Panelboards 11 Quik-Spec™ Coordination Panelboard Specifications QuikShip™ PANELBOARDS All SQSCP configurations of the standard NEMA 1 enclosure can be specified for shipment within 10 business days of order when specified. MLO (Main Lug Only) Mains Fused disconnect switch Non-fused disconnect switch Assembly SCCRs 200kA, 100kA or 50kA AC, 100kA or 20kA@125Vdc Voltage ratings Applicable on any 600Vac or less, or 125Vdc or less systems Bus amperages 400A, 225A, 200A, 100A, 60A or 30A Circuits: 18, 30 or 42* Branch circuits Amps: Up to 100A Type: 1-, 2- and 3-Pole Feed: top & bottom Mounting: surface or flush Panels Door/Trim: regular or door-in-door NEMA Ratings: 1 & 3R. Other ratings available, consult factory. Feed-Through: single and double Through-lugs & loadside disconnect Sub-Feed Feed/Sub-Through Fused loadside disconnect, (up to 1/2 of main amp rating) Neutrals 200A, 400A and 800A unbonded and bonded Grounds Non-isolated or isolated Enclosure sizes Spare fuses Options 11-76 Standard size panelboard (20” W x 5¾” D x 33”- 69” H)* Spare fuse compartment holds up to six fuses Surge protection device (TVSS) for high and low energy transients. Depending on configuration. 125Vdc rating applicable to only 40 amp or less CCPBs on MLO panels only. Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog Panelboards Quik-Spec™ Coordination Panelboard Specifications 11 Catalog Symbol: SQSCP4 Panelboards for commercial/industrial branch or service entrance applications on systems up through 600Vac. The SQSCP is especially designed to address the NEC® Selective Coordination Requirements for Emergency, Legally Required Standby, Healthcare Essential Electrical and Critical Operation Power Systems (COPS) per NEC® 700.27, 701.18, 517.26 and 708.54. Not for applications requiring AFCI protected circuits. The SQSCP is configured to order for the application. To confirm availability of options and constructions, contact your Siemens distributor. Ratings Volts: 600Vac (or less), 125 Vdc Amps: 30, 60, 100, 200, 225, 400A SCCR: 20kA or 100kA @ 125Vdc–See panelboard short circuit ratings table for AC ratings. Agency information ▪ UL 67–Standard for panelboards ▪ UL 50/UL 50E–Enclosures for electrical equipment ▪ CSA 22.2, No. 29-M1989– Panelboards and encl. panelboards ▪ UL listed, class CTL panelboard (meets 2002 NEC® 408.1 limit of 42 overcurrent devices per panel) ▪ UBC and CBC Seismic Qualified and IBC Approved PANELBOARDS Description Main options ▪ Main lug only (MLO) ▪ Fused main disconnect ▪ Non-fused main disconnect Branch disconnect options ▪ 1-, 2-, and 3-pole 15, 20, 30, 40, 50, 60, 70, 90, and 100A rejecting branch disconnects (see table for details). Branch ampacity on 125Vdc panels limited to SCCPB 40A or less. Branch circuit positions ▪ 18, 30 and 42 Neutral options ▪ Unbonded and bonded 200A, 400A and 800A Ground options ▪ Isolated and non-isolated Enclosures ▪ NEMA 1 and NEMA 3R. Other ratings available. Consult factory. Spare fuse compartment ▪ Six space spare fuse compartment standard on all models Panelboard Short-circuit Current Ratings AC main options DC SCCR Main lug only (MLO)a 70-200A main disc. no fusesa or w/ Class J fuses 225-400A main disc. no fusesa or w/ Class J fuses SCCP_CF main disc. (60A) b Main lug only (MLO)a High 200kA 200kA 100kA 200kA 100kA Std. 50kA 50kA 50kA 50kA 20kA a Class b J, T or RK1 fuses upstream, max amps = panel amps. CUBEFuse® disconnect Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 11-77 • Revised • 02/26/12 Panelboards 11 SCCPB Branch Disconnects, CUBEFuse® Replacement parts and performance data PANELBOARDS Fuse and disconnect performance data For details and specifications, access the following data sheets online at www.usa.siemens.com/panelboards I CUBEFuse® Specifications Catalog Symbols J STCF_ (6-100A Indicating version) STCF_RN (1-100A Non-indicating version) Description The CUBEfuse® is a finger-safe, dual-element, time delay UL Class CF power fuse with Class J fuse electrical performance charcteristics. 