CURRENT LIMITING LIGHTING CONTROL PANEL Supplemental

advertisement
D1.15.0.LA
Project:
CURRENT LIMITING
LIGHTING CONTROL PANEL
Supplemental Overcurrent Protection
City of Los Angeles Approved Version
Fixture Type:
Location:
Contact/Phone:
PRODUCT DESCRIPTION
The Juno Trac-Master® Current Limiting Lighting Control Panel is THE solution for complying
with stringent energy codes like ASHRAE 90.1 and California Title 24. Typically for track
lighting, it is defined as a sub-branch circuit current limiter designed to limit available wattage to lighting circuits, to only that necessary to meet the lighting design criteria. The TracMaster panel employs supplementary current limiting protectors configured specifically for
the lighting design in the space. Rather than lighting loads being calculated by the greater of
maximum fixture wattage ratings or an arbitrary watts per foot multiplier, the
Trac-Master panel enables calculations to instead be made based on the rating of the
supplementary protector. Because it limits a circuit not the lighting equipment itself, the
Trac-Master Lighting Control Panel provides maximum flexibility to accommodate frequent
lighting design modifications and layout changes, especially typical for retail spaces.
PRODUCT SPECIFICATIONS
Features Designed to be installed between the branch circuit breaker and the lighting equipment • Not intended to be used
as a branch circuit protective device • Factory pre-assembled and customized • No programming required.
Construction Heavy-duty 16 gauge die formed steel enclosure • Hinged door with key-locking latch • Removable front panel with
factory labeled breaker wiring data simplifies installation • Ample quantity of combination ( 1/2”, 3/4”, 1” ) knockouts provide maximum installation flexibility for top, bottom and side conduit connections • Precision 35mm DIN rail mounting secures breakers in
place • Includes ample ground terminals for all circuits • Mini panel accommodates 1 to 12 circuits, standard panel accommodates
6 to 21 circuits and large panel accommodates 22 to 42 circuits • Mini panel available in surface mount configuration only
• Standard and large available in surface mount or flush mount configurations.
Finish Durable powder coat paint • Industrial gray color standard.
Supplementary Protectors Single pole supplementary protectors • Rated for 120/277VAC operation • Available in individual
amperage ratings including 0.5A, 1A, 2A, 3A, 4A, 5A, 6A, 7A, 8A, 10A, 13A and 15A, selected based on actual lighting loads
• Protectors should be loaded to a maximum of 80% of rating to avoid nuisance tripping • Wiring installs directly into protector
terminal • Color-coded ON/OFF indicator clearly identifies status • Easily resettable in an accessible location in the event of an
overcurrent situation • UL 1077, CSA 22.2, IEC 60947-2 approved.
Labels UL Listed • cUL Listed • City of Los Angeles Approved • Approved by the California Energy Commission to meet the requirements of Title 24 • Complies with ASHRAE 90.1.
Warranty Product is warranted against defects in material and workmanship for a period of 3 years.
Product specifications subject to change without notice.
ORDERING INFORMATION
Supplementary Protector ratings are determined by the electrical layout drawings. A submittal package will be provided by Juno for
approval following receipt of order and single line drawings. Supplementary Protector ratings and position are not required to be
specified as part of the catalog number. Specifications assistance is available thru local Juno Lighting Group sales representatives or
by contacting Juno Lighting Group Technical Services at (888) 387-2212.
Ordering Examples: CLS10M, CLS16, CLS21F
CLS
Series
Number of Circuits per Panel
CLS = Trac-Master Current Limiting Lighting
Control Panel
REV-10/12
6-21 for Standard Panel
22-42 for Large Panel
1-12 for Mini Panel
Panel Style
Blank = Standard Panel (6-21 circuits)
or Large Panel (22-42 circuits)
M = Mini Panel (1-12 circuits)
Mounting Style
Blank = Surface Mount
F = Flush Mount (Standard or Large Panel Only)
D1.15.0.LA
CURRENT LIMITING LIGHTING CONTROL PANEL
6"
DIMENSIONS
MINI 1-12 CIRCUIT PANEL - SURFACE MOUNT
9 1/16"
3 1/8"
12 3/4"
3 15/16"
1300 S. Wolf Road • Des Plaines, IL 60018 • Phone (847) 827-9880 • Fax (847) 827-2925
220 Chrysler Drive • Brampton, Ontario • Canada L6S 6B6 • Phone (905) 792-7335 • Fax (905) 792-0064
Visit us at www.junolightinggroup.com
Printed in U.S.A. ©2016 Acuity Brands Lighting, Inc.
