CH- E-16 – GTP CONTENT GTP No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 Name of Items 11kV VCB (Outdoor) 33kV VCB (Outdoor) & 33 kV VCB (Indoor) 11kV CT 33kV CT 11kV Metering Unit 55sqmm AAAC HTTV meter POWER TRF STATION TRF-100 kVA Transformer oil 33kv HG fuse 11kv HG fuse 33kv Isolator 11kV Isolator 33KV AB SWITCH 11KV AB SWITCH PSC Pole 100sqmm AAAC 148sqmm AAAC 33kv Pin Insulator 11kv Pin Insulator 33 kV Surge Arrester 11kv Surge Arrester Numerical Relay 25KVA DTR GTP 63 KVA DTR GTP 100 KVA DTR GTP 33kV & 11kV V cross arm RS joist HT STAY SET Stay wire Tension clamp Suspension clamp Back clamp F clamp Flexible cu bond Earthing pipe Earthing Coil 33 kV B&S Insulator CH- E-16 – GTP CONTENT 40 41 42 43 44 45 11 kV B&S Insulator LT Distribution Box LT 3 half-core LT 2-CORE ACSR Zebra 11kV 3 Core line 300sqmm GTP NO-1 Guaranteed Technical Particulars of 11kV Circuit Breaker(Indoor) SI. No Name of the Particulars Desired Value 1 Make 2 Service type 3 No. of Poles 4 Nominal system voltage 11 kV 5 Highest system voltage 12kV 6 Rated normal current at 50°C Bidder's Offer Indoor 3 i) For Bus-bar of Circuit Breaker 1250A ii) For Interrupter 630A 7 Rated short circuit breaking current (rms) 25kA 8 Rated short circuit making current (peak) 62.5kA 9 Rated short time current withstand capability for 3 sec. 25kA Page No-1 of 2 / 11kv VCB 10 Rated insulation level: i) One minute power frequency withstand voltage to earth (wet and dry) rms 28kV ii) Impulse withstand voltage to earth with 1 .2/50 µsec, wave of +ve and —ve polarity (Peak) 75KV 11 First — pole — to clear factor 1.5 12 Rated operating sequence (for auto reclosing) 0-0.3 Sec- CO-3 minCO 13 Maximum break time 3 cycles 14 Rated out of phase breaking current 25% of the symmetrical short circuit breaking current 15 Maximum pole scatter 10 mili seconds 16 Rated Auxiliary supply for spring charge motor, lamp & heater circuit. 230V A.C 17 Rated supply voltage for trip/close coil 48 V D.C Page No-2 of 2 / 11kv VCB GTP NO - 2 (i) Guaranteed Technical Particulars of 33 KV VCB (Outdoor) SI. No Name of the Particulars 1 Make 2 Service type Indoor 3 No. of Poles 3 4 Nominal system voltage 33KV 5 Highest system voltage 36KV 6 Rated normal current at 50°C i) 7 For Interrupter Rated short circuit breaking current (rms) 25KA Rated short circuit making current (peak) 62.5KA 9 Rated short time current withstand capability for 3 sec. 25KA i) Rated insulation level: One minute power frequency withstand voltage to earth (wet and dry) rms Impulse withstand voltage to earth with 1 .2/50psec, wave of +ve and —ve polarity (Peak) Bidder's Offer 1250A 8 10 ii) Desired Value 70kv 170KV Page No-1 of 3 / 33KV VCB intdoor type First — pole — to clear factor 11 12 13 14 Rated operating sequence (for auto reclosing) Maximum break time Rated out of phase breaking current 1.5 0-0.3 Sec- CO-3 min-CO 3 cycles 25% of the symmetrical short circuit breaking current 15 Maximum pole scatter 16 Rated Auxiliary supply for spring charge motor, lamp & heater circuit. 230V A.C 17 Rated supply voltage for trip/close coil 48V D.C 18 Minimum creepage distance (mm) 900 mm 19 Minimum protected creepage distance (mm) 20 Total break time in MS 21 At 10% rated interrupting capacity <80ms 21 a At rated interrupting current <80ms 21 b Arcing Time <15ms 22 Make time <100ms 23 Minimum reclosing time at full rated interrupted MVA from the instant of Trip coil energisation 10 mili seconds As Per IS 300ms Page No-2 of 3 / 33KV VCB intdoor type 24 Minimum dead time for 3 phase closing 25 one time dry power frequency withstand test voltage between line terminal and ground objects 70kv 26 onemin dry power frequency withstand test voltage between terminal with breaker contacts open 80kV 27 Type of main contacts 28 Type of Aux. Contacts 29 Materials of auxilliary contacts 30 Voltage distribution between breaker 31 Type of device if any ,used to limit the rate of rise or restriking voltage Nil 32 Voltage grading device if any used Nil 33 Number of auxiliary contacts provided 34 300ms Copper Alloy i) those closed when breaker is closed 6 i) those open when breaker is closed 6 Type of operating mechanism Page No-3 of 3 / 33KV VCB intdoor type Spring charged due to closing both manual and motorized Spring operated i) Opening Spring charged due to closing both manual and motorized Spring operated ii) Closing 35 Frequency at which contacts are to be replaced 36 Nos of terminal connetor 37 Short circuit type test certificate furnished 38 Circuit breaker weight 39 Minimum clearance in air 40 After 100 full short circuit operations 6 i) Between phases >480mm ii)Live parts to earth >320mm iii) Live parts to ground level >3700mm iv)Between Liver parts & ground object >320mm Bushing of insulators Page No-4 of 3 / 33KV VCB intdoor type i) Type of bushing Porcelain ii)Dry 1 min power frequency withstand test voltage 70kV iii) Dry flash over value >75kV iv) Wet flashover value >75kV v) 1.2/50 impulse withstand 170KVp vi) Creepage distance 900 mm vii) Puncture value of bushing >75kV viii) Weight of bushing <45kG Page No-5 of 3 / 33KV VCB intdoor type GTP NO -2 (ii) Guaranteed Technical Particulars of 33 KV VCB (Indoor) SI. No Name of the Particulars 1 2 3 4 5 6 Desired Value Bidder's Offer Make Service type No. of Poles Nominal system voltage Highest system voltage Indoor 3 33KV 36KV Rated normal current at 50°C i) 800A For Bus-bar of Circuit Breaker ii) For Interrupter 630A 7 Rated short circuit breaking current (rms) 25KA 8 9 Rated short circuit making current (peak) Rated short time current withstand capability for 3 sec. 10 Rated insulation level: i) One minute power frequency withstand voltage to earth (wet and dry) rms 62.5KA 25 kA 70kV Page No-6 of 3 / 33KV VCB intdoor type ii) Impulse withstand voltage to earth with 1 .2/50psec, wave of +ve and —ve polarity (Peak) 11 First — pole — to clear factor 12 Rated operating sequence (for auto reclosing) 170KV 1.5 0-0.3 Sec- CO-3 min-CO 13 Maximum break time 14 Rated out of phase breaking current 15 16 Maximum pole scatter Rated Auxiliary supply for spring charge motor, lamp & heater circuit. 