10 Seconds minimum operating time at 500% rated current. Ratings I – CCPB Branch Disconnects Poles Ampacity Part No. 1-pole 2-pole SCCPB-1-(amp)CF 15A, 20A, 30A, 40A, 50A, 60A, 70A, 90A, 100A 3-pole SCCPB-2-(amp)CF SCCPB-3-(amp)CF J – CUBEFuse® Fuses For CCPB Part No. Non-indicating Part No. STCF(amps)RN Indicating Part No. STCF(amps) STCF1RN, STCF3RN, STCF6RN, STCF10RN, STCF15RN STCF17-1/2 RN STCF20RN STCF25RN STCF30RN STCF35RN STCF40RN STCF45RN STCF50RN STCF6 STCF10 STCF15 STCF17-1/2 STCF20 STCF25 STCF30 STCF35 STCF40 STCF45 STCF50 SCCPB-(# of poles)-60CF STCF60RN STCF60 SCCPB-(# of poles)-70CF STCF70RN STCF70 SCCPB-(# of poles)-90CF STCF80RN STCF90RN STCF80 STCF90 SCCPB-(# of poles)-100CF STCF100RN STCF100 SCCPB-(# of poles)-15CF SCCPB-(# of poles)-20CF SCCPB-(# of poles)-30CF SCCPB-(# of poles)-40CF SCCPB-(# of poles)-50CF CCPB disconnect can accept CUBEFuses® with amp ratings less than or equal to the amp rating of the SCCPB disconnect. 1A indicating CUBEFuse® not available. Correct fit with SCCPB disconnect requires indicating CUBEFuse® with date code R38 or later. a 11-78 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog Volts: Amps: IR: 600Vac/300Vdc 1-100 (non-indicating version) 6-100 (indicating version) 300kA RMS Sym. (UL) 200kA RMS. Sym (CSA) 100kA DC (UL & CSA) Agency Information ▪ UL Listed Special Purpose Fuse: Guide JFHR, File E56412 ▪ CSA Certified Fuse: Class 1422- 02, File 53787 ▪ CE compliance for the European Union low voltage directive Other Ratings/Specifications Watts Loss at rated current: STCF30: 3.99W STCF60: 6.23W STCF100: 9.51W Operating and Storage Temperature Range 14 to 149°F(-10 to 65°C) Material Specifications ▪ Case: Glass filled PES (Polyethersulfone) ▪ Terminals: Copper alloy ▪ Terminal plating: Electroless tin ▪ Indicator lens: PES (Polyethersulfone) (indicating version only) ▪ Indicator: Energetic chemical CUBEFuse®, Low-Peak®, Quik-Spec™, QuikShip™, and easyID™ are valuable trademarks of Cooper Industries in the United States and other countries. • Revised • 02/26/12 Panelboards SCCPB Branch Disconnects, CUBEFuse® Specifications 11 SCCPB Horsepower Ratings 120 SCCPB-(poles)-15CF 15 0.5 3 5 SCCPB-(poles)-20CF 20 0.75 3 7.5 SCCPB-(poles)-30CF 30 1.5 5 15 10 SCCPB-(poles)-40CF 40 2 7.5 20 10 SCCPB-(poles)-50CF 50 3 7.5 20 10 SCCPB-(poles)-60CF 60 3 7.5 20 10 SCCPB-(poles)-70CF 70 3 15 30 40 SCCPB-(poles)-90CF 80 5 20 40 50 SCCPB-(poles)-100CF 100 5 20 50 50 240 480 PANELBOARDS HP Rating @ Vac Amp Rating SCCPB Disconnect 600 7.5 10 Branch Disconnects SCCPB Part No. Poles SCCPB-1-15CF 1 SCCPB-2-15CF 2 SCCPB-3-15CF 3 SCCPB-1-20CF 1 SCCPB-2-20CF 2 SCCPB-3-20CF 3 SCCPB-1-30CF 1 SCCPB-2-30CF 2 SCCPB-3-30CF 3 SCCPB-1-40CF 1 SCCPB-2-40CF 2 SCCPB-3-40CF 3 SCCPB-1-50CF 1 SCCPB-2-50CF 2 SCCPB-3-50CF 3 SCCPB-1-60CF 1 SCCPB-2-60CF 2 SCCPB-3-60CF 3 SCCPB-1-70CF 1 SCCPB-2-70CF 2 SCCPB-3-70CF 3 SCCPB-1-90CF 1 SCCPB-2-90CF 2 SCCPB-3-90CF 3 SCCPB-1-100CF 1 SCCPB-2-100CF 2 SCCPB-3-100CF 3 Fuse Amp Range Max. SCCBP Amp. 1-15 Non-indicating Fuses (Standard) Indicating