Analysis of Transient Overvoltages within a 345kV Korean Thermal

advertisement
Journal of Electrical Engineering & Technology Vol. 7, No. 3, pp. 297~303, 2012 297
http://dx.doi.org/10.5370/JEET.2012.7.3.297
Analysis of Transient Overvoltages within a 345kV
Korean Thermal Plant
Sang-Min Yeo† and Chul-Hwan Kim*
Abstract – This paper presents the simulation results for the analysis of a lightning surge, switching
transients and very fast transients within a thermal plant. The modeling of gas insulated substations
(GIS) makes use of electrical equivalent circuits that are composed of lumped elements and distributed
parameter lines. The system model also includes some generators, transformers, and low voltage
circuits such as 24V DC rectifiers and control circuits. This paper shows the simulation results, via
EMTP (Electro-Magnetic Transients Program), for three overvoltage types, such as transient
overvoltages, switching transients, very fast transients and a lightning surge.
Keywords: Surge, Transient Overvoltages, Switching, Lightning, Gas Insulated Switchgear, EMTP
1. Introduction
Power systems consist of various facilities such as
power stations, substations, transmission lines and various
loads, etc. Transient overvoltages may occur within a
power system when a system status change occurs due to
an event such as a fault, lightning or even normal operation.
Generally, modeling of switching devices, such as circuit
breakers and disconnector switches, are implemented by
ideal switches for analysis within a switching transient
simulation. However, the contacts of a disconnector switch
move slowly during opening and closing operations, which
causes numerous pre-strikes between the contacts. Prestrikes occur when the dielectric strength between the
contacts of the disconnector switch are exceeded by
overvoltages. Therefore, the effects of pre-strikes due to
disconnector switching continue for a relatively long time
compared to the time in a circuit breaker [1-5].
Specifically, in gas insulated switchgear (GIS), a large
number of restrikes across the switching contacts will
occur when disconnector switches or circuit breaker
operation occurs. Each restrike generates very fast transient
overvoltages (VFTO), which enter the substation and may
propagate inside depending on the substation layout.
VFTOs typically have a very short rise time, in the range of
4 to 100 ns, and are followed by high frequency
oscillations, in the range of 1 to 50 MHz. Therefore, the
analysis of switching transients and very fast transients in
GIS is extremely important [6-11]. Also, when lightning
hits a nearby tower or the shield wire of an incoming line,
this can cause a backflashover, which is when the resultant
lightning surge enters the substation and may propagate
inside depending on the substation layout. Hence, as in the
†
Corresponding Author: Power & Industrial Systems R&D Center,
Hyosung Corporation, Korea. (harc@hyosung.com)
*
School of Information and Communication Engineering,
Sungkyunkwan Univerity, Korea. (hmwkim@hanmail.net)
Received: April 29, 2011; Accepted: February 3, 2012
case of switching transients, the transients caused by a
lightning surge also need to be analyzed.
In 2005, when a disconnector closed within a 345kV
Korean thermal plant, the circuit breakers for the exciter
protection of two generators tripped except the operation of
any protective relay. The tripping of the circuit breakers
caused inoperation to occur for two generators, which then
caused a productivity decrease for the entire plant. Thus,
analysis is required in order to discover the trip cause for
the circuit breakers due to disconnector switching. In this
paper, the authors analyze the VFTOs due to disconnector
switching, including the switching transient and lightning
overvoltages.
This paper shows the simulation results of transient
overvoltages within a GIS. Also, both a 345kV thermal
plant and a pre-strike model of a disconnector switch are
modeled by EMTP and then it is further simulated to
analyze the transient overvoltages via various transients.
2. Background Theory
The components in a GIS have already been previously
modeled by the authors via several transient simulations
[12, 13]. The previous papers include more details about
modeling as follows, except for in the case of lightning
surges. Therefore, these factors are described briefly within
this paper.
2.1 Very fast transients
VFTs may occur within a GIS at any time and will cause
an instantaneous voltage change, one example being the
change caused by disconnector switching. These transient
over-voltages are generally below the basic insulation level
(BIL) of the GIS and are connected to equipment with
Analysis of Transient Overvoltages within a 345kV Korean Thermal Plant
2.2 Pre-strike
P2
1.2uH
0.0463nF
C9
Fig. 2. Equivalent model of the grounding system per unit
length
2.4 Lightning surge
Generally, lightning strikes that occur directly on a
substation are ignored because it is safely assumed that the
substation is shielded appropriately. On the contrary,
lightning strikes to the tower or shield wire can cause
backflashover due to line insulation flashover between the
tower and the phase conductor, and can enter the substation
and propagate inside according to the substation layout [9].
In this paper, the standard 1.2x50us impulse waveform is
used for the lightning surge model, as shown in Fig. 3.
BUS1
R1
?i
+
0.0001
R2
+
400
?v
a
+
The pre-strike phenomena of the switches are considered
in order to simulate the switching transients. In this paper,
the authors refer to references 4 and 5 for modeling the
pre-strike, which consists of a calculation for the withstand
voltage (Vw), a comparison of the withstand voltage, the
switch voltage, a controlled switch, and a probe for
measuring the switch terminal voltage. Fig. 1 shows the
model of a pre-strike in EMTP [14].
L2
+
P1
+
lower voltage classes. However, they frequently contribute
to the life reduction of the insulation within the system [9].
The propagation of VFT through the GIS can be
analyzed by representing GIS sections as low-loss
distributed parameter transmission lines. The main
frequencies depend on the length of the GIS sections
affected by the disconnector operation and are in the range
of 1 to 50MHz. Also, an internally generated VFT will
propagate throughout the GIS and reach the bushing where
it will cause both a transient enclosure voltage and a
traveling wave that will propagate along the overhead
transmission line.
R1
+
570
298
1
2
1
2
lim2
1
?s #KVr#
ABS
Vw
scope
1
Compare
2
?s
Csw
Icramp1
a
Csw
Fm6
1
2
C1
1
0
PROD
c_gfun
c
+
-
1
1.2us/63kA
Fm7
Gain2
Fig. 3. Lightning surge model
DIV
Vsw
f(t)
c
Fm5
+Inf
sum2
+
Vsw
v(t)
C4
sg2
Fm4
PROD
3. Simulation and Results
#toper#
t
Fig. 1. Model of a pre-strike by EMTP
It is confirmed via the simulation results that the
verification of the pre-strike model is properly
implemented.
3.1 System Model
This paper models a 345kV thermal plant via EMTP.
The modeled system, as shown in Fig. 4, is comprised of
six generators and six transformers, and connects to other
systems via six transmission lines.
2.3 Grounding system
The operational safety and proper functioning of electric
systems are influenced by their earth terminations.
Local inequalities of reference potential for a grounding
system are sources of malfunction and may cause the
destruction of components that are electrically connected to
the grounding system. Therefore, ground system modeling is
necessary in order to analyze the effects of reference potential
disturbances during various operation abnormalities.
The presented methodology extends the validity range of
well-known grounding system models towards higher
frequencies, in the range of a few MHz. The approach is
based on the three basic concepts that have been developed
[15, 17].
