EMERGENCY LIGHTING We light your world™ 10.6.15 DBEL R R OPTIONAL WET location COLD Weather ILLUMINATION HOUSING • Long-life, efficient ultra-bright white LED. • Decorative, low-profile, architectural design. • 5 watt LED per unit. • Die-cast aluminum housing. • Mirror-bright reflector and prismatic polycarbonate refractor. • Durable powder-coated finishes in white, black and dark bronze. • Sealed and gasketed. ELECTRICAL • Dual 120/277 voltage. • Charge rate/power“ON”LED indicator light and push to test switch for mandated code compliance testing. • 4.8V long-life, maintenance-free, rechargeable NiCd battery. • Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Self-diagnostic test feature continually diagnoses units performance and tests system to ensure reliable operation and to meet electrical and life safety codes. OPTIONS • CW: Cold-weather unit for use in freezer applications. (in temperatures as low as (-20°C ­– 40°C) . WARRANTY/LISTING • Five year warranty on all electronics and housing. Battery pro-rated for five years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for wet locations. (0°C ­– 50°C) DIMENSIONS MOUNTING • Surface mount via easy connect back plate that fits most standard size junction boxes. • Universal K/O pattern on back plate for wall mount. Decorative Outdoor LED Emergency Unit STANDARD 61/8” 101/2” 35/8” ORDERING INFORMATION Sample Part Number: DBEL-BR-SDT Model DBEL WWhite BBlack Specifications and dimensions subject to change without notice. Housing Color Options SDTSelf-diagnostics CWCold Weather BR Dark Bronze 2 DBEL R R Catalog Number DBEL-­‐SDT DBEL-­‐SDT-­‐CW Input Watts (W) 120V 277V 2.7 2.8 2.9 3.0 Input Amps (A) 120V 277V 0.026 0.012 0.031 0.014 CENTER-TO-CENTER SPACING GUIDELINES For reference only. Decorative Outdoor LED Emergency Unit (continued) ELECTRICAL INFORMATION Meets NFPA101 Requirements for: 11’ center-to-center spacing - 4’ path of egress 1’ from the wall- 7 1/2’ mounting height. Specifications and dimensions subject to change without notice. 3 E-1 R R ILLUMINATION HOUSING • Adjustable long lasting, efficient ultra-bright white LED lamp heads. • One, one watt white LED per lamp head. • Unique all inclusive lamp, reflector and lens assembly. • Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. OPTIONS • ELECTRICAL SPV: 120/230 volt tap in 50/60 Hz. WARRANTY/LISTING • Dual 120V/277V standard. Optional dual 120V/230V available. • One year warranty on all electronics and housing. • Unique bi-color LED indicator light alerts occupant on battery condition (green-normal, red-check battery). • UL listed for damp locations (0°C- 30°C / 32°F - 86°F standard). • 3.6V long-life, maintenance-free, rechargeable Ni-Cad battery. • Meets UL924, NFPA101 Life Safety Code, NEC, OSHA, Local and State Codes. • Internal solid-state transfer switch automatically connects the internal battery to LED lamp heads for minimum 90-minute emergency illumination. • LED Low-Profile, Thermoplastic Emergency Light STANDARD DIMENSIONS Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. 73/4” MOUNTING • Surface mount back plate fits most standard size junction boxes and snaps into place. • Suitable for wall or ceiling mount. 71/4 ” 41/2” Sample Part Number: E-1 ORDERING INFORMATION Model Specifications and dimensions subject to change without notice. 3” 21/16” 11/4 ” Housing Color Options E-1 W White RC B Black SPV Remote Capacity 120/230 Volt 50/60Hz 4 E-1 R R LED Low-Profile, Thermoplastic Emergency Light (continuied) ELECTRICAL INFORMATION 120V 0.33 0.52 E-1 E-1 RC 230V 0.33 0.52 277V 0.37 0.60 120V 0.046 0.068 230V 0.044 0.068 277V 0.052 0.070 REMOTE LAMP COMPATIBILITY Maximum Wattage Allowed E-1 2 Remote Head Family Total Wattage RHLED-1-3.6 RHLED-2-3.6 2.0 RHLED-1-HL-3.6 1.5 RHLED-1-WP-3.6 1.0 RHLED-2-WP-3.6 2.0 RHLED-1-WP-HL-3.6 1.5 RHLED-1-KX-3.6 1.0 RHLED-2-KX-3.6 2.0 RHLED-1-KX-HL-3.6 1.5 Specifications and dimensions subject to change without notice. 1.0 E-1.ss.v1 5 LEDR-1 R R LED Emergency Unit STANDARD OPTIONAL ILLUMINATION HOUSING • Long lasting, efficient ultra-bright white LED lamp heads. • • 1 watt (8 LEDs x 0.125 watt) per head. • High-performance chrome-plated metalized reflector and plastic lens for optimal light distribution. • Adjustable LED lamp heads provide optimal center-to-center spacing. High-lumen option available for increased centerto-center spacing. Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. OPTIONS ELECTRICAL • SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • HL: 12-LED heads (12 LEDs x 0.125 watt) per head provide increased center-to-center spacing. • SPV: 208/220/240 multi-tap voltage in 50/60Hz. • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push to test switch for mandated code compliance testing. • 3.6V long-life, maintenance-free, rechargeable NiCd battery. • • Internal solid-state transfer switch automatically connects the internal battery to LED lamp heads for minimum 90-minute emergency illumination. Five year warranty on all electronics and housing. Batteries pro-rated for five years. • UL listed for damp locations. (0°C ­– 50°C) • Meets UL924, NFPA101 Life Safety Code, NEC, OSHA, Local and State Codes. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. WARRANTY/LISTING DIMENSIONS MOUNTING • Surface mount via quick-connect back plate; fits most standard size junction boxes and snaps into place to make internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. 33/4” 53/8” 101/8” 145/8” 33/4” 21/2” ORDERING INFORMATION Sample Part Number: LEDR-1 Notes: Model 1. Not available with SDT options. LEDR-1 W White SDT Self-Diagnostics B Black SPV 208/220/240 Volt, 50/60Hz Specifications and dimensions subject to change without notice. Housing Color Options HL (1) High-Lumen 6 LEDR-1 R R LED Emergency Unit (continued) ELECTRICAL INFORMATION CATALOG NUMBER INPUT WATTS (W) INPUT AMPS (A) 120V 277V 208V 220V 240V 120V 277V 208V 220V 240V LEDR-1 1.8 1.8 2.6 3.5 3.1 0.022 0.010 0.024 0.029 0.025 LEDR-1 SDT 1.6 1.6 - - - 0.020 0.010 - - - CENTER-TO-CENTER SPACING GUIDELINES For reference only. Meets NFPA 101 Requirements for: 10’ center-to-center spacing - 3’ path of egress 1’ from wall - 7 1/2’ mounting height. LEDR-1.ss.v1 Specifications and dimensions subject to change without notice. 7 LEDR-5HO R R OPTIONAL ILLUMINATION HOUSING • Long lasting, efficient ultra-bright white LED lamp heads. • • 1 watt (8 LEDs x 0.125) per head. • High-performance chrome-plated metalized reflector and plastic lens for optimal light distribution. • Adjustable LED lamp heads provides optimal center-tocenter spacing. High-lumen option available for increased center-to-center spacing. ELECTRICAL Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. OPTIONS • SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • HL: 12-LED heads (12 LEDs x 0.125 watt) per head provide increased center-to-center spacing. • SPV: 208/220/240 multi-tap voltage in 50/60 Hz. • Dual 120/277 voltage standard. Optional multi-tap 208/220/240 voltage available. • Can operate up to 3 watts remote capacity. • Charge rate/power “ON” LED indicator light and push to test switch for mandated code compliance testing. • Five year warranty on all electronics and housing. Battery pro-rated for five years. • 3.6V long-life, maintenance-free, rechargeable NiCd battery. • • Internal solid-state transfer switch automatically connects the internal battery to LED lamp heads for minimum 90-minute emergency illumination. Meets UL924, NFPA101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (0°C ­– 50°C) • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. WARRANTY/LISTING DIMENSIONS 33/4” MOUNTING • Surface mount via quick-connect back plate; fits most standard size junction boxes and snaps into place to make internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. Remote Capable LED Emergency Unit STANDARD 53/8” 101/8” 145/8” 33/4” 21/2” Sample Part Number: LEDR-5HO