FP120-Z1 power supply kit (70 W) – Data sheet A6V10416448

advertisement
Cerberus™ FIT
Power supply kit (70 W)
FP120-Z1
This standalone power supply is intended for decentralized supply to external devices.
FP120-Z1 has an integrated operating and fault indicator, and makes it possible to
forward faults via potential-free contacts.
●
●
●
●
●
●
●
●
●
●
A6V10416448_f_en_-2016-03-23
Output power 70 W
Two separately fused, reactionless DC 24 V outputs, limited to 2 A in total
Short-circuit-proof
Current limited
Mains voltage monitored
Batteries monitored
Battery charging with temperature compensation
Uninterruptible power supply in battery operation
Supplies other consumers (complies with EN 54 and VdS)
AC 230 V or AC 115 V
Building Technologies
Control Products and Systems
Properties
●
●
●
●
●
●
●
●
●
Integrated operating and fault indicator.
Fault forwarding possible via potential-free contacts.
The power supply (70 W) converts mains voltage to system voltage and charges the
batteries.
The DC 24 V system voltage is electrically isolated.
For the supply of consumers in accordance with EN 54-4 and VdS.
The output voltage is short-circuit-proof and battery charging is current-limited.
Must not be connected in parallel.
The battery charge voltage is regulated with temperature compensation.
A jumper can be used to switch the mains voltage from AC 230 V to AC 115 V.
Monitoring of mains voltage and the batteries
● A failure of the AC 230 V supply voltage or a higher internal battery resistance are
detected and an error message is generated.
Uninterruptible power supply
● If the mains voltage fails, the supply switches automatically from mains operation to
battery operation.
Protecting the battery against total discharge
● When the final voltage is reached, the battery switches off automatically.
Use
The power supply kit FP120-Z1 is for the following use:
● Standalone power supply for decentralized supply to external devices (DC 24 V) in
accordance with EN 54-4 and VdS.
Possible configuration
● Installation of various battery types from 7 Ah to 17 Ah
● Installation of input/output module FDCIOxxx
● Installation of a TS35 U-rail to mount several modules, such as FDCIOxxx/Z3B171
2
Building Technologies
Fire Safety
Cerberus™ FIT
A6V10416448_f_en_-2016-03-23
5
6
7
8
4
3
9
2
10
1
Installation situation FP120-Z1
Building Technologies
Fire Safety
1
LED function display
6
Connection card FP120-Z1 mainboard
2
Battery
7
U-rail TS35, 122 mm long
3
Housing
8
Installation positions for input/output
modules and relay modules
4
Power supply (70 W)
9
Front panel
5
Mains connection terminals
10
Cover cap
Cerberus™ FIT
3
A6V10416448_f_en_-2016-03-23
Components / accessories / spare parts
Component
Type
Designation
Order no.
Weight
FP120-Z1
Power supply kit (70 W)
S4400-S122-A1
3,920 kg
Scope of delivery
The power supply kit (70 W) is supplied mounted with housing, a left-hand installation frame
with integrated power supply (70 W) FP2015 and FP120-Z1 mainboard, a right-hand
installation frame for optional components, and a pre-wired connection for the battery, as
well as mounting instructions for wall mounting and optional components: Document ID
A6V10393173.
Accessories
The following accessories are not included in the scope of delivery and must be ordered
separately.
Type
Designation
Order no.
Weight
TS35/122
U-rail TS35/7.5/122
BPZ:5644780001
0.041 kg
FA2003-A1
Battery (12 V, 7 Ah, VDS)
A5Q00019353
2.450 kg
FA2004-A1
Battery (12 V, 12 Ah, VDS)
A5Q00019354
3.930 kg
FA2005-A1
Battery (12 V, 17 Ah, VDS)
A5Q00019677
5.640 kg
Type
Designation
Order no.
