t
D Microprocessor-based controller
D Environmentally sealed user interface
D LCD display, 4 lines x 20 characters, backlit
D Dynamic function keypad with tactile feedback pushbuttons allows complete programming and viewing capability at the door
D LED indicators: Source available, transfer switch position, service required (fault), and “not in auto”
D
Broadrange voltage sensing (208--600 VAC) on all phases
D Phase-to-phase sensing and monitoring with 0.5% accuracy on both sources
D Frequency sensing with 0.5% accuracy on both sources
D Anti-single phasing protection
D Phase rotation sensing for three-phase systems
D Real-time clock with automatic adjust for daylight saving time and leap year
D Time-stamped event log
D Fail-safe transfer for loaded test and exercise functions
D DIP switches: password disable and maintenance
D
Modbus r
RTU and Modbus r
TCP/IP protocols
(Modbus r register map available)
D RJ45 connector for 10/100 ethernet connection
D USB port with read/write compatibility
D Isolated RS-485 ports
D One-year limited warranty
Voltage:
Current:
208--600 VAC 50/60 Hz
150--3000 amps
D UL 1008 listed at 480 VAC, file # E108981
D CSA certification available
D IBC seismic certification available (NEMA 1 enclosures only)
D Bypass/isolation switches for uninterrupted power to the load during switch maintenance and testing
D Standard-transition or programmed-transition modes of operation
D Ratings from 150 to 3000 amps
D Ratings of bypass switch and automatic transfer switch identical
D Available in 2, 3, or 4 pole configurations
D Available to 600 VAC, 60 or 50 Hz
D Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 amps
D NEMA type 1 enclosure
D
Exceeds UL 1008 requirements for temperature rise after overload and endurance tests in unventilated enclosure
D Auxiliary position contacts: two closed on normal switch position, two closed on emergency switch position
(rated 15 A @ 240 VAC)
D Engine start contacts rated 10 A @ 32 VDC
D
Standard-transition transfer time less than 100 milliseconds
(6 cycles @ 60 Hz)
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 1
D Programming and monitoring methods: d Monitoring and password-protected programming at the door using the keypad and display d
Program and monitor using a PC with Monitor III integrated generator set and ATS monitoring software d Transfer files through the USB port
D System voltage and frequency
D Voltage unbalance
D Over/undervoltage and over/underfrequency for all phases of the normal and emergency sources
D Adjustable time delays
D Load/no load/auto-load test and load/no-load exercise functions
D Programmable inputs and outputs
D Time-based and current-based* load control
D Load bank control for exercise or test
D Pre/post-transfer, nine individual time delays for selected loads
D
ABC/BAC/none phase rotation selection with error detection
D Resettable historical data
D In-phase monitor
D Password protection, three security levels
* Requires current sensing kit.
D Contactor position: source N and source E
D Source available: source N and source E
D Service required (fault indication)
D Not in automatic mode
D System status
D Line-to-line voltage
D Line-to-neutral voltage
D Active time delays
D Source frequency
D Preferred source selection
D
System settings
D
Common alarms
D
Load current, each phase [
D
Inputs and outputs
D Faults
D Time/date
D Address
D Event history
D Maintenance records
D Exerciser schedule
D Exerciser mode
D Time remaining on active exercise
D Scroll up/down/forward/back
D Increase/decrease/save settings
D End time delay
D Start/end test or exercise
D Reset fault
D Lamp test
D Maintenance mode
D Password disable
t
D USB port with read/write capability
D Isolated RS-485 ports
D RJ-45 connector for 10/100 ethernet connection
D Modbus r RTU and Modbus r TCP/IP protocols
(Modbus r register map available)
D USB Port. Upload or download files from a PC or a memory device through the USB port.
d Application software d Event history files d
Language files d Parameter settings d Usage reports d Feature configuration
D Time-stamped voltage and frequency readings
D Minimum and maximum current and voltage readings for a selected time period
D View up to 99 time and date-stamped events on the display or on a personal computer equipped with optional Monitor III software.
D Download up to 2000 events with Monitor III software or download complete event history file to a PC or a memory device connected to the USB port.
