Signaling Line Circuits (J19 & J20) Class-B, Style-4, Class-A, Style-6 Class-A, Style-7 (requires isolator modules) 28Vdc Max 350 ma (max. - short circuit) 40 ohms (max.) 0.5 microfarads (max.) Twisted, unshielded, low-capacitance fire-alarm wire Communications Circuit (J8) Per RS-485 Standard (-7.5 to +12.5Vdc Max) Per RS-485 Standard (250mA Max @ short circuit) Twisted, shielded, low-capacitance, fire-alarm wire 4,000 Ft. per twisted pair Max. Wire Length: Use the following initiating and control devices only: See Installation, Operation, & Maintenance Manual, P/N 06-237058-001 Use the following remote control modules only: Device Type Model Nos. Photoelectric Detector Ionization Detector Heat Detector Duct detector Monitor Module Control Module HSSD Interface Mod. Addr. AlarmLine Mod. Addr. Signal Module Remote Release Module PSD-7152, PSD-7140 CPD-7052, CPD-7040 THD-7252 DH-2000 PSDI / CPDI, DH-4000 AI AO AIM, APIC AAM RRM ASM, ASM-6SB RRM Module Type Display / Control Display + ASM + AO THD7252 AI CPD7052 PSD7152 P IN-A Caution: IN- S Power Limited To PMU, To PMU, AUX-1 or 2 + AUX-1 or 2 - P NORM OUT- OUT+ IN+ SLC 1 or 2 Do not use looped wire under terminals of detector bases for Models PSD-7152, CPD-7052, and THD-7252. Break SLC wire run to provide supervision of connections. S IN- ISOL OUT- IN+ OUT+ NORM ISOL IN- OUT- IN+ OUT-A OUT-B OUT-B J8 J8 P J19 RS232 A RS232 A or RS232 B P J9 BACKPLANE COMMS OUT J10 24 VDC IN Release circuits wired as non-power-limited. J17 J18 R-NAC 1 OUT+ ISOL P Device Type Model Nos. Actuator / Protractor Control Heads 83-132500-500, 83-131082-001 890181 (WK-890181-000), 895630 (81-895630-000), 899175 (WK-899175-900), 897494-000 (WK-897494-000), 48650001 (82-486500-010), 81-100000-001, 06-118329-001 (FM only), 06-118384-001 (UL only), 87-120099-001, 87-120099-600, 90-487100-001, 38-509837-001, 38-509834-001, 897494-530 (WK-897494-530), 3-101-46A/2 (D21070) (FM only) FM Groups A, B, D, E, F, G, I, J, and K 10 ohm Current Limiting Resistor Blk NORM OUT+ OUT- P To Backplane J10 ISOL OUT- NORM P OUT+ IN+ IN- OUT- ISOL J5 J15 J12 SYS GND - To PMU J3, J4 or J5 To optional PMU2 J12 J13 P + End-of-Line Resistor 10 k +/- 5%, 0.5 W + Power Management Unit (PMU) J9 Auxiliary (AUX-1 & AUX-2) 19.2 to 27.6 VDC Special Application Current: 2.0A, 470uF (max.) J11 J9 AUX-1 + - AUX-2 + IN+ IN- OUT- Red End-of-Line Resistor 10 k +/- 5%, 0.5 W J17 or J18 P R-NAC 1 or 2 OUT+ IN+ IN- OUT- S Regulated 24 VDC, 28 Vdc max. Wiring: Class A, Style Z or Class B, Style Y NAC Current: 2.0 A (max., Non-Synchronized), 1.5A (max., Synchronized) Voltage Drop: 2.0 V (max.) (Non-Power-Limited when In-Line Device not used) See General Note 3. Or Solenoid Circuit J17 or J18 (Class A, Style Z) Solenoid P/N 83-100034-001 (part of 90-487100-001) In-Line Releasing Device, P/N 76-800000-004 (Must be close nippled to solenoid enclosure) Blk Red (Non-Power-Limited when In-Line Device not used) See General Note 3. OUT+ IN+ IN- N.C. End-of-Line Resistor 10 k +/- 5%, 0.5 W Keep as close to connector as possible White N.O. Microswitch P/N 87-120039-001 S Class B, Style Y wiring shown in solid lines. Additional wiring for Class A, Style Z shown in dashed lines (EOL device at terminal block). Black OUT- Suitable for Synchronized and Non-Synchronized Notification Appliances. Use polarized notification appliances only. Maximum single notification-appliance current: 2.0 A See Installation, Operation, & Maintenance Manual, P/N 06-237058-001, for wiring impedance limitations. P