LV HRC fuse switch-disconnectors The “9” series LV HRC fuse switch-disconnectors of the DIN sizes 00 - 4a are suitable for surface mounting on mounting plates and for direct mounting on busbars. The different sizes are available as 1-pole, 2-pole, 3-pole and 4 -pole versions. • Surface mounting • Busbar mounting • 1 - pole, 2 - pole, 3 - pole and 4 - pole • Retrofittable cable connections • Fuse monitor • Position indication • DIN rail fixing parts LV HRC fuse switch-disconnectors, size 1 Example: Surface mounting with accessories, 1-pole Basic construction 1 Base of disconnector U-LTL1-1 2 Protective cover, top BO-LTL1-1 3 Protective cover, bottom BU-LTL1-1 4 Swing-in device D-LTL1-1/9 Connection accessories 5ab) Screw terminal F-LTL1-M10 6 Clamp-type terminal S1 7 V terminal clamp P1 8 Double V-terminal clamp P12 Covering accessories (Protection against contact) 9 Handle protection, top and bottom GOU-LTL1-1 Accessories for mechanical fuse monitoring Position indicator, “ON” 10ab) Mech. fuse monitor K-LTL1-1/H 11ab) Position indicator, “ON” (electrical interlocking) eV-LTL123-1 LV HRC fuse switch-disconnectors with quasi-instantaneous circuit 12 Quasi-instantaneous circuit LTL1-1/9/Q C 6 LV HRC fuse switch-disconnectors LV HRC fuse switch-disconnectors, size 00 Example: Surface mounting with accessories, 3 - pole Basic construction 1 Base of disconnector U - LTL00 - 3 2 Protective cover, top BO - LTL00 - 3 3 Protective cover, bottom BU - LTL00 - 3 4 Swing-in device D - LTL00 - 3/9 Connection accessories 5 Screw terminal F - M8x16 6 Clamp - type terminal S00 7 V - terminal clamp P0070 8 Box terminal F50 Covering accessories (Protection against contact) 9 Handle protection, top/bottom GOU - LTL00 - 3 Fixing accessories 10 DIN rail fixing parts Z - LTL00 - 3 Accessories for interlocking, mechanical fuse monitoring and “ON” position indication 11 Protective cover interlock VHG - LTL00123 - 3 12 Mech. fuse monitor K - LTL00 - 3/H 13 Position indicator, “ON” (electrical interlocking) eV - LTL00 - 3 Accessories: Swing - in device with electronic fuse monitor 14 Swing-in device ES00 – D - LTL00 C 7 LV HRC fuse switch-disconnectors Sizes 00 - 4a / 160A - 1600A 1 - pole / surface mounting AC 690V Product definition LV HRC fuse switch-disconnectors in accordance with EN 60947-3 with swing-in device for accomodating one LV HRC fuse - link in accordance with DIN 43620, sizes 00/160 A to 4a/1600 A. Applications Switchgear for system, cable and motor protection in alternating and direct current systems. The disconnectors are frequently used in battery - powered direct current systems such as UPS systems. Operational principle Using amanually - operated swing - in device, the LV HRC fuse - link is swung in (making operation) and pulled out (breaking operation). Product construction Swing - in devicemade ofhalogen - free self – extinguishing plastics. Split latch - on contact cover. Standard disconnectors are equipped with screw terminals, but can be retrofitted with direct - connection terminals. Size LTL... Size 00 Size 1 Size 3 Size 4a Size 4a Rated operational current (A) Std.P Type 160 250 630 1250 1600 1 1 1 1 1 00-1/9 1-1/9 3-1/9 4A-1X/1250/8 4A-1X/1600/8 Sizes 00 - 3 / 160A - 630A 2 - pole / surface mounting AC 690V Product definition LV HRC fuse switch-disconnectors in accordance with EN 60947-3 with swing - in device for accomodating 2 LV HRC fuse-links in accordance with DIN 43620, sizes 00/160A to 3/630A. Applications Switchgear for system, cable and motor protection in direct current systems. The disconnectors are frequently used in battery - powered direct current systems such as UPS systems. Operational principle Usingmanually - operated swing - in devices, the LV HRC fuse - links are swung in (making operation) and pulled out (breaking operation). Product construction Swing-in devicemade of halogen-free self-extinguishing plastics. Split latch-on contact cover. Standard disconnectors are equipped with screw terminals, but can be retrofitted with directconnection terminals. Size LTL... Size 00 Size 1 Size 3 C 8 Rated operational current (A) Std.P Type 160 250 630 1 1 1 00-2/9 1-2/9 3-2/9 LV HRC fuse switch-disconnectors Sizes 00 - 4a / 160A - 1600A 3 - pole / surface mounting AC 690V Product definition LV HRC fuse switch - disconnectors in accordance with EN 60947-3 with swing-in device for accomodating 3 LV HRC fuse - links in accordance with DIN 43620, sizes 00 - 4a / 160 A - 1600 A. Applications Switchgear for system, cable and motor protection in three - phase systems up to 690V AC. The disconnectors are fitted in switchgear cabinets or insulating cases. Operational principle Usingmanually - operated swing - in devices, the LV HRC fuse - links are swung in (making operation) and pulled out (breaking operation). Product construction Swing-in devicemade of halogen - free self – extinguishing plastics. Size 00 and 1 disconnectorswith seal. Split latch-on contact cover. Standard disconnectors are equipped with bolt connections, but can be retrofitted with direct - connection terminals. Size LTL... Size 00 Size 00 Size 1 Size 1 Size 2 Size 2 Size 3 Size 3 Size 4a Size 4a Size 4a Size 4a Size 4a Size 4a Size 4a Size 4a Rated operational current (A) Switched poles 160 160 250 250 400 400 630 630 1250 1250 1600 1600 1250 1250 1600 1600 3-pole 3-pole 3-pole 3-pole 3-pole 3-pole 3-pole 3-pole 1-pole 3-pole 1-pole 1-pole 3-pole 1-pole 3-pole 3-pole Electronic fuse Quasi-instantamonitor neous circuit Without With Without With Without With Without With Without Without Without Without Without Without Without Without Without Without Without Without Without Without Without Without Without With Without With Without With Without With Std.P Type 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 00-3/9 00-3/9/ES00 1-3/9 1-3/9/ES00 2-3/9 2-3/9/ES00 3-3/9 3-3/9/ES00 4A-3X/1250/8 4A-3X3/1250/8/Q 4A-3X/1600/8 4A-3X/1600/8/Q 4A-3X3/1250/8 4A-3X/1250/8/Q 4A-3X3/1600/8 4A-3X3/1600/8/Q Sizes 00 - 3 / 160A - 630A 4 - pole / surface mounting AC 690V Product definition LV HRC fuse switch - disconnectors in accordance with EN 60947-3 with swing-in device for accomodating 4 LV HRC fuse-links in accordance with DIN 43620 or 3 LV HRC fuse - links and one disconnecting blade, sizes 00-3 /160 A – 630 A. Applications Switchgear for system, cable and motor protection in three - phase networks (TN-S networks, separate N and PE conductors). Operational principle Usingmanually-operated swing - in devices, the LV HRC fuse - links are swung in (making operation) and pulled out (breaking operation). All 4 poles are switched simultaneously. Product construction Swing-in device made of halogen - free self - extinguishing plastics. Split latch - on contact cover. Standard disconnectors are equipped with screw terminals, but can be retrofitted with direct-connection terminals. Size LTL... Size 00 Size 1 Size 3 Rated operational current (A) Std.P Type 160 250 630 1 1 1 00-4/9 1-4/9 3-4/9 C 9 LV HRC fuse switch-disconnectors Technical data for fuse switch-disconnectors (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107) Mechanical Fuse links characteristics Electrical characteristics Type Rated operational voltage Rated operational current Conventional free air thermal current with fuses Conventional free air thermal current with solid links Rated frequency Rated insulation voltage Rated conditional short-circuit current Rated short-time withstand current (1sec) Utilization category