This paper uses a grounding system model via the circuit
approach method, as mentioned in [18] and shown in Fig. 2.
Fig. 4. System Model
3.1.1 Very fast transients and lightning surge section
In order to successfully simulate VFT overvoltage,
accurate models are needed for various equipment devices
in the range of zero hertz to a few megahertz. However,
Sang-Min Yeo and Chul-Hwan Kim
component modeling within all frequency ranges is very
difficult and impracticable. Thus, for reasons of practicality,
the modeling of frequency-dependent power system
components is implemented within a specific frequency
range [9]. The equivalent GIS model consists of various
pieces of equipment that function differently for varying
frequency ranges. Therefore, equivalent typical equipment
models for very fast transients are used [6-8, 10-13, 17].
For the simulation of the lightning surges, the system
model is derived from plant layout drawings and should
include the lightning surge characteristics. For this reason,
the modeling method is similar to the method used for the
case of VFT. Though the plant modeling for VFT is more
complicated rather than typical modeling for a lightning
surge, when the lightning surge is simulated the authors use
the modeled system for the VFT in order to reduce effort
and time due to repeated modeling.
Fig. 5 shows the equivalent model of the circuit breaker
from the equivalent model of GIS components. The other
components are modeled by similar procedure [4, 6-13].
299
DEV9 7
DEV99
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV97 3
DEV1 02
P1 P2
DEV9 71
DEV97 2
DEV9 70
DEV96 8
DEV9 69
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV44
DEV4 5
DEV48
DEV4 6
DEV47
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV6 5
DEV66
P1 P2
P1 P2
DEV4 9
DEV50
P1 P2
P1 P2
DEV18 1
DEV18 2
P1 P2
P1 P2
DEV8 80
DEV8 82
P1 P2
P1 P2
P1 P2
1
R2 5
R2 6
DEV8 92
DEV8 83
DEV88 4
DEV8 85
DEV88 6
DEV8 87
DEV89 0
DEV8 88
DEV8 89
DEV8 91
DEV90 3
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV18 5
DEV183
DEV250
DEV252
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV3 3
DEV1 84
P1 P2
P1 P2
P1 P2
P1 P2
DEV15 6
DEV16 2
DEV34
DEV41
DEV16 4
P1 P2
P1 P2
DEV42
DEV16 5
DEV1 66
P1 P2
Gnd 56
s cope
DEV16 8
t m l _6 _3
DEV1 67
tm l_ 6_ 2
P1 P2
DEV2 69
DEV27 0
P1 P2
DEV273
P1 P2
DEV21 6
P1 P2
DEV61
P1 P2
p1
P1 P2
DEV56
P1 P2
P1 P2
P1 P2
P1 P2
DEV6 0
P1 P2
DEV14 6
P1 P2
P1 P2
P1 P2
DEV36
P1 P2
DEV35
P1 P2
P1 P2
DEV2 9
P1 P2
tm l_ 5_ 3
DEV7 2
P1 P2
DEV272
DEV2 54
DEV244
t m l _6 _0
DEV2 3
P1 P2
DEV3 2
P1 P2
DEV2 7
P1 P2
P1 P2
P1 P2
P1 P2
DEV28
DEV2 48
DEV24 2
DEV24 3
P1 P2
DEV25 9
P1 P2
DEV55
P1 P2
DEV2 5
P1 P2
DEV2 61
DEV5 3
P1 P2
DEV26 0
DEV52
P1 P2
DEV3 1
P1 P2
P1 P2
P1 P2
DEV24 9
t m l_ 6_ 1
DEV1 3
P1 P2
DEV14
DEV22
P1 P2
DEV67
DEV2 53
DEV247
P1 P2
DEV2 51
P1 P2
P1 P2
P1 P2
DEV18 0
P1 P2
P1 P2
DEV201
DEV1 79
P1 P2
DEV75
DEV74
DEV275
DEV1 27
DEV1 30
DEV27 4
P1 P2
P1 P2
P1 P2
DEV76
P1 P2
P1 P2
DEV12 9
P1 P2
P1 P2
DEV12 5
P1 P2
DEV2 76
DEV1 24
P1 P2
P1 P2
DEV12 3
P1 P2
DEV2 20
DEV1 22
P1 P2
P1 P2
P1 P2
P1 P2
DEV27 1
P1 P2
P1 P2
P1 P2
DEV455
P1 P2
DEV2 85
P1 P2
DEV4 60
DEV454
P1 P2
P1 P2
DEV5 04
DEV77
DEV44 2
P1 P2
P1 P2
DEV44 1
P1 P2
DEV4 50
P1 P2
P1 P2
DEV6 00
DEV453
DEV51 8
P1 P2
t m l_ 3_ 3
DEV5 17
DEV4 59
DEV456
P1 P2
P1 P2
P1 P2
P1 P2
DEV50 9
P1 P2
DEV4 58
DEV4 57
DEV4 61
DEV5 08
DEV8 0
P1 P2
P1 P2
DEV2 77
P1 P2
DEV2 21
DEV7 9
P1 P2
DEV7 8
P1 P2
P1 P2
P1 P2
P1 P2
DEV8 3
DEV4 65
P1 P2
DEV47 0
DEV6 01
DEV60 2
P1 P2
P1 P2
P1 P2
DEV4 64
DEV46 9
P1 P2
P1 P2
P1 P2
P1 P2
DEV4 63
DEV4 62
DEV4 66
DEV46 8
DEV46 7
P1 P2
DEV50 7
DEV27 8
P1 P2
P1 P2
DEV8 8
DEV94
P1 P2
P1 P2
DEV1 48
P1 P2
DEV22 4
DEV2 29
P1 P2
DEV8 7
P1 P2
DEV93
P1 P2
DEV8 4
P1 P2
P1 P2
DEV90
P1 P2
P1 P2
P1 P2
P1 P2
DEV8 9
P1 P2
DEV95
DEV6 11
P1 P2
DEV1 10
P1 P2
DEV6 12
DEV61 0
P1 P2
P1 P2
DEV52 1
DEV5 49
