technical catalogue

advertisement
Building Management Controls & Peripherals
Electrical, Panel Accessories & Cable Management
TECHNICAL CATALOGUE
VOLUME 3
E.C.Products
Building Management Controls & Peripherals
Welcome
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Welcome to this new E. C. Products Limited Technical
Catalogue. Here you will find all the technical information,
installation/connection details for our updated range of
Building Management Controls and Peripherals as well as
our range of Industrial Electrical Controls and Panel & Cable
Accessories including AC Contactors, thermal overloads,
miniature circuit breakers relays, and a range of accessories for
installation. The price list attached is correct at the time of going
to press but please check the website for the latest prices and
any offers that may be available.
E. C. Products Limited (ECP) are dedicated to providing you
with the highest quality products at the most competitive prices
and to ensure that the quality and price is maintained, we
have worked very closely with our suppliers from throughout
the World to bring you a very real alternative to your current
provider of Peripherals and Control Gear.
Our aim is to provide you with the best possible service and
customer support. Many of the products you will find here are
available for next day delivery from our extensive stock and
we are always willing to offer assistance and technical support
when you need it most. Also, if the product you require is not
listed in this Catalogue, then a multitude of alternative products,
sizes and colours can be provided to order within a short
delivery period. Contact our office for details.
Thank you for taking the time to look through this Catalogue,
we would welcome the opportunity to become your preferred
supplier of these products. Please contact us should you require
further information about how we may be able to assist you.
2
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
AV-DP Differential Air pressure
and Velocity Transmitter
EP-TF72
Thermal Fuse
GS-CMD5B
Carbon Monoxide Sensor
Page 6
Page 20
Page 27
R600
Protection Relays
MIX18
Modbus & BACnet
PAG
Magnehelic Gauges
Page 36
Page 48
Page 61
EBMPIR
Batten Mount PIR
LDP
Liquid DP Switch
TE-AL
Anti– Ligature Sensor
Page 52
Page 63
Page 74
TE LP
Low Profile Sensors
TE-ET
Telescopic Sensor
TS-ET2 Electronic Multi stage
Thermostat
Page 75
Page 76
Page 89
FA
Panel Vetilation
ENC DED
Hinged Door Enclosure
Xenon Beacons
Page 105
Page 106
Page 119
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
New products
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
3
Contents
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
4
E.C.Products
Building Management Controls & Peripherals
Contents
4–20mA Temperature������������������81
Fan speed controllers�������������������12
Radiant temperature sensors�������� 73
Air pressure������������������������������� 57
Flying lead temperature sensors��� 77
RCBO�������������������������������������� 113
Air velocity���������������������������������� 5
Gas leak������������������������������������31
RCCB�������������������������������������� 112
Anti-ligature temperature sensors���74
Gas sensors������������������������������ 25
Relays & bases�������������������������� 34
Averaging temperature sensors�����75
Gas valves�������������������������������� 28
Room temperature sensors����������� 71
Ball valves��������������������������������� 96
Humidity����������������������������������� 69
Selector Switches���������������������� 116
Bespoke�����������������������������������107
Immersible temperature sensors�����76
Shoe valves������������������������������� 98
Busbar�������������������������������������120
Inverters������������������������������������ 33
Smoke detection������������������������ 32
Butterfly valves��������������������������� 97
IO modules������������������������������� 37
Solenoid valves�������������������������� 99
Button temperature sensors���������� 73
Isolators����������������������������������� 111
Strap-on temperature sensors������� 80
Cable��������������������������������������125
Lighting control�������������������������� 49
Telescopic temperature sensors�����76
Cable glands����������������������������120
Liquid pressure��������������������������� 62
Temperature charts��������������������� 82
Ceiling sensor���������������������������� 72
Low profile temperature sensors����75
Terminals��������������������������������� 121
Condensation sensors����������������102
Mains switch isolators���������������� 112
Thermostats������������������������������� 86
Contactors�������������������������������108
MCB��������������������������������������� 113
Thimble temperature sensors���������74
Contents������������������������������������� 4
MCB enclosures������������������������ 111
Thyristors����������������������������������� 65
Controllers���������������������������������� 8
Metering����������������������������������� 53
Timers��������������������������������������103
Current��������������������������������������14
Modbus IO modules������������������� 48
Water leak�������������������������������101
Damper actuators�����������������������18
Moror starters��������������������������� 110
Window temperature sensors������ 80
DIN Rail�����������������������������������120
Outside temperature sensors�������� 72
Wind speed�������������������������������� 7
Duct temperature sensors������������ 78
Overloads��������������������������������109
Wiring accessories��������������������123
Emergency���������������������������������19
Panel lamps������������������������������ 117
Xenon beacons������������������������� 119
Enclosures��������������������������������106
Power supplies��������������������������� 67
Zone valves����������������������������� 100
Fan coil controllers����������������������12
Pressure independent valves�������� 95
Fan coil valves��������������������������� 93
Push Buttons����������������������������� 114
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Duct Air Velocity Sensors AV
Description
Technical Specification
The AV range of Air Velocity Sensors are designed to measure
the air velocity in HVAC ducts and provide a linear 0...10Vdc
output signal across the range. The unit operates on a thermal
principle based upon the cooling effect from the air speed.
Features
•Economical air velocity sensors
•0...10Vdc output
•Choice of measuring range
Part Code
Description
AV-4
Duct Air Velocity Sensor 0...4 m/s
AV-8
Duct Air Velocity Sensor 0...8 m/s
AV-16
Duct Air Velocity Sensor 0...16 m/s
Power Supply:24Vac/dc
Output Signal:0...10Vdc
Accuracy:
± 1% at mid range at 20°C
Response Time: < 2 seconds
Probe:
8mm diameter aluminium x 200mm long
Temperature:–10…+60°C
Humidity:
0...80% RH
Air velocity
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Air Flow Probes AV-FP
Description
Technical Specification
The AV-FP range of economical air flow sensors sense
differential (velocity) pressure of VAV units and other locations
in main or branch ducts. Four different lengths allow selection
of the sensor to yield accurate readings on terminal unit inlet
diameters from 100mm to 500mm.
The sensor operates by measuring the velocity pressure using a
differential pressure transmitter such as the PA-LP.
Mounting:
Integral flange with gasket
Connections: ¼” nipples for 3/8” OD polyethylene tubing
Weight:31g
Ambient:
0°C to 50°C
Dimensions
Features
•Economical air flow sensors
•Integral flange and gasket
•Choice of four different lengths
•Connections for ¼“ tubing
•Ideal for VAV units
Part Code
Description
Dim A
Sensing
points
AV-FP1002
80mm air flow probe
80mm
1 set
AV-FP1003
140mm air flow probe
140mm
2 sets
AV-FP1004
195mm air flow probe
195mm
3 sets
AV-FP1005
250mm air flow probe
250mm
4 sets
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
5
E.C.Products
Building Management Controls & Peripherals
Air velocity
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Multi-point Air Flow Probes AV-MP
Description
The AV-MP range of Air Velocity Pitot Tubes can be used with
our ranges of Air Differential Pressure Sensors to calculate
airflow in larger ducts or in areas of turbulent airflow. The
units come in pairs suitable for duct sizes up to 2 metres (larger
upon request).
Features
•Polished Stainless Steel or Grey ABS
•Gaskets included for duct sealing
•Push on connectors for 6mm ID PVC tubing
•Use with DF or PA-LP range of Air DP sensors
Description
AV-MP600
Multi-point Velocity Probe - 600mm
AV-MP700
Multi-point Velocity Probe - 700mm
AV-MP800
Multi-point Velocity Probe - 800mm
AV-MP1000
Multi-point Velocity Probe - 1000mm
AV-MP1250
Multi-point Velocity Probe - 1250mm
AV-MP1500
Multi-point Velocity Probe - 1500mm
AV-MP1750
Multi-point Velocity Probe - 1750mm
AV-MP2000
Multi-point Velocity Probe - 2000mm
For ABS, add: /ABS
Other sizes available to order
Technical Specification
Probe:
Nipples:
Flange:
Lengths:
Part Code
26mm Diameter Polished Stainless Steel or Grey ABS
Plated brass to suit 6mm ID PVC tubing
52mm diameter Chromed cast Steel
See part codes
Transmitter For Air Velocity and Differential Pressure AV-DP
Description
Technical Specification
The AV-DP Differential Pressure Transmitter is an extremely
versatile transmitter for monitoring pressure and air velocity.
This compact package is loaded with features such as field
selectable English or Metric ranges, Adjustable damping of
output signal and the option to select a square root output for
use with pitot tubes and other similar flow sensor.
Features
•Field upgradeable LCD display
•Five ranges available
•Plug in Display Available
•Selectable Air Velocity or Diff. Pressure
Part Code
Description
AV-DP-100V
Air DP Transmitter 25, 50, 100 Pa 0-10V
AV-DP-100
Air DP Transmitter 25, 50, 100 Pa 4-20mA
AV-DP-1250V Air DP Transmitter 250, 500, 1250 Pa 0-10V
AV-DP-1250
Air DP Transmitter 250, 500, 1250 Pa 4-20mA
AV-DP-2000V Air DP Transmitter 2kPa 0-10V
AV-DP-2000
Air DP Transmitter 2kPa 4-20mA
Measured Media:Air and non-combustible, compatible
gases.
Accuracy:±1% for 50, 100, 500, 1250 Pa, 2, 3,
5 kPa
±2% for 25, 250 Pa
Stability:
±1% / year FSO.
Temperature Limits:
–18 to 66°C.
Pressure Limits:6.8 kPa maximum operation; 68kPa,
burst.
Supply:10-35Vdc (2-wire); 17-36 Vdc or
isolated 21.6-33Vac (3-wire).
Output Signals:
4-20mA (2-wire); 0-10V (3-wire).
Response Time:Adjustable 0.5 to 15 sec. time
constant. Provides a 95% response
time of 1.5 to 45 seconds.
Zero & Span Adjustments:Digital push button.
Current Consumption:
40 mA max.
Display (optional):
4 digit LCD.
Electrical Connections:1.5mm²
Process Connections: 5 mm ID Tube
Enclosure Rating:
NEMA 4X (IP66).
Mounting Orientation: Diaphragm in vertical position.
AV-DP-3000V Air DP Transmitter 3kPa 0-10V
AV-DP-3000
Air DP Transmitter 3kPa 4-20mA
AV-DP-5000V Air DP Transmitter 5kPa 0-10V
6
AV-DP-5000
Air DP Transmitter 5kPa 4-20mA
AV-DP-LCD
Plug-in Display
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Wind Speed & Direction Sensor AV-WS
Description
Technical Specification
The AV-WSD wind speed and direction sensor provides
wind speed and direction measurements and converts those
measurements into a potentiometric or pulsed output which can
be read by a PLC or Building Management System.
Features
•Converts wind speed to a pulsed output
•Zero bounce contact closure output
Part Code
Description
AV-WSS
Wind Speed Sensor
AV-WSD
Wind Speed & Direction Sensor
Electrical conn:
Flying lead 3m long
Ambient temperature:–20°C/+70°C
Dimensions:
Height 280mm
Protection:IP65
Weight:500g
Wind speed output:
1 contact closure per 1.493m/s
(zero bounce)
Min. start speed:
0.5 m/s
Accuracy:±2%
Contact rating:
50W, 100Vdc max, 1A
Direction output:
0-1KΩ for 0-357°
Mechanical travel:
360° endless travel
Electrical travel:
357° (±2°)
Resistance tolerance:±3%
Linearity tolerance:±0.5%
Wind speed
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Wind Speed & Direction Sensor AV-WSD
Description
Features
The AV-WSD combined Wind Speed and Direction sensor
is manufactured from anodized aluminium alloy, UPVC and
stainless steel with moulded polypropylene cups. The units are
lightweight yet very robust.
The sensors are designed to be mounted to a mast of between
30...50 mm diameter by means of a V-shaped clamp and
bracket. This allows simple orientation to North using the
compass provided; the only setting up required.
Wind Direction is sensed by a precision conductive
potentiometer which combines exceptionally long life with
high sensitivity.
Wind speed is derived from a Hall Effect solid state magnetic
switch activated by magnets in the cup rotor running in
precision stainless steel ball race and ‘Oilite’ bearings giving
very high sensitivity and very long life.
Part Code
Description
AV-WSD-10
Wind speed and direction sensor 0...10V
AV-WSD-20
Wind speed and direction sensor 4-20mA
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
•Converts wind speed to a 0...10Vdc or 4-20mA output
•Converts wind direction to a 0...10Vdc or 4-20mA output
•Lightweight and robust
Technical Specification
Electrical connection: 4-core cable 25m supplied as standard
Weight:250g
Wind speed output:
0...10Vdc range 0...50m/s
OR 4-20mA
Accuracy:±5%
Direction output:
0...10Vdc range 0...360°
OR 4-20mA
Mechanical travel:
360° endless travel
Resistance tolerance:±5%
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
7
E.C.Products
Building Management Controls & Peripherals
Controllers
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
1 Channel Electronic Thermostat CAD-1DS
Description
Technical Specification
The CAD-1DS is a DIN rail mountable single channel electronic
thermostat compatible with Building Management Systems. The
unit monitors air or liquid temperatures and controls one user
programmable switching relay in response.
Features
•Wide temperature range
•Night setback input
•Heating or cooling function
•Digital LED display with temperature
•DIN rail mountable, small footprint
8
Part Code
Description
CAD-IDS
1 channel electronic thermostat
CAD-POT
Remote setpoint adjuster
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Input Supply: 24Vac/dc ±15% 35mA max.
230Vac 1VA
Sensor Type:
Any 10KΩ Type T sensor from our range
Temp. Range:
–5°C to +95°C
Differential:1-10°C
Output Signal: 1 x C/O relay contact 10(5)A @ 240Vac
Mounting:
DIN rail carrier 91 x 82 x 51 mm
Terminals:
Rising clamp suitable for 0.5-2.5mm²
Ambient:
–20°C to +50°C
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
2/8 Channel Electronic Thermostat CAD-2DS
Relay Expansion Module CAD-XR2
Description
Technical Specification
The CAD-2DS is a DIN rail mountable single channel electronic
thermostat compatible with Building Management Systems. The
unit monitors air or liquid temperatures and controls up to eight
user programmable switching relay in response.
The CAD-XR2 is a DIN rail mountable two relay expansion
module for use with CAD-2DS electronic thermostat to provide
up to eight user programmable switching relays.
Features
•Wide temperature range
•Night setback input
•Heating or cooling function
•Digital LED display with temperature
•Adjustable stage and inter-stage differential
•Use CAD-XR2 with CAD-2DS to expand outputs
•DIN rail mountable, small footprint
Input Supply: 24Vac/dc ±15% 150mA max.
230Vac 6VA
Sensor Type:
Any 10KΩ Type T sensor from our range
Temp. Range:
–5°C to +95°C
Differential:1-10°C
Output Signal: 2 x C/O relay contact 10(5)A @ 240Vac
6 x optional plug-in relays with CAD-XR2
Terminals:
Rising clamp suitable for 0.5-2.5mm²
Ambient:
–20°C to +50°C
Part Code
Description
CAD-2DS
2/8 channel electronic thermostat
CAD-XR2
2 relay expansion module
CAD-POT
Remote setpoint adjuster
Controllers
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Room Temperature Controller RTR-S
Description
Technical Specification
The RTR-S series are proportional temperature controllers for
room applications and are available with selectable internal or
external sensor and both heating and cooling outputs.
Units can be supplied with numerical scale setpoint adjustment
or simple ±8K adjustment around a fixed setpoint. The
RTR-S014/015 also includes a fan speed selector switch.
Features
•Choice of setpoint adjustment
•Heating and Cooling outputs
•LED indication
Power Supply: 24Vac/dc
Temperature Sensor: Internal or External PT1000
Control Range:
RTR-S012/014: +5…+30°C
RTR-S013/015: 21°C ±8
Outputs:
1 x heating and 1 x cooling
0...10V or 10...0V selectable
Proportional Band:
Internally adjustable +0.5…+3K
Neutral Zone:
Internally adjustable +1…+3K
Current Consumption: max. 5 mA
Enclosure: Pure White ABS
Dimensions: 95 x 97 x 30 mm
Electrical Connections: up to 2.5mm² via screw terminals
Humidity:
<90% RH, non-precipitating
Protection:IP30
Part Code
Description
RTR-S012
Room temperature controller +5…+30°C
RTR-S013
Room temperature controller 21°C ±8
RTR-S014
Room temperature controller +5…+30°C with fan speed switch
RTR-S015
Room temperature controller 21°C ±8 with fan speed switch
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
9
E.C.Products
Building Management Controls & Peripherals
Controllers
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
2 channel Temperature controller CAD-PI
Description
Technical Specification
The CAD-PI is a DIN rail mountable single (optionally up to 3)
channel electronic proportional temperature controller. The unit
monitors air or liquid temperatures and controls from one to
three proportional analogue channels.
Features
•One proportional channel, two extra optional
•Night setback input
•Heating, cooling or both function
•Digital LED display with temperature
Part Code
Description
CAD-PI
1 channel temperature controller
CAD-XM1
1 channel expansion module
Input Supply:
24Vac/dc ±15% 75mA max.
Sensor Type:
Any 10KΩ Type T sensor from our range
Temp. Range:
–5°C to +95°C
Span:1-20°C
Output Signal:
1 x 0...10V proportional (2 more optional)
Mounting:
DIN rail carrier 114 x 82 x 60 mm
Terminals:
Rising clamp suitable for 0.5-2.5mm²
Ambient:
–20°C to +50°C
Proportional & Integral Temperature Controller CR-PI
Description
Technical Specification
The CR-PI DIN rail mounted controller is a compact and cost
effective solution for monitoring air or liquid temperature. The
units have two analogue outputs as standard, remote setpoint
potentiometer input, temperature sensor input, low limit sensor
input and setback input. The outputs can be used to control
various terminal devices ie. damper motors, valve actuators,
step controllers, relay modules, power controllers etc.
Features
•2 Analogue Outputs - Heating and/or Cooling
•Proportional and Integral Control
•Remote Setpoint option
•Adjustable Setback
•0-10V or 2-10Vdc Output
•Adjustable Proportional band
•Adjustable Integral time
•Output Voltage can be displayed
•Monitors Minimum & Maximum Temperatures
•DIN rail mounting
10
Part Code
Description
CR-PI
2 channel temperature controller
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Power Supply:
24Vac ± 10% 24Vdc +10/–0%
Power Consumption: Typical 40mA
(approx 120mA when LCD in use)
Inputs:
Control Temperature: –10...110°C
Low Temperature: –20...+ 20°C
External Setpoint: 1...11K ohm
Setback Volt free contact or Open collector
Output Signal:
2 x 0...10Vdc or 2...10Vdc
LCD Display:
2 Line 8 digit LCD
Set Up Pushbuttons: Increase, Menu, Decrease
Set Up Values:
Setpoint: –10…+110°C
Low Limit: Off, –20...+20°C
Setback: 0...30°C
Deadband: 0...30°C
Proportional Band: 1...30°C
Integral Time: Off, 1...500 secs
Mode: Cool-Cool, Heat-Cool, Heat-Heat
Setpoint: None, ±4°C, ±20°C
Output Values: 0 to 10V, 2 to 10V
Temperature Element:10K3A1
Dimensions:
82 x 68 x 47mm
Weight:
85 gms
Terminals:
Terminals for 0.5 to 2.5mm2 cable
Ambient Range:
0 to 50°C
Country of Origin: United Kingdom
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Setpoint Adjuster SP10V
Description
Technical Specification
The SP-10V is ideal for control of devices which require a 0-10V
analogue signal. This can be used for commissioning purposes
or for manual control between 0-100%
Features
Power Supply:24Vac/dc.
Output Signal:0...10Vdc.
Connection:
1.5mm Rising Cage Terminal
Dimensions:
86 x 86mm
Controllers
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
•Flush Mount on single gang box.
•24Vac/dc power supply.
•Control of multiple devices.
•Standard finish white, other finishes available
Part Code
Description
SP10V
0-10V Setpoint adjuster
Setpoint Adjuster SP10K
Description
Technical Specification
The SP-10K is ideal for control of devices which require a
1-11KΩ resistive signal. This can be used for commissioning
purposes or for manual control.
Output Signal:1-11KΩ.
Connection:
1.5mm Rising Cage Terminal
Dimensions:
86 x 86mm
Features
•Flush Mount on single gang box.
•Passive device
•Control of multiple devices.
Part Code
Description
SP10K
1-11KΩ Setpoint adjuster
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
11
E.C.Products
Building Management Controls & Peripherals
Fan coil controllers
Fan speed controllers
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
12
Fan Speed Controller FSC
Description
Technical Specification
The FSC Fan Speed Controller is a compact, TRIAC based
fan & motor control designed for HVAC markets. The unit can
automatically control most single phase AC fans and motors via
an analogue signal or temperature sensor. The units is available
in a choice of current ratings and an optional DIN rail mounting
kit or polycarbonate enclosure can be provided.
Features
•Temperature Sensor or 0...20mA/0...10Vdc control signal
•Fan On/Fan Off threshold adjustable
•Many selectable options
Power Supply:95-250Vac
Frequency:
47-64 Hz
Current Ratings:
See Part Codes below
Control Signals:
20K Temperature Sensor
0...20mA or 0...10Vdc
Fixed speed option also available
Fixed Speed settings:27...99%
Dimensions:
88.9 x 68.6 x 26.9/52.3 mm
Enclosure dimensions: 130 x 130 x 100 mm
Electrical Connections: up to 2.5mm² via screw terminals
Ambient:
–25°C…+70°C, <90% RH
(rating will derate above 40°C)
Protection: IP20
Floating/Modulating Thermostat SRE05
Description
Technical Specification
SRE05 floating/modulating thermostat is mainly used for
air conditioning, heating and cooling systems. It uses a 10K
NTC Temperature sensor, providing temperature control for
Air conditioning and fan coil cooling/heating by means of a
control signal When the thermostat is powered on or off, it will
output a return signal to fully close the valve.
Features
•Auto-return function when powered on or off.
•Power surge and instant pulse protection.
•Overtime protection function.
•LCD (with backlight) showing ambient temperature and state.
•Percentage display corresponding to DC voltage output value
(SRE05P & SRE05F).
•Selectable external temperature sensor (NTC thermistor).
•Cool/heat selection.
•Fits standard one gang back box
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Temperature range:10-30°C
Supply Voltage:
24Vac at 0.6VA (No load)
Accuracy:
+/- 0.5°C
External Sensor:10K3A1
Dimensions:
86 x 86 mm
Part Code
Description
SRE05P-24V
Temperature Control 0-10V
SRE05A-24V
Temperature Control on/off
SRE05F-24V
Temperature Control Floating 150sec
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Description
Fan coil controllers
Electronic Fan Coil Controller SRE06
Technical Specification For All Models
SRE06 thermostats are mainly used in central air-conditioning
and heating system. It provides temperature control for central
air-conditioning fan coil cool/heat motorized valves or other
actuating mechanism via a control signal which is produced by
comparing actual measured temperature and the temperature
setpoint. It can also control the fan blower of fan coil units and
adjust the fan speed
Accuracy:±0.5°C
Control range:10°c...30°C
Temperature sensor:
NTC thermistor 10KΩ
Operating temperature:0...55°C
Storage temperature:10...60°C
Ambient humidity:
90% rh maximum
Features
•Auto-return function when turn off or power on
•Power surge and instant pulse protection
•Large LCD shows the ambient temperature, state and
air volume
•With system switch and fan speed switch
•Internal or external temperature sensor (NTC thermistor)
•Cool/Heat shift (summer or winter)
•With ABS fireproof plastic, compliance with UL-94 standard
•With flexible installation and convenient wire-connection
Model Specific Technical Specification
SRE06A (Heat/Cool)
SRE06B (Cool Only)
SRE06C
SRE06F
SRE06P
Power supply:
AC24V
AC230V
AC24V
AC230V
AC24V
AC230V
AC24V
AC230V
Output:
AC24V 1A
AC230V 1A
AC24V 1A
AC230V 1A
AC24V 1A
AC230V 1A
DC0-10V
10mA
DC0-10V
5mA
5VA
0.6VA
5VA
0.6VA
5VA
0.6VA
5VA
AC230V
(2A)
AC24V (2A)
AC230V (2A)
AC24V (2A)
AC230V (2A)
AC24V
(2A)
AC230V
(2A)
Power consumption: 0.6VA
Fan voltage:
AC24V
(2A)
Control range:
–
–
–
–
>150s OR >300s (optional)
–
–
Return time:
–
–
–
–
Total runtime for valve in the
same direction >150s (>300s),
uses overtime protection state
–
–
Part Code
Description
SRE06A-24
24V On/Off Thermostat - Heat or Cool
SRE06A-230
230V On/Off Thermostat - Heat or Cool
SRE06B-24
24V On/Off Thermostat - Cool only
SRE06B-230
230V On/Off Thermostat - Cool only
SRE06C-24
24V On/Off Thermostat - Heat & Cool
SRE06C-230
230V On/Off Thermostat - Heat & Cool
SRE06F-24
24V Floating Output Thermostat
SRE06F-230
230V Floating Output Thermostat
SRE06P-24
24V Modulating Output Thermostat
SRE06P-230
24V Modulating Output Thermostat
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
13
E.C.Products
Building Management Controls & Peripherals
Current
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
AC Current Switches CSW
Description
Technical Specification
The CSW series of AC current switches activate a normally
open (NO) contact closure via a solid-state switch whenever
the monitored primary circuit current exceeds a pre-set level.
Models are available to switch various load types, feature
integral LEDs to indicate device power and also the switch
status and can be provided in solid or split core configuration.
The CSW-Axx models include a multi-turn adjustment to set the
trip threshold to the desired value and the CSW-Fxx models
operate as a go/no-go status indicators with a factory set
minimum threshold value. The switches can monitor up to 200
Amps continuous and feature an auto-range circuit to eliminate
manual jumpers. All models are UL, CE and RoHS compliant.
The CSW series current switches are accurate, reliable, easy
to install and require less servicing than differential pressure
switches, or flow switches.
Power Supply:
Setpoint:
Output Switch:
Hysteresis:
Response Time:
Enclosure Size:
Enclosure Material:
Conductor Hole Size:
Operating Temperature:
None: self-powered
Solid core - 0.5A...200A
Split core - 1.5A...200A
(CSW-F fixed at 0.5A)
Solid state 0.3A @ 135V ac/dc
ASx2 1A @ 250Vac
< 2% FS max.
< 200 mS
Solid core - 61 x 90 x 25 mm
Split core - 63 x 100 x 32 mm
UL 94V-0 flammability rated ABS
Solid core - 19mm diameter
Split core - 22.6 x 22.6 mm
–25°C to + 70°C
The CSW series current switches can be used to monitor
devices with a maximum continuous operating current of up to
200 Amps and the power supply is induced from the conductor
being monitored. All of these units come with an unconditional
5 year limited warranty.
Features
•Auto-ranging up to 200A
•Power induced from monitored conductor
•True digital switching and very low leakage
•Choice of output rating
•Fixed or adjustable setpoint
•Five Year Warranty
14
Part Code
Description
CSW-NO-FSD
Solid Core Fixed Setpoint Current Switch
CSW-NO-FSP
Split Core Fixed Setpoint Current Switch
CSW-NO-ASD
Solid Core Adjustable Setpoint Current Switch 0.3A @ 135Vac/dc
CSW-NO-ASP
Split Core Adjustable Setpoint Current Switch 0.3A @ 135Vac/dc
CSW-NO-ASD2
Solid Core Adjustable Setpoint Current Switch 1A @ 250Vac
CSW-NO-ASP2
Split Core Adjustable Setpoint Current Switch 1A @ 250Vac
DRC
Din rail clip
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Analogue Output Current Sensors CS
Description
Technical Specification
The CS series current sensors monitor the current flowing to
electrical equipment or buildings. The magnitude of this current
is then converted into a linear 4-20mA or 0 to 10 VDC output
signal, which can be monitored by a Building Management
System. The units have jumper selectable input ranges. These
current sensors should be used in load trending (current
monitoring) type applications and are fast acting, accurate,
reliable, and extremely easy to install.
All of the current sensors come with a limited five year factory
warranty
Features
•Jumper selectable current ranges
•0...10Vdc or 4...20mA outputs
•Version available for use with Variable Speed Drives
Part Code
Description
CS-SD10L
0...10 Vdc Solid Core 0...10/20/50A
CS-SD10
0...10 Vdc Solid Core 0...100/150/200A
CS-SP10L
0...10 Vdc Split Core 0...10/20/50A
CS-SP10
0...10 Vdc Split Core 0...100/150/200A
CS-SD420L
4...20mA Solid Core 0...10/20/50A
CS-SD420
4...20mA Solid Core 0...100/150/200A
CS-SP420L
4...20mA Split Core 0...10/20/50A
CS-SP420
4...20mA Split Core 0...100/150/200A
Power Supply:
0...10Vdc output - Self-powered
4...20mA output - nominal 24Vdc
supply
Selectable Ranges:
Low Range - 0...10/20/50A
High Range - 0...100/150/200A
Frequency:
40...100 Hz
(VSD Version 10...400Hz)
Insulation Class:
600Vac RMS
Accuracy: ± 1%
Response Time:
0.5 S
Enclosure Size:
Solid core - 61 x 90 x 25 mm
Split core - 63 x 100 x 32 mm
Enclosure Material:
UL 94V-0 flammability rated ABS
Conductor Hole Size: Solid core - 19mm diameter
Split core - 22.6 x 22.6 mm
Operating Temperature: –30°C to + 70°C
Certification: CE, UL and RoHS
Current
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
CS-SD420LT 4...20mA Solid Core 0...10/20/50A for use with variable speed drives
CS-SD420T
4...20mA Solid Core 0...100/150/200A for use with variable speed drives
DRC
Din rail clip
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
15
E.C.Products
Building Management Controls & Peripherals
Current
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Current Switches CS-x
Description
Technical Specification
The CS-x series current switches are available in a solid-core
or split-core with Normally-Open (N/O) output configurations.
All of these sensors will have a solid-state output with a fixed or
adjustable trip point (setpoint). These current switches are ideal
for providing status information on any type of AC current using
equipment. The solid-vcore units are an excellent choice for
new installations while the split-core versions are more suited
to retrofit or existing installations. The CS-x current switches are
accurate, reliable, easy to install, and require less servicing
than differential pressure switches, flow switches and paddle
wheels.
A current switch can be used to monitor fan and pump status,
motors, compressors, and any other electrical equipment for
proper operation. A change in the operating current may
indicate mechanical failure or that the unit has been turned off.
These current switches can be used to monitor devices with a
maximum continuous operating current of up to 250 Amps and
will not need to be externally powered, since the power for the
switch is induced from the conductor being monitored. Another
great feature of these current switches is that they include
“Status” LEDs that will indicate whether the current is above or
below the fixed trip point. All of these units come with a unique
35 mm Din Rail mounting flange and an unconditional 5 year
limited warranty.
Power Supply:
None - Self-powered
Setpoint:
CS-F - 0.5A
CS-FL - 0.2A
CS-FS - 2.5A
CS-FSL - 1.5A
CS-A - 1...250A
CS-AL - 0.5...250A
CS-AS - 3...200A
CS-ASL - 2...200A
Output Switch: 0.3A @ 200V ac/dc
Current Range:0...250A
Frequency:40...1kHz
Isolation Voltage:1270Vac
Enclosure Size: Solid core - 58 x 86 x 25 mm
Split core - 68 x 86 x 28 mm
Enclosure Material:
UL 94V-0 flammability rated ABS
Conductor Hole Size: 19.8mm diameter
Operating Temperature: –15°C to + 40°C
Certification:
CE, UL and RoHS
Features
•Lowest Operating Trip Points in the Industry
•LED Status Indication
•Integral Din Rail Mounting Flange
•Easy Installation, Non-Polarity Sensitive
•Accepts up to a 350 MCM Cable
•Operates up to 250 continuous Amps
•Limited 5 Year Warranty
•RoHS and WEEE Compliant
16
Part Code
Description
CS-F
Solid core fixed setpoint current switch, NO, 0.5A trip point, 0...250A
CS-FL
Solid core fixed setpoint current switch, NO, 0.2A trip point, 0...250A
CS-FS
Split core fixed setpoint current switch, NO, 2.5A trip point, 0...250A
CS-FSL
Split core fixed setpoint current switch, NO, 1.5A trip point, 0...250A
CS-A
Solid core adjustable setpoint current switch, NO, 1A to 250A trip point, 0...250A
CS-AL
Solid core adjustable setpoint current switch, NO, 0.5A to 250A trip point, 0...250A
CS-AS
Split core adjustable setpoint current switch, NO, 3A to 200A trip point, 0...250A
CS-ASL
Split core adjustable setpoint current switch, NO, 2A to 200A trip point, 0...250A
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Analogue Output Current Sensors CTA/CTV
Description
Technical Specification
The CTA/CTV Series current sensors monitor the current flowing
to electrical equipment or buildings. The magnitude of this
current is then converted into a linear 4...20 mA or 0...10Vdc
output signal, which can be monitored by your Building
Management, DDC, or PLC controller. All of these sensors have
jumper selectable input ranges. These current sensors should
be used in load trending (current monitoring) type applications.
The solid-core units are an excellent choice for new installations
while the split-core versions
are more suited to retrofit or existing installations. The current
sensors are fast acting, reliable, and extremely easy to install.
No additional din rail mounting clips are necessary, due to the
unique design of the integral din rail mounting flange.
All of these current sensors are factory calibrated using an NIST
Traceable standard and shipped with the jumper placed in the
largest jumper selectable range.
Power Supply:
CTV - Self-powered
CTE - +12...30Vdc
Output: CTV - 0...10Vdc
CTA - 4...20mA
Accuracy:±1%
Current Range:
0...250A (range as per code)
Frequency:30...1kHz
Isolation Voltage:1270Vac
Enclosure Size: Solid core - 58 x 86 x 25 mm
Split core - 68 x 86 x 28 mm
Enclosure Material:
UL 94V-0 flammability rated ABS
Conductor Hole Size: 19.8mm diameter
Operating Temperature: –15°C to + 40°C
Certification:
CE, UL and RoHS
Current
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
The CTA units must be externally powered using a +12 to 40
VDC power supply while the CTV are self-powered inducing the
supply from the monitored conductor.
All of these current sensors come with a limited five year factory
warranty.
Features
•Fast Response Time
•Integral Din Rail Mounting Flange
•Easy Wiring, Polarity Sensitive Output
•Accepts up to a 350 MCM Cable
•Operates up to 250 continuous Amps
•Highly Accurate
•5 Year Limited Warranty
Part Code
Description
CTV-50
0...10Vdc solid core current sensor, 0...10, 0...20, 0...50 A
CTV-250
0...10Vdc solid core current sensor, 0...100, 0...200, 0...250 A
SCTV-50
0...10Vdc split core current sensor, 0...10, 0...20, 0...50 A
SCTV-250
0...10Vdc split core current sensor, 0...100, 0...200, 0...250 A
CTA-50
4...20mA solid core current sensor, 0...10, 0...20, 0...50 A
CTA-250
4...20mA solid core current sensor, 0...100, 0...200, 0...250 A
SCTA-50
4...20mA split core current sensor, 0...10, 0...20, 0...50 A
SCTA-200
4...20mA split core current sensor, 0...100, 0...200 A
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
17
E.C.Products
Building Management Controls & Peripherals
Damper actuators
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
18
Belimo Damper Actuators
Description
Belimo damper actuators are suitable for motorised control
of dampers in air ducts, they are available in wide range of
torque ratings, voltages and control signals, available with
built in SPDT auxiliary end switches. Additional auxiliary end
switches can be added.
Without switch c/w switch
LM24A
LM24A-S
5Nm Actuator 24Vac/dc open/close
LM230A
LM230A-S
5Nm Actuator 230Vac open/close
NM24A
NM24A-S
10Nm Actuator 24Vac/dc open/close
NM230A
NM230A-S
10Nm Actuator 230Vac open/close
SM24A
SM24A-S
20Nm Actuator 24Vac/dc open/close
SM230A
SM230A-S
20Nm Actuator 230Vac open/close
GM24A
40Nm Actuator 24Vac/dc open/close
GM230A
40Nm Actuator 230Vac open/close
LM24A-SR
5Nm Actuator 24Vac/dc Modulating 0-10vdc
NM24A-SR
10Nm Actuator 24Vac/dc Modulating 0-10vdc
SM24A-SR
20Nm Actuator 24Vac/dc Modulating 0-10vdc
GM24A-SR
40Nm Actuator 24Vac/dc Modulating 0-10vdc
LF24
LF24-S
4Nm Actuator 24Vac/dc Spring Return
LF230
LF230-S
4Nm Actuator 230Vac Spring Return
NF24A
NF24A-S2
10Nm Actuator 24Vac/dc Spring Return
NF230A
NF230A-S2
10Nm Actuator 230Vac Spring Return
SF24A
SF24A-S2
20Nm Actuator 24Vac/dc Spring Return
SF230A
SF230A-S2
20Nm Actuator 230Vac/dc Spring Return
EF24A
EF24A-S2
30Nm Actuator 24Vac/dc Spring Return
EF230A
EF230A-S2
30Nm Actuator 230Vac Spring Return
GK24A-1
40Nm Actuator 24Vac/dc Super Cap Spring Return
LF24-SR
4 Nm Actuator 24Vac/dc Modulating 0-10vdc Spring Return
NF24A-SR
10 Nm Actuator 24Vac/dc Modulating 0-10vdc Spring Return
SF24A-SR
20 Nm Actuator 24Vac/dc Modulating 0-10vdc Spring Return
GK24A-SR
40 Nm Actuator 24Vac/dc Modulating 0-10vdc Spring Return
S1A
Auxiliary switch 1 x SPDT for use with LM, NM, SM, GM & GK
S2A
Auxiliary switch 2 x SPDT for use with LM, NM, SM, GM & GK
S2A-F
Auxiliary switch 2 x SPDT for use with LF, NF & SF
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Emergency Stop Buttons EP-EM
Description
Technical Specification
The EP-EM1 range of emergency stop switches are for use
in the manual shut down of systems in the event of fire or other
emergency.
