STANDARD ENGINEERING DETAILS Part 1 – Paving & Drainage Index to Sheets SHEET TITLE Supplementary Details for Manholes and Inlets Driveways: Residential and Commercial Approaches Typical Roadway Sections Pavement and Milling – Street Restoration Curb Ramp Notes and Details Curb Ramp Details A Curb Ramp Details B Curb Ramp Details C Curb Ramp Details D Dumpster/Compactor Pad Details ENGINEERING BUREAU • PUBLIC WORKS DEPARTMENT No. 1 2 3 4 5 5A 5B 5C 5D 6 CITY HALL • P.O. BOX 4990 • 400 SOUTH ORANGE AVENUE • ORLANDO, FLORIDA 32802-4990 PHONE 407-246-3267 • FAX 407-246-2892 NOTES (TOPS, FRAMES, AND COVER) 1. All steel bars shall have 1 1/4 " minimum cover unless otherwise shown and shall be hooked where indicated. Washer Welded To Smooth Bar Or Nut & Washer On Threaded 2. Manhole top Type 7 slabs shall be of Class II concrete. Jam Nut Or Spot Weld With Single Nut & Washer For Standard Structures; Concrete as specified in ASTM C-478 may be used for precast units; Structures Manhole top Type 7 slabs may be of cast-in-place or precast construction. The optional key is for precast tops and in lieu of dowels. Frame and slab openings are to be omitted when top is used over a junction box. " 7 n. i M 3" Frames 12" Manhole top Type 8 may be of cast-in-place or precast concrete construction. For concrete construction, the Approved Alternate Other types of ladder bars appearing on (Plain Bars, Nuts & the Florida Departments of Transportation Washers Hot Galvanized List" may be used. "Qualified Products For Alt. G Structure) be in accordance Installation shall manufacturers with the ladder bar recommendations. " -4 ’ 1 concrete and steel reinforcement shall be the same as the supporting wall unit. Note: Ladder bars are required only when called for in the plans. 1" Dia. Plain Bars Or can be adjusted with from one to six courses of brick. 4. Nut & Washer For Alternate G see General Note No. 2. 1" Dia. Plain Bars An eccentric cone may be used. Or Approved Alternate 4" 3. Bar For Standard Structures; Jam Nut With Single Nut & Washer For Alternate G Structures 5. Manhole tops shall be secured to structures by optional construction joints as shown on Sheet 3 of 6. Ladder Shall Extend From 2’ Above Floor Up 7" 24" 2" Half Wall Thickness PICTORIAL VIEW Min. OPTIONAL BAR TYPES LADDER BARS FOR STRUCTURES OVER 10’ IN DEPTH REX M PA REX M PA D 400 D 400 EN124 R TO E RMSEW DIN I N OA G M TO E RMSEW S R EN124 S A D E FR ANCE H20 NG LO ADI H20 VARIES L OVERLAP NOT FOR USE IN ASPHALT PAVEMENT AREA VARI ES DEDICATED PUBLIC R.O.W.: VARI ES MANHOLE FRAME & COVER FOR USE IN