D Two (2) programmable inputs
D Two (2) programmable outputs, isolated form C (SPDT) contacts rated 1 amp @ 30 VDC, 500 mA @120 VAC
D System voltage, 208--600 VAC *
D System frequency, 50/60 Hz *
D
Single/three-phase operation *
D Standard/programmed-transition operation *
D Preferred source selection
D Phase rotation: ABC/BAC/none selection with error detection
D Voltage and frequency pickup and dropout settings
D Voltage unbalance, enable/disable
D In-phase monitor: enable/disable and phase angle
D Transfer commit/no commit
D
Source/source mode: utility/gen, gen/gen, utility/utility, or utility/gen/gen for 3-source systems
D Passwords, system and test
D Time, date, automatic daylight saving time enable/disable
D Time delays (see table)
D Exerciser: calendar mode, loaded/unloaded up to 21 events
D Test: loaded/unloaded/auto load (1--60 minutes)
D Remote test: loaded/unloaded
D Automatic override on generator failure (loaded test and exercise)
D Peak shave delay enable/disable
D Current monitoring [
D Pre/post-transfer, 9 individual time delays for selected loads
D Current-based load control settings: high/low current levels and load add/remove priority for 9 separate loads [
D Prime power sequence alternates between two generator sets
D
Resettable historical data
Main Board I/O Specifications
Output contact type Isolated form C (SPDT)
Output contact rating 1 amp @ 30 VDC, 500 mA @120 VAC
I/O terminals wire size range #12--24 AWG
* System parameters factory-set per order
[
Requires optional current sensing kit.
Modbus r is a registered trademark of Schneider Electric.
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 2
t
D External time delay input
D External battery fault
D External common fault
D Inhibit transfer
D Peak shave/area protection input
D External test
D Three-source system disable
D Bypass disable
D Chicago alarm control
D Common alarm events
D Contactor position
D Exercise active
D Failure to acquire standby source
D Failure to transfer
D
Generator engine start, source N and E
D
I/O module faults
D Load bank control
D Load control active (pre/post transfer delay, up to 9 outputs)
D Loss of phase fault, source N and E
D External battery fault
D Non-emergency transfer
D Not in automatic mode
D Over/underfrequency faults, source N and E (generator)
D Over/undervoltage faults, source N and E
D Peak shave/area protection active
D Phase rotation error, source N and E
D Preferred source supplying load
D Software-controlled relay outputs (four maximum)
D Source available, preferred and standby
D Standby source supplying load
D Synchronizing output
D Test active
D Transfer switch auxiliary contact fault
D Transfer switch auxiliary contact open
D Voltage unbalance
Parameter
Voltage and Frequency Sensing
Undervoltage dropout
Undervoltage pickup
Overvoltage dropout *
Overvoltage pickup
Unbalance enable
Unbalance dropout
Unbalance pickup
Voltage dropout time
Underfrequency dropout
Underfrequency pickup
Overfrequency dropout
Overfrequency pickup
Frequency dropout time
Adjustable Time Delays
Time Delay Default Adjustment Range
Engine start, Source S2 3 sec.
0--6 sec.
[
Engine start, Source S1 (gen/gen) 3 sec.
Engine cooldown, Source S2
Engine cooldown, S1 (gen/gen)
Fail to acquire standby source
Fail to acquire preferred source
Transfer, preferred to standby
Transfer, standby to preferred
Transfer, off to standby
Transfer, off to preferred
Fail to synchronize
Auto load test duration
Default
90% of pickup
90% of nominal
115% of nominal*
95% of dropout
Disable
20%
10%
0.5 sec.
99% of pickup
90% of nominal
101% of pickup
110% of nominal
3 sec.
5 sec.
2 sec.
1 min.
1 min.
3 sec.
15 min.
1 sec.
1 sec.
60 sec.
30 min.
Adjustment
Range
75%--98%
85%--100%
106%--135%
95%--100%
Enable/Disable
5%--20%
3%--18%
0.1--9.9 sec.
95%--99%
80%--95%
101%--115%
105%--120%
0.1--15 sec.
* 690 volts, maximum. Default = 110% for 600 volt applications.
0--60 min.
1 sec. -- 60 min.
10 sec -- 15 min.
1--60 min.
(1 min. increments)
Prime power run duration 6 min.
6 min. -- 100 days
(6 min. increments)
Load Control Time Delays:
Pretransfer to preferred
Post-transfer to preferred
Pretransfer to standby
0 sec.
