Cerberus™ FIT Power supply kit (70 W) FP120-Z1 This standalone power supply is intended for decentralized supply to external devices. FP120-Z1 has an integrated operating and fault indicator, and makes it possible to forward faults via potential-free contacts. ● ● ● ● ● ● ● ● ● ● A6V10416448_f_en_-2016-03-23 Output power 70 W Two separately fused, reactionless DC 24 V outputs, limited to 2 A in total Short-circuit-proof Current limited Mains voltage monitored Batteries monitored Battery charging with temperature compensation Uninterruptible power supply in battery operation Supplies other consumers (complies with EN 54 and VdS) AC 230 V or AC 115 V Building Technologies Control Products and Systems Properties ● ● ● ● ● ● ● ● ● Integrated operating and fault indicator. Fault forwarding possible via potential-free contacts. The power supply (70 W) converts mains voltage to system voltage and charges the batteries. The DC 24 V system voltage is electrically isolated. For the supply of consumers in accordance with EN 54-4 and VdS. The output voltage is short-circuit-proof and battery charging is current-limited. Must not be connected in parallel. The battery charge voltage is regulated with temperature compensation. A jumper can be used to switch the mains voltage from AC 230 V to AC 115 V. Monitoring of mains voltage and the batteries ● A failure of the AC 230 V supply voltage or a higher internal battery resistance are detected and an error message is generated. Uninterruptible power supply ● If the mains voltage fails, the supply switches automatically from mains operation to battery operation. Protecting the battery against total discharge ● When the final voltage is reached, the battery switches off automatically. Use The power supply kit FP120-Z1 is for the following use: ● Standalone power supply for decentralized supply to external devices (DC 24 V) in accordance with EN 54-4 and VdS. Possible configuration ● Installation of various battery types from 7 Ah to 17 Ah ● Installation of input/output module FDCIOxxx ● Installation of a TS35 U-rail to mount several modules, such as FDCIOxxx/Z3B171 2 Building Technologies Fire Safety Cerberus™ FIT A6V10416448_f_en_-2016-03-23 5 6 7 8 4 3 9 2 10 1 Installation situation FP120-Z1 Building Technologies Fire Safety 1 LED function display 6 Connection card FP120-Z1 mainboard 2 Battery 7 U-rail TS35, 122 mm long 3 Housing 8 Installation positions for input/output modules and relay modules 4 Power supply (70 W) 9 Front panel 5 Mains connection terminals 10 Cover cap Cerberus™ FIT 3 A6V10416448_f_en_-2016-03-23 Components / accessories / spare parts Component Type Designation Order no. Weight FP120-Z1 Power supply kit (70 W) S4400-S122-A1 3,920 kg Scope of delivery The power supply kit (70 W) is supplied mounted with housing, a left-hand installation frame with integrated power supply (70 W) FP2015 and FP120-Z1 mainboard, a right-hand installation frame for optional components, and a pre-wired connection for the battery, as well as mounting instructions for wall mounting and optional components: Document ID A6V10393173. Accessories The following accessories are not included in the scope of delivery and must be ordered separately. Type Designation Order no. Weight TS35/122 U-rail TS35/7.5/122 BPZ:5644780001 0.041 kg FA2003-A1 Battery (12 V, 7 Ah, VDS) A5Q00019353 2.450 kg FA2004-A1 Battery (12 V, 12 Ah, VDS) A5Q00019354 3.930 kg FA2005-A1 Battery (12 V, 17 Ah, VDS) A5Q00019677 5.640 kg Type Designation Order no. Weight FP2015-A1 Power supply (70 W) S54400-B121-A1 0.576 kg Spare part 4 Building Technologies Fire Safety Cerberus™ FIT A6V10416448_f_en_-2016-03-23 Product documentation Document ID Title A6V10393194 Power supply kit A (70 W) FP120-Z1 – Technical manual A6V10393173 Power supply kit A (70 W) FP120-Z1 – Mounting Related documents such as environmental declarations, CE declarations, etc., can be downloaded at the following Internet address: http://siemens.com/bt/download Building Technologies Fire Safety Cerberus™ FIT 5 A6V10416448_f_en_-2016-03-23 Notes Disposal This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as possible. More specifically, the following measures have been undertaken: ● Use of reusable materials ● Use of halogen-free plastics ● Electronic parts and synthetic materials can be separated Larger plastic parts are labeled according to ISO 11469 and ISO 1043. The plastics can be separated and recycled on this basis. Electronic parts and batteries must not be disposed of with domestic waste. ● Take electronic parts and batteries to local collection points or recycling centers. ● Contact local authorities for more information. ● Observe national requirements for disposing of electronic parts and batteries. 6 Building Technologies Fire Safety Cerberus™ FIT A6V10416448_f_en_-2016-03-23 Technical data Mains supply System supply output Voltage AC 97…127 V, AC 196…253 V, 50 / 60 Hz Current 0.5…1 A Power consumption Max. 90 VA Designation 'AUX 1', 'AUX 2' Voltage 2x DC 20.2…28.6 V, depending on charge and temperature Current (sum of both outputs) Battery supply output Mains fault monitoring signal Battery fault monitoring signal Connections Building Technologies Fire Safety ● Maximum output current with battery charge (Imax a) 0.9 A ● Maximum output current without battery charge (Imax b) 2.0 A ● Minimum output current (I min ) 0.05 A Output power 70 W Ripple Max. 5 % Designation 'Accu' Voltage DC 20.5…28.6 V, depending on charge and temperature Charging current Max. 1.6 A, the charging current is reduced at full load Connectable batteries 2x 12 V / 7…17 Ah Battery types recommended by Siemens in accordance with 'Components / accessories / spare parts' chapter Battery internal resistance (Rimax) Max. 1 Ω, batteries incl. line Batteries are monitored for ● ● ● Low discharge protection Battery voltage DC 20.5…21.0 V Designation 'MAINS' Active in event of ● Design Potential-free changeover contact DC 30 V/1 A Designation 'BATT' Active in event of ● ● Design Potential-free changeover contact DC 30 V/1 A Mains supply, battery supply and monitoring signals Plug-type connection and terminals 0.2…2.5 mm2 Cerberus™ FIT Short-circuit Open line Presence No mains voltage, signaling within 10 s Battery fault Battery voltage <DC 21.0 V 7 A6V10416448_f_en_-2016-03-23 Mechanical data Approvals 0786 15 Dimensions (W x H x D) 430 x 399 x 124 mm Weight 3,920 kg, without batteries Housing color ∼ RAL 9010 pure white Protection category (IEC 60529) IP 30 VdS G214130 LPCB Pending Siemens Switzerland Ltd, Gubelstrasse 22 CH-6301 Zug, Switzerland Technical data: see doc. A6V10393194 FP120 - Power Supply Equipment 24V/70W for use in fire detection and fire alarm systems installed in buildings FP120-Z1 305/2011/EU (CPR): EN 54-4 ; 2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2014/35/EU (LVD): EN 60950-1 ; 2011/65/EU (RoHS): EN 50581 Declared performance and conformity can be seen in the Declaration of Performance and the EC Declaration of Conformity, which is obtainable via the Customer Support center: Tel. +49 89 9221-8000 or http://siemens.com/bt/download DoP No.: 0786-CPR-21414; DoC No.: CED-FP120 Dimensional drawing 350 40 49 310 40 40 55 Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies 8 Building Technologies Fire Safety Document ID A6V10416448_f_en_-Edition 2016-03-23 320 55 © Siemens Switzerland Ltd, 2014 Technical specifications and availability subject to change without notice. Cerberus™ FIT A6V10416448_f_en_-2016-03-23