Student Resource Building University of California Santa Barbara Clement Fung Lighting | Electrical Option APPENDIX E Electrical System Single Line Diagram Overcurrent Protection Study Overcurrent Protection Device Specifications 2400 3600 4800 6000 7200 9600 200 300 400 500 600 800 4 7 12 18 35 75 10000 Time(s) 10000 150 40 18 10 7 0.03 400 800 1200 1600 2000 2400 3200 100 800 600 500 400 300 200 Time(s) Actual Current (A) % of Rated Current 400 Transformer T1A (primary) 1200 100 Breaker Rating (A) Actual Current (A) 1200 Main Switchboard (MS) % of Rated Current Breaker Rating (A) Overcurrent Protection and Coordination 0.9 2 3.5 6 15 70 10000 Time(s) 345 690 1035 1380 1725 2070 2760 Actual Current (A) 800 10000 70 30 17 10 6 0.04 Time(s) Transformer T1A (secondary) 400 300 250 200 150 100 50 Actual Current (A) 50 Panel H3Aa 0.7 150 300 450 600 750 900 1200 Actual Current (A) 150 2 3 5 10 45 10000 Time(s) 10000 120 40 20 9.5 5.2 0.04 Time(s) Feeder to Panel L1Aa 480 360 300 240 180 120 60 Actual Current (A) 60 Panel H2A 800 600 500 400 300 200 100 Actual Current (A) 100 Panel H1A 0.035 0.8 2 4.5 12 40 10000 Time(s) 1600 1200 1000 800 600 400 200 Actual Current (A) 200 Feeder to H1A 1.5 2.5 4 6 17 45 10000 Time(s) Time (Seconds) 0.01 0.1 1 10 100 1000 10000 10 100 Current (A) 1000 Time-Current Curves For Branch Circuit Protection "Path B-C-D-E" 10000 1200A 100A 200A 60A 50A Time (Seconds) 0.01 0.1 1 10 100 1000 10000 10 100 Current (A) 1000 Time-Current Curves For Branch Circuit Protection "Path B-1-2" 10000 1200A 400A 800A 150A Application Data 29-167N Page 3 AB DE-ION Circuit Breakers Types ND, CND, HND, CHND, NDC, CNDC Equipped With Type NES Digitrip RMS 310 Trip Units With Adjustable Short Time Delay (Phase Protection) CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 1 HOUR 2 HOURS 10,000 Circuit Breaker Time/Current Curves (Phase Current) Series C® N-Frame Circuit Breakers Equipped With Type NES Digitrip RMS 310 Trip Units The NES Digitrip RMS 310 Trip Units are AC only devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types ND, CND, HND, CHND, NDC, and CNDC. 5,000 3,000 Adjustable Short Time Delay Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug 2,000 Push to Trip Standard Fixed Rating Plug Short Delay Pickup x In 5 4 6 Cat.– /n– “Y” 3 Engaged Digitrip RMS 310 Trip Unit 40°C Ambient 7 2 8 TEST Remove 1,000 Frame Rating Amperes (Max.) 500 800 300 200 1 MINUTE 100 Long Delay➀ Maximum Total Clearing Time 1200 Long Delay➀ Minimum Total Clearing Time 50 Available Rating Plugs Ampere Type Rating (I n ) Catalog Number Short Delay Pickup Range Amperes 800 700 630 600 550 500 450 400 400, 500, 600, 800 400, 500, 630, 800 1200 1000 900 800 700 630 600 600, 800, 1000, 1200 8NES800T 8NES700T 8NES630T➃ 8NES600T 8NES550T 8NES500T 8NES450T 8NES400T A8NES800T1 A8NES800T2➃ 12NES1200T 12NES1000T 12NES900T➃ 12NES800T 12NES700T 12NES630T➃ 12NES600T A12NES1200T1 1600-6400 1400-5600 1260-5040 1200-4800 1100-4400 1000-4000 900-3600 800-3200 800-6400 800-6400 2400-9600 2000-8000 1800-7200 1600-6400 1400-5600 1260-5040 1200-4800 1200-9600 Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Adj. Adj. Fixed Fixed Fixed Fixed Fixed Fixed Fixed Adj. Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Type 240V 480V 65 50 ND, CND 100 65 HND, CHND 200 100 NDC, CNDC 30 2X 20 IEC 947-2 220-240V 65 100 200 600V 25 35 50 380-415V 50 65 100 ICS = .25 ICU ICW = 15 kA @ .5S Uimp = 8kV 10 Notes 4X Curve accuracy applies from -20°C to +55°C ambient. For possible ampere derating for ambient above 40°C, refer to Cutler-Hammer. Short Delay Pick Up Settings (Tolerance ±10%) 6X 5 3 For ground fault time-current curves see SC-5377-92A. 8X ➀ There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. ➁ For high fault current levels a fixed instantaneous override is provided at 14000A (Tolerance ±15%). 7X TIME IN SECONDS 2 Digitrip RMS 300 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 1 ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. ➃ Not UL/CSA Listed. 5X 3X .5 300 MS .3 200 MS .2 100MS .1 .1 I .03 .03 .02 .02 20 .001 CURRENT IN AMPS October 1997 60,000 70,000 80,000 90,000 100,000 .002 50,000 .003 .002 40,000 .003 30,000 .005 20,000 .01 .005 .001 2 3 4 5 6 7 8 9 10 .5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) Interrupting Rating Determines End of Curve➂ 10,000 .01 Fixed Instantaneous Overide➁ 200,000 .05 SECONDS .05 Curve No. SC-5376-92A Application Data 29-167N Page 2 AB DE-ION Circuit Breakers Types ND, CND, HND, CHND, NDC, CNDC Equipped With Type NES Digitrip RMS 310 Trip Units With I 2t Ramp Short Time Delay (Phase Protection) CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) .5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 1 HOUR 2 HOURS 10,000 Circuit Breaker Time/Current Curves (Phase Current) Series C® N-Frame Circuit Breakers Equipped With Type NES Digitrip RMS 310 Trip Units The NES Digitrip RMS 310 Trip Units are AC only devices that employ microprocessor based technology that provides true RMS current sensing means for proper correlation with thermal characteristics of conductors and equipment. They are used with Circuit Breaker Types ND, CND, HND, CHND, NDC, and CNDC. 5,000 3,000 I2t Ramp Short Time Delay 2,000 Typical Trip Unit Nameplate Digitrip RMS 310 Rating Plug Standard Fixed Rating Plug Push to Trip Short Delay Pickup x In 5 4 6 Cat.– /n– “Y” 3 1,000 Engaged Frame Rating Amperes (Max.) 500 300 800 200 1 MINUTE 100 Long Delay➀ Maximum Total Clearing Time Long Delay➀ Minimum Total Clearing Time 1200 50 30 3X 2X 8 10 TEST Remove Available Rating Plugs Type Ampere Rating (In) Catalog Number Short Delay Pickup Range Amperes 800 700 630 600 550 500 450 400 400, 500, 600, 800 400, 500, 630, 800 1200 1000 900 800 700 630 600 600, 800, 1000, 1200 8NES800T 8NES700T 8NES630T➃ 8NES600T 8NES550T 8NES500T 8NES450T 8NES400T A8NES800T1 A8NES800T2➃ 12NES1200T 12NES1000T 12NES900T➃ 12NES800T 12NES700T 12NES630T➃ 12NES600T A12NES1200T1 1600-6400 1400-5600 1260-5040 1200-4800 1100-4400 1000-4000 900-3600 800-3200 800-6400 800-6400 2400-9600 2000-8000 1800-7200 1600-6400 1400-5600 1260-5040 1200-4800 1200-9600 Fixed Fixed Fixed Fixed Fixed Fixed Fixed Fixed Adj. Adj. Fixed Fixed Fixed Fixed Fixed Fixed Fixed Adj. Interrupting Ratings – 50/60 Hz RMS Sym. Amperes (kA) UL/CSA Breaker Type 240V 480V 65 50 ND, CND 100 65 HND, CHND 200 100 NDC, CNDC 20 Digitrip RMS 310 Trip Unit 40°C Ambient 7 2 IEC 947-2 220-240V 65 100 200 600V 25 35 50 380-415V 50 65 100 ICS = .25 ICU ICW = 15 kA @ .5S Uimp = 8kV Short Delay Pick Up Settings (Tolerance ± 10%) 4X 5 3 1 Curve accuracy applies from -20°C to +55°C ambient. For possible ampere derating for ambient above 40°C, refer to Cutler-Hammer. Digitrip RMS 300 trip units are suitable for functional field testing with test kit Cat. No. STK2. For field testing using primary injection methods, follow NEMA publication AB-4-1991. 8X 5X For ground fault time-current curves see SC-5377-92A. ➀ There is a memory effect that can act to shorten the long delay. The memory effect comes into play if a current above the long delay pick up value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip in shorter time than normal. The amount of time delay reduction is inverse to the amount of time that has elapsed since the previous overload. Approximately five minutes is required between overloads to completely reset the memory. 6X ➁ For high fault current levels a fixed instantaneous override is provided at 14000A (Tolerance ±15%). ➂ The end of the curve is determined by the interrupting rating of the circuit breaker. See above tabulation. .5 ➃ Not UL/CSA Listed. .3 7X .2 .1 .05 .05 .03 .03 .02 .02 20 .001 CURRENT IN AMPS 60,000 70,000 80,000 90,000 100,000 .002 50,000 .003 .002 40,000 .003 30,000 .005 20,000 .01 .005 .001 2 3 4 5 6 7 8 9 10 .5 .6 .7 .8 .9 1 CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In) Interrupting Rating Determines End of Curve➂ 10,000 .01 Fixed Instantaneous Overide➁ 200,000 .1 SECONDS TIME IN SECONDS 2 Notes Curve No. SC-5375-92A October 1997 Application Data 29-167L Page 2 AB DE-ION Circuit Breakers Types LDB, LD, HLD Equipped With Type LT Thermal-Magnetic Trip Unit 60,000 70,000 80,000 90,000 100,000 50,000 40,000 30,000 20,000 6000 7000 8000 9000 10,000 5000 4000 3000 2000 600 700 800 900 1000 500 400 300 200 70 80 90 100 60 50 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 10,000 10,000 2 HOURS Series C® L-Frame Circuit Breakers Equipped With Type LT Thermal-Magnetic Trip Unit 5,000 Catalog Types LDB, LD, HLD Circuit Breakers, 2, 3 and 4 Poles For application and coordination purposes only. Thermal calibration based on 40°C ambient, cold start. Connected with four (4) feet of rated wire (75°C) per terminal. Tested in open air with current in all poles. Instantaneous calibration based on single-pole tests. 3,000 2,000 1 HOUR 5,000 1 HOUR 2 HOURS Circuit Breaker Time/Current Curves 3,000 2,000 Maximum Voltage 600 V., Ac (50/60 Hz.) 250 V., Dc 1,000 1,000 Breaker Rating Rated Amperes (In) Instantaneous Trip Amperes (See Figure Below) 500 to 1000% of trip unit rating (Dc values are approximately 40% higher) 300, 350, 400, 500, 600 500 300 Maximum 240 V., (Ue) Icu Ics 100 LDB LD HLD 65 65 100 50 17 17 25 200 kA, Dc 380 V., (Ue) Icu Ics 415 V., (Ue) Icu Ics 250 V., (Ue) Icu Ics 40 40 65 40 40 65 10 10 20 10 10 17 10 10 17 50 Note: For additional information on the trip unit, see IL 29C606. 