DEV1 17
P1 P2
P1 P2
DEV51 5
P1 P2
DEV5 51
DEV5 23
DEV5 13
P1 P2
DEV51 9
DEV51 2
P1 P2
DEV4 75
P1 P2
P1 P2
DEV5 14
DEV6 05
P1 P2
P1 P2
DEV51 0
P1 P2
P1 P2
P1 P2
DEV4 72
DEV4 74
DEV47 1
P1 P2
DEV4 76
DEV4 73
P1 P2
DEV1 52
DEV1 00
P1 P2
P1 P2
P1 P2
DEV1 53
DEV1 15
DEV2 30
P1 P2
P1 P2
DEV98
P1 P2
P1 P2
DEV1 14
DEV2 40
P1 P2
P1 P2
DEV15 4
DEV11 9
DEV15 5
DEV12 1
P1 P2
P1 P2
P1 P2
DEV22 5
DEV22 6
P1 P2
DEV61 4
P1 P2
P1 P2
DEV28 2
DEV11 8
DEV55 4
DEV55 5
P1 P2
P1 P2
DEV12 0
P1 P2
P1 P2
DEV2 80
P1 P2
P1 P2
P1 P2
DEV2 79
DEV96
P1 P2
DEV61 6
P1 P2
P1 P2
DEV60 9
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV5 47
P1 P2
DEV5 52
DEV5 53
DEV53 3
DEV1 12
P1 P2
P1 P2
P1 P2
DEV5 31
DEV6 13
DEV4 80
DEV4 85
DEV52 4
P1 P2
DEV53 0
DEV49 0
P1 P2
P1 P2
P1 P2
DEV5 48
DEV5 22
P1 P2
DEV49 5
DEV6 06
DEV6 07
P1 P2
P1 P2
DEV5 32
DEV60 3
P1 P2
DEV52 8
DEV60 4
P1 P2
P1 P2
P1 P2
P1 P2
DEV4 79
P1 P2
P1 P2
DEV4 84
P1 P2
P1 P2
P1 P2
DEV52 7
DEV48 9
P1 P2
P1 P2
DEV5 26
DEV49 4
P1 P2
P1 P2
DEV48 8
DEV48 7
DEV49 1
DEV52 5
P1 P2
P1 P2
P1 P2
DEV4 78
DEV4 77
DEV4 81
P1 P2
DEV4 83
P1 P2
DEV51 6
DEV49 3
DEV49 2
DEV49 6
P1 P2
P1 P2
DEV89 9
P1 P2
DEV61 5
P1 P2
P1 P2
P1 P2
P1 P2
DEV5 43
DEV53 4
DEV5 35
DEV53 6
DEV53 7
DEV5 41
DEV53 9
DEV5 40
DEV54 2
DEV5 50
DEV61 7
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV6 08
DEV1 31
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV50 0
P1 P2
DEV17 7
P1 P2
P1 P2
DEV24 6
tm l_ 5_ 2
DEV7 0
P1 P2
DEV5 46
P1 P2
DEV5 62
P1 P2
DEV56 3
DEV50 3
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV44 9
P1 P2
DEV5 05
P1 P2
P1 P2
P1 P2
DEV4 51
P1 P2
DEV5 02
tm l _4 _3
DEV4 31
DEV44 0
P1 P2
DEV4 48
DEV44 6
P1 P2
DEV4 99
P1 P2
DEV1 6
P1 P2
P1 P2
DEV1 76
P1 P2
DEV24 5
v (t)
DEV6 18
P1 P2
DEV4 45
P1 P2
DEV49 8
P1 P2
DEV4 97
P1 P2
DEV44 4
R28
P1 P2
DEV8 79
P1 P2
DEV91 2
DEV88 1
P1 P2
DEV82 7
DEV8 76
P1 P2
DEV6 20
DEV4 82
DEV4 86
P1 P2
DEV90 9
DEV9 10
1
P1 P2
P1 P2
DEV82 6
DEV82 5
P1 P2
DEV8 78
P1 P2
DEV82 4
DEV87 7
P1 P2
DEV82 3
DEV87 5
DEV5 44
P1 P2
P1 P2
DEV9 11
P1 P2
DEV6 19
P1 P2
DEV206
DEV2 41
DEV5
DEV7
DEV25 6
P1 P2
DEV6
P1 P2
P1 P2
DEV10
tm l_5 _1
DEV25 7
P1 P2
tm l_ 5_ 0
DEV21
P1 P2
DEV2
P1 P2
DEV9
P1 P2
DEV1 5
P1 P2
P1 P2
DEV4
P1 P2
P1 P2
DEV17 8
P1 P2
DEV3
P1 P2
DEV8
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV578
DEV58 2
DEV5 77
P1 P2
P1 P2
DEV55 6
P1 P2
DEV55 7
DEV55 9
P1 P2
DEV5 79
P1 P2
P1 P2
P1 P2
DEV5 61
P1 P2
DEV1 75
P1 P2
P1 P2
DEV19 6
DEV4 3
P1 P2
DEV4 36
DEV17 4
P1 P2
DEV19 0
s cope
DEV4 37
DEV5 81
P1 P2
P1 P2
tm l_ 4_ 0
P1 P2
P1 P2
DEV5 99
P1 P2
Gnd 34
DEV1 73
P1 P2
P1 P2
DEV1 94
DEV1
P1 P2
P1 P2
t m l _4_ 1
P1 P2
DEV41 5
P1 P2
DEV40 1
DEV37 3
DEV5 98
DEV44 3
DEV36 8
P1 P2
DEV40 4
DEV42 2
P1 P2
p2
P1 P2
P1 P2
P1 P2
DEV4 29
DEV4 27
DEV43 9
DEV43 8
P1 P2
DEV5 45
P1 P2
DEV40 2
P1 P2
DEV37 8
P1 P2
DEV37 7
P1 P2
P1 P2
P1 P2
DEV41 3
DEV4 24
P1 P2
P1 P2
DEV3 96
P1 P2
DEV42 0
DEV40 3
P1 P2
DEV3 54
DEV37 9
DEV4 34
P1 P2
DEV4 30
t m l _3 _2
P1 P2
P1 P2
P1 P2
DEV34 5
DEV31 8
DEV34 6
P1 P2
DEV32 4
P1 P2
DEV41 9
P1 P2
DEV3 57
DEV35 3
P1 P2
DEV17 2
DEV1 87
P1 P2
P1 P2
DEV4 18
P1 P2
P1 P2
DEV597
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV4 00
DEV5 96
P1 P2
DEV590
DEV35 5
P1 P2
DEV35 0
DEV4 32
DEV580
DEV3 99
P1 P2
DEV40 9
DEV41 7
P1 P2
P1 P2
DEV34 9
P1 P2
P1 P2
DEV34 8
P1 P2
P1 P2
P1 P2
DEV34 7
DEV41 0
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV5 95
P1 P2
P1 P2
P1 P2
DEV3 31
P1 P2
P1 P2
P1 P2
DEV3 08
P1 P2
P1 P2
DEV5 93
DEV5 94
P1 P2
P1 P2
DEV576
P1 P2
DEV5 73
P1 P2
P1 P2
P1 P2
DEV58 9
t m l _3_ 1
DEV40 6
P1 P2
DEV40 7
P1 P2
P1 P2
DEV57 2
tm l_ 4_ 2
DEV58 3
P1 P2
DEV5 88
DEV3 16
tm l_ 3_ 0
P1 P2
P1 P2
DEV31 7
DEV33 2
DEV33 4
DEV32 3
DEV33 3
P1 P2
DEV33 5
P1 P2
P1 P2
DEV33 0
P1 P2
DEV90 8
P1 P2
DEV90 0
P1 P2
DEV8 73
DEV91 3
P1 P2
DEV4 0
P1 P2
DEV5 70
P1 P2
P1 P2
DEV79 5
P1 P2
DEV80 3
DEV90 1
DEV8 64
DEV8 71
P1 P2
DEV8 11
P1 P2
DEV8 18