ORDERING INFORMATION NOTES: 1. Not available with SDT options. Model Housing Color LEDR-5HO W White B Black Specifications and dimensions subject to change without notice. Options SDT Self-Diagnostics HL High-Lumen SPV 208/220/240 volt, 50/60 Hz1 8 LEDR-5HO R R Catalog Number Input Watts (W) Input Amps (A) 120V 277V 208V 220V 240V 120V 277V 208V 220V 240V LEDR-5HO 2.1 2.1 2.8 3.6 3.3 0.025 0.012 0.025 0.029 0.025 LEDR-5HO-SDT 1.9 1.9 - - - 0.020 0.010 - - - CENTER-TO-CENTER SPACING GUIDELINES For reference only. Remote Capable LED Emergency Unit (continued) ELECTRICAL INFORMATION Meets NFPA101 Requirements for: 10’ center-to-center spacing - 3’ path of egress 1’ from the wall- 7 1/2’ mounting height. REMOTE LAMP COMPATIBILITY Reference Remote Lamp Head Specification Sheets for complete catalog number ordering information. MAXIMUM WATTAGE ALLOWED LEDR-5HO REMOTE HEAD FAMILY 3.0 TOTAL WATTAGE RHLED1-3.6 1.0 RHLED2-3.6 2.0 RHLED1-WP-3.6 1.0 RHLED2-WP-3.6 2.0 RHLED1-KX-3.6 1.0 RHLED1-KX-3.6 2.0 RHLED1-HL-3.6 1.5 RHLED2-HL-3.6 3.0 RHLED1-WP-HL-3.6 1.5 RHLED2-WP-HL-3.6 3.0 RHLED1-KX-HL-3.6 1.5 RHLED1-KX-HL-3.6 3.0 LEDR5HO.ss.v1 Specifications and dimensions subject to change without notice. 9 LEDRX-5HO R R OPTIONAL ILLUMINATION HOUSING • Long lasting, efficient ultra-bright white LED lamp heads. • 1 watt (8 LEDs x 0.125) per head. • High-performance chrome-plated metalized reflector and plastic lens for optimal light distribution. • Adjustable LED lamp heads provides optimal center-tocenter spacing. High-lumen option available for increased center-to-center spacing. • Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. OPTIONS ELECTRICAL • SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • HL: 12-LED heads (12 LEDs x 0.125 watt) per head provide increased center-to-center spacing. • SPV: 208/220/240 multi-tap voltage in 50/60Hz. • Dual 120/277 voltage standard. Optional multi-tap 208/220/240 voltage available. • Can operate up to 3 watts remote capacity. • Charge rate/power “ON” LED indicator light and push to test switch for mandated code compliance testing. • Five year warranty on all electronics and housing. Battery pro-rated for five years. • 3.6V long-life, maintenance-free, rechargeable NiCd battery. • • Internal solid-state transfer switch automatically connects the internal battery to LED lamp heads for minimum 90-minute emergency illumination. Meets UL924, NFPA101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (0°C ­– 50°C) • WARRANTY/LISTING Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. DIMENSIONS MOUNTING • 51/4” Surface mount via quick-connect back plate; fits most standard size junction boxes and snaps into place to make internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. ORDERING INFORMATION Notes: 1. Not available with SDT options. 111/8” 37/8” Sample Part Number: LEDRX-5HO Model Housing Color LEDRX-5HO W White B Black Specifications and dimensions subject to change without notice. Remote Capable LED Emergency Unit STANDARD Options SDT Self-Diagnostics HL High-Lumen SPV 208/220/240 Volt, 50/60Hz (1) 10 LEDRX-5HO R R Remote Capable LED Emergency Unit (continuued) ELECTRICAL INFORMATION CENTER-TO-CENTER SPACING GUIDELINES For reference only. Meets NFPA101 Requirements for: 10’ center-to-center spacing - 3’ path of egress 1’ from the wall- 7 1/2’ mounting height. REMOTE LAMP COMPATIBILITY Maximum Wattage Allowed LEDRX-5HO Remote Head Family 3 Total Wattage RHLED-1-3.6 1.0 RHLED-2-3.6 2.0 RHLED-1-HL-3.6 1.5 RHLED-2-HL-3.6 3.0 RHLED-1-WP-3.6 1.0 RHLED-2-WP-3.6 2.0 RHLED-1-WP-HL-3.6 1.5 RHLED-2-WP-HL-3.6 3.0 RHLED-1-KX-3.6 1.0 RHLED-2-KX-3.6 2.0 RHLED-1-KX-HL-3.6 1.5 RHLED-2-KX-HL-3.6 3.0 Specifications and dimensions subject to change without notice. 11 LEDRX-5HL R R ILLUMINATION HOUSING • Long lasting, efficient ultra-bright white LED lamp heads. • 1.7 watt (8 LEDs x 0.2125) per head. • High-performance chrome-plated metalized reflector and plastic lens for optimal light distribution. • Adjustable LED lamp heads provides optimal center-tocenter spacing. • WARRANTY/LISTING ELECTRICAL • Dual 120/277 voltage standard. • Charge rate/power “ON” LED indicator light and push to test switch for mandated code compliance testing. • 3.6V long-life, maintenance-free, rechargeable NiCd battery. • Internal solid-state transfer switch automatically connects the internal battery to LED lamp heads for minimum 90-minute emergency illumination. • • Five year warranty on all electronics and housing. Battery pro-rated for five years. • Meets UL924, NFPA101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (0°C ­– 50°C) DIMENSIONS 51/4” Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. MOUNTING • Surface mount via quick-connect back plate; fits most standard size junction boxes and snaps into place to make internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. ORDERING INFORMATION Special voltage options available. Specifications and dimensions subject to change without notice. Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. High Lumen LED Emergency Unit STANDARD 111/8” 37/8” Sample Part Number: LEDRX-5HL Model Housing Color LEDRX-5HL W White BBlack 12 LEDRX-5HL R R High Lumen LED Emergency Unit ELECTRICAL INFORMATION CENTER-TO-CENTER SPACING GUIDELINES For reference only. 1 0.06 0.12 0.22 0.23 0.48 0.89 0.88 1.18 1.14 1.12 0.98 0.98 0.99 1.16 1.21 1.08 0.98 0.76 0.94 0.55 0.22 0.22 0.10 0.06 2 0.09 0.21 0.29 0.26 0.46 1.23 1.17 2.00 2.25 1.26 1.78 1.26 1.18 1.98 2.23 2.20 1.89 1.09 0.64 0.65 0.43 0.23 0.10 0.07 3 0.09 0.21 0.32 0.37 1.12 1.98 2.13 3.01 2.45 2.86 1.33 1.20 1.10 1.98 2.26 3.96 2.56 2.08 1.21 0.72 0.48 0.26 0.12 0.07 4 0.12 0.23 0.33 0.39 1.03 2.00 3.86 4.08 3.13 3.00 2.34 1.33 1.69 2.01 2.45 4.06 3.95 2.36 1.10 0.65 0.32 0.28 0.15 0.10 5 0.15 0.30 0.35 0.43 0.96 1.15 2.73 2.80 2.95 2.86 1.14 1.08 1.17 1.87 2.37 2.00 2.87 2.06 1.02 0.73 0.32 0.29 0.12 0.11 6 0.15 0.28 12 0.41 11 0.53 10 0.68 9 0.83 8 1.21 7 1.78 6 1.98 5 1.24 4 1.10 3 0.91 2 0.74 1 0.84 0 1.25 1 1.10 2 1.98 3 1.23 4 0.97 5 0.38 6 0.30 7 0.32 8 0.13 9 0.10 10 11 Meets NFPA101 Requirements for: 22’ center-to-center spacing - 6’ path of egress 0’ from the wall- 7½’ mounting height. LEDRX-5HL.ss.v1 Specifications and dimensions subject to change without notice. 13 R-1 R R OPTIONAL ILLUMINATION OPTIONS • Two fully-adjustable 5.4 watt, glare-free lamp heads. • Smooth thermoplastic reflector and plastic lens for optimal light distribution. ELECTRICAL • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable Sealed lead acid battery. SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • HTR: Optional internal heater for cold temperature applications. • USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act. • NC: Long-life 6V maintenance free, rechargeable NiCD battery. WARRANTY/LISTING •Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Five year warranty on all electronics and housing. Batteries pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (20°C ­– 50°C) DIMENSIONS MOUNTING • Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Top and back K/O available for conduit application. • Suitable for wall or ceiling mount. 49/16” 61/2” 121/4” 16” HOUSING • Incandescent Emergency Unit STANDARD Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. 