outdoor unit

advertisement
Manual No. '14 • KX-DB-201
DATA BOOK
VRF INVERTER MULTI-SYSTEM AIR-CONDITIONERS
(OUTDOOR UNIT)
KXZ series (Heat pump type)
Standard series
Single use (Used also for combination)
FDC280KXZE1, 335KXZE1, 400KXZE1, 450KXZE1, 475KXZE1, 500KXZE1, 560KXZE1
Combination use
FDC615KXZE1, 670KXZE1, 735KXZE1, 800KXZE1, 850KXZE1, 900KXZE1, 950KXZE1, 1000KXZE1,
1060KXZE1, 1120KXZE1, 1200KXZE1, 1250KXZE1, 1300KXZE1, 1350KXZE1,1425KXZE1,
1450KXZE1, 1500KXZE1, 1560KXZE1, 1620KXZE1, 1680KXZE1
Corrosion protection treatment series (Non-CE Marking models)
Single use (Used also for combination)
FDCS280KXZE1, 335KXZE1, 400KXZE1, 450KXZE1, 475KXZE1, 500KXZE1, 560KXZE1
Combination use
FDCS615KXZE1, 670KXZE1, 735KXZE1, 800KXZE1, 850KXZE1, 900KXZE1, 950KXZE1, 1000KXZE1,
1060KXZE1, 1120KXZE1, 1200KXZE1, 1250KXZE1, 1300KXZE1, 1350KXZE1,1425KXZE1,
1450KXZE1, 1500KXZE1, 1560KXZE1, 1620KXZE1, 1680KXZE1
•
Note:
(1) Regarding the Indoor unit series, refer to the No.'14 • KX-DB-206
(2) Regarding the Duct Connected-High static Pressure-type Outdoor Air Processing Unit Series
(FDU500∼1800FKXE6), refer to the DATA BOOK No.'08 • KX-DB-122
'14• •KX-DB-201
KX-DB-201
'14
PREFACE
PREFACE
Combination table for KX4, KX6 and KXZE1 series
Connectable
remote control
3-wire type
Category
Outdoor unit
Indoor unit
Same or
Same series Same series Mixed series Mixed series Mixed series Mixed series Mixed series Same series
RC-E1
3-wire type
RC-E1R
2-wire type
RC-E3
RC-E4
RC-E5
RC-EX1A
KXE4
KXE4(A)
KXE4A
KXE4A
KXE4A
KXE4R
KXE4BR
KXE5R
KXE4R
KXE4BR
KXE5R
KXE4A
KXE4R
KXE4BR
KXE5R
KXE4R
KXE4BR
KXE5R
KXE6
KXE6A
KXE6B
KXE6D
KXE6F
KXE6
KXE6A
KXE6B
KXE6D
KXE6F
KXE6
KXE6A
KXE6B
KXE6D
KXE6F
KXE6
KXE6A
KXE6B
KXE6D
KXE6F
FDCA-HKXE4
5HP
YES[D]
YES[D]
NO
NO
NO
NO
NO
NO
FDCA-HKXE4
8-48HP
NO
YES[D]
NO
NO
NO
NO
NO
NO
FDCA-HKXE4A
FDCA-HKXE4R
5HP
5,6HP
NO
YES[D]
YES[D] 1
NO
NO
YES[D]
NO
NO
8-48HP
8-48HP
8-48HP
8-48HP
NO
YES[D]
YES[D]
YES[D]
YES[D]
YES[D]
YES[D]
FDC-KXE6
4,5,6HP
NO
NO
NO
NO
NO
NO
NO
YES[B] 6
FDC-KXE6
8-48HP
NO
NO
NO
NO
NO
YES[C]
YES[C]
YES[B]
FDC-KXZE1
10-60HP
NO
NO
NO
NO
NO
NO
NO
YES[A]
FDCA-HKXE4A
Heat pump FDCA-HKXE4R
(2-pipe)
FDCA-HKXE4BR
systems
FDCA-HKXE4D
1
YES[D]
1 Except FDKA71KXE5R
Note (1) YES: Connectable (See following table in detail), NO: Not connectable
Connected indoor unit
Outdoor unit
Dip switch
setting of
outdoor
unit
Same series Mixed series
KXZE1/KXE6
Superlink
protocol
Limitation
YES[A] 2
KXZE1
KXE6
Ⅱ(New)
New (for
New (for
KXZE1/KXE6) KXZE1/KXE6)
YES[B] 2
KXE6
KXE6
Ⅱ(New)
New (for
New (for
KXZE1/KXE6) KXZE1/KXE6)
YES[C]
KXE6
KXE4 series
YES[D]
KXE4 series
KXE4 series KXE4 series
KXE6 & KXE4
Ⅰ(Previous)
series
Previous
(for KXE4)
Previous
(for KXE4)
Previous
(for KXE4)
Previous
(for KXE4)
2 If outdoor unit system (YES [A] or YES [B]) is connected to other outdoor unit systems (YES [C] and/or YES [D]) in one
superlink network, the dip switch of outdoor unit KXZE1 (YES [A]) or KXE6 of (YES [B]) should be set from (New) to (Previous).
In this case the superlink protocol and limitation of outdoor unit system (YES [A] or YES [B]) are switched to Previous (for KX4).
(2) Combination with new Central control, PC windows central control and BMS interface unit
YES[A]
&
YES[B]
YES[C]
&
YES[D]
Connectable
I/U
Superlink
protocol
Connectable
network
Connectable
I/U
Superlink 5
protocol
Connectable
network
Central control, PC windows central control and BMS interface unit
SC-SL1N-E SC-SL2NA-E SC-SL4-AE/BE SC-WGWNB-A/B SC-LGWNA-A SC-BGWNA-A/B
128
128
96
128
16
64
(128x1)
(64x2) 3
(48x2)
(64x2) 3
New
New
New
New
2
New
2
New
1
1
1
16
48
144
(48x3)
96 4
(48x2)
Previous
Previous
Previous
Previous
Previous
Previous
1
1
3
2
2
2
96 4
(48x2)
2
96 4
(48x2)
3 Maximum number of AC Cell is limited up to 96.
In case the number of connected indoor units are more than 96, some AC Cells should hold 2 or more indoor units.
4 In case of other Central control like SC-SLxN-E is connected in the same network, the connectable indoor unit is limited up to 64(32x2).
5 In case of previous superlink protocol, the superlink mode of new central control should be set "Previous".
6 In case of (YES[A] or YES[B]), previous central control is available to use. But the limitation of connectable indoor unit and so on is
complied with the rule of previous superlink.
gs+8$"
'14 • KX-DB-201
CONTENTS
1. GENERAL INFORMATION ............................................................................... 1
1.1 Specific features............................................................................................ 1
1.2 How to read the model name ........................................................................ 1
1.3 Table of models ............................................................................................. 2
1.4 Outdoor units combination table ................................................................... 3
2. OUTDOOR UNIT ................................................................................................ 4
2.1 Specifications ................................................................................................ 4
2.2 Exterior dimensions....................................................................................... 7
2.3 Electrical wiring ............................................................................................. 9
2.4 Noise level................................................................................................... 12
2.5 Corrosion protection treatment series ......................................................... 13
3. RANGE OF USAGE & LIMITATIONS .............................................................. 14
4. PIPING SYSTEM ............................................................................................. 22
5. SELECTION CHART........................................................................................ 25
6. WARNINGS ON REFRIGERANT LEAKAGE ................................................ 48
'14 • KX-DB-201
1. GENERAL INFORMATION
1.1 Specific features
Connectable indoor capacity
Capacity from 50% to 130% is possible.
Item
Number of connectable units
Model
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
FDC(S)280KXZE1
FDC(S)335KXZE1
FDC(S)400KXZE1
FDC(S)450KXZE1
FDC(S)475KXZE1
FDC(S)500KXZE1
FDC(S)560KXZE1
FDC(S)615KXZE1
FDC(S)670KXZE1
FDC(S)735KXZE1
FDC(S)800KXZE1
FDC(S)850KXZE1
FDC(S)900KXZE1
FDC(S)950KXZE1
FDC(S)1000KXZE1
FDC(S)1060KXZE1
FDC(S)1120KXZE1
FDC(S)1200KXZE1
FDC(S)1250KXZE1
FDC(S)1300KXZE1
FDC(S)1350KXZE1
FDC(S)1425KXZE1
FDC(S)1450KXZE1
FDC(S)1500KXZE1
FDC(S)1560KXZE1
FDC(S)1620KXZE1
FDC(S)1680KXZE1
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
to
24
29
34
39
41
43
48
53
58
63
69
73
78
80
80
80
80
80
80
80
80
80
80
80
80
80
80
Connectable capacity
140
168
200
225
238
250
280
308
335
368
400
425
450
475
500
530
560
600
625
650
675
713
725
750
780
810
840
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
364
435
520
585
617
650
728
799
871
955
1040
1105
1170
1235
1300
1378
1456
1560
1625
1690
1755
1852
1885
1950
2028
2106
2184
Note
For outdoor unit, EN61000-3-2 and EN61000-3-12 are not applicable as consent by the utility company or notification to the utility company is given before usage.