DEV8 09
DEV8 62
P1 P2
DEV8 19
P1 P2
P1 P2
P1 P2
DEV8 17
DEV8 61
+
DEV82 9
DEV18
P1 P2
DEV56 9
R2
P1 P2
DEV13 2
DEV1 33
DEV14 4
P1 P2
P1 P2
P1 P2
DEV1 40
DEV14 3
DEV1 45
P1 P2
P1 P2
P1 P2
DEV14 7
P1 P2
DEV64
P1 P2
+
+
1
DEV28 6
P1 P2
P1 P2
P1 P2
1
P1 P2
DEV8 55
DEV7 87
P1 P2
DEV8 53
P1 P2
P1 P2
P1 P2
DEV8 70
P1 P2
DEV8 10
P1 P2
DEV87 2
P1 P2
P1 P2
DEV8 08
DEV8 16
DEV86 3
P1 P2
+
1
DEV1 7
P1 P2
DEV5 71
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV90 2
DEV8 46
P1 P2
P1 P2
DEV7 86
DEV7 85
DEV8 44
P1 P2
DEV79 4
DEV79 3
P1 P2
P1 P2
P1 P2
P1 P2
DEV80 1
DEV8 43
DEV80 2
DEV7 84
DEV79 2
P1 P2
P1 P2
DEV8 69
DEV86 8
P1 P2
P1 P2
P1 P2
DEV8 74
P1 P2
DEV56 7
DEV58 5
P1 P2
P1 P2
DEV4 28
DEV4 26
P1 P2
DEV91 9
DEV92 0
DEV90 5
DEV906
DEV90 4
P1 P2
DEV76 3
DEV9 07
P1 P2
DEV77 1
P1 P2
DEV8 52
P1 P2
DEV8 60
DEV85 9
P1 P2
P1 P2
DEV8 15
DEV8 67
P1 P2
P1 P2
DEV8 07
P1 P2
P1 P2
P1 P2
DEV8 58
P1 P2
P1 P2
DEV8 14
DEV8 13
P1 P2
DEV82 2
DEV82 1
DEV82 8
P1 P2
P1 P2
+
R2 7
DEV96 6
P1 P2
v(t)
P1 P2
1
DEV5 1
P1 P2
DEV9 65
P1 P2
DEV5 87
P1 P2
P1 P2
P1 P2
DEV7 52
P1 P2
P1 P2
DEV76 2
P1 P2
P1 P2
DEV77 0
DEV76 1
P1 P2
DEV8 37
P1 P2
DEV76 9
DEV89 8
P1 P2
DEV9 57
P1 P2
DEV85 4
P1 P2
DEV80 0
P1 P2
DEV780
P1 P2
DEV80 4
P1 P2
DEV8 06
DEV8 12
DEV8 20
P1 P2
DEV31 5
P1 P2
DEV5 84
P1 P2
+
P1 P2
P1 P2
DEV91
P1 P2
DEV96 3
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV84 5
P1 P2
P1 P2
DEV7 83
P1 P2
DEV79 1
P1 P2
P1 P2
P1 P2
P1 P2
DEV85 0
P1 P2
P1 P2
DEV79 0
DEV86 6
DEV78 9
P1 P2
P1 P2
DEV79 8
DEV8 65
DEV591
P1 P2
P1 P2
P1 P2
DEV91 8
DEV89 7
DEV7 47
P1
P2
DEV7 53
P1 P2
P1 P2
DEV777
DEV7 45
P1 P2
DEV8 35
P1 P2
P1 P2
P1 P2
DEV8 51
DEV7 44
DEV7 54
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV76 0
DEV76 8
P1 P2
DEV776
DEV8 42
DEV84 1
P1 P2
DEV79 9
DEV7 82
DEV7 88
P1 P2
DEV79 6
P1 P2
DEV79 7
DEV85 7
P1 P2
P1 P2
DEV8 05
DEV8 40
P1 P2
DEV8 56
DEV574
DEV9 14
DEV9 15
P1 P2
DEV68 7
DEV71 5
DEV71 4
P1 P2
P1 P2
DEV8 93
DEV8 6
P1 P2
DEV56 6
DEV5 86
P1 P2
t m l _2_ 1
DEV7 19
P1 P2
DEV71 2
DEV71 0
P1 P2
P1 P2
DEV71 3
DEV71 1
P1 P2
DEV7 18
P1 P2
P1 P2
DEV70 9
P1 P2
DEV83 6
DEV75 5
P1 P2
DEV778
P1 P2
DEV74 6
P1 P2
DEV8 34
P1 P2
P1 P2
DEV7 43
DEV7 56
P1 P2
DEV83 3
P1 P2
DEV76 7
P1 P2
P1 P2
DEV8 49
P1 P2
DEV74 2
P1 P2
P1 P2
DEV8 32
P1 P2
DEV84 8
P1 P2
P1 P2
P1 P2
DEV93 6
P1 P2
P1 P2
DEV95 5
DEV6 38
DEV68 1
DEV68 4
DEV6 97
P1 P2
P1 P2
DEV70 8
P1 P2
P1 P2
DEV6 94
DEV72 0
P1 P2
DEV7 27
P1 P2
DEV71 7
P1 P2
P1 P2
P1 P2
DEV93 7
P1 P2
DEV6 58
P1 P2
t m l _2 _0
P1 P2
DEV6 57
P1 P2
P1 P2
P1 P2
DEV6 50
P1 P2
DEV89 6
P1 P2
DEV6 52
DEV6 49
DEV6 59
P1 P2
P1 P2
DEV7 38
DEV70 6
DEV6 48
P1 P2
DEV6 45
P1 P2
P1 P2
DEV6 36
tm l_1 _1
DEV67 5
P1 P2
P1 P2
P1 P2
P1 P2
t m l _1 _2
P1 P2
P1 P2
P1 P2
P1 P2
DEV7 33
tm l_1 _3
P1
P2
DEV7 51
P1 P2
DEV75 9
P1 P2
DEV83 1
DEV83 9
P1 P2
DEV8 94
P1 P2
R49
+
+
R30
DEV8 2
P1 P2
DEV5 65
P1 P2
DEV7 41
DEV75 0
DEV775
P1 P2
1
P1 P2
1
DEV8 1
P1 P2
DEV9 62
P1 P2
DEV56 4
P1 P2
P1 P2
P1 P2
DEV8 47
DEV8 95
DEV85
P1 P2
DEV96 4
P1 P2
P1 P2
DEV6 47
DEV6 54
DEV6 93
Gn d1 2
s cope
DEV72 4
DEV74 0
DEV6 9
P1 P2
DEV9 61
DEV5 92
P1 P2
DEV64 4
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV6 71
DEV6 65
DEV6 62
DEV6 68
DEV70 2
DEV69 8
P1 P2
P1
P2
DEV70 0
P1 P2
DEV70 5
P1 P2
P1 P2
DEV7 32
DEV7 31
DEV7 30
DEV7 29
P1 P2
P1 P2
P1 P2
DEV75 8
DEV75 7
DEV76 6
DEV76 5
P1 P2
P1 P2
DEV774
DEV7 81
P1 P2
DEV773
DEV8 38
P1 P2
P1 P2
DEV6 37
DEV68 9
P1 P2
P1 P2
P1 P2
P1 P2
DEV9 54
P1 P2
DEV94 8
DEV93 8
P1 P2
P1 P2
P1 P2
DEV93 9
P1 P2
P1 P2
t m l _1 _0
P1 P2
P1 P2
DEV65 5
DEV6 35
DEV6 26
P1 P2
P1 P2
P1 P2
DEV6 31
DEV6 25
DEV6 33
DEV6 27
P1 P2
DEV6 34
P1 P2
P1
P2
DEV6 32
DEV64 3
P1 P2
DEV95 6
P1 P2
P1 P2
DEV68
P1 P2
DEV6 39
P1 P2
P1 P2
DEV8 30
P1
P2
DEV9 51
DEV9 53
P1 P2
P1 P2
DEV7 39
P1 P2
P1 P2
P1 P2
P1 P2
P1 P2
DEV7 49
DEV96 0
P1
P2
DEV9 52
p3
DEV7 48
P1 P2
DEV9 59
P1 P2
P1 P2
P1 P2
v (t)
P1 P2
P1 P2
P1 P2
DEV5 75
