Short circuit calculations Purpose of Short-Circuit Calculations – Dimensioning of switching devices – Dynamic dimensioning of switchgear – Thermal rating of electrical devices (e.g. cables) – Protection coordination – Fault diagnostic – Input data for – Earthing studies – Interference calculations – EMC planning – ….. Short-Circuit Calculation Standards – IEC 60909: Short-Circuit Current Calculation in Three-Phase A.C. Systems • European Standard EN 60909 » German National Standard DIN VDE 0102 » further National Standards • Engineering Recommendation G74 (UK) Procedure to Meet the Requirements of IEC 60909 for the Calculation of Short-Circuit Currents in Three-Phase AC Power Systems – ANSI IIEEE Std. C37.5 (US) IEEE Guide for Calculation of Fault Currents for Application of a.c. High Voltage Circuit Breakers Rated on a Total Current Basis. Short-Circuit Calculations Scope of IEC 60909 – – – – three-phase a.c. systems low voltage and high voltage systems up to 500 kV nominal frequency of 50 Hz and 60 Hz balanced and unbalanced short circuits – three phase short circuits – two phase short circuits (with and without earth connection) – single phase line-to-earth short circuits in systems with solidly earthed or impedance earthed neutral – two separate simultaneous single-phase line-to-earth short circuits in a systems with isolated neutral or a resonance earthed neutral (IEC 60909-3) – maximum short circuit currents – minimum short circuit currents Short-Circuit Calculations Types of Short Circuits 3-phase 2-phase 1-phase Copyright © Siemens AG 2007. All rights reserved. Variation of short circuit current shapes fault at voltage peak fault located in the network fault located near generator fault at voltage zero crossing Short-Circuit Calculations Far-from-generator short circuit Ik” ip Ik A Initial symmetrical short-circuit current Peak short-circuit current Steady-state short-circuit current Initial value of the d.c component Short-Circuit Calculations Definitions according IEC 60909 (I) • initial symmetrical short-circuit current Ik” • r.m.s. value of the a.c. symmetrical component of a prospective (available) short-circuit current, applicable at the instant of short circuit if the impedance remains at zero-time value • initial symmetrical short-circuit power Sk” • fictitious value determined as a product of the initial symmetrical short-circuit current Ik”, the nominal system voltage Un and the S" factor 3 √3: U I" k • n k NOTE: Sk” is often used to calculate the internal impedance of a network feeder at the connection point. In this 2 case the definition given should be used in the following form: c Un Z Sk" Short-Circuit Calculations Definitions according IEC 60909 (II) • decaying (aperiodic) component id.c. of short-circuit current • mean value between the top and bottom envelope of a shortcircuit current decaying from an initial value to zero • peak short-circuit current ip • maximum possible instantaneous value of the prospective (available) short-circuit current • NOTE: The magnitude of the peak short-circuit current varies in accordance with the moment at which the short circuit occurs. Short-Circuit Calculations Near-to-generator short circuit Ik” ip Ik A IB Initial symmetrical short-circuit current Peak short-circuit current Steady-state short-circuit current Initial value of the d.c component Symmetrical short-circuit breaking current 2 2 IB tB Short-Circuit Calculations Definitions according IEC 60909 (III) • steady-state short-circuit current Ik • r.m.s. value of the short-circuit current which remains after the decay of the transient phenomena • symmetrical short-circuit breaking current Ib • r.m.s. value of an integral cycle