DIN HV Distribution DIN HV fuses are partial-range high voltage currentlimiting fuses for use in distribution circuits from 2.3 - 38kV. Their compact dimensions and non-venting characteristics make them ideal for restricted enclosures. DIN HV fuses have excellent short circuit performance and good low overcurrent clearing capability. When used in combination with fusible switches with fuse-activated trip feature, full range clearing capability is achieved. True full-range fuses are available in certain voltage and amp ranges. Please contact Fusetek for more information. Features ! ! ! ! ! ! ! Highly standardised DIN 43 625 dimensions. Excellent short circuit performance. Ceramic bodies, pure silver elements. '30' series fuses have temperature sensitive striker to protect against extended overload conditions, or external overheating. Sealed for indoor or outdoor use.(on Driescher products - use 'F' suffix on part number) Striker pin can be used for visual indication or to actuate a 'trip all phase' mechanism. High amp ratings available for larger installations. DRS factory paralleled configurations available. Fully plated parts for cool running. Installation Notes 1. DIN fuses are partial range devices with a minimum interrupting rating. Care must be taken to ensure that anticipated currents below the fuse's minimum breaking current (m.b.c) are cleared by other devices. In this regard, DIN fuses are similar to ANSI - 'E' rated fuses. Full range DIN fuses are available in limited voltage and amp ranges. Please contact our offices for information. 2. When DIN fuses are used in conjunction with a trip-all-phase-device, the minimum breaking capacity of the switch or contactor must be equal to or greater than the m.b.c of the fuse. 3. Voltage ranges specified are minimum and maximum voltages for safe operation. The normal +/-10% utility tolerance on voltage must be taken into account when selecting a voltage range. 4. When replacing fuses in the field, ensure that contact clips are clean and free of corrosion, dirt, grease etc... Ensure that the fuse clips still have good tension. (if the fuse will spin easily in the fuse clips, the clips have lost their tension and should be replaced) 5. Fuses should be replaced in sets of three to avoid nuisance blowing caused by element damage. Dimensions All DIN fuse share common end fittings which fit into 45mm fuse clips. The only dimensional variables are the body length (L) and body diameter (D). As this varies depending on voltage, amperage and other factors, please refer to the tables in this section for D and L dimensions. Striker pins meet industry and DIN requirements for force/travel and can be used for mechanical actuation or visual indication. Transformer application The fuse ratings recommended in the following tables have been chosen with the following conditions in mind: ! ! ! Fuses must pass normal primary winding magnetising inrush currents: These are taken as 12x the normal full load current(FLC) at .1 sec, and 25x FLC at .01 sec. Certain applications may require the use of a higher fuse rating. Please contact FUSETEK with application details. After a sustained power outage, the fuse must be able to withstand an overload of approximately 6 x FLC for 1 sec. and 3 x FLC for 10 sec. The maximum voltage rating of the fuse must be equal to, or greater than the maximum line-to-line system voltage. Capacitor application Refer to capacitor selection chart on page 44. Be sure to consider the switching options and proximity of other banks when establishing a base FLC to apply. Companion Products Insulators, clips, single pole bases - page 47-48. For information on our range of load break switches, see the loadbreak section on page 33. Current cut-off characteristics (all voltage classes) 100 500 400 355 315 250 200 160 125 100 80 63 50 40 32 25 20 16 10 6.3 peak curent (A) x 1000 10 1 0.1 0.1 pg 20 1 10 Prospective Short Circuit - rms Amps x 1000 100 Note: I2t and interrupting ratings shown in following tables are at maximum system voltage. 3.0/7.2kV Melting Time Current Characteristics General Specifications 1000 Part Number 100 30 098 13 Time in seconds 10 1 30 099 13 mbc A total I2t x 1000 6.3 25 0.37 10 40 0.57 16 56 2.0 70 4.9 90 7.8 31.5 110 10.3 40 140 19.5 50 170 34 63 210 69 280 145 320 210 390 399 600 580 800 740 1000 1200 A 20 25 80 100 DxL (mm) 53 67 292 292 I.R kA 63kA rms 63kA rms 125 30 100 13 0.1 160 85 292 40kA 200 6.3 16 10 25 40 63 20 31.5 50 100 160 80 125 30 100 14 250 355 500 200 315 400 250 315 85 292 40kA rms 355 0.01 10 100 1000 RMS Amperes 10000 100000 30 110 14 400 85 442 40kA rms 1260 1800 1420 2300 1600 2900 500 2000 4800 Other body lengths and configurations available. Please contact Fusetek. Minimum fuse for transformers rated 7.2kV or less kVA 2.4kV 4.16kV 4.8kV 6.9kV Dimensions (mm) 15 6.3A 6.3A 6.3A 10A 30 16A 10A 10A 16A 45 16A 16A 16A 25A 75 25A 20A 16A 40A 112.5 40A 25A 20A 50A 150 40A 31.5A 25A 50A 225 50A 50A 40A 80A 300 100A 63A 50A 40A 500 160A 100A 80A 63A 750 250A 125A 100A 80A 1000 315A 160A 160A 100A 1500 500A 250A 250A 160A 2000 355A 315A 200A 2500 500A 400A 250A 3000 500A 315A 4000 400A 6/12kV Melting Time Current Characteristics General Specifications 1000 Part Number 100 30 004 13 Time in seconds 10 1 30 012 13 mbc A total I2t x 1000 6.3 25 0.37 10 40 0.57 16 56 2.0 70 4.9 90 7.8 31.5 110 10.3 40 140 19.5 50 170 34 63 210 69 280 145 320 210 390 399 600 580 A 20 25 80 100 DxL (mm) 53 67 292 292 I.R kA 63kA rms 63kA rm 125 0.1 6.3 16 10 25 20 40 31.5 63 50 100 160 80 125 250 200 315 30 020 13 160 85 292 30 020 14 200 85 292 800 740 40kA 537 rms 537 1000 1100 1260 1800 30 211 14 250 85 30 211 14 315 85 63kA 0.01 10 100 1000 10000 RMS Amperes Minimum fuse for transformers rated 12kV kVA 6.9kV 7.2kV 8.3kV 15 6.3A 6.3A 6.3A 30 6.3A 6.3A 10A 45 16A 10A 16A 75 16A 16A 16A 112.5 20A 20A 20A 150 25A 25A 25A 225 31.5A 31.5A 40A 300 40A 40A 40A 500 63A 63A 63A 750 80A 80A 80A 1000 100A 100A 100A 1500 160A 160A 125A 2000 200A 200A 160A 2500 250A 250A 250A 3000 315A 315A 315A 4000 see 7.2kV class - or less 12kV 6.3A 6.3A 6.3A 10A 16A 16A 20A 25A 40A 50A 63A 100A 125A 160A 200A 250A Other body lengths and configurations available. Please contact Fusetek. Dimensions (mm) 10/17.5kV Melting Time Current Characteristics General Specifications 1000 Part Number 100 mbc A total I2t x 1000 6.3 25 0.37 10 40 0.57 56 2.0 70 4.9 90 7.8 31.5 110 10.3 40 140 19.5 170 34 210 69 280 145 A DxL (mm) I.R kA 16 30 231 13 20 53 442 63kA rms 25 Time in seconds 10 50 30 232 13 1 63 67 442 63kA rms 80 30 233 13 0.1 100 125 85 DRS15/160B4 160 85 DRS15/200B4 200 85 DRS15/250B8 250 6.3 16 10 25 40 63 100 160 250 400 20 32 50 80 125 200 315 DRS15/315B8 315 DRS15/400B8 400 0.01 10 100 1000 10000 RMS Amperes 100000 Minimum fuse for transformers rated 17.5kV or less kVA 12.47kV 13.2kV 13.8kV 14.4kV 45 6.3A 6.3A 6.3A 6.3A 75 10A 10A 6.3A 10A 112.5 16A 16A 10A 16A 150 16A 16A 16A 16A 225 20A 20A 20A 20A 300 25A 20A 20A 20A 500 40A 40A 31.5A 31.5A 750 50A 50A 50A 50A 1000 63A 63A 63A 63A 1500 100A 80A 80A 100A 2000 125A 125A 100A 100A 2500 160A 125A 125A 125A 3000 200A 200A 200A 200A 4000 250A 250A 250A 250A 5000 315A 315A 315A 315A 6000 400A 400A 315A 400A 7000 400A 400A 400A 400A 63kA rms 320 210 390 399 40kA 480 300 20kA 800 590 375 1000 442 40kA rms 480 2000 442 20kA 800 4000 442 442 442 2x 85 Other body lengths and configurations available. Please contact Fusetek. Dimensions (mm) 20/27.6kV Melting Time Current Characteristics General Specifications 1000 Time in seconds 442 63kA 25 .26 53 442 63kA 40 .56 53 442 63kA 6.3 53 30 289 13 10 16 30 287 13 1 total I2t x 1000 30 289 13 30 288 13 10 mbc A A 30 289 13 100 I.R kA Part Number DxL (mm) 56 2.0 20 70 5.0 25 90 7.8 110 12.0 31.5 40 53 442 63kA rms 140 20.0 50 170 33.5 63 210 69 80 100 67 442 63kA rms 280 145 320 210 0.1 6.3 16 10 25 40 20 31.5 63 50 100 80 0.01 10 100 1000 10000 Other body lengths and configurations available. Please contact Fusetek. RMS Amperes Fuse selection for transformers rated 25.8kV or less kVA 17kV 23kV 24kV 25.8kV 112.5 10A 10A 10A 10A 150 10A 10A 10A 16A 225 16A 16A 16A 20A 300 16A 16A 16A 20A 500 20A 20A 20A 25A 750 31.5A 31.5A 25A 40A 1000 40A 40A 40A 50A 1500 63A 63A 50A 80A 2000 80A 80A 63A 100A 2500 80A 80A 80A 3000 100A 100A 80A Dimensions (mm) 30/36kV Melting Time Current Characteristics General Specifications Part Number 1000 mbc A total I2t x 1000 25 0.37 40 0.57 56 2.0 20 70 4.9 25 90 7.8 110 10.3 140 19.5 170 34 A DxL (mm) I.R kA 6.3 10 100 30 008 13 Time in seconds 10 30 016 13 30 024 13 1 DRS30/75B5 16 31.5 40 50 63 75 DRS30/100B5 100 DRS30/125A9 125 0.1 DRS30/150B9 150 DRS30/200B9 200 6.3 16 10 25 40 20 31.5 63 50 100 80 160 250 125 200 315 DRX30/250B9 250 DRX30/315B9 315 0.01 10 100 1000 10000 RMS Amperes Fuse selection for transformers kVA 25.8kV 27.6kV 112.5 6.3 10A 150 10A 10A 225 16A 16A 300 16A 16A 500 20A 20A 750 25A 25A 1000 31.5A 40A 1500 50A 50A 2000 63A 63A 2500 75A 80A 3000 100A 80A 4000 125A 160A 5000 160A 200A 6000 200A 200A 7000 250A 200A 10000 315A 315A rated 36kV 34.5kV 6.3A 10A 10A 16A 16A 20A 25A 40A 50A 63A 75A 100A 125A 160A 200A 250A or less 36kV 6.3A 6.3A 10A 16A 16A 20A 25A 40A 50A 63A 75A 100A 125A 160A 200A 250A 53 40kA 537 rms 67 537 40kA rms 85 537 40kA rms 210 69 38 85 537 20ka rms 225 300 88 2x 66 537 16kA 158 140 2x 85 537 20kA rms 225 200 300 580 2x 85 537 Contact Fusetek Other body lengths and configurations available. Please contact Fusetek. DRS/DRX fuses are rated 38kV max. Dimensions (mm) E Rated Distribution fuses FC series power fuses are current limiting partial-range fuses usually used for fusing the primary windings of medium voltage distribution transformers and associated distribution circuits. Their high degree of current limitation greatly reduces the thermal and mechanical stresses imposed on system components during a short circuit. They can be used indoors or outdoors in a suitable enclosure and conform to standard N.American dimensions. E Rating Defined 100E or less: Fuse must open in 300sec at 200-240% of its rated current Features ! ! ! ! ! ! General purpose 'E' rated characteristics. Pure silver elements Fully plated metal parts for cool running. Excellent current limitation for substantial reduction of short circuit stresses. Blown fuse indicator pin for visual indication or mechanical actua tion (except 2" body) All D case (3" diam.) fuses can be supplied hermetically sealed and without indicator for use in Hazardous location applications. over 100E: Fuse must open in 600sec. at 220-264% of its rated current. Thus, fuses with identical E ratings will provide similar overload protection and coordination with transformer and other protective devices. Companion Products Standoff insulators, fuse clips and bases. Please see accessories section in rear of this section. For other ratings and designs, please contact Fusetek. Retrofitting Fusetek power fuses are dimensionally compatible with and interchangeable with other manufacturers' fuses having the same dimensions and ratings. Standard 'E' rated characteristics ensure electrical equivalency. Fuses should be replaced in sets of three to avoid nuiscance blowing caused by element damage. Tag Variations 3" diameter E rated fuses are available with the following options. Add the suffixes shown to the end of the part number - example; X Bi W CL - 2" longer tube to line up with some manufacturers' longer bodies. Offset mounting brackets for bolt mounting. Hookeye disconnect feature. ITE/Gould style clip-lock mounting. See page 17 for drawing details of these options. pg 34 2" Format (B diam.) Vac Type 2.5/2.7kV 4.8/5.5kV 7.2/8.3kV 13.8/15.5kV 23/25.8kV B Dimensions L CC 9.2 7.0 11.2 10.0 14.2 13.0 14.2 17.2 22.5 13.0 16.0 21.0 General Specifications Fig. 1 Part Number Ratings available FC468 FC469 1, 2, 3, 5, 7, 10, 15, 20, 25A 1, 2, 3, 5, 7, 10, 15, 20, 25A I.R rms sym. 50kA 50kA FC471 1, 2, 3, 5, 7, 10, 15, 20, 25A 50kA FC472 FC473 FC474 1, 2, 3, 5, 7, 10, 15A 1, 2, 3, 5, 7, 10, 15, 20, 25A 1, 3, 5, 7,10A 50kA 40kA 32kA 3" Format (D diam.) Dimensions Vac Type L CC D 2.4/2.75 10.8 4.8/5.5 D 7.2/8.3 DD D 13.8/15.5 30/38kV 12.0 17.8 14.0 D DD D DD 1 ***E-1C-2.75 2 ***-2C-2.75 1 4 15.8 12.0 17.8 14.0 15.8 12.0 17.8 14.0 15.8 12.0 17.8 14.0 18.8 15.0 21.8 18.0 23.8 20.0 D-ITE DD 23/25.8 15.8 D-ITE DD Part Number 7.0 DD D Fig. 2 1 2 15.0 21.8 18.0 23.8 20.0 22.5 20.0 30.8 27.0 10, 15, 20, 25, 30, 40, 50, 65, 80, 100, 125, 150, 175, 200E 125, 150, 175, 200, 225, 250, 300, 350, 400, 450E I.R rms sym. 50kA ***-1C-5.5 5NLE-*** 10, 15, 20, 25, 30, 40, 50, 65, 80, 100, 125, 150, 175, 200E ***-1CL-5.5 ***-2C-5.5 5NLE2-*** ***-1C-8.3 8NLE-*** ***-2C-8.3 8NLE2-*** 50kA 150, 200, 225, 250, 300, 350, 400, 450E 10, 15, 20, 25, 30, 40, 50, 65, 80, 100E 50kA 125, 150, 175 200, 250, 300E ***-1C-15.5 1 15GSE-*** 15NLE-*** 3 18.8 Ratings available 10, 15, 20, 25, 30, 40, 50, 65, 80, 100E ***-1CL-15.5 40kA ***-2C-15.5 2 15GSE2-*** 65, 80, 100, 125, 150, 175, 200E 15NLE-*** 1 ***-1C-25.8 15, 20, 25, 30, 40, 50E 2 ***-2C-25.8 65, 80, 100E 1 ***-1C-38 15, 20, 25, 30, 40E 2 ***-2C-38 50, 65, 80E 40kA 20kA pg 35 E rated fuse Application E rated fuses are used to isolate the voltage transformer from the supply in the event of a primary winding failure. Properly selected fuses will also operate quickly if there is a short circuit on the secondary side of the transformer. To provide optimum protection without nuisance blowing, it is necessary to consider the following points: ! ! ! The interrupting rating must be equal to or greater than the largest anticipated short circuit. The fuse must pass the magnetising inrush to the primary windings without damage or operation. This inrush is normally considered to be 12 times the primary FLC for 0.1 second. The fuse's voltage rating must be equal to, or greater than the system voltage. 3 phase FLC = kVA x 1000 vAC x 1.73 Single phase FLC = kVA x 1000 vAC all 2" (B) Format Melting Time current Characteristics Transformer Application Table Transformer Fuse Primary FLC (A) rating (A) from to 0.30 0.62 1.0 1.5 2.5 4.8 7.5 11.2 15.0 1 100 2 3 5 7 10 15 20 25 10 Time in seconds 0 0.31 0.63 1.1 1.6 2.6 4.9 7.6 11.3 1000 1 1 2 3 5 7 10 15 20 25 0.1 0.01 1 10 100 RMS Amperes pg 36 1000 5.5kV - 3" Body 'E' rated Distribution fuses Melting Time Current Characteristics General Specifications Part Number 1000 100 I.R kA XXXE-1C-5.5 1 0.1 10 20 30 50 80 15 25 40 65 125 200 300 400 100 150 250 350 XXXE-2C-5.5 0.01 10 100 1000 10000 100000 20 15 30 20 40 25 50 30 60 80 3 50 50kA 15.8 rms 100 65 130 80 160 100 200 125 250 150 300 200 400 250 500 300 400 2x3 15.8 50kA rms 450 RMS Amperes mbc A 10 40 10 Time in seconds DxL (mm) A 600 800 900 To complete part number, replace XXX with amp rating Fuse selection for transformers rated 5.5kV or less kVA 2.4kV 4.16kV 4.8kV 5.5kV 15 10E - - - 30 15E 15E 10E 10E 45 20E 15E 15E 15E 75 30E 20E 15E 15E 112.5 40E 25E 20E 20E 150 65E 30E 30E 25E 225 80E 50E 40E 40E 300 100E 65E 65E 50E 500 125E 100E 100E 80E 750 250E 125E 100E 100E 1000 300E 200E 125E 125E 1500 450E 250E 250E 200E 2000 - 350E 300E 250E 2500 - 450E 350E 350E 3000 - - 450E 400E Dimensions (in.) Fig. 1 - D Fig. 2 - DD pg 37 8.3kV - 3" Body 'E' rated Distribution fuses Melting Time Current Characteristics General Specifications Part Number 1000 100 **E-1C-8.25 Time in seconds 10 DxL (inch) A 22.5 .25 15 35 .40 20 50 .65 25 60 .90 70 1.3 90 2.0 50 125 3.0 65 150 4.0 190 6.0 100 240 8.5 125 300 12.5 150 360 18.0 480 28.0 250 600 37.0 300 720 50.0 840 65.0 960 80.0 30 3 80 10 15 0.1 25 40 65 100 150 250 350 20 30 50 80 125 200 300 400 **E-2C-8.3 0.01 10 100 1000 10000 100000 RMS Amperes **E-3C-8.3 mbc total I2t A x1000 10 40 1 I.R kA 15.8 200 350 400 50 2x3 3x3 ** - add amp rating to complete part number Fuse selection for transformers rated 8.3kV or less kVA 5.5kV 6.9kV 7.2kV 8.3kV 45 10E 10E 10E - 75 15E 15E 15E - 112.5 20E 15E 15E 10E 150 25E 20E 20E 15E 225 40E 30E 30E 20E 300 40E 40E 40E 30E 500 80E 65E 65E 50E 750 100E 100E 100E 80E 1000 150E 125E 100E 100E 1500 250E 125E 150E 150E 2000 300E 200E 200E 200E 2500 350E 300E 250E 250E 3000 400E 350E 350E 300E 3500 - 350E 350E 350E 4000 - - 400E 350E pg 38 Dimensions (in.) Fig.1 - D Fig. 2 - DD 15.5kV - 3" Body 'E' rated Distribution fuses Melting Time Current Characteristics General Specifications Part Number 1000 100 **E-1C-15.5 Time in seconds 10 DxL (mm) A I.R kA 10 22.5 1.9 15 34 3.2 20 45 4.7 25 56 6.5 68 8 90 13 113 16 146 23 80 180 30 100 225 41 125 280 58 338 75 450 115 562 149 675 199 30 3 40 50 65 1 10 0.1 15 20 30 50 80 125 200 300 25 40 65 100 150 250 **E-2C-15.5 18.8 32kA 150 2x3 200 **E-3C-15.5 0.01 10 100 1000 mbc total I2t A x1000 250 300 3x3 10000 insert amp rating for ** in above part numbers to complete RMS Amperes Fuse selection for transformers rated 15.5kV or less kVA 12.47kV 13.2kV 13.8kV 14.4kV 112.5 15E 15E 15E 10E 150 15E 15E 15E 15E 225 25E 20E 20E 20E 300 30E 30E 30E 30E 500 50E 50E 50E 50E 750 80E 80E 80E 65E 1000 100E 100E 100E 80E 1500 125E 125E 125E 125E 2000 150E 150E 150E 150E 2500 200E 150E 150E 150E 3000 200E 200E 200E 200E Dimensions (in.) Fig. 1 - D Fig. 2 - DD pg 39 HV DIN fuse bases DRIWISA™ fuse bases are available in single or 3 pole versions in 630 or 1250A (dual clip) versions. Supported voltages are 7.2, 17.5, 25.8 and 38kV. Base is heavy duty galvanised steel with epoxy resin standoff insulators. 630A silver plated clips are standard. 3 pole versions can be fitted with auxilliary microswitches for remote blown-fuse annunciation. Note: these bases can be modified to accept North American E rated fuses. Please contact Fusetek for details. Part numbers for 630A single & 3 pole DIN fuse bases Fuse body length (BL) Vac No. Poles BL=192mm BL=292mm BL=442mm BL=537mm 1 SP07/061AMN SP07/062AMN SP07/064AMN SP07/065AMN 3 DSP07/061AMN DSP07/062AMN DSP07/064AMN DSP07/065AMN 1 - SP15/062AMN SP15/064AMN SP15/065AMN 3 - DSP15/062AMN DSP15/064AMN DSP15/065AMN 1 - - SP20/064AMN SP20/065AMN 3 - - DSP20/064AMN DSP20/065AMN 1 - - - SP30/065AMN 3 - - - DSP30/065AMN 7.2kV 17.5kV 25.8kV 38kV Specifications MAXIMUM RATED BASIC IMPULSE LEVEL WITHSTAND VOLTAGE VOLTAGE CURRENT (BIL) 1.2 x 50 s 60 hZ 1 min DRY A Up kV Ud kV SERIE kV Ur pg 32 Ir TO GROUND ACROSS TO GROUND ACROSS AND BETWEEN OPEN AND BETWEEN OPEN POLES GAP POLES GAP 07 7.2 630 60 70 20 23 15 17.5 630 95 110 38 45 20 25.8 630 125 140 60 66 30 38 630 150 165 80 88 FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD HHD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS The striker pin system is connected by means of a high resistance parallel conductor. After melting the main fuse elements the striker pin will indicate the operation status of the fuse and open a load break switch or actuate a microswitch for remote indication. The temperature limiting function of the fuse striker pin Design and construction SIBA HV Fuse-links have parallel connected pure silver fuse-elements. The design and method of production of the elements ensures narrow tolerances of time-currentcharacteristics. The fuse elements are wound on a ceramic support and are attached to the silver plated connection caps by means of spot-welding. The connection caps are fitted inside the silver plated copper end caps by spot welding. The copper end caps themselves are press-fitted onto the porcelain tube which is glazed inside and outside. The end caps are furthermore mechanically fixed to the porcelain tube and additionally sealed by a durable elastic sealing medium. This sealing method has been proven over many decades of positive field experience and ensures tightness against ingress of humidity. Striker pin SIBA HV Fuse-links are available with striker pins of the force: • 80 N (Part No. 30 … 13 for basic-type) and • 120 N (Part No. 30 … 14 for variant-type) The characteristics of both striker pins corresponds to IEC 60282-1, VDE 0670 Part 4 and are of the energycategory “medium”. SIBA HV Fuse-links up to and including 160 A with a striker pin of 80 N are equipped with an integrated temperature limiter as standard. The temperature limiter is fitted inside the striker pin system. The SIBA striker pin system therefore has the following functions: • thermal protection of adjacent equipment, especially SF6 Insulated switchgear • limitation of failure current at the overload region • improved properties for the switch-fuse combinations according IEC 60420 The integrated temperature limiter avoids inadmissible high temperatures – no matter for whatever reason they are generated – in gas-insulated switchgear or narrow switchgear enclosures. By means of a melting activator temperatures inside the fuse link enclosure are limited to below approx. 