Analogue signal Conditioning

advertisement
Analogue signal Conditioning
Analogue signal Conditioning
Overview
D.2
Introduction
D.4
WAVESERIES
D.12
WAVESERIES – DC/DC
D.14
WAVESERIES – PT100/RTD
D.28
WAVESERIES – Thermocouple signal converter, configurable
D.34
WAVESERIES – Thermocouple signal isolator/converter
D.35
WAVESERIES – Frequency signal isolator/converter, configurable
D.36
WAVESERIES – Bridge-type measuring isolating transformer
D.38
WAVESERIES – Limit value monitoring
D.39
WAVESERIES – universal signal converters and trip amplifiers, configurable
D.40
WAVESERIES – Current monitoring
D.42
WAVESERIES – Voltage monitoring
D.46
WAVESERIES – Signal-converter accessories
D.49
WAVESERIES – Accessories
D.50
CMA – Current monitoring
D.51
MCZ-SERIES
D.52
MCZ-SERIES – DC/DC passive isolator
D.53
MCZ-SERIES – PT100/RTD signal isolator
D.54
MCZ-SERIES – Frequency signal isolator
D.55
MCZ-SERIES – Limit value monitoring
D.56
MCZ-SERIES – Accessories
D.57
MICROINTERFACE Analogue
D.58
MICROSERIES
D.60
MICROSERIES – DC/DC 3-way isolator
D.61
MICROSERIES – Feed isolator
D.63
MICROSERIES – PT100/RTD signal isolator
D.65
MICROSERIES – Thermocouple signal isolator/converter
D.66
MICROSERIES – Accessories
D.68
RS-SERIES – AD/DA converter
D.70
MANN SERIES
D.74
MANN SERIES – Signal isolators
D.82
MANN SERIES – Signal converters
D.90
MANN SERIES – Signal-converter accessories
D.108
MANN SERIES – Process alarms
D.110
MANN SERIES – Multi-Channel processing modules
D.130
MANN SERIES – Indicators and configurable displays
D.134
MANN SERIES – Universal auto-manual stations
D.148
MANN SERIES – Counters/Totalisers
D.150
MANN SERIES – Calibrators
D.154
D.1
Analogue signal Conditioning
Contents
D
Analogue signal Conditioning
Overview
What is new?
3 phase voltage monitor
Page D.47
MICROINTERFACE analogue
Page D.58
MICROANALOGUE RPS with HART
option
Page D.64
• For high / low voltage monitoring
of AC supplies
• 80...400 V AC measurements
• 2 CO output relays
• DIP switch settable
• High density analog field interface
for PLCs / SMSs
• 8 channels use only 62 mm rail space
• Each channel function can be different
• Multi-pin connectors to the PLC / SMS
•
•
•
•
Linearising functions, for…
Page D.103
Multi-channel processing
Page D.130
Panel display range includes
Page D.136
• Flow in pipes (square root extraction),
or open channel flow (over weirs)
• Level-to-volume conversion
• Special sensor characteristics
• Useful when a local display, or
an additional function, is needed.
• RTD (4 channel) and DC V / mA
(8 channel) models
• Built-in arithmetic functions
• Relay and analogue output options
• RS422/485 (Modbus)
communications options
• Loop powered digital displays
• Auxiliary powered temperature,
frequency and dc options
• Analogue and multi-relay
output options
• 8 digit flow rate/volume monitor
D
D.2
Provides power for input transmitter
Passes HART communications
High isolation voltage
6mm wide housing
Universal signal isolator/converter –
WAVEPak DC/DC
Page D.88
Current Test – without removing
cables!
Page D.88
Analogue signal Conditioning
Overview
Universal transmitter – ITX Plus
Page D.90
Power
–
3
5 –
Milliamp input
4
6
Isolator/
convertor
Output
8
2
+
+
Portacal as an ammeter
D
WavePak
• DC V and mA inputs / outputs
in one unit
• Push-button calibratable
• Provides power for input loop,
if required
• mA Input may be source or sink
• Just use an ammeter across
the “test” terminals
• Saves time with system commissioning
• For input and output testing
• Will be incorporated into further
Weidmüller developments
• Temperature, resistance, pot
and DC inputs
• 4...20mA OLP output
• User-definable linearization
• Computer-configurable
Instrument Calibrators
Page D.159
Transmitter input power supply
Wider range of Approvals
Isolator
+24 V DC
Flow
Tx
I
CurrentInput
4...20 mA
V/I
Output
0...11 V /
0...22 mA
% \ u
PS
24 V DC supply
• Sources and meters
of low DC V and mA
• For checking instrument
and valve operation
• Low cost tools for instrument
engineers and technicians
• Compact, portable, easy to use.
• Now available with more Weidmüller
dc input conditioners
• Saves cost of providing separate DC
power for transmitters
• Simplifies cabling installation
• Improves isolation and reliability of
measurement systems
• More WAVESERIES now offer C1D2
• MANN SERIES now has UL (Listing)
• WAVESERIES GL approvals
are expanding
• Further approvals are in process for
WAVE-, MICRO- and MANN SERIES.
D.3
Analogue signal Conditioning
D
Introduction
Analogue signal conditioning questionary
Where…are analogue conditioners used?
What…functions do analogue conditioners provide?
In all types of electronic industrial and marine measurement and
control systems – for example in processes such as power
plants, steelworks, water and waste plant, oil and gas production
and chemical processing. In fact, wherever temperature, pressure, level, flow, weight, speed etc is measured and controlled
as part of a continuous or batch production process. Such
measurement parameters – after being accurately produced –
must not be degraded on their way from the field to the control
room, despite external influences from the atmosphere and
installation. Conversion or changes to these signals requires
electronics of the highest quality, which can also withstand wide
ambient temperature changes, electro-magnet interference, a
vibrating environment, corrosive or hazardous atmospheres.
One or more of the following:
1) Isolation of high level DC measurement and control signals.
(Why do we need isolation? – see the notes that follow later
in this brochure.)
2) Conversion of high level signals, such as 0...5 V input to
4…20 mA output
3) Amplify, linearise and transmit low level sensor inputs, such
as millivolts from thermocouples, into high level DC outputs to
enable transmission over distances 100 m or more.
4) Initiate status indications and alarms by creating relay contact
closure outputs from analogue inputs.
D.4
Why…do we need separate analogue module nowadays?
Surely the control system (PLC or DCS) can perform the
same functions?
1) Sometimes this is true, but look at where the cabling from the
field devices (transmitters, sensors, valves and actuators)
needs to go. It will usually go not just straight to the control
system. Many signals are also passed to local indicators and
alarms, and each will need isolating from the others.
2) Often sensors - like thermocouples for temperature – need
isolating, converting and linearising locally to a standardized
high level signal (e.g. 4…20 mA) for long distance
transmission – instead of running expensive compensation
cable to the control system.
Analogue signal Conditioning
Introduction
How…can I select the right product for my application?
1) Weidmüller has a formidable range of analogue conditioners,
covering most application requirements, and our range is
expanding. We also have some useful tools for selection and
configuration.
2) If you cannot find a suitable product for your application, it
doesn’t mean we don’t have one! Tell us your requirement,
and if we can’t provide a solution from our current range of
products, there may be a customized version that we could
create for you.
3) Where the control system has no isolated analogue inputs,
a separate isolator will often be needed.
4) Where the control system cannot provide power for the
senor / transmitter and it is convenient to do this from an
isolating module.
5) Where a high integrity, dedicated display is required, separate
from the control system display, and the input needs splitting.
6) Where local linearization is needed for a plant operator –
for example where a liquid volume indicator is needed for
filling a bulk storage tank, but the measurement is level (level
to volume conversion depends on the shape of the tank).
7) Where the control system only takes 4…20 mA analogue
inputs and the sensors provide other less common ranges,
such as 0…20 mV, 2…10 V, 0…10 kΩ, 0…1mA, 4…12 kHz,
0…5 A AC etc
8) Where the control system needs to be protected from
electrical noise pulses on it’s analogue inputs
9) Where expansion of the analogue inputs would mean an
expensive new I/O board for the control system
D.5
D
Analogue signal Conditioning
Introduction
Different types of analogue signaling
The working environment can be measured in many different
forms, e.g. in terms of temperature, humidity or air pressure. The
values of these physical variables change constantly. Elements
that monitor the statuses and status changes of a given environment and supply an indication of this changing environment
must be able to portray the continuous change.
D
In industrial monitoring tasks, sensors are responsible for
registering ambient statuses. Sensors provide signals which
allow detailed conclusions for downstream evaluation and
monitoring systems with detailed conclusions about the
statuses or status changes, e.g. in a production process.
Sensor signals monitor continuous changes in the field. They
occur in digital and analogue form. As a rule, they supply an
electrical voltage or current value which corresponds proportionally to the physical variables being monitored.
If automation processes are expected to reach certain statuses
or keep them constant, then analogue signal conditioning is
required. It is also important in areas where this has already
been part of long established practice, e.g. in process engineering or the chemicals industry.
In process engineering, standardised electrical signals are
normally used. Currents of 0 … 20 mA, 4 … 20 mA or voltages
of 0 ... 10 V have become established as the output variables
for sensors recording various different physical parameters.
Weidmüller takes account of the growing preference for
automation – including and in particular with analogue signal
conditioning – and offers a wide range of products tailor-made
to the requirements involved in handling sensor signals. Units
for the common signals (0 ... 20 mA, 4 ... 20 mA, 0 ... 10 V)
generate an output signal as a proportional value of the
variable input signal. “Protective separation”, e.g. of the sensor
circuit from the evaluation circuit, is also taken into account.
“Protective separation” prevents mutual interference among
several sensor circuits, e.g. as in the case of earth loops in
interlinked measuring circuits.
The wide range of Weidmüller products completely covers
the functions involved in signal conversion, signal separation
and signal monitoring. The products can thus handle nearly all
applications in industrial measuring technology, and safeguard
elementary functions between field signals and further processing systems. The mechanical properties of the products are
built up around a consistent concept.
D.6
Signal converters can be used with other Weidmüller products
and combined with each other. They are designed to entail a
minimum wiring workload and maintenance in both electrical
and mechanical terms.
The product range contains the following functions:
• DC/DC converters
• Current converters
• Voltage converters
• Temperature transformers for resistance thermometers and
thermoelements
• Frequency converters
• Potentiometer transducers
• AC transducers
• Bridge transducers (strain gauges)
• Threshold monitoring modules
• AD/DA converters
The products are available as pure signal conversion, 2-way
isolation, 3-way isolation and passive disconnectors –
depending on the production functions in each case.
Analogue signal Conditioning
Introduction
2-way isolation separates the signals from each other electrically and decouples
the measuring circuits. Potential differences – caused by long line lengths and
common reference points – are eliminated. Furthermore, the electrical separation
protects against irreparable damage caused by overvoltages as well as inductive
and capacitive interference.
3-way isolation decouples the supply voltage from the input and output circuits
as well and enables the function to operate with just one operating voltage.
D
The passive separator offers an extra, decisive advantage – it requires no additional voltage supply. The power supply to the module is achieved via the input or
output circuit and is transmitted to the input/output. This current loop feed is characterised by a very low consumption.
A number of products are available for temperature measurements. For example,
PT100 signals in 2-, 3- and 4-wire systems are converted into standard 0…20 mA,
4…20 mA and 0…10 V signals.
The modules for connecting conventional thermoelements are fitted with cold trap
compensation as standard. Furthermore, they amplify and linearise the voltage signal
provided by the thermocouple. This guarantees accurate analogue signal conditioning while eliminating sources of interference or error.
Frequency converters convert frequencies into standard analogue signals.
Downstream controls can therefore directly process pulse strings for measuring
rpm or speed.
AD or DA converters are required for bringing together the analogue signal forms
mapping the local conditions and the digital processing in the process monitoring
system. Weidmüller can supply such components for the customary 0…20 mA,
4…20 mA and 0 …10 V input and output signals. 8-bit processors are available
on the digital side.
Current monitoring modules make it possible to control limiting currents and AC
currents up to 60 A. A switching operation is triggered when the set current values
are not met or exceeded. Components with analogue outputs monitor the current
load continuously via downstream controls.
Voltage monitoring modules can be used to monitor AC and DC voltages.
Adjustable switching thresholds can be used to reliably detect and notify in the
event of fluctuations caused by switching operations or mains overloads.
D.7
Analogue signal Conditioning
Introduction
Technical data
• The feed can be effected from either the input or the output
side. Isolation is by transformer barrier. The advantages are:
cessation of network influences, outstanding accuracy, low
signal delay and low potential requirement. Passive isolators
are not non interacting; a change in load in the output circuit
will influence the input circuit.
Ground Loops
D
Common Mode Noise Elimination
• Generally, signals emitted by sensors have low levels and are
thus susceptible to capacitive and inductive interference,
such as those generated by motors, frequency changers and
other change processes.
This noise contents the measuring value and frequently
destroy expensive analog I/O cards in the control electronics.
Through the utilisation of analog signal isolators this interferace, which usually action both signal lines in common mode
(push push), is effectively eliminated through the zero
potential input.
• The voltage supply‘s secondary side is earthed for the
purpose of setting up fast and secure ground loop monitoring.
If an analog signal is fed in from a separate voltage supply or
if the sensing device itself is earthed, then transient currents
will flow between the ground potentials across the interconnected ground connectors, which in turn corrupts the
measuring signal.
Analog signal isolating amplifiers prevent this form of measuring signal corruption and influence.
2-port Isolation
Active Isolator / Passive Isolator
• Active isolators draw their power supply from a separate
supply terminal to ensure that they can operate perfectly.
Depending upon the applications the input, output and
additionally the power supply are isolated from each other.
Only one supply is required for 3-port isolation. However, it is
isolated from the input and output circuits. Thus even in the
event of a short circuit, surge voltage or reverse polarity, the
downstream control electronics cannot be damaged. Isolating
the signals between the input and output can be conducted
either optically or by transformer barrier depending upon the
transfer rate. Active isolators are non interacting, i.e. a
change in the load does not exert any influence on an input
circuit.
• Passive isolators generate the current required for the supply
from the measuring signal. The current required internally is
so small that transfer problems do not occur here.
D.8
• The simplest form of analog signal isolator is that of 2-port
isolation. It serves to isolate the input circuit from the output
circuit as well as the two auxiliary voltages from each other.
Depending upon the isolator design and the observed isolation data one refers here to base isolation (galvanic isolation)
or safe separation. For current signals, 4...20 mA input current loop fed modules
are available. An additional auxiliary voltage for the input
circuit is not requin with here. By connecting the input and output side voltage supplies, the
2-port isolation can be converted to operate as a simple
signal converter. This is of particular interest where isolation is
not required for an application, but a signal conversion has to
be performed.
3-port Isolation
Temperature Signal Measuring Method
• 3-port isolation is the most universal form of signal isolator
• An optical coupler or transformer isolates the input from the
output circuit. Together with the clearance and creepage
distances it serves to define the isolation level. For example,
the input signal is converted by means of pulse-width modulation into a frequency signal and demodulated again on the
output side to form an analog value. An amplifier then
generates a standardised analog signal. A galvanic isolated
DC/DC converter feeds the input and output circuit with a
potential free supply voltage. It too determines the isolation
level through its data, air and creepage distances.
In the case of these three isolation paths (input/output,
input/auxiliary voltage, output/auxiliary voltage) one refers to
3-port isolation.
• Measurements using thermocouples
When conducting measurements using thermocouples the
voltage that is generated when two differently alloyed metals
come into contact with each other is measured.
A differential amplifier is then used to recondition the signal.
The easiest (and thus the most cost effective) method of sub
sequent processing is conducted by means of an amplifier
circuit, which converts these signals into standard signals.
High-end components process the measuring signal using a
microprocessor, which simultaneously reconditions the signal
(filtering, linearisation)
Cold Junction Compensation For Thermocouples
• Recording temperatures by using thermocouples encounters
the problem of a thermal voltage forming at the clamping
terminals on the signal converter on account of the different
materials in the conductors and bus bar. This voltage then
counteracts the thermal element‘s voltage.
Temperature Signal Measuring Method
• Measurement using resistors (RTD)
When measuring with temperature-dependent resistors a
current of approx. 1.5mA is passed through the resistor from
a constant current source in the signal converter.
In order to compensate for the error to the measured value
which arises here, the temperature is measured at the
clamping terminal. The microprocessor in the signal converter
reads the value measured there and calculates it against the
measured value. This procedure is known as cold junction
compensation.
Voltage at the measuring point (Vmeas)
+ Voltage at the terminal (Vterminal)
= Voltage at the thermocouple (Vthermo)
=> Temperature at the thermocouple (Tthermo)
An operational amplifier is used to measure the potential
drop at the resistor (2-wire circuit).
In order to take account of lead length, the voltage drop is
measured at the return conductor and calculated with double
the value (3-wire circuit). This thus simulates the wire
resistances from the feed and return lines.
Accurate measurements are achieved by separately measuring the voltage drop at the feed and return lines (4-wire
circuit). The values for the supply lines are calculated against
the measured value.
Linearisation
• Temperature-dependent components do not normally have
linear characteristic curves. To ensure that further processing
can take place with the necessary accuracy, these characteristic curves have to be linearised to some extent.
The graph showing measurements of thermocouples, in particular, reveals significant deviations at some points from the
"ideal graph”. As a consequence, the signal which has been
measured is worked up by a microprocessor.
D.9
Analogue signal Conditioning
Introduction
D
Analogue signal Conditioning
Introduction
The secondary winding supplies the measuring electronics
with a proportional current signal. Because of power loss this
method of measuring current is limited to smaller currents up
to 5 A. These converters react sensitively to peak loads and
therefore have to be fused on the primary winding side.
Measuring Current Using A Hall-type Sensor
D
The microprocessor compares the value measured with the
characteristic curve for the thermocouple in its memory and
calculates the corresponding value on the “ideal characteristic
curve”. At the output, it supplies the latter to an amplifier, which
produces the analogue value in linear form. The output stage
converts this into a standardised value or into a switching output with a switching threshold.
The linearisation of PT100-elements can be undertaken via
simple amplifier stages. The first stage corrects the peak val
ue of the graph of the measurements. The deviation at the
end of the graph resulting from this is corrected by a second
stage. The under- and over-shooting generated in this way is
very slight and is covered by the tolerance for the module.
• Hall-type sensor principle
Hall-type sensors also measure the magnetic flux B and
supply a proportional voltage at the measured output, which
is then reconditioned to form a standard signal by an amplifier
circuit.
• Components with Hall-type sensors are ideally suited to
measuring higher currents, as any possible high residual
currents from motors or peak loads cannot damage the
component. Additionally, they are also ideal for measuring
direct and alternating currents of various curve shapes.
Current Measurement Using A Measuring Transformer
• Transformer principle Each conductor through which current
flows is surrounded by a magnetic field H, the intensity of
which is proportional to the current. The field, which is
bundled in a magnetic core, generates a magnetic flux B,
through which suitable sensors are used to measure current.
Converters with transformer-type couplings are used to
establish the most cost effective measurement method for
simple sinusoidal currents. The current to be measured flows
directly through the measuring transformer‘s primary winding.
D.10
Root Mean Square Measurement / Crest Factor
• The root mean square value (r.m.s) of a sinusoidal shaped
alternating current is the value, which in an ohmic resistor
converts the same (effective) output as that of an equal sized
direct current.
• Non sinusoidal shaped signals can only be measured with
“True RMS” capable devices and/or further processed.
• True RMS = True root mean square
• Root mean square measurement is required where the
(effective) output content of alternating voltages or
currents are to be measured or evaluated.
• The crest factor indicates the ratio of the crest factor to the
root mean square value.
Load / Load Resistor
Hysteresis
• The load is a load resistor on the output side of a measuring
transducer or isolating amplifier.
For current outputs the load is generally 500 Ω.
Voltage outputs usually have a 10 KΩ load.
• Hysteresis indicates the percentage difference between the
input and output points of a switching contact. It should not
be lower than a given minimum value, as otherwise a
specified chase can no longer be implemented.
Peak value
Root mean
square value
Broken-wire Detection
D
• When measuring transformers with
broken wire detection the input signal is monitored permanently. In the event of a fault (broken wire) the output signal
exceeds its rated range. The downstream control circuit can
then analyse the fault case.
Response Time
Galvanic Isolation / Safe Separation
• Galvanic isolation is understood to mean an electrical isolation between the input and output circuit and the circuit‘s
supply voltage. It can be set up either optically using an opto
coupler or with a transformer. The isolation serves to
safeguard the measuring circuit against damage and to
eliminate ground loops, which could cause the measured
signal to be corrupted.
• Safe separation is specified under the German DIN VDE 0106
Section 101 standard. This fundamental safety standard is
intended to safeguard persons against hazardous body
currents and describes the basic requirements for safe separation in electrical operating equipment. Thus, for instance,
the voltage supply of 50 V AC/ 120 V DC as under 50178
may not be exceeded. If this voltage is exceeded a reinforced
or double insulated and thus an increase in the clearance and
creepage distances is stipulated.
Cut-off Frequency
• Cut-off frequencies indicate the dynamic transfer characteristic of an isolation amplifier.
• The given frequency is the (-3dB-) limit, at which a distinct
change occurs to the signal.
• An increased cut-off frequency leads to a transmission of
higher-frequency alternating components, which corrupts the
required signal.
Analogue signal Conditioning
Introduction
• Response time refers to the change in output signal for
an input signal jump (10...90 %). It is directly related to the
cut-off frequency (inversely proportional).
Accuracy / Temperature Coefficient
• Accuracy describes the capability of a measuring device to
deliver a measured value as accurately as possible. It relates
to the end value and is given for ambient temperature (23°C).
Example:
An RTD is given with an accuracy of 1 %. The measuring
range is set to 0-200 °C. The expected effective error of:
200*1 % = +/– 2K applies across the entire measurement
range.
• Temperature coefficiency describes the deviations in accuracy
of the measuring devices dependent on the ambient
temperature. It is given as a % or in parts per million / Kelvin
(ppm /K).
Example:
An RTD with an accuracy of 1 % and a measuring range of
0-200 °C has a temperature coefficiency of 250 ppm / K. If
the device is operated at +40 °C, it will then contribute the
following to an expected absolute error:
(([40°C-23°C] *250ppm/K) +1%) *200K) = +/- 2,85K
across the entire measurement range.
D.11
Analogue signal Conditioning
WAVESERIES
WAVESERIES
The modules in the WAVE SERIES are ideal when users need
analogue separating transducers. Weidmüller’s WAVE SERIES
combines the compact, space-saving design of the WAVEBOX
housing with many different functions. The product range offers
a wide range of signal transducers.
D
Features
• Independent connection system – screw or tension clamp
with plug-in socket connector
• Assembly without tools
• Fast commissioning – plug-in spare boards
• Standardised current and voltage signals
• Cross-connectors for low wiring workload
• Highly functional
• Clear type designations for simple selection
• Ideal size – for more space in the control cabinet
• A cost effective solution
Replacement
The PCB can be removed from the enclosure without any tools. Simply press in the
locking hook at the top and pull out the upper part with connection plane and PCB.
Cross-connection
Cross-connectors are used to connect units in the same
series to bridge and transmit the power supply from one
module to the next.
Safety
“Protective separation” has to be guaranteed as per EN 50178. WAVE SERIES
complies with this requirement to the full with analogue signal transmission with
potential separation.
Coding
The coding elements can be used to code the module for screw and also tension clamp
connections without loss of poles. In this way, it is not possible to confuse the plugs.
Connecting
BLZ (screw) or BLZF (tension clamp) connectors offer the greatest
possible flexibility at the wiring stage (up to 2.5 mm2).
Housing (WAVEBOX)
The WAVEBOX is an ideal combination of technology, design and functionality. The
enclosure is made of recyclable plastic and comes in three different widths. It needs
practically no tools for assembly and fulfils the EMC requirements. Ventilation slots
allow good heat dissipation.
D.12
WAVESERIES Analog PRO is a versatile group of auxiliary
powered, 3 port isolating transmitters, with customer settable
inputs / outputs via DIP switches, and DC mA and V outputs.
PRO DC/DC – converts DC inputs from as low as 20 mV
and up to 200 V.
PRO Thermo – provides linearised outputs, relating to temperature ranges for all of the commonly used thermocouple
measurements up to 1820 °C
PRO RTD – connects by 2, 3 or 4 wires to Platinum, Copper
or Nickel resistance thermometers for ranges between -200 °C
and 850 °C.
PRO Frequency – provides the sensor supply, and measure
speeds, rates, frequencies, converting PNP, NPN inputs,
including Namur standard initiators, up to 100 kHz
• Inputs and DC outputs are selectable via DIP switches,
without further calibration
• Hall-effect sensor option, which allows the cable measured
to be fed through the WAVECONTROL housing, making the
use of a current transformer unnecessary for applications up
to 60 A.
• DIN rail mountable current transformers for measurements up
to 500 A
D
WAVEDATA is a useful isolator option for interface conversion,
with:
• A choice of RS232 to RS 485/422 or RS 232 to
TTY interfacing
• 3-way isolation
• DIP switch configurability
PRO Bridge – measures weight and load, providing the load
cell sensor supply, accepting inputs from 10 mV up to ±500 mV
Interface conversion with
WAVEdata
WAVETOOL is a support software application for
WAVEANALOG PRO products. Downloadable to your PC or
laptop, WAVETOOL is there to help you…
AC and DC current monitoring
Current transformers are available as
with WAVECONTROL
input source for WAVECONTROL
Analogue signal Conditioning
WAVESERIES
• Verify that the input / output combination required can
be done
• Illustrate the DIP switch positions required
WAVECONTROL is a sub-section of the WAVESERIES range,
focused on AC voltage and current monitoring. Typical applications include low voltage distribution line or phase voltage
measurements, and current monitoring for AC motors. Apart
from including the Wave construction features above
WAVECONTROL offers.
• Direct AC or DC current inputs up to 60 A, or AC voltages
up to 450 V.
D.13
Input current loop feed
CCC LP
CCC LP
• Reliable isolation
(1-channel)
(2-channel)
Input
/0(4)…20 mA current loop
Input
/0(4)…20 mA current loop
18 V /50 mA /max. current
< 100 μA ent
approx. 3V at RL = 0 M approx. 13V at RL = 500 M(IIN =20mA)
Output
/0(4)…20 mA /Output current
/≤ 500 Ω voltage/Current
< 0.1% of final value
≤ 50 ppm/K of final value
< 0.1% of measurement value/100 Ω load resistance
< 20 mVeff
approx. 170 kHz y
General data
-25 °C…+70 °C ature
-40 °C…+80 °C ure
CSA / GL / cULus / CE
Insulation coordination
EN 50178 (protective separation)
EN 55011, EN 61000-6
300 V voltage
6 kV se withstand voltage
4 kVeff / 1 s output
III e category
2 llution severity
≥ 5,5 mm & creepage distance
18 V /50 mA /max. current
< 100 μA ent
approx. 3V at RL = 0 M approx. 13V at RL = 500 M(IIN =20mA)
Output
/0(4)…20 mA /Output current
/≤ 500 Ω voltage/Current
< 0.1% of final value
≤ 50 ppm/K of final value
< 0.1% of measurement value/100 Ω load resistance
< 20 mVeff
approx. 170 kHz y
General data
-25 °C…+70 °C ature
-40 °C…+80 °C ure
CSA / GL / cULus / CE
Insulation coordination
EN 50178 (protective separation)
EN 55011, EN 61000-6
300 V voltage
6 kV se withstand voltage
4 kVeff / 1 s output
III e category
2 llution severity
≥ 5,5 mm & creepage distance
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
• Very low power consumption
U E [V]
Analogue signal conditioning
WAVESERIES - DC/DC passive isolator
14
12
10
8
6
4
2
0
0
100
200
300
RL
400
500
600
D
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Pick-up current
Voltage drop t RL = 0 approx. 13V at RL = 500 M(IIN =20mA)
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy f final value
Temperature coefficient value
Influence of load impedance lue/100 Ω load resistance
Residual ripple eff
Chopper frequency
General data
Operating temperature
Storage temperature
Approvals / cULus / CE
Insulation coordination
Standards (protective separation)
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS5 CCC LP 0-20/0-20mA
WAZ5 CCC LP 0-20/0-20mA
Qty.
1
1
Order No.
8444950000
8444960000
Type
WAS5 CCC LP 0-20/0-20mA
WAZ5 CCC LP 0-20/0-20mA
Note
Accessories
Note
D.14
Markers see Accessories WAVESERIES
Markers see Accessories WAVESERIES
Qty.
1
1
Order No.
8463580000
8463590000
Output current loop feed
OLP
• Electrical isolation
• Very low power consumption
• Input range selected via DIP switch
• No calibration necessary
Analogue signal conditioning
WAVESERIES - DC/DC passive isolator
D
Technical data
Input
Input voltage
max. voltage
Input resistance, voltage/Current 0 kΩ /51 Ω
Input current
max. current
Input
0…(5)10 V e
Output
Output current rent loop)
Output signal limit
Load impedance, voltage/Current -1/ 20 mA e.g. 600 M a 24
Accuracy measuring range final value
Temperature coefficient
Residual ripple sub> at 500 Ω
Step response time 0 Hz: 50 ms
Cut-off frequency (-3dB)
General data
Supply voltage max. 30 V DC
Operating temperature
Storage temperature
Default setting
Approvals s
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Setting options/switch position
30 V DC tage
0…5V: 210 kΩ; 0…10V: 430 kΩ /51 Ω
0(4)…20 mA
40 mA urrent
Output
4…20 mA (current loop)
approx. 24 mA limit
/RL = (UB-12 V) / 20 mA e.g. 600 M at 24 V
0.2% of measuring range final value
≤ 150 ppm/K fficient
50 mVeff at 500 Ω
< 10 Hz: 80 ms; 100 Hz: 50 ms
10 Hz/ 100 Hz switchable
General data
min. 12 V DC/ max. 30 V DC
0°C…+55°C (fitted)
-20 °C…+85 °C ure
0…20mA, 10 Hz
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
4 kVeff / 5 s output
III e category
2 llution severity
≥ 5,5 mm & creepage distance
Input
1
2
SW 1
3
4
0…20 mA
4…20 mA
0…5 V
n
n
n
n
n
n
n
n
n
n
n
n
0…10 V
Transmission frequency
10 Hz
100 Hz
n
n
n
n
n
n
n
n
n
n
n
n
n
n
= on
= off
Example of application
230Vac
24Vdc
~
~
24Vdc
1
2
3
230Vac
WAVE ANALOG
OLP
8543720000/8543730000
7
8
9
4 ... 20mA
0...10V
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
SPS
RL
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS5 OLP
WAZ5 OLP
Qty.
1
1
Order No.
8543720000
8543730000
Note
Accessories
Note
Markers see Accessories WAVESERIES
D.15
Analogue signal conditioning
WAVESERIES - DC/DC passive isolator
Signal distributor
2OLP
• Electrical isolation
• Input and output current loop feed
• Very low power consumption
• No calibration necessary
D
Technical data
Input
Input current rrent loop)
max. current
Voltage drop
Input
4…20 mA (current loop)
Example of application
Output
Output current (current loop)
Output signal limit
Load impedance, voltage/Current -12 V) / 20 mA e.g. 600 M
Accuracy 0.1%, max. 0.2%
Temperature coefficient
Step response time
Cut-off frequency (-3dB)
General data
Supply voltage max. 30 V DC
Operating temperature
Storage temperature
Approvals s / C1D2ATEX
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
40 mA urrent
3.8 V e drop
Output
2 x 4…20 mA (current loop)
approx. 31 mA limit
/RL = (UB-12 V) / 20 mA e.g. 600 M at 24 V
typical 0.1%, max. 0.2%
≤ 150 ppm/K fficient
< 20 ms ponse time
30 Hz f frequency (-3dB)
General data
min. 12 V DC/ max. 30 V DC
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CE / cULus / C1D2 / ATEX
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
4 kVeff / 5 s output
III e category
2 llution severity
≥ 5,5 mm & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
mm2
mm
Note
24V DC
Sensor
230 V AC
~
24 V DC
4 ... 20 mA
1
WAVE ANALOG
2
2OLP
3 8581160000/8581170000
4 ... 20 mA
SPS
RL1
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Ordering data
Screw connection
Tension clamp connection
Type
WAS5 CCC 2OLP
WAZ5 CCC 2OLP
Note
Accessories
Note
D.16
Markers see Accessories WAVESERIES
Qty.
1
1
10
11
12
4 ... 20 mA
RL2
Tu=23°C, single module
Type of connection
7
8
9
Order No.
8581160000
8581170000
On output side,
power supply
4…20 mA/4…20 mA
4…20 mA/0…20 mA
4…20 mA/0…10 V
• Signal conversion
• Electrical isolation between input
and output signals
• Power supply can be crossconnected using ZQV cross
connection system
Analogue signal conditioning
WAVESERIES - DC/DC 2-way isolator
D
Technical data
Input
Input voltage/Input current
max. voltage
max. current
Input
/4…20 mA (current loop) t
Input
/4…20 mA (current loop) t
Input
/4…20 mA (current loop) t
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy 0.2% of final value
Temperature coefficient value
Step response time lly 20 ms)
Cut-off frequency (-3dB) Hz)
General data
Supply voltage n; 20 %
Current consumption T = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals us / CE
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
7 V voltage
25 mA urrent
Output
/4…20 mA age/Output current
/≤ 500 Ω voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 20 ms)
≥ 15 Hz (typically 20 Hz)
General data
24 V DC ± 20 %
< 32 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
7 V voltage
25 mA urrent
Output
/0…20 mA age/Output current
/≤ 500 Ω voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 20 ms)
≥ 15 Hz (typically 20 Hz)
General data
24 V DC ± 20 %
< 32 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
7 V voltage
25 mA urrent
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 20 ms)
≥ 15 Hz (typically 20 Hz)
General data
24 V DC ± 20 %
< 20 mA at IOUT = 10 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Note
Tu=23°C, single module
Tu=23°C, single module
Tu=23°C, single module
Type
(Qty.=1) Order No.
WAS4 CCC DC 4-20/4-20MA 8444980000
WAZ4 CCC DC 4-20/4-20MA 8444990000
Type
(Qty.=1) Order No.
WAS4 CCC DC 4-20/0-20MA 8445010000
Type
(Qty.=1)
WAS4 CVC DC 4-20/0-10V
WAZ4 CVC DC 4-20/0-10V
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Ordering data
Type of connection
Screw connection
Tension clamp connection
Order No.
8445040000
8445050000
Note
Accessories
Note
D.17
Analogue signal conditioning
WAVESERIES - DC/DC 2-way isolator
Voltage supply
both sides
0…20 mA/0…20 mA
0…20 mA/4…20 mA
0…20 mA/0…10 V
Input
/0…20 mA ge/Input current
Input
/0…20 mA ge/Input current
Input
/0…20 mA ge/Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy 0.2% of final value
Temperature coefficient value
Step response time lly 16 ms)
Cut-off frequency (-3dB) Hz)
General data
Supply voltage n; 20 %
Current consumption, input = 20 mA
Current consumption, output = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals us / CE
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
/25 mA ltage/max. current
/50 Ω ance, voltage/Current
Output
/0…20 mA age/Output current
/≤ 500 Ω voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 16 ms)
≥ 15 Hz (typically 25 Hz)
General data
24 V DC ± 20 %
< 11 mA at IIN = 20 mA
< 32 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
/25 mA ltage/max. current
/50 Ω ance, voltage/Current
Output
/4…20 mA age/Output current
/≤ 500 Ω voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 16 ms)
≥ 15 Hz (typically 25 Hz)
General data
24 V DC ± 20 %
< 11 mA at IIN = 20 mA
< 32 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
/25 mA ltage/max. current
/50 Ω ance, voltage/Current
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 16 ms)
≥ 15 Hz (typically 25 Hz)
General data
24 V DC ± 20 %
< 11 mA at IIN = 20 mA
< 20 mA at IOUT = 10 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Note
Tu=23°C, single module
Tu=23°C, single module
Tu=23°C, single module
Type
(Qty.=1) Order No.
WAS4 CCC DC 0-20/0-20MA 8445070000
Type
(Qty.=1) Order No.
WAS4 CCC DC 0-20/4-20MA 8446970000
Type
(Qty.=1)
WAS4 CVC DC 0-20/0-10V
WAZ4 CVC DC 0-20/0-10V
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
• Signal conversion
• Electrical isolation between input
and output signals
• Power supply can be crossconnected using ZQV cross
connection system
D
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Ordering data
Type of connection
Screw connection
Order No.
8447020000
8447030000
Note
Accessories
Note
D.18
Voltage supply
both sides
0…10 V/0…20 mA
0…10 V/4…20 mA
0…10 V/0…10 V
• Signal conversion
• Electrical isolation between input
and output signals
• Power supply can be crossconnected using ZQV cross
connection system
Analogue signal conditioning
WAVESERIES - DC/DC 2-way isolator
D
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Input
0…10 V / age/Input current
Input
0…10 V / age/Input current
Input
0…10 V / age/Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy 0.2% of final value
Temperature coefficient value
Step response time lly 25 ms)
Cut-off frequency (-3dB) Hz)
General data
Supply voltage n; 20 %
Current consumption, input = 10 V
Current consumption, output = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals us / CE
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
15 V / oltage/max. current
500 kΩ / ce, voltage/Current
Output
/0…20 mA age/Output current
/≤ 500 Ω voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 25 ms)
≥ 13 Hz (typically 17 Hz)
General data
24 V DC ± 20 %
< 11 mA at UIN = 10 V
< 32 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
15 V / oltage/max. current
500 kΩ / ce, voltage/Current
Output
/4…20 mA age/Output current
/≤ 500 Ω voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 25 ms)
≥ 13 Hz (typically 17 Hz)
General data
24 V DC ± 20 %
< 11 mA at UIN = 10 V
< 32 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
15 V / oltage/max. current
500 kΩ / ce, voltage/Current
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 30 ms (typically 25 ms)
≥ 13 Hz (typically 17 Hz)
General data
24 V DC ± 20 %
< 11 mA at UIN = 10 V
< 20 mA at IOUT = 10 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Note
Tu=23°C, single module
Tu=23°C, single module
Tu=23°C, single module
Type
(Qty.=1) Order No.
WAS4 VCC DC 0-10/0-20MA 8447050000
WAZ4 VCC DC 0-10/0-20MA 8447080000
Type
(Qty.=1) Order No.
WAS4 VCC DC 0-10/4-20MA 8447100000
WAZ4 VCC DC 0-10/4-20MA 8447110000
Type
(Qty.=1)
WAS4 VVC DC 0-10/0-10V
WAZ4 VVC DC 0-10/0-10V
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Ordering data
Type of connection
Screw connection
Tension clamp connection
Order No.
8447130000
8447140000
Note
Accessories
Note
D.19
Analogue signal conditioning
WAVESERIES - DC/DC 3-way isolator
10 Hz limiting frequency
0…(4)20 mA/0…(4)20 mA
0…20 mA/4…20 mA
0…20 mA/0…10 V
Input
/0(4)…20 mA Input current
Input
/0…20 mA ge/Input current
Input
/0…20 mA ge/Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy
Temperature coefficient
Step response time
Cut-off frequency (-3dB)
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature ounting)
Storage temperature
Approvals s
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
max. voltage
25 mA urrent
Output
/0(4)…20 mA /Output current
/≤ 600 Ω voltage/Current
0.2 % cy
± 250 ppm/K ient
≤ 45 ms se time
10 Hz f frequency (-3dB)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (horiz. mounting)
-20 °C…+85 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
max. voltage
25 mA urrent
Output
/4…20 mA age/Output current
/≤ 600 Ω voltage/Current
0.2 % cy
± 250 ppm/K ient
≤ 45 ms se time
10 Hz f frequency (-3dB)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (horiz. mounting)
-20 °C…+85 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
max. voltage
25 mA urrent
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
0.2 % cy
± 250 ppm/K ient
≤ 45 ms se time
10 Hz f frequency (-3dB)
General data
24 V DC ± 25 %
< 1.3 W at IOUT = 5 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (horiz. mounting)
-20 °C…+85 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Note
Tu=23°C, single module
Tu=23°C, single module
Tu=23°C, single module
• Signal conversion
• Electrical isolation between
input/output signal / power supply
• Power supply can be crossconnected via plug-in bridges
D
Technical data
Input
Input voltage/Input current
max. voltage
max. current
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
(Qty.=1)
WAS5 CCC 0-20/0-20mA
WAZ5 CCC 0-20/0-20mA
Order No.
8540180000
8540190000
Type
(Qty.=1)
WAS5 CCC 0-20/4-20mA
Order No.
8540250000
Type
(Qty.=1)
WAS5 CVC 0-20mA/0-10V
Order No.
