www.us.schneider-electric.com
QO® Miniature Circuit
Breakers
QO® Plug-On Circuit Breakers
Class 685, 690, 730, 912, 950 / Refer to Catalog: 0730CT9801
QO-HID
QO arc-fault circuit breakers provide branch feeder
protection (i.e. QO115AFI) or combination protection (i.e.
QO115CAFI) as required by the NEC and local code
adoption, and comply with UL1699.
HID circuit breakers are for use on circuits feeding
fluorescent and high intensity discharge (HID) lighting
systems such as mercury vapor, metal halide, or high
pressure sodium. These circuit breakers are physically
interchangeable with QO circuit breakers.
Table 1.6:
1P
QO-AFI
QO Arc Fault Circuit Breakersa
Circuit Breaker Type Ampere
Rating
Branch Feeder Arcfault Interrupter
Combination Arc-fault
Interrupter
New!
1P
QO-GFI
1P 120 Vac
1P 120 Vac
10 k AIR
22 k AIR
1 Space Required
1 Space Required
Cat. No.
QO115AFI
QO120AFI
QO115CAFI
QO120CAFI
15
20
15
20
$ Price
Cat. No.
$ Price
160.00 QO115VHAFI 315.00
160.00 QO120VHAFI 315.00
188.00 QO115VHCAFI 356.00
188.00 QO120VHCAFI 356.00
QO-GFI Circuit Breakers
Qwik-Gard Circuit Breakers
With Ground Fault Circuit Interrupter
2P
QO-GFI
15
20
25
30
40
50
60
2P Common Trip
120/240 Vac
1P 120 Vac
Ampere
Ratingc
10 k AIR
22 k AIR
10 k AIR
1 Space Required
1 Space Required
2 Spaces Required
Cat. No. $ Price
QO115GFI 155.00
QO120GFI 155.00
QO125GFI 155.00
QO130GFI 155.00
—
—
—
—
—
—
Cat. No.
$ Price
QO115VHGFI 321.00
QO120VHGFI 321.00
QO125VHGFI 321.00
QO130VHGFI 321.00
—
—
—
—
—
—
Cat. No.
QO215GFI
QO220GFI
QO225GFI
QO230GFI
QO240GFI
QO250GFI
QO260GFId
$ Price
275.00
275.00
275.00
275.00
275.00
275.00
275.00
QO-EPD
QO-K Key
Operated
QO-EPD circuit breakers provide overload and short circuit
protection combined with Class B ground fault protection.
They are designed to provide ground fault protection of
equipment at a 30 milliampere level. They are not
designed to protect people from electrical shock.
Table 1.8:
QO-EPD Circuit Breakers
1P
120 Vac
Ampere
Ratingc
QO
1P
With Shunt Trip
15
20
25
30
40
50
60
2P Common Trip
120/240 Vac
10 k AIR
10 k AIR
1 Space Required
2 Spaces Required
Cat. No.
QO115EPD
QO120EPD
QO125EPD
QO130EPD
—
—
—
$ Price
Cat. No.
273.00 QO215EPD
273.00 QO220EPD
273.00 QO225EPD
273.00 QO230EPD
—
QO240EPD
—
QO250EPD
—
QO260EPDd
$ Price
440.00
440.00
440.00
440.00
440.00
440.00
440.00
QO-SWN
Switch Neutral Common Trip 2002 NEC® 514.11
Table 1.9:
Two-wire
QO-SWN
Three-wire
QO-SWN
© 2007 Schneider Electric
All Rights Reserved
10
15
20
25
30
40
50
Ampere
Ratingc
$ Price
63.00
63.00
63.00
63.00
63.00
63.00
63.00
Cat. No.
QO310SWN
QO315SWN
QO320SWN
QO325SWN
QO330SWN
QO340SWN
QO350SWN
DE2A
$ Price
95.00
95.00
95.00
95.00
95.00
95.00
95.00
Discount
Schedule
10 k AIR
10 k AIR
2 Spaces Required
3 Spaces Required
Table 1.11:
QO-K Circuit Breakers
120 Vac—10 k AIR (1 Space Required)
Ampere
Rating c
10
15
20
25
30
Cat. No.
$ Price
QO110K
QO115K
QO120K
QO125K
QO130K
109.00
109.00
109.00
109.00
109.00
QO-HM
High magnetic trip circuit breakers are recommended for
applications where high initial inrush may occur and for
individual dimmer applications.
