ISO 9001: 2000 Circuit Breakers Switch Disconnectors Disconnectors Earthing Switches Operating Devices Accessories 3AH5 Vacuum circuit - breaker Catalogue No 04.01.02.EN Vacuum circuit-breaker 3AH5 1. SPECIAL FEATURES Today's circuit-breakers must satisfy all kinds of requirements encountered in the switching of ohmic, inductive or capacitive currents. They have to remain reliable when idle, just as they have to handle a high number of operating cycles. The low short-circuit ratings in distribution networks and the high breaking currents in industrial applications illustrate the extremes that prevail. The new 3AH5 vacuum circuit-breaker is a true allrounder. Its compact dimensions allow it to fit into any switchgear assembly. The expanded range of its technical data make it ideal for use throughout the medium-voltage spectrum. Vacuum technology enhances efficiency Vacuum is the most efficient quenching medium for medium-voltage switchgear. We have optimized the switching-in-vacuum principle to the extent that it is superior to other quenching technologies in every respect. For example, the dielectric and contact resistance remain constant, and a high level of summated current is attained. Notable features of our all-round 3AH5 vacuum-circuit breaker include: - High reliability - Proven technology - Maintenance-free - Lifetime up to 10,000 operating cycles - Compact dimensions - Uncomplicated control panel Further characteristics compromise: - Uniform post-insulator design - Rated voltage from 12 to 36 kV - Rated short-circuit breaking currents from 13,1 to 31,5 kA - Rated normal currents from 800 to 2 500 A - Pole center distances from 160 to 350 mm 2. CONSTRUCTION AND MODE OF OPERATION Pole assemblies, mechanisms The pole assemblies consist of: - vacuum interrupters - 2 interrupter supports 1 2 3 The vacuum interrupters are freely accessible, therefore enabling the insulating parts to be easily cleaned in the case of difficult ambient conditions (fouling). 4 The operating motion results from the operating rod [15], lever [14] and contact-pressure spring [9] to the bracket [10] attached to the drive bolt [5]. Page 2/12 12 5 6 The pole assemblies are mounted on the housing of the operating mechanism by means of post insulators. Vacuum interrupter [4] is mounted rigidly to the upper interrupter support [1]. The lower part of the interrupter is inserted in the lower interrupter support [7]. The struts [3] and [12] absorb the external forces arising from switching operations and contact pressure. 11 13 7 8 9 14 10 Vacuum circuit-breaker 3AH5 24 kV, 25 kA , 1250 A 15 Section through the pole assembly Legend 1 - upper interrupter support, 2 - upper teminal, 3 - outer strunt, 4 - vacuum interrupter, 5 - drive bolt of the vacuum interrupter, 6 - flexible connector, 7 - lower interrupter support, 8 - lower terminal, 9 - opening and contact-pressure spring, 10 - bracket, 11 - upper post insulator, 12 - inner strut, 13 - lower post insulator, 14 - lever, 15 - operating rod ZWAE Sp. z o.o. Vacuum circuit-breaker 3AH5 Arc-quenching system As the contacts are galvanically separated, the current that is to be interrupted initiates a metal-vapour arc discharge. Current continues flowing through the metal-vapour plasma until the next current zero. The arc extinguishes at approximately current zero. The metalvapour loses its conductivity within a few microseconds, which very quickly re-establishes the dielectric strength of the contact gap. In order to prevent impermissible overvoltages when performing switching operations in inductive circuits, the lowest possible value. Due to the use of a special contact material, the chopping current in the 3AH5 vacuum circuit-breaker is only 2 to 3 A. Due to the rapid recovery of the dielectric strength of the contact gap, the arc is safetly quenched even in cases where contact separation occurs immediately before a current zero. Consequently, the