8540270000
Note
Accessories
Note
D.20
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
10 Hz limiting frequency
4…20 mA/0…20 mA
4…20 mA/0…10 V
• Signal conversion
• Electrical isolation between
input/output signal / power supply
• Power supply can be crossconnected via plug-in bridges
Analogue signal conditioning
WAVESERIES - DC/DC 3-way isolator
D
Technical data
Input
Input voltage/Input current
max. voltage
max. current
Input
/4…20 mA ge/Input current
Input
/4…20 mA ge/Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy
Temperature coefficient
Step response time
Cut-off frequency (-3dB)
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature ounting)
Storage temperature
Approvals s
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
max. voltage
25 mA urrent
Output
/0…20 mA age/Output current
/≤ 600 Ω voltage/Current
0.2 % cy
± 250 ppm/K ient
≤ 45 ms se time
10 Hz f frequency (-3dB)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (horiz. mounting)
-20 °C…+85 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
max. voltage
25 mA urrent
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
0.2 % cy
± 250 ppm/K ient
≤ 45 ms se time
10 Hz f frequency (-3dB)
General data
24 V DC ± 25 %
< 1.3 W at IOUT = 5 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (horiz. mounting)
-20 °C…+85 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Note
Tu=23°C, single module
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Type
(Qty.=1)
WAS5 CCC 4-20/0-20MA
Order No.
8540200000
Type
(Qty.=1)
WAS5 CVC 4-20mA/0-10V
Order No.
8540230000
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
D.21
Analogue signal conditioning
WAVESERIES - DC/DC 3-way isolator
10 Hz limiting frequency
0…10 V/0…20 mA
0…10 V/4…20 mA
0…10 V/0…10 V
Input
0…10 V / age/Input current
Input
0…10 V / age/Input current
Input
0…10 V / age/Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy
Temperature coefficient
Step response time
Cut-off frequency (-3dB)
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature ounting)
Storage temperature
Approvals s
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
15 V voltage
max. current
Output
/0…20 mA age/Output current
/≤ 600 Ω voltage/Current
0.2 % cy
± 250 ppm/K ient
≤ 45 ms se time
10 Hz f frequency (-3dB)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (horiz. mounting)
-20 °C…+85 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
15 V voltage
max. current
Output
/4…20 mA age/Output current
/≤ 600 Ω voltage/Current
0.2 % cy
± 250 ppm/K ient
≤ 45 ms se time
10 Hz f frequency (-3dB)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (horiz. mounting)
-20 °C…+85 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
15 V voltage
max. current
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
0.2 % cy
± 250 ppm/K ient
≤ 45 ms se time
10 Hz f frequency (-3dB)
General data
24 V DC ± 25 %
< 1.3 W at IOUT = 5 mA
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (horiz. mounting)
-20 °C…+85 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Note
Tu=23°C, single module
• Signal conversion
• Electrical isolation between
input/output signal / power supply
• Power supply can be crossconnected via plug-in bridges
D
Technical data
Input
Input voltage/Input current
max. voltage
max. current
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
(Qty.=1)
WAS5 VCC 0-10V/0-20MA
WAZ5 VCC 0-10V/0-20MA
Order No.
8540310000
8540320000
Type
(Qty.=1)
WAS5 VCC 0-10V/4-20MA
WAZ5 VCC 0-10V/4-20MA
Order No.
8540290000
8540300000
Type
(Qty.=1)
WAS5 VVC 0-10V/0-10V
WAZ5 VVC 0-10V/0-10V
Order No.
8540330000
8540340000
Note
Accessories
Note
D.22
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
20 kHz limiting frequency
0(4)…20 mA/0(4)…20 mA
0…20 mA/0…10 V
• Signal conversion
• Electrical isolation between
input/output signal / power supply
• Power supply can be crossconnected via plug-in bridges
Analogue signal conditioning
WAVESERIES - DC/DC 3-way isolator
D
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Input
/0(4)…20 mA Input current
Input
/0…20 mA ge/Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy f final value
Temperature coefficient value
Step response time lly 30 μs)
Cut-off frequency (-3dB) )
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals us / CE
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Coupling capacitance, I/O, power supply
Surge category
Pollution severity
Clearance & creepage distance
/50 mA ltage/max. current
/50 Ω ance, voltage/Current
Output
/0(4)…20 mA /Output current
/≤ 500 Ω voltage/Current
< 0.2% of final value
≤ 250 ppm/K of final value
≤ 40 μs (typically 30 μs)
≥ 15 kHz (typ. 20 kHz)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
1 nF ing capacitance, I/O, power supply
III e category
2 llution severity
≥ 3 mm ce & creepage distance
/50 mA ltage/max. current
/50 Ω ance, voltage/Current
Output
0…10 V / tage/Output current
≥ 2 kΩ / , voltage/Current
< 0.2% of final value
≤ 250 ppm/K of final value
≤ 40 μs (typically 30 μs)
≥ 15 kHz (typ. 20 kHz)
General data
24 V DC ± 25 %
< 1.3 W at IOUT = 5 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
1 nF ing capacitance, I/O, power supply
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Note
Tu=23°C, single module
Tu=23°C, single module
Type
(Qty.=1) Order No.
WAS5 CCC HF 0-20/0-20MA 8447160000
WAZ5 CCC HF 0-20/0-20MA 8447170000
Type
(Qty.=1)
WAS5 CVC HF 0-20/0-10V
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Ordering data
Type of connection
Screw connection
Tension clamp connection
Order No.
8447220000
Note
Accessories
Note
D.23
Analogue signal conditioning
WAVESERIES - DC/DC 3-way isolator
20 kHz limiting frequency
4…20 mA/0…20 mA
4…20mA/0…10V
Input
/4…20 mA ge/Input current
Input
/4…20 mA ge/Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy 0.2% of final value
Temperature coefficient value
Step response time lly 30 μs)
Cut-off frequency (-3dB) )
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals us / CE
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Coupling capacitance, I/O, power supply
Surge category
Pollution severity
Clearance & creepage distance
/50 mA ltage/max. current
/50 Ω ance, voltage/Current
Output
/0…20 mA age/Output current
/≤ 500 Ω voltage/Current
< 0.2% of final value value
≤ 250 ppm/K of final value
≤ 40 μs (typically 30 μs)
≥ 15 kHz (typ. 20 kHz)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
1 nF ing capacitance, I/O, power supply
III e category
2 llution severity
≥ 3 mm ce & creepage distance
/50 mA ltage/max. current
/50 Ω ance, voltage/Current
Output
0…10 V / tage/Output current
≥ 2 kΩ /≤ 600 Ω ent
< 0.2% of final value value
≤ 250 ppm/K of final value
≤ 40 μs (typically 30 μs)
≥ 15 kHz (typ. 20 kHz)
General data
24 V DC ± 25 %
< 1.3 W at IOUT = 5 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
1 nF ing capacitance, I/O, power supply
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Note
Tu=23°C, single module
Tu=23°C, single module
Type
(Qty.=1) Order No.
WAS5 CCC HF 4-20/0-20MA 8447250000
Type
(Qty.=1)
WAS5 CVC HF 4-20/0-10V
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
• Signal conversion
• Electrical isolation between
input/output signal / power supply
• Power supply can be crossconnected via plug-in bridges
D
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Ordering data
Type of connection
Screw connection
Order No.
8447280000
Note
Accessories
Note
D.24
20 kHz limiting frequency
0…10 V/0…20 mA
0…10 V/4…20 mA
• Signal conversion
• Electrical isolation between
input/output signal / power supply
• Power supply can be crossconnected via plug-in bridges
Analogue signal conditioning
WAVESERIES - DC/DC 3-way isolator
D
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Input
0…10 V / age/Input current
Input
0…10 V / age/Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy 0.2% of final value
Temperature coefficient value
Step response time lly 30 μs)
Cut-off frequency (-3dB) )
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals us / CE
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Coupling capacitance, I/O, power supply
Surge category
Pollution severity
Clearance & creepage distance
15 V / oltage/max. current
500 kΩ / ce, voltage/Current
Output
/0…20 mA age/Output current
/≤ 500 Ω voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 40 μs (typically 30 μs)
≥ 15 kHz (typ. 20 kHz)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
1 nF ing capacitance, I/O, power supply
III e category
2 llution severity
≥ 3 mm ce & creepage distance
15 V / oltage/max. current
500 kΩ / ce, voltage/Current
Output
/4…20 mA age/Output current
/≤ 500 Ω voltage/Current
± 0.2% of final value
≤ 250 ppm/K of final value
≤ 40 μs (typically 30 μs)
≥ 15 kHz (typ. 20 kHz)
General data
24 V DC ± 25 %
< 1.5 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
1 nF ing capacitance, I/O, power supply
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Note
Tu=23°C, single module
Tu=23°C, single module
Type
(Qty.=1) Order No.
WAS5 VCC HF 0-10/0-20MA 8447310000
Type
(Qty.=1) Order No.
WAS5 VCC HF 0-10/4-20MA 8447340000
WAZ5 VCC HF 0-10/4-20MA 8447350000
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Ordering data
Type of connection
Screw connection
Note
Accessories
Note
D.25
Analogue signal conditioning
WAVESERIES - DC/DC 3-way isolator
20 kHz limiting frequency
0…10 V/0…10 V
-10…+10 V/-10…+10 V
Input
0…10 V / age/Input current
Input
-10…+10 V / /Input current
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy 0.2% of measuring range
Temperature coefficient ring range
Step response time lly 30 μs)
Cut-off frequency (-3dB) )
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 5 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals us / CE
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Coupling capacitance, I/O, power supply
Surge category
Pollution severity
Clearance & creepage distance
15 V / oltage/max. current
500 kΩ / ce, voltage/Current
Output
0…10 V / tage/Output current
≥ 2 kΩ / , voltage/Current
± 0.2% of final value nge
≤ 250 ppm/K of final value nge
≤ 40 μs (typically 30 μs)
≥ 15 kHz (typ. 20 kHz)
General data
24 V DC ± 25 %
< 1.3 W at IOUT = 5 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
1 nF ing capacitance, I/O, power supply
III e category
2 llution severity
≥ 3 mm ce & creepage distance
± 15 V / x. current
500 kΩ / ce, voltage/Current
Output
-10…+10 V / e/Output current
≥ 2 kΩ / , voltage/Current
± 0.2% of measuring range
≤ 250 ppm/K of measuring range
≤ 40 μs (typically 30 μs)
≥ 15 kHz (typ. 20 kHz)
General data
24 V DC ± 25 %
< 1.3 W at IOUT = 5 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CE / cULus / CE
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
1.2 kVeff / 5 s tput
1 nF ing capacitance, I/O, power supply
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Note
Tu=23°C, single module
• Signal conversion
• Electrical isolation between
input/output signal / power supply
• Power supply can be crossconnected via plug-in bridges
D
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Tension clamp c.
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
(Qty.=1)
WAS5 VVC HF 0-10/0-10V
WAZ5 VVC HF 0-10/0-10V
Order No.
8447370000
8447380000
Type
(Qty.=1) Order No.
WAS5 VVC HF +-10V/+-10V 8561610000
Note
Accessories
Note
D.26
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
configurable
PRO DC/DC
• Universal adjustable via DIP switch
• Service tool WAVETOOL via Internet
• Voltage supply 20…230 V AC/DC
• Low power loss
• Adjustable transmission frequency
Analogue signal conditioning
WAVESERIES - DC/DC 3-way isolator
Switch position/setting options
Switch
Input
Input range
0 … ±60 mV
0 … ±100 mV
0 … ±150 mV
0 … ±300 mV
0 … ±500 mV
0 … ±1 V
0 … ±5 V
0 … ±10 V
0 … ±100 V
Technical data
Input
Input voltage/Input current 00 V /± 0.1mA…± 100 mA
Input resistance, voltage/Current . 100 Ω; >5 mA: approx. 5 Ω
max. current b> < 5 mA: < 100 mA, IIN > 5 mA < 300 mA
Output
Output voltage/Output current ;20 mA
Load impedance, voltage/Current
Accuracy f final value
Temperature coefficient lue
Cut-off frequency (-3dB)
Offset or 10 mV
Adjustment range, zero point nge of chosen output range
Adjustment range, amplification lected output range
Displacement 0%, 50%, 100% of measuring range
General data
Supply voltage DC +10 %/ 48…62 Hz
Power consumption
Operating temperature
Storage temperature
Default setting 0V / 10Hz
Approvals cURus
Insulation coordination
Standards
EMC standards EN 61326/A1, EN 61000-6 /-2
Rated voltage
Impulse withstand voltage 4)
Isolation voltage input, output
Surge category
Pollution severity
Input
± 20 mV…± 200 V /± 0.1mA…± 100 mA
ca. 1 MΩ /< 5 mA: approx. 100 Ω; >5 mA: approx. 5 Ω
IIN < 5 mA: < 100 mA, IIN > 5 mA < 300 mA
Output
0…±10 V /0…±20 mA
≥ 1 kΩ /≤ 600 Ω ent
< 0.1% of final value
≤ 60 ppm/K of end value
> 10 kHz/ < 10 Hz (-3dB)
20 μA or 10 mV
± 25% of measuring range of chosen output range
0.33…3.30 x final value of selected output range
-100%, -50%, 0%, 50%, 100% of measuring range
General data
22…230 V AC/DC +10 %/ 48…62 Hz
approx. 1 W ption
-10 °C…+70 °C ature
-40 °C…+85 °C ure
0…10V / 0…10V / 10Hz
GL / CE / cURus
Insulation coordination
EN 50178
DIN EN 61326. EN 61326/A1, EN 61000-6 /-2
600 V voltage
5 kV, 1.2/50 μs (IEC 255-4)
4 kVeff nput, output
III e category
2 llution severity
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
2
n
n
n
4
1
2
S2
3
4
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
0 … ± ~0.3 mA
n
n
n
0 … ±1 mA
n
0 … ±5 mA
n
n
n
n
0 … ±10 mA
0 … ±20 mA
n
n
n
0 … ±50 mA
n
4 … ±20 mA*
n
n
*Offset conversion not calibrated
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Switch S2
calibratet ranges
Span-pot. activated: input x 0.33 ... x 3.30
4
n
Switch
Output
S1
S3
Output range
0 … ±10 V
5
6
7
1
2
n
n
n
n
n
2 … 10 V
0 … ±5 V
n
n
n
n
n
n
n
n
n
n
1…5V
0 … ±20 mA
n
n
n
n
n
n
n
n
n
n
4 … 20 mA
n
n
n
n
n
8
9
S1
10
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
+100 %
n
Zero pot. activated: additional ±25 %
n
n
n
Offset
(in % of output voltage)
0%
-100 %
-50 %
+50 %
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
1
S1
3
S2
5
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS4 PRO DC/DC
WAZ4 PRO DC/DC
Qty.
1
1
Order No.
8560740000
8560750000
Switch S3
Bandwidth 10 kHz
Bandwidth 10 Hz
Set range can be documented on side of housing.
n
3
n
n
= on
n=
off
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
D.27
D
Analogue signal conditioning
WAVESERIES - PT100/RTD - signal converter
PT100, 2-conductor converter
PT100/2 0(4)…20 mA
PT100/2 0…10 V
Input
Sensor 2-conductor
Supply current
Input
PT100/2-conductor
1.45 mA urrent
Input
PT100/2-conductor
1.45 mA urrent
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy 0.5% of measuring range
General data
Supply voltage/Current consumption IOUT = 20 mA
Operating temperature/Storage temperature
Approvals us / CE
Standards EN 60751, IEC751
EMC standards 61000-6
Output
/0(4)…20 mA /Output current
/≤ 500 Ω voltage/Current
± 0.5% of measuring range
General data
24 V DC ± 20 % /< 48 mA at IOUT = 20 mA
0 °C…+55 °C /-20 °C…+85 °C emperature
CSA / cULus / CE
EN 50178, EN 60751, IEC751
EN 55011, EN 61000-6
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
± 0.5% of measuring range
General data
24 V DC ± 20 % /< 38 mA at IOUT = 20 mA
0 °C…+55 °C /-20 °C…+85 °C emperature
CSA / cULus / CE
EN 50178, EN 60751, IEC751
EN 55011, EN 61000-6
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
• 2-conductor system
• Temperature range adjustable from 200°C…+800°C
• Power supply can be cross-connected with
plug-in bridges
• No electrical isolation between input and output
circuit
D
Technical data
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tu=23°C, single module
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tu=23°C, single module
Ordering data
Temperature input range
adjustable -200…+800°C
adjustable -200…+800°C
Special adjustment
Special adjustment
0…100 °C
0…100 °C
Note
Application
D.28
Type of connection
Screw connection
Tension clamp connection
Screw connection
Tension clamp connection
Tension clamp connection
Screw connection
Type
Qty.
WTS4 PT100/2 C 0/4-20mA
1
WTZ4 PT100/2 C 0/4-20mA
1
WTS4 PT100/2 C 0/4-20mA variable
1
WTZ4 PT100/2 C 0/4-20mA variable
1
WTZ4 PT100/2 C 0-20mA 0…100C
1
WTS4 PT100/2 C 4-20mA 0…100C
1
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Order No.
8432210000
8432220000
8432219999
8432229999
8432220001
8432210011
Type
WTS4 PT100/2 V 0-10V
WTZ4 PT100/2 V 0-10V
WTS4 PT100/2 V 0-10V variable
WTZ4 PT100/2 Vn 0-10V variable
WTS4 PT100/2 V 0-10V 0…100C
Qty.
1
1
1
1
1
Specify temperature range for special calibrations.
Order No.
8432180000
8432190000
8432189999
8432199999
8432180001
PT100, 3-conductor converter
PT100/3 0(4)…20 mA
PT100/3 0…10 V
• 3-conductor system
• Temperature range adjustable from 200°C…+800°C
• Power supply can be cross-connected with
plug-in bridges
• No electrical isolation between input and output
circuit
Analogue signal conditioning
WAVESERIES - PT100/RTD - signal isolator/converter
D
Technical data
Input
Sensor 3-conductor
Supply current
Input
PT100/3-conductor
1.45 mA urrent
Input
PT100/3-conductor
1.45 mA urrent
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy 0.5% of measuring range
General data
Supply voltage/Current consumption IOUT = 20 mA
Operating temperature/Storage temperature
Approvals us / CE
Standards EN 60751, IEC751
EMC standards 61000-6
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
± 0.5% of measuring range
General data
24 V DC ± 20 % /< 38 mA at IOUT = 20 mA
0 °C…+55 °C /-20 °C…+85 °C emperature
CSA / cULus / CE
EN 50178, EN 60751, IEC751
EN 55011, EN 61000-6
Output
/0(4)…20 mA /Output current
/≤ 500 Ω voltage/Current
± 0.5% of measuring range
General data
24 V DC ± 20 % /< 48 mA at IOUT = 20 mA
0 °C…+55 °C /-20 °C…+85 °C emperature
CSA / cULus / CE
EN 50178, EN 60751, IEC751
EN 55011, EN 61000-6
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tu=23°C, single module
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tu=23°C, single module
Ordering data
Temperature input range
adjustable -200…+800°C
adjustable -200…+800°C
Special adjustment
Special adjustment
0…100 °C
Note
Type of connection
Screw connection
Tension clamp connection
Screw connection
Tension clamp connection
Screw connection
Type
WTS4 PT100/3 V 0-10V
WTZ4 PT100/3 V 0-10V
WTS4 PT100/3 V 0-10V variabel
WTZ4 PT100/3 V 0-10V variabel
WTS4 PT100/3 V 0-10V 0…100C
Qty.
1
1
1
1
1
Specify temperature range for special calibrations.
Order No.
8432090000
8432130000
8432099999
8432139999
8432090001
Type
Qty.
WTS4 PT100/3 C 0/4-20mA
1
WTZ4 PT100/3 C 0/4-20mA
1
WTS4 PT100/3 C 0/4-20mA variable
1
WTZ4 PT100/3 C 0/4-20mA variable
1
Order No.
8432150000
8432160000
8432159999
8432169999
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Application
D.29
Analogue signal conditioning
WAVESERIES - PT100/RTD - signal isolator/converter
PT100, 4-conductor converter
PT100/4 0(4)…20 mA
PT100/4 0…10 V
Input
Sensor 4-conductor
Supply current
Input
PT100/4-conductor
1.45 mA urrent
Input
PT100/4-conductor
1.45 mA urrent
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy ; mrange < 600K: 0.1%; measuringasuring range
General data
Supply voltage/Current consumption IOUT = 20 mA
Operating temperature/Storage temperature
Approvals us / CE
Standards EN 60751, IEC751
EMC standards 61000-6
Output
/0(4)…20 mA /Output current
/≤ 500 Ω voltage/Current
100K ≤ mr < 600K: 0.1%; mr ≥ 600K: 0.2%; of measuring range
General data
24 V DC ± 20 % /< 48 mA at IOUT = 20 mA
0 °C…+55 °C /-20 °C…+85 °C emperature
CSA / cULus / CE
EN 50178, EN 60751, IEC751
EN 55011, EN 61000-6
Output
0…10 V / tage/Output current
≥ 1 kΩ / , voltage/Current
100K ≤ mr < 600K: 0.1%; mr ≥ 600K: 0.2%; of measuring range
General data
24 V DC ± 20 % /< 38 mA at IOUT = 20 mA
0 °C…+55 °C /-20 °C…+85 °C emperature
CSA / cULus / CE
EN 50178, EN 60751, IEC751
EN 55011, EN 61000-6
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
• 4-conductor system
• Temperature range adjustable from 200°C…+800°C
• Power supply can be cross-connected with
plug-in jumpers
• No electrical isolation between input and output
circuit
D
Technical data
mm2
mm
Note
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tu=23°C, single module
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tu=23°C, single module
Ordering data
Temperature input range
adjustable -200…+800°C
adjustable -200…+800°C
Special adjustment
Special adjustment
0…100 °C
Note
Application
D.30
Type of connection
Screw connection
Tension clamp connection
Screw connection
Tension clamp connection
Screw connection
Type
Qty.
WTS4 PT100/4 C 0/4-20mA
1
WTZ4 PT100/4 C 0/4-20mA
1
WTS4 PT100/4 C 0/4-20mA variable
1
WTZ4 PT100/4 C 0/4-20mA variable
1
WTS4 PT100/4 C 4-20mA 0…100C
1
Cross-connectors for power supply and
markers - see WAVESERIES accessories
Order No.
8432270000
8432280000
8432279999
8432289999
8432270011
Type
WTS4 PT100/4 V 0-10V
WTZ4 PT100/4 V 0-10V
WTS4 PT100/4 V 0-10V variabel
WTZ4 PT100/4 V 0-10V variabel
WTS4 PT100/4 V 0-10V 0…100C
Qty.
1
1
1
1
1
Specify temperature range for special calibrations.
Order No.
8432240000
8432250000
8432249999
8432259999
8432240001
RTD, signal isolator/converter
PRO RTD 1000
PRO RTD
• Universally adjustable via DIP switch
• 3-way isolation
• Linearisation
• Power supply can be cross-connected using
ZQV cross connection system
Analogue signal conditioning
WAVESERIES - PT100/RTD - signal disconnector/converter, configurable
D
Technical data
Input
Sensor 2-/3-/4-cond., Ni100/2-/3-/4-cond., potentiometer:
min. 0-100 M, max. 0-100 kM, resistor: 0-450 M
Temperature input range
Output
Output current/Output voltage
Offset current/Offset voltage
Load impedance, voltage/Current
Step response time -conductor: 1.2 s/2.2 s; potentiometer:
0.5 s/1.1 s
Line resistance in measuring circuit
Influence of cable resistance onductor resistance
Wire break detection value > 20 mA, >10 V)
Fine adjustment of FSR; Poti: ± 12.5% … ± 25%
Status indicator ond. broken: LED flashing/Error: LED off
General data
Supply voltage n; 25 %
Power consumption at IOUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting 0…100°C / 4…20 mA / man. fine calib.: off /
slow step response
Approvals cULus
Insulation coordination
Standards EN 60751, IEC 751, DIN 43760
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Input
PT100/2-/3-/4-cond., Ni100/2-/3-/4-cond., potentiometer:
Input
PT1000/2-/3-/4-cond.; Ni1000/2-/3-/4-cond.; potentiometer:
min. 0-100 M, max. 0-100 kM, resistor: 0-450 M
configurable nput range
Output
0(4)…20 mA /0…10 V oltage
max. 100 μA /max. 0.05 V tage
≥ 1 kΩ /≤ 600 Ω ent
fast/slow: 2-/3-/4-conductor: 1.2 s/2.2 s; potentiometer: 0.5
s/1.1 s
50 Ω for 3- and 4-conductor it
max. + 0.25°C at 50 Ω conductor resistance
LED flashes (output value > 20 mA, >10 V)
≥ +/- 5%, Version 1:>=12.5% / Poti:12.5%…25% ± 25%
active: LED on/cond. broken: LED flashing/Error: LED off
General data
24 V DC ± 25 %
830…880…980mW at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C perature
-20 °C…+85 °C ure
PT100/3-cond./ 0…100°C / 4…20 mA / man. fine calib.: off /
slow step response
GL / CE / cULus
Insulation coordination
EN 50178, EN 60751, IEC 751, DIN 43760
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
min. 0-1kM, max. 0-100kM; resistor: 0-4.5kM 0-450 M
configurable nput range
Output
0(4)…20 mA /0…10 V oltage
max. 100 μA /max. 0.05 V tage
≥ 1 kΩ /≤ 600 Ω ent
fast/slow:2-/3-/4-cond.: 1.2s/2.3s; potentiometer: 0.5s/1.2s
s/1.1 s
50 Ω for 3- and 4-conductor it
max. + 0.25°C at 50 Ω conductor resistance
LED flashes (output value > 20 mA, >10 V)
± 12.5% of FSR; Poti: ± 12.5% … ± 25%
active: LED on/cond. broken: LED flashing/Error: LED off
General data
24 V DC ± 25 %
830…880…980mW at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C perature
-20 °C…+85 °C ure
PT1000/3-cond./ 0…100°C / 4…20mA / man. adjustment: off
/ slow step response
GL / CE / cULus
Insulation coordination
EN 50178, EN 60751, IEC 751, DIN 43760
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS5 PRO RTD
WAZ5 PRO RTD
Qty.
1
1
Order No.
8560700000
8560710000
Type
WAS5 PRO RTD 1000
Qty.
1
Order No.
8679490000
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
D.31
Analogue signal Conditioning
WAVESERIES – PT100/RTD signal separator/converter, configurable
WAVEANALOG PRO RTD
WAVEANALOG PRO RTD 1000
Switch positions/setting options
Switch positions/setting options
Input
Selection of input
Switch 1
PT100 2-conductor
PT100 3-conductor
PT100 4-conductor
R
2-conductor
NI100 2-conductor
NI100 3-conductor
NI100 4-conductor
Potentiometer
1
2
3
= on
= off
Input
Selection of input
Switch 1
PT10002-conductor
PT10003-conductor
PT10004-conductor
R
2-conductor
NI1000 2-conductor
NI1000 3-conductor
NI1000 4-conductor
Potentiometer
1
2
3
= on
= off
Selection of output
Switch 2
Output
6
7
0...10 V
0...5 V
0...20 mA
4...20 mA
Selection of the
step response
step response
slow
fast
D
␽min
0
–10
–20
–25
–30
–40
–50
–60
–70
–80
–90
–100
–150
–200
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Selection of minimum input size
Switch 1
Rmin
Potimin
4
5
6
0Ω
0%
10 Ω
10 %
20 Ω
20 %
20 Ω
25 %
30 Ω
30 %
40 Ω
40 %
50 Ω
50 %
60 Ω
60 %
70 Ω
70 %
80 Ω
80 %
90 Ω
100 Ω
150 Ω
200 Ω
Special range
␽min
7
Special range
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Choice of measuring range
T
40K
50K
60K
70K
80K
90K
100K
110K
120K
125K
130K
140K
150K
160K
170K
180K
190K
200K
250K
300K
350K
400K
450K
500K
550K
600K
650K
700K
750K
800K
850K
900K
D.32
R
20
25
30
35
40
45
50
55
60
62.5
65
70
75
80
85
90
95
100
125
150
175
200
225
250
275
300
325
350
375
400
425
450
Potentiometer
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
20
25
30
35
40
45
50
55
60
62.5
65
70
75
80
85
90
95
100
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
-----------------------------
Selection of minimum input size
Switch 1
Rmin
Potimin
4
5
6
0Ω
0%
100 Ω
10 %
200 Ω
20 %
200 Ω
25 %
300 Ω
30 %
400 Ω
40 %
500 Ω
50 %
600 Ω
60 %
700 Ω
70 %
800 Ω
80 %
900 Ω
1000 Ω
1500 Ω
2000 Ω
0
–10
–20
–25
–30
–40
–50
–60
–70
–80
–90
–100
–150
–200
1
2
3
4
5
v
T
40K
50K
60K
70K
80K
90K
100K
110K
120K
125K
130K
140K
150K
160K
170K
180K
190K
200K
250K
300K
350K
400K
450K
500K
550K
600K
650K
700K
750K
800K
850K
900K
R
200
250
300
350
400
450
500
550
600
625
650
700
750
800
850
900
950
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
Potentiometer
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
Ω
20
25
30
35
40
45
50
55
60
62.5
65
70
75
80
85
90
95
100
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
-----------------------------
S.2
8
Accuracy, slow/fast step response
7
PT 100, Ni100: 0.3 % of measuring range 0.8 %
Measuring range:
Potentiometer: 0.2 % of final value / 0.3 %
Resistance: 0.2 % of final value / 0.3 %
Temperature coefficient
Measuring range ≥ 200 K
≤ 200 ppm / °C
100 K ≤ Measuring range < 200 K ≤ 250 ppm / °C
40 K ≤ Measuring range < 100 K ≤ 400 ppm / °C
Examples for setting zero and range
Choice of measuring range
Switch 2
Switching on the
manual adjustment
manual
S.1
adjustment
8
off
on
Switch 2
1
2
3
4
5
v
Temperature setting:
Output
DIP switch
Range
4 … 20 mA
–10 °C … +110 °C
75 … 110°C
Range
Range adjustment
120 °C
± 12.5 %
Zero
–25 °C
–10 °C
5 °C
95 °C
110 °C
125 °C
Span
5 °C
110 °C
125 °C
140 °C
WAVETOOL Setting aid
The service tool is used for fast, uncomplicated configuration of WAVEANALOGUE PRO.
Download from the internet:
http://www.weidmueller.com
RTD, signal isolator/converter
PRO RTD Cu
• Universally adjustable via DIP switch
Selection of connection
Switch 1
Connection
1
3-wire
n
4-wire
n
• 3-way isolation
• Linearisation
• Power supply can be cross-connected using
ZQV cross connection system
Selection of senor
Switch 1
Type
2
3
Cu 10
n
n
Cu 25
n
n
n
Cu 50
n
Cu 100
n
n
Selection of minimum input values
Switch 1
␽min
4
5
6
- 0 °C
n
n
n
Technical data
Input
Sensor Cu 25, Cu 50, Cu 100; 3-/4-conductor
Temperature input range C
Input
Cu 10, Cu 25, Cu 50, Cu 100; 3-/4-conductor
adjustable -200…+260°C
Output
Output current/Output voltage
Offset current/Offset voltage
Load impedance, voltage/Current
Step response time 2.2 s
Line resistance in measuring circuit 5 Ω Cu 50; 50 Ω Cu 100
Influence of cable resistance or resistance
Wire break detection value > 20 mA, >10 V)
Fine adjustment of FSR
Status indicator ond. broken: LED flashing/Error: LED off
General data
Supply voltage n; 25 %
Power consumption W at IOUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting 0…100°C; 4…20 mA; no filter,
no manual fine calib.; slow step response
Approvals cULus
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Output
0(4)…20 mA /0…10 V oltage
max. 100 μA /max. 0.05 V tage
≥ 1 kΩ /≤ 600 Ω ent
fast: 1.2 s/ slow: 2.2 s
5 Ω Cu 10; 15 Ω Cu 25; 25 Ω Cu 50; 50 Ω Cu 100
max. + 0.25°C at max. conductor resistance
LED flashes (output value > 20 mA, >10 V)
± 12.5% of FSR
active: LED on/cond. broken: LED flashing/Error: LED off
General data
24 V DC ± 25 %
880…980…1030mW at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C perature
-20 °C…+85 °C ure
CU 10/3-cond.; 0…100°C; 4…20 mA; no filter,
no manual fine calib.; slow step response
GL / CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
≥ 3 mm ce & creepage distance
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Type
WAS5 PRO RTD Cu
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Qty.
1
Order No.
8638950000
7
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
-150 °C
-200 °C
n
n
n
n
n
n
n
n
special range
n
n
n
n
-10 °C
-20 °C
-25 °C
-30 °C
-40 °C
-50 °C
-60 °C
-70 °C
-80 °C
-90 °C
-100 °C
Selection of the measurement range
Switch 2
Span
1
2
3
4
40 K
n
n
n
n
50 K
n
n
n
n
60 K
n
n
n
n
70 K
n
n
n
n
80 K
n
n
n
n
n
90 K
n
n
n
100 K
n
n
n
n
n
110 K
n
n
n
120 K
n
n
n
n
125 K
n
n
n
n
130 K
n
n
n
n
140 K
n
n
n
n
150 K
n
n
n
n
n
160 K
n
n
n
170 K
n
n
n
n
n
180 K
n
n
n
190 K
n
n
n
n
n
200 K
n
n
n
210 K
n
n
n
n
n
220 K
n
n
n
230 K
n
n
n
n
n
n
240 K
n
n
250 K
n
n
n
n
n
n
260 K
n
n
270 K
n
n
n
n
n
280 K
n
n
n
290 K
n
n
n
n
n
300 K
n
n
n
350 K
n
n
n
n
n
n
400 K
n
n
450 K
n
n
n
n
n
n
460 K
n
n
Selection of Output
Switch 2
Output
6
7
0...10 V
n
n
n
0...20 mA
n
4...20 mA
n
n
Selection of
step set time
Time of
Switch 2
step response
8
slow
n
fast
n
n
D
5
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Switching on the
manual fine adjustment
Switch 1
man. adj.
8
n
off
on
n
n
n
Analogue signal conditioning
WAVESERIES - PT100/RTD - signal disconnector/converter, configurable
= on
= off
D.33
Analogue signal conditioning
WAVESERIES - Thermocouple signal converter, configurable
Thermal converter type
K, J, T, E, N, R, S, B
Thermo Select
• No calibration necessary
• Cold-junction compensation
• Output signal selectable
• Power supply can be cross-connected with
plug-in bridges
• Suitable for insulated thermoelements
• No electrical isolation between input and output
circuit
Switch position/setting options
SW 1
D
Technical data
Input
Sensor element (IEC 584) type: K,J,T,E,N,R,S,B
Temperature input range
Input
Thermocouple (IEC 584) type: K,J,T,E,N,R,S,B
-200…+1820 °C t range
Output
Output voltage/Output current
Load impedance, voltage/Current
Temperature coefficient range + 0.075 K)/K
Step response time ; without filter: 6 s
Wire break detection value > 20 mA, >10 V)
General data
Supply voltage n; 20 %
Current consumption T = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals us / CE
Insulation coordination
Standards EN 60584, IEC 584
EMC standards 61000-6
Output
0…10 V /0(4)…20 mA urrent
≥ 1 kΩ /≤ 500 Ω ent
± (200 ppm from range + 0.075 K)/K
with filter: 1.1 s; without filter: 6 s
LED flashes (output value > 20 mA, >10 V)
General data
24 V DC ± 20 %
< 38 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
CSA / cULus / CE
Insulation coordination
EN 50178, EN 60584, IEC 584
EN 55011, EN 61000-6
Type
K
J
T
E
1
n
n
n
n
N
R
S
B
n
n
n
n
2
n
n
n
n
n
n
n
n
SW 2
3
n
n
n
n
n
n
n
n
SW 1
Tmin
0 C°
-10 C°
-20 C°
-30 C°
-40 C°
-50 C°
-100 C°
-150 C°
-200 C°
+50 C°
+100 C°
+150 C°
+200 C°
+250 C°
+500 C°
4
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
5
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
6
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
SW 2
Output 6
0 - 10 V n
0 - 20 mA n
4 - 20 mA n
7
n
n
n
7
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Span
100 C°
150 C°
200 C°
250 C°
1
n
n
n
n
2
n
n
n
n
300
350
400
450
500
550
600
C°
C°
C°
C°
C°
C°
C°
n
n
n
n
n
n
n
n
n
n
n
n
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1600
1700
1800
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
C°
n
n
n
n
n
n
n
n
n
n
= on
= off
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
3
n
n
n
n
n
4
n
n
n
n
5
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Filter 8
off n
on n
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Tu=23°C, single module
Ordering data
Temperature coefficient
K -200°C ...-150°C
± (5K + 0.1% of set range)
-150°C ...1200°C ± (3K + 0.1% of set range)
1200°C ...1372°C
± (4K + 0.1% of set range)
J -200°C ...-150°C
± (4K + 0.1% of set range)
-150°C ...1200°C ± (3K + 0.1% of set range)
T -200°C ...-150°C
± (5K + 0.1% of set range)
-150°C ...400°C
± (3K + 0.1% of set range)
E -200°C ...-150°C
± (4K + 0.1% of set range)
-150°C ...1000°C ± (3K + 0.1% of set range)
N
Type of connection
Screw connection
Tension clamp connection
Type
WTS4 THERMO
WTZ4 THERMO
Qty.
1
1
Order No.
8432300000
8432310000
R
S
Note
B
Accessories
Note
D.34
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
-200°C
-150°C
-50°C
200°C
-50°C
200°C
50°C
250°C
500°C
...-150°C
...1300°C
...200°C
...1760°C
...200°C
...1760°C
...250°C
...500°C
...1820°C
± (6K + 0.1% of set range)
± (3K + 0.1% of set range)
± (10K + 0.1% of set range)
± (6K + 0.1% of set range)
± (10K + 0.1% of set range)
± (6K + 0.1% of set range)
± (25K + 0.1% of set rangeh)
± (10K + 0.1% of set range)
± (6K + 0.1% of set range)
Thermal converter type
K, J, T, E, N, R, S, B
PRO Thermo
Select of
thermocoupler
SW1
Typ
1
2
K
n
n
J
n
n
n
T
n
E
n
n
N
n
n
R
n
n
n
S
n
B
n
n
• 3-way isolation
• No calibration necessary
• Cold-junction compensation
• Output signal selectable
• Power supply can be cross-connected using
ZQV cross connection system
Selection of
temperature span
SW2
Span
1 2 3 4 5
100°C
n n n n n
Technical data
Input
Sensor element (IEC 584) type: K,J,T,E,N,R,S,B
Temperature input range
Input
Thermocouple (IEC 584) type: K,J,T,E,N,R,S,B
-200…+1820 °C t range
Output
Output voltage/Output current
Load impedance, voltage/Current
Offset current/Offset voltage
Step response time ilter: max. 7.5 ms
Line resistance in measuring circuit
Wire break detection value > 20 mA, >10 V)
Fine adjustment itchable)
Status indicator ond. broken: LED flashing/Error: LED off
General data
Supply voltage n; 25 %
Power consumption W at IOUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting 0°C; 4…20mA; filter: off; man. calib.: off
Approvals cULus
Insulation coordination
Standards EN 60584, IEC 584
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Output
0…10 V /0(4)…20 mA urrent
≥ 1 kΩ /≤ 600 Ω ent
max. 100 μA /max. 0.05 V tage
max. 1.4 s; with filter: max. 7.5 ms
50 Ω ance in measuring circuit
LED flashes (output value > 20 mA, >10 V)
± 5% (switchable)
active: LED on/cond. broken: LED flashing/Error: LED off
General data
24 V DC ± 25 %
800…850…950 mW at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
type K; 0…1000°C; 4…20mA; filter: off; man. calib.: off
GL / CE / cULus
Insulation coordination
EN 50178, EN 60584, IEC 584
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s output
III e category
2 llution severity
≥ 3 mm ce & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS5 PRO Thermo
WAZ5 PRO Thermo
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
Qty.
1
1
3
n
n
n
n
n
n
n
n
Selection of minimum
temperature
SW1
␽min
4 5 6
0°C
n n n
-10°C
n n n
-20°C
n n n
-30°C
n n n
-40°C
n n n
-50°C
n n n
-100°C
n n n
-150°C
n n n
-200°C
n n n
+50°C
n n n
+100°C
n n n
+150°C
n n n
+200°C
n n n
+250°C
n n n
500°C
n n n
Special range n n n
Order No.
8560720000
8560730000
150°C
200°C
250°C
300°C
350°C
400°C
450°C
500°C
550°C
600°C
650°C
700°C
750°C
800°C
850°C
900°C
950°C
1000°C
1050°C
1100°C
1150°C
1200°C
1250°C
1300°C
1350°C
1400°C
1450°C
1500°C
1600°C
1700°C
1800°C
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
7
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Selection of
output
SW2
Output
6
7
n
0...10V
n
0...20mA
4...20mA
n
n
n
n
Switching on the
manual fine adjustment
SW1
man. adjust.