100°C. This design especially considers continuity of current supply for the end user for as long as possible. The system reacts in such a way that short time overloads do not cause the fuse to interrupt the circuit unnecessarily. Only when inadmissible values are exceedes the fuse will open the switch via the striker pin. Higher temperatures on plastic fuse enclosures in SF6insulated switchgear can be caused by: • selection of a fuse rating too low for transformer protection • fuses are loaded with fault currents below the minimum operating current • deterioration of fuse links caused by transient fault currents (e.g. lightning strike) • transformer faults currents (e.g. winding short-current) • overloading of the fuse when loaded with currents as described in IEC 420 Test Duty 3 • additional temperatures rise because of poor clip fitting Fuse-links with integrated temperature limiter are compatible with standard Fuse links. All coordination schedules can be used. Further information on our temperature limiter, design, construction, can be obtained from our website. HHD 1 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Selection Guide Rated Voltage AC kV DIN Size E mm Class Part No. Selection Guide Page Techn. Data Page 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 3/7.2 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 6/12 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 10/17.5 192 192 192 192 292 292 292 292 442 442 442 192 192 292 292 292 292 442 442 442 442 537 537 292 292 292 367 367 367 367 442 442 442 Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up 30 002 13 30 010 13 30 018 13 30 018 14 30 098 13 30 099 13 30 100 13 30 100 14 30 109 13 30 110 13 30 110 14 30 119 13 30 267 13 30 004 13 30 012 13 30 020 13 30 020 14 30 101 13 30 102 13 30 103 13 30 103 14 30 211 13 30 211 14 30 255 13 30 221 13 30 222 13 30 176 13 30 177 13 30 178 13 30 178 14 30 231 13 30 232 13 30 233 13 HHD 5 HHD 5 HHD 5 HHD 5 HHD 6 HHD 6 HHD 6 HHD 6 HHD 7 HHD 7 HHD 7 HHD 8 HHD 8 HHD 9 HHD 9 HHD 9 HHD 9 HHD 10 HHD 10 HHD 10 HHD 10 HHD 11 HHD 11 HHD 12 HHD 12 HHD 12 HHD 13 HHD 13 HHD 13 HHD 13 HHD 14 HHD 14 HHD 14 HHD 23 HHD 23 HHD 23 HHD 23 HHD 23 HHD 23 HHD 23 HHD 23 HHD 24 HHD 24 HHD 24 HHD 25 HHD 25 HHD 25 HHD 25 HHD 25 HHD 25 HHD 26 HHD 26 HHD 26 HHD 26 HHD 26 HHD 26 HHD 27 HHD 27 HHD 27 HHD 27 HHD 27 HHD 27 HHD 27 HHD 28 HHD 28 HHD 28 HHD 2 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Selection Guide Rated Voltage AC kV DIN Size E mm Class Part No. Selection Guide Page Techn. Data Page 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 10/24 20/36 20/36 20/36 20/36 6/12 6/12 6/12 10/24 10/24 10/24 292 292 442 442 442 537 537 537 537 442 537 537 537 292 292 292 442 442 442 Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up General purpose General purpose General purpose General purpose General purpose General purpose 30 180 13 30 225 13 30 006 13 30 014 13 30 022 13 30 203 13 30 204 13 30 196 13 30 196 14 30 181 13 30 008 13 30 016 13 30 024 13 30 004 93 30 012 93 30 020 93 30 006 93 30 014 93 30 022 93 HHD 15 HHD 15 HHD 16 HHD 16 HHD 16 HHD 17 HHD 17 HHD 17 HHD 17 HHD 18 HHD 19 HHD 19 HHD 19 HHD 21 HHD 21 HHD 21 HHD 22 HHD 22 HHD 22 HHD 29 HHD 29 HHD 29 HHD 29 HHD 29 HHD 30 HHD 30 HHD 30 HHD 30 HHD 31 HHD 31 HHD 31 HHD 31 HHD 32 HHD 32 HHD 32 HHD 32 HHD 32 HHD 32 Selection Guide Fuse-bases Article Rated Voltage AC kV DIN-Size E mm Part No. Techn. Data Page Indoor Fuse-bases 7.2 12 24 36 24 7.2 12 24 36 192 292 442 537 292 192 292 292 537 31 001 02 31 003 02 31 005 02 31 007 02 31 221 01 31 002 01 31 004 01 31 006 01 31 008 01 HHD 40 HHD 40 HHD 40 HHD 40 HHD 40 HHD 41 HHD 41 HHD 41 HHD 41 Outdoor Fuse-bases HHD 3 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Selection Guide Article Microswitch fitting consists of Part No. Techn. Data Page Fuse Clip 31 001 10 31 001 14 34 002 01 HHD 42 HHD 42 HHD 43 Distance Plate 31 002 01.3 HHD 43 Microswitch Length mm 660 900 Selection Guide Accessories Article Rated Voltage kV Extension Adapter Test Fuse-link for gas insulated switchgear Contact Clip 200 A indoor and outdoor Contact Clip heavy duty Storage Holder HHD 4 Part No. Techn. Data Page 12/24 34 006 01 HHD 44 24 33 010 03 HHD 45 31 003 02.20 HHD 46 34 001 01.20 HHD 46 33 004 01 33 006 01 33 008 01 HHD 47 HHD 47 HHD 47 12 24 36 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E=192 mm Rated voltage AC 3/7.2 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 002 13 30 002 13 30 002 13 30 002 13 30 002 13 30 002 13 30 002 13 30 002 13 30 010 13 30 010 13 30 010 13 30 010 13 30 018 13 30 018 14 30 018 14 Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 3.35 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 53 53 53 53 53 53 53 53 67 67 67 67 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 50 50 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 2.9 2.9 2.9 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Prefered Standard size 3/7.2 kV A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 5 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 292 mm A F O N Rated voltage AC 3/7.2 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 315 A 355 A 30 098 13 30 098 13 30 098 13 30 098 13 30 098 13 30 098 13 30 098 13 30 098 13 30 099 13 30 099 13 30 099 13 30 099 13 30 100 13 30 100 14 30 100 14 30 100 14 30 100 14 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 6 (45 mm) (33 mm) (10 mm) (35 mm) FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 3.35 3.35 3.35 53 53 53 53 53 53 53 53 67 67 67 67 85 85 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 50 50 50 50 50 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 3.8 3.8 3.8 3.8 3.8 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 442 mm Rated voltage AC 3/7.2 kV Rated current Part No. 100 A 125 A 160 A 200 A 250 A 315 A 355 A 400 A 500 A 30 109 13 30 109 13 30 110 13 30 110 14 30 110 14 30 110 14 30 110 14 30 110 14 30 110 14 Class Back up D= Diameter inch mm 2.64 2.64 3.35 3.35 3.35 3.35 3.35 3.35 3.35 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 67 67 85 85 85 85 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 50 50 50 50 50 50 2.9 2.9 5.4 5.4 5.4 5.4 5.4 5.4 5.4 Pack (kg/1) 1 1 1 1 1 1 1 1 1 A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 7 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 192 mm A F O N Rated voltage AC 6/12 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 30 119 13 30 119 13 30 119 13 30 267 13 30 267 13 30 267 13 30 267 13 30 267 13 30 267 13 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 8 (45 mm) (33 mm) (10 mm) (35 mm) FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.64 2.64 2.64 2.64 2.64 2.64 53 53 53 67 67 67 67 67 67 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 1.2 1.2 1.2 1.5 1.5 1.5 1.5 1.5 1.5 Pack (kg/1) 1 1 1 1 1 1 1 1 1 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 292 mm Rated voltage AC 6/12 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 004 13 30 004 13 30 004 13 30 004 13 30 004 13 30 004 13 30 004 13 30 004 13 30 012 13 30 012 13 30 012 13 30 012 13 30 020 13 30 020 14 Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 53 53 53 53 53 53 53 53 67 67 67 67 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 50 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 3.8 3.8 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Prefered Standard size 6/12 kV A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 9 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 442 mm A F O N Rated voltage AC 6/12 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 101 13 30 101 13 30 101 13 30 101 13 30 101 13 30 101 13 30 101 13 30 101 13 30 102 13 30 102 13 30 102 13 30 102 13 30 103 13 30 103 14 30 103 14 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 10 (45 mm) (33 mm) (10 mm) (35 mm) FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 3.35 53 53 53 53 53 53 53 53 67 67 67 67 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 50 50 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.9 2.9 2.9 2.9 5.4 5.4 5.4 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 537 mm Rated voltage AC 6/12 kV Rated current Part No. 100 A 125 A 160 A 200 A 250 A 315 A 30 211 13 30 211 13 30 211 13 30 211 14 30 211 14 30 211 14 Class Back up D= Diameter inch mm 3.35 3.35 3.35 3.35 3.35 3.35 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 85 85 85 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 50 50 50 6.8 6.8 6.8 6.8 6.8 6.8 Pack (kg/1) 1 1 1 1 1 1 A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 11 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 292 mm A F O N Rated voltage AC 10/17.5 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 30 255 13 30 255 13 30 255 13 30 221 13 30 221 13 30 221 13 30 221 13 30 221 13 30 221 13 30 222 13 30 222 13 30 222 13 30 222 13 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 12 (45 mm) (33 mm) (10 mm) (35 mm) FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.64 2.64 2.64 2.64 2.64 2.64 3.35 3.35 3.35 3.35 53 53 53 67 67 67 67 67 67 85 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 3.8 3.8 3.8 3.8 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 367 mm Rated voltage AC 10/17.5 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 176 13 30 176 13 30 176 13 30 176 13 30 176 13 30 177 13 30 177 13 30 177 13 30 177 13 30 178 13 30 178 13 30 178 13 30 178 13 30 178 14 Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 2.64 3.35 3.35 3.35 3.35 3.35 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 53 53 53 53 53 67 67 67 67 85 85 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 40 2.0 2.0 2.0 2.0 2.0 3.0 3.0 3.0 3.0 4.8 4.8 4.8 4.8 4.8 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 13 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 442 mm A F O N Rated voltage AC 10/17.5 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 231 13 30 231 13 30 231 13 30 231 13 30 231 13 30 231 13 30 231 13 30 232 13 30 232 13 30 232 13 30 233 13 30 233 13 30 233 13 30 233 14 1.77 ” (45 mm) 1.30 ” (33 mm) 0.40 ” (10 mm) 1.38 ” (35 mm) HHD 14 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 3.35 3.35 3.35 3.35 53 53 53 53 53 53 53 67 67 67 85 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 40 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.9 2.9 2.9 5.4 5.4 5.4 5.4 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 292 mm Rated voltage AC 10/24 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 30 180 13 30 180 13 30 180 13 30 225 13 30 225 13 30 225 13 30 225 13 30 225 13 30 225 13 Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.64 2.64 2.64 2.64 2.64 2.64 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 53 53 53 67 67 67 67 67 67 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 Pack (kg/1) 1 1 1 1 1 1 1 1 1 A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 15 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 442 mm FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Rated voltage AC 10/24 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 30 006 13 30 006 13 30 006 13 30 006 13 30 006 13 30 006 13 30 006 13 30 014 13 30 014 13 30 014 13 30 022 13 30 022 13 D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 3.35 3.35 Prefered Standard size 10/24 kV A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 16 (45 mm) (33 mm) (10 mm) (35 mm) Class Back up 53 53 53 53 53 53 53 67 67 67 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 40 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.9 2.9 2.9 5.4 5.4 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 537 mm Rated voltage AC 10/24 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 203 13 30 203 13 30 203 13 30 203 13 30 203 13 30 203 13 30 203 13 30 204 13 30 204 13 30 204 13 30 196 13 30 196 13 30 196 13 30 196 14 30 196 14 Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.64 2.64 2.64 3.35 3.35 3.35 3.35 3.35 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 53 53 53 53 53 53 53 67 67 67 85 85 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 40 31.5 31.5 31.5 2.8 2.8 2.8 2.8 2.8 2.8 2.8 3.7 3.7 3.7 6.8 6.8 6.8 6.8 6.8 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 17 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 442 mm A F O N Rated voltage AC 20/36 kV Rated current Part No. 6.3 A 10 A 16 A 30 181 13 30 181 13 30 181 13 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 18 (45 mm) (33 mm) (10 mm) (35 mm) FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Class Back up D= Diameter inch mm 2.10 2.10 2.10 53 53 53 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 20 20 20 2.2 2.2 2.2 Pack (kg/1) 1 1 1 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 537 mm Rated voltage AC 20/36 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 30 008 13 30 008 13 30 008 13 30 008 13 30 008 13 30 016 13 30 016 13 30 024 13 30 024 13 30 024 13 Class Back up D= Diameter inch mm 2.10 2.10 2.10 2.10 2.10 2.64 2.64 3.35 3.35 3.35 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 53 53 53 53 53 67 67 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 40 40 40 40 40 40 40 40 40 40 2.6 2.6 2.6 2.6 2.6 3.5 3.5 6.0 6.0 6.0 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 Prefered Standard size 20/36 kV A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 19 HHD FUSES HIGH VOLTAGE FUSES FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS GERMAN DIN STANDARD – GENERAL PURPOSE According IEC 60 282-1 and VDE 0670 Part 4, a General-Purpose-Fuse interrupts fault currents between the rated breaking current and the current which causes melting within one hour. The protection range of the SIBAVS-Protector extends this basic demand. The minimum breaking current is about 1.5 times the rated current. In combination with the temperature released striker pin a full range protection is possible. Additional feature is the small powerloss of the VS-Protector. It is up to 40 % smaller than the standard DIN-fuse. The dimensions of the VS-Protector are VS-Protector for the overload and short-circuit range according to DIN 43625. The rated voltages 12 and 24 kV and also the available current ratings allow protection of transformers up to 630 kVA. The function of the VS-Protector is comparable to a typical Back up Fuse link. The melting elements of pure silver are wound inside onto a ceramic support. A short section in the center of the fuse is designed as a “Heat chamber”. Inside this chamber the elements are made of silver-alloy. They generate a certain level of temperature at overloads. As a result the fuses interrupt at low fault-currents without ageing. HHD 20 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 292 mm Rated voltage AC 6/12 kV Rated current Part No. 6.3 A 8A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 30 004 93 30 012 13 30 012 93 30 012 93 30 012 93 30 012 93 30 012 93 30 012 93 30 020 93 30 020 93 30 020 93 30 020 93 Class General purpose D= Diameter inch mm 2.10 2.64 2.64 2.64 2.64 2.64 2.64 2.64 3.35 3.35 3.35 3.35 FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS 53 67 67 67 67 67 67 67 85 85 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 3.8 3.8 3.8 3.8 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 A F O N 1.77 ” 1.30 ” 0.40 ” 1.38 ” (45 mm) (33 mm) (10 mm) (35 mm) HHD 21 HHD FUSES HIGH VOLTAGE FUSES GERMAN DIN STANDARD DIN Size E= 442 mm A F O N Rated voltage AC 10/24 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 30 006 93 30 014 93 30 014 93 30 014 93 30 014 93 30 022 93 30 022 93 1.77 ” 1.30 ” 0.40 ” 1.38 ” HHD 22 (45 mm) (33 mm) (10 mm) (35 mm) FOR AIR & GAS INSULATED SWITCHGEARS OUTDOOR SWITCHGEARS Class General purpose D= Diameter inch mm 2.10 2.64 2.64 2.64 2.64 3.35 3.35 53 67 67 67 67 85 85 Standard DIN 43625 · IEC 60282-1 Rated breaking current kA Weight 40 40 40 40 40 40 40 2.2 2.9 2.9 2.9 2.9 5.4 5.4 Pack (kg/1) 1 1 1 1 1 1 1 Electrical Characteristics DIN Size E= 192 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 002 13 30 002 13 30 002 13 30 002 13 30 002 13 30 002 13 30 002 13 30 002 13 30 010 13 30 010 13 30 010 13 30 010 13 30 018 13 30 018 14 30 018 14 DIN Size E= 292 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 315 A 355 A 30 098 13 30 098 13 30 098 13 30 098 13 30 098 13 30 098 13 30 098 13 30 098 13 30 099 13 30 099 13 30 099 13 30 099 13 30 100 13 30 100 14 30 100 14 30 100 14 30 100 14 FUSES Rated voltage AC 3/7.2 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 63 63 63 63 50 50 22 34 56 70 90 110 140 170 210 280 320 390 600 800 1,000 Rated voltage AC 3/7.2 kV 22 34 56 70 90 110 140 170 210 280 320 390 600 800 1,000 1,260 1,420 Power loss W Pre-arcing I2t-value A2s 10 17 17 13 16 21 27 30 38 47 64 98 124 146 210 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 90,000 230,000 371,000 Power loss W Pre-arcing I2t-value A2s 10 17 17 13 16 21 27 30 38 47 64 98 103 134 191 281 336 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 90,000 230,000 371,000 545,000 825,000 178.0 113.0 50.0 27.0 21.0 17.0 13.0 9.3 6.8 4.8 3.8 3.3 2.4 1.9 1.6 Total I2t value @ 3 kV @ 7.2 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 330,000 480,000 750,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 570,000 704,000 1,101,000 Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 63 63 63 63 50 50 50 50 HHD 178.0 113.0 50.0 27.0 21.0 17.0 13.0 9.3 6.8 4.8 3.8 3.3 2.3 1.9 1.6 1.2 1.0 Total I2t value @ 3 kV @ 7.2 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 330,000 480,000 750,000 1,066,000 1,420,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 570,000 704,000 1,101,000 1,616,000 2,225,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 23 HHD Electrical Characteristics FUSES DIN Size E= 442 mm Rated current Part No. 100 A 125 A 160 A 200 A 250 A 315 A 355 A 400 A 500 A 30 109 13 30 109 13 30 110 13 30 110 14 30 110 14 30 110 14 30 110 14 30 110 14 30 110 14 Rated voltage AC 3/7.2 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 50 50 50 50 50 50 320 390 600 800 1,000 1,260 1,420 1,600 2,000 3.8 3.3 2.3 2.1 1.8 1.5 1.3 1.1 0.85 Power loss W Pre-arcing I2t-value A2s 64 98 85 155 233 281 320 347 430 33,000 47,000 90,000 230,000 371,000 545,000 825,000 1,000,000 1,668,000 Total I2t value @ 3 kV @ 7.2 kV A2s A2s 130,000 180,000 330,000 480,000 750,000 1,066,000 1,420,000 1,900,000 3,162,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 24 210,000 390,000 570,000 704,000 1,101,000 1,616,000 2,225,000 2,528,000 4,500,000 Electrical Characteristics DIN Size E= 192 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 30 119 13 30 119 13 30 119 13 30 267 13 30 267 13 30 267 13 30 267 13 30 267 13 30 267 13 DIN Size E= 292 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 004 13 30 004 13 30 004 13 30 004 13 30 004 13 30 004 13 30 004 13 30 004 13 30 012 13 30 012 13 30 012 13 30 012 13 30 020 13 30 020 14 FUSES Rated voltage AC 6/12 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 22 34 56 70 90 110 140 170 210 Rated voltage AC 6/12 kV 22 34 56 70 90 110 140 170 210 280 320 390 600 800 Power loss W Pre-arcing I2t-value A2s 16 28 28 23 29 38 50 56 63 45 75 250 640 1,050 1,700 2,900 5,700 10,700 Power loss W Pre-arcing I2t-value A2s 16 28 28 23 29 38 50 56 63 76 104 159 173 234 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 90,000 230,000 297 189 87 46 36 29 22 16 12 Total I2t value @ 6 kV @ 12 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 63 63 63 63 50 HHD 297.0 189.0 84.0 45.0 34.0 28.0 22.0 16.0 12.0 8.5 6.5 5.5 3.9 3.0 Total I2t value @ 6 kV @ 12 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 330,000 480,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 570,000 704,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 25 HHD Electrical Characteristics FUSES DIN Size E= 442 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 101 13 30 101 13 30 101 13 30 101 13 30 101 13 30 101 13 30 101 13 30 101 13 30 102 13 30 102 13 30 102 13 30 102 13 30 103 13 30 103 14 30 103 14 DIN Size E= 537 mm Rated current Part No. 100 A 125 A 160 A 200 A 250 A 315 A 30 211 13 30 211 13 30 211 13 30 211 14 30 211 14 30 211 14 Rated voltage AC 6/12 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 63 63 63 63 50 50 22 34 56 70 90 110 140 170 210 280 320 390 600 800 1,000 Rated voltage AC 6/12 kV 320 390 600 800 1,000 1,260 Pre-arcing I2t-value A2s 16 28 19 22 28 37 48 54 58 70 96 147 172 193 269 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 90,000 230,000 371,000 Power loss W Pre-arcing I2t-value A2s 96 147 172 193 274 382 33,000 47,000 90,000 230,000 371,000 545,000 297.0 189.0 87.0 46.0 36.0 29.0 22.0 16.0 12.0 8.5 6.5 5.5 3.9 2.9 2.6 Total I2t value @ 6 kV @ 12 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 330,000 480,000 750,000 6.5 5.5 3.9 3.2 2.6 2.2 Total I2t value @ 6 kV @ 12 kV A2s A2s 130,000 180,000 330,000 480,000 750,000 1,066,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 26 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 570,000 704,000 1,101,000 Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 50 50 50 Power loss W 210,000 390,000 570,000 704,000 1,101,000 1,616,000 Electrical Characteristics DIN Size E= 292 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 30 255 13 30 255 13 30 255 13 30 221 13 30 221 13 30 221 13 30 221 13 30 221 13 30 222 13 30 222 13 30 222 13 30 222 13 30 222 13 DIN Size E= 367 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 176 13 30 176 13 30 176 13 30 176 13 30 176 13 30 177 13 30 177 13 30 177 13 30 177 13 30 178 13 30 178 13 30 178 13 30 178 13 30 178 14 FUSES Rated voltage AC10/17.5 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 53 53 53 63 63 63 63 63 85 85 85 85 85 22 34 56 70 90 110 140 170 210 280 320 390 600 Rated voltage AC 10/17.5 kV 22 34 56 70 90 110 140 170 210 280 320 390 600 800 Power loss W Pre-arcing I2t-value A2s 21 38 37 40 56 65 84 101 106 137 182 235 290 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 90,000 Power loss W Pre-arcing I2t-value A2s 21 38 37 40 56 65 84 101 106 137 182 235 290 330 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 90,000 230,000 397.0 252.0 116.0 62.0 48.0 39.0 29.0 21.0 16.0 11.0 8.7 7.5 5.2 Total I2t value @ 10 kV @ 17.5 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 330,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 570,000 Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 63 63 63 63 40 HHD 397.0 252.0 116.0 62.0 48.0 39.0 29.0 21.0 16.0 11.0 8.7 7.5 5.2 3.85 Total I2t value @ 10 kV @ 17.5 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 330,000 480,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 570,000 704,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 27 HHD Electrical Characteristics FUSES DIN Size E= 442 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 231 13 30 231 13 30 231 13 30 231 13 30 231 13 30 231 13 30 231 13 30 232 13 30 232 13 30 232 13 30 233 13 30 233 13 30 233 13 30 233 14 Rated voltage AC 10/17.5 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 63 63 63 63 40 22 34 56 70 90 110 140 170 210 280 320 390 600 800 397.0 252.0 116.0 62.0 48.0 39.0 29.0 21.0 16.0 11.0 8.7 7.5 5.2 3.85 Power loss W Pre-arcing I2t-value A2s 21 38 37 42 56 60 84 101 106 137 182 235 290 330 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 90,000 230,000 Total I2t value @ 10 kV @ 17.5 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 330,000 480,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 28 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 570,000 704,000 Electrical Characteristics DIN Size E= 292 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 30 180 13 30 180 13 30 180 13 30 225 13 30 225 13 30 225 13 30 225 13 30 225 13 30 225 13 DIN Size E= 442 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 30 006 13 30 006 13 30 006 13 30 006 13 30 006 13 30 006 13 30 006 13 30 014 13 30 014 13 30 014 13 30 022 13 30 022 13 FUSES Rated voltage AC 10/24 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 22 34 56 70 90 110 140 170 210 Rated voltage AC 10/24 kV 22 34 56 70 90 110 140 170 210 280 320 390 Power loss W Pre-arcing I2t-value A2s 29 52 59 46 56 72 106 108 132 45 75 250 640 1,050 1,700 2,900 5,700 10,700 Power loss W Pre-arcing I2t-value A2s 29 52 59 46 56 72 106 108 132 174 234 320 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 546 347 160 86 66 53 41 29 21 Total I2t value @ 10 kV @ 24 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 63 63 40 HHD 546 347 151 83 62 52 41 29 22 16 13 11 Total I2t value @ 10 kV @ 24 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 29 HHD Electrical Characteristics FUSES DIN Size E= 537 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 203 13 30 203 13 30 203 13 30 203 13 30 203 13 30 203 13 30 203 13 30 204 13 30 204 13 30 204 13 30 196 13 30 196 13 30 196 13 30 196 14 Rated voltage AC 10/24 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 63 63 63 63 63 63 63 63 63 63 63 40 31.5 31.5 22 34 56 70 90 110 140 170 210 280 320 390 600 800 546.0 347.0 160.0 86.0 66.0 53.0 43.0 29.0 21.0 16.0 13.0 11.0 8.0 5.3 Power loss W Pre-arcing I2t-value A2s 29 52 57 45 55 70 103 101 121 147 240 320 381 440 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 33,000 47,000 90,000 230,000 Total I2t value @ 10 kV @ 24 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 130,000 180,000 330,000 480,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 30 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 210,000 390,000 570,000 704,000 Electrical Characteristics DIN Size E= 442 mm Rated current Part No. 6.3 A 10 A 16 A 30 181 13 30 181 13 30 181 13 DIN Size E= 537 mm Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 30 008 13 30 008 13 30 008 13 30 008 13 30 008 13 30 016 13 30 016 13 30 024 13 30 024 13 30 024 13 FUSES Rated voltage AC 20/36 kV Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 20 20 20 22 34 56 Rated voltage AC 20/36 kV 22 34 56 70 90 110 140 170 210 280 Power loss W Pre-arcing I2t-value A2s 44 78 74 45 75 250 Power loss W Pre-arcing I2t-value A2s 44 78 79 66 87 102 144 186 224 280 45 75 250 640 1,050 1,700 2,900 5,700 10,700 21,000 819 521 241 Total I2t value @ 20 kV @ 36 kV A2s A2s 210 350 1,100 360 560 3,000 Class