Instruction Manual YOKOGAWA Model YTA80 Head-Mounted Fieldbus Temperature Transmitter IM 01C50C04-01E-E 3rd Edition FOUNDATION™ FIELDBUS TRANSMITTER YTA80 Contents Safety instruction..................................................................................3 Declaration of Conformity.....................................................................4 ATEX Documentation............................................................................6 Feature..................................................................................................7 Applications...........................................................................................8 Specifications........................................................................................9 Connections, input..............................................................................14 Connections, output............................................................................15 Block diagram.....................................................................................16 Bus installation....................................................................................17 Appendix:............................................................................................19 ATEX Installation YTA80QA01 ATEX Installation YTA80QA02 2 Safety instructions Ex installation: •For a safe installation of the YTA80 in hazardous area the following must be observed. The module must only be installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. •The sensor circuit is not infallibly galvanically isolated from the Fieldbus input circuit. However, the galvanic isolation between the circuits is capable of withstanding a test voltage of 500Vac during 1 minute. •Production year of the transmitters can be taken from the first 2 digits of the serial number. •There are no user serviceable parts inside the transmitters. •The transmitter YTA80/KS2 must be mounted in an enclosure in order to provide a degree of ingress protection of at least IP20. If the transmitter is installed in a potentially explosive atmosphere where equipment category 1G is required and if the enclosure in which the transmitter is mounted is made of aluminium, then the requirements of EN 50284, clause 4.3.1 must be taken into account. •YTA80/KS2 may only be installed in a potentially explosive atmosphere caused by the presence of combustible dust when mounted in a metal enclosure form B according to DIN 43729 that is providing a degree of ingress protection of at least IP 6X in accordance with EN 60529, that is suitable for the application and is correctly installed. •Cable entries and blanking elements shall be used that are suitable for the application and correctly installed. •For an ambient temperature ≥ 60°C, heat resistant cables shall be used with a rating of at least 20K above the ambient temperature. •The surface temperature of the enclosure is equal to the ambient temperature plus 20K, for a dust layer with a thickness up to 5 mm. •The transmitter YTA80/KS2 shall be mounted in an enclosure providing a degree of ingress protection of at least IP54 in accordance with EN 60529. •Provisions must be made to prevent the rated supply voltage being exceeded by more than 40%. 3 4 5 ATEX-Documentation This setion is only applicable to the countries in the European Union. GB All instruction manuals for ATEX Ex related products are available in English, German and French. Should you require Ex related instructions in your local language, you are to contact your nearest Yokogawa office or representative. DK Alle brugervejledninger for produkter relateret til ATEX Ex er tilgængelige på engelsk, tysk og fransk. Skulle De ønske yderligere oplysninger om håndtering af Ex produkter på eget sprog, kan De rette henvendelse herom til den nærmeste Yokogawa afdeling eller forhandler. I Tutti i manuali operativi di prodotti ATEX contrassegnati con Ex sono disponibili in inglese, tedesco e francese. Se si desidera ricevere i manuali operativi di prodotti Ex in lingua locale, mettersi in contatto con l’ufficio Yokogawa più vicino o con un rappresentante. E Todos los manuales de instrucciones para los productos antiexplosivos de ATEX están disponibles en inglés, alemán y francés. Si desea solicitar las instrucciones de estos artículos antiexplosivos en su idioma local, deberá ponerse en contacto con la oficina o el representante de Yokogawa más cercano. NL Alle handleidingen voor producten die te maken hebben met ATEX explosiebeveiliging (Ex) zijn verkrijgbaar in het Engels, Duits en Frans. Neem, indien u aanwijzingen op het gebied van explosiebeveiliging nodig hebt in uw eigen taal, contact op met de dichtstbijzijnde vestiging van Yokogawa of met een vertegenwoordiger. 