8
off
n
on
n
Switching on the
filter function
SW2
Filter
8
off
n
on
n
n
n
= on
= off
Temperature coefficient
K -200°C ...-150°C ± (5K + 0,1% of set range)
-150°C...1200°C ± (3K + 0,1% of set range)
1200°C...1372°C ± (4K + 0,1% of set range)
J -200°C ...-150°C ± (4K + 0,1% of set range)
-150°C...1200°C ± (3K + 0,1% of set range)
T -200°C ...-150°C ± (5K + 0,1% of set range)
-150°C ...400°C ± (3K + 0,1% of set range)
E -200°C ...-150°C ± (4K + 0,1% of set range)
-150°C...1000°C ± (3K + 0,1% of set range)
N -200°C ...-150°C ± (6K + 0,1% of set range)
-150°C...1300°C ± (3K + 0,1% of set range)
R -50°C ...200°C ± (10K + 0,1% of set range)
200°C...1760°C ± (6K + 0,1% of set range)
S -50°C ...200°C ± (10K + 0,1% of set range)
200°C...1760°C ± (6K + 0,1% of set range)
B 50°C ...250°C ± (25K + 0,1% of set range)
250°C ...500°C ± (10K + 0,1% of set range)
500°C...1820°C ± (6K + 0,1% of set range)
D.35
Analogue signal conditioning
WAVESERIES - Thermocouple signal isolator/converter
D
Analogue signal conditioning
WAVESERIES - Frequency signal isolator/converter, configurable
f/DC isolator/converter
PRO Frequency
• 3-way isolation
• Max. input frequency 100 kHz
• Input and output ranges adjustable via DIP
switch
• No calibration necessary
• Adjustable for special range
Selecting the
operating mode
Switch 2
Operating mode 3
4
0…fmax
fmin…fmax
n
n
n
n
saving
fmin
n
n
D
f= (A+B) x C
Technical data
Selecting
Input
Sensor/ ire PNP/NPN, namur initiator, push-pull step /
Rated input level resis: Namur: approx. 1.7 mA/approx. 0.2
mA;
NPN: approx. 6.5 V/approx. 0.2V; PNP: approx. 6.7V/approx.
0.5V
Resolution sp. 5 ppm of measurement value
Output
Output voltage/Output current
Load impedance, voltage/Current
Offset current/Offset voltage
Accuracy output range
Temperature coefficient t range
Step response time riod time of input frequency
Status indicator
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting .20mA
Approvals s
Insulation coordination
Standards (protective separation)
EMC standards 61000-6 /-2, EN 61326
Rated voltage
Impulse withstand voltage
Isolation voltage input, output/
Surge category
Pollution severity
Clearance & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Input
2-, 3-wire PNP/NPN, namur initiator, push-pull step /
Threshold / Hysteresis: Namur: approx. 1.7 mA/approx. 0.2
mA;
NPN: approx. 6.5 V/approx. 0.2V; PNP: approx. 6.7V/approx.
0.5V
0.1 mHz resp. 5 ppm of measurement value
Output
0…10 V /0(4)…20 mA urrent
≥ 1 kΩ /≤ 600 Ω ent
max. 100 μA /max. 0.05 V tage
0.2% of output range
max. 200 ppm/K of output range
360 ms + 2-fold period time of input frequency
green LED icator
General data
24 V DC ± 25 %
max. 1.6 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
0…10kHz / 4…20mA
CE / cULus
Insulation coordination
EN 50178 (protective separation)
EN 55011, EN 61000-6 /-2, EN 61326
300 V voltage
6 kV se withstand voltage
4 kVeff / 5 s / utput/
III e category
2 llution severity
≥ 5,5 mm & creepage distance
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
Selecting
the frequency
Switch 1
2
3
4
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
A
0
1
2
1
n
n
n
3
4
5
6
n
n
n
n
7
8
n
n
9
10
11
12
n
n
n
n
13
14
n
n
n
n
15
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
0.2
0.3
0.4
0.5
0.6
0.7
n
n
n
n
n
n
n
n
n
0.8
n
0.9
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
Selecting
the frequency
n
n
n
Switch 2
1
2
C
x1
x10
n
n
x100
x1000
n
n
n
n
n
n
Selecting the output
Switch 2
Output
0...10 V
5
n
0...20 mA
4...20 mA
7
n
8
n
n
n
6
n
n
n
n
n
n
n
0…5 V
n
n
n
n
Special range (frequency generator is required)
Switch 2
Function
save min. frequency
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 12.5 x 112.4
B
0
0.1
the frequency
Switch 1
5
6
7
8
n
n
n
n
n
n
n
n
save max. frequency
select special range
1
n
n
n
2
n
3
n
4
n
n
n
n
n
n
n
n = on
n = off
Tu=23°C, single module
Application
Registering motor
revolutions using Namur
sensor
~
24 V DC
Type
WAS4 PRO Freq
WAZ4 PRO Freq
Qty.
1
1
Order No.
8581180000
8581190000
Note
N-
Accessories
Note
D.36
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
7
8
5
6
PRO FREQUENCY
8581180000/8581190000
Screw connection
Tension clamp connection
WAVEANALOG
Type of connection
N+
Namur
<= 1,2mA
activated:
not activated: >= 2,1mA
1
2
3
4
SPS
0…20 mA
230 V AC
Ordering data
WAVEANALOG PRO Frequency
Analogue signal conditioning
WAVESERIES – Frequency signal separator/converter, configurable
Settings help, for any input and
output values
Setting the input range using the DIP
switches (doesn’t require a frequency
generator):
There are 2 different methods:
1. Lower measuring frequency = 0 Hz
• Choose operating mode “= … fmax”
S2.3 = 0 and S2.4 = 0
• Set the upper measuring frequency
using DIP switches S1 and S2.1, S2.2
(see table)
• That’s all!
2. Lower measuring frequency ≠ 0 Hz
• First the lower measuring frequency
must be saved.
Select mode “save fmin”.
S2.3 = 1 and S2.4 = 0.
Set the frequency using DIP switches
S1 and S2.1, S2.2 (see table)
To save the frequency, briefly connect
the module to the power supply.
• Select mode “fmin … fmax”
S2.3 = 0 and S2.4 = 1
• Set the upper measuring frequency
using DIP switches S1 and S2.1, S2.2
(see table).
• That’s all!
Adjusting the input range using
a frequency generator:
Connection configuration
for the sensors
3-wire initiator with PNP output
• Select the switch setting for saving the
frequency: S2.1 = 0, S2.2 = 1, S2.3 = 1
and S2.4 = 1
• Apply min. frequency to the module
• Connect the module to the power
supply
• The LED lights up when the input frequency is being measured. If the LED
goes off, the frequency has been saved
and the module can be disconnected
from the power supply again.
• Repeat with max. frequency:
S2.1 = 1, S2.2 = 0, S2.3 = 1
and S2.4 = 1
• Select special range:
S2.1 = 1, S2.2 = 1, S2.3 = 1
and S2.4 = 1
(1)
(2)
(3)
(4)
3-wire initiator with NPN output
(1)
(2)
(3)
(4)
3-w
+15V
PNP
NPN / Namur
GND
D
3-w
+15V
PNP
NPN / Namur
GND
2-wire initiator
Nam
(1)
(2)
(3)
(4)
+15V
PNP
NPN / Namur
GND
(residual current < 1 mA)
Push pull output cascade
U=24V
(1)
(2)
(3)
(4)
+15V
PNP
NPN / Namur
GND
3-wire initiator with PNP output and external supply
(1)
(2)
(3)
(4)
+15V
PNP
NPN / Namur
GND
U=24V
3-wire initiator with NPN output and external supply
(1)
(2)
(3)
(4)
+15V
PNP
NPN / Namur
GND
(1)
(2)
(3)
(4)
+15V
PNP
NPN / Namur
GND
U=24V
Namur initiator
Namur initiator
N+
N-
D.37
Analogue signal conditioning
WAVESERIES - Bridge-type measuring isolating transformer
configurable
PRO BRIDGE
• 3-way isolation
Switch position/setting options
• Input and output ranges adjustable via DIP
switch
SW 1
Input voltage
0…10 mV
• No calibration necessar
• Inverse output signals possible
1 2 3 4 5 6 7 8 9 10
n n n n
n n n n
n n n n
n n n n
0…20 mV
0...50 mV
0...100 mV
n n n n
n n n n
n n n n
n n n n
0...200 mV
0...500 mV
-10 mV...10 mV
- 20 mV...20 mV
- 50 mV...50 mV
n n n n
n n n n
n n n n
n n n n
- 100 mV...100 mV
- 200 mV...200 mV
- 500 mV...500 mV
Output
n n
0...+5 V
0...20 mA
n n
n n
4...20 mA
n n
Bridge supply voltage
+10V
n n n
n n n
+5V
Input
-500 mV…+500 mV /
> 1 MΩ , voltage
Output
Output voltage/Output current …10 V /0…20 mA, 20…0 mA,
4…20 mA, 20…4 mA
Load impedance, voltage/Current
Offset current/Offset voltage
Accuracy output range
Temperature coefficient utput range
Step response time ms
Status indicator
Wire break detection 4 mA
Bridge supply voltage .2 V; offset adjustable; max. 40mA
General data
Supply voltage n; 25 %
Power consumption ub>OUT = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting mV / 0…10 V / + 10 V / standard
Approvals s
Insulation coordination
Standards
EMC standards 2
Rated voltage
Impulse withstand voltage
Isolation voltage input, output/
Surge category
Pollution severity
Clearance & creepage distance
Output
0…5 V, 5…0 V, 10…0 V, 0…10 V /0…20 mA, 20…0 mA,
4…20 mA, 20…4 mA
≥ 1 kΩ /≤ 600 Ω ent
max. 100 μA /max. 0.05 V tage
0.3% of output range
± 250 ppm/K of output range
typically < 200 ms
green LED icator
output: 0 V resp. 0/4 mA
+10 V, +5 V, 4.8…10.2 V; offset adjustable; max. 40mA
General data
24 V DC ± 25 %
max. 1.9 W at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
-500 mV…+500 mV / 0…10 V / + 10 V / standard
CE / cULus
Insulation coordination
EN 50178
EN 61000-6 /-2
300 V voltage
4 kV se withstand voltage
2 kVeff / 5 s / utput/
III e category
2 llution severity
+4.8...+10.2V adjustable
+4.8...+10.2V adjustable
man. adjustment and
offset possible
n n n
n n n
Transmission method
n
n
standard output signal
inverse output signal
n
n
= on
= off
Status LED
LED on
LED off
LED blinks slow
normal operating
Error
measurement range undershoot
Uin < Umax – 10 %
LED blinks fast
measurement range overshoot
Uin < Umax + 10 %
Application
230 Vac
~
24 Vdc
Power supply +
F
10 11 12
7
8
R3
R1
(DMS)
Bridge
U
R2
Bridge
R4
-
PLC
9
0...5V
Input
Input voltage/ mV /
Input resistance, voltage
WAVEANALOG
PRO Bridge
Technical data
8581200000/8581210000
D
0...+10 V
1
2
3
4
5
6
Power supply -
Measuring bridge
Example for bridge supply voltage
≥ 3 mm ce & creepage distance
Temperature adjustment:
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Input voltage
0…10 mA
Output
Bridge supply voltage
0…10 V
+4.8…10.2 V
Bridge excitation
1 mV/V
(Declaration from manufacturer)
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS5 PRO Bridge
WAZ5 PRO Bridge
Qty.
1
1
Order No.
8581200000
8581210000
Exitation voltage
+4.8V
10.2V
10V
Offset range 10%
Note
Offset (Output)
Accessories
Note
D.38
Cross-connectors for power supplies and
markers - refer to WAVESERIES accessories
0V
0V
1V
9V
10V 11V
Relay output
DC/Alarm
• 3-way isolation
• Low trip / High trip
• FAILSAFE / NON-FAILSAFE
• 2 Relay outputs
Analogue signal conditioning
WAVESERIES - Limit value monitoring
Switch position/setting options
SW 1
function
Channel A High Trip
Channel A Low Trip
Channel B High Trip
Channel B Low Trip
FAILSAFE, Channel 1 & 2
NON FAILSAFE, Chan. 1 & 2
n
n
Input
Input voltage
Input current
Input resistance, voltage/Current
Input
0…10 V tage
0(4)…20 mA
≥ 100 kΩ /≤ 110 Ω ent
Output
2 change-over contacts
AgNi 90/10 erial
1…90% (independently for channel 1 and channel 2)
1…90% (independently for channel 1 and channel 2)
/253 V AC voltage, min./max.
3 A inuous current
Open-circuit/closed-circuit principle
≤ 500 ppm/K fficient
LED green ON: OK, LED red ON: alarm (per channel)
General data
24 V DC ± 25 %
typically 1 W both relays picked up
≤ 2 A arrying capacity of cross-connect.
0°C…+55°C (fitted)
-20 °C…+85 °C ure
channel A/B: low trip and FAILSAFE
CE / cULus
Insulation coordination
EN 50178
EN 61000-4-2, -3, -4, -5, -6
300 V voltage
4 kV se withstand voltage
2 llution severity
III e category
≥ 3 mm ce & creepage distance
Output
Contact complement acts
Contact material
Switching thresholds ly for channel 1 and channel 2)
Hysteresis ndependently for channel 1 and channel 2)
Switching voltage, min./max.
Continuous current
Function cuit/closed-circuit principle
Temperature coefficient
Status indicator , LED red ON: alarm (per channel)
General data
Supply voltage n; 25 %
Power consumption h relays picked up
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting w trip and FAILSAFE
Approvals s
Insulation coordination
Standards
EMC standards -3, -4, -5, -6
Rated voltage
Impulse withstand voltage
Pollution severity
Surge category
Clearance & creepage distance
Isolation voltage input, output
2
3
4
n
n
n
n
n
n
= on
= off
NON FAILSAFE:The relay picks up when the alarm is trigered
FAILSAFE:
The relay drops out when the arlarm is triggered. An alarm is also triggered in the
FAILSAFE mode, if for example, the operating voltage to the moduls fail
Low Trip:
Alarm is triggered if the signal is undershoot
the threshold.
High Trip:
Alarm is triggered if the signal is overshoot
the threshold.
Signal threshold:Adjustments of the signal threshold
(1...90)% are made for channel 1 with the
potentiometer P1, and separately for channel 2 via potentiometer P2.
Hysterese:
Adjustments of the hysteresis (1...10)% are
made for channel 1 with the potentiometer
P3, and separately for channel 2 via potentiometer P3.
WAVEANALOG DC/Alarm
– Alarm indication
Example 1
100%
Sc alSignal threshold
ll 2 / high
1 /trip
high trip
5% Hysteresis
Input range
Technical data
1
n
n
50%
1
threshold
/ high trip
SchalSignal
chwelle
1 / high2trip
10% Hysteresis
Relay 2 NON FAILSAFE
0
1
Relay 1 NON FAILSAFE
0
Zeit
2 kVeff / 5 s output
Example 2
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 17.5 x 112.4
100%
Signal threshold 1 / high trip
5% Hysteresis
Input range
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS5 DC/Alarm
WAZ5 DC/Alarm
Qty.
1
1
Order No.
8543820000
8543880000
10% Hysteresis
50%
Signal threshold 2 / low trip
1
Relay 2 FAILSAFE
0
1
Note
Relay 1 FAILSAFE
0
Time
Accessories
Note
Cross-connectors for power supply and
markers - see WAVESERIES accessories
D.39
D
Analogue signal conditioning
WAVESERIES – universal signal converters and trip amplifiers, configurable
One module fits all …
In the case of signal processing this is a big benefit. The
maintenance engineer who hasn’t got the right spare isolator or
transmitter, and has to run part of the plant on manual control
for a day or two before the replacement arrives understatands
this. It wastes his time and money. So Weidmüller have designed a signal processor with unique flexibility.
D
In one module the Wave TTA is an intelligent signal
• Isolator
• Convertor
• Transmitter
• Lineariser
• Trip-amplifier
The new Wave TTA is a „universal“ Transmitter Trip-Amplifier. It
is part of Weidmüller’s well-established WAVESERIES family of
analogue signal conditioners, which are widely used in process
and factory automation applications.
The TTA is unique. It has a combination of high performance
and exceptional configurability. Designed for process industry
applications, the TTA will work accurately and stably over a
wide ambient temperature range, and over a wide supply voltage range, and with most types of sensor inputs. For 2 wire current transmitters, 24 V DC power is provided. Alternatively the
TTA can be a passive input for the current source.
For linearised and/or isolated analogue outputs, the user has a
choice of standard or rangeable DC milliamps and voltage ranges. These can be set as either direct or reverse acting. The
user can also select upscale or downscale output in the event
of a sensor break or an open circuit in the input.
The TTA provides 2 independently settable changeover-relay
outputs, for use as high and low level alarms or control points.
Configuring the versatile TTA to change input and output parameters is simple, and performed from a computer via an interface (CBX100 USB).
Powering the TTA is flexible too. When the auxiliary supply is
anything between 18 and 264 V (AC or DC), one module can
take it.
Physically, the TTA comes in a black WAVESERIES UL 94 V0
housing, for mounting on TS35 DIN rail. Pluggable connectors,
allow screw or tension clamp wiring. A screwdriver-releasable
front flap gives access to the configuration interface socket.
Most commonly used temperature sensors and DC inputs are
accepted, and the TTA also allows the user to define his own
characteristic, so special sensor types and linearization can easily be acommodated.
To help simplify installation and loop commissioning, test terminals are provided to permit input and output signal checks without removing cabling.
Ordering data
Screw connection
Tension clamp connection
Type
WAS6 TTA
WAZ6 TTA
Note
Accessories
Note
D.40
CBX100 USB Interface – 7940025031
Connects the WAVE TTA with a PC for calibration
Qty.
1
1
Order No.
8939670000
8939680000
WAVE TTA
WAS6 TTA / WAZ6 TTA
Universal signal converters and trip amplifers
• Inputs and outputs can can be
configured via PC
• Universal input signals
• Loop-powered or passive input
• Pluggable connection terminals
Analogue Inputs
3 Port Isolation
J V, I
V, I
PS
+24 V DC
Relay
Channel 1
Relay
Channel 2
Output
0 ... 11 V /
0 ... 22 mA
D
18-264 V AC/DC supply
Technical data
Input
Type, thermocoupleR, S, T (IEC 60584)
Type, RTD T1000, (EN 60571) Ni100, Ni1000, (JIS1604),
Cu10, Cu25, Cu50, Cu100 (DIN 43760) 2-/3-/4-Leiter
Potentiometer / currentΩ /
Resistance…5 kΩ
Frequency 00 kHz
Voltage 00 mV (min. Soanne 4 mV), -20…50 V DC (min.
Spanne 0,5 V)
Current.50mA (min. Spanne 0,4 mA)
Current Loop Supply
Output signal during wire break / max.
Accuracynne (DC, RTD); 0,2 % Spanne (oder 1 °C) + CJ
Fehler
Temperature coefficient
Eingang
B, E, J, K, L, N, R, S, T (IEC 60584)
PT100, PT1000, (EN 60571) Ni100, Ni1000, (JIS1604), Cu10,
Cu25, Cu50, Cu100 (DIN 43760) 2-/3-/4-conductor
100 Ω…100 kΩ
10 Ω…5 kΩ
2 Hz…100 kHz
-200…500 mV (min. span 4 mV),
-20…50 V DC (min. span 0.5 V)
-20…50mA (min. span 0.4 mA)
24 V DC / 22 mA rsorgung
configurable / i Drahtbruch/max.
< 0.1 % span (DC, RTD); 0.2 % span (or 1 °C) + CJ error
< 0.1 % / K (DC, RTD); < 0.1 % FSR / K + CJ error 0.07 °C/K
(thermocouples) oeffizient
Ausgang (Analog)
Can be set from -10…+10 V (min. span 2.5 V)
Can be set from 0…20 mA (min. span 5 mA)
> 10 kΩ @ 0…10 V / > 20 kΩ @ -10…+10 V
< 700 Ωm
Direct or inverted
Linear, x1/2, x3/2, x5/2 or user-defined curve (101 points)
Ausgang (Digital)
2 x 1 CO contact (hard gold plated)
AgSnO 5μm Au
250 V . Schaltspannung AC
3 A erstrom
Allgemeine Angaben
18…264 V AC/DC ng
Output (analogue)
Output voltage
Output current
Load resistance, voltage
Current
Signal output
Transmit function
Output (digital)
Typeechsler (hartvergoldet)
Contact base material
Max. switching voltage AC
Continuous current
General data
Supply voltage
Power consumption
Operating temperatureerating ab 65 °C)
Storage temperature
Step response time mV Eingänge), 110 ms…1 s (V, mA
Eingänge)
Approvals
Humidity
Insulation coordination
Standards
EMC standards
Rated voltage
Impulse withstand voltage
Pollution severity
Overvoltage category
Clearance & creepage distance
Insulation voltage
Clamping range (rated- / min. / max)
Length x width x height
< 3.5 W saufnahme
-40 °C…+70 °C (derating from 65 °C)
-40 °C…+85 °C
50 ms…1 sec (RTD, mV inputs), 110 ms…1 sec
(V, mA inputs)
CE; cULus / C1D2 / Zone 2 ATEX in preparation
5…95 % no condensation
Allgemeine Angaben
EN 50178 (protective separation)
EN 55011, EN 61000-6
300 V (100 V input/output)
6 kV
2
III
≥ 5,5 mm (1 mm input/output)
2.5 kV
mm2
mm
Analogue signal conditioning
WAVESERIES – universal signal converters and trip amplifiers, configurable
Typical functions
Isolator
I
I, V
PS
Converter
f, I, V
I, V
PS
Transmitter
J
I, V
PS
Lineariser
I, V
I, V
PS
Trip amplifier
J
PS
2.5 / 0.5 / 2.5
92.4 x 45 x 112.4
Note
D.41
Analogue signal conditioning
WAVESERIES - Current monitoring
Relay output
20/40/60 A ac
1/5/10 A AC
• Current ranges adjustable via DIP switch
• Switchable hysteresis
• Operating or closed-circuit current principle
1
4 +24V 2
3
0V
5
CC
6
D
CC
IN
10
12
100% 11
10%
Setpoint
14
K1
~
12
11
~
7
CC
+24V 1
2
OV 3
12
10%
100%
Setpoint
K1
8
11
14
9
CC
Technical data
Input
Input current 0…40 A AC/ 0…60 A AC
Input frequency
max. current onductor cross-section
max. voltage 400 V AC depends on wire insulation
Sensor orming (internally)
Diameter of entry
Output
Switching thresholds with front potentiometer
Hysteresis of threshold value
Switching voltage, min./max.
Switching current min./max.
Continuous current
Step response time
Temperature coefficient
Status indicator
General data
Supply voltage n; 10 %
Current consumption riggered)/ 24 mA (relay triggered)
Current-carrying capacity of cross-connect.
Operating temperature/Storage temperature
Default setting Hysteresis / operating current principle
Approvals s
Contact complement ct
Insulation coordination
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Pollution severity
Surge category
Clearance & creepage distance
Isolation voltage input, output
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Input
0…1 A AC/ 0…5 A AC/ 0…10 A AC C
Input
0…20 A AC/ 0…40 A AC/ 0…60 A AC
50…60 Hz ency
100 A for 1s nductor cross-section
250 V AC > 400 V AC depends on wire insulation
Transforming (internally)
Diameter of entry
Output
adjustable 10…100% with front potentiometer
5% or 10% of threshold value
6 V AC/DC /60 V DC/ 250 V AC
100 mA /7 A rrent min./max.
0.7 A DC / 3 A AC t
typ. 700 ms e time
≤ 800 ppm/K fficient
green LED icator
General data
24 V DC ± 10 %
8.3 mA (relay not triggered)/ 24 mA (relay triggered)
≤ 2 A arrying capacity of cross-connect.
0 °C…+50 °C /-20 °C…+70 °C emperature
0…5 A / 10% Hysteresis / operating current principle
CE / cULus
1 changeover contact
Insulation coordination
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 llution severity
III e category
50…60 Hz ency
depends on conductor cross-section
400 V AC, > 400 V AC depends on wire insulation
Hall sensor (internal) y)
8 mm ter of entry
Output
adjustable 10…100% with front potentiometer
5% or 10% of threshold value
6 V AC/DC /60 V DC/ 250 V AC
100 mA /7 A rrent min./max.
0.7 A DC / 3 A AC t
typ. 700 ms e time
≤ 250 ppm/K fficient
green LED icator
General data
24 V DC ± 10 %
23 mA (relay not triggered)/ 47 mA (relay triggered)
≤ 2 A arrying capacity of cross-connect.
0 °C…+50 °C /-20 °C…+70 °C emperature
0…40 A / 10% Hysteresis / operating current principle
CE / cULus
1 changeover contact
Insulation coordination
EN 55011, EN 61000-6
300 V voltage
4 kV se withstand voltage
2 llution severity
III e category
≥ 3 mm ce & creepage distance
4 kVeff / 5 s output
≥ 3 mm ce & creepage distance
4 kVeff / 5 s output
Screw connection
2.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Tu=23°C, single module
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS2 CMR 1/5/10A ac
WAZ2 CMR 1/5/10A ac
Qty.
1
1
Order No.
8516560000
8516570000
Type
WAS2 CMR 20/40/60A ac
WAZ2 CMR 20/40/60A ac
Note
Accessories
Note
D.42
Cross-connectors for power supply and
markers - see WAVESERIES accessories
Cross-connectors for power supply and
markers - see WAVESERIES accessories
Qty.
1
1
Order No.
8513340000
8526600000
Analogue output
1/5/10 A AC 4…20 mA
1/5/10 A AC
Loop Powered
• Input/output electrically isolated
• DIP switches for setting input and output ranges
• No calibration necessary
1
+ 24V 7
NC
Out + 7
2
CC
I
3
1
NC
2
Output 8
IN
CC
U/I
0V 9
3
IN
NC 8
I
Out - 9
I
Technical data
Input
Input current …5 A AC/ 0…10 A AC
Input frequency
max. current
Voltage of measuring circuit
Sensor orming (internally)
Output
Output current/Output voltage
Offset current
Output signal limit 24 mA
Load impedance, voltage/Current
Step response time
Accuracy R
Temperature coefficient
Status indicator HING: signal out of range;
LED OFF: Error
General data
Supply voltage n; 10 %
Current consumption /sub> =20 mA
Current-carrying capacity of cross-connect.
Operating temperature/Storage temperature
Default setting .20 mA
Approvals C1D2;ATEX
Insulation coordination
Standards (protective separation)
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Pollution severity
Surge category
Clearance & creepage distance
Isolation voltage input, output
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Input
0…1 A AC/ 0…5 A AC/ 0…10 A AC
Input
0…1 A AC/ 0…5 A AC/ 0…10 A AC
50…60 Hz ency
100 A for 1s
250 V AC f measuring circuit
Transforming (internally)
Output
0(4)…20 mA /0…10 V oltage
max. 100 μA nt
approx. 13 V resp. 24 mA
≥ 1 kΩ /≤ 600 Ω ent
typ. 700 ms e time
0.5% FSR
≤ 200 ppm/K fficient
LED ON: OK; FLASHING: signal out of range;
LED OFF: Error
General data
24 V DC ± 10 %
40 mA at IOUT =20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+50 °C /-20 °C…+70 °C emperature
0…5 A AC, 4…20 mA
CE;cULus; 1D2;ATEX
Insulation coordination
EN 50178 (protective separation)
EN 55011, EN 61000-6
300 V voltage
6 kV se withstand voltage
2 llution severity
III e category
50…60 Hz ency
100 A for 1s
250 V AC f measuring circuit
Transforming (internally)
Output
4…20 mA (current loop) / age
max. 100 μA nt
approx. 24 mA esp. 24 mA
/≤ 600 Ω voltage/Current
typ. 700 ms e time
0.5 % FSR
≤ 200 ppm/K fficient
LED ON: OK; FLASHING: signal out of range;
LED OFF: Error
General data
13…30 V DC mn; 10 %
40 mA at IOUT =20 mA
Current-carrying capacity of cross-connect.
0 °C…+50 °C /-20 °C…+70 °C emperature
0…5 A AC, 4…20 mA
CE;cULus;C1D2;ATEX
Insulation coordination
EN 50178 (protective separation)
EN 55011, EN 61000-6
300 V voltage
6 kV se withstand voltage
2 llution severity
III e category
≥ 5,5 mm & creepage distance
4 kVeff / 5 s output
≥ 5,5 mm & creepage distance
4 kVeff / 5 s output
Screw connection
2.5 / 0.5 / 2.5
72 x 22.5 x 92.4
Screw connection
2.5 / 0.5 / 2.5
72 x 22.5 x 92.4
Tension clamp connection
1.5 / 0.5 / 2.5
72 x 22.5 x 92.4
Tu=23°C, single module
Tension clamp connection
1.5 / 0.5 / 2.5
72 x 22.5 x 92.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS1 CMA 1/5/10A ac
WAZ1 CMA 1/5/10A ac
Qty.
1
1
Order No.
8523400000
8523410000
Type
WAS1 CMA LP 1/5/10A ac
WAZ1 CMA LP 1/5/10A ac
Qty.
1
1
Order No.
8528650000
8528660000
Note
Accessories
Note
Analogue signal conditioning
WAVESERIES - Current monitoring
Cross-connectors for power supply and
markers - see WAVESERIES accessories
D.43
D
Analogue signal conditioning
WAVESERIES - Current monitoring
Analogue output
5/10 A AC/DC
20/25/30 A AC/DC
Input
0…5 A AC/DC / 0…10 A AC/DC / 0…30 A AC/DC
Input
0…20 A AC/DC / 0…25 A AC/DC / 0…30 A AC/DC
0…2 kHz (true RMS to DC converter)
depends on conductor cross-section
400 V AC, >400V AC depends on conductor insulation
Hall sensor (internal)
8 mm ter of entry
Output
0(4)…20 mA /0…10 V oltage
max. 150 μA nt
approx. 13 V resp. 24 mA
≥ 1 kΩ /≤ 600 Ω ent
typ. 700 ms e time
1 % FSR
≤ 650 ppm/K fficient
LED ON: OK; FLASHING: signal out of range;
LED OFF: Error
General data
24 V DC ± 10 %
50 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+50 °C /-20 °C…+70 °C emperature
0…5 A, 4…20 mA
CE / cULus
Insulation coordination
EN 50178 (protective separation)
EN 55011, EN 61000-6
300 V voltage
6 kV se withstand voltage
2 llution severity
0…2 kHz (true RMS to DC converter)
depends on conductor cross-section
400 V AC, >400V AC depends on conductor insulation
Hall sensor (internal)
8 mm ter of entry
Output
0(4)…20 mA /0…10 V oltage
max. 150 μA nt
approx. 13 V resp. 24 mA
≥ 1 kΩ /≤ 600 Ω ent
typ. 700 ms e time
1 % FSR
≤ 650 ppm/K fficient
LED ON: OK; FLASHING: signal out of range;
LED OFF: Error
General data
24 V DC ± 10 %
50 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+50 °C /-20 °C…+70 °C emperature
0…25 A, 4…20 mA
CE / cULus
Insulation coordination
EN 50178 (protective separation)
EN 55011, EN 61000-6
300 V voltage
6 kV se withstand voltage
2 llution severity
III e category
≥ 5,5 mm & creepage distance
4 kVeff / 5 s output
III e category
≥ 5,5 mm & creepage distance
4 kVeff / 5 s output
Screw connection
2.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Screw connection
2.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
• Input/output electrically isolated
• DIP switches for setting input and output ranges
• No calibration necessary
D
Technical data
Input
Input current C / 0…25 A AC/DC / 0…30 A AC/DC
Input frequency RMS to DC converter)
max. current onductor cross-section
Voltage of measuring circuit n conductor insulation
Sensor ensor (internal)
Diameter of entry
Output
Output current/Output voltage
Offset current
Output signal limit 24 mA
Load impedance, voltage/Current
Step response time
Accuracy
Temperature coefficient
Status indicator HING: signal out of range;
LED OFF: Error
General data
Supply voltage n; 10 %
Current consumption /sub> = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature/Storage temperature
Default setting 0 mA
Approvals s
Insulation coordination
Standards (protective separation)
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Pollution severity
Surge category
Clearance & creepage distance
Isolation voltage input, output
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Tu=23°C, single module
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS2 CMA 5/10A uc
WAZ2 CMA 5/10A uc
Qty.
1
1
Order No.
8526610000
8526620000
Type
WAS2 CMA 20/25/30A uc
WAZ2 CMA 20/25/30A uc
Note
Accessories
Note
D.44
Cross-connectors for power supply and
markers - see WAVESERIES accessories
Cross-connectors for power supply and
markers - see WAVESERIES accessories
Qty.
1
1
Order No.
8545830000
8545840000
Analogue output
40/50/60 A AC/DC
• Input/output electrically isolated
• DIP switches for setting input and output ranges
• No calibration necessary
Analogue signal conditioning
WAVESERIES - Current monitoring
D
Technical data
Input
Input current C / 0…50 A AC/DC / 0…60 A AC/DC
Input frequency RMS to DC converter)
max. current onductor cross-section
Voltage of measuring circuit n conductor insulation
Sensor ensor (internal)
Diameter of entry
Input
0…40 A AC/DC / 0…50 A AC/DC / 0…60 A AC/DC
0…2 kHz (true RMS to DC converter)
depends on conductor cross-section
400 V AC, >400V AC depends on conductor insulation
Hall sensor (internal)
8 mm ter of entry
Output
0(4)…20 mA /0…10 V oltage
max. 150 μA nt
approx. 13 V resp. 24 mA
≥ 1 kΩ /≤ 600 Ω ent
typ. 700 ms e time
1 % FSR
≤ 650 ppm/K fficient
LED ON: OK; FLASHING: signal out of range;
LED OFF: Error
General data
24 V DC ± 10 %
50 mA at IOUT = 20 mA
≤ 2 A arrying capacity of cross-connect.
0 °C…+50 °C /-20 °C…+70 °C emperature
0…50 A, 4…20 mA
CE / cULus
Insulation coordination
EN 50178 (protective separation)
EN 55011, EN 61000-6
300 V voltage
6 kV se withstand voltage
2 llution severity
Output
Output current/Output voltage
Offset current
Output signal limit 24 mA
Load impedance, voltage/Current
Step response time
Accuracy
Temperature coefficient
Status indicator HING: signal out of range;
LED OFF: Error
General data
Supply voltage n; 10 %
Current consumption /sub> = 20 mA
Current-carrying capacity of cross-connect.
Operating temperature/Storage temperature
Default setting 0 mA
Approvals s
Insulation coordination
Standards (protective separation)
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Pollution severity
Surge category
Clearance & creepage distance
Isolation voltage input, output
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
III e category
≥ 5,5 mm & creepage distance
4 kVeff / 5 s output
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS2 CMA 40/50/60A uc
WAZ2 CMA 40/50/60A uc
Qty.
1
1
Order No.
8513330000
8526590000
Note
Accessories
Note
Cross-connectors for power supply and
markers - see WAVESERIES accessories
D.45
Analogue signal conditioning
WAVESERIES - Voltage monitoring
Relay output
VMR V AC
• 3-way isolation
single-phase
• Monitoring of single-phase systems up to 260 V
AC/DC
• 4 input ranges selected by DIP switches
• 1 relay with change-over contact
• Switchable hysteresis
• Switch adjusted via potentiometer
• Reset input
Table of setting options
14 12
8705640000 06
Technical data
Input
Input voltage ..140 / 140…210 / 210…260 V AC / DC
Input frequency
max. voltage C
Input
24…70 / 70…140 / 140…210 / 210…260 V AC / DC
Output
Switching voltage, min./max.
Switching current min./max.
Continuous current/AC switching capacity
Hysteresis AC, small = 5 V / large = 10 V
Temperature coefficient
Step response time
Repeat accuracy ange
Status indicator LED red/yellow = alarm status
General data
Supply voltage ring circuit
Reset input voltage, min.-max.
Pulse length, min.
Default setting N = 1,2,5,8 / OFF = 3,4,6,7
Operating temperature module
Storage temperature
Approvals s
Insulation coordination
Standards
EMC standards 61000-6 /-2, EN 61326
Rated voltage input/reset input, reset input/output: 300 V
Impulse withstand voltage input, reset input/output: 4 kV
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance ut, reset input/output: 3 mm
50…60 Hz ency
260 V AC / DC
Output
/250 V AC voltage, min./max.
/8 A hing current min./max.
3 A /1000 VA urrent/AC switching capacity
24…70 V AC, small = 5 V / large = 10 V
≤ 250 ppm/K fficient
< 300 ms onse time
< 0.3% of set range
LED green = OK / LED red/yellow = alarm status
General data
from the measuring circuit
18 V DC-30 V DC tage, min.-max.
700 ms length, min.
DIP switches: ON = 1,2,5,8 / OFF = 3,4,6,7
-10°C…+55°C single module
-20 °C…+70 °C ure
CE / cULus
Insulation coordination
EN 50178
EN 55011, EN 61000-6 /-2, EN 61326
input/output, input/reset input, reset input/output: 300 V
input/output, input/reset input, reset input/output: 4 kV
2 kVeff nput, output
III e category
2 llution severity
input/output, input/reset input, reset input/output: 3 mm
1 2 3 4 5 6 7 8
n n n n
n n n n
n n n n
n n n n
n
n
n
n
Memory out
Hysteresis
Hysteresis small
Hysteresis large
Input voltage
AC voltage
DC voltage
n
n
n
n
n
n
= on
= out
Status indicator
Set value not exceeded.
Alarm status.
Alarm status can be reset because
set value has been exceeded.
Abb.1: Overvoltage monitoring
Alarm set to “high trip“
(Set permanently to closed-circuit principle.)
(Set permanently to closed-circuit principle.)
100%
Input range
24V AC/DC…260V AC/DC
Input
24 V AC/DC...70 V AC/DC
70 V AC/DC...140 V AC/DC
140 V AC/DC...210 V AC/DC
210 V AC/DC...260 V AC/DC
Trip
High Trip
Low Trip
Memory
Memory on
Operating point
Hysteresis
50%
Time
1
Relay/High Trip/ Memory out
Output
Input
D
11
11
5
6
10
WAS5 VMR 1ph
Reset
+ 18 V DC…60 V DC
1
2 nc
3 –
Setpoint
4 nc
0
1
Relay/High Trip/ Memory on
Reset
0
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Screw connection
2.5 / 0.5 / 2.5
96.5 x 17.5 x 112.5
1
Reset for output
0
min. 700ms
Abb.2: Undervoltage monitoring
Alarm set to “low trip”
(Set permanently to closed-circuit principle.)
Note
(Set permanently to closed-circuit principle.)
100%
Type of connection
Screw connection
Type
WAS5 VMR 1ph
Qty.
1
Order No.
8705640000
Input range
Ordering data
Operating point
Hysteresis
50%
Time
1
Note
D.46
Output
1
1
Relais/Low Trip/Memory on
0
Accessories
Note
Reset
Relais/Low Trip /Memory out
0
Markers, refer to WAVESERIES accessories
0
Reset for output
min. 700ms
Relay output
VMR V AC
• 2-way isolation
3-phase
• Monitoring of single and 3-phase networks of
80…400 V AC/DC
• Setting via DIP switch
• Under- and overvoltage monitoring
• Phase-failure detection
Analogue signal conditioning
WAVESERIES - Voltage monitoring
• 2 relays with changeover contact
80…250 V AC/DC L1
7
8
9
12
14
80…250V AC/DC L2
4
N
5
80…250V AC/DC L3
6
WAS2 VMR 3ph
Table of setting options
11
21
L1
L2
L3
22
24
06
10
11
12
Technical data
Input
Input voltage 3~
Input voltage 1~ C
Input current < 10 mA DC
Input
80…250 V AC/DC
Output
Switching voltage, min./max.
Continuous current/AC switching capacity
Hysteresis l value
Temperature coefficient
Step response time
Repeat accuracy ange
Status indicator
General data
Supply voltage ring circuit
Reset input voltage, min.-max.
Pulse length, min.
Default setting N = 1,2,4 / OFF = 3
Operating temperature
Storage temperature
Approvals
Insulation coordination
Standards
EMC standards 61000-6 /-2, EN 61326
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance circuit, output circuit 1/output
circuit 2: 3 mm; input/output: 5.5 mm
200…400 V AC/DC
< 15 mA AC / < 10 mA DC
Output
/250 V AC voltage, min./max.
3 A /750 VA current/AC switching capacity
5% of final value
≤ 300 ppm/K fficient
< 300 ms onse time
< 0.3% of set range
green LED icator
General data
from the measuring circuit
- eset input voltage, min.-max.
Pulse length, min.
DIP switches: ON = 1,2,4 / OFF = 3
0 °C…+50 °C erature
-25 °C…+85 °C ure
CE;cULus;
Insulation coordination
EN 50178
EN 55011, EN 61000-6 /-2, EN 61326
600 V voltage
6 kV se withstand voltage
4 kVeff / 1 min. put
III e category
2 llution severity
Output circuit: 1.8 mm; input circuit, output circuit 1/output
circuit 2: 3 mm; input/output: 5.5 mm
Input
3 phases 80 V AC/DC...250 V AC/DC
1 phase 200 V AC/DC...400 V AC/DC
Limit value
Setting to upper switching point
Setting to lower switching point
Hysteresis
Hysteresis, small
Hysteresis, large
Fault tolerance
Operating current method
Closed-circuit current method
n
n
1
2
n
3
4
n
n
D
n
n
n
n
n
= on
= off
Status indicator
Voltage is in set range
Fig. 1: Overvoltage and undervoltage monitoring,
example of setting
– 3-phase monitoring
– Setting limit value to upper operating point:
230 V Hysteresis 5% = -12,5 V
– Lower operating point 10% less 230 V - 25 V = 205 V
Hysteresis 5% = + 12,5 V
– The device operates with the operating current principle.
