Hilton Hotel and Royale Palms Myrtle Beach, South Carolina July 11, 2011 Michael C. Dougherty, PE A.J. Molnar, PE Southeastern Consulting Engineers, Inc. Charlotte, NC What is Arc Flash? Definitions Per the National Fire Protection Association (NFPA): ○ Arc – “Occurs when an insulating medium such as air is breached by a conducting component.” ○ Arc Flash – “The energy released during an arcing fault”. This occurs when current flows through a medium that is not intended to conduct electrical current. Because the arc current is not intended, the arc current releases energy that also is not intended, thus exposing a worker to unexpected hazards. What is Arc Flash? Definitions (continued) ○ Arc Flash Hazard - “a dangerous condition associated with the release of energy caused by an electric arc.” ○ Flash Hazard Analysis – A study investigating a worker’s potential exposure to arc-flash energy, conducted for the purpose of injury prevention and the determination of safe work practices and the appropriate levels of Personal Protective Equipment (PPE).” ARC FLASH EXAMPLE ARC FLASH EXAMPLE Types of Electric Faults Bolted Fault - solidly connected fault path Arcing Fault – current flows through ionized air Arcing faults release most of the energy of the fault out into the surrounding environment. Bolted faults most of the energy flows through the faulted equipment. Arc Flash Facts An arc flash is a source of intense heat, light, sound, and pressure. Arc temperature can reach 35,000˚F – this is four times hotter than the surface of the sun. Fatal burns can occur at distances over 10 ft. Five to ten Arc Flash explosions occur in electric equipment every day in the United States. Over 2000 people per year are treated for severe burns from electrical arcs. As much as 80% of all electrical injuries are burns resulting from an arc-flash and/or the ignition of flammable clothing. Personnel Hazards Direct injury Pressure wave Contact with energized parts Radiation burns from intense heat & light Indirect injury Shrapnel from component parts - the blast can hurl shrapnel at velocities over 700mph. Molten Copper and Steel Breathing superheated air & arc by-products Potential Causes of Arc Flash An arc flash can be caused a number of ways, including: Tracking across insulation surfaces Accidental contact with energized parts Inadequate short circuit ratings Tools dropped on energized parts Wiring errors and loose connections Contamination, such as dust on insulating surfaces Corrosion of equipment parts and contacts Improper work procedures Equipment failures Animals Interrupting 500kV with Air Break Switch Industry Standards and Regulations used to protect workers from Arc Flash NEC 2008 OSHA 29 CFR 1910 NFPA 70E - 2009 IEEE 1584 National Electrical Safety Code® (NESC) - 2007 2007 NESC Article 410.A.3 “Effective as of January 1, 2009, employers are to ensure that an assessment is performed to determine potential exposure to an electric arc for employees who work on or near energized parts or equipment. If the assessment determines a potential employee exposure greater than 2 cal/cm2 exists, the employer shall require employees to wear clothing or a clothing system that has an effective arc rating not less than the anticipated level of arc energy.” How do you comply with NESC 410.A.3? Utilities must perform an assessment of their entire electric system and verify that their PPE is providing adequate protection. The assessment utilizes voltage, clearing time and fault current to determine the available incident energy. You can determine this by using NESC tables 410-1 and 410-2 or by performing an arc flash hazard analysis. ○ When an arc hazard analysis is performed, it shall include a calculation of the estimated arc energy based on the available fault current, the duration of the arc(cycles), and the distance from the arc to the employee A comparison of these two options NESC Tables 410-1 & 410-2 To utilize the tables, you must calculate single phase to ground fault current and then identify upstream protective device clearing times. Not very accurate for “actual” fault current and clearing time. Perform an Arc flash hazard analysis, and document the incident energy exposure. IEEE 1584 (SKM, ETAP, Easypower, Duke Heat Flux, and others) ArcPro Software by Kinectrics IEEE 1584 Guide for performing Arc Flash Hazard calculations for incident energy and determining proper PPE. Calculations verified over voltage range from 208V to 15kV. Three-phase