Power System Series Resonance Studies by Modified Admittance Scan Felix O. Kalunta, MNSE, Frank N. Okafor, FNSE, Member, IEEE, Osita U. Omeje Abstract – This paper presents a modified method of formulating the loop admittance matrix which is deployed to identify the series resonant frequencies in large electrical networks involving numerous shunt capacitances. Three matrices were assembled from the network R, L and C elements and later synthesized to obtain the network loop admittance matrix. Its application to a sample network has shown the practicability and effectiveness of this method. This paper also seeks to demonstrate the impact of certain factors like cable capacitance and skin effect on the value of resonant frequencies. Index Terms – Harmonic Resonance, Loop Admittance Matrix, Power Quality and Series Resonance. I. INTRODUCTION The application of capacitor banks in the power industry has yielded some utility benefits such as power factor correction, voltage support and release of system capacity. However, their interaction with system inductive supply circuit [1, 2] causes power quality problems by way of amplifying high order harmonics. These could lead to overheating, failure of the capacitor banks themselves or blowing of power transformer units resulting in constant interruption in production schedules. Another concern is that the broadband spectrum emitted in the process could result in emission limits being exceeded for non-characteristic harmonics and for inter-harmonics. The challenge is how to theoretically predict the resonant frequencies based on which appropriate mitigation measures can be included at the planning stage or the magnitude of amplified currents for the power equipment to be de-rated in order to withstand this exigency. There is also the need to indicate which of the system component is under the threat of series resonance [3]. The papers [4 – 5] describes the use of frequency scan technique to detect the possible resonant frequencies in the electrical network while [5, 6] presented a harmonic resonance mode assessment based on the analysis of eigenvalues and eigenvectors of the system bus impedance matrix. Further details of modal analysis in the study of resonance are treated in the technical literature [9-11]. _______________________________________________ Felix O. Kalunta is currently pursuing his Ph.D degree with the Department of Electrical/Electronic Engineering, University of Lagos, Nigeria. He is on study leave from Federal Institute of industrial Research Lagos, Nigeria (e-mail: felka3@yahoo.co.uk). Osita U. Omeje is currently pursuing his Ph.D degree with the Department of Electrical/Electronic Engineering, University of Lagos, Nigeria (e-mail: ositaomeje@gmail.com) Frank N. Okafor is a professor with the Electrical/Electronic Engineering Department, University of Lagos, Nigeria. (e-mail: cfrankok@yahoo.com). These methods are primarily suitable for parallel resonance problem with little adaptation to the analysis of series resonance. The reason lies in the close relationship between loop impedance and the occurrence of series resonance. An attempt to apply the modal analysis to series resonance problem was also made [8] but yielded an incomplete solution. A dummy branch method was later incorporated into the modal analysis but the approach seems more like a short circuit study which does not reflect the actual series resonance scenario. The loop admittance scan technique is an