52729 - Honeywell Power Products

advertisement
Honeywell
12 Clintonville Road
Northford, CT 06472
http://www.honeywellpower.com
HRB610
Multi-Voltage Control Relay
PN 52729:A1 05/08/2009 ECN 09-029
Product Installation Document
1 Overview
The HRB610 Multi-voltage Control relays offer SPDT 10 amp resistive contacts which may be operated by one of four
input control voltages. A single relay may be energized from a voltage source of 12 VDC or 12 VAC by wiring to the
input terminals. A single relay may also be energized for 24 VDC or 24 VAC operation by cutting a resistor.
Each relay position contains a red LED which indicates the relay coil is energized. Relays may be ‘snapped apart’ from
the standard six module assembly and used independently. These devices are ideal for applications where local contacts
are required for system status, remote contacts for control of electrical loads, and general purpose switching. They are
suitable for access control, energy/building management, and lighting control systems.
2 Features and Specifications
• Power Requirements: 12/24 VAC/VDC @ 50 mA coil draw per module position.
• Coil input is diode polarized to allow reverse polarity control.
• One red LED per module position.
• Resistive Load: 10 A @ 120 VAC/28 VDC, 7 A @ 230 VAC.
• Contact Construction: Dry Form “C” SPDT per module position.
• Ambient Temperature: 32°F to 120°F (0°C to 49°C) @ 95% RH (@32°C); Non condensing/Non freezing.
• Wiring: Solid or stranded #12 to #22 AWG terminals.
• Product Dimensions: 2.0”L x 1.6”W x 1.0”D (individual module).
• Single relay modules may be ‘snapped apart’ from a standard six position master and used separately.
• Six pieces of foam tape included for installation.
• Snap Track (optional) to mount 2 relays that have been vertically left intact.
3 Installation Instructions
1.
In order to break the relay cluster apart (optional), put a pencil on a flat surface, position the scoring line on top
of the pencil and push lightly. Relay should break away from cluster easily.
2.
Mount relay(s) using foam tape included or Snap Track (optional) to desired location.
3.
Connect trigger input or voltage source to screw terminals marked +/AC and -/N.
4.
Connect screw terminals marked NC (normally closed), NO (normally open) and C (common) to operate desired
devices.
Continued on next page...
4 Wiring and Application Diagrams
WIRING EXAMPLE
J1
RELAY ENERGIZED LED ON
NC
NO COM
SPDT CONTACT
10A @ 120VAC / 28VDC,
7A @ 230VAC
CUT J1 FOR 24V
+AC
-N
(+)
(-)
12VDC @ 50mA, 24VDC @ 50mA
AC
N
12VAC @ 50mA, 24VAC @ 50mA
J1
APPLICATION EXAMPLE
WHEN RELAY COIL ENERGIZES,
‘NC’ CONTACTS ARE SWITCHED
TO OPEN POSITION, REMOVE
POWER TO TURN OFF LOAD
LOAD
POWER
SOURCE
NC
+AC
-N
NO COM
+AC
-N
LOAD
+AC
-N
RELAY
POWER
SUPPLY
NOTE: For additional information
2
•
Visit our website http://www.honeywellpower.com
•
Contact Technical Support (877) HPP-POWR
•
E-mail us at hpp_techserv@honeywell.com
HRB610 Installation Document P/N 52729:A1 05/08/2009