Fuses (Opt’l) 15 STCF1RN, STCF3RN, STCF6RN, STCF10RN, STCF15RN STCF6 STCF10 STCF15 17.5-20 20 STCF17-1/2 RN STCF20RN STCF17-1/2 STCF20 25-30 30 STCF25RN STCF30RN STCF25 STCF30 35-40 40 STCF35RN STCF40RN STCF35 STCF40 45-50 50 STCF45RN STCF50RN STCF45 STCF50 60 60 STCF60RN STCF60 70 70 STCF70RN STCF70 80-90 90 STCF80RN STCF90RN STCF80 STCF90 100 100 STCF100RN STCF100 a SCCPB disconnect can accept CUBEFuses® with amp ratings less than or equal to the amp rating of the SCCPB disconnect. Correct fit with SCCPB disconnect requires indicating CUBEFuses® with date code R30 or later. Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 11-79 Panelboards PANELBOARDS 11 Enclosure/System Types, AC & DC Voltages AC Voltages NEMA 1 ▪ Flush or surface mount. ▪ Galvanized steel with removable end walls –blank or with knockouts to order. ▪ Box sizes: 20” W x 5.75” D x 33”, 50”, 59” or 69” H (510 W x 145 D x 838, 1270, 1500 or 1753mm H). Box can be rotated 180° to accommodate conduit feed. ▪ Enclosure and chassis mounting instructions are found in supplied literature. ▪ Chassis mounts directly onto studs in the enclosure. ▪ Trim finished with gray powder coat paint over phosphatized steel (ANSI 61). ▪ Door and door-in-door configurations with locks. ▪ Door locks use key #2A1910-2. ▪ Circuit directory card is located on the inside of the door. ▪ Trim screws are concealed. 1 phase, 2 wire ▪ 120V 1 phase, 2 wire ▪ 240V 1 phase, 2 wire 1 phase, 3 wire ▪ 120/240V 1 phase, 3 wire A B 1 phase, 2 wire, Wye ▪ 277V 1 phase, 2 wire N C 1 phase, 2 wire, Delta ▪ 480V 1 phase, 2 wire NEMA 3R ▪ Surface mount only. ▪ Finished with gray powder coat paint over phosphatized steel (ANSI 61). ▪ Bottom feed only, no knockouts ▪ Box sizes: 20” W x 7.7” D x 34.5”, 51.5”, 60.5” or 70.5 H (510 W x 195 D x 876, 1310, 1535 or 1791mm H). ▪ Enclosure and chassis mounting instructions are found in supplied literature ▪ Chassis mounts directly onto studs in the enclosure. ▪ Gasketed door has vault handle with lock. ▪ Door locks use key #2A1910-1. ▪ Circuit directory card is located on the inside of the door. A B C 1 phase, 3 wire, Delta ▪ 240/480V 1 phase, 3 wire A B C 3 ▪ ▪ ▪ phase, 4 wire, Wye 208Y/120V 3 phase, 4 wire 480Y/277V 3 phase, 4 wire 600Y/347V 3 phase, 4 wire A B N C 3 phase, 4 wire, Delta ▪ 240/120V 3 phase, 4 wire ▪ 480/240V 3 phase, 4 wire Busing Tin-plated copper with sufficient cross section to meet UL 67 temperature rise requirements. Distributed 1- & 3-phase busing All SCCPB branch disconnects can be mounted in any branch circuit position. phase, 3 wire, Delta 240V, 3 phase, 3 wire 480V, 3 phase, 3 wire 600V, 3 phase, 3 wire 240V, 3 phase, 3 wire, grounded B ▪ 480V, 3 phase, 3 wire, grounded B ▪ 600V, 3 phase, 3 wire, grounded B A B N C 3 ▪ ▪ ▪ ▪ A B C A B N 1 phase, 3 wire, Wye ▪ 208Y/120V 1 phase, 3 wire ▪ 480Y/277V 1 phase, 3 wire DC voltage 1 phase, 2 wire ▪ 125Vdc, 2 wire Single-phase 11-80 Three-phase Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog (Up to 125Vdc, MLO option only, SCCPB 40A or less.) C N +125Vdc • Revised • 02/26/12 Panelboards Dimensions and Panelboard Configurations NEMA 1 NEMA 3R Encl. Height Dimensions (inches) H HC MH CH DH RH SH DW D 33 33.0 N/A 29.0 26.0 28.9 25.0 2.0 20.0 5.7 50 50.0 N/A 43.0 40.0 37.9 39.0 3.5 20.0 5.7 59 59.0 N/A 52.0 49.0 46.9 48.0 3.5 20.0 5.7 69 69.0 N/A 62.0 59.0 56.9 58.0 3.5 20.0 5.7 33 33.0 34.5 35.5 26.0 28.9 25.0 2.0 20.0 6.3 50 50.0 51.5 52.5 40.0 37.9 39.0 2.0 20.0 6.3 59 59.0 60.5 61.5 49.0 46.9 48.0 2.0 20.0 6.3 69 69.0 