0 sec.
0 sec.
0 sec.
0--60 min.
Post-transfer to standby
Load add Source1/Source2
Load remove Source1/Source2
0 sec.
0 sec.
Note: Time delays are adjustable in 1 second increments, except as noted.
[
Engine start time delay can be extended to 60 minutes with an
External Battery Supply Module Kit.
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 3
D Switches are factory-wired, interconnected, and tested prior to shipment.
D All current-carrying components provide withstand current ratings in excess of those specified in UL-1008 standards.
D The contactor is electrically operated and mechanically held by a simple, over-center mechanism.
D The transfer switch has a double-throw, interlocked operation. Mechanical and electrical interlocks ensure proper sequence of operation.
D The transfer switch has segmented silver tungsten alloy contacts with separate arcing contacts on all sizes of switches. Transfer switches have arc quenching grids, enclosed arc chambers, and wide contact air gap to ensure superior source-to-source isolation on all units.
D The transfer switch components are accessible for inspection and maintenance without removal of the switch or the power conductors.
D A mechanical indicator and transparent chamber cover aid inspection, improve safety, and ease position designation.
D The disconnect switch inhibits transfer when activated.
D The automatic transfer switch is located on a drawout mechanism to facilitate maintenance.
D
Emergency power systems can be electrically tested without disturbing the load.
D Power cables do not have to be disconnected to remove the automatic transfer switch.
D The engine start circuit is maintained during bypass operation. Normal power failure causes the engine start contact to close even with the automatic transfer switch removed.
D The electrical controls are mounted on the enclosure door and connected by a wire harness and multipin disconnect plugs. The automatic transfer switch and/or the control panel may be tested, isolated, or removed for maintenance without load interruption.
D
Diagnostic lights and detailed instructions allow simple step-by-step operation.
D Bypass switch contacts are closed only during the bypass isolation operation.
D A silver-plated, copper bus interconnection for the automatic transfer switch and bypass switch is standard for all sizes of switches.
D The programmed transition function allows the load’s magnetic field to collapse before transferring to either source.
D Switching is accomplished by a dual DC solenoid drive for rapid operation and long life.
D
The time delay after the opening of the closed contacts and before the closing of the open contacts is adjustable.
D The transfer switch is suited for applications where the load consists of large motors and/or transformers.
The bypass-isolation transfer switch consists of two major components: an automatic transfer switch and a bypass-isolation switch.
The automatic transfer switch power switching components are available in standard and programmed-transition configurations and constructed for rugged, reliable operation.
The bypass section is a manually operated transfer switch that includes a manual load transfer handle and a control and interlock system. The switches are mounted in a compact enclosure and completely interconnected, requiring only the source and load connections. Once installed, no cables need to be removed to isolate the transfer switch module for maintenance or inspection.
Additional load-break contacts that cause load interruption during bypass-isolation functions are not required. The bypass- isolation switch contacts are out of the system’s current path except during actual bypass operation. Therefore, they are not constantly exposed to the destructive effects of potential fault currents. The normal source, emergency source, and load are connected between the automatic transfer switch and the bypass-isolation switch through solid-braced isolating contacts that open when the transfer switch is isolated.
The transfer switch has three positions:
D Automatic: The automatic transfer switch is supplying power to the load, and the bypass switch is in the open position. This position is the normal operating position.
D Test: The bypass switch is closed and supplying power to the load. The automatic transfer switch’s electrical controls are powered and the test switch on the enclosure door can be used to test the automatic transfer switch.
D Isolate: The bypass switch is closed and supplying power to the load. The automatic transfer switch is withdrawn from all power and is ready for maintenance.
The bypass-isolation switch has the same design as the transfer switch and thus has the same electrical ratings.
