b.100 x 5 no. of 10 mm thick bars 1b.30 x 10 1b.40 x 10 1b.50 x 10 1b.50 x 10 1b.63 x 10 1b.63 x 10 1b.80 x 10 2b.50 x 10 2b.63 x 10 2b.63 x 10 2b.80 x 10 2b.100 x 10 3b.100 x 10 3b.100 x 10 4b.100 x 10 4b.100 x 10 5b.100 x 10 6b.100 x 10 7b.100 x 10 8b.100 x 10 Ti: 60 °C no. of 5 mm thick bars 2b.30 x 5 2b.40 x 5 2b.50 x 5 2b.63 x 5 3b.50 x 5 3b.50 x 5 3b.63 x 5 3b.80 x 5 3b.100 x 5 3b.100 x 5 4b.100 x 5 4b.100 x 5 5b.100 x 5 no. of 10 mm thick bars 1b.30 x 10 1b.40 x 10 1b.50 x 10 1b.63 x 10 2b.50 x 10 2b.50 x 10 2b.50 x 10 2b.63 x 10 2b.80 x 10 2b.80 x 10 3b.80 x 10 3b.80 x 10 4b.80 x 10 4b.100 x 10 4b.100 x 10 4b.100 x 10 6b.100 x 10 7b.100 x 10 8b.100 x 10 Example Conditions: c drawout version c vertical connections c Ti: 40 °C c service current: 1100 A. Solution : For Ti = 40 °C use an NT12 or NW12 which can be connected with two 63 x 5 mm bars or with one 63 x 10 mm bar. Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 103 Masterpact Schneider Electric Temperature derating Installation recommendations Temperature derating The table below indicates the maximum current rating, for each connection type, as a function of the ambient temperature around the circuit breaker and the busbars. Circuit breakers with mixed connections have the same derating as horizontally connected breakers. For ambient temperatures greater than 60 °C, consult us. Ti: temperature around the circuit breaker and its connection version drawout connection front or rear horizontal temp. Ti 40 45 fixed 50 55 rear vertical 60 40 45 front or rear horizontal 50 55 60 40 45 NT06 H1/L1 NT08 H1/L1 NT10 H1/L1 NT12 H1 NT16 H1 630 800 1000 1250 1600 630 800 1000 1250 1520 1480 1430 1600 NW08 N/H/L NW10 N/H/L NW12 N/H/L NW16 N/H/L NW20 H1/H2/H3 NW20 L1 NW25 H1/H2/H3 NW32 H1/H2/H3 NW40 H1/H2/H3 800 1000 1250 1600 2000 2000 2500 3200 4000 3100 3000 2900 3900 3750 3650 800 1000 1250 1600 2000 2000 2500 3200 4000 800 1000 1250 1600 2000 – – 2500 3200 3850 4000 NW40b H1/H2 NW50 H1/H2 NW63 H1/H2 4000 5000 – – – 4000 5000 6300 4000 5000 6200 – – 1980 1890 1900 1850 1800 – – 50 55 630 800 1000 1250 1560 1510 1600 rear vertical 60 40 45 50 55 60 – – – 630 800 1000 1250 1550 1600 – – 800 1000 1250 1600 1920 2000 – – – – 2500 3200 3900 3800 4000 – – 4000 5000 6300 Power dissipation and input / output resistance Total power dissipation is the value measured at IN, 50/60 Hz, for a 3 pole or 4 pole breaker (values above the power P = 3RI2). The resistance between input / output is the value measured per pole (cold state). version NT06 H1/L1 NT08 H1/L1 NT10 H1/L1 NT12 H1 NT16 H1 NW08 N1 NW08 H/L NW10 N1 NW10 H/L NW12 N1 NW12 H/L NW16 N1 NW16 H/L NW20 H/L NW25 H1/H2/H3 NW32 H1/H2/H3 NW40 H1/H2/H3 NW40b H1/H2 NW50 H1/H2 NW63 H1/H2 drawout fixed power dissipation (Watts) input/output resistance (µohm) power dissipation (Watts) input/ouput resistance (µohm) 55/115 (H1/L1) 90/140 (H1/L1) 150/230 (H1/L1) 250 460 137 100 220 150 330 230 480 390 470 600 670 900 550 590 950 38/72 38/72 38/72 36 36 42 30 42 30 42 27 37 27 27 19 13 11 7 7 7 30/45 50/80 80/110 130 220 62 42 100 70 150 100 220 170 250 260 420 650 390 420 660 26/39 26/39 26/39 26 26 19 13 19 13 19 13 19 13 13 8 8 8 5 5 5 104 Masterpact Schneider Electric Derating in switchboard Factors affecting switchboard design Basis of tables The temperature around the circuit breaker and its connections: This is used to define the type of circuit breaker to be used and its connection arrangement. Vents at the top and bottom of the cubicles: Vents considerably reduce the temperature inside the switchboard, but must be designed so as to respect the degree of protection provided by the enclosure. For weatherproof heavy-duty cubicles, a forced ventilation system may be required. The heat dissipated by the devices installed in the switchboard: This is the heat dissipated by the circuit breakers under normal conditions (service current). The size of the enclosure: This determines the volume for cooling calculations. Switchboard installation mode: Free-standing, against a wall, etc. Horizontal partitions: Partitions can obstruct air circulation within the enclosure. c switchboard dimensions c number of circuit-breakers installed c type of breaker connections c drawout versions c ambient temperature outside of the switchboard: Ta (IEC 60439-1). Masterpact NT06-16 H1/L1 (switchboard 2000 x 400 x 400 mm) Type NT06 H1/L1 NT08 H1/L1 NT10 H1/L1 NT12 H1 NT16 H1 2b. 40x5 2b. 50x5 3b. 63x5 3b. 63x5 1250 1250 1400 1520 Switchboard composition 4 3 2 1 Connection type E47710A Busbar dimensions (mm) 4 Ventilated switchboard (➞ IP31) 3 Ta = 35°C 2 1 4 3 Ta = 45°C 2000 2 1 4 3 Ta = 55°C 2 1 3b. 80x5 3b. 63x5 630 630 800 800 2b. 63x5 H1/L1 H1/L1 1000/1000 1000/1000 630 630 800 800 1000/950 1000/1000 1250 1250 1330 1440 630 630 800 800 1000/890 1000/960 1200 1250 1250 1340 630 630 800 800 1000/960 1000/1000 1250 1250 1330 1400 630 630 800 800 1000/910 1000/980 1220 1250 1260 1330 630 630 800 800 1000/860 1000/930 1150 1230 1200 1260 3b. 50x5 400 400 4 3 2 Ta = 35°C 1 4 3 Ta = 45°C 2 1 4 3 Ta = 55°C 2 1 E47709A Non ventilated switchboard (➞ IP54) 2000 400 400 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 105 Masterpact Schneider Electric Derating in switchboards Installation recommendations Masterpact NT06-08 H1/L1 (switchboard 2300 x 1100 x 500 mm) Type Switchboard composition NT06 H1/L1 NT08 H1/L1 2b. 40x5 2b. 50x5 5 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard (➞ IP31) E47712B Ta = 35°C 2300 Ta = 45°C 200 300 600 Ta = 55°C 500 Non ventilated switchboard (➞ IP54) E47711B Ta = 35°C 2300 Ta = 45°C 200 300 500 600 Ta = 55°C 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 106 Masterpact Schneider Electric Masterpact NT10-16 H1/L1 (switchboard 2300 x 1100 x 500 mm) Type Switchboard composition NT10 H1/L1 NT12 H1 NT16 H1 3b. 63x5 3b. 63x5 3b. 80x5 5 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard (➞ IP31) E47712B Ta = 35°C 2300 Ta = 45°C 200 300 600 Ta = 55°C 500 Non ventilated switchboard (➞ IP54) E47711B Ta = 35°C 2300 Ta = 45°C Ta = 55°C 200 300 5 4 3 2 1 5 4 3 2 1 5 4 3 2 1 5 4 3 2 5 4 3 2 5 4 3 2 H1/L1 2b. 63x5 H1/L1 H1/L1 3b. 63x5 3b. 50x5 H1/L1 1000/1000 1000/1000 1000/1000 1000/1000 1000/1000 1000/1000 1000/1000 1000/1000 1000/1000 1000/1000 1000/960 1000/1000 1000/1000 1000/1000 1000/920 1000/950 1000/930 1000/900 1000/1000 1000/970 1000/950 1000/950 1000/1000 1000/960 1000/1000 1000/1000 1000/1000 1000/970 1000/900 1000/950 1000/910 1000/950 1000/1000 1000/960 1000/930 1000/850 1000/900 1000/860 1000/880 1000/970 1000/910 1000/870 1250 1250 1250 1250 1250 1210 1250 1250 1250 1250 1250 1250 1460 1600 1500 1550 1250 1250 1250 1250 1250 1250 1400 1500 1420 1480 1250 1250 1250 1250 1250 1250 1300 1400 1330 1370 1250 1250 1250 1250 1250 1250 1400 1500 1370 1400 1250 1250 1250 1180 1190 1220 1350 1430 1300 1320 1250 1200 1210 1120 1130 1150 1250 1350 1210 1250 600 500 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 107 Masterpact Schneider Electric Derating in switchboards Installation recommendations Masterpact NW08-10 N/H/L (switchboard 2300 x 800x 900 mm) Type NW08 N/H/L NW10 N/H/L 2b. 50x5 3b. 63x5 Switchboard composition 4 3 2 1 Connection type Busbar dimensions (mm) 2b. 63x5 Ventilated switchboard (➞ IP31) E47714A Ta = 35°C 2300 Ta = 45°C Ta = 55°C 900 800 Non ventilated switchboard (➞ IP54) E47713A Ta = 35°C 2300 Ta = 45°C Ta = 55°C 900 800 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 Note The values indicated in these tables have been extrapolated from test data arnd theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 108 Masterpact Schneider Electric Masterpact NW12-16 N/H/L (switchboard 2300 x 800 x 900 mm) Type NW12 N1 NW12 H/L NW16 N1 NW16 H/L 3b. 63x5 3b. 50x5 3b. 63x5 3b. 50x5 3b. 80x5 3b. 63x5 3b. 80x5 3b. 63x5 Switchboard composition 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard (➞ IP31) E47714A Ta = 35°C 2300 Ta = 45°C Ta = 55°C 900 800 Non ventilated switchboard (➞ IP54) E47713A Ta = 35°C 2300 Ta = 45°C Ta = 55°C 900 800 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 1250 1250 1200 1250 1200 1130 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1240 1250 1250 1250 1210 1250 1170 1210 1250 1200 1140 1200 1100 1170 1200 1250 1250 1250 1250 1250 1250 1250 1550 1600 1600 1600 1600 1600 1600 1600 1250 1250 1250 1250 1250 1250 1250 1470 1600 1500 1600 1600 1600 1600 1600 1250 1250 1250 1250 1250 1250 1250 1380 1500 1380 1500 1520 1600 1470 1600 1250 1250 1250 1250 1250 1250 1250 1440 1550 1425 1550 1600 1600 1600 1600 1250 1250 1250 1250 1250 1250 1250 1360 1470 1360 1470 1500 1600 1500 1600 1250 1250 1250 1250 1250 1250 1250 1280 1380 1280 1380 1400 1520 1400 1520 