1.2
How to read the model name
(1) Outdoor unit
Example:
FDC S 735 KXZ E
1
Series No.
Application power source...See the specifications
Multi KXZ series
Nominal capacity (nominal cooling capacity : 73.5kW)
Corrosion protection treatment models (Nothing : Standard models)
Model name (Outdoor unit)
-
-
'14 • KX-DB-201
(2) Indoor unit
Example: FDT 28 KX
E
6F
Series No.
Application power source...See the specifications
Multi KX series
Nominal capacity (nominal cooling capacity : 2.8 kW)
Model name Indoor unit :FDT, FDTC, FDTW, FDTS,
FDTQ, FDU, FDUM, FDUT, FDK, FDE, FDFL, FDFU, FDFW, FDUH,
FDU-F
1.3 Table of models
Capacity
Model
Ceiling cassette-4 way type
(FDT)
Ceiling cassette-4 way compact type
(FDTC)
Ceiling cassette-2 way type
(FDTW)
Ceiling cassette-1 way type
(FDTS)
Ceiling cassette-1 way compact type
(FDTQ)
Duct connected-High static pressure type
(FDU)
Duct connected-Low/Middle static pressure type
(FDUM)
Duct connected (thin)-Low static pressure type
(FDUT)
Wall mounted type
(FDK)
Ceiling suspended type
(FDE)
Floor standing (with casing) type
(FDFL)
Floor standing (without casing) type
(FDFU)
Floor standing-2 way type
(FDFW)
Duct connected-compact and Flexible type
(FDUH)
Outdoor air processing unit
(FDU-F)
Outdoor units to be combined
(FDC)
15
○
22
○
28
36
45
56
71
90
112
140
160
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
224
280
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
FDC280KXZE1-FDC1680KXZE1
Note (1) Reference No. of data book : ’14·KX-DB-206
-
-
○
'14 • KX-DB-201
1.4 Outdoor units combination table
Combination Outdoor unit models
Item
Indoor unit
Number of
connectable units
2 to 53 units
-
Connectable
capacity
308 _ 799
335 _ 871
-
368
2 to 63 units
-
-
400
-
-
-
425
2
-
-
-
450
-
-
2
-
-
475
-
-
-
-
2
-
500
-
-
-
-
-
1
1
530
FDC(S)1120KXZE1
-
-
-
-
-
-
2
560
FDC(S)1200KXZE1
-
-
3
-
-
-
-
600
FDC(S)1250KXZE1
-
-
2
1
-
-
-
625
FDC(S)1300KXZE1
-
-
1
2
-
-
-
650
FDC(S)1350KXZE1
-
-
-
3
-
-
-
675
FDC(S)1425KXZE1
-
-
-
-
3
-
-
713
FDC(S)1450KXZE1
-
-
-
-
2
1
725
FDC(S)1500KXZE1
-
-
-
-
-
3
-
FDC(S)1560KXZE1
-
-
-
-
-
2
1
780
FDC(S)1620KXZE1
-
-
-
-
-
1
2
810
FDC(S)1680KXZE1
-
-
-
-
-
-
3
840
FDC(S)615KXZE1
FDC280
KXZE1
1
FDC335
KXZE1
1
FDC400
KXZE1
-
FDC450
KXZE1
-
FDC475
KXZE1
-
FDC500
KXZE1
-
FDC560
KXZE1
-
FDC(S)670KXZE1
-
2
-
-
-
-
FDC(S)735KXZE1
-
1
1
-
-
-
FDC(S)800KXZE1
-
-
2
-
-
FDC(S)850KXZE1
-
-
1
1
FDC(S)900KXZE1
-
-
-
FDC(S)950KXZE1
-
-
FDC(S)1000KXZE1
-
FDC(S)1060KXZE1
Models
750
_
955
_ 1040
_ 1105
_ 1170
_ 1235
_ 1300
_ 1378
_ 1456
_ 1560
_ 1625
_ 1690
_ 1755
_ 1852
_ 1885
_ 1950
_ 2028
_ 2106
_ 2184
2 to 58 units
2 to 69 units
2 to 73 units
2 to 78 units
2 to 80 units
2 to 80 units
2 to 80 units
2 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
3 to 80 units
(a) Outdoor unit side branch pipe set (Option)
Outdoor unit
Branch pipe set
For two units (for FDC615KXZE1-1120KXZE1)
DOS-2A-3
For three units (for FDC1200KXZE1-1680KXZE1)
DOS-3A-3
Note (1) Be sure to use this when combining units.
(b) Branch pipe set (Option)
Total capacity downstream
Branching pipe set
Less than 180
DIS-22-1G
180 or more but less than 371
DIS-180-1G
371 or more but less than 540
DIS-371-1G
540 or more
DIS-540-3
(c) Header pipe set (Option)
Total capacity downstream
Header set model type
Number of branches
Less than 180
HEAD4-22-1G
4 branches at the most
180 or more but less than 371
HEAD6-180-1G
6 branches at the most
371 or more but less than 540
HEAD8-371-2
8 branches at the most
540 or more
HEAD8-540-3
8 branches at the most
-
-
-
-
Cooling
Heating
Cooling
Heating
Cooling
Heating
MPa
mm (in)
CMM
Pa
PCB003Z817
PCB003Z819
Gas line : φ22.22 (7/8")
Liquid line : φ9.52 (3/8")
220 / 200
20˚C
Heating*2
-
19˚C
7.32×1
Propeller fan×2
2.9 (M-MA32R)
Microcomputer controlled De-Icer
Electronic expansion valve
R410A
M fin & inner grooved tubing
40x1
9.32×1
Direct line starting
11.5
4.64×2
7˚C
35˚C
DB
6˚C
24˚C
WB
Outdoor air temperature
PCB003Z817
PCB003Z819
ISO-T1
Standards
Adapted to RoHS directive
Gas line : Brazing / Liquid line : Flare
High 4.15 Low 2.21
Hole for drain ( φ20×10pcs, φ45×3pcs)
Necessary (both Liquid & Gas lines)
PCB003Z818
PCB003Z818
PCB003Z818
PCB003Z820
PCB003Z820
PCB003Z821
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1"UNITARY AIR-CONDITIONERS"
(3) Refrigerant piping size applicable to European installations are shown in parentheses.
27˚C
Cooling*1
WB
Indoor air temperature
DB
ltem
Operation
5.94×1
2048×1350×720
4.2 (M-MA32R)
33×2
4.91×2
GTC5150NC47LF×2
370
13.97
13.49
22.6 / 20.7
21.8 / 20.0
94 / 94
94 / 94
61 / 62
FDC500KXZE1
FDCS500KXZE1
50.0
56.0
PCB003Z818
PCB003Z821
386×2
Direct start
280 / 200
280 / 260
280 / 260
280 / 260
280 / 260
Max.50
Rubber mount (for compressor)
Compressor overheat protection / overcurrent protection / power transistor overheating
protection / abnormal high pressure protection
Liquid line : φ12.7 (1/2")
Gas line : φ25.4 (1")
Gas line : φ25.4 (1")
Gas line : φ28.58 (11/8")
( φ22.22 (7/8") )
( φ28.58 (11/8") )
11.0
2.25 (M-MA32R)
kg
l
W
33×1
W
4.76×1
GUC5185ND47V×1
GTC5150NC47LF×1
kW
317
272
10.96
10.69
17.5 / 16.2
17.5 / 16.2
95 / 94
93 / 92
60 / 62
FDC450KXZE1
FDC475KXZE1
FDCS450KXZE1
FDCS475KXZE1
45.0
47.5
50.0
53.0
3 Phase 380-415V 50Hz / 380V 60Hz
13.98
13.98
12.50
13.00
22.4 / 20.5
22.6 / 20.7
20.4 / 18.7
21.0 / 19.2
95 / 95
94 / 94
93 / 93
94 / 94
61 / 62
61 / 61
1690×1350×720
8.96
9.04
14.6 / 13.4
14.8 / 13.5
93 / 93
93 / 93
61 / 58
FDC400KXZE1
FDCS400KXZE1
40.0
45.0
kg
7.24
7.28
11.9 / 10.9
12.0 / 11.0
92 / 92
92 / 92
55 / 57
FDC335KXZE1
FDCS335KXZE1
33.5
37.5
mm
dB (A)
%
A
kW
kW
FDC280KXZE1
FDCS280KXZE1
28.0
31.5
Notes (1) The data are measured at the following conditions.