Features
Reset Type:
Switch Rating:
Housing Dimensions:
EP-EM1, EP-EM1M, EP-EM1-S - Twist reset
EP-EM1K, EP-EM1M-K - Key reset
10(6)A @ 240Vac SPDT
80 x 73 x 50mm
Emergency
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
•Twist or key reset versions
•Metal Boxed Versions
•6A @ 230Vac rated
Part Code
Description
EP-EM1
Emergency stop button - twist reset
EP-EM1K
Emergency stop button - key reset
EP-EM1M
Metal Boxed Emergency stop button - twist reset
EP-EM1M-K Metal Boxed Emergency stop button - key reset
EP-EM1-S
Shrouded Emergency stop button - twist reset
Electro Thermal Link EP-TL2
Description
Technical Specification
The EP-TL2 is for installing in a position where a fire hazard
may occur, e.g. above boilers and interrupt the electrical supply
to a gas valve or alarm. The link consists of a cast aluminium
enclosure with a perforated cover having a temperature
sensitive fuse.
Switch Rating:
5A @ 240Vac SPDT
Melting Point:72°C
Housing Dimensions: 75 x 50 x 30mm
Features
•Pressed steel housing
Part Code
Description
EP-TL2
Electro Thermal Link
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
19
E.C.Products
Building Management Controls & Peripherals
Emergency
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Thermal Fuse EP-TF72
Description
Technical Specification
The EP-TF72 Thermal fuse is for detecting boiler overheat and
will cut the supply to a gas safety valve. It has been designed to
give a faster response time than the conventional metal cased
fuse, incorporating a 72°C thermal non-resettable fuse. The
housing will withstand 150°C
Features
Electrical rating:
230V @5 Amp
Switching Point:72°C
Housing Material: Flame retardant Poycarbonate+20%GF
Dimensions:
70mm Dia x 40mm
Conduit Entry:20mm
Electrical connection: Rising Clamp 0.5 to 2.5mm² cable
•Robust Moulding
•Easily accessible terminals
•Fast response time
•Well ventilated enclosure
Part Code
Description
EP-TF72
Thermal Fuse 72°C
Fireman’s Switch EP-FM
Description
Technical Specification
The EP-FM1 Fireman’s Switch is for use in the event of fire or
other emergency. Usually located at exits to gas plant rooms,
units are key operated 3 position latching switches. A key
guard with plastic window is available.
Switch Rating:
Keys:
Connections:
Dimensions:
6A @ 240Vac SPDT
2 supplied
4 x 100mm flying leads
86 x 86 x 50mm
Features
•3 position switch
•Normal/Off/Extract
•Supplied c/w two keys
•6A @ 230Vac rated
•Keyguard and replacement window available
20
Part Code
Description
EP-FM1
3 position fireman's switch
EP-FMKG
Key guard
EP-FMW
Replacement window for key guard
EP-FMHC
Hinged Cover
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Air Flow Switch FL-SL1E
Description
Technical Specification
The FL-DBSL is a paddle switch intended to monitor air flow
within a duct and provide a switched output on detection of
either a specific air velocity or flow failure.
Cut out Value:
Min - 1.0 m/s, Max - 8.0 m/s
Cut in Value:
Min - 2.5 m/s, Max - 9.2 m/s
Contacts: Dust-tight microswitch with SPDT contacts
Switch capacity: 15 (8) A, 24...250 Vac
Working: –40...+85 °C
10...90% r.h. (non condensing)
Internal duct temp: –10...+85 °C
Level:Brass
Paddles:
Stainless steel AISI 301
Housing:
Galvanized steel sheet plate, ABS cover
Storage:
-40...+85 °C
Protection:
IP65 on the external duct side
Size:
113 x 70 x 65 mm
Weight:
630 g
Features
•Adjustable switching point
•15A @ 230Vac rated
•Stainless steel paddle
Part Code
Description
FL-SL1E
Air Flow Switch
Flow & level
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Liquid Flow Switch FL-SF1K
Description
Technical Specification
The FS1 paddle switch is intended to monitor liquid flow within
pipes and provide a switched output upon detection of either a
specific flow rate or flow failure. The unit screws directly into a
1” BSPT boss and has adjustable paddle lengths.
Features
•Adjustable switching point
•15A @ 230Vac rated
•Stainless steel paddle
Part Code
Description
FL-SF1K
Liquid Flow Switch
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Operating temp:–20°C/+110°C
Materials:
Paddle - Stainless steel
Rod
- Brass
Encl.
- Thermoplastic
Protection:IP65
Switch rating:
15(8)A SPDT @ 230Vac
Weight:670g
Dimensions:
97 x 79 x 65mm (without paddle)
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
21
E.C.Products
Building Management Controls & Peripherals
Emergency
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Liquid Level Switch FL-SQ01
Description
Technical Specification
The FL-DBSQ is a float switch intended to monitor the liquid
level in a tank or vessel and provide a switched output for
local alarm, pump or valve control. The differential between
switching is equivalent to approximately 14mm. The unit mounts
into a 1” BSPT female boss. Access is not required to the inside
of the tank.
Features
•1” BSPT mounting boss
•15A @ 230Vac rated
•Polypropylene float
Mounting:
1” BSPT boss
Operating temp: Ambient 0°C/+70°C
Media 0°C/+110°C
Materials:
Float - Polypropylene
Rod
- Brass
Bellows– Phosphor bronze
Encl. - ABS
Protection:IP65
Switch rating:
15(8)A SPDT @ 230Vac
Weight:300g
Switching diff.:14mm
Part Code
Description
FL-SQ01-01
Liquid Level Switch - Brass
Liquid Level Switch RFS
Description
Technical Specification
Stainless steel level switch suitable for high or low level control
Features
•All Stainless Steel
•High temperature up to 120ºC
•Rugged hinge
•Optional DIN Plug
•½” thread
•External fitting
•Compact design
22
Part Code
Description
RFS-12P-2
Stainless steel level switch
RFS REDUCER
1” adaptor
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Mounting:
1/2” BSPT
Operating Temp:–40/120°C
Material:
Float Stainless Steel 316
Body Stainless Steel 304
Connection:
Din Plug
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Level Switches FL-xMS
Description
Technical Specification
A range of Level Switches designed for high and low liquid
level detection in tanks and vessels. Units consist of a lever arm
reed switch assembly and a tank fixing assembly. Units fit from
the inside of the tank and tighten on to a back nut and are
available for top or side mounting.
Features
•Low cost solution
•Top or side mounted versions
Technical Specification
FL-SMS:
Contact Form:
Installation Dependant
Switching Voltage Max. V:
240 Vac / 200 Vdc
Switching Current Max. A:0.5
Carry Current Max. A:1.0
Switching Capacity Max. VA:50W
Contact Resistance Max. mOhms:200
Lead Wire:
XLPE AWG22
Reversible Switch Action:YES
Operating Pressure Max. Kg/cm2:4.0
Operating Temperature Deg.°C: –20° +80°
Material:Polypropylene
Suitable Specific Gravity:0.75
Weight g:22
Mounting Hole Diameter mm:16.0
FL-TMS:
Contact Form:
Reversible Float
Switching Voltage Max. V:
125 Vac Break Down
250 Vac
Switching Current Max. A:0.5
Carry Current Max. A:1.0
Switching Capacity Max. VA:
10W SPST
Contact Resistance Max. mOhms:200
Lead Wire:
UL 1007 AWG22 PVC
Operating Pressure Max. Kg/cm2:1.0
Operating Temperature Deg.°C: –20° +80°
MaterialPolypropylene
Suitable Specific Gravity:0.8
Weight g:12
Mounting Hole Diameter mm:10
Part Code
Description
FL-SMS
Side Mounted Level Switch
FL-TMS
Top Mounted Level Switch
Emergency
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Ultrasonic Level Sensor FL-ULS2
Description
Technical Specification
The FL-ULS2 is designed for level measurement in tanks
or sumps and provides a 4-20mA output relating to the
distance between the sensor and the surface being detected.
Measurement is made by non-intrusive ultrasonic technology
and the unit fixes in the top of the tank.
Features
•Non contact sensing
•Pre-calibrated to set ranges
•4-20mA output
•IP68 housing
•Built-in temperature compensation
Part Code
Description
FL-ULS2
Ultrasonic Level Sensor
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Measuring range:0.5...8m
Resolution:1mm
Operating frequency:50kHz
Accuracy:
0.25% of measuring range
Output:4...20mA
Supply:20...38Vdc
Power consumption:0.5W
Operating temperature:–10…+60°C
Static pressure limits: –0.25...2 bar
Materials:
Casing Glass filled polypropylene
Transducer UPVC
Mounting flange:
ANSI 3” 150lb, DN80 PN16
Protection:IP68
Dimensions:
178 x 192mm dia.
Weight:2.42kg
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
23
E.C.Products
Building Management Controls & Peripherals
Emergency
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Capacitance Level Sensors FL-CAP
Description
Technical Specification
These sensors are designed for level measurement in tanks or
sumps providing a 4-20mA output relating to the level of fluid
in the tank. The FL-CAP1 is suitable for conducting liquids such
as water whilst the FL-CAP2 is designed for use with clean, low
viscosity non-conducting liquids such as oil.
Features
•Suitable for a wide range of media
•4-20mA output
•No moving parts
Output:4...20mA
Supply:20...38Vdc
Insertion length:
1 to 3m versions
Process connection: 1” BSP
Process temperature: 50°C max
Ambient temperature:0...+60°C
Display:
3½ digit 12mm Red LED
Max. pressure:
20 bar @ 20°C
Electrode insulation:Polypropylene
Stem Material:
316 st. stl.
Termination housing: Flameproof IP65
Protection: IP65
Conducting Liquids
Non-conducting Liquids
Description
FL-CAP1-1.0
FL-CAP2-1.0
Capacitance Level Sensor - 1 metre
FL-CAP1-1.5
FL-CAP2-1.5
Capacitance Level Sensor - 1.5 metres
FL-CAP1-2.0
FL-CAP2-2.0
Capacitance Level Sensor - 2 metres
FL-CAP1-2.5
FL-CAP2-2.5
Capacitance Level Sensor - 2.5 metres
FL-CAP1-3.0
FL-CAP2-3.0
Capacitance Level Sensor - 3 metres
Float Level Switch FL-11x
Description
Technical Specification
The FL-11x sealed float switch is a switch which regulates the
fluid level in a tank or well. The unit is water resistant and is
capable of being used for oil, most acids and alkalis. The float
contains a micro switch inside a water tight enclosure and is
connected by a flexible cable.
Operating temp:0...+70°C
Protection:IP68
Switch rating:
10(8)A SPDT @ 250Vac
Max. Pressure:
1 bar
Dimensions:
97 x 79 x 65mm (without cable)
Features
•Adjustable switching point
•Easy to install
•Reliable and maintenance free
24
Part Code
Description
FL-113
Float Level Switch - 3 metre cable
FL-115
Float Level Switch - 5 metre cable
FL-118
Float Level Switch - 8 metre cable
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Space/Duct Air Quality Sensors xLQ
Description
Technical Specification
The self-calibrating microprocessor-controlled duct air quality
sensor is used to determine the air quality on basis of a
mixed gas sensor/VOC sensor. It is used to measure the air
quality for quantitative evaluation of room air pollution with
contaminating gases. The air quality sensor does not trace
concentrations of individual gases, but assesses the mixed gas
concentration. Detectable gases: mixed gas, vapours of VOCs,
cigarette smoke, automobile exhaust gases, human exhalation,
combustion smoke (from wood, paper, plastics). The sensor‘s
lifetime depends on the type of burden and gas concentration.
Features
Power supply:
24 Vac/dc, 70 mA at 24 V
Sensor:
VOC sensor (metal oxide)
Measuring range:
0…100 % AQ;
referred to calibrating gas
Output signal:
0...10 V or 4...20 mA (selectable)
Measuring accuracy: ± 20 % of final value
Ambient temperature:0 ...+ 50 °C
Electrical connection: 0.14 - 1.5 mm² screw terminals
Response time:
< 60s
Enclosure: Duct or Space Mounting
Protection type:
Space - IP 30 Duct - IP65
Gas sensors
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
•Self-calibrating
•Microprocessor controlled
•Duct or Space Versions
•Selectable output
Part Code
Description
RLQ
Space Air Quality Sensor - selectable output
KLQ
Duct Air Quality Sensor - selectable output
Space Carbon Dioxide Sensor CO2-2000
Description
Technical Specification
Dual wavelength NDIR CO2 sensor providing either Digital,
0-10V or 4-20mA output. Dual wavelength technology
provides enhanced long term stability and accuracy. The Dual
wavelength optical measurement technology allows the CO2
sensor to maintain accuracy and stability even when subjected
to shocks and vibrations. Selectable jumper for choosing either
4-20mA or 0-10V.
Features
•Dual Wavelength NDIR sensing method
•Selectable ouput
•Auto calibration function
•Thermistor Option Available
Part Code
Description
CO2-2000
Space Carbon Dioxide Sensor
Response time:
(63%) < 30 sec
Measurement time interval:1.5 sec
Ambient Temperature:
0ºC to 50ºC
Ambient Humidity:
0ºC to 95% RH (Non-condensing)
Gas flow rate:
0.2 to 1 m/sec
Power supply (rectified):
16 to 24VDC
Power Consumption:
70mA average
Analog Outputs:
0-10VDC or 4-20mA
Dimensions Space: 85 x 85 x 30mm
Dimensions Duct:
Housing: 120 x 80 x 53mm
Probe: 24mm dia. x 160mm
C02-2000-D Duct Carbon Dioxide Sensor
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
25
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Space Carbon Dioxide Sensor CO2
Description
Technical Specification
This self-calibrating microprocessor-controlled CO2 measuring
instrument is used for the detection of CO2 content in air within
a range of 0 ppm to 2000 ppm CO2. Measuring signals are
converted into standard signals of 0–10 V. The CO2 content of
air is determined by an NDIR sensor.
Features
•Self-calibrating
•Microprocessor controlled
•0...10V output
•Wall mounted
•Option of 5 LED Indication
Part Code
Description
RCO2
Space Carbon Dioxide Sensor - 0...10Vdc output
RTM-CO2
Space Carbon Dioxide and Temperature Sensor
Power supply:
CO2 sensor:
Measuring range:
Output:
Measuring accuracy:
Pressure dependence:
Long-term stability:
Warm-up period:
Ambient temperature:
Electrical connection:
Enclosure:
Protection type:
24 V AC ⁄ DC
optical sensor (NDIR)
0...2,000 ppm CO2
0...10 V
± 40 ppm, ± 5 % v.EW
± 1,6 % ⁄ kPa
± 1 % of final value per year
1 hour
0 …+ 50 °C
0.14 - 1.5 mm2 via screw terminals
Wall Mounting
IP 30
RTM-CO2-A Space Carbon Dioxide and Temperature Sensor
c/w LED Indication
Duct Carbon Dioxide Sensor A/CO2-D
Description
Technical Specification
CO2 transmitters can be used in a broad range of applications
including air quality monitoring in buildings. CO2 concentration
levels in buildings are monitored to provide an indication
of occupancy and to drive a ventilation control strategy. An
effective DCV (Demand Controlled Ventilation) strategy will
conserve energy and maintain indoor air quality.
Features
•Simple installation
•Ideally suited for larger HVAC air ducts
•Offers standard 0-10 volt output
•Patented absorption infrared/gas sensing engine provides
high accuracy in a compact low-cost package
•Patented ABC Logic™ self-calibration system eliminates the
need for manual calibration in most applications
•Lifetime calibration guarantee
26
Part Code
Description
A/CO2-D
Duct Carbon Dioxide Sensor - 0..10Vdc output
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Measurement Range: 0-2000 PPM factory calibrated
Duct Air Velocity:
0 to 450 meter/min
Temp Dependence:
0.2% of full scale per ºC
Stability:
<2% of full scale
over the life of the sensor
(15 years typical)
Accuracy:
±40 ppm +3% of reading
@ 22ºC (72ºF) when compared with
factory certified reference
Non-linearity:
<1% of full scale @ 22ºC (72ºF)
Pressure Dependence: 0.13% of reading per mm of mercury
Response Time:
3 mins typical for a 90% step change
Sampling Rate:
Every two seconds, 25% duty cycle
Warm-up Time:
< two minutes (operational);
10 minutes to achieve max. accuracy
Operating Conditions: Temperature: 0...50ºC
Humidity: 0...95% RH, non-condensing
Storage Conditions:–20ºC...70ºC
Output:
0...10 Vdc
Power Supply:
18...30 Vac, 50/60 Hz or 18...42 Vdc
Dimensions:
Probe Length: 10.46 cm
Probe Diam: 3.14 cm
Junction Box Depth: 4.06 cm
Height: 7.62 cm
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Carbon Monoxide Sensor GS-CP01
Description
Technical Specification
The GS-CP01 is a fixed gas detector with high-quality
electrochemical/catalytic gas sensor which has the advantages
of good repeatability, long life-span and easy operation.
It can monitor the gas concentration in air and output a
4-20mA signal. It is suitable for gas detection in car parking
or industrial environment where toxic gas or combustible gas
leaks. Versions are available for wall or duct mounting
Features
•0–500ppm
•Analogue Output
•High & Low Level Alarm Output
•IP66 Protection
•Wall or duct mounting versions
Detection method:Electrochemical
Range:0-500ppm
Resolution:1ppm
Low alarm level:35ppm
High alarm level:200ppm
Output:4-20mA
Response time:<60s
Shelf Life & life expectancy: > 2 Years
Coverage:
up to 400M²
Supply voltage:
24Vdc +/-25%
Ambient temperature range:–20°C to 50°C
Dimensions:
L165 x W118 x H62
Part Code
Description
GS-CP01
Wall Mount Carbon Monoxide Sensor
GS-CP01-D
Duct Mount Carbon Monoxide Sensor
Gas sensors
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Carbon Monoxide Sensor GS-CMD5B1
Description
Technical Specification
The CMD Series carbon monoxide detector uses an
electrochemical sensor to monitor the carbon monoxide level
and outputs a 4-20 mA signal. The standard product features
a 2-wire loop-powered output. Optionally, the device may be
configured with an alarm relay and operates in 3-wire sourcing
mode. Optional Modbus communications output is available.
Features
•Robust compact design
•Optional alarm output
•Modbus option
•Long life expectancy
Part Code
Description
GS-CMD5B1000 CO detector loop powered 4-20mA
GS-CMD5B1100
Measurement:Electrochemical
Sample Method:Diffusion
Measurement Range: 0-300 ppm
Accuracy:
± 5 ppm or ± 5% of reading
@ 0-50˚C, 15-90% RH
Agency Approvals:
Sensor is UL Recognized for
ANSI/UL-2034, UL-2075, E240671
Operating Conditions: –20-50˚C, 15-90% RH
Stability:
< 5% signal loss/year
Response Time:
< 35 seconds for 90% step change
Life Expectancy:
5-7 years in air
Typical Coverage Area:700m² or 15m radius
Dimensions:
71 w x 104 h x 46 d mm
Enclosure:
ABS - UL94-V, IP65
Power Supply:
24 Vdc ±20% for 2 wire Loop powered
24 Vdc ±20% or 24 Vac ±10% with
relay option
CO detector, 4-20mA 3 wire,
with relay output
GS-CMD5B-MOD CO detector, Modbus
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
27
E.C.Products
Building Management Controls & Peripherals
Gas valves
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Electro-Hydraulic Gas Valves GV-PS
Description
Technical Specification
GV-PS Auto Reset Electro-Hydraulic Gas Solenoid are used for
the shutting off of gas supplies in the event of an emergency.
This range is available in sizes from 1½“ up to 10” and are
fitted with closed position switches as standard.
Features
•Manual reset switch available
•EN161 approved
•Sizes from 1½“ up to 10“
•Closed position switch fitted as standard
28
Part Code
Description
GV-PS6683
Electro-hydraulic Gas Valve - 1½” screwed
GV-PS6684
Electro-hydraulic Gas Valve - 2” screwed
GV-PS6685
Electro-hydraulic Gas Valve - 2½” screwed
GV-PS6686
Electro-hydraulic Gas Valve - 3” screwed
GV-PS6687F
Electro-hydraulic Gas Valve - 4” flanged
GV-PS6689F
Electro-hydraulic Gas Valve - 6” flanged
GV-PS66810F
Electro-hydraulic Gas Valve - 8” flanged
GV-PS66811F
Electro-hydraulic Gas Valve - 10” flanged
GV-PS-MRS
Manual Reset Switch
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Operating Voltage: 240V @ 50Hz, -15%/+10%
Operating Pressure: 200mbar max.
Closure time:
Max. 1 second
Protection:IP54
Media:
Non-corrosive gases and air
Connections:
Up to 3”: Screwed
4” and above: Flanged
Materials:
Die-cast aluminium
Ambient:
Operating temp: -15°C to +60°C
Switch Rating:
5(2)A @ 250Vac/30Vdc
Power Consumption:Opening: 200VA
Fully open: 18VA
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Gas Solenoid Valves GV-VMR/GV-EVRM
Description
Technical Specification
The VMR type valve is a fast opening single-stage solenoid
valve, normally closed. This type of device is suitable for air
or gas blocking and releasing controls, required in gas power
burners, atmospheric gas boilers, furnaces and others gas
consuming appliances. The VMR type valves are made in
accordance with EN161 standards and the CE test certificate is
issued from GASTEC (Pin 0063AQ1350)
Features
•1/2” to 6” pipes sizing.
•G1/4” pressure gauge port
•Closed position indicator
•Fine mesh filter incorporated
•Suitable for air and non-aggressive gases
Connections:
Threaded ISO 228/1 from Rp ½” to Rp 2”
Flanged PN16 from DN65 to DN150
Voltage rating:
230 Vac 50/60 Hz
Voltage tolerance:
–15% / +10%
Environment temp:
–15°C / +60° C
Max. working pressure:200 / 360 mbar
Seal:NBR
Opening/Closing time: < 1 sec.
Protection class:
IP 54
Cable gland:PG09
Auto reset
Manual reset
Description
GV-VMR12
GV-EVRM12
Gas Solenoid Valve ½” screwed
GV-VMR22/SW
GV-EVRM22/SW
Gas Solenoid Valve ¾” screwed
GV-VMR32/SW
GV-EVRM32/SW
Gas Solenoid Valve 1” screwed
GV-VMR352/SW
GV-EVRM352/SW
Gas Solenoid Valve 1¼” screwed
GV-VMR42/SW
GV-EVRM42/SW
Gas Solenoid Valve 1½” screwed
GV-VMR62/SW
GV-EVRM62/SW
Gas Solenoid Valve 2” screwed
GV-VMR72/SW
GV-EVRM72/SW
Gas Solenoid Valve 2½” flanged
GV-VMR82/SW
GV-EVRM82/SW
Gas Solenoid Valve 3” flanged
GV-VMR92/SW
GV-EVRM92/SW
Gas Solenoid Valve 4” flanged
GV-VMR932/SW
GV-EVRM932/SW
Gas Solenoid Valve 5” flanged
GV-VMR952/SW
GV-EVRM952/SW
Gas Solenoid Valve 6” flanged
GV-PCS-3
CPI Switch for ¾ & 1" Gas Valve
GV-PCS-4
CPI Switch for 1¼&1½" Gas Valve
GV-PCS-6
CPI Switch for 2" Gas Valve
GV-PCS-8
CPI Switch for 2½&3" Gas Valve
GV-PCS-9
CPI Switch for 4" Gas Valve
GV-PCS-95
CPI Switch for 5 & 6" Gas Valve
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Gas valves
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
29
E.C.Products
Building Management Controls & Peripherals
Gas valves
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Gas Valve Auto Reset EVP-NCxxx
Description
Technical Specification
The EVP valves are fast acting Gas Solenoid Valve, Normally
closed, these are suitable for Gas safety applications to shut off
gas supplies rapidly in Burners, boilers, furnaces and other gas
consuming appliances.
Features
•Available for ½” to 8” pipe sizes
•Threaded port for closed position switch
•Suitable for air and non-aggressive gases
•Gas interception automatic normally closed solenoid valves
that open when the coil is powered and close when there is
no tension.
•These solenoid valves can be controlled by pressure switch,
thermostat etc.
•They can be equipped with a flow regulator and adjustable
slow opening kit
•Threaded Connections
Part Code
Description
EVP-NC15
½” Gas Valve Auto Reset Screwed
EVP-NC20
¾” Gas Valve Auto Reset Screwed
EVP-NC25
1” Gas Valve Auto Reset Screwed
EVP-NC32
1¼” Gas Valve Auto Reset Screwed
EVP-NC40
1½” Gas Valve Auto Reset Screwed
EVP-NC50
2” Gas Valve Auto Reset Screwed
EVP-NC65
2½” Gas Valve Auto Reset Flanged
EVP-NC80
3” Gas Valve Auto Reset Flanged
EVP-NC100
4” Gas Valve Auto Reset Flanged
EVP-NC125
5” Gas Valve Auto Reset Flanged
EVP-NC150
6” Gas Valve Auto Reset Flanged
EVP-NC200
8” Gas Valve Auto Reset Flanged
EVP-030066
CPI switch for use with ½–¾” gas valve
EVP-040066
CPI switch for use with 1“ gas valve
EVP-060066
CPI switch for use with 1¼–1½“ gas valve
EVP-070066
CPI switch for use with 2“ gas valve
EVP-090066
CPI switch for use with 2½–3“ gas valve
EVP-100066
CPI switch for use with 4“ gas valve
EVP-11120066
CPI switch for use with 5–6“ gas valve
Power Supply Voltage Tolerance:–15%..+10%
Max Pressure:
200 or 360 mbar
Environment Temperature:
–15° +60°
Max Superficial Temperature:85°C
Protection Degree:IP65
Closing Time:<1s
Opening Time:<1s
8” gas valve has built in CPI switch
30
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Gas Leak Detection GLD
Description
Technical Specification
The GLD gas leak detection range is suitable for use in Boiler
Rooms and other Commercial applications to provide safety
and shut down functions in the event of gas leakage.
Control units are available in 1, 2 or 3 channels for connection
to 1, 2 or 3 remote sensors. They are mounted in DIN rail
housings with the option of panel or wall mount enclosures.
Output relays to operate auxiliary devices such as Solenoid
Gas Valves or Sirens and fault remote signalling are fitted to
all units.
Power supply is 230Vac or 12-24Vdc and sensors are available
for both Natural Gas, LPG/Propane and Carbon Monoxide.
Features
•1, 2 & 3 channel options
•Audio & visual alarms
•Adjustable alarm sensitivity
•Relay output for gas valves
•Relay outputs for remote alarms
•Auto or manual reset
Power Supply:
Power Consumption: Relay Outputs:
Pre-alarm Thresholds:
Alarm Thresholds:
Sensors:
Materials:
Ambient:
Part Code
Description
GLD361
DIN rail Single Channel Gas Leak Detection Controller
GLD651
DIN rail Single Channel Gas Leak Detection Controller
GLD652
DIN rail Two Channel Gas Leak Detection Controller
GLD653
DIN rail Three Channel Gas Leak Detection Controller
GLD150
Natural Gas Sensor
GLD250
Propane/LPG Sensor
GLD350
Carbon Monoxide Sensor
GLD644
Panel mount Kit for GLD651,652 & 653
GLD615
Wall mount kit for GLD651, 652, 653
GLD316
Panel mount Kit for GLD361
GLD315
Wall mount kit for GLD361
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
GLD361: 230Vac ±10% @ 50Hz
GLD65*: 12V ±10%
GLD361: 3VA
GLD65*: 7VA
GLD361: 5(1)A @ 250V SPDT
GLD65*: 2 x 5(1)a @ 250V SPDT
Natural Gas: 0.3% to 0.8%
(3000 to 8000ppm)
LPG: 0.14% to 0.35%
(1400 to 3500ppm)
CO: 0.012% to 0.03%
(120 to 300ppm)
Natural Gas: 0.5% to 1.25%
(5000 to 12500ppm)
LPG: 0.22% to 0.56%
(2200 to 5600ppm)
CO: 0.02% to 0.05% (200 to 500ppm)
Natural Gas: GLD150
LPG: GLD250
CO: GLD350
Base: Nylon, Cover: ABS
Storage: –25°C to +60°C
Operating: 0°C to +45°C
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Gas leak
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
31
E.C.Products
Building Management Controls & Peripherals
Smoke detection
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Duct Smoke Detector SD-2000
Description
The SL-2000 Series Smoke Duct Detector is the latest innovation
for early detection of smoke and products of combustion
present in air moving through HVAC ducts in Commercial,
Industrial, and Residential applications. The unit is designed to
prevent the recirculation or spread of smoke by air handling
systems, fans, and blowers. Complete systems may be shut
down in the event of smoke detection. The SD-2000 is designed
and built to meet all local code requirements regarding HVAC
supply and return duct smoke detectors. Output terminals are
provided for a wide range of remote accessories such as horns,
strobes, remote status indicators, and test/reset key switches or
push buttons.
The SD-2000 includes many features that represent true
innovations from current generation duct smoke detectors.
Our traditional installer/servicer-friendly approach has been
closely followed and expanded throughout the SD-2000. This
philosophy provides a new level of efficiency in after-purchase
value to both the installer/servicer and end-user. Our attention
to detail has yielded a host of “No-Tools Required” features, as
well as a multi-application performance level as yet unmatched
in the industry. Innovative product combined with unsurpassed
customer service equals the right combination for all of your
projects. The key features detail many of the customer-driven
innovations incorporated in the SD-2000 Series.
Features
•Both models listed for high-temperature applications
•Operating voltages: 230VAC, 115VAC, 24VAC, 24VDC
•Interconnect up to 30 units for common functions
•Patent pending “No-Tools Required” front or rear
•loading and removing sampling/exhaust tubes
•Patent pending “Test Port Valve” allows for aerosol smoke
•testing without cover removal
•Instantaneous cover removal trouble indication
•Staggered terminal blocks for easier wiring
•Flashing LED on detector head indicates normal operation
•Magnet test capability (magnet included)
•More wiring space than competitive models
•Duct wall gaskets on back of enclosure are pre-installed
•Reset switch is also an alarm test switch
•Unit includes green pilot and red alarm visual indicators
Part Code
•External mounting tabs do not require cover removal
to install
•Colored cover gasket indicates proper cover seal
•Compact, lightweight size means easy handling
•Two sets of 10A form “C” alarm contacts
•One set of 2A form “A” alarm contacts
•One set of 10A form “C” trouble contacts
•Large terminal connection screws
•Standard interchangeable photoelectric or ionization heads
•Complete wiring details permanently attached to unit
Technical Specification
Model Number:
SD-2000-N Ionization
SD-2000-P Photoelectric
Sampling Tubes:
STN-1.0 Sampling tube for 12”
or less duct
STN-2.5 Sampling tube for
6” to 2.5’ duct
STN-5.0 Sampling tube for
2.5’ to 5.0’ duct
STN-10.0 Sampling tube for
5.0’ to 10.0’
Power Requirements: 230VAC Standby 8 mA, Alarm 18mA
115VAC Standby 14 mA, Alarm 32mA
24VAC Standby 55 mA, Alarm 190mA
24VDC Standby 14 mA, Alarm 68mA
Alarm Contacts Rating: 2 sets rated at 10 Amps @ 115VAC
1 set rated at 2 Amps
Trouble Contacts Rating: 1 set rated at 10 Amps @ 115VAC
Air Velocity:
100 to 4,000 ft./min.
Ambient Temperature:0...60°
Ambient Humidity:
10-85% RH
Wiring:
Solid or stranded: #12 to #22 AWG
Material:
Grey plastic backbox,
clear plastic cover
(Makrolon 94V-0)
Dimensions:
13 ½” L x 4 ½” W x 2 ¼” H
Weight:
2 ½ lbs.
Hardware:
7” exhaust tube, sampling tube end
cap, mounting template, test magnet
and mounting hardware included
Description
SD-2000-N Duct smoke detector housing with ionisation sensor
SD-2000-P
Duct smoke detector housing with photoelectric sensor
STN1
Sampling tube 1-2'
STN2.5
Sampling tube 2-4'
STN5
Sampling tube 4-8'
STN10
Sampling tube 8-12'
Please order Sampling Tubes separately
32
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Invertek Drive ODE-2-xxxxx-3KAxx
Description
Technical Specification
Rich in features the Optidrive E2 is the most commercially
competitive Optidrive in the Optidrive family. Innovative and
compact the Optidrive E2 range combines good looks with
robustness, reliability and easy to use performance.
The product is dedicated to low power applications where total
costs are ultra-competitive, including:
•Optidrive E2 has only 14 standard parameters to adjust in its
basic form, thus Optidrive’s legendary ease of use could not
be easier or quicker to get started with.
•Optidrive E2 can be supplied with or without an internal
rfi filter
Overload Capacity: 150% for 60 secs
175% for 2 secs
Output Frequency:0…500Hz
Input Frequency: 48–62Hz
Voltage:
110–115 +/- 10% 1 Phase (0.5–1.5HP)
200–240 +/- 10% 1 Phase
(0.37–4kW/0.5–5HP)
200–240 +/- 10% 3 Phase
(1.5–3.7kW / 2–5HP)
380–480 +/- 10% 3 Phase
(0.75–11kW/ 1–15HP)
Inverters
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Features
•Small mechanical envelope
•Rugged industrial 50°C ambient rating for hot and tough
applications
•Simple mechanical and electrical installation
•Simple operation, powerful features easy to use
•Fast setup, factory default settings ok for most applications,
only 14 basic parameters
•Motor current and RPM indication
Part Code
Description
ODE-0.75KW-IP20
Invertek Drive 0.75Kw 3 Phase IP20
ODE-1.5KW-IP20
Invertek Drive 1.5Kw 3 Phase IP20
ODE-2.2KW-IP20
Invertek Drive 2.2Kw 3 Phase IP20
ODE-4KW-IP20
Invertek Drive 4Kw 3 Phase IP20
ODE-5.5KW-IP20
Invertek Drive 5.5Kw 3 Phase IP20
ODE-7.5KW-IP20
Invertek Drive 7.5Kw 3 Phase IP20
ODE-11KW-IP20
Invertek Drive 11Kw 3 Phase IP20
ODE-0.75KW-IP66
Invertek Drive 0.75Kw 3 Phase IP66
ODE-1.5KW-IP66
Invertek Drive 1.5Kw 3 Phase IP66
ODE-2.2KW-IP66
Invertek Drive 2.2Kw 3 Phase IP66
ODE-4KW-IP66
Invertek Drive 4Kw 3 Phase IP66
ODE-5.5KW-IP66
Invertek Drive 5.5Kw 3 Phase IP66
ODE-7.5KW-IP66
Invertek Drive 7.5Kw 3 Phase IP66
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
33
E.C.Products
Building Management Controls & Peripherals
Relays & bases
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Relays and Bases Rx
Description
Features
A range 2, 3 & 4 pole relays and bases in a choice of
coil voltage.
