Pump Controller Type ABS PC 441 81307126O COMLI/Modbus - Version 1.50 EN Reference Manual 1 Comli/Modbus IO number layout 1.1 Digital outputs Main Controller PC 441 DO1 0 DO2 1 DO3 2 DO4 3 DO5 4 DO6 5 DO7 6 DO8 7 DO3 10 DO4 11 DO5 12 DO6 13 DO7 14 DO8 15 Exp. Module CA 781 DO1 8 DO2 9 “P1-P4 Control”, “Reset M.Prot.” ,“Remote Control” , “Mixer” ,”Cleaner” and “Drain pump” allows remote write. 1.2 Pump status (P1-P4) IO-Bit P1 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 IO-Bit P2 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 IO-Bit P3 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 IO-Bit P4 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 Function Note Pump relay Pump run indication Pump blocked Pump alarm blocked Pump fail Fallen motor protector Fallen temperature protector DI Leakage Pump blocked Field Bus Error Leakage 1(oil chamber) Leakage 2 (connect chamber) Leakage 3 (motor housing) High temp 1 (stator wiring) High temp 2 (upper bearing) High temp 3 (lower bearing) High vibrations Wrong phase order Phase missing Dry run Pump Reversing Cycle Run** Pump Reversing Relay High Tariff pump down Alt. Stop Cycle Run Pump Exercise Run Remote control possible Run confirm DI not in auto Alarm ackn. required DI Pump fail Remote reset possible DI Temperature protector DI Leakage Communication Failure (CAN) CA 441 CA 441 CA 441 CA 442 CA 442 CA 442 CA 442 CA 443 CA 443 CA 443 Remote control possible 40 41 42 43 44 45 46 47 72 73 74 75 76 77 78 79 104 105 106 107 108 109 110 111 136 137 138 139 140 141 142 143 Start float On Stop float On Hand flag Start flag Stop flag Set point Max runtime reached Optimal SW pump run Same for P1-P4 Forced pump run Manual start Manual stop Tariff Control, Backup Run etc. Type 1.3 DI1 160 DI2 161 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DI10 DI11 DI12 DI13 DI14 DI15 DI16 162 163 164 165 166 167 168 169 170 171 172 173 174 175 1.4 IO-Bit Digital inputs Pump pit status Function Note 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 Remote block Pressure block Low level float High level Low level High level float Drain pump float Mixer pump block High inflow Low inflow Backup start High pressure Low pressure Overflow Spare=0 Sensor Error Mixer Relay Mixer run indicator Fallen motor protector mixer Drain pump relay Drain pump run indicator Fallen motor prot. drain pump Cleaner relay Mixer M.prot reset error Drain Pump M.prot reset error Wrong phase order block Incoming phase missing block Over voltage block Under voltage block Unbalanced voltages block High freq. block Low freq. block Write resets timout timer. 0=Deblock, 1=Block 224 225 226 227 Mixer blocked Drain Pump blocked Hi tariff CA 622 Main master running Ext. Blocked from digital input Ext. Blocked from digital input Hi tariff active Modbus main power monotior Analogue sensor Remote control possible DI motor protector / Remote reset possible Remote control possible DI motor protector / Remote reset possible Remote control possible From power monitor CA443 “ “ “ “ “ “ IO-Bit 248 249-253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 Function Spare Spare CA 622 Connected CA 511 Connected CA 441-1 Connected CA 441-2 Connected CA 441-3 Connected CA 441-4 Connected CA 442-1 Connected CA 442-2 Connected CA 442-3 Connected CA 442-4 Connected CA 443-0 Connected CA 443-1 Connected CA 443-2 Connected CA 443-3 Connected CA 443-4 Connected CA 442-5 Connected CA 442-6 Connected CA 781 Connected Note 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 CA 441-1 DI 1 (P1) CA 441-1 DI 2 (P1 or P2) CA 441-1 DI 3 (P1 or P3) CA 441-1 DI 4 (P1 or not used) CA 441-1 DI 1 Open circuit failure CA 441-1 DI 2 Open circuit failure CA 441-1 DI 3 Open circuit failure CA 441-1 DI 4 Open circuit failure CA 441-2 DI 1 (P2) CA 441-2 DI 2 (P2) CA 441-2 DI 3 (P2) CA 441-2 DI 4 (Not used) CA 441-2 DI 1 Open circuit failure CA 441-2 DI 2 Open circuit failure CA 441-2 DI 3 Open circuit failure CA 441-2 DI 4 Open circuit failure Leakage monitor 1 P1 or P1-P4 1= Leakage Modbus Master RS485 Display Unit Leakage monitor 1 = Connected to field bus Temperature monitor Master power monitor Exp. Temp monitor P1 and P2 Exp. Temp monitor P3 and P4 Exp. AO/DO module 1 = Open circuit failure Leakage monitor P2 1= Leakage 1= Open circuit failure IO-Bit 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313-319 320 321 322 323 324 325 326 327 328 329-335 336 337 338 339 340 341 342 343 344 345-351 352 353 354 355 356 357 358 359 360 361-367 Function CA 441-3 DI 1 (P3) CA 441-3 DI 2 (P3) CA 441-3 DI 3 (P3) CA 441-3 DI 4 (Not used) CA 441-3 DI 1 Open circuit failure CA 441-3 DI 2 Open circuit failure CA 441-3 DI 3 Open circuit failure CA 441-3 DI 4 Open circuit failure CA 441-4 DI 1 (P4) CA 441-4 DI 2 (P4) CA 441-4 DI 3 (P4) CA 441-4 DI 4 (Not used) CA 441-4 DI 1 Open circuit failure CA 441-4 DI 2 Open circuit failure CA 441-4 DI 3 Open circuit failure CA 441-4 DI 4 Open circuit failure CA 442-1 T1 High temp 1(P1) CA 442-1 T2 High temp 2(P1 or P2) CA-442-1 T3 High temp 3(P1 or P3) CA442-1 T4 High Temp (P1 or P4) CA-422-1 High Vibration (P1) CA-442-1 T1 Cable Error CA-442-1 T2 Cable Error CA-442-1 T3 Cable Error CA-442-1 T4 Cable Error Spare = 0 CA 442-2 T1 High temp 1 (P2) CA 442-2 T2 High temp 2 (P2) CA-442-2 T3 High temp 3 (P2) CA-442-2 T4 High temp 4 (P2) CA-422-2 High Vibration (P2) CA-442-2 T1 Cable Error CA-442-2 T2 Cable Error CA-442-2 T3 Cable Error CA-442-2 T4 Cable Error Spare=0 CA 442-3 T1 High temp 1 (P3) CA 442-3 T2 High temp 2 (P3) CA-442-3 T3 High temp 3 (P3) CA-442-3 T4 High temp 4 (P3) CA-422-3 High Vibration (P3) CA-442-3 T1 Cable Error CA-442-3 T2 Cable Error CA-442-3 T3 Cable Error CA-442-3 T4 Cable Error Spare=0 CA 442-4 T1 High temp 1 (P4) CA 442-4 T2 High temp 2 (P4) CA-442-4 T3 High temp 3 (P4) CA-422-4 T4 High temp 4 (P4) CA-422-4 High Vibration (P4) CA-442-4 T1 Cable Error CA-442-4 T2 Cable Error CA-442-4 T3 Cable Error CA-442-4 T4 Cable Error Spare=0 Note Leakage monitor P3 1= Leakage 1= Open circuit failure Leakage monitor P4 1= Leakage 1= Open circuit failure Temperature monitor 1 P1 or P1-P4 1 = High Temperature 1 = High vibration P1 1=Open circuit or short circuit Temperature monitor 2 P2 1 = High Temperature 1 = High vibration P2 1=Open circuit or short circuit Temperature monitor 3 P3 1 = High Temperature 1 = High vibration P3 1=Open circuit or short circuit Temperature monitor 4 P4 1 = High Temperature 1 = High vibration P4 1=Open circuit or short circuit IO-Bit 368 369 370 371 372 373 374 375 376 377-383 384 385 386 387 388 389 390 391 392 393-399 Function CA442-5 T1 High temp stator L2 (P1) CA442-5 T2 High temp stator L3 (P1) CA442-5 T3 High temp stator L2 (P2) CA442-5 T4 High temp stator L3 (P2) CA442-5 Not Used CA442-5 T1 Cable Error CA442-5 T2 Cable Error CA442-5 T3 Cable Error CA442-5 T4 Cable Error Spare = 0 CA442-6 T1 High temp stator L2 (P3) CA442-6 T2 High temp stator L3 (P3) CA442-6 T3 High temp stator L2 (P4) CA442-6 T4 High temp stator L3 (P4) CA442-6 Not used CA442-6 T1 Cable Error CA442-6 T2 Cable Error CA442-6 T3 Cable Error CA442-6 T4 Cable Error Spare = 0 Note Temp monitor 5 P1/P2 Temp monitor 6 P3/P4 1.5 Comp. Pump Status (P1-P4) Firmware PC 441 Ver. 1.04 or higher. IO-Bit P1 400 401 402 403 404 405 406 407 IO-Bit P2 408 409 410 411 412 413 414 415 IO-Bit P3 416 417 418 419 420 421 422 423 IO-Bit P4 424 425 426 427 428 429 430 431 Function Note Pump Blocked Pump Error Blocked Pump External Blocked Leakage High Temperature* Spare = 0 ITT MinCas Leakage ITT MiniCas High Temp. Extern. or Internal Pump Internal Failure External Reason to Block Comb. of all Leakage. Sensors Comb. of all Temp. Sensors Simulate ITT MiniCas “ “ * Remote reset possible (if required) Firmware PC 441 Ver 1.30 or higher IO-Bit P1 432 433 434 435 436 437 439 439 IO-Bit P2 440 441 442 443 444 445 446 447 IO-Bit P3 448 449 450 451 452 453 454 455 IO-Bit P4 456 457 458 459 460 461 462 463 Function Note High Temperature stator T1(L1) High Temperature stator T4(L1) Internal flag Internal flag Internal flag High Temp latched (man reset) Internal flag Spare = 0 CA442 CA442 IO-Bit P1 464 465 466 467 468 469 470 471 IO-Bit P2 472 473 474 475 476 477 478 479 IO-Bit P3 480 481 482 483 484 485 486 487 IO-Bit P4 488 489 490 491 492 493 494 495 Function Note High Temperature stator L2 High Temperature stator L3 CA 622 master running Drive NOT enabled Drive fault CA 622 master running Spare = 0 Spare=0 CA442-5 and CA442-6 CA442-5 and CA442-6 Modbus pump VFD OK 0=OK to start Drive error Modbus pump power monitor OK 1.6 IO-Bit 496 497 504 505 511 IO-Bit 992 993 994 995 996 Comp. alarm status Function Not ackn, B-Alarm Not ackn. A-Alarm Active B-Alarm Active A-Alarm Ackn, Alarm Call 1.7 Require manual reset Note Same as ackn. to R333, 0=PC 442 discon/ 1=System discon System info Function Ackn. Personal alarm Spare = 0 Local mode Modem error Line error Note 1.8 Alarm status IO-Bit Octal Hex Alarm 0 = IO 1024 and so on 1024-1275 2000-2373 400-4FB Alarm status indicate 1 if alarm is active 0 when alarm is off, independent of alarm type (A/B) Alarm numbers, which are set “Inactive”, always show 0. Alarm no. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 IO-Bit 1024 1025 1026 1027 1028 1029 1030 1031 1032 1033 1034 1035 1036 1037 1038 1039 1040 1041 1042 1043 1044 1045 1046 1047 1048 1049 1050 1051 1052 1053 1054 1055 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 1056 1057 1058 1059 1060 1061 1062 1063 1064 1065 1066 1067 1068 1069 1070 1071 1072 1073 1074 1075 1076 1077 1078 Description Unused Power fail Low supply voltage NV checksum error Personal alarm High level pump pit Low level pump pit High level float Low level float High inflow Low inflow Backup start Remote blocked High pressure Low pressure Overflow Back-Pressure block Drain pump float Sensor error No run confirm mixer Fallen Motor Protector Mixer No run confirm drain pump Fallen Motor Protector Drain pump To many pumps blocked Motor protector Drain pump/Mixer reset error Gen. alarm wrong phase order Gen. alarm incoming phase missing Gen. alarm over voltage Gen. alarm under voltage Gen. alarm unbalanced phase voltages Gen. alarm high frequency Gen, alarm low frequency Pump 1 P1 : No run confirm P1 : Fallen motor protector P1 : High motor current P1 : Low motor current P1 : D.IN Leakage P1 : D.IN High temperature P1 : Low pump capacity P1 : D.IN Pump Error P1 : Phase missing P1 : Motor protector reset unsuccessful P1 : Max continuous runtime P1 : Alarm blocked P1 : Dry run (low Cos φ ) P1 : Not in auto P1 : Motor drive - CA 622 com error (Modbus timeout) P1 : Drive fault (tripped VFD or soft starter) P1 : Leakage 1 (Oil chamber) CA 441 Field Bus (CAN) P1 : Leakage 2 (Connect chamber) “ P1 : Leakage 3 (Motor housing ) “ P1 : Power monitor - CA 622 com error (Modbus timeout) P1 : High temperature 1 (Stator wiring) CA 442 Field Bus (CAN) P1 : High temperature 2 (Upper bearing) “ P1 : High temperature 3 (Lower bearing) “ Alarm no. 55 56 57 58 59 60 61 62 63 IO-Bit 1079 1080 1081 1082 1083 1084 1085 1086 1087 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 1088 1089 1090 1091 1092 1093 1094 1095 1096 1097 1098 1099 1100 1101 1102 1103 1104 1105 1106 1107 1108 1109 1110 1111 1112 1113 1114 1115 1116 1117 1118 1119 96 97 98 99 100 101 102 103 104 105 106 107 108 109 Alarm no. 110 111 112 113 114 1120 1121 1122 1123 1124 1125 1126 1127 1128 1129 1130 1131 1132 1133 IO-Bit 1134 1135 1136 1137 1138 Description P1 : High vibrations CA 442 Field Bus (CAN) P1 : Wrong phase order CA 443 Field Bus (CAN) P1 : High temperature stator L2 CA442-5 T1 (CAN) P1 : High temperature stator L3 CA442-5 T2 (CAN P1 : CA 442-5 T1 Cable error P1 : CA 442-5 T2 Cable error P1 : Unused P1 : Unused P1 : Unused Pump 2 P2 : No run confirm P2 : Fallen motor protector P2 : High motor current P2 : Low motor current P2 : D.IN Leakage P2 : D.IN High Temperature P2 : Low pump capacity P2 : D.IN Pump Error P2 : Phase Missing P2 : Motor protector reset error P2 : Max continuous runtime P2 : Alarm blocked P2 : Dry run P2 : Not in auto P2 : Motor drive - CA 622 com error (Modbus timeout) P2 : Drive fault (tripped VFD or soft starter) P2 : Leakage 1 (Oil chamber) CA 441 Field Bus (CAN) P2 : Leakage 2 (Connect chamber) “ P2 : Leakage 3 (Motor housing) “ P2 : Power monitor - CA 622 com error (Modbus timeout) P2 : High temperature 1 (Stator) CA 442 Field Bus (CAN) P2 : High temperature 2 (Upper bearing) “ P2 : High temperature 3 (Lower bearing) “ P2 : High Vibrations “ P2 : Wrong phase order CA 443 Field Bus (CAN) P2 : High temperature stator L2 CA442-5 T3 (CAN) P2 : High temperature stator L3 CA442-5 T4 (CAN) P2 : CA 442-5 T3 Cable error P2 : CA 442-5 T4 Cable error P2 : Unused P2 : Unused P2: Unused Pump 3 P3 : No run confirm P3 : Fallen motor protector P3 : High motor current P3 : Low motor current P3 : D.IN Leakage P3 : D.IN High temperature P3 : Low pump capacity P3 : D.IN Pump Error P3 : Phase missing P3 : Motor protector reset error P3 : Max Continuous run time P3 : Alarm blocked P3 : Dry run P3 : Not in auto Description P3 : Motor drive - CA 622 com error (Modbus timeout) P3 : Drive fault (tripped VFD or soft starter) P3 : Leakage 1 CA 441 Field Bus (CAN) P3 : Leakage 2 “ P3 : Leakage 3 “ 115 116 117 118 119 120 121 122 123 124 125 126 127 1139 1140 1141 1142 1143 1144 1145 1146 1147 1148 1149 1150 1151 