– All 3 phases monitored in parallel
U
Upper operating point
Hysteresis
Input range
200…400 V AC/DC
10%
Hysteresis
Lower operating point
0
Time
1
Output
1
2
3
0
Relay 1/Operating current
principle, Overvoltage
1
0
Relay 2/Operating current
principle, Undervoltage
Fig. 2: Overvoltage and undervoltage monitoring,
example of setting
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
– 3-phase monitoring
– Setting limit value to lower operating point:
150 V Hysteresis 5% = +12,5 V
– Upper operating point 20% greater 150 V + 50 V = 200 V
Hysteresis 5 % = –12,5 V
– The device operates with the closed-circuit current principle.
– All 3 phases monitored in parallel
Screw connection
2.5 / 0.5 / 2.5
96.5 x 22.5 x 112.5
Note
U
Ordering data
Upper operating point
Screw connection
Type
WAS2 VMR 3ph
Qty.
1
Order No.
8705630000
Hysteresis
Input range
Type of connection
20%
Hysteresis
Lower operating point
0
Note
Time
Output
1
Accessories
Note
Markers, refer to WAVESERIES accessories
0
1
0
Relay 1 /Closed-circuit
current principle,
Overvoltage
Relay 2 /Closed-circuit
current principle,
Undervoltage
D.47
Analogue output
VMA V AC
• 3-way isolation
• Max. measuring voltage 450 V ACeff
• Output ranges selectable via DIP switch
• No calibration necessary
0V
0…30V
0…70V
0…130V
0…250V
0…450V
D
1
2
3
4
5
6
0…10V 7
0/4…20mA 8
GND1 9
+24V 10
0…20mA 4…20mA
SW1 OFF ON
SW2 OFF ON
GND2 11
Technical data
Input
0…30 / 0…70 / 0…130 / 0…250 / 0…450 V AC
Output
Output voltage/Output current
Offset voltage/Offset current
Load impedance, voltage/Current
Accuracy …60 Hz) typ. 1%/ 2% (70…400 Hz) typically 1.5%
Temperature coefficient
Step response time
Status indicator
General data
Supply voltage n; 25 %
Current consumption IOUT =20 mA
Current-carrying capacity of cross-connect.
Default setting A
Operating temperature/Storage temperature
Approvals
Insulation coordination
Standards
EMC standards N 61000-2-6, EN 61326
Rated voltage : 300 V; input/output, supply/output: 600 V
Impulse withstand voltage t/output, supply/output: 6kV
Isolation voltage input, output/
Surge category
Pollution severity
Clearance & creepage distance tput, supply/output: 5.5 mm
40…400 Hz sinus
45 / 100 / 180 / 270 / 475 V AC (short time)
Output
0…10 V /0(4)…20 mA urrent
max. 0.02 V /max. 40 μA rrent
≥ 1 kΩ /≤ 600 Ω ent
1.3% (40…60 Hz) typ. 1%/ 2% (70…400 Hz) typically 1.5%
≤ 250 ppm/K fficient
< 300 ms onse time
green LED icator
General data
24 V DC ± 25 %
40…30…24 mA at IOUT =20 mA
≤ 2 A arrying capacity of cross-connect.
0…10V/0…20mA
0 °C…+50 °C /-20 °C…+70 °C emperature
CE;cULus;
Insulation coordination
EN 50178
EN 61000-6, EN 61000-2-6, EN 61326
supply/output: 300 V; input/output, supply/output: 600 V
supply/output: 4 kV; input/output, supply/output: 6kV
4 kVeff / 5 s / utput/
III e category
2 llution severity
supply/output: 3 mm; input/output, supply/output: 5.5 mm
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Screw connection
2.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
mm2
mm
Note
Tension clamp connection
1.5 / 0.5 / 2.5
92.4 x 22.5 x 112.4
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
WAS2 VMA V ac
WAZ2 VMA V ac
Note
Accessories
Note
D.48
Cross-connectors for power supply and
markers - see WAVESERIES accessories
Qty.
1
1
Order No.
8581220000
8581230000
Application
230 Vac
~
24 Vdc
SPS
10 11 12
7
L1
L2
L3
8
9
M
3~
U
1
2
3
4
5
6
0 20 mA
Input
Input voltage 70 / 0…130 / 0…250 / 0…450 V AC
Input frequency us
max. voltage 80 / 270 / 475 V AC (short time)
WAVE CONTROL
VMA Va c
8581220000/85811230000
Analogue signal conditioning
WAVESERIES - Voltage monitoring
CBX100 USB
Analogue signal conditioning
WAVESERIES – Signal-converter accessories
• Interface for configuration
• USB port for PC
• Tx and Rx status displays
D
Technical data
Connections
Display
Status indicator
Eingang
LED (send / receive)
Eingang
General data
Isolation voltage
Operating temperature / storage temerature
Air humidity
Software
Interface
Approvals
500 V for 60s
–20 °C...+70 °C / –25 °C...+70 °C
10…90 % (no condensation)
T-Set as of V.4.2 (can be downloaded from www.mannseries.com)
USB
CE, cULus
Converter
1
2
3
4
Output
Input
PC
CBX100
Note: Disconnect the charging unit before operating the CBX100
Note:
Ordering data
Type
Interface device
Type
CBX100 USB
Qty.
1
Order No.
7940025031
Note:
Accessories
Note:
D.49
Analogue signal conditioning
WAVESERIES – Accessories
WAVEBOX S 22.5
WAVEBOX L 22.5
D
WAVEBOX 12.5
WAVEBOX 17.5
Dimensions in mm
Accessories
Cross-connection ZQV 2.5N/2, black
Cross-connection ZQV 2.5N/2, red
Type
ZQV 2.5N/2 sw
ZQV 2.5N/2 rt
Qty
60
60
Order No.
1718080000
1717900000
Cross-connection ZQV 2.5N/2, blue
Cross-connection ZQV 2.5N/2, yellow
ZQV 2.5N/2 bl
ZQV 2.5N/2 ge
60
60
1717990000
1693800000
Markers
WS 10/5 MutliCard for plotter labelling
WS 10/5 blank
WS10/5
WS10/5 Blank
144
200
1061160000
1060860000
D.50
Analogue output
CMA 250/5 A
CMA 100/5 A
CMA 500/5 A
• Max. conductor diameter 35 mm
• Can be mounted sideways
• For mounting on rail TS 35
Analogue signal conditioning
CMA - Current monitoring
D
Technical data
Input
Input current
Input frequency 0Hz / Class 1.5: 16…400Hz
max. current ent Ith >3 kA
Voltage of measuring circuit hed conductor)
Diameter of entry
Output
Output current
Load impedance, voltage/Current
Accuracy / 1.5; residual current factor < 5
General data
Operating temperature
Storage temperature
Approvals
Insulation coordination
Isolation voltage input, output
Dimensions
Clamping range (rating- / min. / max.) mm2
Length x width x height
mm
Input
100 A AC rent
Input
250 A AC rent
Input
500 A AC rent
Class 1: 50…60Hz / Class 1.5: 16…400Hz
Thermal current Ith >3 kA
600 Veff (unfinished conductor)
35 mm er of entry
Output
5 A AC current
/≤ 600 Ω voltage/Current
class 1 / 1.5; residual current factor < 5
General data
-5 °C…+40 °C erature
-40 °C…+85 °C ture
CE;cURus;
Insulation coordination
4 kVeff / 1 min. tput
Class 1: 50…60Hz / Class 1.5: 16…400Hz
Thermal current Ith >3 kA
600 Veff (unfinished conductor)
35 mm er of entry
Output
5 A AC current
/≤ 600 Ω voltage/Current
class 1 / 1.5; residual current factor < 5
General data
-5 °C…+40 °C erature
-40 °C…+85 °C ture
CE;cURus;
Insulation coordination
4 kVeff / 1 min. tput
Class 1: 50…60Hz / Class 1.5: 16…400Hz
Thermal current Ith >3 kA
600 Veff (unfinished conductor)
35 mm er of entry
Output
5 A AC current
/≤ 600 Ω voltage/Current
class 1 / 1.5; residual current factor < 5
General data
-5 °C…+40 °C erature
-40 °C…+85 °C ture
CE;cURus;
Insulation coordination
4 kVeff / 1 min. tput
Screw connection (secondary)
Screw connection (secondary)
Screw connection (secondary)
50 x 78 x 90.5
50 x 78 x 90.5
50 x 78 x 90.5
Note
Ordering data
Type of connection
Screw connection (secondary)
Type
CMA 100/5A
(Qty.=1)
Order No.
8662140000
Type
CMA 250/5A
(Qty.=1)
Order No.
8664570000
Type
CMA 500/5A
(Qty.=1)
Order No.
8664580000
Note
Accessories
Note
D.51
Analogue signal conditioning
MCZ-SERIES
Advantages of the MCZ-SERIES
Width
Just 6 mm wide (without cover plate), the MCZ-SERIES
offers enough space for electronic circuits.
Connecting
D
Tension clamp connection
Cross-connection
The power supply and another potential can be crossconnected
D.52
Input current loop feed
MCZ CCC
Passive isolator for electrical isolation of standard
0/4…20 mA signals. It takes its power from the
measuring signal and does not need any auxiliary
power supply. Special features of this component
are its low power consumption and the operating
current of <100 μA.
Analogue signal conditioning
MCZ-SERIES - DC/DC passive isolator
15
U E [V]
12
9
6
3
0
0
100
200
300
RL
400
500
600
4
-
5
OUT
Z
18V
2
-
C
C
IN
Z
18V
+
+
D
1
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Pick-up current
Voltage drop t 20 mA
Input
/0(4)…20 mA current loop
15 V /50 mA /max. current
< 100 μA ent
2.5….3 V at 20 mA
Output
max. 10 V /0(4)…20 mA rrent
/≤ 500 Ω voltage/Current
< 0.1% of final value
≤ 50ppm/K of measure. value at 0 M load resistance
0.05% of measurement value/100 Ω load resistance
< 10 mVeff
approx. 200 kHz y
General data
-25 °C…+60 °C ature
-40 °C…+85 °C ure
CSA / UL/UR / CE
Insulation coordination
EN 60529, EN 61010-1
EN 61000-6 ds
510 Veff put, output
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy f final value
Temperature coefficient . value at 0 M load resistance
Influence of load impedance 100 Ω load resistance
Residual ripple eff
Chopper frequency
General data
Operating temperature
Storage temperature
Approvals UR / CE
Insulation coordination
Standards EN 61010-1
EMC standards
Isolation voltage input, output
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Tension clamp connection
1.5 / 0.5 / 1.5
91 x 6 x 63.2
Note
Ordering data
Type of connection
Tension clamp connection
Type
MCZ CCC 0-20mA/0-20mA
Qty.
10
Order No.
8411190000
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to MCZ-SERIES accessories
D.53
Analogue signal conditioning
MCZ-SERIES - PT100/RTD - signal isolator
PT100, 2-/3-conductor converter
MCZ PT100/3 CLP
• For 2- or 3-conductor PT100 sensors
• Loop-fed output current
• High accuracy and linearity
D
Technical data
Input
Sensor 2-/3-conductor (to IEC 751)
Supply current/Supply voltage
Input
PT100/2-/3-conductor (to IEC 751)
0.8 mA /9 - 30 V DC y voltage
Output
Output current rent loop)
Load impedance, voltage/Current
Accuracy/Influence of cable resistance .006 K/Ω
Response time
General data
Operating temperature/Storage temperature
Approvals ;CE;
Standards EN 60751, IEC751
EMC standards 0-6
Output
4…20 mA (current loop)
/≤ 600 Ω voltage/Current
typical 0.2%, max. 0.5% of FSR /max. 0.006 K/Ω
10 ms se time
General data
0 °C…+50 °C /-20 °C…+85 °C emperature
CSA;UL/UR;CE;
EN 50178, EN 60751, IEC751
EMVG, EN 61000-6
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Tension clamp connection
1.5 / 0.5 / 1.5
91 x 6 x 63.2
Tu=23°C, single module
Ordering data
Temperature input range
0…100 °C
0…120 °C
0…150 °C
0…200 °C
0…300 °C
-50…+150 °C
-40…+100 °C
Note
D.54
Type of connection
Tension clamp connection
Tension clamp connection
Tension clamp connection
Tension clamp connection
Tension clamp connection
Tension clamp connection
Tension clamp connection
Type
MCZ PT100/3 CLP 0…100C
MCZ PT100/3 CLP 0…120C
MCZ PT100/3 CLP 0…150C
MCZ PT100/3 CLP 0…200C
MCZ PT100/3 CLP 0…300C
MCZ PT100/3 CLP -50C…+150C
MCZ PT100/3 CLP -40C…100C
Cross-connectors for power supplies and
markers - refer to MCZ-SERIES accessories
Qty.
10
10
10
10
10
10
10
Order No.
8425720000
8483680000
8604420000
8473010000
8473020000
8473000000
8604430000
DC/f converter
MCZ CFC
MCZ VFC
The conversion of analogue signals to frequencies
means it is possible to import analogue signals
from the field via the counter inputs of the
controller.
Vcc
4
+24V
Output
5
f
f f/2f/4f/16
Input
f
Vcc
5
+24V
1
0...10V
OV
2
U
Output
5
f
f f/2f/4f/16
16kHz
Input
1
0...20mA
OV
2
f
I
16kHz
D
3 GND
3 GND
Input
0…10 V / age/Input current
Input
/0…20 mA ge/Input current
30 V / oltage/max. current
100 kΩ / ce, voltage/Current
1 V at 20 mA
Output
0…1/ 4/ 8/ 16 kHz
PNP, Ub-0.7 V
max. 20 mA ent
0.2% of FSR
≤ 250 ppm/K fficient
LED, pulsing tor
General data
24 V DC ± 10 %
14 mA without load
≤ 20 A rrying capacity of cross-connect.
0 °C…+50 °C erature
-20 °C…+85 °C ure
CE; ovals
Insulation coordination
EN 50178
EN 55011, EN 61000-6
100 V voltage
1.5 kV withstand voltage
1 kV DC n voltage input, output
III e category
2 llution severity
≥ 1.5 mm & creepage distance
/50 mA ltage/max. current
/50 Ω ance, voltage/Current
1 V at 20 mA
Output
0…1/ 4/ 8/ 16 kHz
PNP, Ub-0.7 V
max. 20 mA ent
0.2% of FSR
≤ 250 ppm/K fficient
LED, pulsing tor
General data
24 V DC ± 10 %
14 mA without load
≤ 20 A rrying capacity of cross-connect.
0 °C…+50 °C erature
-20 °C…+85 °C ure
CE; ovals
Insulation coordination
EN 50178
EN 55011, EN 61000-6
100 V voltage
1.5 kV withstand voltage
1 kV DC n voltage input, output
III e category
2 llution severity
≥ 1.5 mm & creepage distance
Tension clamp connection
1.5 / 0.5 / 1.5
91 x 6 x 63.2
Tension clamp connection
1.5 / 0.5 / 1.5
91 x 6 x 63.2
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Voltage drop
Output
Output frequency kHz
Output level V
Output current
Accuracy FSR
Temperature coefficient
Status indicator
General data
Supply voltage n; 10 %
Current consumption
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals
Insulation coordination
Standards
EMC standards 61000-6
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Ordering data
Type of connection
Tension clamp connection
Type
MCZ VFC 0-10V
Qty.
10
Order No.
8461470000
Type
MCZ CFC 0-20MA
Qty.
10
Order No.
8461480000
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to MCZ-SERIES accessories
Analogue signal conditioning
MCZ-SERIES - Frequency signal isolator
Cross-connectors for power supplies and
markers - refer to MCZ-SERIES accessories
D.55
Analogue signal conditioning
MCZ-SERIES - Limit value monitoring
Transistor output
MCZ SC 0…20 mA
MCZ SC 0…10 V
• 2 digital outputs
• Monitoring of upper and lower limits
4
Output1
max.50mA
5
D
Output2
max.50mA
P1
Th1
P2
Th2
4
2
OV
3 Vcc
+24V
Output1
max.50mA
Input
0...20mA
1
S1 S2 Uth
off x 300mV...10V
on off 30mV...1V
on off 10mV...100mV
2
OV
3 Vcc
+24V
P1
Th1
P2
Th2
5
Input
0...20mA
1
Output2
max.50mA
Technical data
Input
Input voltage/Input current
Input resistance, voltage/Current
Voltage drop
Input
0…10 V / age/Input current
Input
/0.5…20 mA /Input current
Output
Contact complement ut PNP
Function TH1: Output 1 active / UINin > UTH2: Output 2 active
Switching thresholds (12 turns)
Hysteresis sted final value
Switching current min./max. ge drop at output transistor: < 1.2
V at 50 mA)
Step response time hreshold at 90% of max. input signal; RI ≤
1 kΩ)
Cut-off frequency (-3dB)
Temperature coefficient /K)
General data
Supply voltage n; 20 %
Current consumption
Operating temperature
Storage temperature
Approvals UR / CE
Insulation coordination
Standards
EMC standards 61000-6
60 kΩ / nce, voltage/Current
Voltage drop
Output
double switch output PNP
UIN < UTH1: Output 1 active / UINin > UTH2: Output 2 active
via 2 potentiometers (12 turns)
1% of adjusted final value
/50 mA - per channel (voltage drop at output transistor: < 1.2
V at 50 mA)
< 250 μs (switch threshold at 90% of max. input signal; RI ≤ 1
kΩ)
100 Hz frequency (-3dB)
250 ppm/K (max. 500 ppm/K)
General data
24 V DC ± 20 %
15 mA t consumption
0 °C…+50 °C erature
-25 °C…+60 °C ure
CSA / UL/UR / CE
Insulation coordination
EN 50178 s
EN 55011, EN 61000-6
/50 Ω ance, voltage/Current
1 V age drop
Output
double switch output PNP
IIN < ITH1: Output 1 active / IIN >ITH2: Output 2 active ve
via 2 potentiometers (12 turns)
1% of adjusted final value
/50 mA - per channel (voltage drop at output transistor: < 1.2
V at 50 mA)
< 250 μs (switch threshold at 90% of max. input signal; RI ≤ 1
kΩ)
100 Hz frequency (-3dB)
max. 250 ppm/K 500 ppm/K)
General data
24 V DC ± 20 %
15 mA t consumption
0 °C…+50 °C erature
-25 °C…+60 °C ure
CSA / UL/UR / CE
Insulation coordination
EN 50178 s
EN 55011, EN 61000-6
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Tension clamp connection
1.5 / 0.5 / 1.5
91 x 6 x 63.2
Tension clamp connection
1.5 / 0.5 / 1.5
91 x 6 x 63.2
mm2
mm
Note
Ordering data
Type of connection
Tension clamp connection
Type
MCZ SC 0-10V
Qty.
10
Order No.
8260280000
Type
MCZ SC 0-20MA
Note
Accessories
Note
D.56
Cross-connectors for power supply and
markers - see MCZ-SERIES accessories
Cross-connectors for power supply and
markers - see MCZ-SERIES accessories
Qty.
10
Order No.
8227350000
MCZ accessories
Analogue signal conditioning
MCZ-SERIES – Accessories
63.2
56
91
D
TS-Contact
Ordering data
End plate
Type
AP MCZ 1.5
Qty
50
Order No.
8389030000
Type
ZQV 4N
ZQV 4N
ZQV 4N
ZQV 4N
ZQV 4N
ZQV 4N
ZQV 4N
ZQV 4N
ZQV 4N
Qty
20
20
20
20
20
20
20
20
20
Order No.
1608950000
1608960000
1608970000
1608980000
1608990000
1609000000
1609010000
1609020000
1609030000
Qty
200
Order No.
1060960000
Ordering data
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
2-poles, yellow
3-poles, yellow
4-poles, yellow
5-poles, yellow
6-poles, yellow
7-poles, yellow
8-poles, yellow
9-poles, yellow
10-poles, yellow
/
/
/
/
/
/
/
/
/
2 ge
3 ge
4 ge
5 ge
6 ge
7 ge
8 ge
9 ge
10 GE
Ordering data
Marker
Type
WS10/6
D.57
Analogue signal conditioning
MICROINTERFACE Analogue
Introduction
MICROINTERFACE Analogue sets standards in analogue signal
processing. It offers wide-ranging functionality within a width of
just 6 mm.
D
The new adapter module MICROINTERFACE Analogue simplifies the wiring of your installation. The time-consuming individual wiring so vulnerable to mistakes is no longer necessary. From
eight MAS modules and two power supply modules, a block is
created that is then electrically bridged with ZQV plug-in
cross-connections.
Mount the MICROINTERFACE Analogue adapter on the signal
terminals (input or output) and connect it. Signal transmission is
via the 15-pole SUB-D plug-in connector with pre-assembled
cables.
D.58
The features of MICROINTERFACE Analogue
• Electrical separation and signal conversion of analogue signals
• Upgrading of SPS I/O cards and fieldbus modules without
electrical separation
• Block setup for 8 or 2 x 4 signals in a width of just 60 mm
• Adapter for all MICROINTERFACE Analogue modules, with mixed assemblies also possible
• Optional power supply via signal line, cross-connectable
Interface module
MI 8 A-I/O S-SUBD15B
MI-A-PSM24 V DC
2 Microanalog power supply modules are required
to provide the power supplies. The voltage
applied may not exceed 50 Veff.
Interface module analogue
Power supplies, module
3
2
Analogue signal conditioning
MICROINTERFACE Analogue
4
0V
5
100nF
1
6
24 V
Technical data
General data
Supply voltage C
Current-carrying capacity ..8: max. 250 mA 250 mA;Power
supply SUB D Pin 9 & 14: 300 mA; 10 & 15: 1.3 A
Operating temperature
Storage temperature
Insulation coordination
Rated voltage
Pollution severity
Surge category
Clearance & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
General data
max. 30 V AC/DC
Signal paths SUB D pin 1…8: max. 250 mA 250 mA;Power
General data
max. 30 V AC/DC
Signal paths SUB D pin 1…8: max. 250 mA 250 mA;Power
supply SUB D Pin 9 & 14: 300 mA; 10 & 15: 1.3 A
0 °C…+50 °C perature
-20 °C…+85 °C ture
Insulation coordination
50 V d voltage
2 ollution severity
III ge category
0.9 mm nce & creepage distance
supply SUB D Pin 9 & 14: 300 mA; 10 & 15: 1.3 A
0 °C…+50 °C perature
-20 °C…+85 °C ture
Insulation coordination
50 V d voltage
2 ollution severity
II rge category
Clearance & creepage distance
SUB D socket, 15-pole
Screw connection
2.5 / 0.5 / 2.5
88 x 6.1 x 97.8
32 x 61 x 42
Note
Ordering data
Type of connection
SUB D socket, 15-pole
Type
MI8A-I/O S SUBD15B
Qty.
10
Order No.
8800220000
Type
MI-A-PSM24Vdc
Qty.
10
Order No.
8800230000
Note
Accessories
Note
D.59
D
Analogue signal conditioning
MICROSERIES
Advantages of the MICROSERIES
Connecting
BLZ screw connection or BLZF tension clamp offers
the the greatest possible flexibility at the wiring stage
(up to 2.5 mm2).
D
Cross-connection
The supply voltage can be bridged from one module to
the next.
Width
MICROANALOGUE sets standards for analogue signal
processing. With a width of just 6 mm, MICROSERIES
is highly functional with a completely enclosed housing.
MICROSERIES is a developing range of temperature transmitters and DC isolators, offering low cost solutions in a miniature
package, but which uses Weidmüller’s high quality connection
options.
MICROSERIES offers some BIG signal conditioning features in
a small package, such as…
• PT100, thermocouple, DC mA and voltage input types
• Extremely high density mounting on Din rail
(6 mm width per module)
• Screw or tension clamp terminal options
• DIP switch-selectable inputs and/or outputs
• 2 port isolation for temperature transmitters
• 3 port isolation for DC isolators
• Cross-connectable supply voltage, to minimise wiring
D.60
DC/DC Select / Hi
A versatile DC isolator / convertor, with
• Selectable voltage and current I/O
• 2.5 kV isolation test voltage
• 3 port isolation
RPS / RPSH
A miniature 4…20 mA isolator with big-product features,
the RPS has…
• Full 300 V isolation rating
• 3 port isolation
• Transmitter power supply
• Optional form to pass HART communications as well
as the 4…20 mA signal
configurable
DC/DC select
• 3-way isolation
• Calibrated changeover via DIP switch
• Cross-connection of power supply
• Low power loss
Analogue signal conditioning
MICROSERIES - DC/DC 3-way isolator
D
Technical data
Input
Input voltage/Input current
Input resistance, voltage/Current
Voltage drop t IIN =20 mA (current input)
Input
0…10 V /0(4)…20 mA rent
Setting options/switch position
100 kΩ /≤ 5 Ω rent
< 0.1 V at IIN =20 mA (current input)
Output
0…10 V /0(4)…20 mA urrent
≥ 10 kΩ /≤ 500 Ω nt
< 0.5% of final value
≤ 150 ppm/K of final value
> 100 Hz requency (-3dB)
General data
24 V DC ± 15 %
approx. 0.6 W ion
≤ 20 A rrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
0…20mA / 0…20mA
CE / cURus
Insulation coordination
EN 50178
DIN EN 61326
50 V voltage
500 Veff / 1 s utput
II ge category
2 llution severity
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy f final value
Temperature coefficient value
Cut-off frequency (-3dB)
General data
Supply voltage n; 15 %
Power consumption
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting 20mA
Approvals s
Insulation coordination
Standards
EMC standards
Rated voltage
Isolation voltage input, output
Surge category
Pollution severity
Input
0
0
0
4
4
4
0
0
0
…
…
…
…
…
…
…
…
…
20
20
20
20
20
20
10
10
10
n
n
= on
= off
Output
mA
mA
mA
mA
mA
mA
V
V
V
0
4
0
0
4
0
0
4
0
… 20 mA
… 20 mA
… 10 V
… 20 mA
… 20 mA
… 10 V
… 20 mA
… 20 mA
… 10 V
Note
4
5
6
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
S2
PS
+
3
mA
IN
+
Screw connection
2.5 / 0.5 / 2.5
88 x 6.1 x 97.8
3
-
2
-
mm2
mm
2
Connection
V
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Switch
S1
1 2 1
4
PS
V/I
5
-
V/I
1
6
OUT
mA
V
+
Tension clamp connection
1.5 / 0.5 / 2.5
92 x 6.1 x 97.8
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
MAS DC/DC select
MAZ DC/DC select
Qty.
1
1
Order No.
8594810000
8594840000
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to MICROSERIES accessories
D.61
Analogue signal conditioning
MICROSERIES - DC/DC 3-way isolator
configurable
DC/DC select HI
• 3-way isolation 2.5kV
• Calibrated changeover via DIP switch
• Cross-connection of power supply
• Low power loss
D
Technical data
Input
Input voltage/Input current
Input resistance, voltage/Current
Voltage drop t IIN =20 mA (current input)
Input
0…10 V /0(4)…20 mA rent
Output
Output voltage/Output current
Load impedance, voltage/Current
Accuracy or current / < 0.3% for voltage of measured value
Temperature coefficient value
Cut-off frequency (-3dB)
General data
Supply voltage n; 15 %
Power consumption
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting 20mA
Approvals s
Insulation coordination
Standards
EMC standards
Rated voltage
Isolation voltage input, output
Surge category
Pollution severity
Setting options/switch position
100 kΩ /≤ 5 Ω rent
< 0.1 V at IIN =20 mA (current input)
Output
0…10 V /0(4)…20 mA urrent
≥ 10 kΩ /≤ 600 Ω nt
< 0.2% for current / < 0.3% for voltage of measured value
≤ 150 ppm/K of final value
> 100 Hz requency (-3dB)
General data
24 V DC ± 15 %
approx. 0.6 W ion
≤ 20 A rrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
0…20mA / 0…20mA
CE / cURus
Insulation coordination
EN 50178
DIN EN 61326
300 V voltage
2.5 kVeff ut, output
II ge category
2 llution severity
Input
0
0
0
4
4
4
0
0
0
…
…
…
…
…
…
…
…
…
20
20
20
20
20
20
10
10
10
n
n
= on
= off
Output
mA
mA
mA
mA
mA
mA
V
V
V
0
4
0
0
4
0
0
4
0
… 20 mA
… 20 mA
… 10 V
… 20 mA
… 20 mA
… 10 V
… 20 mA
… 20 mA
… 10 V
Note
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Type
MAS DC/DC select HI
Note
Accessories
Note
D.62
Cross-connectors for power supplies and
markers - refer to MICROSERIES accessories
Qty.
1
Order No.
8757530000
4
5
6
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
S2
PS
+
3
mA
IN
+
Screw connection
2.5 / 0.5 / 2.5
88 x 6.1 x 97.8
3
-
2
-
mm2
mm
2
Connection
V
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Switch
S1
1 2 1
4
PS
V/I
5
-
V/I
1
6
+
OUT
mA
V
without HART
MAS RPS
• 2-conductor system
• 3-port isolation
• Power supply can be cross-connected
3
0V
4
Analogue signal conditioning
MICROSERIES - Feed isolator
24 V DC
cc
cc
5
2
PS
V
Out
+
1 I
Current
Loop
I 6
D
+
Technical data
Input
Input current nsor circuit)
Sensor uctor
Supply voltage ant for 3…22 mA
Input
4…20 mA (sensor circuit)
2-conductor
16.5 V / constant for 3…22 mA
Output
4…20 mA rent
22…25 mA al limit
/≤ 500 Ω voltage/Current
< 0.1 %
≤ 2 ms esponse time
< 30 μA
≤ 50 ppm/K efficient
< 10 mVeff
General data
24 V DC ± 15 %
approx. 1 W ption
≤ 20 A rrying capacity of cross-connect.
0 °C…+55 °C perature
-25 °C…+85 °C ure
CE;cURus;
Insulation coordination
EN 50178 s
DIN EN 61326 class B
300 V voltage
1.5 kVeff put, output
II ge category
2 ollution severity
Output
Output current
Output signal limit
Load impedance, voltage/Current
Accuracy
Step response time
Offset current ;A
Temperature coefficient
Residual ripple eff
General data
Supply voltage n; 15 %
Power consumption
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals
Insulation coordination
Standards
EMC standards class B
Rated voltage
Isolation voltage input, output
Surge category
Pollution severity
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Screw connection
2.5 / 0.5 / 2.5
88 x 6.1 x 97.8
Note
Ordering data
Type of connection
Screw connection
Type
MAS RPS
Qty.
1
Order No.
8721150000
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to MICROSERIES accessories
D.63
Analogue signal conditioning
MICROSERIES - Feed isolator
with HART
MAS RPSH
• 2-conductor system
• 3-way isolation
• With Hart transmission
• Output signal switchable
3
24 V DC
0V
4
cc
cc
2
5
PS
V
Out
D
+
1 I
Current
Loop
I 6
+
Technical data
Input
Input current nsor circuit)
Sensor uctor
Supply voltage ant for 3…22 mA
Input
4…20 mA (sensor circuit)
2-conductor
16.5 V / constant for 3…22 mA
Output
0(4)…20 mA t
0…10 V oltage
22…25 mA resp. 11…12.5 V
≥ 10 kΩ /≤ 500 Ω nt
IOUT: < 0.1% / UOUT: < 0.2%
≤ 2 ms esponse time
< 30 μA
≤ 50 ppm/K efficient
< 10 mVeff
General data
24 V DC ± 15 %
approx. 1 W ption
to HART specification
≤ 20 A rrying capacity of cross-connect.
0 °C…+55 °C perature
-25 °C…+85 °C ure
CE;cURus;
Insulation coordination
EN 50178 (protective separation)
DIN EN 61326 class B
600 V voltage
2.5 kVeff put, output
II ge category
2 ollution severity
Output
Output current
Output voltage
Output signal limit …12.5 V
Load impedance, voltage/Current
Accuracy T: < 0.1% / UOUT: < 0.2%
Step response time
Offset current ;A
Temperature coefficient
Residual ripple eff
General data
Supply voltage n; 15 %
Power consumption
Communication fication
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Approvals
Insulation coordination
Standards (protective separation)
EMC standards class B
Rated voltage
Isolation voltage input, output
Surge category
Pollution severity
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Setting options/switch position
mm2
mm
Output
4 … 20 mA
0 … 20 mA
0 … 10 V
n
n
Screw connection
1.5 / 0.5 / 2.5
88 x 6.1 x 97.8
Note
Ordering data
Type of connection
Screw connection
Type
MAS RPSH
Note
Accessories
Note
D.64
Cross-connectors for power supplies and
markers - refer to MICROSERIES accessories
Qty.
1
Order No.
8721170000
= on
= off
1
Switch
2
3
4
n
n
n
n
n
n
n
n
n
n
n
n
PT100, 2-/3-conductor converter
PT100 Output select
• 2-way isolation between input/output and
power supply
• PT100 2-/3-conductor
• Output can be switched via DIP switch
Analogue signal conditioning
MICROSERIES - PT100/RTD signal isolator
D
Technical data
Input
Sensor 2-/3-conductor (to IEC 751)
Supply current
Temperature input range
Input
PT100/2-/3-conductor (to IEC 751)
0.8 mA current
0…100 °C input range
Output
0…10V / 0…5V /0(4)…20 mA
≥ 10 kΩ /≤ 300 Ω, ≤ 400 Ω @ 24 V
< 0.5% of measuring range
≤ 250 ppm/K of final value
< 0.7 s ponse time
General data
24 V DC ± 10 %
approx. 0.6 W ion
≤ 20 A rrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
0…20mA etting
CE / cURus / C1D2 / ATEX in preparation
Insulation coordination
EN 50178, EN 60751, IEC751
EN 55011, EN 61000-6 /-2, EN 61326
100 V voltage
1.5 kV withstand voltage
500 Veff / 1 s utput
III e category
2 llution severity
≥ 1.5 mm & creepage distance
Output
Output voltage/Output current A
Load impedance, voltage/Current , ≤ 400 Ω @ 24 V
Accuracy f measuring range
Temperature coefficient value
Step response time
General data
Supply voltage n; 10 %
Power consumption
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting
Approvals s / C1D2ATEX in preparation
Insulation coordination
Standards EN 60751, IEC751
EMC standards 61000-6 /-2, EN 61326
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
Setting options/switch position
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
88 x 6.1 x 97.8
Output
0 … 10 V
1
0 … 20 mA
4 … 20 mA
0…5V
n
n
Switch
2
3
4
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
= on
= off
Connection
PS
+
3
ϑ
Pt100
2
1
-
4
ϑ
V/I
-
5
6
OUT
mA
V
+
Tension clamp connection
1.5 / 0.5 / 2.5
92 x 6.1 x 97.8
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
MAS PT100 0…100C
MAZ PT100 0…100C
Qty.
1
1
Order No.
8594820000
8594850000
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to MICROSERIES accessories
D.65
Analogue signal conditioning
MICROSERIES - Thermocouple signal isolator/converter
Thermal isolator/converter type K
Thermo K Output Select
• 2-way isolation between input/output and
power supply
• Cold-junction compensation
• Linearisation
• Output can be switched via DIP switch
D
Technical data
Input
Sensor element to IEC 584, type: K
Temperature input range
Input
Thermocouple to IEC 584, type: K
0…1000 °C input range
Output
Output voltage/Output current A
Load impedance, voltage/Current , ≤ 400 Ω @ 24 V
Accuracy f measuring range
Temperature coefficient value
Step response time
Wire break detection 0 mA, > 10 V
Residual ripple eff
General data
Supply voltage n; 10 %
Power consumption
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting
Approvals s / C1D2ATEX in preparation
Insulation coordination
Standards EN 60584, IEC 584
EMC standards 61000-6 /-2, EN 61326
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Output
0…10V / 0…5V /0(4)…20 mA
≥ 10 kΩ /≤ 300 Ω, ≤ 400 Ω @ 24 V
< 0.6% of measuring range
≤ 250 ppm/K of final value
< 0.7 s ponse time
output value: > 20 mA, > 10 V
< 20 mVeff
General data
24 V DC ± 10 %
approx. 0.6 W ion
≤ 20 A rrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
0…20mA etting
CE / cURus / C1D2 / ATEX in preparation
Insulation coordination
EN 50178, EN 60584, IEC 584
EN 55011, EN 61000-6 /-2, EN 61326
100 V voltage
1.5 kV withstand voltage
500 Veff / 1 s utput
III e category
2 llution severity
≥ 1.5 mm & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
88 x 6.1 x 97.8
Setting options/switch position
Note
Accessories
Note
D.66
Cross-connectors for power supplies and
markers - refer to MICROSERIES accessories
n
n
n
n
4
n
n
n
n
n
n
mA
V
PS
-
+
3
IN
+
Tension clamp connection
1.5 / 0.5 / 2.5
92 x 6.1 x 97.8
Type
Qty.
MAS Thermo-K 0…1000°C Output select1
MAZ Thermo-K 0…1000°C Output select1
4 … 20 mA
0…5V
Switch
2
3
n
n
n
n
Connection
Ordering data
Screw connection
Tension clamp connection
1
n
n
n = on
n = off
Tu=23°C, single module
Type of connection
Output
0 … 10 V
0 … 20 mA
Order No.
8594830000
8594860000
2
1
4
ϑ
V/I
-
5
6
+
OUT
Thermal isolator/converter type J
Thermo J Output Select
• 2-way isolation between input/output and
power supply
• Cold-junction compensation
• Linearisation
• Output can be switched via DIP switch
Analogue signal conditioning
MICROSERIES - Thermocouple signal isolator/converter
D
Technical data
Input
Sensor element to IEC 584, type: J
Temperature input range
Input
Thermocouple to IEC 584, type: J
0…700 °C input range
Output
Output voltage/Output current A
Load impedance, voltage/Current , ≤ 400 Ω @ 24 V
Accuracy f measuring range
Temperature coefficient value
Step response time
Wire break detection 0 mA, > 10 V
Residual ripple eff
General data
Supply voltage n; 10 %
Power consumption
Current-carrying capacity of cross-connect.
Operating temperature
Storage temperature
Default setting
Approvals s / C1D2ATEX in preparation
Insulation coordination
Standards EN 60584, IEC 584
EMC standards 61000-6 /-2, EN 61326
Rated voltage
Impulse withstand voltage
Isolation voltage input, output
Surge category
Pollution severity
Clearance & creepage distance
Output
0…10V / 0…5V /0(4)…20 mA
≥ 10 kΩ /≤ 300 Ω, ≤ 400 Ω @ 24 V
< 0.7% of measuring range
≤ 250 ppm/K of final value
< 0.7 s ponse time
output value: > 20 mA, > 10 V
< 20 mVeff
General data
24 V DC ± 10 %
approx. 0.6 W ion
≤ 20 A rrying capacity of cross-connect.
0 °C…+55 °C erature
-20 °C…+85 °C ure
0…20mA etting
CE / cURus / C1D2 / ATEX in preparation
Insulation coordination
EN 50178, EN 60584, IEC 584
EN 55011, EN 61000-6 /-2, EN 61326
100 V voltage
1.5 kV withstand voltage
500 Veff / 1 s utput
III e category
2 llution severity
≥ 1.5 mm & creepage distance
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Note
Screw connection
2.5 / 0.5 / 2.5
88 x 6.1 x 97.8
Setting options/switch position
Output
0 … 10 V
0 … 20 mA
1
n
n
4 … 20 mA
0…5V
n
n
Switch
2
3
n
n
n
n
n
n
4
n
n
n
n
n
n
mA
V
n = on
n = off
Connection
PS
-
+
3
IN
+
2
1
4
ϑ
V/I
-
5
6
OUT
+
Tension clamp connection
1.5 / 0.5 / 2.5
92 x 6.1 x 97.8
Tu=23°C, single module
Ordering data
Type of connection
Screw connection
Tension clamp connection
Type
Qty.
MAS Thermo-J 0…700°C Output select 1
MAZ Thermo-J 0…700°C Output select 1
Order No.
8615210000
8615240000
Note
Accessories
Note
Cross-connectors for power supplies and
markers - refer to MICROSERIES accessories
D.67
Analogue signal conditioning
MICROSERIES – Accessories
MICROanalog
Screw connection
Tension clamp connection
88
90
97.8
90
97.8
6.1
6.1
D
92
Ordering data
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
2-poles, red
3-poles, red
4-poles, red
10-poles, red
41-poles, red
Type
ZQV 4N
ZQV 4N
ZQV 4N
ZQV 4N
ZQV 4N
/
/
/
/
/
2 rt
3 rt
4 rt
10 rt
41 rt
Qty
60
60
60
20
10
Order No.
