Application Data AD29167K Effective April 2013 Supersedes June 2012 AB DE-IONT circuit breakers Time/current characteristic curves for Eaton Series C K-Frame circuit breakers Contents Description Curve No. Page Series CT Type DK Circuit Breakers ...............................................................SC-4117-87B ...................... 3 Series C Types KDB, KD, HKD Circuit Breakers Equipped with Type KT Thermal-Magnetic Trip Unit .....................................SC-4118-87B ...................... 4 Series C Type KDC Circuit Breakers Equipped with Type KT Thermal-Magnetic Trip Unit .............................................................SC-4119-87B ...................... 5 Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES DigitripE RMS 310+ Trip Units (250A and 400A) Long Delay (LD) and Short Delay (SD) with Flat Response and Override (KES3250LSI, KES3400LSI, KES3250LSIG, KES3400LSIG) ........................................................................TD012007EN ..................... 6 Long Delay Response and Short Delay with I2T Response Curve and Override (KES3250LS, KES3400LS, KES3250LSG, KES3400LSG) .....................................................TD012008EN ..................... 7 Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310+ Trip Units (250A and 400A) Long Delay (LD) and Short Delay (SD) with Flat Response and Override (KES3250LSI, KES3400LSI, KES3250LSIG, KES3400LSIG) ........................................................................TD012012EN ...................... 8 Long Delay Response and Short Delay with I2T Response Curve and Override (KES3250LS, KES3400LS, KES3250LSG, KES3400LSG) .....................................................TD012013EN ...................... 9 Ground Fault Delay Response and Maintenance Mode for Series C Types KD, CKD, HKD, CHKD, and KDC Circuit Breakers Equipped with Digitrip RMS 310+ Trip Units (250A and 400A) Ground Fault Delay Response Curve (250A and 400A) .................................TD012009EN ................... 10 Remote Maintenance Mode Setting (250A and 400A) ..................................TD012010EN .................... 11 Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units Types KES3125LS, KES3125LSG ....................................................................SC-5642-93 .......................12 Types KES3125LSI, KES3125LSIG .................................................................SC-5643-93 .......................13 Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units Types KES3125LS, KES3125LSG ....................................................................SC-5648-93 .......................14 Types KES3125LSI, KES3125LSIG .................................................................SC-5649-93 .......................15 Ground Fault Protection (KES3125LSG, KES3125LSIG) .................................SC-5652-93 .......................16 Application Data AD29167K Effective April 2013 Appendix Description Curve No. Page Obsoleted Type KES Digitrip RMS 310 Trip Units (250A and 400A) Replaced with Type KES Digitrip RMS 310+ Trip Units on Front Page Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units Types KES3400LS, KES3400LSG ...................................................................SC-5638-93 ....................... 17 Types KES3400LSI, KES3400LSIG .................................................................SC-5639-93 .......................18 Types KES3250LS, KES3250LSG ...................................................................SC-5640-93 .......................19 Types KES3250LSI, KES3250LSIG .................................................................SC-5641-93 .......................20 Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units Types KES3400LS, KES3400LSG ...................................................................SC-5644-93 ...................... 21 Types KES3400LSI, KES3400LSIG .................................................................SC-5645-93 ...................... 22 Types KES3250LS, KES3250LSG ...................................................................SC-5646-93....................... 23 Types KES3250LSI, KES3250LSIG .................................................................SC-5647-93 ...................... 24 Ground Fault Protection (KES3400LSG, KES3400LSIG) .................................SC-5650-93 ...................... 25 Ground Fault Protection (KES3250LSG, KES3250LSIG) .................................SC-5651-93 ...................... 26 NNote: Individual oversize copies of curves listed above printed on onion-skin paper are available in limited quantity. When ordering onion-skin curves, use number at bottom of page where curve appears, e.g., SC-4117-87B. Requests for full sets of curves will not be honored. 2 eaton www.eaton.com Application Data AD29167K Effective April 2013 10,000 2 HOURS 2 HOURS 50,000 40,000 30,000 Circuit Breaker Time/Current Curves Series C ® K-Frame Circuit Breakers 5,000 For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four (4) feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. 3,000 Maximum Voltage 240 Vac (60 Hz) 250 Vdc 2,000 500 Instantaneous Trip Amperes 200 1,000 500 to 1000% of trip unit rating (See Figure Below) (DC values are approximately 40% higher) 500 Interrupting Rating Breaker RMS Sym Type Amperes @ 240 Vac DK 65,000 (250–400A) Maximum Single-Pole Trip Times at 25°C 300 Amperes @ 240 Vdc 300 10,000 Single-pole data at 25°C based on NEMA Procedures (AB 4-1991) for verifying performance of molded-case circuit breakers. Minimum Maximum 200 Note: For additional information on the trip unit, see IL 29C603. 100 100 50 50 30 30 20 20 7.5 Typical Trip Unit Nameplate 10 10 7.5 C Thermal Magnetic Trip Unit 5 10 5 7.5 Push to Trip 5 Amps (In) Magnetic Multiples Of In 10 40°C 1 MINUTE 1 MINUTE 3,000 2,000 Breaker Rating Rated Amperes (I n ) 250 300 350 400 1,000 1 HOUR Catalog Type DK Thermal-Magnetic Circuit Breakers, 250–400 Amperes, Two- and Three-Poles, 240 Vac Max., 250 Vdc 5,000 1 HOUR 20,000 6000 7000 8000 9000 10,000 5000 4000 3000 2000 600 700 800 900 1000 500 400 300 200 70 80 90 100 10,000 60 50 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 60,000 70,000 80,000 90,000 100,000 AB DE-ION Circuit Breakers 5 10 Cat. No. 5 Individual Pole Adjustments 3 3 1 1 .5 5X ±20% 10X 2 .5 ±10% .3 .3 .2 .2 .1 .1 .05 .05 .03 .03 .02 .02 Maximum Interrupting Time .01 .01 60,000 70,000 80,000 90,000 100,000 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 50,000 40,000 30,000 20,000 6000 7000 8000 9000 10,000 5000 4000 3000 .001 2000 .001 600 700 800 900 1000 .002 500 .002 400 .003 300 .003 200 .005 60 70 80 90 100 .005 50 TIME IN SECONDS TIME IN SECONDS Adjustable Magnetic Trip 2 Figure 1. Series C Type DK Circuit Breakers eaton www.eaton.com 3 Application Data AD29167K Effective April 2013 10,000.000 K-Frame Circuit Breaker Time/Current Curves For application and coordination purposes only. Based on cold start at rated ambient temperature. Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series. Tested in open air. Breaker Rating Rated Amperes (I m) Instantaneous Trip 100, 125, 175, 200, Settings are 500 to 1000% of trip 225, 250, 300, 350, 400 unit rating. For DC, instantaneous trip may be 42% higher. Maximum Minimum 1000.000 Interruption Rating (UL/CSA Listed) Breaker Symmetrical rms Amperes (kA) Type KDB KD HKD 100.000 10.000 240 Vac 65 65 100 480 Vac 35 35 65 600 Vac 25 25 35 Amps(kA) 250 Vdc 10 10 22 Time in Seconds Maximum Single-Pole Trip Times at 25°C +30%–20% +30%–20% 1.000 Adjustable Magnetic Trip 0.100 Maximum Minimum Interruption Rating Determines End of Curve 0.010 0.001 10 100 1000 10,000 Current in Percent of Breaker Trip Unit Rating (In) 100,000 Figure 2. Series C Types KDB, KD, HKD Circuit Breakers Equipped with Type KT Thermal-Magnetic Trip Unit 4 eaton www.eaton.com 1,000,000 Application Data AD29167K 10,000 2 HOURS 2 HOURS 50,000 40,000 30,000 Circuit Breaker Time/Current Curves Series C® K-Frame Circuit Breakers Equipped with Type KT Thermal-Magnetic Trip Unit 5,000 Catalog Type KDC Current Limiting Circuit Breakers, 2-, 3- and 4-Pole For application and coordination purposes only. Based on 40°C ambient, cold start. Connected with four (4) feet of rated wire (60°C up to 125 amps. 75°C above 125 amps) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. 3,000 2,000 1 HOUR 5,000 1 HOUR 20,000 6000 7000 8000 9000 10,000 5000 4000 3000 2000 600 700 800 900 1000 500 400 300 200 70 80 90 100 10,000 60 50 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 60,000 70,000 80,000 90,000 100,000 Effective April 2013 3,000 2,000 Maximum Voltage 600 Vac (60 Hz) 250 Vdc 1,000 500 (250–400A) 300 (125–225A) 200 1,000 Breaker Rating Rated Amperes (In) Instantaneous Trip Amperes 100, 125, 150, 175, 200, 225, 250, 300, 350, 400 500 to 1000% of trip unit rating (See Figure Below) (Dc values are approximately 40% higher) Interrupting Rating (UL/CSA) RMS Sym Amperes Breaker Type @ 240 Vac @ 480 Vac Maximum Single-Pole Trip Times at 25°C 200,000 KDC 500 Amperes 100,000 @ 600 Vac @ 250 Vdc 50,000 22,000 300 Single-pole test data at 25°C based on NEMA Procedures (AB 4-1991) for verifying performance of molded-case circuit breakers. (100A) 200 Note: For additional information on the trip unit, see IL 29C603. 100 Minimum Maximum 50 50 30 30 20 1 MINUTE 1 MINUTE 100 20 7.5 Typical Trip Unit Nameplate 10 10 7.5 C Thermal Magnetic Trip Unit 5 10 5 5 Amps (In) Magnetic Multiples Of In 7.5 Push to Trip 10 40°C 5 10 Cat. No. 5 Individual Pole Adjustments 3 3 2 1 1 .5 5X ±20% 10X 2 TIME IN SECONDS TIME IN SECONDS Adjustable Magnetic Trip .5 ±10% .3 .3 .2 .2 .1 .1 .05 .05 .03 .03 .02 .02 Maximum Interrupting Time 600 Vac .01 .01 480 Vac .005 .005 240 Vac .003 .003 Interrupting Rating Determines End of Curve .002 .001 60,000 70,000 80,000 90,000 100,000 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 50,000 40,000 30,000 20,000 6000 7000 8000 9000 10,000 5000 4000 3000 2000 600 700 800 900 1000 500 400 300 200 60 70 80 90 100 .001 50 .002 Figure 3. Series C Type KDC Circuit Breakers Equipped with Type KT Thermal-Magnetic Trip Unit eaton www.eaton.com 5 Application Data AD29167K Effective April 2013 Current in Multiples of (Ir) 2 HOURS .5 .7 1 2 3 4 7 5 10 20 30 10000 9000 8000 7000 Circuit Breaker Time/Current Curves (Phase Current) 6000 1 HOUR 5000 K-Frame Circuit Breakers (250A and 400A) KDB, CKDB, HKDB, CHKDB Series C circuit breakers using 310+ trip unit 1.15 4000 3000 Long Delay (LD) and Short Delay (SD) with Flat Response (LSI, LSIG) 2000 In IR 1000 900 800 700 A B C D E F G H Maximum Total Clearing Time 600 250A 400A 100A 125A 150A 160A 175A 200A 225A 250A 160A 200A 225A 250A 300A 315A 350A 400A 500 Notes: 400 1. Curve accuracy applies from –20°C to +55°C ambient. Temperatures above +88°C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40°C, refer to Eaton. 300 1 MINUTE 200 2. Application frequency is 50/60 Hertz. 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. Available Long Delay Time: 2, 4, 7, 10, 12, 15, 20, 24 sec. Shown at 6 x IR 2, 4, 7, 15, 24 seconds +0/–30% 100 90 80 70 60 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 50 5. The left portion of the curve is shown as a multiple of the Long Delay Setting. (Long Delay Pickup = 115% of Ir). Range is 110%–120%. 40 30 . . 24 20 TIME IN SECONDS 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 15 Minimum Total Clearing Time 10 9 8 7 6 7. The Short Delay Pick Up has 9 settings/positions, 2–8 and 10, 12 IR. 8. For high fault current levels, an additional fixed instantaneous hardware override is provided at 4400A (Tolerance ±15%). For IR = In = 400A, the fixed instantaneous hardware override takes precedence over the SDPU setting of 12 x IR. . Interrupting Ratings—50/60 Hz RMS Sym. Amperes (kA) 7 5 240V 480V 600V 4 KD, CKD HKD, CHKD 65 100 35 65 25 35 . Breaker Type 240V 380V 415V 2 KD, CKD HKD, CHKD 65 100 40 65 40 65 . 4 3 2 2 1 .9 .8 .7 .6 UL/CSA Breaker Type 4 IEC 947-2 1 12 Available Short Delay Pick Up Settings 2–8, 10, 12 x IR ±5% (See Note 7) 6 3 8 5 .5 .4 .3 .5 .4 .2 300 ms (P, Q, R) .3 .1 .2 TIME IN SECONDS 7 120 ms (M, N, O) .1 .09 .08 .07 10 .06 Inst. (J, K, L) .05 .05 Fixed Instantaneous Override 4400A .04 .03 Interrupting Rating Determines End of Curve .02 .01 .04 .03 .02 30 40 50 70 100,000 Current in Multiples of (Ir) 20 50,000 10 40,000 7 30,000 5 20,000 4 10,000 3 5000 2 4000 1 3000 .7 2000 .001 .5 1000 .01 Current in Amps Figure 4. Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310+ Trip Units (250A and 400A), Long Delay (LD) and Short Delay (SD) with Flat Response and Override (KES3250LSI, KES3400LSI, KES3250LSIG, KES3400LSIG) 6 eaton www.eaton.com Application Data AD29167K Effective April 2013 Current in Multiples of (Ir) 2 HOURS .5 .7 1 2 3 4 7 5 10 20 30 10000 9000 8000 7000 Circuit Breaker Time/Current Curves (Phase Current) 6000 1 HOUR 5000 K-Frame Circuit Breakers (250A and 400A) KDB, CKDB, HKDB, CHKDB Series C circuit breakers using 310+ trip unit 1.15 4000 3000 Long Delay (LD) and Short Delay (SD) with I2T Response (LS, LSG) 2000 In IR 1000 900 800 700 A B C D E F G H Maximum Total Clearing Time 600 250A 400A 100A 125A 150A 160A 175A 200A 225A 250A 160A 200A 225A 250A 300A 315A 350A 400A 500 Notes: 400 1. Curve accuracy applies from –20°C to +55°C ambient. Temperatures above +88°C cause an over temperature protection trip. For possible continuous ampere derating for ambient above 40°C, refer to Eaton. 