Detailed Specifications

advertisement
GE Molded Case Circuit Breakers
J600 Line Circuit Breakers
125-600 Amperes
600 Volts ac
250 Volts dc
Type TJ J Noninterchangeable Trip (Includes Line and Load Lugs)
Suitable for reverse feed.
Adjustable
Trip
125
150
175
200
225
250
300
350
400
Lugs
Type TJK
400NA
2-Pole. 400 Amp Frame
600 Vac, 250 Vdc
Amp
Ampere
Rating
Lo
Hi
375
1250
1500
1750
450
525
600
675
750
900
1050
1200
2000
2250
2500
3000
3500
4000
-
-
Catalog Number
TJJ426125WL
TJJ426150WL
TJJ426175WL
TJJ426200WL
TJJ426225WL
TJJ4262SOWL
TJJ426300WL
TJJ426350WL
TJJ426400WL
-
TJJ426Y400O®
3-Pole, 400 Amp Frame
600 Volts ac
List
Price,
GO-135B
$2118.00
2118.00
2118.00
2118.00
2118.00
2118.00
2118.00
2118.00
2118.00
Catalog Number
TJJ436125WL
TJJ436150WL
TJJ436175WL
TJJ436200WL
TJJ436225WL
TJJ436250WL
TJJ436300WL
TJJ436350WL
TJJ436400WL
1577.00
Copper/
Lugs
List
Price,
GO-135B
$2573.00
2573.00
2573.00
2573.00
2573.00
2573.00
2573.00
2573.00
2573.00
TJJ436Y400S)®
Included
in price
(1)6-600 kcmil
(2)2/0-250 kcmil
1904.00
Types TJK, THJK Interchangeable Trip
Adjustable
Trip Range
Amp
Complete Circuit Breaker
Includes line and load lugs
Ampere
Rating
Standard
Lo
Hi
Catalog Number
Frame Only
Hi-Break"
List
Price,
GO-135B
Catalog Number
List
Price,
GO-135B
$2116.00
2118.00
2118.00
2118.00
2118.00
2118.00
2118.00
2118.00
2118.00
THJK426125WL
THJK426150WL
THJK426175WL
THJK426200WL
THJK426225WL
THJK426250WL
THJK426300WL
THJK426350WL
THJK426400WL
$3085.00
3085.00
3085.00
3085.00
3085.00
3085.00
3085.00
3085.00
3085.00
List
Price,
GO-13SB
Catalog Number
Term nal Lugs for Front
Connection
(Cof per/Aluminum) ®
Trip Unit Only
' Use with
Standard and
Hi-Break Frames
List
Price,
GO-135B
Catalog Number
(Order 2 per
Pole)
List
Price,
GO-135B
Wire Size
400 Amp Frame
Two-Pole
125
150
175
200
225
250
300
350
400
.
400NA
375
450
525
600
675
750
900
1050
1200
2000
2250
2500
3000
3500
4000
TJK426125WL
TJK426150WL
TJK426175WL
TJK426200WL •
TJK426225WL
TJK426250WL
TJK426300WL
TJK426350WL
TJK426400WL
-
-
TJK426Y4000®
1874.00
TJK436125WL
TJK436150WL
TJK436175WL
TJK436200WL
TJK436225WL
TJK436250WL
TJK436300WL
TJK436350WL
TJK436400WL
2573.00
2573.00
2573.00
2573.00
2573.00
2573.00
2573.00
2573.00
2573.00
1250
1500
1750
-
TJK426FOOO
Standard
Frame
$ 1598.00
THJK426FOOO
Hi-Break
2565.00
TJK426T125
TJK426T150
TJK426T175
TJK426T200
TJK426T225
TJK426T250
TJK426T300
TJK426T350
TJK426T400
$464.00
464.00
464.00
464.00
464.00
464.00
464.00
464.00
464.00
TJKY3®
212.00
TJK436T125
TJK436T150
TJK436T175
TJK436T200
TJK436T225
TJK436T250
TJK436T300
TJK436T350
TJK436T400
464.00
464.00
464.00
464.00
464.00
464.00
464.00
464.00
464.00
-
TJK436TM1400®