17 Rated supply voltage for trip/close coil 48V D.C 18 Minimum creepage distance (mm) 900 mm 19 (a) ( b) 20 21 Total break time in MS At 10% rated interrupting capacity At rated interrupting current Arcing Time Make time <80ms <80ms <15ms <100ms 22 23 24 Minimum reclosing time at full rated interrupted MVA from the instant of Trip coil energisation Minimum dead time for 3 phase closing one time dry power frequency withstand test voltage between line terminal and ground objects 3 cycles 25% of the symmetrical short circuit breaking current 10 mili seconds 48 V DC/230V A.C 300ms 300ms 70kv Page No-7 of 3 / 33KV VCB intdoor type 25 26 27 28 29 30 31 32 33 one time dry power frequency withstand test voltage between terminal with breaker contacts open Type of main contacts Type of Aux. Contacts Materials of auxilliary contacts Voltage distribution between breaker Type of device if any ,used to limit the rate of rise or restriking voltage Voltage grading device if any used Number of auxiliary contacts provided i) those closed when breaker is closed ii) those open when breaker is closed Type of operating mechanism i) Opening ii) Closing 34 Frequency at which contacts are to be replaced 35 Nos of terminal connetor 36 37 Short circuit type test certificate furnished Circuit breaker weight 80kv Copper Alloy Nil Nil 6 6 Spring charged due to closing both manual and motorized Spring operated Spring charged due to closing both manual and motorized Spring operated After 100 full short circuit operations 6 GTP NO – 3 GUARANTEED TECHNICAL PARTICULARS FOR 11KV CURRENT TRANSFORMERS Sl. No. Name of the Particulars Desired Value 1 Make 2 Type of CT Installation 3 Type of mounting 4 Suitable for system frequency 5 Rated Voltage (KV rms) 11 6 Nominal System Voltage (KV rms) 11 7 Highest System Voltage (KV rms) 12 8 Current Ratio (A/A) 9 Method of earthing the system where the current transformers will be installed 10 Rated Continous Thermal Current (A) 11 Single phase, dead tank, oil-filled Poly Crate hermetically sealed outdoor, self-cooled. Pedestal type 50 HZ (- 5% to +3%) 400-200 -100/1-1-1 A Effectively earthed 120% of rated primary current Acceptable limit of temperature rise above 500C ambient temperature for continuous operation at rated continuous thermal current (a)W inding 400C (b) OIL 350C Bidder’s Offer (c )External surface of the core, metallic parts in contact with or adjacent to, insulation. 11 1.2/50 micro second lighting impulse withstand voltage (kVP) 12 (dry) 13 1 Minute dry power frequency withstand voltage primary (kV rms) 14 1 Minute dry power frequency withstand voltage secondary (KV rms) 40ºC 75 28 3 15 Minimum creepage distance of porcelain Housing (mm) 350 Rated short time withstand current for 3 second duration at all 16 ratios (KA rms) 25 Instrument security factor at all ratios for metering core 17 18 Maximum rated short time thermal current density of the primary winding copper conductor (A/mm2 ) at all ratios Type of Core Not more than 5.0 92 Torroidal type 0. 15g (Vertical) 19 Seismic acceleration Accuracy class of standard C.T to be used during testing 20 towards determination of ratio errors and phase angle errors for metering cores. 0.3g (Horizontal) 0.05 or better. GTP NO -4 GUARANTEED TECHNICAL PARTICULARS FOR 33 KV CURRENT TRANSFORMERS Sl. Name of the Particulars No. 1 Make Desired Value Single phase, dead tank, oil filled, hermetically sealed, outdoor, self-cooled 2 Type of CT/Installation. 3 Type of mounting. 4 Suitable for system frequency. 5 Rated voltage (KV rms) 33 6 Nominal system voltage (KV rms) 33 7 Highest system voltage (KV rms) 36 8 Current ratio (A/A) 9 Method of earthing the system where the current transformer will be installed. 10 Rated continuous thermal current (A) Bidder's Offer Pedestal type 50 HZ (+ 5 % to -3%) a) 400-200/1-1-1A Solidly Effectively earthed. 120 % of rated primary current Page No-1 of 3 / 33kv CT 11 (a) (b) (c) Acceptable limit of temperature rise above 50°C ambient temperature for continous operation at rated continuous thermal current. Winding 45°C Oil 40°C External surface of the core, metallic parts in contact with or adjacent to, 45°C insulation. 12 Acceptable partial discharge level Less than 10 pico coulombs 13 Maximum radio interference voltage at l. l times the maximum rated voltage. Less than 500 micro volts 14 l.2/50 micro second lightning impulse withstand voltage (KVP) (dry) 170 15 16 1 minute dry power frequency withstand voltage primary (KV rms) Switching Impulse with stand and voltage (KVP) 70 17 l Minute dry power frequency withstand voltage secondary (KV rms) 3 18 Minimum creepage distance of porcelain Housing (mm) 900 19 Rated short time withstand current for 3 second at all ratios (KA rms) 25KA 20 Instrument security factor at all ratios for metering core. Not more than 5.0 Page No-2 of 3 / 33kv CT 21 Minimum rated short time thermal current density of the primary winding at all ratios (A/mm2) 22 Application, current ratio, output burden, accuracy class, minimum knee point voltage, secondary winding resistance, maximum excitation current at minimum knee point voltage etc. 23 Type of core 24 Seismic acceleration 25 Accuracy class of standard C.T. to be used during testing towards determination of ratio errors and phase angle errors for metering cores. As per clause No9.6.3- Note of IS: 2705 (Part-I)/l992 0.15g (Vertical) 0.3g (Horizontal) 0.05 or better. Page No-3 of 3 / 33kv CT GTP NO- 5 GUARANTEED TECHNICAL PARTICULARS OF OUTDOOR OIL IMMERSED 3P4W,11 KV,5A MU (CT: PT UNITS). Sl no Particulars Requirement 1 Maker’s name & adress To be indicated 2 Manufacturer’s Type & Design To be indicated 3 Type of cooling To be indicated 4 Nominal System Voltage 11 KV 5 Highest System Voltage 12 KV 6 Frequency. Specification of CT & PT of Metering Unit 50 HZ 7 To be furnished by the bidder Current Transformer Type Accuracy Class A Oil immersed 0.2 Rated output 15 VA Insulation level 28KVrms / 75 KVpk Short time thermal current rating for 1 sec Saturation factor Normal current density of primary winding Knee Point Voltage CT Primary 6 KA for up to20/5A & 13KA for >20/5A To be indicated =<1 .6 Amps per Sq.mm To be indicated Page No-1 of 9 / 11kV metering unit Continuous percentage over load 120% ISF As per IS Potential Transformer B Type PT ratio Rated output VA/phase Class of accuracy Oil immersed 11 KV/√3V /110/ √3V 50 0.2 Insulation level 28KVrms / 75 KVpk Winding connection Rated voltage factor & duration 8 Star/Star To be indicated Dimension of MS hot dip Galvanized tank i Height mm ii Breadth mm iii Length mm Thickness of MS Tank Side walls 9 i) Bottom To be indicated 3.15mm ii Top 5 mm iii Edge bending in the Top Cover To be provided iv Standard pressure & duration that can be withstand. To be indicated Weight of core and winding 10 Current transformer A. Core To be indicated Primary winding To be indicated Page No-2 of 9 / 11kV metering unit Secondary winding To be indicated Potential transformer B. Core To be indicated Primary winding To be indicated Secondary winding To be indicated i) Quantity of oil in Ltr 11 ii) 12 ( Min 45 Ltrs) To be indicated Grade of Oil To be indicated Total weight of complete ME including all accessories and oil To be indicated Resistance of primary & secondary winding per phase at 75° C:CT Winding (i) Primary 13 PT Winding 14 To be indicated (ii) Secondary To be indicated (i) Primary To be indicated (ii) Secondary To be indicated Maximum attainable winding temperature 85° C Minimum phase to phase distance 255mm Shortest distance between metal part & earth 190 mm 15 Make & type of HT bushing To be indicated Page No-3 of 9 / 11kV metering unit 16 Creepage distance of HV bushing 17 18 19 i ii iii 20 Bi-metallic terminal connector with nut, plain washer, spring washer & check nut suitable for aluminum conductor as per CT rating. 