300 1 MINUTE 200 2. Application frequency is 50/60 Hertz. 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. Available Long Delay Time: 2, 4, 7, 10, 12, 15, 20, 24 sec. Shown at 6 x IR 2, 4, 7, 15, 24 Seconds +0/–30% 100 90 80 70 60 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 50 5. The left portion of the curve is shown as a multiple of the Long Delay Setting (Long Delay Pickup = 115% of IR). Range is 110%–120%. 40 30 . . TIME IN SECONDS 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 24 20 8. Short Delay I2T band has a tolerance of ±15%. 15 Minimum Total Clearing Time 10 9 8 7 6 7. The Short Delay Pickup has 9 settings/positions: 2–8 and 10, 12 IR. 9. Breakpoint back to FLAT response occurs at 8x IR for upper line of the I2T curve. . 10. For high fault current levels, an additional fixed instantaneous hardware override is provided at 4400A (Tolerance ±15%). For IR = In = 400A, the fixed instantaneous hardware override takes precedence over the SDPU setting of 12 x IR. 7 5 . 4 Interrupting Ratings—50/60 Hz RMS Sym. Amperes (kA) 4 3 2 . 3 2 2 4 1 .9 .8 .7 .6 UL/CSA Breaker Type 240V 480V 600V KD, CKD HKD, CHKD 65 100 35 65 25 35 IEC 947-2 Breaker Type 240V 380V 415V KD, CKD HKD, CHKD 65 100 40 65 40 65 5 .5 7 .4 .1 .3 12 8 Available Short Delay Pickup Settings 2–8, 10, 12 x IR ±5% (See Note 7) .2 6 .1 .09 .08 .07 10 . .06 67 ms .05 .04 Fixed Instantaneous Override 4400A .04 .03 TIME IN SECONDS I2T Short Delay (See Note 8) .05 Interrupting Rating Determines End of Curve .02 .01 .03 See Note 9 .02 .01 40 50 70 100,000 30 50,000 20 40,000 10 20,000 7 30,000 5 10,000 4 Current in Multiples of (Ir) 5000 3 4000 2 3000 1 2000 .7 1000 .001 .5 Current in Amps Figure 5. Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310+ Trip Units (250A and 400A), Long Delay Response and Short Delay with I2T Response Curve and Override (KES3250LS, KES3400LS, KES3250LSG, KES3400LSG) eaton www.eaton.com 7 Application Data AD29167K Effective April 2013 Current in Multiples of (Ir) 2 HOURS .5 .7 1 2 3 4 7 5 10 20 30 10000 9000 8000 7000 Circuit Breaker Time/Current Curves (Phase Current) 6000 1 HOUR 5000 K-Frame Circuit Breakers (250A and 400A) KDC Series C circuit breakers using 310+ trip unit 1.15 4000 3000 Long Delay (LD) and Short Delay (SD) with Flat Response (LSI, LSIG) 2000 In IR 1000 900 800 700 A B C D E F G H Maximum Total Clearing Time 600 250A 400A 100A 125A 150A 160A 175A 200A 225A 250A 160A 200A 225A 250A 300A 315A 350A 400A 500 Notes: 400 1. Curve accuracy applies from –20°C to +55°C ambient. Temperatures above +88°C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40°C, refer to Eaton. 300 1 MINUTE 200 2. Application frequency is 50/60 Hertz. 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. Available Long Delay Time: 2, 4, 7, 10, 12, 15, 20, 24 sec. Shown at 6 x IR 2, 4, 7, 15, 24 Seconds +0/–30% 100 90 80 70 60 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 50 5. The left portion of the curve is shown as a multiple of the Long Delay Setting. (Long Delay Pickup = 115% of IR). Range is 110%–120%. 40 30 . . TIME IN SECONDS 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 24 20 8. For high fault current levels, an additional fixed instantaneous hardware override is provided at 4400A (Tolerance ±15%). For IR = In = 400A, the fixed instantaneous hardware override takes precedence over the SDPU setting of 12 x IR. 15 Minimum Total Clearing Time 10 9 8 7 6 7. The Short Delay Pickup has 9 settings/positions, 2–8 and 10, 12 IR. . Interrupting Ratings—50/60 Hz RMS Sym. Amperes (kA) 7 5 . 4 UL/CSA Breaker Type 240V 200 KDC 480V 600V 100 65 4 3 IEC 947-2 Breaker Type . 2 240V KDC 200 380V 415V 100 50 2 2 1 .9 .8 .7 .6 1 4 12 Available Short Delay Pickup Settings 2–8, 10, 12 x IR ±5% (See Note 7) 6 3 8 5 .5 .4 300 ms (P, Q, R) .3 .1 7 120 ms (M, N, O) .1 .09 .08 .07 10 .06 Inst. (J, K, L) .05 TIME IN SECONDS .2 .05 Fixed Instantaneous Override 4400A .04 .03 Interrupting Rating Determines End of Curve Maximum Interrupting Time .02 600 Vac .01 480 Vac 240 Vac .04 .03 Current in Multiples of (Ir) 20 30 40 50 200,000 10 100,000 7 50,000 5 40,000 4 30,000 3 20,000 2 10,000 1 5000 .7 4000 .5 3000 .001 .01 2000 .02 Current in Amps Figure 6. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310+ Trip Units (250A and 400A), Long Delay (LD) and Short Delay (SD) with Flat Response and Override (KES3250LSI, KES3400LSI, KES3250LSIG, KES3400LSIG) 8 eaton www.eaton.com Application Data AD29167K Effective April 2013 2 HOURS Current in Multiples of (Ir) 10000 9000 8000 7000 .5 .7 1 3 4 5 7 10 20 30 Circuit Breaker Time/Current Curves (Phase Current) 6000 5000 1 HOUR 2 K-Frame Circuit Breakers (250A and 400A) KDC Series C circuit breakers using 310+ trip unit 1.15 4000 3000 Long Delay (LD) & Short Delay (SD) with I2T Response (LS, LSG) 2000 In IR 1000 900 800 700 A B C D E F G H Maximum Total Clearing Time 600 250A 400A 100A 125A 150A 160A 175A 200A 225A 250A 160A 200A 225A 250A 300A 315A 350A 400A 500 Notes: 400 1. Curve accuracy applies from –20°C to +55°C ambient. Temperatures above +88°C cause an overtemperature protection trip. For possible continuous ampere derating for ambient above 40°C, refer to Eaton. 300 1 MINUTE 200 2. Application frequency is 50/60 Hertz. 3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset memory. Available Long Delay Time: 2, 4, 7, 10, 12, 15, 20, 24 sec. Shown at 6 x Ir 2, 4, 7, 15, 24 Seconds +0/–30% 100 90 80 70 60 4. The right portion of the curve is determined by the interrupting rating of the circuit breaker. 50 5. The left portion of the curve is shown as a multiple of the Long Delay Setting (Long Delay Pickup = 115% of Ir). Range is 110%–120%. 40 30 . . 20 TIME IN SECONDS 6. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 24 8. Short Delay I2T band has a tolerance of ±15%. 15 Minimum Total Clearing Time 10 9 8 7 6 7. The Short Delay Pickup has 9 settings/positions: 2–8 and 10, 12 IR. 9. Breakpoint back to FLAT response occurs at 8x IR for upper line of the I2T curve. . 10. For high fault current levels, an additional fixed instantaneous hardware override is provided at 4400A (Tolerance ±15%). For IR= In= 400A, the fixed instantaneous hardware override takes precedence over the SDPU setting of 12 x IR. 7 5 . 4 4 Interrupting Ratings—50/60 Hz RMS Sym. Amperes (kA) . Breaker Type 3 2 3 4 1 .9 .8 .7 .6 200 KDC 2 2 UL/CSA 240V 480V 600V 100 65 IEC 947-2 Breaker Type 240V KDC 200 380V 415V 100 50 5 .5 7 .4 .1 .3 12 8 Available Short Delay Pickup Settings 2–8,10, 12 x IR ±5% (See Note 7) .2 6 .1 .09 .08 .07 10 . .06 67 ms .05 .04 Fixed Instantaneous Override 4400A .04 Maximum Interrupting Time .03 TIME IN SECONDS I2T Short Delay (See Note 8) .05 .02 600 Vac .01 480 Vac 240 Vac .03 See Note 9 .02 .01 Interrupting Rating Determines End of Curve 40 50 70 200,000 30 100,000 Current in Multiples of (Ir) 20 50,000 10 40,000 7 30,000 5 20,000 4 10,000 3 5000 2 4000 1 3000 .7 2000 .001 .5 Current in Amps Figure 7. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310+ Trip Units (250A and 400A), Long Delay Response and Short Delay with I2T Response Curve and Override (KES3250LS, KES3400LS, KES3250LSG, KES3400LSG) eaton www.eaton.com 9 Application Data AD29167K Effective April 2013 .1 .2 .3 .4 .7 .5 1.0 2.0 10000 9000 8000 7000 Circuit Breaker Time/Current Curves (Ground Current) 6000 5000 K-Frame Circuit Breakers (250A and 400A) KDB, CKDB, HKDB, CHKDB, and KDC Series C circuit breakers using 310+ trip unit 4000 3000 Ground fault delay response notes: 2000 1. Curve accuracy applies from –20°C to +55°C ambient. Temperatures above +88°C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40°C, refer to Eaton. 2. Application frequency is 50/60 Hertz. 1000 900 800 700 3. Trip units are suitable for functional field testing with test kit style # 70C1056G52. 600 4. For LD Response and SD with Flat Response curve, see TD012007EN. 500 5. For LD Response and SD with I2T Response curve, see TD012008EN. 400 6. For Ground Fault Delay Response (this curve), see TD012009EN. 300 68C 4081 H03 REMOTE MM STATUS TEST / ALARM 200 1 MINUTE IR ∑ Push to Trip 100 90 80 70 60 C B D E F A I sd (x IR ) t R (s) G H LONG 10 12 15 7 20 4 24 2 4 3 SHORT 5 6 7 2 .6 .8 1.0 .4 .3 I g (x In) .2 GND 120 tg 8 10 12 I i Inst. (ms) GND 300 50 40 TIME IN SECONDS 30 68C 4081 H04 20 REMOTE MM STATUS IR ∑ Push to Trip 10 9 8 7 C B D E F A G H t R (s) LONG 10 12 15 7 20 4 24 2 TEST / ALARM I sd (x IR ) 4 3 SHORT 5 6 7 2 8 10 12 I i .6 .8 1.0 .4 .3 I g (x In) .2 GND M N O L K J R P Q * t sd / t g (ms) SHORT / GND Ground Fault Pickup Settings (Tolerance 10%) 6 5 Note: Refer to table below for variations. 4 3 In Ir Available Sensors (In): 250A 400A 2 .4X .2X 1 .9 .8 .7 1X .6X .3X A B C D E F G H 250A 400A 100A 125A 150A 160A 175A 200A 225A 250A 160A 200A 225A 250A 300A 315A 350A 400A .8X .6 .5 .4 300 ms (L, O, R) .3 Curves in this Family: Long Delay Response and Short Delay with Flat Response — TD012007EN Long Delay Response and Short Delay with I2T Response — TD012008EN .2 Ground Fault Response Curve — TD012009EN 120 ms (K, N, Q) .1 .09 .08 .07 Remote Maintenance Mode Setting — TD012010EN .06 Inst. (J, M, P) .05 .04 .03 .02 .01 .1 .2 .3 .4 .5 .7 1.0 2.0 Ground Current in Multiple of (In) Figure 8. Series C Types KD, CKD, HKD, CHKD, and KDC Circuit Breakers Equipped with Digitrip RMS 310+ Trip Units (250A and 400A), Ground Fault Delay Response Curve (250A and 400A) 10 eaton www.eaton.com Application Data AD29167K Effective April 2013 KES 310+ Trip Unit Nameplates 68C 4081 H01 K-Frame Circuit Breakers (250A and 400A) KDB, CKDB, HKDB, CHKDB and KDC Series C circuit breakers using 310+ trip unit REMOTE MM STATUS IR∑ Response: The Remote Maintenance Mode Setting provides an instantaneous response time of 30 ms or less. Push to Trip C B D E F A G H LONG 10 12 15 7 20 4 24 2 TEST / ALARM I sd (xIR) t R (s) 4 3 SHORT 5 6 7 2 8 10 12 I i This curve is for 50 Hz and 60 Hz applications. 68C 4081 H02 REMOTE MM TEST / ALARM STATUS Notes: IR∑ 1. The Remote Maintenance Mode feature must be ENABLED via application of 24 Vdc for these curves to apply. The blue LED is lit when in Maintenance Mode. Push to Trip C B 2. The end of the curve is determined by the interrupting rating of the circuit breaker. 3. Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current. 68C 4081 H03 D E F A G H Push to Trip 68C 4081 H04 D E F A G H Push to Trip A LONG 10 12 15 7 20 4 24 2 4 3 G H LONG 10 12 15 7 20 4 24 2 8 10 12 I i 120 SHORT 5 6 7 2 8 10 12 I i 4 3 2 8 10 12 I i 300 SHORT .6 .8 1.0 .4 .3 I g (xIn) .2 GND 120 tg Inst. TEST / ALARM SHORT 5 6 7 t sd (ms) Inst. TEST / ALARM I sd (xIR) t R (s) IR∑ D E F 2 REMOTE MM STATUS Contact Eaton for additional information. C B SHORT 5 6 7 I sd (xIR) t R (s) IR∑ C B I sd (xIR) 4 3 REMOTE MM STATUS 4. Nominal Values (Pickup) (Tolerance is ±15%) 2.5 x In. 5. These curves are comprehensive for the complete family of KD Frame electronic breakers, including all frame sizes, ratings, and constructions. The total clearing times shown are conservative and consider the maximum response times of the trip unit, the circuit breaker opening, and the interruption of the current in the worst case conditions such as: maximum rated voltages, single-phase interruption, and minimum power factor. Faster clearing times are possible depending on the specific system conditions. t R (s) LONG 10 12 15 7 20 4 24 2 (ms) GND 300 .6 .8 1.0 .4 .3 I g (xIn) .2 GND M N O L K J R P Q * t sd / t g (ms) SHORT / GND Remote Maintenance Mode Trip 10 9 8 7 6 5 4 3 2 1 .9 .8 .7 .6 2.5 .5 TIME IN SECONDS .4 .3 .2 .1 .09 .08 .07 .06 Application determines end of curve .05 .04 .03 .02 50 30 40 20 7 8 9 10 5 6 4 3 2 .6 .7 .8 .9 1 .5 .01 Current in Multiples of Rating ( In ) Figure 9. Series C Types KD, CKD, HKD, CHKD, and KDC Circuit Breakers Equipped with Digitrip RMS 310+ Trip Units (250A and 400A), Remote Maintenance Mode Setting (250A and 400A) eaton www.eaton.com 11 Application Data AD29167K Effective April 2013 10,000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 2 HOUR S Circuit Breaker Time/Current Curves (Phase Current) 5,000 1 HOUR Series C® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units Catalog Types KES3125LS, KES3125LSG Digitrip RMS 310 Trip Units for use with Circuit Breaker Types KD, HKD, CKD, and CHKD, 125A. max. 3,000 Fixed Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 5 2 1,000 6 7 TEST 8 Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE Catalog Number 125 110 100 90 70 70, 90, 100, 125 Fixed Fixed Fixed Fixed Fixed Adjustable 1KES 125T 1KES 110T 1KES 100T 1KES 90T 1KES 70T A1KES 125T1 3X 2X 480V 600V 35 65 25 35 240V 380V 415V 65 100 40 65 40 65 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 20 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 10 Short Delay Pickup Settings (Tolerance ±10%) 4X 5 Short Delay Pickup Range Amperes 250–1000 220–880 200–800 180–720 140–560 140–1000 IEC 947-2 Breaker Type KD, CKD HKD, CHKD 50 30 3 derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). 8X See above tabulation. For ground fault time/current curve, see SC-5652-93. 6X 1 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere The end of the curve is determined by the interrupting rating of the circuit breaker. 5X 2 TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KD, CKD 65 HKD, CHKD 100 Long Delay Minimum Total Clearing Time 100 Ampere Rating (In) .5 7X .3 .2 .1 .1 .