Connecting method
MAX. Pressure
Drain
Insulation for piping
Accessories
Exterior dimensions
Electrical wiring
Installation data
Refrigerant piping size
Safety equipment
Sound Pressure Level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
compressor type & Q'ty
Motor
Starting method
Crankcase heater
Refrigerant equipment
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
fan type & Q'ty
Motor
Starting method
Air flow (Standard)
Static pressure
Shock & vibration absorber
Power factor
Running current
Power consumption
Nominal cooling capacity*1
Nominal heating capacity*2
Power source
Models
PCB003Z818
PCB003Z821
310 / 290
5.36×2
16.62
15.95
26.9 / 24.6
25.8 / 23.6
94 / 94
94 / 94
64 / 66
FDC560KXZE1
FDCS560KXZE1
56.0
63.0
'14 • KX-DB-201
2. OUTDOOR UNIT
2.1 Specifications
• Single use (Used also for combination)
PCB003Z816
-
-
Models
Liquid line
Gas line
Oil equalization
Cooling
Heating
Cooling
Heating
Cooling
Heating
φmm
kg
%
A
kW
kW
φmm
kg
%
A
kW
kW
27˚C
20˚C
Cooling*1
Heating*2
-
19˚C
WB
95.0
106.0
27.96
26.00
45.2 / 41.4
42.0 / 38.4
94 / 94
94 / 94
740
φ15.88
7˚C
35˚C
DB
6˚C
24˚C
WB
ISO-T1
Standards
FDC950KXZE1
FDCS950KXZE1
FDC475KXZE1
FDCS475KXZE1
FDC475KXZE1
FDCS475KXZE1
Outdoor air temperature
φ31.75 ( φ34.92)
φ12.7
φ28.58
67.0
75.0
17.92
18.08
29.2 / 26.8
29.6 / 27.0
93 / 93
93 / 93
544
FDC670KXZE1
FDCS670KXZE1
FDC335KXZE1
FDCS335KXZE1
FDC335KXZE1
FDCS335KXZE1
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1"UNITARY AIR-CONDITIONERS"
(3) Refrigerant piping size applicable to European installations are shown in parentheses.
DB
Indoor air temperature
Operation
ltem
90.0
100.0
27.96
25.00
44.8 / 41.0
40.8 / 37.4
95 / 95
93 / 93
634
FDC900KXZE1
FDCS900KXZE1
FDC450KXZE1
FDCS450KXZE1
FDC450KXZE1
FDCS450KXZE1
61.5
69.0
16.20
16.32
26.5 / 24.3
26.8 / 24.5
93 / 93
93 / 93
544
FDC615KXZE1
FDCS615KXZE1
FDC280KXZE1
FDCS280KXZE1
FDC335KXZE1
FDCS335KXZE1
Notes (1) The data are measured at the following conditions.
Refrigerant
piping size
Net weight
Power factor
Running current
Power consumption
Cooling
Heating
Cooling
Heating
Cooling
Heating
Liquid line
Gas line
Oil equalization
Power source
Nominal cooling capacity*1
Nominal heating capacity*2
Combination unit
Refrigerant
piping size
Net weight
Power factor
Running current
Power consumption
Power source
Nominal cooling capacity*1
Nominal heating capacity*2
Combination unit
Models
Adapted to RoHS directive
φ9.52
FDC1000KXZE1
FDCS1000KXZE1
FDC500KXZE1
FDCS500KXZE1
FDC500KXZE1
FDCS500KXZE1
3 Phase 380-415V 50Hz / 380V 60Hz
100.0
112.0
27.94
26.98
45.2 / 41.4
43.6 / 40.0
94 / 94
94 / 94
740
φ9.52
FDC735KXZE1
FDCS735KXZE1
FDC335KXZE1
FDCS335KXZE1
FDC400KXZE1
FDCS400KXZE1
3 Phase 380-415V 50Hz / 380V 60Hz
73.5
82.5
19.92
19.73
32.1 / 29.6
32.3 / 29.7
94 / 94
93 / 92
589
φ38.1 ( φ34.92)
106.0
119.0
30.59
29.44
49.5 / 45.3
47.6 / 43.6
94 / 94
94 / 94
740
FDC1060KXZE1
FDCS1060KXZE1
FDC500KXZE1
FDCS500KXZE1
FDC560KXZE1
FDCS560KXZE1
80.0
90.0
21.92
21.38
35.0 / 32.4
35.0 / 32.4
95 / 94
93 / 92
634
φ15.88
φ31.75 ( φ34.92)
FDC800KXZE1
FDCS800KXZE1
FDC400KXZE1
FDCS400KXZE1
FDC400KXZE1
FDCS400KXZE1
φ19.05
112.0
126.0
33.24
31.90
53.8 / 49.2
51.6 / 47.2
94 / 94
94 / 94
740
FDC1120KXZE1
FDCS1120KXZE1
FDC560KXZE1
FDCS560KXZE1
FDC560KXZE1
FDCS560KXZE1
85.0
95.0
24.94
23.19
39.9 / 36.7
37.9 / 34.9
95 / 95
93 / 92
634
FDC850KXZE1
FDCS850KXZE1
FDC400KXZE1
FDCS400KXZE1
FDC450KXZE1
FDCS450KXZE1
'14 • KX-DB-201
• Combination use
PCB003Z816
-
-
Models
Liquid line
Gas line
Oil equalization
Cooling
Heating
Cooling
Heating
Cooling
Heating
φmm
kg
%
A
kW
kW
φmm
kg
%
A
kW
kW
19˚C
27˚C
20˚C
Cooling*1
Heating*2
7˚C
35˚C
DB
6˚C
24˚C
WB
Outdoor air temperature
150.0
168.0
41.91
40.47
67.8 / 62.1
65.4 / 60.0
94 / 94
94 / 94
1110
ISO-T1
Standards
FDC1500KXZE1
FDCS1500KXZE1
FDC500KXZE1
FDCS500KXZE1
FDC500KXZE1
FDCS500KXZE1
FDC500KXZE1
FDCS500KXZE1
125.0
140.0
35.90
33.88
57.4 / 52.9
55.4 / 51.1
95 / 94
93 / 92
951
FDC1250KXZE1
FDCS1250KXZE1
FDC400KXZE1
FDCS400KXZE1
FDC400KXZE1
FDCS400KXZE1
FDC450KXZE1
FDCS450KXZE1
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1"UNITARY AIR-CONDITIONERS"
(3) Refrigerant piping size applicable to European installations are shown in parentheses.
-
WB
Indoor air temperature
DB
ltem
Operation
145.0
162.0
41.93
39.49
67.8 / 62.1
63.8 / 58.4
94 / 94
94 / 94
1110
FDC1450KXZE1
FDCS1450KXZE1
FDC475KXZE1
FDCS475KXZE1
FDC475KXZE1
FDCS475KXZE1
FDC500KXZE1
FDCS500KXZE1
120.0
135.0
32.88
32.07
52.5 / 48.6
52.5 / 48.6
95 / 94
93 / 92
951
FDC1200KXZE1
FDCS1200KXZE1
FDC400KXZE1
FDCS400KXZE1
FDC400KXZE1
FDCS400KXZE1
FDC400KXZE1
FDCS400KXZE1
Notes (1) The data are measured at the following conditions.