PRIVATE PROPERTY: VARI ES N.T.S. MANHOLE FRAME & COVER FOR USE IN #5 SLAG 1’-0" XG700 MIRAFI FILTER FABRIC MANHOLE COVERS CMP (PERF.) SPECIFICATIONS VARI ES 1. PAMREX or similar approved Manhole Cover and Frame 2. Covers and Frames shall be manufactured from Ductile Iron in accordance with ISO 1083 3. Covers to be hinged and incorporate a 90^ blocking system to prevent accidental closure. EXFILTRATION TRENCH SECTION N.T.S. 4. Covers shall be one-man operable using standard tools and shall be capable of withstanding an average load of 120,000 lbs. 5. Frames shall be circular and shall incorporate a seating gasket; Frame depth shall not exceed 4". 6. The Flange shall incorporate bedding slots and bolt holes. 7. All components shall be black coated. F RLA ND O O, F OR L "T L" IDA C IT Y O 8. Manhole cover and frame for use in asphalt paved roadways shall be US Foundry 420JT or 120JT. H E FILENAME: CATEGORY: C SCALE: 2/25/2009 DRAWN BY: GAP/EL IF T IT Y B EAU DRAIN DRAINAGE.DGN DATE: U CE AN FR N.T.S. APPROVED BY: RMH ENGINEERING STANDARDS MANUAL DEPARTMENT OF PUBLIC WORKS PROJECT / CONSTRUCTION MANAGEMENT BUREAU CITY OF ORLANDO, FLORIDA TITLE: SUPPLEMENTARY DETAILS FOR MANHOLES AND INLETS SHEET 1 SOD PER APPROVED PLAN 6" 2’ 24’ TYPE "F" CURB & GUTTER 2’ 6" C /FT. 02’ 0. MINIMUM 8" COMPACTED BASE MINIMUM 12" COMPACTED SUB-BASE FINAL LAYER THICKNESSES TO BE DETERMINED BY THE ENGINEERS PAVEMENT DESIGN CALCULATIONS. TYPICAL ROADWAY SECTION OF CONST. N.T.S. R/W LI MI TS 5’ 2’ 26’ 13’-3" 26’ 5’ 2’2’ 22’ 2’-3" /FT. 03’ 0. /FT. 02’ 0. 2’-3" 6" 6" 0. 02’ /FT. 11’-9" 2’ 0. 03’ /FT. /FT. 02’ 0. 0. 02’ /FT. SOD SEED SEED 6" 2’ LEVEL SOD 6" 2’ LEVEL SOD 6" 6" 4" CONC. S/W 2’ LEVEL SOD 4" CONC. S/W 2’ LEVEL SOD MINIMUM 12" COMPACTED SUBGRADE MINIMUM 12" COMPACTED SUBGRADE STABILIZED SUBGRADE LBR 40, TYP. TYPE "F" CURB & GUTTER STABILIZED SUBGRADE LBR 40, TYP. TYPE "E" CURB & GUTTER RLA ND O O, L" "T N.T.S. IDA C IT Y TYPICAL DIVIDED ROADWAY SECTION F OR L F O FINAL LAYER THICKNESSES TO BE DETERMINED BY THE ENGINEERS PAVEMENT DESIGN CALCULATIONS. H ROADWAY.DGN E FILENAME: CATEGORY: C 6/3/2009 DRAWN BY: EL/DG IF T IT Y B EAU ROADWAY SCALE: DATE: U R/W 13’-3" 2’2’ LI MI TS 11’-9" OF CONST. 