47/8” 21/2” Sample Part Number: R-1 ORDERING INFORMATION Special voltage options available. Specifications and dimensions subject to change without notice. Model Housing Color Options R-1 W White SDT Self Diagnostics B Black NC NiCad Battery HTR Internal Heater USA Assembled in USA 14 R-1 R R Incandescent Emergency Unit (continued) ELECTRICAL INFORMATION Input Watts (W) 120V 277V 4.0 5.0 4.5 4.5 Catalog Number R-­‐1 R-­‐1SDT Input Amps (A) 120V 277V 0.040 0.020 0.040 0.030 CENTER-TO-CENTER SPACING GUIDELINES For reference only. 1 0.05 0.05 0.07 0.09 0.13 0.13 0.16 0.23 0.30 0.27 0.28 0.42 0.37 0.33 0.31 0.23 0.20 0.14 0.10 0.08 0.08 0.05 0.03 0.02 2 0.06 0.07 0.09 0.10 0.12 0.17 0.19 0.24 0.27 0.31 0.38 0.40 0.37 0.37 0.32 0.27 0.24 0.17 0.13 0.10 0.09 0.05 0.05 0.04 3 0.07 0.08 0.08 0.11 0.14 0.16 0.19 0.23 0.28 0.38 0.37 0.43 0.44 0.33 0.31 0.32 0.21 0.18 0.13 0.12 0.10 0.06 0.05 0.04 4 0.05 0.06 0.08 0.13 0.15 0.16 0.19 0.20 0.29 0.31 0.31 0.29 0.36 0.35 0.27 0.22 0.20 0.15 0.13 0.11 0.10 0.06 0.05 0.04 5 0.05 0.06 0.10 0.12 0.13 0.16 0.17 0.17 0.23 0.27 0.27 0.29 0.30 0.28 0.24 0.21 0.17 0.13 0.10 0.06 0.10 0.07 0.05 0.04 6 0.03 0.06 0.08 0.11 0.12 0.14 0.14 0.18 0.21 0.23 0.22 0.24 0.25 0.25 0.19 0.17 0.17 0.12 0.10 0.10 0.08 0.06 0.06 0.03 1 2 3 4 5 6 7 Specifications and dimensions subject to change without notice. 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 15 R-5HO R R OPTIONAL ILLUMINATION OPTIONS • Two fully-adjustable 5.4 watt, glare-free lamp heads. • Smooth plastic reflector and lens for optimal light distribution. • SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act. ELECTRICAL • Dual 120/277 voltage. • Offers “11W” of remote capacity. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • Five year warranty on all electronics and housing. Battery pro-rated for two years. • LVD (low voltage disconnect) prevents battery from deep discharge. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • 6V maintenance-free, rechargeable Sealed lead acid battery. • UL listed for damp locations. (20°C ­– 40°C) • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. WARRANTY/LISTING Remote Capable Incandescent Emergency Unit STANDARD DIMENSIONS 49/16” MOUNTING • Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Top and back K/O for conduit applications. • Suitable for wall or ceiling mount. 61/2” 121/4” 16” 47/8” 21/2” HOUSING • Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. Sample Part Number: R-5HO ORDERING INFORMATION Special voltage options available. Specifications and dimensions subject to change without notice. Model Housing Color Options R-5HO W White SDT Self Diagnostics B Black USA Assembled in the USA 16 R-5HO R R Input Watts (W) 120V 277V 4.1 4.6 5.2 5.2 Catalog Number R-­‐5HO R-­‐5HO-­‐SDT CENTER-TO-CENTER SPACING GUIDELINES Consult factory for details. REMOTE LAMP COMPATIBILITY R-­‐5HO Maximum Wattage Allowed 11 Remote Head Family RH1-­‐6V5.4W RH1-­‐6V7.2W RH1-­‐6V9W RH2-­‐6V5.4W RHR-­‐1-­‐6V5.4W RHR-­‐1-­‐6V7.2W RHR-­‐1-­‐6V9W RHR-­‐2-­‐6V5.4W RH16-­‐1-­‐6V5W RH16-­‐2-­‐6V5W RH1-­‐WP-­‐6V5.4W RH1-­‐WP-­‐6V7.2W RH1-­‐WP-­‐6V9W RH2-­‐WP-­‐6V5.4W Specifications and dimensions subject to change without notice. Input Amps (A) 120V 277V 0.037 0.018 0.06 0.03 Remote Capable Incandescent Emergency Unit (continued) ELECTRICAL INFORMATION Total Wattage 5.4 7.2 9 10.8 5.4 7.2 9 10.8 5 10 5.4 7.2 9 10.8 17 LEDR-2 R R ILLUMINATION HOUSING • Long-life, efficient ultra-bright white LED lamp heads. • 1 watt (8 LEDs x 0.125 watt) per head. • • High-performance, chrome-plated metallized reflector and plastic lens for optimal light distribution. • Two fixed or adjustable LED lamp heads provide optimal center-to-center spacing. Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. OPTIONS • SPV. 208/220/240 multi-tap voltage in 50/60Hz. WARRANTY/LISTING ELECTRICAL • • Dual 120/277 voltage standard. Optional multi-tap 208/220/240 voltage available. Five year warranty on all electronics and housing. Battery pro-rated for five years. • • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (0°C ­– 50°C) • 3.6V long-life, maintenance-free, rechargeable NiCd battery. • Internal solid-state transfer switch automatically connects the internal battery to LED lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. Adjustable Optics LED Emergency Unit STANDARD DIMENSIONS 21/4” 91/2” MOUNTING 45/8” • Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. Sample Part Number: LEDR-2 ORDERING INFORMATION Model Housing Color LEDR-2 W White BBlack Housing Color SPV 208/220/240 Volt, 50/60Hz Specifications and dimensions subject to change without notice. 18 LEDR-2 R R Adjustable Optics LED Emergency Unit (continued) ELECTRICAL INFORMATION Input Watts (W) 120V 277V 2.1 2.1 Catalog Number LEDR-­‐2 Input Amps (A) 120V 277V 0.025 0.01 CENTER-TO-CENTER SPACING GUIDELINES For reference only. 1 0.03 0.04 0.06 0.06 0.08 0.12 0.18 0.24 0.24 0.30 0.36 0.33 0.34 0.37 0.43 0.45 0.49 0.52 0.36 0.36 0.18 0.10 0.07 0.04 2 0.03 0.04 0.06 0.07 0.11 0.20 0.40 0.03 0.60 0.55 0.48 0.46 0.45 0.58 0.80 1.35 1.39 1.04 0.57 0.47 0.32 0.13 0.09 0.06 3 0.03 0.04 0.06 0.10 0.11 0.33 0.79 1.11 1.34 1.36 0.92 0.60 0.47 0.92 1.72 1.87 1.61 1.05 0.61 0.52 0.33 0.24 0.10 0.05 4 0.03 0.04 0.06 0.10 0.18 0.37 0.69 1.07 1.53 1.71 1.52 1.02 0.53 1.20 1.65 1.65 1.33 0.87 0.57 0.50 0.34 0.20 0.09 0.05 5 0.03 0.04 0.06 0.09 0.16 0.31 0.58 0.91 1.22 1.44 1.41 1.00 0.45 0.72 1.05 1.00 0.78 0.55 0.34 0.24 0.20 0.12 0.07 0.05 6 0.03 0.04 0.06 0.07 0.10 0.19 0.33 0.53 0.84 0.94 0.92 0.61 0.33 0.39 0.53 0.53 0.44 0.28 0.27 0.20 0.15 0.10 0.06 0.03 12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 Meets NFPA101 Requirements for: 14’ center-to-center spacing - 3’ path of egress 2’ from the wall- 7 1/2’ mounting height. LEDR-2.ss.v1 Specifications and dimensions subject to change without notice. 19 R-2 R R ILLUMINATION HOUSING • Two fixed optics 5.4 watt, glare-free lamp heads. • • Smooth thermoplastic reflector and plastic lens for optimal light distribution. Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. WARRANTY/LISTING ELECTRICAL • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • LVD (Low voltage disconnect) prevents battery From deep discharge. • Five year warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • ETL listed for damp locations. (20°C ­– 50°C) Fixed-Optics Incandescent Emergency Unit STANDARD DIMENSIONS 1113/16” 51/8” 23/8” MOUNTING • Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Suitable for wall or ceiling mount. ORDERING INFORMATION Special voltage options available. Sample Part Number: R-2 Model Housing Color R-2 W BBlack White Specifications and dimensions subject to change without notice. 20 R-2 R R Catalog Number R-­‐2 Input Watts (W) 120V 277V 4.0 5.0 CENTER-TO-CENTER SPACING GUIDELINES For reference only. Specifications and dimensions subject to change without notice. Input Amps (A) 120V 277V 0.045 0.020 Fixed-Optics Incandescent Emergency Unit (continued) ELECTRICAL INFORMATION 21 PAR-1 R R OPTIONAL ILLUMINATION HOUSING • Two fully adjustable 5.4W glare free PAR-type lamp heads. • High performance chrome-plated metallized reflector and plastic lens for optimal light distribution. • Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. OPTIONS • ELECTRICAL • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. USA: Substantial transformation assembly in the U.S. complies with “AssembLED in the USA” under the Buy American Act. WARRANTY/LISTING • Five year warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (0°C ­– 50°C) DIMENSIONS MOUNTING PAR-Type Lamp Head Emergency Unit STANDARD 141/2” 41/4” • Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. 133/4” 51/8” ELECTRICAL INFORMATION Input Watts (W) 120V 277V 3.6 5.5 Catalog Number PAR-­‐1 Input Amps (A) 120V 277V 0.034 0.017 Sample Part Number: PAR-1 ORDERING INFORMATION Special Voltage options available. Specifications and dimensions subject to change without notice. Model Housing Color PAR-1 W White BBlack Options USA Assembled in the USA 22 R-16 R R ALL LE HEAD D OPTIO N OPTIONAL ILLUMINATION • OPTIONS Two fully adjustable, 5W, MR-16 halogen lamp heads standard. Optional 3.3W white LED lamp heads. ELECTRICAL • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • • SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • HTR: Optional internal heater for cold temperature applications. • USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act. • LED: 3.3 watt high-performance MR-16 base LED Lamps. WARRANTY/LISTING Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Five year warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (20°C ­– 40°C) MOUNTING • MR-16 Emergency Unit STANDARD DIMENSIONS Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. 