P1 P2
DEV6 40
P1 P2
DEV5 7
DEV9 40
P1 P2
P1 P2
DEV7 23
P1 P2
DEV9 58
P1 P2
DEV93 1
P1 P2
P1 P2
DEV9 47
DEV6 29
DEV6 90
DEV6 3
P1 P2
DEV28 4
DEV93 4
P1 P2
P1 P2
P1 P2
DEV62 2
DEV92
P1 P2
DEV9 30
R3
P1 P2
DEV9 27
P1 P2
DEV92 9
DEV93 5
DEV9 26
DEV9 43
P1 P2
P1 P2
DEV62 4
DEV58
P1 P2
DEV9 67
DEV9 28
P1 P2
DEV92 5
P1 P2
DEV94 6
P1 P2
DEV76 4
DEV1 01
1
DEV94 4
DEV94 5
P1 P2
DEV77 2
DEV10 3
DEV9 24
DEV779
DEV1 05
P1 P2
DEV94 2
DEV10 4
P1 P2
DEV94 9
DEV92 3
tm l_2 _3
DEV9 41
P1 P2
DEV93 2
P1 P2
P1 P2
P1 P2
DEV93 3
P1 P2
DEV6 23
R9
R1
+
+
1
DEV9 22
P1 P2
1
DEV95 0
+
+
DEV106
P1 P2
DEV1 07
(a) The layout of real grounding system
1
R24
R23
(b) the model of the entire grounding system
Fig. 7. Model of the grounding system
a
LF Load8
164MW
LF Load6
2MVAR
154MW
LF Load7
2MVAR
184MW
2MVAR
545MW
41MVAR
CP
TLM8
+
0.05nF
TLM7
77.43
+
C3
CP
8.60
+
8.60
CP
TLM5
+
0.05nF
C4
77.43
7576_2
DEV3
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
GISbusbar
GISbusbar
GISbusbar
76BUS_E
inst./pu
p
7672
Open Block
Lp
Rp
SWBlock_Open
GISbusbar
7600
Close Block
Lp
Rp
7621
7671
Close Block
Lp
Rp
SAMHAE2
GIS Bus Bar
BUS1
BUS2
GISbusbar
GIS Bus Bar
BUS1
BUS2
Gen6
Lp Rp
DS_C
7622
Lp Rp
DS_C
GISbusbar
7572
SWBlock_Open
GIS Bus Bar
BUS1
BUS2
Open Block
Lp
Rp
7522
Lp Rp
DS_C
7500
Close Block
Lp
Rp
DSOpen
DS_O
Lp Rp
7571
GISbusbar
GIS Bus Bar
BUS1
BUS2
7521
Close Block
Lp
Rp
SAMHAE1
20us| 1E15| 0
Gen5
GISbusbar
+
7475_2
GIS Bus Bar
BUS1
BUS2
7421
Lp Rp
DSClose
DS_C
Lp Rp
DEV8
74GIS
GIS Bus Bar
BUS1
BUS2
CBClose
DSClose
7400
CB_C
Lp Rp
7401
DS_C
Lp Rp
7471
DS_C
Gen4
GIS Bus Bar
BUS1
BUS2
+
DEV9
DS_C
Lp Rp
+
Close Block
Lp
Rp
GISbusbar
7372
7322
Close Block
Lp
Rp
7300
Close Block
Lp
Rp
7321
GISbusbar
Lp Rp
7371
Close Block
Lp
Rp
7200
Close Block
Lp
Rp
DS_C
7271
Gen3
7221
Close Block
Lp
Rp
DS_C
GIS Bus Bar
BUS1
BUS2
Lp Rp
GISbusbar
Gen2
GIS Bus Bar
BUS1
BUS2
?vi
GISbusbar
CP
+
C5
0.05nF
TLM3
55.43
Lp Rp
7272
GIS Bus Bar
BUS1
BUS2
SAMCHEONPO1
Close Block
Lp
Rp
GISbusbar
DS_C
GIS Bus Bar
BUS1
BUS2
7222
Lp Rp
DS_C
DSClose
SAMCHEONPO2
CBClose
DSClose
GISbusbar
DS_C
Lp Rp
CB_C
Lp Rp
DS_C
Lp Rp
Close Block
Lp
Rp
GIS Bus Bar
BUS1
BUS2
7152
71GIS
7100
7101
7171
7121
GISbusbar
DS_C
Lp Rp
DSClose
GISbusbar
CBClose
GIS Bus Bar
BUS1
BUS2
CB_C
Lp Rp
DSClose
DS_C
DS_C
Lp Rp
Lp Rp
Gen1
Close Block
Lp
Rp
GIS Bus Bar
BUS1
BUS2
7A52
7AGIS
7A00
7A01
7A71
7A22
DS_C
SW1
DEV1
7B7A_1
7A71_1
7172_1
7273_1
7374_1
7475_1
7576_1
DEV4
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
Lp Rp
DS_C
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
GISbusbar
GISbusbar
GISbusbar
GISbusbar
GISbusbar
GISbusbar
7071DS_C
GISbusbar
GISbusbar
GISbusbar
DY_7
0.48/0.15
1
v(t)
p6
SM
inst./pu
p
SM1
3
6.9/6.9/21 22kV
620MVA
inst./pu
p
YY1
YY2
6.9/0.48
2
1
1
YgYgD_np1
1
6.9/0.48
2
1
AUXTR6_2ND
SUBTR_2ND
inst./pu
p
Out_Sgn
CTRL_Block
scope
scope
CTR4N_V
CTR4N_C
CTRL5
Control & DC Part
IN_VAC
IN_SGN
GND
Out_Sgn
CTRL_Block
scope
scope
CTR5N_V
CTR5N_C
inst./pu
CTRL6
p
Control & DC Part
IN_VAC
IN_SGN
GND
v(t)
p12
Control & DC Part
SSUBTR6_2ND
i(t)
CTR3N_C
scope
scope
TR6N_V
TR6N_C
inst./pu
p
2
2
CTRL_Block
scope
scope
CTR3N_V
SSUBTR4_2ND
inst./pu
CTRL4
p
IN_VAC
IN_SGN
GND
v(t)
p11
Out_Sgn
i(t)
CTR2N_C
CTRL3
Control & DC Part
IN_VAC
IN_SGN
GND
v(t)
p10
CTRL_Block
scope
scope
CTR2N_V
inst./pu
p
v(t)
p9
Out_Sgn
i(t)
CTR1N_C
v(t)
p8
CTRL_Block
scope
scope
CTR1N_V
CTRL2
Control & DC Part
IN_VAC
IN_SGN
GND
i(t)
i(t)
Out_Sgn
CTRL_Block
scope
scope
CTR6N_V
CTR6N_C
DEV5
tml_1_0
tml_1_1
tml_1_2
tml_1_3
tml_2_0
tml_2_1
tml_2_2
tml_2_3
tml_3_0
tml_3_1
tml_3_2
tml_3_3
tml_4_0
tml_4_1
tml_4_2
tml_4_3
tml_5_0
tml_5_1
tml_5_2
tml_5_3
tml_6_0
tml_6_1
tml_6_2
tml_6_3
In addition, the entire grounding system is modeled by
the layout of real grounding system and the equivalent
model in Figs. 2 and 7 shows the model of the entire
grounding system used in this paper.
