Nortrax 20 07 00 190 David Manchester Road, Ottawa INSULATION

advertisement
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
PART 1 1.1.
1.2.
1.3.
1.4.
PRODUCTS ........................................................................................................................ 1
MATERIALS – GENERAL ..................................................................................................................... 1
PIPE INSULATION ................................................................................................................................ 2
SHEET METAL INSULATION ............................................................................................................... 7
EQUIPMENT INSULATION .................................................................................................................. 9
PART 3 -
3.1.
3.2.
GENERAL ........................................................................................................................... 1
WORK INCLUDED ................................................................................................................................ 1
SUBMITTALS ........................................................................................................................................ 1
ENVIRONMENTAL REQUIREMENTS ................................................................................................. 1
QUALITY ASSURANCE ........................................................................................................................ 1
PART 2 -
2.1.
2.2.
2.3.
2.4.
20 07 00
INSULATION
EXECUTION ..................................................................................................................... 10
PROTECTION ..................................................................................................................................... 10
INSTALLATION ................................................................................................................................... 11
INDEX
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
PART 1 1.1.
1.2.
.1
Comply with Division 1, General Requirements and all documents referred to therein.
.2
Provide all labour, materials, products, equipment and services to supply and install thermal
insulation, vapour barriers and finishes for mechanical work as indicated on the Drawings
and specified in this Section of these Specifications.
.3
Insulation requirements shall comply with Part 5 of the Model National Energy Code of
Canada, latest version and insulation thickness shown are the minimum acceptable.
SUBMITTALS
Submit samples and specification sheets of all types of insulation materials specified in this
Section of the Specifications. Include manufacturers installation instructions.
ENVIRONMENTAL REQUIREMENTS
.1
1.4.
Maintain ambient temperatures and conditions required by manufacturers of adhesives,
mastics and insulating cements.
QUALITY ASSURANCE
.1
Insulation materials must be manufactured at facilities certified and registered with an
approved Registrar to conform to ISO 9000 quality standard.
PART 2 2.1.
GENERAL
WORK INCLUDED
.1
1.3.
20 07 00
INSULATION
Page 1
PRODUCTS
MATERIALS – GENERAL
.1
Acceptable insulation manufacturers are Owens Corning Canada, Johns Manville, Manson
Insulation Inc., Knauf Fiber Glass and Certainteed.
.2
Provide insulation and covers in strict accordance with authorities governing combustibility
and fireproofing of materials and in accordance with manufacturer's recommendations.
.3
Provide non-combustible insulation, jackets and finishes having a Flame Spread/Smoke
Developed rating of 25/50 or less, meeting CAN/ULC S-102 requirements.
.4
Attain a complete and continuous vapour barrier over insulation applied to cold and dual
temperature piping, sheet metal and equipment. Use either factory applied vapour barrier
jacket or field applied Reinforced Foil Flame Resistant Kraft vapour barrier jacket. Apply to
piping, fittings, valves and inline components, sheet metal and fittings and equipment. Seal
longitudinal and circumferential laps with Childers CP82 or Bakor 230-39 adhesive. If vapour
barrier jacket is not lapped, seal joints with self-adhering {100mm} [4"] wide plain aluminum
foil tape, or adhere {100mm} [4"] wide aluminum foil tape with Childers CP82 or Bakor 23039 adhesive. Jacketing with self-adhesive laps and self-adhesive vapour barrier tape will be
an acceptable alternative closure system.
.5
Recover all exposed insulation and insulation finishes with minimum {0.20kg/squaremetre}
[6oz.] canvas, and two applications of Childers CP50 or Bakor 120-09 white fire resistant
coating. An acceptable alternative recovering will be PVC fitting covers and jacketing,
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
20 07 00
INSULATION
Page 2
installed as per manufacturer's instructions, and conforming to the specified Flame
Spread/Smoke Developed Rating.
2.2.
