LV HRC fuse switch-disconnectors, size 1

advertisement
LV HRC fuse switch-disconnectors
The “9” series LV HRC fuse switch-disconnectors of the DIN sizes 00 - 4a are suitable for surface mounting on
mounting plates and for direct mounting on busbars. The different sizes are available as 1-pole, 2-pole, 3-pole and
4 -pole versions.
• Surface mounting
• Busbar mounting
• 1 - pole, 2 - pole, 3 - pole and 4 - pole
• Retrofittable cable connections
• Fuse monitor
• Position indication
• DIN rail fixing parts
LV HRC fuse switch-disconnectors, size 1
Example: Surface mounting with accessories, 1-pole
Basic construction
1 Base of disconnector U-LTL1-1
2 Protective cover, top BO-LTL1-1
3 Protective cover, bottom BU-LTL1-1
4 Swing-in device D-LTL1-1/9
Connection accessories
5ab) Screw terminal F-LTL1-M10
6 Clamp-type terminal S1
7 V terminal clamp P1
8 Double V-terminal clamp P12
Covering accessories
(Protection against contact)
9 Handle protection, top and bottom GOU-LTL1-1
Accessories for mechanical fuse monitoring
Position indicator, “ON”
10ab) Mech. fuse monitor K-LTL1-1/H
11ab) Position indicator,
“ON” (electrical interlocking) eV-LTL123-1
LV HRC fuse switch-disconnectors with quasi-instantaneous circuit
12 Quasi-instantaneous circuit LTL1-1/9/Q
C 6
LV HRC fuse switch-disconnectors
LV HRC fuse switch-disconnectors, size 00
Example: Surface mounting with accessories, 3 - pole
Basic construction
1 Base of disconnector U - LTL00 - 3
2 Protective cover, top BO - LTL00 - 3
3 Protective cover, bottom BU - LTL00 - 3
4 Swing-in device D - LTL00 - 3/9
Connection accessories
5 Screw terminal F - M8x16
6 Clamp - type terminal S00
7 V - terminal clamp P0070
8 Box terminal F50
Covering accessories
(Protection against contact)
9 Handle protection, top/bottom GOU - LTL00 - 3
Fixing accessories
10 DIN rail fixing parts Z - LTL00 - 3
Accessories for interlocking,
mechanical fuse monitoring and
“ON” position indication
11 Protective cover interlock VHG - LTL00123 - 3
12 Mech. fuse monitor K - LTL00 - 3/H
13 Position indicator, “ON” (electrical interlocking) eV
- LTL00 - 3
Accessories: Swing - in device
with electronic fuse monitor
14 Swing-in device ES00 – D - LTL00
C 7
LV HRC fuse switch-disconnectors
Sizes 00 - 4a / 160A - 1600A
1 - pole / surface mounting AC 690V
Product definition
LV HRC fuse switch-disconnectors in accordance with EN 60947-3 with swing-in device for accomodating one LV HRC fuse - link in accordance with DIN 43620, sizes 00/160 A to 4a/1600
A.
Applications
Switchgear for system, cable and motor protection in alternating and direct current systems.
The disconnectors are frequently used in battery - powered direct current systems such as
UPS systems.
Operational principle
Using amanually - operated swing - in device, the LV HRC fuse - link is swung in (making
operation) and pulled out (breaking operation).
Product construction
Swing - in devicemade ofhalogen - free self – extinguishing plastics. Split latch - on contact
cover. Standard disconnectors are equipped with screw terminals, but can be retrofitted with
direct - connection terminals.
Size
LTL...
Size 00
Size 1
Size 3
Size 4a
Size 4a
Rated operational current (A)
Std.P
Type
160
250
630
1250
1600
1
1
1
1
1
00-1/9
1-1/9
3-1/9
4A-1X/1250/8
4A-1X/1600/8
Sizes 00 - 3 / 160A - 630A
2 - pole / surface mounting AC 690V
Product definition
LV HRC fuse switch-disconnectors in accordance with EN 60947-3 with swing - in device for
accomodating 2 LV HRC fuse-links in accordance with DIN 43620, sizes 00/160A to 3/630A.
