Arc Flash Analysis Nicholas Abraitis, EIT GRP Engineering, Inc. Petoskey, MI Arc Flash Analysis • • • • • • • Understanding Arc Flash Required System Data Arc Flash Analysis Setting and Preferences Delta Windings on Transformers Windmil Arc Flash Results Methods to Reduce Incident Energy in Arcs Summary Understanding Arc Flash Causes of Arc Flash • • • • • Dust Dropping tools Accidental contact Faulty installation Corrosion and equipment failure Understanding Arc Flash Factors Determining Incident Energy in Arcs • • • • • Duration of the arc Bolted fault current Enclosed or in open air Gap between conductors Proximity of worker to the arc Understanding Arc Flash Hazards of Arc Flash • • • • • • Fire Burns Sound Blasts of 140dB Heat upwards of 35,000 F Flying objects and molten metals Blast pressure upwards of 2000 lbs/ft2 2012 NESC Requirements Rule 410A3 • Complete an assessment to determine the potential exposure to an electric arc at all points of their electrical system. Optionally, use NESC Tables 410-1, 410-2, 410-3 to determine the effective arc rating of clothing or a clothing system to be worn by employees working on or near energized lines, parts, or equipment at voltages 50V to 800,000V. • Include estimated arc-energy based on available fault current, duration of the arc in cycles, and the distance from the arc to the employee in the assessment. • Require employees wear clothing or a clothing system that has an effective arc rating not less than the anticipated level of arc energy. IEEE Standard 1584 Applies to the following system parameters • • • • • • Three phase faults Frequency of 50Hz to 60Hz Voltage range of 208V to 15,000V Bolted fault current 700A to 106,000A Enclosures of commonly available sizes Gaps between conductors 13mm to 152mm Required System Data • Create the devices in Light Table • Set the pick up curve, tap, time dial, and CT ratios for each breaker or recloser • Check the “Use LT” box in the EQDB for all over-current devices • Accurate connectivity and construction of lines, protective devices, and equipment Arc Flash Analysis Settings • Model Subset – Selected Current Work Environment with entire model active • Selected an Explicit Working Distance of 18 inches, can set different working distances for each element using the Global Editor and setting the field named “Arc Flash Working Distance” • Use Typical Values Determined by Equipment Type, configured in Arc Flash Preferences • Use Max Arcing Time, calculated based on available fault current and device operating time in Light Table • Fault Current Analysis was previously run on the reduced model, box can be unchecked Arc Flash Preferences • Sets the typical gap between conductors (mm) and the distance x factor • Based on IEEE 1584 table Delta Windings on Transformers • Unbalance causes a neutral shift • Windmil models a pseudo source at the delta banks to represent the fault contributions for the neutral shifts. • Modeling the pseudo source is referred to as the “looped” method • Analysis is exponentially longer for each element in the model • Large delta systems can run several days without finishing analysis How Can We Make the Analysis Run Faster? • Run circuit reducer to reduce the number of elements in the model • Run looped method on selected elements vs. all elements • Remove the delta system from the model and replace it using thevenin equivalent sources Current Model • • • • 138kV wye system 34.5kV delta system 13.2kV wye system Generation assets on the 138kV and 34.5kV systems • Model has 138kV:34.5kV wye to delta transformers and 34.5kV:13.2kV delta to wye transformers Current Model Zoomed in Model Reduction • Select first element downline of the delta transformers secondary and run fault current analysis in looped method for the selected element • Record the positive and zero sequence impedances of the element • Create Zsm Impedance in the EQDB • Insert a source as the parent of the element with the newly created impedance code • Disconnect and remove the delta system from the model Model Reduction – Central Substation • Selected one OCR on the secondary of each 34.5kV:13.2kV delta to wye transformer • Ran Fault Current analysis • Recorded the thevenin equivalent positive and zero sequence impedances Model Reduction • Replace 34.5kV:13.2kV transformers with thevenin equivalent sources • Remove the upline 138kV and 34.5kV transmission system • Sources include contributions from all upline generation Model Reduction Completed • Removed three 138kV:34.5kV transformers and seventeen 34.5kV:13.2kV transformers • All generation assets removed from model • All 138kV and 34.5kV transmission lines removed Windmil Arc-Flash Analysis Results • Analysis was completed in minutes and not in days • Arc Flash was calculated for the entire 13.2kV distribution system Relating the Incident Energy to Required PPE Table from NFPA 70E Reducing the Available Fault Current Arc Flash Incident Energy vs. Available Fault Current ARC FLASH INCIDENT ENERGY (CAL/CM2) 50.00 45.00 40.00 35.00 30.00 25.00 20.00 15.00 10.00 5.00 0.00 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 AVAILABLE FAULT CURRENT (KA) Working distance (18in) and protective device clearing time (.4s) held constant Reducing the Incident Energy in Arcs Reducing the available fault current • Limit on-line generation • Install current-limiting reactors • Do not operate substation transformers in parallel Reduce the Protective Device Operating Time Arc Flash Incident Energy vs Protective Device Operating Time ARC FLASH INCIDENT ENERGY (CAL/CM2) 60.00 50.00 40.00 30.00 20.00 10.00 0.04 0.05 0.045 0.055 0.06 0.065 0.07 0.08 0.075 0.085 0.1 0.09 0.15 0.2 0.25 0.3 0.4 0.35 0.45 0.5 0.55 0.6 0.7 0.65 0.8 0.75 0.85 0.9 0.95 1 0.00 PROTECTIVE DEVICE OPERATING TIME (S) Working distance (18in) and available fault current (15,000A) held constant Reducing Incident Energy in Arcs Reduce the protective device operating time • • • • • Change the tap setting Change the curve type Change the time delay Add zone protection Add an instantaneous element Increase the Working Distance Arc Flash Incident Energy vs Working Distance 200.00 ARC FLASH INCIDENT ENERGY (CAL/CM2) 180.00 160.00 140.00 120.00 100.00 80.00 60.00 40.00 20.00 0.00 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 WORKING DISTANCE (INCH) • Available fault current (15,000A) and protective device operating time (.4s) held constant Reducing Incident Energy in Arcs Increase the working distance • Use hook sticks to complete work when applicable • Use remote breaker racking devices on indoor switchgear • Use infrared windows Summary • Having accurate connectivity in the model is crucial to Arc Flash Analysis • Need to have all protective devices modeled in Light Table and linked to the Milsoft model • Transformer banks with delta configured windings cause analysis to run for prolonged periods of time • Reducing the protective device clearing times or increasing the working distances have the greatest effect on the incident energy contained in an arc • The safest way to avoid an arc flash injury is to de-energize the equipment as part of the work procedures Contact Information Nicholas Abraitis Electrical Engineer nabraitis@grp-engineering.com Petoskey Office GRP Engineering, Inc. 660 Cascade W. Pkwy Suite 65 459 Bay Street Grand Rapids, MI 49546 Petoskey, MI 49770 616.942.7183 231.439.9683 616.285.6448 Fax 231.439.9698 Fax