Folheto TEMP-WM e TEMP-DM English.cdr

advertisement
TEMPERATURE TRANSMITTER - TEMP WM-DM
INTRODUCTION
The TEMP-WM and TEMP-DM transmitter series
incorporate the best high accuracy and great stability
temperature sensors. They convert the measured values
into linear 4 to 20 mA signals and optional 0 to 10 Vdc
output can also be offered under request.
The microprocessor based circuit enables full
configuration of output range when used with the
TxConfig PC interface and the Windows® based software.
The TEMP-WM model is dedicated to wall mounted
applications and the TEMP-DM version is suitable for duct
and through-the-wall applications.
FEATURES & SPECIFICATIONS
Temperature:
! Cable input: PG7 cable gland
! Accuracy: 0,5 °C @ 25 °C
! Output:
! Repetibility: ±0,1 °C
! Range: programmable between -50 and 120 °C (please check
operational limits)
!
! Response Time: up to 30 s in fairly still air
TEMPERATURE TRANSMITTER
C
! Operacional limits:
- Electronic module(WM-DM): -20 to +65 °C, 0 to 95% RH
- Sensor and Probe (DM): -40 to +100 °C
Note: When measuring temperatures higher than +65 °C or
lower than -20 °C, only 50% of the probe total length must be
inserted into the measured environment
General Features:
! Power:
- 12 to 30 Vdc (model 4-20 mA)
- 18 to 30 Vdc (model 0-10 V)
!
!
!
!
- Two-wire loop powered 4-20 mA or 20-4 mA
- Voltage output: 0-10 Vdc or 10-0 Vdc (optional)
Output resolution:
- 0,006 mA (4-20 mA)
- 0,003 V (0-10 Vcc)
Output load (RL):
- Model 4-20 mA: RL (max. in Ohms) = (Vdc - 12) / 0.02; where:
Vdc=power voltage in Volts
- Model 0-10 Vdc: 10 kOhms minimum
Ingress Protection:
- Electronic module case: IP65
- Sensor probe: IP40
Internal protection against reversed voltage wire polarity
No electrical isolation between input, output and power
circuits
ELECTRICAL CONNECTIONS
4-20 mA MODEL
0-10 V MODEL
LOAD
POWER
SUPPLY
6
Vdc
POWER
SUPPLY
OUT 1
5
6
Vdc
4
Load - represents a measuring
instrument (indicator,
controller, recorder, etc.).
OUTPUT: 0-10 Vdc
5
4
3
2
OUT 1
1
TRANSMITTER
TRANSMITTER
RECOMMENDATIONS FOR INSTALLATION
! Input and communication signal conductors must pass
through the system plant separated from the electrical
network conductors, if possible, in grounded conduits.
! The supply for the instruments must be provided from a
proper network for instrumentation.
C6
! In control and monitoring applications, it is essential to
consider what may occur if any of the system parts should fail.
! We recommend the use of RC FILTERS (47 R and 100nF, series)
in parallel with contactor and solenoid coils which are close or
connected to the transmitter.
info@novusautomation.com
www.novusautomation.com
NOVUS AUTOMATION
Phone +1-786-235 2674
TEMPERATURE TRANSMITTER - TEMP WM-DM
CONFIGURATION
INSTALATION
TEMP-WM and TEMP-DM configuration is performed by using
the TxConfig software and TxConfig USB interface connected to
the PC.
With the configuration one can set the transmitted output range,
correct measuring deviations (zero correction) and choose sensor
failure conditions (upscale or downscale). Sensor internal
information as serial number, product version and model can also
be digitally presented in the programming software menu.
TEMP-WM Model
This compact electronic module performs fast and accurate
measurements and isolates the sensor from internal module self
heating. The sensor probe must be installed facing down.
Remove the four module cover screws to access the electrical
terminal connectors and the two wall mounting fixing holes.
70 mm
48,7 mm
The factory default settings are:
! Temperature measuring range: 0 to 100 °C
! Upscale signal outputs when sensor break or failure
9V battery energy
Loop powered
4
6
5
4
3
2
1
39 mm
RS232
TxConfig interface
4
5
6
TxConfig interface
5
60 mm
6
Connect to PC
RS232 serial port
Connect to PC
RS232 serial port
39 mm
1 2 3 4 5 6
1 2 3 4 5 6
Current loop powered
9V Battery
Transmitter
Connectors
C
USB
Loop powered
USB powered
STATUS
STATUS
TEMP-DM Model
Sharing the same case and electronics as the TEMP-WM module,
the TEMP-DM holds the sensor at the tip of a 150, 250 or 400 mm
stainless steel or plastic sheath. A plastic flanged fixture is part of
the unit.
1
2
3
4
5
6
Transmitter
Connectors
1
Current loop powered
2
3
4
5
6
35 mm
Transmitter
Connectors
TxConfig Interface Connections
60 mm
13,7 mm
FLANGE
38,0mm
4,0mm
14,0mm
21,0mm
46,0mm
3,0 mm
1,5 m
13,0 mm
TxConfig software main screen
NOVUS AUTOMATION
Phone +1-786-235 2674
info@novusautomation.com
www.novusautomation.com
C7
TEMPERATURE TRANSMITTER
Transmitter
Connectors
Download