Applications
Switchgear for system, cable and motor protection in direct current systems. The disconnectors are frequently used in battery - powered direct current systems such as UPS systems.
Operational principle
Usingmanually - operated swing - in devices, the LV HRC fuse - links are swung in (making
operation) and pulled out (breaking operation).
Product construction
Swing-in devicemade of halogen-free self-extinguishing plastics. Split latch-on contact cover.
Standard disconnectors are equipped with screw terminals, but can be retrofitted with directconnection terminals.
Size
LTL...
Size 00
Size 1
Size 3
C 8
Rated operational current (A)
Std.P
Type
160
250
630
1
1
1
00-2/9
1-2/9
3-2/9
LV HRC fuse switch-disconnectors
Sizes 00 - 4a / 160A - 1600A
3 - pole / surface mounting AC 690V
Product definition
LV HRC fuse switch - disconnectors in accordance with EN 60947-3 with
swing-in device for accomodating 3 LV HRC fuse - links in accordance with DIN
43620, sizes 00 - 4a / 160 A - 1600 A.
Applications
Switchgear for system, cable and motor protection in three - phase systems
up to 690V AC. The disconnectors are fitted in switchgear cabinets or insulating cases.
Operational principle
Usingmanually - operated swing - in devices, the LV HRC fuse - links are swung
in (making operation) and pulled out (breaking operation).
Product construction
Swing-in devicemade of halogen - free self – extinguishing plastics. Size 00
and 1 disconnectorswith seal. Split latch-on contact cover. Standard disconnectors are equipped with bolt connections, but can be retrofitted with direct
- connection terminals.
Size
LTL...
Size 00
Size 00
Size 1
Size 1
Size 2
Size 2
Size 3
Size 3
Size 4a
Size 4a
Size 4a
Size 4a
Size 4a
Size 4a
Size 4a
Size 4a
Rated operational current (A)
Switched poles
160
160
250
250
400
400
630
630
1250
1250
1600
1600
1250
1250
1600
1600
3-pole
3-pole
3-pole
3-pole
3-pole
3-pole
3-pole
3-pole
1-pole
3-pole
1-pole
1-pole
3-pole
1-pole
3-pole
3-pole
Electronic fuse Quasi-instantamonitor
neous circuit
Without
With
Without
With
Without
With
Without
With
Without
Without
Without
Without
Without
Without
Without
Without
Without
Without
Without
Without
Without
Without
Without
Without
Without
With
Without
With
Without
With
Without
With
Std.P
Type
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
00-3/9
00-3/9/ES00
1-3/9
1-3/9/ES00
2-3/9
2-3/9/ES00
3-3/9
3-3/9/ES00
4A-3X/1250/8
4A-3X3/1250/8/Q
4A-3X/1600/8
4A-3X/1600/8/Q
4A-3X3/1250/8
4A-3X/1250/8/Q
4A-3X3/1600/8
4A-3X3/1600/8/Q
Sizes 00 - 3 / 160A - 630A
4 - pole / surface mounting AC 690V
Product definition
LV HRC fuse switch - disconnectors in accordance with EN 60947-3 with swing-in device for accomodating 4 LV HRC fuse-links
in accordance with DIN 43620 or 3 LV HRC fuse - links and one disconnecting blade, sizes 00-3 /160 A – 630 A.
Applications
Switchgear for system, cable and motor protection in three - phase networks (TN-S networks, separate N and PE conductors).
Operational principle
Usingmanually-operated swing - in devices, the LV HRC fuse - links are swung in (making operation) and pulled out (breaking
operation). All 4 poles are switched simultaneously.
Product construction
Swing-in device made of halogen - free self - extinguishing plastics. Split latch - on contact cover. Standard disconnectors are
equipped with screw terminals, but can be retrofitted with direct-connection terminals.
Size
LTL...