Back up Rated Minimum Cold breaking breaking resistance current kA current A mOhm 40 40 40 40 40 40 40 40 40 40 HHD 819 521 241 129 99 80 60 44 32 23 Total I2t value @ 20 kV @ 36 kV A2s A2s 210 350 1,100 2,900 4,700 6,600 12,000 20,000 40,000 78,000 360 560 2,000 4,800 7,500 12,000 19,000 33,000 66,000 140,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGES HHD 33 AND HHD 34 HHD 31 HHD Electrical Characteristics FUSES DIN Size E= 292 mm Rated current Part No. 6.3 A 8A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 30 004 93 30 012 93 30 012 93 30 012 93 30 012 93 30 012 93 30 012 93 30 012 93 30 020 93 30 020 93 30 020 93 30 020 93 DIN Size E= 442 mm Rated current Part No. 6.3 A 8A 10 A 16 A 20 A 25 A 31.5 A 40 A 30 006 93 30 014 93 30 014 93 30 014 93 30 014 93 30 014 93 30 022 93 30 022 93 Rated voltage AC 6/12 kV Breaking Cold current resistance kA mOhm 63 63 63 63 63 63 63 63 63 63 63 63 150 120 100 40 31 25 20 16 15 12 9 7.7 Rated voltage AC 10/24 kV Breaking Cold current resistance kA mOhm 40 40 40 40 40 40 40 40 273 220 180 70 55 45 41 33 Class General Purpose Power loss W Pre-arcing I2t-value A2s Total I2t value @ 12 kV A2s 7 9 12 12 15 18 23 29 42 54 79 108 110 180 240 530 850 1,330 2,100 3,400 5,500 8,500 16,200 23,500 900 1,400 2,000 4,400 7,000 11,000 18,000 28,000 33,000 68,000 142,000 183,000 Class General Purpose Power loss W Pre-arcing I2t-value A2s Total I2t value @ 24 kV A2s 13 17 22 19 27 38 54 77 110 180 240 530 850 1,330 2,100 3,400 900 1,400 2,000 4,400 7,000 11,000 18,000 28,000 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGE HHD 35 HHD 32 Electrical Characteristics FUSES Time Current Characteristics HHD Back up Virtual Pre-arcing Time t(s) RMS Prospective Current I(A) Cut Off Current Diagram Back up Cut-off Current Peak Ic (kA) Prospective Short Circuit Current I(kA) HHD 33 HHD Electrical Characteristics FUSES Time Current Characteristics Back up Virtual Pre-arcing Time t(s) RMS Prospective Current I(A) Cut Off Current Diagram Back up Cut-off Current Peak Ic (kA) Prospective Short Circuit Current HHD 34 I(kA) Electrical Characteristics FUSES Time Current Characteristics HHD General Purpose Virtual Pre-arcing Time t(s) RMS Prospective Current I(A) Cut Off Current Diagram General Purpose Cut-off Current Peak Ic (kA) Prospective Short Circuit Current I(kA) HHD 35 HHD FUSES HV fuse link Vertical Cross Section Weather resistant label Integrated temperature limiter Sealing compound Shaped cap Melting element support Thermal Zone (at General Purpose fuse only) Ceramic insulating tube Silver melting element welded to contact strap Connecting straps pastened to contactcap by resistance welding Force / distance diagram 80 N 120 N Quarzsand mm HHD 36 mm FUSES HHD Recommendation for the protection of main transformer with HV-Fuse links DIN Standard Protection using LV-Fuse links* operating class gG / gL on the low voltage side Transformer rated capacity (kVA) 6 - 7.2 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 10 - 16 20 - 31.5 25 - 40 31.5 - 50 40 - 63 50 - 80 63 - 100 80 - 100 100 - 125 125 - 160 160 160 - 200 250 2 x 160 2 x 200 Line Voltage (kV) 10 - 12 20 - 24 Rated current of the HV-fuse (A) 10 16 - 20 16 - 25 20 - 31.5 25 - 40 31.5 - 50 40 - 50 50 - 80 63 - 80 80 - 125 100 - 125 125 - 160 160 200 250 6.3 10 10 - 16 16 - 20 16 - 20 20 - 25 20 - 25 25 - 40 31.5 - 50 40 - 63 63 63 - 80 80 100 125 TYPE A 30 - 36 LV fuse gG / gL (A) 4 - 6.3 6.3 - 10 10 10 - 16 16 16 - 20 20 - 25 20 - 25 25 - 31.5 31.5 - 40 40 - 50 40 - 50 50 63 80 63 125 160 200 250 315 400 500 630 800 1000 1250 – – – * Use of the recommended HV-Fuse links in connection with LV-fuse links of other manufacturer must be checked before installation TYPE A SIBA HV SIBA LV - gG / gL SIBA LV - gG / gL HHD 37 HHD FUSES Recommendation for the protection of main transformer with HV-Fuse links DIN Standard Protection without using a common LV-Fuse link on the low voltage side; the individual cable exits are protected with a LV-Fuse link operating class gL / gG Transformer rated capacity (kVA) 6 - 7.2 10 - 12 Line Voltage (kV) 15 - 17.5 20 - 24 Rated current of the HV-fuse (A) 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 10 - 16 16 - 31.5 20 - 40 31.5 - 50 31.5 - 63 40 - 80 50 - 100 63 - 100 80 - 125 100 - 160 125 - 160 160 - 200 250 2 x 160 2 x 200 10 16 - 25 16 - 31.5 20 - 31.5 25 - 40 25 - 40 31.5 - 50 40 - 63 50 - 80 63 - 100 80 - 125 100 - 160 160 200 250 6.3 - 10 16 20 20 - 25 20 - 31.5 25 - 31.5 31.5 31.5 - 50 31.5 - 63 40 - 80 63 - 100 63 - 100 100 125 160 TYPE B SIBA HV SIBA LV - gG / gL HHD 38 6.3 10 10 - 16 16 - 20 16 - 20 16 - 25 16 - 25 20 - 40 25 - 50 31.5 - 63 40 - 63 50 - 80 80 100 125 TYPE B 30 - 36 4 - 6.3 6.3 - 10 6.3 - 10 10 - 16 10 - 16 10 - 20 16 - 25 16 - 25 20 - 31.5 20 - 40 25 - 50 31.5 - 50 50 63 80 FUSES HHD Application recommendation for protection of capacitors with HV-Fuse links DIN Standard Assignment of rated currents of HV-Fuse links to DIN Standard to Capacitor rated capacities Capacitor rated capacity (kVAr) 6 - 7.2 50 100 200 250 300 400 500 750 1000 1250 1600 2000 10 20 40 50 63 80 100 160 200 250 315 315 Line Voltage (kV) 10 - 12 20 - 24 Rated current of the HV-fuse (A) 6.3 10 20 25 31.5 40 50 80 100 125 160 200 6.3 6.3 10 16 16 20 25 40 50 63 80 100 To control the occuring voltage during switch off Fuse link should be chosen from the next higher voltage range. e.g. 10 kV Capacitor with 20 kV Fuse links. (See also IEC 549, Chapter II, § 3.2) HHD 39 HHD FUSES HV Fuse-bases Rated Voltage 7.2 kV Part No. 31 001 02 A B C D E F G H I J K L 13.78 ” (350 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 7.60 ” (193 mm) 6.14 ” (156 mm) 12.20 ” (310 mm) 9.53 ” (242 mm) 0.60 ” (15 mm) 2.17 ” (55 mm) 1.38 ” (35 mm) 14.96 ” (380 mm) for indoor application Rated Voltage 12 kV Part No. 31 003 02 Rated Voltage 24 kV Part No. 31 005 02 Rated Voltage 36 kV Part No. 31 007 02 Rated Voltage 24 kV Part No. 31 221 01* A B C D E F G H I J 17.72 ” (450 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 11.54 ” (293 mm) 6.14 ” (156 mm) 16.14 ” (410 mm) 9.53 ” (242 mm) 0.60 ” (15 mm) 7.10 ” (180 mm) A B C D E F G H I J 23.62 ” (600 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 17.44 ” (443 mm) 9.30 ” (236 mm) 22.60 ” (574 mm) 12.68 ” (322 mm) 0.60 ” (15 mm) 11.80 ” (300 mm) A B C D E F G H I J 27.36 ” (695 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 21.18 ” (538 mm) 12.83 ” (326 mm) 26.60 ” (676 mm) 16.22 ” (412 mm) 0.60 ” (15 mm) 14.96 ” (380 mm) A B C D E F G H I J 17.72 ” (450 mm) 1.38 ” (35 mm) 3.35 ” (85 mm) 0.70 ” (18 mm) 11.54 ” (293 mm) 9.30 ” (236 mm) 16.14 ” (410 mm) 12.68 ” (322 mm) 0.60 ” (15 mm) 7.10 ” (180 mm) L 18.90 ” (480 mm) L 24.80 ” (630 mm) L 28.54 ” (725 mm) L 18.90 ” (480 mm) * Reduced Length for 24 kV Fuse links, E= 292 mm HHD 40 FUSES HV Fuse-bases Rated Voltage 7.2 kV Part No. 31 002 01 A B C D E F G H I J K L N O P 13.78 ” (350 mm) 1.38 ” (35 mm) 4.72 ” (120 mm) 0.80 ” (20 mm) 7.60 ” (193 mm) 9.33 ” (237 mm) 16.14 ” (410 mm) 12.80 ” (325 mm) 0.60 ” (15 mm) 2.17 ” (55 mm) 1.38 ” (35 mm) 14.96 ” (380 mm) 3.15 ” (80 mm) 0.43 ” (11 mm) 14.57 ” (370 mm) HHD for outdoor application Rated Voltage 12 kV Part No. 31 004 01 Rated Voltage 24 kV Part No. 31 006 01 Rated Voltage 36 kV Part No. 31 008 01 A B C D E F G H I J 17.72 ” (450 mm) 1.38 ” (35 mm) 4.72 ” (120 mm) 0.80 ” (20 mm) 11.54 ” (293 mm) 9.33 ” (237 mm) 20.08 ” (510 mm) 12.80 ” (325 mm) 0.60 ” (15 mm) 7.10 ” (180 mm) A B C D E F G H I J 23.62 ” (600 mm) 1.38 ” (35 mm) 4.72 ” (120 mm) 0.80 ” (20 mm) 17.44 ” (443 mm) 12.09 ” (307 mm) 25.98 ” (660 mm) 15.55 ” (395 mm) 0.60 ” (15 mm) 11.81 ” (300 mm) A B C D E F G H I J 27.36 ” (695 mm) 1.38 ” (35 mm) 4.72 ” (120 mm) 0.80 ” (20 mm) 21.18 ” (538 mm) 15.24 ” (387 mm) 30.91 ” (785 mm) 18.70 ” (475 mm) 0.60 ” (15 mm) 14.95 ” (380 mm) L N O P 18.90 ” (480 mm) 3.15 ” (80 mm) 0.43 ” (11 mm) 18.50 ” (470 mm) L N O P 24.80 ” (630 mm) 3.15 ” (80 mm) 0.43 ” (11 mm) 24.40 ” (620 mm) L N O P 28.54 ” (725 mm) 3.15 ” (80 mm) 0.43 ” (11 mm) 29.33 ” (620 mm) HHD 41 HHD FUSES Microswitch L= 660 mm L= 900 mm Part No. 31 001 10 31 001 14 Microswitch Part No. 28 001 04 250 V / 6 A 1 change over contact Flexible Cable Connection bar of the spring clip contact Part No. 34 002 01 HHD 42 HV-Fuse cap FUSES Fuse Clip HV-Spring clip contact with connection bar A B F G H L M 1.38 ” 1.26 ” 0.24 ” 2.80 ” 3.74 ” 3.66 ” M 10 1.26 ” 1.38 ” 0.24 ” 0.40 ” 0.20 ” 0.70 ” 0.26 ” Part No. 34 002 01 (35 mm) (32 mm) (156 mm) (71.5 mm) (95 mm) (93 mm) Spacer A B C D E F G HHD Part No. 31 002 01.3 (32 mm) (35 mm) (6 mm) (18 mm) (5 mm) (18 mm) (6.5 mm) HHD 43 00 HHD FUSES 24 kV Extension adapter for high voltage Fuses 12kV Part No. 34 006 01 A B C D F G H L 1.77 ” 0.06 ” 2.00 ” 1.73 ” 1.77 ” 0.20 ” 2.76 ” 7.28 ” (45 mm) (1.5 mm) (51 mm) (44 mm) (45 mm) (5 mm) (70 mm) (185 mm) A E1 E2 F L 1.77 ” (45 mm) 11.50 ” (292 mm) 17.40 ” (442 mm) 1.30 ” (33 mm) 20.00 ” (508 mm) HV-Fuse with 24 kV Extension adapter (Part No. 34 006 01) HHD 44 FUSES Test-Fuse HHD with time delayed release for testing the release mechanism in enclosed medium voltage switchgear Part No. 33 010 03 1.77 ” (45 mm) 2.76 ” (70 mm) 7.56 ” (192 mm) 1.34 ” (34 mm) 0.30 ” (8 mm) 1.06 ” (27 mm) 10.24 ” (260 mm) Force (N) A D E F G H L Clamp lever for timer To change E an adaptor is available from 192 mm to 292 mm Part No. 34 004 02 from 192 mm to 442 mm Part No. 34 006 02 Travel (mm) HHD 45 00 HHD FUSES HV-Contact clip Rated Current 200 A for indoor and outdoor application Part No. 31 003 02.20 B G H HV-Contact clip Rated Current > 200 A 1.26 ” (32 mm) 2.80 ” (71.5 mm) 3.74 ” (95 mm) for indoor and outdoor application Part No. 34 001 01.20 B G H HHD 46 1.26 ” (32 mm) 2.90 ” (73.5 mm) 4.92 ” (125 mm) HHD HHD 48 FUSES DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Overview DRIWISA™ high voltage, current-limiting fuses are devices with a high interrupting capacity to protect high voltage systems against short-circuits. They are selective elements for individual operation, with very well defined time-current characteristics, ideal for protection of transformers, motors, capacitors banks, cables, lines and other high voltage equipment installed in switchgear and distribution networks. The accumulated experience for almost 30 years of DRIESCHER Y WITTJOHANN, S.A. in Mexico with the support of FRITZ DRIESCHER GmbH in Germany, has permitted the use of the electrical principles and phenomena involved during the fusing and arcing process, which are the basis to design and manufacture the fuses with a high dependability and quality level. The company has also characterized herself for the support and instructing capacity for its customers, making sure, that every technical problem the client has, is solved to a complete satisfaction. DRIWISA™ high voltage, current-limiting fuses are designed and manufactured according to international standards. This means, that the mechanical and dimensional features, such as the tube diameters and lenghts and the force of the tripping pin of the fuses are according to these standards. The electrical features and specifications, such as the maximum interrupting current (I1), the critical interrupting current (I2), and the minimum interrupting current (I3) have been satisfactorily tested in internationally recognized labotarories. DRIWISA™ fuses are built within a service range from 2.4 to 38 kV. The DRS series is built for indoor use, while the DRS series (with "F" end-code) is used in outdoor applications, even for installation in tropical and very humid climates, for system frecuencies from 40 to 60 Hz. These fuses can be installed on special fuse-holders, non-load isolator switches and load-break disconnecting switches, thus giving an adecuate protection against the dangerous thermic and dynamic stresses during a short-circuit (refer to the corresponding sections in the catalogue). Fuses from the DRK series, having tapped end-caps, may be used for capacitor protection, being screwed directly onto the capacitor bushings. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-1 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Currrent-limiting: When protecting equipment such as transformers, motors, capacitors, cables or lines with DRIWISA™ fuses the currents flowing in case of a short-circuit are considerably reduced, due to the current-limiting characteristic of the fuses (refer to Figure 5 in the Fuse Manual). Fuses not sensitive to transformer or motor inrush currents: Due to their relatively slow time-current characteristic, DRIWISA™ fuses installed to protect transformers or motors do not exhibit premature fusion or degradation of the fuse-elements if selected according to the recommendations given in Technical Bulletins 201 and 202. Permanently fixed fuse-elements: The fuse-elements are wound on special element-holders with dented borders to ensure they are held in place permanently, thus avoiding dislocation and preventing internal short-circuits, which would provoke a degradation of the fuses characteristics. Tripping device with excellent operation characteristics: DRIWISA™ fuses are equipped with a tripping device (striker pin) acting through a stored-energy mechanism in a precompressed spring, which trips with a force of 120 N (120 kp), large enough to even open disconnecting switches which have not been operated during an extended period of time, thus presenting friction and resistance due to dust, dirt and corrosion (refer to Figure 3 in the Fuse Manual). High interrupting capacity: DRIWISA™ fuses display a high interrupting capacity which permits the interruption of very high short-circuit currents (refer to Figure 6 in the Fuse Manual). Selectivity and protection coordination: Maintaining a ratio of 1:1.6 between fuses installed in series the right coordination and protection selectivity is achieved, which makes isolation and faultdetection easy. Unnecessary power interruptions can be avoided (refer to section "Selection" in the Fuse Manual). Special sealing of fuses for outdoor service: The sealing of the fuses is accomplished by the use of special epoxic resins to avoid moisture penetration. For outdoor service fuses a special weld is used to perfectly seal against humidity. Repair with factory warranty: Due to their special design and construction DRIWISA™ fuses are the only ones that permit repairing in the factory, guaranteeing their original characteristics, when the porcelain tube has not been damaged. This means an interesting economic saving feature and an alternative for recicling materials, as a contribution to the environment protection. Immediate availability: Due to the large distribution network set up by DRIESCHER Y WITTJOHANN S.A. with authorized representatives located at strategic locations, DRIWISA™ fuses are made available on short notice, thus representing a great advantage for the immediate replacement of used elements. Technical support: DRIESCHER Y WITTJOHANN, S.A. offers her customers immediate technical support and advise when needed as for the proper selection of the right fuse for each particular case, to protect transformers, motors, capacitors, distribution lines and any other high voltage equipment, editing technical bulletins with complementary information on the fuses and on subjects related to their application, selection and maintenance. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-2 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE SELECTION CHART DRIESCHER Y WITTJOHANN, S.A. manufactures DRIWISA™ fuses types DRS, DRK and DRN for the voltage and current ratings shown in the Tables of pages 5 to 11 with the interrupting capacities and dimensions given in the corresponding columns. The following versions are available: TYPE END-CODE CHARACTERISTICS / APPLICATION DRS without end-code Indoor service, with striker-pin from 2 Amperes. For transformer, motor and overhead lines and cable feeders protection. Commonly used in combination with load-break switches and vacuum contactors. DRS....F ....F Outdoor service, for polluted or humid environments. For transformer, motor and overhead lines and cable feeders protection. DRK without end-code Indoor service, tapped end-caps, without striker pin. For capacitor protection. Screw-mounted on bushings. DRN without end-code Indoor service, without striker-pin, 1, 2 and 4 Amperes only for potential transformer protection. They have special "e" lenghts. For mounting on fuse-holders. SERIE MAXIMUM VOLTAGE (phase to phase) kV DR....04 4.8 DR....07 7.2 DR....12 12 DR....13 13.8 DR....15 17.5 DR....20 25.8 DR....30 38 Selection criteria are chosen according to the application, as described in Technical Bulletins 201 to 205. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-3 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE General specifications Fuse dimensions according to international standards. DRS..A ∅2 e Type DRS and DRS…F with striker-pin Indoor service: without end-code Outdoor service: with “F” end-code L DRS..B 66 mm 85 mm size e 1 192 mm 2 292 mm 4 442 mm 5 537 mm + 66 mm e DW-2002 DRK..A ∅2 e Type DRK and DRK…F without striker-pin For capacitor protection Indoor and outdoor service L DRK..B 66 mm 85 mm size e 1 192 mm 2 292 mm 4 442 mm 5 537 mm + 66 mm e DW-2003 Voltage DRN e L Type DRN and DRN…F without striker-pin Indoor service: without end-code Outdoor service: with “F” end-code For potential transformer protection. 1, 2 and 4 Amp. size e 1 162 mm 2 280 mm 4 433 mm e + 60 mm 7.2 y 17.5 kV 25.8 kV 38 kV Dim ensions in m m HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 DW-2001 EDITION 2003 I-4 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Fuses with striker pin for transformer, motor and overhead lines and cable feeders protection. TYPE INTERRUPTING MINIMUM RATED CURRENT In A CAPACITY I1 kA INTERRUPTING CURRENT I3 A e mm 2 4 6 10 16 25 32 40 50 63 75 100 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 20 20 5 10 15 25 40 63 80 100 125 189 240 300 292 292 292 292 292 292 292 292 292 292 292 292 358 358 358 358 358 358 358 358 358 358 358 358 2 4 6 10 16 25 32 40 50 63 75 100 125 160 200 200 80 80 80 80 80 80 80 80 80 40 63 40 40 20 25 25 5 10 15 25 40 63 80 100 125 189 240 300 375 480 800 800 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 537 2 4 6 10 16 25 32 40 50 63 63 75 100 125 160 125 160 40 40 40 40 40 40 40 40 25 25 40 25 25 40 25 40 25 5 10 15 25 40 63 80 100 125 189 189 240 300 375 480 375 480 442 442 442 442 442 442 442 442 442 442 442 442 442 442 442 537 537 DIMENSIONS L ∅1 mm mm ∅2 mm WEIGHT approx. kg 45 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 66 85 85 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 3.2 3.2 508 508 508 508 508 508 508 508 508 508 508 508 508 508 508 603 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 4.5 4.5 4.5 4.5 4.5 5.4 508 508 508 508 508 508 508 508 508 508 508 508 508 508 508 603 603 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 85 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 4.3 4.3 4.3 4.3 4.3 5.4 5.4 Vmax = 13.8 kV DRS13/002-A2 DRS13/004-A2 DRS13/006-A2 DRS13/010-A2 DRS13/016-A2 DRS13/025-A2 DRS13/032-A2 DRS13/040-A2 DRS13/050-A2 DRS13/063-A2 DRS13/075-B2 DRS13/100-B2 Vmax = 17.5 kV DRS15/002-A4 DRS15/004-A4 DRS15/006-A4 DRS15/010-A4 DRS15/016-A4 DRS15/025-A4 DRS15/032-A4 DRS15/040-A4 DRS15/050-A4 DRS15/063-A4 DRS15/075-B4 DRS15/100-B4 DRS15/125-B4 DRS15/160-B4 DRS15/200-B4 DRS15/200-B5 Vmax = 25.8 kV DRS20/002-A4 DRS20/004-A4 DRS20/006-A4 DRS20/010-A4 DRS20/016-A4 DRS20/025-A4 DRS20/032-A4 DRS20/040-A4 DRS20/050-A4 DRS20/063-A4 DRS20/063-B4 DRS20/075-B4 DRS20/100-B4 DRS20/125-B4 DRS20/160-B4 DRS20/125-B5 DRS20/160-B5 HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-5 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Fuses with striker pin for transformer, motor and overhead lines and cable feeders protection. TYPE INTERRUPTING MINIMUM RATED CURRENT In A CAPACITY I1 kA INTERRUPTING CURRENT I3 A e mm 125 160 125 160 200 250 315 40 40 63 63 63 40 40 375 480 375 480 800 1000 1260 192 192 292 292 292 292 292 258 258 358 358 358 358 358 2 4 6 10 16 25 32 40 50 63 75 100 40 40 40 40 40 40 40 40 40 40 40 40 5 10 15 25 40 63 80 100 125 189 240 300 192 192 192 192 192 192 192 192 192 192 192 192 2 4 6 10 16 25 32 40 50 63 75 100 100 125 160 200 250 315 400 500 63 63 63 63 63 63 63 63 63 63 63 63 63 40 40 63 40 40 20 20 5 10 15 25 40 63 80 100 125 189 240 300 300 375 480 800 1000 1260 1600 2000 125 160 200 63 63 63 375 480 800 DIMENSIONS L ∅1 mm mm ∅2 mm WEIGHT approx. kg 45 45 45 45 45 45 45 85 85 85 85 85 85 85 2.6 2.6 3.2 3.2 3.2 3.2 3.2 258 258 258 258 258 258 258 258 258 258 258 258 45 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 66 66 66 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 292 292 292 292 292 292 292 292 292 292 292 292 442 442 442 442 442 442 442 442 358 358 358 358 358 358 358 358 358 358 358 358 508 508 508 508 508 508 508 508 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 85 85 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 292 292 292 358 358 358 45 45 45 85 85 85 3.1 3.1 3.1 Vmax = 4.8 kV DRS04/125-B1 DRS04/160-B1 DRS04/125-B2 DRS04/160-B2 DRS04/200-B2 DRS04/250-B2 DRS04/315-B2 Vmax = 7.2 kV DRS07/002-A1 DRS07/004-A1 DRS07/006-A1 DRS07/010-A1 DRS07/016-A1 DRS07/025-A1 DRS07/032-A1 DRS07/040-A1 DRS07/050-A1 DRS07/063-A1 DRS07/075-A1 DRS07/100-A1 Vmax = 7.2 kV DRS07/002-A2 DRS07/004-A2 DRS07/006-A2 DRS07/010-A2 DRS07/016-A2 DRS07/025-A2 DRS07/032-A2 DRS07/040-A2 DRS07/050-A2 DRS07/063-A2 DRS07/075-A2 DRS07/100-A2 DRS07/100-B4 DRS07/125-B4 DRS07/160-B4 DRS07/200-B4 DRS07/250-B4 DRS07/315-B4 DRS07/400-B4 DRS07/500-B4 Vmax = 12 kV DRS12/125-B2 DRS12/160-B2 DRS12/200-B2 HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-6 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Fuses with striker pin for transformer, motor and overhead lines and cable feeders protection. TYPE INTERRUPTING MINIMUM RATED CURRENT In A CAPACITY INTERRUPTING CURRENT I3 A 2 4 6 10 16 25 32 40 50 63 75 100 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 16 20 20 I1 kA e mm DIMENSIONS L ∅1 mm mm ∅2 mm WEIGHT approx. kg 603 603 603 603 603 603 603 603 603 603 603 603 66 66 66 66 66 66 66 66 66 66 85 85 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 5.4 5.4 Vmax = 38 kV DRS30/002-A5 DRS30/004-A5 DRS30/006-A5 DRS30/010-A5 DRS30/016-A5 DRS30/025-A5 DRS30/032-A5 DRS30/040-A5 DRS30/050-A5 DRS30/063-A5 DRS30/075-B5 DRS30/100-B5 5 10 15 25 40 63 80 100 125 189 240 300 537 537 537 537 537 537 537 537 537 537 537 537 45 45 45 45 45 45 45 45 45 45 45 45 Fuses without striker-pin for potential transformer protection: Vmax = 7.2 kV DRN07/001-A1R DRN07/002-A1R DRN07/004-A1R DRN07/001-A1 DRN07/002-A1 1 2 4 1 2 40 40 40 40 40 3 5 10 3 5 162 162 162 192 192 228 228 228 258 258 45 45 45 45 45 66 66 66 66 66 1.4 1.4 1.4 1.5 1.5 1 2 4 1 2 31.5 31.5 31.5 31.5 31.5 3 5 10 3 5 162 162 162 292 292 228 228 228 358 358 45 45 45 45 45 66 66 66 66 66 1.4 1.4 1.4 2.1 2.1 1 2 4 1 2 31.5 31.5 31.5 40 40 3 5 10 3 5 280 280 280 442 442 346 346 346 508 508 45 45 45 45 45 66 66 66 66 66 1.9 1.9 1.9 2.1 2.1 1 2 4 1 2 31.5 31.5 31.5 31.5 31.5 2.5 5 10 2.5 5 433 433 433 537 537 499 499 499 603 603 45 45 45 45 45 66 66 66 66 66 3.2 3.2 3.2 3.3 3.3 Vmax = 13.8 kV DRN13/001-A1R DRN13/002-A1R DRN13/004-A1R DRN13/001-A2 DRN13/002-A2 Vmax = 23 kV DRN20/001-A2R DRN20/002-A2R DRN20/004-A2R DRN20/001-A4 DRN20/002-A4 Vmax = 38 kV DRN30/001-A4R