Table 1.12:
QO-HM Circuit Breakers
1P
Ampere
Ratingc
Cat. No
120 Vac—10 k AIR
15 A
20 A
$ Price
QO115HMab
QO120HMab
20.40
20.40
Non-automatic (Standard) Miniature Switches
Miniature non-automatic switches have the same physical
packaging as miniature circuit breakers, but open only
when the handle is switched to the OFF position.
Non-automatic switches provide no overcurrent protection
or short circuit protection. They must not be used on
systems that have an available fault current greater than
the values listed in the table.
Non-automatic switches are UL Listed per UL 1087 and
are CSA certified.
Table 1.13:
QO Non-Automatic Miniature Switches,
240 Vac 10 kA
60
100
a
10 k AIR
3 Spaces Required
10 k AIR
1 Space Required
Key operated QO circuit breakers are available in singlepole construction and can be mounted in any single-pole
space which will accept a standard QO. These circuit
breakers can be turned ON or OFF or to RESET with a
special key (catalog number QOK10) included with the
circuit breaker. These circuit breakers are UL Listed and
available as shown in the table.
3 Wire 120/240 Vac
2 Spaces Required
3P Common Trip
240 Vac
QO-K
Ampere
Rating
10 k AIR
Cat. No.
QO210SWN
QO215SWN
QO220SWN
QO225SWN
QO230SWN
QO240SWN
QO250SWN
2P Common Trip
120/240 Vac
Cat. No.
$ Price Cat. No. $ Price
Cat. No.
$ Price
QO115HIDb
25.40 QO215HID
58.00 QO315HID 200.00
QO120HIDb
25.40 QO220HID
58.00 QO320HID 200.00
QO125HID
25.40 QO225HID
58.00 QO325HID 200.00
QO130HID
25.40 QO230HID
58.00 QO330HID 200.00
QO140HID
25.40 QO240HID
58.00
—
—
QO150HID
25.40 QO250HID
58.00
—
—
15
20
25
30
40
50
QO-SWN Circuit Breakers
2 Wire 120 Vac
Ampere
Ratingc
QO-HID Circuit Breakers
1P 120/240 Vac
QO-GFI
Qwik-Gard® circuit breakers provide overload and short
circuit protection, combined with Class A ground fault
protection. Class A denotes a ground fault circuit
interrupter that will trip when a fault current to ground is 6
mA or more, for people protection. Do not connect to more
than 250 feet of load conductor for the total one-way run to
prevent nuisance tripping.
Table 1.7:
Table 1.10:
b
c
d
2P
Cat. No.
QO200
QO2000
3P
$ Price
46.90
133.00
Cat. No.
QO300
QO3000
$ Price
165.00
244.00
UL Listed as HACR type for use with air conditioning, heating and
refrigeration equipment having motor group combinations and marked
for use with HACR type circuit breakers.
UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac
fluorescent lighting loads.
10–30 A circuit breakers are suitable for use with 60oC or 75oC
conductors. 35–60 A circuit breakers are suitable for use with 75oC
conductors.
Suitable only for feeding 240 Vac and 208 Vac loads. Does not contain
load neutral connection.
Interrupting Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 7-2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 7-12
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Page 7-53
1-3
1
QO® Arc-Fault Circuit Breaker
LOAD CENTERS
FOR CURRENT INFORMATION
QO® Miniature Circuit
Breakers
QO® Plug-On Circuit Breakers
Class 730, 731, 733 / Refer to Catalog: 0730CT9801
www.us.schneider-electric.com
FOR CURRENT INFORMATION
1
®
Square D brand QO miniature circuit breakers are plug-on products for use in QO load centers, NQOD panelboards, NQOD OEM interiors or
Speed-D® switchboard distribution panels. Bolt-on QOB circuit breakers are for use in NQOD panelboards or interiors.a
The Square D exclusive Qwik-Open® mechanism, with a trip reaction within 1/60th of a second, is standard on all 1P 15A and 20 A circuit breakers.
QO 1P
Table 1.1:
LOAD CENTERS
Amperes
Rating b
1 Space Required
QOT 1P Tandem
1 Space Required
QO 2P
2 Spaces Required
QO2200 2P 200 A
4 Spaces Required
QO 3P
3 Spaces Required
10 k AIR
10 A
15 A
20 A
25 A
30 A
35 A
40 A
45 A
50 A
60 A
70 A
80 A
90 A
100 A
110 A
125 A
150 A
Plug-On Circuit Breakers
Table 1.2:
1P—120/240 Vac
2P—120/240 Vac
Common Trip
Cat. No.
Cat. No.