Size 00
Size 1
Size 3
Rated operational current (A)
Std.P
Type
160
250
630
1
1
1
00-4/9
1-4/9
3-4/9
C 9
LV HRC fuse switch-disconnectors
Technical data for fuse switch-disconnectors
(in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)
Mechanical
Fuse links
characteristics
Electrical characteristics
Type
Rated operational voltage
Rated operational current
Conventional free air thermal current with fuses
Conventional free air thermal current with solid links
Rated frequency
Rated insulation voltage
Rated conditional short-circuit current
Rated short-time withstand current (1sec) Utilization category
Rated making capacity
Rated breaking capacity
Rated impulse withstand voltage
Operating cycles with current
Total power loss at Ith (without fuse)3)
Size to DIN 43 620
Max. rated current (gL/gG)
Max. permis. power loss per fuse-link3)
Operating cycles without current
Weight1)
Busbar distance (3-pole)
Flat terminal Bolt diameter
Cable lug (DIN 46 235)
Flat bar
Tightening torque
Ue
Ie
Ith
Ith
Ui
Icw
Uimp
Pv
IN
Pv
Ma
V
A
A
A
Hz
V
kAeff
kAeff
A
A
kV
W
A
W
kg
mm
mm2
mm
Nm
-
mm2
Ma
Nm
-
mm2
Ma
Nm
Clamping cross-section
-
mm2
Tightening torque
Clamping cross-section
Tightening torque
Ma
Ma
Nm
mm2
Nm
Clamping cross-section
-
mm2
Tightening torque
Front side Device fitted
Operational state
Front cover open
Ambient temperature2)
Rated operating mode
Actuation
Mounting position
Altitude
Pollution degree
Overvoltage category
Ma
Nm
Tu
-
°C
m
-
Clamping cross-section
Operating conditions
Type of
protection
Cable connection
Tightening torque
C 10
Clamping cross-section
Tightening torque
AC500
160
160
40-60
50
AC-22B
480
480
LTL00-1/9
LTL00-2/9
LTL00-3/9
LTL00-3/9/40 - 60
LTL00-4/9
LTL00aG-3/9
AC690
DC220
100
160
100
160
210(TM00)
40-60
AC750
50
25
AC-22B
DC-22B
300
640
300
640
DC440
100
100
AC500
250
250
-
40-60
25
50
DC-21B
150
150
AC-22B
750
750
LTL1-2/9
LTL1-3/9
LTL1-3/9/60
LTL1-3/9/100
LTL1-4/9
LTL1aG-3/9
AC690
DC220
200
250
200
250
325()TM1
40-60
AC750
50
25
AC-22B
DC-22B
600
1000
600
1000
DC440
200
200
25
DC-21B
300
300
8
200
6.9
300
2.7
160
100
200
6.2
300
2.7
200
12.9
200
8.3
160
100
250
200
0
200
8.6
200
5.5
1
12
1700
0,31/0,63/0,71/1,1
40/50/60
M8
1 x10- 95 (max. width 25mm)
20 x 10
Dec-15
1,5 - 70 Cu/ribbon 6 x 9 x 0,8
S 00
2.6
10 - 70 Al/Cu
P 00
2.6
35 x 95 Al/Cu
P00 - 95
2.6
2 x 1,5 - 25 Al/Cu
9.5
1,5 - 70 Cu/ribbon 6 x 9 x 0,8
F 50/
F 70
2.6
IP20
IP10
- 25 to + 55
Continuous operation
Dependent manual operation
Vertical, horizontal
Up to 2000
3
III
250
23
1400
1,1/2,15/3,5/4,55
60/100
M10
1 x 25 -150
30 x 10
30 - 35
25 - 150 Cu/ribbon 6 x 16 x 0,8
S1
9.5
70 - 150 Al/Cu
P1
4.5
2 x 70 - 95 Al/Cu
P12
4.5
200
LV HRC fuse switch-disconnectors
Technical data for fuse switch-disconnectors
(in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)
LTL2-3/9
LTL2aG-3/9
Cable connection
Mechanical
Fuse links
characteristics
Electrical characteristics
Type
Rated operational voltage
Rated operational current
Conventional free air thermal current with fuses
Conventional free air thermal current with solid links
Rated frequency
Rated insulation voltage
Rated conditional short-circuit current
Rated short-time withstand current (1sec)
Utilization category
Rated making capacity
Rated breaking capacity
Rated impulse withstand voltage
Operating cycles with current
Total power loss at Ith (without fuse)3)
Size to DIN 43 620
Max. rated current (gL/gG)
Max. permis. power loss per fuse-link3)
Operating cycles without current
Weight1)