adaptation of frequency scan for locating the resonance peaks in a series resonance problem. Calculations are performed to determine the loop admittance matrix of the concerned network, while the driving point admittances are the determinants of the resonant frequencies. The complexities involved in the calculation of the loop admittance matrix for large power networks especially when cable capacitance is involved have necessitated the need for a modified admittance scan. In such cases, matrix of network elements R, L and C are easily assembled by computer programming and later synthesized to form a loop impedance matrix. This is the approach adopted in this paper. The formation of dummy loops in the calculation of the network matrices is applied in order to account for the shunt capacitances without altering the network topology. Other factors that affect resonance characteristics like skin effect of cables are also investigated in this paper. This study will account for skin effect by calculating the resistance R of the cable at various discrete frequencies using an equation that varies according to cable type [11]. 𝑅 = 𝑅1 ( 0.187 + 0.532√ℎ ), where h≥2.35 ----------- (1) where 𝑅1 is the resistance of the cable at the fundamental frequency and h is the harmonic order. II. MODAL ANALYSIS APPLIED TO SERIES RESONANCE The determination of series resonant frequencies is based on mesh analysis at each harmonic frequency h in per unit. Resonance mode analysis in this case is based on the fact that the loop impedance matrix of a power network becomes singular at resonant frequencies. This requires the calculation of the eigenvalues of the system as well as their sensitivities to changes in system parameters. Imagine that a system experiences resonance at frequency h according to the frequency scan analysis. It implies that some elements of the loop current vector have large values at h. This in turn implies that the inverse of the [𝑍ℎ ] matrix has large elements. This phenomenon is primarily caused by the fact that one of the eigen-values of the Z – matrix is close to zero. In fact, if the system had no damping, the Z – matrix would become singular due to one of its eigenvalues becoming zero. The above reasoning leads us to believe that the characteristics of the smallest eigenvalue of the [𝑍ℎ ] matrix could contain useful information about the cause of the harmonic resonance. The above analysis can be formally stated as follows: [𝑉]ℎ = [𝑍𝑙𝑜𝑜𝑝 ]ℎ [𝐼𝑙𝑜𝑜𝑝 ]ℎ The current vector for each harmonic order is as follows [𝐼𝑙𝑜𝑜𝑝 ]ℎ = [𝑍𝑙𝑜𝑜𝑝 ]−1 ℎ [𝑉]ℎ , h = 1, 2, 3… n ---------- (2) Where[𝑍𝑙𝑜𝑜𝑝 ]ℎ , is the loop impedance matrix [𝑉]ℎ is the harmonic loop voltage vector. As usual, the loop impedance matrix can be decomposed into the following form: [𝑍] = [L][D][T] is the eigen-decomposition of the [𝑍] matrix at frequency h. [L] and [T] are the left and right eigenvector matrices of [Z] [D] - diagonal eigenvalue matrix of Z. 𝑇= 𝐿−1 is due to the fact that 𝑌 is symmetric. Equation (2) now becomes [𝐼]=[𝐿][𝐷]−1 [𝑇] [𝑉] ------------------------ (3) If [𝑇][𝑉] and [𝑇][𝐼] are defined as the modal voltage and current vectors respectively. It can be seen that admittance scan equation has been transformed into the following form: λ1−1 0 𝐽1 0 0 𝑉𝑚1 −1 𝐽2 0 λ2 0 0 [𝑉𝑚2 ] ------------- (4) [ ]= ⋮ ⋮ 0 0 ⋱ 0 −1 𝑉 𝐽𝑛 [ 0 0 0 λ𝑛 ] 𝑚𝑛 This can be abbreviated as, ∴ [𝐽𝑘 ]ℎ = [λ−1 𝑘 ]ℎ [𝑉𝑚𝑘 ]ℎ -------------------- (5) The inverse of the eigen value, λ𝑘−1 , has the