Rated making capacity Rated breaking capacity Rated impulse withstand voltage Operating cycles with current Total power loss at Ith (without fuse)3) Size to DIN 43 620 Max. rated current (gL/gG) Max. permis. power loss per fuse-link3) Operating cycles without current Weight1) Busbar distance (3-pole) Flat terminal Bolt diameter Cable lug (DIN 46 235) Flat bar Tightening torque Ue Ie Ith Ith Ui Icw Uimp Pv IN Pv Ma V A A A Hz V kAeff kAeff A A kV W A W kg mm mm2 mm Nm - mm2 Ma Nm - mm2 Ma Nm Clamping cross-section - mm2 Tightening torque Clamping cross-section Tightening torque Ma Ma Nm mm2 Nm Clamping cross-section - mm2 Tightening torque Front side Device fitted Operational state Front cover open Ambient temperature2) Rated operating mode Actuation Mounting position Altitude Pollution degree Overvoltage category Ma Nm Tu - °C m - Clamping cross-section Operating conditions Type of protection Cable connection Tightening torque C 10 Clamping cross-section Tightening torque AC500 160 160 40-60 50 AC-22B 480 480 LTL00-1/9 LTL00-2/9 LTL00-3/9 LTL00-3/9/40 - 60 LTL00-4/9 LTL00aG-3/9 AC690 DC220 100 160 100 160 210(TM00) 40-60 AC750 50 25 AC-22B DC-22B 300 640 300 640 DC440 100 100 AC500 250 250 - 40-60 25 50 DC-21B 150 150 AC-22B 750 750 LTL1-2/9 LTL1-3/9 LTL1-3/9/60 LTL1-3/9/100 LTL1-4/9 LTL1aG-3/9 AC690 DC220 200 250 200 250 325()TM1 40-60 AC750 50 25 AC-22B DC-22B 600 1000 600 1000 DC440 200 200 25 DC-21B 300 300 8 200 6.9 300 2.7 160 100 200 6.2 300 2.7 200 12.9 200 8.3 160 100 250 200 0 200 8.6 200 5.5 1 12 1700 0,31/0,63/0,71/1,1 40/50/60 M8 1 x10- 95 (max. width 25mm) 20 x 10 Dec-15 1,5 - 70 Cu/ribbon 6 x 9 x 0,8 S 00 2.6 10 - 70 Al/Cu P 00 2.6 35 x 95 Al/Cu P00 - 95 2.6 2 x 1,5 - 25 Al/Cu 9.5 1,5 - 70 Cu/ribbon 6 x 9 x 0,8 F 50/ F 70 2.6 IP20 IP10 - 25 to + 55 Continuous operation Dependent manual operation Vertical, horizontal Up to 2000 3 III 250 23 1400 1,1/2,15/3,5/4,55 60/100 M10 1 x 25 -150 30 x 10 30 - 35 25 - 150 Cu/ribbon 6 x 16 x 0,8 S1 9.5 70 - 150 Al/Cu P1 4.5 2 x 70 - 95 Al/Cu P12 4.5 200 LV HRC fuse switch-disconnectors Technical data for fuse switch-disconnectors (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107) LTL2-3/9 LTL2aG-3/9 Cable connection Mechanical Fuse links characteristics Electrical characteristics Type Rated operational voltage Rated operational current Conventional free air thermal current with fuses Conventional free air thermal current with solid links Rated frequency Rated insulation voltage Rated conditional short-circuit current Rated short-time withstand current (1sec) Utilization category Rated making capacity Rated breaking capacity Rated impulse withstand voltage Operating cycles with current Total power loss at Ith (without fuse)3) Size to DIN 43 620 Max. rated current (gL/gG) Max. permis. power loss per fuse-link3) Operating cycles without current Weight1) Busbar distance (3-pole) Bolt diameter Cable lug (DIN 46 235) Flat bar Tightening torque Ue Ie Ith Ith Ui Icw Uimp Pv IN Pv Ma V A A A Hz V kAeff kAeff A A kV W A W kg mm mm2 mm Nm - mm2 Ma Nm - mm2 Ma Nm Clamping cross-section - mm2 Tightening torque Front side Device fitted Operational state Front cover open Ambient temperature2) Rated operating mode Actuation Mounting position Altitude Pollution degree Overvoltage category Ma Nm Tu - °C m - Clamping cross-section Tightening torque Clamping cross-section Operating conditions Type of protection Tightening torque AC500 400 400 40-60 50 AC-22B 1200 1200 AC690 DC220 315 400 315 400 520(TM2) 40-60 AC750 50 25 AC-22B DC-22B 945 1600 945 1600 DC440 315 315 AC500 630 630 - 40-60 25 50 DC-21B 475 475 AC-22B 1890 1890 LTL3-1/9 LTL3-2/9 LTL3-3/9 LTL3-4/9 LTL3-aG3/9 AC690 DC220 500 630 500 630 1000(TM3) 40-60 AC750 50 25 AC-22B