Busbar distance (3-pole)
Bolt diameter
Cable lug (DIN 46 235)
Flat bar
Tightening torque
Ue
Ie
Ith
Ith
Ui
Icw
Uimp
Pv
IN
Pv
Ma
V
A
A
A
Hz
V
kAeff
kAeff
A
A
kV
W
A
W
kg
mm
mm2
mm
Nm
-
mm2
Ma
Nm
-
mm2
Ma
Nm
Clamping cross-section
-
mm2
Tightening torque
Front side Device fitted
Operational state
Front cover open
Ambient temperature2)
Rated operating mode
Actuation
Mounting position
Altitude
Pollution degree
Overvoltage category
Ma
Nm
Tu
-
°C
m
-
Clamping cross-section
Tightening torque
Clamping cross-section
Operating conditions
Type of
protection
Tightening torque
AC500
400
400
40-60
50
AC-22B
1200
1200
AC690
DC220
315
400
315
400
520(TM2)
40-60
AC750
50
25
AC-22B
DC-22B
945
1600
945
1600
DC440
315
315
AC500
630
630
-
40-60
25
50
DC-21B
475
475
AC-22B
1890
1890
LTL3-1/9
LTL3-2/9
LTL3-3/9
LTL3-4/9
LTL3-aG3/9
AC690
DC220
500
630
500
630
1000(TM3)
40-60
AC750
50
25
AC-22B
DC-22B
1500
2520
1500
2520
DC440
500
500
25
DC-21B
750
750
8
200
27
200
16.7
400
315
200
18
200
11.2
200
52
200
32.8
200
34.6
200
21.8
400
315
630
500
630 48
800
1,7/3,92/5,35/7,1
60/100
M10
1 x 25 - 300
40 x 10
30 - 35
Band 11 x21 x 1
S3
23
120 - 240 Al/Cu
P3
11
2 x 120 - 240 Al/Cu
P 32
11
500
2
3
34
800
3.1
60/100
M 10
1 x 25 - 240
30 x 10
30 - 35
25 - 240 Cu/r. 10 x 16 x 0,8
S2
23
120 - 240 Al/Cu
P2
11
2 x 120 - 150 Al/Cu
P 22
11
IP20
IP10
- 25 to + 55
Continuous operation
Dependent manual operation
Vertical, horizontal
Up to 2000
3
III
C 11
LV HRC fuse switch-disconnectors
Technical data for fuse switch-disconnectors
(in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)
LTL4a-1/1250
LTL4a-3/1250
Operating conditions
Type of
protec.
Cable connection
Mech.
Fuse links
charact.
Electrical characteristics
Type
C 12
Rated operational voltage
Rated operational current
Conventional free air thermal current with fuses
Conventional free air thermal current with solid links
Rated frequency
Rated insulation voltage
Rated conditional short-circuit current
Rated short-time withstand current (1sec)
Utilization category
Rated making capacity
Rated breaking capacity
Rated impulse withstand voltage
Operating cycles with current
Total power loss at Ith (without fuse)3)
Size to DIN 43 620
Max. rated current (gL/gG)
Max. permis. power loss per fuse-link3)
Operating cycles without current
Weight1)
Bolt diameter
Cable lug (DIN 46 235)
Flat bar
Tightening torque
Ue
Ie
Ith
Ith
Ui
Icw
Uimp
Pv
IN
Pv
–
Ma
V
A
A
A
Hz
V
kAeff
kAeff
A
A
kV
W
A
W
kg
mm2
mm
Nm
Clamping cross-section
-
mm
Tightening torque
Clamping cross-section
Tightening torque
Clamping cross-section
Tightening torque
Operational state
Front cover open
Ambient temperature2)
Rated operating mode
Actuation
Mounting position
Altitude
Pollution degree
Overvoltage category
Ma
Ma
Ma
Tu
-
Nm
mm2
Nm
mm2
Nm
°C
m
-
2
AC500
1250
1250
1250
LTL4a-1/1600
LTL4a-1/1600
AC690
1000
1000
1600
AC500
1600
1600
AC690
1000
1000
80
80
AC-22B
2400
2400
AC-21B
1500
1500
52
33.3
1600
164 1000
164
40-60
AC800
80
80
-
AC-22B
3750
3750
AC-21B
1500
1500
8
100
32
20.5
4a
1250
110
1000
110
500 5,3/15,7
1x M16
400
2 x M12
max. 80 x 30
50-60
KV2HG/2/300/AF40
- 50
35 - 40
KV2HG/2/300/AF402 x (95-300)
50
2 x (95-300)
40
K3G/3/A40-50
3 x (95-150)
K3G/3/A40-50
3x (95-150)
K3G/4/A40-50
50
IP20
IP10
- 25 to +55
Continuous operation
Dependent manual operation
Vertical
Up to 2000
3
III
4x (95-150)
50
K3G/4/A40-50
4 x (95-150)
LV HRC fuse switch-disconnectors
Technical data for switch - disconnectors
Operating conditions
Type of
protec.
