Easicheck Modules

advertisement
EASICHECK™
• Saves time and cost on testing & maintenance
EasiCheck™ offers an advanced, versatile and flexible
solution to automatic testing, which is easy to use and
• Tests fully comply with BS5266 & EN50172
provides a high level of integrity. Each panel can monitor
• Easy to use control panel
up to 250 luminaires, continuously checking battery
• 250 address capacity per panel
voltage and charge current. Functionality and duration
tests are performed automatically at frequencies that
• Stand alone or network up to 63 panels
exceed the requirements of the current codes of practice.
• Events log and test reports can be printed
All faults are displayed on the panel, providing location
• Colour graphics software package available
text and the nature of the fault, to aid maintenance.
EasiCheck™ is suitable for all size of projects, but
particularly medium to large installations, where panels
can be networked or where optional site monitoring or
colour graphics software is required, providing central
199
WHERE TO USE EASICHECK™
•
•
•
•
Hospitals
Universities, schools and colleges
Museums
Airports
•
•
•
•
Shopping centres
Retail outlets
Offices
Industrial facilities
Emergency Luminaires - Testing Systems
PC control.
EASICHECK™
200
SYSTEM OPERATION
PANEL
• An EasiCheck™ interface module is fitted into all suitable
dedicated emergency luminaires and mains luminaires
converted for emergency operation
• Each module is given a unique address number, using a hand
held programmer
• Every luminaire is then connected to a 2 core data BUS cable,
which is linked back to the control panel. A single panel can
accommodate up to 250 luminaires (self contained systems) or
255 luminaires and addressable devices (central power
systems)
• When switched on, the panel will self learn the number of
luminaires connected to it
• Text information can be allocated to each system component,
including central battery units and changeover devices etc for
central power system versions, during commissioning by a
Cooper Lighting and Security service engineer
• The panel can then be programmed to carry out automatic test
sequences according to BS5266 or EN50172. Testing can
also be initiated manually. All test data is sent back and stored
at the control panel. Additionally, the system carries out
continuous real time monitoring of all connected devices
• Central battery unit status is constantly monitored on central
power systems version. Multiple CBU's can be controlled by a
single panel
• In the event of a fault, the precise location of the device is
displayed at the control panel along with accurate details of
the nature of the fault and an alarm is raised
• Luminaire status is provided locally via a 2 colour LED built into
each fitting (self contained versions)
• A printer can be connected, which automatically prints details
of any system events as soon as they occur
• The system can be enhanced by networking up to 63 panels.
Central PC monitoring and a global network printer can also
be incorporated. An advanced colour graphics software
package is available to provide central and remote system
control and monitoring
Constructed from flame retardant polycarbonate. 2 line x 40
character LCD display and soft touch 5 button keypad. A single
panel can accommodate up to 250 luminaires or interfaces.
If a greater number are required, up to 63 panels can be linked
using a networking card. Access to panel functions is by means
of a secure password. All functions controlled by the keypad,
via a series of user friendly menus with context sensitive help
information. System and luminaire faults can be viewed without
input of password. Panel has printer connection facility and battery
back-up. An on-board alarm is fitted, which is activated when
faults are identified. Alarm can be muted using keypad.
Panel is used to facilitate following functions:
- Set up test types and times
- Set up testing groups
- Initiate manual tests
- Display real time current/voltage of single luminaire
- Print test results (remote printer)
In
-
addition, LED indicators display the following status:
Power on
Emergency mode
General fault
System fault
Test in progress
Disable luminaire groups
Fault indication in luminaire groups 1-16
DIMENSIONS
12 Cable
Entry Points
L
A
C
B
H
MUTE
BUZZER
Emergency Luminaires - Testing Systems
1
2
3
4
SCROLL
5
D
H (mm)
L (mm)
D (mm)
A
B
C
270
332
90
283
242
198
LUMINAIRE INTERFACE
Compact module fitted into all emergency luminaires to be
connected to the system. Self-contained and slave luminaire
versions. Requires allocation of address by hand held programmer,
prior to being connected to data BUS cable.
Dims: L54xW38xD24mm.
HAND HELD PROGRAMMER
Used to program address into all interface devices. Simple to use.
Sprung probes are held against interface contacts and program
button pressed until display confirms successful programming.
Display increments address automatically by 1, ready for next
interface. Address number can be manually allocated, if required,
using “Tens” and “Units” buttons. Can also be used to read back
the address of a programmed interface.
Dims: L152xW82xD35mm.
Luminaire interface
201
PRINTER
High speed thermal printer for connection directly to a dedicated
panel, or as a network printer using separate interface. Provides
print out of system status, event log as faults occur, or test results.
Virtually silent operation. Requires adjacent mains power socket
outlet for connection of power supply unit.
Dims: L155xW100xD75mm.
MAINS CHANGEOVER COMBINED MODULE
Used to changeover from normal mains to emergency 230V AC
supply. EasiCheck™ addressable version of ACM1.
Dims: L215xW37xD30mm.
Hand held programmer
OTHER INTERFACES & DEVICES
Emergency Luminaires - Testing Systems
There is a comprehensive range of network interfaces and devices
for self-contained and central power supply installations that are
available to meet project requirements. For information, please
contact our Technical Support and Application department.
Tel: 01302 303350.
LUMINAIRES
EasiCheck™ can be integrated into the majority of Menvier and
JSB self contained and slave emergency luminaires or exit signs
and most Crompton Lighting emergency converted fluorescent
luminaires (when powered via a static inverter). See the individual
product entries for details of compatibility.