arcing time of the last poles to clear is no more than 15 ms. With AC circuit-breakers the actual task of the arc-quenching system is to deionize the contact gap immediately after current zero. In the case of all the conventional methods of arc-quenching this means that the arc is being cooled even before the minimum quenching gap and the subsequent current zero are recharged. As a result, the arc power is unintentionally increased to a considerable degree. With the vacuum circuit-breaker, on the other hand, the arc is not cooled. The metal-vapour plasma has a high conductivity which results in a extremely low arc voltage with values from only 20 to 200 V. Operating mechanisms The whole operating mechanism is contained in a single housing, including the releases, auxiliary switches, indicators and actuating devices. Stored-energy operating mechanism The operating drive is usually a stored-energy mechanism. The mechanism operates the pole assemblies through rods. The closing spring can be charged either electrically or manually. It latches in when charging is complete. The closing spring acts as the stored-energy mechanism. To close the breaker, the closing spring can be unlatched either mechanically by means of the local "CLOSE" pushbutton or electrically by remote control. The closing spring charges the contact-pressure spring as the breaker closes. Vacuum interrupter (example) Drive and terminal bolt Guide Metal bellows Arcing chamber Moving contact piece Fixed contact piece Insulator Connecting disc For this reason, and due to the short arcing times, the amount of energy conversion in the contact gap is very low. This relatively low stress level means that the quenching system is maintenance-free. Due to very low pressures of less than 10-9 bar in the interrupter under steady-state conditions, contact gaps of only 6 to 20 mm are required to achieve a high dielectric strength. The breaker is now capable of performing the OPEN-CLOSE-OPEN switching sequence that is required for an unsuccessful auto-reclosing operation. All stored-energy mechanisms perform the switching duties of synchronizing and rapid load transfer (U) as well as auto-reclosing. Snap-action operating mechanism During closing operation, the contact-pressure springs are charged at the same time, therefore a storedenergy mechanism is available for opening. Opening can be initiated on all vacuum circuit-breakers by various releases or locally by the OPEN pushbutton. If there is a failure of power to the motor, the spring can always be recharged manually. The now discharged closing spring will be charged again automatically by the mechanism motor. ZWAE Sp. z o.o. Page 3/12 Vacuum circuit-breaker 3AH5 Trip-free mechanism The 3AH5 vacuum circuit-breakers are equipped with a trip-free mechanism according to IEC 60056 and VDE 0670. In the event of an opening command being given after a closing operation has been initiated, the moving contacts return to the open position and remain there even if the closing command is sustained. This means that the contacts of vacuum circuit-breakers are momentarily in the closed position under these circumstances, which is permitted according to IEC 60056 and VDE 0670. Motors of operating mechanism The motors operate in short-time duty and therefore the voltage and power consumption do not have to be in conformance with the data of the rating plate. Protection of the motors The inrush current in the motor can be neglected since it is of very brief duration. 3. SECONDARY EQUIPMENT The scope of the 3AH5 vacuum circuit-breaker secondary equipment depends on the particular application and offers a variety of possible variations which satisfy nearly every requirement. Releases A release is a device which transfers commands from an external source, such as a control room, to the latching mechanism of the circuit-breaker so that it can be opened or closed. The releases are designed for short-time duty up to 1 minute. In the case of 3AH5 vacuum circuit-breakers the pulse time has to be limited externally. 