151/2” 51/8” HOUSING • 121/4” Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. ELECTRICAL INFORMATION Input Watts (W) 120V 277V 3.5 4.9 4.5 4.5 Catalog Number R-­‐16 R-­‐16-­‐SDT ORDERING INFORMATION Special voltage options available. Specifications and dimensions subject to change without notice. Model Housing Color Input Amps (A) 120V 277V 0.031 0.019 0.040 0.030 Options Sample Part Number: R-16 R-16 W White SDT Self-Diagnostics B Black HTR Internal Heater USA Assembled in the USA LED 3.3W High Lumen White LED Lamp 23 R-16-HO R R OPTIONAL ALL LE HEAD D OPTIO N ILLUMINATION • HOUSING Two fully adjustable 5W MR-16 halogen lamp heads standard. Optional 3.3W white LED lamp heads. • Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. OPTIONS ELECTRICAL • Offers 10W of remote capacity (6V DC output) when using standard 5W halogen lamps and 13W of remote capacity (6V DC output) when using optional 3.3W LED lamps. • SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • Dual 120/277 voltage. • • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act. • LVD (low voltage disconnect) prevents battery from deep discharge. • LED: 3.3 watt high-performance MR-16 base LED lamps. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. Remote Capable MR-16 Emergency Unit STANDARD WARRANTY/LISTING • Five year warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (20°C ­– 40°C) MOUNTING • Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. DIMENSIONS 151/2” 51/8” 121/4” ORDERING INFORMATION Special Voltage options available. Sample Part Number: R-16-HO Model Housing Color Options R-16-HO W White SDT Self-Diagnostics B Black USA Assembled in the USA Specifications and dimensions subject to change without notice. LED 3.3W High Lumen White LED Lamp 24 R-16-HO R R Remote Capable MR-16 Emergency Unit (continued) ELECTRICAL INFORMATION Input Watts (W) 120V 277V 3.7 4.2 5.2 5.2 Catalog Number R-­‐16-­‐HO R-­‐16-­‐HO-­‐SDT Input Amps (A) 120V 277V 0.039 0.022 0.06 0.03 CENTER-TO-CENTER SPACING GUIDELINES Consult factory for details. REMOTE LAMP COMPATIBILITY MAXIMUM WATTAGE ALLOWED R-16-HO with 5W halogen 10 R-16-HO with 3W LED 13 REMOTE HEAD FAMILY TOTAL WATTAGE RH16-1 5 RH16-2 10 RHR-1 (5.4 watt) 5.4 RHR-2 (5.4 watt) 10.8 RHR-1 (7 watt) 7 RHR-1 (9 watt) 9 RHR-1 (12 watt) 12 RH-1 (5.4 watt) 5.4 RH-2 (5.4 watt) 10.8 RH-1 (7 watt) 7 RH-1 (9 watt) 9 RH-1 (12 watt) 12 RH1-WP (5.4 watt) 5.4 RH1-WP (7.2 watt) 7.2 RH1-WP (9 watt) 9 RHLED-1-16-MV 3.3 RHLED-2-16-MV 6.6 R-16-HO.ss.v1 Specifications and dimensions subject to change without notice. 25 RMR-16 R R OPTIONAL ALL LE HEAD D OPTIO N ILLUMINATION • HOUSING Two fully adjustable ultra-bright, round, 7W, MR-16 halogen lamp heads standard. Optional 3.3W white LED lamp heads. Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. OPTIONS ELECTRICAL • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. MOUNTING • • Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Top and side knockout for conduit applications. • Suitable for wall or ceiling mount. • USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act. • LED: 3.3 watt high-performance MR-16 base LED Lamps. Semi-Recessed MR-16 Emergency Unit STANDARD WARRANTY/LISTING • Five year warranty on all electronics and housing. Battery pro-rated for two years.. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (20°C ­– 40°C) DIMENSIONS 3” 133/4” 51/8” ELECTRICAL INFORMATION Input Watts (W) 120V 277V 4.2 5.2 Catalog Number RMR-­‐16 Input Amps (A) 120V 277V 0.039 0.021 Sample Part Number: RMR-16 ORDERING INFORMATION Special Voltage options available. Specifications and dimensions subject to change without notice. Model Housing Color Options RMR-16 W White USA Assembled in the USA B Black LED 3.3W High Lumen White LED Lamp 26 RMR-16-WP R R OPTIONAL WET location COLD Weather ALL LE HEAD D OPTIO N ILLUMINATION • OPTIONS Two fully adjustable, ultra-bright, round, 7.2W MR-16 halogen lamp heads standard. Optional 3.3W white LED lamp heads available. ELECTRICAL • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • HTR: Optional internal heater for cold temperature (-9°C – 40°C) applications. • CW: Optional internal heater and battery blanket for extreme cold temperature (-25°C – 50°C) applications. • USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act. • LED: 3.3 watt high-performance MR-16 base LED lamps. WARRANTY/LISTING • 6V maintenance-free, rechargeable Sealed lead acid battery. • • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • UL listed for wet locations. (20°C ­– 40°C). DIMENSIONS MOUNTING • Five year warranty on all electronics and housing. Battery pro-rated for two years. Wet Location Semi-Recessed MR-16 Emergency Unit STANDARD Wall mount via knockouts on the back of the housing. 41/4” HOUSING • Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in neutral gray or black finish. • Fully-gasketed clear polycarbonate cover offers protection against wet, non-hazardous dust, corrosive atmospheres and to water spray or splashing water locations. ORDERING INFORMATION 1413/16” 55/8” Sample Part Number: RMR-16-WP Special Voltage options Model available. RMR-16 Specifications and dimensions subject to change without notice. Housing Color G B Gray Black Options WP Wet Location HTR Internal Heater CW Internal heater with battery blanket USA Assembled in the USA LED 3.3W High Lumen White LED Lamps 27 RMR-16-WP R R Wet Location Semi-Recessed MR-16 Emergency Unit (continued) ELECTRICAL INFORMATION Input Watts (W) Catalog Number Input Amps (A) 120V 277V 120V 277V RMR-16-WP 6.0 6.2 0.053 0.025 RMR-16-WP-CW 5.3 6.0 0.050 0.025 CENTER-TO-CENTER SPACING GUIDELINES RMR-16-WP with two 7.2W MR-16 Halogen Lamp Heads* For reference only. 1 0.03 0.04 0.05 0.06 0.08 0.13 0.23 0.38 0.40 0.42 0.44 0.40 0.33 0.33 0.36 0.21 0.14 0.14 0.14 0.07 0.06 0.04 0.03 0.02 2 0.03 0.04 0.05 0.07 0.10 0.17 0.43 1.00 0.90 0.90 0.38 0.34 0.47 0.45 0.46 0.39 0.19 0.12 0.10 0.10 0.06 0.05 0.04 0.02 3 0.03 0.04 0.06 0.11 0.13 0.30 1.71 2.20 3.92 2.02 0.35 0.31 0.61 1.65 2.67 1.00 0.45 0.13 0.09 0.07 0.06 0.06 0.04 0.02 4 0.03 0.05 0.06 0.10 0.16 0.95 1.30 4.50 4.80 2.20 0.70 0.53 1.44 4.58 4.53 3.42 0.54 0.15 0.09 0.06 0.04 0.06 0.04 0.03 5 0.04 0.06 0.09 0.17 0.20 1.20 2.82 4.01 3.38 1.30 0.52 0.51 0.60 3.37 4.36 3.05 0.62 0.17 0.09 0.06 0.05 0.05 0.01 0.02 6 0.03 0.05 12 0.07 11 0.11 10 0.17 9 0.55 8 1.53 7 1.97 6 1.10 5 0.90 4 0.43 3 0.52 2 0.62 1 1.20 0 1.13 1 1.77 2 0.59 3 0.17 4 0.09 5 0.04 6 0.04 7 0.05 8 0.05 9 0.03 10 11 * Consult factory for LED lamp head performance data. Meets NFPA101 Requirements for: 14’ center-to-center spacing - 3’ path of egress 2’ from the wall- 7 1/2’ mounting height. Specifications and dimensions subject to change without notice. RMR-16-WP.ss.v1 28 RMR-16-65/125 R R OPTIONAL ALL LE HEAD D OPTIO N ILLUMINATION • OPTIONS Two fully adjustable ultra-bright, round, 12W, MR-16 halogen lamp heads standard. Optional 3.3W white LED lamp heads. • LED: 3.3 watt high-performance MR-16 base LED lamps. WARRANTY/LISTING ELECTRICAL • Offers 26W of remote capacity (6V/12V DC output) when using standard 12W halogen lamps and 43W of remote capacity (6V/12V DC output) when using optional 3.3W LED lamps. Five year warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • Dual 120/277 voltage. • UL listed for damp locations. (20°C ­– 40°C) • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Remote Capable MR-16 Emergency Unit STANDARD DIMENSIONS MOUNTING • Surface mount via easy connect back plate, which fits most standard junction boxes and snaps into place making internal electrical connections. • Conduit mount knockout on top of housing and backplate. • Suitable for wall or ceiling mount. HOUSING • Injection-molded, engineering-grade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. Sample Part Number: RMR-16-65 ORDERING INFORMATION Special Voltage options available. Model Housing Color RMR-16-65 W White (6 Volt) RMR-16-125 B Black (12 Volt) Specifications and dimensions subject to change without notice. Options LED 3.3W High Lumen White LED Lamp 29 RMR-16-65/125 R R Remote Capable MR-16 Emergency Unit (continued) ELECTRICAL INFORMATION REMOTE LAMP COMPATIBILITY MAXIMUM WATTAGE ALLOWED RMR-16-65/125 with 12W halogen 26 RMR-16-65/125 with 3.3W LED 43 REMOTE HEAD FAMILY RH16-1 TOTAL WATTAGE REMOTE HEAD FAMILY (cont.) TOTAL WATTAGE 5 RH-1 (9 watt) 9 RH16-2 10 RH-2 (9 watt) 18 RHR-1 (5.4 watt) 5.4 RH-1 (12 watt) 12 RHR-2 (5.4 watt) 10.8 RH-2 (12 watt) 24 RHR-1 (7 watt) 7 RH1-WP (5.4 watt) 5.4 RHR-2 (7 watt) 14 RH1-WP (7.2 watt) 7.2 RHR-1 (9 watt) 9 RH1-WP (9 watt) 9 RHR-2 (9 watt) 18 RH1-WP (12 watt) 12 RHR-1 (12 watt) 12 RH2-WP (5.4 watt) 10.8 RHR-2 (12 watt) 24 RH2-WP (7.2 watt) 14.4 RH-1 (5.4 watt) 5.4 RH2-WP (9 watt) 18 RH-2 (5.4 watt) 10.8 RH2-WP (12 watt) 24 RH-1 (7 watt) 7 RHLED-1-16-MV 3.3 RH-2 (7 watt) 14 RHLED-2-16-MV 6.6 NOTE: Voltages of the remote lamp head must match the voltage of the individual unit. Reference individual remote lamp head specification sheets for voltage compatibility. Specifications and dimensions subject to change without notice. RMR-16-65/125.ss.v1 30 EMRL-1 R R ILLUMINATION MOUNTING • Adjustable ultra-bright 8W bi-pin halogen lamp head. • • Sealed beam PAR36-type gimbal trim with smooth chromeplated metallized reflector and plastic lens offers optimal light distribution. WARRANTY/LISTING • Five year warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. ELECTRICAL • Dual 120/277 voltage. • Junction box with 3/4” knockouts for AC input. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. Compatible with drywall or drop ceiling mount installations. Bar hangers included. DIMENSIONS Adjustable Recessed Emergency Down-light Unit STANDARD 71/8” 73/32” 8” HOUSING • Steel mounting frame and housing. • 6” recessed housing with mounting bar hangers. • Impact-resistant thermoplastic adjustable gimbal trim. • Trim securely attached to housing with spring clips. ELECTRICAL INFORMATION Input Watts (W) 120V 277V 10 10 Catalog Number EMRL-­‐1 ORDERING INFORMATION Specifications and dimensions subject to change without notice. Model Housing Color EMRL-1 WHT White BLK Black BGE Beige Input Amps (A) 120V 277V 0.05 0.05 Sample Part Number: EMRL-1-WHT-GIMBAL GIMBAL 31 R-7 R R OPTIONAL ILLUMINATION OPTIONS • Two fully adjustable 5.4W par type lamp heads. • High-performance chrome-plated metal reflectors and plastic lens for optimal light distribution. • SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • USA: Substantial transformation assembly in the U.S. complies with “AssembLED in the USA” under the Buy American Act. ELECTRICAL • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • WARRANTY/LISTING • Five year warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for dry locations. (25°C) Recessed Incandescent Emergency Unit STANDARD DIMENSIONS Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. 127/8” 91/8” 25/8” MOUNTING • Bar hangers on the back box for recessed mount. • Compatible with drywall or drop ceiling mount installations. Bar hangers included. 91/4” HOUSING • Durable 20 gauge steel trim plate in white or black finish. • Trim securely attached to housing with spring clips. ELECTRICAL INFORMATION Input Watts (W) 120V 277V 5.0 5.0 Catalog Number R-­‐7/SDT Input Amps (A) 120V 277V 0.05 0.03 Sample Part Number: R-7 ORDERING INFORMATION Special Voltage options available. Specifications and dimensions subject to change without notice. Model Housing Color Options R-7 W White SDT Self Diagnostics B Black USA Assembled in the USA 32 DXR-LED R R Fifteen energy-efficient, ultra bright LEDs per emergency lighting head! LED Emergency Light STANDARD HOUSING ILLUMINATION • Heavy 20-gauge steel construction. • Ultra bright, all white LED–more lumen output than standard incandescent model. • Durable white powder-coated finish. • 15 LEDs per head with lumen output equal to 9W incandescent. • Thermoplastic emergency lamp heads • White or black finish • 1.5 watts per head. OPTIONS ELECTRICAL • Dual 120/277 voltage. 60Hz input • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • Maintenance-free, rechargeable sealed nickel cadium battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Smaller unit offers remote capability for up to two heads, while the larger unit can accomodate up to five remote heads. WARRANTY/LISTING • Five Year Warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. • Brown out protection, low voltage disconnect. • Transfer/Charging Cirguitry (no relays or fuses). DIMENSIONS MOUNTING • Keyhole mounting knocksout on the rack for wall mounting. 14-1/8” • Knockouts provided on top and sides for conduit entry. 12-1/2” 2-1/4” ORDERING INFORMATION Special Voltage options available. 12-1/2” 8-3/8” 6-13/16” 9-5/8” 2” Sample Part Number: DXR-LED-B-2-HO Model Housing Color No. of Heads Options DXR-LED W White 2 2 LED Heads HO Remote Capability Black 3 3 LED Heads Specifications and dimensions subject to change without notice. B 33 DXR R R OPTIONAL ILLUMINATION OPTIONS • Adjustable, glare-free PAR-Type lamp heads. • 6V model offers 7.2W lamps, standard. • 12V 50W model offers 9W lamps, standard. 12V 100W model offers 12W lamps, standard. • HTR: Optional internal heater for cold temperature applications. • USA: Substantial transformation assembly in the U.S. complies with “AssembLED in the USA” under the Buy American Act. ELECTRICAL WARRANTY/LISTING • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable Sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • • Five Year Warranty on all electronics and housing. Battery pro-rated for two years. Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • Remote Capable Incandescent Emergency Unit STANDARD UL listed for dry locations. (25°C) DIMENSIONS MOUNTING • Knockouts on the back for wall mount. • Side and top knockouts for conduit feed applications. 143/16” 14” HOUSING • 123/4” ORDERING INFORMATION Special Voltage options available. 125/8” 31/4” Injection-molded, engineering-grade, 5VA flame retardant, hight-impact thermoplastic construction. 5” Sample Part Number: DXR-12-10 ModelVoltage DXR Capacity Options 6 6 Volts 5 50 Watt 12 12 Volts 10 100 Watt 20SB USA Specifications and dimensions subject to change without notice. HTR Internal Heater (Available with 50W units only) 12V20W Sealed Beam Halogen (Available with 12V units only) Assembled in the USA 34 DXR R R Input Watts (W) 120V 277V 15.1 17.7 20.5 21.1 19.6 23.4 29.3 33.5 Catalog Number DXR-­‐65 DXR-­‐610 DXR-­‐125 DXR-­‐1210 Input Amps (A) 120V 277V 0.142 0.068 0.189 0.089 0.178 0.093 0.273 0.131 CENTER-TO-CENTER SPACING GUIDELINES Consult factory for details. REMOTE LAMP COMPATIBILITY 6 VOLT Remote Head Family RHR-­‐1-­‐6V5.4W RHR-­‐2-­‐6V5.4W RHR-­‐1-­‐6V7.2W RHR-­‐2-­‐6V7.2W RHR-­‐1-­‐6V9W RHR-­‐2-­‐6V9W RH1-­‐6V5.4W RH2-­‐6V5.4W RH1-­‐6V7.2W RH2-­‐6V7.2W RH1-­‐6V9W RH2-­‐6V9W RH1-­‐WP-­‐6V5.4W RH2-­‐WP-­‐6.5.4W RH1-­‐WP-­‐6V7.2W RH2-­‐WP-­‐6V7.2W RH1-­‐WP-­‐6V9W RH2-­‐WP-­‐6V9W 6 VOLT Maximum Remote Capacity Available 35.6 watts 85.6 watts Catalog Number: DXR650 DXR610 12 VOLT Maximum Remote Capacity Available 32 watts 76 watts 10 watts 60 watts Catalog Number: DXR125 DXR1210 DXR12520SB DXR121020SB Model # DXR-65 DXR-610 DXR-125 DXR-1210 Watts for 1-1/2 hrs. 50 100 50 100 Voltage 6 6 12 12 Wattage 5.4 10.8 7.2 14.4 9 18 5.4 10.8 7.2 14.4 9 18 5.4 10.8 7.2 14.4 9 18 12 VOLT Remote Head Family RHR-­‐1-­‐12V7W RHR-­‐2-­‐12V7W RHR-­‐1-­‐12V9W RHR-­‐2-­‐12V9W RHR-­‐1-­‐12V12W RHR-­‐2-­‐12V12W RH1-­‐12V7W RH2-­‐12V7W RH1-­‐12V9W RH2-­‐12V9W RH1-­‐12V12W RH2-­‐12V12W RH1-­‐WP-­‐12V7W RH2-­‐WP-­‐12V7W RH1-­‐WP-­‐12V9W RH2-­‐WP-­‐12V9W RH1-­‐WP-­‐12V12W RH2-­‐WP-­‐12V12W Wattage 7 14 9 18 12 24 7 14 9 18 12 24 7 14 9 18 12 24 Remote Capable Incandescent Emergency Unit (continued) ELECTRICAL INFORMATION Total Connected Heads/Fixtures 4 hrs. 2 hrs. 1.5 hrs. 2* 4* 2** 4** 4* 9* 3** 7** 6* 12* 5** 10** *Based on 7.2 watt lamps, standard **Based on 9 watt lamps, standard Specifications and dimensions subject to change without notice. 