QO110
QO115 de
QO120de
QO125d
QO130d
QO135 d
QO140 d
QO145 d
QO150 d
QO160 d
QO170 d
—
—
—
—
—
—
$ Price
19.40
19.40
19.40
19.40
19.40
19.40
19.40
19.40
19.40
19.40
44.70
—
—
—
—
—
—
QO210
QO215d
QO220d
QO225d
QO230d
QO235d
QO240d
QO245d
QO250d
QO260d
QO270d
QO280d
QO290d
QO2100d
QO2110d
QO2125d
2P—240 Vac c
Common Trip
$ Price
Cat. No.
44.70
—
44.70 QO215H
44.70 QO220H
44.70 QO225H
44.70 QO230H
44.70
—
44.70 QO240H
44.70
—
44.70 QO250H
44.70 QO260H
89.00 QO270H
126.00 QO280H
126.00 QO290H
126.00 QO2100H
285.00
—
285.00
—
3P—240 Vac
Common Trip
$ Price
Cat. No.
$ Price
—
133.00
133.00
133.00
133.00
—
133.00
—
133.00
133.00
149.00
210.00
210.00
210.00
—
—
QO310
QO315d
QO320d
QO325d
QO330d
QO335d
QO340d
QO345d
QO350d
QO360d
QO370d
QO380d
QO390d
QO3100d
—
—
165.00
165.00
165.00
165.00
165.00
165.00
165.00
165.00
165.00
165.00
210.00
244.00
244.00
244.00
—
—
QO2150dfk
327.00
—
—
—
—
175 A
—
—
QO2175dfk
200 A
—
—
QO2200dfk
Molded Case Switch 60 A max.–240 Vac
—
Molded Case Switch 100 A max.–240
—
Vac
22 k AIRd
15 A
QO115VH e
42.30
QO215VHg
20 A
QO120VH e
42.30
QO220VHg
25 A
QO125VH
48.50
QO225VHg
30 A
QO130VH
48.50
QO230VHg
327.00
327.00
—
—
—
QO200
—
—
46.90
—
—
QO300
—
—
165.00
QO3000i
244.00
—
QO2000i 133.00
97.00
97.00
97.00
97.00
—
—
—
—
—
—
—
—
QO315VHg
QO320VHg
QO325VHg
QO330VHg
247.00
247.00
247.00
247.00
Ampere Rating
Poles
Suffix
10–30 A
35–60 A
35–50 A
70–110 A
60–100 A
1, 2, 3
1,2
3
2
3
5237
Table 1.3:
5238
5273
Wire Sizesb
Circuit Breaker Ampere Rating
Type
10–30 A
QO
10–30 A
1P
35–70 A
10–30 A
10–30 A
QO
35–70 A
2P
80–125 A
150–200 A
QO
3P
QOB-VH
10–30 A
35–70 A
80–125 A
110–150 A
QOT
15–20 A
12–8 Al 14–8 Cu
15–30 A
40, 50, 60 A
10–60 A
12–8 Al 14–8 Cu
12–4 Al 14–6 Cu
12–2 Al 14–2 Cu
QO-PL
Table 1.4:
QOT Tandem Circuit
Breakers
40 A
—
—
QO240VHg
97.00
—
—
QO340VHg
247.00
50 A
—
—
QO250VHg
97.00
—
—
QO350VHg
247.00
Ampere Ratingb
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
QO260VHg
QO270VHg
QO280VHg
QO290VHg
QO2100VHgh
QO2110VHgh
QO2125VHgh
QO2150VHfgk
QO2175VHfgk
QO2200VHfgk
97.00
149.00
210.00
210.00
210.00
689.00
689.00
707.00
707.00
707.00
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
QO360VHg
QO370VHg
QO380VHg
QO390VHg
QO3100VHg
—
—
—
—
—
247.00
318.00
353.00
353.00
353.00
—
—
—
—
—
1P—120/240 Vac
15 A & 15 A
QOT1515
15 A & 20 A
QOT1520
20 A & 20 A
QOT2020
2P—120/240 Vac Common Trip
—
—
—
—
—
—
QOH240 i
QOH245 i
QOH250i
211.00
211.00
211.00
—
—
—
—
—
—
—
—
—
—
—
—
60 A
70 A
80 A
90 A
100 A
110 A
—
—
—
—
—
—
—
—
—
—
—
—
QOH260i
QOH270
QOH280
QOH290
QOH2100
QOH2110i
211.00
352.00
434.00
434.00
434.00
926.00
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
125 A
—
—
QOH2125
926.00
—
—
—
—
60 A
70 A
80 A
90 A
100 A
110 A
125 A
150 A
175 A
200 A
42 k AIRd
40 A
45 A
50 A
DE2A
Discount
Schedule
Wire Size
(AWG/kcmil)
14–8 Al/Cu
(2) 14–10 Cu
8–2 Al/Cu
14–8 Al/Cu
(2) 14–10 Cu
8–2 Al/Cu
4–2/0 Al/Cu
4–300 Al/Cu
14–8 Al/Cu, (2) 14-10
Cu
8–2 Al/Cu
4–2/0 Al/Cu
4–300 Al/Cu
QO-AFI, QO-GFI &
QO-EPD
Cat. No.d
$ Price
38.60
38.60
38.60
Order two QOT1515 or QOT2020 circuit breakers and
handle tie QOTHT for common switching of center two
poles.