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 109 Masterpact Schneider Electric Derating in switchboards Installation recommendations Masterpact NW20-40 N/H/L (switchboard 2300 x 800 x 900 mm) Type NW20 H1/H2/H3 NW20 L1 NW25 H1/2/3 NW32 H1/2/3 NW40 H1/2/3 3b. 100x5 3b. 100x5 4b. 100x5 3b. 100x10 4b. 100x10 Switchboard composition 4 3 2 1 Connection type Busbar dimensions (mm) Ventilated switchboard (➞ IP31) E47714A Ta = 35°C 2300 Ta = 45°C Ta = 55°C 900 800 Non ventilated switchboard (➞ IP54) E47713A Ta = 35°C 2300 Ta = 45°C Ta = 55°C 900 800 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 2000 2000 2000 2000 2000 2000 1830 2000 2375 2500 3040 3200 3320 3700 2000 2000 2000 2000 1810 1960 1750 1920 2250 2380 2880 3100 3160 3500 2000 2000 1880 2000 1700 1850 1640 1800 2100 2250 2690 2900 2960 3280 2000 2000 2000 2000 1800 1900 1750 1890 2125 2275 2650 2850 3040 3320 1900 1960 1900 1960 1680 1810 1660 1800 2000 2150 2550 2700 2880 3120 1800 1920 1780 1920 1590 1700 1550 1700 1900 2020 2370 2530 2720 2960 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 110 Masterpact Schneider Electric Masterpact NW40b-63 H1/H2 (switchboard 2300 x 1400 x 1500 mm) Type NW40b H1/H2 NW50 H1/H2 NW63 H1/H2 5b. 100x10 7b. 100x10 8b. 100x10 4000 4000 4700 5000 6050 4000 4000 4450 4850 5670 4000 4000 4200 4600 5350 4000 4000 4350 4650 5290 4000 4000 4100 4400 5040 3840 3840 3850 4150 4730 Switchboard composition 4 3 2 1 Connection type Busbar dimensions Ventilated switchboard (➞ IP31) E47716B Ta = 35°C Ta = 45°C 2300 Ta = 55°C 4 3 2 1 4 3 2 1 4 3 2 1 1500 1400 Non ventilated switchboard (➞ IP54) E47715B Ta = 35°C Ta = 45°C 2300 Ta = 55°C 4 3 2 1 4 3 2 1 4 3 2 1 1500 1400 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 111 Masterpact Schneider Electric Substitution kit Fixed / drawout devices 800 to 3200 A Installation recommendations It is possible to replace a Masterpact (M08 to M32) with a new Masterpact (NW08 to NW32) with the same power rating. Substitution is possible for the following types of circuit breakers: c N1, H1, H2 for both fixed and drawout versions c L1 for drawout versions up to 2000 A. Mounting diagram Fixed version Drawout version Y 2Ø9,5 X 25 E59219A E59218B Y Ø14 2 Ø11,5 x 22 124 162 150 Ø9,5 Ø14 4 Ø6,5 Ø11,5 10 110 2Ø11 X 6 175 Ø11 200 (3P) 315 (4P) Ø10,5 Ø11 F 2 Ø11 X 6 200 167,5 (3P) 282,5 (4P) 267,5 (4P) : Masterpact NW : Masterpact M F 162,5 Fixing points are identical for Masterpact (M08 to M32) and Masterpact (NW08 to NW32), except for the four-pole craddle. Door cut-out c without an escutcheon, the cut-out is identical (270 x 325 mm). c with the former escutcheon, the cut-out is identical (270 x 325 mm). c with the new escutcheon, the cut-out is different. Drawout version 295 mini (3P) 410 mini (4P) 300 mini (3P) 415 mini (4P) E59221A E59220A Fixed version 295 mini 300 mini Y Y 270 (1) 379 (2) 270 (1) 316 (2) 135 (1) 158 (2) X 325 (1) 364 (2) X 135 (1) 222 (2) 153,3 (1) 162,5 (1) 182 (2) 325 (1) 364 (2) 162,5 (1) 182 (2) 47 (1) Power connections Select a set of retrofit connectors to replace the standard connectors and avoid any modifications to the busbars (see the retrofit section in "orders and quotations") Note: (1) Without escutcheon (2) With escutcheon References X and Y represent the symmetry planes for three-pole devices 112 Masterpact Schneider Electric E59217A NW08 to NW32 M08 to M32 Electrical diagrams Correspondences between Masterpact NW and Masterpact M terminal blocks AT BPF B4 262 B2 B3 C2 C2 254 C12 C12 252 D4 D2 A4 84 84 C3 82 82 K2 Q3 184 BPO 182 Z5 Q2 Z21 Z21 Z4 Q1 Z22 Z3 484 Z11 Z2 474 Z12 Z1 V3 V2 V1 equivalent functions using M2C or M6C VN charged ALR, V, MR6, R options L3 254 L2 252 L1 A3 N A2 power ready to close Remote operation fault Control unit fault E59222A Power MCH Q I SDE1 SDE2 S1 S2 Micrologic U MN MX1 MX2 XF PF CH Res A1 251 B1 251 B1 C11 C11 A1 D1 D1 C1 81 K1 181 F2+ F2+ 471 F1 T4 F1 X2 X1 T3 T2 T1 SG2 SG1 M3 M2 M1 or (1) or or C1 M6C 81 M2C 24 V DC Craddle contacts 372 374 914 912 922 924 932 312 934 314 314 322 324 312 324 332 334 Test 322 334 354 332 352 814 364 824 connected 812 362 822 disconnected 832 ..4 ..4 ..6 ..2 ..2 12 14 12 connected and closed 834 not connected or connected and open closed 14 22 24 22 24 32 34 32 closed 34 42 44 42 44 open ..8 E59223A Indication contacts EF . . OF4 OF3 OF2 OF1 OF . . OF CT3 CD3 CD2 CD1 CE3 CE2 CT2 CT1 CE1 or 911 311 311 371 321 321 921 331 331 931 811 351 ..1 ..1 821 11 11 New or additional functions 361 21 21 Identical to Masterpact M 831 31 31 ..5 41 41 CE Different than Masterpact M (1) The current transformer for the external neutral must be replaced 113 Masterpact Schneider Electric 114 Masterpact Schneider Electric Additional characteristics Masterpact Presentation Functions and characteristics Dimensions and connection Electrical diagrams Installation recommendations Tripping curves Limitation curves References 115 Masterpact 1 9 53 81 91 116 118 121 Schneider Electric Tripping curves Additional characteristics E46350 Micrologic 2.0 10 000 5 000 Ir = 0,4…1 x In 2 000 1 000 500 200 100 tr = 0,5...24 s 50 20 10 5 t(s) 2 Isd = 1,5…10 x Ir 1 .5 .2 .1 .05 .02 .01 .005 .002 .001 .5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 I / Ir Micrologic 5.0, 6.0, 7.0 E46276 10 000 5 000 Ir = 0,4…1 x In 2 000 1 000 500 200 100 tr = 0,5…24 s 50 20 10 5 t(s) Isd = 1,5…10 x Ir 2 1 I2t ON .5 .2 0,4 0,3 0,3 0,2 0,2 0,1 .1 .05 .02 .01 0,4 I2t OFF 0 0,1 0 Ii = 2…15 x In . OFF .005 .002 .001 .5 .7 1 2 3 4 5 7 10 x Ir 116 Masterpact 20 3 5 7 10 20 30 x In Schneider Electric Earth-fault protection (Micrologic 6.0) E46266 10 000 5 000 2 000 Ig = A…J x In (1) 1200 A max. 1 000 500 200 100 50 20 10 5 t(s) I2t ON 2 1 .5 .2 I2 t .1 .05 0.4 0.4 0.3 0.2 0.1 0.3 0.2 0.1 OFF 0 0 .02 .01 .005 .002 .001 .05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300 I / In (1) Ig = In x… Ig < 400 A 400 A i Ig i 1200 A Ig > 1200 A A B C D E F G 0,3 0,2 500 0,3 0,3 640 0,4 0,4 720 0,5 0,5 800 0,6 0,6 880 0,7 0,7 960 0,8 0,9 1 0,8 0,9 1 1040 1120 1200 H J E47587 IDMTL curve (Micrologic P and H) 100 000 HVF 10 000 5 000 2 000 1 000 EIT 500 t(s) 200 100 VIT 50 SIT 20 10 DT 5 2 1 .5 .5 .7 1 2 3 4 5 7 10 20 I / Ir 117 Masterpact Schneider Electric Limitation curves Current limiting Additional characteristics Voltage 380/415 V AC E47519 300 Masterpact NW H3 200 Masterpact NW L1 k 100 80 70 60 50 Masterpact NT L1 40 30 20 10 20 30 40 60 100 200 kA rms E47520 Voltage 660/690 V AC 300 Masterpact NW H3 200 Masterpact NW L1 k 100 80 70 60 50 Masterpact NT L1 40 30 20 10 20 30 40 60 100 200 kA rms 118 Masterpact Schneider Electric Energy limiting Voltage 380/415 V AC E47521 10 9 5 3 Masterpact NW H3 2 10 8 Masterpact NW L1 5 2 As 3 2 10 7 Masterpact NT L1 5 3 2 10 6 10 20 30 40 60 100 150 200 300 kA rms Voltage 660/690 V AC 9 E47522 10 5 Masterpact NW H3 3 2 8 10 Masterpact NW L1 5 2 As 3 2 7 10 Masterpact NT L1 5 3 2 6 10 10 20 30 40 60 100 150 200 300 kA rms 119 Masterpact Schneider Electric 120 Masterpact Schneider Electric Masterpact References Presentation Functions and characteristics Dimensions and connection Electrical diagrams Installation recommendations Additional characteristics 1 9 53 81 91 121 Accessories for communication Bus Order form NT06 to NT16 fixed circuit breakers 122 123 Circuit breaker selection Indication contacts Remote operation 124 126 127 NT06 to NT16 drawout circuit breakers 128 Circuit breaker selection Chassis locking and accessories Indication contacts Remote operation 128 130 131 132 Accessories for NT06 to NT16 fixed and drawout circuit breakers NT06 to NT16 fixed switch-disconnectors 133 Circuit breaker selection 136 NT06 to NT16 drawout switch-disconnectors Circuit breaker selection 138 NW08 to NW63 fixed circuit breakers Circuit breaker selection Indication contacts Remote operation 140 142 143 NW08 to NW63 drawout circuit breakers Circuit breaker selection Chassis locking and accessories Indication contacts Remote operation 144 146 148 149 Accessories for NW08 to NW63 fixed and drawout circuit breakers NW08 to NW63 fixed switch-disconnectors 150 Circuit breaker selection 152 NW08 to NW63 drawout switch-disconnectors 121 Circuit breaker selection 154 Retrofit solutions 156 Connection for fixed devices Connection for drawout devices 156 157 Masterpact Schneider Electric Orders and quotations Accessories for communication Bus Digipact display module DMB300 display module E67954 50894 DMC300 display module E67955 50895 Spare parts Memory card DMC300PCM 50959 Digipact Bus pre-wired system Data concentrator DC150 110-240 V AC, 50/60 Hz and 115-125 V DC 50823 E79014 Auxiliary supply voltage Junction block 50778 E67956 Junction block for internal Bus