Refrigerant
piping size
Net weight
Power factor
Running current
Power consumption
Cooling
Heating
Cooling
Heating
Cooling
Heating
Liquid line
Gas line
Oil equalization
Power source
Nominal cooling capacity*1
Nominal heating capacity*2
Combination unit
Refrigerant
piping size
Net weight
Power factor
Running current
Power consumption
Power source
Nominal cooling capacity*1
Nominal heating capacity*2
Combination unit
Models
Adapted to RoHS directive
FDC1560KXZE1
FDCS1560KXZE1
FDC500KXZE1
FDCS500KXZE1
FDC500KXZE1
FDCS500KXZE1
FDC560KXZE1
FDCS560KXZE1
3 Phase 380-415V 50Hz / 380V 60Hz
156.0
175.0
44.56
42.93
72.1 / 66.0
69.4 / 63.6
94 / 94
94 / 94
1110
φ19.05
φ38.1 ( φ34.92)
φ9.52
FDC1300KXZE1
FDCS1300KXZE1
FDC400KXZE1
FDCS400KXZE1
FDC450KXZE1
FDCS450KXZE1
FDC450KXZE1
FDCS450KXZE1
3 Phase 380-415V 50Hz / 380V 60Hz
130.0
145.0
38.92
35.69
62.3 / 57.2
58.3 / 53.6
95 / 95
93 / 93
951
φ19.05
φ38.1 ( φ34.92)
φ9.52
162.0
182.0
47.21
45.39
76.4 / 69.9
73.4 / 67.2
94 / 94
94 / 94
1110
FDC1620KXZE1
FDCS1620KXZE1
FDC500KXZE1
FDCS500KXZE1
FDC560KXZE1
FDCS560KXZE1
FDC560KXZE1
FDCS560KXZE1
135.0
150.0
41.94
37.50
67.2 / 61.5
61.2 / 56.1
95 / 95
93 / 93
951
FDC1350KXZE1
FDCS1350KXZE1
FDC450KXZE1
FDCS450KXZE1
FDC450KXZE1
FDCS450KXZE1
FDC450KXZE1
FDCS450KXZE1
168.0
189.0
49.86
47.85
80.7 / 73.8
77.4 / 70.8
94 / 94
94 / 94
1110
FDC1680KXZE1
FDCS1680KXZE1
FDC560KXZE1
FDCS560KXZE1
FDC560KXZE1
FDCS560KXZE1
FDC560KXZE1
FDCS560KXZE1
142.5
159.0
41.94
39.00
67.8 / 62.1
63.0 / 57.6
94 / 94
94 / 94
1110
FDC1425KXZE1
FDCS1425KXZE1
FDC475KXZE1
FDCS475KXZE1
FDC475KXZE1
FDCS475KXZE1
FDC475KXZE1
FDCS475KXZE1
'14 • KX-DB-201
• Combination use
PCB003Z816
'14 • KX-DB-201
2.2 Exterior dimensions
Models FDC280KXZE1, 335KXZE1
FDCS280KXZE1, 335KXZE1
PCB003Z817
-
-
'14 • KX-DB-201
Models FDC400KXZE1, 450KXZE1, 475KXZE1, 500KXZE1, 560KXZE1
FDCS400KXZE1, 450KXZE1, 475KXZE1, 500KXZE1, 560KXZE1
PCB003Z818
-
-
-
Mark
CH1
CM1
CNA-Z
CT1
C1-1,2
DM1
EEVH1,2
EEVSC
F
FMC1
FMo1,2
IPM
J11,12
J13
J14
J15
J16
LED1
LED1(INV)
LED2
LED3
L1-1,2
L3
RD
52X1-4
52X1-3
DM1
CNR WH
CNI2 WH
Inverter
PWB2-1
52X1-1
PWB3-1
-
CT1
BK
WH
RD
GN
CNI3 BK
LED1
(INV)
L3
Inspection(Red)
Normal(Yellow)-Flashing
Normal(Green)
Service(green for service)
D.C.reactor
D.C.reactor
Mark
PSH
PSL
PWB1∼3
R1-1∼1-4
SV1
SV6
SV11
SW1
SW2
SW3-1
SW3-2 ON
OFF
SW3-3
SW3-4 ON
OFF
SW3-5 ON
OFF
SW3-6
SW3-7 ON
OFF
SW3-8
CNI1
WH
A2 B2
A1 B1
BK
RD
CNX1
YE
CNW RD
CNFAN1 WH
CNR1 WH
CNFAN2 RD
CNM1 GY
BK
CH1
BR
FMo1
M
FMo2
Parts name
High pressure sensor
Low pressure sensor
Printed wiring board(PCB)
Rush current suppression resistor
Solenoid valve(CM1:bypass)
Solenoid valve(oil separator CM1)
Solenoid valve(gas bypass)
Address setting SW outdoor unit No.(2 digits)
Address setting SW outdoor unit No.(1 digit)
inspection LED reset
Auto backup operation
Regular operation
Spare
Refrigerant quantity check
Regular operation
Check operation
Regular operation
Spare
Forced cooling/heating
Regular operation
Spare
BETWEEN INDOOR UNIT AND OUTDOOR UNIT,BETWEEN
OUTDOOR UNITS ON THE SAME REFRIGERANT LINE.
BETWEEN OUTDOOR UNITS ON THE DIFFERENT
REFRIGERANT LINES.
MS
3∼
V
Parts name
Crankcase heater
Compressor motor
Connector
Current sensor
Electrolytic capacitor
Diode module
Expansion valve for heating
Expansion valve for SC
Fuse
Fan for IPM
Blower motor
Intelligent power module
Set up model(volt)
External input select level/pulse
Defrost recover temp
Defrost start temp
Spare
E
CNA WH
W
P
IPM1
U V W
N
R1-4
+
C1-2
R1-3
+
C1-1
+
AC1 AC2 AC3
U
CM1
BL
CNSL1,2
BK
NETWORK CONNECTOR
WH
WH
BL
BK
WH
Meaning of marks
TB2
A1
B1
A2
B2
Power source
3 Phase
380-415V 50Hz
/380V 60Hz
R1-1
R1-2
RD
RD
RD
52X1-3
Circuit
breaker
Earth leakage
breaker
(Impulse
withstanding type)
Signal line
RD
BL
BL
YE L1-2 WH
RD
WH
GY
52X1-2
RD
WH
BL
52X1-4
RD
WH
BL
WH
YE L1-1
WH
RD
BL
GY
RD
WH
BL
BK
Noise filter
M
SW2
CNN1 RD
CNA3 CNA1
WH WH
Mark
SW4-1∼4
SW4-5
SW4-6
SW4-7
SW4-8
SW5-1 ON
OFF
SW5-2 ON
OFF
SW5-3 ON
OFF
SW5-4
SW5-5 ON
OFF
SW5-6 8
SW6-1 3
SW6-4 ON
OFF
SW7
SW8
SW9
CNEEV1 RD
1 2 3 4 5 6 7 8
SW3
SW1
CONTROL
PWB1
ON
OFF
RD F(4A)
L1i L2i L3i Ni
CNEEV2 BL
EEVSC
M
J11
J13
CNEEV3 WH
J12
EEVH2
M
Parts name
Model setting
Spare
Spare
Address setting switch(master・slave)
Address setting switch(master・slave)
Trial operation
Regular operation
Trial operation mode/cooling
Trial operation mode/heating
Pump down operation
Regular operation
Spare
Super Link communication
Super Link communication
Spare
Spare
High Head
Standard
Data clear/insert
7-segment indicate(unit's place)
7-segment indicate(ten's place)
EEVH1
M
SW7
SW8
SW9
LED1
J14
J15
CNV
t°
t°
Mark
TB1,2
Tho-A
Tho-C1
Tho-D1
Tho-H
Tho-P1
Tho-R1
Tho-R2
Tho-R3
Tho-R4
Tho-S
Tho-SC
20S
52X1-1∼1-4
63H1-1
7SEG1
7SEG2
FMC1
t°
t°
t°
t°
t°
Color
Black
Blue
Brown
Green
Gray
Orange
Red
White
Yellow
Pink
Yellow
YE/GN
/Green
Mark
BK
BL
BR
GN
GY
OR
RD
WH
YE
PK
t°
Demand
input
External
input
Silent mode
input
Color mark
t°
CNU1
BL
CNP1
YE
CNF2
GN
WH
CNS2 RD
CNF1
WH
WH
CNS1 GN
CNB4
RD
WH
CNG2 WH
Cooling/Heating
forced input
WH
Reserve
output
Operation
output
Trouble
output
RD
WH
BK PSH
RD
WH
BK PSL
CNG1 BL
CNY WH
CNH BL
CNZ1 RD
CNL1 BL
CNL2 WH
CNB3
BK
CNN8 PK
CNB2
RD
CNQ1 WH
High pressure switch(for protection)
7-segment L.E.D.(function indication)
7-segment L.E.D.(data indication)
4way valve
Solenoid for CM
63H1-1
Parts name
Terminal block
External air thermistor
Under-dome thermistor
Discharge pipe thermistor
Sub-cooling coil thermistor 2
Power transistor thermistor
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(inlet)
Heat exchanger thermistor(inlet)
Suction pipe thermistor
Sub-cooling coil thermistor 1
Compressor
Terminal block
V(White)
t°
CNTH WH
PC
(RS232C)
U(Red)
t°
LED3
1 2 3 4 5 6 7 8
SW6
LED2
W(Blue)
J16
1 2 3 4 5 6 7 8
SW5
CNN6 PK
CNN9 BK
7SEG2
SV1
SV11
1 2 3 4 5 6 7 8
SW4
7SEG1
CNN2 GN
RD
L1o L2o L3o No
BL
OR
YE
WH
YE/GN
RD F(4A)
BL
RD
BL
BL
OR
YE
WH
BL
BL
OR
YE
WH
BK
WH
OR
YE
BL
GN
PK
WH
OR
YE
BL
GN
PK
BK
RD
BK
RD
RD
BL
SV6
BK
Tho-R1
BK
Tho-R2
20S
BK
Tho-D1
BK