Manually operated, it features high-speed, quick-make, quick-break contact action. The bypass-isolation switch has three positions:
D Automatic: Normal bypass contacts open and emergency bypass contacts open
D Bypass Normal: Normal bypass contacts closed and emergency bypass contacts open
D Bypass Emergency: Normal bypass contacts open and emergency bypass contacts closed
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 4
Environmental Specifications
Operating Temperature --20
°
C to 70
°
C (--4
°
F to 158
°
F)
Storage Temperature --40
°
C to 85
°
C (--40
°
F to 185
°
F)
Humidity 5% to 95% noncondensing
Input and Output Connection Specifications
Component Wire Size Range
Main board I/O terminals
I/O module terminals
#12--24 AWG
#14--24 AWG
Al/Cu UL-Listed Solderless Screw-Type Terminals for
External Power Connections
Switch Rating, amps
150--400
600
Normal, Emergency, and Load Terminals
Cables per Pole Range of Wire Sizes*
2
1
2
1/0 to 250 MCM
#4 AWG to 600 MCM
#2 AWG to 600 MCM
800--1200
1600--2000
4
8
#2 AWG to 600 MCM
1/0 to 750 MCM
2600--3000 12 1/0 to 750 MCM
* Use 60
°
C minimum wire for #14 to #1 AWG. Use 75
°
C minimum wire for 1/0 AWG and larger.
The ATS meets or exceeds the requirements of the following specifications:
D Underwriters Laboratories UL 508, Standard for Industrial
Control Equipment
D Underwriters Laboratories UL 1008, Standard for Automatic
Transfer Switches for Use in Emergency Standby Systems, file # E108981
D CSA C22.2 No. 178 certification at 600 VAC available, file # LR58301
D
NFPA 70, National Electrical Code
D NFPA 99, Essential Electrical Systems for Health Care
Facilities
D NFPA 110, Emergency and Standby Power Systems
D IEEE Standard 446, IEEE Recommended Practice for
Emergency and Standby Power Systems for Commercial and Industrial Applications
D NEMA Standard ICS 10--2005, Electromechanical AC
Transfer Switch Equipment
D EN61000-4-4 Fast Transient Immunity Severity Level 4
D IEC 60947-6-1, Low Voltage Switchgear and Control Gear;
Multifunction Equipment; Automatic Transfer Switching
Equipment
D EN61000-4-5 Surge Immunity Class 4
(voltage sensing and programmable inputs only)
D IEC Specifications for EMI/EMC Immunity: d CISPR 11, Radiated Emissions d IEC 1000-4-2, Electrostatic Discharge d IEC 1000-4-3, Radiated Electromagnetic Fields d IEC 1000-4-4, Electrical Fast Transients (Bursts) d IEC 1000-4-5, Surge Voltage d IEC 1000-4-6, Conducted RF Disturbances d IEC 1000-4-8, Magnetic Fields d IEC 1000-4-11, Voltage Dips and Interruptions
D IEEE 472 (ANSI C37.90A) Ring Wave Test
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 5
Weights and dimensions are shown for transfer switches in NEMA type 1 enclosures. Consult the factory for other available enclosures.
Note: Weights and dimensions are provided for reference only and should not be used for planning installation. See your local distributor for submittal drawings.
Number of
Poles
2
3
Amps
150, 225, 260, 400
150, 225, 260, 400
600
800, 1000, 1200
1600, 2000
Height
2184 (86.00) *
2184 (86.00) *
2362 (93.00) *
2362 (93.00) *
2286 (90.00)
Dimensions, mm (in.)
Width
762 (30.00)
762 (30.00)
914 (36.00)
1016 (40.00)
1016 (40.00)
Depth
787 (31.00)
787 (31.00)
718 (28.25)
[
718 (28.25)
[
1552 (61.12)
4
2600, 3000
150, 225, 260, 400
600
800, 1000, 1200
2286 (90.00)
2184 (86.00) *
2362 (93.00) *
2362 (93.00) *
2286 (90.00)
2286 (90.00)
1016 (40.00)
762 (30.00)
1016 (40.00)
1168 (46.00)
1270 (50.00)
1270 (50.00)
1857 (73.12)
787 (31.00)
718 (28.25)
[
718 (28.25)
[
1552 (61.12) 1600, 2000
2600, 3000 1857 (73.12)
* Height includes removeable 76 mm (3 in.) lifting eyes on 150--1200 amp models.
[
Depth with optional adapter bay for bottom cable entry is 1074 mm (42.3 in.). (600--1200 amp models only.)
Weight, kg (lb.)
