909e Series 2/4 Zone Panel Operating and Configuration Manual Version V01 CONTROLS & INDICATIONS • • • FIRE indication per zone. The zone led will flash on non-silenced zones and be continuously lit on silenced zones. FAULT indication per zone. Pulses once to show detector removed, twice for open circuit and three times for short circuit. Also when lit continuously indicates zone disabled. SUPPLY HEALTHY led. Extinguished for a supply fault, (internal normal/standby supply fault green/red LED's). Supply faults include, 1. Main supply failure 2. Battery open circuit 3. Battery volts low 4. Earth fault to -ve 5. Earth fault to +ve • • • • • • • • • • • Green & Red led's OFF Red led OFF-Green led ON Red led OFF-Green led ON (Supply Healthy led pulses twice.) (Supply Healthy led pulses three times.) COMMON FAULT led. Lights for any fault, pulses twice for supply fault. SOUNDER FAULT led. Pulses twice for open circuit and three times for short circuit faults on the common sounder circuits (if fitted). Continuously lit indicates disablement of all common and sav-wire sounders, (this can only be done in test mode). For fault indications this nonlatching in normal conditions, but latches when there is a fire. In test mode the led pulses to show which circuit is faulty. Once for circuit 1, twice for circuit 2 and three times if both circuits are faulty. INTERNAL FAULT led. (Latching fault indication if the microprocessor is reset due to power failure, fails a watchdog test or fails a memory check). The processor will try to restart after a fault, but if it fails a memory check twice in a row then it will STOP in it's safe state, and the panel will be inoperable. AUXILIARY ISOLATED. Indication that auxiliary relays have been disabled in the event of a fire or fault. SILENCE-RESOUND ALARM. Push button that silences sounders or resounds them, when in fire. MUTE BUZZER. Push button that silences fault buzzer when in fault condition. Pressing and holding this button performs a lamp test. This button is also used to scroll zones for isolate mode. May also be used to silence the buzzer when in fire after the sounders have been silenced. EVACUATE. Push button control. Operation is exactly the same as if it was a fire zone and the push button initiated a fire. Remote evacuate is identical except it is non-latching and doesn’t operate the aux. relay or the fire led. RESET. This resets the panel and detectors, unless the panel is in fire condition and the sounders have not yet been silenced. During the reset sequence the panel lights all the LED's and sounds the internal buzzer. This has a timed 5 second reset pulse to ensure proper resetting of heads even for short blips of the button. This reset procedure may also occur for INTERNAL faults, POWER UP and when in test mode. Holding down the reset button will display the panel configuration data. TEST MODE. Internal push button (with external led). In test mode, zones will now autoreset after 3 seconds, and on receipt of alarm will only operate sounders for 1* second, unless the sounders have been isolated. Sounders in savwire zones not being tested do not sound. Pressing the test button once sets the panel into test mode and also automatically isolates the auxiliary relays. Pressing the test mode button a second time isolates the sounders as well to enable silent testing. Pressing the button a third time clears test mode and re-instates the auxiliaries and sounders. Test mode (+ outputs automatically isolated for test) will automatically clear after about 20 minutes, if no zones are tested. Note! Outputs isolated using isolate mode will not be cleared. *(Note! some beacons take time to charge up and may not operate in test mode.) ISOLATE MODE. Led. Illuminated if any zone, and or auxiliaries / sounders have been isolated. ISOLATE MODE. Push button switch that enables an engineer to select circuits to be isolated or de-isolated. The isolated zones are indicated by the zonal fault LED's. Sounder and auxiliary circuits have their own leds. PAGE 2 ISOLATE MODE Circuits that may be isolated are, zones, auxiliaries and sounders. (N.B. sounders may only be isolated in test mode, and can remain disabled when test mode is de-activated. Sounders may be re-enabled when not in test mode if required). To select isolate mode follow this procedure. 