SW6000 Datasheet - Metrix-Vibration Monitoring Solutions

advertisement
SW6000 ELECTRONIC VIBRATION SWITCH
Datasheet
OVERVIEW
This electronic switch is a versatile excessive vibration
protection instrument. In its standard configuration, the
SW6000 is an economical single set point vibration switch
loaded with standard features and packaged in an industrial
grade housing.
Fully configured, the SW6000 provides for local machine
control with optional LCD readout, real time remote operator
interface via 4-20 mA and an external BNC (weather-proof
only) for easy analyst access to the buffered dynamic vibration
signal. Optional hazardous area certifications.
FEATURES
•
•
•
•
•
•
•
Low cost, unitized protection system
Weatherproof/optional ex-proof rated
Single or optional dual setpoint
Velocity or displacement response
Adjustable trip delay
Setpoint test feature
Buffered, dynamic vibration signal output for analysis
APPLICATIONS
•
•
•
•
•
•
•
Centrifugal Pumps
Reciprocating Compressors
Centrifuges
Cooling Towers
Industrial Fans
Electric Motors
Natural Gas/Diesel Engines
C
US
1180
TYPICAL INSTALLATIONS
switch
CENTRIFUGAL PUMP/MOTOR
ENGINE COMPRESSOR
www.metrixvibration.com • dps@metrixvibration.com • 281.940.1802
Doc# 1009462 • SW6000 • Mar2016-RevF • Page 1 of 3
SW6000 ELECTRONIC VIBRATION SWITCH
Datasheet
WEIGHT & DIMENSIONS
Units: mm [in]
Weight: 2.2 kg [4.4 lbs]
Note:
1) Optional BNC connector and weatherproof reset button available only on non-agency approved locations.
2) Cover locking set screw on ATEX/IECEx versions only.
SPECIFICATIONS
Sensor
Internal piezoelectric accelerometer
Signal Conditioner
Amplifier/integrator to obtain velocity or
displacement response.
Triac Outputs
Optional Buffered,
Dynamic Signal
Output
“A” = 1, 2, 5 or 6; 250 VAC, 1A, optically
isolated; standard is N.C. (fail-safe), N.O. field
selectable
Sensitivity: 100 mV/g ±2% @ 25°C.
Frequency Response:
• Acceleration: 2 Hz to 500 Hz
• Non-linearity: Less than 1% of full scale (F.S.)
Field Wiring
Maximum
Vibration Input
0 to 490 m/sec2 (50 g), peak; 0 to 100 mm/
sec (4 in./sec), peak
Maximum wire gauge: 14 AWG; Wire clamp
type screw terminal block 500 Vrms isolation
from circuit
Housing
Weatherproof aluminum cast
Frequency
Response
• Velocity: 2 Hz to 500 Hz
• Displacement: 2 Hz to 200 Hz
Adjustable Trip Delay Factory set at 1 sec.; 1-15 sec adjustable
Temperature Limits
• No Display: -40° to +85°C (-40° to +185°F)
• W/Display: -10° to +70°C (+14° to +158°F)
Output Sensitivity vs
Temperature
Less than .05%/°C (calibrated at 25°C)
Cross Axis Response
Less than 10%
Input Power
Option C
• Nom. 115 VAC, 95 to 125, 50/60 Hz
• Nom. 230 VAC, 190 to 250, 50/60 Hz
• Nom. 24 VDC, 20 to 28
Galvanic Isolation
Power from circuit
Environmental Rating NEMA 4/4X
Electromagnetic
Compatibility
CE Marked
Optional Hazardous
Area Certification
Ordering Options “D”
Optional Display
2½ digit LCD (Ordering Option “A”)
Optional FET
Transistor Output
50 VDC, 0.5 A, N.C. (fail-safe) standard, N.O.
field selectable
Optional 4-20 mA
Source Output
Proportional between 4-20 mA with 20 mA
set to full scale. Zero and Span calibrated
±2%. Non-linearity < 2%. 600 ohms maximum load resistance.
www.metrixvibration.com • dps@metrixvibration.com • 281.940.1802
Doc# 1009462 • SW6000 • Mar2016-RevF • Page 2 of 3
SW6000 ELECTRONIC VIBRATION SWITCH
Datasheet
HOW TO ORDER
A B B C -D E F
SW6000-
-
Without Display
Input Power
1 115 VAC, single phase, 50/60 Hz
1 one limit, triac
2 230 VAC, single phase, 50/60 Hz
2 two limit, triacs
3 20 - 28 VDC
A Limits and Displays
C
3 one limit, FET
4 two limits, FETs
D Certifications Local Reset Options
With Display
2
CSA, US/C, Class I, Div 1, Groups B, C & D, T4A, NEMA 4/4X
5 one limit, triac
3
CSA, US/C, Class I, Div 1, Groups B, C & D, T4A, NEMA 4/4X
w/ external reset
4
ATEX/IECEx Ex d IIB + H2 T4 Gb
5
ATEX/IECEx Ex d IIB + H2 T4 Gb with external reset
8
Non-agency approved locations
9
Non-agency approved locations with external reset
E
Input/Output Options
6
two limit, triacs
7 one limit, FET
8 two limits, FETs
Note: Use triacs in motor starter circuits. FET transistor output(s)
recommended for PLC DC inputs.
B B Full Scale Range
Velocity Response
0
No options
0
1 1.0 in/sec (25.4 mm/sec) peak
2
External BNC for dynamic signal access*
0
2 2.0 in/sec (50.8 mm/sec) peak
5
0
3 20 mm/sec (0.79 in/sec) peak
4-20 mA proportional to full scale range and separate startup
and monitor time delays
0
4 50 mm/sec (1.97 in/sec) peak
7
Options 2 & 5*
3
1 1.0 in/sec (25.4 mm/sec) true RMS
3
2 2.0 in/sec (50.8 mm/sec) true RMS
3
3 20 mm/sec (0.79 in/sec) true RMS
3
4 50 mm/sec (1.97 in/sec) true RMS
Displacement Response
5
1 20 mils, (508 microns) peak
5
2 50 mils, (1270 microns) peak
6
1 200 microns, (7.87 mils) peak
6
2 500 microns, (19.69 mils) peak
* D= 8 or 9 only
F
Mouting/Conduit Entries
0
1/2” NPT stud mount/ 3/4” NPT conduit entry
1
M20 x 1.5 stud mount/ M20 x 1.5 conduit entry
2
1/2-20 UNF stud mount/ 3/4” NPT conduit entry
3
3/4” NPT stud mount/ 3/4” NPT conduit entry
ACCESSORIES
Part Number
7084-001
Name
Flange Mounting Adapter
Description
Stainless Steel adapter for surface mount
the SW6000. 1/2” NPT center hole. Three equally
spaced 6.6 (.26) diameter mount holes
on 38 (1.50) diameter circle
Used with
Any SW6000 with 1/2” NPT stud (“F”= 0)
Weight: 0.5 kg [1 lb]
www.metrixvibration.com • dps@metrixvibration.com • 281.940.1802
Doc# 1009462 • SW6000 • Mar2016-RevF • Page 3 of 3