300mm (Min) 6 nos to be provided Type of core material To be indicated Type & thickness of gasket used on Top cover tank To be indicated Secondary terminal box To be indicated HV bushing To be indicated Details of Metering Unit CT details A Cross section area of each turn of CT winding (in sq. mm.) Primary winding To be indicated Secondary winding To be indicated No. of turns Primary winding To be indicated Secondary winding To be indicated Winding material Page No-4 of 9 / 11kV metering unit Primary winding To be indicated Secondary winding To be indicated PT details B i Cross Section area of each turn of PT (in sq. mm.) a Primary winding To be indicated b Secondary winding To be indicated ii Number of turns a Primary winding To be indicated b Secondary winding To be indicated c Winding materials i Primary winding Secondary winding Identification/marking of Primary terminals Incoming Outgoing Secondary terminals CTs PTs Size and material of Primary studs Secondary studs ii 21 i. a b ii a b 22 i. ii To be indicated To be indicated RM, YM, BM RL, YL, BL 1s1- 1s2, 2s1-2s2, 3s1-3s2 r,y,b,n M12 up to 20A & M16 >20A M6 Page No-5 of 9 / 11kV metering unit 23 24 25 Secondary Chamber shall have double door type & sealing arrangement in both the doors. Secondary chamber shall have double door (inner & outer) with suitable arrangement for sealing of both the doors. The inner door shall be of transparent polycarbonate so that secondary terminal connections can be viewed with out breaking the inner door seals. Name Plate The name plate shall be nondetachable type & fixed with rivets, not with bolts & nuts. The nameplate should bear year, month of manufacture , Guaranty period & other data as per IS. Sealing arrangements The secondary terminal box cover, tank cover and inspection cover sealing arrangements have to be done with sealing bolts at all corners and bolts should be at least 10 mm diameter GI bolts spaced maximum 70 mm apart. Sealing holes also to be provided in the bolts fitted with bushing & body for sealing, so that one can not open the bushing with out breaking seals. Page No-6 of 9 / 11kV metering unit 26 Galvanization of Tank Metering Unit tank including top cover shall be hot deep galvanized. 27 Gap between I/C & O/G Studs of same phase minimum 15º angle with the vertical axis to maintain a good distance at stud levels. GUARANTEE TECHNICAL PARTICULARS FOR OIL Sl. No Characteristic. Particulars. The oil shall be clear and transparent and free from suspended matter or sediments and should conform to or latest versions. IS-335/93 1 Appearance. 2 Density at 27 degrees C (max) 3 Kinematic Viscosity at 27 degrees C (max) 4 To be furnished by the bidder Interfacial Tension at 27 Degrees C (max) Flash point, pensky – marten (closed) (min) 5 0.89 g/cm. 27 CST. 0.04 N/M. 140 Degrees C. Pour point (max) 6 -10 Degrees C. Neutralisation Value: 7. a) Total acidity (max) b) In-organic acidity alkalinity. 0.01. Nil Page No-7 of 9 / 11kV metering unit 8 Corrosive sulphur. Non-corrosive. Electric Strength (breakdown voltage/ minute) 9 10 a) New unfiltered oil. 30 KV (rms) b) After filtration. 50 KV (rms) Dielectric dissipation factor(Tan delta at 90 Deg. C (min)). 0.005. Specific resistance (Resistivity). 11 12 a) At 90 Deg. C (min) 30x1 012 ohms- cm. b) At 27 Deg. C (min) 500x1 012 ohms-cm Oxidation stability a) Neutralisation value after oxidation (max) b) Total sludge after oxidation (max) 0.2 mg KOH/g 0.05% by Weight. Ageing characteristics after accelerating ageing (open breaker method with copper catalyst) for 96 Hrs.as per ASTM D. 1934-1978) a) Specific resistance (Resistivity) a. At 27 Deg. C (min) b. At 90 Deg. C (min) 2.5 x 1012 ohms-cm 0.20 x 1012 ohms-cm 13 Page No-8 of 9 / 11kV metering unit b) Dielectric dissipation factor Tan delta at 90 Deg. C (max) 0.2 c) Total sludge value (max) 0.5 d) Total acidity (max) 0.5 14 Presence of oxidation inhibitor. Nil 15 Water content (max) 50 ppm Page No-9 of 9 / 11kV metering unit GTP NO-6 GUARANTEED TECHNICAL PARTICUALRS OF 55MM2 AAAC Sl.No. Description 1 Manufacture’s Address 2 Indian Standard No. IS 398 (Part-4)1 994 3 IEC Standard No.IEC 1089 4 Materials of conductor Unit 55mm 2 IS 398 (Part-4)1 994 IEC 1089 AAAC Balco, Hindalco,Kunj Alloys,Nalco & any other approved sources. 5 Aluminum alloy redraw rod manufacturer 6 Drawing aluminum wire manufacturer 7 Standing complete conductor manufacturer 8 Nos. of Strands 9 Dia of each strand mm 10 Total cross-sectional area of conductor mm 11 Overall dia of stranded conductor Mm 9.45 12 Mass of conductor per kilometer(without grease) Kg 149.2 7 2 3.15 55 Bidder'sOffer 13 Mass of grease per kilometer of conductor (Approx.) Kg N.A. 14 Total mass of greased conductor per ki lometer(Approx.) Kg 149.2 without grease 15 Conductor grease type 16 Ultimate strength of conductor Newton 16030 17 Assumed equivalent modulous of elasticity of conductor N/ mm 2 62038 18 Assumed equivalent co-efficient of elasticity N/ mm 2 62038 19 Assumed equivalent co-efficient of linear expansion Per °C 23.0x1 0-6 20 Maximum length of conductor supplied in one drum Km 6.0±5% 21 Maximum D.C. resistance at 20ºC Ohm/Km 0.621 22 Maximum full load current at 75°C (40°C ambient) Ampere 191 23 Individual Aluminum alloy strands a. Tensile breaking stress N.A. N/ mm 2 299.4 b. Elongation on 200mm length in breaking % 4 c. Maximum electrical resistance at 20°C Ohm/Km 4.29 24 Particulars of raw material Minimum purity of Aluminum alloy % 97.25 Type Si-Mg i. Si % 0.50 to 0.90 ii. Mg % 0.6 to 0.90 iii. Fe Max % 0.5 iv. Cu Max % 0.1 v.Mn Max % 0.03 vi. Cr Max % 0.03 vii.Zn Max % 0.1 viii. % 0.06 % 0.03 Aluminum redraw rod conforming to Elements B Max ix. Other Element each Max Total Max 25 DC resistance of conductor at 20°C(Max) 26 Standard length of conductor that can be manufactured 0.1 Ohm/Km 0.621 Meter 2000±5% 27 Maximum length of conductor that can be manufactured 28 Toleranceonstandardlengthofconductor 29 Direction of layer for outside layer 30 Weight of the drum (only) Meter 3000 % ±5% RH/LH RH Kg 150 to 180 GTP NO-7 GUARANTEED TECHNICAL PARTICULARS FOR 3 PHASE 4 WIRE CT! PT OPERATED FULLY STATIC AMR COMPATIBLE TRI-VECTOR ENERGY METERS ( Common Protocol Energy Meter Conforming to companion standard for IEC 62056!IS1 5959) Category-A Sl. Particulars No. Desired Value 1 Make 2 Type 3 Country of origin 4 Application 5 Rated Voltage 6 Rated Current (Basic current) 7 Frequency 50 Hz ± 5 % 8 Overload capacity 200% of Ib 9 Minimum starting current in % of base current 10 Short Time Current 3PH 4 Wire, Tri vector Energy Meter (AMR Compatible) India 3 phase 4 wire, CT PT operated (i)For CT/PT operated HT Meters-Suitable for operation from 11 0V Ph-Ph or 63.5V Ph-N 1A for -/1A,5A for -/5A As per IS 14697: 1999 As per IS 14697: 1999 11 Loss in potential circuit Less than 1.5 Watt & 8VA per phase 12 Loss in Current circuit Less than 1 VA 13 Power Factor Bidder’s Data 0.0 Lag -Unity- 0.0 Lead Page No-1 of 10 / HTTV 3 PH Meter 14 Change in error due to a. Variation in frequency 50 Hz +/- 5% b. Variation in temperature As per IS 14697: 1999 Variation in voltage As per IS 14697: 1999 c. 15 Accuracy Class Constructional Requirement/Meter Cover LT- 0.5s, HT-0.2s As per Clause:-5.0 of Tech. 16 Sealing arrangement 17 Meter Cover & Case 18 Meter Case Opening Temper Recording Specification. As per Clause:-5.1 of Tech. Specification. As per Clause:-5.1.1 of Tech. Specification. 