Technical Specification
Dimensions (L x W x H):
Number and type of contacts:
Contact material:
Max. switching voltage AC/DC:
Min. switching voltage:
AC1:
DC1:
Rated load
Max. inrush current:
Rated current:
Max. breaking capacity AC1:
Contact resistance:
Max. operating frequency:
Rated Coil voltage:
Rated power consumption:
At rated load AC1:
No load:
50/60Hz, AC:
DC:
AC:
DC:
Insulation category:
Insulation rated voltage:
Rated surge voltage:
Operating time (typical value):
Release time (typical value):
Electrical life resistive AC1:
Mechanical life (cycles):
Weight:
Ambient temperature:
Storage:
Operating:
Cover protection category:
Vibration resistance:
34
•Choice of coil voltages
•Complete with test flag
•Optional LED
R2
27.5 x 21.2 x 35.6 mm
2 C/O
AgNi
250V/250V
5V
12A/250Vac
12A/24Vdc
24A
12A
3000VA
≤ 100mΩ
1200 cycles/hr
18000 cycles/hr
See price table
R3
27.5 x 21.2 x 35.6 mm
3 C/O
AgNi
250V/250V
5V
10A/250Vac
10A/24Vdc
20A
10A
2500VA
≤ 100mΩ
1200 cycles/hr
18000 cycles/hr
See price table
R4
27.5 x 21.2 x 35.6 mm
4 C/O
AgNi
250V/250V
5V
6A/250Vac
6A/24Vdc
12A
6A
1500VA
≤ 100mΩ
1200 cycles/hr
18000 cycles/hr
See price table
See price table
1.6VA
0.9W
C250
250Vac
4000Vac
AC: 10mS DC: 13mS
AC: 8mS DC: 3mS
≥ 105
≥2 x 107
35g
–40…+85°C
–40…+55°C
IP40
5g 10...150 Hz
See price table
1.6VA
0.9W
C250
250Vac
2500Vac
AC: 10mS DC: 13mS
AC: 8mS DC: 3mS
≥ 105
≥2 x 107
35g
–40…+85°C
–40…+55°C
IP40
5g 10...150 Hz
See price table
1.6VA
0.9W
B250
250Vac
2500Vac
AC: 10mS DC: 13mS
AC: 8mS DC: 3mS
≥ 105
≥2 x 107
35g
–40…+85°C
–40…+55°C
IP40
5g 10...150 Hz
2 pole
3 pole
4 pole
Description
R2-12D-L
R3-12D-L
R4-12D-L
Relay with Test Flag + LED 12VDC
R2-24D-L
R3-24D-L
R4-24D-L
Relay with Test Flag + LED 24VDC
R2-24A-L
R3-24A-L
R4-24A-L
Relay with Test Flag + LED 24VAC
R2-110A-L
R3-110A-L
R4-110A-L
Relay with Test Flag + LED 110VAC
R2-230A-L
R3-230A-L
R4-230A-L
Relay with Test Flag + LED 230VAC
R2-T
R3-T
R4-T
Standard Base
R2-M
R3-M
R4-M
Base with separate coil & contact circuits
R-CLIP
Retain/Eject clip for Rx-M/T bases
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Relays and Bases RMx
Description
Features
A range 1 & 2 pole relays and bases in a choice of
coil voltage.
•Choice of coil voltages
•12Vdc coil suitable for use with Trend BMS
•Small footprint
Technical Specification
Dimensions (L x W x H mm):
Number and type of contacts:
Max. switching voltage AC/DC:
AC1:
DC1:
Rated load:
Max. inrush current:
At rated load
AC1:
No load:
50/60Hz, AC:
DC:
AC:
DC:
Max. operating frequency:
Rated Coil voltage:
Rated power consumption:
Electrical life resistive AC1:
Mechanical life (cycles):
Weight:
Storage:
Operating:
Ambient temperature:
Cover protection category:
Vibration resistance:
RM87
29 x 12.7 x 15.7
1 C/O
400V/300V
10A/250Vac
10A/24Vdc
20A
RM85
29 x 12.7 x 15.7
1 C/O
400V/300V
16A/250Vac
16A/24Vdc
30A
RM84
29 x 12.7 x 15.7
2 C/O
400V/300V
8A/250Vac
8A/24Vdc
15A
600 cycles/hr
600 cycles/hr
600 cycles/hr
72000 cycles/hr
See price table
See price table
0.75VA
0.25W
≥ 105
≥3 x 107
14g
-40…+85°C
-40…+70°C
IP40
10 g 10...150 Hz
72000 cycles/hr
See price table
See price table
0.75VA
0.4W
≥ 105
≥3 x 107
14g
-40…+85°C
-40…+70°C
IP40
10 g 10...150 Hz
72000 cycles/hr
See price table
See price table
0.75VA
0.4W
≥ 105
≥3 x 107
14g
-40…+85°C
-40…+70°C
IP40
10 g 10...150 Hz
1 pole
1 pole 16A
2 pole
Description
RM87-12D
RM85-12D
RM84-12D
Miniature Relay 12VDC
RM87-24D
RM85-24D
RM84-24D
Miniature Relay 24VDC
RM87-24A
RM85-24A
RM84-24A
Miniature Relay 24VAC
RM87-110A
RM85-110A
RM84-110A
Miniature Relay 110VAC
RM87-230A
RM85-230A
RM84-230A
Miniature Relay 230VAC
RM87-T
RM84-T
RM84-T
Standard Base
RM-CLIP
Retain/Eject clip for RMx-T bases
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Relays & bases
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
35
E.C.Products
Building Management Controls & Peripherals
Relays & bases
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Phase Protection Relays Description
Technical Specification
The phase protection relay monitors phase failure, phase
sequence and imbalance giving LED indication and volt free
SPDT contact.
Dimensions:
90 x 17.5 x 60mm
Contact rating:
N/O 5A, N/C 3A
Power Consumption: 20VA max.
Operating Voltage: 154 to 500Vac
Phase failure Trip: <154 Volts
Phase Imbalance
30 Volts
Response Time:
200msec max.
Operating Temp:0–50°C
Features
•3 wire input
•LED Indication
•Slim space saving design
•Din rail mounting
Part Code
Description
R600PSR
Phase failure Relay
Voltage Protection Relay Description
Technical Specification
The Voltage Protection Relay monitors phase sequence, under
voltage and over voltage giving LED indication and a volt free
SPDT contact.
Features
•3 wire input
•LED Indication
•Slim space saving design
•Din rail mounting
36
Part Code
Description
R600VPR
Voltage Protection Relay
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Dimensions:
90mm x 17.5mm x 60mm
Contact rating:
N/O 5A, N/C 3A
Power Consumption: 20VA max.
Operating Voltage: 170 to 290 Vac
Under Voltage:
170 to 224 Vac
Over Voltage:
236 to 290 Vac
Trip Delay:
0.2 to 10 Seconds
Operating Temp:0–50°C
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Single Relays & Bases IOR1
Description
Technical Specification
The IOR1 range of single relay modules are suitable for a wide
range of voltages and are supplied complete with DIN rail
mounting base and retaining clip.
Features
•DIN rail mounting base included
•Choice of voltage
•Retaining clip prevents relay falling out
Contact Data
Type of Contact:
1 x changeover contact
Contact Material:AgNi
Max. Switching Voltage:400Vac/300Vdc
Min. Switching Voltage:5V
Rated Load:12A/250Vac
Max. inrush Current:20A
Contact Resistance:
< 100 mΩ
Max. Operating Frequency:600 cycles/hour at rated load
IO modules
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Coil Data
Rated Voltage:
See table
Coil Resistance:
See table
Rated Power Consumption: AC - 0.75VA DC - 0.25W
Operating Range:
See table
General Data
Operating Time:
Typical 7 ms
Release Time:
Typical 3 ms
Ambient Temperature:–40°C…+85°C
Dimensions:
75 x 15.5 x 67mm
Coil Resistance
Coil Operating Range at 20°C
Part Code
Description
±10% at 20°C
Min
Max
IOR1-12DC
12Vdc Single Relay and Base
580Ω
9.0Vdc
36.0Vdc
IOR1-24DC
24Vdc Single Relay and Base
1440Ω
16.8Vdc
61.2Vdc
IOR1-24AC
24Vac Single Relay and Base
400Ω
19.2Vac 50Hz
28.8Vac 50Hz
IOR1-230AC
230Vac Single Relay and Base
38500Ω
184.0Vac 50Hz
276.0Vac 50Hz
M61G
Plug in LED module with diode 6–24V
M63G
Plug in LED module with diode 110–230V
Adjustable Single Relay Module IOVR1
Description
Technical Specification
The IOVR1 is a SPCO change over relay output from a 0 to
10Vdc with fully adjustable switch point.
Features
•DIN rail mounting
•LED status indication
•24 Vac/dc powered
•Buffered 0 to 10V output
Part Code
Description
IOVR1
Adjustable Single Relay Module
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Input Signal:
Output Contacts:
Power Supply:
Hysteresis:
Dimentions:
0...10Vdc 1mA min. into 22kΩ impedance
8A @ 230Vac (resistive load)
24Vac ±10% @ 50Hz or
24Vdc +15%/-6%, 65mA max.
5 or 10% link selectable
35 x 82 x 47mm
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
37
E.C.Products
Building Management Controls & Peripherals
IO modules
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Two Stage Relay Module IOR2
Description
Technical Specification
This IO module is used with DDCs to convert an analogue
control input signal to a time proportional raise/lower, high/
low or binary relay output. Typically it is used to control valve
and Damper actuators from an analogue signal. It is designed
so that every status is clearly indicated with LEDs to facilitate
operation and commissioning.
Features
•DIN rail mounting
•Relay status LEDs indication
•Link selectable raise/lower, hi/low or binary modes and
time function
•On/Off/Auto links for ease of commissioning
Part Code
Description
IOR2
Two Stage Relay Module
Input Signal:
Output Contacts:
Power Supply:
Hysteresis:
Operating Modes:
LED Indication:
Manual Override:
Terminals:
Ambient:
Dimensions:
0...10Vdc 1mA min. into 22kΩ impedance
8A @ 230Vac (resistive load)
24Vac ±10% @ 50Hz or
24Vdc +15%/-6%, 65mA max.
±0.2Vdc about switching points
Hi/Lo, Raise/Lower, Binary
Green LED - Power Supply condition
Red LED - Input Voltage condition
On/Off/Auto jumper selectable
Rising clamp 0.5-2.5mm² cable
-10°C to +40°C, 0-80% RH non-condensing
52mm(H) x 62mm(W) x 83mm approx
Three Stage Relay Module IOR3
Description
Technical Specification
This IO module is used with DDCs to convert an analogue
control input signal to a time proportional raise/lower, high/
low or binary relay output. Typically it is used to control valve
and Damper actuators from an analogue signal. It is designed
so that every status is clearly indicated with LEDs to facilitate
operation and commissioning.
Features
•DIN Rail mounting
•Relay status LEDs indication
•Link selectable binary, heat/cool, staged, sequenced
•On/Off/Auto links for ease of commissioning
•Built in timing for raise/lower applications
38
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Input Signal:
0...10Vdc 1mA min. into 22kΩ impedance
Output Contacts: 8A @ 230Vac (resistive load)
Power Supply:
24Vac ±10% @ 50Hz or
24Vdc +15%/-6%, 65mA max.
Hysteresis:
±0.2Vdc about switching points
Operating Modes: Binary, Heat/cool, Staged, Sequenced
LED Indication:
Green LED - Power Supply condition
Red LED - Input Voltage condition
Manual Override: On/Off/Auto jumper selectable
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–10°C to +40°C, 0-80% RH
non-condensing
Dimensions:
52mm(H) x 62mm(W) x 83mm approx
Part Code
Description
IOR3
Three Stage Relay Module
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Four Stage Relay Modules IOR4
Description
Technical Specification
This IO module is used with DDCs to convert an analogue
control output to a binary, 2 x raise/lower, staged or
sequenced relay output. LEDs indicate correct operation and
low current draw from 0-10Vdc controller means that the IOR4
can work successfully with most BEMs controllers.
Features
•DIN Rail mounting
•Relay status and fault finding LEDs indication
•Link selectable binary, staged, sequenced
•On/Off/Auto links for ease of commissioning
Part Code
Description
IOR4
Four Stage Relay Module
Input Signal:
0...10Vdc 1mA min. into 22kΩ impedance
Output Contacts: 8A @ 230Vac (resistive load)
Power Supply:
24Vac ±10% @ 50Hz or
24Vdc +15%/-6%, 65mA max.
Hysteresis:
±0.2Vdc about switching points
Operating Modes: Binary, 2 x raise/lower, Staged,
Sequenced
LED Indication:
Green LED - Power Supply condition
Red LED - Input Voltage condition
Manual Override: On/Off/Auto jumper selectable
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–10°C to +40°C, 0-80% RH non-condensing
Dimensions:
52mm(H) x 89mm(W) x 83mm approx
IO modules
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Six Stage Relay Modules IOR6
Description
Technical Specification
This IO module is used with DDCs to convert an analogue
control output to a staged, reverse staged or sequenced
relay output. LEDs indicate correct operation and low current
draw from 0-10Vdc controller means that the IOR6 can work
successfully with most BEMs controllers.
Features
•DIN Rail mounting
•Relay status and fault finding LEDs indication
•Link selectable staged, reverse staged, sequenced
•On/Off/Auto links for ease of commissioning
Part Code
Description
IOR6
Six Stage Relay Module
Input Signal:
0...10Vdc 1mA min. into 22kΩ impedance
Output Contacts: 8A @ 230Vac (resistive load)
Power Supply:
24Vac ±10% @ 50Hz or
24Vdc +15%/-6%, 65mA max.
Hysteresis:
±0.2Vdc about switching points
Operating Modes: Staged, Reverse Staged, Sequenced
LED Indication:
Green LED - Power Supply condition
Red LED - Input Voltage condition
Manual Override: On/Off/Auto jumper selectable
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–10°C to +40°C, 0-80% RH
non-condensing
Dimensions:
52mm(H) x 116mm(W) x 83mm approx
IOR8 available upon request, POA
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
39
E.C.Products
Building Management Controls & Peripherals
IO modules
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Single Fixed Relay Module IOMR1
Description
Technical Specification
The IOMR1 is designed to provide a manual override of the
output from a BMS Controller (or similar) and is particularly
useful for commissioning or temporary control applications. The
IOMR1 can also be used as an alternative to the IOR1-12DC
relay module, with the added advantages of ON/OFF/AUTO
Links The unit has a fixed switchpoint at 6V.
Features
•0/10 Vdc Input
•Fixed switchpoint at 6Vdc
•24V ac or dc powered
•Complete with DIN carrier
•ON/OFF/AUTO links for commissioning
•LED indication
Supply Voltage:
24V ac or dc
Input Signal:0/10Vdc
Switchpoint.:6Vdc
Output contacts: 1 x SPCO
Rating:
12A @ 230Vac
LED Indication:
ON when relay is energised
Ambient:
0°C to 40°C/5-90% RH
Storage:0/+50°C
Terminals:
Rising clamp 0.5-2.5mm² cable
Dimensions:
76mm(H) x 23mm(W) x 45mm approx
Country of Origin: United Kingdom
Part Code
Description
IOMR1
Single Fixed Relay Module
Four Channel Relay Override Module IOMR4
Description
Technical Specification
The IOMR4 is designed for applications which require
independent manual override of digital output channels from
BMS Controllers. The outputs can be switched without a
controller being present which makes the IOMR4 useful for
temporary control or commissioning. Link selection enables up
to 4 outputs to be switched from Input 1. High Quality Rising
Clamp Terminals are used for all connections.
The IOMR4 is powered by 24V ac or dc and features LED
indication of Power ON and LED indication for each energised
relay. The IOMR4 is designed to mount on TS35 section
DIN Rail.
Input Signal:
Must Operate:
Output Contacts:
Contact Rating:
Power Supply:
Manual Override:
Terminals:
LED Indicators:
Ambient Range:
Dimensions:
4 x 0-10V dc, (2mA typical)
5V dc
4 x SPCO
12A/250V ac (res.)
24V ac or dc +/-10%
ON/OFF/AUTO (Link Selectable)
Rising Clamp for 0.5-2.5mm2 Cable
ON when relay energised
0 to 50’C
78mm x 92.5mm x 48mm approx.
Features
•4 x 0-10V dc Input
•4 x SPCO Relay Outputs
•On/Off/Auto Override
•High Quality Rising Clamp Terminals
•DIN Rail Mounting (TS35)
•LED Indication
Part Code Description
IOMR4
40
Four Channel Relay Override Module
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Four Channel Digital Input Multiplexer IOD4
Description
Technical Specification
The Digital Input Expander allows 4 volt free inputs to be
monitored by a single analogue input channel. The resultant
analogue value can be decoded by the A to D function module
in an BMS controller to produce internal digital status bits for
alarm monitoring or other status input applications.
Features
•Expand capacity of existing ddc for cost effective installation.
•Visual indication of LED inputs for easy commissioning
•Application includes monitoring status of equipment
Supply voltage:
Supply current:
Input Channels:
Input Threshold:
Distance: Output:
I:
V: LED:
Dimensions:
Ambient limits:
24Vdc or Vac ± 15%
50mA max (I mode)
30mA max (V mode)
4 volt free contact switch 24Vdc
Upper 17.5V max (ON) level
Lower 7.5V min (OFF) level
Max. distance of IOD4 from controller
25m (V mode) 1000m (I mode)
Mode selectable by link header
current/voltage (I/V)
0 to 20mA, max. resistance of load 250Ω
0 to 10Vdc, max. current 1mA
Single LED per input channel,
LED on indicates contact closed
68 x 83 x 53mm
Storage: –10°C to +70°C
Operating: –10°C to +50°C
Humidity: 0 to 90% RH non-condensing
Part Code
Description
IOD4
Four Channel Digital Input Multiplexer
IO modules
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Six Channel Digital Input Multiplexer IODIM6-MI
Description
Technical Specification
The IODIM6-MI multiplexes 6 VFC or 24Vac/dc signals into
a single analogue output. 0-10Vdc, 2-10Vdc or 4-20mA,
and 0-20mA output variants are available making the unit
compatible with a large range of BMS equipment. The input
registers as active when the contact is closed. Additionally,
jumpers are fitted to allow each input to be manually
overridden for commissioning and testing purposes. The output
sequence can also be reversed as required by some types of
controller and control strategies.
Features
•6 x VFC or 24Vac/dc inputs
Inputs:
6 x Volt free contacts or 24Vac/dc input signals
Output:
Voltage, 0-10Vdc at maximum load 10mA
(2-10Vdc link selectable)
Current, 4 to 20mA (link selectable
0-20mA), max resistance of load 500Ω
LED Indication:
ON when Input is ON
Power Supply:
24Vac or dc (+/-15%)
Power Consumption:24Vdc 40mA Max
24Vac 60mA max
Terminals:
Rising Clamp for 0.5-2.5mm2 Cable
Ambient Temp:0-50°C
Dimensions:
75 x 68 x 45mm (max.)
•Reverse Action
•Voltage and Current Output Variants
•DIN Rail Mounting
•Operates From 24Vac or dc Power Supply
•LED Input Status Indication
Part Code
Description
IODIM6-MI-V
6 Digital Input Multiplexer - Voltage Output
IODIM6-MI-I
6 Digital Input Multiplexer - Current Output
•Input Simulation
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
41
E.C.Products
Building Management Controls & Peripherals
IO modules
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
10 Channel Alarm Integrator IO-ALM10
Description
Technical Specification
The IO-ALM10 series of Alarm Integrators monitor up to 10
Input Channels and provide a relay output in the event of an
alarm signal appearing on any one or more inputs. The
IO-ALM10 Alarm Integrators are self-powered from the alarm
input and are designed for mounting on TS35 section DIN rail.
Features
•10 input channels
•1 x SPCO Relay Outputs
•Self powered
•DIN Rail Mounting (TS35)
•24Vac/dc, and 230Vac versions available
Alarm Inputs:
Output:
Contact Rating:
Power Supply:
Terminals:
Dimensions:
Ambient Temperature:
Part Code
Description
IO-ALM10-24
24Vac/dc 10 Channel Alarm Integrator Module
IO-ALM10-230
230Vac 10 Channel Alarm Integrator Module
IO-ALM10-24 - 10 x 24Vac/dc
IO-ALM10-230 - 10 x 230Vac
1 x SPCO Relay
12A@230Vac (resistive)
Self-Powered from Input
Rising Clamp for 0.5-2.5mm2 cable
55 x 75 x 48mm approx.
0 – 50°C
Volt Free To Voltage Converter IOFS24-10
Description
Technical Specification
The IOFS24-10 has been designed to give 3 dc voltages using
volt free inputs, the outputs can be adjusted between 0 and 10
volts. This Module can be used for switched fan speed control
where a 0-10 volt signal is needed but only 3 set speeds are
needed.
Output:
3x adjustable dc voltages
Supply Voltage: 24Vac/dc +/- 10%
Termination:
Rising Clamp for 0.5 to 2.5mm² Cable.
Ambient:
–10 to +50°C
Dimensions:47mm(W)x49mm(D)x93mm(H)
Features
•Din rail mounting
•Power on LED indication
•24Vac/dc Supply
•Adjustable outputs via multi turn trimmer
42
Part Code
Description
IOFS24-10
Volt Free To Voltage Converter
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Multi Input Remote Alarm CAD-AP
Description
Technical Specification
A versatile audible/visual alarm point accepting a wide range
of input triggers and selectable audible alarms.
Features
•Multi-Mode Operation
•Triggers on 24vAC/DC, 240vAC or 0-10v Input
•Rising or Falling Alarm feature on 0-10v Input
•Delay Timer
•High Intensity LED for Visual Indication
•User Selectable Audible Alarm with Mute
•Surface or flush mounting
Part Code
Description
CAD-AP
Multi input remote alarm panel
Input Supply:
Input Triggers:
Output Signals:
Mounting:
24V AC/DC 18mA
24V AC/DC, 240vAC, 0-10v Analogue Input
1 x Visual High-Intensity LED
1 x Audible Piezo Sounder
Standard 1 Gang back box
IO modules
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Multi Input Monitoring Panel IO-MPA12
Description
Technical Specification
The IO-MPA12 provides audible and visual status indication
of up to 12 monitored points. The front panel gives visual and
audible local alarm with mute and the option to connect remote
alarm and mute function. The labelling can be done by the user
making this an ideal solution for many applications. The inputs
can be configured to operate on normally open or normally
closed volt free inputs with option of 2 voltage inputs.
Features
•Configurable I/O can be set to alarm on normally open or
normally closed condition
•Local mute facility with visual “alarm muted” indication
•Connections for remote alarm indication and mute facility
•10 Volt free inputs and 2 x 24 volt inputs
Part Code
Description
IO-MPA12
Multi input monitoring panel
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Power Supply:100-240Vac
Current Rating: 0.55A max
Connectivity:10 x VFC Alarm Inputs: 24Vdc @ 20mA
2 x Relay Alarm Inputs: 24Vac/dc max
Common Alarm Output: 24Vdc 50mA max
Alarm lamp Output:
24Vdc 50mA max
Muted Lamp Output:
24Vdc 50mA max
Remote Buzzer Output: 24Vdc 50mA max
Remote Mute Button:
24Vdc @ 20mA
Operating Temperature: 0°C to +50°C
Enclosure Rating:
IP54
Dimensions (WxHxD): 360 x 200 x 150mm
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
43
E.C.Products
Building Management Controls & Peripherals
IO modules
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Raise/Lower to Analogue Module AUD
Description
Technical Specification
The AUD converts a floating point signal into a linear analogue
output. There are two inputs on the AUD, one to increase the
analogue output and one to decrease the analogue output.
The output of the AUD is stable when the inputs are both off.
A contact closure or voltage signal to either input will cause
the output of the AUD to begin to ramp either up or down
depending on which input was activated. If both inputs are
“ON” the output will reset to the lowest value of the selected
range.
Features
•Field Selectable Rate of Change
•Field Adjustable Output with Manual Override Potentiometer
•255 Step Resolution
•Current or Voltage Output
•LED Status Indicators
•No Wrap Around
•Relay, Transistor, or Triac Input
Part Code
Description
AUD
Raise/Lower to Analogue Output Module
Supply Voltage:
24...35Vdc or 21.6...28Vac 50/60 Hz
Supply Current:
208 mA max
Signal Source:
Relay contact closure, transistor
or triac
Signal Trigger Level:
Normal Mode: 5 to 26.4 VDC
24 to 26.4 VAC
Triac Mode: 24 to 26.4 VAC
Range Rates of Change:45, 60, 120, 240 seconds
Voltage Preset Ranges: Dip Switch Selectable: 0...1Vdc,
1...2Vdc, 0...4Vdc, 1...5Vdc,
0...10Vdc, 1...11Vdc, 0...13Vdc,
1...14Vdc
Voltage Ranges:
Adjustable 0...20Vdc
Voltage Output Load: 3300 ohms minimum at 20 Volts ± 10%
400 ohms minimum at 10 Volts ± 10%
Current Preset Ranges: Dip Switch Selectable: 0...16mA,
4...20mA
Current Ranges:
Adjustable 0...20mA
Current Output Load: 0 to 750 ohms maximum.
Accuracy:
+/- 3% of span for adjustable ranges
Resolution:
256 steps (all ranges)
Power Output (for user): 24 VDC (+/- 10%), 48mA maximum
Dimensions:
3.75” L x 2.25” W x 1.15” H
Weight:
1.5 oz.
Mounting:
DIN rail mounted
Operating Temperature:0...70°C
Storage Temperature:–20...80°C
Operating Humidity: 10% to 95% non-condensing
Analogue Rescaling Module ARM
Description
Technical Specification
The ARM analogue rescaling module accepts voltage or current
inputs and rescales them to voltage or current outputs. A range
of preset values are link selectable and fine adjustments can be
made using trim potentiometers. The ARM can also reverse the
signal. Units are supplied in a DIN rail mounting housing.
Features
Input signals:
Ambient range:
Output signals:
Power supply:
Dimensions:
0 to 35Vdc
0 to 44mA
–10°C to +50°C
0.25 to 20Vdc
1 to 44mA
24Vac/dc @ 200mA max.
94 x 55 x 26mm
•Field selectable ranges
•Reverse or normal output
•Factory calibrated
•LED power indication
•DIN rail mounting
44
Part Code
Description
ARM
Analogue Signal Rescaling Module
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Voltage to Current Conversion Module IO-VI
Description
Technical Specification
The IO-VI module will convert a 0-10Volt signal to 4-20mA
current output. Din rail mounting with rising clamp terminals
24Vac/dc supply.
Input Signal:0-10Vdc
Output Signal:4-20mA
Power Supply: 24Vac +/- 15%@<70mA
24Vdc +15%/-10%@<30mA
Input Load:
100KΩ (I<0.1mA) approx.
Output Load: 500Ω Max
Terminals:
Rising Clamp for 0.5 to2.5mm² Cable
Ambient Temp:0-50°C
Dimensions:
34mm(W) x 82mm(H) x 43mm
Features
•Power supply 24Vac/dc
•0-10Vdc Input
•4-20mA Output
•Din Rail Mounting
•No scaling Necessary
Part Code
Description
IO-VI
Voltage to mA Conversion Module
IO modules
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Max, Min, Average Module IO6N1
Description
Technical Specification
The IO6N1 is a microprocessor controlled interface designed
to provide maximum flexibility with a minimum of cost. With a
variety of standard inputs the IO6N1 provides the user with the
ability to interface several devices to the analog output. The
IO6N1 can average two to six inputs, output the highest of two
to six inputs, output the lowest of two to six inputs or output the
difference of two inputs. Input ranges are jumper selectable and
all modes and analog output are DIP switch selectable. Output
signal is optically isolated from input signals. The IO6N1 also
accepts up to 6 digital inputs (binary sequence) and outputs a
proportional analog signal. The power output terminal can be
used for power if the inputs are only contact closures.
24Vac (+/- 10%), 50/60 Hz
255 mA maximum
24Vdc or 15Vdc
(jumper selectable)
100 mA maximum
Supply Voltage:
Supply Current:
Power Out:
Input Mode (Six Analog)
Voltage Range/Impedance:
Current Range/Impedance:
0...5Vdc @ 1M Ω
0...10Vdc @ 20,000 Ω
0...20Vdc @ 10,000 Ω
0...20mA @ 249 Ω
(all ranges jumper selectable)
Input Mode (Binary)
Features
•Multiple Inputs
•Up to Six Analogue or up to Six Digital (Binary Sequence)
Inputs
•Selectable Output can:
•Read Two to Six Inputs and Output the Average
•Read Two to Six Inputs and Output the Lowest
•Read Two to Six Inputs and Output the Highest
•Read Analogue Input One and Two and Output the Difference
•LED Power and Status Indicators
•Input and Output is optically isolated
•Selectable modes of operation using jumpers and DIP Switches
•24 VAC Powered
•Equipped with plug-in terminal blocks
Part Code
Description
IO6N1
Max, Min, Average Module
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Six Digital:
15Vdc, 24Vdc or 24Vac
+/-10% @ 100KΩ
One Analog Output:
0...5Vdc @ 1000 Ω
0...10Vdc @ 1000 Ω
0...20Vdc @ 1000 Ω
0...20mA @ 500 Ω maximum
All ranges DIP switch selectable
Analog Mode Output Resolution +/-2% of full scale
Binary Mode Output Resolution 64 steps of resolution
Dimensions:
10.16 x 11.75 x 2.54 cm
Weight:
6.6 oz (187grams)
Mounting:
DIN rail mounted
Operating Temperature:0...70°C
Storage Temperature:–20...80°C
Operating Humidity:
10% to 95% non-condensing
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
45
E.C.Products
Building Management Controls & Peripherals
IO modules
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Electro-Pneumatic Converter IOEPC
Description
Technical Specification
The IOEPC is an electric to pneumatic transducer which
converts an analogue input signal to a proportional pneumatic
output. The unit will automatically modulate its control valve to
regulate the branch line pressure to the selected set point as
determined by the input signal. The unit offers four selectable
input ranges of 0 to 5, 0 to 10, 0 to 15 VDC and 0 to 20 mA.
Output pressure ranges are jumper shunt selectable for 0 to
10, 0 to 15 and 0 to 20 psig, and adjustable in all ranges.
A 0-5 VDC feedback signal indicating the resultant branch
line pressure, is also provided. This signal varies linearly with
branch pressure range selected. EPC’s are designed with
electrical terminals on one end and pneumatic connections on
the other, allowing for maximum convenience in wiring and
tubing installation when panel mounted.
Features
•Connections oriented for convenient panel installation
•Field selectable analog input ranges and pressure output
ranges
•Analog Feedback on branch pressure
•Field adjustable offset and span
•EPC bleeds at the rate of 41 scim
•Closed loop control, 1% accuracy at room temperature
•Plug-in Terminal Block
•Not Position Sensitive
•50/60 Hz Compatible
•Supplied with snap track and integral-in-barb filter
46
Part Code
Description
IOEPC
Electro Pneumatic Converter
IOEPC-G
Electro Pneumatic Converter with gauge
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Power Supply Voltage: 24 VDC (+10%/-5%)
24 VAC (+/-10%) 50/60 Hz
at terminals
Supply Current:
180 mA max.
Feedback Signal Output: Factory Calibrated 0-5 VDC
Input Signal Ranges:
0-5 VDC@ Infinite ohms
0-10 VDC@ Infinite ohms
0-10 VDC@ Infinite ohms
0-20 mA @ 250 ohms
Air Supply:
Maximum 25 psig 172.38 kPa),
minimum 18 psig (124.11 kPa)
Main Air Supply:
0-10 psig ( 68.95 kPa)
0-15 psig (103.43 kPa)
0-20 psig (137.9 kPa)
jumper selectable output pressure
ranges
Accuracy:
1% full scale at room temperature
2% full scale @ 32 to 120°F
Override Contact Rating: 24 VAC or 24 VDC, 1 A maximum
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Dual Phase Cut Module IOPC2
Description
Technical Specification
The IOPC2 converts two 0-10V dc Input Signals to drive
two separate 0-20V 50Hz phase-cut outputs, at 30VA per
channel for the control of small valve or damper actuators. The
IOPC2 features opto-isolation, is powered from 24V ac (with
a common connection to input signal) and has Rising Clamp
Screw Terminals. The output from the IOPC2 can be boosted to
60VA by using two IOPCA1, 1 per channel.
Features
•2 x 20V 30VA Phase Cut Outputs
•2 x 0-10Vdc Inputs
•Opto Isolated
•High Quality Rising Clamp Terminals
•DIN Rail Mounting (TS35)
•Optional 60VA Amplifier Module
Part Code
Description
IOPC2
Dual Phase Cut Module 30VA
IOPCA
Phase Cut Amplifier Module 60VA
IOPC2:
Input Signal:
Output Signal:
Power Supply:
Terminals:
LED Indicators:
Ambient Temp.
Dimensions:
2 x 0-10Vdc
2 x 20V phase cut - 30VA per channel
24Vac (common to 0-10Vdc input)
Rising Clamp for 0.5-2.5mm2 Cable
ON when Power on
Range: 0 to 50°C
78mm x 92.5mm x 55mm (approx.)
IO modules
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
IOPCA1:
Input Signal:
20V Phase Cut from AX-PCM-2-30
Output Signal: 0-20V Phase Cut - 60VA
Power Supply:24Vac
Terminals:
Rising Clamp for 0.5-2.5mm2 Cable
LED Indicators: ON when Power on
Ambient Temp: Range: 0 to 50°C
Dimensions:
47mm x 92.5mm x 50mm (approx.)
Phase Cut Module IOPC1-120
Description
Technical Specification
The IOPC1-120 is designed to convert a single 0-10Vdc Input
Signal to drive a 0-20V 50Hz phase-cut output, at 120VA,
to drive larger valve and damper actuators. The IOPC1-120
features opto-isolation, is powered from 24Vac (with common
connection to input signal) and has high quality rising clamp
screw terminals.
Features
•120VA Phase Cut Output
•0–10Vdc Input
•Opto-Isolated
•High Quality Rising Clamp Terminals
•DIN Rail Mounting (TS35)
•Integral Heatsink
Part Code
Description
IOPC1-120
Phase Cut Module 120VA
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Input Signal:
0-10Vdc (2mA)
Output Signal: 0-20V full wave rectified 50Hz phase cut
VA Rating:120VA
Power Supply: 24Vac (Common to 0-10Vdc input)
Terminals:
Rising Clamp for 0.5-2.5mm2 Cable
LED Indicators: ON when Power on
Ambient Temp: 0 to 50°C
Dimensions:
139mm x 92.5mm x 78mm (approx.)
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
47
E.C.Products
Building Management Controls & Peripherals
Modbus IO modules
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Modbus & BACnet IO Modules MIX
Description
Technical Specification
The MIX module is designed for distributed control systems
using the Building JACE controller. The MIX18 provides 5UI,
5DI, 4AO and 4DO and The MIX38 provides 8UI, 12DI,
6AO and 12DO both support Modbus RTU/ASCII or BACnet
MSTP communication protocol allowing communication
with the building JACE. The advantage of using two open
communication standards allows use in both new and existing
installations as a part of the BMS. Additionally the MIX18
provides rotary switches for setting the address which simplifies
and speeds up the implementation process. Effective processor
with ARM Cortex M3 core allows fast communication and
ensures no delays during data transfer. The module is mounted
in a housing adapted for DIN rail mounting or directly on
a panel. Separate easy to remove connectors allow quick
wiring without removing the entire module. In addition labelled
connectors help installation and replacement process. To
increase the versatility of the module all relay outputs allow
direct control of 230VAC at max 3 Amps which eliminates the
requirement of additional relays resulting in cost savings.
Power Supply:24Vac/dc
Dimensions:
MIX18, 88x110x62mm
MIX38, 160x110x62mm
Protection:IP40
Operating Temp:
–10°C to 50°C
Interface:
RS485 half-duplex
Features
•A large number of all types of IO
•All digital inputs can work as high speed, counters up to
100Hz
•Universal inputs have 16-bit resolution which increases the
accuracy of the measurement
•Wide range of supported temperature sensors (NTC, PT1000
etc.)
•Automatic detection of the signal type in the case of universal
inputs
•Digital outputs 230VAC max 3A allow direct control without
additional relays
•Analogue output with max 20mA load allow direct control of
relays, 12Vdc or SSR with PWM support
•LED’s indicate the status of inputs and outputs
•Support open standards: BACnet and Modbus
•RS485 communication port, half duplex
•Simple and fast addressing from 1 to 99
•24VAC/DC power supply
48
Part Code
Description
MIX18
18 point Modbus/ BACnet IO Module
MIX38
38 point Modbus/ BACnet IO Module
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Light Level Sensor AHKF/RHKF
Description
Technical Specification
These light intensity sensors measures the light level in
applications such as monitoring lighting conditions at
workplaces, in outdoor areas and business facilities. It is used
for daylight-dependant constant light control, as light intensity
or twilight sensor and to control sunshade equipment avoiding
unnecessary heating-up of rooms.
Features
•Outside or inside versions
•Choice of output signal
•Selectable ranges
Power supply:
24 V AC ⁄ DC, max 10 mA @ 24 V DC
Sensor:Photodiode
Measuring ranges: AHKF - 0…500/20K/60K Lux
(switchable via jumpers)
RHKF - 0…500/1K/60K Lux
Output:
4...20 mA (active) or 0 - 10 Vdc
Ambient temp:
–10…+ 50 °C
Electrical connection:0.14 - 1.5 mm² via terminal screws
Measuring error:
< ± 10 % of final value
Temperature drift: < ± 5 % of final value ⁄ 10 K
Enclosure:
Plastic colour pure white
Dimensions:
AHKF - 72 x 64 x 39.4 mm
RHKF - 79 x 81 x 26 mm
4...20mA
0...10Vdc
Description
RHKF-I
RHKF-U
Inside Light Level Sensor 0…500/1K/60K Lux
AHKF-I
AHKF-U
Outside Light Level Sensor 0…500/20K/60K lux
Lighting control
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Wall mount sensor SPIR-FVF
Description
Technical Specification
The SPIR-FVF series of presence detector switches are designed
to provide automatic control of lighting, heating or ventilation
loads. They detect movement using a PIR sensor and turn the
load on. When an area is no longer occupied the load will
switch off after an adjustable time out period.