70.5 71.5 59.0 56.9 58.0 2.0 20.0 6.3 PANELBOARDS Encl. Type 11 NEMA 1 and 3R Enclosure Dimensions Available panelboard configurations Based on enclosure height, panel amp rating and number of branch circuit positions Encl. height (inches) Panel amp rating 33” 30–200 30–60 70–200 50” 30–200 225–400A 70–200 30–200 59” 225–400A 69” 225–400A Branch positions Available configurations 18 · Main lug only, with or without feed-through lugs · Non-fused disconnect, no loadside options 30 · Main lug only, no loadside options 18 · 30 through 60A fused main disconnect with or without feed-through lugs or TVSS device 30 · 30 through 60A fused main disconnect with or without feed-through lugs or TVSS device 42 · 30 through 60A fused main disconnect with or without feed-through lugs or TVSS device 18 · 70 through 200A fused main disconnect with or without feed-through lugs or TVSS device 30 · 70 through 200A fused disconnect with or without feed-through lugs 18 · Main lug only with TVSS device · Non-fused disconnect, with feed-through lugs or TVSS device 30 · Main lugs only, with feed-through lugs or TVSS device · Non-fused disconnect, with or without feed through lugs 42 · Main lug only, with or without feed-through lugs or TVSS device · Non-fused disconnect, with or without feed-through lugs 18 · Main lug only, with ot without feed through lugs or TVSS device · Non-fused disconnect, with or without feed-through lugs 30 · Main lug only, with or without feed-through lugs 30 · 70 through 200A fused main disconnect, with TVSS device 42 · 70 through 200A fused main disconnect with or without feed-through lugs or TVSS device 42 · Non-fused disconnect with TVSS device 18 · Main lug only with loadside disconnect · Non-fused disconnect, with TVSS device · 225 through 400A fused disconnect with or without feed-through lugs or TVSS device 30 · Main lug only, with TVSS device · 225 through 400A fused disconnect, with no loadside options 42 · Main lug only, with or without feed-through lugs or TVSS device · Non-fused disconnect, with no loadside options 18 · Non-fused disconnect, with loadside disconnect 30 · Main lug only with loadside disconnect · 225 through 400A fused disconnect with feed-through lugs or TVSS device 42 · Non-fused disconnect, with or without feed through lugs or TVSS device · 225 through 400A fused main disconnect, with or without feed-through lugs or TVSS device Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 11-81 Panelboards PANELBOARDS 11 NEMA 1 and NEMA 3R Dimensions NEMA 1 Enclosures and Interior 0.3 21 (7/8, 1-1/8) Concentric KO 2.9 3.1 (1-3/4, 2, 2-1/2, 3, 3-5/8, 4-1/8) Concentric KO 1.5 2.2 1.1 7.4 0.5 Knockout Endwall Blank Endwall Enclosures Available with 2 Blank, 2 Knockout, or 1 Each Endwall DETAIL A 11.3 Flush Mount DW + 3.0 Flush Mount DW + 3.0 Surface Mount DW Surface Mount DW SH A Ground Flush Mount H + 3.0 Door Lock Neutral MH CH RH Surface Mount H H DH Spare Fuse Compartment 16.0 2.0 20.0 D Box with Interior Front View (Door in Door Option Shown on Right) Side View of Box 0.2 NEMA 3R Enclosures Interior same as NEMA 1 0.25 Mounting Hole Emboss 0.5 DETAIL B SCALE 1 : 4 7.68 Top End Wall (No Knockouts) D B 0.65 SH 2.0 0.6 2X MH HC H Box Interior Same as NEMA 1 13.0 DW Front View Bottom End Wall (No Knockouts) 11-82 Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog Side View Panelboards Fuse Curves 11 PANELBOARDS Time-Current Characteristic Curves– Average Melt Current Limitation Curves Siemens Industry, Inc. SPEEDFAX™ 2011 Product Catalog 11-83