.6
Recover insulation and insulation finishes outside the building or exposed to the weather with
one {1.5mm} [1/16"] thick layer of Childers Encacel X or Bakor 110-26 fire retardant black
mastic vapour barrier coating. Embed a layer of woven glass reinforcing fabric into the wet
coating, lapping ends and edges at least {75mm} [3"]. Apply a top coating of {1.5mm} [1/16"]
thick Encacel X or Bakor 110-26 over the entire surface of the fabric. Seal the entire
covering to achieve a watertight assembly.
.7
In lieu of above recovering of insulation and insulation finishes outside the building,
aluminum jacket with aluminum fittings may be substituted. Band all transverse seams with
waterproof mastic tape and caulk all longitudinal seams with silicone caulking. Seal the
entire covering to achieve a watertight assembly.
PIPE INSULATION
.1
Provide insulation materials with a minimum thermal conductivity of {0.036 W/m.ºC} [0.24
BTU.in/(hr.ft2ºF] at {38ºC} [100ºF] mean temperature.
.2
On hot piping applications, hold insulation in place with flare type staples (outward clinch).
.3
On cold and dual temperature piping applications, apply vapour barrier jacket over insulation
and seal longitudinal and circumferential laps with Childers CP82 or Bakelite 230-39
adhesive. Seal all pipe terminations, including fittings, wall penetrations and pipe supports
with vapour barrier mastic. For chilled water and brine systems provide vapour seal pipe
terminations every four (4) pipe sections.
.4
Apply pipe insulation over {40mm} [1-1/2"] in thickness in two layers with joints staggered.
.5
Insulate fittings with fabricated mitered or preformed sections of specified insulation.
.6
Insulate over flanges and mechanical couplings with specified insulation and thickness, sized
to suit flange diameters. Fill spaces between insulation and adjoining pipe insulation with
similar material.
.7
Insulate valves and inline components with flexible insulation density {12kg/cubicmetre}
[3/4lbs./cu.ft.] compressed not more than 50% of original thickness. Build up to specified
thickness with approved asbestos free finishing cement.
.8
Do not insulate terminal unit automatic control valves installed in hot piping. Do not insulate
terminal unit automatic control valves which are installed in cold and dual temperature piping
and which are located over condensate drain pans.
.9
Provide removable {1.31mm} [18gauge] galvanized sheet metal enclosures lined with
Armaflex II sheet insulation {25mm} [1"] thickness on pipeline strainers to facilitate screen
access.
.10
Under all hangers used on primary chilled water, domestic chilled water, domestic chilled
water recirculation, dual temperature water and domestic cold water, provide an insert
between support shield and piping for piping {38 mm} [1½"] or larger. Fabricate using T-12
calcium silicate or other high density insulating material suitable for temperature application.
Insulation inserts shall not be less than the following lengths:
Pipe Size
Length
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
20 07 00
INSULATION
Page 3
{40 mm - 60 mm} [1½" – 2½"]
{75 mm - 150 mm} [3" - 6"]
{200 mm - 250 mm} [8" - 10"]
{300 mm and over} [12" and over]
.11
.12
{250 mm} [10"]
{300 mm} [12"]
{400 mm} [16"]
{550 mm} [22"]
Provide one of the following pipe insulation types, and as scheduled in the Pipe Insulation
Table.
.1
Type P1: Owens Corning 850 Pipe Insulation, Johns Manville Micro-Lok AP-T PLUS
Fiberglas Pipe Insulation, Manson Fiberglas Pipe Insulation or Knauf Pipe Insulation
with factory applied all-purpose vapour barrier jacket where scheduled.
.2
Type P2: Johns Manville Thermo 12 Gold throughout molded hydrous calcium
silicate type, indicating asbestos free pipe insulation. Density shall be not less than
{224kg/cubicmetre} [14lbs./cu.ft.]. Insulation shall be banded securely in place with
{20mmx0.5mm} [3/4"x.020"] stainless steel bands on maximum {300mm} [12"]
centres.
.3
Type P3: Owens Corning Flex-Wrap Pipe Insulation, Johns Manville Pipe & Tank,
Manson Multi-Flex or Knauf Flex-Wrap with protective reinforced foil scrim, {48 kg
/cubic metre} [3.0 lbs /cu.ft.] density.
