GAMMA Building Management Systems N 502 Combi Switch Actuator Compact and universal Advantages • 8 long-range inputs for 12 to 230 V AC/DC • 8 outputs (relay contacts) for 230 V AC, 16 A • Bus-independent operation, each input affects the output of the same name The recording and transmission of binary information (such as switching states), and the switching of devices and lighting, are functions that are frequently required in non-residential and residential buildings. The N 502 combi switch actuator offers these two applications together in a single innovative device. In its delivery state, each input of each switchover function affects the output of the same name. For this reason, if a conventional momentary contact switch or several parallel switches are connected, the respective output can be switched over at each pushbutton actuation. You can use the pushbutton at the top of the device to specify if the respective output is to operate as a remote control switch or as a time switch (with adjustable ON period that can be set over the same pushbutton). The N 502 therefore supports use without a bus connection and in conventional installations. Using Engineering Tool Software (ETS), in a KNX installation, the inputs and outputs of the N 502 combi switch actuator can be freely parameterized and used for any function as usual. GAMMA www.siemens.com/gamma • Each output can be used as either a remote control switch or a time switch (with adjustable time) • With bus operation, full flexibility and userdefinable parameters • Integrated 8-bit scene control • Small footprint of just 8 MW • Outstanding value for money Combination Devices Input/output devices Technical specifications Type Specifications N 502 N 502 combi switch actuator • • • • • • • • • • • • • • • 8 inputs for DC or AC in the range from 12 ... 230 V 8 relay contact outputs Rated contact operating voltage 230 V AC Rated contact operating current 16 A, p.f. = 1 Green LED to indicate operational readiness Pushbutton to switch between bus and direct mode Yellow LED to indicate direct mode activated A pushbutton for each output to switch the output in direct mode via a toggling function by a short actuation and for changing the output mode between remote control relay and time switch relay by holding down the pushbutton for some seconds 1 red LED per output to indicate the switching state 1 red LED per input to indicate the current signal state Electronics power supply via an integrated power supply unit for 230 V AC Device functional even without bus connection or if bus voltage absent or bus communication interrupted or not yet activated Device preset at the factory for direct switching of an output through a toggling function via the input of the same name Selectable function for each input when using the Engineering Tool Software (ETS): - Switching status/binary value transmission - Switching, edge-triggered - Switching, short/long operation - 1-button dimming - 1-button solar protection control - 1-button group control (sequence control) - 1-bit scene control - 8-bit scene control - 8-bit value, edge-triggered - 8-bit value, short/long operation - 16-bit floating point value, edge-triggered - 16-bit floating point value, short/long operation Or with selectable function for each pair of inputs: - 2-button dimming with stop telegram - 2-button solar protection control • Selectable blocking / releasing of each input via a corresponding blocking object • Sending of the input objects after a change of status • Selectable cyclical sending of the input objects • Setting by means of the ETS, whether all outputs are to be configured identically or individually • Selectable mode for each output (normal mode, time switch mode) • Variable On and Off delay times for each output • Selectable logic operation (AND/OR) for one input with a further communication object and with variable start value of the logic operation at bus voltage recovery • Optional addition of a night mode object for each output for time-limited switching On of the output (and hence the illumination) at night • Variable On period in night mode or in time switch mode • Optional signal in night mode or time switch mode, whereby the light flashing on and off briefly three times warns of impending OFF • Status object for reporting direct mode • An optional status object per output for status reporting • Sending of status objects on request and/or automatically after a change • Integrated 8-bit scene control and interlinking of outputs with up to 8 scenes • Selectable switching state for each output after mains or bus power failure, as well as after bus or mains voltage recovery • Integrated bus coupling unit with only half a standard bus load • Bus connection both via bus terminal and contact system to a data rail • Modular installation device for mounting on TH 35 mounting rail to EN 60715 • Module width 8 MW (1 MW = 18 mm) Selection and ordering data (Dated 03/2008) Type Version DT Order No. N 502 N 502 combi switch actuators A 5WG1 502-1AB01 PU PS1)/ P. unit PG Unit(s) Unit(s) 1 1 Weight per unit approx. kg 030 0.500 5WG1 502-1AB01 1) You can order this quantity or a multiple thereof. Siemens AG Industry Sector Building Technologies Electrical Installation Technology Postfach 10 09 53 93009 REGENSBURG GERMANY www.siemens.com/gamma Subject to change without notice Order No.: E86060-K8230-E520-A1-7600 Dispo 18302 PI 0308 1. SB 2 En / 803079 Printed in Germany © Siemens AG 2008 The information provided in this brochure contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.