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 1152 1153 1154 1155 1156 1157 1158 1159 1160 1161 1162 1163 1164 1165 1166 1167 1168 1169 1170 1171 1172 1173 1174 1175 1176 1177 1178 1179 1180 1181 1182 1183 160 161 162 163 164 Alarm no. 165 166 167 1184 1185 1186 1187 1188 IO-Bit 1189 1190 1191 168 169 170 171 172 173 174 1192 1193 1194 1195 1196 1197 1198 P3 : Power monitor - CA 622 com error (Modbus timeout) P3 : High temperature 1 CA 442 Field Bus (CAN) P3 : High temperature 2 “ P3 : High temperature 3 “ P3 : High vibrations “ P3 : Wrong phase order CA 443 Field Bus (CAN) P3 : High temperature stator L2 CA442-6 T1 (CAN) P3 : High temperature stator L3 CA442-6 T2 (CAN) P3 : CA 442-6 T1 Cable error P3 : CA 442-6 T2 Cable error P3 : Unused P3 : Unused P3 : Unused Pump 4 P4 : No run confirm P4 : Fallen motor protector P4 : High motor current P4 : Low motor current P4 : D.IN Leakage P4 : D.IN high temperature P4 : Low pump capacity P4 : D.IN Pump Error P4 : Phase missing P4 : Motor protector reset error P4 : Max continuous runtime P4 : Alarm blocked P4 : Dry run P4 : Not in auto P4 : Motor drive - CA 622 com error (Modbus timeout) P4 : Drive fault (tripped VFD or soft starter) P4 : Leakage 1 CA 441 Field Bus (CAN) P4 : Leakage 2 “ P4 : Leakage 3 “ P4 : Power monitor - CA 622 com error (Modbus timeout) P4 : High temperature 1 CA 442 Field Bus (CAN) P4 : High temperature 2 “ P4 : High temperature 3 “ P4 : High vibration “ P4 : Wrong phase order CA 443 Field Bus (CAN) P4 : High temperature stator L2 CA442-6 T3 (CAN) P4 : High temperature stator L3 CA442-6 T4 (CAN) P4 : CA 442-6 T3 Cable error P4 : CA 442-6 T4 Cable error P4 : Unused P4 : Unused P4: Unused AI User High alarm free choice AI2 Low alarm free choice AI2 High alarm free choice AI3 Low alarm free choice AI3 High alarm free choice AI4 Description Low alarm free choice AI4 High alarm free choice AI5 Low alarm free choice AI5 Pulse channels High precipitation pulse channel 1 High effect pulse channel 1 High flow pulse channel 1 Low flow pulse channel 1 High precipitation pulse channel 2 High effect pulse channel 2 High flow pulse channel 2 175 176 177 178 179 180 181 182 183 1199 1200 1201 1202 1203 1204 1205 1206 1207 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 1208 1209 1210 1211 1212 1213 1214 1215 1216 1217 1218 1219 1220 1221 1222 1223 1224 1225 1226 1227 1228 1229 1230 1231 1232 1233 1234 1235 1236 1237 1238 1239 Low flow pulse channel 2 High precipitation pulse channel 3 High effect pulse channel 3 High flow pulse channel 3 Low flow pulse channel 3 High precipitation pulse channel 4 High effect pulse channel 4 High flow pulse channel 4 Low flow pulse channel 4 Communication failures/ Cable errors CA 441-1 CAN Communication failure CA 441-2 CAN Communication failure CA 441-3 CAN Communication failure CA 441-4 CAN Communication failure CA 442-1 CAN Communication failure CA 442-2 CAN Communication failure CA 442-3 CAN Communication failure CA 442-4 CAN Communication failure CA 443-0 CAN Communication failure CA 443-1 CAN Communication failure CA 443-2 CAN Communication failure CA 443-3 CAN Communication failure CA 443-4 CAN Communication failure Modem error Line Error Comb. Field bus error alarm CA 441-1 IN 1 Cable/sensor error . Open circuit CA 441-1 IN 2 Cable/sensor error CA 441-1 IN 3 Cable/sensor error CA 441-1 IN 4 Cable/sensor error CA 441-2 IN 1 Cable/sensor error CA 441-2 IN 2 Cable/sensor error CA 441-2 IN 3 Cable/sensor error CA 441-2 IN 4 Cable/sensor error CA 441-3 IN 1 Cable/sensor error CA 441-3 IN 2 Cable/sensor error CA 441-3 IN 3 Cable/sensor error CA 441-3 IN 4 Cable/sensor error CA 441-4 IN 1 Cable/sensor error CA 441-4 IN 2 Cable/sensor error CA 441-4 IN 3 Cable/sensor error CA 441-4 IN 4 Cable /sensor error Field Bus “ “ “ “ “ “ “ “ “ “ “ “ Alarm no. 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 IO-Bit 1240 1241 1242 1243 1244 1245 1246 1247 1248 1249 1250 1251 1252 1253 1254 1255 1256 1257 1258 1259 1260 1261 1262 1263 1264 1265 1266 1267 1268 1269 1270 1271 1272 1273 1274 1275 1276 Description CA 442-1 IN 1 Cable error. Open circuit or short circuit CA 442-1 IN 2 Cable error CA 442-1 IN 3 Cable error CA 442-1 IN 4 Cable error CA 442-2 IN 1 Cable error CA 442-2 IN 2 Cable error CA 442-2 IN 3 Cable error CA 442-2 IN 4 Cable error CA 442-3 IN 1 Cable error CA 442-3 IN 2 Cable error CA 442-3 IN 3 Cable error CA 442-3 IN 4 Cable error CA 442-4 IN 1 Cable error CA 442-4 IN 2 Cable error CA 442-4 IN 3 Cable error CA 442-4 IN 4 Cable error Alarm digital input 1 Type = Alarm Input Alarm digital input 2 Alarm digital input 3 Alarm digital input 4 Alarm digital input 5 Alarm digital input 6 Alarm digital input 7 Alarm digital input 8 Alarm digital input 9 Alarm digital input 10 Alarm digital input 11 Alarm digital input 12 Alarm digital input 13 Alarm digital input 14 Alarm digital input 15 Alarm digital input 16 CA 442-5 CAN Communication failure. Extra Temp. Monitor P1 and P2 CA 442-6 CAN Communication failure. Extra Temp. Monitor P3 and P4 CA 781 CAN Communication failure AO/DO Exp. Module CA 622 CAN Communication failure Modbus Master -> VFD Main Power monitor - CA 622 com error (Modbus timeout) 1.9 Alarm 0 = IO 1280 and so on Latched alarm status IO-Bit 1280-1531 Octal 2400-2773 Hex 500-5FB Latched alarm status is set to 1 when alarm goes active and are updated after Comli/Modbus readout with actual alarm status. This is made to not lose alarms, witch have gone inactive before the call is ready. 1.10 Acknowledged alarms Alarm 0 = IO 1536 and so on IO-Bit 1536-1787 Octal 3000-3373 Hex 600-6FB Status for ackn. alarm are set to 0 each time a new alarm occurs and gives the possibility for a central system to ackn. each alarm individually. The ackn,. works the same way as local ackn. on PC 441 and is made by writing a 1 to actual alarm bit. This ackn. is time stamped in the local alarm list. Even local ackn. in substation ackn, actual IO-bits. You can also ackn. all alarm by write to R333 ( if you have select that function ). For system that can handle the Comli/Modbus telegram for time stamped events, we recommend to use that method for readout of new alarms. 1.11 Pending alarms Alarm 0 = IO 1792 and so on IO-Bit 1792-2043 Octal 3400-3773 Hex 700-7FB Pending alarms bits maybe active even if alarm is set inactive. 1.12 Configurations bits Pit flags 1 : Same as bit mapped register R2010. IO-Bit 2048 2049 2050 2051 2052 2053 2054 2055 2056 2057 2058 2059 2060 2061 2062 2063 Function Remote pump block Back pressure pump block Low level float pump block Start Level Tracking Sensor type connected Alternate Runtime alternation Start pump on level change Stop pump on level change Alternative stop level Inflow calculation Calc. pump capacity Backup run P1 Backup run P2 Backup run P3 Backup run P4 Note 0=Off / 1=On 0=Off / 1=On 0=Off / 1=On 0=Off/ 1=On 0=Analogue sensor/ 1= Start/stop floats 0=Every pump stop / 1=Last pump stop 0=Off / 1=On 0=Off / 1=On 0=Off / 1=On 0=Off / 1=On 0=Off / 1=On 0=Off / 1=On 0=Off / 1= On 0=Off / 1= On 0=Off/ 1=On 0=Off/ 1=On Pit flags 2 : Same as bit mapped register R2011. 2064 2065 2066 2067 2068 2069 2070 2071 2072 2073 2074 2075 2076 2077 2078 2079 Pit shape Emptying/Filling pit Tariff control High float check of level sensor Low float check of level sensor Level change check of level sensor P1 in primary pump group P2 in primary pump group P3 in primary pump group P4 in primary pump group Station Application Over voltage block Under voltage block Unbalanced voltages block High freq. block Low freq. block 0=Rectangular / 1=Conical 0=Emptying / 1=Filling 0=Off / 1= On 0=Off / 1= On 0=Off / 1= On 0=Off / 1= On 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=Pump Controller / 1= Pump monitor (v1.14) 0=Off / 1=On Power monitor CA 443-0 0=Off / 1=On 0=Off / 1=On 0=Off / 1=On 0=Off / 1=On Pump 1-4 flags 1 : Same as bit mapped register : R2200/R2250/R2300/R2350 IO-Bit P1 2080 2081 2082 2083 2084 2085 2086 2087 2088 2089 2090 2091 2092 2093 2094 2095 IO-Bit P2 2112 2113 2114 2115 2116 2117 2118 2119 2120 2121 2122 2123 2124 2125 2126 2127 IO-Bit P3 2144 2145 2146 2147 2148 2149 2150 2151 2152 2153 2154 2155 2156 2157 2158 2159 IO-Bit P4 2176 2177 2178 2179 2180 2181 2182 2183 2184 2185 2186 2187 2188 2189 2190 2191 Function Note Relay Control pump Auto reset motor protector Control run (pump exercise) Pump in alternation group Alternative stop level active Max Cont. runtime stop pump Dry run stop pump Reversing pump Leakage 1 Oil chamber stop pump Leakage 2 Con chamber stop pump Leakage 3 Mot housing stop pump Type of pump control Hi temp stator wiring stop pump Hi temp upper bearing stop pump Hi temp lower bearing stop pump High vibration stop pump 0=No / 1= Yes 0=Off / 1= On 0=Off / 1= On 0=No / 1= Yes 0=Off / 1= On 1=No/ 1= Yes 1=No/ 1= Yes 1=No /1 = Yes 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 0=Normal, 1=VFD (PID) 1=No /1= Yes 1=No /1=Yes 1=No /1=Yes 1=No /1= Yes Pump 1-4 flags 2 : Same as bit mapped register : R2201/R2252/R2301/R2351 IO-Bit P1 2096 2097 2098 2099 2100 2101 2102 2103 2104 2105 2106 2107 2108 2109 2110 2111 IO-Bit P2 2128 2129 2130 2131 2132 2133 2134 2135 2136 2137 2138 2139 2140 2141 2142 2143 IO-Bit P3 2160 2161 2162 2163 2164 2165 2166 2167 2168 2169 2170 2171 2172 2173 2174 2175 IO-Bit P4 2192 2193 2194 2195 2196 2197 2198 2199 2200 2201 2202 2203 2204 2205 2206 2207 Function Note Alarm no run confirm block pump Alarm fallen M.prot block pump Alarm high curr. block pump Alarm low curr. block pump Alarm D.IN leakage block pump Alarm D.IN high temp. block pump Alarm low capacity block pump Alarm D.IN pump fail block pump Alarm leakage 1 block pump Alarm leakage 2 block pump Alarm leakage 3 block pump Alarm Dry Run block pump Alarm high temp 1 block pump Alarm high temp 2 block pump Alarm high temp 3 block pump Alarm high vibration block pump 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 1=No /1=Yes 1=No /1=Yes 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 1=No /1= Yes 1=No/ 1= Yes 1=No/ 1=Yes Field Bus Flags (CAN) : Same as bit mapped register : 4170 + 4171 IO-Bit 2208 2209 2210 2211 2212 2213 2214 2215 2216 2217 2218 2219 2220 2221 2222 2223 2224 Function CA 441-1 Connected to field bus CA 441-2 Connected to field bus CA 441-3 Connected to field bus CA 441-4 Connected to field bus CA 442-1 Connected to field bus CA 442-2 Connected to field bus CA 442-3 Connected to field bus CA 442-4 Connected to field bus CA 443-0 Connected to field bus CA 443-1 Connected to field bus CA 443-2 Connected to field bus CA 443-3 Connected to field bus CA 443-4 Connected to field bus CA 442-5 Connected to field bus CA 442-6 Connected to field bus CA 781 Connected to field bus CA 622 Connected to field bus Note 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes 0=No / 1=Yes Leakage monitor Temperature monitor Power monitor Exp. Temp. monitor P1/P2 Exp. Temp. monitor P3/P4 Exp. AO/DO Exp. Modbus Master -> VFD 1.13 Text Addresses All text addresses are given in Hex format. All addresses below 1000H allow max 20 character str Address(Hex) Description Scale/Unit/Note 1 2 3 4 Analogue in 2 Analogue in 3 Analogue in 4 Analogue in 5 User text User text User text User text 101 102 103 104 Analogue in 2 Analogue in 3 Analogue in 4 Analogue in 5 User unit User unit User unit User unit 1.14 Digital input alarms Address(Hex) 300 301 302 303 304 305 306 307 308 309 30A 30B 30c 30D 30E 30F Description Digital in 1 Digital in 2 Digital in 3 Digital in 4 Digital in 5 Digital in 6 Digital in 7 Digital in 8 Digital in 9 Digital in 10 Digital in 11 Digital in 12 Digital in 13 Digital in 14 Digital in 15 Digital in16 DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text DI alarm text 1.15 Pump Tag Name Address(Hex) 590 591 592 593 Description Pump 1 Pump 2 Pump 3 Pump 4 Tag Name (max 11 char) Tag Name Tag Name Tag Name 1.16 Tele and alarm setup Address(Hex) Description 0801 0802 0803 0804 Tel. no. alarm call 1 Tel. no. alarm call 2 Tel. no. alarm call 3 Tel. no. alarm call 4 080b GPRS Fallback SMS number 0810 0811 0812 0813 0814 0815 0816 0817 0818 0819 0820 Extra Hayes init. before calling Hayes init after disconnecting line PIN code for GSM modem PUK code for GSM modem SMSC number. International format (Leave blank for SIM card default) GPRS IP address GPRS apn. GPRS apn continued. GPRS User name GPRS Password Net operator GSM/GPRS 0830 0831 Station name Id string to send on connect 1.17 Digital history time stamped events I chronological order Event type : ALARM ON/ALARM OFF/ALARM ACKN./D.IN-D.OUT ON/OFF Text like : Date(yymmddmmss)[TAB]Event type[TAB]Source Address(Hex) 2000 2001 2002 …… 2FFF Description Last time stamped event Event before last And so on. Max 4096 events backwards 2 PC 441 COMLI/Modbus Register 2.1 Register no 0 Description Scale factor/ unit / note Local Mode 2.2 Register no Remote/Local status 1 = Local Analogue inputs/Outputs in engineering units Description Scale factor/ unit / note 1 2 3 4 5 AIN 1. Pit level AIN 2. Current P1/User AIN 3. Current P2/User AIN 4. Current P3/User AIN 5. Current P4 /Pressure/User 0.01 m (0.01ft) 0.1 A / User defined 0.1 A / User defined 0.1 A / User defined 0.1 A / 0.1 bar / User defined (0.1 PSI) 8 9 AO 1. mA output AO 2. mA output 0.001 mA 0.001 mA 2.3 Register no 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 36 Actual values in engineering units Description Scale factor/ unit / note Inflow Outflow Overflow level Overflow flow m3/h Overflow flow l /s Last pump capacity P1 Last pump capacity P2 Last pump capacity P3 Last pump capacity P4 Precipitation/Effect/Flow Ch 1 Precipitation/Effect/Flow Ch 2 Precipitation/Effect/Flow Ch 3 Precipitation/Effect/Flow Ch 4 Supply voltage AIN 1 mA AIN 2 mA AIN 3 mA AIN 4 mA AIN 5 mA Pit level above sea Back Pressure 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) 1 mm (0.01 Inch) 0.1 m3/h (1 GPM) 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) 0.1 l/s*ha/ 0.1 kW/m3/h (0.01 inch/h, 1 GPM) 0.1 l/s*ha/ 0.1 kW/m3/h (0.01 inch/h, 1 GPM) 0.1 l/s*ha/ 0.1 kW/m3/h (0.01 inch/h, 1 GPM) 0.1 l/s*ha/ 0.1 kW/m3/h (0.01 inch/h, 1 GPM) 0.1 V 0.001 mA 0.001 mA 0.001 mA 0.001 mA 0.001 mA 0.01 m (0.01ft) Reg 1 with sea level offset added 0.1 bar (0.1 PSI) All temperatures in °F. If US units selected. 