6 SF Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet ovat saatavilla englannin-, saksan- ja ranskankielisinä. Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita omalla paikallisella kielellännne, ottakaa yhteyttä lähimpään Yokogawa-toimistoon tai -edustajaan. P Todos os manuais de instruções referentes aos produtos Ex da ATEX estão disponíveis em Inglês, Alemão e Francês. Se necessitar de instruções na sua língua relacionadas com produtos Ex, deverá entrar em contacto com a delegação mais próxima ou com um representante da Yokogawa. F Tous les manuels d’instruction des produits ATEX Ex sont disponibles en langue anglaise, allemande et française. Si vous nécessitez des instructions relatives aux produits Ex dans votre langue, veuillez bien contacter votre représentant Yokogawa le plus proche. D Alle Betriebsanleitungen für ATEX Ex bezogene Produkte stehen in den Sprachen Englisch, Deutsch und Französisch zur Verfügung. Sollten Sie die Betriebsanleitungen für Ex-Produkte in Ihrer Landessprache benötigen, setzen Sie sich bitte mit Ihrem örtlichen Yokogawa-Vertreter in Verbindung. S Alla instruktionsböcker för ATEX Ex (explosionssäkra) produkter är tillgängliga på engelska, tyska och franska. Om Ni behöver instruktioner för dessa explosionssäkra produkter på annat språk, skall Ni kontakta närmaste Yokogawakontor eller representant. GR ATEX Ex . Ex , Yokogawa . Feature FOUNDATION™ FIELDBUS TRANSMITTER - YTA80 • FOUNDATION™ Fieldbus ver. ITK 4.6 • FISCO-certified • Linkmaster capability with F.F. Application: • Linearised temperature measurement with RTD or TC sensor. • Difference, average or redundancy temperature measurement with RTD or TC sensor. • Linear resistance, potentiometer and bipolar mV measurement. Technical characteristics: • • • • • • Bus transmitter with FOUNDATIONTM Fieldbus communi­cation. The simulation mode function can be activated by way of a magnet. Polarity-independent bus connection. 24 bit A/D converter ensures high resolution. FOUNDATION™ Fieldbus function blocks: 2 analogue and 1 PID. FOUNDATION™ Fieldbus capability: Basic or LAS. Mounting / installation: • For DIN form B sensor head mounting. In non-hazardous areas the YTA80 can be mounted on a DIN rail with a special fitting. 7 Applications 8 Specifications : /KN2 YTA80 : /KS2 *NB! Please remember to order sim pin type 8422 if the simulation mode function is to be used. Electrical specifications: Specifications range: -40°C to +85°C Common specifications: Supply voltage, DC Standard, YTA80/KN2.............................. 9.0...32 V ATEX, YTA80/KS2.................................... 9.0...30 V In FISCO installations.............................. 9.0...17.5 V Consumption................................................ < 11 mA Max. current increase in the event of an error................................ < 7 mA Isolation voltage, test................................... 1.5 kVAC for 60 s Isolation voltage, operation.......................... 50 VRMS / 75 VDC Warm-up time............................................... 30 s Signal / noise ratio....................................... min. 60 dB Response time (programmable)................... 1...60 s Updating time............................................... < 400 ms Execution time, analogue input.................... < 50 ms Signal dynamics, input................................. 24 bit Calibration temperature............................... 20...28°C Accuracy, the greater of general and basic values: General values Input type All Absolute accuracy Temperature coefficient ≤ ±0,05% of reading ≤ ±0.002% of reading / °C 9 Basic values Basic accuracy Temperature coefficient Pt100 and Pt1000 ≤ ±0.1°C ≤ ±0.002°C / °C Ni100 ≤ ±0.15°C ≤ ±0.002°C / °C Cu10 ≤ ±1.3°C ≤ ±0.02°C / °C Lin. R ≤ ±0.05 Ω ≤ ±0.002 Ω / °C Input type Volt ≤ ±10 µV ≤ ±0.2 µV / °C TC type: E, J, K, L, N, T, U ≤ ±0.5°C ≤ ±0.010°C / °C TC type: B, R, S, W3, W5 ≤ ±1°C ≤ ±0.025°C / °C EMC immunity influence................................. < ±0.1% of reading Extended EMC immunity: NAMUR NE 21, A criterion, burst................... < ±1% of reading Vibration....................................................... Lloyd’s