of the symmetrical a.c. component of the prospective short-circuit current at the instant of contact separation of the first pole to open of a switching device Short-Circuit Calculations Purpose of Short-Circuit Values Design Criterion Physical Effect Relevant short-circuit current Breaking capacity of circuit breakers Thermal stress to arcing chamber; arc extinction Symmetrical short-circuit breaking current Ib Mechanical stress to equipment Forces to electrical devices (e.g. bus bars, cables…) Peak short-circuit current ip Thermal stress to equipment Temperature rise of electrical Initial symmetrical shortdevices (e.g. cables) circuit current Ik” Fault duration Selective detection of partial Minimum symmetrical shortshort-circuit currents circuit current Ik Protection setting Earthing, Interference, EMC Potential rise; Magnetic fields Maximum initial symmetrical short-circuit current Ik” Equivalent Voltage Source Short-circuit Equivalent voltage source at the shortcircuit location real network Q A F equivalent circuit ZN Q ZT A ZL ~ I"K c.U n 3 Operational data and the passive load of consumers are neglected Tap-changer position of transformers is dispensable Excitation of generators is dispensable Load flow (local and time) is dispensable Short circuit in meshed grid Equivalent voltage source at the short-circuit location • real network equivalent circuit Voltage Factor c • c is a safety factor to consider the following effects: • • • • voltage variations depending on time and place, changing of transformer taps, neglecting loads and capacitances by calculations, the subtransient behaviour of generators and motors. Voltage factor c for calculation of Nominal voltage maximum short circuit currents minimum short circuit currents -systems with a tolerance of 6% 1.05 0.95 -systems with a tolerance of 10% 1.10 0.95 Medium voltage >1 kV – 35 kV 1.10 1.00 High voltage >35 kV 1.10 1.00 Low voltage 100 V – 1000 V Short Circuit Impedances and Correction Factors Short Circuit Impedances • For network feeders, transformer, overhead lines, cable etc. • impedance of positive sequence system = impedance of negative sequence system • impedance of zero sequence system usually different • topology can be different for zero sequence system • Correction factors for – generators, – generator blocks, – network transformer • factors are valid in zero, positive, negative sequence system Network feeders • At a feeder connection point usually one of the following values is given: – the initial symmetrical short circuit current Ik” – the initial short-circuit power Sk” c U n c U n2 ZN " " Sk 3 Ik XN • ZN 1 (R / X )2 If R/X of the network feeder is unknown, one of the following values can be used: – R/X = 0.1 – R/X = 0.0 for high voltage systems >35 kV fed by overhead lines Network transformer Correction of Impedance ZTK = ZT KT – general c max K T 0,95 1 0,6 x T – at known conditions of operation KT c max Un Ub 1 x T (IbT IrT ) sinbT • no correction for impedances between star point and ground Network transformer Impact of Correction Factor 1.05 1.00 KT 0.95 0.90 cmax = 1.10 cmax = 1.05 0.85 0.80 0 5 10 15 20 xT [%] • The Correction factor is KT<1.0 for transformers with xT >7.5 %. Reduction of transformer impedance Increase of short-circuit currents Generator with direct Connection to Network Correction of Impedance ZGK = ZG KG – general KG c max Un UrG 1 xd sinrG – for continuous operation above rated voltage: UrG (1+pG) instead of UrG • turbine generator: X(2) = X(1) • salient pole generator: X(2) = 1/2 (Xd" + Xq") Generator Block (Power Station) Correction of Impedance 2 ZS(O) = (tr ZG +ZTHV) KS(O) Q G – power station with on-load tap changer: 2 2 UnQ c max UrTLV