40 Temperature 1 P1 0.1 °C Normally stator (°F) CA 442-1 41 Temperature 2 P1 0.1 °C Normally upper bearing 42 Temperature 3 P1 0.1 °C Normally lower bearing 43 Temperature 4 P1 0.1 °C Normally stator 44 Vibrations P1 0.1 mm/s (0.01 Inch/s) 45 Temperature 1 P2 0.1 °C Normally stator 46 Temperature 2 P2 0.1 °C Normally upper bearing 47 Temperature 3 P2 0.1 °C Normally lower bearing 48 Temperature 4 P2 0.1 °C Normally stator 49 Vibrations P2 0.1 mm/s (0.01 Inch/h) 50 Temperature 1 P3 0.1 °C Normally stator 51 Temperature 2 P3 0.1 °C Normally upper bearing 52 Temperature 3 P3 0.1 °C Normally lower bearing 53 Temperature 4 P3 0.1 °C Normally stator 54 Vibrations P3 0.1 mm/s (0.01 Inch/h) 55 Temperature 1 P4 0.1 °C Normally stator 56 Temperature 2 P4 0.1 °C Normally upper bearing 57 Temperature 3 P4 0.1 °C Normally lower bearing 58 Temperature 4 P4 0.1 °C Normally stator 59 Vibrations P4 0.1 mm/s (0.01 Inch/h) Pt100 Sensor Register no Description Scale factor/ unit / note 60 61 62 63 64 65 66 67 Main Effect Main voltage L1 Main voltage L2 Main voltage L3 Main frequency Main current L1 Main current L2 Main current L3 0.1 kW 0.1 V 0.1 V 0.1 V 0.01 Hz 0.1 A 0.1 A 0.1 A Power monitor CA 443-0 70 71 72 73 74 75 76 77 78 79 P1 Effect P1 Cos φ P1 Current P1 Current L1 P1 Current L2 P1 Current L3 P1 L1-L2 voltage P1 L2-L3 voltage P1 L3-L1 voltage P1 Average LL voltage 0.1 kW 0.01 0.1 A Max of L1,L2 and L3 0.1 A 0.1 A 0.1 A 0.1 V 0.1 V 0.1 V 0.1 V Power monitor CA 443-1 80 81 82 83 84 85 86 87 88 89 P2 Effect P2 Cos φ P2 Current P2 Current L1 P2 Current L2 P2 Current L3 P2 L1-L2 voltage P2 L2-L3 voltage P2 L3-L1 voltage P2 Average LL voltage 0.1 kW 0.01 0.1 A Max of L1,L2 and L3 0.1 A 0.1 A 0.1 A 0.1 V 0.1 V 0.1 V 0.1 V Power monitor CA 443-2 90 91 92 93 94 95 96 97 98 99 P3 Effect P3 Cos φ P3 Current P3 Current L1 P3 Current L2 P3 Current L3 P3 L1-L2 voltage P3 L2-L3 voltage P3 L3-L1 voltage P3 Average LL voltage 0.1 kW 0.01 0.1 A Max of L1,L2 and L3 0.1 A 0.1 A 0.1 A 0.1 V 0.1 V 0.1 V 0.1 V Power monitor CA 443-3 100 101 102 103 104 105 106 107 108 109 P4 Effect P4 Cos φ P3 Current P4 Current L1 P4 Current L2 P4 Current L3 P4 L1-L2 voltage P4 L2-L3 voltage P4 L3-L1 voltage P4 Average LL voltage 0.1 kW 0.01 0.1 A Max of L1,L2 and L3 0.1 A 0.1 A 0.1 A 0.1 V 0.1 V 0.1 V 0.1 V Power monitor CA 443-4 Register no Description Scale factor/ unit / note 110 111 112 113 114 115 116 117 118 119 Prog. Version Main Phase L1 Main Phase L2 Main Phase L3 Main Phase L1-L2 Main Phase L1-L3 Main Cos φ Main L1-L2 voltage Main L2-L3 voltage Main L3-L1 voltage 100 = Prog Ver 1.00 +/- 90 ° +/- 90 ° +/- 90 ° +/-359° +/-359° 0.01 0.1 V 0.1 V 0.1 V 120 121 122 123 124 125 126 127 128 129 Prog Version P1 Phase L1 P1 Phase L2 P1 Phase L3 P1 Phase L1-L2 P1 Phase L1-L3 P1 Voltage L1 P1 Voltage L2 P1 Voltage L3 P1 Frequency 100 = Prog Ver 1.00 +/- 90 ° +/- 90 ° +/- 90 ° +/-359° +/-359° 0.1 V 0.1 V 0.1 V 0.01 Hz Power monitor CA443-1 130 131 132 133 134 135 136 137 138 139 Prog Version P2 Phase L1 P2 Phase L2 P2 Phase L3 P2 Phase L1-L2 P2 Phase L1-L3 P2 Voltage L1 P2 Voltage L2 P2 Voltage L3 P2 Frequency 100 = Prog Ver 1.00 +/- 90 ° +/- 90 ° +/- 90 ° +/-359° +/-359° 0.1 V 0.1 V 0.1 V 0.01 Hz Power monitor CA443-2 140 141 142 143 144 145 146 147 148 149 Prog Version P3 Phase L1 P3 Phase L2 P3 Phase L3 P3 Phase L1-L2 P3 Phase L1-L3 P3 Voltage L1 P3 Voltage L2 P3 Voltage L3 P3 Frequency 100 = Prog Ver 1.00 +/- 90 ° +/- 90 ° +/- 90 ° +/-359° +/-359° 0.1 V 0.1 V 0.1 V 0.01 Hz Power monitor CA443-3 150 151 152 153 154 155 156 157 158 159 Prog Version P4 Phase L1 P4 Phase L2 P4 Phase L3 P4 Phase L1-L2 P4 Phase L1-L3 P4 Voltage L1 P4 Voltage L2 P4 Voltage L3 P4 Frequency 100 = Prog Ver 1.00 +/- 90 ° +/- 90 ° +/- 90 ° +/-359° +/-359° 0.1 V 0.1 V 0.1 V 0.01 Hz Power monitor CA443-4 Master power monitor CA443-0 Register no Description Scale factor/ unit / note 160 161 162 163 164 Prog Version DI1 AD Value DI2 AD Value DI3 AD Value DI4 AD Value 100 = Prog Ver 1.00 0-100.00% 0-100.00% 0-100.00% 0-100.00% 165 166 167 168 169 Prog Version DI1 AD Value DI2 AD Value DI3 AD Value DI4 AD Value 0-100.00% 0-100.00% 0-100.00% 0-100.00% 170 171 172 173 174 Prog Version DI1 AD Value DI2 AD Value DI3 AD Value DI4 AD Value 0-100.00% 0-100.00% 0-100.00% 0-100.00% 175 176 177 178 179 Prog Version DI1 AD Value DI2 AD Value DI3 AD Value DI4 AD Value 0-100.00% 0-100.00% 0-100.00% 0-100.00% 180 181 182 183 184 185 186 187 188 189 Prog Version mA-In Vibrations T1 AD Value T2 T3 T4 T1 Limit T2 T3 T4 Temp. monitor CA442-1 0.001 mA -20.00-80.00 Pt100 / 0-100.00% Klixon/PTC 190 191 192 193 194 195 196 197 198 199 Prog Version mA-In Vibrations T1 AD Value T2 T3 T4 T1 Limit T2 T3 T4 Temp. monitor CA442-2 0.001 mA -20.00-80.00 Pt100 / 0-100.00% Klixon/PTC 200 201 202 203 204 205 206 207 208 209 Prog Version mA-In Vibrations T1 AD Value T2 T3 T4 T1 Limit T2 T3 T4 Temp. monitor CA442-3 0.001 mA -20.00-80.00 Pt100 / 0-100.00% Klixon/PTC Leakage monitor CA441-1 Leakage monitor CA441-2 Leakage monitor CA441-3 Leakage monitor CA441-4 Register no Description Scale factor/ unit / note 210 211 212 213 214 215 216 217 218 219 Prog Version mA-In Vibrations T1 AD Value T2 T3 T4 T1 Limit T2 T3 T4 Temp. monitor CA442-4 0.001 mA -20.00-80.00 Pt100 / 0-100.00% Klixon/PTC 240 241 242 243 244 245 246 247 248 249 Prog Version mA-In T1 AD Value T2 T3 T4 T1 Limit T2 T3 T4 Temp. monitor CA442-5 0.001 mA -20.00-80.00 Pt100 / 0-100.00% Klixon/PTC 250 251 252 253 254 255 256 257 258 259 Prog Version mA-In T1 AD Value T2 T3 T4 T1 Limit T2 T3 T4 Temp. monitor CA442-6 0.001 mA -20.00-80.00 Pt100 / 0-100.00% Klixon/PTC CA 781 Exp. AO/DO module 260 Prog Version 261 AO 1. mA output 262 AO 2. mA output Exp. AO/DO CA 781 0.001 mA 0.001 mA CA 622 Exp. AO/DO module 264 Prog Version Exp. AO/DO CA 781 CA 442-5 Exp. temp. module P1 nd P2 270 Temperature P1 stator L2 271 Temperature P1 stator L3 272 Temperature P2 stator L2 273 Temperature P2 stator L3 0.1 °C 0.1 °C 0.1 °C 0.1 °C (°F) (°F) (°F) (°F) CA 442-5 T1 CA 442-5 T2 CA 442-5 T3 CA 442-5 T4 Pt100 Sensor Pt100 Sensor Pt100 Sensor Pt100 Sensor CA 442-5 Exp. temp. module P3 and P4 275 Temperature P3 stator L2 276 Temperature P3 stator L3 277 Temperature P4 stator L2 278 Temperature P4 stator L3 0.1 °C 0.1 °C 0.1 °C 0.1 °C (°F) (°F) (°F) (°F) CA 442-6 T1 CA 442-6 T2 CA 442-6 T3 CA 442-6 T4 Pt100 Sensor Pt100 Sensor Pt100 Sensor Pt100 Sensor 2.4 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 2.5 IO 0 -15 IO 16 -31 IO 32 -47 IO 48 -63 IO 64 -79 IO 80 -95 IO 96 -111 IO 112-127 IO 128-143 IO 144-159 IO 160-175 IO 176-191 IO 192-207 IO 208-223 IO 224-239 IO 240-255 Read only Read only Read only Read only Read only Read only Read only Read only Read only Read only Read only Read only Read only Read only Read only Read only Acknowledge alarm dialup Register no 333 34 2.6 IO-bits 0-255 Description Scale factor/ unit / note Write to ackn. Alarm dialup “ “ “ “ “ for value 1 master takes response for disconnecting GPRS status Register no 334 335 336 337 338 339 340 Description Scale factor/ unit / note GPRS CSQ GPRS connect count GPRS connect status urc.ProfileId urc.Cause urc.InfoId Previous urc.IfoId Signal strength 0-31 2.7 Register no 0=dsisconnected, 1=reconnecting, 2=connected From last ^SIS msg From last ^SIS msg From last ^SIS msg ^SIS msg before last Raw AD values Description Scale factor/ unit / note 399 400 401 402-403 404-405 406-407 408-409 410-411 Factory reserved Factory reserved Factory reserved AI 1 AI 2 AI 3 AI 4 AI 5 Level Current P1/User Current P2/User Current P3/User Current P3/Back-Pressure/User 414 415 416 417 418 AI 1 AI 2 AI 3 AI 4 AI 5 2.8 Unfiltered AI values Level Current P1/User Current P2/User Current P3/User Current P4/Backpressure/User 0.01% 0.01% 0.01% 0.01% 0.01% 2.9 Register no Communication status Description Scale factor/ unit / note Service port 420 Overflow counter 421 Parity error counter 422 Framing error counter 423 Break counter 424 Error messages counter 425 Ok Messages counter 426 Checksum error counter Com port 430 Overflow counter 431 Parity error counter 432 Framing error counter 433 Break counter 434 Error messages counter 435 Ok Messages counter 436 Checksum error counter Field bus (CAN) 440 Error messages counter 441 Ok messages counter USB Port 460 Overflow counter 461 Parity error counter 462 Framing error counter 463 Break counter 464 Error messages counter 465 Ok Messages counter 466 Checksum error counter 2.10 General info Register no Description Scale factor/ unit / note 443 444 445 446 447 449 Program version Special version Station type CPU clock frequency Program version in hex GSM-GPRS signal (CSQ) 100 = 1.00 0 = Standard version 60=PC 441 1/1000 in MHz and three decimals 1.00 = 0x100 0-31, 99=unknown (also in Reg 34) 451 CA 511 Firmware version V.1.24 = current CA 511 version 583-584 31-32 Station number “ “ Station identification for monitoring systems (32 bits fromV.1.44) “ “ “ “ 2.11 Modbus Drive status Register no Description Scale factor/ unit / note 480 481 482 483 484 485 487 P1 Set frequency P1 Actual frequency P1 Actual speed P1 Torque P1 Torque P1 Volt P1 Power 0.01 Hz 0.01 Hz 1 RPM 0.1 % 0.1 Nm 0.1 V 0.01 KW 490 491 492 493 494 495 497 P2 Set frequency P2 Actual frequency P2 Actual speed P2 Torque P2 Torque P2 Volt P2 Power 0.01 Hz 0.01 Hz 1 RPM 0.1 % 0.1 Nm 0.1 V 0.01 KW 500 501 502 503 504 505 507 P3 Set frequency P3 Actual frequency P3 Actual speed P3 Torque P3 Torque P3 Volt P3 Power 0.01 Hz 0.01 Hz 1 RPM 0.1 % 0.1 Nm 0.1 V 0.01 KW 510 511 512 513 514 515 517 P4 Set frequency P4 Actual frequency P4 Actual speed P4 Torque P4 Torque P4 Volt P4 Power 0.01 Hz 0.01 Hz 1 RPM 0.1 % 0.1 Nm 0.1 V 0.01 KW 2.12 Register no 990 991 992 993 994 No decimals for flow values. Default 1 dec. (us = 0) Description Scale factor/ unit / note Inflow decimals Outflow decimals Pump capacity P1/P2/P3/P4 Overflow flow Pulse flow channel 1-4 0-4 0-4 0-4 0-4 0-4 2.13 Accumulated total values Register no 1000-1001 1002-1003 1004-1005 1006-1007 1008-1009 1010-1011 1012 1013 1014-1015 1016-1017 1018-1019 1020-1021 1022 1023 1024-1025 1026-1027 1028-1029 1030-1031 1032-1033 1034-1035 1036-1037 1038-1039 1040-1041 1042-1043 1044-1045 1046-1047 1048-1049 1050-1051 1052-1053 1054-1055 Description Scale factor/ unit / note Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 nominal cap. P2 nominal cap. P2 runtime P2 start count P3 runtime P3 start count P3 nominal cap. P4 nominal cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count times sec 0.1 m3 (1 gal) 0.1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.14 Accumulated values today Register no 1100-1101 1102-1103 1104-1105 1106-1107 1108-1109 1110-1111 1112 1113 1114-1115 1116-1117 1118-1119 1120-1121 1122 1123 1124-1125 1126-1127 1128-1129 1130-1131 1132-1133 1134-1135 1136-1137 1138-1139 1140-1141 1142-1143 1144-1145 1146-1147 1148-1149 1150-1151 1152-1153 1154-1155 Description Scale factor/ unit / note Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 avg. cap. P2 avg. cap. P2 runtime P2 start count P3 runtime P3 start count P3 avg. cap. P4 avg. cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count times sec 0.1 m3 (1 gal) 1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.15 Accumulated values yesterday Register no 1200-1201 1202-1203 1204-1205 1206-1207 1208-1209 1210-1211 1212 1213 1214-1215 1216-1217 1218-1219 1220-1221 1222 1223 1224-1225 1226-1227 1228-1229 1230-1231 1232-1233 1234-1235 1236-1237 1238-1239 1240-1241 1242-1243 1244-1245 1246-1247 1248-1249 1250-1251 1252-1253 1254-1255 Description Scale factor/ unit / note Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 avg. cap. P2 avg. cap. P2 runtime P2 start count P3 runtime P3 start count P3 avg. cap. P4 avg. cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count times sec 0.1 m3 (1 gal) 1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.16 Accumulated values 2 days ago Register no 1300-1301 1302-1303 1304-1305 1306-1307 1308-1309 1310-1311 1312 1313 1314-1315 1316-1317 1318-1319 1320-1321 1322 1323 1324-1325 1326-1327 1328-1329 1330-1331 1332-1333 1334-1335 1336-1337 1338-1339 1340-1341 1342-1343 1344-1345 1346-1347 1348-1349 1350-1351 1352-1353 1354-1355 Description Scale factor/ unit / note Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 avg. cap. P2 avg. cap. P2 runtime P2 start count P3 runtime P3 start count P3 avg. cap. P4 avg. cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count times sec 0.1 m3 (1 gal) 1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.17 