BK
Tho-R3
BK
Tho-R4
BK
Tho-SC
52X1-2
BK
Tho-S
BK
BK
52X1-1
YE
Tho-A
BK
BK
Tho-H
BK
Tho-P1
-
Tho-C1
TB1
L1
L2
L3
N
'14 • KX-DB-201
2.3 Electrical wiring
Models FDC280KXZE1, 335KXZE1
FDCS280KXZE1 335KXZE1
PCB003Z819
Power source
3 Phase
380-415V 50Hz
/380V 60Hz
10 -
52X1-4
52X1-3
DM1
CNR WH
Mark
CH1
CM1
CNA-Z
CT1
C1-1,2
DM1
EEVH1,2
EEVSC
F
FMC1
FMo1,2
IPM
J11,12
J13
J14
J15
J16
LED1
LED1(INV)
LED2
LED3
L1-1∼3
L3
R1-4
+
C1-2
R1-3
+
C1-1
LED1
(INV)
CNI3 BK
Inspection(Red)
Normal(Yellow)-Flashing
Normal(Green)
Service(green for service)
D.C.reactor
D.C.reactor
Defrost recover temp
Defrost start temp
Spare
BK
BK
WH
RD
RD
GN
RD
WH
BL
L1o L2o L3o No
L1i L2i L3i Ni
GN E Noise filter
PWB3-2 CN1
RD
WH
BL
BK
L3
Mark
PSH
PSL
PWB1∼3
R1-1∼1-5
SV1
SV6
SW1
SW2
SW3-1
SW3-2 ON
OFF
SW3-3
SW3-4 ON
OFF
SW3-5 ON
OFF
SW3-6
SW3-7 ON
OFF
SW3-8
BK
GN
CNI1
WH
A2 B2
A1 B1
BK
RD
CNX1
YE
CNW RD
CNFAN1 WH
CNR1 WH
BK
CNFAN2 RD
CNM1 GY
BK
CH1
BR
FMo1
M
FMo2
Parts name
High pressure sensor
Low pressure sensor
Printed wiring board(PCB)
Rush current suppression resistor
Solenoid valve(CM1:bypass)
Solenoid valve(oil separator CM1)
Address setting SW outdoor unit No.(2 digits)
Address setting SW outdoor unit No.(1 digit)
inspection LED reset
Auto backup operation
Regular operation
Spare
Refrigerant quantity check
Regular operation
Check operation
Regular operation
Spare
Forced cooling/heating
Regular operation
Spare
BETWEEN INDOOR UNIT AND OUTDOOR UNIT,BETWEEN
OUTDOOR UNITS ON THE SAME REFRIGERANT LINE.
BETWEEN OUTDOOR UNITS ON THE DIFFERENT
REFRIGERANT LINES.
Parts name
Crankcase heater
Compressor motor
Connector
Current sensor
Electrolytic capacitor
Diode module
Expansion valve for heating
Expansion valve for SC
Fuse
Fan for IPM
Blower motor
Intelligent power module
Set up model(volt)
External input select level/pulse
MS
3∼
V
CT1
BK
CNA WH
W
P
IPM1
U V W
N
CNSL1,2
BK
NETWORK CONNECTOR
WH
WH
BL
BK
WH
CNI2 WH
+
-
AC1 AC2 AC3
U
CM1
BL
Inverter
PWB2-1
Meaning of marks
TB2
A1
B1
A2
B2
RD
RD
R1-5
R1-1
RD
WH
BL
RD
52X1-1
RD
52X1-3
YE
Circuit
breaker
Earth leakage
breaker
(Impulse
withstanding type)
Signal line
YE L1-2 WH
R1-2
GY
52X1-2
RD
WH
BL
GY
RD
WH
BL
BK
L1-1
RD
WH
BL
52X1-4
RD
WH
BL
YE L1-3 WH
WH
RD
RD
BL
M
SW2
CNA3 CNA1
WH WH
Mark
SW4-1∼4
SW4-5
SW4-6
SW4-7
SW4-8
SW5-1 ON
OFF
SW5-2 ON
OFF
SW5-3 ON
OFF
SW5-4
SW5-5 ON
OFF
SW5-6 8
SW6-1 3
SW6-4 ON
OFF
SW7
SW8
SW9
CNEEV1 RD
1 2 3 4 5 6 7 8
SW3
CONTROL
PWB1
ON
OFF
SW1
CNN1 RD
BL
SW7
SW8
SW9
CNEEV2 BL
EEVSC
M
J11
J13
EEVH2
M
J14
J15
CNV
t°
t°
Mark
TB1,2
Tho-A
Tho-C1
Tho-D1
Tho-H
Tho-P1
Tho-R1
Tho-R2
Tho-R3
Tho-R4
Tho-S
Tho-SC
20S
20UF
52X1-1∼1-4
63H1-1
7SEG1
7SEG2
FMC1
t°
t°
t°
t°
t°
Color
Black
Blue
Brown
Green
Gray
Orange
Red
White
Yellow
Pink
Yellow
YE/GN
/Green
Mark
BK
BL
BR
GN
GY
OR
RD
WH
YE
PK
t°
Demand
input
External
input
Color mark
t°
CNU1
BL
CNP1
YE
CNF2
GN
WH
CNS2 RD
CNF1
WH
WH
CNS1 GN
CNB4
RD
WH
CNG2 WH
Silent mode
input
WH
Cooling/Heating
forced input
Reserve
output
Operation
output
Trouble
output
RD
WH
BK PSH
RD
WH
BK PSL
CNG1 BL
CNY WH
CNH BL
CNZ1 RD
CNL1 BL
CNL2 WH
CNB3
BK
CNN8 PK
CNB2
RD
CNQ1 WH
High pressure switch(for protection)
7-segment L.E.D.(function indication)
7-segment L.E.D.(data indication)
4way valve
Capacity control
Solenoid for CM1
63H1-1
Parts name
Terminal block
External air thermistor
Under-dome thermistor
Discharge pipe thermistor
Sub-cooling coil thermistor 2
Power transistor thermistor
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(inlet)
Heat exchanger thermistor(inlet)
Suction pipe thermistor
Sub-cooling coil thermistor 1
Compressor
Terminal block
V(White)
t°
CNTH WH
PC
(RS232C)
U(Red)
t°
LED3
1 2 3 4 5 6 7 8
SW6
LED2
W(Blue)
J16
1 2 3 4 5 6 7 8
CNEEV3 WH
J12
CNN7 GN
CNN6 PK
LED1
20UF
SV1
BL
SW5
Parts name
Model setting
Spare
Spare
Address setting switch(master・slave)
Address setting switch(master・slave)
Trial operation
Regular operation
Trial operation mode/cooling
Trial operation mode/heating
Pump down operation
Regular operation
Spare
Super Link communication
Super Link communication
Spare
Spare
High Head
Standard
Data clear/insert
7-segment indicate(unit's place)
7-segment indicate(ten's place)
EEVH1
M
7SEG2
1 2 3 4 5 6 7 8
SW4
7SEG1
CNN2 GN
BL
OR
YE
WH
L1i L2i L3i Ni
RD
L1o L2o L3o No
RD F(4A)
BL
OR
YE
WH
GN E Noise filter
PWB3-1 CN1
RD
BL
BL
OR
YE
WH
YE/GN
RD F(4A)
WH
OR
YE
BL
GN
PK
WH
OR
YE
BL
GN
PK
BK
RD
BK
RD
RD
BL
SV6
BK
Tho-R1
BK
Tho-R2
20S
BK
Tho-D1
BK
BK
Tho-R3
BK
Tho-R4
BK
Tho-SC
52X1-2
BK
Tho-S
BK
BK
52X1-1
YE
Tho-A
BK
BK
Tho-H
BK
Tho-P1
-
Tho-C1
TB1
L1
L2
L3
N
'14 • KX-DB-201
Models FDC400KXZE1, 450KXZE1
FDCS400KXZE1, 450KXZE1
PCB003Z820
Mark
CH1,2
CM1,2
CNA-Z
CT1,CT2
C1-1,2,C2-1,2
DM1,2
EEVH1,2
EEVSC
F
FMC1,2
FMo1,2
IPM
J11,12
J13
J14
J15
J16
LED1
LED1(INV)
LED2
LED3
L1-1,2,L2-1,2
L3
R1-1
RD
52X1-4
52X1-3
DM1
CNI2 WH
Inverter
PWB2-1
CNR WH
CNSL1,2
BK
NETWORK CONNECTOR
WH
WH
BL
BK
WH
PWB3-1
Noise filter
-
U
MS
3∼
V
Inspection(Red)
Normal(Yellow)-Flashing
Normal(Green)
Service(green for service)
D.C.reactor
D.C.reactor
Defrost recover temp
Defrost start temp
Spare
CNI3 BK
LED1
(INV)
RD
52X2-4
52X2-3
DM2
Inverter
PWB2-2
CNR WH
CNI3 BK
BK
BK
WH
RD
GN
L3
L1i L2i L3i Ni
U
N
U
CM2
MS
3∼
V
CNI2 WH
LED1
(INV)
CNA WH
W
P
IPM2
V W
R2-4
+
C2-2
R2-3
+
C2-1
+
AC1 AC2 AC3
-
Mark
PSH
PSL
PWB1∼3
R1-1∼2-4
SV1
SV2
SV6
SV7
SV11
SW1
SW2
SW3-1
SW3-2 ON
OFF
SW3-3
SW3-4 ON
OFF
SW3-5 ON
OFF
SW3-6
SW3-7 ON
OFF
CT2
L1o L2o L3o No
GN E Noise filter
PWB3-2
CNI1
WH
A2 B2
A1 B1
BK
RD
CNX1
YE
CNW RD
CNFAN1 WH
CNR2 BL
CH1
BR
CNR1 WH
CH2
BR
FMo1
M
BK
CNM1 GY
BK
CNFAN2 RD
FMo2
Parts name
High pressure sensor
Low pressure sensor
Printed wiring board(PCB)
Rush current suppression resistor
Solenoid valve(CM1:bypass)
Solenoid valve(CM2:bypass)
Solenoid valve(oil separator CM1)
Solenoid valve(oil separator CM2)
Solenoid valve(gas bypass)
Address setting SW outdoor unit No.(2 digits)
Address setting SW outdoor unit No.(1 digit)
inspection LED reset
Auto backup operation
Regular operation
Spare
Refrigerant quantity check