Cable
connection
Mech.
Fuse links
charact.
Electrical
characteristics
Type
Rated operational voltage
Rated operational current
Conventional free air thermal current with fuses
Conventional free air thermal current with solid links
Rated frequency
Size to DIN 43 620
Max. rated current (gL/gG)
Max. permis. power loss per fuse-link
Ue
Ie
Ith
Ith
IN
Pv
V
A
A
A
Hz
A
W
LTL1-3/1200
AC 1200
250 200 325 40-60
1
200 25
LTL2-3/1200
AC 1200
400 315 520
40-60
2
315
35
LTL3-3/1200
AC 1200
630
630
1000
40-60
3
630
70
Weight1)
–
kg
6.1
6.5
7.5
Flat terminal Bolt diameter
Cable lug (DIN 46 235
Flat bar
Tightening torque
Front side - operational state- Device fitted
Front cover open
Ambient temperature2)
Rated operating mode
Actuation
Mounting position
Altitude
Pollution degree
Overvoltage category
Ma
-
mm2
mm
Nm
°C
m
-
M9
25 -150
30x10
30-35
M10
25 - 240
30x10
30-35
IP 20
IP 10
-25 to +55
Cont. operation
Vert./ horizontal
Up to 2000
3
III
M16
25 - 300
40x10
30-35
Tu
-
Without packaging
) 35°C normal temperature, at 55°C with reduced operating current
1)
2
C 13
LV HRC fuse switch-disconnectors
Technical data for fuse switch - disconnectors
(in accordance with IEC/EN 60947-3 and VDE 0660 Part 107)
Operating conditions
Type of
protec.
Cable connection
Mechanical
characteristics
Fuse links
Electrical characteristics
Type
Rated operational voltage
Rated operational current
Conventional free air thermal current with fuses
Conventional free air thermal current with solid links
Rated frequency
Rated insulation voltage
Rated conditional short-circuit current
Rated short-time withstand current (1sec)
Utilization category
Rated making capacity
Rated breaking capacity
Rated impulse withstand voltage
Operating cycles with current
Total power loss at Ith (without fuse)3)
Size to DIN 43 620
Max. rated current (gL/gG)
Max. permis. power loss per fuse-link3)
Operating cycles without current
Weight1)
Busbar distance (3-pole)
Busbar thickness
Busbar width
Bolt diameter
Cable lug (DIN 46 235)
Flat terminal
Flat bar
Tightening torque
Clamping cross-section
Terminal
Tightening torque
Clamping cross-section
Terminal
Tightening torque
Terminal Clamping cross-section
Tightening torque
Terminal Clamping cross-section
Tightening torque
Operational state
Front side Device fitted
Front cover open
Ambient temperature2)
Rated operating mode
Actuation
Mounting position
Altitude
Pollution degree
Overvoltage category
Ue
Ie
Ith
Ith
Ui
Icw
Uimp
Pv
IN
Pv
Ma
Ma
Ma
Ma
Ma
Tu
-
V
A
A
A
Hz
V
kAeff
kAeff
A
A
kV
W
A
W
kg
mm
mm
mm
mm2
mm
Nm
mm2
Nm
mm2
Nm
mm2
Nm
mm2
Nm
°C
m
-
Without packaging
35°C normal temperature, at 55°C with reduced operating current
3)
Data for 3-pole version
1)
2)
C 14
AC400
125
125
160(TM00)
40-60
AC500
50
AC22B
300
300
300
18
0
125
F50
F50
LTL000-3/9/60...