unit of admittance and is named modal admittance. One can easily see that if 𝜆1 = 0 or is very small, a small applied mode 1 voltage will lead to a large mode 1 current. On the other hand, the other modal currents will not be affected since they have no 'coupling' with mode 1 voltage. In other words, one can easily identify the 'locations' of resonance frequencies in the modal domain. After identifying the critical mode of resonance, it is possible to find the 'participation' of each loop in the resonance. This can be done using the well-known participation factor theory described in [10]. III. FORMULATION OF LOOP ADMITTANCE SCAN The admittance scan is a series resonance counterpart of the bus impedance scan. The scan is performed in one network mesh at a time. A sinusoidal voltage of unit amplitude ∆𝑉 = 1, and of certain harmonic frequency is inserted into this mesh and the corresponding loop current is calculated. The process is repeated for other harmonic frequencies in per unit. For the purpose of illustration, consider a radial network in fig. 1 containing capacitor banks with a non-linear load connected to bus J through a transformer and a long cable. The network is partitioned along the point of common coupling between the consumer distribution network and public utility supply as in fig. 2. The consumer side of the network is modeled at each harmonic frequency h, and the system supply side is reduced to its Thevenin equivalent also at each harmonic frequency. There are two buses where voltage amplification could be excited by parallel resonance and also three meshes or loops where current amplification can occur by series resonance. Fig. 1: A simple consumer premises supplied from the public utility network Fig. 2: The equivalent circuit model of the 2 – bus consumer network The application of loop analysis to fig. 2 produces the following equation, [𝑉]ℎ = [𝑍𝑙𝑜𝑜𝑝 ]ℎ [𝐼𝑙𝑜𝑜𝑝 ]ℎ The current vector at each harmonic frequency, h is as follows [𝐼𝑙𝑜𝑜𝑝 ]ℎ = [𝑍𝑙𝑜𝑜𝑝 ]−1 ℎ [𝑉]ℎ , h = 1, 2, 3 … n ------------- (6) The matrix [𝑍𝑙𝑜𝑜𝑝 ]ℎ is known as the loop impedance matrix. The inverse of the loop impedance matrix is known as loop admittance matrix, 𝑌𝑙𝑜𝑜𝑝 𝑌𝑙𝑜𝑜𝑝 = [𝑍𝑙𝑜𝑜𝑝 ]−1 ---------------------------- (7) This matrix is the counterpart of bus impedance matrix and is therefore useful in the determination of the frequencies at which harmonic series resonance occurs. Equation (6) can now be written as 𝐼1 𝑙𝑜𝑜𝑝 𝑌11 [𝐼2 ] = [𝑌21 𝐼3 𝑌31 𝑌13 𝑙𝑜𝑜𝑝 𝑉1 𝑌23 ] [𝑉2 ] ------------------ (8) 𝑉3 𝑌33 𝑌12 𝑌22 𝑌32 For the purpose of resonance analysis, only the driving point 𝑙 admittances 𝑌𝑘𝑘 are required. 𝐼 𝑙 Therefore 𝑌𝑘𝑘 = [𝑉𝑘 ] 𝑘 𝑉𝑗 =0 , ∀𝑘 ≠𝑗 [𝐼𝑙𝑜𝑜𝑝 ]ℎ𝑘 = [𝑌𝑙𝑜𝑜𝑝 ]ℎ𝑘𝑘 [𝑉𝑙𝑜𝑜𝑝 ]ℎ𝑘 , 𝑉𝑗 = 0 ∀ 𝑘 ≠ 𝑗 ---- (9) Suppose 𝑉𝑘 = 1𝑝. 𝑢 for all h =1, 2, 3 … n [𝐼𝑙𝑜𝑜𝑝 ]ℎ𝑘 = [𝑌𝑙𝑜𝑜𝑝 ]ℎ𝑘𝑘 ------------------------ (10) A graph of [𝐼𝑙𝑜𝑜𝑝 ]𝑘 against h is equivalent to a graph of [𝑌𝑙𝑜𝑜𝑝 ]𝑘𝑘 against h. Therefore, driving point admittance versus frequency plot is obtained for each mesh in the network. Therefore, driving point admittance versus frequency plot is obtained for each mesh in the network. This technique when applied for the determination of series resonant frequencies in power networks can be referred to as admittance scan. The off – diagonal or transfer admittances could be considered in the admittance scan when dealing with many harmonic sources applied simultaneously at different network meshes. The current change in the k-th mesh due to the insertion of unit harmonic voltages in meshes k, i and j is stated as 𝐶𝑝−1 = the inverse shunt capacitance at p-th dummy loop. 