TJK436TM2400®
TJK436TM3400®
558.00
558.00
558.00
-
TJKY3®
212.00
-
0)
6-600 kcmil
or Twin
2/0-250
TCAL43®
$ 14.00
TCAL43®
14.00
(1)
6-600 kcmil
or Twin
2/0-250 kcmil
TCAL43®
14.00
(1)
6-600 kcmil
or Twin
2/0-250 kcmil
Three-Pole
125
150
175
200
225
250
300
350
400
375
450
525
600
675
750
900
1050
1200
2000
2250
2500
3000
3500
4000
400A
600
1200
350
2000
4000
1000
-
-
Mag
Only
400NA
1250
1500
1750
—
TJK436Y400® @
—
2330.00
THJK436125WL
THJK436150WL
THJK436175WL
THJK436200WL
THJK436225WL
THJK436250WL
THJK436300WL
THJK436350WL
THJK436400WL
3675.00
3675.00
3675.00
3675.00
3675.00
3675.00
3675.00
3675.00
3675.00'
—
-
TJK436FOOO
Standard
Frame
2025.00
THJK436FOOO
Hi-Break
Frame
3127.00
600 Amp Frame
Two-Pote
250
300
350
400
750
900
1050
1200
2500
3000
3500
4000
TJK626250WL
TJK626300WL
TJK626350WL
TJK626400WL
2812.00
2812.00
2812.00
2812.00
THJK626250WL
THJK626300WL
THJK626350WL
THJK626400WL
3704.00
3704.00
3704.00
3704.00
TJK626FOOO
Standard
Frame
1535.00
450
500
600
1350
1500
1800
4500
5000
6000
TJK626450WL
TJK626500WL
TJK626600WL
2848.00
2848.00
2848.00
THJK626450WL
THJK626500WL
THJK626600WL
3740.00
3740.00
3740.00
THJK626FOOO
Hi-Break
Frame
2427.00
-
-
TJK626Y600O®
1844.00
600NA
-
TJK626T250
TJK626T300
TJK626T350
TJK626T400
1221.00
1221.00
1221.00
1221.00
TJK626T450
TJK626T500
TJK626T600
1221.00
1221.00
1221.00
212.00
TJKY36®
-
Twin 4/0-350
kcmil-Cu
or Twin '
300-500
kcmil-AI
Three-Pole
TJK636T250
TJK636T300
TJK636T350
TJK636T400
1221.00
1221.00
1221.00
1221.00
TJK636T45D
TJK636T500
TJK636T600
1221.00
1221.00
1221.00
=
TJK636TM1600®
TJK636TM2600®
1465.00
1465.00
-
TJKY36®
250
300
350
400
750
900
1050
1200
2500
3000
3500
4000
TJK636250WL
TJK636300WL
TJK636350WL
TJK636400WL
3539.00
3539.00
3539.00
3539.00
THJK636250WL
THJK636300WL
THJK636350WL
THJK636400WL
4457.00
4457.00
4457.00
4457.00
450
500
600
1350
1500
1800
4500
5000
6000
TJK636450WL
TJK636500WL
TJK636600WL
3593.00
3593.00
3593.00
THJK636450WL
THJK636500WL
THJK636600WL
4511.00
4511.00
4511.00
600
1800
2000
6000
.
-
-
-
-
2595.00
-
600A
Mag
Only
600NA
I
-
TJK636Y600CD®
© Molded-case switch includes
line and load lugs.
TJK636FOOO
Standard
.Frame
2234.00
THJK636FOOO
Hi-Break
Frame
3152.00
Internal accessory installation
requires dummy trip unit. See
page 4-51 for additional
details. Nonautomatic trip unit
and dummy trip unit not UL
listed for field installation.
Alternate lug for 750 kcmil
Cu/AI cable, Catalog Number
TCAL47 List Price $26.00,
GO-135B.
0 Not UL listed.
For optional lugs, see page
TCAL43O
14.00
0)
6-600 kcmil
or Twin
2/0-250 kcmil
TCAL63
23.00
Twin 4/0-350
kcmii-Cu or
Twin 300-500
kcmil-AI
212.00
Accessories:
See pages 4-48 to 4-65.