arcs in enclosures or open air. No single phase faults Shifts from lab tested standard formula to Lee Method for 25kV faults and above. Lee method is based on theoretical behavior of arcs. No data indicating Lee Method has been verified for 25kV and above. ARCPRO Physics based model which calculates the thermal parameters of electric arcs. Calculations are very similar to IEEE 1584 for 15kV systems. Typically utilized for analysis of 25kV systems and above. Single-phase arcs in open air only. This is typically more suited to the majority of distribution system situations. Multipliers (adjustment factors) are applied to incident energy for three phase and faults in a box (enclosures such as padmounted transformers. Arc Flash Analysis Steps 1. Data collection 1. Data Collection Secure arc flash calculations and upstream protective device settings from Wholesale provider Bring Electric system maps up to date and create accurate substation one-lines if not already available Collect substation equipment nameplate information and protective device settings Collect distribution system information to create typical feeder for overhead and underground. This includes recloser and fuse information. Arc Flash Analysis Steps 1. Data collection 2. Determine system operating modes…choose worst case 2. Determine System operating modes Identify modes of operation: ie utility only, extended parallel generation only, multiple scenarios with generators in parallel with utility, etc. Run the analyses on worst case. Arc Flash Analysis Steps 1. Data collection 2. Determine system operating modes…choose worst case 3. Calculate available fault current throughout system 3. Calculate the available fault current Utilizing data collected in Step 1, create a system single line and system parameters in SKM software. In SKM, calculate the available fault current at each bus identified in the system oneline. For systems 25kV and above, first calculate the single phase fault current in SKM, identify clearing times and then input into ARCPRO. Arc Flash Analysis Steps 1. Data collection 2. Determine system operating modes…choose worst case 3. Calculate available fault current throughout system 4. Calculate arc flash incident energy levels 4. Calculate incident energy levels In SKM, calculate the incident energy levels at each bus in the system. For systems 25kV and above, calculate the single line to ground incident energy in ARCPRO, then apply adjustment factors to convert from single phase faults to three phase faults and faults in enclosures (such as padmounts) What is Incident Energy? Unit of measure is cal/cm2 or Joules/cm2 A calorie is the energy required to raise one gram of water one degree Celsius at one atmosphere. One cal/cm2 is equivalent to the amount of energy produced by a cigarette lighter in one second The onset of second degree burns will occur at 1.2 cal/cm2 per second. (See chart below) Incident Energy (cal/cm2) 1.2 Degree Burn 2nd degree burn to skin 4 Ignite a cotton shirt 8 3rd degree burn to bare skin Arc Flash Analysis Steps 1. Data collection 2. Determine system operating modes…choose worst case 3. Calculate available fault current throughout system 4. Calculate arc flash incident energy levels 5. Calculate arc flash protection boundaries 5. Calculate the Arc Flash Protection boundaries In SKM or ARCPRO, calculate the Arc Flash Protection boundaries at each bus. ARC Flash protection boundaries are an approach limit measured from exposed live parts within which an unprotected person could receive a second degree burn if an arc flash were to occur. Appropriate PPE must be worn inside this boundary Arc Flash Protection Boundaries Arc flash hazard and flash protection boundary varies with: Type of equipment and equipment configuration Available short circuit current Voltage Fault duration – protectice devices upstream of the arcing fault and their settings. Approach Boundaries Note: The flash protection boundary is the distance at which the incident energy equals 1.2 cal/cm2. Arc Flash Analysis Steps 1. Data collection 2. Determine system operating modes…choose worst case 3. Calculate available fault current throughout system 4. Calculate arc flash incident energy levels 5. Calculate arc flash protection boundaries 6. Determine protective device characteristic and arc duration 6. Determine protective device characteristic and arc duration Using the SKM software calculate the clearing times for the available faults. Clearing