Accumulated values 3 days ago Register no 1400-1401 1402-1403 1404-1405 1406-1407 1408-1409 1410-1411 1412 1413 1414-1415 1416-1417 1418-1419 1420-1421 1422 1423 1424-1425 1426-1427 1428-1429 1430-1431 1432-1433 1434-1435 1436-1437 1438-1439 1440-1441 1442-1443 1444-1445 1446-1447 1448-1449 1450-1451 1452-1453 1454-1455 Description Scale factor/ unit / note Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 avg. cap. P2 avg. cap. P2 runtime P2 start count P3 runtime P3 start count P3 avg. cap. P4 avg. cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count times sec 0.1 m3 (1 gal) 1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.18 Accumulated values 4 days ago Register no 1500-1501 1502-1503 1504-1505 1506-1507 1508-1509 1510-1511 1512 1513 1514-1515 1516-1517 1518-1519 1520-1521 1522 1523 1524-1525 1526-1527 1528-1529 1530-1531 1532-1533 1534-1535 1536-1537 1538-1539 1540-1541 1542-1543 1544-1545 1546-1547 1548-1549 1550-1551 1552-1553 1554-1555 Description Scale factor/ unit / note Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 avg. cap. P2 avg. cap. P2 runtime P2 start count P3 runtime P3 start count P3 avg. cap. P4 avg. cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count times sec 0.1 m3 (1 gal) 1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.19 Accumulated values 5 days ago Register no 1600-1601 1602-1603 1604-1605 1606-1607 1608-1609 1610-1611 1612 1613 1614-1615 1616-1617 1618-1619 1620-1621 1662 1663 1624-1625 1626-1627 1628-1629 1630-1631 1632-1633 1634-1635 1636-1637 1638-1639 1640-1641 1642-1643 1644-1645 1646-1647 1648-1649 1650-1651 1652-1653 1654-1655 Description Scale factor/ unit / note Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 avg. cap. P2 avg. cap. P2 runtime P2 start count P3 runtime P3 start count P3 avg. cap. P4 avg. cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count times sec 0.1 m3 (1 gal) 1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.20 Accumulated values 6 days ago Register no 1700-1701 1702-1703 1704-1705 1706-1707 1708-1709 1710-1711 1712 1713 1714-1715 1716-1717 1718-1719 1720-1721 1762 1763 1724-1725 1726-1727 1728-1729 1730-1731 1732-1733 1734-1735 1736-1737 1738-1739 1740-1741 1742-1743 1744-1745 1746-1747 1748-1749 1750-1751 1752-1753 1754-1755 Description Scale factor/ unit / note Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 avg. cap. P2 avg. cap. P2 runtime P2 start count P3 runtime P3 start count P3 avg. cap. P4 avg. cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count times sec 0.1 m3 (1 gal) 1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.21 Accumulated values 7 days ago Register no 1800-1801 1802-1803 1804-1805 1806-1807 1808-1809 1810-1811 1812 1813 1814-1815 1816-1817 1818-1819 1820-1821 1822 1823 1824-1825 1826-1827 1828-1829 1830-1831 1832-1833 1834-1835 1836-1837 1838-1839 1840-1841 1842-1843 1844-1845 1846-1847 1848-1849 1850-1851 1852-1853 1854-1855 Description Overflow count Overflow time Overflow volume Pumped volume P1 runtime P1 start count P1 avg. cap. P2 avg. cap. P2 runtime P2 start count P3 runtime P3 start count P3 avg. cap. P4 avg. cap. P4 runtime P4 start count Pulse Ch 1 Pulse Ch 2 Pulse Ch 3 Pulse Ch 4 Energy P1 Energy P2 Energy P3 Energy P4 Total Energy Energy efficiency Mixer runtime Mixer start count Drain pump runtime Drain pump start count Scale factor/ unit / note times sec 0.1 m3 (1 gal) 1 m3 (1 gal) sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times sec times 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) sec times 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh/ mm/m3 (0.01 inch) 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.1 kWh 0.001 kWh/m3 (1 kWh/Mgal) sec times sec times 2.22 System configuration Register no Description Scale factor/ unit / note 2000 2001 2002 2003 2004 2005 2006 Menu language Date format Units LCD Back light time Pit fill graphics range Alarm alert on time Alarm alert pause time 0=Swe/1=Eng/2=Ger/3=Fre …….. 0=YY:MM:DD / 1=DD:MM/YY/ 2=MM:DD:YY 0=Metric / 1= Us Units (Only metric support in V.1.xx min 0= always On centimetre (0.01 ft) min, 0=No limit, Do function = Alarm alert min 2007 2008 2009 2012 Main voltage Main frequency Hide Start-Stop levels CA 511 Main graphics 1 V (type 400V) 1 Hz (type 50Hz) 0=NO, 1=YES 0=Pit, 1=P1, 2=P2… 2.23 Pit configuration Register no Description Scale factor/ unit / note 2010 2011 Pit flags 1 Pit flags 2 Bit mapped register, See IO-bits. “ “ “ “ “ 2013 2014 Min time between relay changes s Max No. pumps running 0-3 0=1 pump 2015 2016 2017 Pump alternation No. Starts to Alt Runtime to alternation 0=Off/1=Normal/2=Asymmetrical Asymmetrical alternation min. Runtime alternation 2018 2019 2020 2021 Min no. pumps running Max no. pumps running Level change to start / time unit 0-4 0-4 0.01 m min Level change start 2022 2023 2024 2025 Min no. pumps running Max no. pumps running Level change to stop / time unit 0-4 0-4 0.01 m min Level change stop 2027 Calculation interval inflow s Inflow 2028 2029 2030 Static head Total head (hf) Flow at duty point 0.01 mH2O (0.01ft) System curve at duty point 0.01 mH2O (0.01ft) 0.1 l/s (GPM) 2031 2032 2033 Flow compensation 2 pumps Flow compensation 3 pumps Flow compensation 4 pumps 1% 1% 1% Alternative to system curve 2036 2037 2038 2039 2040 2041 2042 2043 2044 2045 2046 2047 2048 2049 2050 2051 2052 2053 2054 2055 Pit level 0 Pit area 0 Pit level 1 Pit area 1 Pit level 2 Pit area 2 Pit level 3 Pit area 3 Pit level 4 Pit area 4 Pit level 5 Pit area 5 Pit level 6 Pit area 6 Pit level 7 Pit area 7 Pit level 8 Pit area 8 Pit level 9 Pit area 9 0.01 m 0.1 m2 0.01 m 0.1 m2 0.01m 0.1 m2 0.01 m 0.1 m2 0.01 m 0.1 m2 0.01m 0.1 m2 0.01 m 0.1 m2 0.01 m 0.1 m2 0.01m 0.1 m2 0.01m 0.1 m2 (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) (0.01 ft) (0.1 ft2) Pit area 2060 2061 2062 2063 2064 Min level calc. pump capacity Max level calc. pump capacity Start delay Calculation time Stop delay 0.01 m 0.01 m s s s (0.01 ft) (0.01 ft) Pump capacity (0.01 ft) (0.01 ft) Register no Description Scale factor/ unit / note 2066 2067 2068 2069 Remote block timeout Pressure block set-point Pressure block timeout Pressure block delay s 0.1 bar s s 0 = No timeout (0.1 PSI) 0 = No timeout 2070 Backup runtime s High float run on time 2072 2073 2074 2075 2076 2077 Sensor level at high float Max difference at high float Sensor level at low float Max difference at low float Sensor control time Min level change 0.01 m +/-0.01 m 0.01 m +/-0.01 m s 0.01m (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) 2080 2081 2082 2083 2084 2085 2086 2087 2088 2089 2090 2091 2092 2093 2094 2095 2096 2097 2098 2099 2100 2101 2102 2105 2106 2107 2108 2109 Hi tariff pump pre-start Pump down level Monday peak 1 On Monday peak 1 Off Monday peak 2 On Monday peak 2 Off Tuesday peak 1 On Tuesday peak 1 Off Tuesday peak 2 On Tuesday peak 2 Off Wednesday peak 1 On Wednesday peak 1 Off Wednesday peak 2 On Wednesday peak 2 Off Thursday peak 1 On Thursday peak 1 Off Thursday peak 2 On Thursday peak 2 Off Friday peak 1 On Friday peak 1 Off Friday peak 2 On Friday peak 2 Off Saturday peak 1 On Saturday peak 2 Off Sunday peak 1 On Sunday peak 1 Off Sunday peak 2 On Sunday peak 2 Off min 0.01 m min min min min min min min min min min min min min min min min min min min min min min min min min min Tariff control (0.01 ft) 0-1440 min 2112 Relative level m.a.s 0.01 m (0.01 ft) 2115 2116 2117 No starts to alt. stop level Alternative stop level Stop delay times 0.01 m s (0.01 ft) 2120 2121 2122 2123 2124 2125 2126 Power monitor block delay Power monitor block off delay Over voltage block set-point Under voltage block set-point Diff L1,L2,L3 block set-point High freq. block set-point Low freq. block set-point s s 0.1 % 0.1 % 0.1 % 0.1 % 0.1 % Sensor check (0.01 ft) 0 = No timeout CA 443 Over/under voltage …… % of main voltage register 2007 “ “ % of main freq. register 2008 2.24 Extra temp. monitor modules CA442-5 & CA442-6 CA 442-5 2140 2141 2142 Extra Temperature monitor P1/P2 Sensor 1 type 0=Off/1=Klixon/2=PTC/3=Pt100 Temperature offset 0.1 °C ( Pt100) Filter constant s ( Pt100) 2145 2146 2147 Sensor 2 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 2150 2151 2152 Sensor 3 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 2155 2156 2157 Sensor 4 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100/4=Vibrations 0.1 °C ( Pt100) s ( Pt100) CA 442-6 2170 2171 2172 Extra Temperature monitor P3/P4 Sensor 1 type 0=Off/1=Klixon/2=PTC/3=Pt100 Temperature offset 0.1 °C ( Pt100) Filter constant s ( Pt100) 2175 2176 2177 Sensor 2 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 2180 2181 2182 Sensor 3 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 2185 2186 2187 Sensor 4 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100/4=Vibrations 0.1 °C ( Pt100) s ( Pt100) 2.25 Pump 1 configuration Register no Description Scale factor/ unit / note 2202 2203 2204 2205 2206 Normal start level Normal stop level High tariff start level High tariff stop level Random start range 0.01 m 0.01 m 0.01 m 0.01 m +/- 0.01m 2208 2209 Start delay Stop delay s s 2212 2213 Running indicator Min run current 0=Off/1=Digtal input/2=Motor Current, 3=CA622 0.1 A 2215 Max continuous runtime min 2216 2217 Nominal Motor Current Nominal Cos φ 0.1A 0.01 2218 2219 Pcap Comp (VFD) Pump Type 2220 2221 2222 2223 2224 2225 2226 Point 1 Total head (Hmax) Point 1 Flow Point 2 Total head Point 2 Flow Point 3 Total head (Hmin) Point 3 Flow Total Head from sensor zero 0.01 mH20 0.1 l/s 0.01 mH2O 0.1 l/s 0.01 mH2O 0.1 l/s 0.01 mH20 2230 2231 2232 Dry run Cos φ set-point Dry run block timeout Dry run block delay 0.01 s s 2235 2236 2237 Leakage block delay s High temperature block delay s High vibrations block delay s 2239 2240 2241 2242 Demand Manual Reset Manual frequency Min. frequency Max. frequency 2200 2201 Pump flags 1 Pump flags 2 Bit mapped register, See IO-bits. “ “ (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) Start/Stop levels Power Factor 0.1% 0/1 Pump cap factor at min Freq (VFD) 0=Fixed, 1=Speed controlled (VFD). (0.01ft) (0.1 GPM) (0.01ft) (0.1 GPM) (0.01 ft) (0.1 GPM) (0.01 ft) QH curve (at pump outlet) Taken from QH curve At pit max level At level sensor zero level) CA 443 Connected 0=No, 1=Only Stator Alarms, 2=All Temp. alarms (v1.16) 0.1 Hz (CA 622 VFD Control) 0.1 Hz (CA 622 VFD Control) 0.1 Hz (CA 622 VFD Control) 2.26 Register no Pump 2 configuration 2250 2251 Pump flags 1 Pump flags 2 Description Scale factor/ unit / note 2252 2253 2254 2255 2256 Normal start level Normal stop level High tariff start level High tariff stop level Random start range 0.01 m 0.01 m 0.01 m 0.01 m +/- 0.01m 2258 2259 Start delay Stop delay s s 2262 2263 Running indicator Min run current 0=Off/1=Digtal input/2=Motor Current, 3=CA622 0.1 A 2265 Max continuous runtime min 2266 2267 Nominal Motor Current Nominal Cos φ 0.1A 0.01 2268 2269 Pcap Comp (VFD) Pump Type 0.1% 0/1 2270 2271 2272 2273 2274 2275 2276 Point 1 Total head (Hmax) Point 1 Flow Point 2 Total head Point 2 Flow Point 3 Total head (Hmin) Point 3 Flow Total Head from sensor zero 0.01 mH20 (0.01ft) QH curve (at pump outlet) 0.1 l/s (0.1 GPM) Taken from QH curve 0.01 mH2O (0.01 ft) 0.1 l/s (0.1 GPM) 0.01 mH2O (0.01 ft) (at pit max level) 0.1 l/s (0.1 GPM) 0.01 mH20 (0.01 ft) (at level sensor zero level) 2280 2281 2282 Dry run current set-point Dry run block timeout Dry run block delay 0.1 A s s 2285 2286 2287 Leakage block delay s High temperature block delay s High vibrations block delay s 2289 2290 2291 2202 Demand Manual Reset Manual frequency Min. frequency Max. frequency Bit mapped register, See IO-bits. “ “ (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) Start/Stop levels Power Factor Pump cap factor at min Freq (VFD) 0=Fixed, 1=Speed controlled (VFD). 0=No, 1=Only Stator Alarms, 2=All Temp. alarms (v1.16) 0.1 Hz (CA 622 VFD Control) 0.1 Hz (CA 622 VFD Control) 0.1 Hz (CA 622 VFD Control) 2.27 Pump 3 configuration Register no Description Scale factor/ unit / note 2300 2301 Pump flags 1 Pump flags 2 Bit mapped register, See IO-bits. “ “ 2302 2303 2304 2305 2306 Normal start level Normal stop level High tariff start level High tariff stop level Random start range 0.01 m 0.01 m 0.01 m 0.01 m +/- 0.01m 2308 2309 Start delay Stop delay s s 2312 2313 Running indicator Min run current 0=Off/1=Digtal input/2=Motor Current, 3=CA622 0.1 A 2315 Max continuous runtime min 2316 2317 Nominal Motor Current Nominal Cos φ 0.1A 0.01 Power Factor 2318 2319 Pcap Comp (VFD) Pump Type 0.1% 0/1 Pump cap factor at min Freq (VFD) 0=Fixed, 1=Speed controlled (VFD). 