4-62.
Prices and data subject to change without notice
1999 Issue
4-23
GF Molded Case Circuit Breakers
Molded Case Circuit Breakers
,
Spectra RMS™, Spectra RMS™ with MicroVersaTrip Plus™ Trip Units, Spectra RMS™ with
MicroVersaTrip PM™ Trip Units, Thermal Magnetic and J/K with MicroVersaTrip® HMS-9 and
Power+™ 4 Trip Units
How to Order
QLine
• Thermal Magnetic Circuit Breakers
• Molded-Case Switches
The catalog number as shown in the following pages includes the
complete breaker or switch. TQD and TJD breakers are complete
with Cu/AI line and load lugs.
Spectra RMS™
• Circuit Breakers
Determine the required breaker frame, 1C rating, and load
requirements. Select frame, trip unit (rating plug), and lug, if
required, catalog numbers from the tables on pages 4-18 and
4-19. Select field-mounted internal accessory catalog numbers,
if required, on page 4-47. Select field-mounted external
accessory catalog numbers, if required, on pages 4-48 through
4-65. Order as separate items. For Spectra breakers with
MicroVersaTrip Plus Trip Units or MicroVersaTrip PM Trip Units
refer to page 4-26 through 4-35.
• Mag-Break Motor Circuit Protectors
Determine the required frame and ampere requirements.
Select frame, trip unit (rating plug), and lug, if required, catalog
numbers from the table on page 4-42. Select accessories as
noted above for circuit breakers. The same accessories are
used with both circuit breakers and motor circuit protectors.
Order as separate items.
• Molded-Case Switches
Determine the required frame and ampere requirements.
Select frame and lug, if required, catalog numbers from the table
on page 4-20. Rating plugs are not used. Select accessories as
noted above for circuit breakers. Internal accessories do not
require dummy trips. The same accessories are used with both
circuit breakers and molded-case switches. Order as separate
items.
Unless otherwise noted, all circuit breakers are UL listed in File E-11592.
Molded-case switches are UL listed in File E-57546. Field-Installable
Internal Accessories are UL listed in File E-57253. Distribution Cable
Accessories for MicroVersaTrip Plus Trip Units and MicroVersaTrip PM Trip
Units are UL listed in File E-57253.
E150 Line
Thermal Magnetic Circuit Breakers
Magnetic Circuit Breakers
Molded-Case Switches
The catalog numbers as shown in the following pages include the
complete breaker or switch. All devices listed come with Cu/AI line
and load lugs. If line lugs are not required on a breaker, eliminate
"WL" from catalog number; for molded-case switches see page
4-3. Unless otherwise noted, all circuit breakers are UL listed in
File E-11592. Molded-case switches are UL listed in File E-57546.
Molded-case switches can also be ordered as complete units
(designated TFK—Y) or as separate components. They are UL
listed only as complete units. To indicate required lugs, see
page 4-3.
Unless otherwise noted, all circuit breakers are UL listed in File
E-11592. Molded-case switches are UL listed in File E-57546.
J 600 Line
• Thermal Magnetic Circuit Breakers
• Magnetic Circuit Breakers
• Molded-Case Switches
These breakers are available with either noninterchangeable trip
(designated Type TJJ) or interchangeable trip (designated Type
TJK and THJK). Type TJJ catalog numbers include frame, trip,
Cu/AI line, and load lugs factory assembled. If line lugs are not
required on the breaker, eliminate "WL" from catalog number, and
subtract price of line lugs from price of complete breaker.
TJK breakers are available in two frames, 400 ampere frame
(125 to 400 amperes) and 600 ampere frame (250 to 600
• .
amperes). Trip units are not interchangeable between frames.
"Complete Circuit Breaker" price includes frame, trip unit, Cu/AI
line, and load lugs. Unit will be shipped unassembled unless order
specifies "must be factory assembled." If line lugs are not
required, eliminate "WL" from catalog number and subtract price
of line lugs from price of complete breaker.