Cables E67957 Cable for internal bus 20-meter roll (0.75 mm2) 100-meter roll (0.75 mm2) 50779 50780 Modbus pre-wired system Connection block 50963 CSD309 RS485 9 pins SubD connector 50964 CDM303 display module cable (L: 3 m) 50960 CCP303 RS485 Modbus cable + power (L: 3 m) (Micrologic) CCS303 RS485 Modbus cable (L: 3 m) (Modbus slave) 50961 50962 CCR301 power + RS485 roll cable (L: 60 m) (Bus Modbus) 50965 E67959 E67958 CJB306 6 connections RS485 block + power E67961 E79015 E67960 Cables Converter RS485/RS232 (ACE909) 12 V DC power supply included RS485/RS232 RS485/Ethernet RS485/Ethernet (SMS compatible) (1) see catalogue Telemecanique. (2) see catalogue Square D. 122 Masterpact 50786 TSX SCA72 174 CEV 300-10 3050 EGW2 (1) (1) (2) Schneider Electric Order form Masterpact NT and NW Locking To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles Basic device VBP - ON/OFF pushbutton locking OFF position locking VCPO - by padlocks VSPO - by keylocks Locking kit without keylocks 1 lock Quantity Masterpact type NT, NW Frame size 06 to 63 Sensor rating A Circuit breaker N1, H1, H2, H3, L1 Switch-disconnector NA, HA, HF Number of poles 3 or 4 Option : Neutral on right side Type of device Fixed Drawout with chassis Chassis alone Drawout without chassis VSPD - chassis locking in ''disconnected'' position VPEC - door interlock Micrologic control unit A - ammeter 2.0 A P - power meter 5.0 A 6.0 A 7.0 A 5.0 P 6.0 P 7.0 P 5.0 H 6.0 H 7.0 H TCE - external sensor (CT) for neutral + earth-fault protection 2 locks (different key profiles) for NW Locking kit Profalux Ronis without keylocks 1 lock 1 lo ck + 1 lock with same key profile 2 locks (different key profiles) Optional connected - disconnected - test position locking Latch on right-hand side of chassis Latch on left-hand side of chassis Indication contacts TCW - external sensor for SGR protection Rectangular sensor 280 x 115 for earth-leakage 470 x 160 protection Additional 1 block of 4 OF for NW EF - combined ''connected/closed'' contacts 1 EF 5 A - 240 V AC for NW 1 EF low-level for NW SDE - ''fault-trip'' indication contacts 1 SDE 5 A - 240 V AC Standard Additional 1 SDE 5 A - 240 V AC 1 SDE low-level Programmable contacts 2 M2C contacts 6 M6C contacts Carriage switches low-level 6 A - 240 V AC CE - ''connected'' position Maxi. 3 for NT and NW Maxi. 2 for NT and 3 for NW CD - ''disconnected'' position Maxi. 1 for NT and 3 for NW CT - ''test'' position AC - actuator for additional carriage switches LT - long-time rating plug (standard setting 0.4 to 1 x Ir) Low setting option 0.4 to 0.8 Ir High setting option 0.8 to 1 Ir LT OFF option PTE - external voltage measurement input AD - external power-supply module BAT - battery module Communication Digipact Modbus Modbus Connection Horizontal Top Vertical Top Front Top Bare-cable connectors 4 x 240 mm2 + connector shield Vertical-connection adapters Cable-lug adapters Interphase barriers Spreaders Disconnectable front-connection adapter 1 lock + 1 lock with same key profile OF - ON/OFF indication contacts Standard 4 OF 6 A - 240 V AC (10 A - 240 V AC and low-level for NW) Max. 4 qty Alternate 1 OF low-level for NT (replaces a standard contact) TCE - external sensor (CT) for double neutral protection (Micrologic P and H with 3-poles) Eco COM Ronis VPOC - racking interlock IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW VDC - mismatch protection H - harmonic meter COM Profalux Max. 2 qty Max. 8 Max. 8 qty qty qty qty qty qty Remote operation Bottom Bottom Bottom Remote ON/OFF NT-FC fixed NT-FC, fixed, draw. NT-FC, fixed, draw. NT, NW-fixed, draw. NT-fixed, drawout NW-fixed Remote tripping VO - safety shutters on chassis NT, NW VIVC - shutter position indication NW and locking MCH - gear motor XF - closing voltage release MX - opening voltage release PF - ''ready to close'' contact V V V low-level 6 A - 240 V AC BPFE - electrical closing pushbutton Res - electrical reset option RAR - automatic reset option MN - undervoltage release V R - delay unit (non-adjustable) Rr - adjustable delay unit 2nd MX - shunt release V Accessories Key for Micrologic control units: 2.0 : basic protection (long-time + inst.) 5.0 : selective protection (long-time + short-time + inst.) 6.0 : selective + earth-fault protection (long-time + short-time + inst. + earth-fault) 7.0 : selective + earth-leakage protection (long-time + short-time + inst. + earth-leakage) CDM - mechanical operation counter CB - auxiliary terminal shield for chassis CDP - escutcheon CP - transparent cover OP - blanking plate Brackets for mounting on backplates 123 Masterpact Schneider Electric Orders and quotations NT06 to NT16 fixed circuit breakers Circuit breaker selection A Masterpact fixed circuit breaker is described by 4 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b a top connection b a bottom connection A communication option and various auxiliaries and accessories many also be added. . Basic circuit breaker Type H1 NT06 NT08 NT10 NT12 NT16 In (A at 40°C) 630 800 1000 1250 1600 3P 4P Icu (kA for U = 220/415 V) - Ics = 100% Icu 42 47110 47115 42 47120 47125 42 47130 47135 42 47140 47145 42 47150 47155 In (A at 40°C) 630 800 1000 3P 4P Icu (kA for U = 220/415 V) - Ics = 100% Icu 150 47112 47117 150 47122 47127 150 47132 47137 Type L1 E46423 NT06 NT08 NT10 Option Neutral on the right (*) Micrologic control unit "ammeter" A Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A basic protection selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 47282 47285 47286 47287 selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 47289 47290 47291 selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 47293 47294 47295 "power meter" P Micrologic 5.0 P Micrologic 6.0 P Micrologic 7.0 P "harmonic meter" H Micrologic 5.0 H Micrologic 6.0 H Micrologic 7.0 H Communication option Modbus COM Modbus COM eco Digipact COM (*) consult us 47405 47406 47409 Auxiliaries and accessories: b for fixed devices: see page 126 b for fixed or drawout devices: see page 133 Switch-disconnector version: see page 136 Source changeover assembly: see page 133 124 Masterpact Schneider Electric Front connection 4P 47328 47329 47330 47331 Bare-cable connectors + 1 connector shield for 4 x 240 mm2 cables 3P (3 parts) 4P (4 parts) 47333 47334 Vertical connection adapters 630/1600 A 3P (3 parts) 4P (4 parts) 33642 33643 Cable lug adapters 630/1600 A 3P (3 parts) 4P (4 parts) 33644 33645 E47757 3P Top Bottom 630/1600 A E46427 E46426 E46887 Front connection accessories Interphase barriers 33648 E79060 3P/4P (3 parts) E74437 Arc chute screen 3P 4P 47335 47336 Rear connection E46429 Vertical connection 3P 4P 630/1600 A Top Bottom 33604 33605 33614 33615 3P 4P 630/1600 A Top Bottom 33606 33607 33616 33617 E46430 Horizontal connection E79060 Rear connection accessories Interphase barriers 3P/4P (3 parts 33648 Common accessories for front and rear connections Spreaders E46431 630/1600 A 3P 4P For front and horizontal rear connection 33622 33623 240 mm2 33013 33014 33015 33016 E47820 Cable lug kits 300 mm2 3P (6 lug kit) 4P (8 lug kit) 3P (6 lug kit) 4P (8 lug kit) 125 Masterpact Schneider Electric Orders and quotations NT06 to NT16 fixed circuit breakers (cont.) Indication contacts E46463 ON/OFF indication contacts (OF) Changeover contacts (6 A - 240 V) 1 low-level OF to replace 1 standard OF (4 max.) 4 (standard) 47339 E47758 "Fault trip" indication contacts (SDE) Changeover contact (5 A - 240 V) 1 additional SDE (5 A - 240 V) 1 additional low-level SDE 1 (standard) 47340 47341 E46434 Programmable contacts (*) (programmed via Micrologic control unit) 2 contacts (M2C) (5 A - 240 V) 6 changeover contacts (M6C) (5 A - 240 V) (*) for Micrologic control units P and H only. 47403 47404 E46435 M2C M6C 126 Masterpact Schneider Electric Remote operation Remote ON/OFF E46436 Gear motor AC 50/60 Hz DC 48 V 100-130 V 200-240 V 277-415 V 440-480 V 24-30 V 48-60 V 100-130 V 200-250 V MCH 47391 47395 47396 47398 47400 47390 47391 47392 47393 E46437 Instantaneous voltage releases Standard AC 50/60 Hz DC Communicating AC 50/60 Hz DC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC Closing release XF 47349 47350 47351 47352 47353 47354 47355 XF com 47310 47311 47312 47313 47314 47315 47316 Opening release MX 47359 47360 47361 47362 47363 47364 47365 MX com 47320 47321 47322 47323 47324 47325 47326 E46438 "Ready to close" contact (1 max.) PF 47342 47343 1 changeover contact (5 A - 240 V) 1 low-level changeover contact E46439 Electrical closing pushbutton BPFE 47512 1 pushbutton E46660 Remote reset after fault trip Electrical reset 110-130 V AC 220-240 V AC Automatic reset Adaptation Res 47344 47345 RAR 47346 (*) Remote tripping E46437 Instantaneous voltage release AC 50/60 Hz DC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC 2nd MX 47369 47370 47371 47372 47373 47374 47375 or MN 47380 47381 47382 47383 47385 MN delay unit E46694 R (non-adjustable) AC 50/60 Hz DC 48-60 V 100-130 V 200-250 V 380-480 V 33684 33685 Rr (adjustable) 33680 33681 33682 33683 (*) no charge. 