19 Terminal & Terminal Block As per Clause:-5.2 of Tech. Specification. 20 Terminal Cover As per Clause:-5.3 of Tech. Specification. 21 Terminal Arrangement As per Clause:-5.4 of Tech. Specification. 22 Connection Diagram As per Clause:-5.5 of Tech. Specification. 23 Sealing of Meter As per Clause:-5.6 of Tech. Specification. Page No-2 of 10 / HTTV 3 PH Meter 24 Working environment & degree of protection. As per Clause:-6 of Tech. Specification. 25 Manufacturing Process assembly & Testing As per Clause:-7 of Tech. Specification. 26 Displays As per Clause:-8.0 of Tech. Specification. 27 Non Volatile Memory 28 Battery Back up Performance under 29 Influence Quantities The data stored in the meters shall not be lost in the event of power failure. The meter shall have Non Volatile Memory (NVM), which does not need any battery backup. The NVM shall have a minimum retention period of 10 years. In case of failure of power supply the meter could be powered up the meter could be powered up through an internal battery backup with a push button arrangement. As per IS -14697/1 999 (re-affirmed 2004) & CBIP Page No-3 of 10 / HTTV 3 PH Meter Technical Report Out Put Device As per Clause:-10 of Tech. 30 Specification. 31 RTC As per Clause:-11 of Tech. Specification. Quantities to be measured & 32 displayed. As per Clause:-12 of Tech. Specification. 33 Demand Integration Period Should be programmable & 15 min by default. 34 MD Reset Auto reset at 24:00 hrs at the end of each billing cycle. 35 Marking As per Clause:-15 of Tech. Specification. 36 Communication Capability As per Clause:-16 of Tech. Specification. 37 HHU As per Clause:-17 of Tech. Specification. 38 Free supply of HHU One DLMS Compliant HHU shall be provided by the supplier to DISCOM free of cost for each 50(fifty) meters for data down loading. It shall be compatible to the DLMS compliant energy meters that are to be procured/supplied on the basis of this technical specification Tamper & Fraud As per Clause:-18 of Tech. 39 Page No-4 of 10 / HTTV 3 PH Meter 39 monitoring features 40 Abnormality Events Detection 41 Load Survey capability Parameter Logged Specification. As per Table A6.1 to A6.7 “Data Exchange for Electricity Meter Reading, Tariff and Load Control – Companion Specification” enclosed). 1 .Real Time Clock – Date and Time. 1 2.Current – IR 3. Current – IY 4.Current – IB 2 5.Voltage – VRN 6.Voltage – VYN 7.Voltage – VBN 8.Block Energy kWh 9.Block Energy – kvarh – lag 10.Block Energy – kvarh – lead 11 .Block Energy – kVAh ii. Logging interval iii. No. of days of Load Survey iv. Apparent Calculation 42 TOD TIMING (Both MD & ENERGY) (PROGRAMMABLE,15 Minutes by default ) 60 power on days Lag + Lead 00: 00 Hrs to 06:00 Hrs 06:00 Hrs to 24:00 H rs Page No-5 of 10 / HTTV 3 PH Meter 43 MD RESET REQUIRED 44 Software Locking 45 Software 46 Meter Reading Protocol AUTO MODE ONLY, MANUAL RESET NOT REQUIRED The meter shall have password protected software locking provision for changing the TOD timings & MD integration period. The firm has to provide required base computer & MRI software for data down loading & analysis with free of cost. The Supplier has to provide Meter Reading Protocols for billing parameters, tamper data etc. at free of cost. GUARANTED TECHNICAL PARTICULARS FOR POLYCARBONATE OR SMC OR COMBINATION OF POLYCARBONATE & SMC PILFER PROOF METER BOX TO HOUSE THE THREE PHASE FOUR WIRE HTTV ENERGY METERS Sl. Characteristics No. Requirements 1 Manufacturer’s / Supplier’s name and address with works address. 2 Material used for box body Poly Carbonate/SMC (Sheet Moulding Compound)ref-IS: 13410/1992 /IS:14772 :2000Combined 3 Color of Box Dark Admiral Gray/off White/Transparent 4 Dimensions of box (L x W x H) 5 Meter Fixing Arrangement Bidders Data 45x38x20 CM (approx) Adjustable Meter Mounting Arrangement may be provided to accommodate any make of Meters (like Secure, L&T etc.). Page No-6 of 10 / HTTV 3 PH Meter 6 Earthing Provisions 7 Thickness of meter box a. From Back Side b. From all other sides 8 To be provided 2.5 mm Back Side 2.0 mm all other side. Clearance of meter from box surface approx. :(Varies from meter to meter) a. Right , Left b. Top side 1 cm c. Bottom side ( from meter terminals) 12 cm d. Bottom side ( from terminals cover) 8 cm e. Front side 11cm 9 Additional “D” Port 10 cm Additional “D” Port provision provided in the inner door of the box with sealing arrangement for downloading data through MRI. Page No-7 of 10 / HTTV 3 PH Meter 10 Doors 11 Push button hole 12 The material of inner door shall be Provision of two (Inner door & outer door) arrangement to be provided. Push button hole shall be done by DISCOMs at the time of installation. SMC For cable entry, one suitable circular holes 13 Cable Entry Hole. 14 Type of Use Meter Box should be suitable for 15 Suitable to house fitted with adjustable glands will be provided at the bottom of the box for cable inlet and outlet. Internal diameter of the gland will be such as to accommodate the control cable having outer diameter 25-30mm.The cable entry hole position can be changed by DISCOMs as per the field requirement & will be narrated during the placement of Purchase Order. Meter Box should be suitable for indoor & outdoor use. The meter box will be suitable to house one number three-phase four-wire HTTV energy meter & a modem of any make. Page No-8 of 10 / HTTV 3 PH Meter 16 The meter box shall comply with IS:1 3410- 1992 Meter Box will have a roof tapering 17 Roof tapering arrangement for easy flow of rainwater, as per sample. 18 Hinges Box cover will be fixed with minimum three nos hinges in each door well protected against corrosion. Box cover will be able to open by more than 120 degrees. Concealed hinges should fix the Box and cover, with hardware from inside in such a manner that it can’t be manipulated from outside. 