Four Zone 2-Wire Conventional Fire Alarm Panel
Product Overview:
Head Office
Wellington
Pertronic Industries F4-3 2W is a four-zone 2-Wire Fire Alarm control unit designed for low cost, Housing NZ Fire
Alarm systems.
The F4-3 2W is modified to meet Housing NZ requirements for small residential applications and meets most
requirements of NZS 4512:2010.
The F4-3 2W supports Pertronic Indicating Manual Call-Points, Indicating Heat Detectors, PS1 sounders and
System Sensor Smoke Detectors with the facility to internally mount one or two 20W Evacuation amplifiers.
PO Box 35-063
Naenae, 5011
Standard Features:
Lower Hutt
‘Normal’, ‘Defect’ and per circuit ‘Fire’ indication on front panel
17 Eastern Hutt Rd
‘Internal Bell Cut-Off’ and ‘External Bell Cut-Off’ (BCO)
Wingate
Alarm reset available from a front panel key-switch
Lower Hutt 5019
Trial Evacuation key-switch
Tel (04) 567-3229
Local or remote Hush button option temporarily silences sounders
Fax (04) 567-3644
for 2 minutes
www.pertronic.co.nz
sales@pertronic.co.nz
tech@pertronic.co.nz
Auckland Office
Detectors are automatically reset at end of the Hush period
Combined Detector and Sounder Circuit: monitored with a 10kΩ
EOL resistor
The combined Sounder and Detector circuit support a mix of
System Sensor 2WTA-B Smoke/Thermal Detectors with in-built
sounder, System Sensor 1151, 2151 Smoke detectors, Pertronic
indicating Heat Detectors and indicating Manual Call-Points and
Pertronic PS1 sounders and strobes
Fire & Defect C/O relays with Fire relay Isolate switch
Automatic Alarm Verification Facility (AVF) provides substantial
protection against transient false alarm activation
Monitored Bell circuit with up two (2) 100VRMS line amplifiers with
voiced Evacuation message
‘Battery Absent’ detection circuitry
Earth Leakage monitoring
Integrated piezo alarm and ‘Piezo on Defect’ warning
System ‘Defect’ LED indicates source of fault
Door Interlock
Brigade ‘Isolate’ and ‘Test’ switches
Electrically isolated interface to an alarm transmitter (SGD)
‘Bell Only’ configuration available (on Circuit 4) to monitor DBA
Fire Alarm Operating Instructions
Fire Alarm Activation
When the Fire Alarm panel activates:
- the fire sounders will sound
- the red ‘Fire’ indicator will flash on the zone(s) in ‘Alarm’ on the panel
a) If the Alarm is a genuine fire:
- Evacuate the building.
- Call 111 and ask for the Fire Service.
b) If the Alarm is a false alarm (eg. burnt toast, steam, etc.)
- push the fire alarm HUSH button(s) to silence the sounders
- investigate the source of the Alarm condition. Open windows to allow smoke/steam to disperse.
If the alarms resound, due to a false alarm, push the HUSH button again for a further silence period.
If the alarms continue to resound after two Hush periods call your fire alarm service company.
When the DEFECT light activates:
In the event of a defect on the system:
- the ‘Defect’ indicator will flash
- the internal buzzer sounds to indicate a system defect
- call your fire alarm service company .
2W Panel NZ Issue 3, 200703
Housing New Zealand: Call 0800 801-601 to request assistance
PO Box 15-867
New Lynn
Auckland 0640
359 Onehunga Mall
Onehunga
Detector Circuits
Auckland 1061
Four (4) zones terminated with 10kΩ EOL resistors
Tel (09) 633-0226
Accepts a mix of Smoke Detectors, indicating Heat Detectors and indicating Manual Call-Points
Fax (09) 633-0228
Smoke detectors operate after a 1 second Alarm Verification Facility (AVF) delay
Indicating Heat detectors and indicating Manual Call-Points give instantaneous (< 0.5 sec) response
Zone circuit self-test on start-up and every 24 hours
Up to 40 System Sensor Series 100 detectors, fitted to B401R relay bases, may be connected to each zone
circuit with up to five (5) Pertronic indicating Heat Detectors and indicating Manual Call-Points
Sounder Circuit
Bell circuit Relay: 12Vdc, 5A. - monitored with a 10kΩ EOL resistance
Recommended Sounders: 2WTA-B Detector-Sounder or Pertronic PS1 Sounder
Alternative Sounder : one or two Pertronic EVAC20W12V Amplifiers
Recommended Speakers : Pertronic PSSB401 Speaker Bases and/or Pertronic PSS1 Speakers
Optional Features:
Front or Rear Service cabinet
Compatible with Pertronic SGD7 or SGD8 for Fire Brigade connection
Specifications
Electrical:
Battery
ISO 9001: 2008
International Standards
Certifications
QAC/R64/0012
Environmental:
Mechanical:
Cabinet: FS or RS
Power Supply
230Vac, 50Hz, 5W
13.7Vdc, 275mA.