127 Masterpact Schneider Electric Orders and quotations NT06 to NT16 drawout circuit breakers Circuit breaker selection A Masterpact drawout circuit breaker is described by 5 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b a chassis b a top connection b a bottom connection A communication option and various auxiliaries and accessories many also be added. . Basic circuit breaker Type H1 3P 4P In (A at 40°C) Icu (kA for U = 220/415 V) - Ics = 100% Icu 630 42 47200 47205 800 42 47210 47215 1000 42 47220 47225 1250 42 47230 47235 1600 42 47240 47245 NT06 NT08 NT10 NT12 NT16 Type L1 3P 4P In (A at 40°C) Icu (kA for U = 220/415 V) - Ics = 100% Icu 630 150 47202 47207 800 150 47212 47217 1000 150 47222 47227 E46441 NT06 NT08 NT10 Option Neutral on the right (*) Micrologic control unit "ammeter" A Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A basic protection selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 33525 33532 33533 33534 selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 47297 47298 47299 selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 47301 47302 47303 3P 33722 33723 4P 33725 33726 3P 33723 4P 33726 "power meter" P Micrologic 5.0 P Micrologic 6.0 P Micrologic 7.0 P "harmonic meter" H Micrologic 5.0 H Micrologic 6.0 H Micrologic 7.0 H Chassis For type H1 630/1250 A 1600 A For type L1 630/1000 A Communication option Modbus COM Modbus eco COM Digipact COM (*) consult us Chassis 33852 33855 + Circuit breaker 47485 33843 47489 Auxiliaries and accessories: b for drawout devices: see page 130 b for fixed or drawout devices: see page 133 Switch-disconnector version: see page 136 Source changeover assembly: see page 133 128 Masterpact Schneider Electric E46440 Chassis front connection 630/1600 A Top Bottom 3P 4P 33727 33728 33733 33734 Front connection accessories 33642 33643 Cable lug adapters 630/1600 A 3P (3 parts) 4P (4 parts) 33644 33645 E46427 E46426 Vertical connection adapters 630/1600 A 3P (3 parts) 4P (4 parts) Chassis rear connection E46429 Vertical connection 630/1600 A Top Bottom 630/1600 A Top Bottom 3P 4P 33729 33730 33735 33736 3P 4P 33731 33732 33737 33738 E46430 Horizontal connection E46428 Rear connection accessories Interphase barriers 3P/4P (3 parts) 33768 Common accessories for front and rear connection Spreaders E46431 630/1600 A 3P 4P For front and horizontal rear connection. 33622 33623 240 mm2 33013 33014 33015 33016 E47820 Cable lug kits 300 mm2 3P (6 lug kit) 4P (8 lug kit) 3P (6 lug kit) 4P (8 lug kit) 129 Masterpact Schneider Electric Orders and quotations NT06 to NT16 drawout circuit breakers (cont.) Chassis locking and accessories Chassis locking "Disconnected" position locking E46685 By padlocks Standard By keylocks Profalux 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) Ronis 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) Optional disconnected/test/connected position locking Locking kit without locks for Profalux Ronis Castell Kirk 33773 33774 33775 33776 33777 33778 33779 Right-hand side of chassis (VPECD) Left-hand side of chassis (VPECG) 33786 33787 Racking interlock (VPOC) 33788 (*) 33769 33770 33771 33772 E46464 Door interlock (1 part) E46465 Racking interlock Breaker mismatch protection 33767 E47765 Breaker mismatch protection (VDC) Chassis accessories Arc chute cover Standard Terminal shield 3P 4P 33763 33764 Safety shutters (VO) 3P 4P 33765 33766 E46700 3P/4P E46698 Auxiliary terminal shield (CB) E46699 Safety shutters (*) no charge. 130 Masterpact Schneider Electric Indication contacts E46467 ON/OFF indication contacts (OF) Changeover contacts (6 A - 240 V) 4 (standard) 1 low-level OF to replace 1 standard OF (4 max.) 33806 E47759 "Fault trip" indication contacts (SDE) Changeover contact (5 A - 240 V) 1 (standard) 1 additional SDE (5 A - 240 V) 47430 1 additional low-level SDE 47431 E46686 Programmable contacts (*) (programmed via Micrologic control unit) 2 contacts M2C (5 A - 240 V) 47483 6 changeover contacts M6C (5 A - 240 V) (*) for Micrologic control units P and H only. 47484 E46687 M2C M6C E46661 Carriage switches (connected / disconnected / test position) Changeover contacts (6A - 240 V) 1 connected position contact (3 max.) 1 test position contact (1 max.) 1 disconnected position contact (2 max.) And/or low-level changeover contacts 1 connected position contact (3 max.) 1 test position contact (1 max.) 1 disconnected position contact (2 max.) 33751 33752 33753 33754 33755 33756 Auxiliary terminals for chassis alone 3 wire terminal (30 parts) 6 wire terminal (10 parts) Jumpers (10 parts) 47071 47072 47900 131 Masterpact Schneider Electric Orders and quotations NT06 to NT16 drawout circuit breakers (cont.) Remote operation Remote ON/OFF E46662 Gear motor AC 50/60 Hz DC 48 V 100-130 V 200-240 V 277-415 V 440-480 V 24-30 V 48-60 V 100-130 V 200-250 V MCH 47461 47465 47466 47468 47470 47460 47461 47462 47463 Instantaneous voltage release Standard AC 50/60 Hz DC Communicating AC 50/60 Hz DC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC Closing release XF 47439 47440 47441 47442 47443 47444 47445 XF com 47411 47412 47413 47414 47415 47416 47417 Opening release MX 33809 33810 33811 33812 33813 33814 33815 MX com 33791 33792 33793 33794 33795 33796 33797 E46664 "Ready to close" contact (1 max.) PF 47432 47433 1 changeover contact (5 A - 240 V) 1 low-level changeover contact E46439 Electrical closing pushbutton BPFE 47512 1 pushbutton E46660 Remote reset after fault trip Electrical reset 110-130 V AC 220-240 V AC Automatic reset Adaptation Res 47434 47435 RAR 47346 (*) Remote tripping E46663 Instantaneous voltage release AC 50/60 Hz DC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC 2nd MX 47449 47450 47451 47452 47453 47454 47455 or MN 33819 33820 33821 33822 33824 MN delay unit E46694 R (non-adjustable) AC 50/60 Hz DC 48-60 V 100-130 V 200-250 V 380-480 V 33684 33685 Rr (adjustable) 33680 33681 33682 33683 (*) no charge. 132 Masterpact Schneider Electric Accessories for NT06 to NT16 fixed and drawout circuit breakers Circuit breaker locking Pushbutton locking device 33897 E46666 By padlocks OFF position locking By padlocks + BPFE support E46666 47514 By keylocks + BPFE support Profalux 1 lock 1 lock + 1 lock with same key profile Ronis 1 lock 1 lock + 1 lock with same key profile Locking kit without locks for Profalux Ronis Kirk Castell 47519 47520 47521 47522 47515 47516 47517 47518 Other circuit breaker accessories Mechanical operation counter 33895 E46667 operation counter CDM E46670 E46669 E46668 Escutcheon and accessories Escutcheon Transparent cover (IP 54) Escutcheon blanking plate Fixed 33718 Drawout 33857 33859 33858 EscutcheonCoverBlanking plate Mechanical interlocking for source changeover E47760 Interlocking using connecting rods Complete assembly with 2 adaptation fixtures + rods 2 Masterpact NT fixed devices 2 Masterpact NT drawout devices 33912 33913 Interlocking using cables (*) Choose 2 adaptation fixtures (1 for each breaker) + 1 set of cables 1 adaptation fixture for Masterpact NT fixed devices 1 adaptation fixture for Masterpact NT drawout devices 1 set of 2 cables (*) Can be used with any combination of NT or NW, fixed or drawout devices. 