DRN30/002-A4R DRN30/004-A4R DRN30/001-A5 DRN30/002-A5 Real rated current is determined applying a factor of 90% over the value given in the table, for instance, a 400 A fuse, 400 x 0.9 = 360 A HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-7 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE DUAL VERSION. Fuses with striker pin for transformer, motor and overhead lines and cable feeders protection. TYPE INTERRUPTING MINIMUM RATED CURRENT In A CAPACITY INTERRUPTING CURRENT I3 A e mm 250 315 40 40 750 960 192 192 258 258 400 500 630 63 40 40 1600 2000 2520 292 292 292 125 150 200 63 63 63 378 480 600 315 400 500 630 63 63 40 40 250 315 400 ∅2 mm WEIGHT approx. kg 45 45 85 85 5.4 5.4 358 358 358 45 45 45 85 85 85 6.4 6.4 6.4 292 292 292 358 358 358 45 45 45 66 66 66 4.4 4.4 4.4 960 1600 2000 2520 442 442 442 442 508 508 508 508 45 45 45 45 85 85 85 85 9.4 9.4 9.4 9.4 63 40 40 750 960 1600 292 292 292 358 358 358 45 45 45 85 85 85 6.4 6.4 6.4 125 150 200 31.5 20 20 378 480 600 292 292 292 358 358 358 45 45 45 66 85 85 4.4 6.4 6.4 250 315 400 40 40 20 750 960 1600 442 442 442 508 508 508 45 45 45 85 85 85 9.4 9.4 9.4 400 25 1600 537 603 45 85 11 200 250 315 25 20 20 600 750 960 442 442 442 508 508 508 45 45 45 85 85 85 9.4 9.4 9.4 250 315 40 25 750 960 537 537 603 603 45 45 85 85 11 11 125 150 200 16 20 20 378 480 600 537 537 537 603 603 603 45 45 45 66 85 85 6.8 11 11 I1 kA DIMENSIONS L ∅1 mm mm Vmax = 4.8 kV Length 1 (192 m m ) DRS04/250-B6 DRS04/315-B6 Length 2 (292 m m ) DRS04/400-B7 DRS04/500-B7 DRS04/630-B7 Vmax = 7.2 kV Length 2 (292 m m ) DRS07/125-A7 DRS07/150-A7 DRS07/200-A7 Length 4 (442 m m ) DRS07/315-B8 DRS07/400-B8 DRS07/500-B8 DRS07/630-B8 Vmax = 12 kV Length 2 (292 m m ) DRS12/250-B7 DRS12/315-B7 DRS12/400-B7 Vmax = 13.8 kV Length 2 (292 m m ) DRS13/125-A7 DRS13/150-B7 DRS13/200-B7 Vmax = 17.5 kV Length 4 (442 m m ) DRS15/250-B8 DRS15/315-B8 DRS15/400-B8 Length 5 (537 m m ) DRS15/400-B9 Vmax = 25.8 kV Length 4 (442 m m ) DRS20/200-B8 DRS20/250-B8 DRS20/315-B8 Length 5 (537 m m ) DRS20/250-B9 DRS20/315-B9 Vmax = 38 kV Length 5 (537 m m ) DRS30/125-A9 DRS30/150-B9 DRS30/200-B9 HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-8 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Fuses without striker-pin for capacitor protection: TYPE INTERRUPTING MINIMUM RATED CURRENT In A CAPACITY I1 kA INTERRUPTING CURRENT I3 A e mm 125 160 125 160 200 250 315 40 40 63 63 63 40 40 375 480 375 480 800 1000 1260 192 192 292 292 292 292 292 258 258 358 358 358 358 358 4 6 10 16 25 32 40 50 63 75 100 40 40 40 40 40 40 40 40 40 40 40 10 15 25 40 63 80 100 125 189 240 300 192 192 192 192 192 192 192 192 192 192 192 6 10 16 25 32 40 50 63 75 100 100 125 160 200 250 315 400 500 63 63 63 63 63 63 63 63 63 63 63 40 40 63 40 40 20 20 15 25 40 63 80 100 125 189 240 300 300 375 480 800 1000 1260 1600 2000 125 160 200 63 63 63 375 480 800 DIMENSIONS L ∅1 mm mm ∅2 mm WEIGHT approx. kg 45 45 45 45 45 45 45 85 85 85 85 85 85 85 2.6 2.6 3.2 3.2 3.2 3.2 3.2 258 258 258 258 258 258 258 258 258 258 258 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 66 66 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 292 292 292 292 292 292 292 292 292 292 442 442 442 442 442 442 442 442 358 358 358 358 358 358 358 358 358 358 508 508 508 508 508 508 508 508 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 85 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.5 292 292 292 358 358 358 45 45 45 85 85 85 3.1 3.1 3.1 Vmax = 4.8 kV DRK04/125-B1 DRK04/160-B1 DRK04/125-B2 DRK04/160-B2 DRK04/200-B2 DRK04/250-B2 DRK04/315-B2 Vmax = 7.2 kV DRK07/004-A1 DRK07/006-A1 DRK07/010-A1 DRK07/016-A1 DRK07/025-A1 DRK07/032-A1 DRK07/040-A1 DRK07/050-A1 DRK07/063-A1 DRK07/075-A1 DRK07/100-A1 Vmax = 7.2 kV DRK07/006-A2 DRK07/010-A2 DRK07/016-A2 DRK07/025-A2 DRK07/032-A2 DRK07/040-A2 DRK07/050-A2 DRK07/063-A2 DRK07/075-A2 DRK07/100-A2 DRK07/100-B4 DRK07/125-B4 DRK07/160-B4 DRK07/200-B4 DRK07/250-B4 DRK07/315-B4 DRK07/400-B4 DRK07/500-B4 85 Vmax = 12 kV DRK12/125-B2 DRK12/160-B2 DRK12/200-B2 HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-9 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Fuses without striker-pin for capacitor protection: TYPE INTERRUPTING MINIMUM RATED CURRENT In A CAPACITY I1 kA INTERRUPTING CURRENT I3 A e mm 4 6 10 16 25 32 40 50 63 75 100 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 20 20 10 15 25 40 63 80 100 125 189 240 300 292 292 292 292 292 292 292 292 292 292 292 358 358 358 358 358 358 358 358 358 358 358 6 10 16 25 32 40 50 63 75 100 125 160 200 200 80 80 80 80 80 80 80 40 63 40 40 20 25 25 15 25 40 63 80 100 125 189 240 300 375 480 800 800 442 442 442 442 442 442 442 442 442 442 442 442 442 537 4 6 10 16 25 32 40 50 63 63 75 100 125 160 125 160 40 40 40 40 40 40 40 25 25 40 25 25 40 25 40 25 10 15 25 40 63 80 100 125 189 189 240 300 375 480 375 480 442 442 442 442 442 442 442 442 442 442 442 442 442 442 537 537 DIMENSIONS L ∅1 mm mm ∅2 mm WEIGHT approx. kg 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 85 85 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.1 3.2 3.2 508 508 508 508 508 508 508 508 508 508 508 508 508 603 45 45 45 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 85 85 85 85 85 85 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 4.5 4.5 4.5 4.5 4.5 5.4 508 508 508 508 508 508 508 508 508 508 508 508 508 508 603 603 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 66 66 66 66 66 66 66 66 66 85 85 85 85 85 85 85 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 2.8 4.3 4.3 4.3 4.3 4.3 5.4 5.4 Vmax = 13.8 kV DRK13/004-A2 DRK13/006-A2 DRK13/010-A2 DRK13/016-A2 DRK13/025-A2 DRK13/032-A2 DRK13/040-A2 DRK13/050-A2 DRK13/063-A2 DRK13/075-B2 DRK13/100-B2 Vmax = 17.5 kV DRK15/006-A4 DRK15/010-A4 DRK15/016-A4 DRK15/025-A4 DRK15/032-A4 DRK15/040-A4 DRK15/050-A4 DRK15/063-A4 DRK15/075-B4 DRK15/100-B4 DRK15/125-B4 DRK15/160-B4 DRK15/200-B4 DRK15/200-B5 Vmax = 25.8 kV DRK20/004-A4 DRK20/006-A4 DRK20/010-A4 DRK20/016-A4 DRK20/025-A4 DRK20/032-A4 DRK20/040-A4 DRK20/050-A4 DRK20/063-A4 DRK20/063-B4 DRK20/075-B4 DRK20/100-B4 DRK20/125-B4 DRK20/160-B4 DRK20/125-B5 DRK20/160-B5 HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-10 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Fuses without striker-pin for capacitor protection: TYPE RATED CURRENT In A INTERRUPTING MINIMUM CAPACITY INTERRUPTING CURRENT I3 A I1 kA e mm DIMENSIONS L ∅1 mm mm ∅2 mm WEIGHT approx. kg 603 603 603 603 603 603 603 603 603 603 603 66 66 66 66 66 66 66 66 66 85 85 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 5.4 5.4 Vmax = 38 kV DRK30/004-A5 DRK30/006-A5 DRK30/010-A5 DRK30/016-A5 DRK30/025-A5 DRK30/032-A5 DRK30/040-A5 DRK30/050-A5 DRK30/063-A5 DRK30/075-B5 DRK30/100-B5 4 6 10 16 25 32 40 50 63 75 100 31.5 31.5 31.5 31.5 31.5 31.5 31.5 31.5 16 20 20 10 15 25 40 63 80 100 125 189 240 300 537 537 537 537 537 537 537 537 537 537 537 45 45 45 45 45 45 45 45 45 45 45 FOR MECHANICAL AND ELECTRICAL SPECIFICATIONS, SEE SECTION I OF CATALOG. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-11 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Fuse selection chart for transformer protection: 1.- Determine the system voltage in kV. 2.- Determine the transformer power in kVA. 3.- Find the rated current of the fuse (In) on the table below, in the intersection of the voltage column and the transformer power row. Pow er in kVA 15 30 45 75 112.5 150 225 300 400 500 750 1000 1250 1500 2000 2500 3000 3750 5000 7500 10000 Operation voltage in kV 4.16 4.8 7.2 13.2 13.8 15 17.5 23 25.8 34.5 36 Com m ents Serie 07 Serie 15 Serie 20 Serie 30 10 4 4 4 2 2 1 1 1 1 1 1 Fuse w ithout 16 10 10 6 4 4 2 2 2 2 1 1 striker-pin 25 16 10 10 4 4 4 4 4 2 2 2 (1and 2 A) 40 25 25 16 6 6 6 6 4 4 4 4 63 32 32 25 10 10 10 10 6 6 4 4 75 40 40 25 16 16 16 10 10 6 6 6 125 63 63 40 25 25 25 16 16 10 10 10 160 100 75 50 32 25 25 25 16 16 10 10 Standard 200 125 100 75 40 40 32 32 25 25 16 16 Fuse w ith 250 160 125 100 50 40 40 32 25 25 16 16 striker-pin 400 200 200 125 75 63 63 50 40 40 25 25 (from 2 Am p) 500 315 250 160 100 100 100 75 50 50 40 32 400 315 200 125 125 100 100 63 63 50 40 2x315 One fuse == 500 400 250 160 125 125 100 75 75 50 50 per-phase == 500 400 200 160 160 160 100 100 75 75 2x315 == == 400 200 200 200 125 125 100 100 2x315 2x125 == == == 500 200 160 160 100 100 2x160 2x160 2x125 == == == 2x315 2x200 2x160 2x160 2x125 2x100 2x100 2x63 2x63 Tw o fuses == == == == == == 2x200 2x200 2x160 2x125 2x100 2x100 per-phase == == == == == == == == == == == == Circuit-breaker == == == == == == == == == == == == required Rated fuse current (In) in Am peres 2.4 4.- For cases not considered in the table, calculate the fuse rated current using the formula below: In = 1.155 x kVA . kV 5.- Choose the next higher current rating from the table below: Standardized fuse current ratings (In) 1 2 4 6 10 Serie Serie Serie Serie 16 30: 20: 15: 07: 25 32 40 50 63 75 100 125 160 200 250 315 400 500 30...38 kV 20...25.8 kV 12...17.5 kV 2.4...7.2 kV 6.- Consult the fuse Selection Charts and determine the corresponding type. 7.- For further details consult Technical Bulletin 201. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 I-12 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE FIGURE 8 DRIWISA™ fuses time-current characteristic curves. For fuses from 1 to 6 A HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-13 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE FIGURE 9 DRIWISA™ fuses time-current characteristic curves. For fuses from 6 to 500 A HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-14 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE FIGURE 10 DRIWISA™ fuses I2t characteristic curve for operation times less than 0.1 sec HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-15 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE RATED CURRENT (A) MAXIMUM RATED VOLTAGES (kV) 4.8 1 2 4 6 10 16 25 32 40 50 63 75 100 125 160 200 250 315 400 500 • • • • • 7.2 • • • • • • • • • • • • • • • • • • • • 12 • • • 13.8 17.5 25.8 38 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • TABLE 1 DRIWISA™ current-limiting fuses manufacturing program DESIGN AND CONSTRUCTION: The fuse design ponders on a several compartments system or series of arcing chambers, where the voltaic arc produced by the fusion and/or evaporation of the fuse link is quenched. Fuse links, formed by one or several 99.9 % pure silver strips, are uniformly wound over a star shaped strip-holder (star-shaped body) built out of steatite (a ceramic material with great mechanical and thermal resistance), in agreement to every particular fuse design. Due to its tooth edges design, the star-shaped body guarantees the fuse link safe and firm position. Together the star-shaped body and the fuse links are put into a porcelain tube which sets up the fuse cilindric body, thus forming the series of arcing chambers (Figure 1). In every one of these arcing chambers a part of the voltaic arc produced by the fusion and/or evaporation of the fuse link when a short-circuit occurs, is started, developed and quenched. This process is described farther on. Therefore the fusion and interrupting process is carried out without the influence of external factors. Fuse links have a group of precision holes regularly spaced lengthwise, calibrated in agreement to each fuse feature, which constitutes a reduction in the conduction cross-section. When a short-circuit current is flowing, it is in these zones where the elements fusion is produced and the voltaic arc during the first part of the current wave is established. Type and number of parallel connected silver strips depend of the fuse rated current. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-6 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE According to the above mentioned, the uniform distribution of the voltaic arc and the resulting voltage of the fuse operation is assured. The high interrupting capacity and the rated current wide range available, are mainly the result of these design features which allow the dissipation of the thermic energy generated during the fusion and/or evaporation process in a uniformly distributed shape. The fuse is filled with silica sand of specific granulometry and formulation, thus providing the proper environment for voltaic arc cooling and quenching through the absorption and dissipation of the generated heat and condensation and solidification of the evaporated metal. DW-2009 DRIWISA™ fuse before and after a short-circuit current interruption Figure 2 shows a fuse after it has operated, where the melted strip elements in each chamber, uniformly distributed and parts of intact strips in the transition points from one chamber to another can be seen. The voltaic arc starts in the middle of each chamber where the thicker melted elements are found. They become thinner at the same time as they get closer to the walls that separate one chamber from another, showing the interrupting characteristic in a distributed shape. Intact strip residues at the transition points indicate the availability of an additional fuse interrupting capacity. Fuse ends have silver coated electrolitic copper caps which are connected inside to the silver strips ends. DRS and DRS...F types have a mechanic indicator which operates through a stored energy system in a preloaded spring mechanism with a striker pin that emerges by one fuse end when the fuse blows out with a force of 120 N (12 Kg-force) and a travel of 35 mm. In accordance with IEC standard classifications, the striker pin features of DRIWISA™ fuses place it as heavy duty (strong) type. Exhaustive tests have demonstrated that it is capable of activating the DRIWISA™ disconnector switch quick make mechanisms even in critical conditions, such as a blocked mechanism after a long period of time without operation, overcoming friction and resistance caused by the presence of dust, dirtiness, rust on hinges or lack of lubrication. Figure 3 shows the mechanic indicator force-displacement characteristic. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-7 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE FIGURE 3 DRIWISA™ fuse before and after a short-circuit current interruption DRIWISA™ fuses work satisfactorily in any mounting position. In every case epoxy-resin is used as a seal between the caps and the porcelain tube, to assure great resistance and long life sealing, waterproof and resistant to most severe and extreme atmospheric conditions. For outdoor fuses, additionally a special welding between the caps and porcelain tube is used to offer an optimum sealing. At facilities with high degree of humidity, coastal, tropic or rainy zones, it is recommended to use outdoor fuses (type DRS...F) even when installed in interiors. In regard to their electrical, dimensional and mechanical characteristics (diameters, lenghts, striker pin operation force, etc) DRIWISA™ fuses are manufactured in accordance with international standards. For further details, consult the catalog Selection Guide (Section I) which contains the specifications and mechanical and electrical data. OPERATION: OPERATION PRINCIPLE: When a short-circuit condition occurs in an electric network, very appreciable thermic and dynamic effects are produced because of the high current values. The interruption of these currents in the shortest time possible is very important, since the damages produced by overheating of conducting parts and by dynamic stresses must be avoided or at least minimized. Current-limiting and high interrupting capacity fuses are used as protection against short-circuit currents. The importance falls on the current-limiting effect, which is the fuse capacity to interrupt a short-circuit current before it reaches its maximum peak value by limiting the value of ID to the breaking current or fusion current IS . This is considerably less than the non-limited short-circuit current (prospective current) Ik" shown in Figure 4 with a dotted line and which corresponds to the short-circuit current available at the point where the fault occurs. Figure 4 shows the current and voltage behavior during a short-circuit current and the interrupting process. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-8 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Ik" IS ID ID = IS tS tL short-circuit prospective current (in case that fuse does not exist) (rms value) fusion current (peak value) let-through current (peak value) short-circuit current limited by the fuse prearcing time (fusion time) arcing time FIGURE 4 Short-circuit current interrupting process in a current-limiting fuse When the short-circuit begins, a minimum resistance opposes the flow of the current ID thus increasing at the same time the current Ik" and starting the temperature elevation process in the fuse link (silver strips). When they reach the IS value, (fuse breaking current or fusion current) the fuse link melts and/or evaporates and interrupts the circuits on several points, with multiple voltaic arcs showing up, whose length increases quickly with the material melting and/or evaporating. Voltage increases rapidly from the moment of the fusion, reaching a maximum (interruption voltage) and the current is limited to the IS value. At this moment a current decreasing process begins. The limiting process is therefore the result of the insertion of the voltaic arcs resistance at several points from the fusion. When arcs turn cold by effect of the surrounding sand consequently the conductivity is reduced and therefore, the resistance to the current flow increases quickly. The current decreases gradually at the same time as the voltage. Near to the next pass through voltage zero, the voltaic arcs are extinguished and the current remains totally interrupted. The described events occur within the first half cycle of the short-circuit current, meaning, in less than 8 to 10 milliseconds. Formation of multiple voltaic arcs at the fuse length as a consecuence of DRIWISA™ fuses special design gives a uniform voltage distribution as result as well as of and the great amount of energy (heat) produced during this short process, thus preventing the posibility of arc reignition. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-9 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Figure 5 shows DRIWISA™ current-limiting fuses characteristic indicating the let-through current maximum value ID (equal to the fusion current IS) with regard to the prospective short-circuit current rms value ( Ik" ) for fuses from 6 to 500 A. FIGURE 5 Maximum let-through current ID refered to the short-circuit prospective current Ik" Line A-A' represents the maximum asymmetrical peak current that would show up in the circuit for every value of the symmetrical short-circuit prospective current Ik" (rms value) in case a fuse would not exist. The value of 1.8 x √2 corresponds to the maximum asymmetric value possible in the network for the first phase to interrupt, which represents the most critical condition. The lines corresponding to every fuse rated current show the maximum let-through current ID (which corresponds to the fusion current IS ) in relation to the short-circuit prospective current Ik" (rms value). For example, for a short-circuit prospective current of Ik" = 20 kA rms a let-through current ID = 1.8 x √2 x 20 kA = 50.9 kA peak would show in case a currentlimiting fuse would not exist. With a 32 A fuse this value is limited to only ID = IS = 4 kApeak within an operation time lower than 10 milliseconds (figure 7). It is obvious that for low currents, for which the fusion time is long (including times over one cycle) the fuse does not act as a current-limiting fuse. Fuses will show their current-limiting characteristic only from a current value where IDpeak is the same as IS. Starting at this level of current, the fuse will operate as a current-limiting fuse (on the right side of the A-A' line in Figure 5). The point where the line corresponding to IS of every fuse meets with the A-A' straight line, defines over the abscissa (X axis) the short-circuit current value as of which the fuse operates as current-limiting. If the short-circuit current is lower, the fuse will not operate as a current-limiting one. For example, a 75A fuse will operate as a current-limiting fuse as of approximately 2000 A of short-circuit. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-10 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE RATED CURRENT (In): The fuse rated current is the maximum current value that the fuse can conduct for indefinite time without reaching fusion and the one to generate an energy such as the fuse can satisfactorily dissipate. INTERRUPTING CAPACITY ( I1 ) (MAXIMUM INTERRUPTING CURRENT) : The interrupting capacity (maximum interrupting current) I1 corresponds to the maximum short-circuit current that a fuse is capable of interrupting safely lying of the neighborhood of several tenths of kA. The interrupting capacity (maximum interrupting current) of DRIWISA™ fuses lies above the short-circuit currents usually available in electric networks. Nevertheless it is recommended to verify the short-circuit current of the network when selecting a fuse. The corresponding Selection Guides specify the maximum interrupting current and the interrupting capacity (MVA) for each type of fuse. When the short-circuit power instead of the short-circuit current is specified, the ratio between them is deduced from the following formula: Pshort-circuit = kVnet x kAshort-circuit x √3 MINIMUM INTERRUPTING CURRENT ( I3 ): For values above In fusion times are very long and they decrease at the same time the current increases (Figure 6). In this range, heat dissipation capacity is lower than the amount of heat generated inside. Therefore severe thermic stresses that may damage the fuse show up. While the current increases, the fusion times are reduced, until a point is reached where the fusion occurs in a relatively short time, before thermic stresses and damages to the fuse show up. This current value is called the minimum interrupting current I3 and corresponds to the lower limit of current ranges that the fuse may satisfactorily interrupt. FIGURE 6 Characteristic time-current curves for current-limiting fuses Considering the above, time-current curves define a minimum interrupting current value ( I3 ) for each fuse type, below which an operation during a long period of time is not recommended, since the current (overcurrent) does not have the magnitude high enough to produce fusion, but produces an excessive heating, modifying the fuse links characteristics and producing thermic damages to the fuse body. Therefore current-limiting fuses must not operate during long periods of time in the range of currents higher than the rated one ( In ) and lower to the minimum interrupting current ( I3 ). However, in case of high currents ( higher to I3 ), that is within the short-circuit current range, the fuse operation is quick, defined and predictible. Figure 7 shows - in a graphic way - the different fuse operation zones and the conditions and limitations of each one. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-11 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE FIGURE 7 Current-limiting fuses operation zones Even though the fusion process is based on known physical principles and laws, when currents higher than In (overcurrents) show up during a time greater than the reply time corresponding to I3 (tI3) or overcurrents of an intermittent type, there are difficulties in analysing and evaluating, because the behavior of the fuse will depend on their magnitude and duration, as well as on the periods between these overcurrents, during which the fuse is able to return to a normal regime or even to the cool condition. If an overcurrent lasts a relatively long time and then stops, it can start fusion or reach the amalgamating condition with a rise in temperature because of energy disipation during that period of time, changing in a significant way the fuse links characteristics. When later found subject to a new overcurrent regime or shortcircuit, the fuses will react in a different way as to the standard characteristic, producing first heatings or inexplicable interruptions and then a reaction completely out of specification. Consulting Figures 8 and 9 which show DRIWISA™ fuses time-current characteristic for the range of available rated currents in the manufacturing program, it can be seen that the minimum interrupting current I3 (begining at the dotted line) for fuses with rated currents up to 63 A, is about 2.5 times higher than the fuse rated current In . For rated currents larger than 63 A, the minimum interrupting current I3 is about 3 times the fuse rated current In, while for fuse rated currents of 200 A and higher it corresponds to 4 times the rated current In. RATED CURRENT SELECTION ( In ): To avoid fuse operation within the overload range, the fuse rated current In is selected with an overdimensioned factor according to the equipment to protect, which for example, in case of transformers lies between 1.6 and 2 times the circuit rated current. This way the fuse will be able to hold up with the magnetization currents (inrush) and even if the transformer works within an overload regime, the fuse will not be exposed to such, due to the transformer higher thermic capacity. Appling this factor it will be possible to coordinate protection with other devices such as overcurrent relays, phase fault relays and protection elements on the low voltage side, for example, fuses, thermomagnetic switches and other protections. Any current higher than I3, will be interrupted in a time no longer than 10 to 100 sec., according to the corresponding curve in Figures 8 and 9. For further information regarding transformer protection, refer to Technical Bulletin 201. In regard to motor protection similar criteria are followed as described in Technical Bulletin 202, while capacitor protection is explained in Bulletin 203. For overhead lines or underground cables it is reccomended to consult Bulletin 204. TIME-CURRENT CHARACTERISTIC CURVES: Graphics in Figures 8 and 9 correspond to DRIWISA™ fuses time-current performance and represent the response curves under cool condition, without previous load (preloading), at surrounding temperature of 20 ° C, with a tolerance margin of + 20%, for operating times larger than 0.01 sec. Graphics in Figure 10 correspond to the I2 t characteristic (Joule integral) applicable for operating times lower than 0.1 sec. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-12 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE The tight tolerance in the fuse links lineal resistance and a strict quality assurance during the manufacturing process guarantee the characteristic curves repeatibility. Applying the overdimensioning factors and following the selection criteria in agreement with the different applications, there is little probability of overloading of the fuse due to values lying above the rated current In to occur. However, in accordance with the knowledge of the net, if the risk probability is high, the protection against overloads with currents larger than In but smaller than I3 during longer periods of time, should be provided by other means, such as overcurrent relays connected to disconnection devices like switches or load-break disconnectors. For further details consult Technical Bulletin 302. The oscillogram in Figure 11 shows the current characteristic performance and the voltage during a short-circuit interruption when a DRIWISA™ fuse type DRS07/100-A2 with 12 kV rated voltage and 100 A rated current subjected to a short-circuit prospective current of Ik" = 63 kA rms is used. The current-limiting effect can be deduced when observing that the maximum let-through current ID reaches a value of 15 kA peak corresponding to the fuse fusion current IS , while the current that would have flown in the test circuit, replacing the fuse by a very low resistance conductor, would have reached a value of 160.5 kA peak of the maximum asymmetrical peak current ( 1.8 x √2 x 63 A = 160.5 kA peak ). Ve IP ID ID = I S Recovery voltage Short-circuit prospective current (rms value) Maximum let-trough current Breaking curent (fusion current) FIGURE 11 Interruption of a 63 kA rms short-circuit current when a fuse type DRS07/100-A2 is used In accordance with international standards, recovery voltage at a system frecuency (Ve) is 87% of the fuse maximum rated voltage (VO). Therefore, in the example shown in Figure 11 the result is: Ve = 0.87 x Vo = 0.87 x 12 kV = 10.5 kV HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-16 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE OPERATION VOLTAGE ( Vn ): The interrupting voltage or maneuver voltage generated during the arc extintion process, by inserting its high resistance and interrupting currents with a high grade of inductance, is of special interest. Transient voltage during interruption must not exceed the insulation levels, usually coordinated in the network, since it would provoke trouble mainly at the insulation of other components of the system, among others, at arresters placed on the line side. For this reason it is important to use fuses with a rated voltage in agreement to the network voltage. When using a fuse with less rated voltage in regard to the network voltage, problems to manage the voltage gradients will present, while using one with greater rated voltage and consequently greater interruption voltage would cause a higher voltage gradient and consequently would create problems with the insulation of other equipments in the system. In multiple tests accomplished on DRIWISA™ fuses, the highest arc interruption voltage value found was of VU = 1.95 x √2 x VO = 2.76 x VO. This value is considerably lower than those admitted by the standards (Table 2). Consequently, using fuses with rated voltages corresponding to network voltages, there is no danger of provoking damages to the insulation of equipments connected to the load side, such as transformers, switches, substations, motors, etc. and avoiding the arresters operation. Table 2 lists the maximum arc interruption voltages admissible for high voltage fuses in accordance with international standards. FUSE RATED SYSTEM RATED VOLTAGE VOLTAGE (MEXICO) MAXIMUM MANEUVER kV rms kV rms kV peak 2.75 3.6 5.5 7.2 8.25 12 15 15.5 17.5 24 25.8 36 38 2.4 ----4.16 6.6 --------13.8 --------23 ----34.5 ----- 9 12 18 23 26 38 47 49 55 75 81 112 119 VOLTAGE Also defined as maximum interruption voltage TABLE 2 Maximum interruption voltage levels corresponding to the fuses rated voltage DRIWISA™ fuses can be installed in three-phase networks whose service voltage does not exceed the fuse rated voltage. In one-phase networks the service voltage must not be larger as 87% of the fuse rated voltage. In other cases, fuse voltage selection must be such that the maximum interruption voltage (maneuver voltage) does not exceed the maximum voltages established for the network (see Table 2). APPLICATION WITH LOAD-BREAK DISCONNECTOR SWITCHES: Using current-limiting fuses in combination with DRIWISA™ load-break disconnector switches, three-phase group operated with automatic and auxilliary trip type LDTP, an economical and reliable connection and disconnection equipment is obtained. In this case, minimum interrupting current values I3 may be considered lower ( from 1.8 to 2 times the fuse rated current In ). This is because of the premature reply of the fuse striker pin, which in case of being used within load-break switches, provokes the tripping of the auxilliary mechanism and the simultaneous opening of the three phases. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-17 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE This way, when the first fuse acts, the disconnector switch operates opening the three poles, interrupting the current of the remaining phases that otherwise would not have been interrupted but until the respectives fuses had acted maybe after several minutes or even hours, subjecting them to thermic stresses and eventually producing damages to the protected equipment, also preventing a two-phase operation. During the interruption of the remaining phases, the disconnector switch is not subject to large stresses because it just has to interrupt the rated load current of the net voltage. In case that some of the other fuses would have started its fusion process, the disconnector switch will only have to deal with the small arcing currents, thus remaining the fault disconnected and isolated. In accordance with international standards, for the extreme condition of operating an unfused load-break switch an inductive power factor = 0.7 (cos φ = 0.7) is specified. However, under short-circuit conditions at the transformer secundary terminals for instance, the value of cos f can be considerably lower, around 0.1. Nevertheless when using a combination of fuses with a DRIWISA™ load-break switch disconnector, this last will just have to disconnect a much lower current value due to the fuse current-limiting characteristic and with a power factor within its rated range, thanks to the high arc resistance of the fuse. The utilization of fuses with striker pin in combination with load-break disconnector switches is recommended for its excellent features and behavior in case of short-circuits at transformer secundary terminals. This is the reason why many electric utilities around the world use and specify DRIWISA™ fuses with striker pin to operate within three-pole load-break disconnector switches. ADVANTAGES: DRIWISA™ high interrupting capacity fuses guarantee a safe operation even for networks with a high short-circuit power. Their current-limiting characteristic guarantees the reduction to a minimum of damages to the network and other equipments, that could originate because of dangerous short-circuit currents dynamic and thermic effects. Because of their relatively slow time-current characteristic, DRIWISA™ fuses used for transformer or motor protection do not show untimely fusion or fuse link degradation if they are selected accordingt to the corresponding recommendations. Fuses are sealed with epoxy resin to achieve great airtightness against humidity. For outdoor use fuses, a special welding between covers and caps is used in order to offer a perfect protection against humidity. Costs savings when the same fuses can be used in networks that have increased their short-circuit power. DRIWISA™ fuses are recyclable and can be repaired with the original manufacturer guarantee by DRIESCHER Y WITTJOHANN, S.A. DRIWISA™ fuses are manufactured in a wide range of operation currents and voltages to satisfy any necessity. DRIWISA™ fuses are standardized in dimensions which makes the selection and replacement easy. USE AND HANDLING PRECAUTIONS: The following precautions must be taken into consideration when handling and using fuses: - Water or humidity must not penetrate into the fuse, since the high temperatures that are reached when fusion takes place, will provoke the abrupt generation of steam which causes the possibility of an explosion. - Handling fuses with precaution, avoid breakage of the porcelain and the caps to get dented. If this happens, DO NOT USE THE FUSE, AS SERIOUS RISK OF DAMAGES, HAZARDS OR INJURIES MAY OCCUR. - Fuse copper caps are silver-plated to give them excellent conductivity and assure a good electric contact. DO NOT USE SANDPAPER OR FIBER TO CLEAN THE CAPS IF THEY ARE DIRTY OR IF THEY HAVE TURNED BLACK, since this does not affect their electric conductivity features. Use a soft cloth lightly wet with silver cleaning solution not containing any abrasive or agressive materials. - Do not place metallic or metallized labels on the fuse body, since this may provoke an external flashover, as the dielectric distance along the air between the caps is reduced. - Fuse repair or rehabilitation must be done by skilled and responsible personnel; they must know about the operation principles and electrical phenomena, and must have the technical ability, skills, equipment and technology to perform these activities. DRIWISA™ fuses can be repaired renewing their original guarantee only by DRIESCHER Y WITTJOHANN, S.A. or they can be exchanged through Authorized Distributors or Service Centers. - When buying or repairing fuses, consider the equipment, installations and personnel value they are protecting and remember that "THE CHEAPEST MAY BE THE MOST EXPENSIVE" . Entrust your installations and personal safety to DRIWISA™ fuses. - Even when just one fuse had operated after a short-circuit condition in a three-phase system, it is necessary and very advisable to replace the set of three fuses since the unblown fuses may have inside damage if the fusion process (pre-arcing) had begun, this will cause later problems such as inexplicable temperature rise or undesirable interruption. This recommendation is also contained in international standards. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-18 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE TRANSPORTATION AND STORAGE: During transport of DRIWISA™ fuses avoid strikes that can break or crack the porcelain fuse body or dent the caps. In case of indoor service fuses, do not allow them to get wet or to stay in humid enviroments to avoid the penetration of moist. When receiving new fuses, inspect them before storage, informing the Authorized Distributor or the factory of any problem. Fuse storage must be done in a closed, cool and dry place. Do not store them in places where there are vibrations, moist or pollution. Keep the fuses inside their original package on a shelf in order to be safe against falling and do not stack more than 5 boxes. MAINTENANCE: DRIWISA™ high voltage and high interrupting capacity fuses do not require any maintenance. However it is recommended that after the fuse operation in a three-phase system, to replace the set of three, even when only one fuse has blown, since the others could have been subjected to thermic stresses that may caused them damages and then cause later problems such as inexplicable temperature rise or unexpected interruptions without any suitable cause. In cases of high or prolonged overloading in the circuit protected by fuses, it is recommended these being verified as to its features in factory or with any Authorized Distributor or Service Center besides to have been subjected to overcurrent, they may have suffered irreversible thermic damages that modify and demote its original characteristics. It is advisable in all cases to be equipped with a set of at least 3 fuses as spare for emergency cases. These fuses must be of the same characteristics to those installed. Keep them following the instructions given in the section "transportation and storage". Fuse copper caps are silver-plated to give them excellent conductivity and assure a good electric contact. Do not use sandpaper or fiber to clean the caps if they are dirty or if they have turned black, since this does not affect their electric conductivity features. Use a soft cloth lightly wet with silver cleaning solution not containing any abrasive or agressive materials. Do not place metallic or metallized labels on the fuse body, since this may provoke an external flashover, as the dielectric distance along the air between the caps is reduced. Fuse repair or rehabilitation must be done by skilled and responsible personnel; they must know about the operation principles and electrical phenomenon, and must have the technical ability, skills, equipment and technology to perform these activities. DRIWISA™ fuses can be repaired renewing their original guarantee only by DRIESCHER Y WITTJOHANN, S.A. or they can be exchange through Authorized Distributors or Service Centers. INSTALLATION AND/OR REPLACEMENT: It is recommended to follow the following instructions when placing or replacing fuses: A) ACCOMPLISH THE SAFETY PREPARATIONS: 1) Use special pliers for the handling of high voltage fuses ( brand DRIWISA™ type DW-018) 2) Use insulating gloves properly guaranteed for use in high voltage. 3) Use a headpiece made of insulating material. 4) Have ready cable, hook stick and equipment to connect to ground. 5) Have ready a sand bed where fuses can be placed. 6) In front of the equipment which contains the fuses, place an insulating platform for high voltage or a wood platform with an insulating rug and stay above it all the time the operation lasts, even more if the environment is humid. 7) If working in branch circuits or remote substations, place placards in the main substation or switch where it let knows that someone is working there "DO NOT CONNECT" " MEN WORKING..." . B) THINK FIRST AND THEN ACT, remember that when working with high voltage, the FIRST MISTAKE may be THE LAST ONE. 8) 9) Disconnect the high voltage supply: 8.1) Be sure that the main load-break disconnector or main switch is open. If not, open it. 8.2) Open the non load-break isolator. 8.3) Connect the ground switch ( in case of having this kind of equipment). Open the door cabinet; stay strategically where the door does not hit you, nor get projections from inside. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-19 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE PRECAUTION: FUSES MAY REACH HIGH TEMPERATURES SO THAT WHEN THE CABINET DOOR IS OPENED, THEY CAN RECEIVE A THERMAL IMPACT, THAT MAY CRASH AND/OR MAKE EXPLODE THE PORCELAIN TUBE. THEREFORE LET THE FRESH AIR ENTER SLOWLY. 10) Connect the ground cable; use the correct size of cable and a hook stick. Connect it first to the substation or switchgear ground bus or grounding structures and then to the phases (in case of not having a ground switch integrated to the equipment). 11) Find out and determine the cause that made the fuse blow, it can be a short-circuit or an overload. Eliminate the trouble, remove the remains and make a general cleaning. 12) Verify the condition of equipment and installations. 13) Inspect the new fuses and make sure they do not show maltreatment, cracks or fissures, check that the porcelain tube is not broken, grooved or scratched, nor the caps are dented or plunged. If some things mentioned before would happen, do not use them since their use is very risky. 14) Fuse copper caps are silver-plated to give them excellent conductivity and assure a good electric contact. DO NOT USE SANDPAPER OR FIBER TO CLEAN THE CAPS IF THEY ARE DIRTY OR IF THEY HAVE TURNED BLACK, since this does not affect their electric conductivity features. Use a soft cloth lightly wet with silver cleaning solution not containing any abrasive or agressive materials. Verify that the fuse striker pin is brought back and is in its place. Do not place metallic or metallized labels on the fuse body, since this may provoke an external flashover, as the dielectric distance along the air between the caps is reduced. 15) Remove the old fuses with pliers DW-018 and replace them for DRIWISA™ fuses of the same characteristics: Type, rated voltage and rated current. Never use fuses of different brands in the same circuit or different type, rated voltage or current even if they're of the same brand, since their characteristics are not the same. In three-phase systems it is recommended to replace the set of three fuses even when only one had blown since the others may be damaged and cause problems later. PRECAUTION: FUSES MAY STAY HOT, PLACE THEM ON THE SAND BED, LETTING ENOUGH TIME PASS BEFORE TOUCHING THEM WITH BARE HANDS. 16) If the fuses are installed in load-break disconnectors, verify the operation of the auxiliary trip mechanism. 17) Place the new fuses carefully, making sure the clips assemblies make the proper contact with the fuse caps. When inserting the fuses in the clip assemblies, make pressure on the ends and not on the middle of the fuse. Do not hit the fuse. 18) Remove all the tools that have been used and verify that are complete and it has not stayed behind anything inside the cabinet. 19) Disconnect the grounding switch or the ground connections, wherever it is the case. 20) Close the cabinet door, connect the non-load isolator switch and connect the high voltage supply. 