3AY1510 closing solenoid The closing solenoid unlatches the charged closing spring of the vacuum circuit-breaker, closing it by electrical means. Available for DC or AC operation. Shunt releases Shunt releases are used for automatic tripping of circuit-breakers by suitable protective relays and for deliberate tripping by electrical means. They are intended for connection to an external power supply (AC or DC) but, in special cases, may also be connected to a voltage transformer for manual operation. Two different types of shunt releases are available: - The 1st shunt release 3AY15 10 is normally included in the basic equipment of the vacuum circuit-breaker. With this design, the electric tripping pulse is fed to the "OPEN" lathing mechanism by means of directacting solenoid armature in order to open the circuitbreaker. - The 3AX1101 shunt release is fitted if 2nd shunt release is required. With this design, the electrical opening command is boosted by means of a solenoid armature unlatching a stored-energy mechanism before being fed to the "OPEN" lathing mechanism in order to open the breaker. Shorter opening times are possible with this release than with the 3AY15 10 type. Page 4/12 3AX1103 undervoltage release An undervoltage release comprises a stored-energy mechanism, an unlatching mechanism and an electromagnetic system which is permanently energized while the circuit breaker is closed. If the voltage falls below a predetermined value, unlatching of the release is enabled and the circuit-breaker is opened via the stored-mechanism. Manual tripping of the undervoltage release is generally performed with an NC contact in the tripping circuit but may also be performed with an NO contact by shortcircuiting the solenoid coil. With this type of release, the short-circuit current is limited bu the built-in resistors. Undervoltage releases can also be connected to voltage transformers. If the operating voltage drops to an impermissibly low level, the vacuum circuit-breaker will be tripped automatically. Unsuccessful attempts at closing when the solenoid coil of the undervoltage release is not energized can be prevented in the following ways: - by normally fitting electrical local closing in conjunction with the undervoltage release and additionally - by connecting the undervoltage release, operated through an NO contact and closing solenoid, to the same operating voltage. Undervoltage release with delay For delayed tripping, the undervoltage release can be combined with stored-energy mechanisms: - Type AN 1901 (for AC), settable delay times: 1 s - 1,8 s - 2,5 s - Type AN 1902 (for DC), settable delay times: 0,5 s - 0,9 s - 1,5 s. These stored-energy mechanisms can either be order together with the vacuum circuit-breaker, or can be purchased separately. Current transformer-operated release comprises: - a stored-energy mechanism - an unlatching mechanism - an electromagnetic system ZWAE Sp. z o.o. Vacuum circuit-breaker 3AH5 It is used when there is no external source of auxiliary power (e.g. a battery). Tripping is effected by means of a protective relay (e.g. overcurrent-time protection) acting on the current transformer-operated release. The following current transformer-operated releases are used: - 3AX11 02 current transformer-operated release with a rated current of 0.5 A or 1 A which requires auxiliary transformers (e.g. type 4AM5) in addition to the main current transformers. The stored-energy mechanism is unlatched when the tripping current is exceeded (90% of the rated current of the current transformer-operated release), thus causing the vacuum circuit-breaker to be opened. - 3AX11 04 current transformer-operated release, lowenergy version for a tripping pulse of min. 0.1 Ws. The transformer current ensures that the protective system