2320 2321 2322 2323 2324 2325 2326 Point 1 Total head (Hmax) Point 1 Flow Point 2 Total head Point 2 Flow Point 3 Total head (Hmin) Point 3 Flow Total Head from sensor zero 0.01 mH20 (0.01 ft) 0.1 l/s (0.1 GPM) 0.01 mH2O (0.01 ft) 0.1 l/s (0.1 GPM) 0.01 mH2O (0.01 ft) 0.1 l/s (0.1 GPM) 0.01 mH20 (0.01 ft) 2330 2331 2332 Dry run Cos φ set-point Dry run block timeout Dry run block delay 0.01 s s 2335 2336 2337 Leakage block delay s High temperature block delay s High vibrations block delay s 2339 2340 2341 2342 Demand Manual Reset Manual frequency Min. frequency Max. frequency (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) Start/Stop levels QH curve (at pump outlet) Taken from QH curve (at pit max level) (at level sensor zero level) CA 443 Connected 0=No, 1=Only Stator Alarms, 2=All Temp. alarms (v1.16) 0.1 Hz (CA 622 VFD Control) 0.1 Hz (CA 622 VFD Control) 0.1 Hz (CA 622 VFD Control) 2.28 Register no Pump 4 configuration 2350 2351 Pump flags 1 Pump flags 2 Description Scale factor/ unit / note 2352 2353 2354 2355 2356 Normal start level Normal stop level High tariff start level High tariff stop level Random start range 0.01 m 0.01 m 0.01 m 0.01 m +/- 0.01m 2358 2359 Start delay Stop delay s s 2362 2363 Running indicator Min run current 0=Off/1=Digital input/2=Motor Current, 3=CA622 0.1 A 2365 Max continuous runtime min 2366 2367 Nominal Motor Current Nominal Cos φ 0.1A 0.01 Power Factor 2368 2369 Pcap Comp (VFD) Pump Type 0.1% 0/1 Pump cap factor at min Freq (VFD) 0=Fixed, 1=Speed controlled (VFD). 2370 2371 2372 2373 2374 2375 2376 Point 1 Total head (Hmax) Point 1 Flow Point 2 Total head Point 2 Flow Point 3 Total head (Hmin) Point 3 Flow Total Head from sensor zero 0.01 mH20 (0.01ft) 0.1 l/s (0.1 GPM) 0.01 mH2O (0.01 ft) 0.1 l/s (0.1 GPM) 0.01 mH2O (0.01 ft) 0.1 l/s (0.1 GPM) 0.01 mH20 (0.01 ft) 2380 2381 2382 Dry run Cos φ set-point Dry run block timeout Dry run block delay 0.01 s s 2385 2386 2387 Leakage block delay s High temperature block delay s High vibrations block delay s 2389 2390 2391 2392 Demand Manual Reset Manual frequency Min. frequency Max. frequency Bit mapped register, See IO-bits. “ “ (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) (0.01 ft) Start/Stop levels QH curve (at pump outlet) Taken from QH curve (at pit max level) (at sensor zero level) 0=No, 1=Only Stator Alarms, 2=All Temp. alarms (v1.16) 0.1 Hz (CA 622 VFD Control) 0.1 Hz (CA 622 VFD Control) 0.1 Hz (CA 622 VFD Control) 2.29 Pump 1-4 common configuration Register no Description Scale factor/ unit / note 2400 Log pump events 0=Timestamp off, 1=on. 2402 2403 2404 Pulse time Pause time Max no attempts s s Max 3 Reset motor protector 2410 2411 2412 2413 Max stand still time Control runtime Start if level > Start if level < min s 0.01 m 0.01 m Control run 2414 2415 2416 2417 2418 2419 2420 2421 2422 Reversing delay time Reversing run time Max no attempts Pump relay when rev Stop pumps before reversing Rev. when fallen M-prot Rev. when D.in pump fail Rev. when low pump capacity Rev. when overcurrent min Reversing pumps s Max 3 0=Off / 1=On 0=Off / 1= On 0=No / 1=Yes 0=No / 1= Yes 0=No / 1= Yes 0=No / 1= Yes (0.01 ft) (0.01 ft) 2.30 Overflow configuration Register no Description Scale factor/ unit / note 2430 2431 2432-2433 2434-2435 2436-2437 2438-3439 2440 Overflow measuring Overflow calculation Exponent 1 Constant 1 Exponent 2 Constant 2 Level at overflow 0=Off /1=Sensor (KV) /2=Level 0=Exp+Const / 1=Lock on inflow 0.0001 0.0001 0.0001 0.0001 0.001 m (0.001ft) 2.31 CA 781 AO/DO Exp. module Exp. DO 2450 2451 2452 2453 2454 2455 2456 2457 2458 2459 2460 2461 2462 2463 2464 2465 2466 2467 2468 2469 2470 2471 2472 2473 DO 1. Function DO 1. Pump no. DO 1. NO/NC DO 2. Function DO 2. Pump no. DO 2. NO/NC DO 3. Function DO 3. Pump DO 3. NO/NC DO 4. Function DO 4. Pump DO 4. NO/NC DO 5. Function DO 5. Pump DO 5. NO/NC DO 6. Function DO 6. Pump DO 6. NO/NC DO 7. Function DO 7. Pump DO 7. NO/NC DO 8. Function DO 8. Pump DO 8. NO/NC 0=Off/ 1=Pump Control/2= Reset motor protector * 0=P1/1=P2/2=P3/3=P4 For some functions 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC Exp. AO 2480 2481 2482 2483 2484 2485 AO 1. Function AO 1. Signal range AO 1. Scale 0%= AO 1. Scale 100%= AO 1. Filter constant AO 1. Data Register 0=Off/1=Pit level/ 2=Inflow * 0=0-20mA / 1=0-20mA 2490 2491 2492 2493 2494 2495 AO 2. Function AO 2. Signal range AO 2. Scale 0%= AO 2. Scale 100%= AO 2. Filter constant AO 2. Data Register 0=Off/1=Pit level/ 2=Inflow * 0=0-20mA / 1=0-20mA s Only for output type “Data Register” s Only for output type “Data Register” 2.32 Digital inputs configuration Register no 2500 2501 2502 2503 2504 2505 2506 2507 2508 2509 2510 2511 2512 2513 2514 2515 2516 2517 2518 2519 2520 2521 2522 2523 2524 2525 2526 2527 2528 2529 2530 2531 2532 2533 2534 2535 2536 2537 2538 2539 2540 2541 2542 2543 2544 2545 2546 2547 Description Scale factor/ unit / note DI 1. Function DI 1. Pump no. DI 1. NO/NC DI 2. Function DI 2. Pump DI 2. NO/NC DI 3. Function DI 3. Pump DI 3. NO/NC DI 4. Function DI 4. Pump DI 4. NO/NC DI 5. Function DI 5. Pump DI 5. NO/NC DI 6. Function DI 6. Pump DI 6. NO/NC DI 7. Function DI 7. Pump DI 7. NO/NC DI 8. Function DI 8. Pump DI 8. NO/NC DI 9. Function DI 9. Pump DI 9. NO/NC DI 10. Function DI 10 Pump DI 10 NO/NC DI 11. Function DI 11. Pump DI 11. NO/NC DI 12. Function DI 12. Pump DI 12. NO/NC DI 13. Function DI 13. Pump DI 13. NO/NC DI 14. Function DI 14. Pump DI 14. NO/NC DI 15. Function DI 15. Pump DI 15. NO/NC DI 16. Function DI 16. Pump DI 16 NO/NC 0=Off/ 1=Run ind./2=Manuel start * 0=P1/1=P2/2=P3/3=P4 For some functions 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Run ind./2=Manuel start 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC See ppendices 3.1 Digital input types 2.33 Digital outputs configuration Register no Description Main controller PC441 2550 2551 2552 2553 2554 2555 2556 2557 2558 2559 2560 2561 2562 2563 2564 2565 2566 2567 2568 2569 2570 2571 2572 2573 DO 1. Function DO 1. Pump no. DO 1. NO/NC DO 2. Function DO 2. Pump no. DO 2. NO/NC DO 3. Function DO 3. Pump DO 3. NO/NC DO 4. Function DO 4. Pump DO 4. NO/NC DO 5. Function DO 5. Pump DO 5. NO/NC DO 6. Function DO 6. Pump DO 6. NO/NC DO 7. Function DO 7. Pump DO 7. NO/NC DO 8. Function DO 8. Pump DO 8. NO/NC Scale factor/ unit / note 0=Off/ 1=Pump Control/2= Reset motor protector * 0=P1/1=P2/2=P3/3=P4 For some functions 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC 0=Off/ 1=Pump Control/2= Reset motor protector 0=P1/1=P2/2=P3/3=P4 0=NO / 1=NC See ppendices 3.2 Digital output types 2.34 Mixer configuration Register no 2580 2581 2582 2583 2584 2585 2586 2587 2588 2589 2590 Description Scale factor/ unit / note Stop pump when mixer run Mixer runtime Start count interval Timer interval Max level for start Min level for start Run indicator Auto reset motor protector Pulse time Pause time Max no attempts 0=No / 1= Yes s times 0=disabled min 0=disabled 0.01 m (0.01 ft) 0.01 m (0.01 ft) 0=Off / 1= Digital input 0=No / 1=Yes s s Max 3 2.35 Cleaner configuration Register no 2595 2596 2597 Description Scale factor/ unit / note Spool on pump start/stop Spool time No start/stop to spool 0=Start / 1=Stop s time 2.36 Drain pump configuration Register no 2600 2601 2602 2603 2604 2605 2606 Description Start delay Stop delay Run indicator Auto reset motor protector Pulse time Pause time Max no attempts Scale factor/ unit / note s s 0=Off / 1=Digital input 0=No / 1=Yes s s Max 3 2.37 Analogue inputs configuration Register no Description Scale factor/ unit / note 2620 2621 2622 2623 2624 2625 AI 1. Function AI 1. Signal range AI 1. Scale 0%= AI 1. Scale 100%= AI 1. Zero offset AI 1. Filter constant Always level sensor input (1) * 0=4-20mA / 1=0-20mA 0.01 m (0.01 ft) 0.01 m (0.01 ft) 0.01 m (0.01 ft) s 2630 2631 2632 2633 2634 2635 2636 AI 2. Function AI 2. Signal range AI 2. Scale 0%= AI 2. Scale 100%= AI 2. Dead band AI 2. Filter constant AI 2. No decimals 2=Current P1 /3=Current P2 ..* 0=4-20mA / 1=0-20mA 0.1 A/0.1 bar/0.1mm/s/User unit (0.1 PSI/0.01 Inch/h) 0.1 A/… 0.1 % s If free choice 2640 2641 2642 2643 2644 2645 2646 AI 3. Function AI 3. Signal range AI 3. Scale 0%= AI 3. Scale 100%= AI 3. Dead band AI 3. Filter constant AI 3. No decimals 2=Current P2 / 3=Current P2….* 0=4-20mA / 1=0-20mA 0.1 A/0.1 bar/0.1mm/s/User unit (0.1 PSI/0.01 Inch/h) 0.1 A/ … 0.1 % s If free choice 2650 2651 2652 2653 2654 2655 2656 AI 4. Function AI 4. Signal range AI 4. Scale 0%= AI 4. Scale 100%= AI 4. Dead band AI 4. Filter constant AI 4. No decimals 2=Current P2 / 3= Current P2 …* 0=4-20mA / 1=0-20mA 0.1 A / … 0.1 A / … 0.1 % s If free choice 2660 2661 2662 2663 2664 2665 2666 AI 5. Function AI 5. Signal range AI 5. Scale 0%= AI 5. Scale 100%= Not Used AI 5. Filter constant AI 5. No decimals 2=Current P2---* 0=4-20mA / 1=0-20mA 0.1 A / ….. 0.1 A / ….. s If free choice See ppendices 3.3 Analogue inputs types 2.38 Analogue outputs configuration Register no Description Scale factor/ unit / note 2700 2701 2702 2703 2704 2705 AO 1. Function AO 1. Signal range AO 1. Scale 0%= AO 1. Scale 100%= AO 1. Filter constant AO 1. Data Register 0=Off/1=Pit level/ 2=Inflow * 0=0-20mA / 1=0-20mA 2710 2711 2712 2713 2714 2715 AO 2. Function AO 2. Signal range AO 2. Scale 0%= AO 2. Scale 100%= AO 2. Filter constant AO 2. Data Register 0=Off/1=Pit level/ 2=Inflow * 0=0-20mA / 1=0-20mA PC 441 s Only for output type “Data Register” s Only for output type “Data Register” See ppendices 3.4 Analogue output types 2.39 Pulse channels configuration Register no Description Scale factor/ unit / note 2725 2726-2727 Ch 2. Function Ch 2. Scale 1 pulse = 0=Precipitation/ 1= Energy / 2= Flow 0.0001 mm / 0.0001 kW/ 0.001m3 (Inch/kW/gal) 2729 2730-2731 Ch 3. Function Ch 3. Scale 1 pulse = 0=Precipitation/ 1= Energy / 2= Flow 0.0001 mm / 0.0001 kW/ 0.001m3 (Inch/kW/gal) 2733 2734-2735 Ch 4. Function Ch 4. Scale 1 pulse = 0=Precipitation/ 1= Energy / 2= Flow 0.0001 mm / 0.0001 kW/ 0.001m3(Inch/kW/gal) 2721 2722-2723 Ch 1. Function Ch 1. Scale 1 pulse = 0=Precipitation/ 1= Energy / 2= Flow 0.0001 mm / 0.0001 kW/ 0.001m3 (Inch/kW/gal) 2.40 Log channels configuration Register no 2740 2741 2742 2743 Description Ch 1. Log signal Ch 1. Pump no. Ch 1. Log interval Ch 1. Function Scale factor/ unit / note 2745 2746 2747 2748 Ch 2. Log signal Ch 2. Pump no. Ch 2. Log interval Ch 2. Function 0=Closed/ 1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2750 2751 2752 2753 Ch 3. Log signal Ch 3. Pump no. Ch 3. Log interval Ch 3. Function 0=Closed/ 1=Level / 2=Inflow /2=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2755 2756 2757 2758 Ch 4. Log signal Ch 4. Pump no. Ch 4. Log interval Ch 4. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2760 2761 2762 2763 Ch 5. Log signal Ch 5. Pump no. Ch 5. Log interval Ch 5. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2765 2766 2767 2768 Ch 6. Log signal Ch 6. Pump no. Ch 6. Log interval Ch 6. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2770 2771 2772 2773 Ch 7. Log signal Ch 7. Pump no. Ch 7. Log interval Ch 7. Function 0=Closed /1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2775 2776 2777 2778 Ch 8. Log signal Ch 8. Pump no. Ch 8. Log interval Ch 8. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2780 2781 2782 2783 Ch 9. Log signal Ch 9. Pump no. Ch 9. Log interval Ch 9. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2785 2786 2787 2788 Ch 10. Log signal Ch 10. Pump no. Ch 10. Log interval Ch 10. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2790 2791 2792 2793 Ch 11. Log signal Ch 11. Pump no. Ch 11. Log interval Ch 11. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 0= Closed/1=Level / 2=Inflow /3=Outflow ………* 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max Register no 2795 2796 2797 2798 Ch 12. Log signal Ch 12. Pump no. Ch 12. Log interval Ch 12. Function Description Scale factor/ unit / note 2800 2801 2802 2803 Ch 13. Log signal Ch 13. Pump no. Ch 13. Log interval Ch 13. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2805 2806 2807 2808 Ch 14. Log signal Ch 14. Pump no. Ch 14. Log interval Ch 14. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2810 2811 2812 2813 Ch 15. Log signal Ch 15. Pump no. Ch 15. Log interval Ch 15. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 2815 2816 2817 2818 Ch 16. Log signal Ch 16. Pump no. Ch 16. Log interval Ch 16. Function 0=Closed/1=Level / 2=Inflow /3=Outflow ……… 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max 0=Closed/1=Level / 2=Inflow /3=Outflow ………* 0=P1/1=P2/2=P3/3=P4 For some signals types min 0=Closed/1=Act. Value/2=Average val/3=Min/4=Max See ppendices 3.5 Log and Trend signals 2.41 Trend curves configuration Register no Description Scale factor/ unit / note 2831 2832-2833 2834-2835 2836 Tr. 1 Signal Tr. 1 Signal max value Tr. 1 Signal min value Tr. 1 Pump no. 0=Off/1=Level/2=Inflow/3=Outflow ………* 0.0001 0.0001 0-3 For some signal types 2841 2842-2843 2844-2845 2846 Tr. 2 Signal Tr. 2 Signal max value Tr. 2 Signal min value Tr. 2 Pump no. 0=Off/1=Level/2=Inflow/3=Outflow ……… 0.0001 0.0001 0-3 2851 2852-2853 2854-2855 2856 Tr. 3 Signal Tr. 3 Signal max value Tr. 3 Signal min value Tr. 3 Pump no. 0=Off/1=Level/2=Inflow/3=Outflow ……… 0.0001 0.0001 0-3 2861 2862-2863 2864-2865 2866 Tr. 4 Signal Tr. 4 Signal max value Tr. 4 Signal min value Tr. 4 Pump no. 0=Off/1=Level/2=Inflow/3=Outflow ……… 0.0001 0.0001 0-3 2830 Sample time See appendices 3.5 Log and Trend signals s 2.42 Overlayed Digital out parameters PC 441 Digital output type PC441: Logic IO configuration Register no Description Scale factor/ unit / note 2880 2881 2882 2883 2884 2885 2886 2887 DO 1. Sign.1 type DO 1. Sign.1 IO no DO 1. Sign.2 type DO 1. Sign.2 IO no DO 1. Sign.3 type DO 1. Sign.3 IO no DO 1. Sign.4 type DO 1. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 2888 2889 2890 2891 2892 2893 2894 2895 DO 2. Sign.1 type DO 2. Sign.1 IO no DO 2. Sign.2 type DO 2. Sign.2 IO no DO 2. Sign.3 type DO 2. Sign.3 IO no DO 2. Sign.4 type DO 2. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 2896 2897 2898 2899 2900 2901 2902 2903 DO 3. Sign.1 type DO 3. Sign.1 IO no DO 3. Sign.2 type DO 3. Sign.2 IO no DO 3. Sign.3 type DO 3. Sign.3 IO no DO 3. Sign.4 type DO 3. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 2904 2905 2906 2907 2908 2909 2910 2911 DO 4. Sign.1 type DO 4. Sign.1 IO no DO 4. Sign.2 type DO 4. Sign.2 IO no DO 4. Sign.3 type DO 4. Sign.3 IO no DO 4. Sign.4 type DO 4. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 2912 2913 2914 2915 2916 2917 2918 2919 DO 5. Sign.1 type DO 5. Sign.1 IO no DO 5. Sign.2 type DO 5. Sign.2 IO no DO 5. Sign.3 type DO 5. Sign.3 IO no DO 5. Sign.4 type DO 5. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 2920 2921 2922 2923 2924 2925 2926 2927 DO 6. Sign.1 type DO 6. Sign.1 IO no DO 6. Sign.2 type DO 6. Sign.2 IO no DO 6. Sign.3 type DO 6. Sign.3 IO no DO 6. Sign.4 type DO 6. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO Register no Description Scale factor/ unit / note 2928 2929 2930 2931 2932 2933 2934 2935 DO 7. Sign.1 type DO 7. Sign.1 IO no DO 7. Sign.2 type DO 7. Sign.2 IO no DO 7. Sign.3 type DO 7. Sign.3 IO no DO 7. Sign.4 type DO 7. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 2936 2937 2938 2939 2940 2941 2942 2943 DO 8. Sign.1 type DO 8. Sign.1 IO no DO 8. Sign.2 type DO 8. Sign.2 IO no DO 8. Sign.3 type DO 8. Sign.3 IO no DO 8. Sign.4 type DO 8. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO Digital output type PC441: Data Register Setpoint Register no 2880 2881 2882 2883 Description Scale factor/ unit / note DO 1. Data Register DO 1. Set-point on DO 1. Set-point off DO 1. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2888 2889 2890 2891 DO 2. Data Register DO 2. Set-point on DO 2. Set-point off DO 2. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2896 2897 2898 2899 DO 3. Data Register DO 3. Set-point on DO 3. Set-point off DO 3. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2904 2905 2906 2907 DO 4. Data Register DO 4. Set-point on DO 4. Set-point off DO 4. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2912 2913 2914 2915 DO 5. Data Register DO 5. Set-point on DO 5. Set-point off DO 5. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2920 2921 2922 2923 DO 6. Data Register DO 6. Set-point on DO 6. Set-point off DO 6. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2928 2929 2930 2935 DO 7. Data Register DO 7. Set-point on DO 7. Set-point off DO 7. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2936 2937 2938 2939 DO 8. Data Register DO 8. Set-point on DO 8. Set-point off DO 8. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2.43 DI 1- DI 16 user text alarms configuration (AL No 232247) Register no Description DI 1 user text alarm : 2960 Priority 2961 Delay DI 2 user text alarm : 2962 Priority 2963 Delay DI 3 user text alarm : 2964 Priority 2965 Delay DI 4 user text alarm : 2966 Priority 2967 Delay DI 5 user text alarm : 2968 Priority 2969 Delay DI 6 user text alarm : 2970 Priority 2971 Delay DI 7 user text alarm : 2972 Priority 2973 Delay DI 8 user text alarm : 2974 Priority 2975 Delay DI 9 user text alarm : 2976 Priority 2977 Delay DI 10 user text alarm : 2978 Priority 2979 Delay DI 11 user text alarm : 2980 Priority 2981 Delay DI 12 user text alarm : 2982 Priority 2983 Delay DI 13 user text alarm : 2984 Priority 2985 Delay DI 14 user text alarm : 2986 Priority 2987 Delay DI 15 user text alarm : 2988 Priority 2989 Delay DI 16 user text alarm : 2990 Priority 2991 Delay Scale factor/ unit / note Alarm 232 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 233 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 234 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 235 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 236 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 237 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 238 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 239 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 240 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 241 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 242 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 243 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 244 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 245 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 246 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 247 0=Inactive, 1=B-alarm, 2=A-alarm s 2.44 Field bus alarms exp. modules (AL 248-252) Register no Description CA 442-5 Communication failure : 2992 Priority 2993 Delay CA 442-6 Communication failure : 2994 Priority 2995 Delay CA 781 Communication failure: 2996 Priority 2997 Delay CA 622 Communication failure: 2998 Priority 2999 Delay Main PM - CA 622 Modbus timeout: 2958 Priority 2959 Delay Scale factor/ unit / note Alarm 248 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 249 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 250 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 251 0=Inactive, 1=B-alarm, 2=A-alarm s Alarm 252 0=Inactive, 1=B-alarm, 2=A-alarm s 2.45 System alarms configuration Register no Description Scale factor/ unit / note Power fail : 3000 Priority 3001 Delay Alarm 1 0=Inactive, 1=B-alarm, 2=A-alarm s Low supply voltage : 3005 Priority 3006 Delay 3007 Limit 3008 Hysteresis Alarm 2 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 V 0.1 V NV Checksum error : 3010 Priority 3011 Delay Alarm 3 0=Inactive, 1=B-alarm, 2=A-alarm s Personal alarm 3015 Priority 3016 Delay 3017 Max time to reset Alarm 4 0=Inactive, 1=B-alarm, 2=A-alarm s min 2.46 Pit alarms configuration Register no Description Scale factor/ unit / note High level : 3020 Priority 3021 Delay 3022 Limit 3023 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.01 m (0.01 ft) 0.01 m (0.01 ft) Low level : 3025 3026 3027 3028 0=Inactive, 1=B-alarm, 2=A-alarm s 0.01 m (0.01 ft) 0.01 m (0.01 ft) Priority Delay Limit Hysteresis High level float : 3030 Priority 3031 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Low level float : 3035 Priority 3036 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s High inflow : 3040 Priority 3041 Delay 3042 Limit 3043 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) Low inflow : 3045 Priority 3046 Delay 3047 Limit 3048 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 l/s (1 GPM) 0.1 l/s (1 GPM) Backup running : 3050 Priority 3051 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Remote block : 3055 Priority 3056 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s High pressure : 3060 Priority 3061 Delay 3062 Limit 3063 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 bar (0.1 PSI) 0.1 bar (0.1 PSI) Low pressure : 3065 Priority 3066 Delay 3067 Limit 3068 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 bar (0.1 PSI) 0.1 bar (0.1 PSI) Overflow float : 3070 Priority 3071 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Register no Description High Back-Presure block: 3075 Priority 3076 Delay Scale factor/ unit / note 0=Inactive, 1=B-alarm, 2=A-alarm s Drain pump float: 3080 Priority 3081 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Sensor error : 3085 Priority 3086 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s No run confirm mixer : 3090 Priority 3091 Delay Motor protector mixer : 3095 Priority 3096 Delay 0=Inactive, 1=B-alarm, 2=A-alarm 0=Inactive, 1=B-alarm, 2=A-alarm s No run confirm drain pump : 3100 Priority 3101 Delay 0=Inactive, 1=B-alarm, 2=A-alarm Motor protector drain pump : 3105 Priority 3106 Delay 0=Inactive, 1=B-alarm, 2=A-alarm To many pump blocked : 3110 Priority 3111 Delay 3112 Limit 0=Inactive, 1=B-alarm, 2=A-alarm s Min no pumps available (0-4) Motor protector reset error Mixer/Drain pump : 3115 Priority 0=Inactive, 1=B-alarm, 2=A-alarm 3116 Delay s 2.47 Power alarms Register no Description Scale factor/ unit / note Wrong phase order : 3120 Priority 3121 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Incoming phase missing : 3125 Priority 3126 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Over voltage : 3130 Priority 3131 Delay 3132 Limit 3133 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 % 0.1 % Under voltage : 3135 Priority 3136 Delay 3137 Limit 3138 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 % 0.1 % Unbalanced voltage : 3140 Priority 3141 Delay 3142 Limit 3143 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 % 0.1 % High frequency : 3145 Priority 3146 Delay 3147 Limit 3148 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 % 0.1 % Low frequency : 3150 Priority 3151 Delay 3152 Limit 3153 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 % 0.1 % 2.48 Pump 1-4 alarms configuration Alarm Parameters No run confirm Delay Fallen motor protect. Delay High motor current Delay Limit Hysteresis Low motor current Delay Limit Hysteresis DIN leakage Delay DIN High temperat. Delay Low pump capacity Delay Limit Hysteresis DIN Pump error Delay Phase missing Delay M.prot reset error Delay Max contin. Runtime Delay Pump alarm blocked Delay Dry run Delay Pump not in auto Delay CA 622 com error Delay Drive fault Delay Al.Ack Resets Drive Register P1 3155 3156 3160 3161 3165 3166 3167 3168 3170 3171 3172 3173 3175 3176 3180 3181 3185 3186 3187 3188 3190 3191 3195 3196 3200 3201 3205 3206 3210 3211 3215 3216 3220 3221 3225 3226 3230 3231 3232 Register P2 3315 3316 3320 3321 3325 3326 3327 3328 3330 3331 3332 3333 3335 3336 3340 3341 3345 3346 3347 3348 3350 3351 3355 3356 3360 3361 3365 3366 3370 3371 3375 3376 3380 3381 3385 3386 3390 3391 3392 Register P3 3475 3476 3480 3481 3485 3486 3487 3488 3490 3491 3492 3493 3495 3496 3500 3501 3505 3506 3507 3508 3510 3511 3515 3516 3520 3521 3525 3526 3530 3531 3535 3536 3540 3541 3545 3546 3550 3551 3552 Register P4 3635 3636 3640 3641 3645 3646 3647 3648 3650 3651 3652 3653 3655 3656 3660 3661 3665 3666 3667 3668 3670 3671 3675 3676 3680 3681 3685 3686 3690 3691 3695 3696 3700 3701 3705 3706 3710 3711 3712 Scale factor/ unit / note Leakage oil chamber Delay Leakage con. Chamb Delay Leakage motor hous. Delay 3235 3236 3240 3241 3245 3246 3395 3396 3400 3401 3405 3406 3555 3556 3560 3561 3565 3566 3715 3716 3720 3721 3725 3726 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S CA622-PM com error Delay High temp. wirings Delay Limit Hysteresis H.temp up. Bearing Delay Limit Hysteresis 3250 3251 3255 3256 3257 3258 3260 3261 3262 3263 3410 3411 3415 3416 3417 3418 3420 3421 3422 3423 3570 3571 3575 3576 3577 3578 3580 3581 3582 3583 3730 3731 3735 3736 3737 3738 3740 3741 3742 3743 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0.1 °C (°F) 0.1 °C (°F) 0=Inactive, 1=B-alarm, 2=A-alarm S 0.1 °C (°F) 0.1 °C (°F) 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0.1 A 0.1 A 0=Inactive, 1=B-alarm, 2=A-alarm S 0.1 A 0.1 A 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0.1 l/s (GPM) 0.1 l/s (GPM) 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm S 0=No, 1=Yes H.temp lo. Bearing Delay Limit Hysteresis High vibrations Delay Limit Hysteresis Wrong phase order Delay H.temp stator L2 Delay H.temp stator L3 Delay CA 442-5/6 L2 Error Delay CA 442-5/6 L3 Error Delay 3265 3266 3267 3268 3270 3271 3272 3273 3274 3275 3280 3281 3285 3286 3290 3291 3295 3296 3425 3426 3427 3428 3430 3431 3432 3433 3435 3436 3440 3441 3445 3446 3450 3451 3455 3456 3585 3586 3587 3588 3590 3591 3592 3593 3595 3596 3600 3601 3605 3606 3610 3611 3615 3616 3745 3746 3747 3748 3750 3751 3752 3753 3755 3756 3760 3761 3765 3766 3770 3771 3775 3776 0=Inactive, 1=B-alarm, 2=A-alarm S 0.1 °C (°F) 0.1 °C (°F) 0=Inactive, 1=B-alarm, 2=A-alarm S 0.1 mm/s (0.01 Inch/s) 0.1 mm/s (0.01 Inch/s) 0=Inactive, 1=B-alarm, 2=A-alarm S 0=Inactive, 1=B-alarm, 2=A-alarm s (using H.temp wirings limit) 0=Inactive, 1=B-alarm, 2=A-alarm s (using H.temp wirings limit) Cable Error Extra temp. monitors Cable Error Extra temp. monitors 2.49 AI2 – AI5 user alarms configuration Register no Description AI 2 High alarm : 3795 Priority 3796 Delay 3797 Limit 3798 Hysteresis AI 2 Low alarm : 3800 Priority 3801 Delay 3802 Limit 3803 Hysteresis AI 3 High alarm : 3805 Priority 3806 Delay 3807 Limit 3808 Hysteresis AI 3 Low alarm : 3810 Priority 3811 Delay 3812 Limit 3813 Hysteresis Scale factor/ unit / note 0=Inactive, 1=B-alarm, 2=A-alarm s User unit and decimals 0=Inactive, 1=B-alarm, 2=A-alarm s User unit and decimals 0=Inactive, 1=B-alarm, 2=A-alarm s User unit and decimals 0=Inactive, 1=B-alarm, 2=A-alarm s User unit and decimals AI 4 High alarm : 3815 Priority 3816 Delay 3817 Limit 3818 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s User unit and decimals AI 4 Low alarm : 3820 Priority 3821 Delay 3822 Limit 3823 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s User unit and decimals AI 5 High alarm : 3825 Priority 3826 Delay 3827 Limit 3828 Hysteresis AI 5 Low alarm : 3830 Priority 3831 Delay 3832 Limit 3833 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s User unit and decimals 0=Inactive, 1=B-alarm, 2=A-alarm s User unit and decimals 2.50 Pulse channels 1-4 alarms configuration Register no Description Scale factor/ unit / note Ch 1 if precipitation selected : 3835 Priority 3836 Delay 3837 Limit 3838 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 l/s*ha (0.01 inch/h) 0.1 l/s*ha (0.01 inch/h) Ch 1 if energy selected : 3840 Priority 3841 Delay 3842 Limit 3843 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 kW 0.1 kW Ch1 if flow selected : High flow 3845 Priority 3846 Delay 