AC500
DC220
100
100
100
100
160(TM00)
160(TM00)
40-60
AC500
AC500
50
25
AC22B
DC22B
300
400
300
400
8
300
300
11.5
11.5
0
0
100
100
12
1700
0.57
60
5 a 10
20 a 30
1,5 -50Cu/páska 6 x 9 x 0,8
2.6
IP 20
IP 10
- 25 to +55
Continuous operation
Dependent manual operation
Vertical, horizontal
Up to 2000
3
III
Accessories
Product definition
CLAMP-TYPE TERMINAL
Direct - connection terminal – clamp - type terminal for Cu conductor and ribbon conductor connection.
V-TERMINAL CLAMP
Direct - connection terminal – V - terminal clamp for Cu conductor and Al conductor connection.
OUTPUT INDICATOR
Output indicator for indication of connected or disconnected state.
MECHANICAL FUSE MONITOR
In conjunction with LV HRC fuse – links with striker, the mechanical fuse monitor indicates fuse failure. Thestriker
actuates a microswitch when the fuse-link is disconnected. The microswitch then passes the failure signal to a control
centre.
OVERREACHING PROTECTION
The upper and lower latch - on overreaching protection covers the connection contacts or cable lugs or bare protruding conductors. The live parts are covered probe-safe.
HANDLE PROTECTION FOR BLADES
The overreaching protection for the contact blades of the LV HRC fuse - links ismovably fitted in the front plate. When
the front plate is swung out, the overreaching protection is swung out from the front plate on the face, thus covering
the contact blades of the fuse – links probe - safe.
SHROUD
The latch-on covering panels cover the switchboard apertures and ensure IP30 protection in the connected state.
DIN RAIL FIXING PARTS
The retrofittable DIN rail fixing parts consist of two hang - up hooks and a slide. They allow size 00 LV HRC fuse switch
– disconnectors to be fixed on two standard rails in accordance with EN 50022 with 100mm to 150mm distance
between rail centres.
PROTECTIVE COVER INTERLOCK
The protective cover interlock can be latched into the protective covers. It is interlocked with the basic frame by a 90°
turn of a screwdriver.
ELECTRONIC FUSE MONITORING
The electronic fuse monitoring feature ES00 can be used in the voltage range AC 400V to AC 690V. It is
self-powered and the infeed can be at either end.
Applications
Direct-connection terminals replace cable lugs. They are suitable for Cu conductors, ribbon conductors and Cu busbars.
Mechanical fuse monitors are used for remote indication of fuse failure. The overreaching protection prevents accidental contact with live parts. The overreaching protection for the contact blades of the LV HRC fuse-links is used for supply
frombelow. It prevents accidental contact with the live contact blades of the fuse - links when the front plate is not entirely
closed. Covering panels are used for panel mounting. They ensure complete covering of the panel cutouts and thus IP30
protection. The DIN rail fixing parts for size 00 LV HRC fuse switch - disconnectors are used in control cabinets in combination with miniature circuit - breakers and in distribution systems in which only standard rails in accordance with EN 50022
are integrated. Protective cover interlocks ensure that the covers can only be removed by a tool, thus complying with BGV
A2 requirements.