times are determined by the intersection of the available arcing fault current and the protective device curve Arc Flash Analysis Steps 1. Data collection 2. Determine system operating modes…choose worst case 3. Calculate available fault current throughout system 4. Calculate arc flash incident energy levels 5. Calculate arc flash protection boundaries 6. Determine protective device characteristic and arc duration 7. Determine working distances 7. Determine working distances IEEE 1584 (SKM) assigns working distances based on equipment type and voltage class. (You are permitted to adjust these distances if within acceptable range) ARCPRO calculates incident energy at various distances. Choose voltage appropriate distance following footnotes from NESC table 410-1 and 410-2. Table 410-2 refers you to or 441-2 for 46kV and above. Arc Flash Analysis Steps 1. Data collection 2. Determine system operating modes…choose worst case 3. Calculate available fault current throughout system 4. Calculate arc flash incident energy levels 5. Calculate arc flash protection boundaries 6. Determine protective device characteristic and arc duration 7. Determine working distances 8. Determine required PPE (risk hazard) category 8. Determine required PPE Using the SKM software calculate the required PPE category. Personal Protective Equipment is the complete clothing system required in order to prevent an incurable burn during an arcing fault. PPE can include eye protection, ear protection, face protection, gloves, & clothing Always perform work de-energized if possible! Classes of Protective Clothing Incident Clothing Energy Category Description ATPV (cal/cm2) 0 - 1.2 0 Untreated Cotton Long Sleeve shirt & Long pants n/a 1.2 -4 1 FR shirt and pants Or FR coverall Minimum 4 4-8 2 Minimum 8 Cotton Underwear + CL.1 8-25 3 Minimum 25 FR Coveralls + CL.2 25-40 4 Double Layer Switching Coat + CL.2 ATPV - Arc thermal performance exposure value (cal/cm2) Minimum 40 Personal Protective Equipment (PPE) Category 0 Long-sleeve shirt and Long pants ○ Made of non-melting/flammable materials ○ Fabric weight at least 4.5 oz/yd2 Hard Hat Safety Glasses Leather Gloves Leather Work Shoes PPE Category 1 – Minimum Arc Rating of 4 cal/cm2 FR Shirt and Pants or FR Coverall Hard Hat Safety Glasses Leather Gloves Leather Work Shoes PPE Category 2 – Minimum Arc Rating of 8 cal/cm2 Cotton Underwear plus FR Shirt and FR Pants Cotton Underwear plus FR Coverall Hard Hat Safety Glasses/Goggles Arc Rated Face Shield or Flash Suit Hood Hearing Protection Leather Protectors worn over rubber gloves Leather Work Shoes PPE Category 3 – Minimum Arc Rating of 25 cal/cm2 Cotton Underwear plus FR Shirt and FR Pants plus FR Coverall Hard Hat with FR Hard Hat Liner Safety Glasses/Goggles Flash Suit Hood Hearing Protection Leather Protectors worn over rubber gloves Leather Work Shoes PPE Category 4 – Minimum Arc Rating of 40 cal/cm2 Cotton Underwear plus FR Shirt and FR Pants plus Multilayer Flash Suit Cotton Underwear plus FR Coverall plus Multilayer Flash Suit Hard Hat with FR Hard Hat Liner Safety Glasses/Goggles Flash Suit Hood Hearing Protection Leather Protectors worn over rubber gloves Leather Work Shoes Arc Flash Mitigation Reduce the Arcing Fault Current Current Limiting Protective Devices Increase the Working Distance Operating Devices remotely ○ SCADA ○ Relays and Breaker controls in Equipment House Extension tools Reduce the Clearing Time Lower protective device settings Differential relaying Arc Flash Mitigation Reduce Clearing Time: Upstream Circuit Breaker Reduce protective device settings Enable Instantaneous Trip Function Disable Reclosing when working on circuit Utilize “maintenance mode” with alternate Settings if necessary (digital relays) Differential relaying Removes fault in minimum time (2 or 3 cycles) Arc Flash relaying Compares over current value to light flash magnitude. Arc Flash Mitigation Reduce the Arcing Fault Current Current Limiting Protective Devices Increase the Working Distance Operating Devices remotely ○ SCADA ○ Relays and Breaker controls in Equipment House Extension tools Reduce the Clearing Time Lower protective device settings ○ Maintenance mode with alternate settings (Digital relays). Instantaneous covers circuit “backbone” Differential relaying Arc Flash design Arc Flash Mitigation Arc Flash Design Strategies: Relocate Relays & Controls to the Equipment House For new substations perform a preliminary Arc Flash analysis to aid in design. Specify