Cut Sheet - Myers Power Products

advertisement
Current Consumption
Inspection Points
Rated Voltage (V)
Motor
21
10.5
8
4.5
4.5
2.3
6.4
3.2
24DC
48DC
60DC
110DC
125DC
220DC
120AC
240AC
Current Consumption (A)
Closing Solenoid
4
2.7
1.7
1.3
1.5
0.65
1.3
0.65
Description of HVF VCB
Open Solenoid
4
2.7
1.7
1.3
1.5
0.65
1.3
0.65
INSPECTION ITEMS DESCRIPTION
INTERVAL
• General Check
3 Years
1. Clean the Insulated surface with dry cloth to remove dust
and moisture.
2. Check the exterior for damage.
3. Check for loose bolts and nuts of the operating mechanism.
4. Check stop ring and stop retainer for damage.
5. Check terminals for loose connection or correction.
• Operation Test
3 years
1. Operate a few times manually and electrically.
Check each part for proper function.
2. Check ON/OFF indicator and counter for proper function.
• Insulation Resistance
1. Measure insulation resistance between phase and between pole
and ground with a 1000V megger. If the measured value is less
than 500M , check the cause.
2. Check the insulation resistance between control circuit and ground
using a 500V megger If the measured value is less than 2M ,
check the cause.
3 years
• Lubrication
10 years or 5000 operations
1. Lubricate each part of operating mechanism.
2. Clean disconnection unit with a dry cloth and a small amount of
grease. (lithium soapbased grease)
• Vacuum Interrupter
10 years or 5000 operations
1. Check the contact erosion limit.
2. Operating the circuit, check the vacuum degree of vacuum bottle.
38Kv Cir
cuit Breaker Retrofits
Circuit
Controlled Power can retrofit any of your existing Minimum Oil, Vacuum, SF-6, Air Magnetic or Air Blast
circuit breakers with our modern Type HVF Vacuum Breaker and extend the life of your equipment. Call us
today for more information.
NO
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
31
32
ITEM
Operating Mechanism Enclosure
Gear Box
Closing Spring
Tripping Spring
Link
Coupling Bar
Breaker Shaft
Dash Pot
Counter
ON/OFF Indicator
Spring Charged Indicator
Closing Button
Tripping Button
Name Plate
Hole for Manual Charging
Motor
Closing Solenoid (Y9)
33
34
35
36
41
42
44
45
46
47
49
55
57
58
59
60
Tripping Solenoid (Y1)
Limit Switch (S21, S22, S3)
AntiPumping Contactor
Auxiliary Switch (S1)
Vacuum Interrupter
Upper Terminal
Lower Pole Support
Ring Contact
Lever
Lower Terminal
Contact Pressure Spring
Insulation Frame
Insulation Rod
Spring Guide
Eye Bolt
Truck
Lubrication Points
Phone: 330.834.3200 • Fax: 330.834.3201
w w w . c o n t r o l l e d p o w e r.com
Controlled Power HVF series vacuum cir
cuit breakers:
circuit
Three pole drawout units for use in 38
kV switchgear
38kV
switchgear..
Typical Breaker Elements
Typical Cir
cuit Diagram
Circuit
38 kV Switchgear Features
Controlled Power has manufactured 38kV switchgear since 1980. Hundreds of 38kV circuit breakers are in reliable operation
in transit, utility, and industrial applications.
The breakers, including vacuum interrupters, are designed and manufactured with advanced vacuum technology and have
been tested according to the latest version of ANSI Standards in ISO 9001 facilities.
The circuit breakers are available in 1200A, 2000A, 2500A, and 3000A (FC) continuous ratings. The breakers are constantly
being improved to satisfy all demands of the market.
HIGH RELIABILITY DURING LONG LIFE TIME
Charge
Indicator
• The HVF Circuit Breaker employs a robust design with rugged components for
increased durability and reduced maintenance.
Close/Open
Indicator
• The HVF Circuit Breaker is capable of back-to-back capacitor switching of 90
MVAR, far in excess of ANSI standards.
• Compact Design (Nominal Dimensions)
Hole for
Manual
Charging
Counter
Width
= 42 Inches
Height = 110 Inches
Depth
Manual
Close
Button
= 148 Inches - Indoor
152 Inches - Outdoor, non walk-in
20 Feet - Outdoor Protected Aisle
Manual
Open
Button
33 Feet - Outdoor Common Aisle
LOW MAINTENANCE
• The HVF Circuit Breaker requires very little maintenance. Only those parts subject
to normal wear and aging need to be serviced to ensure reliable operation.