C 15
Accessories
C 16
Flat termination
Size 00
Size 1
Size 2
Size 3
Std.P
3
3
3
3
Type
F-LTL00-M8
F-LTL1-M10
F-LTL2-M10
F-LTL3-M10
Clamp-type terminal
Size 00/1,5-70 mm² Cu (also for GU00)
Size 1
Size 2
Size 3
Std.P
3
3
3
3
Type
S00-Z
S1
S2
S3
V-terminal clamp
Size 00/10-70 mm² Al/Cu
Size 1
Size 2
Size 3
Std.P
3
3
3
3
Type
P0070-Z
P1
P2
P3
Handle protection 3-pole, surface mounting
Size 00, top or bottom
Size 1, top
Size 2, top
Size 3, top (also for busbar mounting)
Size 1, bottom
Size 2, bottom
Size 3, bottom, (also for busbar mounting)
Std.P
1
1
1
1
1
1
1
Type
LTL00-3
GO-LTL1-3
GO-LTL2-3
GO-LTL3-3
GU-LTL1-3
GU-LTL2-3
GU-LTL3-3
Handle protection 3-pole, busbar mounting
Size 00, top, system-measurement 195mm
Size 00, top, extended, system-measurement 230mm
Size 2, top
Size 1, top, extended
Size 00, bottom, system-measurement 195mm
Size 2, bottom
Size 00, bottom, extended, system-measurement 230mm
Size 1, bottom, extended
Size 2, extension top/bottom
Std.P
Type
GO-LTL00-3/195
GOV-LTL00-3/230
GOV-LTL2-3
GOV-LTL1-3
GU-LTL00-3/195
GUV-LTL2-3
GUV-LTL00-3/230
GUV-LTL1-3
GV-LTL2-3
Handle protection 1-pole, surface- and busbar mounting
Size 00, top or bottom
Size 1, top or bottom
Size 3, top or bottom
Std.P
1
1
1
1
1
Type
GOU-LTL00-1
GOU-LTL1-1
GOU-LTL3-1
Dimensional drawings
LTL00-1/9
LTL1-1/9, LTL3-1/9
Type
LTL1-1/9
LTL3-1/9
A
69
91
B
230
270
C
317
430
D
68
96
E
119
147
F
16,5
9
G
115
135
H
177
220,5
I
25
30,5
C 17
Dimensional drawings
LTL4A-1x/1250(1600)/8
1250 A
1600 A
LTL00-2/9
C 18
B
270
311
C
315
339
Dimensional drawings
LTL1-2/9, LTL3-2/9
Type
LTL1-2/9
LTL3-2/9
A
138
182
B
230
270
C
317
430
D
68
96
E
123,5
151,5
F
23
15,5
G
115
135
H
177
220,5
I
25
30,5
LTL...-3/9, LTL...-3/9/ES00
Type
LTL00-3/9
LTL1-3/9
LTL2-3/9
LTL3-3/9
A
105,5
184
210
254
B
149
230
256
270
C
220
317
397
430
D
45
68
81
96
E
86
119
133
147
F
20,5
16,5
16,5
9
G
74,5
115
128
135
H
120
177
205
220,5
I
17
25
25
30,5
K
33
58
66
82
L
116
149
163
177
L1
126
159
173
187
C 19
Dimensional drawings
LTL4A-3x(3)/.../8/(Q)
1250 A
1600 A
LTL00-4/9
C 20
B
270
311
C
315
339
Dimensional drawings
LTL1-4/9, LTL3-4/9
Type
LTL1-4/9
LTL3-4/9
S00-Z
A
253
345
B
230
270
C
317
430
D
68
96
E
123,5
151,5
F
23
15,5
G
115
135
H
177
220,5
I
25
30,5
K
58
82
P0070-Z
C 21
Dimensional drawings
S00, S1, S2, S3
Type
S00
S1
S2
S3
A
25
37
42
50
B
15
20
22
25
C
15
25
28
30
D
M5
M6
M8
M8
E
Max. 15
Max. 28
Max. 30
Max. 30
F
5,5
6,5
8,5
8,5
P1, P2, P3, P12, P22, P32
C 22
Type
P0070
P0095
P1
P12
P2
P22
P3
P32
A
25
29
37
37
42
42
50
50
B
15
15
20
20
22
22
25
25
C
15
18
25
25
28
28
30
30
D
M5
M5
M6
M6
M8
M8
M8
M8
E
Max. 25
Max. 28
Max. 30
Max. 42
Max. 40
Max. 55
Max. 44
Max. 66
F
5,5
5, 5
6,5
6,5
8,5
8,5
8,5
8,5
Download