digital relays to provide flexibility with regards to settings and communications. Specify equipment with an emphasis on minimizing arc flash exposure. Arc Flash Mitigation Safety and Design Considerations: Arc Flash Boundary Identified Specify Arc Resistant MV Switchgear LV Switchgear View Port for Infrared inspection Infrared Ports Monitoring without exposure Arc Flash Mitigation Safety and Design Considerations: Arc Flash Boundary Identified Arc Resistant View Port for Infrared inspection Hinged covers vs. bolted Remote Racking Mimic Bus (Touch panel) PPE Storage on site if necessary Arc Flash Analysis Example #1 12.47kV system – 12.47kV Circuit Breaker Arc Flash Calculation Summary Time Current Curve (TCC) Protected by upstream CO-7 relay Arc Flash Calculation Summary 12.47kV system 12.47kV Circuit Breaker 12.47kV Circuit Breaker 4640A Arc Flash Analysis Example #2 12.47kV system – Substation 240V AC Panel Arc Flash Calculation Summary Time Current Curve (TCC) Protected by upstream 3A Fuse Arc Flash Calculation Summary 12.47kV system 240V AC Panel 240V AC Panel Arc Flash Analysis Example #3 12.47kV system – 100A Fuse Time Current Curve (TCC) Arc Flash Calculation Summary Protected by upstream 3000A breaker Arc Flash Calculation Summary 12.47kV system 12.47kV 100A FUSE 12.47kV 100A FUSE Arc Flash Analysis Example #4 100kV system – 100kV Circuit Switcher Arc Flash Calculation Summary – NESC 2007 Arc Flash Calculation Summary – NESC IEEE 1584 ArcPro Total Heat Flux Calculation ArcPro Heat vs. Distance Table Protected by SEL 587Z Differential Relay Arc Flash Calculation Summary 100kV system 100kV Circuit Switcher 100kV Circuit Switcher Apply 3phase adjustment factor of 2.2 to incident energy. Total is 1.12 cal/cm@ Arc Flash Calculation Summary 100kV system 100kV Circuit Switcher 100kV Circuit Switcher Typical Summary of Results 69kv & 100kV equipment can range from Category 0 to Dangerous This is dependent upon working distance and clearing time We recommend all work be performed de-energized Most equipment on overhead 15kV and 25kV lines is Category 1. Category will increase is instantaneous function is disabled or fault location is past pickup. Transformers Secondary side below 240V ○ Category 0 Secondary side of 240V, less than 125 KVA ○ Category 0 Secondary side of 240V, 125 KVA and above ○ Category 2 Typical Summary of Results Transformers – Secondary side of large transformers (208V or 480 V) have potential for high incident energy levels. Typical Hazard Risk Categories: Transformer Size PPE Category Up to 300 KVA Category 2 500 KVA to 1000 KVA Category 3 1000kVA to 1500kVA Category 4 2000kVA and Over Dangerous Perform all work on padmounted transformer secondaries de-energized if possible. Typical Summary of Results Inside Substations Line side of Feeder Circuit Breakers have higher incident energy when the only upstream device is Wholesale provider’s relay or Fuse. It is better to have control over relay settings Load side of Feeder Circuit Breakers ○ Category can be any where from 0 up to 3. FLASH PROTECTION Flash Protection Boundary An approach limit measured from exposed live parts within which an unprotected person could receive a second degree burn if an arc flash were to occur. Appropriate PPE must be worn inside this boundary. Approach Boundaries Note: The flash protection boundary is the distance at which the incident energy equals 1.2 cal/cm2. Example of “WARNING” Label Example of “DANGER label” Brady GlobalMark Printer How does the Arc Flash Analysis effect your Safety Program? Electric Utilities should provide proper PPE for workers based on results of the study. Work rules should be enacted for common work tasks. Provide customers with arc flash information Typically do not provide upstream protective device info. Contractors must wear properly rated PPE for work being performed. Mutual aid work must be coordinated very carefully when working on other electric systems. Crews should not work on any equipment that has available incident energy greater than their PPE. Future of Arc Flash Constantly evolving issue. NESC 2012 will most likely have many changes. Proposed new Table 410-1 for voltages from 50 – 1000V (AC) that is Task specific. Arc Flash research and testing on systems 15kV and higher will continue. This should provide better data for future software programs. QUESTIONS? THANK YOU FOR YOUR TIME Michael C. Dougherty, PE A.J. Molnar, PE Southeastern Consulting Engineers, Inc. Charlotte, NC