35 NYDXR R R ILLUMINATION MOUNTING • Adjustable, glare-free PAR-Type lamp heads. • Field installable third lamp head included with the 27W and 50W models. • 6V 18W model offers 2-9W lamps, standard. • 6V 27W model offers 3-9W lamps, standard. • 12V model offers 12W lamps, standard. • 12V 50W model offers 3-12W lamps, standard. • Knockouts on the back for wall mount. • Side and top knockouts for conduit feed applications. WARRANTY/LISTING ELECTRICAL • Dual 120/277 voltage. • 12V model offers 14W of remote capacity. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V maintenance-free, rechargeable sealed lead acid battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Five year warranty on all electronics and housing. Battery pro-rated for two years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for dry locations. (25°C) New York Approved Emergency Unit STANDARD DIMENSIONS 157/8” 91/8” HOUSING • Durable powder-coated 20 gauge steel construction in white or black finish. • Injection-molded engineering grade high-impact thermoplastic heads. 161/2” 101/2” 101/8” 21/2” 141/2” 21/2” Sample Part Number: NYDXR-6-2-50-18-9 ORDERING INFORMATION Model Voltage NYDXR 6 6 Volt Head # Unit Watts 2 2 Heads 18 18 Watts* Lamp Watts 9 9 Watts* 12 12 Volt 3 3 Heads 27 27 Watts* 12 12 Watts** Color W White B Black 50 50 Watts** * Available in 6V only ** Available in 12V only Specifications and dimensions subject to change without notice. 36 NYDXR R R Input Watts (W) 120V 277V 7.1 8.0 7.1 8.0 15.2 15.8 Catalog Number NYDXR-­‐18W NYDXR-­‐27W NYDXR-­‐50W Input Amps (A) 120V 277V 0.066 0.031 0.066 0.031 0.143 0.065 CENTER-TO-CENTER SPACING GUIDELINES For reference only. New York Approved Emergency Unit (continued) ELECTRICAL INFORMATION Meets NFPA101 Requirements for: 16’ center-to-center spacing - 3’ path of egress 1’ from the wall- 7 1/2’ mounting height. REMOTE LAMP COMPATIBILITY NYDXR-­‐12V50W with (2) 9W heads NYDXR-­‐12V50W with (2) 12W heads NYDXR-­‐12V50W with (3) 9W heads NYDXR-­‐12V50W with (3) 14W heads Maximum Wattage Allowed 32 26 23 14 Remote Head Family RH1-­‐12V7W RH1-­‐12V9W RH1-­‐12V12W RH2-­‐12V7W RH2-­‐12V9W RH2-­‐12V12W RHR-­‐1-­‐12V7W RHR-­‐1-­‐12V9W RHR-­‐1-­‐12V12W RHR-­‐2-­‐12V7W RHR-­‐2-­‐12V9W RHR-­‐2-­‐12V12W RH1-­‐WP-­‐12V7W RH1-­‐WP-­‐12V9W RH1-­‐WP-­‐12V12W RH2-­‐WP-­‐12V7W RH2-­‐WP-­‐12V9W RH2-­‐WP-­‐12V12W Total Wattage 7.2 9 12 14.4 18 24 7.2 9 12 14.4 18 24 7.2 9 12 14.4 18 24 Specifications and dimensions subject to change without notice. NYDXR-­‐6V27W with (2) 9W heads NYDXR-­‐6V27W with (3) 9W heads Maximum Wattage Allowed 9 0 Remote Head Family RH1-­‐6V5.4W RH1-­‐6V7.2W RH1-­‐6V9W RHR-­‐1-­‐6V5.4W RHR-­‐1-­‐6V7.2W RHR-­‐1-­‐6V9W RH16-­‐1-­‐6V5W RH1-­‐WP-­‐6V5.4W RH1-­‐WP-­‐6V7.2W RH1-­‐WP-­‐6V9W Total Wattage 5.4 7.2 9 5.4 7.2 9 5 5.4 7.2 9 37 LEDTFX-2 R R WET location COLD Weather ILLUMINATION MOUNTING • Sealed and gasketed weather proof lamp heads with high performance chrome plated metallized reflector and tempered glass lenses for optimal light distribution. • Long lasting efficient Ultra-bright white LED lamp heads. • 1.875W (15 LEDs x 0.125) per head. • External mounting brackets for simplified wall mounting. WARRANTY/LISTING • Five year warranty on all electronics and housing. Battery pro-rated for five years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. ELECTRICAL • UL listed for wet locations. (-20º C — 50º C ). • Dual 120/277 voltage. • Can operate up to 3.7 watts remote capacity in temperatures 0°C ­– 50°C. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • 9.6V long life, maintenance-free, rechargeable NiCd battery. • Internal solid-state transfer switch automatically connects the internal battery to LED lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Standard unit without remote loads can be used in cold weather freezer applications (-20º C — 50º C ). DIMENSIONS Wet-Location Remote Capable LED Emergency Unit STANDARD 57/8” 123/16” 35/8” 65/10” HOUSING • Corrosion-resistant 5VA flame retardant UV stabilized polycarbonate in gray or black finish. • Sealed and gasketed housing with hinged cover. • Sealed test switch. 8” ORDERING INFORMATION Special Voltage options available. Model Housing Color LEDTFX-2 GGray BBlack Specifications and dimensions subject to change without notice. Sample Part Number: LEDTFX-2 38 LEDTFX-2 R R Input Watts (W) 120V 277V 2.7 2.7 Catalog Number LEDTFX-­‐2 Input Amps (A) 120V 277V 0.030 0.013 CENTER-TO-CENTER SPACING GUIDELINES For reference only. Meets NFPA101 Requirements for: 16’ center-to-center spacing - 3’ path of egress 1’ from the wall- 7 1/2’ mounting height. Wet-Location Remote Capable LED Emergency Unit (continued) ELECTRICAL INFORMATION REMOTE LAMP COMPATIBILITY LEDTFX-­‐2 Maximum Wattage Allowed 3 Remote Head Family RHLED1-­‐CLPCXTE RHLED2-­‐CLPCXTE RHLED1-­‐WP-­‐CLPCXTE RHLED2-­‐WP-­‐CLPCXTE RHLED1-­‐CLPCXTE-­‐HL RHLED2-­‐CLPCXTE-­‐HL RHLED1-­‐WP-­‐CLPCXTE-­‐HL RHLED2-­‐WP-­‐CLPCXTE-­‐HL Specifications and dimensions subject to change without notice. Total Wattage 1 2 1 2 1.5 3 1.5 3 39 TFX-2 R R OPTIONAL WET location ILLUMINATION OPTIONS • Sealed and gasketed weather proof lamp heads with tempered glass lenses. • HTR: Optional internal heater for cold temperature applications. • 7.2W incandescent wedge base lamps. • USA: Substantial transformation assembly in the U.S. complies with “Assembled in the USA” under the Buy American Act. ELECTRICAL • Dual 120/277 voltage. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • • LVD (low voltage disconnect) prevents battery from deep discharge. Five year warranty on all electronics and housing. Batteries are pro-rated warranted for two years. • • 6V maintenance-free, rechargeable Sealed lead acid battery. Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. WARRANTY/LISTING • UL listed for wet locations. (5°C ­– 40°C) DIMENSIONS 61/2” MOUNTING • Wet-Location Incandescent Emergency Unit STANDARD External mounting brackets for simplified wall mounting provided. 127/8” 6” 63/8” HOUSING • Corrosion-resistant 5VA flame retardant, UV-stabilized polycarbonate in gray finish. • Sealed and gasketed housing with hinged cover. • Sealed test switch. • Integral breather vent. 83/8” Sample Part Number: TFX-2 ORDERING INFORMATION Special Voltage options available. ModelOptions TFX-2 HTR Internal Heater USA Assembled in the USA RC Remote Capable Specifications and dimensions subject to change without notice. 40 TFX-2 R R Input Watts (W) 120V 277V 8.5 10.0 Catalog Number TFX-­‐2 Input Amps (A) 120V 277V 0.073 0.040 CENTER-TO-CENTER SPACING GUIDELINES For reference only. Meets NFPA101 Requirements for: 14’ center-to-center spacing - 3’ path of egress 3’ from the wall- 7 1/2’ mounting height. Wet-Location Incandescent Emergency Unit (continued) ELECTRICAL INFORMATION REMOTE LAMP COMPATIBILITY TFX-­‐2 Maximum Wattage Allowed 15 Remote Head Family RH1-­‐6V5.4W RH1-­‐6V7.2W RH1-­‐6V9W RH1-­‐6V12W RH2-­‐6V5.4W RH2-­‐6V7.2W RHR-­‐1-­‐6V5.4W RHR-­‐1-­‐6V7.2W RHR-­‐1-­‐6V9W RHR-­‐1-­‐6V12W RHR-­‐2-­‐6V5.4W RHR-­‐2-­‐6V7.2W RH16-­‐1-­‐6V5W RH16-­‐2-­‐6V5W RH1-­‐WP-­‐6V5.4W RH1-­‐WP-­‐6V7.2W RH1-­‐WP-­‐6V9W RH1-­‐WP-­‐6V12W RH2-­‐WP-­‐6V5.4W RH2-­‐WP-­‐6V7.2W Specifications and dimensions subject to change without notice. Total Wattage 5.4 7.2 9 12 10.8 14.4 5.4 7.2 9 12 10.8 14.4 5 10 5.4 7.2 9 12 10.8 14.4 41 CA26S10 R R ILLUMINATION HOUSING • Two fully adjustable ultra-bright, 12W bi-pin halogen par-36 type lamp heads. • Durable 20-gauge steel construction in neutral white finish. WARRANTY/LISTING ELECTRICAL • Dual 120/277 voltage. • Five year warranty on all electronics and housing. Battery pro-rated for two years. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • LVD (low voltage disconnect) prevents battery from deep discharge. • • 6V maintenance-free rechargeable Sealed lead calcium battery. UL listed. DIMENSIONS • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 120-minute emergency illumination. 43/4” • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. 111/2” 5/8 8” ” 7/8 MOUNTING 7/8 • Knockouts on the back for wall mount. • Side and top knockouts for conduit feed applications. Chicago Approved Emergency Light STANDARD ” K.O. ” K.O. 53/4” 13” 27/8” ELECTRICAL INFORMATION Input Watts (W) 120V 277V 7.2 7.7 Catalog Number CA26S10 ORDERING INFORMATION Input Amps (A) 120V 277V 0.068 0.031 Sample Part Number: CA26S10 ModelHousing CA26S10 Specifications and dimensions subject to change without notice. W White 42 CADXR R R CADXR 50 & 100 WATT CADXR - 27 WATT ILLUMINATION • WARRANTY/LISTING Two, 6V 12W adjustable bi-pin halogen lamp heads. ELECTRICAL • Dual 120V/277V. • Charge rate/power “ON” LED indicator light and push to test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V Sealed lead acid, maintenance-free, rechargeable battery - one per 27 watt unit, two per 50 watt unit and four per 100 watt unit. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 120-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Remote capacity available on all models. See back for additional details. • Five year warranty on all electronics and housing. Battery pro-rated for two years. • UL listed for damp locations (20°-50°C/68°F­—122°F standard). • Meets UL924, NFPA101 Life Safety Code, NEC, OSHA, Local and State Codes. • Meets city of Chicago requirements. DIMENSIONS Chicago Approved Steel Emergency Lighting STANDARD 27 Watt Capacity MOUNTING • Knockouts on the back for wall mount. • Side and top knockouts for conduit feed applications. HOUSING • Durable 20-gauge steel construction. • Neutral white or black finish. Sample Part Number: CADXR-27 ORDERING INFORMATION Model Voltage Watts for 90 Minutes 6V1 27 27W Notes: 1. Available in 27 watt only. CADXR BLANK 6 6V2 5 50W 2. Not available in 27 watt. 12 12V2 10 100W Specifications and dimensions subject to change without notice. Housing Color W White B Black 43 CADXR R R Catalog Number Input Watts (W) Input Amps (A) CADXR27 120V 11.0 277V 11.0 120V 0.11A 277V 0.04A CADXR65 18.0 18.0 0.17A 0.07A CADXR125 26.0 26.0 0.25A 0.10A CADXR610 23.0 23.0 0.21A 0.10A CADXR1210 32.0 32.0 0.30A 0.13A MAXIMUM WATTAGE ALLOWED CADXR 27/50/100 watt 3/26/76 NOTE Voltages of the remote lamp head must match the voltage of the individual unit. Reference individual remote lamp head specification sheets for voltage compatibility. Remote Head Family Total Wattage Remote Head Family Total Wattage RH16-1 5 RH-2 (9 watt) 18 RH16-2 10 RH1-WP 7.2 RHR-1 (5.4 watt) 5.4 RH2-WP 14.4 RHR-2 (5.4 watt) 10.8 SRH-1 (7.2 watt) 7.2 RHR-1 (7.2 watt) 7.2 SRH-2 (7.2 watt) 14.4 RHR-2 (7.2 watt) 14.4 SRH-1 (9 watt) 9 RHR-1 (9 watt) 9 SRH-2 (9 watt) 18 RHR-2 (9 watt) 18 SRH-1 (12 watt) 12 RH-1 (5.4 watt) 5.4 SRH-2 (12 watt) 24 RH-2 (5.4 watt) 10.8 SRHLED-1 5.3 RH-1 (7.2 watt) 7.2 SRHLED-2 10.3 RH-2 (7.2 watt) 14.4 RHLED-1-16-MV 3.3 9 RHLED-2-16-MV 6.6 RH-1 (9 watt) Specifications and dimensions subject to change without notice. Chicago Approved Steel Emergency Lighting (continued) ELECTRICAL INFORMATION CADXR.ss.v1 44 CAR R R ILLUMINATION • WARRANTY/LISTING Two, 6V or 12V 12W adjustable bi-pin halogen lamp heads. ELECTRICAL • Dual 120V/277V. • Charge rate/power “ON” LED indicator light and push to test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V Sealed lead acid, maintenance- free, rechargeable battery — one per 27 watt unit and two per 50 watt unit. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 120-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Five year warranty on all electronics and housing. Battery pro-rated for two years. • UL listed for damp locations (20°-50°C/68°F-122°F standard). • Meets UL924, NFPA101 Life Safety Code, NEC, OSHA, Local and State Codes. • Meets city of Chicago requirements. DIMENSIONS MOUNTING • Conveniently designed for use with T-bar grid ceilings. • Holes provided on enclosure for wire-suspension mount. Chicago Approved Steel Recessed Emergency Lighting STANDARD HOUSING • Durable 20-gauge steel construction. • Neutral white or black finish. ELECTRICAL INFORMATION CAR-627 CAR-650 CAR-1250 120V 11.0 18.0 26.0 277V 11.0 18.0 26.0 120V 0.11A 0.17A 0.25A 277V 0.04A 0.07A 0.10A Sample Part Number: CAR-6-27 ORDERING INFORMATION Notes: 1. Available in 6V only Specifications and dimensions subject to change without notice. Model CAR Voltage 6 6V 12 12V Watts for 90 Minutes Housing Color 27 27W1 WWhite 50 50W B Black 45 CALEDDXR R R Remote Test Module STANDARD OPTIONAL ILLUMINATION HOUSING • Ultra-bright, energy efficient, long-life Red LED. • • UV-stabilized ultra-clear acrylic edgelit panel provides consistent, uniform illumination. Premium-grade, extruded aluminum housing (also available in black or white powder-coated finishes). • • Double face utilizes factory installed silver or white mylar background panel. Self-adhesive Chevron appliques and guide template provided for directional indication. • NY compliant 8” Exit letters. OPTIONS ELECTRICAL • Dual 120/277 voltage standard. Optional multi-tap 208/220/240 voltage available. • Charge rate/power “ON” LED indicator light and push-to-test switch for mandated code compliance testing. • 4.8V long-life, maintenance-free, rechargeable NiCd battery. • Internal solid-state transfer switch automatically connects the internal battery to LED board for minimum 90-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • SDT: Self-diagnostic test feature performs monthly, biannually, and annually tests to ensure reliable operation and to meet electrical and life safety codes. • SPV: 208/220/240 multi-tap voltage in 50/60 Hz. WARRANTY/LISTING • Five year warranty on all electronics and housing. Battery pro-rated for five years. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Codes. • UL listed for damp locations. (20°C ­– 50°C) DIMENSIONS MOUNTING • Aluminum mounting canopy included for top, end or back mount. ELECTRICAL INFORMATION Catalog Number Input Watts (W) CALEDDXR Input Amps (A) 120V 277V 208V 220V 240V 120V 277V 208V 220V 240V 3.6 4.0 3.9 3.93 3.98 0.030 0.020 0.022 0.022 0.020 3.6 4.0 - - - 0.030 0.020 - - - Sample Part Number: CALEDDXR ORDERING INFORMATION Special voltage options available. NOTES: 1. With single face only. 2. Not available with SDT options. MODEL CALEDDXR Specifications and dimensions subject to change without notice. No. of FACES LETTER 1 Single Face R Red 2 Double Face PANEL C Clear1 M Mirror W White HOUSING BATTERY W White Blank AC Only B Black EM Battery Backup A Aluminum OPTIONS SDT Self-diagnostics SPV 208/220/240 volt, 50/60 Hz2 46 LEDCADXR R R ILLUMINATION • WARRANTY/LISTING Two, 6V 5.3W adjustable white LED lamp heads. ELECTRICAL • Dual 120V/277V. • Charge rate/power “ON” LED indicator light and push to test switch for mandated code compliance testing. • LVD (low voltage disconnect) prevents battery from deep discharge. • 6V sealed lead acid, maintenance-free, rechargeable battery. • Internal solid-state transfer switch automatically connects the internal battery to lamp heads for minimum 120-minute emergency illumination. • Fully automatic solid-state, two-rate charger initiates battery charging to recharge a discharged battery in 24 hours. • Remote capacity 10W optional. • Five year warranty on all electronics and housing. Battery pro-rated for two years. • UL listed for damp locations (20°-50°C/68°F­—122°F standard). • Meets UL924, NFPA101 Life Safety Code, NEC, OSHA, Local and State Codes. • Meets city of Chicago requirements. DIMENSIONS Chicago Approved Steel LED Emergency Lighting STANDARD MOUNTING 113/8” • Knockouts on the back for wall mount. • Side and top knockouts for conduit feed applications. 