21) Replace damaged fuses for new fuses, of the same rated voltage and current. In some cases, when the fuse operation is because of overloads, verify the load calculations and if necessary ask for three new fuses at the adecuate rated current according to the new calculation. DRIWISA™ fuses can be repaired including their original guarantee only by DRIESCHER Y WITTJOHANN, S.A. or they can be exchanged through Authorized Distributors or Service Centers. Fuse repair or rehabilitation must be done by skilled and responsible personnel; they must know about the operation principles and electric phenomena, and must have the technical ability, skills, equipment and technology to perform these activities. Do not expose installations, equipments and own security. SELECTION: When selecting current-limiting fuses always consider the following factors: - Network rated voltage Interrupting capacity Installation altitude Fuse rated current, according to application Coordination with other protections Type of service (indoor or outdoor) Dimensions Availability of spare, service and technical assistance Security and reliability : always use DRIWISA™ fuses HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-20 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE Fuse selection must be done in agreement to the equipment to protect, since the selection criteria are different for each application. For further information consult additionally the following information which is included in section J: TECHNICAL BULLETIN No. 201 202 203 204 205 206 302 304 CONTENTS Recommendations for protection with current-limiting fuses: TRANSFORMERS. Recommendations for protection with current-limiting fuses: MOTORS. Recommendations for protection with current-limiting fuses: CAPACITORS. Recommendations for protection with current-limiting fuses: OVERHEAD LINES AND CABLE FEEDERS. Considerations and criteria for the parallel-connection of fuses (two-per phase arrangement). Equivalency between DRIWISA™ fuses and american fuses type "R" and "E". Shunt-trip coil for electrical remote control. Selection of non-load break isolator switches and load-break disconnector switches with fuse-holders. Selectivity and coordination of protections is reached by keeping a rate of 1 : 1.6 between fuse rated currents, being the smallest the one connected closest to the load and the biggest the one connected from the supply side, assuring this way that the smallest blow first, interrupting and isolating the fault. In case of transformer protection, to establish selectivity and coordination with protections on the low voltage side it is necessary to refer to the high voltage fuses time-current characteristic curves and to the curves of the devices and/or fuses of the low voltage side (for further information refer to Technical Bulletin 201). Sometimes, for big transformer protection, it is necessary to appeal to a two-per-phase fuse arrangement to reach the required rated current value. For these cases it is recommended to consult Technical Bulletin 205 before deciding on this arrangement. For motor protection it is required to know the starting time, the maximum starting current, and the motor startings frecuency to select the correct fuse. It is recommended to consult Technical Bulletin 202. Capacitor and capacitor-bank protection invest special importance, because of the increasing use they have to keep the power factor within the acceptable limits and the relative rank of difficulty for its adequate protection, since connection currents reach, in many cases, levels very close to those of short-circuit. For further information consult Technical Bulletin 203. For fuse selection for overhead lines and cable feeders, the selection criteria are described in Technical Bulletin 204, considering that it must be done in function of the transversal section and the admissible current in the conductor. In the fuse selection for networks and circuits with high probabilities of long duration or high overloadings which require therefore of fuses with high currents rates, it is reminded that these must be used for protection against short-circuits and not for protection against overloading. Requeriments for specific arrangements in networks have to be calculated in detail by the customer to control and/or verify the continuous load regime over the fuses, the interruption current, and the fuse interrupting capacity. All data corresponding to voltage, current, interrupting capacity given in this Manual and/or Selection Guides of Catalogs, Technical Bulletins, etc., are refered to installation heights up to 1000 m over sea level and an enviroment temperature up to 40 ° C. In any way, once selected the correct fuse for its application, consider the installation altitude correction factors included in Table 3, in the fuse rated current as in the interrupting capacity and rated voltage reduction. If it is calculated with the correction by altitude in the rated current, do not use the temperature rising correction and viceversa. In some cases, a temperature correction factor should be additionally considered, in those cases in which the fuses are installed inside of cabinets or switchboards with little ventilation and/or high temperatures, in accordance with Table 4. When there exist several sizes of fuses for a specific rate of current, it is advisable to consider the future installation growth (greater rated current) or the increase of short-circuit capacity, this means to verify if for the selected fuse size exist larger rated currents or interrupting capacities, in such a way that when selecting them it is chosen a size that allows to increase the capacity, by means of just changing fuses by others of greater current or interrupting capacity when this growth requires it. Bulletin 206 establishes equivalency criteria between american fuses curves type "R" y "E" and DRIWISA™ fuses curves. Fuses must have a rated voltage equal or greater to the system highest voltage between phases, when they are used in three-phase systems with neutral firmly grounded or with neutral connected through an impedance or resistance. When using fuses in systems with isolated neutral (not grounded), the rated voltage should be at least 1.15 times the system highest voltage between phases. When fuses are used in one-phase systems, its rated voltage should be at least 1.15 times greater than the voltage between phase and ground. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-21 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE CORRECTION FACTORS BY INSTALLATION ALTITUDE AND TEMPERATURE: Installation altitude Correction factor Correction factor Correction factor (meters over sea level) for rated current for voltage and for temperature interrupting capacity rising 0 1000 1200 1500 1800 2100 2400 2700 3000 3600 a a a a a a a a a a 1000 1200 1500 1800 2100 2400 2700 3000 3600 4200 1.00 0.995 0.990 0.985 0.980 0.970 0.965 0.960 0.950 0.935 1.00 0.98 0.95 0.92 0.89 0.86 0.83 0.80 0.75 0.70 1.000 0.992 0.980 0.968 0.956 0.944 0.932 0.920 0.896 0.872 TABLE 3 Correction factors by altitude according to international standards Operation Temperature (°C) - 20 - 10 0 + 10 + 20 + 30 + 40 + 50 a a a a a a a a Correction factor for fusion time - 10 0 + 10 + 20 + 30 + 40 + 50 + 60 1.03 1.02 1.01 1.01 1.00 0.99 0.98 0.98 TABLE 4 Correction factors by temperature DRIWISA™ fuses are manufactured in a range from 2.4 to 38 kV in series DRS, DRN, and DRK, in lenghts in agreement to voltage level and dimensions in ccordance with international standards, as described in Figures and Tables of the Selection Guide of Section I, and they are used in combination with load-break fused disconnector switches and fuse-holders. The more common use is for transformers, motors, capacitors, potential transformers, overhead lines and feeder cables protection in substations and for medium and high voltage (2.4 kV up to 38 kV) industrial, rural and urban applications. NOTES: Selection criteria, calculation factors and electric and mechanical data, are included in this manual, Technical Bulletins of reference and Selection Guides and specifications, are exclusively for high interrupting capacity current-limiting DRIWISA™ fuses to be used in high voltage systems. Concepts and recommendations described in this manual should be considered and applied in agreement to the specific conditions of every case. When using similar fuses of other brands the corresponding data must be obtained or consulted with the respective manufacturer. HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-22 DRIWISA™ HIGH VOLTAGE CURRENT-LIMITING FUSES HIGH INTERRUPTING CAPACITY INDOOR AND OUTDOOR USE COMPLEMENTARY INFORMATION FIGURE 12 Structure of DRIWISA™ information regarding current-limiting fuses and related subjects For further information contact: DRIESCHER Y WITTJOHANN, S.A. San Luis Tlatilco # 29 Parque Industrial Naucalpan 53470, Naucalpan, Edo. de México Tel: (525) 300-8219 300-0210 Fax: (525) 301-3707 e-mail: driwisa@df1.telmex.net.mx HIGH VOLTAGE EQUIPMENT MANUFACTURERS SAN LUIS TLATILCO Nº 29 PARQUE INDUSTRIAL NAUCALPAN, C.P.53470 NAUCALPAN, EDO. DE MEX. TEL. (5255) 5300 8219, (5255) 5300 0210 FAX (5255) 5301 3707 EDITION 2003 H-23 HV Expulsion cut-out fuselinks Specifications Voltage Rating: 7.2-34.5kV Speeds O/L Capacity K - fast T - slow 150% for both speeds Amp Range: 1-200A Approvals: complies with ANSI/NEMA Ratings: 1, 2, 3, 6, 8, 10, 12, 15, 20, 25, 30, 40, 50, 65, 70, 80, 100, 140, 200A Description Fusetek expulsion links are semi-enclosed buttonhead pattern fuse-links for use in standard expulsion distribution cut-outs. They are available in 'K' (fast) or 'T' (slow) speed and have industry standard, removeable button heads. Their braided leads are tin-plated copper and of sufficient length for the voltage ratings encountered in the field. Part Numbers Amps K Speed T Speed 1 CM1KA23 CM1TA23 2 CM2KA23 CM2TA23 3 CM3KA23 CM3TA23 6 CM6KA23 CM6TA23 8 CM8KA23 CM8TA23 10 CM10KA23 CM10TA23 12 CM12KA23 CM12TA23 15 CM15KA23 CM15TA23 20 CM20KA23 CM20TA23 25 CM25KA23 CM25TA23 30 CM30KA23 CM30TA23 40 CM40KA23 CM40TA23 50 CM50KA23 CM50TA23 65 CM65KA23 CM65TA23 80 CM80KA23 CM80TA23 100 CM100KA23 CM100TA23 140 CM140KA23 CM140TA23 200 CM200KA23 CM200TA23 1234567890123456789 < 23" > 26" available as special order (change 23 to 26 in p/n) pg 45 Delle Retrofit kits Fusetek adapter kits allow obsolete Delle Alsthom fuses to be upgraded to a standard DIN HV fuse. These kits are designed to replace all the hardware from the existing insulators up. ! ! ! Upgrade obsolete equipment to modern DIN HV fuses. Direct bolt-in replacement. DIN fuses have superior electrical performance to fuses being replaced. Note: Adapter kits consist of 1 pair of 45mm fuse clips, transition plates and hardware. Fuses must be purchased seperately. See table below for fuse and adapter kit part numbers. If complete bases are required, please contact Fusetek. Adapter Kits for upgrading Delle Alsthom HV fuses Delle Delle fuse part number FD3, 3M FD4 FD5 FD6 FD7 FLR3 FLR5 FLP2 FLP3 FTR3 Fusetek amp range Service kV 6.3-320A 6.3-125A 6.3-125A 6.3-100A 6.3-50A 63-125A 63-125A 160-200A 3.2/6.6 10/12 13.2/15 20/24 30/34.5 6.6 15 5.5 250A 3.2 160-200A 6.6 250A 5.5 2-10A 16-50A 6.6 16-32A 15 FTR6 FTR7 FTR7 2-10A 16-50A 2-10A 16-50A 2-10A 16-50A 2-10A 16-50A FK103 7.2kV Din series pg.21 FK104 7.2kV Din series pg.21 7.2kV Din series pg.21 17.5kV Din series pg.23 17.5 kV Din series pg.23 25.8 kV Din series pg.24 25.8Kv Din series pg.24 38kV Din series pg.25 not req’d FK100 FK101 FK106 FK107 40-50A FTR6 FK102 FK107 7.2kV Din series 12kV Din series 17.5kV Din series 25.8kV Din series 38kV Din series 7.2kV Din series 17.5kV Din series See page pg.21 pg.22 pg.23 pg.24 pg.25 pg.21 pg.23 Fuse type FK105 2-10A FTR5 Adapter kit part number 15 20 20 30 FK106 FK107 FK106 FK107 FK111 FK112 FK108 FK109 FLR7 FK110 63-100A 25/30 38kV Din series pg.25 Delle replacement consists of one adapter kits (2 pair clips, adapter paltes and hardware) plus a DIN fuse. FD series Delle fuses are standard DIN distribution fuses and do not require an adapter kit. pg 46 HV Indicators DRIWISA™ voltage indicators emit a red glow to indicate presence of voltage in switchgear up to 38kV. They operate by capacitive effect, ionizating a gas inside a sealed tube. One end is connected to the live part and the path is completed through air. Standard model (photo) has articulated arm and dust hood. Economy model includes glow tube and mounting clips only. !#Available in standard and economic models !#Compact dimensions !#No maintenance required !#Replaceable indicator tube. Part Numbers for HV Indicators System voltage Standard model Economy model 7.2kV DW-019-0 17.5kV DW-019-1 25.8kV DW-019-2 DW-019-12 38kV DW-019-3 DW-019-13 DW-019-10 HV Indicators for remote signaling Our microswitch assembly allow remote annuciation of fuse operation. It consists of an insulated Bowden cable operating a microswitch. On end of the cable in terminated in a bracket at the fuse end, the other terminating in a bracket that also houses the microswitch. The actuating force is provided by the fuse striker pin. !#Provide remote annunciation of fuse operation (per phase.) !#Easily adaptable to a variety of clip/fuse configurations. !#No maintenance required !#Standard Form C NO/NC contacts. Insulation rating Max cable length Part Number up to 36kV 590mm 31 001 10 pg 47 Epoxy resin insulators In stock solutions for supported high voltage busbar, clips or other components. Hole pattern matches our 630A 45mm, clips shown on next page. RATED Vac MAX. Vac Class Cantilever Strength No. of fins N Withstand Vac 60 Hz B.I.L kV(1min) kV TYPE MODEL kV KV A A A A DWA-07A DWA-15A DWA-20A DWA 30A 6.6 13.8 23 34.5 7.2 17.5 25.8 38 4 4 4 4 4000 4000 4000 4000 1 4 5 9 27 45 55 75 60 95 125 150 B B B B DWA-07B DWA-15B DWA-20B DWA-30B 6.6 13.8 23 34.5 7.2 17.5 25.8 38 8 8 8 8 8000 8000 8000 8000 1 4 5 9 27 45 55 75 60 95 125 150 C C C C DWA-07C DWA-15C DWA-20C DWA-30C 6.6 13.8 23 34.5 7.2 17.5 25.8 38 16 16 16 16 16000 16000 16000 16000 3 5 7 11 27 45 55 75 60 95 125 150 ______________________________________________________________________________________________________________________________________________________________ GENERAL DIMENSIONS: TYPE MODEL A B C D mm mm mm inches height base dia upper face dia lower hole φ E inches F inches upper hole φ radial hole φ G H mm mm C to C of radial hole creepage distance A A A A DWA-07A DWA-15A DWA-20A DWA 30A 100 165 210 300 60 75 82 100 60 57 57 71 1/2 5/8 5/8 5/8 3/8 3/8 3/8 3/8 1/4 1/4 1/4 1/4 36 36 36 36 115 230 290 430 B B B B DWA-07B DWA-15B DWA-20B DWA-30B 100 165 210 300 75 85 90 100 75 77 77 100 5/8 3/4 3/4 1 5/8 5/8 5/8 5/8 3/8 3/8 3/8 3/8 46 46 46 46 120 230 290 433 C C C C DWA-07C DWA-15C DWA-20C DWA-30C 100 165 210 300 127 127 127 127 127 127 127 127 3/4 3/4 3/4 1 5/8 5/8 5/8 5/8 3/8 3/8 3/8 3/8 66 66 66 66 253 403 533 719 ______________________________________________________________________________________________________________________________________________________________ pg 48 FC45R - reinforced 45mm clip Rating - 200A H95mm W - 40mm L32mm w/o tang Mntg holes - 2 - 1/4" &1/2" on clip centerline. see below for tang info. DW-820-13 1250A dual 45mm Rating - 1000A H92mm W - 171mm L82mm incl. tang Mtng. holes -to fit our insulators. See page 47. FC3R - 3" spring clip DW-820-2 heavy duty 45mm clip Rating - 630A H92mm W - 80mm L96.5mm incl. tang fMtng. holes - drilled to match our insulator bolt pattern. See page 47. PT1 - 1" spring clip Rating - 60A H1.30" W - 1.12" L0.625" Mntg. hole - 0.26" on clip centerline. PT156 - 1-9/16" spring clip Rating - 600A H4.5" W - 4.3" L1.5" Mntg. holes - 2 x 3/8" holes, 2" apart on clip centerline. Metric/UNC Adapter Rating - 200A H95mm W - 40mm L32mm w/o tang Mntg hole - 1 x 1/2" on clip centerline. see below for tang info. Extension for FC45R & PT156 stud Receptacle Use terminal tang when clip is mounted to non conducting support or alternate termination is required. For use with PT156 part no. PT156-EXT Thread Specs & Part Numbers Part No. Stud Receptacle S13-R12 S38-R12 S12-R13 S12-R38 1/2-13 unc 3/8-16 unc M12 M12 M12 M12 1/2-13 unc 3/8-16 unc For use with FC45R part no. FC45R-EXT pg 49 TCCF 2.4/4.8kV Capacitor fuses TCCF fuses are current-limiting, partial range fuse designed to provide short circuit protection for capacitors. The primary application of these fuses is for the individual unit fusing of three phase capacitors in metal enclosed equipments. They are non-indicating and nondisconnecting. ! ! ! Direct stud-mounting on 1/2-13 capacitor studs eliminates seperate holder. replaces Westinghouse and CGE fuses Adapters are available to convert to other stud threads(pg49) p/n example TCCF- 50A Ratings: Vac: Application Please refer to the fuse selection chart on page 44 of this publication. 25, 50, 75, 100, 125, 200A 25 - 75A 4.8kV 100 - 200A 2.4kV I.R: 50kA rms symm m.b.c 200% of rating Approvals: self certified to ANSI 47.40 TFCF Melting time current characteristics For higher amp and voltage ratings please refer to our Dreischer section on pages 26-31. 1000 Dimensions (mm) 100 Stud 1/2-13unc Time in seconds------> 20 25 50 75 100 200 125 10 50 185 225 1 0.1 20 Boss 1/2-13unc internal pg 42 0.01 1 25 hex 10 100 RMS Amperes-------> 1000 10000 TFCF 600V Capacitor fuses TFCF fuses are current limiting fuses designed for unit fusing of 600v (or less) capacitors. They are threaded for M12 metric capacitor bushings, but may be adapted to 3/8 or 1/2" UNC threads with the adapters shown on page 48. ! Metric threaded for direct screw on mounting to metric capacitor studs. ! Excellent short circuit performance. ! Fully plated metal parts for cooler running. TFCF fuses should be selected at 250-300% of the nominal capacitor full load current or next nearest size up. If capacitor is installed in close proximity to other capacitor banks, or is switched frequently, select higher amp fuses within this range. 600Vac 200kA IR p/n example TFCF- 50A Melting Time Current Characteristics General Specifications - in. (mm) Part number 1000 Amp ratings L D 6, 10, 15, 20, 25, 30A 35, 40, 50, 60A TFCF 100 70, 80, 90, 100A Time in seconds------> 110,125, 150, 175, 200A Stud M12 external 10 1.18 (30) 4.13" 1.10" (105) (28) 4.84" 1.62" (123) (41) top .78 (20) 1 D 6 10 L 15 20 30 40 60 80 100 125 175 25 35 50 70 90 110 150 200 0.1 bottom .78 (20) 0.01 1 10 100 RMS Amperes-------> 1000 10000 .85 (22) Boss M12 internal pg 43 Fuse Selection chart for Capacitors Applicable for all current limiting fuses - high and low voltage. Use dotted line for single phase and star connections, solid line for delta connections. Above 100A, curves are identical. For auto-switching, or switching in close proximity to other capacitor banks, multiply capacitor FLA x 1.6 before using scale at bottom. Read up from capacitor FLA scale at bottom to intersection of appropriate curve (star or delta). Fuse rating is whatever band intersection occurs in. Read fuse rating on left scale. pg 44 Stud Mount Capacitor fuses All the Driescher fuses listed on the preceding 2 pages can be ordered with tapped 1/2-13unc inserts for mounting directly to capacitor bushings. (see page 26 for dimensions). Additional sizes are listed below. To order this feature, change the DRS to DRK. eg: DRK07/100-A2 Note: DRK series fuses have the striker pin omitted. Electrical data and nominal dimensions are the same as for DRS. Part Numbers Amps Interrupting Rating I.R mVA m.b.c (A) Major Dimensions (mm) TL L D 258 192 66 2.4 - 7.2kV DRK07/4-A1 DRK07/6-A1 DRK07/10-A1 DRK07/16-A1 DRK07/25-A1 DRK07/32-A1 DRK07/40-A1 DRK07/50-A1 DRK07/63-A1 DRK07/75-A1 DRK07/100-A1 4A 6A 10A 16A 25A 32A 40A 50A 63A 75A 100A 40kA 500 10A 15A 25A 40A 63A 80A 100A 125A 158A 225A 300A Driescher Current Cut-off characteristics all voltage classes 100 peak current (A) x 1000 500 400 315 250 200 160 125 100 75 10 63 50 40 32 25 16 10 6.3 1 1 pg 30 10 Prospective Short Circuit - rms amps x 1000 100 Driescher DIN 43 625 melting time current characteristics 1000 Time in seconds------> 100 10 1 0.1 6 10 16 25 32 40 50 63 75 100 0.01 1 10 100 1000 160 250 400 630 125 200 315 500 10000 100000 RMS Amperes-------> pg 31 Driescher DIN HV Distribution Driescher fuses are preferred in some utility applications due to their faster characteristic which improves upstream co-ordination with utility devices. ! Very high amp ratings available ! Available in stud mount versions for mount ing on capacitor bushings. ! Interchangeable with other standard DIN dimension HV fuses. Please see application notes for DIN fuses on page 19. Dresicher fuses have standard DIN 43 625 dimensions. Please refer to the specification tables on the following pages for dimensions and technical data. Dimensions (mm) 1/2-13unc inserts for DRK series (both ends indentical) TL pg 26 Transformer application The fuse ratings recommended in the following tables have been chosen with the following conditions in mind: ! ! ! Fuses must pass normal primary winding magnetising inrush currents: These are taken as 12x the normal full load current(FLC) at .1 sec, and 25x FLC at .01 sec. Certain applications may require a higher amp rating than recommended. Please contact Fusetek with application details. After a sustained power outage, the fuse must be able to withstand an overload of approximately 6 x FLC for 1 sec. and 3 x FLC for 10 sec. The maximum voltage rating of the fuse must be equal to, or greater than the maximum line-to-line system voltage including utility tolerances. Minimum fuse rating for Transformer Application Tx K va System kV 2.4 4.16 4.8 7.2 13.8 14.4 15.5 23 25.8 27.6 34 2 1 1 1 1 Fuse amp rating 15 6 6 30 4 3 2 2 16 10 6 4 3 3 2 2 2 2 1 45 25 16 16 10 4 4 4 3 2 2 2 75 32 25 25 16 6 6 6 4 4 3 3 112.5 50 32 32 25 10 10 10 6 6 6 4 150 63 40 40 32 16 16 16 10 6 6 6 225 100 63 50 40 25 25 25 16 10 10 10 300 100 75 63 50 32 25 25 16 16 16 10 400 125 100 75 63 32 32 32 25 25 25 16 500 200 100 100 75 40 40 40 32 25 25 25 750 250 160 125 100 63 63 50 32 32 32 32 1000 315 200 160 125 75 75 63 50 50 32 32 1250 400 250 200 160 75 75 75 63 50 40 40 1500 500 315 250 200 100 100 100 75 63 63 50 2000 630 400 315 250 160 160 100 75 75 75 63 2500 - 500 400 315 160 160 125 100 100 100 75 3000 - 630 500 315 200 200 160 125 100 100 100 3750 - - 630 400 250 250 200 125 125 100 100 4000 - - 800 500 250 250 200 160 125 125 100 5000 - - - 630 315 315 250 200 160 160 125 6000 - - - 630 355 315 315 250 200 200 160 7000 - - - 800 400 400 400 250 250 250 200 8000 - - - - - - - 315 250 250 200 10000 - - - - - - - - 315 315 250 Capacitor Application All Dreischer fuses can be supplied with 1/2-13unc threaded inserts (single barrel only) for direct mounting to capacitor bushings. Characteristics remain unchanged from standard Dreischer fuses. Change DRS in part number to DRK if this option is required. See selection table on page 44 for correct fuse sizing. pg 27 Driescher DIN distribution fuses Part Numbers Amps Interrupting Rating I.R mVA m.b.c (A) Major Dimensions (mm) TL L 258 192 D 2.3 - 4.8kV DRS04/125-B1 125A DRS04/160-B1 160A DRS04/200-B2 200A DRS04/250-B2 250A DRS04/315-B2 315A DRS04/400-B7 400A DRS04/500-B7 500A DRS04/630-B7 600A 40kA 63kA 500 375A 530 480A 500 40kA 330 63kA 500 40kA 330 800A 85 1000A 1260A 800A 358 292 1000A Double 85 1260A 2.4 - 7.2kV DRS07/2-A2 2A 5A DRS07/4-A2 4A 10A DRS07/6-A2 6A 15A DRS07/10-A2 10A 25A DRS07/16-A2 16A DRS07/25-A2 25A 1000 40A DRS07/32-A2 32A DRS07/40-A2 40A 100A DRS07/50-A2 50A 125A DRS07/63-A2 63A DRS07/75-A2 75A DRS07/100-A2 100A 63A 63kA 80A 358 292 66 508 442 85 358 292 double 66 508 442 double 85 358 292 85 358 292 double 85 508 442 66 158A 800 225A 300A 4.8 - 7.2kV DRS07/125-B4 125A DRS07/160-B4 160A DRS07/200-B4 200A DRS07/250-B4 250A DRS07/315-B4 315A DRS07/400-B4 400A DRS07/500-B4 500A 63kA 1300 500 40kA 500 20kA 300 63kA 800 375A 480A 800A 1000A 1260A 1600A 1750A 2.4/7.2kV DRS07/125-A7 125A DRS07/150-A7 150A DRS07/200-A7 200A DRS07/315-B8 315A DRS07/400-B8 400A DRS07/500-B8 500A DRS07/630-B8 630A 158A 225A 300A 63kA 40kA 1300 500 500 480A 800A 1000A 1260A 7.2-12kV DRS12/125-B4 125A DRS12/160-B4 160A DRS12/200-B4 200A DRS12/250-B7 250A DRS12/315-B7 315A DRS12/400-B7 400A 63kA 375A 480A 40kA 63kA 500 800A 375A 480A 40kA 800A 10 - 17.5kV DRS15/2-A4 2A 5 DRS15/4-A4 4A 10 DRS15/6-A4 6A DRS15/10-A4 10A 25 DRS15/16-A4 16A 40 pg 28 80Ka 2000 15 Part Numbers Amps Interrupting Rating I.R mVA m.b.c (A) Major Dimensions (mm) TL L D 10 - 17.5kV continued DRS15/25-A4 DRS15/32-A4 DRS15/40-A4 DRS15/50-A4 DRS15/63-A4 DRS15/75-B4 DRS15100-A4 DRS15/125-B4 DRS15/160-B4 DRS15/200-B4 DRS15/200-B5 DRS15/250-B8 DRS15/315-B8 DRS15/400-B8 DRS15/400-B9 20/25.8kV 25A 32A 40A 50A 63A 75A 100A 125A 160A 200A 200A 250A 315A 400A 400A DRS20/6-A4 DRS20/10-A4 DRS20/16-A4 DRS20/25-A4 DRS20/32-A4 DRS20/40-A4 DRS20/50-A4 DRS20/63-A4 DRS20/75-B4 DRS20/100-B4 DRS20/125-B4 DRS20/160-B4 DSR20/200-B8 DRS20/250-B8 DRS20/315-B8 DRS20/250-B9 DRS20/315-B9 6A 10A 16A 25A 32A 40A 50A 63A 75A 100A 125A 160A 200A 250A 315A 250A 315A 80 32 20 40 20 25 40 20 25 40 2000 1600 100 2000 1600 1600 1000 500 750 1600 1000 500 750 1600 25 1000 20 800 25 1000 20 800 40 25 1600 1000 63 80 100 125 158 225 300 375 480 800 800 375 480 800 800 15 25 40 63 80 100 125 158 225 300 375 480 300 375 480 375 480 66 508 442 85 603 508 537 442 508 442 603 537 508 442 double 85 66 85 508 442 double 85 603 537 30/38kV DRS30/2-A5 DRS30/4-A5 DRS30/6-A5 DRS30/10-A5 DRS30/15-A5 DRS30/25-A5 DRS30/32-A5 DRS30/40-A5 DRS30/50-A5 DRS30/63-A5 DRS30/75-B5 DRS30/100-B5 DRS30/125-A9 DRS30/150-B9 DRS30/200-B9 DRX30/250-B9 DRX30/315-B9 2A 4A 6A 10A 16A 25A 32A 40A 50A 63A 75A 100A 125A 150A 200A 250A 315A 32 2000 16 20 20 16 1600 1000 2000 2000 1000 20 2000 30 30 1000 1000 5 10 15 25 40 63 80 100 125 158 225 300 158 225 300 375 480 603 603 603 603 603 603 603 603 603 603 603 603 603 537 537 66 85 double 66 537 double 85 pg 29 Stud Mount Capacitor fuses All the Driescher fuses listed on the preceding 2 pages can be ordered with tapped 1/2-13unc inserts for mounting directly to capacitor bushings. (see page 26 for dimensions). Additional sizes are listed below. To order this feature, change the DRS to DRK. eg: DRK07/100-A2 Note: DRK series fuses have the striker pin omitted. Electrical data and nominal dimensions are the same as for DRS. Part Numbers Amps Interrupting Rating I.R mVA m.b.c (A) Major Dimensions (mm) TL L D 258 192 66 2.4 - 7.2kV DRK07/4-A1 DRK07/6-A1 DRK07/10-A1 DRK07/16-A1 DRK07/25-A1 DRK07/32-A1 DRK07/40-A1 DRK07/50-A1 DRK07/63-A1 DRK07/75-A1 DRK07/100-A1 4A 6A 10A 16A 25A 32A 40A 50A 63A 75A 100A 40kA 500 10A 15A 25A 40A 63A 80A 100A 125A 158A 225A 300A Driescher Current Cut-off characteristics all voltage classes 100 peak current (A) x 1000 500 400 315 250 200 160 125 100 75 10 63 50 40 32 25 16 10 6.3 1 1 pg 30 10 Prospective Short Circuit - rms amps x 1000 100 Driescher DIN 43 625 melting time current characteristics 1000 Time in seconds------> 100 10 1 0.1 6 10 16 25 32 40 50 63 75 100 0.01 1 10 100 1000 160 250 400 630 125 200 315 500 10000 100000 RMS Amperes-------> pg 31 Driescher HV loadbreak switches DRIWISA™ load-break switches are used to connect or disconnect high voltage distribution circuits under load conditions. The fused version of the switch provides automatic 3 phase disconnect if any of the fuses operates. Operation of the fused and non-fused versions can also be initiated through a shunt trip or manual operation. !