Fig. 8 shows the layout of the 345kV thermal plant, also
shown in Fig. 4, when modeled by EMTP.
Out_Sgn
i(t)
SSUBTR3_2ND
CTRL1
Control & DC Part
IN_VAC
IN_SGN
GND
v(t)
p7
Fig. 6. The model of control circuit
2
i(t)
DEV10
SM
SM2
3
6.9/6.9/2122kV
620MVA
2
AUXTR5
inst./pu
p
Gen6
scope
scope
TR5N_V
TR5N_C
i(t)
2
DY_6
20.9/345
1
v(t)
p1
MAINTR5
20.9/345
1
C9
DY_5
0.48/0.15
1
DY_4
0.48/0.15
1
2
+
2
v(t)
p5
SM
GEN4
3
6.9/6.9/21 22kV
660MVA
YY3
6.9/0.48
2
1
YY4
6.9/0.48
2
1
DY_3
0.48/0.15
1
2
YY5
6.9/0.48
2
1
i(t)
MAINTR4
21/3451
v(t)
p2
1
6.9/6.9/21
AUXTR4
2
660MVA
GEN3
322kV
2
AUXTR3
1
1
inst./pu
p
SUBTR4_2ND
2
0.05nF
scope
scope
TR4N_V
TR4N_C
inst./pu
p
AUXTR4_2ND
DY_1
0.48/0.15
1
YY6
6.9/0.48
2
1
Gen4
scope
scope
TR3N_V
TR3N_C
i(t)
MAINTR3
21/3451
C1
Gen3
inst./pu
p
SM
i(t)
2
+
2
v(t)
p3
2
2
GEN2
3
6.9/6.9/21 22kV
660MVA
AUXTR2
0.05nF
scope
scope
TR2N_V
TR2N_C
SM
i(t)
MAINTR1
21/3451
SM
125
660MVA
C8
c
GEN1
322kV
-
1
Compare
2
?s
Detect_125
2
+
MAINTR2
21/3451
2
v(t)
p4
+
Trip_R
?vi
+
386E
+
scope
scope
TR1N_V
TR1N_C
DY_2
0.48/0.15
1
v (t)
p13
CP
TLM6
Load5
P
Q
549MW
32MVAR
6.16
+
CP
TLM4
Load4
P
Q
545MW
29MVAR
CP
+
C6
0.05nF
TLM1
55.43
PI
PI2
+
GISbusbar
CBClose
DSClose
Lp Rp
7BGIS
7B22
GIS Bus Bar
BUS1
BUS2
DS_C
Lp Rp
7B00
CB_C
Lp Rp
7B01
DS_C
Lp Rp
7B71
GISbusbar
GISbusbar
DSClose
SINGOSUNG1
GISbusbar
GIS Bus Bar
BUS1
BUS2
GISbusbar
DS_C
Lp Rp
GISbusbar
GISbusbar
7B52
GISbusbar
SINGOSUNG2
GISbusbar
GIS Bus Bar
BUS1
BUS2
7374_2
GIS Bus Bar
BUS1
BUS2
2
IN_SGN
7273_2
GIS Bus Bar
BUS1
BUS2
0.192
In_Sgn
scope
inst./pu inst./pu
p
p
7172_2
GIS Bus Bar
BUS1
BUS2
Out_Sgn
GND
BUS1
7576DS_C7576DS_R
inst./pu
p
7A71_2
GIS Bus Bar
BUS1
BUS2
6.9/6.9/21
+
7576DS_L
7B7A_2
GIS Bus Bar
BUS1
BUS2
AUXTR1
v (t)
p2
C5
!v
15600uF
disconnector
+
DEV2
1
2
sum1
v(t)
1
+
GIS Bus Bar
BUS1
BUS2
386E_VLL
scope
v (t)
p14
p1
D7
+
a
DC_24VPU
scope
+
c
TRIP_R
?v
Tr0_1
Gain2
0.039
DC_24V
scope
TRIP_E
VM +
386E_V
IN_VAC
DC_125VPU
scope
+
C6
!v
7.794e-3
DC_125V
scope
Trip_E
2uF
v (t)
p6
?vi
+
D4
D5
D6
+
C7
!v
386E_SW
Gain1
D1
D2
D3
In order to simulate the effect of various transients on
control circuit, the model of control circuit is shown in Fig. 6.
Based on the feature of real control circuit, the model of
control circuit is simplified.
2uF
PI
PI1
+
+
Fig. 5. The equivalent model of the circuit breaker
a
b
c
C8
0.05nF
(b) Close status
Close Block
Lp
Rp
(a) Open status
C7
0.05nF
6.16
+
CP
TLM2
Load1
P
Q
342MW
46MVAR
Load3
P
Q
292MW
46MVAR
Load2
P
Q
b
full_gnd
Fig. 8. 345kV thermal plant for very fast transients and
lightning surges
Analysis of Transient Overvoltages within a 345kV Korean Thermal Plant
300
3.1.2 A switching transients section
In order to simulate switching transients due to a prestrike on the disconnector switch, the system model uses
the pre-strike model mentioned previously. Fig. 9 shows
the GIS part of the system model applied to the pre-strike
model. The system model is same except the GIS part with
the pre-strike model.