Features
•Wall mounting on standard single gang back box
•Volt free changeover contact
•Suitable for lighting and heating control
•Built in adjustable time delay function
Part Code
Description
SPIR-FVF
Wall mounted presence detector 230v
SPIR-FVF/24
Wall mounted presence detector 24v
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Load:
10 Amp resistive load
10 Amp incandescent lighting
6 Amp fluorescent lighting
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting
(switch primary of transformer)
Fluorescent lighting
(max 6 fittings recommended)
For fluorescent lighting total power factor
correction capacitance must not exceed 40μF
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
Supply Voltage:
220–240 Volts AC 50 Hz or
12–24Vac/dc for 24 Volt Version
Time Out Period:
Adjustable 10 secs to 60 mins in 2 ranges
Light Level:
Optional adjustment by thumbwheel
light to dark
Fixing Method:
Surface fixing 25mm deep plastic
surface mount moulded box
Flush fixing 25mm steel wall box or 32mm
deep cavity wall box
Terminal Capacity:1.5mm2
Material:
Flame retardant ABS
Type:
Class 2
Temperature:
–10°C to 35°C
Conformity:EMC-89/336/EEC
LVD-73/23/EEC
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
49
E.C.Products
Building Management Controls & Peripherals
Lighting control
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Ceiling Mount Microwave Sensor MWS3A
Description
Technical Specification
The MWS3A-PRM-LV (microwave) detector provides automatic
control of low voltage loads including lighting and BMS systems
with optional manual control. The MWS3A-PRM-LV detects
movement using a highly sensitive microwave detector. This
works by emitting low power microwave signals and measuring
the reflections as the signals bounce off moving objects.
The MWS3A-PRM-LV has a unique adjustable sensor head that
allows the area of detection to be optimised for the application.
Features
•Flush ceiling mount or ceiling surface mount
•Low voltage operation
•Suitable for long range detection in corridors or warehousing
50
Load
LV:
Low voltage supply with relay output rating
16A resistive 10A inductive
Supply Voltage:
Min 11.5VDC max 36VDC,
Min 10VAC max 26.5VAC
Time Out Period:
Adjustable 10 seconds to 99 minutes
Light Level:
Light to dark
Terminal Capacity:2.5mm2
Material:
Flame retardant ABS
Type:
Class 2
Temperature:
–10°C to 35°C
Safety:
The microwave radiation emitted by these
units is extremely low power.
At a distance of >50mm the power density
is <6% of the ANSI IEEE C95.1 –1991
recommended microwave power density.
At a distance of 5mm from the unit it is
<84% of recommended power density.
Conformity:EMC-89/336/EEC
LVD-73/23/EEC
Part Code
Description
MWS3A-PRM-LV
Microwave presence/absence detector with relay output
MWS3A-DBB
Surface mounting box
UN-LCDHS
IR remote control programming handset with LCD screen
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Infra-Red Handset UHS5
Description
Technical Specification
The UHS5 is a compact infrared handset used for the basic
programming of IR enabled EC Products Lighting Controls
Part Code
Description
UHS5
Infra-Red Handset
Dimensions: 86mm x 4mm x 67mm
Weight:0.017kg
Battery:
3Vdc lithium battery CR2025 (supplied with unit)
IR range:7m
Temperature: 0°C to 35°C
Humidity:
5 to 95% non-condensing
Lighting control
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Ceiling Mount Sensor EBDSPIR–VFC
Description
Technical Specification
The SPIR-VFC series of presence detector switches are designed
to provide automatic control of lighting, heating or ventilation
loads. They detect movement using a PIR sensor and turn the
load on. When an area is no longer occupied the load will
switch off after an adjustable time out period.
Features
•Flush Ceiling mounting
•Volt Free changeover contact
•Suitable for lighting and heating control
•Built in adjustable Time delay function
Part Code
Description
EBDSPIR-VFC
Ceiling mounted presence detector 230v
EBDSPIR-VFC/24
Ceiling mounted presence detector 24v
EBD-BB
Round Surface Mount Back Box
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Load:
6 Amp resistive load
2 Amp inductive load
Supply Voltage:
230Vac 50Hz or 12-24Vac/dc
(+/- 10%) for 24 Volt Version
Time Out Period:
Adjustable 10s to 30m
Light Level:
Light to dark
Terminal Capacity: 2.5 mm2
Material:
Flame retardant ABS
Type:
Class 2
Temperature:
–10°C to 35°C
Conformity:EMC-89/336/EEC
LVD-73/23/EEC
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
51
E.C.Products
Building Management Controls & Peripherals
Lighting control
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Wall Mount Microwave Sensors MWS1
Description
Technical Specification
The MWS1A series of microwave presence detector switches
are designed to provide automatic control of lighting, heating
or ventilation loads. The MWS1A detects movement using a
highly sensitive microwave detector. This works by emitting low
power microwave signals and measuring the reflections as the
signals bounce of moving objects. The MWS1A is optimised for
wall mounting applications to give detection over long distances.
Features
MWS1A-PRM-LV:
Supply Voltage:Min 11.5VDC max 36VDC, min 10VAC
max 26.5VAC
Power consumption: On 1.01W
Off 712mW
Load:Low voltage supply with relay output rating
16A resistive 10A inductive
MWS1A-PRM-VFC:
•Detects movement within the units detection range, allowing
load control in response to changes in occupancy
•Receives control and programming commands from an IR
(infrared) handset
•An integral adjustable photocell allows the lights to be kept
off if there is sufficient ambient light
•When movement is detected the load will automatically
turn on. When the area is no longer occupied the load will
automatically switch off after an adjustable time period.
The output can be overridden on and off by activating the
proximity sensor
Part Code
Description
MWS1A-PRM-LV
Microwave Motion Sensor wall mount 24V
Supply Voltage:
230VAC +/- 10%
Frequency:50Hz
Power consumption: On 1.15W
Off 790mW
Load:
Normally closed contact:
2 Amp maximum, Minimum load 100mA
Normally open contact:
6 Amp fluorescent lighting and resistive
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary
of transformer)
MWS1A-PRM-VFC Microwave Motion Sensor wall mount 230V
Batten Mount PIR Detector EBMPIR-MB-PIR
Description
Technical Specification
The EBMPIR-MB is a miniature PIR (passive infrared) presence
detector providing automatic control of lighting loads with
optional manual control using an infrared handset.
It is specifically designed for mounting onto a batten style
luminaire. The unit detects movement using a PIR sensor and
turns the load on. When an area is no longer occupied the
load will switch off after an adjustable time out period.
Features
•Easy Retrofit
•230Volt Switched Live
•Programmable Lux level and Time delay
•Suitable for outdoor use
52
Part Code
Description
EBMPIR-MB-PIR
Batten Mount PIR Detector
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Supply Voltage:
230VAC +/- 10%
Max Switching Load:2 Amps fluorescent & incandescent lighting
2 Amps compact fluorescent lighting
2 Amps low energy lighting
2 Amps low voltage lighting (switch primary
of transformer).
Power consumption: On 799mW, Off 807mW
Cable specification: 1m 1/1.13 solid core cable 105ºC
Material:
Flame retardant ABS/PC
IP rating:IP65
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Description
Metering
Water Meters with Pulsed Output DxxMJ/DxxW
Technical Specification For All Models
This range of water meters have been designed to measure the
volume of water flowing through a pipeline and are provided
with a Reed Switch Pulser which can be connected to remote
reading systems.
Features
•Dry type sealed counter
•Pulsed output
•Hot & Cold water versions available
•Conform to ISO4064
Operating Medium Temp: Cold Water - <40°C
Hot Water - <90°C
Max. Error:
Qmin up to Qt : ±5%
Qt up to Qs : ±2%
Water Pressure:
10 bar
Reed Switch Voltage:24Vac/dc
Reed Switch Current:
0.01A max.
Model Specific Technical Specification
DxMJ:
Dn Size
Part No
Nominal
Flow
Max Flow
mm
Trans.
Flow
m³/hr
Min. Flow
L/hr
Pulse
Options*
Body
Length
Length w.
Couplings
litres/pulse
Height
Width
Weight
mm
Kg
D15MJ
15
3
1.5
120
30
1-10-100
145
230
105
100
D20MJ
20
5
2.5
200
50
1-10-100
190
280
106
100
1.5
1.7
D25MJ
25
7
3.5
280
70
10-100
260
370
115
104
2.8
D32MJ
32
12
6
480
120
10-100
260
375
115
105
3.2
D40MJ
40
20
10
800
200
10-100
300
420
148
125
5.4
D50MJ
50
30
15
1050
300
10-100
300
435
173
126
8.2
DxW:
Dn Size
Part No
Max
Flow
Nominal
Flow
mm
Trans.
Flow
Min.
Flow
m³/hr
Pulse
Options*
Length
Height
litres/pulse
Ø Outer
mm
Bolt
circle
Bolt Ø
Weight
centres
Kg
D50W
50
30
15
3
0.45
100-1000
200
225
165
125
4xM16
16.3
D65W
65
50
25
5
0.75
100-1000
200
242
185
145
4xM16
17
D80W
80
80
40
8
1.2
100-1000
225
255
200
160
8xM16
18
D100W
100
120
60
12
1.8
100-1000
250
265
220
210
8xM16
22.8
28.3
D125W
125
200
100
20
3.0
100-1000
250
275
250
210
8xM16
D150W
150
300
150
30
4.5
1000-10,000
300
325
285
240
8xM20
46
D200W
200
500
250
50
7.5
1000-10,000
350
352
340
295
12xM20
59.6
Cold Water
Hot Water
Description
D15MJC
D15MJH
15mm Screwed Water Meter
D20MJC
D20MJH
20mm Screwed Water Meter
D25MJC
D25MJH
25mm Screwed Water Meter
D32MJC
D32MJH
32mm Screwed Water Meter
D40MJC
D40MJH
40mm Screwed Water Meter
D50MJC
D50MJH
50mm Screwed Water Meter
D50WC
D50WH
50mm Flanged Water Meter
D65WC
D65WH
65mm Flanged Water Meter
D80WC
D80WH
80mm Flanged Water Meter
D100WC
D100WH
100mm Flanged Water Meter
D125WC
D125WH
125mm Flanged Water Meter
D150WC
D150WH
150mm Flanged Water Meter
D200WC
D200WH
200mm Flanged Water Meter
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
53
E.C.Products
Building Management Controls & Peripherals
Metering
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Compact Heat Meters MU-DHMIL
Description
Technical Specification For All Models
The MU-DHMIL is an Integrated multijet flow meter with two
PT500 sensors and an Energy Calculator . The unit has been
designed for district heating or cooling systems and is an
integrated intelligent unit. It can output the data such as Data/
Pulse output to a BMS or in M-bus format. The unit stores the
data six times a day in non-volatile memory, has 12 monthly
values and a one year billing date which is selectable. The unit
comes a Lithium Battery with a minimum 6 year life.
Features
•Measures Heating or Cooling
•Three versions with Qp 0.6 , 1.5 or 2.5 m3/hr
•Integrated meter & calculator
•Pulse or M-Bus output options
•Data is logged for 15 months
•Very High accuracy
•Matched pair of temperature sensors & cable
•Supplied with Ball valve sensor pocket
Power Suppl
D-Cell Lithium HiCap Battery
Display Type: 8 + 3 digit LCD 7mm high
Display Units:
MWh , optional KWh, GJ
Measurement Cycle: Controlled 12.5 to 60 seconds
Nominal Flow Rate: See below
Meters:
15 or 20mm Multijet
Sensors:
2 temperature inputs PT500
Outputs:
Pulse output or M-Bus
Pulse Length:
32 ms , 30Vdc@10ma
Nominal Pressure:
10 bar
Temperature Range: 1 to 130 deg C
Ambient Temperature: 0 to 55 deg C
Protection:IP54
Weight: 0.2 Kgs
Model Specific Technical Specification
Meters
MU-DHMIL20-06
MU-DHMIL20-15
MU-DHMIL25-25
Nominal Flow in m3/hr
0.6
1.5
2.5
Maximum Flow in m3/hr
1.2
3
5
Nominal Diameter DN
15
15
20
Pressure drop at Qp
0.158
0.196
0.165
Pressure drop at Qs
0.604
0.746
0.631
Low Threshold Values - Vertical
3.5 l/hr
7.0 l/hr
10.0 l/hr
Low Threshold Values - Horizontal
4.0 l/hr
7.0 l/hr
10.0 l/hr
Temperature Range - Technical
5...90°C
5...90°C
5...90°C
Dimensions
74.9 x 109.9 mm
74.9 x 109.9 mm
80.1 x 109.9mm
Height from pipe middle
59.3mm
59.3mm
77.8mm
Installation length flow sensor
110mm
110mm
130mm
External Thread flow sensor
G3/4”
G3/4”
G1”
Sensors
54
Sensor colour code
Blue
Red
Black
Low Threshold Value sensor
2.5 l/hr
3.0 l/hr
5.0 l/hr
Part Code
Description
MU-DHMIL-20-06
Compact Heat Meter Package 20mm 0.6m³/hr
MU-DHMIL-20-15
Compact Heat Meter Package 20mm 1.5m³/hr
MU-DHMIL-25-25
Compact Heat Meter Package 25mm 2.5m³/hr
MU-DHMPTBV20
¾” Ball Valve with Sensor Pocket
MU-DHMPTBV25
1” Ball Valve with Sensor Pocket
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Heat Meter Integrator MU-DHMPI
Description
Technical Specification
The MU-DHMPI is an exceptionally versatile Heating Calculator.
The unit has been designed for district heating or cooling
systems and is an integrated intelligent unit. It can output the
data such as Data/Pulse output to a BMS or in M-bus format.
The unit comes with a pair of matched Pt500 sensors and with
as standard a Lithium Battery with a minimum 6 year life or the
option of a 230Vac supply.
Features
•Measures Heating or Cooling
•1,10,100,1000 Litre / pulse options
•Pulse or M-Bus output options
•230 Vac or Lithium Battery
•Data is logged for 15 months
Part Code
Description
MU-DHMPI-PO-LB Heat Meter, pulsed output, battery powered
Power Supply:
230Vac, +/- 15%
D-Cell Lithium HiCap Battery
(minimum 6 years life)
Power Consumption: <1 Watt
Display Type:
7 + 3 digit LCD 7mm high
Nominal Flow Rate:
Qn 0.6 to 600 m3/hr
Inputs: Max 2 temperature inputs PT500
1 flow meter inputs (pulse/litre)
Outputs:
Pulse output or M-Bus
Litre per pulse options: 1, 10, 100, 1000 (specify)
Pulse Length:
32ms, 30Vdc@10ma
Temperature Range: 5 to 150°C
Differential Range:
3K to 100K
Ambient Temperature: 0 to 55°C
Protection:IP54
Conformity:
EN 1434, DS2340, OIML R75,
PTB approved CE; LVD,
EN 50 081-1 and EN 50 082-1
Metering
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
MU-DHMPI-MS-LB Heat Meter, Mbus output, battery powered
MU-DHMPI-PO
Heat Meter, pulsed output, 230Vac powered
MU-DHMPI-MS
Heat Meter, Mbus output, 230Vac powered
kWh Meter MU-EM
Description
Technical Specification
A DIN 96x96 panel mounting Electronic kWh Meter. Easy to
install and convenient to use. Equally suitable for both 3 wire
and 4 wire 3ph unbalanced loads (optionally for single phase
or balanced 3ph systems), these Meters have been designed to
measure accurately irrespective of the type of load – ideal for a
motor or heater, or for a modern electronically controlled load.
Features
•DIN 96x96 Standard Format
•Installation Aids – ‘Right First Time’
•Accuracy better than Class 1
•Isolated Pulse Output
•RS485 MODBUS® Option
•IP54 Protection Category
•Large Clear Display
Part Code
Description
MU-EM368-21
Panel Mount kWh Meter Pulse OP
MU-EM368-22
Panel Mount kWh Meter Modbus & Pulse
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
System:
3 Phase 3 or 4 Wire Unbalanced
Load
Voltage:
400/230V. 3 Phase 3 or 4 Wire.
Current:
5A from external CTs. Fully isolated
Measurement Range:
Voltage 50% to 120%
Current 0.2% to 120%
Frequency Range:
Fundamental 45 to 65Hz
Burden:
Voltage <0.1VA per phase
Current <0.1VA per phase
Overload:
Voltage x4 for 1 hour
Current x40 for 0.5 second max
Auxiliary Supply:
230V 50/60 Hz ±15%
Load:
2VA max.
Overload:
x1.2 continuous
Accuracy:
kWh Better than Class 1
Pulse Output:
1 Pulse per unit of energy
Optional Output:
MODBUS® Serial Comms
Temperature Operating: –10°C to +65°C
Dimensions:
96 x 96 x 50 mm
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
55
E.C.Products
Building Management Controls & Peripherals
Metering
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Modbus Single Phase Energy Meter MU-80Modbus
Description
Technical Specification
The MU-80Modbus Energy meter is a low cost inline meter with
RS485 Modbus communication. It has a slim design allowing
it to fit into a normal distribution board. With a multi-function
backlit display it is easily readable even in dark locations.
Features
•Direct inline connection
•Multifunction backlit display
•Battery backup
•Terminals for 10mm² cable
•Modbus RS485 Communication
•Din Rail Mounting
Part Code
Description
MU-80Modbus
80A Inline Energy meter Modbus
Current range:5–80Amps
Voltage:
230Vac ±20%
Display:
Active Energy(kWh), Voltage(V), Current(A)
Active Power(Kw), Reactive Power(kWAr)
Apparent Power(KVA), Power Factor(cosΦ)
Max Cable size:10mm²
Frequency:50/60Hz
Moulded Current Transformers MU-M
Description
Technical Specification
A range of high quality current transformers the MU-M range
provides accurate measurement of high primary currents,
converting to a 5 Amp secondary current, proportional to the
primary current.
Features
•High Quality
•Comprehensive Measuring Class Accuracies
•Wide Range of Current Ratings
•Wire Sealable Terminal Covers
56
Part Code
Description
MU-M50
Moulded Current Transformer 50:5A
MU-M100
Moulded Current Transformer 100:5A
MU-M150
Moulded Current Transformer 150:5A
MU-M250
Moulded Current Transformer 250:5A
MU-SC100
Split Core Current Transformer 100:5A
MU-SC150
Split Core Current Transformer 150:A
MU-SC200
Split Core Current Transformer 200:5A
MU-SC250
Split Core Current Transformer 250:5A
MU-SC300
Split Core Current Transformer 300:5A
MU-SC400
Split Core Current Transformer 400:5A
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
System Voltage:
720V maximum
Test Voltage:
3kV for 1 minute
System Frequency:
50Hz or 60Hz.
Primary Ratings:
From 50A to 250A (others to order)
Secondary Outputs:5A
Short Circuit Thermal: 3kA for 1 second
Overload Withstand:
1.2 times rated current continuously
Secondary Terminals: M5 screw clamps
Operating Temperature: –20°C to +70°C
Humidity:
Up to 95% RH (non condensing
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Air Differential Pressure Sensor DF
Description
Technical Specification
The DF pressure sensor range is used for measuring aboveatmospheric, below-atmospheric or differential pressures in air.
A piezo-resistive measuring element guarantees high reliability
and accuracy. These pressure sensors are used in clean room,
medical and filter technology, in ventilation and air conditioning
ducts, in spray booths, in large scale catering establishments
for monitoring filters, for flow measuring or for triggering
frequency inverters.
Features
•Differential pressure for air controls
•Choice of output signal
•User selectable output ranges
Power Supply:24Vac/dc
Measuring Range:
See below
Output Signal:
0...10Vdc or 4...20mA
Media Temperature:0...+50ºC
Pressure Connection:
Hose Ø = 4/6 mm
Type of Pressure: Differential
Medium:
Air, non-aggressive,
non-combustible gases
Accuracy:
±3% of final value (at 20ºC)
Zero Point Offset:
Max. +2% of final value
Over Pressure:
Max. 10x measuring range
Long Term Stability:
±1% per year
Media Contacting Parts: Brass, Ni, Nylon, PU, Si
Temperature Drift Values: ±2.5% of final value/10K
Current Consumption:
< 20 mA
Linearity:
±0.8% of final value
Enclosure:
30% glass reinforced polyamide
Dimensions:
72 x 64 x 39.4 mm
Electrical Connections:
Up to 1.5mm² via screw terminals
Cable Union:M16
Humidity:
<95% RH, non-precipitating
Protection:IP65
Accessories: Duct connection set included
Part Code
Description
DF-1141-0010
Air DP Sensor 0...10Vdc output - 0...100/300/500/1000 Pa
DF-1142-0010
Air DP Sensor 4...20mA output - 0...100/300/500/1000 Pa
DF-1141-0050
Air DP Sensor 0...10Vdc output - 0...1000/2000/3000/5000 Pa
DF-1142-0050
Air DP Sensor 4...20mA output - 0...1000/2000/3000/5000 Pa
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Air pressure
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
57
E.C.Products
Building Management Controls & Peripherals
Air pressure
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Air Differential Pressure Sensor PA-LP
Description
Technical Specification
The PA-LP are low cost pressure sensors with a choice of
uni-directional spans. These pressure transmitters incorporate a
durable piezo-resistive, silicon micro-machined sensing element
to enable low pressure measurements down to 300 pascals.
The transmitter is available with a choice of either 4-20mA or
2-10Vdc output and are suitable for 24 Vac/dc power supply.
Features
•Differential pressure for air controls
•Choice of output signal
•Wide choice of output ranges
58
Power Supply:24Vac/dc
Supply Current:
23mA minimum
Output Signal:
2 wire 4...20mA or 3 wire 2...10Vdc
Media Temperature:0...+50ºC
Pressure Connection: ¼” brass barbed fittings
Type of Pressure:Differential
Medium:
Air, non-aggressive,
non-combustible gases
Accuracy:
±1.1% of final value (at 20ºC)
Zero Point Offset:
Max. +2% of final value
Over Pressure:
Max. 10x measuring range
Temp. Drift Values:
±2. of final value/10K
Enclosure:Polycarbonate
Dimensions:
108 x 85 x 34 mm
Electrical Connections: Up to 1.5mm² via screw terminals
Cable Union:M16
Humidity:
<95% RH, non-precipitating
Protection:IP54
Accessories: Duct connection set included
2…10Vdc
4...20mA
Description
PA-LP-3-10-P-E
PA-LP-3-20-P-E
Air Differential Pressure Sensor 0...300 Pa
PA-LP-5-10-P-E
PA-LP-5-20-P-E
Air Differential Pressure Sensor 0...500 Pa
PA-LP-10-10-P-E
PA-LP-10-20-P-E
Air Differential Pressure Sensor 0...1000 Pa
PA-LP-16-10-P-E
PA-LP-16-20-P-E
Air Differential Pressure Sensor 0...1600 Pa
PA-LP-25-10-P-E
PA-LP-25-20-P-E
Air Differential Pressure Sensor 0...2500 Pa
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Pressure transducer PTH-3202
Description
Technical Specification
PTH is a series of pressure transducers which are ideal for
monitoring and controlling pressure differentials in ventilation
systems. PTH transducers are particularly suitable when a
measurement of the actual air pressure is required for demand
control ventilation.
PTH transducers take up very little space and are designed for
direct installation at the measuring point. PTH transducers are
exceptionally compact and easy to install as there is ample
room for attaching cables.
Features
•Temperature-compensated output signal
•No risk of dust-related errors
•Flexible design
•Signal fluctuation damping
•Protection against incorrect installation and calibration
Part Code
Description
PTH-3202
Multi range, Selectable output
PTH-3202-DF
Multi range, Selectable output with Display
Supply voltage:
24V AC ±15%, 50/60 Hz,
13.5-28V DC
Transducer output:
0-10V, 2-10V DC,
4-20 mA, 0-20 mA DC
Measuring range:
–50/+50 Pa, 0/100 Pa, 0/150 Pa
0/300Pa, 0/500 Pa, 0/1000 Pa,
0/1600 Pa, 0/2500 Pa
Ambient Temp. Operation:–20/+40°C
(transient -30/+50°C)
Accuracy at –20/+40°C: ±3% (> 350 Pa), ±10 Pa (< 350 Pa)
Linearity at -20/+40°C: < ±1% of entire transducer range
Maximum pressure:
20 kPa
Power consumption:
2 VA (+5/+40°C), 4 VA (–20/+5°C))
Damping period:
0,4 secs. and 10 secs.
Dimensions:
75 x 36 x 91 mm
Cable dimension:
3 x max. 1,5 mm2
Pressure tubes:
2 x ø 6,2
Enclosure:IP54
Weight:
80 g
Air pressure
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Air Differential Pressure Switch AFS-222
Description
Technical Specification
The AFS-222 Air Differential Pressure Switch is a general
purpose proving switch designed for HVAC and Energy
Management applications. It can be used to sense positive,
negative, or differential air pressure. The plated housing
contains a diaphragm, a calibration spring and a snap-acting
SPDT switch. The sample connections located on each side of
the diaphragm accept 6mm OD copper tubing via the integral
compression ferrule and nut.
Features
•Robust Steel zinc plated housing
•Brass 6mm compression connections
•Wide adjustment range
•HT Version supplied with Brass connection Flanges
Part Code
Description
AFS-222
Air Differential Pressure Switch
AFS-222-HT
High Temp Air Differential Switch
AFS-4M
4 Meter Copper Tube
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Set Point Range:
13pa to 3000pa
Approximate Switching Differential:5pa to 200pa
Measured Media:
Air
Maximum Pressure:
3000pa
Operating Temperature Range:
-40 to 82°C
HT Version 300°C
(Min 2 Meters of Copper
tube must be used)
Electrical Rating:
10(2) Amp.
Contact Arrangement:SPDT.
Electrical Connections:Screw-type terminals with
cup washers.
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
59
E.C.Products
Building Management Controls & Peripherals
Air pressure
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Air Differential Pressure Switch 930
Description
Technical Specification
This 930 range of air differential pressure switches are suitable
for low differential switching applications, and are ideal for
providing indication of fan status or ‘filter dirty’ conditions.
Features
•Close switching differential
•IP65 enclosure option
Max. operating pressure:50 mbar
Pressure Connections:
6mm ID push-on tubing
Electrical rating:
1.5A(0.4) @ 250Vac
Approvals:
Switch according to
VDE0630UG1652
Connections:
Via 0.25” receptacles
Cable Entry:PG11
Housing Material:
Plastic moulding
Protection:
IP54 (IP65 mounted in
130 x 130 x 99mm
enclosure c/w nipples)
Ambient Range:
–20ºC to +85ºC
Installation Category:
IEC 664 Category II
Pollution Degree:
IEC 664 Degree 1
Weight:250g
IP54
IP65
Description
930-80
930-80-IP65
Air DP Switch 20...200 Pa with duct kit
930-83
930-83-IP65
Air DP Switch 50...500 Pa with duct kit
930-85
930-85-IP65
Air DP Switch 200...1000 Pa with duct kit
Air Differential Pressure Switch Accessories
Description
A range of accessories for use with our range of air
pressure products.
60
Part Code
Description
PA1-K
Duct Connection Set
PA1-B
Right Angled Mounting Bracket
PA1-K2
Plastic Pitot Tube
PA-T
Plastic Tee Piece
PA-Y
Plastic Y Piece
PA-TUBE
PVC Tubing per 30m Reel
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Magnehelic Gauges PAG
Description
Technical Specification
The Magnehelic gauge is the industry standard to measure
fan and blower pressures, filter resistance, air velocity,
furnace draft, pressure drop across orifice plates, liquid
levels with bubbler systems and pressures in fluid amplifier
or fluidic systems. It also checks gas-air ratio controls and
automatic valves. A single case size is used for most models of
Magnehelic gauges. They can be flush or surface mounted with
standard hardware supplied. Although calibrated for vertical
position, many ranges above 250Pa may be used at any angle
by simply re-zeroing. However, for maximum accuracy, they
must be calibrated in the same position in which they are used.
These characteristics make Magnehelic gauges ideal for both
stationary and portable applications. A 116mm hole is required
for flush panel mounting. Complete mounting and connection
fittings, plus instructions, are supplied with each instrument.
Accuracy:
±2% of FS
Overpressure:Relief plug opens at approximately 1.72bar,
standard gauges only
Connections:
1/8˝ female NPT
Dimensions:
101.6 mm diameters dial
Temperature:
–6.67 to 60°C
Media:
Air and non-combustible, compatible gases
Air pressure
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Features
•Die cast aluminium case and bezel
•Suitable for air and non-combustible gases
•Overpressure protection
•Shock and vibration resistant
Part Code
Description
PAG-2000-60PA
Magnehelic Gauge 0-60Pa
PAG-2000-100PA
Magnehelic Gauge 0-100Pa
PAG-2000-125PA
Magnehelic Gauge 0-125Pa
PAG-2000-250PA
Magnehelic Gauge 0-250Pa
PAG-2000-300PA
Magnehelic Gauge 0-300Pa
PAG-2000-500PA
Magnehelic Gauge 0-500Pa
PAG-2000-750PA
Magnehelic Gauge 0-750Pa
PAG-2000-1000PA
Magnehelic Gauge 0-1000Pa
PAG-2000-0.5KPA
Magnehelic Gauge 0-0.5kPa
PAG-2000-1KPA
Magnehelic Gauge 0-1kPa
PAG-2000-1.5KPA
Magnehelic Gauge 0-1.5kPa
PAG-2000-2KPA
Magnehelic Gauge 0-2kPa
PAG-2300-60PA
Magnehelic Gauge Centre Zero 30-0-30Pa
PAG-2300-100PA
Magnehelic Gauge Centre Zero 50-0-50Pa
PAG-2300-120PA
Magnehelic Gauge Centre Zero 60-0-60a
PAG-2300-200PA
Magnehelic Gauge Centre Zero 100-0-100Pa
PAG-2300-250PA
Magnehelic Gauge Centre Zero 125-0-125Pa
PAG-2300-300PA
Magnehelic Gauge Centre Zero 150-0-150Pa
PAG-2300-500PA
Magnehelic Gauge Centre Zero 250-0-250Pa
PAG-2300-1000PA
Magnehelic Gauge Centre Zero 500-0-500Pa
Note: other ranges and scale options available
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
61
E.C.Products
Building Management Controls & Peripherals
Liquid pressure
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Liquid Differential Pressure Switch FD113
Description
Technical Specification
The FD113 is a differential pressure switch which is used for
monitoring flow status across pumps, chillers etc. The unit has
and adjustable setpoint with scale and ¼” BSP female pipe
connections.
Features
•Wide Pressure Range
•Suitable for mains voltages
•Visible Setpoint Scale
•SPDT Switch Output for high or low pressure setting
Part Code
Description
FD113
Liquid Differential Pressure Switch
PL14
Copper tube connection kit inc. 4 fittings
Range:
0.3...4.5 bar
Switching differential: 0.2 bar
Pipe connections:
1/4” BSP female
Ambient temperature:–20…+70°C
Liquid temperature: 0 to 110°C
Switch rating:
5(3)A @ 240Vac
Protection:IP30
Dimensions:
128 x 175 x 48mm
Weight:800g
Liquid Differential Pressure Switch 1382
Description
Technical Specification
This series of pressure switches are used to monitor the
difference between two pressures. For example, they can be
used to monitor filter condition and signal when the filter is
becoming blocked. They can also be used as flow monitoring
switches if used across orifice plates etc.
Features
•Five standard pressure ranges
•Diaphragm operated
•Fully adjustable
•Pressure connections 1/8” bsp parallel female brass
•With plug and socket
•CE marked
•Complete with mounting bracket
•Enclosure rating IP65
62
Part Code
Description
1382P-0.25
Liquid DP Switch 20...250 mbar
1382P-1
Liquid DP Switch 0.07...1 bar
1382P-4
Liquid DP Switch 0.2...4 bar
PL18
Copper tube connection kit inc. 4 fittings
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Pressure Ranges:
Type
1382P-1
1382P-4
1382P-0.25
Max. Line Pressure:
Electrical Ratings:
Overload:
Materials:
Pressure Connections:
Pressure Range
Hysteresis
0.07 to 1 bar
0.04 bar
0.2 to 4 bar
0.07 bar
20 to 250 mbar
10 mbar
Pressure range >250mbar: 34 bar
Pressure range <125 mbar: 14 bar
5A @ 250V 50Hz Inductive load
4 times the range
Diaphragm: Beryllium Copper
All Seals: Nitrile rubber
Connection:Brass
Housing:
Aluminium/Zinc diecast
Cover:
Glass Filled Nylon
1/8” BSP Female
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Liquid Differential Pressure Switch LDP
Description
Technical Specification
The Series LDP is a differential pressure switch that makes a
contact output based on the
differential between two pressure sources. Wetted materials of
brass and fluoroelastomer
which are suitable for use with most gases and water based
solutions. The switch can be used for low differential pressure
indication with set point on a decrease of pressure.
Features
•Four Pressure ranges available
•External Screw set point adjustment
•Robust housing
•Weatherproof
Wetted Materials: Connection: Brass
Diaphragm:Fluoroelastomer
Temperature Limits: –1 to 60°C
Pressure Limits:13.8 bar
Continuous single side only pressure should
not exceed 1.25x full differential range
Enclosure Rating:
Weatherproof UL type 4X (IP65)
Repeatability:
±2% of full range
Switch Type:SPDT
Electrical Rating:
5 A @ 125/250 Vac, 5 A res. @ 30 Vdc
Electrical Connection:Removable terminal block
Process Connection: 1/4˝ NPT female
2 NPT to 6mm compression fittings supplied
Set Point Adjustment:External screw
Liquid pressure
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Part Code Description
LDP-0.7
Liquid Differential Pressure Switch 0.17 to 0.69 bar
LDP-1.7
Liquid Differential Pressure Switch 0.69 to 1.72 bar
LDP-3.5
Liquid Differential Pressure Switch 1.72 to 3.45 bar
LDP-5
Liquid Differential Pressure Switch 3.46 to 5.17 bar
Liquid Differential Pressure Sensor 482
Description
Technical Specification
The 482 range of Liquid DP sensors use a piezo-resistive sensor
and incorporate zero and span adjustment. They are ideal
for use in areas requiring exact pressure measurement, low
hysteresis and long term stability in all applications where air,
oil or water is to be monitored.
Features
•Economical Differential Pressure Sensors
•0...10Vdc or 4...20mA output
•Choice of measuring range
•Supplied with 1 metre flying lead
•Complete with mounting bracket
Output Signal:
0...10Vdc 3 wire or 4...20mA 2 wire
Power Supply:
0...10Vdc - 24Vac/dc
4...20mA - 24Vdc
Pressure Ranges:
See below
Over Pressure:
1.5 x FS
Accuracy:
0.25% FS
Repeatability:
0.2% FS/Year typical
Pressure Connection: 1/8” BSP female
Temperature:–20…+80°C
Humidity:
0...80% RH
0...10Vdc
4...20mA
Description
482-0.4V
482-0.4
Liquid Differential Pressure Sensor 0...0.4 bar
482-1V
482-1
Liquid Differential Pressure Sensor 0...1 bar
482-2V
482-2
Liquid Differential Pressure Sensor 0...2 bar
482-4V
482-4
Liquid Differential Pressure Sensor 0...4 bar
482-7V
482-7
Liquid Differential Pressure Sensor 0...7 bar
482-10V
482-10
Liquid Differential Pressure Sensor 0...10 bar
Copper tube connection kit inc. 4 fittings
PL18
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
63
E.C.Products
Building Management Controls & Peripherals
Liquid pressure
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Liquid Pressure Switch PS1
Description
Technical Specification
The PS1 is a cost effective pressure switch suitable for
monitoring pumps, chillers, valves etc. The unit has an
adjustable setpoint with adjustable differential and has a gauge
to show the liquid pressure.
Features
•Wide Pressure Range
•Suitable for mains voltages
•Visible Setpoint Scale
•SPDT Switch Output
Part Code
Description
PS1
Liquid Pressure Switch –0.5...7 bar
Range:
–0.5...7 bar
Differential:
0.5...5 bar
Pressure Connection: ¼” BSP male
Contact Rating:
24(10) @ 230Vac
Protection:IP44
Ambient Temperature:–50…+70°C
Liquid Temperature:–50…+70°C
Dimensions:
86 x 75 x 44mm
Liquid Static Pressure Sensor PT603
Description
Technical Specification
The PT603 range of Liquid Pressure sensors use a piezo-resistive
sensor and incorporate IP65 connector for wiring with a ¼”
BSP threaded connection.
They are ideal for use in areas requiring exact pressure
measurement, low hysteresis and long term stability in all
applications where air, oil or water is to be monitored.
Features
•Economical Pressure Sensors
•0...10Vdc or 4...20mA output
•Choice of measuring range
•1/4” BSP threaded connection
64
Output Signal:
0...10Vdc 3 wire or 4...20mA 2 wire
Power Supply:
0...10Vdc - 24Vac/dc
4...20mA - 24Vdc
Load Resistance:
0...10Vdc - >50KΩ
4...20mA - <800Ω
Pressure Ranges:
See below
Accuracy:
0.2% FS
Repeatability:
0.1% FS/Year typical
Pressure Connection: ¼” BSP male
Wiring:
IP65 Hirschmann Connector
Temperature:–10…+80°C
Humidity:
0...80% RH
0...10Vdc
4...20mA
Description
PT603-0.1V
PT603-0.1
Liquid Static Pressure Sensor 0-100 mbar
PT603-0.25V
PT603-0.25
Liquid Static Pressure Sensor 0-250 mbar
PT603-0.6V
PT603-0.6
Liquid Static Pressure Sensor 0-600 mbar
PT603-1V
PT603-1
Liquid Static Pressure Sensor 0-1 bar
PT603-4V
PT603-4
Liquid Static Pressure Sensor 0-4 bar
PT603-6V
PT603-6
Liquid Static Pressure Sensor 0-6 bar
PT603-10V
PT603-10
Liquid Static Pressure Sensor 0-10 bar
PT603-25V
PT603-25
Liquid Static Pressure Sensor 0-25 bar
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Single Phase DIN Rail Thyristor Controllers TCD1
Description
Technical Specification
The DIN Rail mounting Power Controllers TCD1 is suitable for
providing control of electric heating loads from an analogue
signal. Applications include electric heating coils, heating
cables and electric furnaces. The units utilise solid-state
switching with “zero crossing technology” to provide accurate
switching control. All items are provided with an alarm output
for over temperature protection and LED Indication of Output
ON. The TCD1 are designed to mount on DIN rail.