#High speed operating mechanism !#Compact dimensions !#ANSI ratings !#Available in fusible and non-fusible versions Note: for complete data please request Dreischer bulletin. Part numbers for 630A, RH operating mech, automatic trip Vac Non fusible 7.2kV Fusible version - for fuse length BL=192mm BL=292mm BL=442mm BL=537mm LDTP07/060CKN LDTP07/061CKN LDTP07/062CKN LDTP07/064CKN LDTP07/065CKN 17.5kV LDTP15/060CKN - - LDTP15/064CKN LDTP15/065CKN 25.8kV LDTP20/060CKN - - LDTP20/064CKN LDTP20/065CKN 38kV LDTP30/060CKN - LDTP30/065CKN Specifications MAXIMUM RATED VOLTAGE CURRENT KV Ur 15 20 30 SHORT-TIME PEAK CURRENT BASIC IMPULSE LEVEL W ITHSTAND VOLTAGE (BIL) 1.2 x 50 s 60 Hz 1 min DRY Up Ud CURRENT SERIE 07 ASYMMETRICAL 7.2 17.5 25.8 38 A KA(rms) KA(rms) KV KV TO GROUND ACROSS TO GROUND ACROSS Ir Ip Ik AND BETWEEN OPEN AND BETWEEN OPEN $ # # POLES GAP POLES GAP 630 65 25 60 70 20 23 1250 99 38.1 60 70 20 23 630 65 25 95 110 38 45 1250 99 38.1 95 110 38 45 630 65 25 125 140 60 66 1250 99 38.1 125 140 60 66 630 65 25 150 165 80 88 1250 99 38.1 150 165 80 88 pg 33 HV Motor Fuses Specifications Voltage Rating: 2500 - 7200Vac Interrupting Rating: Amp Range: 50kA rms. symm. 2R-36R (50-650A) Designed to: Ansi (2.5 & 5.5) IEC 269-2 (7.2kV) Ratings available: 2.5kV 5.5kV 7.2kV 2, 4, 5, 6, 9, 12R 2, 4, 5, 6, 9, 12, 18, 24, 30, 36R 50-355A (2R-18R) Description MR series fuses are current-limiting backup fuses designed to protect medium voltage motors and their associated control. They have standardised dimensions and are fully interchangeable with other fuses of the same type and rating. Blown fuse indication is standard on all types. The design of the striker travel and force 'R' Rating Defined meets standard requirements for mechanical actuation. Features ! ! ! ! Integral indicating pin for visual or mechanical operation 2.5kV and 5.5kV fuses can be hermetically sealed and supplied without indicator for use in hazardous location application. fully plated metal parts for low contact resistance standard 'R' ratings ensure interchangeability. Installation notes The 'R' rating for a fuse is established by dividing the 20-35 second melt current of the fuse by 100. In this way, fuses having the same 'R' rating will melt at the same current level at 20s - thus ensuring identical motor starting capability and coordination with the overload relays. When replacing motor starting fuses, always match the 'R' rating - not the amp rating - to maintain identical co-ordination and motor starting capability. Fusetek MR fuses can replace any manufacturers' motor fuse having the same dimensions. Ensure that fuse clips still have good tension and clean all contact surfaces before re-installing fuses. The striker pin should be pointing up when installing fuses. Fuses should be replaced in sets of three to avoid nuisance blowing caused by element damage. Motor Circuits There are motor/fuse selection charts in each section. To use these fuse charts it is necessary to know the starting current and run-up time of the motor. For starting conditions not shown, please contact Fusetek. ! ! ! Select appropriate run-up time (6 or 15 seconds) Read down to appropriate starting current range. Read across to find 'R' rating. Companion Products Insulators, fuse clips, adapter kits - see rear of HV section. Loadbreak switches pg 14 2.5kV Motor fuses - 7" centre Clip- in style Melting Time Current Characteristics General Specifications Part Number Time in seconds 1 I.R total I2t kA x 1000 FLA 70-2R-1C-2.75 2R 70 75 100-3R-1C-2.75 3R 100 150 130-4R-1C-2.75 4R 130 230 150-5R-1C-2.75 5R 150 170-6R-1C-2.75 6R 170 200-9R-1C-2.75 9R 200 230-12R-1C-2.75 12R 230 390-18R-2C-2.75 18R 390 450-24R-2C-2.75 24R 450 100 10 DxL (inches) ’R’ 3 300 50 10.8 kA rms 380 550 720 2x3 1700 2200 0.1 2R 3R 4R 6R 9R 12R 24R 5R 18R 0.01 100 1000 10000 RMS Amperes 100000 Fuse selection for Motors rated 2.5kV or less Current Cut-off at rated voltage Motor Starting Current (A) for 6 sec. run-up 100 for 15 sec. run-up from to from to 2R 140 165 120 150 3R 165 250 150 215 4R 250 340 215 350 5R 340 430 300 420 6R 430 550 420 480 9R 550 800 480 680 12R 800 1400 680 1200 18R 1400 1650 1200 1400 24R 1650 2300 1400 1800 Peak amps x 1000 Fuse Rating 24R 18R 12R 9R 6R 5R 4R 3R 2R 10 1 0.1 0.1 1 10 100 Prospective Short Circuit - rms Amps x 1000 pg 15 5.5kV Motor fuses - 12" centre Clip-in style Melting Time Current Characteristics General Specifications 100 Time in seconds 10 1 DxL (inches) I.R kA total I2t x1000 Part Number A F.L.A 70-2R-1C5.5 2R 70 75 100-3R-1C-5.5 3R 100 150 130-4R-1C-5.5 4R 130 230 150-5R-1C-5.5 5R 150 170-6R-1C-5.5 6R 170 200-9R-1C-5.5 9R 200 230-12R-1C-5.5 12R 230 390-18R-2C-5.5 18R 390 450-24R-2C-5.5 24R 450 550-30R-2C-5.5 30R 550 650-36R-2C-5.5 36R 650 300 3 380 15.8 550 50kA rms 720 1700 2x3 2200 3300 5200 0.1 2R 3R 4R 6R 9R 12R 24R 36R 5R 18R 30R 38R 0.01 100 1000 10000 RMS Amperes 100000 Fuse selection for Motors rated 5.5kV or less Current Cut-off at rated voltage Motor Starting Current (A) for 6 sec. run-up for 15 sec. run-up from to from to 2R 140 165 120 150 3R 165 260 150 225 4R 260 360 225 315 5R 360 435 315 375 6R 435 540 375 450 9R 540 780 450 675 12R 780 1080 675 950 18R 1080 1650 950 1350 24R 1650 2100 1350 1800 30R 2100 2750 1800 2250 36R 2750 3300 2250 2850 pg 16 100 Peak amps x 1000 Fuse Rating 38R 36R 30R 24R 18R 12R 9R 6R 5R 4R 3R 2R 10 1 0.1 0.1 1 10 Prospective Short Circuit - rms Amps x 1000 100 7.2kV Motor fuses - British bolt-in style Melting Time Current Characteristics General Specifications Part Number 1000 100 Time in seconds------> 3027136 10 1 F.L.A Equiv R rating 50 2R 63 3R 80 - 100 4R 125 5R 140 6R 160 - 200 9R 250 12R 315 18R DxL (inches) I.R kA 3 50 15.8 0.1 50 63 0.01 100 80 125 160 100 140 200 1000 250 315 10000 100000 RMS Amperes-------> Fuse selection for Motors rated 7.2kV or less Current Cut-off at rated voltage Motor Starting Current (A) for 6 sec. run-up for 15 sec. run-up from to from to 2R 0 195 0 172 3R 196 278 173 240 4R 279 435 241 375 5R 436 503 376 412 6R 504 585 413 510 9R 586 825 511 675 12R 826 1300 676 675 18R 1301 1800 676 1500 100 Peak Current - assym. amps x 1000 Fuse Rating 315 250 200 160 140 125 100 80 63 50 10 1 0.1 0.1 1 10 Prospective Short Circuit - rms Amps x 1000 100 pg 17 Other types and tag arrangements Our 3" diameter R and E rated ferrule (clip-in) are available with modified caps/tags as shown below.The modification of the end fittings does not affect the electrical performance of the fuse. Please refer to the appropriate basic ferrule fuse data. 2" Hookeye Feature - add 'W' to part number Bolt-in Tags - add 'Bi' to part number 2" Extension - add 'X' to part number Types Option Availability Plain Ferrule GE Bolt in tags add 1B or 1iB to part number Bi bolt-in " " " " " " " " " " " " W " " " " " " Hookeye 1B bolt-in 1iB bolt-in " " " " " CL " " " ClipLoc ITE Clip-Loc feature - add 'CL' to part number pg 18 X body extension 25.8kV - E 38kV - E 1iB 2.75kV - R 5.5kV - R 8.3kV - R 2.75kV - E 5.5kV - E 8.3kV - E 15.5kV - E 1B " " " " Potential Transformer fuses FC series fuses are current limiting, non-indicating, partial range HRC fuses available in a variety of voltage, amperage and interrupting ratings. (see chart). FC series are North American dimensioned PT fuses and provide equals to Westinghouse and CGE. BPT series are British dimensioned PT fuses and offer equals to GEC, Brush, CCL, and EMP. ! ! ! Pure silver elements Fully plated metal parts for cool running. Excellent current limitation for substantial reduction of short circuit stresses. Retrofitting Fusetek PT fuses can replace any other manufacturers' PT fuse with same dimensions and voltage/amp rating. When replacing fuses, ensure that fuse clips still have good spring tension. Adjust or replace if necessary. Make sure contact surfaces are clean and free of corrosion. Companion Products Insulators, fuse clips and bases. Please see the end of this section for these items. PT Fuses - General Specifications Vac Part Number North American dimensions FC460 625 FC461 2.75kV FC462 2.75kV FC463 4.8NPT 4.8kV FC464 5.5kV FC465 FC466 8.3kV FC467 15.5kV FCA22 25.8kV British dimensions 5.5BPT 5.5kV 8.5BPT 8.5kV Other types 7003409 1.2kV 7003709 3.0kV 7004010 6.0kV 7004310 10.0kV FC493-1/2E 15.5kV pg 40 Ratings D x L (inches) I.R rms symm. 1/2, 1, 2, 3, 5A 1/4, 1/2, 1, 1, 2, 3A 13/16 1/2, 1, 1.5 2, 3, 5A 1-9/16 1/2, 1, 2, 3, 5A 13/16 1/2, 1, 1.5 2, 3, 5A 1-9/16 1/2, 1, 1.5 2, 3, 5A 1/2, 1, 1.5 2, 3, 5A 1/2, 1, 2, 3, 5A 1-9/16 1-9/16 1-9/16 4.6 4.6 7.4 9.5 5.6 7.4 9.5 9.5 12.8 17.5 1/2, 1, 3, 5A 1/2, 1, 3A 1.0 1.0 5.6 7.6 40kA 40kA 125mA-6.3A 125mA-4A 125mA-4A 125mA-2A Ozonator 1/2A only 8mm 8mm 8mm 8mm 15mm 50mm 85mm 120mm 150mm 153mm 35A 35A 35A 35A 30kA 37.5kA 37.5kA 50kA 50kA 50kA 35kA 32kA Application PT fuses are used to isolate the voltage (or PT) transformer from the supply in the event of a primary winding failure. Properly selected fuses will also operate quickly if there is a short circuit on the secondary side of the transformer. To provide optimum protection without nuisance blowing, it is necessary to consider the following points: ! The interrupting rating must be equal to or greater than the largest anticipated short circuit. The fuse must pass the magnetising inrush to the primary windings without damage or operation. This inrush is normally considered to be 12 times the primary FLC for 0.1 second. The fuse's voltage rating must be equal to, or greater than the system voltage. 3 phase FLC = kVA x 1000 vAC x 1.73 Single phase FLC = kVA x 1000 vAC all PT fuses Transformer Application Table Transformer Primary FLC (A) from to Fuse rating (A) 0 0.15 1/2 0.16 0.30 1 0.31 0.43 1.5 0.44 0.60 2 .061 1.0 3 1.1 1.54 5 1000 Melting Time current Characteristics 100 10 Time in seconds ! ! 1 1/2 1 1.5 2 3 5 0.1 0.01 0.1 1 10 100 RMS Amperes pg 41 Potential Transformer fuses FC series fuses are current limiting, non-indicating, partial range HRC fuses available in a variety of voltage, amperage and interrupting ratings. (see chart). FC series are North American dimensioned PT fuses and provide equals to Westinghouse and CGE. BPT series are British dimensioned PT fuses and offer equals to GEC, Brush, CCL, and EMP. ! ! ! Pure silver elements Fully plated metal parts for cool running. Excellent current limitation for substantial reduction of short circuit stresses. Retrofitting Fusetek PT fuses can replace any other manufacturers' PT fuse with same dimensions and voltage/amp rating. When replacing fuses, ensure that fuse clips still have good spring tension. Adjust or replace if necessary. Make sure contact surfaces are clean and free of corrosion. Companion Products Insulators, fuse clips and bases. Please see the end of this section for these items. PT Fuses - General Specifications Vac Part Number North American dimensions FC460 625 FC461 2.75kV FC462 2.75kV FC463 4.8NPT 4.8kV FC464 5.5kV FC465 FC466 8.3kV FC467 15.5kV FCA22 25.8kV British dimensions 5.5BPT 5.5kV 8.5BPT 8.5kV Other types 7003409 1.2kV 7003709 3.0kV 7004010 6.0kV 7004310 10.0kV FC493-1/2E 15.5kV pg 40 Ratings D x L (inches) I.R rms symm. 1/2, 1, 2, 3, 5A 1/4, 1/2, 1, 1, 2, 3A 13/16 1/2, 1, 1.5 2, 3, 5A 1-9/16 1/2, 1, 2, 3, 5A 13/16 1/2, 1, 1.5 2, 3, 5A 1-9/16 1/2, 1, 1.5 2, 3, 5A 1/2, 1, 1.5 2, 3, 5A 1/2, 1, 2, 3, 5A 1-9/16 1-9/16 1-9/16 4.6 4.6 7.4 9.5 5.6 7.4 9.5 9.5 12.8 17.5 1/2, 1, 3, 5A 1/2, 1, 3A 1.0 1.0 5.6 7.6 40kA 40kA 125mA-6.3A 125mA-4A 125mA-4A 125mA-2A Ozonator 1/2A only 8mm 8mm 8mm 8mm 15mm 50mm 85mm 120mm 150mm 153mm 35A 35A 35A 35A 30kA 37.5kA 37.5kA 50kA 50kA 50kA 35kA 32kA Application PT fuses are used to isolate the voltage (or PT) transformer from the supply in the event of a primary winding failure. Properly selected fuses will also operate quickly if there is a short circuit on the secondary side of the transformer. To provide optimum protection without nuisance blowing, it is necessary to consider the following points: ! The interrupting rating must be equal to or greater than the largest anticipated short circuit. The fuse must pass the magnetising inrush to the primary windings without damage or operation. This inrush is normally considered to be 12 times the primary FLC for 0.1 second. The fuse's voltage rating must be equal to, or greater than the system voltage. 3 phase FLC = kVA x 1000 vAC x 1.73 Single phase FLC = kVA x 1000 vAC all PT fuses Transformer Application Table Transformer Primary FLC (A) from to Fuse rating (A) 0 0.15 1/2 0.16 0.30 1 0.31 0.43 1.5 0.44 0.60 2 .061 1.0 3 1.1 1.54 5 1000 Melting Time current Characteristics 100 10 Time in seconds ! ! 1 1/2 1 1.5 2 3 5 0.1 0.01 0.1 1 10 100 RMS Amperes pg 41 HV DIN fuse bases DRIWISA™ fuse bases are available in single or 3 pole versions in 630 or 1250A (dual clip) versions. Supported voltages are 7.2, 17.5, 25.8 and 38kV. Base is heavy duty galvanised steel with epoxy resin standoff insulators. 630A silver plated clips are standard. 3 pole versions can be fitted with auxilliary microswitches for remote blown-fuse annunciation. Note: these bases can be modified to accept North American E rated fuses. Please contact Fusetek for details. Part numbers for 630A single & 3 pole DIN fuse bases Fuse body length (BL) Vac No. Poles BL=192mm BL=292mm BL=442mm BL=537mm 1 SP07/061AMN SP07/062AMN SP07/064AMN SP07/065AMN 3 DSP07/061AMN DSP07/062AMN DSP07/064AMN DSP07/065AMN 1 - SP15/062AMN SP15/064AMN SP15/065AMN 3 - DSP15/062AMN DSP15/064AMN DSP15/065AMN 1 - - SP20/064AMN SP20/065AMN 3 - - DSP20/064AMN DSP20/065AMN 1 - - - SP30/065AMN 3 - - - DSP30/065AMN 7.2kV 17.5kV 25.8kV 38kV Specifications MAXIMUM RATED BASIC IMPULSE LEVEL WITHSTAND VOLTAGE VOLTAGE CURRENT (BIL) 1.2 x 50 s 60 hZ 1 min DRY A Up kV Ud kV SERIE kV Ur pg 32 Ir TO GROUND ACROSS TO GROUND ACROSS AND BETWEEN OPEN AND BETWEEN OPEN POLES GAP POLES GAP 07 7.2 630 60 70 20 23 15 17.5 630 95 110 38 45 20 25.8 630 125 140 60 66 30 38 630 150 165 80 88 Next Medium Voltage Fuses 2400 - 25,500 VAC ■ Current Limiting Current limiting “E” and “R” rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of the fuse. This provides visual identification of a blown fuse and can be used as a trigger for external devices. GENERAL INFORMATION The terms “Medium Voltage” and “high voltage” have been used interchangeably by many people to describe fuses operating above 600 volts. Technically speaking, “medium voltage” fuses are those intended for the voltage range from 2,400 to 38,000 VAC. “High voltage fuses are for circuits carrying voltages greater than 38,000 VAC. “E” Rated fuses are considered to be general purpose fuses and can be used to protect against low and high values of fault current. “R” rated fuses are designed for back-up protection. They must be used in series with other devices, such as motor overload relays, in order to achieve both overload and short circuit protection. Littelfuse now offers a complete selection of “E” and “R” rated medium voltage fuses for the protection of transformers, potential transformers, feeders, and motor circuits. Single, double, and triple barrel designs are available to cover a wide range of current, voltage, and interrupting ratings. Conventional ferrule type, clip lock, and bolt-in mounting configurations are now available for virtually any application. Hermetically sealed fuses for use in hazardous environments are also offered. Contact the factory or your local Littelfuse representative for additional fuse ratings or custom mounting configurations. Medium voltage fuses are not intended to provide overload protection in the same sense as fuses rated 600 volts or less. Medium voltage fuse current ratings do not have the same meanings as the ampere ratings of low voltage fuses. All medium voltage fuses are limited in their ability to interrupt low value overcurrents, especially those between 100% and 200% of the fuse’s continuous current rating. They are designed to carry their rated current without exceeding the temperature rise permitted by NEMA and ANSI standards. Additional application data can be found in the Fuse Application section of the POWR-GARD Products catalog (PF101). 24 Hour Emergency Service is available. Call 1-800-227-0029. APPLICATIONS ■ ■ ■ ■ ■ Power Transformer Protection Potential Transformer Protection Motor Controller Back-up Protection Fused Switches Feeder Circuits Bolt-in Mount Fuses 61 Previous Next R Rated Medium Voltage Fuses Current Limiting FEATURES CHARACTERISTICS “R” rated fuses provide required short-circuit protection for medium voltage motors, motor controllers and associated circuitry. These components have limited ability to absorb the energy of large short circuit currents. Medium voltage motor controllers contain overload relays which provide both overload protection and locked rotor protection to the motor. The controllers are also intended to interrupt low value short circuits within the capability of the motor controller. This protects the medium voltage fuse from sustained overcurrents which are less than their minimum interrupting rating. Voltage Rating: 2,400 volts – 15,500 volts Current Range: 2R – 36R OPTIONS ■ ■ ■ Hermitically sealed for use in hazardous locations (add “S” suffix to part number) Hookeye attachment (add “W” suffix to part number) Bolt-in mounting configurations NEMA Standards for “R” rated medium voltage power fuses require that they operate within 15-35 seconds when subjected to an rms current 100 times the “R” rating. For example, a fuse with a 2R rating will open within 15 to 35 seconds on an applied current of 2 x 100 = 200 amperes. Part Number System 130 - 4R -1C - 5.5 Max Voltage (KV) Style (C-Cartridge) No. of Barrels Rating (size) Continuous Current 3"DIA Dim.A Clip Center D 2.75 KV RATED Catalog Number 70-2R-1C-2.75 100-3R-1C-2.75 130-4R-1C-2.75 150-5R-1C-2.75 170-6R-1C-2.75 200-9R-1C-2.75 230-12R-1C-2.75 390-18R-2C-2.75 450-24R-2C-2.75 6.38" 9.75" DD FIGURE 3 Old Catalog Number LCK 2R LCK 3R LCK 4R LCK 5R LCK 6R LCK 9R LCK 12R LCK 18R LCK 24R DDD FIGURE 2 Size 2R 3R 4R 5R 6R 9R 12R 18R 24R Maximum Continuous Current @ 40 deg C. 70 100 130 150 170 200 230 390 450 Add “w” suffix to part number for hookeye attachment. 62 *For hookeye attachment; add “W” suffix to part number Dim.B FIGURE 1 R Hookeye Feature* Dim. A (inches) Dim. B (inches) 7" 10.875" 7" 10.875" Minimum Interrupting Rating RMS Amps 170 250 340 390 500 760 1000 1500 1950 Max Interrupting Rating RMS Asym 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 Figure Number 1 1 1 1 1 1 1 2 2 Previous Next R Rated Medium Voltage Fuses Current Limiting 6.38" 3"DIA Dim.A (Clip Center) Dim.B FIGURE 4 R 5.5 KV 14”Clip Centers 5.5 KV RATED R 8.25 KV RATED FIGURE 5 Catalog Number 70-2R-1C-5.5 100-3R-1C-5.5 130-4R-1C-5.5 150-5R-1C-5.5 170-6R-1C-5.5 200-9R-1C-5.5 230-12R-1C-5.5 390-18R-2C-5.5 450-24R-2C-5.5 480-26R-2C-5.5 550-30R-2C-5.5 600-32R-2C-5.5 650-36R-2C-5.5 550-30R-3C-5.5 600-32R-3C-5.5 650-36R-3C-5.5 Old Catalog Number LCL 2R LCL 3R LCL 4R LCL 5R LCL 6R LCL 9R LCL 12R LCL 18R LCL 24R — — — — — — LCL 36R Size 2R 3R 4R 5R 6R 9R 12R 18R 24R 26R 30R 32R 36R 30R 32R 36R Maximum Continuous Current @ 40 deg C. 70 100 130 150 170 200 230 390 450 480 550 600 650 550 600 650 70-2R-1C-5.5X 100-3R-1C-5.5X 130-4R-1C-5.5X 150-5R-1C-5.5X 170-6R-1C-5.5X 200-9R-1C-5.5X 230-12R-1C-5.5X 390-18R-2C-5.5X 450-24R-2C-5.5X — — — — — — — — — 2R 3R 4R 5R 6R 9R 12R 18R 24R 70 100 130 150 170 200 230 390 450 Size 2R 3R 4R 5R 6R 9R 12R 18R 24R Maximum Continuous Current @ 40 deg C. 70 100 130 150 170 200 230 390 450 Catalog Number 70-2R-1C-8.25 100-3R-1C-8.25 130-4R-1C-8.25 150-5R-1C-8.25 170-6R-1C-8.25 200-9R-1C-8.25 230-12R-1C-8.25 390-18R-2C-8.25 450-24R-2C-8.25 9.75" Old Catalog Number — — — — — — — — — FIGURE 6 Dim. A (inches) Dim. B (inches) 12" 15.875" 12" 15.875" 12" 15.875" 14" 17.875" 14" 17.875" Dim. A (inches) Dim. B (inches) 12" 15.875" 12" 15.875" Minimum Interrupting Rating RMS Amps 170 250 340 390 500 760 1000 1500 1950 2100 2400 2600 2900 2400 2600 2900 Max Interrupting Rating RMS (Asym) 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 Figure Number 4 4 4 4 4 4 4 5 5 5 5 5 5 6 6 6 170 250 340 390 500 760 1000 1500 1950 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 4 4 4 4 4 4 4 5 5 Minimum Interrupting Rating RMS Amps 190 225 330 440 500 740 955 1440 1910 Max Interrupting Rating RMS (Asym) 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 Figure Number 4 4 4 4 4 4 4 5 5 Add “w” suffix to part number for hookeye attachment. 