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve .01 .005 .003 .002 100,000 CURRENT IN AMPS 50,000 .001 40,000 20 30,000 6 7 8 9 10 20,000 5 10,000 4 5000 3 4000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 3000 .6 .7 .8 .9 1 2000 .5 1000 .001 Figure 10. Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3125LS, KES3125LSG 12 eaton www.eaton.com Application Data AD29167K Effective April 2013 10,000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 6 7 8 9 10 5 20 2 HOUR S Circuit Breaker Time/Current Curves (Phase Current) Series C ® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units 1 HOUR 5,000 Catalog Types KES3125LSI, KES3125LSIG Digitrip RMS 310 Trip Units for use with Circuit Breaker Types KD, HKD, CKD, and CHKD, 125A. max. 3,000 Adjustable Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 5 2 1,000 6 7 8 Time • ms 200 100 300 TEST INST Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE Catalog Number 125 110 100 90 70 70, 90, 100, 125 Fixed Fixed Fixed Fixed Fixed Adjustable 1KES 125T 1KES 110T 1KES 100T 1KES 90T 1KES 70T A1KES 125T1 Short Delay Pickup Range Amperes 250–1000 220–880 200–800 180–720 140–560 140–1000 480V 600V 35 65 25 35 IEC 947-2 Breaker Type KD, CKD HKD, CHKD 50 30 240V 380V 415V 65 100 40 65 40 65 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 2X 20 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 4X 10 Short Delay Pickup Settings (Tolerance ±10%) 6X 5 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 8X 2 For ground fault time/current curve, see SC-5652-93. 7X TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type 65 KD, CKD 100 HKD, CHKD Long Delay Minimum Total Clearing Time 100 Ampere Rating (In) 1 1 5X 3X .5 300 ms .3 200 ms .2 100 ms .1 .1 I .05 .05 .04 .03 .02 .02 SECONDS .03 .01 Fixed Instantaneous Override Interrupting Rating Determines End of Curve .01 .005 .003 CURRENT IN AMPS 50,000 .001 40,000 20 30,000 6 7 8 9 10 20,000 5 10,000 4 5000 3 4000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 3000 .6 .7 .8 .9 1 2000 .5 1000 .001 100,000 .002 Figure 11. Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3125LSI, KES3125LSIG eaton www.eaton.com 13 Application Data AD29167K Effective April 2013 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 Circuit Breaker Time/Current Curves (Phase Current) 2 HOUR S 10,000 Series C® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units 1 HOUR 5,000 Catalog Types KES3125LS, KES3125LSG Digitrip RMS 310 Trip Units for use with Circuit Breaker Types KDC, 125A. max. 3,000 Fixed Short Delay Time Typical Trip Unit Nameplate Short Delay Digitrip RMS 310 Rating Plug 2,000 Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 1,000 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE TEST Available Rating Plugs Ampere Rating (In) Type Catalog Number 125 110 100 90 70 70, 90, 100, 125 Fixed Fixed Fixed Fixed Fixed Adjustable 1KES 125T 1KES 110T 1KES 100T 1KES 90T 1KES 70T A1KS 125T1 Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KDC 200 Long Delay Minimum Total Clearing Time 100 6 7 8 Digitrip RMS 310 Trip Unit 40oC Remove 500 5 2 Short Delay Pickup Range Amperes 250–1000 220–880 200–800 180–720 140–560 140–1000 480V 100 600V 50 50 IEC 947-2 Breaker Type KDC 30 3X 2X 380V 415V 200 100 100 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 20 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 10 Short Delay Pickup Settings (Tolerance ±10%) 4X 5 240V 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A See above tabulation. For ground fault time/current curve, see SC-5652-93. 1 6X TIME IN SECONDS The end of the curve is determined by the interrupting rating of the circuit breaker. 8X 5X (Tolerance ±15%). 2 .5 7X .3 .2 .1 .1 .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve 600 Vac .01 480 Vac 240 Vac .005 .003 CURRENT IN AMPS 200,000 .001 100,000 20 50,000 6 7 8 9 10 40,000 5 30,000 4 20,000 3 10,000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 5000 .6 .7 .8 .9 1 4000 .5 3000 .001 2000 .002 Figure 12. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3125LS, KES3125LSG 14 eaton www.eaton.com Application Data AD29167K Effective April 2013 10,000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 2 HOUR S Circuit Breaker Time/Current Curves (Phase Current) Series C® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units 1 HOUR 5,000 Catalog Types KES3125LSI, KES3125LSIG Digitrip RMS 310 Trip Units for use with Circuit Breaker Type KDC, 125A. max. 3,000 Adjustable Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 5 2 1,000 6 7 8 Time • ms 200 100 300 TEST INST Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE Type Catalog Number 125 110 100 90 70 70, 90, 100, 125 Fixed Fixed Fixed Fixed Fixed Adjustable 1KES 125T 1KES 110T 1KES 100T 1KES 90T 1KES 70T A1KES 125T1 Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Long Delay Minimum Total Clearing Time 100 Ampere Rating (In) 240V 200 Type KDC 50 Short Delay Pickup Range Amperes 250–1000 220–880 200–800 180–720 140–560 140–1000 480V 100 600V 50 IEC 947-2 Breaker Type 240V 380V 415V KDC 200 100 100 30 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 2X 20 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. . 4X 10 Short Delay Pickup Settings (Tolerance ±10%) 6X 5 3 derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. 8X 2 For ground fault time/current curve, see SC-5652-93. 7X TIME IN SECONDS Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere 1 1 5X 3X .5 300 ms .3 200 ms .2 100 ms .1 .1 I .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve Maximum Interrupting Time 600 Vac .01 480 Vac 240 Vac .005 .003 .002 200,000 CURRENT IN AMPS 100,000 .001 50,000 20 40,000 6 7 8 9 10 30,000 5 20,000 4 10,000 3 5000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 4000 .6 .7 .8 .9 1 3000 .5 2000 .001 Figure 13. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3125LSI, KES3125LSIG eaton www.eaton.com 15 Application Data AD29167K Effective April 2013 500 175 200 225 250 150 125 100 75 50 25 GROUND CURRENT-AMPERES 10,000 2 HOURS Circuit Breaker Trip/Current Curves (Ground Current) 1 HOUR 5,000 Type Digitrip RMS 310 Trip Unit for use with Circuit Breaker Types KD, HKD, KDC, CKD, and CHKD For use with Trip Unit Catalog Numbers KES3125LSG KES3125LSIG 3,000 2,000 Digitrip RMS 310 Rating Plug Cat. Push to Trip In 1,000 Digitrip RMS 310 Rating Plug 300 Push to Trip Engaged 200 Remove Ground Fault Pickup • x Ir 6 7 3 2 5 5 6 7 8 Time • ms 300 150 500 TEST INST Ig = 25A Short Delay Pickup • x Ir 4 3 2 4 8 Digitrip RMS 310 Trip Unit 40oC Cat. In 5 2 Remove 500 Short Delay Pickup • x Ir 4 3 Engaged Ground Fault Time • ms 200 100 300 Pickup • x Ir 3 2 INST Digitrip RMS 310 Trip Unit 40oC 4 5 Time • ms 300 150 INST 500 TEST Ig = 25A Notes Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. 