Features
•Selectable Control Input
•2Kw, 4kW and 7kW Models
•Over Temperature Protection
•24Vac/dc or self-powered options
•LED Indication
•DIN Rail Mounting
Part Code
Description
TCD1-2
Single Phase DIN Rail Thyristor Controller 2Kw
TCD1-4
Single Phase DIN Rail Thyristor Controller 4Kw
TCD1-7
Single Phase DIN Rail Thyristor Controller 7Kw
TCD1-x-SP
Self-powered Option Factory fitted
Input:
Selectable 0...10V, 0...5V, 2...10V,
4...20mA
Power Supply:
24Vac/dc +/-10%
(self-powered option)
Alarm Output:
24V alarm output drops to 0V on alarm
for connecting to external relay
Max Heater Duty:
2Kw, 4Kw or 7Kw
dependent on model
Rated Load:
Load@220V Dissipated Heat
2Kw9A
9W
4Kw18A
23W
7Kw30A
35W
Rated Supply:
220...255Vac, 50/60Hz
LED Indication:
ON when output is on.
Terminals:
Rising cage terminals
Ambient Temp. Range: Maximum 45°C without de-rating
Dimensions:
2Kw - 75 x 94 x 80 mm
4/7Kw - 170 x 94 x 102 mm
Country of Origin: United Kingdom
Thyristors
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Three Phase DIN Rail Thyristor Controllers TCD3
Description
Technical Specification
The DIN Rail mounting Power Controllers TCD3 are suitable for
providing control of electric he ating loads from an analogue
signal. Applications include electric heating coils, heating
cables and electric furnaces. The units utilise solid-state
switching with “zero crossing technology” to provide accurate
switching control. All items are provided with an alarm output
for over temperature protection and LED indication of Output
ON. The TCD3 are designed to mount on a DIN rail.
Features
•Selectable Control Input
•12kW and 18kW Models
•Over Temperature Protection
•24Vac/dc or self-powered options
•LED Indication
•DIN Rail Mounting
Part Code
Description
TCD3-12
Three Phase DIN Rail Thyristor Controller 12Kw
TCD3-18
Three Phase DIN Rail Thyristor Controller 18Kw
TCD3-x-SP
Self-powered Option Factory fitted
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Input:
Selectable 0...10V, 0...5V, 2...10V,
4...20mA
Power Supply:
24Vac/dc +/-10%
(self-powered option)
Alarm Output:
24V alarm output drops to 0V on
alarm for connecting to external relay
Rated Load:
Load/Ph Dissipated Heat
12Kw16A
33W
18Kw25A
50W
Max Heater Duty:
12Kw or 18Kw dependent on model
Rated Supply:
380...440Vac, 50/60Hz
LED Indication:
ON when output is on.
Terminals:
Rising cage terminals
Ambient Temp. Range:Maximum 45°C without de-rating
Dimensions:
170 x 110 x 102 mm
Country of Origin: United Kingdom
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
65
E.C.Products
Building Management Controls & Peripherals
Thyristors
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Three Phase Panel Mounted Thyristor Controllers TCP3
Description
Technical Specification
The panel mounting Power Controllers TCP3 are suitable for
providing control of electric heating loads from an analogue
signal. Applications include electric heating coils, heating
cables and electric furnaces. The units utilise solid-state
switching with “zero crossing technology” to provide accurate
switching control. All items are provided with an alarm output
for over temperature protection and LED Indication of
Output ON. The TCP3 are designed to mount on the control
panel backplate.
Features
Input:
Selectable 0...10V, 0...5V, 2...10V,
4...20mA
Power Supply:
24Vac/dc +/-10% (self-powered option)
Alarm Output:
24V alarm output drops to 0V on alarm
for connecting to external relay
Max Heater Duty:
27Kw, 36Kw or 57Kw
dependent on model
Rated Load:
Load/Ph Dissipated Heat
27Kw37A
36Kw50A
57Kw80A
84W
100W
160W
Rated Supply:
380...440Vac, 50/60Hz
LED Indication:
ON when output is on.
Terminals:
Control - Rising cage terminals
Power - DIN rail terminals
Ambient Temp. Range:Maximum 45°C without de-rating
Dimensions:
27/36Kw - 257 x 102 x 142 mm
57Kw - 257 x 200 x 158 mm
Country of Origin: United Kingdom
•Selectable Control Input
•27Kw, 36Kw and 57Kw Models
•Over Temperature Protection
•24Vac/dc or self-powered options
•LED Indication
•Panel Mounted
Part Code
Description
TCP3-27
Three Phase Panel Mount Thyristor Controller 27Kw
TCP3-36
Three Phase Panel Mount Thyristor Controller 36Kw
TCP3-57
Three Phase Panel Mount Thyristor Controller 57Kw
TCP3-x-SP
Self-powered Option Factory fitted
Slim Line Switch Mode Power Supplies DR15
Description
Technical Specification
The DR15 power supplies are a slim 17.5mm wide Din rail
mounting 15W dc power supply, ideal for applications where
space is critical and only low DC power is needed, with visual
indication of input voltage and supply on. Fitted with and
internal replaceable input fuse and auto recovery short circuit
protection.
Output current:@ –20 to +40°C, 230 Vac input 12 Volt 1.25A
/ 24V 0.63A
Rated power:
12 Watts
Output power: @–20...+40°C, 230 Vac input 15 Watts
Input voltage:
110 to 240 Vac
Dimensions:
17.5mm wide, 60mm deep
Features
•High efficiency (up to 91%)
• Short circuit protection: hiccup (auto-recovery) Mode
• Dual and series connection permissible
• Input protection: replaceable internal fuse
66
Part Code
Description
DR15-12
12Vdc 15W Switch mode power supply
DR15-24
24Vdc 15W Switch mode power supply
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Universal Input Power Supply DRx0-xx
Description
Technical Specification
These Switch mode power supplies are a universal AC
voltage input with a regulated dc output capable of supplying
2.5Amps. The Units incorporate LED power on indication and
have dual output terminals. This Unit has a small footprint so is
ideal when space on the DIN is restricted.
Features
•DIN rail mounting
•Universal AC input
•LED indicator for power on
•3 year warranty
Part Code
Description
DR30-12
Universal Input 12Vdc Power Supply
DR60-24
Universal Input 24Vdc Power Supply
AC Input Voltage:
85-264Vac, 47-63Hz
AC inrush Current: Cold start 27A at 115Vac,
36A at 230Vac
Output Voltage:
DR30-12: 12Vdc
DR60-24: 24Vdc
Adjustment Range: ±10% rated voltage
Output Current:0...2.5A
Output Power:
DR30-12: 30W
DR60-24: 60W
LED Indication:
Power On
Accuracy:±1%
Efficiency:84%
Overvolt Protection: 115%...135% rated output voltage
Overload Protection: 120%...140% rated output voltage
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–20°C to +50°C @ 100%,
60°C @ 80% load
Dimensions:
93mm(H) x 78mm(W) x 55mm approx
Power supplies
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Din Rail Mount AC Power Supplies PSD
Description
Technical Specification
The PSD Din Rail Mounted Power Supplies are designed for
applications where a low current AC Supply is required such as
valves and Damper actuators.
Features
•Din Rail mounting
•Compact
•Fused Primary and Secondary
•240Vac Primary, 24Vac Secondary
•1.5VA, 6VA and 15VA Versions
Part Code
Description
PSD-1.5
Din Rail Transformer 24Vac 1.5VA
PSD-6
Din Rail Transformer 24Vac 6VA
PSD-15
Din Rail Transformer 24Vac 15VA
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Output:24Vac
Supply Voltage:230Vac
Current ratings: 1.5VA, 6VA and 15VA
Termination:
Rising Clamp for 0.5 to 2.5mm² Cable.
Fuse rating: 1.5VA100mA
6VA250mA
15VA630mA
Dimensions:1.5VA: 47 x 55 x 93 mm
6VA: 58 x 60 x 93 mm
15VA: 80 x 69 x 93 mm
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
67
E.C.Products
Building Management Controls & Peripherals
Power supplies
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
24Vac to 24Vdc Power Supplies PS-24
Description
Technical Specification
The PS-24 is a DIN rail mounted power supply providing a
regulated 24Vdc output from a 24Vac supply and is suitable for
all DC power requirements such as sensors.
Features
•Regulated 24Vdc Output at 1A
•Fused output protection
•LED Power indication
•DIN rail mounting
Part Code
Input Supply: 24Vac ±15%
Output Supply: 24Vdc ±10% @ 1A
Output Fuse:1A
LED Indication: Power ON
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
0°C to +50°C, 0-80% RH non-condensing
Dimensions:
76mm(H) x 57mm(W) x 62mm approx
Description
PS-24AC-DC-E 24Vac to 24Vdc Power Supply - Earthed Output
PS-24AC-DC-F 24Vac to 24Vdc Power Supply - Floating Output
230Vac Transformers PS
Description
Technical Specification
The PS 230Vac to 24Vac Transformers are available in a choice
of power ratings and are suitable for a wide of range of power
supply applications requiring a 24Vac supply.
Features
Input Voltage:
Output Voltage: 24Vac ±10%
Terminals:
Rising clamp 0.5 – 2.5mm² cable
Ambient:
–10°C to +50°C, 0-95% RH non-condensing
•M4 Stud Earth Connector
•Ratings up to 250V
68
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
220/240Vac ±5%
Outline Dimensions (mm)
Part Code
Rated Power
(VA)
W
L
H
PS-25
25
60
78
72
PS-50
50
77
75
70
PS-100
100
86
82
78
PS-150
150
97
82
85
PS-250
250
115
93
98
Part Code
Description
PS-25
230Vac transformer 25VA
PS-50
230Vac transformer 50VA
PS-100
230Vac transformer 100VA
PS-150
230Vac transformer 150VA
PS-250
230Vac transformer 250VA
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Humidity Sensors RHTRx / RHTDx / RHTOx
Description
Technical Specification
This type of relative humidity and temperature sensors utilize
state-of-the-art single chip multi-sensor module comprising a
calibrated digital output to enable stability and immunity to
interference. Application of CMOS processes with patented
micro-machining ensures highest reliability and excellent longterm stability. The device includes a capacitive polymer sensing
element for RH and a bandgap temperature sensor. Both are
seamlessly coupled to a 14 bit analog to digital converter, and
a serial interface circuit on the same chip. Due to its integrated
sensing and D/A conversion, it enables high signal quality, fast
response time and immunity to external disturbance.
Features
•High Noise immunity for stability by digitized signals
•Output is selectable 0-10V or 4-20mA
•No loss of accuracy up to 100% RH
•4 selectable temperature ranges
•24V AC/DC supply
•Direct Thermistor Option
Humidity:
RH sensor:
Capacitive polymer
Accuracy:
+/- 3% or +/-2% @ 25°C
Response time:
< 8 sec
Long term stability:< 2% RH per year
Hysteresis:
+/- 1% RH
Output:0-100%RH
Humidity
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Temperature:
Bandgap temperature sensor
Accuracy: ±0.5 deg C at 25°C
Response time:
< 8 sec
Housing material:ABS
Ambient range: –20°C to +50°C
Power Supply:
24AC/DC supply for 0-10V
24Vdc supply for 3 wire 4-20mA
Connection:
0.5-1.5 mm cable.
Dimensions:
RHTR:
RHTD:
RHTO:
Part Code Description
RHTR2
2% Space Humidity & Temperature Sensor
RHTR3
3% Space Humidity & Temperature Sensor
RHTR2-T
2% Space Humidity Sensor with direct thermistor
RHTR3-T
3% Space Humidity Sensor with direct thermistor
RHTD2
2% Duct Humidity & Temperature Sensor
RHTD3
3% Duct Humidity & Temperature Sensor
RHTD2-T
2% Duct Humidity Sensor with direct thermistor
RHTD3-T
3% Duct Humidity Sensor with direct thermistor
RHTO2
2% Outside Humidity & Temperature Sensor
RHTO3
3% Outside Humidity & Temperature Sensor
RHTO2-T
2% Outside Humidity Sensor with direct thermistor
RHTO3-T
3% Outside Humidity Sensor with direct thermistor
RH-SS1
Radiation Shield for RHTD
85 x 85 x 28 mm
96mm dia. Housing x 56mm high
Probe - 230mm long
96mm dia. Housing x 56mm high
Probe - 85mm long
Please specify thermistor type when ordering direct
thermistor outputs
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
69
E.C.Products
Building Management Controls & Peripherals
Humidity
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Humidity & Temperature Sensors RFF/RFTF/KFF/KFTF
Description
Technical Specification
The RFF/KFF range of humidity sensors is used in refrigeration
and air conditioning. They convert the humidity and
temperature measurements into analogue signals of 0...10Vdc
or 4...20mA. A capacitive RH sensor and NTC thermistor
provide accurate measurements and long term stability.
Power Supply:
Sensors:
Measuring Range:
Operating Range:
Accuracy:
Outputs:
Connection:
Enclosure:
Features
•Humidity only or Humidity & Temperature
•Temperature Outputs
•Optional Direct Thermistor for temperature measurement
•Choice of outputs
•Space or Duct Mount Versions
Part Code
Description
RFF-I
3% Space Humidity Sensor 4...20mA output
RFF-U
3% Space Humidity Sensor 0...10Vdc output
RFF-x-T
Direct Thermistor Option for RFF-I/RFF-U
RFTF-I
3% Space Humidity & Temperature Sensor 4...20mA output
RFTF-U
3% Space Humidity & Temperature Sensor 0...10Vdc output
KFF-I
3% Duct Humidity Sensor 4...20mA output
KFF-U
3% Duct Humidity Sensor 0...10Vdc output
KFTF-I
3% Duct Humidity & Temperature Sensor 4...20mA output
KFTF-U
3% Duct Humidity & Temperature Sensor 0...10Vdc output
24Vac/dc for 0..10Vdc output
15...36Vdc for 4...20mA output
max. load 500Ω
Capacitive Humidity sensor, NTC temp.
Humidity - 0...100% RH
Temperature - 0...50°C
Humidity - 10...90% RH
Temperature - 0...50°C
Humidity - ±3% RH 40...60% RH
otherwise ±5%
Temperature - ±0.8K at 20°C
0...10Vdc or 4...20mA
0.5-1.5 mm cable.
RFF - White ABS 79 x 81 x 26 mm
KFF - Polyamide 72 x 64 x 39.4 mm
Duct Humidistats DBKH
Description
Technical Specification
Relative duct humidity control in air conditioning systems with
set point adjustment by knob and control of 1 stage humidifiers
and dehumidifiers. Well-suited in domestic, commercial and
industrial areas for a large variety of applications in the air
conditioning field.
Features
•Exposed or concealed Setpoint adjustment
•Suitable for swimming pool applications
70
Part Code
Description
DBKH-10
Duct Humidistat
DBKH-10U
Duct Humidistat, concealed setpoint
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Sensitive elem.:
Several synthetic fabric bands.
Contacts:
SPDT contacts
Switch capacity: Humidify: 2 A, 250 Vac
Dehumidify: 5 A, 230 Vac
Differentials:4%
Working temp.: 0...+60 °C
Storage:
–20...+70 °C
Temp. coeff.:
–0.2% r.h./K at 20 °C
Max air velocity: 15 m/s
Housing:ABS
Weight:
0.12 kg
Size:
115 x 70 x 35 mm
Protection:IP20
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Space Humidistats DBZH
Description
Technical Specification
Relative space humidity control in air conditioning systems with
set point adjustment by knob and control of 1 stage humidifiers
and dehumidifiers. Well-suited in domestic, commercial and
industrial areas for a large variety of applications in the air
conditioning field.
Features
•Exposed or concealed Setpoint adjustment
•Suitable for swimming pool applications
Part Code
Description
DBZH-101
Space Humidistat
Sensitive elem.:
Several synthetic fabric bands.
Contacts:
SPDT contacts
Switch capacity: Humidify: 2 A, 250 Vac
Dehumidify: 5 A, 230 Vac
Differentials:4%
Working temp.: 0...+60 °C
Storage:
–20...+70 °C
Temp. coeff.:
–0.2% r.h./K at 20 °C
Max air velocity: 15 m/s
Housing:ABS
Weight:
0.12 kg
Size:
115 x 70 x 35 mm
Protection:IP20
Room temperature sensors
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Space Temperature Sensors TE-Rx
Description
Part Code
Description
The TE-R range of space temperature sensors are designed to
interface with a wide variety of HVAC control equipment.
Units are available with a high quality thermistor element or
platinum element.
TE-RT
10K3A1, Trend
TE-RA
10K4A1, Andover, Delta
TE-RH
20K6A1, Honeywell
The housing is designed for direct surface mounting and with
fixing holes for standard recessed patress and conduit boxes.
TE-R100
PT100A
TE-R1K
PT1000A, Cylon
TE-RLAN
Ni1000 TK5000, Siemens
TE-RSAT
Satchwell
TE-RTAC
1.8K3A1, TAC
TE-R3K
3K3A1, Alerton
TE-RD
30K6A1, Drayton
TE-RP
50K6A1, Priva
TS-GD
Sensor guard
The housing is designed to maximise air flow through it thus
providing fast response times and returning values indicative of
the space in which it is installed.
Features
•Flame retardant ABS housing
•Wide choice of sensor options
Technical Specification
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:
Flame retardant ABS
Colour:White
Protection:IP30
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–20°C to +60°C, 0-95% RH non-condensing
Dimensions: 85mm(H) x 85mm(W) x 30mm approx
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Room temperature sensors
DBZH-101U Space Humidistat, concealed setpoint
For Set point, add: /T
For Button, add: /B
For Switch, add: /S
For Red LED, add: /R
For Green LED, add: /G
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
71
E.C.Products
Building Management Controls & Peripherals
Ceiling sensor
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Ceiling Mounted Temperature Sensor TE-DTFx
Description
Small built-in temperature sensor for in-wall installation. It is
preferably installed in walls and ceilings, fitting in well with the
overall view of architecture.
Features
•Wide choice of sensor options
Technical Specification
Description
TE-DTF/T
10K3A1, Trend
TE-DTF/A
10K4A1, Andover, Delta
TE-DTF/H
20K6A1, Honeywell
TE-DTF/100
PT100A
TE-DTF/1K
PT1000A, Cylon
TE-DTF/LAN
Ni1000 TK5000, Siemens
TE-DTF/TAC
1.8K3A1, TAC
For other lengths add length to end of Part number when
ordering. Lengths available from Stock 50, 65, 75, 100, 200,
250, 300, 350, 400, 500, 600, 700, 800, 1000mm
Measuring range: –20...+ 90 °C
Sensor Type:
Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C,
RTD - Class A
Connecting cable: ca. 135 mm, 2 x 0.25 mm²
Colour:
Signal white
Connecting head:Aluminium
Process connection: Inside suspended ceiling,
cutout Ø = 26 mm
Humidity:
< 95 % r. H.
Protection type:
IP 30
Outside temperature sensors
Part Code
Outside Air Temperature Sensors TE-Ox
Description
The TE-O range of outside air temperature sensors are designed
to interface with a wide variety of HVAC control equipment.
Units are available with a high quality thermistor element or
platinum element.
The housing has a quick release lid for ease of installation
and the sensor sealed into a brass lug mounted into the side
of the housing.
Features
•IP65 Flame retardant ABS housing
•Brass sensor lug
•Wide choice of sensor options
•Available with radiation shield
Part Code
Standard
With Radiation Shield Description
TE-OT
TE-OT/RS
10K3A1, Trend
TE-OA
TE-OA/RS
10K4A1, Andover, Delta
TE-OH
TE-OH/RS
20K6A1, Honeywell
TE-O100
TE-O100/RS
PT100A
TE-O1K
TE-O1K/RS
PT1000A, Cylon
TE-OLAN
TE-OLAN/RS
Ni1000 TK5000, Siemens
TE-OSAT
TE-OSAT/RS
Satchwell
TE-OTAC
TE-OTAC/RS
1.8K3A1, TAC
TE-O3K
TE-O3K/RS
3K3A1, Alerton
TE-OD
TE-OD/RS
30K6A1, Drayton
TE-OP
TE-OP/RS
50K6A1, Priva
Technical Specification
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:
Flame retardant ABS
Probe:
Brass Lug
Protection:IP65
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–20°C to +50°C, 0-95% RH non-condensing
72
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Description
The Black Bulb temperature sensor determines the effective
portion of active radiation or also the effective radiant heat at
the measured location. Due to the measuring method applied
by the dark radiation temperature sensor in combination with its
positioning in the room, excellent measuring results are achieved.
Features
•Flame retardant ABS housing
Space
IP65
Description
TE-RB/T
TE-OB/T
10K3A1, Trend
TE-RB/A
TE-OB/A
10K4A1, Andover, Delta
TE-RB/H
TE-OB/H
20K6A1, Honeywell
TE-RB/100
TE-OB/100
PT100A
TE-RB/1K
TE-OB/1K
PT1000A, Cylon
TE-RB/LAN
TE-OB/LAN
Ni1000 TK5000, Siemens
TE-RB/TAC
TE-OB/TAC
1.8K3A1, TAC
Technical Specification
Sensor Type: Thermistor or RTD element
Housing:
Flame retardant ABS - white
Protection:IP30/IP65
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–20°C to +60°C, 0-95% RH
Button Temperature Sensors TE-Bx
Description
The TE-B range of button temperature sensors are designed to
interface with a wide variety of HVAC control equipment.
Units are available with a high quality thermistor element or
platinum element.
Features
•Button type housing for discrete temperature measurement
•Plastic, stainless steel or brass versions
•Wide choice of sensor options
Technical Specification
Sensor Type: Thermistor or RTD element
Accuracy: Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:White Plastic, Satin Brass, Polished Brass or
Stainless Steel
Protection:IP30
Termination: 300mm of PVC flying lead
Ambient:
0°C to +50°C, 0-95% RH non-condensing
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Part Code
Description
TE-BT
10K3A1, Trend
TE-BA
10K4A1, Andover, Delta
TE-BH
20K6A1, Honeywell
TE- B100
PT100A
TE- B1K
PT1000A, Cylon
TE-BLAN
Ni1000 TK5000, Siemens
TE-BTAC
1.8K3A1, TAC
TE-B3K
3K3A1, Alerton
TE-BD
30K6A1, Drayton
TE-BP
50K6A1, Priva
For Plastic, add:
/P
For Satin Brass, add:
/B
Button temperature sensors
Black Bulb Temperature Sensors TE-RB/OBx
Radiant temperature sensors
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
For Polished Brass, add: /PB
For Stainless Steel, add: /SS
For Matching Plate add:/BP for brass
/PBP for Polished brass
/SP for Stainless
/PP for Plastic
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
73
E.C.Products
Building Management Controls & Peripherals
Thimble temperature sensors
Anti-ligature temperature sensors
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Anti-Ligature Sensor TE-AL
Description
The TE-AL Anti-Ligature sensors are designed for use where
Space temperature needs to be monitored and a discrete finish
is required, they are available in 3 standard finishes but can
also be a customer specific finish.
Features
•Extremely low profile
•3 Standard finishes available from stock
•Wide choice of sensor types
Technical Specification
Sensor Type:
Accuracy:
100°C
Plate finishes:
Protection:
Termination:
Ambient:
Thermistor or RTD element
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C, ±0.35°C @
White plastic, brass or stainless steel
IP30
250mm flying lead
0°C to +50°C, 0-95% RH non-condensing
Description
TE-AL-T
10K3A1, Trend
TE-AL-A
10K4A1, Andover, Delta
TE-AL-H
20K6A1, Honeywell
TE- AL-100
PT100A
TE-AL-1K
PT1000A, Cylon
TE-AL-LAN
Ni1000 TK5000, Siemens
TE-AL-TAC
1.8K3A1, TAC
TE-AL-3K
3K3A1, Alerton
TE-AL-D
30K6A1, Drayton
TE-AL-P
50K6A1, Priva
For Plastic, add: /P
For Satin Brass, add: /B
For Polished Brass, add: /PB
For Stainless Steel, add: /SS
Thimble Temperature Sensors TE-Tx
Description
Part Code
Description
The TE-T range of thimble temperature sensors are designed to
Interface with a wide variety of HVAC control equipment.
Units are available with a high quality thermistor element or
platinum element.
TE-TT
10K3A1, Trend
TE-TA
10K4A1, Andover, Delta
TE-TH
20K6A1, Honeywell
The sensor is housed in a white plastic thimble type enclosure
with optional aluminium, brass or stainless steel versions also
available.
TE-T100
PT100A
TE-T1K
PT1000A, Cylon
TE-TLAN
Ni1000 TK5000, Siemens
TE-TSAT
Satchwell
TE-TTAC
1.8K3A1, TAC
TE-T3K
3K3A1, Alerton
TE-TD
30K6A1, Drayton
TE-TP
50K6A1, Priva
TE-Tx-B
Brass Thimble
TE-Tx-AL
Aluminium Thimble
TE-Tx-SS
St. Stl. Thimble
TE-Tx-PB
Polished Brass
Features
•Thimble type housing for discrete temperature measurement
•Plastic, brass, stainless steel or aluminium versions
•Wide choice of sensor options
Technical Specification
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:
White plastic, brass, aluminium or stainless steel
Protection:IP30
Termination: 2 metres of PVC flying lead
Ambient:
0°C to +50°C, 0-95% RH non-condensing
74
Part Code
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Description
Part Code
Description
The TE-AV range of duct averaging temperature sensors are
designed to interface with a wide variety of HVAC control
equipment. Units are available with a high quality thermistor
element or platinum element.
TE-AVT
10K3A1, Trend
TE-AVA
10K4A1, Andover, Delta
TE-AVH
20K6A1, Honeywell
The housing has a quick release lid for ease of installation and
gasket for sealing to the duct. The probe is flexible copper and
is available in standard 2 metre length.
TE-AV100
PT100A
TE-AV1K
PT1000A, Cylon
TE-AVSAT
Satchwell
TE-AVTAC
1.8K3A1, TAC
TE-AV3K
3K3A1, Alerton
TE-AVP
50K6A1, Priva
Features
•IP65 Flame retardant ABS housing
•Stainless steel probe
•Wide choice of sensor options
Technical Specification
Sensor Type: Thermistor or RTD element - see order codes
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:
Flame retardant ABS
Probe:
6mm diameter flexible copper 2000mm
Protection:IP65
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–20°C to +85°C, 0-95% RH non-condensing
Low Profile Temperature Sensor TE-LP
Description
The TE-LP Low profile temperature sensor is for applications
where the conventional Thimble sensor is too obtrusive such
as high end housing and offices, it offers good response
characteristics due to the vertical groves on the front. It is
available in 5 finishes as standard but other specified finishes
can be made to order.
Features
•Low profile design
•8mm Diameter fixing.
•5 finishes available as standard.
•Wide range of sensor types available.
Description
TE-LPT
10K3A1, Trend
TE-LPA
10K4A1, Andover, Delta
TE-LPH
20K6A1, Honeywell
TE- LP100
PT100A
TE- LP1K
PT1000A, Cylon
TE-LPLAN
Ni1000 TK5000, Siemens
TE-LPTAC
1.8K3A1, TAC
TE-LP3K
3K3A1, Alerton
TE-LPD
30K6A1, Drayton
TE-LPP
50K6A1, Priva
For Plastic, add /P
Technical Specification
Sensor Type:Thermistor or RTD element
Accuracy: Thermistor: ±0.2°C, 0...70°C
RTD: Class A ±0.15°C @ 0°C, ±0.35°C @ 100°C
Housing:
Brass, Stainless Steel or Plastic
Termination: 250mm Lead
Ambient:
0°C to +50°C, 0-95% RH non-condensing
Dimensions: M8 Threaded fixing, 19mm diameter face x 4.5mm
T: +44 (0)20 8569 4100
Part Code
F: +44 (0)20 8569 4111
For Satin Brass, add /B
For Polished Brass, add /PB
Low profile temperature sensors
Duct Averaging Temperature Sensors TE-AVx
Averaging temperature sensors
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
For Stainless Steel, add /SS
For Matching Plate, add /BP for brass
/PBP for Polished brass
/SP for Stainless
/PP for Plastic
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
75
E.C.Products
Building Management Controls & Peripherals
Telescopic temperature sensors
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Telescopic Duct/Immersion Sensor TE-ET380
Description
Part Code
Description
The TE-ET380 is a Telescopic sensor suitable for mounting in
Ducts or in an Immersion pocket. It can be used for applications
where a non-standard length is required extending from 150 to
380mm.
TE-ET380/T
10K3A1, Trend
TE-ET380/A
10K4A1, Andover, Delta
TE-ET380/H
20K6A1, Honeywell
The housing has a quick release lid for ease of installation and
a gasket is supplied for sealing to a duct. The probe is chrome
plated brass with a Stainless steel tip for good corrosion
resistance. The sensor will fit our standard Brass or Stainless
Steel pockets. Special length pockets can be ordered.
TE-ET380/100
PT100A
TE-ET380/1K
PT1000A, Cylon
TE-ET380/LAN
Ni1000 TK5000, Siemens
TE-ET380/SAT
Satchwell
TE-ET380/TAC
1.8K3A1, TAC
TE-ET380/3K
3K3A1, Alerton
TE-ET380/D
30K6A1, Drayton
TE-ET380/P
50K6A1, Priva
Features
•IP65 Flame retardant ABS housing
•Telescopic probe
•Chrome plated brass probe stainless Steel tip
•Wide choice of sensor options
Technical Specification
Immersible temperature sensors
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C, ±0.35°C @ 100°C
Housing:
6mm OD Chrome plated probe, Stainless steel tip
Protection:IP65
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
-20°C to +85°C, 0-95% RH non-condensing.
76
Immersible Sensor TE-FL*/IM/5
Description
The TE-FL range of Immersible temperature sensors are designed
to interface with a wide variety of HVAC control equipment.
These sensors can be completely submersed to a depth of 4
meters.
Features
•5 meter standard length
•PVC outer sleeve
•150mm Stainless Steel probe
Technical Specification
Sensor Type:
Thermistor or RTD element
Accuracy:Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:150mm x 6mm Stainless steel probe,
Cable PVC 8mm OD outer sleeve
Protection:IP68
Termination:
5 metres of PVC Flying lead
Ambient:
0°C to +50°C, 0-95% RH non-condensing
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Part Code
Description
TE-FLT/IM/5
10K3A1, Trend
TE-FLA/IM/5
10K4A1, Andover, Delta
TE-FLH/IM/5
20K6A1, Honeywell
TE-FL100/IM/5
PT100A
TE-FL1K/IM/5
PT1000A, Cylon
TE-FLLAN/IM/5
Ni1000 TK5000, Siemens
TE-FLSAT/IM/5
Satchwell
TE-FLTAC/IM/5
1.8K3A1, TAC
TE-FL3K/IM/5
3K3A1, Alerton
TE-FLD/IM/5
30K6A1, Drayton
TE-FLP/IM/5
50K6A1, Priva
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Description
Part Code
Description
TE-FLT
10K3A1, Trend
TE-FLA
10K4A1, Andover, Delta
TE-FLH
20K6A1, Honeywell
TE-FL100
PT100A
TE-FL1K
PT1000A, Cylon
TE-FLLAN
Ni1000 TK5000, Siemens
TE-FLSAT
Satchwell
TE-FLTAC
1.8K3A1, TAC
TE-FL3K
3K3A1, Alerton
TE-FLD
30K6A1, Drayton
TE-FLP
50K6A1, Priva
TE-FLx-5
5 metre cable
Part Code
Description
TE-FX/T
10K3A1, Trend
TE-FX/A
10K4A1, Andover, Delta
TE-FX/H
20K6A1, Honeywell
TE- FX/100
PT100A
TE- FX/1K
PT1000A, Cylon
•Flexible plastic probe
TE-FX/LAN
Ni1000 TK5000, Siemens
•Round conduit box mounting.
TE-FX/SAT
Satchwell
•Adjustable length.
TE-FX/TAC
1.8K3A1, TAC
•Supplied with 1.5M flying lead
TE-FX/3K
3K3A1, Alerton
TE-FX/D
30K6A1, Drayton
TE-FX/P
50K6A1, Priva
The TE-FL range of flying lead temperature sensors are designed
to interface with a wide variety of HVAC control equipment.
Units are available with a high quality thermistor element or
platinum element. The sensor is housed in a plastic cap with 2
or 5 metres of cable.
Features
•2 and 5 metre cable options
•Plastic sensor cap
•Wide choice of sensor options
Technical Specification
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:
Plastic cap 6mm x 20mm
Protection:IP30
Termination: 2 or 5 metres of PVC flying lead
Ambient:
0°C to +50°C, 0-95% RH non-condensing
Flexible Ceiling Mount Probe TE-FX
Description
The TE-FX Flexible probe is designed to mount vertically from a
ceiling where there could be movement of large objects such
as freezer cabinets in Supermarkets, they can be simply pushed
out of the way without fear of damage or breakage
Features
Technical Specification
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C, ±0.35°C @ 100°C
Housing:
White ABS housing and White
Butyrate Tube 9.5mm dia x 700mm
Protection:IP30
Termination: 1.5 Meters of PVC lying lead
Ambient: 0°C to +50°C, 0-95% RH non-condensing
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Flexible temperature sensors
Flying Lead Temperature Sensors TE-FLx
Flying lead temperature sensors
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
77
E.C.Products
Building Management Controls & Peripherals
Duct temperature sensors
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Duct Temperature Sensors TE-Dx
Description
Technical Specification
The TE-D range of duct temperature sensors are designed to
interface with a wide variety of HVAC control equipment.
Units are available with a high quality thermistor element or
platinum element.
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:
Flame retardant ABS
Probe:
6mm diameter stainless steel 150mm
or 450mm
Protection:IP65
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–20°C to +85°C, 0-95% RH non-condensing
The housing has a quick release lid for ease of installation
and gasket for sealing to the duct. The probe is stainless steel
for maximum corrosion resistance and is available in two
standard lengths.
Features
•IP65 Flame retardant ABS housing
•Stainless steel probe
•Wide choice of sensor options
Part Code
Description
TE-DT
10K3A1, Trend
TE-DA
10K4A1, Andover, Delta
TE-DH
20K6A1, Honeywell
TE-D100
PT100A
TE-D1K
PT1000A, Cylon
TE-DLAN
Ni1000 TK5000, Siemens
TE-DSAT
Satchwell
TE-DTAC
1.8K3A1, TAC
TE-D3K
3K3A1, Alerton
TE-DD
30K6A1, Drayton
TE-DP
50K6A1, Priva
TE-Dx/450
450mm Long Probe
For other lengths add length to end of Part number when
ordering. Lengths available from Stock 50, 65, 75, 100, 200,
250, 300, 350, 400, 500, 600, 700, 800, 1000mm
78
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Immersion Temperature Sensors TE-Ix
Description
Part Code
Description
The TE-I range of immersion temperature sensors are designed
to interface with a wide variety of HVAC control equipment.
Units are available with a high quality thermistor element or
platinum element.
TE-IT
10K3A1, Trend
TE-IA
10K4A1, Andover, Delta
TE-IH
20K6A1, Honeywell
The housing has a quick release lid for ease of installation
and gasket for sealing to the duct. The probe is stainless steel
for maximum corrosion resistance and brass or stainless steel
pockets are available.
TE-I100
PT100A
TE-I1K
PT1000A, Cylon
TE-ILAN
Ni1000 TK5000, Siemens
TE-ISAT
Satchwell
TE-ITAC
1.8K3A1, TAC
TE-I3K
3K3A1, Alerton
TE-ID
30K6A1, Drayton
TE-IP
50K6A1, Priva
Features
•IP65 Flame retardant ABS housing
•Stainless steel probe
•Brass or Stainless Steel Pocket
•Wide choice of sensor options
For other lengths add length to end of Part number when
ordering. Lengths available from Stock 50, 65, 75, 100, 200,
250, 300, 350, 400, 500, 600, 700, 800, 1000mm
Technical Specification
Immersion temperature sensors
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:
Flame retardant ABS
Probe:
6mm diameter stainless steel 150mm
Pocket:
Brass or Stainless Steel ½” BSPT thread
Protection:IP65
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–20°C to +85°C, 0-95% RH non-condensing
Immersion Pockets TE-IxP
Description
Technical Specification
This range of immersion sensor pockets are designed to be
screwed directly into pipework to provide a dry environment for
immersion temperature sensors. Pockets are available in both
brass and 316 stainless steel. Brass pockets are recommended
for use with standard LPHW and DHWS systems whilst stainless
steel variants can be used on high temperature and pressure
installations (including steam) and are also recommended for
chilled water and other low temperature applications.
