Current Consumption Inspection Points Rated Voltage (V) Motor 21 10.5 8 4.5 4.5 2.3 6.4 3.2 24DC 48DC 60DC 110DC 125DC 220DC 120AC 240AC Current Consumption (A) Closing Solenoid 4 2.7 1.7 1.3 1.5 0.65 1.3 0.65 Description of HVF VCB Open Solenoid 4 2.7 1.7 1.3 1.5 0.65 1.3 0.65 INSPECTION ITEMS DESCRIPTION INTERVAL • General Check 3 Years 1. Clean the Insulated surface with dry cloth to remove dust and moisture. 2. Check the exterior for damage. 3. Check for loose bolts and nuts of the operating mechanism. 4. Check stop ring and stop retainer for damage. 5. Check terminals for loose connection or correction. • Operation Test 3 years 1. Operate a few times manually and electrically. Check each part for proper function. 2. Check ON/OFF indicator and counter for proper function. • Insulation Resistance 1. Measure insulation resistance between phase and between pole and ground with a 1000V megger. If the measured value is less than 500M , check the cause. 2. Check the insulation resistance between control circuit and ground using a 500V megger If the measured value is less than 2M , check the cause. 3 years • Lubrication 10 years or 5000 operations 1. Lubricate each part of operating mechanism. 2. Clean disconnection unit with a dry cloth and a small amount of grease. (lithium soapbased grease) • Vacuum Interrupter 10 years or 5000 operations 1. Check the contact erosion limit. 2. Operating the circuit, check the vacuum degree of vacuum bottle. 38Kv Cir cuit Breaker Retrofits Circuit Controlled Power can retrofit any of your existing Minimum Oil, Vacuum, SF-6, Air Magnetic or Air Blast circuit breakers with our modern Type HVF Vacuum Breaker and extend the life of your equipment. Call us today for more information. NO 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 31 32 ITEM Operating Mechanism Enclosure Gear Box Closing Spring Tripping Spring Link Coupling Bar Breaker Shaft Dash Pot Counter ON/OFF Indicator Spring Charged Indicator Closing Button Tripping Button Name Plate Hole for Manual Charging Motor Closing Solenoid (Y9) 33 34 35 36 41 42 44 45 46 47 49 55 57 58 59 60 Tripping Solenoid (Y1) Limit Switch (S21, S22, S3) AntiPumping Contactor Auxiliary Switch (S1) Vacuum Interrupter Upper Terminal Lower Pole Support Ring Contact Lever Lower Terminal Contact Pressure Spring Insulation Frame Insulation Rod Spring Guide Eye Bolt Truck Lubrication Points Phone: 330.834.3200 • Fax: 330.834.3201 w w w . c o n t r o l l e d p o w e r.com Controlled Power HVF series vacuum cir cuit breakers: circuit Three pole drawout units for use in 38 kV switchgear 38kV switchgear.. Typical Breaker Elements Typical Cir cuit Diagram Circuit 38 kV Switchgear Features Controlled Power has manufactured 38kV switchgear since 1980. Hundreds of 38kV circuit breakers are in reliable operation in transit, utility, and industrial applications. The breakers, including vacuum interrupters, are designed and manufactured with advanced vacuum technology and have been tested according to the latest version of ANSI Standards in ISO 9001 facilities. The circuit breakers are available in 1200A, 2000A, 2500A, and 3000A (FC) continuous ratings. The breakers are constantly being improved to satisfy all demands of the market. HIGH RELIABILITY DURING LONG LIFE TIME Charge Indicator • The HVF Circuit Breaker employs a robust design with rugged components for increased durability and reduced maintenance. Close/Open Indicator • The HVF Circuit Breaker is capable of back-to-back capacitor switching of 90 MVAR, far in excess of ANSI standards. • Compact Design (Nominal Dimensions) Hole for Manual Charging Counter Width = 42 Inches Height = 110 Inches Depth Manual Close Button = 148 Inches - Indoor 152 Inches - Outdoor, non walk-in 20 Feet - Outdoor Protected Aisle Manual Open Button 33 Feet - Outdoor Common Aisle LOW MAINTENANCE • The HVF Circuit Breaker requires very little maintenance. Only those parts subject to normal wear and aging need to be serviced to ensure reliable operation. • Routine checks are required after 3 years and no lubrication is required until 10 years in normal operation. CIRCUIT BREAKER FEATURES • Both 31.5kA and 40kA interrupting ratings are available. Why pay for the high interrupting breaker unless it is necessary? Dimensions: HVF Draw-out T ype VCB (38Kv) Type Dimensions in mm • The HVF Breaker utilizes self-aligning/self-coupling secondary disconnects that assure positive connection of relay circuits to the trip coil of the circuit breaker. • No manual connection of a plug and socket or umbilical cord by a technician is required. Heavy-duty utility grade contacts are furnished instead of light duty electronic type connectors. 