63230-400-204/A1 February 2002 Chapter 5—Wiring Wiring CTs, PTs, and Control Power to the Circuit Monitor The circuit monitor supports a variety of 3-phase power system wiring connections, including 3-wire delta and 4-wire wye. The metering voltage inputs support direct connection to 3-phase power systems from 208V L–L/120V L–N through 600V L-L/347V L–N. In addition, the circuit monitor supports higher voltages through potential transformers (PTs). The circuit monitor can also be used with line-to-line rated PTs connected line to neutral, which results in a line-to-neutral voltage of 69 V. Table 5–2 lists the supported system connections and references the wiring diagrams on pages 35 through 44. Figures 5–4 through 5–13 beginning on page 35 show wiring to the circuit monitor for connections to the current transformers CTs, PTs, and control power. Figure 5–14 on page 45 shows dc control power. WIRING CTS, PTS, AND CONTROL POWER TO THE CIRCUIT MONITOR Table 5–2: Supported Types of System Connections System Wiring 3∅, 3-Wire Delta Number of CTs Auxiliary CT Number of PTs 2 None 2 3 None 3 None PT Connection Currents Voltages System Type➀ Figure Number A, B➁, C A-B, B-C, C-A➁ 3∅3W2CT (30) Figure 5–5 on page 36 2 A, B, C A-B,B-C,C-A➁ 3∅3W3CT (31) Figure 5–6 on page 37 3 A, B, C, N➁ A-N, B-N, C-N A-B➁, B-C➁, C-A➁ 3∅4W3CT (40) Figure 5–7 on page 38 3∅4W4CT (41) Figure 5–8 on page 39 Open Delta Wye-Wye 3∅, 4-Wire Wye, Ground 4 Neutral 3 A, B, C, N, G➁ A-N, B-N, C-N A-B➁, B-C➁, C-A➁ 3 None 2 A, B, C, N➁ A-N, B-N➁, C-N A-B➁, B-C➁, C-A➁ 3∅4W3CT2PT Figure 5–11 (42) on page 42 A, B, C, N, G➁ A-N, B-N➁, C-N A-B➁, B-C➁, C-A➁ 3∅4W4CT2PT Figure 5–12 (43) on page 43 Open Wye 4 Neutral 2 ➀ The “system type” is a code assigned to each type of system connection. ➁ Indicates a value that is calculated rather than measured directly. © 2002 Schneider Electric All Rights Reserved 33