Features
•½” BSPT threaded connection
•Brass or Stainless Steel versions
•Suitable for ECP range of immersion sensors
Materials:
TE-IBP: Brass
TE-ISP: 316 Stainless Steel
Max System Pressure: TE-IBP: 10 bar
TE-ISP: 16 bar
Operating Temp. Range: TE-IBP: 0°C to +110°C
TE-ISP: –20°C to +400°C
Dimensions:
Boss: 1/2” BSPT
Probe: 110mm x 8mm OD (6mm ID)
Overall Length: 148mm
Country of Origin: India
Part Code
Description
TE-IBP
Brass Immersion Pocket
TE-ISP
Stainless Steel Immersion Pocket
For other lengths add length to end of Part number when
ordering. Lengths available from Stock 50, 65, 75, 100, 200,
250, 300, 350, 400, 500, 600, 700, 800, 1000mm
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
79
E.C.Products
Building Management Controls & Peripherals
Window temperature sensors
Strap-on temperature sensors
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
80
Strap-on Temperature Sensors TE-Sx
Description
Technical Specification
The TE-S range of strap-on temperature sensors are designed to
interface with a wide variety of HVAC control equipment.
Units are available with a high quality thermistor element or
platinum element.
The housing has a quick release lid for ease of installation
and the sensor is housed in a shaped copper lug for surface
temperature measurement.
Features
•IP65 Flame retardant ABS housing
•Copper lug for surface attachment
•Wide choice of sensor options
Sensor Type: Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C
RTD - Class A ±0.15°C @ 0°C,
±0.35°C @ 100°C
Housing:
Flame retardant ABS
Probe:
6mm dia. shaped copper 50mm long
with 1m cable
Protection:IP65
Terminals:
Rising clamp 0.5-2.5mm² cable
Ambient:
–20°C to +85°C, 0-95% RH non-condensing
Part Code
Description
TE-ST
10K3A1, Trend
TE-SA
10K4A1, Andover, Delta
TE-SH
20K6A1, Honeywell
TE-S100
PT100A
TE-S1K
PT1000A, Cylon
TE-SLAN
Ni1000 TK5000, Siemens
TE-SSAT
Satchwell
TE-STAC
1.8K3A1, TAC
TE-S3K
3K3A1, Alerton
TE-SD
30K6A1, Drayton
TE-SP
50K6A1, Priva
Window Surface Temperature Sensors TE-OFTFx
Description
Technical Specification
Small surface-contacting resistance thermometer in aluminium
enclosure. It is used for temperature detection on flat or
slightly convex surfaces, for instance for measuring surface
temperatures of windows, for monitoring formation of
condensate, or as heating surface feeler, e.g. at windows or walls.
Features
•Wide choice of sensor options
Part Code
Description
TE-OFTF/T
10K3A1, Trend
TE-OFTF/A
10K4A1, Andover, Delta
TE-OFTF/H
20K6A1, Honeywell
TE-OFTF/100
PT100A
TE-OFTF/1K
PT1000A, Cylon
TE-OFTF/LAN
Ni1000 TK5000, Siemens
TE-OFTF/TAC
1.8K3A1, TAC
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Measuring range: –30...+ 105 °C
Sensor Type:
Thermistor or RTD element
Accuracy:
Thermistor - ±0.2°C, 0...70°C,
RTD - Class A
Process connection: To be attached to the surface measured
using appropriate adhesive
Protective sleeve:Aluminium
Dimensions:
8 x 8 x 40 mm
Connecting cable: PVC; 1.5 m, LiYY, 2 x 0.25 mm²
Humidity:
< 95 % r. H.
Protection type:
IP 54
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
4...20mA Temperature Sensors TE-x420
Description
Technical Specification
The TE-420 range of temperature sensors are designed to
interface with a wide variety of HVAC control equipment.
Units are available with a high quality PT100 platinum element
and 4...20mA output transmitter which is supplied in a default
range but can be re-programmed to suit any temperature range
required. Units are available in most sensor styles shown in
this catalogue. For flue gas sensor scaling can be between
-200 to 400°C.
Features
Sensor Type:
PT100 100Ω @ 0°C, 2 or 3 wire,
Class A
Output:
2 wire 4...20mA current loop
Accuracy:
0.1°C ±0.05% of reading
+ sensor accuracy
Power Supply:10...30Vdc
Loop Voltage Effect: 0.2 uA/V
Thermal Drift:
1 uA/°C
Max. Output Load: 700Ω @ 24Vdc
4–20mA Temperature
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
•4...20mA loop powered output
•Range can be reprogrammed by the user
•Choice of sensor styles
Part Code
Description
TE-R420
Space Temperature Sensor –10°C…+40°C
TE-D420
Duct Temperature Sensor –10°C…+40°C
TE-I420
Immersion Temperature Sensor –10°C…+110°C
TE-S420
Strap-on Temperature Sensor –10°C…+110°C
TE-O420
Outside Air Temperature Sensor –10°C…+40°C
TE-T420*
Thimble Temperature Sensor –10°C…+40°C
TE-T420/B*
Brass Thimble Temperature Sensor –10°C…+40°C
TE-T420/AL*
Aluminium Thimble Sensor –10°C…+40°C
TE-T420/SS*
St. Stl. Thimble Temperature Sensor –10°C…+40°C
TE-FL420*
Flying Lead Temperature Sensor –10°C…+40°C
TE-FG420
Flue gas sensor, specify Scaling when ordering
* Units supplied complete with junction box
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
81
E.C.Products
Building Management Controls & Peripherals
Temperature charts
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Temperature Sensor Compatibility Chart
Element Type
Room
Aquatrol
Honeywell
10K3A1
Type T
10K4A1
Type A
20K6A1
Type H
PT100
Type 100
PT1000
Type 1K
Outside
•
T8120B
Johnson
•
Satchwell
•
Duct
•
T7416A
T7043E
Immersion
Bullet
•
•
•
•
T7106A
T7043F
T7044C
•
•
•
•
•
TE-6361V
TE-636GV-1
•
Clamp
DOT10K2
DOS10K2
DDT10K1
DWT10K1
DST10K1
•
T7076D
Seachange
SEN/PTR/ROM
SEN/PR/OAT
SEN/PR/DCT
SEN/PR/IMM
SEN/PR/CLP
Trend
TE-TS
TE-TO
TE-TD
TE-TI
TE-TC
•
Andover
TTS-S Series
TT-O Series
TT-I Series
TT-ST
•
•
SEN/FL
Delta Controls
•
•
•
•
•
•
Siebe
•
•
•
•
•
•
York <40°C
•
•
•
•
•
•
Honeywell
T7460H,
T7470A,
DRF20-S, RF20
T4712
VF20T,
VF20NT,
VF20L,
VF20LN,
WPF20,
T7425A
VF20A,
WPF20A
Sauter
EGT430/F011
•
•
•
•
Serck
AF20, DAF20,
T7416A1022
EGT466/F011
EGT447/F011
•
•
LF20
•
•
Siemens/
Landis & Staefa
QAA100
QAA2010
QAC2010
FK-TP/200
QAM2110
QAE2110
Honeywell
T7412
T7416A1014
T7411
T7413
Sauter
EGT430/F101
EGT401/F101
EGT446/F101
EGT447/F101
•
KFT20, KFT20B,
DKF20
EGT456/F011
•
QAP2010
T7414
•
EGT411/F101
EGT456/F101
Serck
•
•
•
•
•
•
Siebe
TS-5811
•
•
•
•
•
Cylon
•
•
•
•
•
•
Ni1000
Type N1K
Sauter
EGT330/F101
EGT301/F101
EGT346/F101
EGT347/F101
EGT348/F101
EGT346/F101
EGT347/F101
EGT348/F101
EGT311/F101
EGT354/F101
EGT356/F101
Ni1000/
TK5000
Type LAN
Siemens/
Landis & Staefa
QAA24/25/
26/27, QAA64
QAC22
QAM2120
QAE2120
QAD22
QAD26
QAP21
QAP22
QAZ21
SAT
Satchwell
DRT, DU, DUS,
DUSF
DOT0002
DOS0002
DDT0001
DWT0001
DST0001
TAC
TAC
•
DDU
•
•
•
•
•
•
Alerton
MS-1000
Series, TS-1050
•
•
•
•
•
30K6A1
Type D
Drayton
A701
50K6A1
Type P
Ambiflex
•
•
•
•
•
•
100K6A1
Type Y
York >40°C
•
•
•
•
•
•
Barber Colman
•
•
•
•
•
•
Siebe
•
•
•
•
•
•
3K3A1
Type 3K
SIE
82
Manufacturer
T: +44 (0)20 8569 4100
A702
•
F: +44 (0)20 8569 4111
A703
A704
E: sales@ecproducts.co.uk
•
W: www.ecproducts.co.uk
Temperature Sensor Resistance Characteristics
10K3A1 - Type T
10K4A1 - Type A
Thermistor, temp coef. -ve Thermistor, temp coef. -ve
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
Ω
667828
335671
176683
96974
72895
55298
42314
32650
31030
29500
28054
26688
25396
24173
23016
21921
20885
19904
18974
18092
17257
16465
15714
15001
14325
13623
13053
12494
11943
11420
10923
10450
10000
9572
9165
8777
8408
8056
6530
5325
4367
3601
2985
2487
2082
1751
1480
1256
1070
916.1
787.0
678.6
587.3
510.1
444.5
388.6
340.8
300.0
234.1
184.8
–
–
–
–
–
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
T: +44 (0)20 8569 4100
Ω
441667
239831
135233
78930
61030
47549
37316
29490
28157
26891
25689
24547
23462
22430
21450
20517
19631
18787
17983
17219
16490
15797
15136
14507
13906
13334
12788
12268
11771
11297
10845
10413
10000
9606
9229
8869
8525
8197
6754
5594
4656
3893
3271
2760
2339
1990
1700
1458
1255
1084
939.6
817.2
713.0
624.1
547.9
482.5
426.0
377.2
298.1
238.0
–
–
–
–
–
20K6A1 - Type H
PT100A - Type 100
PT1000A - Type 1K
Thermistor, temp coef. -ve
Thermistor, temp coef. +ve
Thermistor, temp coef. +ve
Temp°C
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
F: +44 (0)20 8569 4111
Ω
71120
67324
63749
60385
57218
54397
51429
48032
46258
43938
41719
39640
37676
36020
34067
32409
30841
29388
27954
26625
25387
24178
23047
21977
20962
20000
19085
18225
17404
16824
16384
16189
14491
13847
13235
12654
12010
11578
11076
10600
10148
9721.1
9314.5
8826.8
8557.5
8205.3
7899.3
7548.9
7243.1
6951.2
6672.6
6404.0
6148.9
5904.6
5671.4
5448.6
5235.7
5092.3
4837.8
4651.6
4473.9
–
–
–
–
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
401
402
403
E: sales@ecproducts.co.uk
Ω
80.3
84.3
88.2
92.2
96.1
100.0
103.9
107.8
109.8
111.7
115.5
119.4
123.2
127.1
130.9
134.7
138.5
142.3
146.1
149.8
153.6
157.3
161.0
164.8
168.5
172.2
175.8
179.5
183.2
186.8
190.5
194.1
197.7
201.3
204.9
208.5
212.0
215.6
219.1
222.7
226.2
229.7
233.2
236.7
240.1
243.6
247.0
–
–
–
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
401
402
403
Ω
803
843
882
921
961
1000
Temperature charts
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
1039
1078
1117
1155
1194
1232
1271
1309
1347
1385
1423
1461
1498
1536
1573
1611
1648
1685
1722
1758
1795
1832
1868
1905
1941
1977
2013
2049
2085
2121
2156
2191
2227
2262
2297
2332
2367
2401
2436
2470
–
–
–
W: www.ecproducts.co.uk
83
E.C.Products
Building Management Controls & Peripherals
Temperature charts
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
84
Temperature Sensor Resistance Characteristics
NI1000 - Type NIK
Thermistor, temp coef. +ve
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
201
202
203
204
205
Ω
743
791
842
893
946
1000
1056
1112
1171
1230
1291
1353
1417
1483
1549
1618
1688
1760
1833
1909
1987
2066
2148
2232
–
–
–
–
–
–
–
Ni1000/TK5000
Type LAN
Thermistor, temp coef. +ve
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
150
170
180
190
T: +44 (0)20 8569 4100
Ω
790.8
826.8
871.7
913.4
934.7
956.2
978.0
1000.0
1004.4
1008.9
1013.3
1017.8
1022.3
1026.7
1031.2
1035.8
1040.3
1044.8
1049.3
1053.9
1058.4
1063.0
1067.6
1072.2
1076.8
1081.4
1086.0
1090.7
1095.3
1100.0
1104.6
1109.3
1114.0
1120.0
1123.4
1128.1
1132.9
1137.6
1161.5
1185.7
1210.2
1235.0
1260.1
1285.4
1311.1
1337.1
1363.5
1390.1
1417.1
1444.4
1472.0
1500.0
1528.3
1557.0
1586.0
1625.4
–
–
–
–
–
–
–
–
Type SAT
Type TAC
3K3A1 - Type 3K
Thermistor, temp coef. -ve
Thermistor, temp coef. -ve
Thermistor, temp coef. -ve
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
F: +44 (0)20 8569 4111
Ω
9719
9584
9349
8968
8708
8396
8031
7614
7525
7434
7341
7246
7150
7053
6954
6853
6752
6649
6545
6440
6334
6228
6121
6013
5905
5786
5684
5580
5471
5362
5254
5147
5039
4933
4827
4721
4617
4513
4012
3545
3117
2730
2386
2082
1816
1585
1385
1213
1064
937
828
734
654
585
525
474
429
391
329
281
–
–
–
–
–
Temp°C
0
5
10
15
20
25
30
35
40
50
60
70
80
90
100
110
120
130
E: sales@ecproducts.co.uk
Ω
5085
4078
3294
2676
2188
1800
1488
1237
1034
740
540
400
300
230
180
–
–
–
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
Ω
200348
100701
53005
29092
21868
16589
12694
9795
9309
8850
8416
8006
7619
7252
6905
6577
6266
5971
5692
5428
5177
4940
4714
4500
4297
4105
3916
3748
3583
3426
3277
3135
3000
2871
2749
2633
2522
2417
1959
1598
1310
1080
895.5
746.2
624.7
525.5
444.0
376.9
321.2
274.8
236.1
203.6
176.2
153.0
133.3
116.6
102.2
89.95
70.23
55.44
–
–
–
–
–
W: www.ecproducts.co.uk
Temperature Sensor Resistance Characteristics
30K6A1 - Type D
50K6A1 - Type P
100K6A1 - Type Y
Type SIE
Thermistor, temp coef. -ve
Thermistor, temp coef. -ve
Thermistor, temp coef. -ve
Thermistor, temp coef. -ve
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
Ω
2497K
1219K
622911
331876
245785
183697
138502
105305
99787
94588
89689
85069
60713
76604
72726
69064
65608
62347
59257
56346
53585
50978
48511
46178
43969
41877
39895
38019
36240
34554
32955
31438
30000
28635
27339
26108
24939
23828
19046
15317
12390
10079
8243
6777
5600
4650
3879
3251
2737
2313
1963
1672
1430
1228
1058
914.6
793.2
690.2
527.4
407.7
-
T: +44 (0)20 8569 4100
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
Ω
4168K
2033K
1038K
553243
409689
306183
230842
175508
166310
157644
149480
141779
134521
127669
121207
115105
109344
103903
98761
93901
89307
84962
80851
76961
73280
69794
66492
63364
60400
57589
54925
52398
50000
47724
45564
43513
41565
39714
31744
25529
20650
16799
13740
11297
9334
7751
6466
5419
4560
3855
3271
2787
2384
2046
1762
1523
1321
1149
878.2
678.8
–
–
–
–
–
F: +44 (0)20 8569 4111
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
Ω
8337K
4067K
2077K
1106K
819378
612366
461683
351017
332619
315288
298959
283558
269041
255337
242414
230210
218688
207807
197521
187803
178613
169924
161702
153923
146560
139588
132984
126729
120799
115179
109850
104796
100000
95449
91128
87026
83129
79428
63489
51058
41301
33598
27479
22593
18669
15502
12932
10837
9121
7710
6543
5574
4767
4092
3525
3047
2642
2299
1756
1357
–
–
–
–
–
E: sales@ecproducts.co.uk
Temp°C
–50
–40
–30
–20
–15
–10
–5
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
140
150
160
170
180
190
200
Ω
10732
10517
10172
9654
9320
8933
8496
8044
7910
7807
7702
7596
7489
7381
7271
7161
7050
6938
6825
6712
6598
6485
6370
6256
6141
6028
5913
5798
5686
5573
5461
5349
5238
5128
5019
4910
4803
4696
4185
3707
3271
2875
2521
2206
1929
1685
1472
1287
1127
986
866
760
670
590
522
462
410
365
290
233
–
–
–
–
–
W: www.ecproducts.co.uk
Temperature charts
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
85
E.C.Products
Building Management Controls & Peripherals
Thermostats
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Frost Protection Thermostat TS-FS
Description
Technical Specification
The TS-FS frost protection thermostats provide a switched output
based on the average temperature detected along a six metre
capillary sensor. The unit is fixed across a duct using capillary
clips, downstream of the frost coil and is used to prevent the
icing up of filters, fans and coils.
Features
•Auto or manual reset versions
•6 metre capillary
•24A @ 240Vac switch rating
Part Code
Description
TS-FS-A
Auto Reset Frost Protection Thermostat
TS-FS-M
Manual Reset Frost Protection Thermostat
TS-FS-A-IP65
Auto Reset Frost Protection Thermostat IP65
TS-FS-M-IP65
Manual Reset Frost Protection Thermostat IP65
TS-FS-FC
Capillary Fixing Clips
Control range:
Differential:
Switch rating:
Reset:
Capillary:
Sensor Type:
Ambient range:
Protection:
–30°C to +15°C
TS-FS-A - 1.5...16°C
TS-FS-M - Fixed 2.5°C
24(10)A @ 230Vac
3A @ 24Vdc
FS-A: Auto
FS-M: Manual
6m x 2mm dia copper
Vapour Charge
Housing: 0°C to 50°C
Capillary: –50...+70°C
IP44 (IP65 to order)
Outside Frost Stat TS90-B3
Description
Technical Specification
Outside wall mount frost protection thermostat.
Part Code
Description
TS90-B3
Outside frost Thermostat
Contact current rating:SPDT contact, 250V 10Amp on Opening
Contact, 3A amp on closing contact
Differential:0.5°C
Range:–5-25°C
Protection:IP65
Dimensions:160x120x75mm
Tamperproof Thermostat TY90-T
Description
Technical Specification
Wall mount bimetallic thermostat with concealed adjustment for
heating and cooling applications.
86
Part Code
Description
TY90-T
Tamperproof Thermostat
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Contact current rating:SPDT contact, 250V 10Amp on Opening
Contact, 3A amp on closing contact
Differential:0.5°C
Range:5-35°C
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Strap-on Thermostat WRP90GD
Description
Technical Specification
The WRP90GD is a thermostat suitable for mounting on pipes
or cylinders. The unit has an exposed setpoint adjustment knob
and comes complete with fixing strap for mounting the unit and
ensuring good surface contact.
Temperature Range:10...90°C
Differential:5°C
Contact Rating:
15(2.5)A @ 250Vac SPDT
Protection:IP20
Thermostats
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Features
•SPDT Contacts
•Complete with fixing Strap
Part Code
Description
WRP90GD
Strap-on/Cylinder Thermostat
Room Thermostat TR101X
Description
Technical Specification
The TR101X is a thermostat suitable for room temperature
monitoring and is wall mounting. The unit has an exposed
setpoint adjustment knob and comes with SPDT contacts for
heating/cooling applications.
Features
Contact Type:
SPDT (Heating/Cooling)
Contact Rating:
16(4)A @ 250Vac
Temperature Range:10...30°C
Differential:1°C
Ambient Storage: –20…+50°C, 0...90% RH
•SPDT Contacts
•Exposed Setpoint Knob
Part Code
Description
TR101X
Room Thermostat
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
87
E.C.Products
Building Management Controls & Peripherals
Thermostats
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Large LCD Screen Digital Programmable Thermostat T-908WHB-3-xx
Description
Technical Specification
5 + 1 + 1 day 2 Wire Volt Free. Heat/Cool. 24/250v 5 Amp
(Battery Operated) Room Thermostat, wireless option available.
Features
•Large LCD display with backlight
•Set points and room temperature display simultaneously
•Maintains the temperature within the range of 0.5ºC to the
set point
•Automatic fan with adjustable 3-fan speed.
•Manual change over
•Never lose user setting in the event of power-off, no battery
is required
•Display temperature recalibrates
•Sleep mode option
Part Code
Description
T-908WHB-3-B
Large LCD Screen Digital Programmable
Thermostat
T-908WHB-3-RF
Wireless Large LCD Screen Digital
Programmable Thermostat
Power source:
Control Centre 2 AA batteries
Receiver 230VAC 50HZ
Frequency band:
433 MHZ (for wireless version only)
Relay contact:
230VAC 16A
Room temp. setting range:Deg C to 35ºC
Accuracy:±0.5ºC
Dimensions:
Control Centre: 115×90×16mm
Receiver: 88x88×40mm
Simple Wireless RF Room Thermostat Volt Free Description
Technical Specification
Wireless digital thermostat, push button or dial set point
Features
•Simple to use
•Display set point and room temperature
•Thermostat sender battery operated
88
Part Code
Description
DRF1
Push button wireless digital thermostat
CC816-RF
Dial wireless digital thermostat
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Frequency band:
433 MHZ
Room temp. setting range:5ºC to 35ºC
Accuracy:0.5ºC
Receiver Input Voltage: 240VAC 50HZ
Receiver Output Voltage: 24..240VAC 50HZ 10(3)A Max
Operating Temperature: 0ºC to 50ºC
Dimensions:
Control Centre: 82×88×25mm
Receiver: 82×82×32mm
Color:White
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Digital Electronic Thermostat 2-8 Stage TS-ET2
Description
Technical Specification
The TS-ET2 is a 2-8 Stage Programmable Electronic Thermostat
with the option of a remote Set point, Low Limit and Setback,
compatible with Building Management Systems. The unit can
control up to 8 stages of heating or cooling.
Features
•Wide temperature range
•Night setback input
•Heating or cooling function
•2 line, 32 character display
•Adjustable stage and inter-stage differential
•Din rail mounting
•4 models available
Part Code
Description
TS-ET2
2 Stage Electronic Thermostat
TS-ET4
4 Stage Electronic Thermostat
TS-ET6
6 Stage Electronic Thermostat
TS-ET8
8 Stage Electronic Thermostat
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Temp sensor:
10K3A1thermistor for control and frost override
Temprange:–20°C to +95°C
Differential range:1°C to 10°C
Temp Override:20°C to +95°C
Night set back:
volt free contact
Offset pot
1K-11K, range –4°C to +4°C of set point
External set point:1k-11k
Output:2 SPCO contacts per 2 stager 10A resistive
230Vac
Dimensions:
137W x 75H x 62H
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Thermostats
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
89
E.C.Products
Building Management Controls & Peripherals
Thermostats
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Wall Mount/Greenhouse Thermostat TS-DBET
Description
Technical Specification
Well-suited for heating, cooling and air conditioning systems
in dusty, damp and strong polluted areas: industrial areas,
commercial buildings, storage room, garages, machine rooms,
factories, greenhouses and agricultural installations.
Features
•Exposed adjustment knob
•Suitable for many applications
Part Code
Description
TS-DBET-22
Wall Mounted Thermostat –30°C…+30°C
TS-DBET-060
Wall Mounted Thermostat 0°C…+60°C
Sensitive element: Liquid-filled coiled copper bulb
Contacts:
SPDT contacts (heat/cool)
Switch capacity: 15(8)A @ 24...250 Vac
Differentials:
TS-DBET-22 - adjustable 1...15K
TS-DBET-090 - fixed 1.5K
Working:
–35...+60°C, 10...90% RH
(non condensing)
Storage:
40...+60°C, < 95% RH
Housing:
Byblend base, ABS cover
Protection:IP65
Size:
108 x 70 x 72 mm
Weight:
450 g
Capillary Thermostats TS-DBTC
Description
Technical Specification
Temperature measurement and monitoring in normal fluids
(water) and in non aggressive gases with a thermo sensitive
element coated with PVC. Well-suited for heating, cooling and
air conditioning systems in domestic areas; industrial areas;
commercial buildings and sport halls.
Features
•Exposed adjustment adjustment knob
•1.5 metre capillary
•SPDT Contacts
90
Part Code
Description
TS-DBTC-060
Capillary Thermostat 0°C…+60°C
TS-DBTC-090
Capillary Thermostat 0°C…+90°C
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Sensitive element: Liquid-filled coiled copper bulb
with 1.5m length capillary
PVC protected bulb: Ø6.8
Contacts: SPDT contacts(heat/cool)
Switch capacity: 16(4)A@ 250 Vac
Differential:
Fixed 3K
Working:
–10...+65 °C 0...90% RH
Storage:
–40...+70 °C < 95% RH.
Housing:
Byblend base, ABS cover
Protection:IP54
Size:
108 x 70 x 72 mm
Weight:
360 g
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Immersion Thermostats TS-DBTV
Description
Technical Specification
Temperature control in pipes with normal fluids (water) for
heating, cooling and air conditioning systems, boilers and
heaters.
Temperature monitoring and safety protection with manual
reset and signal contact. Well-suited for general applications in
strong polluted domestic and industrial areas.
Features
•Concealed Adjustment Knob
•Supplied with pocket
•SPDT Contacts
Part Code
Description
TS-DBTV-090U
Immersion Thermostat 0°C…+90°C
TS-DBTV-11
Immersion Thermostat +50°C…+120°C
Sensitive element:
Contacts:
Switch capacity:
Differentials:
Working:
Storage:
Housing:
Protection:
Size:
Weight: Copper bulb with 120 mm pocket
SPDT contacts(heat/cool)
15(8)A @ 24...250 Vac
Fixed 3K
–35...+65 °C,10...90% RH
–40...+70 °C, < 95% RH
Byblend base, ABS cover
IP65, class I
108 x 70 x 72 mm
570 g
Thermostats
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Duct Thermostats TS-DBTZ
Description
Technical Specification
Temperature monitoring in air or non aggressive gas ducts.
Well-suited for general applications in strong polluted domestic
and industrial areas.
Features
•Concealed Adjustment Knob
•Integrated bulb holder
•SPDT Contacts
Part Code
Description
TS-DBTZ-2U
Duct Thermostat –30°C…+30°C
TS-DBTZ-090U
Duct Thermostat 0°C…+90°C
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Sensitive element: Liquid-filled coiled copper bulb with
200mm protection spring and
mounting bracket
Contacts:
SPDT contacts (heat/cool)
Switch capacity: 15(8)A @ 24...250 Vac
Differentials:1/3K
Working:
–35...+65°C,10...90% RH
Storage:
–40...+70°C, < 95% RH
Housing:
Byblend base, ABS cover
Protection:IP65
Size:
108 x 70 x 72 mm
Weight:
690 g
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
91
E.C.Products
Building Management Controls & Peripherals
Thermostats
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Cost Effective Industrial Thermostats TS
Description
Technical Specification
This range of industrial thermostats are suitable for applications
in boiler rooms and plant rooms where cost is critical, rated to
IP40 they are suitable for indoor applications only.
The Immersion Thermostats are supplied with 120mm Pocket ½”
BSP fitting and a cable restraint with external adjustment. For
Duct mounting a vented duct tube can be ordered separately
IP Rating:
IP40 Immersion and capillary. Space IP55
Current Rating:
NC16(3)A @250Vac/NO 6(1)A @ 250Vac
Switching Tolerance:±5%
Differential:2-5°C
Ambient:90°C
The Capillary thermostat has a 1.5 meter capillary with a
6.5mm diameter bulb, external adjustment and a cable
restraint.
The Industrial Space thermostat is IP55 rated with concealed
adjustment, it has a Stainless Steel coiled Capillary and is
ideally suited for use in green houses and farm buildings.
Features
•Large LCD display with backlight
•Set points and room temperature display simultaneously
•Maintains the temperature within the range of 0.5ºC to the
set point
•Automatic fan with adjustable 3-fan speed.
•Manual change over
•Never lose user setting in the event of power-off, no battery
is required
•Display temperature recalibrates
•Sleep mode option
92
Part Code
Description
TS9510-01
Immersion Thermostat 0-60°C
TS9510-02
Immersion Thermostat 0-90°C
TS9510-03
Immersion Thermostat 30-120°C
TS95H30-54
Immersion Thermostat 20-70°C manual High Limit 85°C
TS9520-01
Capillary Thermostat 0-60°C
TS9520-02
Capillary Thermostat 0-90°C
TS9520-04
Capillary Thermostat -35+35°C
TS9502-01
Industrial Space Thermostat 5-60°C
TS9502-02
Industrial Space Thermostat -35+35°C
TS-DFK
Vented Duct Mounting Flange
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Terminal Unit Valves VFX
Description
Technical Specification
The VFX valves are used in heating, cooling and air
conditioning systems. The valves are normally closed and
are compact, reliable and easily mounted. A plastic cap
is available that ensures stem protection and for manual
adjustment. A range of Electrothermal Actuators is also
available to be used with the VFX valve bodies.
Nominal Pressure:PN16
Stroke:2.5mm
Regulation Mode:Linear
Leakage:
Perfect sealing
Valve Body:
Forged brass
Stem and Plug:
PA + GF
Stem Gland Seal: FKM “o” ring
Max. ΔP:
2.5 bar
Fluids:
Water with max. 40% glycol
Fluid Temperature:+2…+95°C
Actuator:
SE1 series electrothermal
Features
•Connection between actuator and valve by threaded male
M30x1.5 ring nut
•2, 3 & 4 port versions available
•Choice of Kvs values and threads
Part Code
Description
VFX214
2 Port ½” Valve Body 1.6 Kvs for use with SE1 Actuators
VFX235
2 Port ¾” Valve Body 2.5 Kvs for use with SE1 Actuators
VFX314
3 Port ½” Valve Body 1.6 Kvs for use with SE1 Actuators
VFX335
3 Port ¾” Valve Body 2.5 Kvs for use with SE1 Actuators
VFX414
4 Port ½” Valve Body 1.6 Kvs for use with SE1 Actuators
VFX435
4 Port ¾” Valve Body 2.5 Kvs for use with SE1 Actuators
Fan coil valves
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Terminal Unit Valve Actuators SE1
Description
Technical Specification
The SE1Electrothermal Actuators are for use with the VFX range
of fan coil valves and are used in heating, cooling and air
conditioning systems. When the actuators are not energized the
valves are normally closed and two action types are available:
on-off and modulating 0...10Vdc.Assembly is easy using the
metal ring and tools are necessary. The actuator is fitted with
valve position indication.
Features
•Connection between actuator and valve by threaded male
M30x1.5 ring nut
•On-off 0...10Vdc modulating versions
•24Vac and 230Vac versions
Power Supply:
SE1M24, SE1T24: 24Vac ±10% 50Hz
SE1T230: 230Vac ±10% 50Hz
Power:
SE1M24: 3.5VA
SE1T24, SE1T230: 3VA
Peak Current:
SE1M24, SE1T24: < 0.25A
SE1T230: < 0.70A
Sensing Element: Special Wax
Running Time:
210 seconds
Wiring:
2 metre PVC cable
Connection:
Metal ring nut M30 x 1.5
Working Temp:0...50°C
Working Humidity: 10...90% RH non-condensing
Storage:–20…+70°C
Protection:IP44
Weight:200g
Part Code Description
SE1T24
24V On/Off Electrothermal Actuator
SE1T230
230V On/Off Electrothermal Actuator
SE1M24
24V Proportional 0...10Vdc Electrothermal Actuator
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
93
E.C.Products
Building Management Controls & Peripherals
Fan coil valves
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Fan Coil Valves V5000
Description
The V5000 valves are primarily designed to regulate the flow
of water and steam in response to the demand of a controller in
zone and terminal unit applications.
Features
•Forged brass body, stainless steel stem and spring
•Inherent flow characteristics: equal percentage
•Rangeability 20:1
•M30 x 1.5 collar
2 way fan coil valves
3 way fan coil valve mixing/diverting with
built in bypass
Part Code
Description
V5510BC
15mm 3 Way Fan Coil Valve
0.4kvs By Pass 0.3kvs (DN10)
V5510CC
15mm 3 Way Fan Coil Valve
0.63kvs By Pass 0.4kvs (DN10)
V5510DC
15mm 3 Way Fan Coil Valve
1 kvs By Pass 0.63kvs (DN10)
V5510EC
15mm 3 Way Fan Coil Valve
1.6kvs By Pass 1kvs (DN10)
V5510JC
15mm 3 Way Fan Coil Valve
2.5kvs By Pass 1.6kvs (DN15)
V5510KC
15mm 3 Way Fan Coil Valve
4kvs By Pass 2.5kvs (DN15)
V5510MC
28mm 3 Way Fan Coil Valve
5kvs By Pass 3.5kvs (DN20)
Part Code
Description
V5210ZC
15mm 2 Way Fan Coil Valve 0.16kvs (DN10)
V5210BC
15mm 2 Way Fan Coil Valve 0.4kvs (DN10)
V5210CC
15mm 2 Way Fan Coil Valve 0.63kvs (DN10)
V5210DC
15mm 2 Way Fan Coil Valve 1kvs (DN10)
V5210EC
15mm 2 Way Fan Coil Valve 1.6kvs (DN10)
Part Code
Description
V5210JC
15mm 2 Way Fan Coil Valve 2.5kvs (DN15)
V5590BC
V5210KC
15mm 2 Way Fan Coil Valve 3.5kvs (DN15)
15mm 3 way Fan Coil Valve
0.4kvs By Pass 0.3 kvs Compression (DN10)
V5210MC
28mm 2 Way Fan Coil Valve 4.5kvs (DN20)
V5590CC
15mm 3 way Fan Coil Valve
0.63kvs By Pass 0.4 kvs Compression (DN10)
Part Code
Description
V5590DC
15mm 3 way Fan Coil Valve
1kvs By Pass 0.63 kvs Compression (DN10)
V5290BC
15mm 2 Way Fan Coil Valve
0.4kvs Compression (DN10)
V5590EC
15mm 3 way Fan Coil Valve
1.6kvs By Pass 1kvs Compression (DN10)
V5290CC
15mm 2 Way Fan Coil Valve
0.63kvs Compression (DN10)
V5290DC
15mm 2 Way Fan Coil Valve
1kvs Compression (DN10)
V5290EC
15mm 2 Way Fan Coil Valve
1.6kvs Compression (DN10
Actuators For use With V5000 Valves
Part Code
Description
VA-7480-0001 24Vac Floating 12 sec/mm
VA-7481-0001 24Vac Floating 8 sec/mm
VA-7480-0003 230Vac Floating 12 sec/mm
VA-7481-0003 230Vac Floating 8 sec/mm
VA-7482-1001 24Vac/dc 0-10V 8 sec/mm
Stroke Length 3.2mm
VA-7482-2001 24Vac/dc 0-10V 8 sec/mm
Stroke Length 4.3mm
94
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Pressure Independent Control valves VP1000
Description
Technical Specification
The VP1000 pressure independent control valve is a
combination of a differential pressure regulator and a
regulating valve for flow adjustment. Installation costs are
considerably reduced as the valve performs the functions of two
valves (balancing and adjustment). To adjust the flow rate, just
set the selected value using the adjustment knob. Choosing the
suitable valve is easy and fast. Flow rate is the only parameter
to consider.
Fluid Temperature:–10/+120°C
Max. working pressure:2500kPa – 25 Bar (max)
Fittings:
BSP female threaded body.
Collar:
M30 x1.5
Features
•Kvs calculation is not necessary
•Valve authority calculation not required
•Specific devices or knowledge are not necessary
•Compact design
•Flow rate adjustment without disassembling the actuators
•Forged brass body
•BSP fitting
Part Code
Body
Flow rate
VP100AAA
15mm
150 l/h – 0.042 l/s with pressure port
VP101AAA
15mm
150 l/h – 0.042 l/s without pressure port
VP100AAE
15mm
600 l/h – 0.167 l/s with pressure port
VP101AAE
15mm
600 l/h – 0.167 l/s without pressure port
VP100AAG
15mm
780 l/h – 0.217 l/s with pressure port
VP101AAG
15mm
780 l/h – 0.217 l/s without pressure port
VP100BAJ
20mm
1000 l/h – 0.278 l/s with pressure port
VP101BAJ
20mm
1000 l/h – 0.278 l/s without pressure port
VP100BAN
20mm
1500 l/h – 0.417 l/s with pressure port
VP101BAN
20mm
1500 l/h – 0.417 l/s without pressure port
VP100CAU
25mm
2200 l/h - 0.611 l/s with pressure port
VP100CAW
25mm
2700 l/h – 0.750 l/s with pressure port
VP100DAW
32mm
2700 l/h – 0.750 l/s with pressure port
VP100DAY
32mm
3000 l/h – 0.833 l/s with pressure port
Pressure independent valves
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Suitable actuators for pressure independent
control valves
Part Code
Supply voltage
Control
Actuator speed
VA-7481-0001
24Vac
Floating
8 sec/mm
VA-7481-0003
230Vac
Floating
8 sec/mm
VA-7482-1001
24Vac/dc
Proportional
8 sec/mm
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
95
E.C.Products
Building Management Controls & Peripherals
Ball valves
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Belimo Control & Shut off Ball Valves
Description
Belimo Ball Valves, shut off and Characterised control valves
with internal thread fitting for use on warm and cold water
systems, bubble tight shut off.