38 KV CELL INTERIOR • Self-aligning/self-coupling secondaries - no manual plug & socket connection required. 38 KV SWITCHGEAR FEATURES • Enclosures are only 42 inches wide. • Drawout CPT’s (up to 15 kVA) or draw-out PT’s can be mounted above circuit breakers in the same enclosure, thus reducing the length of the lineup. • Grounded metal shutters. • Closed door racking is available. • Full set of ANSI interlocks. • Remote trip/close is available. • Rugged construction. • Separate disconnect, test and connected positions. • Remote electronically operated racking device is available. • Both manually operated and electrically operated ground and test devices are available. Ratings & Additional Products Description Type No. ____________________________________________ Application standard _________________________________ Rated voltage (Kv) ___________________________________ Rated current (A) ____________________________________ Rated interrupting current (Ka) _________________________ Rated Close & Latch (Ka) ______________________________ Frequency (Hz) ______________________________________ Rated Low Frequency Withstand (Kv, RMS) ______________ Impulse withstand voltage (Kv,B.I.L.) ___________________________________________ Breaking time (cycles) ________________________________ Operating duty ______________________________________ Operating life at rated current (times) ___________________ Closing operation ______________ Operation system ____ ______________ Control voltage ______ Closing & tripping control (V) _____ Control voltage ______ Auxiliary contacts ____________________________________ Weight of breaker Mainbody (Lbs.) _____________________ All circuit braker ratings are based on K = 1.0 HVF705 ANSI C37.06 / ANSI C37.09 38 1200, 2000, 2500, 3000 31.5 or 40 82 or 104 60 80 170 5 0 -0.3s-CO-3min-CO 20,000 Motor Spring Stored Energy DC 48, 60, 110, 125, 220 /AC 120, 240 DC 48, 60, 110, 125, 220 /AC 120, 240 4NO + 4NC (Max. 10NO + 10NC) 1200a- 750 2000a- 800 2500a- 850 3000a- 850 • Drawout potential transformers can be mounted above a circuit breaker. • Drawout control power transformers (up to 15kVA) can be mounted above a circuit breaker. • Space saving design - reduce size of building required to house the switchgear. Controlled Power HVF series vacuum cir cuit breakers: circuit Three pole drawout units for use in 38 kV switchgear 38kV switchgear.. Typical Breaker Elements Typical Cir cuit Diagram Circuit 38 kV Switchgear Features Controlled Power has manufactured 38kV switchgear since 1980. Hundreds of 38kV circuit breakers are in reliable operation in transit, utility, and industrial applications. The breakers, including vacuum interrupters, are designed and manufactured with advanced vacuum technology and have been tested according to the latest version of ANSI Standards in ISO 9001 facilities. The circuit breakers are available in 1200A, 2000A, 2500A, and 3000A (FC) continuous ratings. The breakers are constantly being improved to satisfy all demands of the market. HIGH RELIABILITY DURING LONG LIFE TIME Charge Indicator • The HVF Circuit Breaker employs a robust design with rugged components for increased durability and reduced maintenance. Close/Open Indicator • The HVF Circuit Breaker is capable of back-to-back capacitor switching of 90 MVAR, far in excess of ANSI standards. • Compact Design (Nominal Dimensions) Hole for Manual Charging Counter Width = 42 Inches Height = 110 Inches Depth Manual Close Button = 148 Inches - Indoor 152 Inches - Outdoor, non walk-in 20 Feet - Outdoor Protected Aisle Manual Open Button 33 Feet - Outdoor Common Aisle LOW MAINTENANCE • The HVF Circuit