30 ➀ Single pole data at 25°C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers. 20 7.5 7.5 10 20 7.5 Push to Trip C Thermal Magnetic Trip Unit Typical Trip Unit Nameplate 10 100 3 3 5 Utilization Category A UIMP = 8 kV 30 10 5 10 5 Amps (In) Magnetic Multiples Of In 10 40°C 5 Cat. No. 5 5 Individual Pole Adjustments 3 3 2 5X ±10% 1 TIME IN SECONDS ±20% 1 10X 2 .5 .5 Adjustable Magnetic Trip .3 .3 .2 .2 .1 .1 .05 .05 .03 Maximum Interrupting Time .03 .02 .02 .01 .01 Interrupting Rating Determines End of Curve .005 .005 CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In) 60,000 70,000 80,000 90,000 100,000 50,000 40,000 30,000 20,000 6000 7000 8000 9000 10,000 5000 4000 3000 2000 500 600 700 800 900 1000 400 .001 300 .001 200 .002 60 .003 .002 70 80 90 100 .003 50 TIME IN SECONDS 300 250 V. 10 10 20 600 V. 25 25 35 1 MINUTE 1 MINUTE kA, Dc 240 V. 480 V. 65 35 65 35 100 65 IEC 947-2 RMS Sym. kA, 50/60 Hz. LDB LD HLD 200 Minimum 500 Interrupting Rating Breaker UL/CSA Type RMS Sym. kA, 50/60 Hz. Maximum Single Pole Trip Times at 25°C 1 Curve No. SC-4547-89B October 1997 Types FD and HFD 225 Amperes AB DE-ION Circuit Breakers Cutler-Hammer 30 40 50 60 70 80 90 600 700 800 900 1000 20 500 6 7 8 9 10 400 5 10,000 300 4 200 3 100 2 2 HOURS 2 HOURS Circuit Breaker Time/Current Curves Molded-Case Circuit Breakers Catalog Types FD/HFD Circuit Breakers, Two, Three and Four Poles For application and coordination purposes only. Based on 40˚C ambient, cold start. Connected with four (4) feet of rated wire (75˚C) per terminal. Tested in open air with current in all poles. 5,000 3,000 Maximum AC Volts: 690 at 50/60 Hz Maximum DC Volts: 250 3,000 Breaker Rating In Amperes 175 200 225 2,000 2,000 ➀ 1,000 Instantaneous Pick-up, Amperes RMS 2400 2400 2400 1 HOUR 5,000 1 HOUR Page Page 36a1 CURRENT IN MULTIPLES OF In 175-225A 1 Technical Data Effective: May 1999 1,000 Interrupting Ratings 500 Maximum Single Pole Trip Times ➁ at 25°C 300 Symmetrical RMS Amperes (kA), Icu 240 Vac 480 Vac 600 Vac 250 Vac FD HFD 65 100 25 65 18 25 10 22 Notes: ➀ Fixed Inverse – Time Overcurrent Release. ➁ Single Pole Test Data at 25°C based on NEMA Procedures (AB 4-1991) for verifying performances of Molded Case Circuit Breakers. ➂ Total Operation Time. ➃ Interrupting Rating Determines End of Curve. In this interruption region: The curve is drawn for In = 200A. For In ≠ 200A, the end points in this region are displaced along the current-axis by a factor (200A/In) 200 500 300 200 100 100 50 50 30 30 Maximum Trip Time 20 20 10 10 5 5 3 3 2 Minimum Trip Time TIME IN SECONDS 1 TIME IN SECONDS 2 1 MINUTE 1 MINUTE Breaker Type 1 175 A .5 .5 200 A .3 .3 225 A .2 .2 .1 .1 .05 .05 .03 .03 ➂ ➃ .02 .02 .01 .01 .001 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 CURRENT IN MULTIPLES OF In AD 29-167F 600 700 800 900 1000 .002 500 .002 400 .003 300 .003 200 .005 100 .005 .001 Curve No. SC-6970-98A Application Data 29-167F Page 36 AB DE-ION Circuit Breakers Types FDB, FD and HFD 150 Amperes 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 300 CURRENT IN AMPERES 150A 5 6 7 8 9 10 2 HOURS Circuit Breaker Time/Current Curves ® Series C F-Frame Circuit Breakers Catalog Types EHD, FDB, FD and HFD Circuit Breakers, Two, Three and Four Poles 5,000 For application and coordination purposes only. Based on 40˚C ambient, cold start. Connected with four (4) feet of rated wire (60˚C up to 125 amps, 75˚C above 125 amps) per terminal. Tested in open air with current in all poles. 