To order the frame, trip, and lugs separately, select the required
components from table. Magnetic breakers must be ordered as
components. A complete breaker consists of frame, trip, and one
line and one load lug per pole.
Price of ordering "Complete Circuit Breaker" vs. frame, trip, and
line and load lugs separately is the same.
Molded-case switches can also be ordered as complete units
(designated Type TJK—Y) or as separate components. They are
UL listed only as complete units. To indicate required lugs, see
page 4-3.
F 225 Line
• Thermal Magnetic Circuit Breakers
• Magnetic Circuit Breakers
• Molded-Case Switches
These breakers are available with either noninterchangeable trips
(designated Type TFJ) or interchangeable trips (designated Types
TFK/THFK). When ordering Type TFJ, catalog number includes
4-2
complete breaker, trip unit, Cu/AI line and load lugs factory
assembled. If line lugs are not required on a breaker, eliminate
"WL" from catalog number, and subtract price of line lugs from
price of complete breaker. If interchangeable trip (Types TFK/
THFK) is required order one of two ways. "Complete circuit
breaker" price includes frame, trip, Cu/AI line and load lugs. Units
will be shipped unassembled unless specified on order "must be
factory assembled." If line lugs are not required on a breaker,
eliminate "WL" from catalog number, and subtract price of line
lugs from price of complete breaker. To order the frame, trip, and
lugs separately, select the required components from table.
Magnetic breakers must be ordered as components. A complete
breaker consists of frame, trip unit, one line lug per pole and one
load lug per pole. Price of "Complete Circuit Breaker" vs. ordering
frame, trip, and line and load lugs separately is the same.
Unless otherwise noted, all circuit breakers are UL listed in File
E-11592. Molded-case switches are UL listed in File E-57546.
1999 Issue
(continued on next page)
Data subject to change without notice
GE Molded Case Circuit Breakers
Molded Case Circuit Breakers
K1200 Line
• Thermal Magnetic Circuit Breakers
• Magnetic Breakers
• Molded-Case Switches
These breakers are available only with interchangeable trip units.
Two frame sizes are available, the 800 ampere frame (300 to 800
amperes) and the 1200 ampere frame (600 to 1200 amperes). Trip
units are not interchangeable between frames.
"Complete Circuit Breaker" price includes frame, trip, Cu/AI line,
and load lugs. Units will be shipped unassembled unless specified
"must be factory assembled." If line lugs are not required on the
breaker, eliminate "WL" from catalog number and subtract price
of line lugs.
To order the frame, trip, and lugs separately, select the required
components from table. Magnetic circuit breakers must be
ordered as components. A complete breaker consists of frame,
trip and one line and one load lug per pole. Price of ordering
"Complete Circuit Breaker" vs. frame, trip, and line and load lugs
separately is the same.
Molded-case switches can also be ordered as complete units
(designated Type TKMA—Y) or as separate components. They
are UL listed only as complete units. To indicate required lugs,
see the table below.
These breakers are available in four types. Type TB1 (15-100
amperes) catalog numbers include frame, trip, line and load lugs,
and current limiters all factory assembled. Types TB4 (125 to 400
amperes), TB6 (300 to 600 amperes) and TB8 (600 to 800 amperes)
include frame, trip and limiters, factory assembled, but do not
include line or load lugs. If line and load lugs are required, order
separately. Unless otherwise noted, TB1, TB4, TB6, and TB8
breaker components are UL listed in File E-42263. Fused
molded-case switches are UL listed in File E-57546.
Mag-Break9 Line
• Magnetic only circuit breakers (motor circuit protectors)
These breakers are available only with noninterchangeable
adjustable magnetic trip, in frame Types E, F, J, K, and Tri-Break.
All breakers are shipped factory assembled, complete with Cu/AI
line and load lugs.
All magnetic only circuit breakers and limiters are UL Component
Recognized in Files E-11592 and E-66390, respectively, unless
otherwise noted.
Accessories
Order accessories from the appropriate table:
Thermal Magnetic Circuit Breakers, Magnetic Circuit Breakers, and
Molded-Case Switches®—pages 4-48 to 4-65.
