L-Frame: LG MPCB Instructions

IL01207006E
Instruction Leaflet for LG-Frame Circuit Breakers
and Motor Circuit Protectors
A
1
Warning
DO NOT ATTEMPT TO INSTALL OR
PERFORM MAINTENANCE ON
EQUIPMENT WHILE IT IS ENERGIZED. DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM
CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO
VOLTAGE IS PRESENT BEFORE
PROCEEDING.
3.438
OFF
2
LINE
[87,33 ]
1.719
[43,66 ]
#10-32 TAP.
.860
[ 21,84 ]
2.396
BREAKER HANDLE
[ 60,86mm]
1.198
4.733
[ 120,22 ]
[ 30,43mm ]
5.577
[141,66 ]
1.905
8.437
[ 214,3 ]
BREAKER HANDLE
10.125
[48,39mm ]
BREAKER HANDLE
[ 257,18]
1.642
[41,71mm]
3.224
[ 81,89mm]
BREAKER HANDLE
2.670
5.480
[ 139,19 ]
(3 POLE)
7.219
[183,36 ]
(4 POLE)
LOAD
Effective February 2009
5.309
[67,82mm ]
[134,85mm]
2.750
[ 69,85 ]
(3 POLE)
7.059
[ 179,3mm]
(4 POLE)
IL01207006E
Mounting
3
Operation
5
25 in-lb
(3 N.m)
Use
110mm screw
(long) on line
end and 100mm
screw (short)
on load end.
Connections
200 in-lb
(22 N.m)
4
For wire seal
applications
ONLY
8mm
Terminal Shield
Required for
TA631L, T631L,
TA632L, T632L
Effective : 2/09
200 in-lb
(22 N.m)
Page 2
IL01207006E
1. LED - This LED idicates an overload
condition is present. It will light if the
continuous current is 85% of the Ie Setting
for a 38 second duration.
2. Ie-Continuous Current Setting. Continuous
Current Values for each lettered setting are
indicated by the chart shown at the left.
Please select the value closest to the
Motor Nameplate Full Load Current (FLA).
The circuit breaker will trip when the current
exceeds 115% of the Ie Continuous Current
Setting. A "Thermal Memory" effect prevents
the breaker from being re-energized.
1
3. Trip Class
The trip class switch has two sets of four
settings:
4
Settings J-M are without phase unbalance detection
J - Trip Class 10
K - Trip Class 15
L - Trip Class 20
M - Trip Class 30
3
TEST /
ALARM
Solid State Motor Protection Trip Unit
IEC 60947-4
Im = 12 x Ie
Ie
I
UL 508
CSA 22.2 No.14 Trip Amps: 115% FLA
STATUS
*
Overload Trip Class
No Phase Unbalance
J=10 K=15 L=20 M=30
Phase Unbalance
N=10 O=15 P=20 Q=30
*
FLA ( Ie)
Class
D E F
M N O
C
G L
P
B
H K
Q
A
J
2
Effective : 2/09
68C 4577 H05
Push to Trip
Settings N-Q are with phase unbalance detection
N - Trip Class 10
O - Trip Class 15
P - Trip Class 20
Q - Trip Class 30
4. Status LED
A green Status light indicates that the Circuit
Breaker is operational. The status light will blink
on and off once each second as long as the
load current exceeds approximately 20% of
the maximum current rating (Ie) of the breaker.