5” 21/2” HOUSING • Durable 20-gauge steel construction. • Neutral white or black finish. Sample Part Number: LEDCADXR-RC ORDERING INFORMATION Model Housing Color Options LEDCADXR W White RC Remote Capacity Specifications and dimensions subject to change without notice. B Black 47 LEDCADXR R R Catalog Number LEDCADXR LEDCADXR-RC LEDCADXR Input Watts (W) Input Amps (A) 120V 8.4 277V 9.4 120V 0.08A 277V 0.04A 8.7 10.0 0.09A 0.05A Maximum Wattage Allowed 10 STEEL - (CHICAGO APPROVED) LED Remote Head Family (steel) SRHLED-1 SRH-1 (7.2 watt) SRH-1 (9 watt) Total Wattage 5.3 7.2 9.0 NON-STEEL Remote Head Family RH16-1 RH16-2 RHR-1 (5.4 watt) RHR-1 (7 watt) RHR-1 (9 watt) RH-1 (5.4 watt) RH-1 (7 watt) RH-1 (9 watt) RH1-WP (5.4 watt) RH1-WP (7.2 watt) RH1-WP (9 watt) RHLED-1-16-MV RHLED-2-16-MV Total Wattage 5 10 5.4 7 9 5.4 7 9 5.4 7.2 9 3.3 6.6 Chicago Approved Steel LED Emergency Lighting (continued) ELECTRICAL INFORMATION NOTE: Voltages of the remote lamp head must match the voltage of the individual unit. Reference individual remote lamp head specification sheets for voltage compatibility. Specifications and dimensions subject to change without notice. LEDCADXR.ss.v1 48 RETROFIT R R LED Retrofit Kits STANDARD SCREW-IN KIT 45/8” 15/8” ILLUMINATION • Kits easily convert incandescent exit signs to energy efficient LED Exit signs. • Ultra bright, long-life red or green LED. HARD WIRE KIT ELECTRICAL Hard wire: • Dual 120/277 voltage. • Energy usage of 2.8W per kit. 413/16” Screw-in: • 120V only. • Energy usage of 2.8W per kit. MOUNTING • Hard wire kits come complete with mounting bracket and double-sided tape for easy installation. • Screw-in kits are supplied with socket adapters for installation in signs with bayonet, intermediate or candelabra bases. 65/8” Energy Efficient: LEDs use a fraction of the wattage of incandescent bulbs! Incandescent EXIT WARRANTY/LISTING • Five year warranty. • Meets UL924, NFPA 101 Life Safety Code, NEC, OSHA, Local and State Code. EXIT Energy Usage Hours ON per year Price per KiloWatt Hour EXIT replaced with Green LED Retrofit Kit 30W (Two 15W lamps) 1.4W (Two 0.7W LED lamps) 24 x 365 = 8760 hours 24 x 365 = 8760 hours $0.09/KWhr $0.09/KWhr EXIT replaced with Red LED Retrofit Kit 2.8W (Two 1.4W LED lamps) 24 x 365 = 8760 hours $0.09/KWhr 24,528 Watts Energy Usage per Year 262,800 Watts 12,264 Watts Dollars Spent per Year $23.65 $1.10 $2.21 - 250,536 WATTS $22.55 238,272 WATTS $21.44 ENERGY SAVINGS PER YEAR SAVINGS PER YEAR *Example based on 9¢/KWhr ORDERING INFORMATION Specifications and dimensions subject to change without notice. ModelKit RFXTE-1 Red Hardwire Kit GFXTE-1 Green Hardwire Kit RFXTE-3 Red Screw-in Kit GFXTE-3 Green Screw-in Kit Sample Part Number: RFXTE-3 49 VANDAL SHIELDS & WIRE GUARDS R R VANDAL SHIELDS 301/4” • High-impact resistant polycarbonate material. • Mounting hardware provided for easy installation in the field. 133/4” 61/2” 18” 71/2” BG-3C 7” BGR-1 73/4” 15” PCS-1 ORDERING INFORMATION 22” Polycarbonate Vandal/Environmental Shield Guards Model # For use with Dimensions PCS-1 EZXTE, EZRXTE, KXTE, CLPU, KZXTE, 2-1/2”x 9-3/16”x 13-3/16” EZTXTE, SXTE, SLXTU, XTU, EXU BG-1 EZXTE, EZRXTE, EZXTE-RC, LEDCXTE, 7-3/4”x 22”x 15” WLEZXTE, WLXTE, ELXTE, PLELRXTE, KXTE, CLPU, KZXTE, EZTXTE, CKXTE, SXTE, SLXTU, NYXTE, NYELXTE, NYKXTE, CXPU, CA, XTU, EXU, DBEL, DXR, TFX-2, CA26S10, LEDTFX-2 BGR-1 R-1, LEDR1, R-2, LEDR-2, R-16, LEDR-5HO, 7-1/2” x 18” x 7” R5HO, R-16-HO, RMR-16, RMR-16-WP BG-3C CXTE, CEX 13-3/4” x 30-1/4” x 6-1/2” BG-1 133/16” 93/16” 21/2” PCS-1 151/4” WIRE GUARD • Durable 9-guage steel construction. • Mounting hardware provided for easy installation in the field. 133/4” 6” ORDERING INFORMATION Wire Guards Model # For use with WG-1 EZXTE, EZRXTE, EZXTE-RC, WLEZXTE WLXTE, PLELRXTE, KXTE, CLPU, CKXTE, SXTE, SLXTU, NYXTE, CXPU, CA, EXU, XTU, R-1, LEDR-1, R-2, LEDR-2, R-16, LEDR-5HO, R-16-HO, RMR-16, DBEL, PAR-1, LEDTFX-2, CA26S10, RMR16-WP WG-3 CXTE, LEDCXTE, NYELXTE, NYKXTE, CEX, DXR WG-1 Dimensions 13-3/4” x 15-1/4” x 6” 305/8” 133/4” 13-3/4” x 30-5/8” x 6” 6” WG-3 Specifications and dimensions subject to change without notice. 50 REMOTE LAMPS R R RH16-2 61/4” 41/4” RH16-1 RHR-1 RH1-WP 6” 41/2” Remote Lamp 41/4” 41/4” 41/4” 6” RH2 RH1 RHR-2 6” RH2-WP 41/2” ILLUMINATION • Smooth thermoplastic or chrome plated metalized reflector with glass lens for optimal light distribution. • Adjustable with MR-16 halogen or wedge base incandescent lamps ELECTRICAL • Powered from low voltage power source with low voltage wiring (not provided). MOUNTING • Universal mounting base plate included with mounting hardware. HOUSING • Indoor application remote heads are injectionmolded, engineeringgrade, 5VA flame retardant, high-impact resistant, thermoplastic in white or black finish. • Outdoor application remote heads are die-cast aluminum, sealed and gasketed in gray or black finish. WARRANTY • Five year warranty. Specifications and dimensions subject to change without notice. ORDERING INFORMATION Model # # of Heads Voltage RH16-1-6V5W 1 6 Volt RH16-2-6V5W 2 6 Volt RH16-1B-6V5W 1 6 Volt RH16-2B-6V5W 2 6 Volt Wattage 5 Watt 5 Watt 5 Watt 5 Watt Application Indoor Indoor Indoor Indoor Color White White Black Black Other voltage and wattage options available. Please contact customer service. Model # # of Heads Voltage RHR-1-6V5.4W 1 6 Volt RHR-1-6V9W 1 6 Volt RHR-2-6V5.4W 2 6 Volt RHR-2-6V9W 2 6 Volt RHR-1-12V7W 1 12 Volt RHR-1-12V12W 1 12 Volt RHR-2-12W7W 2 12 Volt RHR-2-12V12W 2 12 Volt RHR-1B-6V5.4W 1 6 Volt RHR-2B-6V5.4W 2 6 Volt Wattage 5.4 Watt 9 Watt 5.4 Watt 9 Watt 7.2 Watt 12 Watt 7.2 Watt 12 Watt 5.4 Watt 5.4 Watt Application Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Color White White White White White White White White Black Black Other voltage and wattage options available. Please contact customer service. Model # # of Heads Voltage RH1-6V5.4W 1 6 Volt RH1-6V9W 1 6 Volt RH2-6V5.4W 2 6 Volt RH2-6V9W 2 6 Volt RH1-12V7W 1 12 Volt RH1-12V12W 1 12 Volt RH2-12V7W 2 12 Volt RH2-12V12W 2 12 Volt RH1-WP-6V7.2W 1 6 Volt RH2-WP-6V7.2W 2 6 Volt RH1B-6V5.4W 1 6 Volt RH2B-6V5.4W 2 6 Volt Wattage 5.4 Watt 9 Watt 5.4 Watt 9 Watt 7.2 Watt 12 Watt 7.2 Watt 12 Watt 7.2 Watt 7.2 Watt 5.4 Watt 5.4 Watt Application Indoor Indoor Indoor Indoor Indoor Indoor Indoor Indoor Outdoor Outdoor Indoor Indoor Color White White White White White White White White Gray Gray Black Black Other voltage and wattage options available. Please contact customer service. 51 R R Warranty Americanlite is pleased to provide a 5 year limited warranty covering the fixtures in this catalogue. Americanlite warrants that the fixtures comply with Americanlite ’s published specifications and are free from defects in materials and workmanship. ® ® ® All our equipment is CE, TUV, FCC or UL approved and manufactured with approved components. Americanlite® reserves the right to change or improve the design or components of any of its products due to parts availability or changes in standards, without assuming any obligation to modify any product previously manufactured and without notice. All equipment is tested and inspected before shipment. This warranty is void if the product is operated outside of its normal operating conditions. The foregoing warranty does not apply to failures caused by acts of God or as a result of any abuse, misuse, abnormal use, or use in violation of any applicable standard, code or instructions for use in installations, including, but not limited to, those contained in the Standards for the International Electrotechnical Commission. Americanlite® reserves and has the right to examine failed fixture to determine the cause of failure, excessive lumen depreciation and patterns of usage. Specifications and dimensions subject to change without notice. 52