3,000 2,000 5,000 3,000 1 HOUR 1 HOUR 2 HOURS 10,000 2,000 Maximum AC Volts: 600 at 60 Hz Maximum DC Volts: 250 Breaker Rating Continuous Amperes 150 Amps 1,000 500 Maximum Single Pole Trip Times at 25°C 1 300 Instantaneous Trip Amperes See Curve Interrupting Rating (UL/CSA Listed) Breaker Symmetrical RMS Amperes (KA) @ 240 V., Ac @ 480 V., Ac @ 600 V., Ac Type FDB FD HFD 1 200 18 65 100 14 25 65 14 18 25 Amps (KA) 250V., Dc 10 10 22 Single pole test data at 25˚C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers. 1,000 500 300 200 50 50 1 MINUTE 100 30 30 20 20 10 10 Minimum Maximum 5 3 3 2 2 1 1 .5 .5 .3 .3 .2 .2 .1 .1 .05 TIME IN SECONDS TIME IN SECONDS 5 1 MINUTE 100 .05 .03 .03 Maximum Interrupting Time .02 .02 .01 .01 Interrupting Rating Determines End of Curve (See Above) .005 .003 .002 .003 CURRENT IN AMPERES 6000 7000 8000 9000 10000 5000 4000 3000 2000 50 60 70 80 90 500 40 600 700 800 900 1000 30 400 20 300 5 6 7 8 9 10 200 .002 100 .001 .005 .001 Curve No. SC-4149-87B October 1997 Application Data 29-167F Page 32 AB DE-ION Circuit Breakers Types EHD, FDB, FD and HFD 100 Amperes 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 300 CURRENT IN AMPERES 100A 5 6 7 8 9 10 2 HOURS Circuit Breaker Time/Current Curves ® Series C F-Frame Circuit Breakers Catalog Types EHD, FDB, FD and HFD Circuit Breakers, Two, Three and Four Poles 5,000 For application and coordination purposes only. Based on 40˚C ambient, cold start. Connected with four (4) feet of rated wire (60˚C up to 125 amps, 75˚C above 125 amps) per terminal. Tested in open air with current in all poles. 3,000 2,000 5,000 3,000 1 HOUR 1 HOUR 2 HOURS 10,000 2,000 Maximum AC Volts: 600 at 60 Hz Maximum DC Volts: 250 Breaker Rating Continuous Amperes 100 Amps 1,000 Instantaneous Trip Amperes See Curve Interrupting Rating (UL/CSA Listed) Breaker Symmetrical RMS Amperes (KA) @ 240 V., Ac @ 480 V., Ac @ 600 V., Ac Type 500 EHD FDB FD HFD 300 200 1 Maximum Single Pole Trip Times at 25°C 1 18 18 65 100 14 14 25 65 -14 18 25 Amps (KA) 250V., Dc 10 10 10 22 Single pole test data at 25˚C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers. 1,000 500 300 200 50 50 1 MINUTE 100 30 30 20 20 10 10 Minimum Maximum 5 3 3 2 2 1 1 .5 .5 .3 .3 .2 .2 .1 .1 .05 TIME IN SECONDS TIME IN SECONDS 5 1 MINUTE 100 .05 .03 .03 Maximum Interrupting Time .02 .02 .01 .01 Interrupting Rating Determines End of Curve (See Above) .005 .003 .002 .003 CURRENT IN AMPERES 6000 7000 8000 9000 10000 5000 4000 3000 2000 50 60 70 80 90 600 700 800 900 1000 40 500 30 400 20 300 5 6 7 8 9 10 200 .002 100 .001 .005 .001 Curve No. SC-4146-87B October 1997 Application Data 29-167F Page 28 AB DE-ION Circuit Breakers Types EHD, FDB, FD and HFD 60 Amperes 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 300 CURRENT IN AMPERES 60A 5 6 7 8 9 10 2 HOURS Circuit Breaker Time/Current Curves ® Series C F-Frame Circuit Breakers Catalog Types EHD, FDB, FD and HFD Circuit Breakers, Two, Three and Four Poles 5,000 For application and coordination purposes only. Based on 40˚C ambient, cold start. Connected with four (4) feet of rated wire (60˚C up to 125 amps, 75˚C above 125 amps) per terminal. Tested in open air with current in all poles. 