Table 1.5:
Replacement Tandem
Circuit Breakers
For Use in Old Style Non-Class CTL
QO Load Centers—10 k AIR
Ampere Ratingb
Cat. No.d
$ Price
1P—120/240 Vac—1 Space Required
15 &A 15 A
QO1515
48.50
15 A & 20 A
QO1520
48.50
20 A & 20 A
QO2020
48.50
20 A & 30 A
QO2030
48.50
30 A & 20 A
QO3020
48.50
Two 1P Individual Trip—120/240 Vac—2 Spaces
Required
65 k AIRd
15 A & 15 A
15 A
QH115e
78.00
QH215
195.00
—
—
QH315d
338.00
15 A & 20 A
20 A
QH120e
78.00
QH220
195.00
—
—
QH320
338.00
20 A & 20 A
25 A
QH125i
78.00
QH225i
195.00
—
—
QH325i
338.00
20 A & 30 A
30 A
QH130
78.00
QH230
195.00
—
—
QH330
338.00
30 A & 20 A
a
See Digest Section 1 for load centers, and Section 9 for panelboards and interiors.
QOT
Tandem
b
10–30 A circuit breakers are suitable for use with 60oC or 75oC conductors. 35–125 A circuit breakers
are suitable for use with 75oC conductors.
c
UL Listed 5 k AIR on corner grounded Delta systems.
d
UL Listed as HACR type for use with air conditioning, heating and refrigeration equipment having motor
group combinations and marked for use with HACR type circuit breakers.
e
UL Listed as SWD (switching duty) rated. Suitable for switching 120 Vac fluorescent lighting loads.
f
Requires four spaces (1 AWG–300 kcmil Al/Cu.) Suitable for switching 120 Vac fluorescent lighting loads.
g
UL Listed for use ahead of QO, QO-GFI, QO-EPD, QOT, and QO-PL 10 k AIR circuit breakers to permit
their application at 22 kA fault level.
h
100 A maximum branch mounted opposite.
i
Order only. Contact your local Field Office.
Pan Rail Slot
j
Includes two circuit breakers (one QO2030 and one QO3020) and handle tie QOTHT.
k
Not suitable for use in 3Ø panels. Use only in 1Ø panel rated 150 A or greater.
Interupting Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-12
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7-53
1-2
QO/QOB Ring Terminal
(20% $ Price Adder)—Factory Installed Only
Order Two QO1515 or QO2020 circuit
breakers and handle tie QOTHT
—
QO20303020j
—
Mounting Cam
Rail Bead
—
89.00
—
Current limiting QOT
tandem circuit
breakers have a
mounting cam as
shown. Installation
into a QO load
center can only be
made in those
positions having a
mounting pan rail
slot. Meets
Paragraph 408.15 of
the NEC®. UL Listed
as Class CTL
© 2007 Schneider Electric
All Rights Reserved
Selection Information
Class 500, 600
www.SquareD.com
For the most up-to-date information
QO® Circuit Breakers
HOM Circuit Breakers
HOM
HOMAFI
HOMGFI
HOMEPD
HOMT
QO
QOB
... ... ... ...
2
3
1
...
... ...
...
...
...
...
...
...
...
...
1
1
1
1
2
1
1
2
2,3l 1,2
3
10
10
10
10
10
10
10
10
10
10
10
22
22
22
22
22
65
65
10
10
22
10
10
22
10
10
10
...
...
10
...
10
10
10
10
10
10
22
22
22
22
22
65
65
10
...
...
...
10
...
...
10
...
...
...
...
...
...
...
...
... ...
10
10
. . . . . . 22 . . . 22d . . . 65
...
...
...
...
...
...
...
...