Pipe Insulation Table:
No
1
Duty
Vapour
Barrier
P-1
P-1
{12mm} [1/2"]
{25mm} [1"]
Yes
Yes
P-1
P-1
{25mm} [1"]
{40mm} [1-1/2"]
No
No
P-1
P-1
P-1
{12mm} [1/2"]
{25mm} [1"]
{25mm} [1"]
Yes
No
Yes
Domestic hot and
domestic tempered water,
and domestic hot water and
tempered water recirculation
less than {40mm} [1-1/2"]
{65mm} [1-1/2"] and larger
3
Thickness
Domestic cold water, and
domestic chilled water, and
domestic chilled water
recirculation
{100mm} [4"] and less
{125mm} [5"] and larger
2
Insulation
Type
Handicap Lavatory
domestic cold water supply
domestic hot water supply
sanitary waste piping
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
No
4
20 07 00
INSULATION
Page 4
Duty
P-1
{25mm} [1"]
No
P-1
P-1
{25mm} [1"]
{50mm} [2"]
Yes
Yes
P-1
P-1
{25mm} [1"]
{40mm} [1-1/2"]
Yes
Yes
P-1
{25mm} [1"]
Yes
P-1
{25mm} [1"]
Yes
P-1
{25mm} [1"]
Yes
Refrigeration machine oil
cooler and purge
all pipe sizes
10
No
No
Horizontal storm drain and
horizontal sanitary drainage
all pipe sizes
9
{25mm} [1"]
{40mm} [1-1/2"]
Condenser water supply and
return inside and outside
building
{100mm} [4”] and less
{125mm} [5”] and larger
8
P-1
P-1
Chilled water supply and
return and dual temperature
supply and return
{150mm} [6”] and less
{200mm} [8”] and larger
7
Vapour
Barrier
Heat reclaim supply and
And return
All sizes
6
Thickness
Primary heated water
supply and return, and
secondary heated water
supply and return (Below {94ºC}
[201ºF])
{50mm} [2”] and less
{65mm} [2-1/2”] and larger
5
Insulation
Type
Sprayed water
all pipe sizes
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
No
20 07 00
INSULATION
Page 5
Insulation
Type
Thickness
Vapour
Barrier
all pipe sizes
P-1
{12mm} [1/2"]
Yes
Makeup, overflow, drain and
equalizer lines for cooling tower
all pipe sizes
P-1
13
Dry sprinkler system drum drips
P-1
{25mm} [1"]
Yes
14
Steam and condensate up to {103
kPa} [15 psig]
P-1
P-1
{40mm} [1-1/2"]
{50 mm} [2"]
No
No
P-1
P-1
P-1
{50 mm} [2"]
{65 mm} [2-/2"]
{90 mm} [31/2"]
No
No
No
P-1
P-1
P-1
{65 mm} [2-/2"]
{75 mm} [3"]
{90 mm} [3-/2"]
No
No
No
11
12
Duty
Horizontal condensate drains
except with fan coil unit enclosure
{50mm} [2”] and less
{65mm} [2-1/2”] and larger
15
Yes
Steam from {104 kPa} [15 psig] to
{827 kPa} [120 psig]
{25 mm} [1”] and less
{32 mm} [1-1/4”] to {100 mm} [4”]
{125 mm} [5”] and larger
16
{25mm} [1"]
Steam above {827 kPa} [120 psig]
{50 mm} [2”] and less
{65 mm} [2-1/2”] to {100 mm} [4”]
{125 mm} [5”] and larger
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
No
20 07 00
INSULATION
Page 6
Insulation
Type
Thickness
Vapour
Barrier
{50mm} [2”] and less
{65mm} [2-1/2”] and larger
P-1
P-1
{40mm} [1-1/2"]
{50 mm} [2"]
No
No
{122ºC-177ºC} [251ºF-350ºF]
{25mm} [1”] and less
{32mm} [1-1/4”] to {100 mm) [4"]
{125mm} [5”] and larger
P-1
P-1
P-1
{50mm} [2"]
{65mm} [2-1/2"]
{90mm} [3-1/2"]
No
No
No
Above {177ºC} [350ºF]
{50mm} [2”] and less
{65mm} [2-1/2”] to {100mm} [4”]
{125mm} [5”] and larger
P-1
P-1
P-1
{65mm} [2-1/2"]
{75mm} [3"]
{90mm} [3-1/2"]
No
No
No
P-1
{25mm} [1"]
Yes