63 Previous Next R Rated Medium Voltage Fuses Current Limiting Littelfuse’s POWR-GARD medium voltage fuses are available in several bolt-in mounting configurations. Contact factory for custom configurations “B” “BI” “IB” Bolt mount Bolt-In mount Inverted-Bolt mount Refer to illustrations for mounting dimensions. (2) .34" X .660 Slots 1.38" Apart 3" Dia. Indicator Indicator Indicator Indicator 3" Dia. Dim.B Dim.B Dim.B (2) .34" Holes 1.38" Apart Dim.A Dim.A FIGURE 7 FIGURE 8 FIGURE 9 Bolt Mount “B” R 2.75 KV 64 Bolt Mount “B” Inverted Bolt “IB” 2.75 KV RATED Catalog Number 70-2R-1B-2.75 100-3R-1B-2.75 130-4R-1B-2.75 150-5R-1B-2.75 170-6R-1B-2.75 200-9R-1B-2.75 230-12R-1B-2.75 390-18R-2B-2.75 450-24R-2B-2.75 70-2R-1IB-2.75 100-3R-1IB-2.75 130-4R-1IB-2.75 150-5R-1IB-2.75 170-6R-1IB-2.75 200-9R-1IB-2.75 230-12R-1IB-2.75 390-18R-2IB-2.75 450-24R-2IB-2.75 Old Catalog Number — — — — FIGURE 10 Inverted Bolt “IB” Size 2R 3R 4R 5R 6R 9R 12R 18R 24R Maximum Continuous Current @ 40 deg C. 70 100 130 150 170 200 230 390 450 2R 3R 4R 5R 6R 9R 12R 18R 24R 70 100 130 150 170 200 230 390 450 Dim. A (inches) Dim. B (inches) 4.6" 13" 7.4" 13" — 13" — 13" Minimum Interrupting Rating RMS Amps 170 250 240 390 500 760 1000 1500 1950 Max Interrupting Rating RMS (Asym) 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 Figure Number 7 7 7 7 7 7 7 8 8 170 250 340 390 500 760 1000 1500 1950 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 9 9 9 9 9 9 9 10 10 Previous .44" X .91" Slots (1.53" c.t.c.) 3"Dia. Indicator Next Indicator Dim.B Dim.B Dim.A Dim.A Front View Dim.A FIGURE 11 FIGURE 12 FIGURE 13 Bolt-In Mount “BI” R 5.5 KV 5.5 KV Bolt Mount “B” 70-2R-1B-5.5 100-3R-1B-5.5 130-4R-1B-5.5 150-5R-1B-5.5 170-6R-1B-5.5 200-9R-1B-5.5 230-12R-1B-5.5 390-18R-2B-5.5 450-24R-2B-5.5 550-30R-2B-5.5 600-32R-2B-5.5 650-36R-2B-5.5 Inverted Bolt “IB” 5.5 KV Catalog Number 70-2R-1BI-5.5 100-3R-1BI-5.5 130-4R-1BI-5.5 150-5R-1BI-5.5 170-6R-1BI-5.5 200-9R-1BI-5.5 230-12R-1BI-5.5 390-18R-2BI-5.5 450-24R-2BI-5.5 480-26R-2BI-5.5 550-30R-2BI-5.5 600-32R-2BI-5.5 650-36R-2BI-5.5 550-30R-3BI-5.5 600-32R-3BI-5.5 650-36R-3BI-5.5 700-38R-3BI-5.5 70-2R-1IB-5.5 100-3R-1IB-5.5 130-4R-1IB-5.5 150-5R-1IB-5.5 170-6R-1IB-5.5 200-9R-1IB-5.5 230-12R-1IB-5.5 390-18R-2IB-5.5 450-24R-2IB-5.5 550-30R-2IB-5.5 600-32R-2IB-5.5 650-36R-2IB-5.5 Bolt-In Mount “BI” 8.25 KV Bolt In Mount “BI” RATED 70-2R-1BI-8.25 100-3R-1BI-8.25 130-4R-1BI-8.25 150-5R-1BI-8.25 170-6R-1BI-8.25 200-9R-1BI-8.25 230-12R-1BI-8.25 390-18R-2BI-8.25 450-24R-2BI-8.25 Old Catalog Number — — — — — — — — — Size 2R 3R 4R 5R 6R 9R 12R 18R 24R 26R 30R 32R 36R 30R 32R 36R 38R Maximum Continuous Current @ 40 deg C. 70 100 130 150 170 200 230 390 450 480 550 600 650 550 600 650 700 2R 3R 4R 5R 6R 9R 12R 18R 24R 30R 32R 36R 70 100 130 150 170 200 230 390 450 550 600 650 2R 3R 4R 5R 6R 9R 12R 18R 24R 30R 32R 36R 70 100 130 150 170 200 230 390 450 550 600 650 2R 3R 4R 5R 6R 9R 12R 18R 24R 70 100 130 150 170 200 230 390 450 Dim. A (inches) Dim. B (inches) 3.6 18" 7.6 18" Minimum Interrupting Rating RMS Amps 170 250 340 390 500 760 1000 1500 1950 2200 2400 2650 2900 Max Interrupting Rating RMS (Asym) 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 Figure Number 11 11 11 11 11 11 11 12 12 12 12 12 12 13 13 13 13 170 250 340 390 500 760 1000 1500 1950 2400 2650 2900 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 7 7 7 7 7 7 7 8 8 8 8 8 170 250 340 390 500 760 1000 1500 1950 2400 2650 2900 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 9 9 9 9 9 9 9 10 10 10 10 10 190 225 330 400 500 740 955 1440 1910 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 80,000 11 11 11 11 11 11 11 12 12 18" 4.6 18" 7.4 18" 8.4 — 18" — 18" 3.6 18" 7.6 18" 65 Previous Next E Rated Medium Voltage Fuses Current Limiting “E” Rated fuses have time current characteristics designed to provide current limiting protection for power transformers, potential transformers, power centers, feeder centers, and unit sub stations. When properly applied, they can protect against high and low value fault currents. NEMA Standards for “E” rated medium voltage fuses require that fuses rated 100E or less open within 300 seconds (5 minutes) when subjected to an RMS value of 200-240% of the fuse’s continuous current rating; and fuses with an “E” rating larger than 100E must open within 600 seconds (10 minutes) when subjected to an rms current of 220-240% of the fuse’s continuous current rating. These values establish one point on the time-current curve. CHARACTERISTICS Voltage Rating: 2,400 volts – 38,000 volts Current Range: 10E – 600E OPTIONS ■ ■ Hermetically Sealed for use in hazardous locations (add “S” suffix to part number) Clip-lock (CL) and bolt-in styles available. Application Note: Since these fuses are used for the protection of general purpose circuits which may contain transformers, motors, and other equipment producing inrush and/or overload currents, fuses should generally be rated at 140% of the normal full load current, and circuits should be analyzed to ensure that system load currents will not exceed the current rating of the fuse. 6.38" 3"DIA Dim.A (Clip Center) Dim.B FIGURE 14 E 2.75 Max. KV RATED 66 Catalog Number 10E-1C-2.75 15E-1C-2.75 20E-1C-2.75 25E-1C-2.75 30E-1C-2.75 40E-1C-2.75 50E-1C-2.75 65E-1C-2.75 80E-1C-2.75 100E-1C-2.75 125E-1C-2.75 150E-1C-2.75 200E-1C-2.75 125E-2C-2.75 150E-2C-2.75 175E-2C-2.75 200E-2C-2.75 225E-2C-2.75 250E-2C-2.75 300E-2C-2.75 350E-2C-2.75 400E-2C-2.75 450E-2C-2.75 9.75" Old Catalog Number LCX 10E — — — LCX 30E LCX 40E LCX 50E LCX 65E LCX 80E LCX 100E — — — LCX 125E LCX 150E LCX 175E LCX 200E LCX 250E LCX 300E LCX 400E — FIGURE 15 Size 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 200E 125E 150E 175E 200E 225E 250E 300E 350E 400E 450E FIGURE 16 Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 7" 10.875" 80,000 7" 10.875" 80,000 Figure Number 14 14 14 14 14 14 14 14 14 14 14 14 14 15 15 15 15 15 15 15 15 15 15 Previous Next E Rated Medium Voltage Fuses Current Limiting E 5.5 Max. KV 5.5 Max. KV RATED Catalog Number 10E-1C-5.5 15E-1C-5.5 20E-1C-5.5 25E-1C-5.5 30E-1C-5.5 40E-1C-5.5 50E-1C-5.5 65E-1C-5.5 80E-1C-5.5 100E-1C-5.5 125E-1C-5.5 150E-1C-5.5 175E-1C-5.5 200E-1C-5.5 125E-2C-5.5 150E-2C-5.5 175E-2C-5.5 200E-2C-5.5 250E-2C-5.5 300E-2C-5.5 350E-2C-5.5 400E-2C-5.5 450E-2C-5.5 500E-3C-5.5 550E-3C-5.5 600E-3C-5.5 5NLE-10E 5NLE-15E 5NLE-20E 5NLE-25E 5NLE-30E 5NLE-40E 5NLE-50E 5NLE-65E 5NLE-80E 5NLE-100E 5NLE-125E 5NLE-150E 5NLE-175E 5NLE-200E 5NLE2-225E 5NLE2-250E 5NLE2-300E 5NLE2-350E 5NLE2-400E 5NLE2-450E Old Catalog Number — — — — LCY 30E LCY 40E LCY 50E LCY 60E LCY 80E LCY 100E LCY 125E LCY 150E LCY 175E LCY 200E — — — — LCY 250E LCY 300E LCY 350E LCY 400E LCY 450E — — — LCU 30E LCU 40E LCU 50E LCU 65E LCU 80E LCU 100E LCU 125E LCU 150E LCU 175E LCU 200E LCU 250E LCU 300E LCU 350E LCU 400E LCU 450E Size 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 125E 150E 175E 200E 250E 300E 350E 400E 450E 500E 550E 660E 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 225E 250E 300E 350E 400E 450E Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 12" 15.875" 80,000 12" 15.875" 80,000 12" 15.875" 80,000 14 17-7/8" 80,000 14" 17-7/8" 80,000 Diagram 14 14 14 14 14 14 14 14 14 14 14 14 14 14 15 15 15 15 15 15 15 15 15 16 16 16 14 14 14 14 14 14 14 14 14 14 14 14 14 14 15 15 15 15 15 15 67 Previous Next E Rated Medium Voltage Fuses Current Limiting E 8.25 Max. KV 8.25 Max. KV RATED E 15.5 Max. KV RATED 68 Catalog Number 10E-1C-8.25 15E-1C-8.25 20E-1C-8.25 25E-1C-8.25 30E-1C-8.25 40E-1C-8.25 50E-1C-8.25 65E-1C-8.25 80E-1C-8.25 100E-1C-8.25 125E-1C-8.25 150E-1C-8.25 125E-2C-8.25 150E-2C-8.25 200E-2C-8.25 250E-2C-8.25 300E-2C-8.25 350E-3C-8.25 400E-3C-8.25 8NLE-10E 8NLE-15E 8NLE-20E 8NLE-25E 8NLE-30E 8NLE-40E 8NLE-50E 8NLE-65E 8NLE-80E 8NLE-100E 8NLE2-100E 8NLE2-125E 8NLE2-150E 8NLE2-200E 8NLE2-250E Catalog Number 10E-1C-15.5 15E-1C-15.5 20E-1C-15.5 25E-1C-15.5 30E-1C-15.5 40E-1C-15.5 50E-1C-15.5 65E-1C-15.5 80E-1C-15.5 100E-1C-15.5 65E-2C-15.5 80E-2C-15.5 100E-2C-15.5 125E-2C-15.5 150E-2C-15.5 175E-2C-15.5 200E-2C-15.5 200E-3C-15.5 250E-3C-15.5 300E-3C-15.5 Old Catalog Number LDZ 30E LDZ 40E LDZ 50E LDZ 65E LDZ 80E LDZ 100E LDZ 125E LDZ 150E LDZ 125E LDZ 150E LDZ 200E LDZ 250E LDZ 300E LDZ 350Z LCZ 30E LCZ 40E LCZ 50E LCZ 65E LCZ 80E LCZ 100E LCZ 100E LCZ 125E LCZ 150E LCZ 200E Old Catalog Number LDN 10E LDN 15E LDN 20E LDN 25E LDN 30E LDN 40E LDN 50E LDN 65E LDN 80E LDN 100E LDN 150E LDN 175E Size 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 125E 150E 200E 250E 300E 350E 400E 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 100E 125E 150E 200E 250E Size 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 65E 80E 100E 125E 150E 175E 200E 200E 250E 300E Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 12" 15-7/8" 80,000 12" 15-7/8" 80,000 12" 15-7/8" 80,000 14" 17-7/8" 80,000 14" 17-7/8" 80,000 Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 15" 18.875" 60,000 15" 18.875" 60,000 15" 18.875" 60,000 Diagram 14 14 14 14 14 14 14 14 14 14 14 14 15 15 15 15 15 16 16 14 14 14 14 14 14 14 14 14 14 15 15 15 15 15 Figure Number 14 14 14 14 14 14 14 14 14 14 15 15 15 15 15 15 15 16 16 16 Previous Next E Rated Medium Voltage Fuses Current Limiting E 15.5 Max. KV 15.5 Max. KV RATED E 25.8 Max. KV RATED E 38 Max. KV RATED Catalog Number 15GSE-65E 15GSE-80E 15GSE-100E 15GSE2-125E 15GSE2-150E 15GSE2-175E 15GSE2-200E 15NLE-10E 15NLE-15E 15NLE-20E 15NLE-25E 15NLE-30E 15NLE-40E 15NLE-50E 15NLE-65E 15NLE-80E 15NLE-100E 15NLE2-80E 15NLE2-100E 15NLE2-125E 15NLE2-150E 15NLE2-175E 15NLE2-200E 15NLE3-150E 15NLE3-175E 15NLE3-250E 15NLE3-300E Catalog Number 15E-1C-25.8 20E-1C-25.8 25E-1C-25.8 30E-1C-25.8 40E-1C-25.8 50E-1C-25.8 65E-2C-25.8 80E-2C-25.8 100E-2C-25.8 Catalog Number 3E-1C-38.0 7E-1C-38.0 10E-1C-38.0 15E-1C-38.0 20E-1C-38.0 25E-1C-38.0 30E-1C-38.0 40E-1C-38.0 50E-2C-38.0 65E-2C-38.0 80E-2C-38.0 Old Catalog Number — — LCN 30E LCN 40E LCN 50E LCN 65E LCN 80ES LCN 100ES LCN 80E LCN 100E LCN 125X LCN 150E LCN 200ED — Old Catalog Number — — Old Catalog Number — — Size 65E 80E 100E 125E 150E 175E 200E 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 80E 100E 125E 150E 175E 200E 150E 175E 250E 300E Size 15E 20E 25E 30E 40E 50E 65E 80E 100E Size 3E 7E 10E 15E 20E 25E 30E 40E 50E 65E 80E Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 18" 21-7/8" 60,000 18" 21-7/8" 60,000 20" 23-7/8" 60,000 20" 23-7/8" 60,000 20" 23-7/8" 60,000 Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 21" 24-5/8" 40,000 21" 24-5/8" 40,000 Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 27" 30-5/8" 20,000 27" 30-5/8" 20,000 Figure Number 14 14 14 15 15 15 15 14 14 14 14 14 14 14 14 14 14 15 15 15 15 15 15 16 16 16 16 Figure Number 14 14 14 14 14 14 15 15 15 Figure Number 14 14 14 14 14 14 14 14 15 15 15 69 Previous Next E Rated Medium Voltage Fuses Current Limiting 4.31 7.94 11.56 Clip Lock Design The clip lock type designs ensures a positive contact between the fuse and the connection cam. The fuse’s clip lock tab slides in between the clip casting and the cam to prevent the fuse from slipping or blowing out of the holder. This positive contact improves heat dissipation and allows fuses to run cooler. E Clip Lock 5.5 Max. KV RATED E Clip Lock 8.25 Max. KV RATED E 70 Clip Lock 15.5 Max. KV RATED Catalog Number 10E-1CL-5.5 15E-1CL-5.5 20E-1C-5.5 25E-1CL-5.5 30E-1CL-5.5 40E-1CL-5.5 50E-1CL-5.5 65E-1CL-5.5 80E-1CL-5.5 100E-1CL-5.5 125E-1CL-5.5 150E-1CL-5.5 225E-2CL-5.5 250E-2CL-5.5 300E-2CL-5.5 350E-2CL-5.5 400E-2CL-5.5 450E-2CL-5.5 500E-3CL-5.5 550E-3CL-5.5 600E-3CL-5.5 Catalog Number 10E-1CL-8.25 15E-1CL-8.25 20E-1C-8.25 25E-1CL-8.25 30E-1CL-8.25 40E-1CL-8.25 50E-1CL-8.25 65E-1CL-8.25 80E-1CL-8.25 100E-1CL-8.25 125E-2CL-8.25 150E-2CL-8.25 175E-2CL-8.25 200E-2CL-8.25 225E-2CL-8.25 250E-2CL-8.25 300E-2CL-8.25 350E-3CL-8.25 Catalog Number 10E-1CL-15.5 15E-1CL-15.5 20E-1CL-15.5 25E-1CL-15.5 30E-1CL-15.5 40E-1CL-15.5 50E-1CL-15.5 65E-1CL-15.5 80E-1CL-15.5 100E-1CL-15.5 125E-2CL-15.5 150E-3CL-15.5 175E-3CL-15.5 200E-3CL-15.5 225E-3CL-15.5 250E-3CL-15.5 300E-3CL-15.5 Old Catalog Number — — — Old Catalog Number — — — Old Catalog Number — — — — Size 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 225E 250E 300E 350E 400E 450E 500E 550E 600E Size 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125E 150E 175E 200E 225E 250E 300E 350E Size 10E 15E 20E 25E 30E 40E 50E 65E 80E 100E 125 150E 175E 200E 225E 250E 300E 1.25 A B .25 3.0 FIGURE 17 FIGURE 18 1.25 FIGURE 19 Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 16.38" 15.13" 80,000 17.38" 16.13" 80,000 17.38" 16.13" 80,000 Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 17.38" 16.13" 80,000 17.38" 16.13" 80,000 17.38" 16.13" 80,000 Dim. A (inches) Dim. B (inches) Max Interrupting Rating RMS (Asym) 19.8" 18.1" 60,000 22.81" 21.13" 60,000 22.81" 19.1" 60,000 22.81" 19.1" 60,000 Figure Number 17 17 17 17 17 17 17 17 17 17 17 17 18 18 18 18 18 18 19 19 19 Figure Number 17 17 17 17 17 17 17 17 17 17 18 18 18 18 18 18 18 19 Figure Number 17 17 17 17 17 17 17 17 17 17 18 19 19 19 19 19 19 Previous Next E Rated Potential Transformer Fuses Current Limiting Potential Transformer (PT) fuses are current limiting fuses with high interrupting ratings designed for the protection of potential transformers. CHARACTERISTICS Voltage Rating: 600VAC – 25,500 VAC Current Range: 1/2E – 10E Application Note: When applying fuses for the protection of transformers, the magnetizing current inrush must be considered. The characteristics of the inrush, which can be matched with a fuse’s time-current curve, should be available from the transformer manufacturer. B A E Size 3E 5E 7E 10E Max Interrupting Rating RMS (Asym) 62,500 62,500 62,500 62,500 1E 2E 4.625 4.625 0.8125 0.8125 40,000 40,000 1E 2E 3E 1E 2E 3E 7.375 7.375 7.375 9.5 9.5 9.5 1.625 1.625 1.625 1.625 1.625 1.625 37,500 37,500 37,500 50,000 50,000 50,000 LCE 1E-4 LCE 2E-4 1E 2E 5.5 5.5 0.8125 0.8125 50,000 50,000 LCQ .5E LCQ 1E LCQ 2E LCQ 3E LCQ 5E LCQ 10E 1/2E 1E 2E 3E 5E 1/2E 1E 2E 3E 5E 10E 7.375 7.375 7.375 7.375 7.375 9.5 9.5 9.5 9.5 9.5 9.5 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 1.625 37,500 37,500 37,500 37,500 37,500 37,500 37,500 37,500 37,500 37,500 37,500 1/2E 1E 2E 3E 9.5 9.5 9.5 9.5 1.625 1.625 1.625 1.625 50,000 50,000 50,000 50,000 2.4 Max. KV 1E-4PT-2.4 2E-4PT-2.4 2.75 Max. KV 1E-6PT-2.75 2E-6PT-2.75 3E-6PT-2.75 1E-8PT-2.75 2E-8PT-2.75 3E-8PT-2.75 4.8 Max. KV 1E-5PT-4.8 2E-5PT-4.8 5.5 Max. KV 1/2E-6PT-5.5 1E-6PT-5.5 2E-6PT-5.5 3E-6PT-5.5 5E-6PT-5.5 1/2E-8PT-5.5 1E-8PT-5.5 2E-8PT-5.5 3E-8PT-5.5 5E-8PT-5.5 10E-8PT-5.5 8.25 Max. KV 1/2E-8PT-8.25 1E-8PT-8.25 2E-8PT-8.25 3E-8PT-8.25 15.5 Max. KV Catalog Number 3E-4PT-6 5E-4PT-6 7E-4PT-6 10E-4PT-6 Diameter Dim. B (inches) 0.8125 0.8125 0.8125 0.8125 1/2E-11PT-15.5 1E-11PT-15.5 2E-11PT-15.5 3E-11PT-15.5 3E-16PT-15.5 5E-16PT-15.5 LCT .5E LCT 1E LCT 2E LCT 3E 1/2E 1E 2E 3E 3E 5E 12.875 12.875 12.875 12.875 17.5 17.5 1.625 1.625 1.625 1.625 1.625 1.625 80,000 80,000 80,000 80,000 80,000 80,000 25.5 Max. KV 600 Volt PT Length Dim. A (inches) 4.625 4.625 4.625 4.625 Old Catalog Number 1/2E-16PT-25.5 1E-16PT-25.5 LCJ 1E-4 LCJ 2E-4 1/2E 1E 17.5 17.5 1.625 1.625 43,500 43,500 LCD 1E-4 LCD 2E-4 71 Previous Live Parts Live parts are available for mounting “E”, “R”, and “PT” single, double, and triple barrel fuses. Mounting clips are available for ferrule type and clip lock style fuses. All clips are sold in pairs. Contact factory for additional live parts. Part Number: 700-500* Part Number: 700-530* .08 For use with all 13/16" diameter PT fuses. .41 X1.06 SLOT For use with all 3” diameter fuses. 1.50 .31 1.56 4.00 .71 .30 .78 .08 1.15 4.66 .05 3.08 * One Pair .78 * One Pair .63 Part Number: 700-520-CL* Mounting Details for Clip Lock Clip Lock Design (For CL-14) 3.63 TRIPLE BARREL 3.63 DOUBLE BARREL Bottom Lever In Closed Position SINGLE BARREL 4.85 1.75 Blown Fuse Indicator 1.00 2.00 4.9 * One Pair 72 TOP VIEW 3.75 2.00 Top Lever in Open Position A 2.00 .56 Dia. (2) Holes For Mounting Cable/Bus .44 DIA. (2) HOLES FUSES HHC MEDIUM VOLTAGE FUSES FOR CAPACITORS NORTH AMERICAN STYLE SIBA Capacitor protection fuses can easily be fitted direct onto capacitor bushings, because they are fitted with threaded holes at both ends. Their electrical characteristic suits the protection requirements of capacitors. The capacitor fuses are available in the following ratings: Voltage ratings: 4.8 / 7.2 / 15.5 kV Amp. ratings: 6.3 - 250 A Features/Benefits Standards: IEC 60 282-1 · IEC 60 549 High interrupting rating 63 kA Characteristic following capacitor protection needs for back up protection Suitable for direct fitting onto capacitor bushing Cartridge type current limiting Special mounting brackets available on request HHC 1 HHC FUSES Selection Guide Thread Rated Voltage AC kV Diameter mm Class Part No. Selector Guide Page Techn. Data Page 1/2” UNC 1/2” UNC 1/2” UNC 1/2” UNC 1/2” UNC 1/2” UNC M16 M16 M16 M16 M16 M16 4.8 4.8 4.8 7.2 7.2 15.5 4.8 4.8 4.8 7.2 7.2 15.5 63.5 76 76 63.5 76 63.5 63.5 76 76 63.5 76 63.5 Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up Back up 30 349 21 30 350 21 30 351 21 30 352 21 30 353 21 30 354 21 30 356 21 30 357 21 30 358 21 30 359 21 30 360 21 30 361 21 HHC 3 HHC 3 HHC 3 HHC 4 HHC 4 HHC 5 HHC 6 HHC 6 HHC 6 HHC 7 HHC 7 HHC 8 HHC 9 HHC 9 HHC 9 HHC 9 HHC 9 HHC 10 HHC 10 HHC 10 HHC 10 HHC 11 HHC 11 HHC 11 HHC 2 HHC FUSES MEDIUM VOLTAGE FUSES FOR CAPACITORS NORTH AMERICAN STYLE Rated voltage AC 4.8 kV Class Back up Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 350 21 30 350 21 30 351 21 30 351 21 thread 1/2” UNC D= Diameter inch mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.99 2.99 2.99 2.99 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 76 76 76 76 Standard IEC 60 282-1 · IEC 60 549 Rated breaking capacity kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.5 2.5 3.6 3.6 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 30 349 21/30 350 21 E L F 10.00 ” (254 mm) 10.75 ” (273 mm) 1.57 ” (40 mm) 30 351 21 E L F 14.13 ” (359 mm) 14.88 ” (378 mm) 1.57 ” (40 mm) HHC 3 HHC FUSES MEDIUM VOLTAGE FUSES FOR CAPACITORS NORTH AMERICAN STYLE Rated voltage AC 7.2 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 353 21 30 353 21 30 353 21 30 352 21 E L F 10.00 ” (254 mm) 10.75 ” (273 mm) 1.57 ” (40 mm) 30 353 21 E L F Class Back up 14.13 ” (359 mm) 14.88 ” (378 mm) 1.57 ” (40 mm) HHC 4 thread 1/2” UNC D= Diameter inch mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.99 2.99 2.99 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 76 76 76 Standard IEC 60 282-1 · IEC 60 549 Rated breaking capacity kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 63 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 3.6 3.6 3.6 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 HHC FUSES MEDIUM VOLTAGE FUSES FOR CAPACITORS NORTH AMERICAN STYLE Rated voltage AC 15.5 kV Class Back up Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 thread 1/2” UNC D= Diameter inch mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 Standard IEC 60 282-1 · IEC 60 549 Rated breaking capacity kA Weight 63 63 63 63 63 63 63 63 63 63 63 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 E L F 14.13 ” (359 mm) 14.88 ” (378 mm) 1.57 ” (40 mm) HHC 5 HHC FUSES MEDIUM VOLTAGE FUSES FOR CAPACITORS NORTH AMERICAN STYLE Rated voltage AC 4.8 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 356 21 30 356 21 30 356 21 30 356 21 30 356 21 30 356 21 30 356 21 30 356 21 30 356 21 30 356 21 30 356 21 30 357 21 30 357 21 30 358 21 30 358 21 30 356 21/30 357 21 E L F 10.00 ” (254 mm) 10.75 ” (273 mm) 1.57 ” (40 mm) 30 358 21 E L F Class Back up 14.13 ” (359 mm) 14.88 ” (378 mm) 1.57 ” (40 mm) HHC 6 thread M16 D= Diameter inch mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.99 2.99 2.99 2.99 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 76 76 76 76 Standard IEC 60 282-1 · IEC 60 549 Rated breaking capacity kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.5 2.5 3.6 3.6 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 HHC FUSES MEDIUM VOLTAGE FUSES FOR CAPACITORS NORTH AMERICAN STYLE Rated voltage AC 7.2 kV Class Back up Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 359 21 30 359 21 30 359 21 30 359 21 30 359 21 30 359 21 30 359 21 30 359 21 30 359 21 30 359 21 30 359 21 30 360 21 30 360 21 30 360 21 thread M16 D= Diameter inch mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.99 2.99 2.99 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 76 76 76 Standard IEC 60 282-1 · IEC 60 549 Rated breaking capacity kA Weight 63 63 63 63 63 63 63 63 63 63 63 63 63 63 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.5 2.5 2.5 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 30 359 21 E L F 10.00 ” (254 mm) 10.75 ” (273 mm) 1.57 ” (40 mm) 30 360 21 L1 L2 F 14.13 ” (359 mm) 14.88 ” (378 mm) 1.57 ” (40 mm) HHC 7 HHC FUSES MEDIUM VOLTAGE FUSES FOR CAPACITORS NORTH AMERICAN STYLE Rated voltage AC 15.5 kV E L F Class Back up Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 30 361 21 30 361 21 30 361 21 30 361 21 30 361 21 30 361 21 30 361 21 30 361 21 30 361 21 30 361 21 30 361 21 14.13 ” (359 mm) 14.88 ” (378 mm) 1.57 ” (40 mm) HHC 8 thread M16 D= Diameter inch mm 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 63.5 Standard IEC 60 282-1 · IEC 60 549 Rated breaking capacity kA Weight 63 63 63 63 63 63 63 63 63 63 63 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 Pack (kg/1) 1 1 1 1 1 1 1 1 1 1 1 Electrical Characteristics Rated voltage AC 4.8 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 350 21 30 350 21 30 351 21 30 351 21 Rated voltage AC 7.2 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 353 21 30 353 21 30 353 21 FUSES Class Back up HHC thread 1/2” UNC Breaking current kA Pre-arcing I2t-value A2s Total I2t-value A2s Power loss W 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 45 75 250 640 1050 1700 2900 5700 10,700 21,000 33,000 47,000 90,000 230,000 371,000 330 500 1,800 4,300 6,700 10,800 17,100 29,700 59,400 126,000 189,000 351,000 513,000 571,000 892,000 11 19 13 14 16 20 26 30 37 42 55 78 93 123 161 Class Back up thread 1/2” UNC Breaking current kA Pre-arcing I2t-value A2s Total I2t-value A2s Power loss W 63 63 63 63 63 63 63 63 63 63 63 63 63 63 45 75 250 640 1050 1700 2900 5700 10,700 21,000 33,000 47,000 90,000 230,000 330 500 1,800 4,300 6,700 10,800 17,100 29,700 59,400 126,000 189,000 351,000 513,000 571,000 16 22 19 21 24 30 39 45 55 63 82 117 139 154 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGE HHC 12 HHC 9 HHC Electrical Characteristics FUSES Rated voltage AC 15.5 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 Rated voltage AC 4.8 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 250 A 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 349 21 30 350 21 30 350 21 30 351 21 30 351 21 Class Back up thread 1/2” UNC Breaking current kA Pre-arcing I2t-value A2s Total I2t-value A2s Power loss W 63 63 63 63 63 63 63 63 63 63 63 45 75 250 640 1050 1700 2900 5700 10,700 21,000 33,000 330 500 1,800 4,300 6,700 10,800 17,100 29,700 59,400 126,000 189,000 21 38 37 40 56 65 84 101 106 137 182 Class Back up thread M16 Breaking current kA Pre-arcing I2t-value A2s Total I2t-value A2s Power loss W 63 63 63 63 63 63 63 63 63 63 63 63 63 63 63 45 75 250 640 1050 1700 2900 5700 10,700 21,000 33,000 47,000 90,000 230,000 371,000 330 500 1,800 4,300 6,700 10,800 17,100 29,700 59,400 126,000 189,000 351,000 513,000 571,000 892,000 11 19 13 14 16 20 26 30 37 42 55 78 93 123 161 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGE HHC 12 HHC 10 Electrical Characteristics Rated voltage AC 7.2 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 125 A 160 A 200 A 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 352 21 30 353 21 30 353 21 30 353 21 Rated voltage AC 15.5 kV Rated current Part No. 6.3 A 10 A 16 A 20 A 25 A 31.5 A 40 A 50 A 63 A 80 A 100 A 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 30 354 21 FUSES Class Back up HHC thread M16 Breaking current kA Pre-arcing I2t-value A2s Total I2t-value A2s Power loss W 63 63 63 63 63 63 63 63 63 63 63 63 63 63 45 75 250 640 1050 1700 2900 5700 10,700 21,000 33,000 47,000 90,000 230,000 330 500 1,800 4,300 6,700 10,800 17,100 29,700 59,400 126,000 189,000 351,000 513,000 571,000 16 22 19 21 24 30 39 45 55 63 82 117 139 154 Class Back up thread M16 Breaking current kA Pre-arcing I2t-value A2s Total I2t-value A2s Power loss W 63 63 63 63 63 63 63 63 63 63 63 45 75 250 640 1050 1700 2900 5700 10,700 21,000 33,000 330 500 1,800 4,300 6,700 10,800 17,100 29,700 59,400 126,000 189,000 21 38 37 40 56 65 84 101 106 137 182 TIME CURRENT CHARACTERISTICS AND CUT OFF CURRENT DIAGRAM PLEASE REFER TO PAGE HHC 12 HHC 11 HHC Electrical Characteristics FUSES Time Current Characteristics Back up Virtual Pre-arcing Time t(s) RMS Prospective Current I(A) Cut Off Current Diagram Back up Cut-off Current Peak Ic (kA) Prospective Short Circuit Current HHC 12 I(kA)