Breaker requires very little maintenance. Only those parts subject to normal wear and aging need to be serviced to ensure reliable operation. • Routine checks are required after 3 years and no lubrication is required until 10 years in normal operation. CIRCUIT BREAKER FEATURES • Both 31.5kA and 40kA interrupting ratings are available. Why pay for the high interrupting breaker unless it is necessary? Dimensions: HVF Draw-out T ype VCB (38Kv) Type Dimensions in mm • The HVF Breaker utilizes self-aligning/self-coupling secondary disconnects that assure positive connection of relay circuits to the trip coil of the circuit breaker. • No manual connection of a plug and socket or umbilical cord by a technician is required. Heavy-duty utility grade contacts are furnished instead of light duty electronic type connectors. 38 KV CELL INTERIOR • Self-aligning/self-coupling secondaries - no manual plug & socket connection required. 38 KV SWITCHGEAR FEATURES • Enclosures are only 42 inches wide. • Drawout CPT’s (up to 15 kVA) or draw-out PT’s can be mounted above circuit breakers in the same enclosure, thus reducing the length of the lineup. • Grounded metal shutters. • Closed door racking is available. • Full set of ANSI interlocks. • Remote trip/close is available. • Rugged construction. • Separate disconnect, test and connected positions. • Remote electronically operated racking device is available. • Both manually operated and electrically operated ground and test devices are available. Ratings & Additional Products Description Type No. ____________________________________________ Application standard _________________________________ Rated voltage (Kv) ___________________________________ Rated current (A) ____________________________________ Rated interrupting current (Ka) _________________________ Rated Close & Latch (Ka) ______________________________ Frequency (Hz) ______________________________________ Rated Low Frequency Withstand (Kv, RMS) ______________ Impulse withstand voltage (Kv,B.I.L.) ___________________________________________ Breaking time (cycles) ________________________________ Operating duty ______________________________________ Operating life at rated current (times) ___________________ Closing operation ______________ Operation system ____ ______________ Control voltage ______ Closing & tripping control (V) _____ Control voltage ______ Auxiliary contacts ____________________________________ Weight of breaker Mainbody (Lbs.) _____________________ All circuit braker ratings are based on K = 1.0 HVF705 ANSI C37.06 / ANSI C37.09 38 1200, 2000, 2500, 3000 31.5 or 40 82 or 104 60 80 170 5 0 -0.3s-CO-3min-CO 20,000 Motor Spring Stored Energy DC 48, 60, 110, 125, 220 /AC 120, 240 DC 48, 60, 110, 125, 220 /AC 120, 240 4NO + 4NC (Max. 10NO + 10NC) 1200a- 750 2000a- 800 2500a- 850 3000a- 850 • Drawout potential transformers can be mounted above a circuit breaker. • Drawout control power transformers (up to 15kVA) can be mounted above a circuit breaker. • Space saving design - reduce size of building required to house the switchgear. Controlled Power HVF series vacuum cir cuit breakers: circuit Three pole drawout units for use in 38 kV switchgear 38kV switchgear.. Typical Breaker Elements Typical Cir cuit Diagram Circuit 38 kV Switchgear Features Controlled Power has manufactured 38kV switchgear since 1980. Hundreds of 38kV circuit breakers are in reliable operation in transit, utility, and industrial applications. The breakers, including vacuum interrupters, are designed and manufactured with advanced vacuum technology and have been tested according to the latest version of ANSI Standards in ISO 9001 facilities. The circuit breakers are available in 1200A, 2000A, 2500A, and 3000A (FC) continuous ratings. The breakers are constantly being improved to satisfy all demands of the market. HIGH RELIABILITY DURING LONG LIFE TIME Charge Indicator • The HVF Circuit Breaker employs a robust design with rugged components for increased durability and reduced maintenance. Close/Open Indicator • The HVF Circuit Breaker is capable of back-to-back capacitor switching of 90 MVAR, far in excess of ANSI standards. • Compact