100 1 MINUTE Series C® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Units For Ground Fault Protection Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 50 For phase time/current curves, see SC-5642-93, SC-5643-93, SC-5648-93, or SC-5649-93. 30 20 4xIG 3xIG 10 5 3 Ground Fault Pickup Settings (Tolerance ±10% Except ±30% on 2xIG Setting) 5xIG 2xIG TIME IN SECONDS 2 1 500 ms .5 300 ms 150 ms .3 .2 .1 I .05 .03 .02 .01 .005 .003 .002 .001 1 2 3 4 5 6 7 8 9 10 GROUND CURRENT-IN MULTIPLES OF Ig = 25A 100 Figure 14. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Ground Fault Protection (KES3125LSG, KES3125LSIG) 16 eaton www.eaton.com Application Data AD29167K Effective April 2013 — OBSOLETE — .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 Circuit Breaker Time/Current Curves (Phase Current) 2 HOUR S 10,000 Series C ® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units 1 HOUR 5,000 Catalog Types KES3400LS, KES3400LSG Digitrip RMS 310 Trip Units for use with Circuit Breaker Types KD, HKD, CKD, and CHKD, 400A. max. 3,000 Fixed Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 5 2 1,000 6 7 TEST 8 Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time Catalog Number 400 350 300 250 225 200 200, 250, 300, 400 250, 300, 350, 400 Fixed Fixed Fixed Fixed Fixed Fixed Adjustable Adjustable 4KES 400T 4KES 350T 4KES 300T 4KES 250T 4KES 225T 4KES 200T A4KES 400T1 A4KES 400T3 Short Delay Pickup Range Amperes 800–3200 700–2800 600–2400 500–2000 450–1800 400–1600 400–3200 500–3200 480V 35 65 600V 25 35 IEC 947-2 240V 380V 415V KD, CKD HKD, CHKD 65 100 40 65 40 65 20 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication 4-1991. 3X Breaker Type 30 2X 1 MINUTE 50 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 10 Short Delay Pickup Settings (Tolerance ±10% ) 4X 5 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). 8X 5X 2 The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve, see SC-5650-93. 1 6X TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KD, CKD 65 HKD, CHKD 100 Long Delay Minimum Total Clearing ime T 100 Ampere Rating (In ) .5 7X .3 .2 .1 .1 .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve .01 .005 .003 .002 100,000 CURRENT IN AMPS 50,000 .001 40,000 20 30,000 6 7 8 9 10 20,000 5 10,000 4 5000 3 4000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 3000 .6 .7 .8 .9 1 2000 .5 1000 .001 Figure 15. Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3400LS, KES3400LSG eaton www.eaton.com 17 Application Data AD29167K Effective April 2013 — OBSOLETE — 10,000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 6 7 8 9 10 5 20 2 HOUR S Circuit Breaker Time/Current Curves (Phase Current) Series C ® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units 1 HOUR 5,000 Catalog Types KES3400LSI, KES3400LSIG Digitrip RMS 310 Units for use with Circuit Breaker Types KD, HKD, CKD, and CHKD, 400A. max. 3,000 Adjustable Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 1,000 300 200 Long Delay Maximum Total Clearing Total 50 200 100 INST 300 TEST RMS 310 Trip Unit Available Rating Plugs Ampere Rating (I n) Type Catalog Number 400 350 300 250 225 200 200, 250, 300, 400 250, 300, 350, 400 Fixed Fixed Fixed Fixed Fixed Fixed Adjustable Adjustable 4KES 400T 4KES 350T 4KES 300T 4KES 250T 4KES 225T 4KES 200T A4KES 400T1 A4KES 400T3 Short Delay Pickup Range Amperes 800–3200 700–2800 600–2400 500–2000 450–1800 400–1600 400–3200 500–3200 480V 600V 35 65 25 35 IEC 947-2 Breaker Type 240V 380V 415V 30 KD, CKD HKD, CHKD 65 100 40 65 40 65 20 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 2X 1 MINUTE 6 7 8 Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KD, CKD 65 HKD, CHKD 100 Long Delay Minimum Total Clearing Time 100 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 4X 10 Short Delay Pickup Settings (Tolerance ±10%) 6X 5 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). The end of the curve is determined by the interrupting rating of the circuit breaker. 8X 2 See above tabulation. For ground fault time/current curve, see SC-5650-93. 7X TIME IN SECONDS Digitrip 40oC Remove 500 5 2 Time • ms 1 1 .5 5X 3X .5 .4 300 ms .3 .3 200 ms .2 .2 100 ms .1 .1 I .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve .01 .005 .003 .002 100,000 CURRENT IN AMPS 50,000 .001 40,000 20 30,000 6 7 8 9 10 20,000 5 10,000 4 5000 3 4000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 3000 .6 .7 .8 .9 1 2000 .5 1000 .001 Figure 16. Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3400LSI, KES3400LSIG 18 eaton www.eaton.com Application Data AD29167K Effective April 2013 — OBSOLETE — .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 Circuit Breaker Time/Current Curves (Phase Current) 2 HOUR S 10,000 Series C ® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units 1 HOUR 5,000 Catalog Types KES3250LS, KES3250LSG Digitrip RMS 310 Units for use with Circuit Breaker Types KD, HKD, CKD, and CHKD, 250A. max. 3,000 Fixed Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 2 Engaged 1,000 5 6 7 TEST 8 Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE 50 Catalog Number 250 225 200 175 150 125 125, 150, 200, 250 Fixed Fixed Fixed Fixed Fixed Fixed Adjustabl e 2KES 250T 2KES 225T 2KES 200T 2KES 175T 2KES 150T 2KES 125T A2KES 250T1 10 600V 25 35 240V 380V 415V 65 100 40 65 40 65 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A 5X (Tolerance ±15%). 8X 2 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. Short Delay Pickup Settings (Tolerance ±10% ) 4X 5 480V 35 65 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 3X 2X 20 Short Delay Pickup Range Amperes 500–2000 450–1800 400–1600 350–1400 300–1200 250–1000 250–2000 IEC 947-2 Breaker Type KD, CKD HKD, CHKD 30 The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve, see SC-5651-93. 1 6X TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KD, CKD 65 HKD, CHKD 100 Long Delay Minimum Total Clearing Time 100 Ampere Rating (In) .5 7X .3 .2 .1 .1 .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve .01 .005 .003 .002 100,000 CURRENT IN AMPS 50,000 .001 40,000 20 30,000 6 7 8 9 10 20,000 5 10,000 4 5000 3 4000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 3000 .6 .7 .8 .9 1 2000 .5 1000 .001 Figure 17. Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3250LS, KES3250LSG eaton www.eaton.com 19 Application Data AD29167K Effective April 2013 — OBSOLETE — 10,000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 2 HOUR S Circuit Breaker Time/Current Curves (Phase Current) Series C® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units 1 HOUR 5,000 Catalog Types KES3250LSI, KES3250LSIG Digitrip RMS 310 Units for use with Circuit Breaker Types KD, HKD, CKD, and CHKD, 250A. max. 3,000 Adjustable Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 5 2 1,000 Time • ms 6 7 200 100 8 INST 300 TEST Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE 50 Catalog Number 250 225 200 175 150 125 125, 150, 200, 250 Fixed Fixed Fixed Fixed Fixed Fixed Adjustable 2KES 250T 2KES 225T 2KES 200T 2KES 175T 2KES 150T 2KES 125T A2KES 250T1 Short Delay Pickup Range Amperes 500–2000 450–1800 400–1600 350–1400 300–1200 250–1000 250–2000 480V 35 65 600V 25 35 IEC 947-2 Breaker Type KD, CKD HKD, CHKD 30 240V 380V 415V 65 100 40 65 40 65 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 2X 20 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. . 4X 10 Short Delay Pickup Settings (Tolerance ±10%) 6X 5 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC , refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). The end of the curve is determined by the interrupting rating of the circuit breaker. 8X 2 See above tabulation. For ground fault time/current curve, see SC-5651-93. 7X TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KD, CKD 65 HKD, CHKD 100 Long Delay Minimum Total Clearing Time 100 Ampere Rating (I n) 1 1 5X 3X .5 300 ms .3 200 ms .2 100 ms .1 .1 I .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve .01 .005 .003 .002 100,000 CURRENT IN AMPS 50,000 .001 40,000 20 20,000 6 7 8 9 10 30,000 5 10,000 4 5000 3 4000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 3000 .6 .7 .8 .9 1 2000 .5 1000 .001 Figure 18. Series C Types KD, CKD, HKD, CHKD Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3250LSI, KES3250LSIG 20 eaton www.eaton.com Application Data AD29167K Effective April 2013 — OBSOLETE — .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 Circuit Breaker Time/Current Curves (Phase Current) 2 HOUR S 10,000 Series C ® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units 1 HOUR 5,000 Catalog Types KES3400LS, KES3400LSG Digitrip RMS 310 Trip Units for use with Circuit Breaker Type KDC, 400A. max. 3,000 Fixed Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 1,000 5 2 6 7 TEST 8 Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE Catalog Number 400 350 300 250 225 200 200, 250, 300, 400 250, 300, 350, 400 Fixed Fixed Fixed Fixed Fixed Fixed Adjustable Adjustable 4KES 400T 4KES 350T 4KES 300T 4KES 250T 4KES 225T 4KES 200T A4KES 400T1 A4KES 400T3 Short Delay Pickup Range Amperes 800–3200 700–2800 600–2400 500–2000 450–1800 400–1600 400–3200 500–3200 480V 100 600V 50 50 IEC 947-2 Breaker Type KDC 30 3X 2X 380V 415V 200 100 100 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. . 10 Short Delay Pickup Settings (Tolerance ±10%) 4X 5 240V Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 20 2 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). The end of the curve is determined by the interrupting rating of the circuit breaker. 8X 5X 3 See above tabulation. For ground fault time/current curve, see SC-5650-93. 1 6X TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KDC 200 Long Delay Minimum Total Clearing Time 100 Ampere Rating (In) .5 7X .3 .2 .1 .1 .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Maximum Interrupting Time 600 Vac .01 480 Vac 240 Vac .005 .003 Interrupting Rating Determines End of Curve .002 200,000 CURRENT IN AMPS 100,000 .001 50,000 20 40,000 6 7 8 9 10 30,000 5 20,000 4 10,000 3 5000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 4000 .6 .7 .8 .9 1 3000 .5 2000 .001 Figure 19. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3400LS, KES3400LSG eaton www.eaton.com 21 Application Data AD29167K Effective April 2013 — OBSOLETE — 10,000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 2 HOUR S Circuit Breaker Time/Current Curves (Phase Current) 5,000 1 HOUR Series C ® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units Catalog Types KES3400LSI, KES3400LSIG, Digitrip RMS 310 Trip Units for use with Circuit Breaker Type KDC, 400A. max. 3,000 Adjustable Short Delay Time Typical Trip Unit Nameplate Short Delay Digitrip RMS 310 Rating Plug 2,000 Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 2 Engaged 1,000 5 6 7 8 Time • ms 200 100 INST 300 TEST Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE Catalog Number Short Delay Pickup Range Amperes 400 350 300 250 225 200 200, 250, 300, 400 250, 300, 350, 400 Fixed Fixed Fixed Fixed Fixed Fixed Adjustable Adjustable 4KES 400T 4KES 350T 4KES 300T 4KES 250T 4KES 225T 4KES 200T A4KES 400T1 A4KES 400T3 800–3200 700–2800 600–2400 500–2000 450–1800 400–1600 400–3200 500–3200 Type KDC 50 240V 480V 600V 200 100 50 IEC 947-2 Breaker Type KDC 30 240V 380V 415V 200 100 100 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 2X 20 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. . 4X 10 Short Delay Pickup Settings (Tolerance ±10%) 6X 5 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). The end of the curve is determined by the interrupting rating of the circuit breaker. 8X 2 See above tabulation. For ground fault time/current curve, see SC-5650-93. 7X TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Long Delay Minimum Total Clearing Time 100 Ampere Rating (In) 1 1 5X 3X .5 300 ms .3 200 ms .2 100 ms .1 .1 I .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve Maximum Interrupting Time me 600 Vac .01 480 Vac 240 Vac .005 .003 .002 200,000 CURRENT IN AMPS 100,000 .001 50,000 20 40,000 6 7 8 9 10 20,000 5 30,000 4 10,000 3 5000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 4000 .6 .7 .8 .9 1 3000 .5 2000 .001 Figure 20. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3400LSI, KES3400LSIG 22 eaton www.eaton.com Application Data AD29167K Effective April 2013 — OBSOLETE — 10,000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 2 HOUR S Circuit Breaker Time/Current Curves (Phase Current) 5,000 1 HOUR Series C® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units Catalog Types KES3250LS, KES3250LSG Digitrip RMS 310 Units for use with Circuit Breaker Type KDC, 250A. max. 3,000 Fixed Short Delay Time Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Short Delay Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 5 2 1,000 6 7 TEST 8 Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE Catalog Number 250 225 200 175 150 125 125, 150, 200, 250 Fixed Fixed Fixed Fixed Fixed Fixed Adjustable 2KES 250T 2KES 225T 2KES 200T 2KES 175T 2KES 150T 2KES 125T A2KES 250T1 Short Delay Pickup Range Amperes 500–2000 450–1800 400–1600 350–1400 300–1200 250–1000 250–2000 480V 600V 100 50 50 IEC 947-2 Breaker Type KDC 30 3X 2X 380V 415V 200 100 100 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. . 10 Short Delay Pickup Settings (Tolerance ±10%) 4X 5 240V Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 20 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). 