1793950000
1793980000
1794010000
1794040000
1794070000
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
Cross-connection,
2-poles, blue
3-poles, blue
4-poles, blue
10-poles, blue
41-poles, blue
ZQV
ZQV
ZQV
ZQV
ZQV
/
/
/
/
/
2 bl
3 bl
4 bl
10 bl
41 bl
60
60
60
20
10
1793960000
1793990000
1794020000
1794050000
1794080000
Qty
200
Order No.
1060960000
4N
4N
4N
4N
4N
Ordering data
Marker
D.68
Type
WS10/6
D
D.69
Analogue signal conditioning
Analogue signal conditioning
RS-SERIES - AD/DA converter
AD converter, 8-bit
RS I-D8 4…20 mA
RS I-D8 0…20 mA
• Hold function for storing the current bit
combination
• More information and table for input/output
characteristics of A/D, D/A converters available
at www.weidmueller.de => downloads
Ie
Ie
24V +
A
24V +
A
D
D
D
0V
0V
1-8
0V
0V
HE
1-8
HE
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Output
Number of outputs )
Output level V = L
Signs
Output current source)
Accuracy 1 LSB
Cut-off frequency (-3dB) us)
Conversion time
General data
Supply voltage n; 20 %
Current consumption current)
Operating temperature
Storage temperature
Approvals
Insulation coordination
Standards
EMC standards
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Input
/0…20 mA ge/Input current
Input
/4…20 mA ge/Input current
3.5 V /25 mA max. current
50 kΩ per input / ge/Current
Output
8 Bit (1-bit sign)
17 V = H, 0 V = L
Signs
≤ 25 mA (as source)
± 1 LSB
5 kHz at full scale (sinus)
≤ 4 μs time
General data
24 V DC ± 20 %
35 mA (plus output current)
0 °C…+50 °C erature
-40 °C…+80 °C ure
CE; ovals
Insulation coordination
EN 50178
EN 61000-6 rds
3.5 V /25 mA max. current
/≥ 51 Ω voltage/Current
Output
8 Bit (1-bit sign)
17 V = H, 0 V = L
Signs
≤ 25 mA (as source)
± 1 LSB
5 kHz at full scale (sinus)
≤ 4 μs time
General data
24 V DC ± 20 %
35 mA (plus output current)
0 °C…+50 °C erature
-40 °C…+80 °C ure
CE; ovals
Insulation coordination
EN 50178
EN 61000-6 rds
Screw connection
4 / 0.5 / 4
70 x 35 x 72
Screw connection
4 / 0.5 / 4
70 x 35 x 72
Note
Ordering data
Type of connection
Screw connection
Note
Accessories
Note
D.70
Type
RS I-D8 0…20MA
Qty.
1
Order No.
1160561001
Type
RS I-D8 4…20MA
Qty.
1
Order No.
1168561001
AD converter, 8-bit
RS U-D8 0…10 V
RS U-D8 +/-10 V
• Hold function for storing the current bit
combination
• More information and table for input/output
characteristics of A/D, D/A converters available
at www.weidmueller.de => downloads
Ue
A
24V +
Ue
0V
0V
D
0V
1-8
24V +
A
D
0V
1-8
HE
D
HE
Technical data
Input
Input voltage/Input current
max. voltage/max. current
Input resistance, voltage/Current
Output
Number of outputs )
Output level V = L
Signs H = positive; L = negative
Output current source)
Accuracy 1 LSB
Cut-off frequency (-3dB) us)
Conversion time
General data
Supply voltage n; 20 %
Current consumption current)
Operating temperature
Storage temperature
Approvals
Insulation coordination
Standards
EMC standards
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Input
-10…+10 V / /Input current
Input
0…10 V / age/Input current
/≤ 55 μA /max. current
≥ 200 kΩ / oltage/Current
Output
8 Bit (1-bit sign)
17 V = H, 0 V = L
MSB: H = positive; L = negative
≤ 25 mA (as source)
± 1 LSB
5 kHz at full scale (sinus)
≤ 4 μs time
General data
24 V DC ± 20 %
35 mA (plus output current)
0 °C…+50 °C erature
-40 °C…+80 °C ure
CE; ovals
Insulation coordination
EN 50178
EN 61000-6 rds
/≤ 25 μA /max. current
≥ 400 kΩ / oltage/Current
Output
8 Bit (1-bit sign)
17 V = H, 0 V = L
MSB: H = positive; L = negative
≤ 25 mA (as source)
± 1 LSB
5 kHz at full scale (sinus)
≤ 4 μs time
General data
24 V DC ± 20 %
35 mA (plus output current)
0 °C…+50 °C erature
-40 °C…+80 °C ure
CE; ovals
Insulation coordination
EN 50178
EN 61000-6 rds
Screw connection
4 / 0.5 / 4
70 x 35 x 72
Screw connection
4 / 0.5 / 4
70 x 35 x 72
Note
Ordering data
Type of connection
Screw connection
Type
RS U-D8 +-10V
Analogue signal conditioning
RS-SERIES - AD/DA converter
Qty.
1
Order No.
1122361001
Type
RS U-D8 0…10V
Qty.
1
Order No.
1160361001
Note
Accessories
Note
D.71
Analogue signal conditioning
RS-SERIES - AD/DA converter
DA converter 8-bit
RS D8-I 4…20 mA
RS D8-I 0…20 mA
• Hold function for storing the current bit
combination
• More information and table for input/output
characteristics of A/D, D/A converters available
at www.weidmueller.de => downloads
1 - 8 H=0 V
1 - 8 H=0 V
Ia
+ 24V
D
A
- 0V
D
0V
Technical data
Input
Input/Output ogue
max. voltage
max. current
Input voltage/Input current
Input resistance, voltage/Current
Signs
Output
Output voltage/Output current
Offset current/Offset voltage
Load impedance, voltage/Current
Accuracy 1 LSB
Conversion time
General data
Supply voltage n; 20 %
Current consumption current)
Operating temperature
Storage temperature
Approvals
Insulation coordination
Standards
EMC standards
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Input
8 Bit / Analogue
Input
8 Bit / Analogue
max. 30 V ge
max. current
5…24 V / age/Input current
50 kΩ per input / ge/Current
Signs
Output
/0…20 mA (as source) urrent
max. 0.08 mA / /Offset voltage
≤ 500 Ω / voltage/Current
± 1 LSB
≤ 30 μs time
General data
24 V DC ± 20 %
25 mA (plus output current)
0 °C…+50 °C erature
-40 °C…+80 °C ure
CE rovals
Insulation coordination
EN 50178
EN 61000-6 rds
max. 30 V ge
max. current
5…24 V / age/Input current
50 kΩ per input / ge/Current
Signs
Output
/4…20 mA (as source) urrent
4 mA / current/Offset voltage
≤ 500 Ω / voltage/Current
± 1 LSB
≤ 30 μs time
General data
24 V DC ± 20 %
25 mA (plus output current)
0 °C…+50 °C erature
-40 °C…+80 °C ure
CE rovals
Insulation coordination
EN 50178
EN 61000-6 rds
Screw connection
4 / 0.5 / 4
70 x 35 x 72
Screw connection
4 / 0.5 / 4
70 x 35 x 72
Note
Ordering data
Type of connection
Screw connection
Note
Accessories
Note
D.72
Type
RS D8-I 0…20MA
Qty.
1
Order No.
1165861001
Type
RS D8-I 4…20MA
Qty.
1
Order No.
1169261001
DA converter 8-bit
RS D8-U 0…10 V
RS D8-U +/-10 V
• Hold function for storing the current bit
combination
• More information and table for input/output
characteristics of A/D, D/A converters available
at www.weidmueller.de => downloads
1 - 8 H=0 V
+ 24V
- 0V
1 - 8 H=0 V
Ua
D
A
+ 24V
- 0V
0V
Ua
D
A
0V
D
Technical data
Input
Input/Output ogue
max. voltage
max. current
Input voltage/Input current
Input resistance, voltage/Current
Signs H = positive; L = negative
Output
Output voltage/Output current current
Offset current/Offset voltage
Load impedance, voltage/Current
Accuracy 1 LSB
Conversion time
General data
Supply voltage n; 20 %
Current consumption current)
Operating temperature
Storage temperature
Approvals
Insulation coordination
Standards
EMC standards
Dimensions
Clamping range (rating- / min. / max.)
Length x width x height
mm2
mm
Input
8 Bit / Analogue
Input
8 Bit / Analogue
max. 30 V ge
2.5 mA rrent
5…24 V / age/Input current
50 kΩ per input / ge/Current
MSB: H = positive; L = negative
Output
-10…+10 V /≤ 10 mA max. current
/≤ 20 mV nt/Offset voltage
≥ 1 kΩ / , voltage/Current
± 1 LSB
≤ 30 μs time
General data
24 V DC ± 20 %
25 mA (plus output current)
0 °C…+50 °C erature
-40 °C…+80 °C ure
CE rovals
Insulation coordination
EN 50178
EN 61000-6 rds
max. 30 V ge
2.5 mA rrent
5…24 V / age/Input current
50 kΩ per input / ge/Current
MSB: H = positive; L = negative
Output
0…10 V /≤ 10 mA max. current nt
/≤ 20 mV nt/Offset voltage
≥ 1 kΩ / , voltage/Current
± 1 LSB
≤ 30 μs time
General data
24 V DC ± 20 %
25 mA (plus output current)
0 °C…+50 °C erature
-40 °C…+80 °C ure
CE rovals
Insulation coordination
EN 50178
EN 61000-6 rds
Screw connection
4 / 0.5 / 4
70 x 35 x 72
Screw connection
4 / 0.5 / 4
70 x 35 x 72
Note
Ordering data
Type of connection
Screw connection
Type
RS D8-U +-10V
Qty.
1
Analogue signal conditioning
RS-SERIES - AD/DA converter
Order No.
1123361001
Type
RS D8-U 0…10V
Qty.
1
Order No.
1160761001
Note
Accessories
Note
D.73
Analogue signal conditioning
MANN SERIES
MANN SERIES Process Instruments
With its MANN SERIES, Weidmüller introduces a comprehensive range of innovative products for the processing of analogue signals. The product series, ranging from simple dedicated units to complex microprocessor-controlled devices, can be
used with almost all signal types and measurement sensors.
The products also offer a variety of integrated functions, such
as timing delays, adjustable threshold values and a programmable ramping function.
D
Included in the MANN SERIES are:
Signal isolators – these products are for typical facility-based
analogue current and voltage signals. They eliminate the measurement errors caused by ground loops or electromagnetic
interference. They can also be used to boost weaker signals
resulting in increased transmission distance or to allow additional devices to be connected to loop calibrators. The signal
isolator is powered from the input/output current loop, or from
a separate auxiliary power supply.
Signal isolators
Signal transmitters – these products convert, filter and isolate any low-level signals coming from typical measuring
devices. This includes mV signals from thermocouples and
PT100 measurement probes, which are converted into normalized current or voltage signals. This range of products includes
not only simple and conventional modular versions, but also
highly-flexible microprocessor-controlled versions.
Signal transmitters
Process alarms – these are special two-channel modules
which monitor facility-specific measurement values. When necessary, they issue alarms to external monitoring systems.
Versions are available for all standard input signals. The setpoint values can be set with an operating panel located on the
front. Microprocessor-controlled modules are available for more
complex applications. They are equipped with standard timing
delays, filter functions, setpoint adjustments and displays.
Process alarms
D.74
TWI 1 / TWI 2
SFI / DFI
WAVEPak DC/DC
ITXPlus
STG
Micromann AR
Micromann UPI
DPA
Micromann R
Multi-channel processing
modules
Micromann Multiplus
Indicators and
configurable displays
PMX420
PMX400
DI350
LPD350
LPD450F
AMS400A
Counters / Totalisers
PTX800
Calibration devices
(hand-held)
Portacal 275
Portacal 1000
Multi-channel processing modules – these are compact
modules which are capable of processing multiple inputs,
outputs and alarms simultaneously. When necessary, they can
transmit analogue or digital values, based on certain results, to
a control system. They are suitable for the remote monitoring
of processes. With their use, cycle times can be shortened within the application and the number or I/O devices can be reduced. This will also lead to a reduction in the costs surrounding
installation, cabling, initial commissioning and maintenance.
Indicators and configurable displays – these are available
in a variety of designs. This includes products ranging from
simple versions powered by current loops, to configurable products with integrated analogue and alarm outputs.
Counters / Totalisers – these products can be used for
measuring flow rate and total. They can process analogue
and digital inputs signals (pulses). There are a wide variety of
adjustment and programming options, such as linearization,
interference suppression, hysteresis and reference values. This
enables these products to be used in a wide variety of applications. On the output side, relay contacts for monitoring limiting
values are available.
Calibration devices – these complete the product offering.
They are specially designed for the calibrating and setting of
analogue signal-processing devices. They provide clean
smoothed standard signals and make use of a load indicator
for quick loop diagnostics.
D.75
Analogue signal conditioning
MANN SERIES
D
Analogue signal conditioning
MANN SERIES
MANN SERIES
MANN SERIES is complementary to Weidmüller’s WAVESERIES, and is a range of signal conditioning products targeted
at the process industries. A greater number of settable options,
adjustable through the module front, make most of the DIN
rail modules wider than WAVESERIES. Extruded aluminium
housings give the MANN SERIES a robust and secure feel for
heavy industry users.
D
Secure data
Despite high levels of adjustability, stored data is secured in the
modules through either password, or cable-link security.
Portable loop calibrators
The MANN SERIES Portacal products offer instrumentation
users a choice of robust hand-held calibrators for routine loop
checking – to make transmitter or valve checking easy.
• Portacal 275
a simple, accurate signal source for DC V and mA, compact
and light and with test points to monitor outputs
• Portacal 1000
measures, simulates voltage and current signals and can step
and ramp through a sequence of calibration points
Highly adjustable
Micromann rail mounted transmitters have:
• High accuracy and stability
• Both analogue and relay outputs
• Front-adjustable parameters for live configuration of input
and output types and ranges, display range, alarm settings
via membrane pushbuttons
• Simple, step-through menu systems, making parameter
setting and saving easy
Micromann UTCAR
D.76
Portacal 1000
Portacal 275
Front panel mounting options
From simple, calibratable digital LCD or LED displays, through
to powerful configurable indicating conditioners and monitors,
Mann Series front panel instruments display the process value.
• LPD350
loop powered (4…20 mA) LCD 3.5 digit display
• DI 350
DC V/mA input, LED 3.5 digit display
Other features of MANN SERIES
• Universal isolators – with adjustable voltage/current I/O
• User-settable characterizing / linearising outputs
• Optional power provided for input transmitters
• Multi-channel monitors with serial communications
(RS485 / Modbus)
• 8 digit indicating Flow Monitor with analogue or pulse
input options
• Auto-Manual station with integral analogue or pulse control
• Software configuration applications
• LPD450F
loop powered (4…20 mA) 4.5 digit field mounted display
DI350
Universal transmitter
The ITXPlus transmitter is unique – it is a single product
which can accept most analogue sensor types (temperature
and DC) and provides an isolated output-loop-powered
4…20 mA signal.
ITXPlus
• Computer-configurable via the CBX100 interface
• High performance measurements
(accuracy, temperature effects)
• PT100, thermocouple, mV, mA, voltage, resistance,
potentiometer-inputs (one unit!)
• Wide ambient temperature range (–10…70°C)
• Preset or user-definable linearization
• 12,5 mm wide rail mounted housing
D.77
Analogue signal conditioning
MANN SERIES
D
Analogue signal conditioning
MANN SERIES
Applications in a process plant I
� INCOMING / OUTGOING DELIVERIES
Product: Transmitter types WAVE PRO Bridge
or MANN SERIES STG
Load cells beneath a “weigh bridge” create a small mV
measurement, which is isolated and amplified into a linear DC
output (e.g. 4…20 mA) for display and recording.
Weigh bridge
D
Output
Load cell
Summator
Strain gauge bridge transmitter
� RAW MATERIALS BULK STORAGE
Product: Transmitter ITXPlus
Level measurements often need conversion to volume, for the
tank contents display for the filling operator. ITXPlus has userdefinable linearization to suit any tank shape.
Tank
Transmit
and
linearise
Product: Field mounted display LPD450F
Where a weatherproof loop powered display is needed for
visualisation.
Volumen
Display
� MIXING / BLENDING LIQUIDS
Liquid B
Liquid A
Flowmetr
Reset
Input
Totaliser
Frequ./Anal.
converter
D.78
Mixing vessel
Outlet
Product: Totalizer / Counter MANN PTX800
Batch control may involve close control of liquid volumes to
be metered and mixed. PTX 800 can accept pulse or analogue
inputs from flowmeters.
Product: Frequency transmitter WAVE PRO Frequency or
MANN UHZAR
Mixing quality may depend on controlling the mixer speed as
the level varies. Shaft speed can be converted to an isolated
analogue output, to be the input to the speed controller.
Analogue signal conditioning
MANN SERIES
� HEAT EXCHANGER CONTROL
4...20 mA
Outlet
RTD
Sensor
Transmitter
Product: Temperature transmitter WAVE PRO RTD or ITXPlus
Typically an RTD probe senses the product temperature.
The transmitter amplifies and isolates the sensor input into a
linear DC output (e.g. 4…20 mA), to be the input to the heating
element controller.
Inlet
D
Heat exchanger
� FINAL PRODUCT STORAGE
Pump
Storage Tank
Product: Current convertor WAVE Control WAS1 CMA LP
Pump monitoring may be done by measuring the AC current
consumed by the pump motor, with a current transformer (CT).
The CT output, typically 0…5 A can be isolated and converted
to DC (e.g. 4…20 mA), to be the input for the control system.
0...100 A
0...5 A
CT
4...20 mA
AC current
D.79
Analogue signal conditioning
MANN SERIES
Applications in a process plant II
� DEDICATED DISPLAYS
Product: Loop splitterWAS5 CCC OLP or MANN DFI
Some parameters are important enough to be separately
displayed apart from the control system. Incoming DC signals
can be split and isolated to maintain the integrity of each
function.
D
Input
Loop splitter
Product: MANN DI350 or MANN LPD 350
Simple display of process parameters can include scaling in
engineering units, and either auxiliary or loop power options.
Output 1
Output 2
Display
� NON-ISOLATED INPUTS
Product: Isolator WAVEPak DC/DC or MAS DC/DC Select
Control systems with non-isolated analogue input cards often
need separate external isolators. The external isolator can also
convert the incoming signal if needed, and provide power for
the signal source.
D.80
Input
Isolator
Output
Analogue signal conditioning
MANN SERIES
� AUTO-MANUAL SWITCHING
Product: MANN AMS 400A
Controlling systems manually is sometimes needed – e.g.
during process start-ups – and to switch smoothly between
auto control and manual is important. The auto-manual switch
is located between the control system output and the control
device actuator, and may need to handle either analogue or
digital input or output signals.
to actuator
Auto control signal
PLC / DCS
� NON-STANDARD INPUTS
Convertor
4...20 mA
0...20 mV
Product: Convertor / isolator WAVE PRO DC/DC
Control systems analogue input ranges are usually limited –
often to just 4…20 mA. A flexible convertor / isolator to cover
DC inputs spans from 20 mV to 200 V is a valuable tool.
D.81
D
Analogue signal conditioning
MANN SERIES – Signal isolators
TWI Series
Signal isolators and splitters, with loop-powered
(two-wire) design, for 4...20 mA current loops
Loop-powered output isolators in the TWI Series are used for
the electrical isolation of current loops between 4...20 mA. They
reduce measurement errors which can be caused by differences in ground potentials. They are either in one- or two-channel
design, and can be used in a variety of applications:
TWI-2 as signal splitter, can be optionally used as a
two-way isolator
Power
supply
+
4 ... 20 mA
Temperature
transmitter
Signal isolators – to eliminate measurement errors caused by
ground loops, electrical interference and motor noise.
Signal splitters – to produce two independent 4...20 mA
outputs from one input signal. The TWI-2 is specified for this
application. Both 4...20 mA current loops are connected serially
on the input side. The isolated output current loops can then be
transmitted independently to an external control system or data
logging device.
Signal amplifiers – to boost signals for increased transmission
distance or allow additional devices to be connected to the
loop.
The electronics is housed in a rugged powder-coated aluminium
housing which clips onto a DIN TS35/TS32 mounting rail. The
pluggable screw connection is located on the front.
Technical features:
•
•
•
•
•
•
Loop-powered output isolator
Single and dual channel versions
Electrical isolation
Long-term consistency, high precision
High common-mode rejection ratio
Independent per-channel adjustment possible for zero point
(earthed neutral) and signal range
• 600 Ω apparent resistance at output, at 24 V DC
• No internal adjustments needed
D.82
Local
display
Input
circuit
4...20 mA
4 ... 20 mA
D
Power
supply
+
Circuit 1
TWI-2 / 4 ... 20 mA
Circuit 2
+
Power
supply
Decentralized
PLC
TWI Series
TWI-1
Signal isolator in 2-wire design
1-channel current output
• Supply via 4…20 mA output loops
(Output loop-powered)
• Pluggable connection terminals
Analogue signal conditioning
MANN SERIES - Signal isolators
• Compact enclosure
• Current or voltage input
• Precision is ± 0.1 % of the signal range
• Front calibration
H
1 + Iin/Vin
2 nc
3 0V
V/I
I
+24 V
nc
Iout
4
5
6
D
L
Connections
Technical data
Input
Input signal 0…10 V (optional)
Input resistance ent input) or 1 MΩ (voltage input)
Input
4…20 mA or 0…10 V (optional)
22 Ω (current input) or 1 MΩ (voltage input)
Output
Output current p-powered
Residual ripple ss
Load resistance, max. mega; (Typically 600 Ω @ 24 V DC)
Settings
Fine calibration 2 turns
Signal amplifier the signal range
Offset n; 25 % of the signal range
General data
Voltage supply loop-current powered
Influence on the voltage supply
Linearity 0.1 % of signal range
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift 0 h
Step response time
Impulse withstand voltage
Rated voltage
Insulation voltage t
Operating temperature/Storage temperature
EMC standards
Approvals
Output
4…20 mA, loop-powered
≤ 10 mVss
[(Vs - 12) / 0.02] Ω (Typically 600 Ω @ 24 V DC)
Settings
Potentiometer, 22 turns
± 25 % of the signal range
± 25 % of the signal range
General data
12…45 V DC - loop-current powered
< 0.05 % of signal range / 10 V
± 0.1 % of signal range
± 0.02 % of signal range
0 to 95 % (no condensation)
± 0,05 % / °C ent
< 0.1 % / 10,000 h
200 ms (10 - 90 %)
4 kV (1.2/50 µs) d voltage
300 Veff
2 kV input / output
-10 °C…+60 °C/-25°C…+70°C temperature
DIN EN 61326 s
CE; cULus provals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 205 g
120 x 20 x 96
mm2
mm
Note
Terminal
1
2
3
4
5
6
Housing
Signal
Signal +
Not used
Input
Signal –
Signal +
Not used
Output
Signal –
PE connection direct on housing
PE connection direct on enclosure
Ordering data
Type
Voltage input
Current input
Note
Type
TWI-1 0-10V
TWI-1 4-20mA
Qty.
1
1
Order No.
7940011660
7940010159
Additional input and output versions available on request
Accessories
Note
D.83
Analogue signal conditioning
MANN SERIES - Signal isolators
TWI Series
TWI-2
Signal isolator in 2-wire design
2-channel current output
• Supply via 4…20 mA output loops
(Output loop-powered)
• Pluggable connection terminals
• Compact enclosure
• Current or voltage input
• Precision is ± 0.1 % of the signal range
• Front calibration
H
1 + Iin/Vin
2
V/I
0V
I
3 + Iin/Vin
D
4
V/I
0V
I
+24 V
5
Iout
6
+24 V
7
Iout
8
L
Connections
Technical data
Input
Input signal 0…10 V (optional)
Input resistance ent input) or 1 MΩ (voltage input)
Input
4…20 mA or 0…10 V (optional)
22 Ω (current input) or 1 MΩ (voltage input)
Output
Output current p-powered
Residual ripple ss
Load resistance, max. mega; (Typically 600 Ω @ 24 V DC)
Settings
Fine calibration 2 turns
Signal amplifier the signal range
Offset n; 25 % of the signal range
General data
Voltage supply loop-current powered
Influence on the voltage supply
Linearity 0.1 % of signal range
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift 0 h
Step response time
Impulse withstand voltage
Rated voltage
Insulation voltage uts
Operating temperature/Storage temperature
EMC standards
Approvals
Output
4…20 mA, loop-powered
≤ 10 mVss
[(Vs - 12) / 0.02] Ω (Typically 600 Ω @ 24 V DC)
Settings
Potentiometer, 22 turns
± 25 % of the signal range
± 25 % of the signal range
General data
12…45 V DC - loop-current powered
< 0.05 % of signal range / 10 V
± 0.1 % of signal range
± 0.02 % of signal range
0 to 95 % (no condensation)
± 0,05 % / °C ent
< 0.1 % / 10,000 h
200 ms (10 - 90 %)
4 kV (1.2/50 µs) d voltage
300 Veff
2 kV inputs / outputs
-10 °C…+60 °C/-25°C…+70°C temperature
DIN EN 61326 s
CE; cULus provals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 238 g
120 x 20 x 96
mm2
mm
Note
Terminal
1
2
3
4
5
6
7
8
Housing
PE connection direct on enclosure
Ordering data
Type
Voltage input
Current input
Special adjustment
Note
Accessories
Note
D.84
Type
TWI-2 0-10V
TWI-2 4-20mA
TWI Variabel
Qty.
1
1
1
Additional input and output versions available on request
Order No.
7940012011
7940010171
8945080000
Signal
Signal +
Input channel 1
Signal –
Signal +
Input channel 2
Signal –
Signal +
Output channel 1
Signal –
Signal +
Output channel 2
Signal –
PE connection direct on housing
D
D.85
Analogue signal conditioning
Analogue signal conditioning
MANN SERIES – Signal isolators
SFI / DFI
Single and dual channel isolators with auxiliary power
supply
DFI as signal splitter / optional as 2-wire-isolator
DFI / 4 ... 20 mA
The SFI is a single-channel, auxiliary-powered isolator for current and voltage signals. The DFI combines two signal isolators
in one housing. They can be used separately or as a signal
splitter.
D
4 ... 20 mA
Leveltransmitter
Decentralized
PLC
4 ... 20 mA
power loop
4 ... 20 mA
The SFI / DFI standard module features a 24 V DC sensor
power supply for each channel. This allows a direct power
supply to passive two-wire sensors. The inputs, outputs and
power supply are isolated from each other..
Measuring
instrument
ext. power supply
Technical features:
•
•
•
•
•
•
Isolator with auxiliary power supply
Single and dual channel versions
Highly accurate (±0.1% of the signal range)
Complete electrical isolation to 1.5 kV
Provides power for active input devices
Independent per-channel adjustment possible for zero point
(earthed neutral) and signal range
• Bipolar inputs
• No internal adjustments needed
SFI wiring
0V
+24 V
10
9
1
2
3
4
+24 V
Iin
0V
Vin
1
2
3
4
5
6
7
8
+24 V
Iin
0V
Vin
I
PS
V/I
12
V
13
V/I
DFI wiring
0V
+24 V
10
9
+24 V
Iin
0V
Vin
I
PS
V/I
D.86
13
V/I
I
V/I
15
V
V/I
Connections
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Housing
12
V
Signal
24 VDC powered
Signal + current input
Input channel 1
Signal – 0 V
Signal + voltage input
24 VDC powered
Signal + current input
Input channel 2
Signal – 0 V
(only DFI)
Signal + voltage input
–
Supply voltage
+
High level
Not used
Signal + output
Output channel 1
Signal - output
Not used
Output channel 2
Signal + output
(only DFI)
Signal - output
PE connection direct on housing
16
SFI / DFI
SFI
DFI
SFI - 1-channel signal isolator
1-channel current output
2-channel current output
• Current or voltage input
• Current or voltage input
• Precision is ± 0.1 % of the signal range
• Precision is ± 0.1 % of the signal range
• Front calibration
• Front calibration
DFI - 2-channel signal isolator / splitter
• External power supply
• Supply of 12 - 50 V DC
Analogue signal conditioning
MANN SERIES - Signal isolators
• Bi-polar inputs
• LED status indicator
• Pluggable connection terminals
• Compact enclosure
H
D
L
Technical data
Input
Input signal …20 mA, 0…10 V or -10…10 V(adjustable)
Input resistance ent input); or 1 MΩ (voltage input)
Sensor supply o 25 mA) per channel
Output
Output signal ..10 V (additional upon request)
Smallest received measuring span
Settings
Fine calibration 0 turns
Signal amplifier the signal range
Offset n; 25 % of the signal range
General data
Voltage supply
Power consumption l load; 3.6 W with no load
Repeat accuracy of signal range
Linearity ; 0,1 % des Signalbereiches>
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Step response time
Impulse withstand voltage
Rated voltage
Insulation voltage uts / power supply
Operating temperature/Storage temperature
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Note
Input
4…20 mA, 0…20 mA, 0…10 V or -10…10 V(adjustable)
Input
4…20 mA, 0…20 mA, 0…10 V or -10…10 V(adjustable)
22 Ω (current input); or 1 MΩ (voltage input)
24 V DC (up to 25 mA) per channel
Output
4…20 mA, 0…10 V (additional upon request)
0…1.5 kΩ output load
Settings
Potentiometer, 20 turns
± 25 % of the signal range
± 25 % of the signal range
General data
12…50 V DC ly
4.5 W with nominal load; 3.6 W with no load
± 0.05 % of signal range
< ± 0,1 % of signal range
0 to 95 % (no condensation)
< 0,05 % °Coefficient
0.1 % / 10,000 h
280 ms (10…90 %)
4 kV (1.2/50 µs) d voltage
300 Veff
2 kV input / output / power supply ly
0 °C…+60 °C/-25°C…+70°C ge temperature
CE; cULusrovals
22 Ω (current input); or 1 MΩ (voltage input)
24 V DC (up to 25 mA) per channel
Output
4…20 mA, 0…10 V (additional upon request)
0…1.5 kΩ output load
Settings
Potentiometer, 20 turns
± 25 % of the signal range
± 25 % of the signal range
General data
12…50 V DC ly
4.5 W with nominal load; 3.6 W with no load
± 0.05 % of signal range
< ± 0,1 % of signal range
0 to 95 % (no condensation)
< 0,05 % °C coefficient
0.1 % / 10,000 h
280 ms (10…90 %)
4 kV (1.2/50 µs) d voltage
300 Veff
2 kV inputs / outputs / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
CE; cULusprovals
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
PE connection direct on enclosure
Ordering data
Type
Voltage input (pre-configured)
Current input (pre-configured)
Special adjustment
Note
Type
SFI 0-10V/4-20mA
SFI 4-20mA/4-20mA
SFI Variabel
Qty.
1
1
1
Additional input and output versions available on request
Order No.
7940016083
7940010212
8945060000
Type
DFI 0-10V/4-20mA
DFI 4-20mA/4-20mA
DFI Variabel
Qty.
1
1
1
Order No.
7940012275
7940010167
8944940000
Additional input and output versions available on request
Accessories
Note
D.87
Analogue signal conditioning
MANN SERIES – Signal isolators
WAVEPak DC/DC
Configurable isolator with auxiliary power supply
The WAVEPak isolator is designed for the conversion of analogue voltage or current signals. It is a four-wire DC isolator with
complete three-way isolation between the input, output and
supply. It delivers measurements with an accuracy of 0.1 %
(typically 0.05 %). 24 V DC is available for providing power to
two-wire transmitters.
Typical applications for the WAVEPak
24 V DC
PLC
Flow
transmitter
Input
4 ... 20 mA
WAVEPak
DC/DC
D
Technical features:
Power supply
•
•
•
•
•
•
•
•
•
•
2 kV between the ports
24 V DC field supply for external sensors
12...60 V DC power supply
Scaleable input to output, also possible reciprocally
Output signal with direct or reverse action
Simple secure calibration possibilities
LED status display
Mounts on TS 35 mounting rail
Compact 12.5 mm housing
CE, cULus
D.88
Output
4 ... 20 V
WAVEPak DC/DC
WAVEPak
Configurable signal isolators/converters
3-way isolator
Wiring possibility A (input passive)
in 4-wire technology
+24 V
1
• External power supply
2
• Supply of 12 - 60 V DC
3
• LED status indicator
• Pluggable connection terminals
4
Iin
0V
7
Iout
PS
0V
0V
V/I
Vin
8
V/I
Analogue signal conditioning
MANN SERIES - Signal isolators
5
Vout
6
Wiring possibility B (input active)
• Adjustable input for current or voltage
+24 V
1
• Input or output scaling
2
• Direct or negated output signal
L
• Optional 24 V DC supply for EX hazardous
areas Sensor
3
4
H
W
Technical data
0V
TP+
0V
7
Iout
PS
+24 V
V/I
V/I
TP–
8
0V
5
Vout
6
Connections
Input
Type m- oder Spannungseingang, per Jumper konfigurierbar
Input signal r 0 to 10 V
Sensor supply DC output
Smallest received measuring span
Input resistance omeingang) oder > 1 MΩ Spannungseingang)
Step response time %)>
Resolution .76 mV per bit
Output
Type m- oder Spannungsausgang, per Jumper konfigurierbar
Output signal 0 to 10 V
Smallest received measuring span
Load resistance current, max.
Load resistance voltage, max.
Residual ripple /sub>
Resolution .76 mV per bit
General data
Voltage supply
Power consumption
Linearity ; 0,1 % (typ. ± 0,05 %)>
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Step response time %)>
Impulse withstand voltage
Data backup ars
Operating temperature/Storage temperature
Approvals Vorbereitung
Insulation coordination
EMC standards
Insulation voltage t / power supply
Rated voltage
Data of Housing
Clamping range (rating- / min. / max.)
mm2
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm
Input
Current or voltage input,configurable with jumpers
0 to 22 mA or 0 to 10 V
20 mA @ 24 V DC output
4 mA or 2 V ceived measuring span [2]
100 Ω (current input) or > 1 MΩ (voltage input)
< 220 ms (10…90 %)>
3.5 µA / 1.76 mV per bit
Output
Current or voltage input,configurable with jumpers
0 to 22 mA or 0 to 10 V
4 mA or 2 V ceived measuring span
≤ 1 kΩ current, max.
≥ 500 kΩ oltage, max.
< 20 mVss
3.5 µA / 1.76 mV per bit
General data
12…60 V DC ly
2.5 W @ 24 V DC on
< ± 0,1 % (typ. ± 0,05 %)
10 to 90 % (no condensation)
≤ 0.05 % / °C ficient
0.1 % / 10,000 h
< 220 ms (10…90 %)
4 kV (1.2/50 µs) d voltage
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
cULus in preparation
Insulation coordination
DIN EN 61326 s
Terminal
1
7
4
3
2
3
3
2
6
5
8
5
Signal
Signal +
Signal –
Signal +
Signal –
Signal +
Signal –
Signal +
Signal –
Signal +
Signal –
Signal +
Signal –
Supply voltage
Voltage input
Current input
Loop Powered Input
Voltage output
Current output
2 kV input / output / power supply
300 Veff
1.5 / 0.5 / 2.5
Screw connection / TS 35
Plastic enclosure / 83 g
92.4 x 12.5 x 112.4
Note
Ordering data
Type
Universaltrenner
Special adjustment
Note
Type
WAVEPak DC/DC
WavePak Variabel
Qty.
1
1
Order No.
7940024139
8945160000
Additional input and output versions available on request
Accessories
Note
D.89
D
Analogue signal conditioning
MANN SERIES – Signal converters
ITXPlus
Universal loop-powered (two-wire) signal isolator/converter
Application 1:
The ITXPlus is a compact, loop-powered, electrically-isolated,
programmable signal isolator/converter. On the input side,
optionally DC-current/voltage signals, 2-, 3-, or 4-wire PT100s,
and thermocouples can be connected. The ITXPlus measures,
filters and isolates the input parameters. It converts them into a
proportional 4...20 mA signal.
4 ... 20 mA
Power
supply
4 ... 20 mA / 24 V DC
ITXPlus
PLC
Application 2:
4 ... 20 mA / 24 V DC
Thermocouple
ITXPlus
PLC
D
For linear temperature measurements, all standard types of
thermocouples and resistance temperature detectors (RTDs)
can be connected. The ITXPlus can also process signals from
any non-linear resistance device, such as an NTC, PTC, or log.
potentiometer. For this, the appropriate characteristic may be
programmed into a table containing up to 101 measurement
values.
Application 3:
4 ... 20 mA / 24 V DC
RTD
ITXPlus
PLC
Application 4:
4 ... 20 mA / 24 V DC
If the sensor is replaced or changed on the input side, then a
fully-automatic calibration may be performed. The internal program also features many square-root, linear and x3/2-/x5/2-transfer functions. Other characterics which have not been pre-programmed can be entered directly using a PC. In this way, any
sensor may be reproduced.
The configuration software is user-friendly and runs on any PC
after installation. It also allows the ITXPlus to be configured
during active operations. The CBX100 interface connects the
ITXPlus with the PC. It implements complete electrical isolation
between the serial port and the signal transmitter.
D.90
Potentiometer
ITXPlus
PLC
The ITXPlus signal converter, which is rail mounted, and the
CBX100 interface have the following technical characteristics:
• A universal input for DC signals/thermocouples and RTD
sensors
• Complete electrical isolation
• Loop-powered output
• Programmable via PC
• Automatic cold-junction compensation for thermocouple
inputs
• Automatic wire-length compensation for resistance temperature detector (RTD) inputs
• Sensor wire-break detection
• Pre-set and user-defined linearisation
• Compact design - 12.5 mm width
• Mounts on TS35 rail
ITXPlus Series
ITXPlus
Universal signal isolators / amplifiers in
Programmable with TSET
2-wire design
• Supply via output loop
(Output loop-powered)
• Programmable with PC
Analogue signal conditioning
MANN SERIES - Signal converters
• Pluggable connection terminals
• Compact enclosure
• Current or voltage input
• Thermocouple
+24 V
+
• Temperature resistance
L
+
+
1
3
4
Iout
I
5
W
Connections
Technical data
Input
Type ersal signal isolator / signal amplifier, thermocouple, RTD
Type, thermocouple / L / N / R / S / T / W3 / W5
- 200…+ 2300 °C je nach Thermoelement
Input current (min. span 1 mA)
Input voltage -100…+200 mV (min. span 0.5 V / 4 mV)
Input resistance ingang) oder 40 Ω (Stromeingang)
Output
Type ent output
Output current
Limits of range
Residual ripple /sub>
Load resistance, max. mega; (Typically 700 Ω @ 24 V DC)
Calibration / set-up terface required 7940025031
General data
Voltage supply DC, powered by loop current
Influence on the voltage supply
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Cycle time s
Digital filter factor
Interference radiation
Step response time 90%)
Impulse withstand voltage
Rated voltage
Insulation voltage t
Transmit function d
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
6
2
• Conversion, isolation and filtering of all standard
types of signals and sensors
H
J/V/I
Input
Universal signal isolator / signal amplifier, thermocouple, RTD
B / C / E / J / K / L / N / R / S / T / W3 / W5
- 200…+ 2300 °C je nach Thermoelement
-10…+20 mA (min. span 1 mA)
-5…+10 V / -100…+200 mV (min. span 0.5 V / 4 mV)
2 MΩ (Voltage input) or 40 Ω (current input)
Output
Current output
4…20 mA rrent
+ 22 mA of range
< 20 mVss
[(Vs - 10) / 0.02] Ω (Typically 700 Ω @ 24 V DC)
PC and CBX100 USB Interface required 7940025031
General data
10…40 V DC, powered by loop current
0.005 % / V n the voltage supply
10…90 % (no condensation)
typ. 0,02 % / °C ficient
0.1 % / 10,000 h
20…200 ms
1…100 filter factor
< ± 0,5 % iation
Typ. 200 ms (10…90%)
4 kV (1.2/50 μs) d voltage
300 Veff
2 kV input / output
direct or inverted
-10 °C…+70 °C/-20 °C…+70 °C emperature
DIN EN 61326 s
Terminal Signal
5
Loop –ve
6
Loop +ve
1
Signal + Power supply
Sensor
Signal + Power supply
Storage
(only for programming)
A-Sense
A
B
B-Sense
A-Sense
A
B
A
B
Signal +
Signal –
Signal +
Signal –
A
Wiper
B
2
1
3
2
4
1
3
2
3
2
1
2
1
2
3
1
2
Supply voltage
Thermocouple
4-wire PT100/RTD
(or resistance)
3-wire PT100/RTD
(or resistance)
2-wire PT100/RTD
(or resistance)
Voltage (mV or V)
Current (mA)
Potentiometer
CE; cULusprovals
mm2
mm
1.5 / 0.5 / 2.5
Screw connection / TS 35
Plastic enclosure / 83 g
92.4 x 12.5 x 112.4
Note
Ordering data
Type
Universal input
Special adjustment
Note
Type
ITX+ 4-20mA/4-20mA
ITX+ Variabel
Qty.