Design (Nominal Dimensions) Hole for Manual Charging Counter Width = 42 Inches Height = 110 Inches Depth Manual Close Button = 148 Inches - Indoor 152 Inches - Outdoor, non walk-in 20 Feet - Outdoor Protected Aisle Manual Open Button 33 Feet - Outdoor Common Aisle LOW MAINTENANCE • The HVF Circuit Breaker requires very little maintenance. Only those parts subject to normal wear and aging need to be serviced to ensure reliable operation. • Routine checks are required after 3 years and no lubrication is required until 10 years in normal operation. CIRCUIT BREAKER FEATURES • Both 31.5kA and 40kA interrupting ratings are available. Why pay for the high interrupting breaker unless it is necessary? Dimensions: HVF Draw-out T ype VCB (38Kv) Type Dimensions in mm • The HVF Breaker utilizes self-aligning/self-coupling secondary disconnects that assure positive connection of relay circuits to the trip coil of the circuit breaker. • No manual connection of a plug and socket or umbilical cord by a technician is required. Heavy-duty utility grade contacts are furnished instead of light duty electronic type connectors. 38 KV CELL INTERIOR • Self-aligning/self-coupling secondaries - no manual plug & socket connection required. 38 KV SWITCHGEAR FEATURES • Enclosures are only 42 inches wide. • Drawout CPT’s (up to 15 kVA) or draw-out PT’s can be mounted above circuit breakers in the same enclosure, thus reducing the length of the lineup. • Grounded metal shutters. • Closed door racking is available. • Full set of ANSI interlocks. • Remote trip/close is available. • Rugged construction. • Separate disconnect, test and connected positions. • Remote electronically operated racking device is available. • Both manually operated and electrically operated ground and test devices are available. Ratings & Additional Products Description Type No. ____________________________________________ Application standard _________________________________ Rated voltage (Kv) ___________________________________ Rated current (A) ____________________________________ Rated interrupting current (Ka) _________________________ Rated Close & Latch (Ka) ______________________________ Frequency (Hz) ______________________________________ Rated Low Frequency Withstand (Kv, RMS) ______________ Impulse withstand voltage (Kv,B.I.L.) ___________________________________________ Breaking time (cycles) ________________________________ Operating duty ______________________________________ Operating life at rated current (times) ___________________ Closing operation ______________ Operation system ____ ______________ Control voltage ______ Closing & tripping control (V) _____ Control voltage ______ Auxiliary contacts ____________________________________ Weight of breaker Mainbody (Lbs.) _____________________ All circuit braker ratings are based on K = 1.0 HVF705 ANSI C37.06 / ANSI C37.09 38 1200, 2000, 2500, 3000 31.5 or 40 82 or 104 60 80 170 5 0 -0.3s-CO-3min-CO 20,000 Motor Spring Stored Energy DC 48, 60, 110, 125, 220 /AC 120, 240 DC 48, 60, 110, 125, 220 /AC 120, 240 4NO + 4NC (Max. 10NO + 10NC) 1200a- 750 2000a- 800 2500a- 850 3000a- 850 • Drawout potential transformers can be mounted above a circuit breaker. • Drawout control power transformers (up to 15kVA) can be mounted above a circuit breaker. • Space saving design - reduce size of building required to house the switchgear. Current Consumption Inspection Points Rated Voltage (V) Motor 21 10.5 8 4.5 4.5 2.3 6.4 3.2 24DC 48DC 60DC 110DC 125DC 220DC 120AC 240AC Current Consumption (A) Closing Solenoid 4 2.7 1.7 1.3 1.5 0.65 1.3 0.65 Description of HVF VCB Open Solenoid 4 2.7 1.7 1.3 1.5 0.65 1.3 0.65 INSPECTION ITEMS DESCRIPTION INTERVAL • General Check 3 Years 1. Clean the Insulated surface with dry cloth to remove dust and moisture. 2. Check the exterior for damage. 3. Check for loose bolts and nuts of the operating mechanism. 4. Check stop ring and stop retainer for damage. 5. Check terminals for loose connection or correction. • Operation Test 3 years 1. Operate a few times manually and electrically. Check each part for proper function. 