specification no. 1........................... Humidity....................................................... Dimensions................................................... Tightness (enclosure / terminal)................... Weight.......................................................... Electrical specifications, input: IEC 60068-2-6 and 60068-2-64 4 g / 2...100 Hz < 95% RH (non cond.) Ø 44 x 20.2 mm IP68 / IP00 55 g RTD and linear resistance input: RTD type Min. value Max. value Norm Pt25...Pt1000 Ni25...Ni1000 Cu10...Cu1000 Lin. resistance Potentiometer -200°C -60°C -50°C 0Ω 0Ω +850°C +250°C +200°C 10 kΩ 100 kΩ IEC60751/JIS C 1604 DIN43760 α = 0.00427 - Cable resistance per wire............................. Sensor current.............................................. Effect of sensor cable resistance (3- / 4-wire). Sensor error detection................................. Short circuit detection.................................. 10 50 Ω Nom. 0.2 mA < 0.002 Ω / Ω Yes < 15 Ω TC input: Type Min. value Max. value Norm B E J K L N R S T U W3 W5 Ext. CJC +400°C -100°C -100°C -180°C -200°C -180°C -50°C -50°C -200°C -200°C 0°C 0°C -40°C +1820°C +1000°C +1200°C +1372°C +900°C +1300°C +1760°C +1760°C +400°C +600°C +2300°C +2300°C +135°C IEC60584-1 IEC60584-1 IEC60584-1 IEC60584-1 DIN 43710 IEC60584-1 IEC60584-1 IEC60584-1 IEC60584-1 DIN 43710 ASTM E988-90 ASTM E988-90 IEC60751 Cold junction compensation (CJC).............. Sensor error detection................................. Sensor error current: when detecting........................................ else........................................................... Short circuit detection.................................. < ±0.5 °C Yes Nom. 4 μA 0 μA < 3 mV Voltage input: Measurement range..................................... -800...+800 mV Min. measurement range (span).................. 2.5 mV Input resistance............................................ 10 MΩ Output: FOUNDATIONTM Fieldbus connection: FOUNDATIONTM Fieldbus protocol.................. FOUNDATIONTM Fieldbus protocol standard... FOUNDATIONTM Fieldbus capability................ FOUNDATIONTM Fieldbus version.................... FOUNDATIONTM Fieldbus function blocks....... FF protocol FF design specifications Basic or Master ITK 4.6 2 analogue and 1 PID 11 Ex data: Signal output / supply, terminal 1 to 2: Max. ambient temperature depends on the Po of the connected barrier. YTA80 / KS2 Class I, Zone 0, EEx ia IIC, Entity / Fisco Unit U i Ii P i L i C i T1...T4 T5 T6 Barrier where Barrier where Po < 0.84 W Po < 1.3 W 30 VDC 30 VDC 120 mADC 300 mADC 0.84 W 1.3 W 1 µH 1 µH 2.0 nF 2.0 nF Tamb. < 85°C Tamb. < 75°C Tamb. < 70°C Tamb. < 65°C Tamb. < 60°C Tamb. < 45°C Suitable for Suitable for FISCO systems FISCO systems 17.5 VDC 250 mADC 2,0 W 1 µH 2.0 nF Tamb. < 85°C Tamb. < 60°C Tamb. < 45°C 15 VDC 900mADC 5.32W 1 µH 2.0 nF Tamb. < 85°C Tamb. < 60°C Tamb. < 45°C YTA80 / KS2 YTA80 / KN2 Class I, Zone 1, EEx ib IIC, Entity / Fisco Zone 2, EEx nA [L] IIC Unit Barriere where Po < 5.32 W FISCO segment coupler No barrier U i Ii P i L i C i T1...T4 T5 T6 30 VDC 250 mADC 5.32 W 1 µH 2.0 nF Tamb. < 85°C Tamb. < 75°C Tamb. < 60°C 17.5 VDC All All 1 µH 2.0 nF Tamb. < 85°C Tamb. < 75°C Tamb. < 60°C 32 VDC 12 Tamb. < 85°C Tamb. < 75°C Tamb. < 60°C Ex / I.S. data: Sensor input, terminal 3, 4, 5 and 6: U o........................................................... : I o............................................................. : Po............................................................ : L o............................................................ : C o. .......................................................... : YTA80 / KN2: KEMA 05ATEX1026X 5.71 VDC 8.4 mA 12 mW 200 mH 40 µF II 3 GD Ex nA [nL] IIC T6.. T4 T4: -40 ≤ Ta ≤85ºC II 3 GD Ex nL IIC T6.. T4 T4: -60 ≤ Ta ≤85ºC II 3 GD Ex nA [ic] IIC T6.. T4 II 3 GD Ex ic IIC T6.. T4 EEx nA [L] II C T4...T6 Observed authority requirements: Standard EMC 2004/108/EC, Emission and immunity EN 61326 ATEX 94/9/EC 2007 EN 60079-0 : 2006, EN 60079-11 : EN 60079-15 : 2005, EN 60079-27 : 2006 YTA80 / KS2: KEMA 05ATEX1025 II 3 GD Ex nA [nL] IIC T6.. T4 Applicable in zone cid:image002. gif@01CBF9BD.21B423A0 EMC 2004/108/EC, Emission and immunity cid:image004. gif@01CBF9BD.21B423A0 13 14 Mechanical specification: Mounting of sensor wires Wires must be mounted between the metal plates. 