{25 mm} [1”] and smaller
{32 mm} [1-1/4”] and larger
P-1
P-1
{25mm} [1"]
{40mm} [1-1/2"]
Yes
Yes
19
Emergency generator exhaust
pipes and mufflers
P-2
{50mm} [2"]
No
20
Heat traced pipe for freeze
protection
P1
P1
P1
{25mm} [1"]
{40mm} [1-1/2"]
{40mm} [1-1/2"]
No
No
No
17
Duty
High temperature heated
water
{94ºC-121ºC} [201ºF-250ºF]
18
Refrigerant piping suction lines
{4.4ºC}[40ºF] and above
Refrigerant piping suction lines
below {4.4ºC} [40ºF]
{12mm} [½"] to {75mm} [3"]
{100mm} [4"]
{125mm} [5"] and above
.13
In lieu of specified pipe insulation, where permitted by governing authorities, and in
concealed locations, Imcoa Polyolefin or Armstrong AP Armaflex pipe insulation in nominal
{12mm} [1/2"] thickness may be substituted for the following applications, on piping not
exceeding {100mm} [4"] diameter, and shall be applied in strict accordance with
manufacturer's recommendations.
.1
domestic cold water
.2
domestic hot and tempered water
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
2.3.
20 07 00
INSULATION
Page 7
.3
domestic hot and tempered water recirculation
.4
heated water water runouts concealed behind perimeter enclosure
.5
condensate drains
SHEET METAL INSULATION
.1
Provide insulation with a minimum thermal resistance of {0.036 W/m.ºC} [0.25
BTU.in/(hr.ft2ºF)] at {24ºC} [75ºF] mean temperature.
.2
Prior to finishing of insulation of hot and cold exposed rectangular ductwork, provide corner
beads similar to Roll-on Type.
.3
Apply vapour barrier over insulation on cold and dual temperature ducts.
.4
Circular silencers and acoustic plenums need not be externally insulated.
.5
Ductwork and casings lined with acoustic insulation {25mm} [1"] or more in thickness need
not be externally insulated. Refer to Section 15890 for Acoustic Insulation.
.6
Provide one of the following external sheet metal insulation types, and as scheduled in the
Sheet Metal Insulation Table.
.1
Type D1: Owens Corning Rigid Duct Insulation, Johns Manville 814 Spin-Glas,
Manson 800 Series Spin-Glas Rigid Insulation Board or Knauf Rigid Insulation
Board, not less than {48kg/cubicmetre} [3lbs./cu.ft.] density. Impale insulation on
mechanically fastened pins located at not greater than {300mm} [12"] centres.
Secure insulation with speed washers.
.2
Type D2: Owens Corning Flexible Duct Insulation, Johns Manville Microlite type 75
Duct Wrap, Manson Microlite Duct Wrap or Knauf Duct Wrap, {12kg/cubicmetre}
[3/4lbs./cu.ft.] density. Adhere insulation to duct surface with Childers CP82 or
Bakelite 230-39 adhesive, which shall be applied in strips {150mm} [6"] wide at not
greater than {300mm} [12"] centres. Lap all edges at least {50mm} [2"] and secure
insulation with fire resistant tying cord, similar to Fiberglas EC9-4-T. Take care that
insulation is not compressed to less than specified thickness. It is recognized that
some compression of insulation will take place immediately under tying cord, but in
no case shall the thickness of the compressed material be less than 75% of original
specified thickness.