Shut off valves with Internal threads PN16
Part Code
Description
Part Code
Description
R2015-S1
2 Port Valve 15mm Kv 15
R3015-S1
3 Port Valve 15mm Kv 15
R2020-S2
2 Port Valve 20mm Kv 32
R3020-S2
3 Port Valve 20mm Kv 32
R2025-S2
2 Port Valve 25mm Kv 26
R3025-S2
3 Port Valve 25mm Kv 26
R2032-S3
2 Port Valve 32mm Kv 32
R3032-S3
3 Port Valve 32mm Kv 32
R2040-S3
2 Port Valve 40mm Kv 31
R3040-S3
3 Port Valve 40mm Kv 31
R2050-S4
2 Port Valve 50mm Kv 49
R3050-S4
3 Port Valve 50mm Kv 49
Characterised Control Valves with Internal Threads PN16
Part Code
Description
Part Code
Description
R2015-1P6-S1
2 Port Valve 15mm Kv 1.6
R3015-1P6-S1
3 Port Valve 15mm Kv 1.6
R2020-6P3-S2
2 Port Valve 20mm Kv 6.3
R3020-6P3-S2
3 Port Valve 20mm Kv 6
R2025-10-S2
2 Port Valve 25mm Kv 10
R3025-10-S2
3 Port Valve 25mm Kv10
R2032-16-S3
2 Port Valve 32mm Kv 16
R3032-16-S3
3 Port Valve 32mm Kv 16
R2040-25-S3
2 Port Valve 40mm Kv 25
R3040-25-S4
3 Port Valve 40mm Kv 25
R2050-40-S4
2 Port Valve 50mm Kv 40
R3050-40-S4
3 Port Valve 50mm Kv 40
Belimo Actuators for Ball Valves
Part Code
Description
Part Code
3 point Open Close
96
Description
Modulating
TR230-3
S1
2 Nm Actuator 230Vac 3-Point
for 15mm Valves
TR24-SR
S1 2 Nm Actuator 24Vac/dc Modulating 0-10vdc
TR24
S1
2 Nm Actuator 24Vac/dc 3 Point
for 15mm Valves
LR24A-SR
S2 5 Nm Actuator 24Vac/dc Modulating 0-10vdc
LR230A
S2
5 Nm Actuator 230Vac 3 Point
for up to 25mm Valves
LR24A
S2
5 Nm Actuator 24Vac/dc 3 Point
for up to 25mm Valves
TRF230
S1 2 Nm Actuator 230Vac Open/Spring Return
TRF24
S1 2 Nm Actuator 24Vac/dc Open/Spring Return
NR24A-SR S3 10 Nm Actuator 24Vac/dc Modulating 0-10vdc
SR24A-SR S4 20 Nm Actuator 24Vac/dc Modulating 0-10vdc
Spring Return
NR230A
S3
10 Nm Actuator 230Vac 3 Point
for up to 40mm Valves
LRF230
S2 5 Nm Actuator 230Vac Open/Spring Return
NR24A
S3
10 Nm Actuator 24Vac/dc 3 Point
for up to 40mm Valves
LRF24
S2 5 Nm Actuator 24Vac/dc Open/Spring Return
NRF230A
S3 10 Nm Actuator 230Vac Open/Spring Return
SR230A
S4 20 Nm Actuator 230Vac 3 Point
for up to 50mm Valves
NRF24A
S3 10 Nm Actuator 24Vac/dc Open/Spring Return
TRF24-SR
S1 2 Nm Actuator 24Vac/dc Modulating 0-10vdc
SR24A
S4 20 Nm Actuator 24Vac/dc 3 Point
for up to 50mm Valves
LRF24-SR
S2 5 Nm Actuator 24Vac/dc Modulating 0-10vdc
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
NRF24-SZ S3 10 Nm Actuator 24Vac/dc Modulating 0-10vdc
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Belimo Butterfly valves and Rotary Actuators
Description
Technical Specification
Belimo Wafer type butterly valves for shut-off functions in open
and closed cold and hot water Systems. The butterly valve is
opened or closed completely by an open-close rotary actuator.
Continuous rotary actuators are can move the valve discs into
any position desired. The disc made of stainless steel is pressed
into the soft-sealing EPDM seat.
Part Code
Description
D625N
25mm Butterfly Valve Wafer Type PN 16
F05
D632N
32mm Butterfly Valve Wafer Type PN 16
F05
D640N
40mm Butterfly Valve Wafer Type PN 16
F05
D650N
50mm Butterfly Valve Wafer Type PN 16
F05
D665N
65mm Butterfly Valve Wafer Type PN 16
F05
D680N
80mm Butterfly Valve Wafer Type PN 16
F05
D6100N
100mm Butterfly Valve Wafer Type PN 16 F05
D6125N
125mm Butterfly Valve Wafer Type PN 16
F07
D6150N
150mm Butterfly Valve Wafer Type PN 16
F07
Media:
Cold and warm water with max 50%
volume of glycol
Media temperature:–20°C ... +120°C
Rated pressure: ps 1600 kPa
Leakage rate:
A, tight (EN 12266-1)
Angle of rotation:90°
Installation position:Vertical to horizontal (in relation to the stem)
Maintenance:Maintenance-free
Fitting:
EN-JS1030 (GGG 40),
Disc:
DIN/EN 1.4301 / AISI SS 304
(Stainless steel)
Stem:
DIN/EN 1.4005 / AISI SS 416
(Stainless steel)
Seat:EPDM
Stem seal:
EPDM O-ring
Stem bearing:RPTFE
Butterfly valves
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Note: sizes available up to 700mm, contact sales office.
Suitable Belimo Actuators for above valves:
Part Code
Description
SR24A-5
20Nm Actuator 24Vac/dc open/close and 3 Point
GR24A-5
40Nm Actuator 24Vac/dc open/close only
GR24A-7
40Nm Actuator 24Vac/dc open/close only
DGR24A-7
60Nm Actuator 24Vac/dc open/close only
SR230A-5
20Nm Actuator 230Vac open/close and 3 Point
GR230A-5
40Nm Actuator 230Vac open/close only
GR230A-7
40Nm Actuator 230Vac open/close only
DGR230A-7 60Nm Actuator 230Vac open/close only
S1A
End Switch 1 x SPDT to suit all above
S2A
End Switch 2 x SPDT to suit all above
Note: -5 for F05 fitting valves. -7 for F07 fitting Valves
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
97
E.C.Products
Building Management Controls & Peripherals
Shoe valves
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Rotary Shoe Valves VR-S/F
Description
Technical Specification
ESBE 3 port rotary shoe valves
Part Code
Description
VR-S20
20mm 3 port screwed rotary shoe valve
VR-S25
25mm 3 port screwed rotary shoe valve
VR-S32
32mm 3 port screwed rotary shoe valve
VR-S40
40mm 3 port screwed rotary shoe valve
VR-S50
50mm 3 port screwed rotary shoe valve
MS-NRE6
Linkage kit HT actuators to Esbe valves
HT24-3
24V open/close motor
HT230-3
230V open/close motor
HT24-SR
24V 0..10Vdc open/close motor
VR-F65
65mm 3 port flanged rotary shoe valve
VR-F80
80mm 3 port flanged rotary shoe valve
VR-F100
100mm 3 port flanged rotary shoe valve
VR-F125
125mm 3 port flanged rotary shoe valve
VR-F150
150mm 3 port flanged rotary shoe valve
SM-VRL
Linkage kit for SM...Actuators
to ESBE 65mm upwards
SM24-A
24V open/close motor
SM24A-SR
24V 0..10Vdc open/close motor
SM230-A
230V open/close motor
Material:
Cast Iron
Operating Pressure Pmax: 6 Bar
Max. Differential Pressure: Mixing - 0.1 Bar,
Diverting - 0.3 Bar
Leakage Rate:<1%
Water Temperature:
+2/+100ºc
SM230A-SR 24V 0..10Vdc open/close motor
ESBE Rotary Shoe Valve Actuator ARA600
Description
Part Code
The ESBE series VR-ARA600 and VR-9 are a compact actuator
designed for operating rotary mixing valves. The actuators
are controlled by 3-point and Modulating signal, and are
recommended for mixing applications. The actuators have an
operating range of 90° and the valves can easily be manually
operated by the pull and turn knob on the front of the actuator.
98
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Description
VR-ARA664 24Vac Open/Close Esbe Actuator
20mm-50mm
VR-ARA652 230Vac Open/Close Esbe Actuator
20mm-50mm
VR-ARA659 24Vac 0-10Vdc Modulating Esbe Actuator
20mm-50mm
VR-92M
24Vac Open/Close Esbe Actuator c/w Switches
65mm-150mm
VR-95M
230Vac Open/Close Esbe Actuator c/w
Switches 65mm-150mm
VR-92P
24Vac 0-10Vdc Modulating Esbe Actuator
65mm-150mm
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Servo operated valves SV
Description
Technical Specification
A range of brass solenoid for air, gas and water complete with
coil and connector
Features
•Available normally closed or normally open
•Brass body and cover
•Stainless steel inner construction
•Optional seal materials
•Response time 16/18 milliseconds
•Operating range -10°C to +50°C
Body:
OT58 Brass
Internals:
Stainless steel
Shading ring:Copper
Electrical parts:
See coil chart
Seal materials:
NBR, Viton® or EPDM
Media:
Air, Gas, Water [hot & cold] Oil,
non-corrosive fluids
Ambient temperature:–10°C to +50°C
Response time:
16/18 milliseconds
Mounting:
Horizontal preferred
Coil Voltages:
12, 24, 110, 230V
Part Code
Description
Part Code
Description
SV15/NC/24
½” Solenoid Valve 24Vac Normally Closed
SV32/NC/24
1¼” Solenoid Valve 24Vac Normally Closed
SV15/NO/24
½” Solenoid Valve 24Vac Normally Open
SV32/NO/24
1¼” Solenoid Valve 24Vac Normally Open
SV15/NC/230
½” Solenoid Valve 230Vac Normally Closed
SV32/NC/230 1¼” Solenoid Valve 230Vac Normally Closed
SV15/NO/230 ½” Solenoid Valve 230Vac Normally Open
Solenoid valves
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
SV32/NO/230 1¼” Solenoid Valve 230Vac Normally Open
SV20/NC/24
¾” Solenoid Valve 24Vac Normally Closed
SV40/NC/24
1½” Solenoid Valve 24Vac Normally Closed
SV20/NO/24
¾” Solenoid Valve 24Vac Normally Open
SV40/NO/24
1½” Solenoid Valve 24Vac Normally Open
SV20/NC/230 ¾” Solenoid Valve 230Vac Normally Closed
SV40/NC/230 1½” Solenoid Valve 230Vac Normally Closed
SV20/NO/230 ¾” Solenoid Valve 230Vac Normally Open
SV40/NO/230 1½” Solenoid Valve 230Vac Normally Open
SV25/NC/24
1” Solenoid Valve 24Vac Normally Closed
SV50/NC/24
2” Solenoid Valve 24Vac Normally Closed
SV25/NO/24
1” Solenoid Valve 24Vac Normally Open
SV50/NO/24
2” Solenoid Valve 24Vac Normally Open
SV25/NC/230 1” Solenoid Valve 230Vac Normally Closed
SV50/NC/230 2” Solenoid Valve 230Vac Normally Closed
SV25/NO/230 1” Solenoid Valve 230Vac Normally Open
SV50/NO/230 2” Solenoid Valve 230Vac Normally Open
Supplied as standard with NBR seals, for information on other seals contact our sales office
Servo operated valves SV and L182
Part Code
Description
L182D01-1-230
Solenoid Valve 1" N/C 230Vac
L182D01-1-24
Solenoid Valve 1" N/C 24Vac
L182D01-3/4-230
Solenoid Valve 3/4" N/C 230Vac
L182D01-3/4-24
Solenoid Valve 3/4" N/C 24Vac
L182D01-1/2-230
Solenoid Valve 1/2" N/C 230Vac
L182D01-1/2-24
Solenoid Valve 1/2" N/C 24Vac
L182 Din Cap
Din Cap Required for above
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
99
E.C.Products
Building Management Controls & Peripherals
Zone valves
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Spring Return Zone Valves DB-VZx-xx
Description
Technical Specification
On-off control of hot or cold water flow. The valves DB-VZ
coupled with synchronous motor SM230/SM24/CA and
SM230/SA, SM24/SA are suitable for heating and cooling
water in zone systems for ON-OFF control.
The synchronous motor opens the valve (normally closed)
Typical applications are for fan-coil units.
Power ON drives the motor, power OFF and the Valve Spring
Returns
2-way valves: the plug closes against the flow;
3-way valves: the plug blocks the flow toward user side.
Features
•Detachable actuator
•Optional auxillary switches
•BSP thread
•Rugged construction
100
Part Code
Description
DB-VZ2-15
2 Port Valve 1/2” BSP Thread
DB-VZ2-20
2 Port Valve 3/4” BSP Thread
DB-VZ2-25
2 Port Valve 1” BSP Thread
DB-VZ3-15
3 Port Valve 1/2” BSP Thread
DB-VZ3-20
3 Port Valve 3/4” BSP Thread
DB-VZ3-25
3 Port Valve 1” BSP Thread
SM230/CA
Actuator 230Vac with Aux Switch
SM24/CA
Actuator 24Vac with Aux Switch
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Synchronous motor
Power supply:
Max electrical load:
Power consumption:
Working temp.:
Working humidy:
Material:
Protection:
Dimensions:
Weight:
230 or 24 Vac
3 A, 125...250 Vac
7 vA
+0...+60 ºC
10...90% r.h.
Plate: casting aluminium alloyed
Cover: fire-proof ABS
IP20, class II
See Data Sheet
See Data Sheet
Valve
Valve type:
2 or 3 ways
Fluid temp.:
+2...+94 ºC
Material:
Valve body: forged brass
Valve rod: stainless steel Aisi 302
Seal material:NBR
Storage temp.:
–20...+70 ºC
<95% r.h.
Dimensions:
See Data Sheet
Weight:
See Data Sheet
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
Water Leak Detection WL
Description
Technical Specification
The WLM4 Leak detection module has 4 inputs with zone
indication and 1 common output with fault indication. Din
rail or wall mount options. The WLM can be used with a
combination of sensors.
Features
•Din rail or Wall mounting
•Status LED indication
•Selectable built in sounder and mute
•24Vac/dc or 230Vac supply
•Compact enclosed design
Part Code
Description
WLM4-24
24 Volt 4 Zone Leak Detection Modules
WLM4-230
230 Volt 4 Zone Leak Detection Modules
CA-XSA-4W
Wall Mount Case
WL-RS1
Rain Sensor with Integral Heater
WL-PS1
Point Sensor
WL-CS5
5 Meter Cable sensor
WL-CS10
10 Meter Cable sensor
WL-CS15
15 Meter Cable sensor
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Output:
10Amp @230Vac Volt Free change over
contact
Supply Voltage:
24Vac/dc +/- 10% or 230Vac 60mA
Max sensor length: 200 Meters
LED Indication:
See description under LED Status
Termination:
Rising Clamp for 0.5 to 2.5mm² Cable
Ambient:
–10 to +40°C
Dimensions:Module: 70 x 60 x 90 mm
Wall Mount case: 110 x 90 x 200 mm
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Water leak
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
101
E.C.Products
Building Management Controls & Peripherals
Condensation sensors
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Condensation Sensor KW
Description
Technical Specification
The condensation control switch is installed on cooling or cold
water piping or on cooled surfaces to detect generation of
dew. Monitoring cooling ceilings or pipes, it can be operated
so that the switching output is activated when dew is generating
on cooling ceilings or the object to be monitored, thus starting a
heating system or other actuators.
Features
•Supplied with fixing strap
•IP65 Protection
•Selectable NC/NO Contact output
•Adjustable sensitivity
Part Code
Description
KW-O/S
Condensation Detector
Power supply:24Vac/dc
Switching threshold: ca. 95 % RH.,
variation of ca. ± 5 % RH
Output signal: 24V NO/NC contact selectable by
jumper
Process connection: metal strap for pipes up to 3“ diameter
Electrical connection: 0.14 - 1.5 mm² via terminal screws
Enclosure:
Material polyamide,colour pure white
Dimensions:
72 x 64 x 39.4 mm
Cable union:
M16, including strain relief
Protection type:
IP 65
Condensation Sensor CBS
Description
Technical Specification
Low cost self contained sensors for detecting the onset of
condensation. The units are available in normally open or
normally closed versions providing volt-free contact or
current outputs. These units are installed on the surface
requiring monitoring.
Features
•Detect onset of condensation
•Suitable for chilled beam airconditioning systems
•Volt free or current output
•Normally open or normally closed versions
•Easily installed using cable tie or metal strap supplied
•24V AC or DC powered
102
Part Code
Description
CBS1-NO
Condensation Detector NO contact
CBS1-NC
Condensation Detector NC contact
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Operating characteristics
Output signals, NO:
2-wire mode dry < 5mA wet >10mA
4-wire mode dry Open cct wet 1KW
Output signals, NC:
2-wire mode dry >10mA wet <5mA
4-wire mode dry 1KW wet Open cct
In 4-wire mode, output is isolated from supply
Operating conditions:
0 to +40°C
Electrical specifications
Supply voltage:
15-30VDC or 21VAC
Maximum supply voltage:40VDC or 27VAC
Max operating current: 14mA DC
Connections:
Flying lead
Mechanical details
Dimensions:
90 x 45 x 32mm
Weight:140g
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Multifunction Timer TM-MFT
Description
Technical Specification
Single channel panel mount timer for digital control. Fully
programmable for daily or weekly cycles supplied with battery
backup by means of a Lithium button cell.
Features
•17.5mm Wide
•7 Time Scales from 1 Second to 100 hours
•Multi Function: 7 Functions
•Multi Voltage: 12-240 VAC/DC
•35mm Din Rail Mount
•8A 250VAC Contact Rating
•CE & UL Approved
Part Code
Description
TM-MFT
Single Channel Panel Mount Timer
Operating Voltage:
12-240VAC/DC (+/-10%)
Power Consumption:
1.9VA (Approx.)
Ambient Humidity:
Max 85% RH
Reset Time:
0.5 Seconds
Ambient Temperature:
–10 to +50ºC
Rated Frequency:
50/ 60 Hz
Mechanical Endurance: 5,000,000 Ops
Contact Rating:
8A 250VAC
Electrical Endurance:
100,000 Ops
Weight:62g
Timers
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Plant Extension Timer EP-PET4
Description
Technical Specification
The EP-PET4 Extension timer is a high output electronic timer
which provides control for a wide range of loads. The unit
allows an appliance to be powered for a set time period which
can be adjusted by the user. A simple LED display shows the
user how much time is left to run. Pressing the switch whilst the
unit is operating allows the user to cancel timing program, and
the memory function of the timer will remember the last time
period selected.
Features
•Duel supply
•1–4 hour timing period
•Flush or surface mount
Part Code
Description
EP-PET4
Plant Extension Timer
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Load:
16 Amp resistive load (inc. immersion heaters)
6 Amp fluorescent lighting
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting
(switch primary of transformer)
Fluorescent lighting
(max 6 fittings recommended)
Supply Voltage: 220-240 Volts AC 50 Hz
24VAC/DC +/- 10%
Time Out Period: 1, 2, 3 or 4 hours (selectable)
Terminal Capacity:4.0mm2
Material:
Flame retardant ABS Class 2
Temperature:
–10°C to 35°C
Conformity:EMC-89/336/EEC
LVD-73/23/EEC
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
103
E.C.Products
Building Management Controls & Peripherals
Timers
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Plant Extension Timer EP-LAP
Description
Technical Specification
The EP-LAP electronic timer switch provides energy saving
functionality in ventilation, boiler and lighting installations.
It is ideal for applications where simple interface is required
to control the extension times of the plant. Other typical
applications include manual override to provide intensive
ventilation during busy periods.
Power Supply:
Relay Contact:
Time Selection:
Accuracy:
Housing:
24Vac or 230Vac
10A @ 230Vac
EP-LAP5 - 1...5 hours
EP-LAP10 - 2...10 hours
<± 1 s/h
White Plastic IP20 85 x 85 x 46
Features
•5 or 10 hour versions
•Flush or surface mounted
•24Vac or 230Vac Power Supply
•Timer Hold Feature
Part Code
Description
EP-LAP5
Plant Extension Timer 5 hours
EP-LAP10
Plant Extension Timer 10 hours
Panel and Surface Mount Digital Timers TM6xxx
Description
Technical Specification
Single channel panel mount timer for digital control. Fully
programmable for daily or weekly cycles supplied with battery
backup by means of a Lithium button cell.
Features
Contact:
16A @230Vac SPCO
Power Consumption:7VA
Ambient Operating Temp:–10 to 55°C
Programming Resolution: 1 Minute.
Clock Accuracy:
<1 sec per day
•4 ON/OFF periods daily
•Override period button
•Smallest clock adjustment 1 minute
•7 day, 5+2 day or individual daily setting
•LED indication
•ON-OFF-AUTO Selection
104
Part Code
Description
TM6192
Single Channel Panel Mount Timer
TM6331
Single Channel Surface Mount Timer
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Din Rail Digital Timers TM8xx
Description
Technical Specification
Single/two channel din rail mount timers for digital control.
Fully programmable for daily or weekly cycles supplied with
battery backup by means of a Lithium button cell.
Contact:
(2x) 12A @230Vac SPCO
Power Consumption:7VA
Ambient Operating Temp:–10 to 55°C
Programming Resolution: 1 Minute.
Clock Accuracy:
<1 sec per day
Features
Timers
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
•4 ON/OFF periods daily per channel
•Override period button
•Smallest clock adjustment 1 minute
•7 day, 5+2 day or individual daily setting per channel
•LED indication
•ON-OFF-AUTO Selection
Part Code
Description
TM848
Single Channel Din Rail Timer
TM812
Two Channel Din Rail Timer
Panel Ventilation FA
Description
The FA range of panel ventilation products include high quality
Fans Grills and Finger Guards for Panel Manufacturers.
Part Code
Description W x H x D
FA-F120-230
Axial Fan 230Vac 165M³/Hr
120 x 120 x 38mm
FA-F120-24
Axial Fan 24Vac 150M³/Hr
120 x 120 x 38mm
FA-FK150-230
Combined Fan And Filter Unit,
Fan 120 x 120 x 38mm
FA-CFG120
Chrome finger guard to fit 120mm Axial Fan
FA-PFG120
Plastic Finger Guard to fit 120mm Axial Fan
FA-TS-NO
Din Rail Mounted Thermostat 10Amp @230Vac
FA-FFG-120
Axial Fan Filter Guard 120mm
FA-FFA-120-IP54 Axial Fan Filter Guard 120mm IP54
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
105
E.C.Products
Building Management Controls & Peripherals
Enclosures
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Hinged Door Enclosures ENC-DED
Description
Technical Specification
Hinged Door Enclosures are made from ABS HB material to
IP65 standard and come complete with a steel back plate,
mounting wall brackets and lockable key. They come in eight
sizes and can be used in various environments including coastal
conditions, dry dusty environments and in heavy humidity.
Features
•Designed to meet protection and combustible standards IP65
and IK08
•Available in eight sizes
•Supplied in grey (RAL 7035) with solid door and base unit
•Come complete with steel back plate, mounting brackets & key
•Wall thickness on the range is 3 – 3.5mm
•Made from UL approved ABS-HB flame retardant plastic
•Comply with the following standards: EN 60439-1, EN
62208, CEI 23-48, CEI 23-49
•Perform within a temperature range of –20° to +85°C
•Suitable for use in sea salt air conditions and dry dust
environments
Part Code
Operating Voltage:
12-240VAC/DC (+/-10%)
Power Consumption:
1.9VA (Approx.)
Ambient Humidity:
Max 85% RH
Reset Time:
0.5 Seconds
Ambient Temperature:
–10 to +50ºC
Rated Frequency:
50/ 60 Hz
Mechanical Endurance: 5,000,000 Ops
Contact Rating:
8A 250VAC
Electrical Endurance:
100,000 Ops
Weight:62g
Description W x H x D
ENC-DED001 200x300x130mm Enclosure with hinged door
ENC-DED002 250x350x150mm Enclosure with hinged door
ENC-DED004 300x400x170mm Enclosure with hinged door
ENC-DED005 300x400x220mm Enclosure with hinged door
ENC-DED006 350x500x190mm Enclosure with hinged door
ENC-DED007 400x500x240mm Enclosure with hinged door
ENC-DED008 400x600x200mm Enclosure with hinged door
ENC-DED010 500x700x250mm Enclosure with hinged door
106
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Bespoke
Bespoke products and user interfaces
Upon request special sensors and interfaces are available.
Engraved plates with set points, push buttons, displays and
sensors. Available in a variety of finishes including brass,
stainless steel and plastic as well as any other electroplated
finish.
Please contact our sales office for more information and
quotations.
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
107
E.C.Products
Building Management Controls & Peripherals
Contactors
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
AC Contactors CC1-Dx
Description
Coil Voltages
The CC1-D Series AC Contactors are suitable for use in circuits
up to the rated voltage of 660Vac 50/60Hz and are suited to
applications such as making, breaking, frequently starting and
controlling AC motors. A range of accessories are available The
units are manufactured to IEC60947-4 and certified SEMKO.
To order these items, please specify coil voltage and contact
type. Example: CC1-D09/B5/NO = 4Kw contactor, 24Vac coil,
normally open contact
Features
Coil Voltages (VAC)
24
230
50Hz
B5
P5
50/60Hz
B7
P7
•Choice of coil voltages
•Up to 95A rated current
•Accessories available
Rated
Current (A)
Power Rating of 3-ph motors
AC3 (Kw)
Part Code
AC3 AC4 220/230V 380/400V 415V
Rated Heat
Electrical Life Mech.
Life x106 No. of contacts
Current (A) lth AC3 x106
CC1-D09
9
3.5
2.2
4
4
20
2
20
3P + NO/ 3P + NC
CC1-D12
12
5
3
5.5
5.5
20
2
20
3P + NO/ 3P + NC
CC1-D18
18
7.7
4
7.5
9
32
2
20
3P + NO/ 3P + NC
CC1-D25
25
8.5
5.5
11
11
40
2
20
3P + NO/ 3P + NC
CC1-D32
32
12
7.5
15
15
50
2
20
3P + NO/ 3P + NC
CC1-D40
40
18.5 11
18.5
22
60
2
20
3P + NO + NC
CC1-D50
50
24
15
22
25
80
2
20
3P + NO + NC
CC1-D65
65
28
18.5
30
37
80
1.6
20
3P + NO + NC
CC1-D80
80
37
22
37
45
125
1.6
10
3P + NO + NC
CC1-D95
95
44
25
45
45
125
1.6
10
3P + NO + NC
AC Contactors Accessories
108
Part Code
Description
CA1-DN11
Top Auxiliary Contact Block 1NO + 1NC for CC1-D
CA1-DN22
Top Auxiliary Contact Block 2NO + 2NC for CC1-D
CA1-DN40
Top Auxiliary Contact Block 4NO for CC1-D
CA1-DN04
Top Auxiliary Contact Block 4NC for CC1-D
CX1-D2
Spare Coils for CC1-D09, D12, D18 (specify voltage eg. CX1-D2/B5)
CX1-D4
Spare Coils for CC1-D25, D32 (specify voltage eg. CX1-D2/B5)
CX1-D6
Spare Coils for CC1-D40 - D95(specify voltage eg. CX1-D2/B5)
CA9-D09-32
Mechanical Interlocks for CC1-D09 to CC1-D32
CA9-D40-95
Mechanical Interlocks for CC1-D40 to CC1-D95
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
E.C.Products
Building Management Controls & Peripherals
Description
Features
CR2-D/K thermal overload relays are designed to protect
AC circuits and motors against overload, phase failure and
prolonged starting of the motor.
Part Code
Overloads
Thermal Overload Relays CR2-x
•Test Button
•Stop Button
•Reset Button
•Trip Indicator
Range
CR2-D1301
0.10-0.16A
CR2-D1302
0.16-0.25A
CR2-D1303
0.25-0.40A
CR2-D1304
0.40-0.63A
CR2-D1305
0.63-1.0A
CR2-D1306
1.0-1.6A
CR2-D1307
1.6-2.5A
CR2-D1308
2.5-4.0A
CR2-D1310
4.0-6.0A
CR2-D1312
5.5-8.0A
CR2-D1314
7.0-10.0A
CR2-D1316
9.0-13.0A
CR2-D1321
12.0-18.0A
CR2-D1322
17.0-25.0A
CR2-D3353
23.0-32.0A
CR2-D3355
30.0-40.0A
CR2-D3357
37.0-50.0A
CR2-D3359
48.0-65.0A
CR2-D3361
55.0-70.0A
CR2-D3363
63.0-80.0A
CR2-D3365
80.0-93.0A
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
109
E.C.Products
Building Management Controls & Peripherals
Moror starters
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Manual Motor Starters CAV2
Description
Features
The CAV2 series motor protection circuit breakers are mainly
used for overload and short circuit protection of AC motors, as
a full voltage starter to start and stop the motor or for
the overload and short circuit protection of the circuit and
power equipment.
•Wide choice of current ranges
•Auxiliary switch available
Standard Kw Power Ratings of 3-phase motors
50/60Hz in category AC-3
110
220V
380V
415V
440V
500V
660V
Setting
Range
Motor Protection Circuit breaker
(Manual Motor Starter) 0.25-0.4A
–
–
–
–
–
–
0.25...4
CAV2-M04
Motor Protection Circuit breaker
(Manual Motor Starter) 0.4-0.63A
–
–
–
–
–
0.37
0.4...0.63
CAV2-M05
Motor Protection Circuit breaker
(Manual Motor Starter) 0.63-1.0A
–
–
–
0.37
0.37
0.55
0.63...1
CAV2-M06
Motor Protection Circuit breaker
(Manual Motor Starter) 1-1.6A
–
0.37
–
0.55
0.75
1.1
1...1.6
CAV2-M07
Motor Protection Circuit breaker
(Manual Motor Starter) 1.6-2.5A
0.37
0.75
0.75
1.1
1.1
1.5
1.6-2.5
CAV2-M08
Motor Protection Circuit breaker
(Manual Motor Starter) 2.5-4A
0.75
1.5
1.5
1.5
2.2
3
2.5...4
CAV2-M10
Motor Protection Circuit breaker
(Manual Motor Starter) 4-6.3A
1.1
2.2
2.2
3
3.7
4
4...6.3
CAV2-M14
Motor Protection Circuit breaker
(Manual Motor Starter) 6-10A
2.2
4
4
4
5.5
7.5
6...10
CAV2-M16
Motor Protection Circuit breaker
(Manual Motor Starter) 9-14A
3
5.5
5.5
7.5
7.5
9
9...14
CAV2-M20
Motor Protection Circuit breaker
(Manual Motor Starter) 13-18A
4
7.5
9
9
9
11
13...18
CAV2-M21
Motor Protection Circuit breaker
(Manual Motor Starter) 17-23A
5.5
11
11
11
11
15
17...23
CAV2-M22
Motor Protection Circuit breaker
(Manual Motor Starter) 20-25A
5.5
11
11
11
15
18.5
20...25
CAV2-M32
Motor Protection Circuit breaker
(Manual Motor Starter) 24-32A
7.5
15
15
15
18.5
26
24...32
CAV2-AN11
Auxiliary Contact Block for CAV2-M
Part Code
Description
CAV2-M03
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Boxed Isolators LW30
Description
Features
The LW30 are a range of boxed isolators in a choice of current
ratings and housed inside an IP65 enclosure
Part Code
Description
LW30-20-400011
4 Pole Boxed Switch Disconnector 20A
LW30-32-400011
4 Pole Boxed Switch Disconnector 32A
LW30-40-400011
4 Pole Boxed Switch Disconnector 40A
LW30-63-400011
4 Pole Boxed Switch Disconnector 63A
LW30-80-400011
4 Pole Boxed Switch Disconnector 80A
•Choice of current ratings
•IP65 enclosure
Isolators
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
LW30-100-400011 4 Pole Boxed Switch Disconnector 100A
Door Interlocked Isolators LW30
Description
Features
The LW30 are a range of door isolators in a choice of current
ratings and are supplied with a 300mm long shaft.
•Choice of current ratings
•300mm shaft
Part Code
Description
LW30-20-400040
4 Pole Door Interlocked Switch Disconnector 20A
LW30-32-400040
4 Pole Door Interlocked Switch Disconnector 32A
LW30-63-400040
4 Pole Door Interlocked Switch Disconnector 63A
LW30-80-400040
4 Pole Door Interlocked Switch Disconnector 80A
LW30-100-400040
4 Pole Door Interlocked Switch Disconnector 100A
Description
Features
A range of enclosures suitable for housing circuit breakers
available as flush or wall mounting and supplied complete with
DIN rail and earth connecting strips.
•Up to 36 ways
•Flush or wall mounted
Flush
Wall
Description
CA-XSA-4F
CA-XSA-4W
Distribution Enclosure Flush or Wall Mount 4 way
CA-XSA-6F
CA-XSA-6W
Distribution Enclosure Flush or Wall Mount 6 way
CA-XSA-8F
CA-XSA-8W
Distribution Enclosure Flush or Wall Mount 8 way
CA-XSA-12F
CA-XSA-12W
Distribution Enclosure Flush or Wall Mount 12 way
CA-XSA-18F
CA-XSA-18W
Distribution Enclosure Flush or Wall Mount 18 way
CA-XSA-24F
CA-XSA-24W
Distribution Enclosure Flush or Wall Mount 24 way
CA-XSA-36F
CA-XSA-36W
Distribution Enclosure Flush or Wall Mount 36 way
T: +44 (0)20 8569 4100
MCB enclosures
Distribution Enclosures CA-XSA-x
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
111
E.C.Products
Building Management Controls & Peripherals
RCCB
Mains switch isolators
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Mainswitch Isolators CAH1
Description
Technical Specification
A range of items suitable to provide isolation functions and to
be used as a main switch.
Features
•Provides function of isolation
•Contact position indication
Part Code
Description
CAH1-100/1P40
Single Pole Isolator/Mainswitch 40A
CAH1-100/1P63
Single Pole Isolator/Mainswitch 63A
CAH1-100/1P80
Single Pole Isolator/Mainswitch 80A
CAH1-100/1P100
Single Pole Isolator/Mainswitch 100A
Residual Current Circuit Breakers CAL2
Description
Technical Specification
A range of Residual Current Circuit Breakers to provide
protection against earth fault/leakage current.
Features
•Contact position Indication
•Finger protected terminals
112
Number of Poles:
1 or 2
Rated Current:
See below
Rated Voltage:
230Vac 50/60Hz
Rated Short-circuit capacity:6kA
Maximmum Current:
1500A for 1 second
Electro-Mechanical Endurance: 10000 cycles
Mounting:
DIN rail
Number of Poles:
2/4 poles
Rated making/breaking capacity:630A
Rated Current:
See below
Rated Voltage:
230/400Vac, 50/60Hz
Rated Residual Operating Current:30mA
Conditional Short Circuit Current:6kA
Tripping Duration:
<0.1 s
Electro-Mechanical Endurance:
4000 cycles
Mounting:
DIN rail
Part Code
Description
CAL2-25I/2P30
Two Pole Residual Current Circuit Breaker 25A 30mA trip
CAL2-40I/2P30
Two Pole Residual Current Circuit Breaker 40A 30mA trip
CAL2-63I/2P30
Two Pole Residual Current Circuit Breaker 63A 30mA trip
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
RCCB with Overcurrent Protection CA30LE
Description
Technical Specification
Rated Voltage:
230/240Vac, 50/60Hz
Short Circuit Capacity:3kA
Rated Current:
See below
Rated Residual Operating Current:30mA
Poles:
1P + n
Tripping Curves:
B, C
Mounting:
DIN rail
Features
•Contact position Indication
•DIN ail mounted
Curve B
Curve C
Description
CA30LE-6B
CA30LE-6C
Two Pole (1P + N) RCBO 6A Curve B or C 30mA trip
CA30LE-16B
CA30LE-16C
Two Pole (1P + N) RCBO 16A Curve B or C 30mA trip
CA30LE-20B
CA30LE-20C
Two Pole (1P + N) RCBO 20A Curve B or C 30mA trip
CA30LE-32B
CA30LE-32C
Two Pole (1P + N) RCBO 32A Curve B or C 30mA trip
Miniature Circuit Breakers DZ47
Description
Technical Specification
A range of miniature circuit breakers suitable 230/400Vac,
50/60Hz rated circuits up to 63 amps. They provide protection
against overload and short circuits in electrical circuits and
equipment in household and commercial applications. They can
also be used for non-frequent changeover of electrical circuits.