15 YTA80 Block diagram: 16 Bus installation: YTA80 / KN2 YTA80 / KS2 17 18 Appendixes Appendix I Appendix II ATEX Installation drawing YTA80QA01 ATEX Installation drawing YTA80QA02 Appendix I ATEX Installation drawing YTA80QA01 Hazardous area Zone 0, 1, 2, 20, 21, 22 Non Hazardous Area Segment Coupler 6 1 5 2 4 3 YTA80 /KS2 Power Supply 6 5 1 4 2 3 YTA80 /KS2 Max 10 modules 6 5 1 4 2 3 YTA80 /KS2 Termination YTA80QA01 20 2010-01-19 Installation notes. The sensor circuit is not infallibly galvanic isolated from the input circuit. However, the galvanic isolation between the circuits is capable of withstanding a test voltage of 500Vac during 1 minute. In a potentially explosive gas atmosphere, the transmitter shall be mounted in an enclosure in order to provide a degree of protection of at least IP20 according to EN60529. If the transmitter is installed in an explosive atmosphere requiring the use of equipment of category 1G and if the enclosure is made of aluminium, it must be installed such, that even in the event of rare incidents, ignition sources due to impact and friction, sparks are excluded; if the enclosure is made of non-metallic materials, electrostatic charging shall be avoided. For installation in a potentially explosive dust atmosphere, the following instructions apply: The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is providing a degree of protection of at least IP6X according to EN60529, that is suitable for the application and correctly installed. Cable entries and blanking elements shall be used that are suitable for the application and correctly installed. For an ambient temperature 60ºC, heat resistant cables shall be used with a rating of at least 20 K above the ambient temperature. The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a dust layer with a thickness up to 5 mm Yokogawa Europe B.V. Euroweg 2 3825 Amersfoort The Netherlands YTA80QA01 2010-01-19 21 Appendix II ATEX Installation drawing YTA80QA02 For safe installation of YTA80 / KN2 the following must be observed. The module shall only be Installed by qualified personnel who are familiar with the national and international laws, directives and standards that apply to this area. Year of manufacture can be taken from the first two digits in the serial number. ATEX Certificate Marking KEMA 05ATEX 1026X II 3 GD Ex nA [nL] IIC T6..T4 II 3 GD Ex nL IIC T6..T4 T4: -40 Ta 85ºC T6: -40 Ta 60ºC II 3 GD Ex nA [ic] IIC T6..T4 II 3 GD Ex ic IIC T6..T4 EN 60079-0 : 2006, EN 60079-11 : 2007, EN 60079-15 : 2005, EN 60079-27 : 2006 Standards Terminal: 3,4,5,6 Terminal: 1,2 Ex nA Terminal: 1,2 Ex nL or Ex ic Terminal: 1,2 FNICO Uo: 5.7 V Io: 8.4 mA Po: 12 mW Lo: 200 mH Co: 40 F U 32 VDC Ui = 32 VDC Li = 1 H Ci = 2.0 nF Ui = 17.5 VDC Li = 1 H Ci = 2.0 nF Special conditions for safe use. For use in a potentially explosive atmosphere of flammable gasses, vapours or mists, the transmitter shall be mounted in an enclosure providing a degree of protection of at least IP54 in accordance to EN60529. For use in the presence of combustible dusts the transmitter shall be mounted in an enclosure providing a degree of protection of at least IP6X in accordance with o EN60529. The surface temperature of the enclosure shall be determined after installation of the transmitter. For an ambient temperature 60ºC, heat resistant cables shall be used with a rating of at least 20 K above the ambient temperature. Yokogawa Europe B.V. Euroweg 2 3825 Amersfoort The Netherlands YTA80QA02 22 2010-01-19 23 Yokogawa has an extensive sales and distribution network. Please refer to the European website YOKOGAWA ELECTRIC CORPORATION World Headquarters 9-32, Nakacho 2-chome, Musashino-shi Tokyo 180-8750 Japan www.yokogawa.com YOKOGAWA ELECTRIC ASIA Pte. LTD. 5 Bedok South Road Singapore 469270 Singapore www.yokogawa.com/sg YOKOGAWA CORPORATION OF AMERICA 12530 West Airport Blvd, Sugar Land, Texas 77478 USA www.yokogawa.com/us YOKOGAWA CHINA CO. LTD. 3F Tower D Cartelo Crocodile Building No.568 West Tianshan Road Changing District Shanghai, China www.yokogawa.com/cn Euroweg 2 3825 HD Amersfoort The Netherlands www.yokogawa.com/eu YOKOGAWA MIDDLE EAST B.S.C.(c) P.O. Box 10070, Manama Building 577, Road 2516, Busaiteen 225 Muharraq, Bahrain www.yokogawa.com/bh IM 12X0X0-E-E Subject to change without notice IM 01C50C04-01E-E Copyright © Subject to change without notice Copyright (www.yokogawa.com/eu) to contact your nearest representative. A5 YOKOGAWA 00-000 (A) I Printed in The Netherlands Printed in the Netherlands, 03-1106 YOKOGAWA ELECTRIC CORPOR World Headquarters