3.2 Simulation conditions
554MW
8MVAR
Load13
P
Q
Load1
P
Q
CP
CP
TLM14
545MW
TLM16 41MVAR
549MW
32MVAR
GISBUS
DEV7
inst./pu
p
+
DEV6
CP
Prestrike
Vsw
Csw
a
Prestrike
Vsw
Csw
b
z s eq1
DEV19
DEV8
GIS Bus Bar
BUS1
BUS2
GIS Bus Bar
BUS1
BUS2
GISbus bar
GISbus bar
+
DEV2
+
+
CP
8.60
+
DEV20
inst./pu
p
77.43
TLM15
+
TLM11
55.43
TLM9
55.43
BUS_Vrad
V0 mag rad
77.43
TLM13
8.60
6.16
scope
BUS_Vmag
scope
CP
6.16
CP
+
PI
PI
PI1
PI3
+
+
Fig. 10. Voltage waveform at 76BUS
+
CP
TLM12
Load12
P
Q
545MW
29MVAR
Load9
P
Q
CP
+
342MW
46MVAR
TLM10
292MW
46MVAR
Load11
P
Q
Load10
P
Q
In order to analyze very fast transients, switching
transients, which occur due to disconnector switching
within the system model, and lightning surges, the simulation
conditions are fixed, as shown in Table 1, 2, and 3,
respectively.
b
c SW2
Prestrike
Vsw
Csw
inst./pu
p
a
c SW3
+
DEV3
DEV1
c
+
c
c SW1
GIS Bus Bar
BUS1
BUS2
(a) #4 Generator
(b) #6 Generator
GISbus bar
Fig. 9. System model for the switching transients
Fig. 11. Voltage waveforms for some generators in the time
domain
Table 1. Simulation conditions for very fast transients
Time step
Maximum simulation time
System condition
Simulation condition
3ns
30us
76BUS have been de-energized
75-76 DS close when simulation starts
Table 2. Simulation conditions for switching transients
Time step
Maximum simulation time
System condition
Simulation condition
125ns
1.3s
76BUS have been de-energized
75-76 DS close when simulation starts
Table 3. Simulation conditions for switching transients
Time step
Maximum simulation time
Simulation condition
3ns
100us
Lightning strike transmission lines at
20us
3.3 Simulation results
the voltages for the others. As shown in Figs. 10 and 11,
overvoltages from the disconnector switching propagate
through the GIS and are reflected and refracted at every
transition point.
(2) Analysis of transients in the frequency domain
Fig. 12 shows the frequency spectrum of the measured
voltages at each generator terminal. Due to the main
frequencies of the VFT overvoltages being in the range of
100kHz to 50MHz, the simulation results shown in Fig. 12
are the same as in the theoretical studies. Additionally,
since the propagation route of the traveling wave is
different from the GIS layout and length, the main
frequency is different from the frequency at the measuring
point. Therefore, both an accurate GIS layout and length
are very important for obtaining exact simulation results
when a VFT is simulated with disconnector switching
within a GIS. Tables 4 and 5 show the summarized the
simulation results.
3.3.1 Very fast transients
(1) Analysis of the transients in the time domain
Fig. 10 shows the voltage waveform, which has a 1.9pu
maximum value and a high speed oscillation, of the
energized 76BUS after closing the disconnect switches (DS).
Fig. 11 shows voltage waveforms, which are different at
each measuring point, for each generator. The voltage at
the #4 generator terminals, close to the 75-76 DSs that
caused the overvoltage, is more affected by the VFTOs
than the voltage at the terminals of the other generators.
Therefore, the voltage for the #4 generator is higher than
(a) #4 Generator
(b) #6 Generator
Fig. 12. Voltage waveforms for some generators in the
frequency domain
Sang-Min Yeo and Chul-Hwan Kim
As shown in the simulation results below, it is clear that
the overvoltages generated by disconnector switching
propagate through the GIS. The propagated overvoltages
affect transformers, generators and buses, especially for a
bus that is energized. As mentioned before, VFTOs caused
by disconnector switching have very high frequencies and
propagate through the GIS and reach all pieces of
equipment. Hence, these high frequency overvoltages may
cause improper operation of low-voltage control circuits.
Table 4. Measured voltage at each generator
Measured
Point
Max. voltage
Max. voltage
deviation
Voltage at each generator (unit : p.u.)
#1 Gen. #2 Gen. #3 Gen. #4 Gen. #6 Gen.
1.184
1.311
1.377
1.336
1.111
0.432
0.651
0.729
0.787
301
after the disconnector switching occurred. Also shown is
the slight difference in the overvoltage magnitude at the
GIS bus bar, of approximately 7kV, from the magnitude of
the normal voltage during disconnector switching. The
dominant frequency of the transient overvoltages is 60Hz,
which is the power frequency, but the disconnector
switching within the GIS creates high frequency
components rather than the dominant one, even if they
have a relatively small magnitude.
Moreover, voltages and currents at the neutral point of
the main transformer have a large magnitude due to the
phase unbalance. Fig. 14 shows the voltage waveforms at
the neutral points of the main transformers.
0.270
Table 5. Measured voltage at each bus
Measured
Point
Max. voltage
Max. voltage
deviation
70BUS
1.27937
0.55189
Voltage at each bus (unit: p.u.)
71BUS
75BUS
76BUS
1.11887
1.22162
1.89149
0.29512
0.49931
1.67597
3.3.2 A switching transients
Fig. 13 shows the 3-phase instantaneous voltage
waveforms and frequency spectrum for the GIS bus bar
Fig. 14. Voltage waveforms at the neutral point of the main
transformer
Even if the magnitudes are different at each measuring
point, the average of the neutral voltage magnitudes is
approximately 15kV. As a result of the neutral voltages, the
grounding system is affected and the ground voltage is
temporarily changed to a non-zero voltage value.
Fig. 15 shows the waveforms of the ground voltages for
the low-voltage control circuits. The duration is short,
about 0.5 seconds, but the voltages have large magnitudes
and high frequencies and, because of this, the control
circuits would be damaged if they did not have appropriate
protection devices, such as a surge protection device.
(a) Instantaneous voltages
Fig. 15. Ground voltage at low-voltage control circuits
(b) Frequency Spectrum
Fig. 13. 3-phase voltage at the GIS bus bar
3.3.3 A lightning surge
Fig. 16 shows the phase voltages at the terminals of each
generator when lightning strikes the BB #2 transmission
line. The simulation results for the other transmission lines
are slightly different from the results shown in Fig. 16.
As shown in Fig. 16, when the lightning surges
302
Analysis of Transient Overvoltages within a 345kV Korean Thermal Plant
propagate through the GIS, the generator transformers also
experience overvoltages, approximately 140kVpeak, due to
lightning surges. Figs. 17-18 show the voltage waveform at
the neutral point of the main transformer and ground
voltage of the low-voltage control circuits, respectively.
Fig. 16. The voltage waveforms at each generator when the
lightning strikes BB #2 T/L
Fig. 17. Voltage waveforms at the neutral point of the main
transformer
5. Conclusions
This paper demonstrates an equivalent model for various
pieces of equipment implemented via EMTP in order to
accurately simulate VFTOs by disconnector switching
within GIS. Also, calculated voltages are shown in both the
time and frequency domains at various measuring points.
It can be concluded from the calculated results that the
VFT overvoltages via disconnector switching within GIS
propagate and reach all pieces of equipment. Also, the high
frequencies of the VFT overvoltage can have an impact on
the low-voltage control circuits. Due to the pre-strike
phenomenon that causes different reactions for each phase,
the phase voltage becomes unbalanced during disconnector
switching and then the generated zero sequence voltage has
a large magnitude. These zero sequence voltages are
revealed as neutral voltages at the neutral point of the
transformer and they will affect the grounding system. The
simulation results show that the switching transient
overvoltages occurring via disconnector switching in GIS
are smaller than ones from other origins. Also, when the
lightning surge enters the various equipment pieces, such
as the GIS, generators, transformers and various devices
electrically connected to the GIS in thermal plant, they
experience significant overvoltages similar to those stated
for the previous cases, i.e. VFTs and switching transients.