3847 Limit 3848 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 m3/h (GPM) 0.1 m3/h (GPM) Ch1 if flow selected : Low flow 3850 Priority 3851 Delay 3852 Limit 3853 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 m3/h (GPM) 0.1 m3/h (GPM) Ch 2 if precipitation selected : 3855 Priority 3856 Delay 3857 Limit 3858 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 l/s*ha (0.01 inch/h) 0.1 l/s*ha (0.01 inch/h) Ch 2 if energy selected : 3860 Priority 3861 Delay 3862 Limit 3863 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 kW 0.1 kW Ch 2 if flow selected : High flow 3865 Priority 3866 Delay 3867 Limit 3868 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 m3/h (GPM) 0.1 m3/h (GPM) Ch 2 if flow selected : Low flow 3870 Priority 3871 Delay 3872 Limit 3873 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 m3/h (GPM) 0.1 m3/h (GPM) Ch 3 if precipitation selected : 3875 Priority 3876 Delay 3877 Limit 3878 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 l/s*ha (0.01 inch/h) 0.1 l/s*ha (0.01 inch/h) Register no Description Scale factor/ unit / note Ch 3 if energy selected : 3880 Priority 3881 Delay 3882 Limit 3883 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 kW 0.1 kW Ch 3 if flow selected : High flow 3885 Priority 3886 Delay 3887 Limit 3888 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 m3/h (GPM) 0.1 m3/h (GPM) Ch 3 if flow selected : Low flow 3890 Priority 3891 Delay 3892 Limit 3893 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 m3/h (GPM) 0.1 m3/h (GPM) Ch 4 if precipitation selected : 3895 Priority 3896 Delay 3897 Limit 3898 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 l/s*ha (0.01 inch/h) 0.1 l/s*ha (0.01 inch/h) Ch 4 if energy selected : 3900 Priority 3901 Delay 3902 Limit 3903 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 kW 0.1 kW Ch 4 if flow selected : High flow 3905 Priority 3906 Delay 3907 Limit 3908 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 m3/h (GPM) 0.1 m3/h (GPM) Ch 4 if flow selected : Low flow 3910 Priority 3911 Delay 3912 Limit 3913 Hysteresis 0=Inactive, 1=B-alarm, 2=A-alarm s 0.1 m3/h (GPM) 0.1 m3/h (GPM) 2.51 Communication alarms configuration Register no Description Scale factor/ unit / note CA 441-1 Communication failure 3915 Priority 3916 Delay Leakage monitor 0=Inactive, 1=B-alarm, 2=A-alarm s CA 441-2 Communication failure 3920 Priority 3921 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 441-3 Communication failure 3925 Priority 3926 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 441-4 Communication failure 3930 Priority 3931 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-1 Communication failure 3935 Priority 3936 Delay Temperature monitor 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-2 Communication failure 3940 Priority 3941 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-3 Communication failure 3945 Priority 3946 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-4 Communication failure 3950 Priority 3951 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 443-0 Communication failure 3955 Priority 3956 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 443-1 Communication failure 3960 Priority 3961 Delay Power monitor 0=Inactive, 1=B-alarm, 2=A-alarm s CA 443-2 Communication failure 3965 Priority 3966 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 443-3 Communication failure 3970 Priority 3971 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 443-4 Communication failure 3975 Priority 3976 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Register no Description Scale factor/ unit / note Modem error : 3980 Priority 3981 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Line error : 3985 Priority 3986 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s Combined field bus error : 3990 Priority 3991 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s 2.52 Sensor errors alarms Register no Description Scale factor/ unit / note CA 441-1 Sensor 1 error : 3995 Priority 3996 Delay Leakage monitor 1 0=Inactive, 1=B-alarm, 2=A-alarm s CA 441-1 Sensor 2 error : 4000 Priority 4001 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-1 Sensor 3 error : 4005 Priority 4006 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-1 Sensor 4 error : 4010 Priority 4011 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-2 Sensor 1 error : 4015 Priority 4016 Delay Leakage monitor 2 0=Inactive, 1=B-alarm, 2=A-alarm s CA 441-2 Sensor 2 error : 4020 Priority 4021 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-2 Sensor 3 error : 4025 Priority 4026 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-2 Sensor 4 error : 4030 Priority 4031 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-3 Sensor 1 error : 4035 Priority 4036 Delay Leakage monitor 3 0=Inactive, 1=B-alarm, 2=A-alarm s CA 441-3 Sensor 2 error : 4040 Priority 4041 Delay 0=Inactive, 1=B-alarm, 2=A-alarm Register no Description Scale factor/ unit / note CA 441-3 Sensor 3 error : 4045 Priority 4046 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-3 Sensor 4 error : 4050 Priority 4051 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-4 Sensor 1 error : 4055 Priority 4056 Delay Leakage monitor 4 0=Inactive, 1=B-alarm, 2=A-alarm s CA 441-4 Sensor 2 error : 4060 Priority 4061 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-4 Sensor 3 error : 4065 Priority 4066 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 441-4 Sensor 4 error : 4070 Priority 4071 Delay 0=Inactive, 1=B-alarm, 2=A-alarm CA 442-1 Sensor 1 error : 4075 Priority 4076 Delay Temperature monitor 1 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-1 Sensor 2 error : 4080 Priority 4081 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-1 Sensor 3 error : 4085 Priority 4086 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-1 Sensor 4 error : 4090 Priority 4091 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-2 Sensor 1 error : 4095 Priority 4096 Delay Temperature monitor 2 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-2 Sensor 2 error : 4100 Priority 4101 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-2 Sensor 3 error : 4105 Priority 4106 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-2 Sensor 4 error : 4110 Priority 4111 Delay 0=Inactive, 1=B-alarm, 2=A-alarm Register no Description Scale factor/ unit / note CA 442-3 Sensor 1 error : 4115 Priority 4116 Delay Temperature monitor 3 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-3 Sensor 2 error : 4120 Priority 4121 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-3 Sensor 3 error : 4125 Priority 4126 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-3 Sensor 4 error : 4130 Priority 4131 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-4 Sensor 1 error : 4135 Priority 4136 Delay Temperature monitor 4 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-4 Sensor 2 error : 4140 Priority 4141 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-4 Sensor 3 error : 4145 Priority 4146 Delay 0=Inactive, 1=B-alarm, 2=A-alarm s CA 442-4 Sensor 4 error : 4150 Priority 4151 Delay Alarm 231 0=Inactive, 1=B-alarm, 2=A-alarm s 2.53 Field bus modules configuration Register no Description Scale factor/ unit / note 4172 CA 441-1 Connections 0=4 pumps / P1 Leakage monitor 4174 CA 442-1 Connections 0=4 pumps / P1 Temperature monitor 4170 Field bus flags Modules connected. Bit mapped register, See IO-bits. CA 441-1 Leakage monitor P1 or P1-P4 4180 Sensor 1 type 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 4181 Sensor 2 type 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 4182 Sensor 3 type 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 4183 Sensor 4 type 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt CA 441-2 Leakage monitor P2 4185 Sensor 1 type 4186 Sensor 2 type 4187 Sensor 3 type 4188 Sensor 4 type 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt CA 441-3 Leakage monitor P3 4190 Sensor 1 type 4191 Sensor 2 type 4192 Sensor 3 type 4193 Sensor 4 type 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt CA 441-4 Leakage monitor P4 4195 Sensor 1 type 4196 Sensor 2 type 4197 Sensor 3 type 4198 Sensor 4 type 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt 0=Off/1=ABS-Standard/2=ABS extended/3=ITT Flygt CA 442-1 Temperature monitor P1 or P1-P4 4210 Sensor 1 type 0=Off/1=Klixon/2=PTC/3=Pt100 4211 Temperature offset 0.1 °C (°F) ( Pt100) 4213 Filter constant s ( Pt100) 4215 4216 4217 Sensor 2 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4220 4221 4222 Sensor 3 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4225 4226 4227 Sensor 4 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100/4=Vibrations 0.1 °C ( Pt100) s ( Pt100) 4230 4231 4232 4233 4234 4235 Sensor 5 type Not used Filter constant Scale 0%= Scale 100%= Nominal Vibration mA Input. 0=Off/4=Vibrations s 0.1 mm/s (0.01 Inch/s) (Vibrations) 0.1 mm/s (001 Inch/s) (Vibrations) 0.1 mm/s (0.01 Inch/s) CA 442-2 Temperature monitor P2 4240 Sensor 1 type 4241 Temperature offset 4242 Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4245 4246 4247 Sensor 2 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4250 4251 4252 Sensor 3 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4255 4256 4257 Sensor 4 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s 4260 4261 4262 4263 4264 4265 Sensor 5 type Not used Filter constant Scale 0%= Scale 100%= Nominal vibrations mA Input. 0=Off/4=Vibrations s 0.1 mm/s (0.01 Inch/s) 0.1 mm/s (0.01 Inch/s) 0.1 mm/s (0.01 Inch/s) CA 442-3 Temperature monitor P3 4270 Sensor 1 type 4271 Temperature offset 4272 Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4275 4276 4277 Sensor 2 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4280 4281 4282 Sensor 3 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4285 4286 4287 Sensor 4 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100/4=Vibrations 0.1 °C ( Pt100) s ( Pt100) 4290 4291 4292 4293 4294 4295 Senor 5 type Not used Filter constant Scale 0%= Scale 100%= Nominal vibrations mA Input. 0=Off/4=Vibrations s 0.1 mm/s (0.01 Inch/s) (Vibrations) 0.1 mm/s (0.01 Inch/s) (Vibrations) 0.1 mm/s (0.01 Inch/s) CA 442-4 Temperature monitor P4 4300 Sensor 1 type 4301 Temperature offset 4302 Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4305 4306 4307 Sensor 2 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4310 4311 4312 Sensor 3 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100 0.1 °C ( Pt100) s ( Pt100) 4315 4316 4317 Sensor 4 type Temperature offset Filter constant 0=Off/1=Klixon/2=PTC/3=Pt100/4=Vibrations 0.1 °C ( Pt100) s ( Pt100) 4320 4321 4322 4323 4324 4325 Sensor 5 type Not used Filter constant Scale 0%= Scale 100%= Nominal vibrations mA Input. 0=Off/4=Vibrations s 0.1 mm/s (0.01 Inch/s) 0.1 mm/s (0.01 Inch/s) 0.1 mm/s (0.01 Inch/s) CA 443-0 Main Power Monitor 4330 Current transformers connected to 4331 Current transformers secondary current 4332 Current transformers nominal current 4333 Current offset 4334 Current Dead band 4335 Filter constant 4336 Phase angle compensation 4340 4341 4342 4343 4344 4345 Phase voltages connected Ext. voltages transformers connected Primary voltage Secondary voltage Offset Voltage Filter Constant CA 443-1 Power Monitor P1 4350 Current transformers connected to 4351 Current transformers secondary current 4352 Current transformers nominal current 4353 Current offset 4354 Current Dead band 4355 Filter constant 4356 Phase angle compensation 4360 4361 4362 4363 4364 4365 Phase voltages connected Ext. voltages transformers connected Primary voltage Secondary voltage Offset Voltage Filter Constant 0=None,1=L1, 2=L1,L2, 3=L1,L2, L3 0.1 A 0.1 A 0.1 A 0.1% 1s 0.1° 0=None, 1=L1, 2=L1,L2, 3=L1,L2,L3 0=None, 1=Yes 1V 1V 0.1V 1s 0=None,1=L1, 2= L1,L2, 3=L1,L2, L3 0.1 A 0.1 A 0.1 A 0.1% 1s 0.1° 0=None, 1=L1, 2=L1,L2 3= L1,L2,L3 0=None, 1=Yes 1V 1V 0.1V 1s CA 443-2 Power Monitor P2 4370 Currents transformers connected to 4371 Current transformers secondary current 4372 Current transformers nominal current 4373 Current offset 4374 Current Dead band 4375 Filter constant 4376 Phase angle compensation 4380 4381 4382 4383 4384 4385 Phase voltages connected Ext. voltages transformers connected Primary voltage Secondary voltage Offset Voltage Filter Constant CA 443-3 Power Monitor P3 4390 Currents transformers connected to 4391 Current transformers secondary current 4392 Current transformers nominal current 4393 Current offset 4394 Current Dead band 4395 Filter constant 4396 Phase angle compensation 4400 4401 4402 4403 4404 4405 Phase voltages connected Ext. voltages transformers connected Primary voltage Secondary voltage Offset Voltage Filter Constant CA 443-4 Power Monitor P4 4410 Currents transformers connected to 4411 Current transformers secondary current 4412 Current transformers nominal current 4413 Current offset 4414 Current Dead band 4415 Filter constant 4416 Phase angle compensation 4420 4421 4422 4423 4424 4425 Phase voltages connected Ext. voltages transformers connected Primary voltage Secondary voltage Offset Voltage Filter Constant 0=None,1=L1, 2=L1,L2 3=L1,L2, L3 0.1A 0.1 A 0.1 A 0.1% 1s 0.1° 0=None, 1=L1, 2=L1,L2, 3=L1,L2,L3 0=None, 1=Yes 1V 1V 0.1V 1s 0=None,1=L1, 2=L1,L2, 3=L1,L2,L3 0.1 A 0.1 A 0.1 A 0.1% 1s 0.1° 0=None, 1=L1, 2=L1,L2 3=L1,L2,L3 0=None, 1=Yes 1V 1V 0.1V 1s 0=None,1=L1, 2=L1,L2, 3= L1,L2, L3 0.1A 0.1 A 0.1 A 0.1% 