• Routine checks are required after 3 years and no lubrication is required until 10
years in normal operation.
CIRCUIT BREAKER FEATURES
• Both 31.5kA and 40kA interrupting ratings are available. Why pay for the high
interrupting breaker unless it is necessary?
Dimensions: HVF Draw-out T
ype VCB (38Kv)
Type
Dimensions in mm
• The HVF Breaker utilizes self-aligning/self-coupling secondary disconnects that
assure positive connection of relay circuits to the trip coil of the circuit breaker.
• No manual connection of a plug and socket or umbilical cord by a technician is
required. Heavy-duty utility grade contacts are furnished instead of light duty
electronic type connectors.
38 KV CELL INTERIOR
• Self-aligning/self-coupling secondaries - no manual plug &
socket connection required.
38 KV SWITCHGEAR FEATURES
• Enclosures are only 42 inches wide.
• Drawout CPT’s (up to 15 kVA) or draw-out PT’s can be mounted above circuit
breakers in the same enclosure, thus reducing the length of the lineup.
• Grounded metal shutters.
• Closed door racking is available.
• Full set of ANSI interlocks.
• Remote trip/close is available.
• Rugged construction.
• Separate disconnect, test and connected positions.
• Remote electronically operated racking device is available.
• Both manually operated and electrically operated ground and test devices are
available.
Ratings & Additional Products Description
Type No. ____________________________________________
Application standard _________________________________
Rated voltage (Kv) ___________________________________
Rated current (A) ____________________________________
Rated interrupting current (Ka) _________________________
Rated Close & Latch (Ka) ______________________________
Frequency (Hz) ______________________________________
Rated Low Frequency Withstand (Kv, RMS) ______________
Impulse withstand voltage
(Kv,B.I.L.) ___________________________________________
Breaking time (cycles) ________________________________
Operating duty ______________________________________
Operating life at rated current (times) ___________________
Closing operation ______________ Operation system ____
______________ Control voltage ______
Closing & tripping control (V) _____ Control voltage ______
Auxiliary contacts ____________________________________
Weight of breaker Mainbody (Lbs.) _____________________
All circuit braker ratings are based on K = 1.0
HVF705
ANSI C37.06 / ANSI C37.09
38
1200, 2000, 2500, 3000
31.5 or 40
82 or 104
60
80
170
5
0 -0.3s-CO-3min-CO
20,000
Motor Spring Stored Energy
DC 48, 60, 110, 125, 220 /AC 120, 240
DC 48, 60, 110, 125, 220 /AC 120, 240
4NO + 4NC (Max. 10NO + 10NC)
1200a- 750
2000a- 800
2500a- 850
3000a- 850
• Drawout potential transformers can be mounted above a
circuit breaker.
• Drawout control power transformers (up to 15kVA) can be
mounted above a circuit breaker.
• Space saving design - reduce size of building required to
house the switchgear.
Controlled Power HVF series vacuum cir
cuit breakers:
circuit
Three pole drawout units for use in 38
kV switchgear
38kV
switchgear..
Typical Breaker Elements
Typical Cir
cuit Diagram
Circuit
38 kV Switchgear Features
Controlled Power has manufactured 38kV switchgear since 1980. Hundreds of 38kV circuit breakers are in reliable operation
in transit, utility, and industrial applications.
The breakers, including vacuum interrupters, are designed and manufactured with advanced vacuum technology and have
been tested according to the latest version of ANSI Standards in ISO 9001 facilities.
The circuit breakers are available in 1200A, 2000A, 2500A, and 3000A (FC) continuous ratings. The breakers are constantly
being improved to satisfy all demands of the market.
HIGH RELIABILITY DURING LONG LIFE TIME
Charge
Indicator
• The HVF Circuit Breaker employs a robust design with rugged components for
increased durability and reduced maintenance.
Close/Open
Indicator
• The HVF Circuit Breaker is capable of back-to-back capacitor switching of 90
MVAR, far in excess of ANSI standards.
• Compact Design (Nominal Dimensions)
Hole for
Manual
Charging
Counter
Width
= 42 Inches
Height = 110 Inches
Depth
Manual
Close
Button
= 148 Inches - Indoor
152 Inches - Outdoor, non walk-in
20 Feet - Outdoor Protected Aisle
Manual
Open
Button
33 Feet - Outdoor Common Aisle
LOW MAINTENANCE
• The HVF Circuit Breaker requires very little maintenance. Only those parts subject
to normal wear and aging need to be serviced to ensure reliable operation.