33200 33201 33209 E70742 Cable-type door interlock 1 complete assembly for Masterpact NT fixed devices 1 complete assembly for Masterpact NT drawout devices 133 Masterpact 33920 33921 Schneider Electric Orders and quotations Accessories for NT06 to NT16 fixed or drawout circuit breakers (cont.) Accessories for Micrologic control units External sensors 33576 E46671 External sensor for earth-leakage protection (TCE) Sensor rating 400/1600 A (for Micrologic P and H with 3P devices) Rectangular sensor for earth-leakage protection 280 mm x 115 mm E46672 33577 Source ground return (SGR) earth fault protection External sensor (SGR) 33579 E46671 MDGF summing module 48891 Voltage measurement input (for breakers supplied via bottom terminals) Voltage measurement input Fixed E46674 Drawout 47506 47507 E46674 Long-time rating plug (limits setting range for higher accuracy) Standard 0.4 to 1 x Ir 33542 Low-setting option 0.4 to 0.8 x Ir 33543 High-setting option 0.8 to 1 x Ir 33544 Without long-time protection off 33545 Zone Selective Interlocking option for Micrologic P and H ZSI Standard E47787 External power supply module L4 L3 t Inpu 24VDC Output 24VDC G2 0A AD 22 G1 24-30 V DC 48-60 V DC 125 V DC 110 V AC 220 V AC 380 V AC 54440 54441 54442 54443 54444 54445 1 24 V battery 54446 Battery module Test equipment Mini test kit E59921 33594 Portable test kit E59554 33595 Special settings For circuit breaker derating Catalogue number to be added to those describing the circuit breaker rating Rating NT08 NT10 NT12 NT16 400 47053 47053 630 33091 33091 33091 800 33092 33092 33092 1000 33093 33093 1250 33094 Note: for ratings In = 100 or 250 A, please contact us. 134 Masterpact Schneider Electric 135 Masterpact Schneider Electric Orders and quotations NT06 to NT16 fixed switch-disconnectors Switch-disconnector selection A Masterpact fixed switch-disconnector is described by 3 catalogue numbers corresponding to: b the basic switch-disconnector b a top connection b a bottom connection A communication option and various auxiliaries and accessories many also be added. . Basic switch-disconnector Type HA NT06 NT08 NT10 NT12 NT16 In (A at 40°C) 630 800 1000 1250 1600 3P Icm (kA peak for U = 220/690 V) 60 47159 60 47161 60 47163 60 47165 60 47167 4P 47160 47162 47164 47166 47168 Communication option 47405 47409 E46675 Modbus COM Digipact COM Auxiliaries and accessories: b for fixed devices: see page 126 b for fixed or drawout devices: see page 133 Source changeover assembly: see page 133 136 Masterpact Schneider Electric Front connection 4P 47328 47329 47330 47331 Bare-cable connectors + 1 connector shield for 4 x 240 mm2 cables 3P (3 parts) 4P (4 parts) 47333 47334 Vertical connection adapters 630/1600 A 3P (3 parts) 4P (4 parts) 33642 33643 Cable lug adapters 630/1600 A 3P (3 parts) 4P (4 parts) 33644 33645 E47757 3P Top Bottom 630/1600 A E46427 E46426 E46887 Front connection accessories Interphase barriers 33648 E79060 3P/4P (3 parts) Rear connection E46429 Vertical connection 3P 4P 630/1600 A Top Bottom 33604 33605 33614 33615 3P 4P 630/1600 A Top Bottom 33606 33607 33616 33617 E46430 Horizontal connection E79060 Rear connection accessories Interphase barriers 3P/4P (3 parts) 33648 Common accessories for front and rear connection Spreaders E46431 630/1600 A 3P 4P For front and horizontal rear connection 33622 33623 240 mm2 33013 33014 33015 33016 E47820 Cable lug kits 300 mm2 3P (6 lug kit) 4P (8 lug kit) 3P (6 lug kit) 4P (8 lug kit) 137 Masterpact Schneider Electric Orders and quotations NT06 to NT16 drawout switch-disconnectors Switch-disconnector selection A Masterpact drawout switch-disconnector is described by 4 catalogue numbers corresponding to: b the basic switch-disconnector b a chassis b a top connection b a bottom connection A communication option and various auxiliaries and accessories many also be added. . Basic switch-disconnector Type HA In (A at 40°C) 630 800 1000 1250 1600 NT06 NT08 NT10 NT12 NT16 3P Icm (kA peak for U = 220/690 V) 60 47248 60 47250 60 47252 60 47254 60 47256 4P 47249 47251 47253 47255 47257 Chassis 630/1250 A 1600 A 3P 33722 33723 4P 33725 33726 E00000 Communication option COM Modbus COM Digipact Chassis 33852 33855 + Switch-disconnector 47485 47489 Auxiliaries and accessories: b for drawout devices: see page 130 b for fixed or drawout devices: see page 133 Source changeover assembly: see page 133 138 Masterpact Schneider Electric E46440 Chassis front connection 630/1600 A Top Bottom 3P 4P 33727 33728 33733 33734 Front connection accessories 33642 33643 Cable lug adapters 630/1600 A 3P (3 parts) 4P (4 parts) 33644 33645 E46427 E46426 Vertical connection adapters 630/1600 A 3P (3 parts) 4P (4 parts) Chassis rear connection E46429 Vertical connection 630/1600 A Top Bottom 630/1600 A Top Bottom 3P 4P 33729 33730 33735 33736 3P 4P 33731 33732 33737 33738 E46430 Horizontal connection Rear connection accessories E46428 Interphase barriers 3P/4P (3 parts) 33768 Common accessories for front and rear connection Spreaders E46431 630/1600 A 3P 4P For front and horizontal rear connection 33622 33623 240 mm2 33013 33014 33015 33016 E47820 Cable lug kits 300 mm2 3P (6 lug kit) 4P (8 lug kit) 3P (6 lug kit) 4P (8 lug kit) 139 Masterpact Schneider Electric Masterpact: price list NW08 to NW63 fixed circuit breakers Circuit breaker selection Unit price (excl.VAT) in French francs A Masterpact fixed circuit breaker is described by 4 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b a top connection b a bottom connection A communication option and various auxiliaries and accessories may also be added. . Basic circuit breaker Type N1 NW08 NW10 NW12 NW16 Type H1 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63 E46442 3P 4P In (A at 40°C) Icu (kA for U = 220/440 V) - Ics = 100% Icu 800 42 48000 48007 1000 42 48014 48021 1250 42 48028 48035 1600 42 48042 48049 3P 4P In (A at 40°C) Icu (kA for U = 220/440 V) - Ics = 100% Icu 800 65 48001 48008 1000 65 48015 48022 1250 65 48029 48036 1600 65 48043 48050 2000 65 48057 48064 2500 65 48070 48076 3200 65 48082 48087 4000 65 48092 48097 4000 100 48106 48109 5000 100 48112 48115 6300 100 48118 48121 Type H2 Basic circuit breaker y 4000 A E46443 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63 Basic circuit breaker u 4000 A 3P 4P In (A at 40°C) Icu (kA for U = 220/440 V) - Ics = 100% Icu 800 100 48002 48009 1000 100 48016 48023 1250 100 48030 48037 1600 100 48044 48051 2000 100 48058 48065 2500 100 48071 48077 3200 100 48083 48088 4000 100 48093 48098 4000 150 48107 48110 5000 150 48113 48116 6300 150 48119 48122 Option Neutral on the right (*) Micrologic control unit "ammeter" A Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A basic protection selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 47282 47285 47286 47287 selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 47289 47290 47291 selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 47293 47294 47295 "power meter" P Micrologic 5.0 P Micrologic 6.0 P Micrologic 7.0 P "harmonic meter" H Micrologic 5.0 H Micrologic 6.0 H Micrologic 7.0 H Communication option Modbus COM Modbus COM eco Digipact COM (*) consult us. 48188 47406 48192 Auxiliaries and accessories: b for fixed devices: see page 22 b for fixed or drawout devices: see page 30 Switch-disconnector version: see page 32 Source changeover assembly: see page 30 BTP207E-50200-NW.fm/20 Schneider Electric Masterpact: price list NW08 to NW63 fixed circuit breakers (cont.) Circuit breaker selection (cont.) Unit price (excl.VAT) in French francs E46444 Front connection 800/1600 A 2000 A 2500/3200 A Top Bottom Top Bottom Top Bottom 3P 48128 48130 48124 48125 48129 48131 4P 48153 48155 48126 48127 48154 48156 3P 48421 48422 4P 48424 48425 3P 48133 48138 48134 48139 4P 48158 48163 48159 48164 Front connection accessories E46889 Disconnectable front connection 1600 A 2000/3200 A Rear connection E46445 Vertical connection 800/2000 A 2500/3200 A 4000 A 4000b/5000 A 6300 A Top Bottom Top Bottom Top 48135 48160 Bottom 48140 48165 Top 48136 48161 Bottom 48141 48166 Top 48137 48162 Bottom 48142 48167 Top Bottom Top Bottom Top Bottom Top Bottom 3P 48143 48148 48144 48149 48145 48150 48146 48151 4P 48168 48173 48169 48174 48170 48175 48171 48176 E46446 Horizontal connection 800/2000 A 2500/3200 A 4000 A 4000b/5000 A Rear connection accessories Interphase barriers 48599 E46428 3P/4P (3 parts) 47829 E47788 Brackets for mounting on a backplate 2 parts Schneider Electric BTP207E-50200-NW.fm/21 Masterpact: price list NW08 to NW63 fixed circuit breakers (cont.) Indication contacts Unit price (excl.VAT) in French francs E46432 ON/OFF indication contacts (OF) Block of 4 changeover contacts (6 A - 240 V) 1 additional block of 4 contacts (2 max.) 1 block (standard) 48198 E46665 "Fault trip" indication contacts (SDE) Changeover contact (5 A - 240 V) 1 additional SDE (5 A - 240 V) 1 additional low-level SDE 1 (standard) 48200 48201 E46434 Programmable contacts (*) (programmed via Micrologic control unit) 2 contacts M2C (5 A - 240 V) 6 changeover contacts M6C (5 A - 240 V) (*) for Micrologic control units P and H only. 47403 47404 E46435 M2C M6C BTP207E-50200-NW.fm/22 Schneider Electric Masterpact: price list NW08 to NW63 fixed circuit breakers (cont.) Remote operation Unit price (excl.VAT) in French francs Remote ON/OFF E46447 Gear motor AC 50/60 Hz DC 48 V 100-130 V 200-240 V 250-277 V 380-415 V 440-480 V 24-30 V 48-60 V 100-130 V 200-250 V MCH 48207 48211 48212 48213 48214 48215 48206 48207 48208 48209 E46437 Instantaneous voltage releases Standard AC 50/60 Hz DC Communicating AC 50/60 Hz DC 12 V DC 24-30 V DC, 24 V AC 48/60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC Closing release XF 47349 47350 47351 47352 47353 47354 47355 XF com 47310 47311 47312 47313 47314 47315 47316 Opening release MX 47359 47360 47361 47362 