2. Check ON/OFF indicator and counter for proper function. • Insulation Resistance 1. Measure insulation resistance between phase and between pole and ground with a 1000V megger. If the measured value is less than 500M , check the cause. 2. Check the insulation resistance between control circuit and ground using a 500V megger If the measured value is less than 2M , check the cause. 3 years • Lubrication 10 years or 5000 operations 1. Lubricate each part of operating mechanism. 2. Clean disconnection unit with a dry cloth and a small amount of grease. (lithium soapbased grease) • Vacuum Interrupter 10 years or 5000 operations 1. Check the contact erosion limit. 2. Operating the circuit, check the vacuum degree of vacuum bottle. 38Kv Cir cuit Breaker Retrofits Circuit Controlled Power can retrofit any of your existing Minimum Oil, Vacuum, SF-6, Air Magnetic or Air Blast circuit breakers with our modern Type HVF Vacuum Breaker and extend the life of your equipment. Call us today for more information. NO 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 31 32 ITEM Operating Mechanism Enclosure Gear Box Closing Spring Tripping Spring Link Coupling Bar Breaker Shaft Dash Pot Counter ON/OFF Indicator Spring Charged Indicator Closing Button Tripping Button Name Plate Hole for Manual Charging Motor Closing Solenoid (Y9) 33 34 35 36 41 42 44 45 46 47 49 55 57 58 59 60 Tripping Solenoid (Y1) Limit Switch (S21, S22, S3) AntiPumping Contactor Auxiliary Switch (S1) Vacuum Interrupter Upper Terminal Lower Pole Support Ring Contact Lever Lower Terminal Contact Pressure Spring Insulation Frame Insulation Rod Spring Guide Eye Bolt Truck Lubrication Points Phone: 330.834.3200 • Fax: 330.834.3201 w w w . c o n t r o l l e d p o w e r.com Current Consumption Inspection Points Rated Voltage (V) Motor 21 10.5 8 4.5 4.5 2.3 6.4 3.2 24DC 48DC 60DC 110DC 125DC 220DC 120AC 240AC Current Consumption (A) Closing Solenoid 4 2.7 1.7 1.3 1.5 0.65 1.3 0.65 Description of HVF VCB Open Solenoid 4 2.7 1.7 1.3 1.5 0.65 1.3 0.65 INSPECTION ITEMS DESCRIPTION INTERVAL • General Check 3 Years 1. Clean the Insulated surface with dry cloth to remove dust and moisture. 2. Check the exterior for damage. 3. Check for loose bolts and nuts of the operating mechanism. 4. Check stop ring and stop retainer for damage. 5. Check terminals for loose connection or correction. • Operation Test 3 years 1. Operate a few times manually and electrically. Check each part for proper function. 2. Check ON/OFF indicator and counter for proper function. • Insulation Resistance 1. Measure insulation resistance between phase and between pole and ground with a 1000V megger. If the measured value is less than 500M , check the cause. 2. Check the insulation resistance between control circuit and ground using a 500V megger If the measured value is less than 2M , check the cause. 3 years • Lubrication 10 years or 5000 operations 1. Lubricate each part of operating mechanism. 2. Clean disconnection unit with a dry cloth and a small amount of grease. (lithium soapbased grease) • Vacuum Interrupter 10 years or 5000 operations 1. Check the contact erosion limit. 2. Operating the circuit, check the vacuum degree of vacuum bottle. 38Kv Cir cuit Breaker Retrofits Circuit Controlled Power can retrofit any of your existing Minimum Oil, Vacuum, SF-6, Air Magnetic or Air Blast circuit breakers with our modern Type HVF Vacuum Breaker and extend the life of your equipment. Call us today for more information. NO 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 31 32 ITEM Operating Mechanism Enclosure Gear Box Closing Spring Tripping Spring Link Coupling Bar Breaker Shaft Dash Pot Counter ON/OFF Indicator Spring Charged Indicator Closing Button Tripping Button Name Plate Hole for Manual Charging Motor Closing Solenoid (Y9) 33 34 35 36 41 42 44 45 46 47 49 55 57 58 59 60 Tripping Solenoid (Y1) Limit Switch (S21, S22, S3) AntiPumping Contactor Auxiliary Switch (S1) Vacuum Interrupter Upper Terminal Lower Pole Support Ring Contact Lever Lower Terminal Contact Pressure Spring Insulation Frame Insulation Rod Spring Guide Eye Bolt Truck Lubrication Points Phone: 330.834.3200 • Fax: 330.834.3201 w w w . c o n t r o l l e d p o w e r.com