• Routine checks are required after 3 years and no lubrication is required until 10
years in normal operation.
CIRCUIT BREAKER FEATURES
• Both 31.5kA and 40kA interrupting ratings are available. Why pay for the high
interrupting breaker unless it is necessary?
Dimensions: HVF Draw-out T
ype VCB (38Kv)
Type
Dimensions in mm
• The HVF Breaker utilizes self-aligning/self-coupling secondary disconnects that
assure positive connection of relay circuits to the trip coil of the circuit breaker.
• No manual connection of a plug and socket or umbilical cord by a technician is
required. Heavy-duty utility grade contacts are furnished instead of light duty
electronic type connectors.
38 KV CELL INTERIOR
• Self-aligning/self-coupling secondaries - no manual plug &
socket connection required.
38 KV SWITCHGEAR FEATURES
• Enclosures are only 42 inches wide.
• Drawout CPT’s (up to 15 kVA) or draw-out PT’s can be mounted above circuit
breakers in the same enclosure, thus reducing the length of the lineup.
• Grounded metal shutters.
• Closed door racking is available.
• Full set of ANSI interlocks.
• Remote trip/close is available.
• Rugged construction.
• Separate disconnect, test and connected positions.
• Remote electronically operated racking device is available.
• Both manually operated and electrically operated ground and test devices are
available.
Ratings & Additional Products Description
Type No. ____________________________________________
Application standard _________________________________
Rated voltage (Kv) ___________________________________
Rated current (A) ____________________________________
Rated interrupting current (Ka) _________________________
Rated Close & Latch (Ka) ______________________________
Frequency (Hz) ______________________________________
Rated Low Frequency Withstand (Kv, RMS) ______________
Impulse withstand voltage
(Kv,B.I.L.) ___________________________________________
Breaking time (cycles) ________________________________
Operating duty ______________________________________
Operating life at rated current (times) ___________________
Closing operation ______________ Operation system ____
______________ Control voltage ______
Closing & tripping control (V) _____ Control voltage ______
Auxiliary contacts ____________________________________
Weight of breaker Mainbody (Lbs.) _____________________
All circuit braker ratings are based on K = 1.0
HVF705
ANSI C37.06 / ANSI C37.09
38
1200, 2000, 2500, 3000
31.5 or 40
82 or 104
60
80
170
5
0 -0.3s-CO-3min-CO
20,000
Motor Spring Stored Energy
DC 48, 60, 110, 125, 220 /AC 120, 240
DC 48, 60, 110, 125, 220 /AC 120, 240
4NO + 4NC (Max. 10NO + 10NC)
1200a- 750
2000a- 800
2500a- 850
3000a- 850
• Drawout potential transformers can be mounted above a
circuit breaker.
• Drawout control power transformers (up to 15kVA) can be
mounted above a circuit breaker.
• Space saving design - reduce size of building required to
house the switchgear.
Controlled Power HVF series vacuum cir
cuit breakers:
circuit
Three pole drawout units for use in 38
kV switchgear
38kV
switchgear..
Typical Breaker Elements
Typical Cir
cuit Diagram
Circuit
38 kV Switchgear Features
Controlled Power has manufactured 38kV switchgear since 1980. Hundreds of 38kV circuit breakers are in reliable operation
in transit, utility, and industrial applications.
The breakers, including vacuum interrupters, are designed and manufactured with advanced vacuum technology and have
been tested according to the latest version of ANSI Standards in ISO 9001 facilities.
The circuit breakers are available in 1200A, 2000A, 2500A, and 3000A (FC) continuous ratings. The breakers are constantly
being improved to satisfy all demands of the market.
HIGH RELIABILITY DURING LONG LIFE TIME
Charge
Indicator
• The HVF Circuit Breaker employs a robust design with rugged components for
increased durability and reduced maintenance.
Close/Open
Indicator
• The HVF Circuit Breaker is capable of back-to-back capacitor switching of 90
MVAR, far in excess of ANSI standards.