47363 47364 47365 MX com 47320 47321 47322 47323 47324 47325 47326 E46438 "Ready to close" contact (1 max.) 1 changeover contact (5 A - 240 V) 1 low-level changeover contact PF 47342 47343 E46677 Electrical closing pushbutton BPFE 48534 1 pushbutton E46665 Remote reset after fault trip Electrical reset 110-130 V AC 220-240 V AC Automatic reset Adaptation Res 48202 48203 RAR 47346 (*) Remote tripping E46437 Instantaneous voltage release AC 50/60 Hz DC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC 2nd MX 47369 47370 47371 47372 47373 47374 47375 or MN 47380 47381 47382 47383 47385 MN delay unit E46694 R (non-adjustable) AC 50/60 Hz DC 48-60 V 100-130 V 200-250 V 380-480 V 33684 33685 Rr (adjustable) 33680 33681 33682 33683 (*) no charge. Schneider Electric BTP207E-50200-NW.fm/23 Masterpact: price list NW08 to NW63 drawout circuit breakers Circuit breaker selection Unit price (excl.VAT) in French francs E46448 A Masterpact drawout circuit breaker is described by 5 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b a chassis b a top connection b a bottom connection A communication option and various auxiliaries and accessories may also be added. . Basic circuit breaker 3P 4P Type N1 NW08 NW10 NW12 NW16 In (A at 40°C) Icu (kA for U = 220/440 V) - Ics = 100% Icu 800 42 48230 48237 1000 42 48244 48251 1250 42 48258 48265 1600 42 48272 48279 Type H1 NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63 In (A at 40°C) Icu (kA for U = 220/440 V) - Ics = 100% Icu 800 65 48231 48238 1000 65 48245 48252 1250 65 48259 48266 1600 65 48273 48280 2000 65 48287 48294 2500 65 48300 48306 3200 65 48312 48317 4000 65 48322 48327 4000 100 48336 48339 5000 100 48342 48345 6300 100 48348 48351 Type H2 E46449 Basic circuit breaker + chassis y 4000 A NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63 In (A at 40°C) Icu (kA for U = 220/440 V) - Ics = 100% Icu 800 100 48232 48239 1000 100 48246 48253 1250 100 48260 48267 1600 100 48274 48281 2000 100 48288 48295 2500 100 48301 48307 3200 100 48313 48318 4000 100 48323 48328 4000 150 48337 48340 5000 150 48343 48346 6300 150 48349 48352 Type H3 NW20 NW25 NW32 NW40 In (A at 40°C) Icu (kA for U = 220/440 V) - Ics = 100% Icu 2000 150 48289 48296 2500 150 48302 48308 3200 150 48314 48319 4000 150 48324 48329 Type L1 Basic circuit breaker + chassis u 4000 A NW08 NW10 NW12 NW16 NW20 In (A at 40°C) Icu (kA for U = 220/440 V) - Ics = 100% Icu 800 150 48233 48240 1000 150 48247 48254 1250 150 48261 48268 1600 150 48275 48282 2000 150 48290 48297 Option Neutral on the right (*) Micrologic control unit "ammeter" A Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A basic protection selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 48358 48360 48361 48362 selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 48363 48364 48365 selective protection selective + earth-fault protection selective + earth-leakage protection 3P/4P 48366 48367 48368 "power meter" P Micrologic 5.0 P Micrologic 6.0 P Micrologic 7.0 P "harmonic meter" H Micrologic 5.0 H Micrologic 6.0 H Micrologic 7.0 H (*) consult us. BTP207E-50200-NW.fm/24 Schneider Electric Masterpact: price list NW08 to NW63 drawout circuit breakers (cont.) Circuit breaker selection (cont.) Unit price (excl.VAT) in French francs E70740 Chassis 3P 4P 48391 48392 48403 48404 48392 48393 48394 48395 48396 48397 48404 48405 48406 48407 48408 48409 48394 48395 48396 48406 48407 48408 48399 48400 48411 48412 For type N1 800/1250 A 1600 A For type H1/H2 800/1600 A 2000 A 2500 A 3200 A 4000 A 4000b/6300 A Chassis y 4000 A For type H3 2000/2500 A 3200 A 4000 A For type L1 800/1600 A 2000 A Auxiliaries and accessories: b for drawout devices: see page 26 b for fixed or drawout devices: see page 30 Switch-disconnector version: see page 32 Source changeover assembly: see page 30 Communication option Chassis Modbus COM Modbus eco COM Digipact COM + Circuit breaker 33852 48384 48385 48388 33855 E46450 Chassis front connection 800/1600 A 2000 A 2500/3200 A Top Bottom Top 3P 48415 48418 48413 4P 48441 48444 48417 Bottom 48414 48420 Top Bottom 48416 48419 48442 48445 3P 4P Chassis rear connection E46445 Vertical connection 800/2000 A 800/1600 A type L1 2500/3200 A 2000 A types H3/L1 4000 A Top Bottom Top Bottom Top 48133 48138 48134 48139 48135 48158 48163 48159 48164 48160 Bottom 48140 48165 4000b/5000 A Top 48136 48161 Bottom 48141 48166 Top 48137 48162 Bottom 48142 48167 800/2000 A 800/1600 A type L1 2500/3200 A 2000 A types H3/L1 4000 A Top Bottom Top Bottom Top Bottom 48143 48148 48144 48149 48145 48150 48168 48173 48169 48174 48170 48175 4000b/5000 A Top 48146 48171 Bottom 48151 48176 6300 A E46446 Horizontal connection E46428 Rear connection accessories Schneider Electric Interphase barriers 3P/4P (3 parts) 48600 BTP207E-50200-NW.fm/25 Masterpact: price list NW08 to NW63 drawout circuit breakers (cont.) Chassis locking and accessories Unit price (excl.VAT) in French francs Chassis locking "Disconnected" position locking E46451 By padlocks Standard By keylocks Profalux 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) Ronis 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) Optional disconnected/test/connected position locking Locking kit without locks for Profalux, Ronis Kirk Castell 48568 48569 48570 48572 48573 48574 33779 Right-hand side of chassis Left-hand side of chassis 48579 48580 1 part 48582 (*) 48564 48565 48566 E46452 Door interlock (1 part) E46453 Racking interlock Racking interlock between crank and OFF pushbutton 1 part 48585 Automatic spring discharge before breaker removal 48554 E46688 1 part Breaker mismatch protection 33767 E46456 Breaker mismatch protection VDC (*) no charge. BTP207E-50200-NW.fm/26 Schneider Electric Masterpact: price list NW08 to NW63 drawout circuit breakers (cont.) Chassis locking and accessories (cont.) Unit price (excl.VAT) in French francs Chassis accessories Arc chute cover Standard 3P 4P 3P 4P 48595 48596 48597 48598 3P 4P 3P 4P 48587 48589 48588 48590 E46457 3P/4P Auxiliary terminal shield (CB) E46458 800/4000 A 4000b/6300 A Safety shutters + locking block E46459 800/4000 A 4000b/6300 A Shutter locking block (for remplacement) 48591 E46460 2 parts for 800/4000 A E46702 Front face shutter position indication and locking Schneider Electric 800/4000 A 4000b/6300 A 3P/4P 3P 4P 48592 48593 48594 BTP207E-50200-NW.fm/27 Masterpact: price list NW08 to NW63 drawout circuit breakers (cont.) Indication contacts Unit price (excl.VAT) in French francs E46689 ON/OFF indication contacts (OF) Block of 4 changeover contacts (6 A - 240 V) 1 additional block of 4 contacts (2 max.) 1 block (standard) 48468 E46690 Combined closed / connected contacts for use with 1 auxiliary contact 1 contact (5 A - 240 V) (8 max.) or 1 low-level contact (8 max.) 48477 48478 E46691 "Fault trip" indication contacts (SDE) Changeover contact (5 A - 240 V) 1 additional SDE (5 A - 240 V) or 1 additional low-level SDE 1 (standard) 48475 48476 E46703 Programmable contacts (*) (programmed via Micrologic control unit) 2 contacts M2C (5 A - 240 V) or 6 contacts M6C (5 A - 240 V) (*) for Micrologic control units P and H only. 48382 48383 E46734 M2C M6C E46661 Carriage switches (connected / disconnected / test position) Changeover contacts (8 A - 240V) 1 connected position contact (3 max.) 1 test position contact (3 max.) 1 disconnected position contact (3 max.) and/or low-level changeover contacts 1 connected position contact (3 max.) 1 test position contact (3 max.) 1 disconnected position contact (3 max.) Actuator for additional carriage switches 33751 33752 33753 33754 33755 33756 48560 Auxiliary terminals for chassis alone 3 wire terminal (30 parts) 6 wire terminal (10 parts) Jumpers (10 parts) BTP207E-50200-NW.fm/28 47898 47899 47900 Schneider Electric Masterpact: price list NW08 to NW63 drawout circuit breakers (cont.) Remote operation Unit price (excl.VAT) in French francs Remote ON/OFF E46692 Gear motor AC 50/60 Hz DC 48 V 100-130 V 200-240 V 250-277 V 380-415 V 440-480 V 24-30 V 48-60 V 100-130 V 200-250 V MCH 48522 48526 48527 48528 48529 48530 48521 48522 48523 48524 E46693 Instantaneous voltage releases Standard AC 50/60 Hz DC Communicating AC 50/60 Hz DC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC Closing release XF 48480 48481 48482 48483 48484 48485 48486 XF com 48448 48449 48450 48451 48452 48453 48454 Opening release MX 48490 48491 48492 48493 48494 48495 48496 MX com 48457 48458 48459 48460 48461 48462 48463 E46695 "Ready to close" contact (1 max.) 1 changeover contact (5 A - 240 V) 1 low-level changeover contact PF 48469 48470 E46677 Electrical closing pushbutton BPFE 48534 1 pushbutton E46691 Remote reset after fault trip Electrical