Oil Alert
1 PHASE DUPLEX - Control Panel
TM
Elevator Sump Pits Transformer Vaults Leachate wells
Description of Operation
The Duplex Oil Alert is a NEMA 1 (indoor rated) Single Phase Duplex control panel that alternates the pumps for
equal wear. It’s designed to pump water out of elevator sump pits, transformer vaults and leachate wells while
containing the oil or hydrocarbons in the pumping tank. Indicator lights on the front door will illuminate if the
systems has power, or if there is a high water or high oil alarm (optional pump overload indicator available).
6
Electrical Ratings
1 Phase
120V or 230V
0-15 Amps
60 Hz.
External Components
1
2
3
4
5
7
8
9
10
11
12
13
14
15
16
17
10 17
11
16
8
ON
ON
OFF
OFF
14X12X8 Nema 1
Thermoplastic
Green Power On Indicator
Blue High Water Indicator
Red High Oil Indicator
Preset Level Sensor
Green Pump 1 Run Indicator
Green Pump 2 Run Indicator
HOA Switches
IEC Motor Contactors
Alternating Relay
Pump Circuit Breakers
Circuit Board
Terminal Blocks
Ground Lug
UL Listed
Control Fuse
Control Relays
2
Power
3
High Water
Oil
Alert
TM
4
High Oil
Pump Control/Alarm System
Contact your maintenance manager or local service provider if
the High Water light or the High Oil light is illuminated.
13
12
Internal Components
6
1
7
15
9
14
Enclosure Dimensions in inches
Width Height Depth
Mounting Holes
Width
Height
M2
H
D
M1
W
13.32 16.04 9.28 10.56 15.27
5
High Level
Probe
D
Pump
Start
High Level
Float
W
M1
Pump
Off
Features and Benefits
Separate alarm & control fuses
Load selector switch on alternator
Preset Level Sensor
H
M2
Engineered Products
PO Box 827 Hawley MN, 56549 Phone 218-483-3034
Fax 218-483-3036 www.alderonind.com
705 South Railroad Street - Unit #1 - Salisbury NC 28144 - 704-642-0280
Oil Alert
1 PHASE DUPLEX - Control Panel
TM
Elevator Sump Pits Transformer Vaults Leachate wells
System Overview
On liquid rise, level reaches pump “start” probe to
start the pump. Pump will remain on until level is
below “off” probe. The “off” probe senses air or oil and
turns the pump off so the oil layer will not be pumped
out of the tank. If the level reaches alarm probe
and mechanical float, the system will differentiate
between water and oil and activate the remote
alarm.
Warning – You must seperate the Power Cord
from the pump and the cord of the Preset Level
Sensor by at least 2” whether the cables are in
the tank and when they are above ground in
separate conduits.
Remote Alarm
Preset Level Sensor
Control Panel
120 V
Receptical
Power
High Water
High Level
Probe
Oil
Alert
TM
High Oil
Pump Control/Alarm System
Contact your maintenance manager or local service provider if
the High Water light or the High Oil light is illuminated.
Pump
Start
High Level
Float
Remote Alarm - Plug Into 120V Outlet
2”
Remote Alarm has additional auxiliary contacts for building alarm/automation system.
Pump
Off
2”
Discharge Pipe
Discharge Pipe
2”
Oil “Film” Detection Level
“High”
Water
Level
Pump“On” Level
Pump“Off” Level
Pump
Pump
Specifications
Sensor
Control Panel
Housing: ABS
Probe: Stainless Steel
Probe
Float: PVC
Enclosure: Type 1
Alarm Panel
Enclosure: Type 1
Power Cord: Plug In
Transformer, 120 VAC
Backup Power: 9 VDC
Battery Backup
LED Alarm Indicators
Audible Alarm: 103 db
buzzer, auto test/reset
Auxiliary Contacts:High Water,
High Oil, OPTIONAL Pump Fail
Order Number
Part
Number Description *For Longer Cord Lengths Consult Factor y.
7851
7852
7853
7854
-4X
Oil Alert,1 Phase, Duplex,120 VAC,15 Amps, Sensor,2 Zone Remote Alarm
W/OVERLOAD - (Specify AMP Range)
Oil Alert,1 Phase, Duplex,120 VAC,15 Amps, 3 Zone Remote Alarm
Oil Alert,1 Phase, Duplex,230 VAC,15 Amps, Sensor,2 Zone Remote Alarm
Oil Alert,1 Phase, Duplex,230 VAC,15 Amps, Sensor, 3 Zone Remote Alarm W/OVERLOAD - (Specify AMP Range)
Place -4X after any of the part numbers above for a Nema 4X System
Engineered Products
PO Box 827 Hawley MN, 56549 Phone 218-483-3034
Fax 218-483-3036 www.alderonind.com
705 South Railroad Street - Unit #1 - Salisbury NC 28144 - 704-642-0280
Download