𝐼𝑘 = 𝑌𝑘𝑘 + 𝑌𝑘𝑖 + 𝑌𝑘𝑗 ------------------ (11) IV. MODIFICATION OF NETWORK MATRICES TO ACCOUNT FOR THE SHUNT CAPACITANCES Procedure: 1. The three (𝑛 × 𝑛) network matrices are assembled as usual in the absence of the shunt capacitances. These are designated as 𝑅𝑜𝑙𝑑 , 𝐿𝑜𝑙𝑑 and 𝐺𝑜𝑙𝑑 respectively. Fig 3: Equivalent circuit diagram showing two dummy loops for shunt capacitors C1 and C2 2. All parallel connection of capacitances can be combined together by summation. 3. Dummy loops m in number are created at each node where the shunt capacitances exist such that the total number of loops becomes(𝑛 + 𝑚), see fig 3. The dummy loops are assigned loop numbers 𝑛 + 1, 𝑛 + 2 , … 𝑛 + 𝑚 4. Extra rows and columns corresponding to the number of the created dummy loops are added to each of the three network matrices to form a partitioned matrix as shown, 𝑅𝑛𝑒𝑤 = [ 𝑅𝑜𝑙𝑑 𝐴′ 𝐿𝑜𝑙𝑑 𝐵′ 𝐵 ] ---------------------- (13) 𝐻 𝐺𝑜𝑙𝑑 𝑈′ 𝑈 ] ----------------------- (14) 𝑉 𝐿𝑛𝑒𝑤 = [ 𝐺𝑛𝑒𝑤 = [ 𝐴 ] ------------------- (12) 𝑄 5. The dummy loops are eliminated using the kron – reduction formular, 𝑅𝑛𝑒𝑤 = 𝑅𝑜𝑙𝑑 − 𝐴𝑄𝐴𝑇 , 𝐿𝑛𝑒𝑤 = 𝐿𝑜𝑙𝑑 − 𝐵𝐻𝐵𝑇 and 𝐺𝑛𝑒𝑤 = 𝐺𝑜𝑙𝑑 − 𝑈𝑉𝑈 𝑇 Fig. 4: The sequential process of carrying out an admittance scan based on the creation of dummy loops 6. The matrix of network elements R, L and G are finally synthesized according to equation (15) to obtain the loop impedance matrix. This is repeated for each harmonic frequency, h. The updated matrices obtained from application of the above procedure to fig. 3 are, [𝑍𝑙𝑜𝑜𝑝 ] = [𝑅𝑛𝑒𝑤 ] + 𝑗𝜔1 ℎ[𝐿𝑛𝑒𝑤 ] − 𝑗[𝐺𝑛𝑒𝑤 ]/𝜔1 ℎ - (15) Where L – 𝑛 × 𝑛 loop inductance matrix R – 𝑛 × 𝑛 loop resistance matrix G – 𝑛 × 𝑛 loop inverse capacitance matrix 𝜔1 – fundamental frequency in rad/s For a dummy loop p created between two actual loops 𝑖 and 𝑗 𝐴𝑖𝑝 = 𝐴𝑝𝑖 = −𝑅𝑠𝑝 , 𝐴𝑗𝑝 = 𝐴𝑝𝑗 = 𝑅𝑠𝑝 , 𝑄𝑝𝑝 = 𝑅𝑠𝑝 , elsewhere the entries are zero. Similarly, 𝐵𝑖𝑝 = 𝐵𝑝𝑖 = −𝐿𝑠𝑝 , 𝐵𝑗𝑝 = 𝐵𝑝𝑗 = 𝐿𝑠𝑝 , 𝐻𝑝𝑝 = 𝐿𝑠𝑝 and 𝑉𝑝𝑝 = 𝐶𝑝−1 , elsewhere the entries are zero. Where R sp = the total resistance in the branch common to loops i, j and p Lsp = the total inductance in the branch common to loops i, j and p 𝑅𝐿𝑜𝑜𝑝 𝑅11 𝑅21 = 𝑅31 −𝑅𝑠1 [ 0 𝑅12 𝑅22 𝑅32 𝑅𝑠1 0 𝐿𝐿𝑜𝑜𝑝 𝐿11 𝐿21 = 𝐿31 −𝐿𝑠1 [ 0 𝐿12 𝐿22 𝐿32 𝐿𝑠1 −𝐿𝑠1 𝐺𝐿𝑜𝑜𝑝 𝐺11 𝐺21 = 𝐺31 0 [ 0 𝐺12 𝐺22 𝐺32 0 0 𝑅11 𝑅23 𝑅33 0 0 𝐿11 𝐿23 𝐿33 0 𝐿𝑠1 𝐺11 𝐺23 𝐺33 0 0 −𝑅𝑠1 𝑅𝑠1 0 𝑅𝑠1 0 0 0 0 --------------- (16) 0 0] −𝐿𝑠1 𝐿𝑠1 0 𝐿𝑠1 0 0 −𝐿𝑠2 𝐿𝑠2 --------- (17) 0 𝐿𝑠2 ] 0 0 0 𝐶1−1 0 0 0 0 ------------ (18) 0 𝐶2−1 ] Equation (15) is then applied after the process of eliminating the dummy loops, 12 𝑌𝑙𝑜𝑜𝑝 = [𝑍𝑙𝑜𝑜𝑝 ]𝑛𝑒𝑤 −1 ------------------ (19) The entire process of carrying out an admittance scan based on the creation of dummy loops is described in the flow chart in fig. 4. The modified admittance scan and modal loop analysis has been applied to the equivalent circuit shown in fig.2, and the results are displayed in Fig. 7 and 8 respectively. With the circuit, series resonance result could be compared to that of parallel resonance solved by frequency scan and Resonance Mode Analysis (see fig. 5 and 6). Modal Admittance (pu) 10 [𝑍𝑙𝑜𝑜𝑝 ] = [𝑅𝑛𝑒𝑤 ] + 𝑗𝜔1 ℎ[𝐿𝑛𝑒𝑤 ] − 𝑗[𝐺𝑛𝑒𝑤 ]/𝜔1 ℎ 8 6 4 2 0 0 10 20 30 40 50 60 Frequency (p.u) Fig. 7: Results of modal Loop analysis on test system 4.5 45 bus1 bus2 bus3 40 Loop1 Loop2 Loop3 4 35 3.5 30 Admittance (pu) Impedance (pu) Loop1 Loop2 Loop3 25 20 15 10 3 2.5 2 1.5 5 1 0 0.5 0 10 20 30 40 50 60 Frequency (p.u) 0 0 10 20 30 40 50 Frequency (p.u) Fig 5: Bus Impedance Scan Results of the test system Fig. 8: Loop Admittance Scan results of the test system. 