reset 110-130 V AC 220-240 V AC Automatic reset Adaptation Res 48472 48473 RAR 47346 (*) Remote tripping E46693 Instantaneous voltage release AC 50/60 Hz DC 12 V DC 24-30 V DC, 24 V AC 48-60 V DC, 48 V AC 100-130 V 200-250 V 277 V AC 380-480 V AC 2nd MX 48510 48511 48512 48513 48514 48515 48516 or MN 48501 48502 48503 48504 48506 MN delay unit E46694 R (non-adjustable) AC 50/60 Hz DC 48-60 V 100-130 V 200-250 V 380-480 V 33684 33685 Rr (adjustable) 33680 33681 33682 33683 (*) no charge. Schneider Electric BTP207E-50200-NW.fm/29 Masterpact: price list Accessories for NW08 to NW63 fixed and drawout circuit breakers Unit price (excl.VAT) in French francs Circuit breaker locking Pushbutton locking device 48536 E46666 By padlocks OFF position locking By padlocks E46735 48539 By padlocks and keylocks Profalux Ronis 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) 48545 48546 48547 48549 48550 48551 Profalux, Ronis Kirk Castell 48541 48542 48543 Locking kit without locks for Other circuit breaker accessories Mechanical operation counter 48535 E46667 operation counter CDM Escutcheon Escutcheon Transparent cover IP 54 Escutcheon blanking plate E46736 E46680 E46679 Escutcheon and accessories Cover Fixed 48601 48605 Drawout 48603 48604 48605 Blanking plate Mechanical interlocking for source changeover E47762 Interlocking of 2 devices using connecting rods Complete assembly with 2 adaptation fixtures + rods 2 Masterpact NW fixed devices 2 Masterpact NW drawout devices Can be used with 1 NW fixed + 1 NW drawout. 48612 48612 Interlocking of 2 devices using cables (*) Choose 2 adaptation fixtures (1 for each device + 1 set of cables) 1 adaptation fixture for Masterpact NW fixed devices 1 adaptation fixture for Masterpact NW drawout devices 1 set of 2 cables (*) Can be used with any combination of NT or NW, fixed or drawout devices. 47926 47926 33209 Interlocking of 3 devices using cables Choose 3 adaptation fixtures (1 complete set with 3 adaptation fixtures + cables 3 sources, only 1 device closed, fixed or drawout devices 2 sources + 1 coupling, fixed or drawout devices 2 normal + 1 replacement source, fixed or drawout devices 48610 48609 48608 Cable-type door interlock 1 complete assembly for Masterpact NW fixed or drawout device BTP207E-50200-NW.fm/30 48614 Schneider Electric Masterpact: price list Accessories for NW08 to NW63 fixed and drawout circuit breakers (cont.) Unit price (excl.VAT) in French francs Accessories for Micrologic control units External sensors E46671 External sensor for earth-fault protection (TCE) Sensor rating 400/2000 A 1000/4000 A 34035 34036 4000/6300 A (for NW40b, NW50, NW63) 48182 33578 Source ground return (SGR) earth fault protection External sensor (SGR) 33579 E46672 Rectangular sensor for earth-leakage protection 470 mm x 160 mm E46671 MDGF summing module 48891 Voltage measurement input (for breakers supplied via bottom terminals) Voltage measurement input Fixed 47506 E46890 Drawout 48533 E46674 Long-time rating plug (limits setting range for higher accuracy) Standard 0.4 at 1 x Ir 33542 Low-setting option 0.4 at 0.8 x Ir 33543 High-setting option 0.8 at 1 x Ir 33544 Without long-time protection off 33545 Zone Selective Interlocking option for Micrologic P and H ZSI Standard E47787 External power supply module L4 L3 t Inpu 24VDC Output 24VDC G2 0A AD 22 G1 24-30 V DC 48-60 V DC 125 V DC 110 V AC 220 V AC 380 V AC 54440 54441 54442 54443 54444 54445 1 24 V battery 54446 Battery module Test equipment Mini test kit E59921 33594 Portable test kit E59554 33595 Special settings For circuit breaker derating Catalogue number to be added to those describing the circuit breaker Rating NW08 NW10 NW12 NW16 400 47053 47053 630 33091 33091 33091 800 33092 33092 33092 1000 33093 33093 1250 33094 1600 2000 2500 Rating NW40 NW40b NW50 NW63 2000 33982 47821 2500 33983 47822 47822 3200 33984 47823 47823 47823 4000 47824 47824 5000 47825 Note: for ratings In = 100 or 250 A, please consult us. Schneider Electric NW20 33093 33094 33095 NW25 33094 33095 33982 NW32 33095 33982 33983 BTP207E-50200-NW.fm/31 Masterpact: price list NW08 to NW63 fixed switch-disconnectors Switch-disconnector selection Unit price (excl.VAT) in French francs E46681 A Masterpact fixed switch-disconnector is described by 3 catalogue numbers corresponding to: b the basic switch-disconnector b a top connection b a bottom connection A communication option and various auxiliaries and accessories may also be added. Basic switch-disconnector y 4000 A . Basic switch-disconnector Type NA NW08 NW10 NW12 NW16 3P In (A at 40°C) Icm (kA peak for U = 220/690 V) 800 88 48004 1000 88 48018 1250 88 48032 1600 88 48046 4P 3P In (A at 40°C) Icm (kA peak for U = 220/690 V) 800 105 48005 1000 105 48019 1250 105 48033 1600 105 48047 2000 105 48061 2500 135 48074 3200 135 48085 4000 135 48095 4000 187 48108 5000 187 48114 6300 187 48120 4P 3P In (A at 40°C) Icm (kA peak for U = 220/690 V) 800 187 48006 1000 187 48020 1250 187 48034 1600 187 48048 2000 187 48062 2500 187 48075 3200 187 48086 4000 187 48096 4P 48011 48025 48039 48053 Type HA NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63 48012 48026 48040 48054 48068 48080 48090 48100 48111 48117 48123 E46682 Type HF Basic switch-disconnector u 4000 A NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 48013 48027 48041 48055 48069 48081 48091 48101 Communication option Modbus COM Digipact COM 48188 48192 Auxiliaries and accessories: b for fixed devices: see page 22 b for fixed or drawout devices: see page 30 Source changeover assembly: see page 30 BTP207E-50200-NW.fm/32 Schneider Electric Masterpact: price list NW08 to NW63 fixed switch-disconnectors (cont.) Switch-disconnector selection (cont.) Unit price (excl.VAT) in French francs E46444 Front connection 800/1600 A 2000 A 2500/3200 A 3P 48128 48130 48124 48125 48129 48131 4P 48153 48155 48126 48127 48154 48156 3P 48421 48422 4P 48424 48425 Top Bottom Top Bottom 3P 48133 48138 48134 48139 4P 48158 48163 48159 48164 Top 48135 48160 Bottom 48140 48165 Top 48136 48161 Bottom 48141 48166 Top 48137 48162 Bottom 48142 48167 Top Bottom Top Bottom Top Bottom Top Bottom 3P 48143 48148 48144 48149 48145 48150 48146 48151 4P 48168 48173 48169 48174 48170 48175 48171 48176 Top Bottom Top Bottom Top Bottom Front connection accessories E46889 Disconnectable front connection 1600 A 2000/3200 A Rear connection E46445 Vertical connection 800/2000 A 2500/3200 A 4000 A 4000b/5000 A 6300 A E46446 Horizontal connection 800/2000 A 2500/3200 A 4000 A 4000b/5000 A Rear connection accessories Interphase barriers 48599 E46428 3P/4P (3 parts) 47829 E47788 Brackets for mounting on a backplate 2 parts Schneider Electric BTP207E-50200-NW.fm/33 Masterpact: price list NW08 to NW63 drawout switch-disconnectors Switch-disconnector selection Unit price (excl.VAT) in French francs A Masterpact drawout switch-disconnector is described by 4 catalogue numbers corresponding to: b the basic switch-disconnector b a chassis b a top connection b a bottom connection A communication option and various auxiliaries and accessories may also be added. . Basic switch-disconnector Type NA NW08 NW10 NW12 NW16 4P 3P In (A at 40°C) Icm (kA peak for U = 220/690 V) 800 105 48235 1000 105 48249 1250 105 48263 1600 105 48277 2000 105 48291 2500 135 48304 3200 135 48315 4000 135 48325 4000 187 48338 5000 187 48344 6300 187 48350 4P 3P In (A at 40°C) Icm (kA peak for U = 220/690 V) 800 187 48236 1000 187 48250 1250 187 48264 1600 187 48278 2000 187 48292 2500 187 48305 3200 187 48316 4000 187 48326 4P 48241 48255 48269 48283 Type HA NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63 E46683 3P In (A at 40°C) Icm (kA peak for U = 220/690 V) 800 88 48234 1000 88 48248 1250 88 48262 1600 88 48276 48242 48256 48270 48284 48298 48310 48320 48330 48341 48347 48353 Type HF E46684 Basic switch-disconnector + chassis y 4000 A NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 48243 48257 48271 48285 48299 48311 48321 48331 Chassis Type NA 800/1250 A 1600 A Basic switch-disconnector + chassis u 4000 A 3P 48391 48392 4P 48403 48404 3P 48392 48393 48394 48395 48396 48397 4P 48404 48405 48406 48407 48408 48409 Type HA/HF 800/1600 A 2000 A 2500 A 3200 A 4000 A 4000b/6300 A Communication option Modbus COM Digipact COM Chassis 33852 33855 + Switch-disconnector 48384 48388 Auxiliaries and accessories: b for drawout devices: see page 26 b for fixed or drawout devices: see page 30 Source changeover assembly: see page 30 BTP207E-50200-NW.fm/34 Schneider Electric Masterpact: price list NW08 to NW63 drawout switch-disconnectors (cont.) Unit price (excl.VAT) in French francs Switch-disconnector selection (cont.) E46450 Chassis front