Regular operation
Check operation
Regular operation
Spare
Forced cooling/heating
Regular operation
BETWEEN INDOOR UNIT AND OUTDOOR UNIT,BETWEEN
OUTDOOR UNITS ON THE SAME REFRIGERANT LINE.
BETWEEN OUTDOOR UNITS ON THE DIFFERENT
REFRIGERANT LINES.
U
CM1
CT1
CNA WH
W
P
IPM1
V W
R1-4
+
C1-2
R1-3
+
C1-1
+
AC1 AC2 AC3
N
E
L1i L2i L3i Ni
L1o L2o L3o No
Parts name
Crankcase heater
Compressor motor
Connector
Current sensor
Electrolytic capacitor
Diode module
Expansion valve for heating
Expansion valve for SC
Fuse
Fan for IPM
Blower motor
Intelligent power module
Set up model(volt)
External input select level/pulse
Meaning of marks
TB2
A1
B1
A2
B2
Power source
3 Phase
380-415V 50Hz
/380V 60Hz
Circuit
breaker
Earth leakage
breaker
(Impulse
withstanding type)
Signal line
RD
RD
52X1-1
RD
52X1-3
BL
YE L1-2 WH
R1-2
GY
BL
GY
RD
WH
BL
BK
52X1-2
RD
WH
BL
52X1-4
RD
WH
BL
WH
52X2-2
YE/GN
GY
YE L1-1
WH
RD
RD
WH
BL
RD
BL
R2-1
R2-2
RD
RD
52X2-1
RD
WH
GY
RD
52X2-3
BL
YE L2-2 WH
BL
BL
RD
WH
BL
BK
RD
WH
BL
52X2-4
RD
WH
BL
WH
M
SW2
CNN1 RD
CNA3 CNA1
WH WH
Mark
SW3-8
SW4-1∼4
SW4-5
SW4-6
SW4-7
SW4-8
SW5-1 ON
OFF
SW5-2 ON
OFF
SW5-3 ON
OFF
SW5-4
SW5-5 ON
OFF
SW5-6 8
SW6-1 3
SW6-4 ON
OFF
SW7
SW8
SW9
CNEEV1 RD
1 2 3 4 5 6 7 8
SW3
CONTROL
PWB1
ON
OFF
SW1
CNM2 RD
BL
20S
CNN3 BL
CNN2 GN
SW7
SW8
SW9
CNEEV2 BL
EEVSC
EEVH1
J13
CNEEV3 WH
J12
EEVH2
M
Parts name
Spare
Model setting
Spare
Spare
Address setting switch(master・slave)
Address setting switch(master・slave)
Trial operation
Regular operation
Trial operation mode/cooling
Trial operation mode/heating
Pump down operation
Regular operation
Spare
Super Link communication
Super Link communication
Spare
Spare
High Head
Standard
Data clear/insert
7-segment indicate(unit's place)
7-segment indicate(ten's place)
M
M
J11
J14
J15
CNV
t°
t°
Mark
TB1,2
Tho-A
Tho-C1,2
Tho-D1,2
Tho-H
Tho-P1,2
Tho-R1
Tho-R2
Tho-R3
Tho-R4
Tho-S
Tho-SC
20S
52X1-1∼2-4
63H1-1,2
7SEG1
7SEG2
BK
BK
CNP2 YE
CNU2 BK
t°
t°
t°
t°
t°
Color
Black
Blue
Brown
Green
Gray
Orange
Red
White
Yellow
Pink
Yellow
YE/GN
/Green
Mark
BK
BL
BR
GN
GY
OR
RD
WH
YE
PK
t°
t°
Tho-C2
t°
Tho-P2
t°
Tho-D2
Demand
input
External
input
Silent mode
input
Color mark
t°
CNU1
BL
BK
CNC2 GN
CNP1
YE
WH
CNS2 RD
CNF2
GN
WH
CNS1 GN
CNF1
WH
WH
CNG2 WH
Cooling/Heating
forced input
WH
Reserve
output
Operation
output
Trouble
output
RD
WH
BK PSH
RD
WH
BK PSL
CNG1 BL
CNY WH
CNH BL
CNZ1 RD
CNL1 BL
CNL2 WH
CNB4
RD
CNN8 PK
FMC2
CNB3
BK
CNQ2 WH
FMC1
CNB2
RD
CNQ1 WH
63H1-2
High pressure switch(for protection)
7-segment L.E.D.(function indication)
7-segment L.E.D.(data indication)
4way valve
Solenoid for CM
63H1-1
Parts name
Terminal block
External air thermistor
Under-dome thermistor
Discharge pipe thermistor
Sub-cooling coil thermistor 2
Power transistor thermistor
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(exhaust)
Heat exchanger thermistor(inlet)
Heat exchanger thermistor(inlet)
Suction pipe thermistor
Sub-cooling coil thermistor 1
Compressor
Terminal block
V(White)
t°
CNTH WH
PC
(RS232C)
U(Red)
t°
LED3
1 2 3 4 5 6 7 8
SW6
LED2
W(Blue)
J16
1 2 3 4 5 6 7 8
SW5
LED1
CNN7 GN
CNN6 PK
CNN9 BK
7SEG2
SV2
SV1
SV11
BL
1 2 3 4 5 6 7 8
SW4
7SEG1
SV7
SV6
RD
YE L2-1
WH
RD
BL
BL
OR
YE
WH
RD
BL
BL
RD
BK
F(4A)
BL
BL
OR
YE
WH
BL
BL
OR
YE
WH
BK
F(4A)
WH
OR
YE
BL
GN
PK
WH
OR
YE
BL
GN
PK
BK
RD
BK
RD
RD
RD
11 RD
BK
Tho-R2
52X2-2
BK
Tho-R1
BK
BK
Tho-R3
52X2-1
BK
Tho-D1
BK
BK
Tho-R4
BK
Tho-SC
52X1-2
BK
Tho-S
BK
BK
52X1-1
YE
Tho-A
BK
BK
Tho-H
BK
Tho-P1
-
Tho-C1
TB1
L1
L2
L3
N
'14 • KX-DB-201
Models FDC475KXZE1, 500KXZE1, 560KXZE1
FDCS475KXZE1, 500KXZE1, 560KXZE1
PCB003Z821
'14 • KX-DB-201
2.4 Noise level
Measured based on JIS B 8616
Mike position as highest noise level in position as below
Distance from front side 1m
Height
1m
N80
70
N70
60
N60
50
N50
40
30
80
70
60
50
40
N40
N3
0
63
125
250
500
1000
2000
4000
30
8000
Cooling
80
N80
70
N70
60
N60
50
N50
40
30
N70
N60
50
N50
40
30
80
70
60
50
40
N40
N3
0
63
125
250
500
1000
2000
4000
30
8000
Mid Octave Band Frequency (Hz)
Sound Pressure Level (dB)
(Standard 2 x 10 -5 Pa)
Sound Pressure Level (dB)
(Standard 2 x 10 -5 Pa)
N80
60
Sound Pressure Level (dB)
(Standard 2 x 10 -5 Pa)
Cooling
63
125
250
500
1000
N80
N70
60
N60
50
N50
40
Cooling
80
250
500
1000
2000
N80
N70
60
N60
50
N50
40
N50
40
30
4000
80
70
60
50
40
N40
N3
0
63
125
250
500
1000
2000
80
70
60
50
30
8000
Mid Octave Band Frequency (Hz)
-
9-
-
12 -
70
60
50
40
N40
N3
0
63
125
250
500
1000
2000
4000
30
8000
Model FDC500KXZE1
FDCS500KXZE1
Noise level 61 dB (A) at cooling
62 dB (A) at heating
N60
50
80
Mid Octave Band Frequency (Hz)
N70
60
Heating
70
30
30
8000
Heating
70
40
0
125
4000
N80
N40
N3
63
2000
4000
Mid Octave Band Frequency (Hz)
Heating
70
30
50
40
0
Model FDC560KXZE1
FDCS560KXZE1
Noise level 64 dB (A) at cooling
66 dB (A) at heating
80
60
Model FDC475KXZE1
FDCS475KXZE1
Noise level 61 dB (A) at cooling
61 dB (A) at heating
Heating
70
70
Cooling
80
Mid Octave Band Frequency (Hz)
Model FDC450KXZE1
FDCS450KXZE1
Noise level 61 dB (A) at cooling
62 dB (A) at heating
Cooling
80
N40
N3
Mid Octave Band Frequency (Hz)
80
Heating
Sound Pressure Level (dB)
(Standard 2 x 10 -5 Pa)
Heating
Model FDC400KXZE1
FDCS400KXZE1
Noise level 60 dB (A) at cooling
62 dB (A) at heating
30
8000
Sound Pressure Level (dB)
(Standard 2 x 10 -5 Pa)
Cooling
80
Model FDC335KXZE1
FDCS335KXZE1
Noise level 61 dB (A) at cooling
58 dB (A) at heating
Sound Pressure Level (dB)
(Standard 2 x 10 -5 Pa)
Sound Pressure Level (dB)
(Standard 2 x 10 -5 Pa)
Model FDC280KXZE1
FDCS280KXZE1
Noise level 55 dB (A) at cooling
57 dB (A) at heating
Cooling
80
Heating
N80
70
N70
60
N60
50
N50
40
30
80
70
60
50
40
N40
N3
0
63
125
250
500
1000
2000
4000
Mid Octave Band Frequency (Hz)
30
8000
'14 • KX-DB-201
2.5 Corrosion protection treatment series
Production by order
KXZ outdoor series are available with special coating applied
for not only sheet metals but also small parts in order to
prevent salt corrosion caused by sea breeze in area along
coast line (Within approximately 500m from coast line).