19 Gasket Soft rubber gasket for protection from ingress of dust and water will be provided on all around the box. 20 Handle Handle/Knob will be provided on the Box door for easy door opening. The box shall be provided with two (inner & outer) doors. A viewing window must be provided in inner door if not transparent. One 21 Inner door, viewing window & D-Port. D-Port provision for communication must be provided in the inner door of each box with sealing arrangements. Page No-9 of 10 / HTTV 3 PH Meter Fixing Holes Box shall be provided with 4 nos. fixing holes of 6 mm diameter at all four corners of meter box. For holding and sealing the outer door, U- 22 Sealing & Latches. shaped latches/clamps with two sealing holes will be provided. Two nos Latches will be provided on the base of the box. These metallic parts will be protected against corrosion. Provision shall be made for sealing of doors at two locations. The viewing window for meter reading will be 24 Viewing window made of break resistant, UV stabilized, transparent Polycarbonate of minimum 2.0 mm. Thickness the transparent window will be properly welded/fixed in rigid way with meter Adjustable meter mounting arrangement to be provided in such a way that the display portion of any make meter can be easily aligned with 25 Adjustable meter mounting Arrangem et the viewing window of outer door, So that meter reading can be done easily without opening any door of meter box. Purchase order No. & Date, Property of 26 Name Plate. Owner Name-OPTCL. will be mentioned on metallic name plate in such a manner that it will not be erased & removed easily. Name of Manufacturer will be embossed on meter box cover. Page No-10 of 10 / HTTV 3 PH Meter GTP NO-8 GUARANTEED TECHNICAL PARTICULARS FOR POWER TRANSFORMERS OF3.1 5 MVA,5 MVA & 8 MVA Sl. No . 1 a) b) c) d) e) f) g) 2 3 a) b) 4 a) b) 5 6 7 8 a) b) 9 10 Name of the Particulars Name and address of the Manufacturer Transformer HV & LV Bushings Bimetallic connectors Transformer Oil On load tap changer Instruments Neutral Bushing CTs Service ( Indoor / Outdoor ) Normal continuous rating in KVA under site conditions at all taps : HV winding (KVA) LV winding (KVA) Rated Voltage HV winding (KV ) LV winding (KV) Rated frequency (Hz) No. of phases Type of transformer Connections HV winding LV winding Connections symbols HV – LV Tappings Bidder's offer a) b) Range Number of steps c) Position of tapping on HT winding for high voltage variation d) e) 11 a) b) c) d) e) Reference ambient temperatures Maximum ambient air temperature (0C) Maximum daily average ambient temperature (0C) Minimum ambient air temperature (0C) Maximum yearly weighted average ambient temperature (0C) Maximum temperature rise over ambient temperature Top oil by thermometer (0C) HV & LV windings by resistance measurement (0C) Hot Spot Temperature rise of windings(0 C) Limit for hot spot temperature for which the transformer is designed (0 C) Temperature gradient between windings and oil (0C) f) Type of maximum winding temperature indicator (0C) 12 a) b) c) d) 13 14 15 Voltage to earth for which the star point will be insulated Cooling type Losses a) No-Load loss at rated voltage & rated frequency (KW) b) Load loss at rated current at Normal Tap at 750 C (KW ) Max. Current density in winding at rated current for normal tap position HV winding (Amps/ sq.mm.) LV winding (Amps / sq.mm.) 16 a) b) 17 a) b) Impedance voltage at rated current ,rated frequency and at 750 C expressed as percentage of rated voltage at :Principal (normal) tap (%) Highest tap (%) c) 18 a) b) c) 19 a) b) Lowest tap (%) Reactance at rated current & frequency as percentage of rated voltage at: Principal (normal) tap Highest Tap Lowest Tap Resistance at 750 C H.V. winding at normal tap position L.V. winding Resistance voltage drop at 750 C winding temperature expressed as percent of rated voltage (%) c) i) Principal/ normal tap ii) Highest tap iii) Lowest tap 20 a) b) c) Insulation level Separate source power frequency voltage withstand i) HV winding (KV rms) ii) LV winding (KV rms) Induced over voltage withstand i) HV winding (KV rms) ii) LV winding (KV rms) Full wave lightning impulse withstand voltage i) HV winding (KV peak) d) Power frequency high voltage tests i) Test voltage for one minute withstand test on high voltage windings (induced) ii) Test voltage for one minute withstand test on low voltage windings iii) Test voltage for one minute withstand test on neutral end of low voltage windings e) Lightning impulse withstand tests i) Impulse test on high voltage winding 1.2/50 p sec full wave withstand (KV peak) ii) Impulse test on low voltage winding 1.2/50 p sec full wave withstand (KV peak) iii) Wave form for impulse test No load current, no load loss, no load power factor at normal 21 ratio and frequency (Amp/ KW/ P.F.) a) 10 percent of rated voltage b) 25 percent of rated voltage c) 50 percent of rated voltage d) 85 percent of rated voltage e) 100 percent of rated voltage f) 105 percent of rated voltage g) 110 percent of rated voltage h) 112.5 percent of rated voltage i) 115 percent of rated voltage j) 120 percent of rated voltage k) 121 percent of rated voltage 22 Efficiency at 75º C at unity power factor a) Full load b) 75% load c) 50% load d) 25% load 23 (a) a) b) The minimum percentage of load at which the transformer will run at maximum efficiency (%) b) Maximum efficiency of the transformer 24 Regulation at full load at 75º C a) At unity power factor (%) b) At 0.8 power factor (lagging) (%) 25 Core data Grade of core material used Thickness of core plate lamination (mm) c) Whether core laminations are of HIB cold rolled grain oriented d) Details of oil ducts in core, if any i) Whether in the plane & at right angle to the plane of winding a) b) c) a) b) c) d) e) f) ii) Across the plane of lamination e) i) Insulation of core lamination ii) Insulation of core plates iii) Type of core joints(Mitred or Mitred Step-lap) 26 Flux density Designed maximum flux density at rated voltage and rated frequency (Tesla) Designed maximum operating flux density which the transformer can withstand for one minute at normal tap (Tesla) Designed maximum operating flux density which the transformer can withstand for five seconds at normal tap (Tesla) 27 Inter-Tap insulation Extent of extreme end turns reinforcement Extent of end turns reinforcement Extent of turn adjacent to tapping reinforced Test voltage for 10 seconds 50Hz inter-turn insulation test on (a) Test voltage for 10 seconds 50Hz inter-turn insulation test on (b) Test voltage for 10 seconds 50Hz inter-turn insulation test on (c) 28 Windings: a) Material b) Type of windings: i) HV windings ii) LV windings c) d) e) 29 Insulation of HV windings Insulation of LV windings Insulation between HV & LV windings Continuous rating under following conditions: a) At 40°C ambient air temp. at site b) At 30°C ambient air temp. at site c) At 20°C ambient air temp. at site 30 Transformer Tank a) Material b) Thickness - Top - Sides - Bottom c) Details of painting - Inner surface - Outer surface 31 Dimensions of 3 phase transformers: a) Max. Height to top of bushings (mm) b) Over-all length (mm) c) Over-all breadth (mm) Weight data of transformer components : (Tolerance + 5% ) 32 (approximate values not allowed ) a) b) c) Core excluding clamping (Kg) Core with clamping (Kg) HV winding insulated conductor (Kg) d) e) f) g) h) i) LV winding Insulated conductor (Kg) Coils with insulation (Kg.) Core and windings (Kg) Weight of steel (Kg) Fittings and accessories (Kg) Oil required for first filling including 10% extra (ltrs / Kg ) 1. Oil in main tank ( Ltrs) Oil in the conservator (Ltrs) Oil in the radiators ( Ltrs ) Oil in the OLTC (Ltrs.) Overall total quantity of oil with 10% extra oil for first filling (ltrs / Kg) 1. Transportation weight excluding accessories (Kg) 2. Shipping details i) Weight of heaviest package (Kg.) ii) Dimension of largest package (Kg) Untanking weight (Kg) Total weight of transformer with oil and fittings (Kg) Bushing data : Type of bushing insulator i) HV ii) LV i i i ) N e utra l Material of bushing (inner part / outer part) Weight of bushing insulator (Kg.) Quantity of oil in one bushing (lt.) Minimum dry withstand & flash over power frequency voltage of bushing (KV) 2. 3. 4. 5. j) k) l) 33 a) b) c) d) e) f) g) h) i) j) k) l) m) Minimum wet withstand & flash over power frequency voltage of bushing (KV) Minimum withstand & flashover impulse level (KV) Voltage rating (KV) Current rating (Amps.) Thermal Short Time current & Duration Rated Dynamic current & its duration Cantilever with stand loading Clearance in oil - phase to phase (mm) n) o) - phase to earth (mm) Creepage distance in oil & air (mm) Minimum level of immersing / medium (oil ) (mm) p) Maximum pressure of immersing medium (oil) Kg/ cm2 q) r) Free space required at top for removal of bushings (mm) Angle of mounting 34 Details of CT to be provided in the neutral for REF protection. a) b) c) Outdoor bushing type No. of cores and their function Location (Line / Neutral) d) Current rating for various cores (Primary / Secondary) e) VA burden / Knee Point voltage (Core wise) f) 35 Magnetising current at half knee point voltage. (mA) Classification (PS class) core wise Test voltage Construction details Conservator (Main Transformer and OLTC) a) Total volume of the Conservator (Cub mtr / Ltr.) g) h) i) b) 36 37 a) b) 38 a) b) c) Volume of the conservator between the highest and lowest level (Cubic mtr. / Ltrs ) Calculated time constants for natural cooling Type of axial coil supports : HV winding LV winding Details of On Load tap changer Make Type Rating i) ii) iii) iv) Rated Voltage Rated current Ste p v olta ge Number of steps v)Rated Short Circuit Current Whether Diverter switch provided with gas vent and buchholz relay (Yes / No ) Whether a separate oil surge relay with trip contacts provided e) (Yes / No) f) Pressure relief valve Details of motor device unit housed in kiosk / mounted on tap g) changer h) running d) Whether Remote control panel provided with Control scheme for simultaneous operation of Tap changer when transformers are in parallel and independent control when in independent i) Details of equipment in the OLTC kiosk operation. j) Details of OLTC panels i) automatic tap changer relay ii) literature of all the relays iii) dimensions of OLTC, Panel L x B x H iv) thickness of sheet v) degree of protection vi) details of equipment supplied 39 Dispatch details : a) Approx. mass of heaviest Package (Kg) b) Approx. dimensions of largest Package i ) Length (mm) i i ) Breadth (mm) a) b) c) d) e) f) a) b) c) d) e) f) g) i i i ) Height (mm) 40 Un-tanking height (mm) 41 Bimetallic connectors HV / LV Normal current rating (A) Short time current rating (A) Tensile strength (Kg) Maximum temperature limit Dimensional sketch enclosed indicating tolerances (Yes/No) Minimum clearance (mm) - Phase to phase Phase to Earth 42CORE ASSEMBLY :Core diameter (mm ) Core window height (mm ) Core leg centre (mm ) Gross core cross – sectional area (m2) Total height of core (mm ) Details of top end frame Details of Bottom end frame Details of clamp plate (material, thickness, insulation) h) i) Total core weight (Kg ) j) Core loss, basing on core loss graph at operating flux density (rated voltage and rated frequency ) ( KW ) k) Core stacking factor l) Net core area (Sq.m) m) Margin towards corner joints, cross-fluxing, dielectric loss (KW) n) Total core loss at rated voltage and rated frequency (KW ) o) Describe location / method of core grounding p) Details of core- belting i) Material , grade and type ii) Width iii) Thickness iv) Fixing method 43 DETAILS OF WINDING a) Type of winding b) Material of the winding conductor c) Maximum current density of windings at rated current and conductor area d) Whether windings are pre-shrunk ? e) Whether adjustable coil clamps are provided for HV and LV windings ? f) Whether steel rings are used for the windings ? If so, whether these are split ? g) Whether electrostatic shields are provided to obtain uniform voltage distribution in the windings ? h) Winding Insulation ( Type & Class ) i) Insulating material , used for i) H.V winding ii) LV winding iii) Tapping connection j) Insulating material used between i) L.V and H.V winding ii) Core & L.V winding k) H.V to H.V winding between phases l) Type of axial supports i) H.V winding ii) L.V winding m) Type of radial supports i) H.V winding ii) L.V winding n) Maximum allowable torque on coil clamping bolts o) Clamping ring details i) Thickness of ring mm ii) Diameter of ring mm iii) No. & size of pressure screw p) Bare conductor size (mm) i) HV ii) LV q) Insulated conductor size (mm) i) HV ii) LV r) No. of conductor in parallel ( Nos.) i) HV ii) LV s) No. of turns / phase i) HV ii) LV t) No. of discs / phase i) HV ii) LV u) No. of turns / Disc i) HV ii) LV v) Gap between discs (mm ) i) HV ii) LV w) Inside diameter (mm ) i) HV ii) LV x) Outside diameter (mm ) i) HV ii) LV y) Axial height after shrinkage (mm ) i) HV ii) LV z) D.C Resistance 0 i) L.V winding at 75 C (Ohms ) 0 ii) H.V winding at normal tap at 75 C (Ohms ) iii) H.V winding at highest tap at 750 C (Ohms ) iv) H.V winding at lowest tap at 750 C (Ohms ) 2 0 2 0 v) Total I R losses at 75 C for normal tap (KW ) vi) Total I R losses at 75 C for highest tap (KW ) vii ) Total I2R losses at 750 C for lowest tap (KW ) 0 vii Stray losses including eddy current losses in winding at 75 C i) (KW) a) Normal tap position b) Highest tap position c) Lowest tap position d) Any special measures, taken to reduce eddy current losses and stray losses. Mention in details ix) Load losses at 750 C (I2 R + Stray ) a) Normal tap position (KW ) b) Highest tap position (KW) c) Lowest tap position (KW ) Details of special arrangement, provided to improve surge voltage x) distribution in the windings. 