120’ WIDE R/W STANDARD CLEARING & GRUBBING N.T.S. APPROVED BY: RMH ENGINEERING STANDARDS MANUAL DEPARTMENT OF PUBLIC WORKS PROJECT / CONSTRUCTION MANAGEMENT BUREAU CITY OF ORLANDO, FLORIDA TITLE: TYPICAL ROADWAY SECTIONS SHEET 3 CONTAINMENT WALL (COMPACTOR PAD ONLY) FENCE SHALL BE CHAIN LINK WITH RIBBON SLEEVE OR WOODED PRIVACY. PAD TO BE PLACED AT GROUND GATES SHALL BE LOCKABLE WITH ANGLE OF PAD WITH DRIVING LANE 100^ - 120^ SWING. TO BE PLACED SHALL ALLOW FOR A STRAIGHT-LINE OUTSIDE OF THE PAD. MANEUVERING DISTANCE OF 50 FT. LEVEL, NOT ELEVATED 6’ -0" GATE REQUIRES POSITIVE STOP TO HOLD GATE OPEN AND CLOSED ANGLE OF PAD WITH DRIVING LANE SHALL ALLOW FOR A STRAIGHT-LINE MANEUVERING DISTANCE OF 50 FT. 12 ’ I N L T E E A R R I O A N R C E 8" 25 ’C LE AR 6’ -0" C I NS I DE EXPANSION JOINT 6’ -0 " EXPANSION JOINT " -0 6’ R EA OM CL FR " 0 L H 0’ AL 1 PT DE O W DS R DE E T LA I NS AT BOL I G OR (OPTIONAL) BOLLARDS AREA 8" ASPHALT OR CONCRETE COMPACTOR PAD IF USED, BOLLARDS TO BE PLACED ON FOUR FOOT CENTERS ACROSS BACK OF ENCLOSURE N.T.S. CONTAINMENT WALL DETAIL N.T.S. M MU NI NG MI ’ RI 50 VE U NE MA 50 ’M I MA NI MU NE M UV ER I NG 8" SECTION VENT STACK AREA PITCHED AWAY 3’-0" CLEARANCE FROM DRAIN BETWEEN 3000 PSI CONCRETE " REBAR - 12" OC EW (OR 6" x 6" - 10 x 10 WIREMESH) AREA PITCHED (I NTERI OR CLEARANCE) 6" 12’ -0" MI N (SI NGLE) N.T.S. 24’ -0" MI N (DOUBLE) COMPACTOR AND FENCE HEAVY DUTY SCREENED DRAIN W/ SEDIMENT BUCKET DUMPSTER PAD TOWARD DRAIN (COMPACTOR ONLY) HEAVY DUTY SCREENED DRAIN W/ SEDIMENT BUCKET (COMPACTOR ONLY) PLACED TO ONE SIDE AND PAD SLOPED APPROPRIATELY OIL/SAND SEPARATOR 4" SCHEDULE 40 PVC TO PERMIT DRAIN TO BE P-TRAP CLEARED W/O REMOVING PAD SECTION W/ SANITARY SEWER CONNECTION VENT LINE THE UNIT WHEN DRAIN & TRENCH BECOMES BLOCKED DRAIN F RLA ND O O, F OR L "T L" IDA C IT Y O N.T.S. E U H C SHEET 6 IF T IT Y B EAU DEPARTMENT OF PUBLIC WORKS PROJECT / CONSTRUCTION MANAGEMENT BUREAU 6’-0" NOTE: SANITARY SEWER CONNECTION NOT ALLOWED FOR DUMPSTER APPLICATION CITY OF ORLANDO, FLORIDA TITLE: DUMPSTER AND COMPACTOR PAD DETAILS 25’-0" CLEAR INSIDE FILENAME: CATEGORY: DUMPSTER.DGN ENGINEERING STANDARDS MANUAL DATE: 12/19/2008 DRAWN BY: EL/WAS/DSG COMPACTOR PAD PLAN GENERAL N.T.S. SCALE: NONE APPROVED BY: RMH STANDARD ENGINEERING DETAILS Part 2 - Wastewater Index to Sheets SHEET TITLE Lift Station Civil Lift Station Antenna Mast Lift Station Electrical Lift Station Electrical Lift Station Electrical Electrical Ground Electrical Ground Electrical Ground Sanitary Sewer Structures Sanitary Sewer Structures Sanitary Sewer Structures No. 7 8 9 10 11 12 13 14 15 16 17 ENGINEERING BUREAU • PUBLIC WORKS DEPARTMENT CITY HALL • P.O. BOX 4990 • 400 SOUTH ORANGE AVENUE • ORLANDO, FLORIDA 32802-4990 PHONE 407-246-3267 • FAX 407-246-2892 GENERAL NOTES: AS REQUIRED FOR GRADE 3) MANHOLES GREATER THAN 5’ DIA. SHALL BE PER ARTICLE 27. MAX. HEIGHT) JOINT SEALER SEE DETAIL 24" ON ALL JOINTS ON ROUND AIR RELEASE AND ROUND MANHOLE STRUCTURES. 