DC-22B 1500 2520 1500 2520 DC440 500 500 25 DC-21B 750 750 8 200 27 200 16.7 400 315 200 18 200 11.2 200 52 200 32.8 200 34.6 200 21.8 400 315 630 500 630 48 800 1,7/3,92/5,35/7,1 60/100 M10 1 x 25 - 300 40 x 10 30 - 35 Band 11 x21 x 1 S3 23 120 - 240 Al/Cu P3 11 2 x 120 - 240 Al/Cu P 32 11 500 2 3 34 800 3.1 60/100 M 10 1 x 25 - 240 30 x 10 30 - 35 25 - 240 Cu/r. 10 x 16 x 0,8 S2 23 120 - 240 Al/Cu P2 11 2 x 120 - 150 Al/Cu P 22 11 IP20 IP10 - 25 to + 55 Continuous operation Dependent manual operation Vertical, horizontal Up to 2000 3 III C 11 LV HRC fuse switch-disconnectors Technical data for fuse switch-disconnectors (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107) LTL4a-1/1250 LTL4a-3/1250 Operating conditions Type of protec. Cable connection Mech. Fuse links charact. Electrical characteristics Type C 12 Rated operational voltage Rated operational current Conventional free air thermal current with fuses Conventional free air thermal current with solid links Rated frequency Rated insulation voltage Rated conditional short-circuit current Rated short-time withstand current (1sec) Utilization category Rated making capacity Rated breaking capacity Rated impulse withstand voltage Operating cycles with current Total power loss at Ith (without fuse)3) Size to DIN 43 620 Max. rated current (gL/gG) Max. permis. power loss per fuse-link3) Operating cycles without current Weight1) Bolt diameter Cable lug (DIN 46 235) Flat bar Tightening torque Ue Ie Ith Ith Ui Icw Uimp Pv IN Pv – Ma V A A A Hz V kAeff kAeff A A kV W A W kg mm2 mm Nm Clamping cross-section - mm Tightening torque Clamping cross-section Tightening torque Clamping cross-section Tightening torque Operational state Front cover open Ambient temperature2) Rated operating mode Actuation Mounting position Altitude Pollution degree Overvoltage category Ma Ma Ma Tu - Nm mm2 Nm mm2 Nm °C m - 2 AC500 1250 1250 1250 LTL4a-1/1600 LTL4a-1/1600 AC690 1000 1000 1600 AC500 1600 1600 AC690 1000 1000 80 80 AC-22B 2400 2400 AC-21B 1500 1500 52 33.3 1600 164 1000 164 40-60 AC800 80 80 - AC-22B 3750 3750 AC-21B 1500 1500 8 100 32 20.5 4a 1250 110 1000 110 500 5,3/15,7 1x M16 400 2 x M12 max. 80 x 30 50-60 KV2HG/2/300/AF40 - 50 35 - 40 KV2HG/2/300/AF402 x (95-300) 50 2 x (95-300) 40 K3G/3/A40-50 3 x (95-150) K3G/3/A40-50 3x (95-150) K3G/4/A40-50 50 IP20 IP10 - 25 to +55 Continuous operation Dependent manual operation Vertical Up to 2000 3 III 4x (95-150) 50 K3G/4/A40-50 4 x (95-150) LV HRC fuse switch-disconnectors Technical data for switch - disconnectors Operating conditions Type of protec. Cable connection Mech. Fuse links charact. Electrical characteristics Type Rated operational voltage Rated operational current Conventional free air thermal current with fuses Conventional free air thermal current with solid links Rated frequency Size to DIN 43 620 Max. rated current (gL/gG) Max. permis. power loss per fuse-link Ue Ie Ith Ith IN Pv V A A A Hz A W LTL1-3/1200 AC 1200 250 200 325 40-60 1 200 25 LTL2-3/1200 AC 1200 400 315 520 40-60 2 315 35 LTL3-3/1200 AC 1200 630 630 1000 40-60 3 630 70 Weight1) – kg 6.1 6.5 7.5 Flat terminal Bolt diameter Cable lug (DIN 46 235 Flat bar Tightening torque Front side - operational state- Device fitted Front cover open Ambient temperature2) Rated operating mode Actuation Mounting position Altitude Pollution degree Overvoltage category Ma - mm2 mm Nm °C m - M9 25 -150 30x10 30-35 M10 25 - 240 30x10 30-35 IP 20 IP 10 -25 to +55 Cont. operation Vert./ horizontal Up to 2000 3 III M16 25 - 300 40x10 30-35 Tu - Without packaging ) 35°C normal temperature, at 55°C with reduced operating current 1) 2 C 13 LV HRC fuse switch-disconnectors Technical data for fuse switch - disconnectors (in accordance