44 DETAILS OF TANK : a) Material of Transformer tank b) Type of tank c) Thickness of sheet (No approximate value to be mentioned) i) Sides (mm) ii) Bottom (mm ) iii) Cover (mm ) iv ) Radiators (mm) d) Inside dimensions of main tank (No approximation in dimensions to be used ) i) Length (mm) ii) Breadth (mm) iii) Height (mm ) e) Outside dimensions of main tank (No approximation in dimensions to be used ) i) Length (mm) ii) Breadth (mm) iii) Height (mm) f) Vacuum recommended for hot oil circulation (torr / mm of Hg) g) Vacuum to be maintained during oil filling in transformer tank (torr / mm of Hg) h) Vacuum to which the tank can be subjected without distortion (torr / mm of Hg) i) No. of bi-directional wheels provided j) Track gauge required for the wheels i) Transverse axis ii) Longitudinal axis k) Type and make of pressure relief device and minimum pressure at which it operates (Kpa ) 45 CONSERVATOR :a) Thickness of sheet (mm) b) Size (Dia x length ) (mm) c) Total volume (Litres) Volume between the highest and lowest visible oil levels d) (Litres) GTP NO- 9 GUARANTEED AND OTHER PARTICULARS FOR 100kVA STATION TRANSFORMERS Sl. No. Name of the Particulars Desired Value Bidder's Offer 1 Make 2 Name of Manufacturer 3 Place of Manufacture 4 Voltage Ratio 33/0.4kV 5 Rating in kVA 100kVA 6 Core Material used and Grade: a) Flux density b) Over fluxing without saturation (Curve to be furnished by the Manufacturer in support of his claim) 7 Maximum temperature rise of: a) windings by resistance method b) Oil by thermometer 8 Magnetizing (no-load) current at: a) 90% Voltage b) 100% Voltage c) 110% Voltage 9 Core loss in watts: a) Normal voltage b) Maximum voltage 10 Resistance of windings at 20°C,750C (with 5% tolerance) a) HV Winding (ohms) b) LV Winding (ohms) Load losses (watts) at 75°C 11 at normal tap(100% Load Condition) TOTAL Losses (Load loss +No Load Loss)at 100% 12 load at 75°C at rated Voltage, frequency & at normal tap. 13 Total Losses at 50% load at 75°C 14 Current density used for: (Ampere/sq mm) a) HV Winding. b) LV Winding. 15 Clearances: (mm) a) Core and LV b) LV and HV c) HV Phase to phase d) End insulation clearance to e) Any earthpoint of winding to tank. 16 Efficiency at 75°C a) Unity P.F and b) 0.8 P.F. 1) 125°C load 2) 100°C load 3) 75°C load 4) 50°C load 5) 25°C load 17 Regulation at: a) Unit P.F. b) 0.8 P.F. at 75ºC 18 % Impedance at 75ºC 19 Flash test:(i) HV 70 kV/ 50HZ for 1 minute (ii) LV 3 kV /50 Hz for 1 minutes. 20 Over potential test (Double voltage and Double frequency for 1 minute) 21 22 Impulse test. Mass of : (kg) a) b) c) d) e) f) 23 Oil Data: 1) 2) 3) 4) 24 Quantity for first filling (minimum) (litre) Grade of oil used. Maker’s name BDV at the time of filling (kV) Transformer: 1) 2) 3) a) b) 25 Core lamination (minimum) Windings (minimum) Tank and fittings Oil Oil quantity (minimum) (litre) Total weight 4) Radiation: 1 ) e x c l u d i n g 2) 3) 4) Overall length x breadth x height (mm x mm x mm) Tank length x breadth x height Thickness of plates for Side plate (min) Top and bottom plate (min) Conservator Dimensions. Heat dissipation by tank walls top and bottom Heat dissipation by cooling tube Diameter and thickness of cooling tube. Whether calculation sheet for selecting cooling area to ensure that the transformer is capable of giving continuous rated output without exceeding temperature rise is enclosed. 26 27 28 29 30 Inter layer insulation provided in design for: 1) Top and bottom layer 2) In between all layer 3) Details of end insulation. Whether wedges are provided at 4) 50ºC turns of the HV coil. Insulation materials provided. a) For Conductors 1 HV 2 LV b) For Core. Material and Size of the wire used. HV Dia (mm) Number of conductors in Total cross sectional area parallel LV Dia (mm) Number of conductors in Total cross sectional area parallel Whether the name plate gives all particulars as required in Particulars of bushings HV/LV tender 1) Maker’s name 2) Type IS-3347/IS-2099/IS-7421 3) Rating as per IS 4) Dry power frequency voltage withstand test 5) Wet power frequency voltage withstand test. Note: The following shall be specifically confirmed: 1) Whether the offer conforms to the limits of impedance mentioned in the specification. 2) Whether the offer conforms to the limits of temperature rise mentioned in the specification. 3) Whether the losses of the transformers offered are within the limits specified. 4) Whether the transformer offered is already type tested for the design and test reports enclosed. Sl. No. Description 1 Core Grade 2 Core diameter(mm) 3 Gross core area(Sq cm) 4 Net core area(Sq cm) 5 6 Flux density(Tesla) Mass of core(Kg) 7 Loss per kg of core at the specified flux density(watt) To be specified by Bidders 8 10 Core window height(mm) Center to enter distance of the core(mm) No.of LV Turns 11 No.of HV turns 12 Size of LV conductor bare/covered (mm) 13 Size o HV conductor bare/covered (mm) 14 No. of parallels 15 Current density of LV winding.(A/sq mm) 9 16 17 18 19 20 21 22 23 24 25 Current density of HV winding.(A/sq mm) Wt. of the LV winding for Transformer (kg) Wt. of the HV winding for Transformer (Kg) No. of LV Coils/phase No. of HV Coils/phase Height of LV Winding.(mm) Height of HV Winding.(mm) ID/OD of HV winding(mm) ID/OD of LV winding(mm) Size of the duct in LV winding(mm) 26 Size of the duct in HV winding(mm) 27 Size of the duct between HV and LV(mm) 29 30 HV winding to LV winding HV winding to tank clearance(mm) clearance(mm) Calculated impedance(%) 31 HV to earth creepage distance(mm) 32 LV to earth creepage distance(mm) 28 GTP NO – 10 GUARANTEED TECHNICAL PARTICULARS of Transformer OIL SL. NO. 1 Name of the Particulars Appearance 4 Density at 29.5° C (Max) gm/cc Viscosity, Kinematic at 27° C (Max) Interfacial Tension at 27° C (Min) Newton / M 5 Flash point, Pensky Marten (closed) in °C (min). 2 3 6 7 Pour point in ° C (Max) Neutralisation value a) Total acidity, mg KOH/gm (Max) b) Inorganic acidity / alkalinity 8 Corrosive sulphur (Copper strip) 19 hours at 140°C 9 Electric strength (Breakdown Voltage ) KV (rms). 10 a) New unfiltered oil (min). b) After filteration (min). Dielectric dissipation factor (Tan Delta) at 90°C (Max). Desired Value Clear and transparent free from suspended matter or sediments. 0.89 27 0.04 140 -6 0.03 Nil Non corrosive 60 60 0.002 Bidder's Offer 11 12 13 Specific resistance (resistivity) a) at 90° C , ohm-cms (Min) 35 x 1012 b) at 27° C , ohm-cms (Min) 1500 x 1012 Oxidation stability. a) Neutralisation value, after Oxidation for 164 hours at 100°C mg KOH/gm (Max). 0.4 b) Total sludge, after 164 hours at 100°C wt. % (max). 0.1 Ageing characteristics after accelerated Ageing (open beaker method with copper Catalyst) for 96 hours at 115°C a) Specific resistance(resistivity) i) at 27°C, ohm-cms (Min) i) at 90°C, ohm-cms (Min) b) Dielectric dissipation factor (Tan Delta ) at 90°C, , ohmcms (Min) c)Total acidity, mg KOH/gm (max) d) Total sludge value, Wt. % (max) 2.5 x 1012 0.2 x 1012 0.2 0.05 0.05 14 Presence of oxidation inhibitor 15 Water content, ppm (max) i) Proportion of classes of hydrocarbons in the crude oil including content of aromatic hydrocarbons. 