TM Part No. 06-237046-001 Rev AB - + + + 12-V Battery Notification-Appliance Circuits (typical for all circuits) S - - Notification-Appliance Circuit + - BATTERY Replaceable Fuse Current Rating: 15A Voltage Rating: 32Vdc min. P 1.0 A @ 30 VDC (resistive) + J10 F1 TBL RELAY C NC NO OUT+ System Ground – to next PMU (16 AWG min.) NORM S R-NAC 1 or 2 L J4 Notification-Appliance Circuit R-NAC 1 or 2 S IN+ IN- + In-Line Releasing Device, P/N 06-220023-001 (Must be close nippled to solenoid enclosure) Red In-Line Releasing Device, P/N 06-220023-001 (Must be close nippled to actuator / protractor) ISOL Solenoid Circuit J17 or J18 (Class B, Style Y) R-NAC 1 or 2 OUT- OUT- Or Actuator / Protractor Circuit IN+ IN- IN+ IN- S J17 or J18 OUT+ OUT+ N J3 Relay-Contact Rating Blk Or IN+ IN- NORM NAC 2 S + End-of-Line Resistor 10 k +/- 5%, 0.5 W J15 NAC 1 NotificationAppliance Circuit R-NAC 1 or 2 OUT+ Use the following releasing devices only: Actuator / Protractor OUT- J17 or J18 28VDC (Max) 2.4 A (max.) Pre-Action / Deluge Valves IN+ IN- J16 R-NAC 2 TB1 J2 J1 J2 PMU COMMS OUT Main Control Board (MCB) 3. A short circuit between conductors in the wiring for the outputs (NACs and R-NAC circuits), and the batterycharging circuit will create a "Short" trouble condition. Voltage: Current: 120 VAC, 50/60 Hz, 3.2 A (single PSU) / 6.4 A (two PSUs) or 240 VAC, 50/60 Hz, 1.6 A (single PSU) / 3.2 A (two PSUs) To Earth-Ground stud on back of back box 2. An open circuit in the wiring for the SLCs, the outputs (NACs, and R-NAC circuits), the RS-485 communications circuit, and the battery-charging circuit will create an "Open" trouble condition. Release Circuits (typical for all circuits) Green TB3 S Black TBL RELAY NC C NO White S To PSU1 To PSU2 RS232 B 1. A short circuit from any field-wiring terminal (except AC-Power-Input Terminals and Form-C Relay Terminals) to earth ground will create a "Ground-Fault" trouble condition. 4. Impedance values for open-circuit and short-circuit conditions are: open circuit: infinite ohms short circuit: zero (0) ohms J4 USB HOST USB DEVICE Electrical Supervision Multiple conductors cannot be used on the terminal blocks. Multiple conductors are to be connected as depicted. OUT- SLC 2 5. End-of-Line Resistor, 10 k +/- 10%, 0.5 W is P/N 06-129025-003 Exception: OUT+ + To AUX-1 or AUX-2 TB3 NC Trouble Relay IN- IN-B J8 RELAY 3 NO C 4. Do not attach power-limited and non-power-limited wiring to the same terminal block. TB2 NC 3. Route non-power-limited wiring at least 1/4 inch away from all power-limited wiring. TB1 NO C Programmable Relays RELAY 2 NC 2. Earth-ground-offset voltage is 6.6 VDC (nom.) relative to system common (e.g., PMU J15-2). RELAY 1 3.0 A @ 30 VDC (resistive) 3.0 A @ 120 VAC (resistive) NO C 1. Wire sizes for all terminal blocks is 12 - 18 AWG. P OUT+ J20 Relay-Contact Rating S IN-A J19 or J20 SLC 1 General Notes: Remote Display & Control Module (RDCM) IN+ S OUT-A Supervised J4 Model No. RDCM R-LAM IN-B Legend: J8 24 VDC PWR Voltage: Current: Recommended Wire: RS485 Voltage: Current: Wiring Resistance: Wiring Capacitance: Recommended Wire: RS485 Wiring: - + S 12-V Battery Battery Circuit Sealed, lead-acid batteries only. Maximum 165 AH. Replace every 3 years or as recommended by battery manufacturer. Charging-Circuit Voltage: 28.0 V (Max.) Charging-Circuit Current: 8.97 A (max.) Typical standby operating times are 24 and 90 hours. See Installation, Operation, & Maintenance Manual, P/N 06-237058-001, for specific battery capacity calculations.