7) RAPID SEAL MUST BE USED IN ACCORDANCE WITH MANUFACTURER’S FRAMES BEDDED IN MORTAR INTERIOR COATING 0.8 DIA. 1 MAX. DI A. CLEANOUT CLEANOUT CAP FINISHED GRADE PAVEMENT 3’ -0" +/- CLEANOUT MIN. 9" COMPACTED 8" MIN. 4" MIN. 5’ CURB RIGHT ANGLE STRAIGHT THROUGH BASE SECTION 6" MIN. FILL BENCHING CRUSHED STONE 24" DEPARTMENT LINE S/W 4" 1’6" MIN. BUILDING PROPERTY 5’ CONCAVE APRON PRECAST MONOLITHIC 12 CONCRETE 3’0" MAX. INSPECTED BY ENGINEERING DEPARTMENT 8" MIN. FLEXIBLE PIPE CONNECTOR RECOMMENDATIONS. 4 COURSES (MAX.) INSPECTED BY 4’ OR 5’ DIA PER SPEC. 2 COURSES OF BRICK (MIN.) PLAN VIEW RAPID SEAL TYPICAL EXTERIOR AND BLDG. JOINTS, CASTINGS AND RISER RINGS: USE BENDS AS NEEDED MANHOLE WALL (FDOT #57) M IN. 6) RAPID SEAL MUST BE USED ON ALL 12" 2’ - 5" M IN. ALL FRAME TYPES. OR APPROVED EQUAL. MANHOLE WALL 4" ON ALL STORM MANHOLES. 5) MANHOLE COVERS TYPICAL FOR MANHOLE FRAME & COVER (U.S.F. 420G-ORS) 4" OR 6" SERVICE LATERAL ADJUSTMENT (2" MIN. - 12" 4) SUBSTITUTE "STORM" FOR "SANITARY" SET COVERS FLUSH IN PAVED AREAS BLDG. RINGS OR BRICK COLLAR 2) FLAT SLAB MANHOLE TOP MAY BE USED W/ APPROVAL BY ENVIRON. SVC. DEPT. & AT ELEVATIONS IN UNPAVED AREAS LINE S/W PRECAST CONCRETE GRADE MANHOLE FRAME AND COVER PROPERTY 5’ SEWER MAIN TYPE I - HEAVY DUTY 1) SEE ARTICLE 27 "SAN. SEWER GRAVITY" OF CITY OF ORLANDO WASTEWATER SPECS. +/0 % . 1 PE SLO "FERNCO" COUPLING TEE OR EQUAL SEWER MAIN 48" DIA SHALLOW PRECAST CONCRETE MANHOLE PVC 4’ OR 5’ DIA BITUMASTIC COATING PER SECTION 27.05(E) N.T.S. PROFILE BELL-END SEE JOINT DETAIL (TYP.) END OF CHANNEL FOR TERMINAL PIPE PIECES 6" WIDE (TYPICAL) HALF-PIPE CHANNEL FOR FLOW THROUGH MANHOLE MAY BE USED 8" MIN (0-10’ DEPTH) INSTALLATION OF LATERAL CONNECTIONS GENERAL NOTES: MANHOLE N.T.S. 1. LATERAL INSTALLATION SHALL BEGIN AT A CITY SEWER CONNECTION POINT AND SHALL BE CONSTRUCTED JUNCTIONS BACK TO THE BUILDING AT A SLOPE SUFFICIENT TO YIELD A FLOW VELOCITY OF 2 FEET PER SECOND. 10" MIN (GREATER THAN 10’ DEPTH) N.T.S. TROWEL-FINISH 2. STREETSIDE CLEANOUT SHALL BE FORMED BY INSTALLING A TEE AND A BEND. CONCRETE WRAPID SEAL TYPICAL TWO-WAY CLEANOUTS ARE ACCEPTABLE. NO WYE CONNECTIONS WILL BE ALLOWED. BENCHING FLOW CHANNEL DETAIL - SANITARY SEWERS 3. BUILDING-SIDE CLEANOUT SHALL BE INSTALLED WITHIN 5 FEET OF THE BUILDING. CONCRETE FILL BENCHING STUB OUT FOR 12 N.T.S. FUTURE USE S L O P E D A. 1 I GROOVE TO BE FORMED WITH AN ACCURATE 4. THE PIPE SECTION BETWEEN THE STREETSIDE CLEANOUT AND THE BUILDING CLEANOUT SHALL BE INSTALLED E P O L S WITH AS FEW BENDS AS POSSIBLE. 