1s 0.1° 0=None, 1=L1, 2=L1,L2, 3=L1,L2,L3 0=None, 1=Yes 1V 1V 0.1V 1s 2.54 Com port configuration Register no Description Service port: 4430 Baudrate Com port: 4432 Baudrate 4433 Parity 4434 Protocol 4435 Handshake 4436 Protocol id 4437 Message timeout 4438 Cross reference 4439 Com port echo Scale factor/ unit / note 0=Off/ 1= 300/2=600 ….10=115200 0=Off/ 1= 300/2=600 ….10=115200 0=None/1=Odd/2=Even 0=Modbus/ 1=Comli/ 2=Modbus TCP 0=Off/1=On s 0=Off, 1=Enabled 0=Off, 1=On 2.55 Modem configuration Register no 4440 4441 4442 4443 4444 4445 4446 Description Scale factor/ unit / note Modem connected to port No signal to answer GPRS TCP/IP port GPRS Heart Beat GPRS SMS Fallback Heart Beat Operator scan Trig modem init 0=None /1=Dial up/2=GPRS CA521/3=GPRS TCP-IP LISTEN min 0=Off / 1=On 0=Off / 1=On Write 1 to trig hayes init script for analogue and GSM modems 2.56 Alarm call configuration Register no 4450 4451 4452 4453 Description Scale factor/ unit / note No call attempts/alarm Ackn. call function 0=No ackn./1=Ring sign/2=Write to R333/3=All com Ackn. alarm R333 0=No / 1=Yes Interval between call attempts s 2.57 Call attempts configuration Register no Description Call attempts 1 : 4460 4461 4462 4463 4464 4465 Alarm receiver Condition for alarm call Send ID-String on connect Timeout alarm ackn. ID–String transmit delay Call order Call attempts 2 : 4470 4471 4472 4473 4474 4475 Alarm receiver Condition for alarm call Send ID-String on connect Timeout alarm ackn. ID–String transmit delay Call order Call attempts 3 : 4480 4481 4482 4483 4484 4485 Alarm receiver Condition for alarm call Send ID-String on connect Timeout alarm ackn. ID–String transmit delay Call order Scale factor/ unit / note 0=Off /1=Central System/2=SMS GSM 0=A-alarm On/1=A-alarm On/Off /2=A+B On /3=A+B On/Off 0=No / 1=Yes s s 0=Backup number, 1=Parallel call 0=Off /1=Central System/2=SMS GSM 0=A-alarm On/1=A-alarm On/Off /2=A+B On /3=A+B On/Off 0=No / 1=Yes s s 0=Backup number, 1=Parallel call 0=Off /1=Central System/2=SMS GSM 0=A-alarm On/1=A-alarm On/Off /2=A+B On /3=A+B On/Off 0=No / 1=Yes s s 0=Backup number, 1=Parallel call Call attempts 4 : 4490 4491 4492 4493 4494 4495 Alarm receiver Condition for alarm call Send ID-String on connect Timeout alarm ackn. ID–String transmit delay Call order 0=Off /1=Central System/2=SMS GSM 0=A-alarm On/1=A-alarm On/Off /2=A+B On /3=A+B On/Off 0=No / 1=Yes s s 0=Backup number, 1=Parallel call 2.58 PID Regulator Register no Description Runtime Settings 220 221 222 223 224 Scale factor/ unit / note Current set-point Process value Output signal Set-point flags Output flags 0.01m (0.01ft) 0.01m (0.01f)t 0.1% 0=Intern set-point, 1 = Extern set-point (AI) 0=Auto, 1=Manuel, 2=Blocked Extern set-point input Max set-point Min set-point Start set-Point Max output Min output Block output Zero dev. output Start output Max output change Direct/Reverse effect Set-point tracking Output when blocked Set-point when start Output state when start 0=Off, 1=AI2, 2=AI3, 3=AI4, 4=AI5 0.01m (0.01ft) 0.01m (0.01ft) 0.01m (0.01ft) 0.1% 0.1% 0.1% 0.1% 0.1% 0.1% / s 0=Reverse, 1=Direct 0=No, 1=Yes 0=Freeze output, 1=Setup block signal 0=Last set-point, 1=Setup start set-point, 2= Extern set-point 0=Last state, 1=Auto, 2=Man , 3=Internal blocked P-Band I-Time D-Time 0- 99.9999 0- 9999.99 s 0- 9999.99 s Last internal set-point Last output state Last set-point state 0.01m (0.01ft) 0=Auto, 1=MAN , 2=Internal Blocked 0=Internal set-point, 1=RSP Settings 4503 4504 4505 4506 4507 4508 4509 4510 4511 4512 4513 4514 4515 4516 4517 4520-4521 4522-4523 4524-4525 4531 4532 4533 VFD 4527 4528 4529 4530 Min speed 0.1% Locked speed pumping out 0.1% Lock speed delay s Locked speed reversing 0.1% (v1.35) CA 622 Modbus Master RS 485 unit 4608 4609 4610 4611 Modbus RS 485 baudrate Modbus RS 485 parity Poll interval Message timeout 0=None, 1=Odd, 2=Even, 3=Mark Main Power Monitor : 4612 Slave Brand 4613 Slave Model 4614 Slave ID Default 5 P1 Drive: 4616 4617 4618 4619 Slave Brand Slave Model Slave ID Control mode Default 1 0=monitor, 1=&control ON/OFF, 2=&manual Speed, 3=&PID P2 Drive: 4620 4621 4622 4623 Slave Brand Slave Model Slave ID Control mode Default 2 0=monitor, 1=&control ON/OFF, 2=&manual Speed, 3=&PID P3 Drive : 4624 4625 4626 4627 Slave Brand Slave Model Slave ID Control mode Default 3 0=monitor, 1=&control ON/OFF, 2=&manual Speed, 3=&PID P4 Drive : 4628 4629 4630 4631 Slave Brand Slave Model Slave ID Control mode Default 4 0=monitor, 1=&control ON/OFF, 2=&manual Speed, 3=&PID P1 Power Monitor : 4632 Slave Brand 4633 Slave Model 4634 Slave ID Default 6 P2 Power Monitor : 4636 Slave Brand 4637 Slave Model 4638 Slave ID Default 7 P3 Power Monitor : 4640 Slave Brand 4641 Slave Model 4642 Slave ID Default 8 P4 Power Monitor : 4644 Slave Brand 4645 Slave Model 4646 Slave ID Default 9 2.59 Overlayed Digital out parameters CA 781 Digital output type CA 781: Logic IO configuration Register no Description Scale factor/ unit / note 4540 4541 4542 4543 4544 4545 4546 4547 DO 1. Sign.1 type DO 1. Sign.1 IO no DO 1. Sign.2 type DO 1. Sign.2 IO no DO 1. Sign.3 type DO 1. Sign.3 IO no DO 1. Sign.4 type DO 1. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 4548 4549 4550 4551 4552 4553 4554 4555 DO 2. Sign.1 type DO 2. Sign.1 IO no DO 2. Sign.2 type DO 2. Sign.2 IO no DO 2. Sign.3 type DO 2. Sign.3 IO no DO 2. Sign.4 type DO 2. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 4556 4557 4558 4559 4560 4561 4562 4563 DO 3. Sign.1 type DO 3. Sign.1 IO no DO 3. Sign.2 type DO 3. Sign.2 IO no DO 3. Sign.3 type DO 3. Sign.3 IO no DO 3. Sign.4 type DO 3. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 4564 4565 4566 4567 4568 4569 4570 4571 DO 4. Sign.1 type DO 4. Sign.1 IO no DO 4. Sign.2 type DO 4. Sign.2 IO no DO 4. Sign.3 type DO 4. Sign.3 IO no DO 4. Sign.4 type DO 4. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 4572 4573 4574 4575 4576 4577 4578 4579 DO 5. Sign.1 type DO 5. Sign.1 IO no DO 5. Sign.2 type DO 5. Sign.2 IO no DO 5. Sign.3 type DO 5. Sign.3 IO no DO 5. Sign.4 type DO 5. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 4580 4581 4582 4583 4584 4585 4586 4587 DO 6. Sign.1 type DO 6. Sign.1 IO no DO 6. Sign.2 type DO 6. Sign.2 IO no DO 6. Sign.3 type DO 6. Sign.3 IO no DO 6. Sign.4 type DO 6. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO Register no Description Scale factor/ unit / note 4588 4589 4590 4591 4592 4593 4594 4595 DO 7. Sign.1 type DO 7. Sign.1 IO no DO 7. Sign.2 type DO 7. Sign.2 IO no DO 7. Sign.3 type DO 7. Sign.3 IO no DO 7. Sign.4 type DO 7. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 4596 4597 4598 4599 4600 4601 4602 4603 DO 8. Sign.1 type DO 8. Sign.1 IO no DO 8. Sign.2 type DO 8. Sign.2 IO no DO 8. Sign.3 type DO 8. Sign.3 IO no DO 8. Sign.4 type DO 8. Sign.4 IO no 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO 0=Off/ 1=True OR 2=Inv OR 3=True AND 4=Inv AND Modbus / Comli IO Digital output type CA 781: Data Register Setpoint Register no 4540 4541 4542 4543 Description Scale factor/ unit / note DO 1. Data Register DO 1. Set-point on DO 1. Set-point off DO 1. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 4548 4549 4550 4551 DO 2. Data Register DO 2. Set-point on DO 2. Set-point off DO 2. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 4556 4557 4558 4559 DO 3. Data Register DO 3. Set-point on DO 3. Set-point off DO 3. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 4560 4561 4562 4563 DO 4. Data Register DO 4. Set-point on DO 4. Set-point off DO 4. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 4572 4573 4574 4575 DO 5. Data Register DO 5. Set-point on DO 5. Set-point off DO 5. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 4580 4581 4582 4583 DO 6. Data Register DO 6. Set-point on DO 6. Set-point off DO 6. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 4588 4589 4590 4591 DO 7. Data Register DO 7. Set-point on DO 7. Set-point off DO 7. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 4596 4597 4598 4599 DO 8. Data Register DO 8. Set-point on DO 8. Set-point off DO 8. Set-point delay Source value register number 0-4529 0-65535 0-65535 seconds 2.60 Register Cross Reference Config 13312 13313 13314 13315 … 13822 13823 Cross reference for Data register 0 Scale factor and sign flag for Data register 0 Cross reference for Data register 1 Scale factor and sign flag for Data register 1 Cross reference for Data register 254 Scale factor and sign flag for Data register 254 2.61 IO Cross Reference Config 13824 13825 … 14079 Cross reference for IO bit 0 Cross reference for IO bit 1 Cross reference for IO bit 255 2.62 Get log data ch1-ch16 Ch1 start at base address R16384 (4000H) Ch2 start at base address R18432 (4800H) Ch3 start at base address R20480 (5000H) Ch4 start at base address R22528 (5800H) Ch5 start at base address R24576 (6000H) Ch6 start at base address R26624 (6800H) Ch7 start at base address R28672 (7000H) Ch8 start at base address R30720 (7800H) Ch9 start at base address R32768 (8000H) Ch10 start at base address R34816 (8800H) Ch11 start at base address R36864 (9000H) Ch12 start at base address R38912 (9800H) Ch13 start at base address R40960 (A000H) Ch14 start at base address R43008 (A800H) Ch15 start at base address R45056 (B000H) Ch16 start at base address R47104 (B800H) Register no Description Scale factor/ unit / note Base + 0 Base + 1 Base + 2 Base + 3 Base + 4 Base + 5 Base + 6 Base + 7 Base + 8 Base + 9 Base +10 Base +11 Base +12 Base +13 . . Base + 1451 Day (block) select No logged days No logged values in block Log signal in block Log object no No decimals Log interval in block Log function in block Year in block Month in block Date in block Time for activate block First logged value Second logged value 0-15, 0=Today,1=Yesterday/2=2 days ago ….15 0-16 Last logged value * 0=Level/1=Inflow….. ** 0-3 0-4 min 0=Closed/1=Act. value/2=Average val/3=Min/4=Max 1-12 1-32 0 = 00:00/1=00:01/2=00:02…1439=23:59 (Interval=1min) 00:00-00:01 ( 1 min interval) 00:01-00:02 23:59-24:00 (1 min interval) * See appendics 3.5 Log and trend signals ** Log object no : Signal type : 7,8,9,10,11,12,13,19,20 Select logged pump P1–P4 , P1=0… P4=3 Signal type : 16 Free choice, Select logged signal AI2-AI5, AI2=0 Signal type : 18 Pulse channel., Select channel CH1-CH4, CH1=0 3 Appendics 3.1 Type no. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Digital input types Function DI Off Run indication (P1-P4) Register setup choose between P1,P2,P3 or P4 Manuel start (P1-P4) Pump not in auto (P1-P4) Start float (P1-P4) Pump failure (P1-P4) Motor protector (P1-P4) High temperature (P1-P4) Leakage (P1-P4) Stop float P1,P2,P3 and P4 Low level float Overflow float High level float Start float drain pump Run indicator drain pump Motor protector drain pump Run indicator mixer Motor protector mixer Local mode Alarm reset Power fail DI pulse channel 1 Only DI 13/14/15/16 DI pulse channel 2 Only DI 13/14/15/16 DI pulse channel 3 Only DI 13/14/15/16 DI pulse channel 4 Only DI 13/14/15/16 Block PID Controller Alarm input (free alarm text) Mixer block (free alarm text) Drain Pump block (free alarm text) 3.2 Type no. Function 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 DO Off Pump control (P1-P4) Register setup choose between P1,P2,P3 or P4 Reset motor protector (P1-P4) Pump fail (P1-P4) Not enough pumps available One pump fail P1,P2,P3 or P4 Master reset motor protectors Mixer control Reset motor protector mixer Drain pump control Reset motor protector drain pump Cleaner control Modem control Remote control Personal alarm High level Alarm alert Not ackn. A-alarm Not ackn. A/B-alarm Active A-alarm Active A/B-alarm Pump Reversing (P1-P4) Not Ackn. B-alarm Active B-alarm Logic IO Data Register Setpoint 3.3 Type no. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Digital output types Analogue inputs types Function AI Off Pit level 0.01m (AI 1) Current P1 0.1A (AI 2-5) Current P2 0.1A (AI 2-5) Current P3 0.1A (AI 2-5) Current P4 0.1A (AI 2-5) Back-Pressure 0.1 bar (AI 2-5) Free Choice User (AI 2-5 ) Vibrations P1 0.1 mm/s (AI 2-5) Vibrations P2 0.1 mm/s (AI 2-5) Vibrations P3 0.1 mm/s (AI 2-5) Vibrations P4 0.1 mm/s (AI2-5) ITT MiniCas Sim. P1 (AI 2-5) ITT MiniCas Sim. P2 (AI 2-5) ITT MiniCas Sim. P3 (AI 2-5) ITT MiniCas Sim. P4 (AI 2-5) Outflow meter (AI 2-5) 3.4 Type no. Analogue outputs types Function 0 1 2 3 4 5 6 7 8 9 10 AO Off Pit level Inflow Outflow Overflow Pulse channel 1 Pulse channel 2 Pulse channel 3 Pulse channel 4 PID Controller output Data Register 3.5 Log and Trend signals Default =unsigned (0-65535) data. Possible negative data as 2-complement. Type no. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 Function Scale/Note Closed Level pit 0.01 m 2-complement Inflow 0.1 l/s Outflow 0.1 l/s Overflow level 0.001 m Overflow flow 0.1 l/s Back-Pressure 0.1 bar Motor current P1-P4 0.1 A Register choose between P1,P2,P3 or P4 Pump capacity P1-P4 0.1 l/s “ Power factor P1-P4 0.01 “ Temp. stator wiring P1-P4 0.1 °C 2-complement Temp. upper bearing P1-P4 0.1 °C “ Temp. lower bearing P1-P4 0.1 °C “ Vibration P1-P4 0.1 mm/s Main voltage 0.1 V Main frequency 0. 1Hz Free choice AI2-AI5 User choice 2-complement Power supply 0.1 V Pulse channel 1-4 0.1 l/s*ha / 0. 1kW Temp. stator wiring L2 P1-P4 0.1 °C 2-complement Temp. stator wiring L3 P1-P4 0.1 °C 2-complement PID regulator out 0.1 % Data register