KS 2 2 UrG UrTHV 1 xd x T sinrG – power station without on-load tap changers: K SO UnQ c max U rTLV 1 p t UrG (1 pG ) UrTHV 1 xd sinrG Asynchronous Motors • Motors contribute to the short circuit currents and have to be considered for calculation of maximum short circuit currents 2 1 UrM ZM ILR / IrM SrM XM • ZM 1 (RM / XM )2 If R/X is unknown, the following values can be used: – R/X = 0.1 medium voltage motors power per pole pair > 1 MW – R/X = 0.15 medium voltage motors power per pole pair ≤ 1 MW – R/X = 0.42 low voltage motors (including connection cables) Special Regulations for low Voltage Motors – low voltage motors can be neglected if ∑IrM ≤ Ik” – groups of motors can be combined to a equivalent motor – ILR/IrM = 5 can be used Calculation of initial short circuit current Calculation of initial short circuit current Procedure – Set up equivalent circuit in symmetrical components – Consider fault conditions – in 3-phase system – transformation into symmetrical components – Calculation of fault currents – in symmetrical components – transformation into 3-phase system Calculation of initial short circuit current Equivalent circuit in symmetrical components (1) (0) (1) (1) (1) (2) (2) (2) (2) (1) (1) (1) positive sequence system (2) negative sequence system (1) (2) (2) (2) (0) (0) (0) (0) (0) (0) (0) zero sequence system Copyright © Siemens AG 2007. All rights reserved. Calculation of initial short circuit current 3-phase short circuit L1-L2-L3-system Z(1)l L1 L2 L3 ~ ~ ~ -Uf 012-system ~ ~ ~ I sc3 c Ur 3 Z (1) Z(1)r c Un 3 (1) Z(2)l Z(2)r ~ ~ (2) Z(0)l Z(0)r ~ ~ (0) UL1 = – Uf UL2 = a2 (– Uf) UL3 = a (– Uf) network left of fault location fault location U(1) = – Uf U(2) = 0 U(0) = 0 network right of fault location Calculation of 2-phase initial short circuit current L1-L2-L3-system Z(1)l 012-system ~ L1 L3 ~ c U r I sc2 Z 1 Z 2 -Uf I sc2 ~ ~ L2 c U r 2 Z 1 I sc2 3 I sc3 2 U c n 3 IL1 = 0 U (1) U ( 2) IL2 = – IL3 I(0) = 0 UL3 – UL2 = – Uf I(1) = – I(2) Z(1)r c Un (1) 3 Z(2)l Z(2)r ~ ~ (2) Z(0)l Z(0)r ~ ~ (0) network left of fault location fault location network right of fault location Calculation of 2-phase initial short circuit current with ground connection L1-L2-L3-system Z(1)l 012-system Z(1)r ~ L1 ~ ~ L2 c Un (1) 3 L3 ~ I scE2E -Uf 3 c U r Z 1 2Z 0 Z(2)l Z(2)r ~ ~ (2) Z(0)l Z(0)r ~ ~ (0) I L1 0 U L2 a c 2 U L3 a c Un 3 Un 3 network left of fault location U (1) U ( 2) c fault location Un 3 network right of fault location U (1) U (0) I(0) = I(1) = I(2) Calculation of 1-phase initial short circuit current L1-L2-L3-System Z(1)l 012-System Z(1)r ~ ~ (1) L1 L2 L3 ~ " I sc1 -Uf 3 c U r Z (1) Z ( 2) Z ( 0) Z(2)l Z(2)r ~ ~ c Un 3 (2) ~ Z(0)l Z(0)r ~ ~ (0) U L1 c IL2 = 0 IL3 = 0 Un 3 network left of fault location fault location U (0) U (1) U ( 2) c I(0) = I(1) = I(2) network right of fault location Un 3 Short Circuit Calculation Results Faults at all Buses Short Circuit Calculation Results Contribution for one Fault Location Example Data of sample calculation • Network feeder: • 110 kV • 3 GVA • R/X = 0.1 Transformer: Overhead line: 110 / 20 kV 40 MVA uk = 15 % PkrT = 100 kVA 20 kV 10 km R1’ = 0.3 Ω / km X1’ = 0.4 Ω / km Impedance of Network feeder c Un2 ZI Sk" 1.1 20 kV ZI 3 GVA 2 ZI 0.1467 RI 0.0146 XI 0.1460 Impedance of Transformer Un2 Z T uk Sn Z T 0.15 20 kV 2 40 MVA ZT 1.5000 Un2 R T PkrT 2 Sn 20 kV 2 RT 100 kVA 40MVA 2 RT 0.0250 XT 1.4998 Impedance of Transformer Correction Factor K T 0.95 c max 1 0.6 x T K T 0.95 1.1 1 0.6 0.14998 K T 0.95873 ZTK 1.4381 RTK 0.0240 XTK 1.4379 Impedance of Overhead Line RL R' XL X' RL 0.3 / km 10 km XL 0.4 / km 10 km RL 3.0000 XI 4.0000 Initial Short-Circuit Current – Fault location 1 R RI RTK X XI XTK R 