1) Enable the controls. 2) Press the isolate mode button. Buzzer will beep, isolate mode led will flash. The zone 1 fault led will flash. (Flashing will be 3/4 S on 1/4 S if circuit was previously isolated, 1/4 S on 1/4 S off if not.) 3) Press isolate mode button to select / deselect circuit. Selected isolated circuits will be lit continuously, panel will then scroll to the next circuit. 4) Press the mute buzzer button to scroll to next zone / circuit. It will scroll automatically after a second or so anyway. Repeat action 3 as necessary. 5) After all isolatable circuits are scrolled through, if any circuits have been disabled the isolate mode led will be illuminated continuously as will led’s denoting the isolated circuit. 6) Pressing RESET at any time between steps 3&5 will clear all disablements and revert to normal operation. This is the preferred way of re-enabling zones as it will reset any detectors that may be in alarm on a disabled zone. CONFIGURATION OF ZONES To change a sav-wire zone to conventional operation remove the relevant zone link 1,2,3 or 4. Important! If common sounder circuits are not used, at least 2 zones MUST be SAVWIRE. Note! Internal "STOP CHARGE" led pulses on every few seconds to test for supply fault. It can take up to 20s to register a supply fault. Also, as batteries are not charged during a fire condition the led is on continuously. PAGE 3 DETECTOR D SOUNDER D D ZONE CIRCUIT 4 FAULT ZONE CIRCUIT 3 FIRE ZONE CIRCUIT 2 CALL POINT NOTES! 1. DEVICES MAY BE FITTED IN ANY ORDER. 2. WIRING MUST BE IN STRICT PARALLEL. 3. FOR SAV-WIRE WHEN SOUNDERS ARE OPERATING HI= -VE LO= +VE WHEN NOT SOUNDING HI= +VE LO= -VE 0.5A q/b 0.5A q/b 0.5A q/b R+ 0V EV COM N/C N/O COM N/C N/O HI1 LO1 HI2 LO2 HI3 LO3 HI4 LO4 0.5A a/s N E L C REPEAT SUPPLY 24v 250mA SHORT FOR CLASS CHANGE SOUNDER 230 V a.c. TYPICAL SAV-WIRE ZONE 0.5A q/b S D CALL POINT DETECTOR 8k2 C ZONE CIRCUIT 1 S 8k2 24v 1A max. TRANSFORMER 1.5A q/b BATT + 0V ISSUE 1 25/7/08 ISSUE DATE Alt No. 909-AN-034 2 14/11/12 PROTECTOR ALARMS (UK) LTD. Title 12V S.L.A BATTERY 12V S.L.A BATTERY 909e 4 ZONE TYPICAL TERMINAL ARRANGEMENT. SAVWIRE VERSION DRAWN APPROVED SCALE KC DRAWING NUMBER PA909-A18 S S S S S S SOUNDER CIRCUIT 2 8k2 SOUNDER CIRCUIT 1 FAULT 8k2 ZONE CIRCUIT 4 FIRE ZONE CIRCUIT 3 D ZONE CIRCUIT 2 C NOTES! 1. DEVICES MAY BE FITTED IN ANY ORDER. 2. WIRING MUST BE IN STRICT PARALLEL. 3. POSITIVE SCHOTTKY DIODE BASES SHOWN. NEGATIVE BASES MAY ALSO BE USED. 4. SOUNDER CIRCUITS WHEN SOUNDING, A= -VE B= +VE WHEN NOT SOUNDING A= +VE B= -VE 0.5A q/b 0.5A q/b 0.5A q/b 0.5A q/b 0.5A q/b 0.5A q/b 230 V a.c. D D ZONE CIRCUIT 1 D C REPEAT SUPPLY 24v 250mA SHORT FOR CLASS CHANGE 47uF 40v D R+ 0V EV COM N/C N/O COM N/C N/O HI1 LO1 HI2 LO2 HI3 LO3 HI4 LO4 A1 B1 A2 B2 D 0.5A a/s 8k2 47uF 40v N E L 8k2 24v 1A max. TRANSFORMER 1.5A q/b BATT + 0V ISSUE 1 25/7/08 ISSUE DATE Alt No. 909-AN-034 2 14/11/12 PROTECTOR ALARMS (UK) LTD. Title 12V S.L.A BATTERY 12V S.L.A BATTERY 909e 4 ZONE TYPICAL TERMINAL ARRANGEMENT. SCHOTTKY DIODE VERSION DRAWN APPROVED SCALE KC DRAWING NUMBER PA909-A18 (A) DETECTOR D SOUNDER D D 8k2 8k2 S S S S S S SOUNDER CIRCUIT 2 SOUNDER CIRCUIT 1 ZONE CIRCUIT 4 FAULT ZONE CIRCUIT 3 FIRE ZONE CIRCUIT 2 CALL POINT NOTES! 1. DEVICES MAY BE FITTED IN ANY ORDER. 2. WIRING MUST BE IN STRICT PARALLEL. 3. FOR SAV-WIRE WHEN SOUNDERS ARE OPERATING HI= -VE LO= +VE WHEN NOT SOUNDING HI= +VE LO= -VE 4. SOUNDER CIRCUITS WHEN SOUNDING, A= -VE B= +VE WHEN NOT SOUNDING A= +VE B= -VE 0.5A q/b 0.5A q/b 0.5A q/b 0.5A q/b 0.5A q/b R+ 0V EV COM N/C N/O COM N/C N/O HI1 LO1 HI2 LO2 HI3 LO3 HI4 LO4 A1 B1 A2 B2 0.5A a/s N E L C REPEAT SUPPLY 24v 250mA SHORT FOR CLASS CHANGE SOUNDER 230 V a.c. TYPICAL SAV-WIRE ZONE 0.5A q/b S D CALL POINT DETECTOR 8k2 C ZONE CIRCUIT 1 S 8k2 24v 1A max. TRANSFORMER 1.5A q/b BATT + 0V ISSUE 1 25/7/08 ISSUE DATE Alt No. 909-AN-034 2 14/11/12 PROTECTOR ALARMS (UK) LTD. Title 12V S.L.A BATTERY 12V S.L.A BATTERY 909e 4 ZONE TYPICAL TERMINAL ARRANGEMENT. SAVWIRE VERSION + COMMON SOUNDER CIRCUITS DRAWN APPROVED SCALE KC DRAWING NUMBER PA909-A18 (B)