.3
Type D3: Owens Corning Rigid Vapour Seal Duct Insulation, Johns Manville 814
Spin-Glas with FSK Facing, Manson Spin-Glas Rigid Insulating Board with reinforced
foil facing, or Knauf Rigid Insulation Board with FSK facing. Density shall be not less
than {48kg/cubic metre} [3lbs./cu.ft.]. Impale on mechanically fastened pins located
at not greater than {300mm} [12"] centres. Secure with speed washers. Butt joints
tightly together and seal washers, breaks and joints with self-adhering {100mm} [4"]
wide plain aluminum tape, or adhere foil with Childers CP82 or Bakelite 230-39
adhesive.
.4
Type D4: Owens Corning Flexible Duct Insulation, Johns Manville Microlite Type 75
Duct Wrap, Manson Microlite Insulation or Knauf Duct Wrap, {12kg/cubic metre}
[3/4lb./cu.ft.] density with factory applied reinforced foil facing. Adhere insulation to
duct surface with Childers CP82 or Bakelite 230-39 adhesive, which shall be applied
in strips {150mm} [6"] wide at not greater than {300mm} [12"] centres. Butt edges of
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
20 07 00
INSULATION
Page 8
insulation tightly together, and seal breaks and joints of facing with self-adhering
{100mm} [4"] wide aluminum tape or adhere foil with Childers CP82 or Bakelite 23039 adhesive.
.7
Sheet Metal Insulation Table
No
Duty
Insulation
Type
Thickness
Vapour
Barrier
1
Panels behind unused portion of
louvres
D3
{50mm} [2"]
Yes
2
Outside air plenums and ducts
Outside air supply fans
D3
{50mm} [2"]
Yes
3
Mixed air plenums and ducts
D3
{40mm} [1-1/2"]
Yes
4
Relief and exhaust air plenums
D3
{40mm} [1-1/2"]
Yes
5
Exhaust ducts between
motorized dampers and building
exterior or final {3m} [10 ft] of
exhaust air ducts whichever is
greater
D3
{25mm} [1"]
Yes
6
Rectangular hot supply ducts
D1
{25mm} [1"]
No
7
Round hot supply ducts
D2
{40mm} [1½"]
No
8
Exposed rectangular cold and
dual temperature supply ducts
D3
{25mm} [1"]
Yes
9
Exposed round cold and dual
temperature supply ducts
D3
{25mm} [1"]
Yes
10
Supply and return ductwork
outside the building or exposed
to the weather
D3
{50 mm} [2"]
Yes
11
Concealed supply air, (including
ducts in shafts) to air terminal
control units, excluding flexible
ducts
D4
{25mm} [1"]
Yes
Concealed supply air ducts from
air terminal control unit
discharge to air terminals
excluding flexible ducts.
D4
{25mm} [1"]
Yes
13
Free standing supply fan
casings
D3
{40mm} [1-1/2"]
Yes
14
Heating and ventilating unit
casings
D3
{25mm} [1"]
Yes
15
Air conditioning unit casings
D3
{40mm} [1-1/2"]
Yes
12
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
No
2.4.
20 07 00
INSULATION
Page 9
Duty
Insulation
Type
Thickness
Vapour
Barrier
16
Field fabricated casings
D3
{40mm} [1-1/2"]
Yes
17
Stair pressurization ductwork
from louvre to shaft.
D3
{50mm} [2"]
Yes
EQUIPMENT INSULATION
.1
Provide insulation with a minimum thermal resistance of {0.57 W/m.ºC} [0.40
BTU/in/(hr.ft2ºF)] at {177ºC} [350ºF] mean temperature.
.2
Apply insulation over {40mm} [1-1/2"] thickness in two layers, with staggered joints.
.3
Apply vapour barrier over insulation on cold and dual temperature equipment.
.4
Provide one of the following equipment insulation types and as scheduled in the Equipment
Insulation Table.
.1
Type E1: to {232ºC} [450ºF] - Owens Corning Type AF500 Series, Johns Manville
800 Series Spin-Glas, Manson AK Board, or Knauf Pipe and Tank Insulation. Cut
and mitre insulation to suit surface contours. Impale insulation on mechanically
fastened pins, located at not greater than {300mm} [12"] centres. Apply expanded
metal lath and lace edges with {1.61mm} [16gauge] galvanized annealed wire.