is supplied with energy, and fills an energy store, the charge of which is available as a tripping pulse>=0.1 Ws at the time tripping. This pulse is switched by the command contact and is capable of activating the current transformer-operated release. The 3AX11 04 current transformer-operated release iss always used in conjunction with a protective relay that takes its supply and release energy for the vacuum circuit-breaker from its own current transformer and is thus not dependent on external auxiliary voltages: - 7SJ41 protective system - protective relay type WIP1 - similar protective systems. Anti-pumping (mechanical and electrical) If constant "CLOSE" and "OPEN" commands are present at the vacuum circuit-breaker at the same time, the vacuum circuit-breaker will return to the open position after closing. It remains in this position until a new "CLOSE" command is given. In this manner, continual closing and opening (= "pumping") is prevented. Breaker tripping signal The NO contact S6 makes brief contact while the circuit-breaker is opening and this is often used to the operate a hazard-warning system which, however, is only allowed to respond to automatic tripping of the circuit-breaker. Therefore, the signal from the NO contact must be interrupted when the circuit-breaker is being opened intentionally. This is accomplished under local control with the cutout switch S7 that is connected in series with the NO contact (see circuit on page 9). Position switch for signalling “Closing spring charged” The charging status of the closing spring in the vacuum circuit-breaker can be interrogated electrically by means of the position switch. ZWAE Sp. z o.o. Varistor module When inductive loads are being disconnected in DC circuits it is possible for switching overvoltages to be produced which might pose a risk to solid-state devices. This risk can be eliminated by connecting varistors across the inductances of the vacuum circuit-breaker (motor, closing solenoid, releases). A suitable varistor module for operating voltages >=60 V to 250 V DC is fitted when ordering; it limits overvoltages to approximately 500 V. Interlocking Mechanical interlocking Sensing devices on the system side check the status of the vacuum circuit-breaker and prevent it from closing if the associated disconnector is not in a position to allow safe operation. The system also prevents the disconnector from being operated while the vacuum circuit-breaker is closed. Similarly, the mechanical interlocking system can also be used for interlocking breaker trucks or withdrawable circuit-breaker units. Electrical interlocking Vacuum circuit-breakers can be incorporated in electromagnetic interlocking schemes for feeders and substations. With electrical interlocking, a magnetic lockout mechanism is fitted to the disconnector or its operating mechanism. The lockout is operated through an auxiliary contact of the vacuum circuit-breaker so that the disconnector can only be operated when the vacuum circuit breaker is open. The vacuum circuit-breaker is, on the other hand, controlled by the disconnector or its operating mechanism so that it may only be closed when the disconnector is at its end positions. Secondary connections (for control circuit) Versions: - terminal strip - 24 - pole plug connector with crimping connections - 64 - pole plug connector Other terminal assignment on request. Auxiliary switch The following versions are available: - 6NO + 6NC - 12NO + 12NC Rated insulation voltage 250 V AC/DC Insulation Class C to VDE 0110 Continuous current 10 A Making current 50 A Breaking capacity at 220 V DC, T = 20 ms 2A Page 5/12 Vacuum circuit-breaker 3AH5 4. EQUIPMENT OF CIRCUIT-BREAKER Basic eqipment - 1st shunt release - Auxiliary switch contacts 2NO + 2NC not wired Capabilities of release combinations Notices Additional equpment - Manual snap-action operating mechanism - Manual stored-energy mechanism By manual