70 bus1 bus2 bus3 Modal Impedance (pu) 60 V. APPLICATION TO A DISTRIBUTION NETWORK 50 The network diagram in fig.9 represents an 11kV underground radial distribution network which feeds nine load centers containing two major harmonic sources and four capacitor banks. It is an expansion of the distribution network used as case study in Reference [7]. The load centers are connected by 35mm2 x 3, 11kV underground cables whose parameters are as follows, 40 30 20 10 0 0 10 20 30 40 50 60 Frequency (p.u) Fig. 6: Results of bus Resonance mode analysis (RMA) The results indicate that the modified loop admittance scan compares favourably to its counterparts: modal-loop analysis and bus impedance scan. The key resonance modes according to the results displayed in Fig. 5 – 8 occur at frequencies (pu) = 4, 17 and 27. The modal admittance scan (fig.7) produces only one resonance peak for each mesh whereas about three peaks are captured in each mesh in the results of modified loop admittance scan. This achievement is because the network topological structure was not altered in the process of applying the proposed technique in localizing the series resonant frequencies. Resistance/ph/km = 0.243Ω, Inductance/ph/km = 5.023 x 10 - 4 H Capacitance/ph/km = 2.456 x 10-8 F The frequency response characteristics resulting from application of modified loop admittance scan across the entire distribution network are shown in fig. 10 – 13. 60 Fig. 12: Frequency response considering the effect of cable capacitance Fig. 9: Diagram showing the 11kV radial distribution network in a consumer premises Fig.13: Frequency response considering cable capacitance and skin effect The results indicate the occurrence of series resonance peaks at the various meshes M1 – M9 as indicated. Fig 10: Frequency response neglecting the effect of cable capacitance and skin effect In figure 10 where the effects of cable capacitance and skin effect are neglected, the resonant frequencies in per unit are h = 6, 7, 14 and 15. In figure 11 where the effect of aggregate harmonic sources is considered, the resonant frequencies are the same as in fig. 10. In figure 12 where only the effect of cable capacitance is considered, the resonance frequencies in per unit are h = 6, 7 and 14. In figure 13 where the effects of cable capacitance and skin effect are considered, the resonance frequencies in per unit are h = 6, 7 and 14. Fig 11: Frequency response for aggregate sources neglecting the effect of cable capacitance and skin effect Comparison between figures 10 - 13 indicates that cable capacitance contributes immensely to the shifting of the resonant frequencies in M3 – M6 while the skin effect only reduces the magnitude of loop admittance and widens the frequency curve. Since resistance instead of inductance or capacitance (that is the main contributors to system resonance) varies according to the skin effect, consequently, considering the skin effect in the calculations does not shift the resonant frequencies. However, the increased resistance could dampen the admittance peaks at resonance points thereby decreasing the branch currents. Skin effect also increases the bandwidth of resonance. This implies the greater chance of current amplification occurring within the neighbourhood of the resonant peaks. Comparison between fig. 10 and 11 