Model No.
FDCS280KXZE1
FDCS335KXZE1
FDCS400KXZE1
FDCS450KXZE1
FDCS475KXZE1
FDCS500KXZE1
FDCS560KXZE1
Nominal Cooling Capacity
28.0kW
33.5kW
40.0kW
45.0kW
47.5kW
50.0kW
56.0kW
Sea breeze
Sea
Additional treatment from the standard series
Parts
Description
Exterior panel
undercoat: Cation electrodeposition coating
topcoat: acrylic baked coating
Base plate
undercoat: Cation electrodeposition coating
topcoat: acrylic baked coating
Drain pan
undercoat: Cation electrodeposition coating
topcoat: acrylic baked coating
Fan motor
application of anticorrosion compound
application of anticorrosion compound
Fan motor base
Fin
Precoated Aluminum Blue Fins in high anticorrosion specification
pipe
application of anticorrosion compound
Side plate
application of anticorrosion compound
Heat exchanger
Compressor
application of anticorrosion compound
Accumulator
application of anticorrosion compound
Receiver
application of anticorrosion compound
Control box
galvanized steel sheet + undercoat: Cation electrodeposition coating
+ topcoat: acrylic baked finish
Baffle plate
Service valve bracket
galvanized steel sheet + undercoat: Cation electrodeposition coating
+ topcoat: acrylic baked finish
Screw tap for exterior panel
zinc coating + chromate treatment + fluorine coating
Screw tap for inside of exterior panel
zinc coating + chromate treatment + fluorine coating
Corrosion protection treatment complies with regulation of The Japan Refrigeration and Air Conditioning Industry Association
Caution
Even if the outdoor unit is protected with the anti-salt damage treatment, it cannot be perfectly free from rusting.
The following points should be kept in mind during installation and maintenance of the outdoor units.
Installation
(1) When installing the outdoor unit close to the coastal area, provide a windbreak to protect it from direct sea breeze and
salt water splash.
(2) Select a well-drained place to install.
(3) If any scratch or damages occurred on the outdoor unit during installation, repair it carefully.
Maintenance
(1) Clean salt grains on the outdoor unit with fresh water periodically.
(2) Apply rust preventive at regular intervals for maintenance depending on the conditions at the installation place
(consulting with the withstanding capacity).
(3) Confirm reset of screw tap after maintenance, if missing it may cause corrosion occurred from the hole of screw tap.
(4) During prolonged non operation periods, protect the unit with covering.
-
13 -
'14 • KX-DB-201
3. RANGE OF USAGE & LIMITATIONS
• Single use (also for combined use)
System
Item
Indoor air temperature
(Upper, lower limits)
FDC280KXZE1
FDCS280KXZE1
FDC335KXZE1
FDCS335KXZE1
Refer to page 19
Outdoor air temperature
(Upper, lower limits)
Indoor units
that can be
used in
combination
Number of connected units
Connectable capacity (1)
Total piping length
1 to 24 units
1 to 29 units
1 to 34 units
140 - 364
168 - 435
200 - 520
(2)
1000m or less
Main pipe length
130m or less
Single direction piping length
Actual length : 160m or less, Equivalent length : 185m or less
Allowable pipe length from the first branching
90m or less (However, difference between the longest and shortest piping : 40m or less(6))
18m or less
Elevation difference between the first branching point and the indoor unit
Difference in
height between
indoor and outdoor
units
50m or less (Max. 70m or less) (5)
Outdoor unit is higher
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
18m or less
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU, FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
5 min or more (from stop to stop or from start to start)
1 cycle time
3 min or more
Stop time
Voltage fluctuation
Within 10% of rated voltage
Voltage drop during start
Within 15% of rated voltage
Phase unbalance
Within 3%
Indoor units
that can be
used in
combination
FDC475KXZE1
FDCS475KXZE1
Connectable capacity (1)
MAX. 90m
1 to 39 units
225 - 585
1 to (Highest
41 units
indoor unit)
238 - 617
Single direction piping length
Allowable pipe length from the first First
branching
branch
18m or less
50m or less (Max. 70m or less) (5)
(Lowest indoor unit)
40m or less (3)
Indoor unit
18m or less
(Highest indoor unit)
Dew
point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU, FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
MAX. 18m
Stop time
MAX. 130m
5 min or more (from stop to stop or from start to start)
(Header)
3 min or more
Voltage fluctuation
Within 10% of rated voltage
Voltage drop
Firstduring
branch start
Within 15% of rated voltage
MAX. 18m
50m
(Outdoor unit is lower : 40m)
Power source
voltage
MAX. 90m
Outdoor unit is lower
1 cycle time
280 - 728
90m or less (However, difference between the longest and shortest piping : 40m or less(6))
Outdoor unit is higher
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
Compressor
stop/start
frequency
250 - 650
130m or less
Actual length : 160m or less, Equivalent length : 185m or less
Elevation difference between the first branching point and the indoor unit
Outdoor
unit
Difference in the elevation
of indoor
units in a system
denotes
1 to 48 units
1000m or less
MAX. 130m
FDC560KXZE1
FDCS560KXZE1
1 to 43 units
MAX. 18m
50m
Total piping length (2)
Difference in
height between
indoor and outdoor
units
FDC500KXZE1
FDCS500KXZE1
Refer to page 19
Indoor unit
Number of connected units
(Outdoor unit is lower : 40m)
FDC450KXZE1
FDCS450KXZE1
MAX. 18m
System
Item
Indoor air temperature
(Upper, lower limits)
Outdoor unit
Outdoor air temperature
(Upper, lower limits)
MAX. 18m
Power source
voltage
MAX. 18m
Compressor
stop/start
frequency
(3)
40m or less
Outdoor unit is lower
Difference in the elevation of indoor units in a system
Main pipe length
FDC400KXZE1
FDCS400KXZE1
Phase unbalance
(Lowest indoor unit)
Within 3%
MAX. 130m
14 -
X. 18m
-
MAX. 18m
50m
nit is lower : 40m)
Note (1) When connecting the indoor unit type FDK, FDFL, FDFU or FDFW Series, limit the connectable capacity not higher than 130%.