3,000 5,000 3,000 1 HOUR 1 HOUR 2 HOURS 10,000 2,000 2,000 Maximum AC Volts: 600 at 60 Hz Maximum DC Volts: 250 Breaker Rating Continuous Amperes 60 Amps 1,000 Interrupting Rating (UL/CSA Listed) Breaker Symmetrical RMS Amperes (KA) @ 240 V., Ac @ 480 V., Ac @ 600 V., Ac Type 500 EHD FDB FD HFD 300 200 1 Maximum Single Pole Trip Times at 25°C 1 18 18 65 100 14 14 25 65 -14 18 25 Amps (KA) 250V., Dc 10 10 10 22 Single pole test data at 25˚C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers. 1,000 500 300 200 100 100 50 50 30 30 20 20 Minimum Maximum 10 10 5 5 3 3 2 2 1 1 .5 .5 .3 .3 .2 .2 .1 .1 .05 TIME IN SECONDS TIME IN SECONDS 1 MINUTE .05 .03 .03 Maximum Interrupting Time .02 .02 .01 .01 Interrupting Rating Determines End of Curve (See Above) .005 .003 .002 CURRENT IN AMPERES 6000 7000 8000 9000 10000 5000 4000 3000 2000 50 60 70 80 90 600 700 800 900 1000 40 500 30 400 20 300 5 6 7 8 9 10 200 .001 .005 .003 .002 100 1 MINUTE Instantaneous Trip Amperes See Curve .001 Curve No. SC-4142-87B October 1997 Application Data 29-167F Page 27 AB DE-ION Circuit Breakers Types EHD, FDB, FD and HFD 50 Amperes 6000 7000 8000 9000 10000 5000 4000 3000 2000 600 700 800 900 1000 500 400 40 50 60 70 80 90 200 30 100 20 300 CURRENT IN AMPERES 50A 5 6 7 8 9 10 2 HOURS Circuit Breaker Time/Current Curves ® Series C F-Frame Circuit Breakers Catalog Types EHD, FDB, FD and HFD Circuit Breakers, Two, Three and Four Poles 5,000 For application and coordination purposes only. Based on 40˚C ambient, cold start. Connected with four (4) feet of rated wire (60˚C up to 125 amps, 75˚C above 125 amps) per terminal. Tested in open air with current in all poles. 3,000 5,000 3,000 1 HOUR 1 HOUR 2 HOURS 10,000 2,000 2,000 Maximum AC Volts: 600 at 60 Hz Maximum DC Volts: 250 Breaker Rating Continuous Amperes 50 Amps 1,000 Interrupting Rating (UL/CSA Listed) Breaker Symmetrical RMS Amperes (KA) @ 240 V., Ac @ 480 V., Ac @ 600 V., Ac Type EHD 14 -18 14 14 FDB 18 18 FD 65 25 HFD 100 65 25 500 300 200 1 Maximum Single Pole Trip Times at 25°C 1 Amps (KA) 250V., Dc 10 10 10 22 Single pole test data at 25˚C based on NEMA Procedures (AB 4-1991) for verifying performance of molded case circuit breakers. 1,000 500 300 200 100 100 50 50 30 30 20 20 Minimum Maximum 10 10 5 5 3 3 2 2 1 1 .5 .5 .3 .3 .2 .2 .1 .1 .05 TIME IN SECONDS TIME IN SECONDS 1 MINUTE 1 MINUTE Instantaneous Trip Amperes See Curve .05 .03 .03 Maximum Interrupting Time .02 .02 .01 .01 Interrupting Rating Determines End of Curve (See Above) .005 .003 .002 .003 CURRENT IN AMPERES October 1997 6000 7000 8000 9000 10000 5000 4000 3000 2000 50 60 70 80 90 500 40 600 700 800 900 1000 30 400 20 300 5 6 7 8 9 10 200 .002 100 .001 .005 .001 Curve No. SC-4141-87B