Quiescent Current
28mA at 12Vdc
Defect Current
30mA at 12Vdc
Alarm Current
135mA at 12Vdc
- plus Sounder load
Battery Charger
Integral Float Charger
13.7Vdc, 250mA
Battery Type
Sealed lead acid (gelcell)
12Vdc, 7AHr - internally mounted
Operating Temperature Range
0 to +40 oC
Humidity
10 to 95% RH (non-condensing)
Dimensions
(H x W x D mm)
350 x 245 x 80
Weight
2.2Kg
- excluding battery
Material
1.2mm mild steel,
powder coated
Colour
Beige
- other colours optional
Power Supply Timer: Automatic 24-Hour load test with automatic ‘Battery Absent’ detection circuitry.
0011-F4-3 2W Four Zone 2-Wire Conventional Fire Alarm Panel Iss 12, 201205
Benefits:
1. The F4-3 2W and its detectors provide a cost effective solution for residential applications.
2. Installation is made simple as the detectors and sounders are wired on the same pair of cables.
3. The sounders and detectors are fully monitored for open and short circuits.
4. Long battery standby period of up to 7 days.
5. The detectors (2WTA-B) have two detection elements (Smoke / Thermal) with built in sounder.
6. Reduced false alarms due to environmental conditions. The 2WTA-B detector sensitivity is automatically adjusted to compensate
for contamination caused by environmental conditions such as dust and dirt.
7. Optional Local or remote Hush button facility enables sounders to be silenced for 3 minutes allowing investigation of alarm.
8. Hush facility may be operated globally and/or per zone
9. Detectors automatically resets at end of the Hush period.
10. Panel Silence and Evacuate facility.
System Wiring:
Link MJ5 Fitted
REMOVE LINK
FOR COMMS
LED8
K17
0V
+5
+13.7
INSERT FOR
DEFECT BUZZER
K3
LED9
MJ2
TP1
LED2
Normal
DEFECT
MJ3
Defect
PERTRONIC
INDUSTRIES
FACTORY
TEST
+5
K2
10
9
TP2
T.E.
Common
10
9
LED1
F4 MASTER BOARD
V4.10 07/06
K1
HS1
FAULT DECODE
1. CCT 1
2. CCT 2
3. CCT 3
4. CCT 4
5. BELL FAULT
6. COMMS ERR
7. BATTERY
8. 20 VOLTS
9. EARTH
10. ROM ERROR
FIRE
1
LED10
VREG2
LED4
U1
2
LED11
LED5
RLY2
K4
RLY1
4
2
3
SGD
MJ4
LED13 LED7
4
INSERT FOR
DBA on CCT4
Bell Monitoring
0V
SW3
Ext Interlock
MJ1
K7
+20
TP3
DISABLE
ENABLE
TP5
+ 1 M
+ 2 M
+ 3 M
+ 4 M (DBA) NORMAL NORMAL
+
+
+
+
K6
S1
SW2
1A
FUSE2
SW1
FUSE1
1
COM
TEST
ISOL
DEF
FIRE
LED12 LED6
VR1
5A
Fire
2
1
K9
TP4
0V
BCO
LED3
NORMAL
MJ5
RD
TD
2
1
DOOR
18V
AC
RESET
K8
DB#0011
PN#PBF4
K11
(+)BELLS(-)
K10
Battery
+
BCO Ext I/Lock
ISOL.
1
M
2
M
Global Hush
3
M
4
M (DBA)
TEST
ATS USE ONLY!
Zonal Hush
10k
EOL
F4-2W Connection 20070129
2-Wire Detector/Sounder Circuit
10k
EOL
Product Codes
NZS Code
F4RS-3 2W
F4FS-3 2W
F4-2W
2WTA-B
1151
2151
B401R
Description
NZS Code
F4 RS Panel with 4-Zone Reversal Relay board
F4 FS Panel with 4-Zone Reversal Relay board
F4-2W board
2W-B, 2 Wire PE I3 Detector + Thermal and Sounder
1151 Low Pro Ion Detector excl Base
2151 Low Pro Photo Detector excl Base
B401R 2-wire base with current limiting resistor.
EVAC20W12V
PSS1-R
PS1-R
SR
AMRH
IHDB-3
CPPIN-3
Description
Evacuation Amplifier 20W, 12V, NZS4512:2010
Pertronic Sounder Speaker 1W Flush Red
Pertronic Sounder AS2220 Flush- Red
SpectrAlert Advance 2 Wire Strobe 12/24V
Remote Hush Unit
Indicating Heat Detector, Blue (57°C)
Conventional Indicating Call-Point
PERTRONIC INDUSTRIES LTD
Head Office:
17 Eastern Hutt Rd, Wingate, Lower Hutt 5019
Telephone (04) 567-3229 Fax (04) 567-3644
www.pertronic.co.nz
sales@pertronic.co.nz
tech@pertronic.co.nz