...
15–30
10
15–30
15–60
1
15–30
2
15–60
3
15–30
2
10
15–20
Current Range
...
...
1
15–30
1
15–30
...
2
15–30
...
1
15–150
...
2
15–30
...
1
15–100
...
1
15–125
...
2
QOB- QOB- QOB-GFI QOB- QOB-EPD
AFI VHAFI
VHGFI
15–30
...
1
...
15–100
...
QHB
QOB-VH
10–100
Unit Mount
Number of Poles
QOB-H . . . . . . . . .
10–200
...
10–100
...
15–50a
...
15–50
...
15–20
...
15–50
...
QO- QO-GFI QO- QO-EPD
VHAFI
VHGFI
QOT
15–20
...
QOAFI
QH
15–200
...
QO-VH
15–50
Bolt-on
QO-H
15–20
Plug-on
Circuit
Breaker
Type
CIRCUIT BREAKERS
Interrupting Ratings
120 Vac
UL/CSA
120/240 Vac
Rating
(kA RMS)
240 Vacc
(50/60 Hz AC)
277 Vac
b
480Y/277 Vac
6
DC Ratings
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
48 Vdc
...
...
...
...
...
...
...
...
5 e 5e 5 e
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
60 Vdc
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
65 Vdc
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
125 Vdc
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
250 Vdc
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
✓
✓
✓
✓
✓
✓
✓
✓
✓
...
✓
...
✓
✓
✓
...
✓
...
...
✓
...
IEC 60947-2 IEC
(50/60 Hz AC) (Ultimate
f
Rating)
Special Ratings
Fed. Specs
W-C-375B/GEN
Other Standard
HACR g
NOM
... ...
HACRh
NOM
HACR g
... ... ...
HACRh
...
... ...
. . . HACR
h
...
NOM
...
NOM
Accessories and Modifications
Shunt Trip
...
...
...
...
...
...
...
...
✓i ✓i ✓i
✓i
✓i ✓i ✓i ✓i ✓ij ✓i ✓i ✓i
...
...
...
...
...
...
...
Undervoltage Trip
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
...
...
...
...
...
...
...
Auxiliary Switches
...
...
...
...
...
...
...
...
✓i ✓i ✓i
✓i
✓i ✓i ✓i ✓i ✓ij ✓i ✓i ✓i
...
✓i
✓i ✓i
✓i
✓i ✓i
...
... ...
Alarm Switch
...
...
...
...
...
...
...
...
✓i ✓i ✓i
✓i
✓i ✓i ✓i ✓i ✓ij ✓i ✓i ✓i
...
✓i
✓i ✓i
✓i
✓i ✓i
Handle Operators
...
...
...
...
...
...
...
...
... ... ...
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
Handle Padlock
Attachment
✓
✓
✓
...
...
...
...
✓k
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Trip System Type
Thermal-magnetic
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Molded Case Switch
...
...
...
...
...
...
...
...
✓
✓
✓
...
... ... ... ...
...
... ...
...
...
...
...
...
...
...
...
Dimensions (1-pole Unit Mount)
Dimensions
(1P
Unit Mount)
Height
IN (mm)
3.13 (79)
3.5 (89)l
Width
IN (mm)
1.00 (25)
0.75 (19)l
Depth
IN (mm)
Pages
2.98 (76)
2.92 (74)l
Page 6-9
Pages 6-10
a HOMT tandem is 30 A maximum. HOMT quad tandem has 20 A maximum on outside poles, and 50 A maximum on the inside poles.
b AFI, EPD and GFI products are rated 60 Hz only.
c See Supplemental Digest for 3 phase corner grounded systems.
d 22 kA @ 240 Vac for 3-pole only.
e 1- and 2-pole, 10–70 A and 3-pole 10–60 A only.
f See Supplemental Digest for circuit breakers with IEC ratings.
g HACR on HOM 1-pole 15–50 A and 2-pole 15–100 A
h HACR on QO, QOB 1-pole 10–70 A, 2-pole 15–100 A, 3-pole 10–100 A; QOB-VH 1-pole 15–70 A, 2-pole 15–125 A, 3-pole 15–100 A
i Factory-installed option only
j Factory-installed accessories are not available on QOB-VH 2-pole 150 A and 3-pole 110–150 A
k Handle padlock attachment available for HOMT quad tandem only.
l See page 6-49 for dimensions for: QOB2150VH, QOB3110VH, QOB3125VH and QOB3150VH.
9/8/03
6-2
© 2003 Schneider Electric
All Rights Reserved