However, though the magnitudes of the overvoltages are
small, it is clear that overvoltages have high frequencies
and can cause high voltages in the grounding system and
will, therefore, damage low-voltage electronic devices.
References
[1]
Fig. 18. Ground voltage of the low-voltage control circuits
The voltages of the neutral point of the main transformer
and at the ground point of the low-voltage control circuits
should be close to zero. However, each voltage has a large
magnitude during a lightning surge strike, as in the case of
switching transients. The magnitude at the neutral point of
the transformers and at the ground point of the control
circuits is approximately 250Vpeak, -580Vpeak, respectively.
These magnitudes are smaller than the magnitudes of the
switching transients, but the lightning surges and the
magnitudes have significantly high frequencies. Therefore,
several control circuits may be damaged by the
overvoltages.
[2]
[3]
[4]
[5]
Salih Carsimamovic, Zijad Bajramovic, Miroslav
Ljevak, Meludin Veledar, “Very Fast Electromagnetic
Transients in Air Insulated Substations and Gas
Insulated Substations due to Disconnector Switching”,
International Symposium on Electromagnetic
Compatibility, 2005. EMC 2005, vol. 2, pp. 382-387,
8-12 Aug., 2005.
Z. Haznadar, S. Carsimamovic, R. Mahmutcehajic,
“More Accurate Modeling of Gas Insulated
Substation Components in Digital Simulations of
Very Fast Electromagnetic Transients”, IEEE Trans.
on Power Delivery, vol. 7, no. 1, pp. 434-441, Jan.,
1992.
EPRI, Electromagnetic Transients Program(EMTP)
Workbook II, EPRI Final Report, EL-4651, vol. 2,
June. 1986.
V. Vinod Kumar, Joy Thomas M., M.S. Maidu,
“Influence of Switching Conditions on the VFTO
Magnitudes in a GIS”, IEEE Trans. on Power
Delivery, vol. 16, no. 4, pp. 539-544, Oct., 2001
Lu Tiechen, Zhang Bo, “Calculation of Very Fast
Transient Overvoltages in GIS”, 2005 IEEE/PES
Sang-Min Yeo and Chul-Hwan Kim
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
Transmission and Distribution Conference &
Exhibition: Asia and Pacific Dalian, China, pp. 1-5,
2005.
Xuzhu Dong, Sebastian Rosado, Yilu Liu, NienChung Wang, E-Leny Line, Tzong-Yih Guo, “Study
of Abnormal Electrical Phenomena Effects on GSU
Transformers”, IEEE Trans. on Power Delivery, vol.
18, no. 3, pp. 835-842, July, 2003.
IEEE Working Group 15.08.09, Tutorial on Modeling
and Analysis of System Transients using Digital
Programs, IEEE PES Special Publication, 1998.
D.A. Woodford, L.M. Wedepohl, “Transmission Line
Energization with Breaker Pre-Strike”, 1997 Conference
on Communications, Power and Computing WESCANEX
'97 Proceedings, pp. 105-108, May 22-23, 1997.
D.A. Woodford, L.M. Wedepohl, “Impact of Circuit
Breaker Pre-Strike on Transmission Line Energization
Transients”, IPST '97, Seattle, pp. 250-253, June 22-26,
1997.
A. Ametani, T. Goto, S. Yoshizaki, H. Omura, H.
Motoyama, “Switching Surge Characteristics in GasInsulated Substation”, Universities Power Engineering
Conference, 2006. UPEC '06. Proceedings of the 41st
International, vol. 3, pp. 941-945, Sept. 2006.
A. Ametani, K. Ohtsuki, N. Nagaoka, “Switching
Surge Characteristics in Gas-Insulated Substations in
Particular Reference to Low-Voltage Control
Circuits”, UPEC 2004, Bristol, UK, Sept., 2004.
S.M. Yeo, H.C. Seo, C.H. Kim, Y.S. Lyu, B.S. Cho,
“EMTP Analysis of Very Fast Transients due to
Disconnector Switching in a 345kV Korean Thermal
Plant”, International Conference of Electrical
Engineering, Okinawa, Japan, paper no. P-093, 6-10
July, 2008.
S.M. Yeo, H.C. Seo, C.H. Kim, Y.S. Lyu, B.S. Cho,
“Investigation of Switching Transients due to
Disconnector Switching”, International Conference
of Electrical Engineering, Okinawa, Japan, paper no.
O-112, 6-10 July, 2008.
DCG-EMTP(Development coordination group of
EMTP) Version EMTP-RV, Electromagnetic Transients
Program. [Online]. Avaliable : http://www.emtp.com.
F.E. Menter, L. Grcev, “EMTP-Based Model for
Grounding System Analysis”, IEEE Trans. on Power
Delivery, vol. 9, no. 4, pp. 1838-1849, Oct. 1994.
L. Grcev, “Modelling of Grounding Systems for
Better Protection of Communication Installations
303
against Effects from Electric Power System and
Lighting”, IEE Conference INTELEC 2001, pp. 461468, 14-18 Oct. 2001.
[17] G. Celli, F. Pilo, “A Distributed Parameter model for
Grounding Systems in the PSCAD/EMTDC
environment”, IEEE Power Engineering Society General
Meeting, 2003, vol. 3, pp. 1650-1655, 13-17 July 2003.
[18] A. Rakotomalala, Ph. Auriol, A. Rousseau, “Lighting
Distribution through Earthing Systems”, IEEE
International Symposium on Electromagnetic Compatibility, pp. 419-423, 22-26 Aug., 1994.
[19] I. Uglesic, S. Hutter, V. Milardic, I. Ivankovic, B.
Filipovic-Grcic, “Electromagnetic Disturbances of
the Secondary Circuits in Gas Insulated Substation
due to Disconnector Switching”, International
Conference on Power Systems Transients, IPST 2003
in New Orleans, USA, 2003.
Sang-Min Yeo was born in Korea,
1976. He received his B.S., M.S., and
Ph.D. degrees in Electrical Engineering
from Sungkyunkwan University in
1999, 2001, and 2009, respectively.
Since October 2009, he joined Power
& Industrial Systems R&D Center,
Hyosung Corporation, Korea. His
current research interests include power system transients,
modeling and simulation for FACTS/HVDC using EMTP,
power system protection and computer application using
EMTP, and signal processing.
Chul-Hwan Kim was born in Korea,
1961. He received his B.S., M.S., and
Ph.D degrees in Electrical Engineering
from Sungkyunkwan University, Korea,
1982, 1984, and 1990 respectively. In
1990 he joined Cheju National
University, Cheju, Korea, as a full-time
Lecturer. He has been a visiting
academic at the University of BATH, UK, in 1996, 1998,
and 1999. Since March 1992, he has been a professor in the
School of Information and Communication Engineering,
Sungkyunkwan University, Korea. His research interests
include power system protection, artificial intelligence
application for protection and control, the modelling/
protection of underground cable and EMTP software.
Download