1
1
Order No.
7940016563
8944980000
Additional input and output versions available on request
Accessories
Note
CBX100 USB Interface - 7940025031
Connects the ITXPlus with the PC for calibration
D.91
D
Analogue signal conditioning
MANN SERIES – Signal converters
ITXPlus Series
ITXPlus
Universal signal isolator / amplifier in 2-wire design
• Output loop-powered
• Programmable with PC
• Pluggable connection terminals
• Compact housing
• Current or voltage input
• Thermocouple
• Temperature resistance
L
• Conversion, isolation and filtering of all standard
types of signals and sensors
D
H
W
Technical data
Thermocouple inputs
Inputs
Typ
Typ
Standard
B
C
E
IEC584
J
K
L
DIN 43710
N
R
IEC584
S
T
W3
ASTM E98890
W5
User-defined Input
Cold-junction compensation
Wire-break recognition
mA
volt
2, 3, 4-wire RTD
mV
Type
Standard
PT 100
DIN 43710
PT 100
JIS
PT 200
DIN 43710
PT 200
JIS
NI 120
DIN 43710
CU 100
DIN 43710
Cable resistance
Sensor current
Influence of cable resistance
sensor (3/4 wire)
Resistance
Accuracy
2–101 values
± 1.0 °C
yes
– 10 mA to + 20 mA to 40 Ω input resistance
(min. range 1 mA)
– 5 V to + 10 V to 2 M Ω input resistance
(min. range 0.5 V)
– 100 mV to + 200 mV to 2 M Ω input resistance
(min range 4 mV)
Lower limit
Upper limit
–200 °C
850 °C
–200 °C
630 °C
–200 °C
850 °C
–200 °C
630 °C
–80 °C
320 °C
–100 °C
260 °C
5 Ω max.
0.1 mA
< 0.002 Ω per Ω wire resistance
Min. range
50 °C
100 °C
0 to 10 k Ω (min. range 10 Ω)
Type
E,J,K,L,N,T,U
Range
< 500 °C
> 500 °C
B, C, R, S,
W3, W5
mV, V, mA
PT100/RTD
Resistance
D.92
Thermocouple, PT100/RTD, mA, volt, mV, resistance
Lower limit
Upper limit
Min. range
400 °C
1828 °C
200 °C
0 °C
2000 °C
–100 °C
1000 °C
50 °C
–100 °C
1200 °C
–180 °C
1372 °C
–100 °C
900 °C
–180 °C
1300 °C
100 °C
–50 °C
1760 °C
200 °C
–50 °C
1760 °C
–200 °C
400 °C
50 °C
0 °C
2300 °C
200 °C
All
Temperature coefficient
± 0.02 °C per C°
ambient temperature
± 0.01?% of end value per °C
ambient temperature
± 0.02 °C per C°
ambient temperature
Accuracy
≤ ± 1.0 °C
≤
≤
≤
≤
±
±
±
±
2.0
0.1
0.5
0.1
°C
% of end value
°C
% of end value
D
D.93
Analogue signal conditioning
Analogue signal conditioning
MANN SERIES – Signal converters
STG
Bridge measurement isolator/transmitter with auxiliary
power
Typical application of STG
24 V DC
D
The STG bridge measurement transmitter produces a bridge
supply voltage and eliminates input-side wire resistance
changes, independently from the wire length. Tare adjustment
controls and test points allow for easy adjustment to suit initial
bridge loading. This product can be mounted on TS 35 or
TS 32 rails.
Technical features:
•
•
•
•
•
•
•
•
•
Stable bridge power supply
Supplies up to four 350 Ω measuring bridges
Tare adjustments for the bridge calibration
Front panel adjustment and test points for accurate
adjustment of excitation voltage
High accuracy of 0.1 % of the set signal range
LED status display
DC power supply
Pluggable screw-connection mechanism
Compact metal housing for rail mounting on
TS 35 or TS 32
D.94
Power supply for measuring bridge
Power
supply
Compensation wires
– + + – – +
1 2 3 4 10 11
+
Load
cell
Signal from
measuring bridge
–
7
13
STG
8
14
+
–
Output,
mA or V
PLC or
other
component
STG
STG
Bridge measuring transducer
• External power supply
• Supply of measuring bridge with 10 V DC,
convertible with jumper to 5 V DC
Analogue signal conditioning
MANN SERIES - Signal converters
• Pluggable connection terminals
• Compact enclosure
• Measuring bridge outputs stable excitation
voltage
• Can feed bridges up to 4x 350 Ω
H
• Tare adjustment and test points to correct for
initial loading
• Front adjustment
• Current displayed with LED
L
0V
10
1
2
3
4
7
8
Sense
– Sense
+ Supply
+24 V
11
PS
+ Supply
– mVin
Iout / Vout
13
V
0V
V/I
+ mVin
–
14
Connections
Technical data
Input
Type ge measuring transducer
Input measurement range
Input resistance
Supply current (= 4 x 350 Ω bridge resistors)
Bridge supply voltage 10 %
Residual ripple ss
Output
Type age and current outputs can be configured with jumpers
Output signal 0/1…5 V, 0 to 10 V
Residual ripple /sub>
Settings
Fine calibration 0 turns
Signal amplifier e signal range
Offset n; 10 % of the signal range
Tare adjustment % oder 0…200 % des Eingangsbereiches
General data
Voltage supply ash;28 V DC)
Power consumption
Linearity smn; 0.05 % of signal range
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Cut-off frequency (-3 dB)
Step response time , optional 1 ms
Insulation voltage t / power supply
Impulse withstand voltage
Rated voltage
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
mm2
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm
Note
Input
Bridge measuring transducer
1 mV to 700 mV ent range
1 MΩ stance
120 mA @ 10 V (= 4 x 350 Ω bridge resistors)
5 V or 10 V ± 10 %
≤ 10 mVss
Output
Voltage and current outputs can be configured with jumpers
0/4…20 mA, 0/1…5 V, 0 to 10 V
< 20 mVss
Settings
Potentiometer, 20 turns
45…105 % of the signal range
± 10 % of the signal range
±100 % or 0 …200 % of input range
General data
24 V DC (20…28 V DC)
3 W @ 24 V DC tion
typ. ± 0.05 % of signal range
± 0.05 % of signal range
0 to 90 % (no condensation)
typ. 0.02 % / °C ficient
0.1 % / 10,000 h
5 Hz, optional 1 kHz 3 dB)
200 ms (10…90 %), optional 1 ms
2 kV input / output / power supply
4 kV (1.2/50 μs) d voltage
300 Veff
0 °C…+60 °C/-25°C…+70°C ge temperature
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Housing
Signal
Sense –
Sense +
Supply+
Supply–
Bridge supply voltage
Not used
Signal +
Signal –
Not used
–
+
Not used
Signal + Output
Signal – Output
Input
Supply voltage
Outputs
Not used
PE connection direct on housing
DIN EN 61326 s
CE; cULusrovals
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 450 g
120 x 46 x 96
PE connection direct on enclosure
Ordering data
Type
Voltage input
Special adjustment
Note
Type
STG 10V/2mV/V/4-20mA
STG Variabel
Qty.
1
1
Order No.
7940011671
8945070000
Additional input and output versions available on request
Accessories
Note
D.95
D
Analogue signal conditioning
MANN SERIES – Signal converters
Micromann AR Series
Universal, electrically-isolated, signal converters with
auxiliary power and alarm monitoring
Typical application of Micromann CLCAR
24 V DC
The Micromann AR Series of signal converters feature an alarm
function. In the sector of process automation, it offers both an
analogue output and a flexible multi-functional interface between the industrial facility and the control room.
D
Appropriate modules are available for a wide variety of input
parameters. This includes signal processing for analogue signals such as current, voltage; temperature (thermocouple and
PT100 temperature probes), frequency, conductivity, curve linearisation, and additional math functions.
All Micromann AR Series modules are equipped with a four-digit
scalable LED display. Scaling for the input parameters is automatically accomplished. The user friendly software makes setting up operating parameters very easy. The user simply chooses the specific parameters using the keyboard and display.
The Micromann AR Series signal converters are equipped to 2
kV complete electrical isolation.
The modules can be mounted on TS35 and TS32 rails.
The pluggable screw connection is located on the front.
Technical features:
•
•
•
•
•
•
•
Programmable current/voltage output
Two alarm outputs with relay LED status display
LED display in engineering units
Complete electrical isolation
DC power supply
Pluggable screw-connections
Compact metal housing
D.96
4...20 mA
input
Tank
Power
supply
24 V DC
Level
transmitter
Alarm in
storage room
mA oder V DC
Micromann
Linearised output
(volume)
Decentralized
PLC
Relay supply
e.g. 230 V AC
Volume
Relay channel 1
Level
Relay channel 2
Alarm in
maintenance area
Common technical data
Display
Type
Display
Display range
Status indicator
Analogue Output
Type
Load resistance, current
Load resistance, voltage
Output current limits
Output voltage limits
Min. input span
Transmit function
Isolation voltage
Residual ripple
Alarm output
Type
Switching current
Isolation
Switching threshold
Alarm function
Relay controlled
Reset
Dynamic hysteresis
General data
Scanning rate
EMC standard
Approvals
Impulse withstand voltage
Analogue signal conditioning
MANN SERIES – Signal converters
Connections
4-digit display
Percent or real-value displayed
-999 to 9999
Trip1 / Trip2 / Processor status
Adjustable voltage/current
≤ 900 Ω
≥1kΩ
0...22 mA
0...11 V
2 mA or 1 V
Direct or reverse influence
2 kV between the ports
< 20 mVss (voltage)
< 40 μA ss (current)
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Housing
Signal
Depending on the
individual module
Inputs
Connections for
Configuration
changing setup
0V
Supply voltage
24 V
NO contact, channel 1
NO contact, channel 2
Alarm outputs
Common
Output signal +
Current output signal –
Analogue outputs
Voltage output signal –
PE connection direct on housing
Two NO contacts with arc suppression
1 A @ 240 V AC / 30 V DC
2 kV between ports
25 % of the display range
High alarm or
low alarm
Un-energized or energized
Automatic or manual
0...4200 s
5 per sec.
DIN EN 61326
CE, cULus
4 kV (1.2/50 μs)
D.97
D
Analogue signal conditioning
MANN SERIES - Signal converters
Micromann AR Series
UCVAR
Universal, galvanically-isolated signal converters
with an alarm function
Current und voltage input
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Conversion, isolation and filtering of signals
0V
ch 1
• Bi-polar inputs
H
+24 V
10
9
• Supply of active input devices
PS
+24 V
1
Iin
2 +
0V
3
Vin
4 +
• Linearization
D
V/I
Connections
Input
Type og current / voltage signals
Input signal / -55…55 V
Input resistance ent input); 1 Ω (voltage input)
Resolution er bit for small ranges
Linearisation
Supply voltage 25 mA)
Smallest received measuring span
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
Terminal
1
2
3
4
5
6
Input
Analog current / voltage signals
-55…+55 mA / -55…55 V
22 Ω (current input); 1 Ω (voltage input)
1 μA/ mV per bit for small ranges
Linear or √ xt]
24 V DC (up to 25 mA)
1 mA or 1 V ceived measuring span [2]
Display
-999…9999 ge
Percentage or real value display
0.001 of displayed value
General data
12…50 V DC ly
6 W @ 24 V DC tion
< ± 0.1 % typically
< ± 0.1 % typically
± 0.05 % of signal range
0 to 90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (for signal jump of 10…90 %),
programmable (250 ms…32 sec.)
2 kV input / output / power supply
4 kV (1.2/50 μs) d voltage
300 Veff
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrprovals
Display
Display range
Display value real value display
Resolution isplayed value
General data
Voltage supply
Power consumption
Accuracy n; 0.1 % typically
Linearity ; 0.1 % typically
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Insulation voltage t / power supply
Impulse withstand voltage
Rated voltage
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Current input / voltage input
Special adjustment
Note
D.98
Iout
Vout
11
12
13
14
+
15
–
16
–
Technical data
Accessories
Iout / Vout
V/I
L
Note
ch 2
Common
Type
UCVAR
UCV Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940010195
8945090000
Signal
24 V DC
Signal + Current
Signal –
Signal + Voltage
Not used
Micromann AR Series
UTCAR
Universal, galvanically-isolated signal converters
with an alarm function
Temperature input / thermocouple
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Thermocouple (J, K, T, E, B, S, R)
0V
H
+24 V
10
9
• Temperature display in °C / °F
ch 1
• Burn-out alarm
2
• Cold-trap compensation
+
PS
Iout / Vout
Iout
V/I
–
11
12
13
14
+
15
–
16
ch 2
Common
J
3
Vout
–
L
Connections
Technical data
Input
Type mocouple (type J,K,T,E,B,S,R) or mV signals
Input signal ranges
Input resistance, max.
Input
Thermocouple (type J,K,T,E,B,S,R) or mV signals
9 adjustable ranges
1 kΩ stance, max.
Display
Depends on input type
°C / °F or V e
1 °C / °F or 0.01 mV
General data
≤ 0.02 / C° ambient temperature
12…50 V DC ly
6 W @ 24 V DC tion
0 to 90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (for signal jump of 10…90 %),
programmable (250 ms…32 sec.)
2 kV input / output / power supply
4 kV (1.2/50 μs) d voltage
300 Veff
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrprovals
Display
Display range put type
Display value
Resolution or 0.01 mV
General data
Cold-junction compensation error re
Voltage supply
Power consumption
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Insulation voltage t / power supply
Impulse withstand voltage
Rated voltage
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Note
Terminal
1
2
3
4
5
6
Signal
Signal + mV
Signal – mV
Signal temperature
Cold-junction
compensation
Not used
Thermocouple (Type J, K, N, T, E,
B, S, R) or mV signals
Input type
J
K
N
T
E
B
S
R
mV
Display limits
highest
870 °C (1598 °F)
1372 °C (2502 °F)
1300 °C (2372 °F)
400 °C (752 °F)
700 °C (1292 °F)
1800 °C (3272 °F)
1768 °C (3214 °F)
1768 °C (3214 °F)
60 mV
lowest
–50 °C (–58 °F)
0 °C (32 °F)
–50 °C (–58 °F)
–50 °C (–58 °F)
–9.99 m
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Temperature converter
Special adjustment
Note
Type
UTCAR
UTC Variabel
Qty.
1
1
Analogue signal conditioning
MANN SERIES - Signal converters
Order No.
7940012190
8945130000
Additional input and output versions available on request
Accessories
Note
D.99
D
Analogue signal conditioning
MANN SERIES - Signal converters
Micromann AR Series
URTAR
Universal, galvanically-isolated signal converters
with an alarm function
Temperature input (RTD)
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Processes 2- or 3-wire PT100 signals
0V
ch 1
• Automatic line compensation
H
+24 V
10
9
• Temperature display in °C / °F
PS
2 A
3 B
4 Bsense
D
ch 2
Common
J
PT 100
Iout / Vout
V/I
–
L
Connections
Technical data
Input
Type -wire PT100 RTD
Input signal for 4 ranges
Line resistance in measuring circuit
cable-length compensation
Input
2-/3-wire PT100 RTD
Terminal
1
2
3
4
5
6
Configurable for 4 ranges
30 Ω ance in measuring circuit
> 0,05 % ngth compensation
Display
Depends on selected range
°C or °F value
1 °C / °F or 0.1 °C / °F
General data
12…50 V DC ly
6 W @ 24 V DC tion
< 1 °C for 1 °C resolution
± 0.05 % of signal range
0 to 90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (for signal jump of 10…90 %),
programmable (250 ms…32 sec.)
2 kV input / output / power supply
4 kV (1.2/50 μs) d voltage
300 Veff
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrrovals
Display
Display range lected range
Display value
Resolution or 0.1 °C / °F
General data
Voltage supply
Power consumption
Accuracy ür 1 °C Auflösung>
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Insulation voltage t / power supply
Impulse withstand voltage
Rated voltage
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Note
Temperature converter
Special adjustment
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
Accessories
Note
D.100
Type
URTAR
URT Variabel
Qty.
1
1
Additional input and output versions available on request
Not used
Max. display range
highest
lowest
700 °C
–200 °C
1292 °F
–328 °F
200,0 °C
–99,9 °C
400 °F
–99,9 °F
PE connection direct on enclosure
Type
Signal
Not used
A
B
B-Sense
2- or 3-wire PT100 RTD
(BS1904:1984 / IEC751:1983)
Ordering data
Note
Iout
Vout
11
12
13
14
+
15
–
16
Order No.
7940010250
8945120000
Resolution
1 °C
1 °F
0.1 °C
0.1 °F
Micromann AR Series
UHZAR
Universal, galvanically-isolated signal converters
with an alarm function
Frequency input
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Wide-range input
0V
+24 V
10
9
• Supply of active input devices
+12 V
1
Pull Up/Down
2
0V
3
Input
4 +
Input
5 –
Vin (High)
6 +
H
L
Input
Type rammable frequencies (no chatter
no-voltage (floating) contacts)
Input signal
Input voltage AC/DC
Smallest received measuring span
Sensor supply mA
Input
Programmable frequencies (no chatter
Terminal
1
2
3
4
5
6
no-voltage (floating) contacts)
0…10 kHz al
50 mV…250 V AC/DC
0.001 Hz received measuring span [2]
12 V DC to 25 mA
Display
-999…9999 ge
Percentage or real value display
0.001 of displayed value
General data
12…50 V DC ly
6 W @ 24 V DC tion
< 0,05 % of signal range
< 0,05 % of signal range
± 0.02 % of signal range
0 to 90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (for signal jump of 10…90 %),
programmable (250 ms…32 sec.)
2 kV input / output / power supply
4 kV (1.2/50 μs) d voltage
300 Veff
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrprovals
Display
Display range
Display value real value display
Resolution isplayed value
General data
Voltage supply
Power consumption
Accuracy des Signalbereiches>
Linearity des Signalbereiches>
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Insulation voltage t / power supply
Impulse withstand voltage
Rated voltage
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
ch 1
PS
ch 2
Common
Iout / Vout
V/I
Iout
Vout
11
12
13
14
+
15
–
16
–
Connections
Technical data
mm2
mm
Note
Signal
12 V DC
Pull Up / Down
0V
Signal +
Signal –
High Signal
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Frequency converter
Special adjustment
Note
Type
UHZAR
UHZ Variabel
Qty.
1
1
Analogue signal conditioning
MANN SERIES - Signal converters
Order No.
7940010184
8945100000
Additional input and output versions available on request
Accessories
Note
D.101
D
Analogue signal conditioning
MANN SERIES - Signal converters
Micromann AR Series
CNDAR
Universal, galvanically-isolated signal converters
with an alarm function
Conductivity measurement
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Suitable for all conductivity probes
0V
H
• Compensation for probe temperature
2
• Programmable cell constant
3
• Linearized probe characteristic
D
+24 V
10
9
• Automatic measuring range selection
Conductivity A
ch 1
PS
Conductivity B
4
A
5
B
6
Bsense
S/J
Iout / Vout
V/I
Connections
Technical data
Input
Type uctivity, PT100 RTD
Input signal (0.1 μS resolution)
0 to 1000 / 5000 μS (1 μS resolution)
0 to 20 mS (0.01 mS resolution)
0 to 200 °C (0.1 °C resolution)
Smallest received measuring span
Supply voltage sub> @ 400 Hz
Battery constant / cm
cable-length compensation >
Temperature compensation up to five measurement points
Display
Display range
Display value , mS/cm or °C
Resolution angssignal
General data
Voltage supply
Power consumption
Accuracy 0.05% of final value
Linearity 0.05 % of signal range
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Insulation voltage t / power supply
Impulse withstand voltage
Rated voltage
Data backup ars
Operating temperature/Storage temperature
EMC standards
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
Input
Conductivity, PT100 RTD
0 to 200 μS (0.1 μS resolution)
0 to 1000 / 5000 μS (1 μS resolution)
0 to 20 mS (0.01 mS resolution)
0 to 200 °C (0.1 °C resolution)
20 % of selected input range span [2]
< 6 Vss @ 400 Hz
0.01…99.99 / cm
< 2 % (up to 30 Ω)
Linear or user-defined, up to five measurement points
Display
-999…9999 ge
μS, mS, μS/cm, mS/cm or °C
see input signal
General data
12…50 V DC ly
6 W @ 24 V DC tion
± 0.05% of final value
± 0.05 % of signal range
± 0.05 % of signal range
0 to 90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (for signal jump of 10…90 %),
programmable (250 ms…32 sec.)
2 kV input / output / power supply
4 kV (1.2/50 μs) d voltage
300 Veff
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Voltage/current output
Special adjustment
Accessories
Note
D.102
Iout
Vout
11
12
13
14
+
15
–
16
–
L
Note
ch 2
Common
Type
CNDAR
CND Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940010232
8944930000
Terminal
1
2
3
4
5
6
Signal
Not used
A Conductivity
B Conductivity
A Temperature
B Temperature
B-Sense Temperature
Micromann AR Series
CLCAR
Universal, galvanically-isolated signal converters
with an alarm function
Linearization
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Linearized measurements of non-linear sensors
0V
+24 V
10
9
• Processing of control signals
ch 1
PS
+24 V
H
1
Iin
2 +
0V
3
Vin
4 +
V/I
Iout / Vout
V/I
Iout
Vout
11
12
13
14
+
15
–
16
–
Connections
Input
Type og current / voltage signals
Input signal / -12…12 V
Input resistance ent input); or 1 MΩ (voltage input)
Smallest received measuring span
Sensor supply o 25 mA)
Input
Analog current / voltage signals
-24…24 mA / -12…12 V
22 Ω (current input); or 1 MΩ (voltage input)
2 mA or 1 V ceived measuring span [2]
24 V DC (up to 25 mA)
Display
-999…9999 ge
Percentage or real value display
0.001 of displayed value
General data
12…50 V DC ly
6 W @ 24 V DC tion
101 adjustable measurement points, universal signal
0 to 90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (for signal jump of 10…90 %),
programmable (250 ms…32 sec.)
2 kV input / output / power supply
4 kV (1.2/50 μs) d voltage
300 Veff
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrovals
Display
Display range
Display value real value display
Resolution isplayed value
General data
Voltage supply
Power consumption
Linearity table measurement points, universal signal
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Insulation voltage t / power supply
Impulse withstand voltage
Rated voltage
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
ch 2
Common
L
Technical data
mm2
mm
Note
Terminal
1
2
3
4
5
6
Signal
24 V DC
Signal + Current
Signal –
Signal + Voltage
Not used
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Voltage/current output
Special adjustment
Note
Type
CLCAR
CLC Variabel
Qty.
1
1
Analogue signal conditioning
MANN SERIES - Signal converters
Order No.
7940010489
8944980000
Additional input and output versions available on request
Accessories
Note
D.103
D
Analogue signal conditioning
MANN SERIES – Signal converters
Micromann UPI Series
Analogue frequency converter with auxiliary power
supply and alarm monitoring
Devices in the Micromann UPI Series convert analogue current
and voltage signals to a proportional frequency.
Measurement errors (which can occur with low input frequencies) are elimated with a adjustable frequency suppression.
In addition, a quadratic function linearizes the signals.
Typical application of Micromann UPI
Flow-rate
transmitter
4...20 mA input
(proportional to rate)
External two-wire measuring transducers can be supplied with
power directly from the analogue frequency converter.
An alarm output is available for monitoring the input signal.
The four-digit LED display is universally scalable.
The selected engineering units are automatically applied for all
parameters.
The user-friendly software makes setting up operating parameters
very easy. The necessary parameters are chosen using the
display and keypad. All modules are completely electrically isolated to 2 kV.
The housing can be snapped onto a DIN TS 35 or TS 32
mounting rail. The pluggable screw connection is located on
the front.
Technical features:
• Conversion of analogue current/voltage signals to a
proportional frequency
• Power supply for external measuring transducers or sensors
• A quadratic function suppresses low frequencies and
linearises the signals
• An alarm channel with LED status display
• LED display in engineering units
• Complete electrical isolation
• DC power supply
D.104
24 V DC
C
UPIT
D
Fluid flow – max. 60,000 L/hr
Pipeline
Variable frequency
pulse output
proportional to volume
e.g. 100 pulses per min
Power supply
Low-flow alarm
Counter indicates
Flow Interator
accumulated litres
(volume counter)
with factor x10
Connections
Common technical data
Input
Type
Input signal limits
Smallest received measuring span
Input resistance
Resolution
Linearisation
Supply voltage
Display
Type
Display range
Display value
Status indicator
General information
Supply voltage
Power input
Accuracy
Linearity
Repeat accuracy
Humidity
Temperature coefficient
Long-term drift
Step response time
Scanning rate
Impulse withstand voltage
Isolation voltage
Data backup
Operating temperature / storage temperature
EMC standard
Approvals
Analogue signal conditioning
MANN SERIES – Signal converters
Analogue current/voltage signals
–55...+55 mA / –55...+55 V
1 mA or 1 V
22 Ω (current input), 1 MΩ (voltage input)
1 μA/1 mV per bit
Linear or √
24 V DC (up to 25 mA)
4-digit display
0 to 9999
Output frequency per sec. / min. / hour
Trip 1 / Processor status
12…50 V DC
6 W @ 24 V DC
< ± 0.1 % typically
< ± 0.1 % typically
± 0.05 % of signal range
0…90 % (no condensation)
≤ 0,02 % / °C
0.1 % / 10,000 h
320 ms (10...90 %)
programmable from 250 ms...32 sec
5 per sec.
4 kV (1.2/50 μs)
2 kV between ports
≥ 100 years
0 °C…+60 °C / –25 °C…+70 °C
DIN EN 61326
CE, cULus
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Housing
Signal
24 V DC
Signal + current
Signal –
Signal + voltage
Inputs (current/
voltage)
Not used
Connections for
changing setup
0V
12...50 V
Configuration
Supply voltage
D
Depending on the
individual module
Not used
PE connection direct on housing
D.105
Analogue signal conditioning
MANN SERIES - Signal converters
Micromann UPI Series
UPIR
Analog frequency converter for all standard
current and voltage signals
Low frequency output [relay]
• Frequency pulse output
• 24 V DC supply of the active input device
• Integrated linearization
• Pluggable connection terminals
• Frequencies up to 25 Hz
0V
NC
PS
+24 V
H
1
Iin
2 +
0V
3
Vin
4 +
D
+24 V
10
9
• 1-pole change-over switch with relay
contact/frequency output and alarm channel
NO
V/I
f
–
L
Connections
Technical data
Output
Type uency-controlled relay output (CO)
Max. output frequency
Time ranges n, h
Insulation lated
Output
Frequency-controlled relay output (CO)
Terminal
11
12
13
14
15
16
25 Hz output frequency
per sec, min, h
Fully insulated
Alarm
Relay output (change-over)
Adjustable, energised or de-energised coil
Manual or automatic
delayed 0…4200 s
1 digital step
All values in display range
3 A @ 240 V AC (resistive load)
3 A @ 24 V DC / 110 V AC (resistive load)
Alarm
Type y output (change-over)
Relay triggering egt oder nicht erregte Spule
Reset l or automatic
Alarm function 4200 s
Dead time step
Range of adjustment ay range
Switching current hmsche Last)
3 A @ 24 V DC / 110 V AC (ohmsche Last)
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Frequency converter
Special adjustment
Note
Accessories
Note
D.106
11
12
13
fout NC
14
+
fout Common
15
fout NO
16
Common
Type
UPIR
UPI Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940010908
8945110000
Signal
Normally closed
Common
Normally open
Normally closed
Common
Normally open
Alarm output
Freqency output
Micromann UPI Series
UPIT
Analog frequency converter for all standard
current and voltage signals
High-frequency output [Transistor]
• Frequency pulse output
• 24 V DC supply of the active input device
• Integrated linearization
Analogue signal conditioning
MANN SERIES - Signal converters
• Pluggable connection terminals
• Frequencies up to 1 kHz
0V
H
+24 V
10
9
• Open collector-transistor output with alarm
channel
PS
+24 V
1
Iin
2 +
0V
3
Vin
4 +
V/I
f
Alarmout
11
fout
12
0V
13
L
Connections
Technical data
Output
Type uenzgesteuerter Transistorausgang
Max. output frequency
Resolution
Time ranges n, h
Insulation r Minuspunkt von Alarmausgang und
frequenzgesteuertem Ausgang
Output
Frequency-controlled transistor output
999.9 Hz put frequency
2 μs lution
per sec, min, h
Common negative return of alarm output and
frequency output
Alarm
Transistor output
Adjustable transistor ON or OFF
Manual or automatic
delayed 0…4200 s
1 digital step
All values in display range
200 mA l switching current
max. 50 V DC ching voltage
Alarm
Type sistorausgang
Relay triggering sistor ON oder OFF
Reset l or automatic
Alarm function 4200 s
Dead time step
Range of adjustment ay range
Nominal switching current
Nominal switching voltage
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
Terminal
11
12
13
mm2
mm
Note
Signal
Alarm output
Frequency pulse output
0V
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Frequency converter
Special adjustment
Note
Type
UPIT
UPI Variabel
Qty.
1
1
Order No.
7940015988
8945110000
Additional input and output versions available on request
Accessories
Note
D.107
D
Analogue signal conditioning
MANN SERIES – Signal-converter accessories
CBX100 USB
• Interface for configuration
• USB port for PC
• Tx and Rx status displays
D
Technical data
Connections
Display
Status indicator
Eingang
LED (send / receive)
Eingang
General data
Isolation voltage
Operating temperature / storage temerature
Air humidity
Software
Interface
Approvals
500 V for 60s
–20 °C...+70 °C / –25 °C...+70 °C
10…90 % (no condensation)
T-Set as of V.4.2 (can be downloaded from www.mannseries.com)
USB
CE, cULus
Converter
1
2
3
4
Output
Input
PC
CBX100
Note: Disconnect the charging unit before operating the CBX100
Note:
Ordering data
Type
Interface device
Note:
Accessories
Note:
D.108
Type
CBX100 USB
Qty.
1
Order No.
7940025031
D
D.109
Analogue signal conditioning
Analogue signal conditioning
MANN SERIES – Process alarms
DPA Series
Two-channel modules for alarm monitoring
Typical application of DPAMA
Modules in the DPA Series are used for alarm monitoring. They
can be configured for a wide variety of industrial signals and
feature two alarm outputs. Setpoint values and deadband can
be individually adjusted by using a potentiometer.
Valve
Power
supply
D
The deadband reduces chatter from the monitoring relay during
switching operations. The reset point of the alarm contact is
individually adjusted in this case away from the hysteresis
(setpoint). In order to generate an alarm in the event of a power
outage, the user should select the “energized” operational
status for one or both of the output relays. A high/low-trip
switching behaviour can also be set independently for each
channel.
24 V DC
Relay supply
z. B. 230 V AC
DPA / 24 V DC
DMA /
4...20 mA 4 ... 20 mA
Relay
channel 2
Relay
channel 1
Alarm
Connections
The following analogue input signals can be processed by the
DPA Series: temperature (thermocouple and PT100 temperature detector), AC/DC currents/voltages, frequencies, measuring
potentiometers, differential currents and differential resistances.
The housing can be snapped onto a DIN TS 35 or TS 32
mounting rail. The pluggable screw connection is located on
the front.
Technical features:
• A wide variety of versions available for many types of input
signals
• Two independent alarm channels with relay output
• LED status display
• Min./max switching commands in any combination
• High repetition accuracy
• Deadband/setpoint adjustment on front panel
• Complete electrical isolation to 2 kV
• DC power supply
• Pluggable screw-connection mechanism
• Compact metal housing
D.110
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Housing
Signal
Depending on the
individual module
Input
Not used
Supply voltage
+
NO contacts
Alarm channel 1
Common
(Relay contacts)
NC contact
NO contacts
Alarm channel 2
Common
(Relay contacts)
NC contact
PE connection direct on housing
Level
transmitter
DPA Series
DPADMA
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Current monitoring 4…20 mA
• Two alarm channels
• External power supply
Analogue signal conditioning
MANN SERIES - Process alarms
• Pluggable connection terminals
• Compact enclosure
• For current signals [mA DC]
0V
NC
• Bi-polar input signals on request
H
1
• Supply of active input devices
2
4
PS
+24 V
Ch 1
11
12
13
NC
14
Common
15
NO
16
Common
NO
Iin
I
0V
Ch 2
L
Connections
Technical data
Input
Type ent input [mA]
Input signal 10 Ω (additional on request)
Input resistance
Input range min./max. mA
Offset 0 % of signal range
Min. set response time
Input
Current input [mA]
Terminal
1
2
3
4
4 - 20 mA @ 10 Ω (additional on request)
≥ 10 Ω e
20 μA…500 mA
0…500 % of signal range
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
24 V DC ± 10 %
High Offset: zero point > signalling range
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
4 kV (1.2/50 μs) d voltage
0.1 % / 10,000 h
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrprovals
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Voltage supply n; 10 %
Options fset: zero point > signalling range
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Impulse withstand voltage
Long-term drift h
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
+24 V
10
9
• Low input impedance
mm2
mm
Note
Signal
24 V DC
Signal +
Not used
Signal –
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Current input
Special adjustment
Note
Type
DPADMA 4-20mA
DPA Variabel
Qty.
1
1
Order No.
7940011294
8944960000
Additional input and output versions available on request
Accessories
Note
D.111
D
Analogue signal conditioning
MANN SERIES - Process alarms
DPA Series
DPADMV
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Voltage monitoring 0…10(100) mV
• Two alarm channels
• External power supply
• Pluggable connection terminals
• Compact enclosure
• For voltage signals [mV DC]
0V
NC
• Bi-polar input signals on request
H
+24 V
10
9
• High input impedance
2
4
D
+
PS
Vin
Ch 1
Common
NO
V
0V
NC
Ch 2
Common
NO
L
Connections
Technical data
Input
Type ages (≤ 100 mV)
Input signal V or 0…100 mV
Input resistance
Input range min./max.
Offset h;500 % of signal range
Min. set response time
Input
Voltages (≤ 100 mV)
0…10 mV or 0…100 mV
10 MΩ tance
8…100 mV DC ax.
0…500 % of signal range
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
24 V DC ± 10 %
High Offset: zero point > signalling range
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
4 kV (1.2/50 μs) d voltage
0.1 % / 10,000 h
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusr provals
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Voltage supply n; 10 %
Options fset: zero point > signalling range
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Impulse withstand voltage
Long-term drift h
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
Terminal
1
2
3
4
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Voltage input
Voltage input
Special adjustment
Note
Accessories
Note
D.112
Type
DPADMV 0-100mV
DPADMV 0-10mV
DPA Variabel
Qty.
1
1
1
Additional input and output versions available on request
Order No.
7940017849
7940017848
8944960000
Signal
Not used
Signal +
Not used
Signal –
11
12
13
14
15
16
DPA Series
DPADCV
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Voltage monitoring 0…10 V / 1…5 V
• Two alarm channels
• External power supply
Analogue signal conditioning
MANN SERIES - Process alarms
• Pluggable connection terminals
• Compact enclosure
• For voltage signals [V DC]
0V
NC
• Bi-polar inputs on request
H
2
Vin
4
0V
PS
Ch 1
11
12
13
NC
14
Common
15
NO
16
Common
NO
V
Ch 2
L
Connections
Technical data
Input
Type oltage [> 500 mV]
Input signal or 1…5 V (additional on request)
Input resistance 10 V) or 500 kΩ (1…5 V)
Input range min./max.
Offset 0 % of signal range
Min. set response time
Input
DC voltage [> 500 mV]
Terminal
1
2
3
4
0…10 V or 1…5 V (additional on request)
1 MΩ (0…10 V) or 500 kΩ (1…5 V)
0.1…300 V DC ax.
0…500 % of signal range
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
24 V DC ± 10 %
High offset: zero point > signal range
High voltage: for ranges > 60 V
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
4 kV (1.2/50 μs) d voltage
0.1 % / 10,000 h
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusr provals
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Voltage supply n; 10 %
Options fset: zero point > signal range
High voltage: for ranges > 60 V
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Impulse withstand voltage
Long-term drift h
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
+24 V
10
9
• High input impedance
mm2
mm
Note
Signal
Not used
Signal +
Not used
Signal –
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Voltage input
Voltage input
Special adjustment
Note
Type
DPADCV 0-10V
DPADCV 1-5V
DPA Variabel
Qty.
1
1
1
Order No.
7940011718
7940012970
8944960000
Additional input and output versions available on request
Accessories
Note
D.113
D
Analogue signal conditioning
MANN SERIES - Process alarms
DPA Series
DPAAVX
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Voltage monitoring 0…250 V AC
• Two alarm channels
• External power supply
• Pluggable connection terminals
• Compact enclosure
• For voltage signals [V AC]
0V
NC
• Accuracy Class 0.5
H
+24 V
10
9
• High input impedance
D
2
Vin
4
Vin
PS
Ch 1
Common
NO
Uac
NC
Ch 2
Common
NO
L
Connections
Technical data
Input
Type nung [AC]
Input frequency range
Input resistance
Input signal (additional on request)
Input range min./max.
Offset 0 % of signal range
Min. set response time
Input
Voltages [AC]
47…63 Hz range
> 1 MΩ ance
0…250 V AC (additional on request)
8 mV…250 V AC .
0…500 % of signal range
typ. 150 ms sponse time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
24 V DC ± 10 %
High Offset: offset > signalling range
High Voltage: input voltage > 60 V AC
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
4 kV (1.2/50 μs) d voltage
0.5 erance class
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULus
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Voltage supply n; 10 %
Options fset: offset > signalling range
High Voltage: input voltage > 60 V AC
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Impulse withstand voltage
Tolerance class
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
Terminal
1
2
3
4
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Voltage input
Special adjustment
Note
Accessories
Note
D.114
Type
DPAAVX 0-125Vac
DPA Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940017847
8944960000
Signal
Not used
AC Voltage
Not used
AC Voltage
DPA Series
DPARTD
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Temperature monitoring (RTD)
• Two alarm channels
• External power supply
Analogue signal conditioning
MANN SERIES - Process alarms
• Pluggable connection terminals
• Compact enclosure
• For temperature signals [°C]
0V
• Automatic cable-length compensation
H
2
A
3
4
B
PS
Ch 1
J
BSENSE
L
Ch 2
11
12
13
14
15
16
Connections
Technical data
Input
Type 0 2-/3-wire
Interference characteristic
Sensor current
Min. set response time
Input
PT100 2-/3-wire
High Alarm ce characteristic
0.5 mA current
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
Cable-length compensation reduces the influence of
conductor resistance by a factor of 100.
24 V DC ± 10 %
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
0.1 % / 10,000 h
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULus
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Cable-length compensation reduces the influence of
conductor resistance by a factor of 100.
Voltage supply n; 10 %
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Impulse withstand voltage
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
+24 V
10
9
• 2- or 3-wire connection
mm2
mm
Note
Terminal
1
2
3
4
Signal
Not used
A
B
B-Sense
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Temperature converter
Temperature converter
Temperature converter
Note
Type
DPARTD 0-100C
DPARTD 0-200C
DPARTD 0-50C
Qty.
1
1
1
Order No.
7940014900
7940017852
7940014212
Additional input and output versions available on request
Accessories
Note
D.115
D
Analogue signal conditioning
MANN SERIES - Process alarms
DPA Series
DPATCX
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Temperature monitoring (thermal converter)
• Two alarm channels
• External power supply
• Pluggable connection terminals
• Compact enclosure
• For all standard thermocouples
0V
NC
• Wire-break recognition can be set
H
+24 V
10
9
• Automatic cold-junction compensation
PS
2
+
3
D
Ch 1
Common
NO
J
NC
Ch 2
_
Common
NO
L
Connections
Technical data
Input
Type moelement
Input signal 1000 C°) (additional on request)
Input resistance
Interference characteristic
Min. set response time
Input
Thermocouple
Type K (0…1000 C°) (additional on request)
10 MΩ tance
High oder Low Alarm teristic
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
Automaticallyon compensation
Wire-break recognition: High Alarm / Low Alarm
24 V DC ± 10 %
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
0.1 % / 10,000 h
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusr provals
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Cold-junction compensation
Options eak recognition: High Alarm / Low Alarm
Voltage supply n; 10 %
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Impulse withstand voltage
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Temperature converter
Special adjustment
Note
Accessories
Note
D.116
Type
DPATCX K/0-1000C
DPA Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940017853
8944960000
Terminal
1
2
3
4
Signal
Not used
Signal +
Not used
Signal –
11
12
13
14
15
16
DPA Series
DPAPOT
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Position monitoring
• Two alarm channels
• External power supply
Analogue signal conditioning
MANN SERIES - Process alarms
• Pluggable connection terminals
• Compact enclosure
• Position detection
0V
+24 V
10
9
• Potentiometer and loop input
NC
H
PS
3 B (100%)
2
4 A (0%)
Ch 1
Common
NO
J
NC
Ch 2
Common
NO
L
Connections
Technical data
Input
Type nductor partial-voltage meter or measuring conductor
Input signal .1 MΩ (percent of potentiometer range)
Min. set response time
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Voltage supply n; 10 %
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Impulse withstand voltage
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
11
12
13
14
15
16
mm2
mm
Note
Input
3-conductor partial-voltage meter or measuring conductor
10 Ω…1 MΩ (percent of potentiometer range)
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
24 V DC ± 10 %
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
0.1 % / 10,000 h
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrprovals
Terminal
1
2
3
4
Signal
Not used
Wiper
B
A
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Resistor input
Resistor input
Special adjustment
Note
Type
DPAPOT 10KM/0-100%
DPAPOT 1KM/0-100%
DPA Variabel
Qty.