D1.15.0.LA
CURRENT LIMITING LIGHTING CONTROL PANEL
DIMENSIONS
STANDARD 6-21 CIRCUIT PANEL - SURFACE MOUNT
STANDARD 6-21 CIRCUIT PANEL - FLUSH MOUNT
15 7/16"
14 1/4"
19 1/8"
17 7/8"
3 13/16"
3 13/16"
LARGE 22-42 CIRCUIT PANEL - SURFACE MOUNT
LARGE 22-42 CIRCUIT PANEL - FLUSH MOUNT
15 7/16"
14 1/2"
33 13/16"
35 1/8"
3 13/16"
3 13/16"
1300 S. Wolf Road • Des Plaines, IL 60018 • Phone (847) 827-9880 • Fax (847) 827-2925
220 Chrysler Drive • Brampton, Ontario • Canada L6S 6B6 • Phone (905) 792-7335 • Fax (905) 792-0064
Visit us at www.junolightinggroup.com
Printed in U.S.A. ©2016 Acuity Brands Lighting, Inc.
D1.15.0.LA
CURRENT LIMITING LIGHTING CONTROL PANEL
MOUNTING TEMPLATE
MINI 1-12 CIRCUIT PANEL MOUNTING TEMPLATE
6"
3 1/8"
STANDARD 6-21 CIRCUIT PANEL MOUNTING TEMPLATE
LARGE 22-42 CIRCUIT PANEL MOUNTING TEMPLATE
5 1/2"
5 1/2"
15"
30 7/8"
1300 S. Wolf Road • Des Plaines, IL 60018 • Phone (847) 827-9880 • Fax (847) 827-2925
220 Chrysler Drive • Brampton, Ontario • Canada L6S 6B6 • Phone (905) 792-7335 • Fax (905) 792-0064
Visit us at www.junolightinggroup.com
Printed in U.S.A. ©2016 Acuity Brands Lighting, Inc.
D1.15.0.LA
CURRENT LIMITING LIGHTING CONTROL PANEL
APPLICATION
Energy codes typically calculate track lighting loads based on linear feet of installed track. Some codes use a multiplier as low as
30 watts/foot while others use a multiplier as high as 70 watts/foot. When using the energy efficient lighting technologies available today, the connected load is typically much less than the per-foot multipliers used by most energy codes. This penalizes lighting
designs that employ track lighting and wastes available lighting watts that could be used more effectively.
Below is a typical track lighting example. The Standard Layout consists of 100’ runs of single circuit track with 32 CMH track
heads, each using 39W lamps, for a total connected load of 1440W. The Revised Layout Using Short Track Segments has the same
1440W connected load but uses sixteen short 4’ track segments (64’), each fed separately, to help minimize the impact of the watts
per foot multiplier. The scenario with the Trac-Master Current Limiting Control Panel uses the original 100’ of single circuit track, with
each monitored by a 4-Amp current limiting supplementary protector that is closely matched to the actual connected load of 1440W
plus a small buffer. This results in the minimum calculated watts per the energy codes.
1. Standard Layout without the Trac-Master Control Panel
2. Revised Layout Using Short Track Segments
The Trac-Master Panel installs between the branch circuit breaker and the track lighting, solving the energy code calculation
discrepancy, making the wattage calculation independent of track length.
3. Standard Layout with the Trac-Master Control Panel
1300 S. Wolf Road • Des Plaines, IL 60018 • Phone (847) 827-9880 • Fax (847) 827-2925
220 Chrysler Drive • Brampton, Ontario • Canada L6S 6B6 • Phone (905) 792-7335 • Fax (905) 792-0064
Visit us at www.junolightinggroup.com
Printed in U.S.A. ©2016 Acuity Brands Lighting, Inc.