16 ii) Details of barrel (Size, gauge inside/outside coating/weight of empty drum not less than 18 Kg.) iii) List of equipments for testing of oil as per revised ISS iv)Electric strength(breakdown voltage ) KV (Min) a) Value of the fresh sample in the supplied sealed drums KV(Min). b) Value after filling in transformer upto & within 3 months (Min) The oil shall not contain anti oxidant additives. 20 GTP NO-11 GUARANTEED TECHNICAL PARTICULARS FOR 33kV , 200 AMP, 3 POLE, H.G. FUSE Sl. No. Name of the Particulars Desired Value 1 Maker's name and country or origin To be specified by the tenderer . 2 Suitable for mounting Horizontal only. 3 Number of supporting post insulator per phase 4 nos. 22KV/24KV Post Insulator per phase as per ISS - 2544/ 1973 4 Post Insulator (a) Maker's name and country or orgin (b) Type of cemeting (c ) (d) (e) (f) (g) (h) (I ) 5 (a) (b) One minute power frequency withstand voltage dry One minute power frequency withstand voltage wet. Visible discharge voltage Dry Flashover Voltage Power frequency puncture withstand voltage Impulse withstand voltage(Switching Position) Creepage distance Impulse withstand voltage for positive and negative polarity (1.2/50 micro second wave) Across the isolating distance To earth & between poles Bidder’s Offer To be specified by the tenderder. To be quoted original cemented only. 80 KV RMS 70 KV RMS. 27 KV RMS To be specified by the tenderder. 1.3 times of actual dry flash over voltage. 170KV (peak) 380mm minimum. (actual creepage distance for which type test have been conducted is to be specified by the bidder ) 195 KV (peak) 170 KV (peak) Page No-1 of 2 / HG FUse 33 kV 6 (a) (b) 7 8 9 10 One minute power frequency withstand voltage Across the isolating distance To earth & between poles Rated normal current and rated frequency. Operating Voltage Vertical clearance from top of insulator cap to mounting Channel Height of the riser for carrying the horns. 11 Details of Arcing Horns 12 Riser Unit (250mm total height). 13 Supporting Channels 14 Galvanisation 15 Weight of each pole (complete) 80 KV (RMS) 70 KV (RMS) 200 amps, 50 Hz , 3 Pole 33 KV 508 mm (minimum) 250mm from the cap (top) of insulator. Copper rod having 8.32 mm dia Silver-plated provided with screwing arrangement for fixing use wire made of copper casting. (Total length 995mm). All the bolts, nuts and washers should be made out of brass. (a) The shape of connectors may be made of straight copper Flat of (b) 170mm height G.I. Riser made of 25mm nominal bore medium gauge G.I. Pipe welded with 2 nos. G.I. Flat of 35 x 5 mm at both ends fixed with 10mm dia stainless steel, bolts and nuts with flat stainless steel spring washers. 100 x 50 x 6 mm M.S. Channel (galvanized) All ferrous parts should be galvanized as per IS-2633/1 972 & all non-ferrous part should be duly electroplated with silver. To be specified by the tenderder. GTP NO-12 GUARANTEED TECHNICAL PARTICULARS FOR 11kV 200 AMP, 3 POLE, H.G. FUSE . Sl. No. Name of the Particulars 1 Maker's name and country or origin 2 Suitable for mounting Horizontal only. 3 Number of supporting post insulator per phase 2 nos. 12KV Post Insulator per phase as per ISS -2544/ 1973 4 Post Insulator Desired Value (a) Maker's name and country or orgin To be specified by the tenderer. (b) Type of cementing To be quoted original cemented only. (c ) One minute power frequency withstand voltage dry 28 KV RMS (d) One minute power frequency withstand voltage wet. 28 KV RMS Bidder’s Offer Page No-1 of 4 / HG FUSE11 kV (e) Visible discharge voltage 9KV RMS Dry Flashover Voltage To be specified by the tenderer. (g) Power frequency puncture withstand voltage 1.3 times of actual dry flash over voltage. (h) Impulse withstand voltage(Switching Position) 75KV (peak) (I ) Creepage distance 380mm minimum. (actual creepage distance for which type test have been conducted is to be specified by the bidder ) 5 Impulse withstand voltage for positive and negative polarity (1.2/50 micro second wave) (f) (a) Across the isolating distance 85KV (peak) (b) To earth & between poles 75 KV (peak) 6 One minute power frequency withstand voltage (a) Across the isolating distance 32 KV (RMS) (b) To earth & between poles 28 KV (RMS) Page No-2 of 4 / HG FUSE11 kV 7 Rated normal current and rated frequency. 200 amps, 50 Hz , 3 Pole 8 Operating Voltage 11 KV 9 Vertical clearance from top of insulator cap to mounting Channel 254 mm (minimum) 10 Height of the riser for carrying the horns. 150mm from the cap (top) of insulator. Details of Arcing Horns Copper rod having 7.62 mm dia Silverplated provided with screwing arrangement for fixing use wire made of copper casting. (Total length 635mm). All the bolts, nuts and washers should be made out of brass. 11 Page No-3 of 4 / HG FUSE11 kV Riser Unit 12 (250mm total height). (a) The shape of connectors may be made of straight copper Flat of size adequate enough to carry a current density not less than 1.5 Amp/ mm2. 2 Nos of 3/8” G.I. Bolts, double nuts, plain and spring washers and 2 nos. solder less bimetallic shockets per each connector suitable up to 100 mm2 AAA conductor. (b) 100mm height G.I. Riser made of 19mm nominal bore medium gauge G.I. Pipe welded with 2 nos. G.I. Flat of 30 x 5 mm at both ends fixed with 10mm dia stainless steel, bolts and nuts with flat stainless steel spring washers. Supporting Channels 75 x 40 x 6 mm M.S. Channel (galvanized) 14 Galvanisation All ferrous parts should be galvanized as per IS-2633/1972 & all non-ferrous part should be duly electroplated with silver. 15 Weight of each pole (complete) To be specified by the tenderer. 13 Page No-4 of 4 / HG FUSE11 kV GTP NO- 13 GURANTEED TECHNICAL PARTICULARS OF ISOLATOR(33kV) Sl.No Name of the Particulars Desired Value Double end break Centre post rotating, gang operated 1 Main switch 2 Service 3 Applicable standard 4 Pole 5 Rated voltage nominal/ Maximum 6 Rated Frequency 7 System earthing Effectively earthed 8 Temperature rise As per relevant IS/IEC publication 9 Insulation level impulse with stand voltage a) Across Isolating distance Bidder's Offer Outdoor IS : 9921 / IEC-129/IEC-62271-102 3 pole gang operator 33/36 kV 50 Hz (+5% to -3%) 195 kVpeak Page No-1 of 2 / 33kV Isolator b) To earth & between poles 170 kVpeak 10 1 minute power frequency withstand voltage a) Across Isolating distance 80 kVpeak b) To earth & between poles 70 kVpeak 11 Rated current in Amp 1250 12 Short time current for 3 sec 25kA 13 Operating mechanism 14 Auxiliary voltage a) Control & Inter lock 15 Motorised 33kV 48 DC 80% to 110% Safe duration of overload Page No-2 of 2 / 33kV Isolator 16 a)150% of rated current 5 minute b)120% of rated current 30 minute Minimum creepage distance of support and Rotating insulator i) Mounting structure ii) Terminal connector type iii) Control 900mm Upright on G.I structure Bimetallic clamp Local Page No-3 of 2 / 33kV Isolator