operating mechanism always with hand Basic Additional releases equipment (additional price) - Motor stored-energy mechanism With closing electromagnet and pumping prevention 1st release 2nd release 3AY15 10 3AX11 01 - Closing solenoid 3AY15 10 - 2nd shunt release - current transformer-operated release 0,5 A (rated current) or > 0,1 Ws (tripping pulse) - Undervoltage release - Auxiliary switch contacts 6NO + 6NC not wired - 24-pole terminal strip 2) - 24-pole plug connector 2) - Breaker tripping signal Signal “Tense spring” included Max. 2 shunt releases available. Available combinations and order numbers look table near 1 1 1 Current transformeroperated release 0,5 A 0,1 Ws 3AX11 02 3AX11 04 Undervoltage release 3AX11 03 1 1 1 1 1 Available for use 1 1 Only with auxiliary switch contacts 6NO + 6NC - - Operating cycle counter - mechanical blockade 3) - - Varistor module (DC > 60 V) In secondary circuit - Halogen-free and flameretardant wiring cables - - Condensation protection (heating for 230 V AC) - Hand crank - 1 1 - For manual charging of the closing spring (also by motor drive) 1) Motor stored-energy mechanism need 2) The wiring of electrical equipment such as motor or shunt trip is made on the terminal strip or on the bottom part of the plug. Terminals of the auxiliary switch are not wired. 3) With manual stroke drive there is only possibilities of mechanical affirmation of state of site of circuit breaker. 5. RELEASES Release Order number of release Power consumption Operating ranges Operation DC AC 50/60Hz approx. approx. W VA Tripping voltage by DC Tripping voltage/current ( AC 50/60 Hz) Closing solenoid 3AY15 10 100 100 85 to 110 % U 85 to 110 % U 1st shunt release (without stored-energy mechanism) 3AY15 10 100 100 70 to 110 % U 85 to 110 % U 2nd shunt release (with stored-energy mechanism) 3AX11 01 70 50 70 to 110 % U 85 to 110 % U Undervoltage release 3AX11 03 20 20 35 to 0 % U 35 to 0 % U Current transformeroperated release (rated current 0,5 A) 3AX11 02 - 10 - 90 to 110 % I a Current transformeroperated release (tripping pulse > 0,1 Ws) 3AX11 04 - - - - 6. PARAMETERS OF AVAILABLE MOTOR DRIVES Rated voltage of operating mechanism max. V min. V W VA Smallest possible rated current of the m. c. b. (G-characteristic) A 26 53 66 20 41 51 350 350 350 - 8 6 4 110 220 121 242 93 187 350 350 - 2 1,6 AC 110 230 121 244 93 187 - 400 400 2 1,6 V DC 24 48 60 Page 6/12 Operating voltage Power consumption of the motor ZWAE Sp. z o.o. Vacuum circuit-breaker 3AH5 7. CONTROL, DISPLAY AND OPERATING ELEMENTS (EXAMPLE) 1 1 Rating plate 2 Hand crank couplingj 2 3 6 3 "Closing spring charged" indicator 7 4 Operating cycle counter 5 "CLOSED/OPEN" indicator 4 6 "CLOSE" pushbutton 5 7 "OPEN" pushbutton 11 8 Motor and gearbox 8 9 12 13 9 Closing spring 10 Closing solenoid 11 LV terminal strip (plug connector) 12 Auxiliary switch S1 10 ZWAE Sp. z o.o. 13 1st shunt release Page 7/12 Vacuum circuit-breaker 3AH5 3AH5 123-1 20 kA / 800 A Major innovations on the 3AH5: - Reduced dimensions - Higher normal currents - Higher short-circuit currents 8. TECHNICAL DATA AND TYPE DESIGNATIONS Ur kV Isc kA Ima kA PCD* mm Type designation 12 Up = 75 kV Ud = 28 kV 13,1 32,8 160 210 3AH5 1213AH5 131- 1 1 16 40 160 210 3AH5 1223AH5 132- 1 1 2 2 20 50 160 210 3AH5 1233AH5 133- 1 1 2 2 25 63 160 210 3AH5 1243AH5 134- 1 1 2 2 31,5 80 210 3AH5 135- 25 63 160 210 3AH5 2043AH5 214- 17,5 Up = 95 kV Ud = 38 kV 24 Up = 125 kV Ud = 50 kV 36 Up = 170 kV Ud = 70 kV I r (Order no. suffix) 800 A 1250 A 1 1 2000 A 2500 A 2 6 2 2 6 2 6 31,5 80 210 3AH5 215- 16 40 210 275 3AH5 2723AH5 282- 20 50 210 275 3AH5 2733AH5 283- 2 2 6 6 25 63 210 275 3AH5 2743AH5 284- 2 2 6 6 16 40 350 3AH5 312- 2 25 63 350 3AH5 314- 2 1 1 2 2 4 * Pole center distance Ir Rated normal current Isc Rated short-circuit breaking current Ima Rated short-circuit making current Page 8/12 Ur Rated voltage Ud Rated short-tme power-frequency withstand