• Compact Design (Nominal Dimensions)
Hole for
Manual
Charging
Counter
Width
= 42 Inches
Height = 110 Inches
Depth
Manual
Close
Button
= 148 Inches - Indoor
152 Inches - Outdoor, non walk-in
20 Feet - Outdoor Protected Aisle
Manual
Open
Button
33 Feet - Outdoor Common Aisle
LOW MAINTENANCE
• The HVF Circuit Breaker requires very little maintenance. Only those parts subject
to normal wear and aging need to be serviced to ensure reliable operation.
• Routine checks are required after 3 years and no lubrication is required until 10
years in normal operation.
CIRCUIT BREAKER FEATURES
• Both 31.5kA and 40kA interrupting ratings are available. Why pay for the high
interrupting breaker unless it is necessary?
Dimensions: HVF Draw-out T
ype VCB (38Kv)
Type
Dimensions in mm
• The HVF Breaker utilizes self-aligning/self-coupling secondary disconnects that
assure positive connection of relay circuits to the trip coil of the circuit breaker.
• No manual connection of a plug and socket or umbilical cord by a technician is
required. Heavy-duty utility grade contacts are furnished instead of light duty
electronic type connectors.
38 KV CELL INTERIOR
• Self-aligning/self-coupling secondaries - no manual plug &
socket connection required.
38 KV SWITCHGEAR FEATURES
• Enclosures are only 42 inches wide.
• Drawout CPT’s (up to 15 kVA) or draw-out PT’s can be mounted above circuit
breakers in the same enclosure, thus reducing the length of the lineup.
• Grounded metal shutters.
• Closed door racking is available.
• Full set of ANSI interlocks.
• Remote trip/close is available.
• Rugged construction.
• Separate disconnect, test and connected positions.
• Remote electronically operated racking device is available.
• Both manually operated and electrically operated ground and test devices are
available.
Ratings & Additional Products Description
Type No. ____________________________________________
Application standard _________________________________
Rated voltage (Kv) ___________________________________
Rated current (A) ____________________________________
Rated interrupting current (Ka) _________________________
Rated Close & Latch (Ka) ______________________________
Frequency (Hz) ______________________________________
Rated Low Frequency Withstand (Kv, RMS) ______________
Impulse withstand voltage
(Kv,B.I.L.) ___________________________________________
Breaking time (cycles) ________________________________
Operating duty ______________________________________
Operating life at rated current (times) ___________________
Closing operation ______________ Operation system ____
______________ Control voltage ______
Closing & tripping control (V) _____ Control voltage ______
Auxiliary contacts ____________________________________
Weight of breaker Mainbody (Lbs.) _____________________
All circuit braker ratings are based on K = 1.0
HVF705
ANSI C37.06 / ANSI C37.09
38
1200, 2000, 2500, 3000
31.5 or 40
82 or 104
60
80
170
5
0 -0.3s-CO-3min-CO
20,000
Motor Spring Stored Energy
DC 48, 60, 110, 125, 220 /AC 120, 240
DC 48, 60, 110, 125, 220 /AC 120, 240
4NO + 4NC (Max. 10NO + 10NC)
1200a- 750
2000a- 800
2500a- 850
3000a- 850
• Drawout potential transformers can be mounted above a
circuit breaker.
• Drawout control power transformers (up to 15kVA) can be
mounted above a circuit breaker.
• Space saving design - reduce size of building required to
house the switchgear.
Current Consumption
Inspection Points
Rated Voltage (V)
Motor
21
10.5
8
4.5
4.5
2.3
6.4
3.2
24DC
48DC
60DC
110DC
125DC
220DC
120AC
240AC
Current Consumption (A)
Closing Solenoid
4
2.7
1.7
1.3
1.5
0.65
1.3
0.65
Description of HVF VCB
Open Solenoid
4
2.7
1.7
1.3
1.5
0.65
1.3
0.65
INSPECTION ITEMS DESCRIPTION
INTERVAL
• General Check
3 Years
1. Clean the Insulated surface with dry cloth to remove dust
and moisture.
2. Check the exterior for damage.
3. Check for loose bolts and nuts of the operating mechanism.
4. Check stop ring and stop retainer for damage.
5. Check terminals for loose connection or correction.
• Operation Test
3 years
1. Operate a few times manually and electrically.
Check each part for proper function.
2. Check ON/OFF indicator and counter for proper function.
• Insulation Resistance
1. Measure insulation resistance between phase and between pole
and ground with a 1000V megger. If the measured value is less
than 500M , check the cause.
2. Check the insulation resistance between control circuit and ground
using a 500V megger If the measured value is less than 2M ,
check the cause.