8X 5X 2 The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. For ground fault time/current curve, see SC-5651-93. 1 6X TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KDC 200 Long Delay Minimum Total Clearing Time 100 Ampere Rating (In) .5 7X .3 .2 .1 .1 .05 .05 Fixed Instantaneous Override .04 .03 .02 SECONDS .03 .02 .01 Interrupting Rating Determines End of Curve 600 Vac .01 480 Vac 240 Vac .005 .003 CURRENT IN AMPS 200,000 .001 100,000 20 50,000 6 7 8 9 10 40,000 5 30,000 4 20,000 3 10,000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 5000 .6 .7 .8 .9 1 4000 .5 3000 .001 2000 .002 Figure 21. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3250LS, KES3250LSG eaton www.eaton.com 23 Application Data AD29167K Effective April 2013 — OBSOLETE — 10,000 .5 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 2 HOUR S Circuit Breaker Time/Current Curves (Phase Current) Series C K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Units 5,000 1 HOUR ® Catalog Types KES3250LSI, KES3250LSIG Digitrip RMS 310 Trip Units for use with Circuit Breaker Type KDC, 250A. max. 3,000 Adjustable Short Delay Time Typical Trip Unit Nameplate Short Delay Digitrip RMS 310 Rating Plug 2,000 Pickup •x Ir Cat. Standard Fixed Rating Plug Push to Trip In 4 3 Engaged 5 2 1,000 Time • ms 6 7 200 100 8 INST 300 TEST Digitrip RMS 310 Trip Unit 40oC Remove Available Rating Plugs 500 300 200 Long Delay Maximum Total Clearing Time 1 MINUTE 50 30 Catalog Number 250 225 200 175 150 125 125, 150, 200, 250 Fixed Fixed Fixed Fixed Fixed Fixed Adjustable 2KES 250T 2KES 225T 2KES 200T 2KES 175T 2KES 150T 2KES 125T A2KES 250T1 Short Delay Pickup Range Amperes 500–2000 450–1800 400–1600 350–1400 300–1200 250–1000 250–2000 480V 100 600V 50 IEC 947-2 Breaker Type 240V 380V 415V KDC 200 100 100 Notes Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 2X 20 There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. . 4X 10 Short Delay Pickup Settings (Tolerance ±10%) 6X 5 3 Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. For high fault current levels, a fixed instantaneous override is provided at 4000A (Tolerance ±15%). The end of the curve is determined by the interrupting rating of the circuit breaker. 8X 2 See above tabulation. For ground fault time/current curve, see SC-5651-93. 7X TIME IN SECONDS Type Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker 240V Type KDC 200 Long Delay Minimum Total Clearing Time 100 Ampere Rating (In) 1 1 5X 3X .5 300 ms .3 200 ms .2 100 ms .1 .1 I .05 .05 Fixed Instantaneous Override .04 .03 .02 .02 SECONDS .03 .01 Interrupting Rating Determines End of Curve Maximum Interrupting Time 600 Vac .01 480 Vac 240 Vac .005 .003 200,000 .001 100,000 20 50,000 6 7 8 9 10 40,000 5 30,000 4 20,000 3 10,000 2 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In ) 5000 .6 .7 .8 .9 1 4000 .5 3000 .001 2000 .002 CURRENT IN AMPS Figure 22. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Types KES3250LSI, KES3250LSIG 24 eaton www.eaton.com Application Data AD29167K Effective April 2013 560 640 720 800 480 400 320 240 80 160 GROUND CURRENT-AMPERES 10,000 8000 — OBSOLETE — 2 HOUR S Circuit Breaker Trip/Current Curves (Ground Current) 5,000 1 HOUR Series C® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units For Ground Fault Protection Type Digitrip RMS 310 Trip Unit for use with Circuit Breaker Types KD, HKD, KDC, CKD, and CHKD For use with Trip Unit Catalog Numbers KES3400LSG KES3400LSIG 3,000 2,000 Digitrip RMS 310 Rating Plug Cat. Push to Trip In 1,000 4 3 Engaged Cat. 300 Push to Trip Engaged 200 Remove Ground Fault Pickup •x Ig 6 7 3 2 8 4 3 5 2 Digitrip 40oC 5 200 100 8 INST 500 TEST INST Ground Fault Time • ms 6 7 Time • ms 300 150 Ig = 80A Short Delay Pickup •x Ir 4 1 Digitrip RMS 310 Trip Unit 40oC Digitrip RMS 310 Rating Plug In 5 2 Remove 500 Short Delay Pickup •x Ir 300 RMS 310 Trip Unit Pickup •x Ig 3 2 1 4 5 Time • ms 300 150 INST 500 TEST Ig = 80A Notes Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. 1 MINUTE 100 Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. For phase time/current curves, see SC-5638-93, SC-5639-93, SC-5644-93, or 50 SC-5645-93. 30 1xIG 20 4xIG 3xIG 10 5 3 2xIG Ground Fault Pickup Settings (Tolerance ±10% Except ±20% on 1xI G Setting) 5xIG TIME IN SECONDS 2 1 500 ms .5 300 ms .3 .2 150 ms .1 I .05 .03 .02 .01 .005 .003 .002 .001 1 2 3 4 5 6 7 8 9 10 GROUND CURRENT-IN MULTIPLES OF Ig = 80A 100 Figure 23. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Ground Fault Protection (KES3400LSG, KES3400LSIG) eaton www.eaton.com 25 Application Data AD29167K Effective April 2013 350 400 450 500 300 250 200 150 50 100 GROUND CURRENT-AMPERES 10,000 5000 — OBSOLETE — 2 HOUR S Circuit Breaker Time/Current Curves (Ground Current) Series C® K-Frame Circuit Breakers Equipped With Type KES Digitrip RMS 310 Trip Units For Ground Fault Protection 1 HOUR 5,000 Type Digitrip RMS 310 Trip Unit for use with Circuit Breaker Types KD, HKD, KDC, CKD, and CHKD For use with Trip Unit Catalog Numbers KES3250LSG KES3250LSIG 3,000 2,000 Digitrip RMS 310 Rating Plug Cat. Push to Trip In 1,000 4 3 2 Engaged Cat. Push to rTip 300 Engaged 200 Remove 6 7 8 3 2 1 Pickup •x Ir 4 3 2 5 6 7 8 5 Time • ms 300 150 INST 500 TEST Ig = 50A Ground Fault Time • ms 200 100 4 300 INST Digitrip RMS 310 Trip Unit 40oC Pickup •x Ig 3 2 1 4 5 Time • ms 300 150 INST 500 TEST Ig = 50A Notes Curve accuracy applies from –20ºC to +55ºC ambient. For possible continuous ampere derating for ambient above 40ºC, refer to Eaton. 100 1 MINUTE Ground Fault Pickup •x Ig Short Delay Digitrip RMS 310 Rating Plug In 5 Digitrip RMS 310 Trip Unit 40oC Remove 500 Short Delay Pickup •x Ir Digitrip RMS 310 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. For phase time/current curves, see SC-5640-93, SC-5641-93, SC-5646-93, or 50 SC-5647-93. 30 1xIG 20 4xIG 3xIG 10 5 3 2xIG Ground Fault Pickup Settings (Tolerance ±10% Except ±20% on 1xIG Setting) 5xIG TIME IN SECONDS 2 1 500 ms .5 300 ms .3 .2 150 ms .1 I .05 .03 .02 .01 .005 .003 .002 .001 1 2 3 4 5 6 7 8 910 GROUND CURRENT-IN MULTIPLES OF Ig = 50A 100 Figure 24. Series C Type KDC Circuit Breakers Equipped with Type KES Digitrip RMS 310 Trip Units, Ground Fault Protection (KES3250LSG, KES3250LSIG) 26 eaton www.eaton.com Application Data AD29167K Effective April 2013 eaton www.eaton.com 27 Application Data AD29167K Effective April 2013 Eaton 1000 Eaton Boulevard Cleveland, OH 44114 United States Eaton.com © 2013 Eaton All Rights Reserved Printed in USA Publication No. AD29167K / Z13590 April 2013 Eaton is a registered trademark. All other trademarks are property of their respective owners.