Secure insulation and metal lath with {40mm} [1-1/2"] OD speed washers. Apply
{12mm} [½"] thick approved asbestos free insulating cement in two coats. Allow to
dry to a smooth finish before recovering. In lieu of the above specified insulation and
metal lath, Foamglas Curved Block may be substituted. Band Foamglas securely in
place with {20mmx0.5mm} [3/4"x.020"] stainless steel bands on maximum {300mm}
[12"] centres. Apply {12mm} [½"] thick approved asbestos free insulating cement in
two coats.
.2
Type E2: to {232ºC} [450ºF] - Owens Corning, Johns Manville, Manson or Knauf
Insulation and application as per Type E1. Cover with {0.40mm} [.016"] thick sheet
aluminum fabricated to the shape of the equipment. Mechanically fastened in place
with bands, sheet metal screws or pop rivets. All corners shall be square and raw
metal edges concealed. Metal covering will not be accepted as a substitute for
specified vapour barrier applied directly in the insulation.
.3
Type E3: to {650ºC} [1200ºF] - Johns Manville Thermo-12 Gold throughout hydrous
calcium silicate type indicating asbestos free insulation, molded in sections or
segments to suit the application. Density shall be not less than {224kg/m3}
[14lbs/cu.ft.]. Insulation shall be bonded securely in place with {20mmx0.5mm}
[3/4"x.020"] stainless steel bands on maximum {300mm} [12"] centres.
.4
Type E4: Armstrong AP Armaflex elastomeric type insulation. Apply to clean and
dry metal surfaces, using 100% Armstrong 520 adhesive coverage on both surfaces
to be joined. Use manufacturer's compression fit method of butt joining sheets.
Finish with two coats of Armaflex Finish, except the following shall be equipped with
a removable {1.31mm} [18gauge] aluminum sheet metal enclosure with insulation
applied as above to inside of cover.
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
.5
.1
chilled water pumps
.2
chilled water pump suction and discharge guides
.3
heated water pumps
.4
condenser water pumps
.5
condenser water pump suction and discharge guides
.6
chiller shell ends
Equipment Insulation Table:
No.
PART 3 3.1.
20 07 00
INSULATION
Page 10
Duty
Insulatio
n Type
Thickness
Vapour
Barrier
1
Chilled water pumps, suction and
discharge guides
E4
{25mm} [1"]
Yes
2
Condenser water pumps, suction and
discharge guides
E4
{25mm} [1"]
Yes
3
Heated water shell and tube heat
exchangers
E1
{25mm} [1"]
No
4
Chilled and dual temperature water
shell and tube heat exchangers
E1
{25mm} [1"]
Yes
5
Domestic hot water storage tanks
E1
{40mm} [11/2"]
No
6
Water meter
E1
{40mm} [11/2"]
Yes
7
Expansion tanks
Insulation
not
required
8
Heated water pumps, suction and
discharge guides
Insulation
not
required
9
Centrifugal refrigeration machines
- suction lines
- chiller shells
- chiller shell ends
E4
E4
E4
{25mm} [1"]
{25mm} [1"]
{25mm} [1"]
Yes
Yes
Yes
10
Cooling tower indoor sump
E2
{25mm} [1"]
Yes
11
Boiler breeching
E3
{50mm} [2"]
No
EXECUTION
PROTECTION
Nortrax
190 David Manchester Road, Ottawa
21 May 2014
Project: 13-104-070
3.2.
20 07 00
INSULATION
Page 11
.1
Protect the work of other trades with tarpaulins.
.2
Protect the work of this trade from being defaced by other trades. Make good any damage
and leave in perfect condition, ready for final painting.
INSTALLATION
.1
Apply insulation over clean dry surfaces, firmly butting all sections together.
.2
Apply insulation, vapour barriers and insulation finishes in strict accordance with
manufacturer's recommendations.
.3
Do not cover equipment nameplates with insulation.
.4
Coordinate related work with other Divisions.
END OF SECTION