with IEC/EN 60947-3 and VDE 0660 Part 107) Operating conditions Type of protec. Cable connection Mechanical characteristics Fuse links Electrical characteristics Type Rated operational voltage Rated operational current Conventional free air thermal current with fuses Conventional free air thermal current with solid links Rated frequency Rated insulation voltage Rated conditional short-circuit current Rated short-time withstand current (1sec) Utilization category Rated making capacity Rated breaking capacity Rated impulse withstand voltage Operating cycles with current Total power loss at Ith (without fuse)3) Size to DIN 43 620 Max. rated current (gL/gG) Max. permis. power loss per fuse-link3) Operating cycles without current Weight1) Busbar distance (3-pole) Busbar thickness Busbar width Bolt diameter Cable lug (DIN 46 235) Flat terminal Flat bar Tightening torque Clamping cross-section Terminal Tightening torque Clamping cross-section Terminal Tightening torque Terminal Clamping cross-section Tightening torque Terminal Clamping cross-section Tightening torque Operational state Front side Device fitted Front cover open Ambient temperature2) Rated operating mode Actuation Mounting position Altitude Pollution degree Overvoltage category Ue Ie Ith Ith Ui Icw Uimp Pv IN Pv Ma Ma Ma Ma Ma Tu - V A A A Hz V kAeff kAeff A A kV W A W kg mm mm mm mm2 mm Nm mm2 Nm mm2 Nm mm2 Nm mm2 Nm °C m - Without packaging 35°C normal temperature, at 55°C with reduced operating current 3) Data for 3-pole version 1) 2) C 14 AC400 125 125 160(TM00) 40-60 AC500 50 AC22B 300 300 300 18 0 125 F50 F50 LTL000-3/9/60... AC500 DC220 100 100 100 100 160(TM00) 160(TM00) 40-60 AC500 AC500 50 25 AC22B DC22B 300 400 300 400 8 300 300 11.5 11.5 0 0 100 100 12 1700 0.57 60 5 a 10 20 a 30 1,5 -50Cu/páska 6 x 9 x 0,8 2.6 IP 20 IP 10 - 25 to +55 Continuous operation Dependent manual operation Vertical, horizontal Up to 2000 3 III Accessories Product definition CLAMP-TYPE TERMINAL Direct - connection terminal – clamp - type terminal for Cu conductor and ribbon conductor connection. V-TERMINAL CLAMP Direct - connection terminal – V - terminal clamp for Cu conductor and Al conductor connection. OUTPUT INDICATOR Output indicator for indication of connected or disconnected state. MECHANICAL FUSE MONITOR In conjunction with LV HRC fuse – links with striker, the mechanical fuse monitor indicates fuse failure. Thestriker actuates a microswitch when the fuse-link is disconnected. The microswitch then passes the failure signal to a control centre. OVERREACHING PROTECTION The upper and lower latch - on overreaching protection covers the connection contacts or cable lugs or bare protruding conductors. The live parts are covered probe-safe. HANDLE PROTECTION FOR BLADES The overreaching protection for the contact blades of the LV HRC fuse - links ismovably fitted in the front plate. When the front plate is swung out, the overreaching protection is swung out from the front plate on the face, thus covering the contact blades of the fuse – links probe - safe. SHROUD The latch-on covering panels cover the switchboard apertures and ensure IP30 protection in the connected state. DIN RAIL FIXING PARTS The retrofittable DIN rail fixing parts consist of two hang - up hooks and a slide. They allow size 00 LV HRC fuse switch – disconnectors to be fixed on two standard rails in accordance with EN 50022 with 100mm to 150mm distance between rail centres. PROTECTIVE COVER INTERLOCK The protective cover interlock can be latched into the protective covers. It is interlocked with the basic frame by a 90° turn of a screwdriver. ELECTRONIC FUSE MONITORING The electronic fuse monitoring feature ES00 can be used in the voltage range AC 400V to AC 690V. It