6" MIN. BELL RING. FORM SEAL WITH COAL TAR MASTIC S L O P E E P O L S PLUG 6. LATERAL CONNECTION OF LIKE MATERIALS SHALL UTILIZE REDUCERS AND/OR TRANSITION PIECES, ETC. 2. DEPTH OF ALL CHANNELS TO BE 80% OF 2" TYPICAL 8" MIN. 9" O.C. EACH WAY TRANSITION GASKETS AND/OR FERNCO ADAPTERS ARE ACCEPTABLE. MANHOLE UNLESS OTHERWISE INDICATED. 3" CL 4" MIN. #4 BARS 5. LATERAL CONNECTIONS OF DISSIMILAR MATERIALS SHALL BE CONNECTED UTILIZING TRANSITION ADAPTERS. 1. MAINTAIN DESIGN SLOPE ACROSS " DEWITT NO. 10 OR APPROVED EQUAL OR JOINT SAME AS DETAIL FOR RISER SECTION 90^ BENDS IN THIS SECTION SHALL NOT BE ALLOWED. ALL BENDS, REGARDLESS OF THE ANGLE, SHALL HAVE A CLEANOUT. NOTES: 0.8 DIA. 7. FIELD SOLVENT JOINTS ARE ACCEPTABLE. PIPE DIAMETER. CONCRETE BASE 8. CLEANOUT CAPS LOCATED IN DRIVEWAYS AND OTHER PAVED AREAS SHALL BE CAST-IN-PLACE RINGS WITH METAL COVERS STAMPED WITH THE WORD "SEWER", ALL OTHERS SHALL BE PVC WITH AN INVERTED HEX-NUT. 3. FINISH OF ALL CHANNELS TO ALLOW PRE-APPROVAL BY CITY ENGINEER ONLY. SMOOTH FLOW. COMPACTED SUBGRADE OR 9" OF CRUSHED ROCK ROUND OR RECTANGULAR CONCRETE STRUCTURE 9. THERE SHALL BE NO DETECTABLE LEVEL OF INFILTRATION OR EXFILTRATION FROM THE SANITARY SYSTEM AT THE TIME OF INSPECTION. ANY EVIDENCE OF LEAKAGE MUST BE CORRECTED PRIOR TO ACCEPTANCE BY THE CITY. 4. CONCRETE BENCH SHALLBE POURED BEFORE SHUTTING DOWN DEWATERING OPERATIONS TO PREVENT FLOTATION. PRECAST CONCRETE MANHOLE N.T.S. 10. REFERENCE ARTICLE 27 "GRAVITY SANITARY SEWERS" OF THE ENGINEERING STANDARDS MANUAL FOR SPECIFIC CODE REQUIREMENTS. TYPICAL MANHOLE PLAN 5. BRICK MAY BE USED TO BUILD UP N.T.S. 11. USE 4" OR 6" PVC (SDR35) PIPE FOR LATERALS AS NOTED ON DRAWINGS AND IN SPECIFICATIONS. CONCRETE BENCH. 12. LATERAL LOCATION NO MORE THAN 5’ FROM PROPERTY LINE NOT IN DRIVEWAY OR APRON. PRECAST CONCRETE GRADE RINGS OR BRICK COLLAR AS REQUIRED FOR TYPE II - HEAVY DUTY GRADE ADJUSTMENT (2" MIN. - 12" MAX. MANHOLE FRAME AND COVER HEIGHT) MANHOLE STRUCTURE P V A T R I E KORBAND (OR EQUAL) TOP SLAB 8" PLASTIC D 400 EN124 2’ - 0" FINISHED GRADE AT R/W LINE PRE-PRIMED JOINT PIPE FILLER NOTE: SEE ARTICLE 27, "SANITARY SEWER-GRAVITY" INSIDE WRAPPER OF CITY OF ORLANDO, ENGINEERING (REMOVED) A D E I N STANDARD MANUAL. R E G M S DIA. AS NOTED A N 3’ TO 4’ MREX PA PRECAST FLAT ITA W N RY SE ADI O S R E L FR ANCE H20 W COMPLETED E JOINT OUTSIDE WITH SQUEEZE BACKFILL PIPE CLAMP OUT (95% PROCTOR STANDARD) PRIVATE COVER CITY COVER 4" D.I. FLEXIBLE CONNECTOR JOINT DETAILS 3. 