1
1
1
Order No.
7940017851
7940017850
8944960000
Additional input and output versions available on request
Accessories
Note
D.117
D
Analogue signal conditioning
MANN SERIES - Process alarms
DPA Series
DPARES
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Resistance monitoring
• Two alarm channels
• External power supply
• Pluggable connection terminals
• Compact enclosure
• 2-wire input
0V
+24 V
10
9
NC
H
2
PS
A
Ch 1
Common
NO
4
D
J
B
NC
Ch 2
Common
NO
L
Connections
Technical data
Input
Type re resistance
Input signal a; (20 Ω…100 kΩ on request)
Min. set response time
Input
2-wire resistance
0…1 kΩ (20 Ω…100 kΩ on request)
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
24 V DC ± 10 %
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
0.1 % / 10,000 h
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrprovals
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Voltage supply n; 10 %
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Impulse withstand voltage
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
Terminal
1
2
3
4
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Resistor input
Special adjustment
Note
Accessories
Note
D.118
Type
DPARES 0-1KM
DPA Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940017917
8944960000
Signal
Not used
A
Not used
B
11
12
13
14
15
16
DPA Series
DPAMAS
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Monitoring of residual current
• Two alarm channels
• External power supply
Analogue signal conditioning
MANN SERIES - Process alarms
• Pluggable connection terminals
• Compact enclosure
• Residual current measuring
0V
+24 V
10
9
• Monitoring of two current signals
NC
H
2
3
PS
Iin (A)
Ch 1
NO
+
Iin (B)
+
4
Common
0V
I
NC
Ch 2
Common
NO
L
Connections
Technical data
Input
Type rrent inputs [mA]
Input signal A (additional upon request)
Input resistance
Min. set response time
Input
2 current inputs [mA]
Terminal
1
2
3
4
4…20 mA (additional upon request)
10 Ω stance
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
output x A-B ction
24 V DC ± 10 %
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
0.1 % / 10,000 h
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusr provals
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Transmit function
Voltage supply n; 10 %
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Impulse withstand voltage
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
11
12
13
14
15
16
mm2
mm
Note
Signal
Not used
Signal A+
Signal B+
Signal –
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Current input
Special adjustment
Note
Type
DPAMAS 4-20mA
DPA Variabel
Qty.
1
1
Order No.
7940016144
8944960000
Additional input and output versions available on request
Accessories
Note
D.119
D
Analogue signal conditioning
MANN SERIES - Process alarms
DPA Series
DPADRT
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Resistance monitoring
• Two alarm channels
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Residual current measuring
0V
+24 V
10
9
• Monitoring of two resistance values
NC
H
PS
2
4
3
Ch 1
Common
NO
J
NC
Ch 2
D
Common
NO
L
Connections
Technical data
Input
Type Widerstände R1 und R2 in 2-Draht Konfiguration
mit R1 > R2
Input signal
Input range min./max. 100 kΩ
Reference resistance ffset
Min. set response time
Input
Two resistance R1 and R2 in 2-wire configuration
with R1 > R2
Input signal
(R1-R2) 20 Ω…100 kΩ
0…1000% of input offset
Typ. 5ms response time
Output
Relay output, change-over contact
2 o. of channels
3 A @ 240 V AC, 3 A @ 24 V DC / 110 V AC
Settings
Potentiometer, 20 turns
1…25 % of max. input value
0…100 % of max. input value
General data
output x R1-R2 ion
High Offset: offset > signalling range
24 V DC ± 10 %
3 W @ 24 V DC tion
± 0.05 % of signal range
0 to 90 % (no condensation)
< 0.04 % / °C oefficient
0.1 % / 10,000 h
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusr provals
Output
Type y output, change-over contact
No. of channels
Switching current A @ 24 V DC / 110 V AC
Settings
Fine calibration 0 turns
Dead time vom max. Eingangswert
Range of adjustment nput value
General data
Transmit function
Options fset: offset > signalling range
Voltage supply n; 10 %
Power consumption
Repeat accuracy of signal range
Humidity % (no condensation)
Temperature coefficient
Long-term drift h
Impulse withstand voltage
Insulation voltage t / power supply
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Resistor input
Special adjustment
Note
Accessories
Note
D.120
Type
DPADRT 200M20-40M
DPA Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940017919
8944960000
Terminal
1
2
3
4
Signal
Not used
R1
R2
Common
11
12
13
14
15
16
D
D.121
Analogue signal conditioning
Analogue signal conditioning
MANN SERIES – Process alarms
Micromann R Series
Universal configurable module for alarm monitoring
Alarm modules from the Micromann R Series feature two relay
outputs with changeover contacts for the purpose of signal
monitoring. They come standard with configurable functions for
setpoint, deadband, high/low-trip switching behaviour, coil
energization and a variable timer delay on each channel.
D
The XFAR offers additional extensions to the standard functions.
This includes an optional alarm function which can be configured in connection with various input parameters, such as a
change in the signal frequency, signal loss or for individual signal formats. The XFAR is equipped with two alarm outputs for
more complex applications. Each can be secured individually.
Typical application of Micromann R
Supply
Liquid tank
24 V DC
Liquid level 4...20 mA
Input signal
tx
Storage area
alarm
UCVR
Supply
voltage
e.g. 240 V AC
Relay output
channel 1
Relay output
channel 2
Main alarm
Technical features:
Each product version is designed for a defined type of signal
and sensor. These types include analogue signals such as current, voltage, temperature (thermocouple and PT100 temperature detector), frequency and conductivity. Modules which have
temperature measuring inputs (PT100, thermocouple) are also
equipped with a wire-break detection mechanism.
The four-digit LED display can be universally scaled, so that
values can be displayed in any engineering unit. The selected
units are automatically applied for all parameters. The user
friendly software makes setting up operating parameters very
easy. Choose the settings you need using the display and the
keypad.
The modules are completely electrically isolated to 2 kV. They
can be snapped on to DIN TS 35 or TS 32 mounting rails. The
pluggable screw connection is located on the front.
D.122
• A wide variety of versions available for many types of input
signals
• Two alarm channel with LED status display relay contact
• LED display in engineering units
• Complete electrical isolation
• DC power supply
• Pluggable screw-connection mechanism
• Compact metal housing
Common technical data
Display
Type
Display range
Display value
Status indicator
Alarm output
Type
Number of channels
Switching current
Switching threshold
Hysteresis
Alarm function
Relay controlled
Reset
Dynamic hysteresis
General information
Supply voltage
Power input
Repeat accuracy
Humidity
Temperature coefficient
Long-term drift
Step response time
Scanning rate
Impulse withstand voltage
Isolation voltage
Data backup
Operating temperature / storage temperature
EMC standard
Approvals
Analogue signal conditioning
MANN SERIES – Process alarms
Connections
Four-digit, red LED, 7 mm
–999 to 9999
Percent or real-value displayed
Trip 1 / Trip 2 / Processor status
Changeover contact
2
1 A @ 240 V AC / 30 V DC (resistive load)
All values are programmable within the display range
> 1 display value
High alarm or
low alarm
Coil un-energized or energized, programmable
Automatic or manual
0...4200 sec.
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Housing
Signal
Depending on the
individual module
Inputs
Connections for
Configuration
changing setup
Supply voltage
+
NO contacts
Common
Alarm channel 1
NC contact
NO contacts
Common
Alarm channel 2
NC contact
PE connection direct on housing
12…50 V DC
6 W @ 24 V DC
± 0.05 % of signal range
0…90 % (no condensation)
≤ 0.02 % / °C
0.1 % / 10,000 h
320 ms (10...90 %)
programmable from 250 ms...32 s
5 per sec.
4 kV (1.2/50 μs)
2 kV between ports
≥ 100 years
0 °C...+60 °C / +25 °C...+70 °C
DIN EN 61326
CE, cULus
D.123
D
Analogue signal conditioning
MANN SERIES - Process alarms
Micromann R Series
UCVR
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Current / voltage monitoring
• Two alarm channels
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Conversion, isolation and filtering of analogue
signals
+24 V
10
NC
• Bi-polar inputs
H
0V
9
PS
24 V
1
Iin
2 +
0V
3
Vin
4 +
• Linear or quadratic input signal
D
V/I
Input
Analog current / voltage signals
-55…+55 mA / -55…+55 V
22 Ω (current input); 1 MΩ (voltage input)
1 μA / 1 mV per bit
1 mA or 1 V ceived measuring span [2]
Linear or √ xt]
24 V DC (up to 25 mA)
Display
Percentage or real value display
-999…9999 ge
0.001 of displayed value
General data
12…50 V DC ly
6 W @ 24 V DC tion
± 0.05 % of signal range
0…90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (10…90 %),
programmable from 250 ms...32 s
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrvals
Display
Display value real value display
Display range
Resolution isplayed value
General data
Voltage supply
Power consumption
Repeat accuracy of signal range
Humidity (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Impulse withstand voltage
Insulation voltage t / power supply
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
Terminal
1
2
3
4
5
6
mm2
mm
Note
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Relay output
Special adjustment
Note
Accessories
Note
D.124
Type
UCVR
UCV Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940010174
8945090000
NC
Ch 2
Common
NO
Connections
Input
Type og current / voltage signals
Input signal / -55…+55 V
Input resistance ent input); 1 MΩ (voltage input)
Resolution V per bit
Smallest received measuring span
Linearisation
Supply voltage 25 mA)
Common
NO
L
Technical data
Ch 1
Signal
24 V DC
Signal + Current
Signal –
Signal + voltage
Not used
11
12
13
14
15
16
Micromann R Series
UTCR
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Temperature monitoring (thermal converter)
• Two alarm channels
• External power supply
Analogue signal conditioning
MANN SERIES - Process alarms
• Pluggable connection terminals
• Compact enclosure
• Thermocouples type J, K, T, E, B, S, R
0V
NC
• Wire-break recognition
H
+24 V
10
9
• Temperature display in °C / °F
PS
2
• Cold-trap compensation
+
3
Ch 1
Common
NO
J
NC
Common
Ch 2
_
NO
L
Connections
Technical data
Input
Type mocouples (Type J, K, N, T, E, B, S, R) or mV
Input signal ranges
Input resistance, max.
Input
Thermocouples (Type J, K, N, T, E, B, S, R) or mV
9 adjustable ranges
1 kΩ stance, max.
Display
°C / °F or mV
Dependent on selected input type
1 °C / °F or 0.01 mV
General data
≤ 0.02 % / °C ambient temperature
12…50 V DC ly
6 W @ 24 V DC tion
± 0.05 % of signal range
0…90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (10…90 %),
programmable from 250 ms...32 s
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrvals
Display
Display value
Display range selected input type
Resolution or 0.01 mV
General data
Cold-junction compensation error ture
Voltage supply
Power consumption
Repeat accuracy of signal range
Humidity (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Impulse withstand voltage
Insulation voltage t / power supply
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
11
12
13
14
15
16
mm2
mm
Note
Terminal
1
2
3
4
5
6
Signal
Signal + mV
Signal – mV
Signal temperature
Cold-junction compensation
Not used
Thermocouples (Type J, K, N, T, E,
B, S, R) or mV signals
Input type
J
K
N
T
E
B
S
R
mV
Max. display range
highest
870 °C (1598 °F)
1372 °C (2502 °F)
1300 °C (2372 °F)
400 °C (752 °F)
700 °C (1292 °F)
1800 °C (3272 °F)
1768 °C (3214 °F)
1768 °C (3214 °F)
60 mV
lowest
–50 °C (–58 °F)
0 °C (32 °F)
–50 °C (–58 °F)
–50 °C (–58 °F)
–9,99 m
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Relay output
Special adjustment
Note
Type
UTCR
UTC Variabel
Qty.
1
1
Order No.
7760000017
8945130000
Additional input and output versions available on request
Accessories
Note
D.125
D
Analogue signal conditioning
MANN SERIES - Process alarms
Micromann R Series
URTR
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Temperature monitoring (RTD)
• Two alarm channels
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Processes 2- or 3-wire PT100 signals
0V
NC
• Compensation for the measurement lines
H
+24 V
10
9
• Temperature display in °C / °F
2
PS
A
3B
4 Bsense
D
Ch 1
NO
J
NC
Ch 2
PT 100
Connections
Input
Type 0 2-/ 3-wire
Input signal for 4 ranges
Line resistance in measuring circuit
Input
PT100 2-/ 3-wire
Configurable for 4 ranges
30 Ω ance in measuring circuit
Display
Dependent on selected range
°C / °F value
1 or 0.1 °C / °F
General data
< 0,05 % ngth compensation
12…50 V DC ly
6 W @ 24 V DC tion
± 0.05 % of signal range
0…90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (10…90 %),
programmable from 250 ms...32 s
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrvals
Display
Display range selected range
Display value
Resolution C / °F
General data
Cable-length compensation
Voltage supply
Power consumption
Repeat accuracy of signal range
Humidity (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Impulse withstand voltage
Insulation voltage t / power supply
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
Terminal
1
2
3
4
5
6
mm2
mm
Note
Ordering data
Relay output
Special adjustment
Note
Accessories
Note
D.126
Type
URTR
URT Variabel
Qty.
1
1
Additional input and output versions available on request
Not used
Max. display range
highest
lowest
700 °C
–200 °C
1292 °F
–328 °F
200,0 °C
–99,9 °C
400 °F
–99,9 °F
PE connection direct on enclosure
Type
Signal
Not used
A
B
B-Sense
2- or 3-wire PT100 RTD
(BS1904:1984 / IEC751:1983)
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
Order No.
7940011087
8945120000
Common
NO
L
Technical data
Common
Resolution
1 °C
1 °F
0,1 °C
0,1 °F
11
12
13
14
15
16
Micromann R Series
UHZR
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Frequency monitoring
• Two alarm channels
• External power supply
Analogue signal conditioning
MANN SERIES - Process alarms
• Pluggable connection terminals
• Compact enclosure
• Wide-range input
0V
1
2
3
4 +
5 –
6 +
H
L
NC
+ 12v
PS
Pull Up/Down
Ch 1
Common
NO
OV
f
Input
Input
NC
Ch 2
Common
NO
Vin (High)
11
12
13
14
15
16
Connections
Technical data
Input
Type rammable frequencies (no-bounce, no-voltage contacts)
Input signal
Input voltage
Smallest received measuring span
Sensor supply mA
Display
Display value real value display
Display range
Resolution isplayed value
General data
Voltage supply
Power consumption
Repeat accuracy of signal range
Humidity (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Impulse withstand voltage
Insulation voltage t / power supply
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
+24 V
10
9
• Supply of active input devices
mm2
mm
Note
Input
Programmable frequencies (no-bounce, no-voltage contacts)
0…10 kHz al
50 mV…250 V
0.001 Hz received measuring span [2]
12 V DC to 25 mA
Display
Percentage or real value display
-999…9999 ge
0.001 of displayed value
General data
12…50 V DC ly
6 W @ 24 V DC tion
± 0.05 % of signal range
0…90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (10…90 %),
programmable from 250 ms...32 s
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrovals
Terminal
1
2
3
4
5
6
Signal
12 V DC
Pull Up / Down
0V
Signal +
Signal –
High Signal +
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Relay output
Special adjustment
Note
Type
UHZR
UHZ Variabel
Qty.
1
1
Order No.
7940015213
8945100000
Additional input and output versions available on request
Accessories
Note
D.127
D
Analogue signal conditioning
MANN SERIES - Process alarms
Micromann R Series
CNDR
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Conductivity monitoring
• Two alarm channels
• External power supply
• Pluggable connection terminals
• Compact enclosure
• Suitable for all conductivity probes
0V
H
• Compensation for probe temperature
2
• Adjustable cell constant
3
Conductivity A
5 B
D
NC
PS
Conductivity B
4 A
• Linearized probe characteristic
+24 V
10
9
• Automatic measuring range selection
S/J
Display
Display value , mS/cm or °C
Display range selected input signal
Resolution μS / 0.01 mS / 0.1 °C
General data
Voltage supply
Power consumption
Repeat accuracy of signal range
Humidity (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Common-mode rejection (CMR) /sub>)
Impulse withstand voltage
Insulation voltage t / power supply
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Note
0 to 200 μS (0.1 μS resolution)
0 to 1000 / 5000 μS (1 μS resolution)
0 to 20 mS (0.01 mS resolution)0 to 200 °C (0.1 °C resolution)
20 % input range d measuring span [2]
≤ 6 Vss @ 400 Hz
0.01…99.99 / cm
< 2 % (up to 30 Ω)
Linear or user-defined, up to five measurement points
Display
μS, mS, μS/cm, mS/cm or °C
Dependent on selected input signal
0.1 μS / 1 μS / 0.01 mS / 0.1 °C
General data
12…50 V DC ly
6 W @ 24 V DC tion
± 0.05 % of signal range
0…90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (10…90 %),
programmable from 250 ms...32 s
40 dB CMRR (1.5 kVrms)
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrprovals
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Relay output
Special adjustment
Note
Accessories
Note
D.128
Type
CNDR
CND Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940017921
8944930000
Terminal
1
2
3
4
5
6
Common
NO
Connections
Input
Conductivity measurement and PT100 RTD
NC
Ch 2
6 Bsense
Input
Type fähigkeitsmessung und PT100 RTD
Input signal (0.1 μS resolution)
0 to 1000 / 50 0 to 20 mS (0.01 mS resolution)0 to 200 °C
(0.1 °C resolution)
Smallest received measuring span
Supply voltage s @ 400 Hz
Battery constant / cm
cable-length compensation >
Temperature compensation up to five measurement points
Common
NO
L
Technical data
Ch 1
Signal
Not used
A Conductivity
B Conductivity
A Temperature
B Temperature
B-Sense Temperature
11
12
13
14
15
16
Micromann R Series
XFAR
Universal, galvanically-isolated signal converters
with an alarm function and two setpoint
adjustments.
Current / voltage monitoring
• Two alarm channels
• External power supply
Analogue signal conditioning
MANN SERIES - Process alarms
• Pluggable connection terminals
• Compact enclosure
• Alarm triggered by rising or falling signal level
• Alarm when deviation occurs from desired
setpoint value
H
• Alarm suppression for each channel
• Suppression of alarm function for undefined
signal levels
L
+24 V
10
1
2
3
4
5
6
7
+ 24v
NC
PS
Iin
+0V
Ch 1
Common
NO
Vin
+
Ch 1 Inhibit pulse
+
Ch 2 Inhibit pulse
+ Inhibit pulse Com 0 V
V/I
NC
Ch 2
Common
NO
11
12
13
14
15
16
Connections
Technical data
Input
Type m- oder Spannungssignale
Input signal / -11…+11 V
Smallest received measuring span
Sensor supply o 25 mA)
Blocking pulse 40 V; Low: < 3 V>
Input resistance ent input); or 1 MΩ (voltage input)
Input
Current or voltage signals
Terminal
1
2
3
4
5
6
7
-22…+22 mA / -11…+11 V
2 mA or 1 V ceived measuring span [2]
24 V DC (up to 25 mA)
High: 4…40 V; Low: < 3 V
22 Ω (current input); or 1 MΩ (voltage input)
Display
Percentage or real value display
-999…9999 ge
0.001 of displayed value
General data
12…50 V DC ly
6 W @ 24 V DC tion
± 0.05 % of signal range
0…90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
320 ms (10…90 %),
programmable from 250 ms...32 s
4 kV (1.2/50 μs) d voltage
2 kV input / output / power supply
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusrprovals
Display
Display value real value display
Display range
Resolution isplayed value
General data
Voltage supply
Power consumption
Repeat accuracy of signal range
Humidity (no condensation)
Temperature coefficient
Long-term drift h
Step response time jump of 10…90 %),
programmable (250 ms…32 sec.)
Impulse withstand voltage
Insulation voltage t / power supply
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
0V
9
mm2
mm
Note
Signal
12 V DC
Signal + Current
Signal –
Signal + voltage
Channel 1 signal of external control (inhibit pulse)
Channel 2 signal of external control (inhibit pulse)
Inhibit pulse 0 V
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium enclosure / 500 g
120 x 46 x 97
PE connection direct on enclosure
Ordering data
Type
Relay output
Special adjustment
Note
Type
XFAR
XF Variabel
Qty.
1
1
Order No.
7940014450
8945150000
Additional input and output versions available on request
Accessories
Note
D.129
D
Analogue signal conditioning
MANN SERIES – Multi-Channel processing modules
Micromann Multiplus Series
Multi-channel signal converters/displays and alarm
monitors
Typical application of Micromann Mulitplus
Tank Farm – for
bulk storage
D
The Micromann Multiplus products allow to simultaneously
process multiple inputs, outputs and limit values. A series of
internal variables are used for this purpose. The variables are
calculated from the input signals. These variables can be used
for limit-value monitoring, for analogue/digital output, and for
visualization.
All products from the Multiplus Series are offered based on a
common platform. The individual versions differ in their definition of the specific input signal and its processing method.
The devices are configurable in English from the front panel
keypad or via the digital (RS422/485-Modbus) communications
port.
The Micromann Multiplus modules are available as AI8 (eightchannel current/voltage module) and RI4 (four-channel PT100
module). They have the following properties:
•
•
•
•
•
•
•
•
•
•
Calculate, monitor and display of each input
Up to four alarm channels
Up to two analogue outputs
RS422/485-Modbus RTU commnications (compatible with
the majority of software applications in industrial applications)
Configuration and DDE client/server software
Built-in suite of single- and multi-variable functions, including
the parameters for linearization, minimum, maximum, average, difference, sum and product
DC power supply
Complete electrical isolation
Highly accurate (typically 0.05 % of the signal range)
PIN numbers for protecting instrument calibration and configuration
D.130
Temperature
transmitter
Up to 8 x analogue inputs
24 V DC
4...20 mA
Level
transmitter
4...20 mA
24 V DC
Multiplus
AI8
AO1 = Lowest level
4...20 mA
Remote
PLC
AO2 = Average Temp
0...20 mA
RS485/MODBUS
Inventory computer
(Up to 4 x relay outputs)
Power for relay
e.g. 240 V AC
DO1 = Tank A
Hi Level alarm
Common technical data
Display
Type
Scaling
Number of displayed characters/digits
Display range
Units
Output
Type
Output current
Output voltage
Smallest received signal range
Number of channels
Alarm
Type
Number of channels
Type of contact
Specifications
Digital interface (optional)
Type
Protocol
Interface type
Baud rate
Parity
Slave ID
General information
Supply voltage
Power input
EMC standards
Humidity
Isolation voltage
Operating temperature / storage temperature
Approvals
Analogue signal conditioning
MANN SERIES – Multi-Channel processing modules
Connections
Display of input or input signals and internal variables
variable
16 digits / 2 rows / background lit
-99999 to +99999
58 defined, 4 user-defined
Display change of 2 to 20 sec. (auto-mode) or manual
Current or voltage output can be adjusted
(in proportion to the set function)
0...20 mA
0...10 V
2 mA or 1 V
0 or 2 (according to order)
Internal alarm via LED, or output signal to external controller
1 (standard) to 4 (according to type)
CO contacts
5 A @ 240 V AC or 24 V DC (resistive load)
Serial interface
Modicom Modbus RTU
RS485 / RS422
4800 / 9600 / 19200
No
1...247
12...50 V DC, other voltages on request
AI8 XXXX: 12 W / RI4 XXXX: 9,5 W
Tested for AS/NZS 3548/2064 (C-Tick), DIN EN 61826
10…90 % (no condensation)
2 kV between ports
0 °C ... 50 °C / –20 °C ... +60 °C
CE, cULus
Terminal
1-14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
Housing
Signal
Input signal, see layout
diagram for the A18 or
R14 module.
Signal +
Analogue Output
Current Channel 1
Voltage Signal +
Analogue Output
Current Channel 2
Voltage –
Power supply
+
Not used
Send signal
RS422/485*
Send signal +
Output
Receive signal +
(* Output for RS485
Receive signal –
ckass 24 & 27 and 25 & 26)
Not used
NC contact
Alarm channel 1
NO contacts
(Standard)
Common
NC contact
Alarm channel 2
NO contacts
(Optional)
Common
NC contact
Alarm channel 3
NO contacts
(Optional)
Common
NC contact
Alarm channel 4
NO contacts
(Optional)
Common
PE connection direct on housing
See notice for options. Order data is on following
pages.
D.131
D
Analogue signal conditioning
MANN SERIES – Multi-Channel processing modules
Micromann Multiplus Series
AI8
Multi channel signal transmitter / displays and limit
value monitoring
Analogue inputs
21
• Eight analogue inputs
• Current and voltage signal
• Power supply for up to eight input devices
H
• Bipolar inputs
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Vin/Iin (Ch 1)
Vin/Iin (Ch 2)
CH 1+2 0 V
Vin/Iin (Ch 3)
Vin/Iin (Ch 4)
CH 1+2 0 V
Vin/Iin (Ch 5)
Vin/Iin (Ch 6)
CH 5+6 0 V
Vin/Iin (Ch 7)
Vin/Iin (Ch 8)
Lh 7+8 0 V
0V
+24 V
V/I
RS485/
422
*Optional
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Current or voltage input
8
–22...+22 mA
–11...+11 V
22 Ω (current input) or 1MΩ (voltage input)
24 V DC ±10 % (up to 160 mA)
linear √, x2; x3/2, x5/2 or user-defined
1…99
120 dB / earth; 60 dB / 0 V
Functions
Variables
• Average of each input variable
• Max. input variable
• Min. input variable
• Difference between two input variables
• (E1 x E2 x E3 x E4) / (E5 x E6 x E7 x E8)
• (E1 - E2) x E3
> 0.02 % of input signal
< 0.005 % / °C at 100 % input variable
120...200 ms (10...90 %)
Accuracy
Temperature coefficient
Step response time
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
mm2
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS 32
Anodized aluminium housing / 850 g
120 x 106 x 96
Note
Ordering data
Type
Voltage
Voltage
Voltage
Voltage
Voltage
Accessories
Note
D.132
+
–
–
+
–
–
–
+
–
+
15
16
17
18
19
20
24
25
26
27
NC
Common
NO
NC
Common
NO
NC
Common
NO
NC
Common
NO
29
30
31
32
33
34
35
36
37
38
39
40
Vout/Iout
Iout
Vout
Vout/Iout
Iout
Vout
Send signal*
Send signal*
Receive signal*
Receive signal*
Ch 1
Ch 2*
Ch 3*
Ch 4*
Connections
Input
Type
Number of inputs
Input current limits
Input voltage limits
Input resistance
Feed voltage
Linearization
Attenuation factor
CMRR
Note
+24 V
V/I
L
Technical data
22
PS
• A variety of output types are available (refer to
the notice on ordering information)
D
0V
input/Current input
input/Current input
input/Current input
input/Current input
input/Current input
Special adjustment
Type
AI8 0042
AI8 2012
AI8 2042
AI8 2112
AI8 2142
AI8 Variabel
Qty.
1
1
1
1
1
1
Order No.
7940018245
7940018246
7940011206
7940018247
7940015938
8944900000
AI8 [1][2][3][4]: 1 = number of analogue outputs; 2 = number of digital
interfaces; 3 = number of relay outputs; 4 = –
Signal
Input 1 +
Input 2 +
Input 1/2 –
Input 3 +
Input 4 +
Input 3/4 –
Input 5 +
Input 6 +
Input 5/6 –
Input 7 +
Input 8 +
Input 7/8 –
0 V DC
24 V DC
Analogue inputs
Current/Voltage
Supply voltage
(field)
Micromann Multiplus Series
RI4
Multi channel signal transmitter / displays and limit
value monitoring
Temperature inputs RTD
0V
21
Ch 1
1
2
3
A
B
Bsense
Ch 2
4
5
6
A
B
Bsense
Ch 3
7
8
9
A
B
Bsense
Ch 4
10
11
12
A
B
Bsense
• Four temperature inputs
• PT100, Ni120, or Cu10 RTDs
• Automatic compensation for the
wire resistances
H
22
+24 V
PS
J
V/I
RS485/
422
Vout/Iout
Iout
Vout
Vout/Iout
Iout
Vout
Send signal*
Send signal*
Receive signal*
Receive signal*
Ch 1
Ch 2*
Ch 3*
Ch 4*
*Optional
• A variety of output types are available (refer to
the notice on ordering information)
L
Technical data
PT100 (1), Ni 120 (2), Cu 10 @ 0 °C (3), Cu 10 @ 10 °C (4)
4
1 = –220…+850 °C / 0.382 °C / 0.5 °C
1 = –220…+220 °C / 0.16 °C / 0.5 °C
2 = –80…+320 °C / 0.203 °C / 0.5 °C
3 = –60…+260 °C / 0.128 °C / 1.0 °C
4 = –60…+260 °C / 0.128 °C / 1.0 °C
Linearisation of temperature input value
1…99
120 dB / earth; 60 dB / 0 V
Linearization
Attenuation factor
CMRR
Functions
Values
• Average of each input variable
• Max. input variable
• Min. input variable
• Difference between two input variables
Refer to temp. of input range / resolution / accuracy
< 0.01 % / °C at 100 % input variable
120…200 ms (10...90 %)
Accuracy
Temperature coefficient
Step response time
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
+
–
–
+
–
–
–
+
–
+
15
16
17
18
19
20
24
25
26
27
NC
Common
NO
NC
Common
NO
NC
Common
NO
NC
Common
NO
29
30
31
32
33
34
35
36
37
38
39
40
Connections
Input
Type
Number of inputs
Temp. of input range / resolution / accuracy
mm2
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Signal
A
B
B-Sense
A
B
B-Sense
A
B
B-Sense
A
B
B-Sense
RTD input
Channel 1
RTD input
Channel 2
RTD input
Channel 3
RTD input
Channel 4
Not used
1.5 / 0.5 / 2.5
Screw connection / TS 35 + TS32
Anodized aluminium housing / 500 g
120 x 106 x 96
Note
Ordering data
Type
Temperature input
Temperature input
Temperature input
Special adjustment
Note
Type
RI4 0012
RI4 0042
RI4 2142
RI4 Variabel
Qty.
1
1
1
1
Analogue signal conditioning
MANN SERIES – Multi-Channel processing modules
Order No.
7940017071
7940018248
7940018250
8945050000
RI4 [1][2][3][4]: 1 = number of analogue outputs; 2 = number of digital
interfaces; 3 = number of relay outputs; 4 = –
Accessories
Note
D.133
D
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays for analogue signals
PMX420 Series
Universal, four-digit, current/voltage display
Typical application of PMX 420 Plus
Power supply
The current/voltage displays of the PMX420 Series are
available as a pure PMX420 display unit or optionally with
analogue outputs/four alarm outputs.
Relay output for Hi / Lo Level
PMX420
Agitator
Flow
Signalling contact
24 V DC
Alarm / Liquid level max.
4 ... 20 mA
Input
Return
Transmitter
The PMX420Plus adds four alarm channels (each with it’s own
status indicator and relay contact outputs) and a fully isolated
analogue current/voltage output.
137.0 mm
96.6 mm
44.7 mm
AL1
Wall thickness Max 18.0 mm
•
•
•
•
D.134
11 12 13 14 15 16 17 18 19 20 21 22
Terminals
1 2 3 4
5 6 7 8 9 10
45.0 mm ( +0. 6/-0.0 m m )
Cut-out
1 5. 5 m m
Four-digit digital LED display
Suitable for current and voltage signals
Bipolar inputs
Integrated square root function
Retrieval of min. and max. values
Integral power supply for active sensors
DC power supply
Complete electrical isolation
Four alarm channels and an analogue current/voltage output
(PMX420Plus)
LED alarm status indication
DIN-standard 1/8 front panel with IP65 protection
Decimal point can be adjusted to any position
Configurable via front-panel keypad
AL4
92.0 mm (+0.8/–0.0 mm)
Technical features:
•
•
•
•
•
•
•
•
•
AL3
15 .5m m
18.0 mm
AL2
60 .0 m m
Device functions can be configured, specifically for the
application, using the integrated keypad on the front panel.
There are also several other handy features like maximum and
minimum value recall, integrated linearization, an acoustic
alarm, a group alarm function, and the option for manual or
automatic alarm reset.
48.8 mm
143.5 mm
96. 6 mm
D
The basic model is suitable for displaying all normalized current
or voltage signals. The inputs signals are electrically isolated,
smoothed and scaled. An integrated power supply can be
used for supplying external sensors and input devices.
Common technical data
Display
Type
Display value
Display range
Status indicator
Input
Type
Input current limits
Input voltage limits
Input resistance
Resolution
Sensor current
Feed voltage
Attenuation factor
Functions
Values
General information
Supply voltage
Power input
Accuracy
Linearity
Repeat accuracy
Humidity
Temperature coefficient
Long-term drift
Cut-off frequency (-3 dB)
Step response time
Impulse withstand voltage
Isolation voltage
Data backup
Operating temperature / storage temperature
EMC standard
Approvals
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays for analogue signals
Connections
4 Digits, red LED, 14.2 mm
Percent or real-value displayed
9999 to +9999
Alarm channel 1-4; status LED
Current or voltage input is programmable
–22…+22 mA (preset for 4...20 mA)
–11…+11 V
25 Ω (current input) or 1.5 MΩ (voltage input)
4 μA / 2 mV
4…20 mA
24 V DC ±1.5 V DC (to 25 mA)
0…99; programmable digital filter
Linear or √
18...50 V DC, other voltages on request
8.5 W at 24 V DC
Typically ± 0.1 % of signal range
< 0.05 %
±0.02 of signal range
0...90 % (no condensation)
< 0.02 % / °C at 100 %
0.1 % / 10,000 h
5 Hz
300 ms (10...90 %)
4 kV (1.2/50 μs)
2 kV between ports
> 10 years without power supply
0 °C…60 °C / –25 °C…+70 °C
DIN EN 61326
CE, cULus
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Signal
–
+
+
–
Signal + sensor supply
Configuration
Signal + voltage input
Signal + current input
Signal 0 V
Not used
NC contact
Common
NO contacts
NC contact
Common
NO contacts
NO contacts
Common
NO contacts
Common
Signal +
Signal –
Supply voltage
High level
Supply voltage
Low level
Inputs
Alarm channel 1
(only PMX420Plus)
Alarm channel 2
(only PMX420Plus)
Alarm channel 3
(only PMX420Plus)
Alarm channel 4
(only PMX420Plus)
Analogue Output
(only PMX420Plus)
D.135
D
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays for analogue signals
PMX420 Series
PMX420
Universal, 4-digit current/voltage display
Display
• Display instrument for control panel installation
• 1/8 DIN standard front
• IP65 front protection
• Pluggable connection terminals
• Four-digit scalable display
• Single channel input
H
5 + 24 V
Vin
7
+
Iin
8
+ 0V
9
L
D
W
Technical data
Terminal
1
2
3
4
5
6
7
8
9
10
Not available
Residual ripple
Alarm
Type
Number of channels
Type of contact
Specifications
Not available
Isolation
Suppression of leakage current
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
mm2
1.5 / 0.5 / 2.5
Screw connection / panel assembly
Plastic housing / 480 g
137 x 96.6 x 48.8 mm
Note
Ordering data
Type
Voltage input/Current input
Special adjustment
Accessories
Note
D.136
PS
V/I
Connections
Output
Type
Scaling
Output current
Output voltage
Transmit function
Load resistance
Note
0V
4
+24 V
3
• Simple menu-driven configuration
Type
PMX420
PMX420 Variabel
Qty.
1
1
Order No.
7940018956
8945030000
Additional input/output range versions available on request
Signal
–
+
+
–
Signal + sensor supply
Configuration
Signal + voltage input
Signal + current input
Signal 0 V
Not used
Supply voltage
High level
Supply voltage
Low level
Inputs
PMX420 Series
PMX420Plus
Universal, 4-digit current/voltage display
Display with analogue output and four alarm
channels
• Display instrument for control panel installation
• 1/8 DIN standard front
• IP65 front protection
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays for analogue signals
• Pluggable connection terminals
• Four-digit scalable display
4
3
7
8
9
L
PS
+24 V
5
• Single channel input
H
0V
+24 V
Ch 1 (opt)
• Simple menu-driven configuration
+
Vin
V/I
Ch
V/I
2 (opt)
Ch 3 (opt)
Iin
Ch 4 (opt)
0V
NO
NC
Common
NO
NC
Common
NO
NC
Common
NO
Vout/Iout
Iout
Vout
W
Technical data
NC
Common
+
–
–
13
14
15
16
17
18
19
20
21
22
23
24
2
3
5
Connections
Output
Type
Scaling
Output current limits
Output voltage limits
Transmit function
Load resistance
Programmable voltage or current output
variable
0…22 mA
0…11 V
Direct or reverse
850 Ω @ 20 mA (current output) / > 500 Ohm
(current output)
20 mVss
Residual ripple
Alarm
Type
Number of channels
Type of contact
Specifications
Internal alarm via LED, or output signal to external controller
4
2 CO and 2 NO
3 A @ 240 V AC (NO / CO)
3 A @ 24 V DC (CO), 3 A @ 24 V DC (NO)
2 kV between ports
internal
Isolation voltage
Suppression of leakage current
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
mm2
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Signal
–
+
+
–
Signal + sensor supply
Configuration
Signal + voltage input
Signal + current input
Signal 0 V
Not used
NC contact
Common
NO contacts
NC contact
Common
NO contacts
NO contacts
Common
NO contacts
Common
Signal +
Signal –
Supply voltage
High level
Supply voltage
Low level
Inputs
Alarm channel 1
Alarm channel 2
Alarm channel 3
Alarm channel 4
Analogue Output
1.5 / 0.5 / 2.5
Screw connection / panel assembly
Plastic housing / 480 g
137 x 96.6 x 48.8 mm
Note
Ordering data
Type
Voltage input/Current input
Special adjustment
Note
Type
PMX420Plus
PMX420 Variabel
Qty.
1
1
Order No.
7940018957
8945030000
Additional input/output range versions available on request
Accessories
Note
D.137
D
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays for temperature
PMX400 Series
Four-digit temperature and frequency display with
analogue-value read-out and alarm monitoring
Typical application of PMX400
Gas phase outlet
Remote
PLC/SMS
The PMX400 Series consists of two modules:
Mixture inlet
Separator
RTD
• Temperature display
• Frequency display / tachometer
Liquid phase outlet
Heater
Contactor
Input
A variety of temperature or frequency signals can be
processed. On the output side, optional analogue signals are
available, as well as either two or four relay contacts for alarm
monitoring. The PMX400 HZX frequency display module offers,
as default, two open-collector outputs as the relay contacts.
The outputs are designated for the alarm function. An integrated power supply can be used for supplying external sensors
and input devices.
4...20 mA output
PMX400
TMP
Output Relay
Channel 2
DC Power Supply
Relay Supply
e.g. 240 V AC
Output Relay
Channel 1
Low temp alarm
137.0 mm
96.6 mm
44.7 mm
48.8 mm
143.5 mm
Technical features:
AL1
D.138
AL3
AL4
60 .0 m m
Cut-out
11 12 13 14 15 16 17 18 19 20 21 22
Terminals
1 2 3 4
5 6 7 8 9 10
45.0 mm ( +0. 6/-0.0 m m )
92.0 mm (+0.8/–0.0 mm)
1 5. 5 m m
• Four-digit digital LED display
• Up to four alarm channels and an analogue current/voltage
output
• Retrieval of min. and max. values
• Integral power supply for active sensors
• DC power supply
• Complete electrical isolation
• LED alarm status indication
• DIN-standard 1/8 front panel with IP65 protection
• Decimal point can be adjusted to any position
• configurable via front-panel keypad
Wall thickness Max 18.0 mm
AL2
15 .5m m
18.0 mm
96. 6 mm
D
Common technical data
Display
Type
Display value
Display range
Status indicator
Output
Type
Scaling
Output signal limits
Load resistance
Residual ripple
Transmit function
General information
Accuracy
Linearity
Repeat accuracy
Humidity
Temperature coefficient
Long-term drift
Cut-off frequency (-3 dB)
Impulse withstand voltage
Isolation voltage
Data backup
Operating temperature / storage temperature
EMC standard
Approvals
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays for temperature
Connections
Four-digit, red LED, 14.2 mm
Percent or real-value displayed
-9999 to +9999
Alarm channel 1-4; Status LED
Current or voltage output
Variable
0…20 mA or 0…11 V
≤ 850 Ω (current), ≥1 MΩ (voltage)
< 20 mVss
direct or reverse
Typically ± 0.1 % of signal range
≥ 0.05 %
± 0.02 % of signal range
0...90 % (no condensation)
≤ 0.02 % / °C
0.1 % / 10,000 h
5 Hz
4 kV (1.2/50 μs)
1 kV between ports
≥ 100 years (without power supply)
0 °C…60 °C / –25 °C…75 °C
DIN EN 61326
CE, cULus
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
8
9
10
11
12
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Signal
–
+
Signal +
Signal - current
Supply voltage.