340 (750)
340 (750)
553 (1220)
615 (1355)
1406 (3100)
1769 (3900)
386 (850)
619 (1365)
712 (1570)
1815 (4000)
2268 (5000)
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 6
Switch
Rating, amps
150
225
260
400
600
Withstand Current Ratings, Maximum Current in RMS Symmetrical Amperes When Coordinated with:
Current-Limiting Fuses Molded-Case Circuit Breakers
Specific Manufacturer’s
(see separate tables)
Maximum
Fuse Size, amps
@ 480 VAC
Maximum
Rating, amps Class
@ 600 VAC
Maximum
Rating, amps Class
Any Manufacturer’s (3 cycles)
Maximum
Amps @
480 VAC
Maximum
Amps @
600 VAC
Maximum
Size, amps
Maximum
Amps @
480 VAC
Maximum
Amps @
600 VAC
200
300
350
600
200,000
100,000
J
RK5,
RK1
200,000 J 35,000 30,000 800 50,000 42,000
750 200,000
J, L,
RK1,
RK5
150,000
J, L,
RK1,
RK5
800 65,000 50,000
800
1000
1200
1600
1000
1200
1500
2000
200,000 L 200,000
2000
2600
2500
200,000 L 150,000
4000
3000
* UL 1008 listed at 480 VAC and CSA listed at 600 VAC.
L
L
50,000
100,000
42,000
85,000
1600
2500
4000
85,000
100,000
65,000
85,000
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 7
The following chart lists contactor withstand and close-on ratings (WCR) with specific manufacturer’s circuit breakers.
Molded-Case Circuit Breakers
Switch
Rating
WCR, RMS
Symmetrical
Amperes
150,
225,
260,
400
600
800,
1000,
1200
50,000
65,000
85,000
Manufacturer
General Electric
Merlin Gerin
ITE
Square D
Cutler-Hammer
ITE
General Electric
Square D
Cutler-Hammer
General Electric
Merlin Gerin
ITE
Square D
Cutler-Hammer
Type or Class
SFL, SFP, TFL, THLC2
SGL4, SGP4, TB4, THLC4, TLB4
SGL6, SGP6, SGPA, TB6, TJL4V, TKL4V, TJL1S--6S
SKL8, SKP8, TB8, SKH8
CF250L, CF250H
CJ400L, CK400H, CJ400H, CK400N
CJ600H
CK800H, CK800N
CFD6, HFD6
CJD6, SCJD6, HHJD6, HHJXD6 SHJD6, HJD6
CLD6, SCLD6, HHLD6, HHLXD6, SHLD6, HLD6
CMD6, SCMD6, HMD6, SHMD6, HMXD6, MD6, MXD6, SMD6
KI, KC
LI, LXI, LX, LE, LC
MX, MH, ME
HJD, JDC
HKD, CHKD, KDC, LCL, LA TRI-PAC
HLD, CHLD, LDC, CLDC
NB TRI-PAC
CLD6, HLD6, SCLD6, SHLD6
CMD6, SCMD6, HMD6, SHMD6
TB6, TJL, SGL6, SGP6
TB8, TP, THP, TC, THC, SKL8, SKP8
LC, LE, LI, LX, LXI
ME, MH, MX, NC, NE, NX
CHDC, CLDC, HLD, LDC
CHMDL, HMDL, NB TRI-PAC, DSL206
SKP8, TB8, THC, THP
SKP12
THP, THC, TRP
CK1000L
CM1600
CMD6, SCMD6
CND6, SCND6
CPD6
NC, NE, NX
PCF, PEF, PHF, PXF
NB TRIPAC
CNDC, NDC
CRDC, PB TRIPAC, PC, PCC, RDC
Maximum
Size, amps
800
250
400
600
800
250
600
250
400
600
800
250
400
600
800
600
800
600
800
800
250
400
600
800
600
800
1200
1600
1200
1600
800
1200
1600
600
800
800
1200
1600
1200
1600
1600,
2000,
2600,
3000
100,000 Any, 4000 Ampere Maximum 4000
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 8
The following chart lists contactor withstand and close-on ratings (WCR) with specific manufacturer’s circuit breakers.