MicroVersaTrip RMS-9 or 4-function Solid-State Circuit Breakers— .
pages 4-48 to 4-65.
x Unless otherwise noted, all circuit breakers are UL listed in File
E-11592. Molded-case switches are UL listed in File E-57546.
© Installation of accessories in molded-case switches requires dummy
trip; see page 4-51 for information. Dummy trip not required for
Tri-Break or Q Line molded-case switches.
R Frame—1000/1600/2000 Amp Molded-Case Circuit Breakers
• Solid-state MicroVersaTrip Plus™ or MicroVersaTrip PM™
Trip Unit
• Interchangeable trip unit via rating plugs
• 65 and 100 kA ratings available
• Standard and 100% rated versions
• Uses standard Power Break* accessories
• Stationary/manual only
Spectra RMS™ Breakers—pages 4-47 to 4-65.
Spectra RMS™ Breakers with MicroVersaTrip Plus™ Trip Units or
MicroVersaTrip PM™ Trip Units—pages 4-32 to 4-35 and 4-47 to 4-65.
Current Limiting Circuit Breakers
• 150, 225, 400 and 600 ampere frame sizes
• UL listed interrupting ratings are 200 kA at 240 and 480 volts ac
maximum and 50 kA at 600 volts ac maximum
• Thermal magnetic construction
Molded-Case Circuit Breaker and Switch
Terminal Configuration Code
Order standard Cu/AI lugs by using suffix codes presented. Order lugs
separately if special lugs are required. For optional lugs, see page 4-62.
Suffix
Breaker/Switch
Type
Circuit Breakers with MicroVersaTrip' Trip Units
• Solid-state construction with MicroVersaTrip RMS-9 digital rms
sensing microprocessor trip units.
• Available in J and K frame construction with ampere ratings from
60-1200A.
For ordering information see pages 4-36 through 4-41. UL listed,
File E-11592. All breakers are UL listed in File E-11592.
TQD/TJD
Molded Case
Breakers,
Thermal
Magnetic
Molded
Case
Switch
Spectra RMS™
Breakers
J.K.
MicroVersaTrip"
Breakers
Mine Duty™
Breakers
Mag- Break*
Breakers
Tri-Break' Line
• Integrally Fused Thermal Magnetic Circuit Breakers
• Integrally Fused Magnetic Circuit Breakers
• Integrally Fused Molded-Case Switches
Blank
Load
Lugs
Only
Load
Lugs
Only
Line and
Load
Lugs
No
Lugs
WL
XL
X2
LL
-
Line
Lugs
Only
No
Lugs
Line and
Load Lugs
-
Line
Lugs
Only
No
Lugs
-
No
Lugs
Line
Lugs
Only
Load
Lugs
Only
Line and
Load Lugs
Order Lugs Separately
No
Lugs
No
Lugs
Line and
Load Lugs
Order Lugs Separately
Order Lugs Separately
-
-
-
—
For E 150 circuit breakers suffix XL is used to specify "no lugs".
Data subject to change without notice
1999 Issue
4-3
pi
N
II
GE Molded Case Circuit Breakers
Molded Case Circuit Breakers
t. VERTICAL
Quick Reference Guide
Ratings do not apply to molded-case switches.
TJJ, TJK, THJK
TFJ, TFK, THFK
E150 (UL File E-11592; Fixed Thermal Magnetic Trip Unit; CSA LR 57114)
Circuit
Breaker
Type
Ampere
Rating
Poles
1
TEY®
15-100
UL Listed Interrupting Ratings—
rms Symmetrical Amps (In Thousands)
ac Voltage
do Voltage
Maximum
Voltage Rating
No.
ac
do
120
277
125
65
2
250
120/240
1
10-100
9>
10-100
TED®
THED®
TEL®
125
250
3
—
1
277,347®
125
480
250
14
65
14
10
—
-
500
15-30
1
277,347®
125
—
15-100
2
480
250
65
10
18
18
65
480,600
—
65
-
—
500®
—
—
10
10
—
—
—
—
-
100
100
5
—
—
—
—
10
—
65
W
A
B
c
E
3'/18
-
-
-
-
3%
24'/64
2'%4
D
5'/4
2
3
26 lb/24
1%
65/ie
2%'
%2
4Vfr
"/16
1%
__
23/4
3%
Z"A>
20®
25
-
10
10
41*
—
—
1%
20®
—
28 lb/8
26 lb/24
23
21%4
/32
24lb/12
'/16
28 lb/8
26 lb/24
——
24lb/12
65/16
41/a
10
24 lb/1 2
s
1
—
Approx.
