IL01207006E Instruction Leaflet for LG-Frame Circuit Breakers and Motor Circuit Protectors A 1 Warning DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING. 3.438 OFF 2 LINE [87,33 ] 1.719 [43,66 ] #10-32 TAP. .860 [ 21,84 ] 2.396 BREAKER HANDLE [ 60,86mm] 1.198 4.733 [ 120,22 ] [ 30,43mm ] 5.577 [141,66 ] 1.905 8.437 [ 214,3 ] BREAKER HANDLE 10.125 [48,39mm ] BREAKER HANDLE [ 257,18] 1.642 [41,71mm] 3.224 [ 81,89mm] BREAKER HANDLE 2.670 5.480 [ 139,19 ] (3 POLE) 7.219 [183,36 ] (4 POLE) LOAD Effective February 2009 5.309 [67,82mm ] [134,85mm] 2.750 [ 69,85 ] (3 POLE) 7.059 [ 179,3mm] (4 POLE) IL01207006E Mounting 3 Operation 5 25 in-lb (3 N.m) Use 110mm screw (long) on line end and 100mm screw (short) on load end. Connections 200 in-lb (22 N.m) 4 For wire seal applications ONLY 8mm Terminal Shield Required for TA631L, T631L, TA632L, T632L Effective : 2/09 200 in-lb (22 N.m) Page 2 IL01207006E 1. LED - This LED idicates an overload condition is present. It will light if the continuous current is 85% of the Ie Setting for a 38 second duration. 2. Ie-Continuous Current Setting. Continuous Current Values for each lettered setting are indicated by the chart shown at the left. Please select the value closest to the Motor Nameplate Full Load Current (FLA). The circuit breaker will trip when the current exceeds 115% of the Ie Continuous Current Setting. A "Thermal Memory" effect prevents the breaker from being re-energized. 1 3. Trip Class The trip class switch has two sets of four settings: 4 Settings J-M are without phase unbalance detection J - Trip Class 10 K - Trip Class 15 L - Trip Class 20 M - Trip Class 30 3 TEST / ALARM Solid State Motor Protection Trip Unit IEC 60947-4 Im = 12 x Ie Ie I UL 508 CSA 22.2 No.14 Trip Amps: 115% FLA STATUS * Overload Trip Class No Phase Unbalance J=10 K=15 L=20 M=30 Phase Unbalance N=10 O=15 P=20 Q=30 * FLA ( Ie) Class D E F M N O C G L P B H K Q A J 2 Effective : 2/09 68C 4577 H05 Push to Trip Settings N-Q are with phase unbalance detection N - Trip Class 10 O - Trip Class 15 P - Trip Class 20 Q - Trip Class 30 4. Status LED A green Status light indicates that the Circuit Breaker is operational. The status light will blink on and off once each second as long as the load current exceeds approximately 20% of the maximum current rating (Ie) of the breaker. Page 3 Eaton Corporation Cutler-Hammer business unit 1000 Cherrington parkway Moon Township, PA 15108-4312 USA tel: 1-800-525-2000 www.cutler-hammer.com ©2001 Eaton Corporation All Rights Reserved Printed USA Publication No. IL01207006EH02 Effective: 2/09