System 3TM

advertisement
s
Data Sheet Fire Safety & Security Products System 3TM
Voltage Regulator Module
Model DC-35S
ARCHITECT AND ENGINEER SPECIFICATIONS
•
Filtered and regulated module
•
Non-interruptible output
• 3/4
Amp. output
•
Fused input
•
Placement supervised
•
Power ON light-emitting diode (LED)
•
UL 864 9th Edition Listed;
FM, CSFM and NYC Fire Department Approved
Product Overview
Specifications
The System 3 Voltage Regulator Module (Model
DC-35S) from Siemens ─ Fire Safety is designed to
provide filtered, VDC power from the bridge-only,
unfiltered, and unregulated VDC output power of
the power supply (Model PS-35S).
A voltage regulator module shall be provided to
supply filtered, regulated power to pre-action /
deluge sprinkler release valves. The module shall
be a Siemens ─ Fire Safety Model DC-35S.
The Voltage Regulator Module provides regulated
power to the Model RM-30─series release modules
for pre-action / deluge sprinkler releasing
applications that are Factory Mutual Approved.
Model DC-35S, which is placement supervised
within System 3, features a Power ON LED and a
fused input. Although the module contains a
potentiometer for precise output-voltage
adjustments, the output is factory configured to
not exceed the limit required for proper function
of System 3.
The regulated power shall be initially routed
through the Siemens ─ Fire Safety Transfer
Module (Model TC-30U), accommodating battery
back-up requirements. The regulated power shall
then be sent through the Model RM-30─series
release modules, which connects and controls the
electronic solenoid pilot valve on the pre-action /
deluge sprinkler releasing system.
Model DC-35S shall receive bridge-only,
unfiltered, and unregulated VDC output power
from the Model PS-35S Power Supply. The output
rating of Model DC-35S shall be 0.75 Amps.
System 3™ Voltage Regulator Module
s Industry, Inc.
Building Technologies Division
3181
Specifications ─ (continued)
Temperature and Humidity Range
Model DC-35S shall be placement supervised
within System 3, and shall be Factory Mutual
Approved for pre-action / deluge sprinkler
control applications.
The System 3 Voltage Regulator Module is UL
864 9th Edition Listed for indoor dry locations
within a temperature range of 120+/-3°F
(49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative
humidity of 93+/-2% at a temperature of 90+/-3°F
(32+/-2°C).
Electrical Ratings
Current
Draws
Input
Circuit:
Output
Circuit:
Up to 0.75A @ 38V
Full Wave Rectified (FWR)
Up to 0.75A @ 28VDC
Details for Ordering
Model
Number
DC-35S
Part
Number
Description
500-491785
Voltage Regulator
Module
Shipping
Weight
Lb.
Kg.
2
0.90
Dimensions
The dimensions for each Model DC-35S
voltage regulator are as follows:
Approximate size: 9.0” (22.9 cm.) [H];
2.25” (5.7 cm.) [W];
2.25” (5.7 cm.) [D]
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.
s Industry, Inc.
Building Technologies Division
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (908) 547-6877
URL: www.SBT.Siemens.com/FIS
(SII‐FS)
Printed in U.S.A. Fire Safety
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 / Canada
Tel: (905) 799-9937
FAX: (905) 799-9858
February 2012
Supersedes sheet dated 12/04