Suitable mains luminaires that are intended for use with a static
inverter system can usually be fitted with an EasiCheck™ slave
interface. For further information please contact our Technical
Support and Application department. Tel: 01302 303350.
EasiCheck™ printer
EASICHECK™
EASICHECK™
TEST PROGRAMMES
EasiCheck™ provides automatic testing that conforms and exceeds the current British Standard BS5266 Part 1 (1999) and the European
Standard EN50172. Other test regimes can also be programmed as required.
BS 5266 TEST REQUIREMENTS
EASICHECK TEST SCHEDULE
Daily
Check for correct operation
Continual
Monitoring of battery and charger status
Monthly
Functionality test not exceeding 25% of rated duration
Weekly or Monthly (selectable)
Test emergency circuit for up to 5 minutes
Six Monthly
Test of at least 1 hour for a 3 hour rated system
Six Monthly
Full duration discharge test
Three Yearly
Full duration discharge test
Yearly
Full duration discharge test
Subsequently
After first 3 years, an annual duration discharge test is required
202
Note: The Fire Precautions (Workplace) Regulations 1997 and EN50172 omit the six monthly 1 hour test, replacing it with an annual full duration discharge test after the first year and every year thereafter
It is recommended that discharge tests are performed at a time of
least risk, such as outside normal working hours, so that following
the test the batteries can be re-charged prior to re-occupation. This
can be difficult in permanently occupied premises. To overcome
this, EasiCheck™ luminaires can be allocated into 1 of up to 16
test groups and the testing of each group staggered. Adjacent
luminaires would be allocated to different groups in order to
provide full duration emergency lighting coverage at all times.
Following a genuine mains failure that has occurred in the previous
24 hours, the next scheduled test is automatically delayed for a
further 24 hours, to allow sufficient time for the batteries to
recharge. Manual tests are also inhibited for 24 hours following a
genuine mains failure or scheduled test. All test results can be
downloaded to an optional printer.
EasiCheck™ wiring schematic, demonstrating how allocation of test groups can stagger the testing of adjacent luminaires
1
4
3
Emergency Luminaires - Testing Systems
2
2
4
1
1
3
2
3
2
2
1
3
4
SYSTEM DESIGN & INSTALLATION
• Determine the number and type of EasiCheck™ compatible
emergency luminaires to be used, using the spacing charts at
the rear of this catalogue
• Specify the luminaires to be complete with EasiCheck™
addressable interface modules
• Locate the control panel in a suitable clean, dry environment,
such as a maintenance office
• Address all luminaires and interface devices as applicable
using the hand held programmer
• Connect data BUS cable. Cable should be 2 core twisted
pair, typically 1.0 - 2.5mm2 depending on volt drop limitations.
Contact Technical Support for full details of the required cable
specification. Polarity must be maintained throughout.
• Circuit configuration for data cable can be a ring, radial or
a preferred combination of a ring with multiple radial spurs
• Short circuit isolators are incorporated into the panel as
standard. Further isolators can be added to the circuit,
if required, to minimise loss of communication due to a
short circuit and make fault finding easier. Note: Loss of
communication does NOT affect the integrity of the emergency
luminaire operation
• The panel is set to auto learn the devices connected to it.
The panel can then be commissioned by Cooper Lighting
and Security, using a PC to download address, group, type of
luminaire, number of cells, duration, descriptive address text
and test times
• The panel can be used to adjust test times, initiate manual tests,
display luminaire voltage and current and print out event logs or
test results
203
EasiCheck™ typical schematic diagram
Optional P.C. Interface
Optional
Printer
Optional
Isolator
Optional
Isolator
Optional
Isolator
Optional
Isolator
Optional
Isolator
Optional Printer Interface
Optional EasiCheck™ Printer
(can also be directly connected to panel)
EASICHECK™
Emergency Luminaires - Testing Systems
Optional
P.C.
EASICHECK™
ENHANCED OPTIONS
EasiCheck™ can be used as a stand alone system or can be
networked, with up to 63 panels being linked. The management
of larger installations with multiple panels can be simplified by
interfacing the system with a PC based monitoring or graphical
control system. Cooper Lighting and Security offer two software
systems for use with EasiCheck™.
• Site Monitoring Software
-
204
-
Simple windows based, text driven package
Monitors the status of all panels and luminaires
All system events and tests are listed as they happen
Identifies the address panel/luminaire and location where a
fault has occurred
Tests can be started or stopped
Panels can be reset following clearing of faults
Alarm buzzer can be muted
-
Comprehensive report menu
Example of site monitoring software
• Colour Graphics
-
Advanced windows based, graphics package
Site plans can be imported
Monitors the status of all panels and luminaires
All system events and tests are listed as they happen
Identifies the address panel/luminaire and location where a
fault has occurred
Offers full PC control of panel functionality
Status, testing and faults can be displayed graphically on site
plans
Reports can be easily created and printed
Emergency Luminaires - Testing Systems
Example of colour graphic software
CATALOGUE NUMBERS
Description
Cat. No.
Control panel - self contained systems
EC1001
Control panel - central power systems
EC1002
Interface module - self contained luminaires
EC110
Interface module - slave luminaires
EC125
Addressable mains changeover relay
EC140
Network card (fitted inside control panel)
EC150/151
Hand held programmer
EC160
Printer
EC170
Example of colour graphic software