94" PIPE ZONE 6" TYPE B - FLAT TOP SLAB N.T.S. N.T.S. MIN. ABOVE ELBOW TYPICAL MANHOLE CONNECTION Passage Dia 24" 4" TO 12" MAX. FILL MATERIAL BETWEEN LATERAL N.T.S. AND TRENCH WALL. Outside Dia 33,46" BUILT ONLY WITH PREAPPROVAL OF WASTEWATER BUREAU 24" MANHOLE COVER PIPE ZONE PER 25" TO BE ONLY USED AS DIRECTED BY WASTEWATER DESIGN STAFF 23" OF Y CI T 8" 2’ - 6" COVER SHALL BE HINGED & INCORPORATE SWEEP SECTION (4"D.I.) CLASS I, II, III TEE FITTING FOR D.I. SEWER PRIVATE 7" FROM DUCTILE IRON IN ACCORDANCE WITH ISO 1083 BANANA BEND OR 10" DIA. ASTM D 2321 L DO 1’ - 8 3/4 " COVER & FRAMES SHALL BE MANUFACTURED OR N MANHOLE COVER & FRAME SHALL BE PAMREX 24" 20 5/8 " A TOP SLAB 2" PRECAST FLAT (10"x10"x4"D.I.) 1’ -0" MANHOLE FRAME AND COVER 3" N.T.S. TYPE III - HEAVY DUTY NOTE: A 90 DEGREE BLOCKING SYSTEM TO PREVENT 24 1/2 " ACCIDENTAL CLOSURE. COVERS SHALL BE ONE MAN F FRAME - TYPE II 1’ - 9 1/2 " OPERABLE USING STANDARD TOOLS & SHALL BE 36" CLEANOUT LOCATIONAS INDICATED IN A LO R ID 40" ATTACHED ELASTOMER SEATING GASKET FOR INFILTRATION CONTROL & TRAFFIC SHOCK. 4- 1/2 " 1- 3/4 " FRAMES SHALL BE CIRCULAR WITH A 24" CLEAR OPENING & SHALL INCORPORATE A 360^ MECHANICALLY CLASS I MAT. BEDDING SHALL BE 95% PROCTOR FRAME - TYPE I TALL RISER CONNECTION N.T.S. (FOR DEPTH TO INVERT OF 10 FT. OF GREATER) THE HINGE BOX SHALL INCLUDE A SELF-CLEANING 2" DUAL WIPER INFILTRATION PLUG. THE FRAME DEPTH OF SHALL NOT EXCEED 4 INCHES. THE FLANGE SHALL BUREAU OF WASTEWATER PREAPPROVAL NEEDED DO CI T N SANITARY FRAME - TYPE III NOT FOR USE IN ASPHALT PAVEMENT AREA. MANHOLE RING AND COVER IN THE ROADWAY SURFACE SHALL BE U.S. FOUNDRY 420JT OR APPROVED EQUAL. N.T.S. A LO R ID TYPICAL MANHOLE COVER PAMREX IS AVAILABLE FROM PORTER ASSOCIATES, INC & O-RING GASKET MACHINED SURFACES MANHOLE FRAME & COVER: (U.S.F. 420G-ORS) OR F RLA ND O O, F "T L" fax: (352) 589-5525 DA I C I TY APPROVED EQUAL OR L N.T.S. PHONE: (352) 589-5988 3/4 " DOVETAIL GROOVE F O 2’ - 1" N.T.S. L COVER WEIGHT: 122 LBS TOTAL WEIGHT: 195 LBS 22 3/4 " A 1’ - 9 1/2 " ALL COMPONENTS SHALL BE BLACK COATED. FRAME WEIGHT: 73 LBS H CATEGORY: DATE: SCALE: E FILENAME: U N.T.S. OR Y 1’ - 8" INCORPORATE BEDDING SLOTS, BOLT HOLES & LIFTING EYES. TYPE C - FLAT TOP SLAB SERVICE CONNECTION DETAIL N.T.S. CAPABLE OF WITHSTANDING A TEST LOAD OF 120,000 LBS. DIA. AS NOTED C I TY UT B EA F I DEPARTMENT OF PUBLIC WORKS WASTEWATER BUREAU CITY OF ORLANDO, FLORIDA WASTEWATER 9/22/2009 DRAWN BY: N.T.S. APPROVED BY: ENGINEERING STANDARDS MANUAL TITLE: SANITARY SEWER STRUCTURES SHEET 15 City of Orlando Wastewater Division Reclaimed Water System Design and Construction Specifications Index of Sheets Sheet No. RGN-1 RGN-2 RGN-3 RGN-4 RGN-5 R-01 R-02 