Molded-Case Circuit Breakers
Switch
Rating, amps
WCR, RMS
Symmetrical
Amperes
150,
225,
260,
400
600
800,
1000,
1200
42,000
50,000
65,000
Manufacturer
General Electric
Merlin Gerin
ITE
Cutler-Hammer
Square D
General Electric
ITE
Square D
Cutler-Hammer
General Electric
Merlin Gerin
ITE
Square D
Cutler-Hammer
Type or Class
THLC2
SGL4, SGP4, TB4, THLC4
SGL6, SGP6, TB6
SKL8, SKP8, TB8
CF250L
CJ400L, CK400H
CK800H
CFD6
CJD6, SCJD6, HHJD6, HHJXD6
CLD6, SCLD6, HHLD6, HHLDX6
CMD6, SCMD6, HMD6, SHMD6, HMXD6
KDC, LCL, LA TRI-PAC
LDC, CLDC
NB TRI-PAC
KI
LI, LXI
TB6, SGL6, SGP6
TB8, THP, THC, SKP8
CLD6, SCLD6
CMD6, HMD6, SCMD6, SHMD6
LI, LXI
NC, NE, NX
CLDC, LDC
NB TRI-PAC, DSL206
SKP8, TB8, THC, THP
SKP12
THC, THP, TRP
MP16H1, MP16H2, MC16H1
CMD6, SCMD6
CND6, SCND6
CPD6, HPD6, HRD6
NC, NE, NX
PCF, PEF, PHF, PXF
NB TRIPAC
PC, PCC, PB TRI-PAC, RDC, CRDC
1600
800
1200
1600
1200
600
800
800
1200
1600
800
600
800
600
800
600
800
250
600
600
1600
800
1600
Maximum
Size, amps
250
400
250
400
600
800
400
600
800
250
400
800
1600,
2000,
2600,
3000
85,000 Any, 4000 Ampere Maximum 4000
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 9
The mounting kit holds up to five optional modules. The maximum total current draw is 300 mA. If an External Battery
Module is installed, there is no current restriction.
Module Current Draw Specifications, mA
Alarm Module 75
Accessories are available either factory-installed or as loose kits, unless otherwise noted.
-
D 90 dB Audible alarm
D Any alarm function can be programmed to trigger the audible alarm
D Chicago alarm function
D Preferred source selection
D Supervised transfer control (supervised transfer control switch required)
D Connection for external alarm
Standard I/O Module
High Power I/O Module
-
75
100
External Alarm Connection Specifications
Wire Size
Contact Voltage Rating
#12--22 AWG Cu
500 mA @ 120 VAC
250 mA @ 240 VAC
Inputs
Available Inputs
Input Definition
Current
Connection Type
Wire Size
Max Distance
Outputs
Outputs Available
Contact Type
Contact Voltage Rating
Connection Type
Wire Size
2
Contact closure
5 mA Max
Terminal Strip
#14--24 AWG
700 feet
6
Form C (SPDT)
2 A @ 30 VDC
500 mA @ 125 VAC
Terminal Strip
#14--24 AWG
-
D Energizes the ATS controls using an external battery when no source power is available
D Allows extended engine start time delays
D Allows the use of any combination of accessory modules
(no current draw restriction, maximum of five modules total)
D Connects to one or two batteries, 12 VDC or 24 VDC system
D Current draw, 140 mA @ 12 VDC, 86 mA @ 24 VDC
D Provides low external battery voltage indication to the transfer switch controller
D Reverse-polarity protected
-
D Available for 600--1200 amp models
-
Inputs
Available Inputs
Input Definition
Current
Connection Type
Wire Size
Max Distance
2
Contact closure
5 mA Max
Terminal Strip
#14--24 AWG
700 feet
Outputs
Outputs Available
Contact Type
Contact Voltage Rating
Connection Type
Wire Size
3
Form C (SPDT)
12 A @ 24 VDC
12 A @ 250 VAC
10 A @ 277 VAC
2 A @ 480 VAC
Terminal Strip
#14--24 AWG
Environmental Specifications
Temperature --40
°
C to 85
°
C (--40
°
F to 185
°
F)
Humidity 35% to 85% noncondensing
-
-
D Monitor current on all phases with 1% accuracy
-
D
Measure and display for both sources: d Voltage d Current d Frequency d Power
D Programmable visual alarms: d High voltage d
Low voltage d
High current
D Serial port for optional network connections
D Password-protected programming menus
D Available factory-installed
D See TT-1506, Digital Power Meters
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 10
-
D 2-year basic
D 5-year basic
D 5-year comprehensive
D 10-year major components
-
-
D Available as loose kit for open units
-
D Allows remote monitoring and limited control of up to four transfer switches connected in an RS-485 network
D Includes surface and flush mounting provisions
-
D Certification depends on application and geographic location. Contact your distributor for details.