indicates that the application of many harmonic frequency sources only impacts on the magnitude of the driving point admittances and therefore is of no consequence to this study which is focused on the resonant frequencies. VI. CONCLUSION The modified loop admittance scan proves to be an acceptable method for capturing all the dominant frequencies involved in series resonance without any restriction to the utilized frequency step. The application of a single unit voltage is sufficient in the definition of admittance scan. Specific achievements are recorded in this study: the determination of series resonant frequencies by the application of loop admittance matrix, the use of matrix partitioning to treat independently the connection of shunt capacitors and the contribution of skin effect as well as cable capacitance on these results. It is noted that skin effect does not contribute to the shifting of resonant frequencies but only cable capacitance. Hence, in the calculation of the resonance peaks, the contribution of skin effect can be neglected. However, skin effect makes a significant contribution to the value of branch currents which necessitates its consideration. VII. REFERENCES [1] Z. Huang, Y. Cui and W. Xu, "Application of Modal Sensitivity for Power System Harmonic Resonance Analysis", IEEE Transactions on Power Systems, vol. 22, 2007, pp. 222–231. [2] J. Li, N. Samaan and S. Williams, "Modeling of Large Wind Farm Systems for Dynamic and Harmonics Analysis", Transmission and Distribution Conference and Exposition, T&D, IEEE/PES, 2008, pp. 1–7. [3] C. Chien and R. Bucknall, "Harmonic Calculations of Proximity Effect on Impedance Characteristics in Subsea Power Transmission Cables", IEEE Transactions on Power Delivery, ISSN: 0885-8977, vol. 24, October 2009, pp. 2150 – 2158. [4] H. K. Lukasz, J. Hjerrild and C. L. Bak, “Wind Farm Structures: Impact on Harmonic Emission and Grid Interaction”, European Wind Energy Conference 2010, Warsaw, Poland, 2010. [5] R. Zheng and M. Bollen, “Harmonic Resonances Due to a Grid-Connected Wind Farm”, In Proceedings of the 14th International Conference on Harmonics and Quality of Power (ICHQP 2010), Bergamo, Italy, 26-29 September 2010, pp. 1 – 7 . [6] J. Arrillaga and W. Neville, “Power System Harmonics”, ISBN: 0470851295, West Sussex: Wiley & Sons, 2003. [7] F. O. Kalunta and F. N. Okafor, “ Harmonic Analysis of Power Networks Supplying Nonlinear Loads”, International Conference on Innovations in Engineering and Technology (IET 2011), Faculty of Engineering, University of Lagos, Nigeria, 8th – 10th August 2011, pp 568 – 577. [8] H. Zhou, Y. Wu, S. Lou and X. Xiong, “Power System Series Harmonic Resonance Assessment based on Improved Modal Analysis”, Journal Of Electrical & Electronics Engineering, Istanbul University, 2007, vol.7, No.2, pp 423 – 430. [9] C. Yang, K. Liu and Q. Zhang, “An Improved Modal Analysis Method for Harmonic Resonance Analysis”, IEEE International Conference on Industrial Technology (ICIT 2008), ISBN: 978-1-4244-1705-6, Chengdu, China, 2008, pp.1–5. [10] K. Md Hasan, K. Rauma et al, “Harmonic Resonance Study for Wind Power Plant”, International Conference on Renewable Energies and Power Quality (ICREPQ’12), Santiago de Compostela, Spain, 8th to 30th March 2012. [11] K. Nisak, K. Rauma et al, “An Overview of Harmonic Analysis and Resonances of a Large Wind Power Plant”, Annual Conference of the IEEE Industrial Electronics Society (IECON 2011), 7–10 November, 2011.