CXX SERIES COMPAC ®Thermoplastic LED Exit erx 7010.5

advertisement
Type: __________________________
Voltage: ________________________
CODES AND STANDARDS
UL Listed to Standard 924.
NFPA 101 (Life Safety Code)
NFPA 70 (NEC)
VOLTAGE INPUT
120/277 VAC selectable input.
FINISH
Units are available in white or black finishes.
Also available in black housing with
aluminum color face plate.
HOUSING
Low profile, snap-together quick mount
design. Flame rated, UV stable ABS ther moplastic housing.
INSTALLATION
Universal mounting (wall, ceiling or end—
canopy provided). Canopy not required for
flat wall mount (electronics contained inside
housing). Optional pendant accessories available. Pop-out chevron directional indicators
are easily removed when required. Exit sign
mounts up to a standard 4" square
outlet box.
LAMPS
Bright red or green energy efficient LED
lamps. Uniform 6" letter illumination (3/4"
stroke).
BATTERY/ELECTRONICS
Maintenance-free nicad battery. Standard
emergency electronics provide a state-of-theart self-test/self-diagnostic circuit. Features
an exclusive system that aids in correcting
wiring mistakes by checking power and
wiring before applying a load to system components. All emergency units have built-in
circuitry protection/low-voltage battery disconnect and transformer isolation. Solid state
charger, test switch and green LED AC status
indicator, along with three red fault indicators.
CXX SERIES COMPAC® Thermoplastic LED Exit
Job Name: ______________________
CATALOG NUMBER (Example: CXXL1RW)
NUMBER
OF FACES
FAMILY
PANEL COLOR
HOUSING
COLOR
OPTIONS
B
CXL - LED (AC only)
CXXL - LED Emergency with
Xtest Diagnostics
(Nicad Battery)
1 - Single Face
3 - Universal (includes
extra stencil face plate)
R - Red
G - Green
Footnotes:
1
For use with AC only exits.
2
For use with Emergency exits.
3
Not to be used in conjunction with FI option.
4
For Emergency operation, DC external backup power.
5
Not to be used in conjunction with F, 2C or FI option.
6
Must order pendant assembly separate.
W - White
B - Black
BA - Black housing
with aluminum
color face plate
(Universal only)
FI - Fire Alarm Flashing
Interface (ER units only)
F - Flasher (ER units only)
2C - 2 Circuit Input 1, 3
DC - DC External Backup (612V)1, 4, 5
DR - Damp Location Rating
SA - Salida
ACCESSORIES (ordered separately)
Stencil face, white panel with red lens
Stencil face, white panel with gr een lens
Pendant Mount Canopy white 6
Pendant Mount Canopy, black6
Pendant Assembly, Rigid Canopy, 12" Stem White* (requires CXPMC)
Pendant Assembly, Rigid Canopy, 12" Stem Black* (requires CXPMC)
Pendant Assembly, Swivel canopy, 12” Stem White* (requires CXPMC)
Polycarbonate Vandal Shield
Wire Guard (Wall mount only)
Mounting kit, white
* Stem lengths available: 12”, 18”, 24”, 30”, 36” and 48”
mcPhilben is a Philips group brand
erx7010.5
CXLSPWR
CXLSPWG
CXPMC
CXPMCB
CXPA12W
CXPA12B
CXPAS12W
PVS2
WG4
CXCW
CXX SERIES COMPAC® Thermoplastic LED Exit
SPECIFICATIONS
Xtest ELECTRONICS
All battery units are STANDARD with
self diagnostic/self-testing circuitry. The
management system controls test parameters within the embedded micro-controller
to verify that all system components are functioning properly. This is accomplished using
various system checks on a continuous basis,
as well hourly and monthly tests. Several
manual test can also be initiated or cancelled
at any time by pressing the test switch.
During automatic self-test or manual test the
green AC status indicator will flash. Any malfunction is reported via the appropriate exter nal
LED indicators.
complies with all the latest UL924 and NFPA 101 requirements for self
diagnostic/ self-testing operation. For complete
details on many of the exclusive features that
the
system offers, including the correction of wiring errors before applying power,
refer to specification sheet ERC2001.2.
DIMENSIONS CXX SERIES
INSTALLATION
The signs mount to a 4 inch octagon or
square outlet box. Signs that are back mounted to a wall require no canopy. Punch out
concealed knock outs on back plate. Ceiling
and end mounted signs require a canopy
(provided with each sign). Canopy mounts to
outlet box via mounting plate (provided with
each exit sign). Exit housing snaps to canopy.
WARRANTY
Full five year warranty on unit.
Xtest STATUS INDICATOR PANEL
1-5/8"
(41.3mm)
SELF-TEST / DIAGNOSTIC
CHARGER
BATTERY
LAMPS
CHG-TEST
8-3/4"
(222.3mm)
Location of sensor for laser activation of manual
test via handheld remote laser tester (this is an
optional feature, specify “LX” option)
12-5/8"
(320.7mm)
(Note: If required, canopy is 6-1/2" x 5-1/4" x 7/8")
TESTING SPECIFICATIONS
Automatic Test:
The system charger and lamps are continually being controlled via predetermined parameters specific to each model configuration, automati cally. The battery is controlled via a true open circuit test each hour after
initial installation. Every thirty days the
System illuminates lamps
under load for 30 minutes, simulating a power outage with a true charger
off condition, without affecting long-term battery life. This is above and
beyond the requirements of the National Electric Code and/or the
National Fire Protection Association, which only requir es a full load test
once every month. This gives you unequaled contr ol and confidence,
knowing you are meeting self-test code requirements each and ever y
month.
Manual Test:
A manual test switch allows for the
system to perform the following tests at any time:
Press Button:
Once– 5 second, charger off, lamps on
Twice– 60 second, charger off, lamps on
Three – 90 minute, charger off, lamps on
6 second hold – fully reinitializes microprocessor
Pressing once during any test will cancel/abort testing.
Fault Indications:
Four LED indicators provide visible indication of system status:
AC/Green
ON
F
ON
Charger/Red
Batt/Red
Lamp/Red
F
F
F
ON
ON
ON
F
ON=On Steady
F
F=Flashing
erx7010.5
F
Action
Status/Fault
None
AC power is on/ok
None
Performing Test
LED/Battery Disconnected or Charger Check connections; if ok, replace cirFault
cuit board
Charger fault
Replace circuit board
Check connection or replace battery
Battery disconnected/fault
Check connection or replace LED strip
LED disconnected or bad
BLANK=Off
DAY-BRITE LIGHTING • www.daybritelighting.com
776 South Green Street • Tupelo, Mississippi 38804 • PH: (662) 842-7212 • F AX: (662) 841-5501
CANADIAN DIVISION
189 Bullock Drive • Markham, Ontario L3P 1W4 • PH: (905) 294-9570 • F AX: (905) 294-9811
©AUGUST 2008 DAY-BRITE LIGHTING DAY-BRITE RESERVES THE RIGHT TO MAKE CHANGES WITHOUT NOTICE.
Download