Weight
FP2015-A1
Power supply (70 W)
S54400-B121-A1
0.576 kg
Spare part
4
Building Technologies
Fire Safety
Cerberus™ FIT
A6V10416448_f_en_-2016-03-23
Product documentation
Document ID
Title
A6V10393194
Power supply kit A (70 W) FP120-Z1 – Technical manual
A6V10393173
Power supply kit A (70 W) FP120-Z1 – Mounting
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following Internet address:
http://siemens.com/bt/download
Building Technologies
Fire Safety
Cerberus™ FIT
5
A6V10416448_f_en_-2016-03-23
Notes
Disposal
This equipment is manufactured using materials and procedures which comply
with current environmental protection standards as best as possible. More
specifically, the following measures have been undertaken:
● Use of reusable materials
● Use of halogen-free plastics
● Electronic parts and synthetic materials can be separated
Larger plastic parts are labeled according to ISO 11469 and ISO 1043. The
plastics can be separated and recycled on this basis.
Electronic parts and batteries must not be disposed of with domestic waste.
● Take electronic parts and batteries to local collection points or recycling
centers.
● Contact local authorities for more information.
● Observe national requirements for disposing of electronic parts and
batteries.
6
Building Technologies
Fire Safety
Cerberus™ FIT
A6V10416448_f_en_-2016-03-23
Technical data
Mains supply
System supply output
Voltage
AC 97…127 V,
AC 196…253 V,
50 / 60 Hz
Current
0.5…1 A
Power consumption
Max. 90 VA
Designation
'AUX 1', 'AUX 2'
Voltage
2x DC 20.2…28.6 V, depending on charge
and temperature
Current (sum of both outputs)
Battery supply output
Mains fault monitoring
signal
Battery fault monitoring
signal
Connections
Building Technologies
Fire Safety
●
Maximum output current with
battery charge (Imax a)
0.9 A
●
Maximum output current without
battery charge (Imax b)
2.0 A
●
Minimum output current (I min )
0.05 A
Output power
70 W
Ripple
Max. 5 %
Designation
'Accu'
Voltage
DC 20.5…28.6 V, depending on charge
and temperature
Charging current
Max. 1.6 A, the charging current is reduced
at full load
Connectable batteries
2x 12 V / 7…17 Ah
Battery types recommended by Siemens in
accordance with
'Components / accessories / spare parts'
chapter
Battery internal resistance (Rimax)
Max. 1 Ω, batteries incl. line
Batteries are monitored for
●
●
●
Low discharge protection
Battery voltage DC 20.5…21.0 V
Designation
'MAINS'
Active in event of
●
Design
Potential-free changeover contact
DC 30 V/1 A
Designation
'BATT'
Active in event of
●
●
Design
Potential-free changeover contact
DC 30 V/1 A
Mains supply, battery supply and
monitoring signals
Plug-type connection and terminals
0.2…2.5 mm2
Cerberus™ FIT
Short-circuit
Open line
Presence
No mains voltage, signaling within 10 s
Battery fault
Battery voltage <DC 21.0 V
7
A6V10416448_f_en_-2016-03-23
Mechanical data
Approvals
0786
15
Dimensions (W x H x D)
430 x 399 x 124 mm
Weight
3,920 kg, without batteries
Housing color
∼ RAL 9010 pure white
Protection category (IEC 60529)
IP 30
VdS
G214130
LPCB
Pending
Siemens Switzerland Ltd, Gubelstrasse 22
CH-6301 Zug, Switzerland
Technical data: see doc. A6V10393194
FP120 - Power Supply Equipment 24V/70W for use in fire detection and fire alarm systems installed in buildings
FP120-Z1
305/2011/EU (CPR): EN 54-4 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2014/35/EU (LVD): EN 60950-1 ; 2011/65/EU (RoHS): EN 50581
Declared performance and conformity can be seen in the Declaration of Performance and the EC Declaration of Conformity,
which is obtainable via the Customer Support center: Tel. +49 89 9221-8000 or http://siemens.com/bt/download
DoP No.: 0786-CPR-21414; DoC No.: CED-FP120
Dimensional drawing
350
40
49
310
40
40
55
Issued by
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies
8
Building Technologies
Fire Safety
Document ID
A6V10416448_f_en_-Edition
2016-03-23
320
55
© Siemens Switzerland Ltd, 2014
Technical specifications and availability subject to change without notice.