R-03 R-04 R-05 R-05A R-06 R-07 R-08 R-09 R-10 R-11 R-12 R-13 R-14 R-15 R-16 R-17 R-18 R-19 R-20 R-21 R-22 R-23 R-24 R-25 R-26 R-27 R-28 R-29 R-30A R-30B R-30C R-30D R-30E R-30F R-30G R-30H R-NEW Title /Description Reclaimed – General Notes Reclaimed – General Notes (Cont’d) Reclaimed – General Notes (Cont’d) Reclaimed – General Notes (Cont’d) Reclaimed – General Notes (Cont’d) Sign Post Installation Typical Residential Utility Layout – Single Service Connections Residential Service Connections Commercial Above Ground 2” Reclaim Water Meter Installation Detail Commercial Service Connection – Above Grade – 3” And Larger Commercial Service Connection – Above Grade – 2” Or Smaller General Slab Design & Bollards Pipe Supports Pressure Gage Installation Trenching with Type A Bedding Trenching with Type B Bedding Trenching in Paved Areas Concrete Pipe Encasement Casing Pipe Spacers Casing Pipe Horizontal Separation Requirements (F.A.C. Rule 62-555.314) Vertical Separation Requirements Crossings or Obstructions Utility Conflicts Air Release Valve Installation – Above Grade Combination Air and Vacuum Release Valve – Below Grade Buried Valve Box Setting Valve Box Collar Detector Ball Location Detail Pipe Identification Pipe Warning Tape Restrained Ductile Iron Joints 3” - 24” Standard Tapping Assembly Dead End Blow-Off Valve Installation Temporary Blow-Off Installation Silt Fence Curb and Gutter Sediment Barrier Silt Fence Drop Inlet Sediment Barrier Curb Inlet Sediment Barrier Attaching Two Silt Fences / Proper Placement of Straw Bale Barrier in Drainage Way Straw Bale Barrier Drop Inlet Sediment Barriers Filter Fabric Drop Inlet Sediment Filter Non-Commercial Reclaim Water Meter Installation Detail for 2” COMMERCIAL ABOVE GROUND RECLAIM WATER METER INSTALLATION DETAIL FOR 2" Fig 264: Loads (lbs) * Weight (lbs) * Dimensions (in) Weight Pipe Size 2.5 3 3.5 4 5 6 8 10 12 14 16 18 20 24 30 32 36 E Complete Saddle Only 9.0 9.2 9.4 15.0 16.7 17.7 20.2 25.2 29.0 40.2 53.2 70.8 104.8 137.0 170.0 181.0 249.0 4.8 5.0 5.2 7.6 8.3 10.3 12.8 17.8 21.6 38.0 42.0 51.0 85.0 110.0 150.0 161.1 229.0 A B D 3.5 3.75 1.5 4 4.25 8.875 5.5 3 2.5 6.875 8.5 9.9375 10.9375 4 3 12.375 13.875 3.5 15.375 17.9375 6 21.3125 4 22.5 24.5 * The special cast iron reducer may be furnished with a hexed shaped smaller end. 2.5 Min Max 8 8.25 8.5 9.25 10 10.5 11.75 13.5 15 16.25 17.75 19.5 21 23.75 27 28.25 30.25 13 13.25 13.5 14 14.75 15.25 16.5 18.25 19.75 20.75 22.25 24 25.5 28.25 31.5 32.75 34.75 Width C 3 3.625 4.625 6.75 8.75 CONSULT MANUFACTURER FOR RESTRAINED LENGTHS FOR PVC PIPE.