connection Top Bottom Top Bottom Top Bottom 3P 48415 48418 48413 48414 48416 48419 4P 48441 48444 48417 48420 48442 48445 800/2000 A 800/1600 A type L1 2500/3200 A 2000 A types H3/L1 Top Bottom Top Bottom 3P 48133 48138 48134 48139 4P 48158 48163 48159 48164 4000 A Top 48135 48160 Bottom 48140 48165 Top 48136 48161 Bottom 48141 48166 Top 48137 48162 Bottom 48142 48167 Top Bottom Top Bottom Top Bottom Top Bottom 3P 48143 48148 48144 48149 48145 48150 48146 48151 4P 48168 48173 48169 48174 48170 48175 48171 48176 800/1600 A 2000 A 2500/3200 A Chassis rear connection E46445 Vertical connection 4000b/5000 A 6300 A E46446 Horizontal connection 800/2000 A 800/1600 A type L1 2500/3200 A 2000 A types H3/L1 4000 A 4000b/5000 A E46428 Rear connection accessories Schneider Electric Interphase barriers 3P/4P (3 parts) 48600 BTP207E-50200-NW.fm/35 Masterpact: price list Retrofit solutions Connection for fixed devices Unit price (excl.VAT) in French francs To replace a Masterpact M with a Masterpact NW, order a retrofit device (without connections) and select a set of connectors corresponding to the replaced device. The Masterpact NW is installed in exactly the same place as the old Masterpact M device, without any modifications required on the switchboard. Horizontal rear connection Device to be replaced Connection to be ordered Masterpact M08 to M12 Type N1/NI Top Bottom Type H1/H2/HI/HF Top Bottom 3P 3 x 48951 3 x 48964 4P 4 x 48951 4 x 48964 3 x 48954 3 x 48965 4 x 48954 4 x 48965 3 x 48954 3 x 48965 4 x 48954 4 x 48965 3 x 48957 3 x 48958 4 x 48957 4 x 48958 1 x 48962 1 x 48961 1 x 48960 1 x 48960 Masterpact M16 Type N1/NI/H1/H2/HI/HF Top Bottom Masterpact M20 and M25 Type N1/NI/H1/H2/HI/HF Top Bottom Masterpact M32 Type H1/H2/HI/HF Top Bottom BTP207E-50200-NW.fm/36 Schneider Electric Masterpact: price list Retrofit solutions (cont.) Connection for drawout devices Unit price (excl.VAT) in French francs To replace a Masterpact M with a Masterpact NW, order a retrofit device (without connections) and select a set of connectors corresponding to the replaced device. The Masterpact NW is installed in exactly the same place as the old Masterpact M device, without any modifications required on the switchboard. Vertical rear connection Device to be replaced Connection to be ordered Masterpact M08 to M12 Type N1/NI Top Bottom Type H1/H2/HI/HF Top Bottom 3P 3 x 48966 3 x 48966 4P 4 x 48966 4 x 48966 3 x 48969 3 x 48969 4 x 48969 4 x 48969 3 x 48969 3 x 48969 4 x 48969 4 x 48969 3 x 48970 3 x 48970 4 x 48970 4 x 48970 1 x 48974 1 x 48974 1 x 48978 1 x 48978 Masterpact M16 Type N1/NI/H1/H2/HI/HF Top Bottom Masterpact M20 and M25 Type N1/NI/H1/H2/HI/HF Top Bottom Masterpact M32 Type H1/H2/HI/HF Top Bottom Horizontal rear connection Device to be replaced Connection to be ordered Masterpact M08 to M12 Type N1/NI Top Bottom Type H1/H2/HI/HF Top Bottom 3P 3 x 48951 3 x 48964 4P 4 x 48951 4 x 48964 3 x 48954 3 x 48965 4 x 48954 4 x 48965 3 x 48954 3 x 48965 4 x 48954 4 x 48965 3 x 48957 3 x 48958 4 x 48957 4 x 48958 Masterpact M16 Type N1/NI/H1/H2/HI/HF Top Bottom Masterpact M20 and M25 Type N1/NI/H1/H2/HI/HF Top Bottom Masterpact M32 neutral on left-hand side Type H1/H2/HI/HF Top Bottom 1 x 48973 1 x 48973 1 x 48976 1 x 48977 Masterpact M32 neutral on right-hand side Type H1/H2/HI/HF Top Bottom Schneider Electric 1 x 48973 1 x 48973 1 x 48977 1 x 48976 BTP207E-50200-NW.fm/37 Masterpact: price list Communication bus accessories and Display Modules Unit price (excl.VAT) in French francs Display modules DMB300 Max. 4 breakers 50894 4900 Color display module Max. 16 breakers 50895 13388 50959 1715 CJB306: 6 SubD 9 pins connectors junction block 50963 502 CSD309: 9 pins SubD with screw terminals 50964 220 CDM303: display module pre-wired cable, 3 m length 50960 268 CCP303: Masterpact or Compact pre-wired cable (4 RS485 wires + 2 power wires) 3 m length 50961 192 E67954 Monochrome display module E67955 DMC300 Spare parts DMC300PCM: DMC300 memory card RS485 Modbus pre-wired system E67958 RS485 Modbus junction block E67959 RS485 Modbus connector E79015 E67960 RS485 Modbus cables 50965 2129 50823 6737 50778 411 50779 50780 385 1883 50786 TSX SCA72 174 CEV 300-10 3050 EGW2 8194 (1) (1) (2) E67961 CCR301: RS485 roll cable (2 RS485 wires + 2 power wires) 60 m length Digipact Bus pre-wired system Data concentrator DC150 110-240 V AC, 50/60 Hz and 115-125 V DC E79014 Auxiliary supply voltage Junction block E67956 Junction block for internal Bus Cables E67957 Cable for internal bus 20-meter roll (0.75 mm2) 100-meter roll (0.75 mm2) Converter RS485/RS232 (ACE909) 12 V DC power supply included RS485/RS232 RS485/Ethernet RS485/Ethernet (SMS compatible) (1) see catalogue Telemecanique. (2) see catalogue Square D. BTP207E-50200-NW.fm/38 Schneider Electric Masterpact: price list Order form Masterpact NT and NW Unit price (excl.VAT) in French francs To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles Basic device Quantity Masterpact type NT, NW Frame size 06 to 63 Sensor rating A Circuit breaker N1, H1, H2, H3, L1 Switch-disconnector NA, HA, HF Number of poles 3 or 4 Option : Neutral on right side Type of device Fixed Drawout with chassis Chassis alone Drawout without chassis Locking VBP - ON/OFF pushbutton locking OFF position locking VCPO - by padlocks Locking kit VSPO - by keylocks without keylocks 1 lock VSPD - chassis locking in ''disconnected'' position VPEC - door interlock Micrologic control unit A - ammeter 2.0 A P - power meter 5.0 A 6.0 A 7.0 A 5.0 P 6.0 P 7.0 P H - harmonic meter 5.0 H 6.0 H 7.0 H TCE - external sensor (CT) for neutral + earth-fault protection TCE - external sensor (CT) for double neutral protection (Micrologic P and H with 3-poles) TCW - external sensor for SGR protection Rectangular sensor 280 x 115 for earth-leakage 470 x 160 protection LT - long-time rating plug (standard setting 0.4 to 1 x Ir) Low setting option 0.4 to 0.8 Ir High setting option 0.8 to 1 Ir LT OFF option PTE - external voltage measurement input AD - external power-supply module BAT - battery module Communication COM Eco COM Digipact Modbus Modbus Connection Horizontal Top Vertical Top Front Top Bare-cable connectors 4 x 240 mm2 + connector shield Vertical-connection adapters Cable-lug adapters Interphase barriers Spreaders Disconnectable front-connection adapter Bottom Bottom Bottom Schneider Electric 1 lock + 1 lock with same key profile 2 locks (different key profiles) for NW Locking kit Profalux Ronis without keylocks 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) Optional connected - disconnected - test position locking Latch on right-hand side of chassis Latch on left-hand side of chassis Indication contacts OF - ON/OFF indication contacts Standard 4 OF 6 A - 240 V AC (10 A - 240 V AC and low-level for NW) Max. 4 qty Alternate 1 OF low-level for NT (replaces a standard contact) Additional 1 block of 4 OF for NW EF - combined ''connected/closed'' contacts 1 EF 5 A - 240 V AC for NW 1 EF low-level for NW SDE - ''fault-trip'' indication contacts 1 SDE 5 A - 240 V AC Standard Additional 1 SDE 5 A - 240 V AC 1 SDE low-level Programmable contacts 2 M2C contacts 6 M6C contacts Carriage switches low-level 6 A - 240 V AC CE - ''connected'' position Maxi. 3 for NT and NW Maxi. 2 for NT and 3 for NW CD - ''disconnected'' position Maxi. 1 for NT and 3 for NW CT - ''test'' position AC - actuator for additional carriage switches Max. 2 qty Max. 8 Max. 8 qty qty qty qty qty qty Remote operation Remote ON/OFF Remote tripping VO - safety shutters on chassis NT, NW VIVC - shutter position indication NW and locking Key for Micrologic control units: 2.0 : basic protection (long-time + inst.) 5.0 : selective protection (long-time + short-time + inst.) 6.0 : selective + earth-fault protection (long-time + short-time + inst. + earth-fault) 7.0 : selective + earth-leakage protection (long-time + short-time + inst. + earth-leakage) Ronis VPOC - racking interlock IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW VDC - mismatch protection NT-FC fixed NT-FC, fixed, draw. NT-FC, fixed, draw. NT, NW-fixed, draw. NT-fixed, drawout NW-fixed Profalux MCH - gear motor XF - closing voltage release MX - opening voltage release PF - ''ready to close'' contact V V V low-level 6 A - 240 V AC BPFE - electrical closing pushbutton Res - electrical reset option RAR - automatic reset option MN - undervoltage release V R - delay unit (non-adjustable) Rr - adjustable delay unit 2nd MX - shunt release V Accessories CDM - mechanical operation counter CB - auxiliary terminal shield for chassis CDP - escutcheon CP - transparent cover OP - blanking plate Brackets for mounting on backplates BTP207E-50200-NW.fm/39