Features
•Protection against overload and short circuit
•Contact position indication
•DIN rail mounted
Number of Poles:
1P, 2P or 3P
Rated Voltage:230/400Vac
Rated Current:
1, 2, 4, 6, 10, 12, 16, 20,
25, 32, 40, 50, 63 amps
Tripping Curve:
B, C or D
Rated Short Circuit Capacity:6kA
Rated Frequency:50/60Hz
Energy Limiting Class:3
Rated Impulse Voltage withstand:6.2kV
Electro-Mechanical Endurance: 4000 cycles
Connection Terminal:
Pillar Terminal with clamp
Connection Capacity:
Rigid conductor
up to 25mm²
Mounting:
DIN rail
Curve B
Curve C
Curve D
Description
DZ47-63/1PxB
DZ47-63/1PxC
DZ47-63/1PxD
Single pole Miniature Circuit Breaker x= current rating see above
–
DZ47-63/2PxC
–
–
DZ47-63/3PxC
DZ47-63/3PxD
T: +44 (0)20 8569 4100
MCB
A range of RCBO units to provide protection against earth
fault/leakage current and overload.
RCBO
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Two pole Miniature Circuit Breaker x= current rating see above
Three pole Miniature Circuit Breaker x= current rating see above
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
113
Push Buttons
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
E.C.Products
Building Management Controls & Peripherals
Pushbutton Switches XB2-xA
Description
XB2 series pushbuttons are used in the control of electrical
circuits. A choice of panel mounting bezel and colours is
available as well as different combinations of contact block.
Illuminated versions can also be supplied.
Features
•Choice of colours
•Choice of bezel
Technical Specification
Rated Insulation Voltage:660V
Operating Temperature:–5…+40°c
Operating Humidity:
45...85% RH
Electrical Life:
50 x 10°C operations
Protection:IP40
Part Code
Description
XB2-BA11
Normally open pushbutton white - metal bezel
XB2-BA21
Normally open pushbutton black - metal bezel
XB2-BA31
Normally open pushbutton green - metal bezel
XB2-BA42
Normally closed pushbutton red - metal bezel
XB2-BA51
Normally open pushbutton yellow - metal bezel
XB2-BA61
Normally open pushbutton blue - metal bezel
XB2-EA11
Normally open pushbutton white - plastic bezel
XB2-EA21
Normally open pushbutton black - plastic bezel
XB2-EA31
Normally open pushbutton green - plastic bezel
XB2-EA42
Normally closed pushbutton red - plastic bezel
XB2-EA51
Normally open pushbutton yellow - plastic bezel
XB2-EA61
Normally open pushbutton blue - plastic bezel
ZB2-BE101
N/O Contact
ZB2-BE102
N/C Contact
Part Code
Description
XB2-BP21
Normally open pushbutton black - IP66
XB2-BP31
Normally open pushbutton green - IP66
XB2-BP42
Normally closed pushbutton red - IP66
XB2-BP51
Normally open pushbutton yellow - IP66
XB2-BP61
Normally open pushbutton blue - IP66
ZB2-BE101
N/O Contact
ZB2-BE102
N/C Contact
Pushbutton Switches IP66 XB2-BP
Description
XB2-BP series pushbuttons are used in the control of electrical
circuits. A choice of colours is available and the units are
supplied with a waterproof boot giving
IP66 protection.
Features
•Choice of colours
•IP66 Protection
Technical Specification
Rated Insulation Voltage:660V
Operating Temperature:–5…+40°c
Operating Humidity:
45...85% RH
Electrical Life:
50 x 105 operations
Protection:IP66
114
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Illuminated Pushbuttons XB2-xW
Description
Technical Specification
XB2 series illuminated pushbuttons are used in the control
of electrical circuits. A choice of panel mounting bezel and
colours is available as well as different combinations of contact
block. Illuminated versions use LEDs for long life.
Features
Rated Insulation Voltage:660V
Operating Temperature:–5…+40°c
Operating Humidity:
45...85% RH
Electrical Life:
50 x 105 operations
Protection:IP40
Push Buttons
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
•Choice of colours
•Choice of bezel
•LED Illumination
Part Code
Description
XB2-BW11
Normally open 24V LED illuminated pushbutton white - metal bezel
XB2-BW31
Normally open 24V LED illuminated pushbutton green - metal bezel
XB2-BW42
Normally closed 24V LED illuminated pushbutton red - metal bezel
XB2-BW51
Normally open 24V LED illuminated pushbutton yellow - metal bezel
XB2-BW61
Normally open 24V LED illuminated pushbutton blue - metal bezel
XB2-EW11
Normally open 24V LED illuminated pushbutton white - plastic bezel
XB2-EW31
Normally open 24V LED illuminated pushbutton green - plastic bezel
XB2-EW42
Normally closed 24V LED illuminated pushbutton red - plastic bezel
XB2-EW51
Normally open 24V LED illuminated pushbutton yellow - plastic bezel
XB2-EW61
Normally open 24V LED illuminated pushbutton blue - plastic bezel
ZB2-BE101
N/O Contact
ZB2-BE102
N/C Contact
Mushroom Head Pushbuttons XB2-BSx
Description
Technical Specification
XB2-BS series pushbuttons are used in the control of electrical
circuits. Units are supplied in a choice of 40mm diameter
mushroom head with turn to release or key
release mechanism.
Rated Insulation Voltage:660V
Operating Temperature:–5…+40°c
Operating Humidity:
45...85% RH
Electrical Life:
50 x 105 operations
Protection:IP40
Features
•40mm diameter mushroom head
•Turn or key to release versions
Part Code
Description
XB2-BS542
Mushroom head pushbutton, turn to release, normally closed
XB2-BS142
Mushroom head pushbutton, key to release, normally closed
XB2-ER60
60mm diameter Emergency Stop warning circle
ZB2-BE101
N/O Contact
ZB2-BE102
N/C Contact
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
115
E.C.Products
Building Management Controls & Peripherals
Selector Switches
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Selector Switches XB2-x
Description
Technical Specification
XB2 series rotary selector switches are used in the control
of electrical circuits . A choice of panel mounting bezel is
available as well as long or short handles, key operated and
2/3 way versions. Illuminated versions in a choice of colours
can also be supplied.
Rated Insulation Voltage:660V
Operating Temperature:–5…+40°c
Operating Humidity:
45...85% RH
Electrical Life:
50 x 10 5 operations
Protection:IP40
Features
•Key operated versions
•Metal or plastic bezel
•2 or 3 way versions
•Illuminated versions
Part Code
Description
XB2-BD21
2 position NO stay put rotary switch - metal bezel
XB2-BD25
2 position NO + NC stay put rotary switch - metal bezel
XB2-BD33
3 position NO + NO stay put rotary switch - metal bezel
XB2-BJ21
2 position NO stay put rotary switch - metal bezel, long handle
XB2-BJ25
2 position NO + NC stay put rotary switch - metal bezel, long handle
XB2-BJ33
3 position NO + NO stay put rotary switch - metal bezel, long handle
XB2-BG21
2 position NO stay put rotary switch - metal bezel, key operated
XB2-BG25
2 position NO + NC stay put rotary switch - metal bezel, key operated
XB2-BG33
3 position NO + NO stay put rotary switch - metal bezel, key operated
XB2-ED21
2 position NO stay put rotary switch - plastic bezel
XB2-ED25
2 position NO + NC stay put rotary switch - plastic bezel
XB2-ED33
3 position NO + NO stay put rotary switch - plastic bezel
XB2-EG21
2 position NO stay put rotary switch - plastic bezel, key operated
XB2-EG25
2 position NO + NC stay put rotary switch - plastic bezel, key operated
XB2-EG33
3 position NO + NO stay put rotary switch - plastic bezel, key operated
XB2-BK21
2 position NO + NC stay put 24V LED illuminated rotary switch white - metal bezel
XB2-BK23
2 position NO + NC stay put 24V LED illuminated rotary switch green - metal bezel
XB2-BK24
2 position NO + NC stay put 24V LED illuminated rotary switch red - metal bezel
XB2-BK25
2 position NO + NC stay put 24V LED illuminated rotary switch yellow - metal bezel
XB2-BK26
2 position NO + NC stay put 24V LED illuminated rotary switch blue - metal bezel
XB2-BK31
3 position NO + NC stay put 24V LED illuminated rotary switch white - metal bezel
XB2-BK33
3 position NO + NC stay put 24V LED illuminated rotary switch green - metal bezel
XB2-BK34
3 position NO + NC stay put 24V LED illuminated rotary switch red - metal bezel
XB2-BK35
3 position NO + NC stay put 24V LED illuminated rotary switch yellow - metal bezel
XB2-BK36
3 position NO + NC stay put 24V LED illuminated rotary switch blue - metal bezel
ZB2-BE101
N/O Contact
ZB2-BE102 N/C Contact
116
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
16mm Panel Indicators AD16DS
Description
Technical Specification
A range of 16/22mm indicator lamps used in electrical circuits
in a variety of voltages. They are primarily used for indication
and alarm signals and conform to IEC60947-5-1. The AD16DS
utilize LEDs for long life and very low energy consumption and
have concealed terminals.
Features
•Choice of colours
•Choice of voltages
•LED for long life
16mm
22mm
24Vac/dc 110Vac
AD16DS-R
AD56DS-R
–24
AD16DS-G
AD56DS-G
AD16DS-B
Operating Temperature:–5…+40°
Operating Humidity:
45...85% RH
Pollution Degree:3
Installation Degree:III
Degree of Protection:IP65
Rated Operating Current: ≤ 80mA
Electrical Life:
≥30000 hours
Brightness:≥60
Rated Operating Voltage: See below
Base Colour:
See below
230Vac
Description
–110
–220
Multi LED 16/22mm panel indicator pure colour red
–24
–110
–220
Multi LED 16/22mm panel indicator pure colour green
AD56DS-B
–24
–110
–220
Multi LED 16/22mm panel indicator pure colour blue
AD16DS-Y
AD56DS-Y
–24
–110
–220
Multi LED 16/22mm panel indicator pure colour yellow
AD16DS-W
AD56DS-W
–24
–110
–220
Multi LED 16/22mm panel indicator pure colour white
Panel lamps
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
22mm Panel Indicators AD56HS
Description
Technical Specification
A range of 22mm indicator lamps used in electrical circuits in
a variety of voltages. They are primarily used for indication
and alarm signals and conform to IEC60947-5-1. The AD56HS
utilize LEDs for long life and very low energy consumption and
have concealed terminals.
Features
•Choice of colours
•Choice of voltages
•LED for long life
•Conical Bezel
Part Code
24Vac/dc 110Vac
Operating Temperature:–5…+40°
Operating Humidity:
45...85% RH
Pollution Degree:3
Installation Degree:III
Degree of Protection:IP65
Rated Operating Current:≤ 80mA
Electrical Life:
≥30000 hours
Brightness:≥60
Rated Operating Voltage:See below
Base Colour
See below
230Vac
Description
AD56HS-R
–24
–110
–220
Multi LED conical 22mm panel indicator pure colour red
AD56HS-G
–24
–110
–220
Multi LED conical 22mm panel indicator pure colour green
AD56HS-B
–24
–110
–220
Multi LED conical 22mm panel indicator pure colour blue
AD56HS-Y
–24
–110
–220
Multi LED conical 22mm panel indicator pure colour yellow
AD56HS-W
–24
–110
–220
Multi LED conical 22mm panel indicator pure colour white
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
117
E.C.Products
Building Management Controls & Peripherals
Panel lamps
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
22mm Panel Indicators with Lamp Test AD56LT
Description
Technical Specification
A range of 22mm indicator lamps used in electrical circuits in a
variety of voltages. They are primarily used for indication and
alarm signals and conform to IEC60947-5-1. The AD56LT utilize
LEDs for long life and very low energy consumption and have
lamp test facility.
Features
•Choice of colours
•Choice of voltages
•LED for long life
•Lamp Test Facility
Part Code
24Vac/dc
110Vac
230Vac
Description
Operating Temperature:–5…+40°
Operating Humidity:
45...85% RH
Pollution Degree:3
Installation Degree:III
Degree of Protection:IP65
Rated Operating Current: ≤ 80mA
Electrical Life:
≥30000 hours
Brightness:≥60
Rated Operating Voltage: See below
Base Colour:
See below
AD56LT-R
–24
–110
–220
Multi LED lamp 22mm panel indicator pure colour red
AD56LT-G
–24
–110
–220
Multi LED lamp 22mm panel indicator pure colour green
AD56LT-B
–24
–110
–220
Multi LED lamp 22mm panel indicator pure colour blue
AD56LT-Y
–24
–110
–220
Multi LED lamp 22mm panel indicator pure colour yellow
AD56LT-W
–24
–110
–220
Multi LED lamp 22mm panel indicator pure colour white
22mm Panel Indicators AD56TW
Description
Technical Specification
A range of 22mm indicator lamps used in electrical circuits in
a variety of voltages. They are primarily used for indication
and alarm signals and conform to IEC60947-5-1. The AD56TW
utilise LEDs for long life and very low energy consumption and
have twin colours.
See AD56LT above.
Features
•Choice of colours
•Choice of voltages
•LED for long life
•Twin Colour
Part Code
AD56TW-RG
118
24Vac/dc 110Vac
–24
–110
T: +44 (0)20 8569 4100
230Vac
Description
–220
Multi LED 22mm panel indicator colour red/green
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
Xenon Beacon BX
Description
Technical Specification
The BX Flashing Xenon Beacon is an IP65 warning Beacon
available in 2 Voltages and 5 different colours which can be
mounted directly or as a bayonet fitting with rear cable entry.
Features
Supply Voltage:
10-28 Vdc or 115-230Vac
Lens colours:
Red, Amber, Blue, Green or Clear
Flash rate:1Hz
IP Rating:IP65
Output:
1.5-2.5 Joules
•Available in 5 Colours
•Robust construction
•Can be mounted Outside
•Bayonet Mounting
•2 Voltage options
Part Code
Description
BX-R24
Red Xenon Beacon 10-28Vdc
BX-A24
Amber Xenon Beacon 10-28Vdc
BX-B24
Blue Xenon Beacon 10-28Vdc
BX-C24
Clear Xenon Beacon 10-28Vdc
BX-G24
Green Xenon Beacon 10-28Vdc
BX-R230
Red Xenon Beacon 115-230Vac
BX-A230
Amber Xenon Beacon 115-230Vac
BX-B230
Blue Xenon Beacon 115-230Vac
BX-C230
Clear Xenon Beacon 115-230Vac
BX-G230
Green Xenon Beacon 115-230Vac
Xenon beacons
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Spanner for 22mm Panel Indicators AD56SPAN
Description
A spanner suitable for tightening locking nuts on the range of
22mm panel indicators.
Part Code
Description
AD56SPAN Spanner for 22mm Panel Indicators
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
119
E.C.Products
Building Management Controls & Peripherals
Cable glands
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Nylon Cable Glands Mx
Description
Features
A range of nylon cable glands in sizes from M12 up to M50
supplied complete with locknut and most sizes in a choice
of colours.
•Wide size range
•Choice of colours
•Complete with locknut
Part Code
Description
M12X1.5
Nylon cable gland M12 x 1.5mm c/w locknut
M16X1.5
Nylon cable gland M16 x 1.5mm c/w locknut
M20X1.5
Nylon cable gland M20 x 1.5mm c/w locknut - Cable size 6-12mm
M20X1.5S
Nylon cable gland M20 x 1.5mm c/w locknut - Cable size 4-9mm
M25X1.5
Nylon cable gland M25 x 1.5mm c/w locknut
M32X1.5
Nylon cable gland M32 x 1.5mm c/w locknut
M40X1.5
Nylon cable gland M40 x 1.5mm c/w locknut
M50X1.5
Nylon cable gland M50 x 1.5mm c/w locknut
Busbar
DIN Rail
Available colours: R = Red, GR = Grey, BLK = Black, W = White
120
DIN Rail
Description
Features
A range of DIN rail available in 2 metre lengths and a choice
of styles.
Part Code
Description
DIN1
35mm Slotted Din rail - 2 metre lengths
DIN2
‘G’ Profile Slotted DIN rail - 2 metre lengths
DIN3
35mm Slotted Din rail deep profile - 2 metre lengths
•Choice of styles
•2 metre lengths
Busbar PB
Description
Features
A range of busbar available in 1 metre lengths and a choice
of poles.
•1, 2 or 3 pole
•Pin Type
Part Code
Description
PB1
Pin type Busbar - Single pole 63A - 1 metre lengths
PB2
Pin type Busbar - Two pole 63A - 1 metre lengths
PB3
Pin type Busbar - Three pole 63A - 1 metre lengths
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
DIN Rail Terminals JXB
Description
Features
A range of DIN rail terminals with some sizes available in a
choice of colours. A range of accessories is also available.
Part Code
Description
JXB-2.5/EK
DIN rail earth terminal 2.5mm² wire
JXB-4/EK
DIN rail earth terminal 4mm² wire
JXB-6/EK
DIN rail earth terminal 6mm² wire
JXB-10/EK
DIN rail earth terminal 10mm² wire
JXB-16/EK
DIN rail earth terminal 16mm² wire
JXB-35/EK
DIN rail earth terminal 35mm² wire
JXB-EW
End stop for DIN rail terminals
JXB10/2.5
Connecting links for JXB-2.5
JXB10/4
Connecting links for JXB-4
JXB10/6
Connecting links for JXB-6
JBX10/10
Connecting links for JXB-10
JXB-TM
Terminal marker Strips 100 pieces blank
JXB-TM100
Terminal marker Strips 100 pieces 1-100
JXB-TM200
Terminal marker Strips 100 pieces 101-200
Grey
Red
•Top hat or ‘G’ profile DIN rail mounting
Blue
Description
JXB-2.5/35/G JXB-2.5/35/R
JXB-2.5/35/B
DIN rail terminal 2.5mm² wire 24A
JXB-4/35/G
JXB-4/35/B
DIN rail terminal 4mm² wire 32A
JXB-4/35/R
JXB-6/35/G
–
–
DIN rail terminal 6mm² wire 41A
JXB-10/35/G
–
–
DIN rail terminal 10mm² wire 57A
JXB-16/35/G
–
–
DIN rail terminal 16mm² wire 76A
JXB-35/35/G
–
–
DIN rail terminal 35mm² wire 125A
JXB-70/35/G
–
–
DIN rail terminal 75mm² wire 192A
JXB-EC2.5/G
–
JXB-EC2.5/B
End Cover for JXB-2.5
JXB-EC4/G
–
JXB-EC4/B
End cover for JXB-4, JXB-6, JXB-10
JXB-EC16/G
–
–
End cover for JXB-16
JXB-EC35/G
–
–
End cover for JXB-35
JXB-EC70/G
–
–
End cover for JXB-70
JXB-RD
–
–
DIN rail fuse terminal 6.3A
JXB-KN
–
–
DIN rail 4mm² knife disconnect terminal
JXB-4/35S1
–
–
DIN rail double level terminal 4mm² wire
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
Terminals
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
121
E.C.Products
Building Management Controls & Peripherals
Terminals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
122
DIN Rail Terminals CON High quality
Description
Features
This range of CON terminals offer a proven screw connection
system for the smallest cross sections ranging from 0.08mm² to
10mm². The protective earth terminals feature a PE foot contact
that is snapped on without screws, ensuring good mechanical
and electrical safety. The terminals also offer an insulated
pluggable jumper system allowing terminals to be easily and
quickly linked.
•Three colours available
•Compact design
•Pluggable Jumpers
•4 sizes available
•Secure Snap-on mounting
Part Code
Description
Part Code
Description
CON-BE2.5
2.5mm Beige Terminal
CON-FT
Din Rail Fuse Terminal
CON-BL2.5
2.5mm Blue Terminal
CON-FT/EC
End Cover For Fuse Terminal
CON-RD2.5
2.5mm Red Terminal
CON-KD
Disconnect Terminal 2.5mm
CON-ET2.5
2.5mm Earth Terminal
CON-DDT/4
Double Deck Terminal 4.0mm
CON-BE4
4.0mm Beige Terminal
CON-DDT/4/EC
End Cover For Double Deck Terminal
CON-BL4
4.0mm Blue Terminal
CON-ES
End Stop
CON-RD4
4.0mm Red Terminal
CON-TM/B
Terminal Markers Blank
CON-ET4
4mm Earth Terminal
CON-TM-1/50
Terminal Markers 1-50
CON-BE6
6.0mm Beige Terminal
CON-TM-51/100
Terminal Markers 51-100
CON-BL6
6.0mm Blue Terminal
CON-TM-101/150 Terminal Markers 101-150
CON-RD6
6.0mm Red Terminal
CON-TM-151/200 Terminal Markers 151-200
CON-ET6
6mm Earth Terminal
CON-TM-201/250 Terminal Markers 201-250
CON-BE10
10.0mm Beige Terminal
CON-TM-251/300 Terminal Markers 251-300
CON- BL10
10.0mm Blue Terminal
CON-TM-301/350 Terminal Markers 301-350
CON- RD10
10.0mm Red Terminal
CON-TM-351/400 Terminal Markers 351-400
CON-ET10
10.0mm Earth Terminal
CON-BB-10
Busbar 10x3mm Copper
CON-2.5/10EC
End Plate for 2.5mm-10mm Terminals
CON-BBS
Busbar Support
CON-2-2.5
Pluggable Insulated Jumper 2.5mm 2 Way
CON-BB-GY4
Busbar Terminal 4mm Green/Yellow
CON-10-2.5
Pluggable Insulated Jumper 2.5mm 10 Way
CON-BB-BL4
Busbar Terminal 4mm Blue
CON-2-4
Pluggable Insulated Jumper 4mm 2 Way
CON-BB-GY16
Busbar Terminal 16mm Green/Yellow
CON-10- 4
Pluggable Insulated Jumper 4mm 10 Way
CON-BB-BL16
Busbar Terminal 16mm Blue
CON-2-6
Pluggable Insulated Jumper 6mm 2 Way
CON-10- 6
Pluggable Insulated Jumper 6mm 10 Way
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Part Code
Description
TCS-3
Terminal Connector Strip 12 way 3A
TCS-6
Terminal Connector Strip 12 way 6A
TCS-15
Terminal Connector Strip 12 way 15A
TCS-30
Terminal Connector Strip 12 way 30A
Wiring accessories
Terminal Connector Strip TCS
Cord End Ferrules E/TE
German
French
Description
E0508-G
E0508-F
Pre-insulated cord end terminals 0.5mm² - bag of 1000
E7508-G
E7508-F
Pre-insulated cord end terminals 0.75mm² - bag of 1000
E1008-G
E1008-F
Pre-insulated cord end terminals 1.0mm² - bag of 1000
E1508-G
E1508-F
Pre-insulated cord end terminals 1.5mm² - bag of 1000
E2508-G
E2508-F
Pre-insulated cord end terminals 2.5mm² - bag of 1000
E4010-G
E4010-F
Pre-insulated cord end terminals 4.0mm² - bag of 1000
E6012-G
E6012-F
Pre-insulated cord end terminals 6.0mm² - bag of 1000
E10-12-G
E10-12-F
Pre-insulated cord end terminals 10mm² - bag of 1000
E16-12-G
E16-12-F
Pre-insulated cord end terminals 16mm² - bag of 500
TE0508-G
TE0508-F
Pre-insulated dual cord end terminals 0.5mm² - bag of 1000
TE7508-G
TE7508-F
Pre-insulated dual cord end terminals 0.75mm² - bag of 1000
TE1008-G
TE1008-F
Pre-insulated dual cord end terminals 1.0mm² - bag of 1000
TE1508-G
TE1508-F
Pre-insulated dual cord end terminals 1.5mm² - bag of 1000
TE2510-G
TE2510-F
Pre-insulated dual cord end terminals 2.5mm² - bag of 1000
Spiral Wrapping CAB
Black
White
Description
CAB-06/B
CAB-06/W
Spiral wrapping band 4-50mm - 10 metres
CAB-12/B
CAB-12/W
Spiral wrapping band 9-65mm - 10 metres
CAB-19/B
CAB-19/W
Spiral wrapping band 15-100mm - 10 metres
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
123
E.C.Products
Building Management Controls & Peripherals
Wiring accessories
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
124
Cable Ties & Bases
Description
A range of self-locking nylon cable ties and stainless steel cable
ties in a choice of lengths.
Part Code
Description
CAS-2.5X100
Black nylon cable tie 2.5mm x 100mm - pack of 100
CAS-3.5X150
Black nylon cable tie 3.5mm x 150mm - pack of 100
CAS-3.5X200
Black nylon cable tie 3.5mm x 200mm - pack of 100
CAS-4.6X250
Black nylon cable tie 4.6mm x 250mm - pack of 100
CAS-4.6X300
Black nylon cable tie 4.6mm x 300mm - pack of 100
CAS-4.6X350
Black nylon cable tie 4.6mm x 350mm - pack of 100
CAS-4.6X400
Black nylon cable tie 4.6mm x 400mm - pack of 100
CAS-9X550
Black nylon cable tie 9.0mm x 550mm - pack of 100
CAS-12X650
Black nylon cable tie 12mm x 650mm - pack of 100
BZ-C4.6X200
Stainless steel cable tie 4.6mm x 200mm - pack of 100
BZ-C4.6X360
Stainless steel cable tie 4.6mm x 360mm - pack of 100
CS-20
Self-adhesive cable tie mounts 20mm x 20mm - pack of 100
CS-30
Self-adhesive cable tie mounts 30mm x 30mm - pack of 100
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
Cable CAB
Description
Technical Specification
Panel cable and four core cable, supplied on 100m reels
Conductors:
Plain annealed flexible copper.
Sheath:
PVC, heat resistant.
Colours:
Black, blue, brown, green/yellow, grey,
orange, pink, red, violet, white, & yellow
Voltage:600/1000V
Temperature:
Maximum 105°C, minimum Bending 0°C
Part Code
Description
Part Code
Description
CAB-R-050
Tri-Rated Cable 0.5mm² Red
CAB-R-100
Tri-Rated Cable 1mm² Red
CAB-BLK-050
Tri-Rated Cable 0.5mm² Black
CAB-BLK-100
Tri-Rated Cable 1mm² Black
CAB-GY-050
Tri-Rated Cable 0.5mm² Green/yellow
CAB-GY-100
Tri-Rated Cable 1mm² Green/yellow
CAB-BL-050
Tri-Rated Cable 0.5mm² Blue
CAB-BL-100
Tri-Rated Cable 1mm² Blue
CAB-Y-050
Tri-Rated Cable 0.5mm² Yellow
CAB-Y-100
Tri-Rated Cable 1mm² Yellow
CAB-BR-050
Tri-Rated Cable 0.5mm² Brown
CAB-BR-100
Tri-Rated Cable 1mm² Brown
CAB-V-050
Tri-Rated Cable 0.5mm² Violet
CAB-V-100
Tri-Rated Cable 1mm² Violet
CAB-P-050
Tri-Rated Cable 0.5mm² Pink
CAB-P-100
Tri-Rated Cable 1mm² Pink
CAB-W-050
Tri-Rated Cable 0.5mm² White
CAB-W-100
Tri-Rated Cable 1mm² White
CAB-O-050
Tri-Rated Cable 0.5mm² Orange
CAB-O-100
Tri-Rated Cable 1mm² Orange
CAB-G-050
Tri-Rated Cable 0.5mm² Grey
CAB-G-100
Tri-Rated Cable 1mm² Grey
CAB-GR-050
Tri-Rated Cable 0.5mm² Green
CAB-GR-100
Tri-Rated Cable 1mm² Green
CAB-R-0-75
Tri-Rated Cable 0.75mm² Red
CAB-R-150
Tri-Rated Cable 1.5mm² Red
CAB-BLK-0-75
Tri-Rated Cable 0.75mm² Black
CAB-BLK-150
Tri-Rated Cable 1.5mm² Black
CAB-GY-0-75
Tri-Rated Cable 0.75mm² Green/yellow
CAB-GY-150
Tri-Rated Cable 1.5mm² Green/yellow
CAB-BL-0-75
Tri-Rated Cable 0.75mm² Blue
CAB-BL-150
Tri-Rated Cable 1.5mm² Blue
CAB-Y-0-75
Tri-Rated Cable 0.75mm² Yellow
CAB-Y-150
Tri-Rated Cable 1.5mm² Yellow
CAB-BR-0-75
Tri-Rated Cable 0.75mm² Brown
CAB-BR-150
Tri-Rated Cable 1.5mm² Brown
CAB-V-0-75
Tri-Rated Cable 0.75mm² Violet
CAB-V-150
Tri-Rated Cable 1.5mm² Violet
CAB-P-0-75
Tri-Rated Cable 0.75mm² Pink
CAB-P-150
Tri-Rated Cable 1.5mm² Pink
CAB-W-0-75
Tri-Rated Cable 0.75mm² White
CAB-W-150
Tri-Rated Cable 1.5mm² White
CAB-O-0-75
Tri-Rated Cable 0.75mm² Orange
CAB-O-150
Tri-Rated Cable 1.5mm² Orange
CAB-G-0-75
Tri-Rated Cable 0.75mm² Grey
CAB-G-150
Tri-Rated Cable 1.5mm² Grey
CAB-GR-0-75
Tri-Rated Cable 0.75mm² Green
CAB-GR-150
Tri-Rated Cable 1.5mm² Green
CAB-0000400
4 Core Belden 8723 100m roll
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
Cable
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
125
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Information
Terms and Conditions
Deliveries
Customers placing orders are taken as having accepted EC
Products Limited terms and conditions in full.
Many items are available for immediate delivery from our
comprehensive stock. However, where delivery is deemed
critical, please consult us to avoid disappointment.
Setting up an account
In order that ECP Limited offer competitive pricing, packing and
delivery is charged separately on all orders.
Should any company require purchasing product using a
credit account, then they should complete and return a Credit
Application form.
The following shows standard charges for parcels up to 30Kg
(heavier parcels are priced individually):
Any company wishing to purchase without a credit account will
be invoiced on a proforma basis and goods dispatched upon
clearance of payment into our bank account.
Placing orders
The following information is required when placing an order:
•Order number
•Invoice address
•Delivery address (if different from invoice address)
•Required delivery date (you will be advised if this cannot
be met)
•Customer contact
•Full description of items required or
ECP Limited Part Numbers
Orders can be placed by phone, fax, mail or email. Verbal
orders should be confirmed in writing.
All prices shown in our catalogues are list prices. Credit
account customers may be given a discount, which would apply
to all products in the catalogue. This discount will only apply
in the event of a customer not having negotiated any special
prices. Discount will be determined at the discretion of ECP
Limited, on the basis of actual turnover expected.
Progressing an order
To progress an order please contact our office and provide
your company name, original date of order and your order
number. If your order has been dispatched but not received
then a proof of delivery can be provided.
Republic of Ireland £28.50 up to 30Kg per parcel.
Overseas deliveries will be charged at the prevailing rate.
Shipment will be carried out via Interlink Express.
If required, a customer collection can be requested, either in
person or by an independent carrier. Our trade counter is open
From 8.30am to 5.30pm
Specials
Pricing, discounts and payment
Unless agreed in writing with ECP Limited all credit terms are
net monthly – defined as payable on or before the last day of
the month following the month of invoice.
•UK next day before 5.30pm £8.50 Up to 20Kg additional
£0.50 per Kg up to 30Kg Max
•UK next day before 12 noon £14.50 up to 10Kg additional
£0.50 per Kg up to 30Kg Max
•UK next day before 10.00am add £18.50 up to 10Kg
additional £0.50 per Kg up to 30Kg Max
•UK Saturday before 12 noon £25.00 up to 10Kg additional
£0.80 per Kg up to 30Kg Max
•Northern Ireland £20.00 up to 10Kg additional £1.00 per
Kg up to 30Kg Max
ECP Limited is always willing to discuss any special
requirements for products you may have and many of the
products in this catalogue are available with custom labelling
and company logos. Please contact our office for full details.
Returns
Any goods being returned to ECP must be accompanied by
a goods return note and shall be inspected upon arrival to
determine their condition. Please state in as much detail as
possible the reason for the return. No credit will be issues
without this information.
ECP Limited will credit or replace, at the discretion of the
customer, any returned items which are deemed to have failed
due to no fault of the customer. When requesting replacements,
it is necessary to raise a new and separate purchase order.
Credits will then be issued against the original order.
Products which are deemed as ‘special products’ will not be
accepted for return other than in the case of failure due to no
fault of the customer.
Goods returned for restocking and in good condition will only
be accepted upon payment of a 15% restocking charge, which
must be paid by the customer.
Goods returned which have been damaged by the customer
will be credited at the discretion of ECP Limited.
126
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Terms & conditions
1. Buyer as used herein means the person ordering goods or
services from E C Products Limited (ECP).
2. Any of the terms and provisions of the Buyer’s order which
are inconsistent with ECP conditions or which are not
expressly contained within our documentation as relating
to a particular supply or service shall not be binding upon
ECP and shall not be considered applicable to that sale.
3. All offers are for supply only and we shall not be governed
by any sub-contract conditions that apply to the Buyer.
4. No waiver, alteration or modification of any of the
provisions on our quotation, shall be binding unless made
in writing and signed by a Director of ECP.
5. Prices quoted are for the quantity mentioned and any
increase or reduction may affect price.
6. If after the date of quotation or contract and before
completion of work or delivery of goods there shall be an
increase in the cost of work or our normal selling price
of the goods, then a corresponding increase shall be
chargeable and payable by the Buyer.
7. All prices quoted are exclusive of V.A.T.
8. Credit terms are Nett Monthly Account: - defined as
payable on or before the last day of the month following
that of the date of the invoice.
9. Should no credit agreements or terms exist, between ECP
and the buyer, payment shall be on a Pro-Forma basis.
10.ECP reserve the right to suspend supply or service of
equipment and any other trading benefits for noncompliance of our terms.
11. The property in all goods supplied by ECP shall remain
vested in ECP until the full price of the goods has been paid
to ECP. The Buyer shall be responsible for cover against
all risks of loss, damage or destruction of such goods until
payment is made to ECP.
12.Delivery dates are approximate and ECP shall not be
liable for any loss,penalties or damage, direct or indirect,
occasioned by delayed delivery and in no case shall
delayed delivery be a ground for rejecting goods.
13.No goods may be returned for credit without prior
agreement from ECP in writing. Current stock items returned
in resaleable condition will be accepted subject to a restocking fee of 15%.
14.Cancellation of orders that have to be made up specially
or specifically to the Buyer’s requirements cannot be
accepted.
15.All warranties in respect of goods not of our manufacture,
the Manufacturer or Distributor warranties will apply.
16.ECP cannot be held responsible for any errors or omissions
in drawings after they have been approved by the Buyer.
17. The Buyer shall hold ECP harmless against any loss,
damage, or expense resulting from infringement of patents
or trade marks arising from compliance by ECP with the
Buyer’s design, specification or instruction.
18.All contracts for sale of goods and service will be
interpreted in accordance with English Law and any
dispute shall be submitted to arbitration under the Laws of
England.
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
127
E.C.Products
Building Management Controls & Peripherals
Suppliers
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
128
T: +44 (0)20 8569 4100
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
E.C.Products
Building Management Controls & Peripherals
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
J15
/J4b
M4
J5
J4
M4
J3
J2
BRENTFORD
COLNBROOK
A4
A315
A30
A316
HOUNSLOW
M25
RICHMOND
A315
J13
A4
A4
J14
LONDON HEATHROW
AIRPORT
J1
Information
Please go to www.ecproducts.co.uk to download the lastest
data sheets and also for the lastest offers and product releases
A30
A30
A244
STAINES
A316
A316
FELTHAM
TWICKENHAM
CKENHAM
A
TWICKENHA
TWICKENHAM
K NHA
A316
A308
SUNBURY
J1
KINGSTON
NG TON
T
KINGSTON
UPO
UPON
PO
ON
N THAMES
T HAM
HA
A
A308
GR
E
EN
NE
LA
J13
/J2
A309
A315
Y WAY
AMBERLE
D
SR
GG
FA
M3
ST
E
AI N
D
SR
A315
D
HOUNSLOW
HEATH
RD
W
HO
N
TO
NG
RLI
E. C. Products Limited
U NS LOW
RD
R
INES
HA
STA
Distributors for Central and Eastern Europe
JSC RATECHNA
Gerosios Vilties 20-18A
Vilnius, LT-03145
Lithuania
Tel: +370 655 76 555
sales@ratechna.lt
www.ratechna.lt
Distributors for Russia, Belorussia, Ukraine
JSC SATORIS
Vasilevsky Ostrov
8-ya Liniya, 77,B
RU 199178 St.Petersburg
Russia
EC House
Amberley Way
Hounslow
Middlesex, TW4 6BH
Tel: +44 (0)20 8569 4100
T: +44 (0)20 8569 4100
Tel: +7 812 640 9801
info@satoris.ru
www.satoris.ru
F: +44 (0)20 8569 4111
E: sales@ecproducts.co.uk
W: www.ecproducts.co.uk
129
E. C. Products Limited, EC House,
Amberley Way, Hounslow, Middlesex, TW4 6BH
Phone: 020 8569 4100
Fax: 020 8569 4111
Email: sales@ecproducts.co.uk
www.ecproducts.co.uk
Download