is self-powered and the infeed can be at either end. Applications Direct-connection terminals replace cable lugs. They are suitable for Cu conductors, ribbon conductors and Cu busbars. Mechanical fuse monitors are used for remote indication of fuse failure. The overreaching protection prevents accidental contact with live parts. The overreaching protection for the contact blades of the LV HRC fuse-links is used for supply frombelow. It prevents accidental contact with the live contact blades of the fuse - links when the front plate is not entirely closed. Covering panels are used for panel mounting. They ensure complete covering of the panel cutouts and thus IP30 protection. The DIN rail fixing parts for size 00 LV HRC fuse switch - disconnectors are used in control cabinets in combination with miniature circuit - breakers and in distribution systems in which only standard rails in accordance with EN 50022 are integrated. Protective cover interlocks ensure that the covers can only be removed by a tool, thus complying with BGV A2 requirements. C 15 Accessories C 16 Flat termination Size 00 Size 1 Size 2 Size 3 Std.P 3 3 3 3 Type F-LTL00-M8 F-LTL1-M10 F-LTL2-M10 F-LTL3-M10 Clamp-type terminal Size 00/1,5-70 mm² Cu (also for GU00) Size 1 Size 2 Size 3 Std.P 3 3 3 3 Type S00-Z S1 S2 S3 V-terminal clamp Size 00/10-70 mm² Al/Cu Size 1 Size 2 Size 3 Std.P 3 3 3 3 Type P0070-Z P1 P2 P3 Handle protection 3-pole, surface mounting Size 00, top or bottom Size 1, top Size 2, top Size 3, top (also for busbar mounting) Size 1, bottom Size 2, bottom Size 3, bottom, (also for busbar mounting) Std.P 1 1 1 1 1 1 1 Type LTL00-3 GO-LTL1-3 GO-LTL2-3 GO-LTL3-3 GU-LTL1-3 GU-LTL2-3 GU-LTL3-3 Handle protection 3-pole, busbar mounting Size 00, top, system-measurement 195mm Size 00, top, extended, system-measurement 230mm Size 2, top Size 1, top, extended Size 00, bottom, system-measurement 195mm Size 2, bottom Size 00, bottom, extended, system-measurement 230mm Size 1, bottom, extended Size 2, extension top/bottom Std.P Type GO-LTL00-3/195 GOV-LTL00-3/230 GOV-LTL2-3 GOV-LTL1-3 GU-LTL00-3/195 GUV-LTL2-3 GUV-LTL00-3/230 GUV-LTL1-3 GV-LTL2-3 Handle protection 1-pole, surface- and busbar mounting Size 00, top or bottom Size 1, top or bottom Size 3, top or bottom Std.P 1 1 1 1 1 Type GOU-LTL00-1 GOU-LTL1-1 GOU-LTL3-1 Dimensional drawings LTL00-1/9 LTL1-1/9, LTL3-1/9 Type LTL1-1/9 LTL3-1/9 A 69 91 B 230 270 C 317 430 D 68 96 E 119 147 F 16,5 9 G 115 135 H 177 220,5 I 25 30,5 C 17 Dimensional drawings LTL4A-1x/1250(1600)/8 1250 A 1600 A LTL00-2/9 C 18 B 270 311 C 315 339 Dimensional drawings LTL1-2/9, LTL3-2/9 Type LTL1-2/9 LTL3-2/9 A 138 182 B 230 270 C 317 430 D 68 96 E 123,5 151,5 F 23 15,5 G 115 135 H 177 220,5 I 25 30,5 LTL...-3/9, LTL...-3/9/ES00 Type LTL00-3/9 LTL1-3/9 LTL2-3/9 LTL3-3/9 A 105,5 184 210 254 B 149 230 256 270 C 220 317 397 430 D 45 68 81 96 E 86 119 133 147 F 20,5 16,5 16,5 9 G 74,5 115 128 135 H 120 177 205 220,5 I 17 25 25 30,5 K 33 58 66 82 L 116 149 163 177 L1 126 159 173 187 C 19 Dimensional drawings LTL4A-3x(3)/.../8/(Q) 1250 A 1600 A LTL00-4/9 C 20 B 270 311 C 315 339 Dimensional drawings LTL1-4/9, LTL3-4/9 Type LTL1-4/9 LTL3-4/9 S00-Z A 253 345 B 230 270 C 317 430 D 68 96 E 123,5 151,5 F 23 15,5 G 115 135 H 177 220,5 I 25 30,5 K 58 82 P0070-Z C 21 Dimensional drawings S00, S1, S2, S3 Type S00 S1 S2 S3 A 25 37 42 50 B 15 20 22 25 C 15 25 28 30 D M5 M6 M8 M8 E Max. 15 Max. 28 Max. 30 Max. 30 F 5,5 6,5 8,5 8,5 P1, P2, P3, P12, P22, P32 C 22 Type P0070 P0095 P1 P12 P2 P22 P3 P32 A 25 29 37 37 42 42 50 50 B 15 15 20 20 22 22 25 25 C 15 18 25 25 28 28 30 30 D M5 M5 M6 M6 M8 M8 M8 M8 E Max. 25 Max. 28 Max. 30 Max. 42 Max. 40 Max. 55 Max. 44 Max. 66 F 5,5 5, 5 6,5 6,5 8,5 8,5 8,5 8,5