Analogue output
(only for AO version)
D
Optional, depending on type
NO contacts
Common
NC contact
NO contacts
Common
NC contact
Alarm channel 1
(only for 4RO version)
Alarm channel 2
(only for 4RO version)
Depending on the individual module
D.139
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays for temperature
PMX400 Series
PMX400TMP
• Suitable for PT100, thermocouple and mV input
signals
• Automatic sensor recognition
• Temperature measurement and monitoring in
°C or °F
• No additional adjustments needed
• Automatic compensation for PT100
measurement leads
• Cold-junction compensation for thermocouple
inputs
• Display instrument for control panel installation
9
L
11
Bsense
A 12
CJC
W
Thermocouple
Technical data
Voltage input / current input
°C, °F or mV
Input
Type
Input signal
Cold-junction compensation
Cable-length compensation
Alarm
Type
Switching current
Insulation voltage
General information
Supply voltage
Power input
Step response time
Scanning rate
Attenuation factor
Functions
Thermocouple, PT 100 RTD or mV
Configurable for 10 ranges
Automatic
Automatic
Status relay, CO contact
3 A @ 240 V AC, 3 A @ 24 V DC (resistive load)
1 kV between ports
20…28 V DC
6 W @ 24 V DC
300 ms (10...90 %)
5 per sec.
0...99, programmable digital filter
AO: with analogue output
RO: with alarm channels
DIN EN 61326
CE, cULus
EMC standard
Approvals
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
mm2
Note
1.5 / 0.5 / 2.5
Screw connection / panel assembly
Anodized aluminium housing / 500 g
137 x 96.6 x 48.8 mm
Monitoring of the analogue/alarm outputs is possible with the basic
software, without any additional adjustments. Adjustments can be
optionally carried out via additional pluggable PCB.
Setup and calibration are made with the front-panel keypad
Type
without analogue/alarm output
with analogue/alarm output
Special adjustment
D.140
mV
J
V/I
Ch 3 (opt)
Ch 4 (opt)
NC
Common
NO
NC
Common
NO
NC
Common
NO
NC
Common
NO
Vout/Iout
Iout
Vout
RTDS
Type
PMX400TMP
PMX400TMP 4RO/AO
PMX400 Variabel
Terminal
1
Signal
–
2
3
4
5
6
7
8
9
10
11
12
8
9
10
11
12
8
9
10
11
12
13
14
15
16
17
18
19
+
Signal +
Signal - current
Signal - voltage
Connections for
changing setup
20
21
22
23
24
Ordering data
Note
Ch 2 (opt)
+
–
–
13
14
15
16
17
18
19
20
21
22
23
24
2
3
5
Connections
Display
Type
Display value
Accessories
PS
B 10
–
Note
+24 V
+
• Pluggable connection terminals
D
2
Ch 1 (opt)
8
• IP65 front protection
H
0V
1
• 1/8 DIN standard front
Qty.
1
1
1
Order No.
7940017862
7940012968
8945020000
Additional input/output range versions available on request
Cold-junction
compensation
Supply voltage
Analogue output
(only for AO version)
Configuration
Thermocouple inputs
Not used
Not used
B
B-Sense
A
RTD inputs
Not used
mV Signal mV Signal +
Not used
NO contacts
Common
NC contact
NO contacts
Common
NC contact
NO contacts
Common
NC contact
NO contacts
Common
NC contact
mV inputs
Alarm channel 1
(only for 4RO version)
Alarm channel 2
(only for 4RO version)
Alarm channel 3
(only for 4RO version)
Alarm channel 4
(only for 4RO version)
Thermocouple (type J, K, N, T, E,
B, S, R), RTD or mV signals
Input Type
J
K
N
T
E
B
S
R
RTD
mV
Max. display range
highest
lowest
870 °C (1598 °F)
1372 °C (2502 °F)
1300 °C (2372 °F)
–50 °C (–58 °F)
400 °C (752 °F)
700 °C (1292 °F)
1800 °C (3272 °F)
0 °C (32 °F)
1768 °C (3214 °F)
–50 °C (–58 °F)
1768 °C (3214 °F)
–50 °C (–58 °F)
820 °C ( 1508 °F)
–220 °C (-364 °F)
200 mV
–200 mV
PMX400 Series
PMX400HZX
• Display instrument for control panel installation
• 1/8 DIN standard front
• IP65 front protection
• Pluggable connection terminals
• Frequency measuring and monitoring
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays for temperature
• Integral power supply for external sensors
• Two outputs for limit-value monitoring
• De-bouncing of switched input impulses
The frequency display on the PMX400HZX can
process the following input signals:
•
•
•
•
•
•
H
L
W
+24 V
2
Vout/Iout
9
Three-wire NPN/PNP
NPN/PNP open-collector
TTL logic
Solid-state switch
No-voltage contacts
Additional voltage pulses
0V
1
12
+
+
(opt)
0V
Alarm Ch 1
0V
10
11
PS
Pull up/down
f
fin
V/I
com
Alarm Ch 2
NC
Ch 3*
+12 V
Common
NO
NC
Ch 4*
Common
NO
Technical data
3
4
5
6
7
13
14
15
16
17
Connections
Display
Type
Display value
Voltage input / current input
Percent or real-value displayed
Input
Type
Input signal
Sensor supply
Input voltage
Alarm (channel 1/2)
Type
Function
Max. Switching current
Alarm (channel 3/4)
Type
Switching current
Isolation
General information
Supply voltage
Power input
Step response time
Attenuation factor
Functions
Programmable frequencies
Configurable for 4 ranges
12 V DC (up to 25 mA)
50 mV…250 V AC or 3...250 V DC
Transistor output
"ON" = 0 V
200 mA "ON", 50 V DC "OFF"
Relay contact (changeover)
3 A @ 240 V AC, 3 A @ 24 V DC (resistive load)
1 kV between ports
24 V DC ±10 %
6 W @ 24 V DC
220 ms (10...90 %)
0..99, programmable digital filter
AO: with analogue output
RO: with alarm channels
DIN EN 61326
CE, cULus
EMC standard
Approvals
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
mm2
Note
Terminal
1
Signal
–
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
+
Signal +
Signal –
Common
Channel 1
Channel 2
Configuration
Pull up / pull down
Signal –
Signal +
12 V DC
Common
NC contact
NO contacts
Common
NC contact
NO contacts
Input
range
0…9.999 Hz
0…99.99 Hz
0…999.9 Hz
0…9999 Hz
Supply voltage
Analogue output
(only for AO version)
Alarm channel 1 and 2
(only for 4RO version)
Inputs/Configuration
(Set-up: 12/8 connection)
Alarm channel 3
(only for 4RO version)
Alarm channel 4
(only for 4RO version)
Offset
Resolution
0…9.998 Hz
0…99.98 Hz
0…999.8 Hz
0…9998 Hz
0.001 Hz
0.01 Hz
0.1 Hz
1 Hz
1.5 / 0.5 / 2.5
Screw connection / panel assembly
Anodized aluminium housing / 500 g
137 x 96.6 x 48.8 mm
Monitoring of the analogue/alarm outputs is possible with the basic
software, without any additional adjustments. Adjustments can be
optionally carried out via additional pluggable PCB.
Setup and calibration made with front-panel keypad
Ordering data
Type
without analogue/alarm output
with analogue/alarm output
Special adjustment
Note
Type
PMX400HZX
PMX400HZX 4RO/AO
PMX400 Variabel
Qty.
1
1
1
Order No.
7940015595
7940011979
8945020000
Additional input/output range versions available on request
Accessories
Note
D.141
D
DI350
3 V-digit digital display with auxiliary power
Typical application of DI350
The DI350 is an inexpensive 3 V-digit digital display for
analogue current and voltage signals, for use in industrial
applications. With this display, analogue signals from 4...20 mA
or 0...10 V can be displayed.
+ 24 V
0V
DI350
4 ... 20 mA = 0-150.0 kl
or %
– Input
+ Input
Tank container
An integrated regulated power supply can be used to supply
two-wire transmitters.
Power supply
Transmitter [dB]
The decimal point can be moved to any of the positions
(1.XXX, 1X.XX, 1XX.X or 1XXX) so that it can display values in
any range.
Wiring diagramm DI350
0V
+24 V
7
The bright seven-segment LEDs are easily visible even in weak
lighting. The special filtering properties of the front face give it a
wide viewing angle.
1
2
3
4
The DIN-standard 1/8 front panel with IP65 protection ensures
reliable operation in wet areas. The connection uses pluggable
screw-connection elements.
8
PS
+ 24 V
0V
Vin/Iin
V/I
0V
Connections
Terminal
1
2
3
4
5
6
7
8
Signal
24 V DC
power supply sensor
0 V DC
power supply sensor
Input signal +
Input signal –
Inputs
Not used
L–
L+
Supply voltage
137.0 mm
96.6 mm
48.8 mm
44.7 mm
143.5 mm
Wall thickness Max 18.0 mm
92.0 mm (+0.8/-0.0 mm)
15.5mm
60.0 mm
15.5mm
18.0 mm
96.6 mm
D
D.142
Cut-out
45.0 mm (+0.6/-0.0 mm)
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays
DI350
DI350
DI350
Display with voltage inputs
Display with current inputs
• Integrated power supply for external sensors
• Integrated power supply for external sensors
• Linearity with an accuracy of 0.1% of the
measuring range
• Linearity with an accuracy of 0.1% of the
measuring range
• Complete electrical isolation
• Complete electrical isolation
• Display instrument for control panel installation
• 1/8 DIN standard front
• 31/2 Digits
Analogue signal conditioning
MANN SERIES - Indicators and configurable displays
• IP65 fully insulated
• Pluggable connection terminals
H
L
D
W
Technical data
Input
Type og voltage signals
Input signal
Input resistance
Supply voltage 25 mA)
Display
Type digits, red LED, 14.2 mm
Display range 1999
Display value real value display
Format / decimal point: 1.000, 100.0, 10.00
Settings
Fine calibration 2 turns
Offset n; 1200 digital steps
Range of adjustment teps
General data
Voltage supply 35 V DC)
Power consumption
Linearity ypically
Humidity (no condensation)
Temperature coefficient
Long-term drift h
Step response time
Impulse withstand voltage
Insulation voltage y
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Input
Analog voltage signals
Input
Analog voltage signals ls
0…10 V gnal
1 MΩ stance
24 V DC (up to 25 mA)
Display
3.5 digits, red LED, 14.2 mm
-1999…1999
Percentage or real value display
1-line / decimal point: 1.000, 100.0, 10.00
Settings
Potentiometer, 22 turns
± 1200 digital steps
20 - 2100 digital steps
General data
24 V DC (12…35 V DC)
6 W @ 24 V DC tion
< 0.1 % typically
0…90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
200 ms (10…90 %)
4 kV (1.2/50 μs) d voltage
1 kV input / supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULus provals
4…20 mA nal
22 Ω stance
24 V DC (up to 25 mA)
Display
3.5 digits, red LED, 14.2 mm
-1999…1999
Percentage or real value display
1-line / decimal point: 1.000, 100.0, 10.00
Settings
Potentiometer, 22 turns
± 1200 digital steps
20 - 2100 digital steps
General data
24 V DC (12…35 V DC)
6 W @ 24 V DC tion
< 0.1 % typically
0…90 % (no condensation)
≤ 0.02 % / °C ficient
0.1 % / 10,000 h
200 ms (10…90 %)
4 kV (1.2/50 μs) d voltage
1 kV input / supply
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULus provals
1.5 / 0.5 / 2.5
Screw connection
Plastic enclosure / 480 g
137 x 96.6 x 48.8
1.5 / 0.5 / 2.5
Screw connection
Plastic enclosure / 480 g
137 x 96.6 x 48.8
Note
Ordering data
Type
Voltage/current input
Special adjustment
Note
Type
DI350 0-10V/0-100.0
DI350 Variabel
Qty.
1
1
Additional input and output versions available on request
Order No.
7940011570
8944950000
Type
DI350 4-20mA/0-100.0
DI350 Variabel
Qty.
1
1
Order No.
7940010185
8944950000
Additional input and output versions available on request
Accessories
Note
D.143
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays
LPD350
3 1/ -digit digital display, in loop-powered (two-wire)
design
2
The LPD350 is a compact, cost effective, 3 1/ digt digital
indicator designed specifically for current loop signals. The
decimal point can be moved to any position (1.XXX, 1X.XX,
1XX.X or 1XXX) so that it can display values in a range of
±1999.
Typical application of LPD350
LPD350
2
Input 24 V DC
4 ... 20 mA
Temperature
probe
WAVEPak
Isolator
Output
4 ... 20 mA
PLC
D
The LPD350 uses a liquid crystal display which can be read
even under poor lighting conditions.
Power supply
No additional wiring is needed for a power supply. The user can
simply break the loop and connect to the LPD350.
75 mm
96.6 mm
44.7 mm
The housing has a DIN-standard 1/8 front panel with IP65
protection. The connection uses pluggable screw-connection
elements.
48.8 mm
65 mm
18.0 mm
Panel thickness max 18.0 mm
Technical features:
Large 3 1/ -digit digital LED display
4...20 mA input
Loop-powered two-wire design (125 Ω loop load)
Direct or reverse-action display
Linearity is ± 0.1 % of the corresponding signal range
DIN-standard front-panel with IP65 protection
Pluggable screw-connection mechanism
D.144
91 mm
96.6 mm
2
Cut-out
45.0 mm (+0.6/-0.0 mm)
92.0 mm (+0.8/-0.0 mm)
•
•
•
•
•
•
•
LPD350
LPD350
Current input
• Display instrument for control panel installation
• 1/8 DIN standard front
• 31/2 Digits
Analogue signal conditioning
MANN SERIES - Indicators and configurable displays
• IP65 fully insulated
• Pluggable connection terminals
H
I
2
Iin
1
0V
L
D
W
Connections
Technical data
Input
Type ent input
Input current
Voltage drop A
Input resistance
Input current, max. 00 mA for 10 sec.
Input current, max. when wired incorrectly
Input
Current input
4…20 mA rent
2.5 V @ 20 mA
125 Ω ance
100 mA constant / 500 mA for 10 sec.
500 mA constant max. when wired incorrectly
Display
3.5 digits, black LCD with clear background, 12.7 mm
-1999…1999
1-line
Settings
Potentiometer, 20 turns
± 1999 digital steps in two switching ranges
0…3998 in three switching ranges
General data
± 0.05 % from signal range ± 1 digital step
± 0.05 % of signal range
Offset ± 0,1 digital steps per °C
Adjustment range ± 0,1 digital steps per °C
200 ms (10…90 %)
2.5 x per sec.
-20 °C…+70 °C/-25 °C…+85 °C emperature
DIN EN 61326 s
CE; cULusprovals
Display
Type digits, black LCD with clear background, 12.7 mm
Display range 999
Format
Settings
Fine calibration 0 turns
Offset n; 1999 Digitalschritte in zwei Schaltbereichen
Range of adjustment haltbereichen
General data
Accuracy 0.05 % from signal range ± 1 digital step
Repeat accuracy of signal range
Temperature coefficient italschritte pro °C
Einstellbereich ± 0,1 Digitalschritte pro °C
Step response time
Sampling rate .
Operating temperature/Storage temperature
EMC standards
Approvals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
mm2
mm
Terminal
1
2
Signal
Input –
Input +
1.5 / 0.5 / 2.5
Screw connection / Control panel assembly
Plastic enclosure / 480 g
75 x 96.6 x 48.8
Note
Ordering data
Type
Current input
Special adjustment
Note
Type
LPD350 4-20mA/0-100.0
LPD350 Variabel
Qty.
1
1
Order No.
7940010163
8944990000
Additional input and output versions available on request
Accessories
Note
D.145
Analogue signal conditioning
MANN SERIES – Indicators and configurable displays in IP67 for field mounting
LPD450F
Intrinsically safe 4 1/ -digit digital display, in
loop-powered (two-wire) design for field mounting
2
The LPD450F is a field instrument which permits the universal
display of process variables.
D
Typical application of LPD450F
4...20 mA current loop /
two-wire
LPD450F display and
flow measurer
Measurement
24 V DC
PLC control
level /
enterprise
management
level
probe
(hall sensor)
The display is loop powered by the 4...20 mA current loop with
no external supply required. The twenty-mm LCD displays can
be read even under poor light conditions.
A sheet of perforated self-adhesive labels comes included in
delivery. They include standard engineering units and can be
used for all label needs. Traffolyte labels are also available as an
option for both engineering units and tag numbers.
Open liquid flow,
container, tube lines
140 mm
65 mm
Mounting holes: 60 mm
Optionally available is a pipe mounting bracket which can be
used for horizontal and vertical mounting.
80 mm
The electronic subassembly is housed in a rugged, glass
reinforced polycarbonate, IP67 case. This housing is suitable for
any industrial environment.
P
Technical features:
70 mm
18 mm
•
•
•
•
•
•
Big 20 mm LCD dispaly
4...20 mA inputs (two-wire loop-powered)
Integrated signal linearization (√, x3/2, x5/2 or user-defined)
Min./max. value display feature
IP67 protection
Pipe mount bracket option
D.146
Mounting holes: 120 mm
LPD450F
LPD450F
Current input
• Display instrument for outdoor use
• 41/2 Digits
• IP67 fully insulated
Analogue signal conditioning
MANN SERIES - Indicators and configurable displays in IP67 for field monting
• Optionally available with fixing clips for pipe
mounting
Iin
H
I
0V
L
D
W
Mounting sketch
Technical data
Input
Input current
Transmit function 2, x5/2 or programmable (2-21 steps)
Input
4…20 mA rent
√ , x3/2, x5/2 or programmable (2-21 steps)
Display
Type character, black LCD with clear background, 20 mm
Display value real value display
Display range 9 (0.00…100.00 factory setting)
Decimal point , 18.888, 188.88, 1888.8
General data
Voltage supply owered, via a 4…20 mA input
Voltage drop
Accuracy 0.05 % from signal range ± 1 digital step
Repeat accuracy of signal range
Temperature coefficient / °C
Adjustment range ± 0.1 digital steps or 0.01 % / °C
Humidity % (no condensation)
Step response time steps from 1…30 sec.
Sampling rate
Change of display
Data backup ars
Operating temperature/Storage temperature
EMC standards
Approvals
Display
4.5-character, black LCD with clear background, 20 mm
Percentage or real value display
±19.999 (0.00…100.00 factory setting)
18888, 1.8888, 18.888, 188.88, 1888.8
General data
Loop-current powered, via a 4…20 mA input
< 4.3 V drop
± 0.05 % from signal range ± 1 digital step
± 0.01 % of signal range
Offset ± 0.01 % / °C
Adjustment range ± 0.1 digital steps or 0.01 % / °C
10 to 90 % (no condensation)
Programmable in 99 steps from 1…30 sec.
16 x per sec.
2 x per sec. splay
≥ 100 years
0 °C…+60 °C/-25°C…+70°C ge temperature
DIN EN 61326 s
CE; cULusprovals
Data of Housing
Clamping range (rating- / min. / max.)
Type of connection / Terminal rail
Type of Housing / Weight
Length x width x height
1.5 / 0.5 / 2.5
Screw connection
Plastic enclosure / 500 g
65 x 140 x 80
mm2
mm
Pipe mount bracket (can
be fitted to suit a vertical
or horizontal pipe)
Note
Ordering data
Type
Current input
Special adjustment
Note
Type
LPD450F 4-20mA
LPD450F Variabel
Qty.
1
1
Order No.
7940010236
8945000000
Additional input and output versions available on request
Accessories
Note
Fixing clip
Pipe Mount Kit - 7940010667
D.147
AMS400A
Universal auto-manual station
Typical application of AMS400A
The AMS400A module is an interface device which can be
used between control units and devices in the field. It carries
out manual take-over of automatically controlled processes.
Proportional 4 to 20 mA output
Digital high/
low output
from PLC
AMS400A
Typical applications are:
• Manual start-up of sensitive processes before handover to
automatic control
• Manual over-ride in case of controller failure or malfunction.
Status output
automatic/manual
The AMS400A offers three different I/O configurations, which
serve as interfaces between:
137.0 mm
96.6 mm
48.8 mm
AUTO
Panel thickness max 18.0 mm
D.148
MAN
ENT
92.0 mm (+0.8/-0.0 mm)
15.5 mm
During analogue-analogue operating mode, it is possible to use
the digital outputs for switching between manual and automatic
operations. Ramp rates and additional handover modes can be
set globally in order to output signals to external controllers.
15.5 mm
18.0 mm
60.0 mm
• Analogue control equipment and analogue control devices
• Digital control equipment and analogue control devices
• Digital control equipment and digital control devices
44.4 mm
143.5 mm
96.6 mm
D
Acknowledge
4 to 20 mA input
PLC
PLC
sensor,
etc.
Cutout
45.0 mm (+0.6/-0.0 mm)
Analogue signal conditioning
MANN SERIES – Universal auto-manual stations
AMS400A
AMS400A
Universal interface device
• 1/8 DIN standard front
• IP65 front protection
• Pluggable connection terminals
1
11
H
12
8
9
L
10
0V
Vin/Iin
2
PS
0V
V/I
Common
Signal amplifier
+24 V
Vout/Iout
0V
0V
Automatic / manual
Change operating mode
NC
Common
NO
NC
Common
NO
Signal reduction
W
Technical data
3
4
5
6
7
13
14
15
16
17
18
Analogue signal conditioning
MANN SERIES – Universal auto-manual stations
Connections
Display
Type
Display value
Display range
Status indicator
Input
Type
Digits, red LED, 14.2 mm
Percent or real-value displayed
–9999 bis +9999
Operating mode (auto./manual)
Input current limits
Input resistance (mA / V)
Scanning rate (current input)
Pulse width, min. (digital input)
Output
Type
Analogue output
Digital output
Signalling contact (RO version only)
Output current limits
Output voltage limits
Load resistance
Residual ripple
Alarm (RO version only)
Type
Number of channels
Type of contact
Specifications
Isolation
General information
Supply voltage
Power input
Accuracy
Linearity
Repeat accuracy
Humidity
Temperature coefficient
Long-term drift
Cut-off frequency (–3 dB)
Step response time
Impulse withstand voltage
Isolation voltage
Data backup
Operating temperature / storage temperature
EMC standards
Approvals
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
Current input or digital input (pulse-controlled or no-voltage
contact)
0…24 mA / 0…12 V DC
50 Ω / 10 MΩ
5 per sec.
64 ms
Analogue and digital output
Voltage or current, adjustable via jumper
Opto, 50 V DC / 200 mA
Status relay
0… 24 mA
0…18 V
900 Ω @ 20 mA
20 mVss
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Signal
–
+
Signal +
Signal –
Signal – 0 V
Automatic / manual
Change operating mode
Common
Signal amplifier
Signal reduction
Signal +
Signal –
NC contact
Common
NO contacts
NC contact
Common
NO contacts
Supply voltage
Analogue Output
D
Status outputs
Digital inputs
Analogue inputs
Relay output,
signal amplifier
Relay output,
signal reduction
Status relay
2
CO contacts
3 A @ 240 V AC or 5 A @ 24 V DC
1,5 kV channel / channel
24 V DC ± 10 %, other voltages on request
6 W @ 24 V DC
typ. ±0,1 % of signal range
< 0,05 %
±0,02 of signal range
0…90 % (no condensation)
< 0.02 % / °C
0.1 % / 10.000 h
5 Hz
300 ms (10...90 %)
4 kV (1.2/50 μs)
1 kV between ports
> 10 years without power supply
0 °C to 60 °C / –25 °C to +70 °C
DIN EN 61326
CE, cULus
mm2
Note
1.5 / 0.5 / 2.5
Screw connection / panel assembly
Plastic housing / 480 g
137 x 96.6 x 48.8 mm
Additional input/output versions available on request.
Ordering data
Type
Analogue Output
Analogue and relay output
Special adjustment
Type
AMS400A 4-20mA/AO
AMS400A 4-20mA/AO/RO
AMS400 variable
Qty
1
1
1
Order No.
7940011895
7940015937
8945000000
Note
D.149
PTX800 Series
Panel-mounted totaliser/counter/rate monitor
Typical application of PTX800
The configurable monitors of the PTX800 Series are available in
two designs:
12 DC sensor supply PTX800D
Pulse input
• PTX800A for analogue current/voltage flow quantity
measurements
• PTX800D with digital inputs (NAMUR, NPN/PNP sensors,
TTL, etc)
Output Control
Relay 1
Remote
PLC/SMS
Remotel „Reset“
Output Control
Relay 2
Liquid flow
Positive Displacement
Flowmeter
The eight-digit LED rate/toal display can be changed via a
button on the front of the unit. Both versions make use of
output relays to close values when the "total" setpoint is
reached. They also have electrically-isolated analogue outputs
for re-transmission.
The PTX800D can be connected on the input side to all
standard initiators (NPN/PNP/Namur) and with other
current/voltage transmitters. The monitor will accept any
periodic signal type and can total the input pulses into a "total"
display.
It can also calculate the resulting flow rate. External proximity
switches can be supplied with 12 V DC directly from the
PTX800D.
44.7 mm
PGM
PGM
ENT
ENT
18.0 mm
Wall thickness Max 18.0mm
AL1
AL2
TOTAL
RATE
60.0 mm
Cut-out
Technical Features
•
•
•
•
•
•
•
•
•
•
•
•
•
RESET
92.0 mm (+0.8/-0.0 mm)
15.5 mm
Gasket
•
D.150
96.6 mm
143.5 mm
15.5 mm
The PTX800A counter processes standardized analogue
current and voltage signals. Linearization and fittering functions
are available for processing measurement signals. In addition,
the counter has a 24 V DC power supply for loop-powered
sensors.
137.00 mm
48.8 mm
The display can be globally scaled based on the flow quantity
per second, minute, hour or day. The flow-quantity counter can
be multiplied by factors of 0.001, 0.01, 0.1, 1, 10, 100 oder
1000. This allows for best use of the display.
Control valves
96.6 mm
D
4...20 mA output
Display of the flow quantity/rate
Easily-readable eight-digit LED display
Up to two outputs for alarm monitoring or control
Optional analogue output
Pulse output
Reset function can be controlled locally or remotely,
for fill-quantity monitoring (batching)
The most recent measured value is stored in case of
a power outage
DC power supply
LED display for values outside of range
Complete electrical isolation
DIN-standard 1/8 front panel with IP65 protection
Integrated power supply for initiators
Changing the device configuration is possible without
performing a new calibration
No internal adjustments needed
45.0 mm (+0.6/-0.0 mm)
Analogue signal conditioning
MANN SERIES – Counters/Totalisers
Common technical data
Display
Type
Brightness
Display value
Partial display
Time range, partial display
Total display
Decimal point
Status indicator
Pulse output
Type
Display value
Pulse duration
Cut-off time
Analogue output (optional)
Type
Display range
Resolution
Load resistance, current
Load resistance, voltage
Residual ripple
Alarm output (optional)
Type
Switching current
Isolation
Input reset
Type
Function
General information
Supply voltage
Power consumption
Accuracy
Linearity
Repeat accuracy
Humidity
Temperature coefficient
Long-term drift
Impulse withstand voltage
Data backup
Operating temperature / storage temerature
Analogue signal conditioning
MANN SERIES – Counters/Totalisers
Connections
Eight digits, red LED, 7.2 mm
Adjustable to 14 levels of brightness
Percent or real-value displayed
Display from 0 to 50,000 (five digits)
per sec., min., hour (PT800A also per day)
Display from 0 to 99,999,999 (8 digits)
Adjustable separately for partial and total display
Alarm 1/2; Status LED
Transistor output
One pulse per signal jump of the total display
32 ms
Minimum of 32 ms
Current or voltage output configurable with jumper
Dependent on the calibration (within 0 to 22 mA,
or 0 to 11 V)
1,6 μA or 0,8 mV / Bit
≤ 900 Ω
≥ 1 kΩ
< 20 mVss
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Signal
L–
L+
Signal +
Signal –
0V
Pulse
Optional, depending on type
Supply voltage.
Analogue output
(optional)
Pulse output
Inputs
D
NO contacts
Common
NC contact
NO contacts
Common
NC contact
Alarm channel 1
(optional)
Alarm channel 2
(optional)
2 relay contacts (CO)
3 A at 240 V AC, 5 A at 24 V DC / 110 V AC (resistive load)
1.5 kV between ports
Normally open
Complete reset (display/alarm)
24 V DC ±10 %
6 W at 24 V DC
< 0,05 %
< 0,05 %
± 0.02 % of signal range
0...90 % (no condensation)
< 0.02 % of signal range
0.1 % / 10,000 h
4 kV (1.2/50 μs)
≥ 100 years
0 °C…60 °C / -25 °C…70 °C
D.151
Analogue signal conditioning
MANN SERIES – Counters/Totalisers
PTX800 Series
PTX800D
Counter/totalisers/rate monitor
Digital pulse frequency input
• Display instrument for control panel installation
• 1/8 DIN standard front
• IP65 front protection
• Pluggable connection terminals
• Scalable pulse and frequency counters for
digital input signals
• Suitable for all standard input initiators
H
• Power supply for external pulse generator
Reset counter
9
Pull up/down
11
L
2
+24 V
Vout/Iout
7
10
D
0V
1
12
f
0V
+
fin
0V
V/I/f
fout
Ch 1 (opt)
Ch 1 (opt)
+12 V
W
Technical data
Digital pulse (NAMUR, PNP/NPN, TTL logic, opto,
Input signal
Sensor supply
Input voltage
Total display, display range
voltage pulses, no-voltage contacts)
0…10 kHz
12 V DC (up to 25 mA)
Programmable from 50 mV...250 V
Programmable ( ≤10 pulses per signal jump)
Terminal
Analogue output (optional)
Type
Input reset
Min. pulse duration
Pulse output
Max. pulse rate
General information
Functions
8
Current or voltage output configurable with jumper
100 ms
16 / s
/AO: with analogue output
/RO: with two alarm channels
DIN EN 61326
CE, cULus
EMC standard
Approvals
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
mm2
Note
1.5 / 0.5 / 2.5
Screw connection / panel assembly
Plastic housing / 500 g
137 x 96.6 x 48.8 mm
Additional input/output range versions available on request
Ordering data
Typ
without analogue/alarm output
with analogue/alarm output
Special adjustment
D.152
Type
PTX800D
PTX800D RO/AO
PTX800 Variabel
Qty
1
1
1
7
Order No.
7940011133
7940012323
8945040000
9
10
11
12
Signal
Reset by connection to
class 12
Setup configuration by
connection to class 12
Pull Up/Down
Signal –/0 V
Signal +
12 V DC
+
3
4
5
6
NC
13
Common
14
NO
15
NC
Common 16
17
NO
18
Connections
Input
Type
Note
(opt)
–
PS
Reset
Configuration
Inputs
PTX800 Series
PTX800A
Counter/totalisers/rate monitor
Analogue current/voltage input
• Display instrument for control panel installation
• 1/8 DIN standard front
• IP65 fully insulated
Analogue signal conditioning
MANN SERIES – Counters/Totalisers
• Pluggable connection terminals
• Configurable counter and totaliser for analogue
current and voltage signals
• Integrated linearization and input filtering
• Power supply for two-wire sensors
• Completely configurable - or proportional
results display
H
L
1
0V
2
+24 V
Vout/Iout
7
Reset counter
8
Reset common
10
11
12
V/I
0V
+
Vin/Iin
0V
V/I/f
fout
Ch 1 (opt)
Ch 1 (opt)
+12 V
W
Technical data
+
(opt)
–
PS
NC
Common
NO
NC
Common
NO
3
4
5
6
13
14
15
16
17
18
Connections
Input
Type
Conversion of linear/square lans input signals into analogue
Input signal limits
Sensor supply
Resolution
Input resistance
Total display, display range
signals
–24...+24 mA / –11...+11 V
24 V DC (up to 25 mA)
0,6 μA / 0,3 mV
22 Ω (current input),1 Mø (voltage input)
0,001, 0,01, 0,1, 1, 10, 100, 1000
Terminal
Analogue output (optional)
Type
Input reset
Min. pulse duration
Pulse output
Max. pulse rate
General information
Functions
7
8
9
10
11
12
Signal
Reset by connection to
class Kl. 8
Common
Setup configuration by
connection to class 8
Signal –/0 V
Signal +
24 V DC
Reset
Configuration
Inputs
Current or voltage output configurable with jumper
250 ms
15 / s
/AO: with analogue output
/RO: with two alarm channels
DIN EN 61326
CE, cULus
EMC standard
Approvals
Housing specifications
Clamping range (nom. / min. / max.)
Connection type / Mounting rail
Housing type / Weight
Length x width x height
mm2
Note
1.5 / 0.5 / 2.5
Screw connection / panel assembly
Plastic housing / 500 g
137 x 96,6 x 48.8 mm
Additional input/output range versions available on request
Ordering data
Typ
without analogue/alarm output
with analogue/alarm output
Special adjustment
Type
PTX800A 4-20mA
PTX800A 4-20mA/RO/AO
PTX800 Variabel
Qty
1
1
1
Order No.
7940010243
7940014374
8945040000
Note
Accessories
Note
D.153
D
Analogue signal conditioning
MANN SERIES – Calibrators
Portacal 275
Hand-held signal source and loop calibrator
The Portacal 275 is a precise hand-held signal source for
current and voltage signals. It can be used in four modes
which allows the calibration of standard current/voltage
transmitters.
D
The operating mode "voltage source" simulates auxiliarypowered transmitters with proportional voltage outputs. The
mode "current source" allows emulation of transmitters with
proportional current outputs. The "mv source" mode simulates
a variety of other analogue signals from many different
applications. The "current sink" mode simulates the outputs of
a two-wire (loop powered) transmitter.
The Portacal 275 is equipped with a scalable potentiometer (0
to 100%) that can be adjusted in steps to an accuracy of
0.1%. Together with the output-range switch, the potentiometer allows for a quick and precise adjustment of the signal
value. A typical accuracy of ± 0.25 % is possible. An integrated
test point, for connecting external measurement devices, allows for a higher accuracy of ± 0.1%.
Technical features:
•
•
•
•
•
•
•
•
•
Light and portable device
Simulates loop-powered transmitter operation
LED for indication of source/sink operating mode
Current ranges: 0 to 20 mA / 4 to 20 mA / Voltage ranges:
–5 V / 1 to 5 V / 0 to 200 mV
0.1 % accurate current source
Test points for current-output monitoring
Switch select 0 %, 100 % or variable output
Signal outputs can be adjusted with spindle potentiometer
for high accuracy
Powered from two 9 V block batteries
D.154
Portacal 275
Portacal 275
Signal source and loop calibrator
Calibrator
+
Current
-
+
Voltage
-
Analogue signal conditioning
MANN SERIES – Calibrators
H
PORTACAL 275
D
L
W
Technical data
Output of voltage mode
Output voltage
Resolution
Output resistance
Accuracy
Output of current mode
Output current
Resolution
Max. load resistance
Wiring diagram
0 (1)…5 V / 0 (40)…200 mV
0.01 V
250 Ω @ V / 10 Ω @ mV
< 0.2 % (0 % und 100 %)
DVM
+
0 (4)…20 mA
0,01 mA
700 Ω (current source)
(V – 4) / 0,02 Ω (current sink)
4…45 V DC
0.1 % (0 % and 100 %)
< 1 μA
Output, variable
Ouput, fixed
Allgemeine Angaben
Temperature coefficient
Accuracy
Supply voltage
Operating temperature
Storage temperature
EMC standards
Approvals
Housing specifications
Connection type
Housing type / Weight
Length x width x height
Device with
current input
–
V+ V- C+ C-
+
–
Calibration of a transmitter with four-wire connection
and current output
out
Max. output voltage at pre-sink
Accuracy
Residual ripple
Settings
Settings range
Portacal 275
(mA source mode)
DVM
Portacal 275
(mA sink mode)
0 (4)...20 mA / 0...200 mV (current source), 0…5 V
(voltage source) or as current sink, selectable with
toggle switch
0…100 % with precision potentiometer
0 or 100 % with toggle switch
40 ppm @ °C
0.25 % of signal range
Battery, 2 x 9 V block, 6 to 22 mA (current source)
2 mA (current sink)
0 °C…60 °C
–25 °C…+70 °C
DIN EN 61326
CE, cULus
+
–
V+ V- C+ C-
Device with
current input
+
–
Power
suppler
+
–
Calibration of a transmitter with two-wire connection
Portacal 275
(voltage output)
V+ V- C+ C-
Device with
voltage or
current input
+
–
Calibration of a transmitter with four-wire connection
and current or voltage input
Socket
Plastic housing / 550 g
31 x 62 x 112 mm
Note
Ordering data
Typ
Type
Portacal 275
Note
2x 1 m test cable sw/rt with banana plug/terminal and
1x bridge pipeline
Qty
1
Order No.
7940010202
Accessories
Note
D.155
Analogue signal conditioning
MANN SERIES – Calibrators
Portacal 1000
Calibration device for current and voltage signals
Typical application of Portacal 1000
The Portacal 1000 is a calibration device which is controlled by
microprocessor. It is used for current and voltage signals. It has
three output modes for simulating signals:
2-wire, 4…20 mA output current
of PT1000
Signal
converter
(ITX+)
D
• Voltage source: for the simulation of externally-supplied
voltage transmitters
• Current source: for the simulation of externally-supplied
current sensors
• Current sink mode: simulates the outputs of a two-wire
(loop-powered) transmitter.
Commonly used calibration functions can be invoked for each
mode by pressing a button. Up to 9 storage locations per
mode are available to save the individual values.
Furthermore, the Portacal 1000 can be programmed in a way
that all modes can be cycled automatically. The corresponding
values are controlled continually for a pre-defined time by
means of a value storage. The following values can be checked
and parameterized:
• Voltage outputs
• Current outputs
• Two-wire transmitter outputs
The Portacal 1000 provides the necessary voltage supply for
the sensor in order to check a two-wire transmitter.
Technical features:
• Complete diagnosis tool for current and voltage supply
• Measuring and simulating of voltage and current signals
• Simulation of function of signal transmitter, which can be
auxiliary-powered or process-powered (two-wire type)
• Continually adjustable step and ramping function
• Accuracy < 0.05 % in all signal domains
• Light and portable
• Supply via NiMH rechargeable battery or comparable battery
• Signal tone at the press of a button
D.156
Portacal 1000
Input
thermocouple
Transmitter Test
Portacal 1000
Instrument Calibrator
Technical data
Output voltage mode
Output voltage
Resolution
Load current
Accuracy
Residual ripple
Interner Speicher
Output current mode
Output current
Resolution
Load resistance
max. input voltage current sink
Accuracy
Residual ripple
Internal storage
Input voltage mode
Input voltage
Input resistance
Accuracy
Input current mode
Input current
Input resistance
Accuracy
Loop powered mode
Type
Input current
Feed voltage
Accuracy
Auto step/ramp mode
Step
Ramp
Number of recorded values
Time interval
Display
Type
Status indicator
Display value
Keyboard
Type
Calibration
Memory
Decimals
General data
Supply voltage
Temperature coefficient
Operating temperature / storage temperature
EMC standard
Approvals
Housing specifications
Connection type / Mounting rail
Housing type / Weight
Length x width x height
0…13 V
0.01 V
0…10 mA
±5 mV
< 1 mV
Nine user-defined voltages
Analogue signal conditioning
MANN SERIES – Calibrators
0…26 mA
0,01 mA
600 Ω @ 20 mA (power source)
100 Ω (current sink)
9…45 V DC
±5 μA
< 1 μA
Nine user-defined currents
H
S
R
D
0…13 V
200 kΩ
±5 mV or ±1 digital step
L
PORTACAL 1000
W
0…26 mA
47 Ω
±5 μA or ±1 digital step
Mode for loop-powered signal-converters
0…26 mA
16 V ±10 %
±5 μA or ±1 digital step
Output of each value within a certain time period
Output via a programmed ramp function
2…9
10…4200 s
Four-digit display with LCD, 12 mm
Five LEDs for output mode, signal amplification and reduction
Percent or real-value displayed
16 buttons with acoustic signal
Adjustable fixed values:
0, 2, 4, 8, 10, 12, 16, 18, 20 mA
0, 1, 2, 4, 5, 6, 8, 9, 10 V
Nine freely-definable values
1 / 0.1 / 0.01 mA or V
Battery, 4x type 'AA'
< 0.01 % / °C at 100 %
0 °C…60 °C / –25 °C…+70 °C
DIN EN 61326
CE, cULus
Socket / –
Plastic housing / 550 g
44 x 100 x 180 mm
Note
Ordering data
Typ
Type
Portacal 1000
Note
2x 1 m test cable sw/rt with banana plug/terminal
Qty
1
Order No.
7940010194
Accessories
Note
D.157
D
D.158
Analogue signal conditioning
Download