D Available on 150--3000 Amp models with NEMA 1 enclosures
-
D Humidistat-controlled 120 VAC strip heater
(customer-supplied voltage source required)
D 125 or 250 watts (sized for enclosure)
D
Protective 15 Amp circuit breaker
-
D Production literature kit
(one kit is included with each transfer switch)
D Overhaul literature kit
-
D Monitors all line-to-neutral voltages
-
D Disconnects power to controller without disconnecting load
D Mounts inside the enclosure
-
D Monitor and control the power system’s generator sets and transfer switches from a personal computer using a single software package
D Monitor and control systems through a Windows r -based graphical user interface
D Monitor and control systems over a local area network, remotely via a modem connection, or through an Ethernet connection
D Password-protected data access: Guest, User, and
Supervisor levels
D Ethernet capability
D Start or stop a test from a remote PC
D View and adjust trip points, time delays, and system parameters
D Assign inputs and outputs
D Available as loose kits: d Software kit with serial cable d Software kit with device modem and cables
-
D Auto, Manual, and Transfer positions
D Automatic and non-automatic modes
D Alarm module required
-
D SPD available for the normal source supply
D Surge protection reduces transient voltages to harmless levels
D Replaceable without disconnecting power
D High-performance EMI/RFI filtering:
--75dB maximum 100 kHz to 100 MHz
D Protection modes: L-L, L-N, L-G, N-G
D Thermal and short circuit fusing
D
LED status indicators
D Remote contacts for customer-supplied status indicators
Form C (NO, NC, C) 60 W DC, 120 VAC, 3A max.
D Audible alarm, 90 dB
D Listed to UL 1449, Edition 3
D See additional specifications below
SPD Specifications
Surge
Current
(I max ), kA
UL SVR,
VAC
Limiting Voltage,
VAC at
3kAmps at
10kAmp
Working
Voltage
120/240
120/208
120/240
277/480
220/380
240/415
3
3
3
Ph.
Split
3
3
100
100
100
400
400/800
800
470
470/890 780/1200
890
780
1200
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 11
KOHLER CO., Kohler, Wisconsin 53044 USA
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales and service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com
Model Mechanism Transition
Controls Voltage Poles Enclosure
Kohler Power Systems
Asia Pacific Headquarters
7 Jurong Pier Road
Singapore 619159
Phone (65) 6264-6422, Fax (65) 6264-6455
Current Rating Miscellaneous
Record the transfer switch model designation in the boxes. The transfer switch model designation defines characteristics and ratings as explained below.
Model
K: Kohler Transfer Switch
Mechanism
G: Bypass/Isolation
Transition
S: Standard
P: Programmed
Controls
D: MPAC t 1500
Microprocessor Controls, Automatic
Enclosure
A: NEMA 1 [
B: NEMA 12 w
C: NEMA 3R w
[
Standard w
Contact the factory
Current Rating: Numbers indicate the current rating of the switch in amperes:
0150
0225
0260
0400
0600
0800
1000
1200
1600
2000
2600
3000
Voltage/Frequency
C: 208 Volts/60 Hz
D: 220 Volts/50 Hz
F: 240 Volts/60 Hz
G: 380 Volts/50 Hz
H: 400 Volts/50 Hz
J: 416 Volts/50 Hz
K: 440 Volts/60 Hz
M: 480 Volts/60 Hz
N: 600 Volts/60 Hz
P: 380 Volts/60 Hz
R: 220 Volts/60 Hz
Number of Poles/Wires
N: 2-pole, 3-wire, solid neutral *
T: 3-pole, 4-wire, solid neutral
V: 4-pole, 4-wire, switched neutral
* 800 A, 480 Volts maximum
Miscellaneous
S: Standard connections
Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler r Power
Systems distributor for availability.
©
2005, 2006, 2007, 2008, 2009, 2010, 2011, 2012 by Kohler Co. All rights reserved.
G11-110 (Model KGS/KGP Transfer Switch) 10/12h Page 12