3 years
• Lubrication
10 years or 5000 operations
1. Lubricate each part of operating mechanism.
2. Clean disconnection unit with a dry cloth and a small amount of
grease. (lithium soapbased grease)
• Vacuum Interrupter
10 years or 5000 operations
1. Check the contact erosion limit.
2. Operating the circuit, check the vacuum degree of vacuum bottle.
38Kv Cir
cuit Breaker Retrofits
Circuit
Controlled Power can retrofit any of your existing Minimum Oil, Vacuum, SF-6, Air Magnetic or Air Blast
circuit breakers with our modern Type HVF Vacuum Breaker and extend the life of your equipment. Call us
today for more information.
NO
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
31
32
ITEM
Operating Mechanism Enclosure
Gear Box
Closing Spring
Tripping Spring
Link
Coupling Bar
Breaker Shaft
Dash Pot
Counter
ON/OFF Indicator
Spring Charged Indicator
Closing Button
Tripping Button
Name Plate
Hole for Manual Charging
Motor
Closing Solenoid (Y9)
33
34
35
36
41
42
44
45
46
47
49
55
57
58
59
60
Tripping Solenoid (Y1)
Limit Switch (S21, S22, S3)
AntiPumping Contactor
Auxiliary Switch (S1)
Vacuum Interrupter
Upper Terminal
Lower Pole Support
Ring Contact
Lever
Lower Terminal
Contact Pressure Spring
Insulation Frame
Insulation Rod
Spring Guide
Eye Bolt
Truck
Lubrication Points
Phone: 330.834.3200 • Fax: 330.834.3201
w w w . c o n t r o l l e d p o w e r.com
Current Consumption
Inspection Points
Rated Voltage (V)
Motor
21
10.5
8
4.5
4.5
2.3
6.4
3.2
24DC
48DC
60DC
110DC
125DC
220DC
120AC
240AC
Current Consumption (A)
Closing Solenoid
4
2.7
1.7
1.3
1.5
0.65
1.3
0.65
Description of HVF VCB
Open Solenoid
4
2.7
1.7
1.3
1.5
0.65
1.3
0.65
INSPECTION ITEMS DESCRIPTION
INTERVAL
• General Check
3 Years
1. Clean the Insulated surface with dry cloth to remove dust
and moisture.
2. Check the exterior for damage.
3. Check for loose bolts and nuts of the operating mechanism.
4. Check stop ring and stop retainer for damage.
5. Check terminals for loose connection or correction.
• Operation Test
3 years
1. Operate a few times manually and electrically.
Check each part for proper function.
2. Check ON/OFF indicator and counter for proper function.
• Insulation Resistance
1. Measure insulation resistance between phase and between pole
and ground with a 1000V megger. If the measured value is less
than 500M , check the cause.
2. Check the insulation resistance between control circuit and ground
using a 500V megger If the measured value is less than 2M ,
check the cause.
3 years
• Lubrication
10 years or 5000 operations
1. Lubricate each part of operating mechanism.
2. Clean disconnection unit with a dry cloth and a small amount of
grease. (lithium soapbased grease)
• Vacuum Interrupter
10 years or 5000 operations
1. Check the contact erosion limit.
2. Operating the circuit, check the vacuum degree of vacuum bottle.
38Kv Cir
cuit Breaker Retrofits
Circuit
Controlled Power can retrofit any of your existing Minimum Oil, Vacuum, SF-6, Air Magnetic or Air Blast
circuit breakers with our modern Type HVF Vacuum Breaker and extend the life of your equipment. Call us
today for more information.
NO
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
31
32
ITEM
Operating Mechanism Enclosure
Gear Box
Closing Spring
Tripping Spring
Link
Coupling Bar
Breaker Shaft
Dash Pot
Counter
ON/OFF Indicator
Spring Charged Indicator
Closing Button
Tripping Button
Name Plate
Hole for Manual Charging
Motor
Closing Solenoid (Y9)
33
34
35
36
41
42
44
45
46
47
49
55
57
58
59
60
Tripping Solenoid (Y1)
Limit Switch (S21, S22, S3)
AntiPumping Contactor
Auxiliary Switch (S1)
Vacuum Interrupter
Upper Terminal
Lower Pole Support
Ring Contact
Lever
Lower Terminal
Contact Pressure Spring
Insulation Frame
Insulation Rod
Spring Guide
Eye Bolt
Truck
Lubrication Points