0.0146 0.0240 X 0.1460 1.4379 R 0.0386 X 1.5839 Ik" Ik" c Un 3 R1 j X1 1.1 20 kV 3 0.03862 1.58392 Ik" 8.0 kA Initial Short-Circuit Current – Fault location 2 R RI RTK RL X XI XTK XL R 0.0146 0.0240 3.0000 X 0.1460 1.4379 4.0000 R 3.0386 X 5.5839 Ik" Ik" c Un 3 R1 j X1 1.1 20 kV 3 3.0386 2 5.58392 Ik" 2.0 kA Peak current Peak Short-Circuit Current Calculation acc. IEC 60909 • maximum possible instantaneous value of expected short " i 2 I circuit current p k 1.02 0.98 e3R / X • equation for calculation: Peak Short-Circuit Current Calculation in non-meshed Networks • The peak short-circuit current ip at a short-circuit location, fed from sources which are not meshed with one another is the sum of the partial short-circuit currents: M G M ip1 ip2 ip3 ip = ip1 + ip2 + ip3 + ip4 ip4 Peak Short-Circuit Current Calculation in meshed Networks • Method A: uniform ratio R/X – smallest value of all network branches – quite inexact • Method B: ratio R/X at the fault location – factor b from relation R/X at the fault location (equation or diagram) – =1,15 b • Method C: procedure with substitute frequency – factor from relation Rc/Xc with substitute frequency fc = 20 Hz R Rc fc – X Xc f – best results for meshed networks Peak Short-Circuit Current Fictitious Resistance of Generator – RGf = 0,05 Xd" for generators with UrG > 1 kV and SrG 100 MVA – RGf = 0,07 Xd" for generators with UrG > 1 kV and SrG < 100 MVA – RGf = 0,15 Xd" for generators with UrG 1000 V NOTE: Only for calculation of peak short circuit current Peak Short-Circuit Current – Fault location 1 Ik" 8.0 kA R 0.0386 X 1.5839 R / X 0.0244 1.02 0.98 e3R / X 1.93 ip 2 Ik" ip 21.8 kA Peak Short-Circuit Current – Fault location 2 Ik" 2.0 kA R 3.0386 X 5.5839 R / X 0.5442 1.02 0.98 e3R / X 1.21 ip 2 Ik" ip 3.4 kA Breaking Current Breaking Current Differentiation • Differentiation between short circuits ”near“ or “far“ from generator • Definition short circuit ”near“ to generator • for at least one synchronous machine is: Ik” > 2 ∙ Ir,Generator or • Ik”with motor > 1.05 ∙ Ik”without motor • Breaking current Ib for short circuit “far“ from generator Ib = Ik” Breaking Current Calculation in non-meshed Networks • The breaking current IB at a short-circuit location, fed from sources which are not meshed is the sum of the partial short-circuit currents: M G M IB1 = μ∙I“k IB2 = I“k IB3 = μ∙q∙I“k IB = IB1 + IB2 + IB3 + IB4 IB4 = μ∙q∙I“k Breaking current Decay Current fed from Generators IB =of μ ∙ I“ k Factor μ to consider the decay of short circuit current fed from generators. Breaking current Decay fed from Asynchronous Motors IB =of μ ∙Current q ∙ I“k Factor q to consider the decay of short circuit current fed from asynchronous motors. Breaking Current Calculation in meshed Networks • Simplified calculation: I b = I k” • For increased accuracy can be used: U"Mj U"Gi " " Ib I (1 i ) IkGi (1 jq j ) IkMj i c Un / 3 j c Un / 3 " k UGi jX"diK IkGi " • • • " " UMj jXMj IkMj " " X“diK subtransient reactance of the synchronous machine (i) X“Mj reactance of the asynchronous motors (j) I“kGi , I“kMj contribution to initial symmetrical short-circuit current from the synchronous machines (i) asynchronous motors (j) as measured at the machine terminals and the Continuous short circuit current Continuous short circuit current Ik r.m.s. value of short circuit current after decay of all transient effects depending on type and excitation of generators statement in standard only for single fed short circuit calculation by factors (similar to breaking current) Continuous short circuit current is normally not calculated by network calculation programs. For short circuits far from generator and as worst case estimation Ik = I”k