Ship Wt./
Std. Pack
1
6^16
10
18
-
H
—
—
—
25
-
42
-
250
10
14
15-100
600
14
-
600
3
-
10
3
-15-150
-
125
5
-
10-150
3
600
—
—
2
'
480
-
15-100
110-150
Jlte^
120
2
277
14
-
3
TEB®
240
Dimensions
(In.)
3%
2"/tn
1s
2 /64
"/,6
2
%2
28 lb/8
-
-
5
6 /ie
4'/B
ytte
27/16
2'%2
11
/16
3Vz lb/1
2
%2
"225 (UL File E-11592; TFJ, Fixed Thermal Magnetic Trip Unit; TFK, THFK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)
Circuit
Breaker
Type
TFJ®
Ampere
Rating
70-225
70-250
TFK®
70-225
THFK®
70-225
TFL®
70-225
No.
Poles
2
UL Listed Interrupting Ratings —
rms Symmetrical Amps (In Thousands)
ac Voltage
dc Voltage
Maximum
Voltage Rating
ac
dc
480
250
3
600
500
2
480
250
3
600
—
2
480
250
3
600
—
3
600
-
120
120/240
240
277
480
22
25
125
600
—
22
65
-
100
100
25
-
65
250
500®
10
—
H
10'/8
18
25
Dimensions
(in.)
10®
10
_
10
—
18
—
—
—
20®
_
18
—
—
-
-
-
25
W
41*
D
3'Vie
Approx.
Ship Wt./
Std. Pack
A
B
C
E
3%
3'/B
"/16
1 3 /16
10 lb/1
•
12 lb/1
101*
4%
31yi«
10 lb/1
3%
3%
"/,e
1*i6
7
"/16
1Vie
11
1*ie
12 lb/1
10 lb/1
10'/B
41*
3^18
3 /6
3%
101*
'41*
3«/16
3%
3%
/16
12 lb/1
-
J600 (UL File E-11592; TJJ, Fixed Thermal Magnetic Trip Unit; TJK, THJK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)
TJK4
250-600
THJK4
250-600
2
250
3
500
2
600
500
2
250
3
—
2
600
3
20
250
3
10
22
42
30
65
250
35
—
17'/2lb/1
10
—
20®
20
40
—
—
—
40
—
-
_
81/4
3 15 /16
18 lb/1
3^16
20 lb/1
1%
16 lb/1
1*6
17Vzlb/1
18 lb/1
3'3/16
-
16lb/1
3%
' 20®
3«/16
20 lb/1
K1200 (UL File E-11592; Interchangeable Thermal Magnetic Trip Unit; CSA LR 40350)
TKM8
2
600
3
TKM12
250
.22
42
10
—
20 <D
22
33 lb/1
5"/16
5'/2
500
39 lb/1
2
1%
3
THKM12
2
250
3
—
65
35
40®
—
—
—
8'/4
2
%
%
5/2
SQ/IB
1%
3
UL listed with poles in series
for 500 Vdc ungrounded
battery applications.
© All UL listed as HACR type.
® 10 amp not UL listed.
Data subject to change without notice
® UL listed/CSA Certified for
10kA @ 347 Vac (TED) and
18kA@ 347V (THED). Also
rated 10kA @ 480V but not
UL listed.
© UL listed at 10,000 amps.
® Discontinued
© Also 10,000 amps at 500 Volts
dc. Not UL listed.
1999 Issue
38 lb/1
41VMW1
33 lb/1
39 lb/1
38 lb/1
41 14 lb/1
500 Vdc on TJJ only.
(continued on page 4-8)
4-7