voltage Up Rated lightning impulse withstand voltage ZWAE Sp. z o.o. 3 4 Motor-operated mechanism 2 1st shunt release ZWAE Sp. z o.o. Manual closing Manual tripping 6 2nd shunt release 8 12 11 Breaker tripping signal 7 14 13 “Closing spring charged” signal 5 15 22 21 Auxiliary switch Designation: K1 - Contactor (anti-pumping system) M1 - Electrical motor S1 - Auxiliary switch S21, S22 - Positional connector (severance of motor drive after spring tension) S3 - Positional connector (opened after enclosing spring tension) S4 - Positional connector (state of spring tension) S6 - Signalling apparatus of automatic setting S7 - Connector for signalling apparatus of state of connection putting away V1, V2 - Varistor components X0 - terminal strip Y1 - First shunt release Y2 - Second shunt release Y9 - Enclosing elektromagnet A - Main contacts of circuit-braker Switching on and anti-pumping 1 52 51 24 23 54 53 26 25 56 55 28 27 58 57 30 29 Vacuum circuit-breaker 3AH5 9. BASIC VERSION OF ELECTRICAL DIAGRAM OF 3AH5 Page 9/12 Vacuum circuit-breaker 3AH5 10. RETROFIT: TROLLEY WITH THE 3AH5 CIRCUIT-BREAKER INSTEAD OF SCI-4 CIRCUIT-BREAKER - EXAMPLE Terminal strip Trolley versions for voltages 17,5 i 24 kV by PCD* 210 i 275 mm. a b 210 598 275 714 * Pole center distance Page 10/12 ZWAE Sp. z o.o. Vacuum circuit-breaker 3AH5 11. DIMENSIONS AND WEIGHTS 12 kV Isc kA Ir A PCD* 160 mm a b c mm mm mm Weight kg PCD* 210 mm a b c mm mm mm Weight kg 13,1 to 16 20 to 25 31,5 31,5 do 1250 do 1250 1250 2500 160 160 - 35 to 45 40 to 45 - 210 210 210 210 40 to 50 45 to 50 50 70 390 405 - 490 490 - 490 505 505 539 592 592 592 592 Figure in parentheses for 2500 A 17,5 kV I kA sc I A PCD* 160 mm a b c mm mm mm 25 31,5 25 to 31,5 to 1250 to 1250 2500 160 - Isc kA Ir A PCD* 210 mm a b c mm mm mm 16 to 25 20 to 25 to 1250 2500 210 516 210 539 r 422 - 490 - Weight kg 40 do 45 - PCD* 210 mm a b c mm mm mm Weight kg 210 210 210 45 do 50 45 to 50 65 522 522 539 592 592 592 Figure in parentheses for 2500 A Partition for pole center distance 160 mm 24 kV 592 592 Weight kg PCD* 275 mm a b c mm mm mm 55 to 70 275 70 to 85 275 646 669 708 708 Weight kg 55 to 70 70 to 85 Figure in parentheses for 2500 A Partition for pole center distance 210 mm 36 kV Isc kA Ir A PCD* 350 mm a b c mm mm mm Weight kg 16 to 25 25 to 1250 2000 350 350 85 to 95 100 to 110 819 819 868 868 Figure in parentheses * Pole pitch ZWAE Sp. z o.o. Page 11/12 Vacuum circuit breaker-3AH5 Offer interrogation - ordering example Type of circuit breaker Stationary Rated voltage ............ kV Rated normal current ............ A Rated short-circuit breaking current ............ kA Pole center distance ............ mm Order number 3AH5 _ _ _ - _ (according to technical data table, page 8) Basic equipment Motor snap-action operating mechanism AC DC ___V Anti-pumping system Electrical local closing 3AY15 10 AC DC ___V 1st shunt release 3AY15 10 AC DC ___V 2nd shunt release 3AX11 01 AC DC ___V Transformer-operated release 0,5 A 3AX11 02 AC DC ___V Transformer-operated release (tripping pulse > 0,1 Ws) 3AX11 04 AC DC ___V Undervoltage release AC DC ___V Auxiliary switch 6NO + 6NC Terminal strip Position switch (self-acting operating) (S6 i S7) Position switch (signal charging state) (S4) Operating cycle counter Varistor module (DC > 60 V) Additional equipment 3AX11 03 Auxiliary switch 12NO + 12NC Plug (instead of terminal strip) Halogen-free and flame-retardant wiring cables Condensation protection, heating for 230 V AC Quantity : Delivery date : Terms of delivery : Terms of payment : ........................................ ........................................ ........................................ ........................................ Zakład Wytwórczy Aparatów Elektrycznych Sp. z o.o. ul. Gdańska 60; 84-300 Lębork Tel.: +48 59 86-336-15; Fax: +48 59 86-333-86 e-mail: zwae@zwae.com.pl www.zwae.com.pl (according to equipment table, page 6)