(2) When the pipe extension length exceeds 510 m, additional refrigerant
MAX. 90m oil must be charged (1,000 cc).
(3) It must be less than 30 m when conducting the cooling operation with the outdoor air temperature lower than 10℃.
(4) I f superlink I (previous superlink) is selected, all the range of usage and limitations, not only the limitations of connectable indoor capacity
and connectable number of indoor unit but also of the piping length, operating temperature range and etc., become same as those of KX4 (See
technical manual
’07·KX·KXR-T-114).
In addition to above limitations, all of new functions for KX6 and KXZ such as automatic address
unitrefrigerant systems and etc. will be
Indoor
unit
denotes
setting functionOutdoor
for multiple
cancelled.
(5)When it is required to install in a range of 50 to 70 m, the limitation of use, etc. are different
from those described here. For details, refer to
(2)
MAX. 40m
page 20.
MAX. 90m (2)
(6)When it is required to install in the difference between the longest and shortest(Highest
piping
more
indoor
unit)than 40m, refer to page 21.
'14 • KX-DB-201
'14 • KX-DB-201
Allowable length of refrigerant piping, height difference between indoor and outdoor unit
(1) Branch pipe System (Branch piping used)
Outdoor unit
Indoor unit
MAX.
denotes
90m (2)
MAX. 40m (3)
Ⅳ
First branch
Ⅴ
Ⅵ
MAX. 90m (2)
(Lowest indoor unit)
(2) Header System (Header used)
Outdoor unit
MAX. 18m
Ⅲ
MAX. 18m
Ⅱ
MAX. 130m
MAX. 18m
(Outdoor unit is lower : 40m)
50m (Max.70m)
(Highest indoor unit)
Ⅰ
Indoor unit
MAX. 40m (3)
Ⅲ
First branch
Ⅳ (Lowest indoor unit)
MAX. 18m
Ⅱ
(Header)
MAX. 18m
MAX. 130m
50m (Max.70m)
(Outdoor unit is lower : 40m)
Ⅰ
MAX. 18m
(Highest indoor unit)
MAX. 90m (2)
(3) Mixed System (Branch piping and Header used)
Outdoor unit
Indoor unit
MAX.90m(2)
Ⅱ
Ⅲ
First branch
(Header)
Ⅴ
MAX.90m(2)
Ⅳ
MAX.18m
MAX.18m
Ⅰ
MAX.130m
MAX.18m
50m (Max.70m)
(Outdoor unit is lower: 40m)
(Highest indoor unit)
(3)
MAX.40m
Ⅵ
(Lowest indoor unit)
Note (1) A branch piping system cannot be connected after a header system.
(2) 90m or less (However, difference between the longest and shortest piping : 40m or less (3))
(3) When it is required to install the difference between the longest and shortest piping more than 40m, refer to page 21.
Important
When the Additional refrigerant quantity (P+I) is over the following table, please separate the refrigerant line.
Outdoor unit
280-670
735-1350
1425-1680
P +I (kg)
40
80
100
P: Additional refrigerant quantity for piping (kg)
I : Additional refrigerant quantity for indoor units (kg)
-
15 -
'14 • KX-DB-201
• Combination use
System
Item
Indoor air temperature
(Upper, lower limits)
FDC670KXZE1
FDCS670KXZE1
FDC615KXZE1
FDCS615KXZE1
FDC735KXZE1
FDCS735KXZE1
Number of connected units
Connectable capacity
(1)
2 to 53 units
2 to 58 units
308 - 799
335 - 871
Total piping length (2)
2 to 63 units
2 to 69 units
2 to 73 units
368 - 955
400 - 1040
425 - 1105
1000m or less
Single direction piping length
Actual length : 160m or less, Equivalent length : 185m or less
130m or less
Main pipe length
Allowable pipe length from the first branching
90m or less (However, difference between the longest and shortest piping : 40m or less (6) )
18m or less
Elevation difference between the first branching point and the indoor unit
Difference in
height between
indoor and outdoor
units
Outdoor unit is higher
50m or less (Max.70m or less) (5)
Outdoor unit is lower
40m or less (3)
Difference in the elevation of indoor units in a system
18m or less
Difference in height between outdoor units
(Same system)
MAX. 0.4m
Difference between an outdoor unit and
on outdoor unit side branch pipe
MAX. 5m
Length of oil equalization piping
MAX. 10m
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
Compressor
1 cycle time
stop/start
Stop time
frequency
Power source
voltage
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU, FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
5 min or more (from stop to stop or from start to start)
3 min or more
Voltage fluctuation
Within
Voltage drop during start
Within
System
Item
Indoor air temperature (Upper, lower limits)
FDC900KXZE1
FDCS900KXZE1
FDC950KXZE1
FDCS950KXZE1
15% of rated voltage
FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE1
FDCS1000KXZE1 FDCS1060KXZE1 FDCS1120KXZE1
Refer to page 19
Outdoor air temperature (Upper, lower limits)
Number of connected units
2 to 78 units
2 to 80 units
Connectable capacity
450 - 1170
475 - 1235
Total piping length (2)
2 to 80 units
2 to 80 units
2 to 80 units
500 - 1300
530 - 1378
560 - 1456
1000m or less
Single direction piping length
Main pipe length
Allowable pipe length from the first branching
Actual length : 160m or less, Equivalent length : 185m or less
130m or less
90m or less (However, difference between the longest and shortest piping : 40m or less (6) )
18m or less
Elevation difference between the first branching point and the indoor unit
Difference in
height between
indoor and outdoor
units
10% of rated voltage
Within 3%
Phase unbalance
Indoor units
that can be
used in
combination
Outdoor unit is higher
50m or less (Max.70m or less) (5)
Outdoor unit is lower
40m or less (3)
Difference in the elevation of indoor units in a system
18m or less
Difference in height between outdoor units
(Same system)
MAX. 0.4m
Difference between an outdoor unit and
on outdoor unit side branch pipe
MAX. 5m
Length of oil equalization piping
MAX. 10m
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
Compressor
1 cycle time
stop/start
Stop time
frequency
Power source
voltage
FDC850KXZE1
FDCS850KXZE1
Refer to page 19
Outdoor air temperature
(Upper, lower limits)
Indoor units
that can be
used in
combination
FDC800KXZE1
FDCS800KXZE1
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU,FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
5 min or more (from stop to stop or from start to start)
3 min or more
Voltage fluctuation
Within
Voltage drop during start
Within
10% of rated voltage
15% of rated voltage
Within 3%
Phase unbalance
Note (1) When connecting the indoor unit type FDK, FDFL, FDFU or FDFW Series, limit the connectable capacity not higher than 130%.
(2) When the pipe extension length exceeds 510 m, additional refrigerant oil must be charged (1,000 cc).
(3) It must be less than 30 m when conducting the cooling operation with the outdoor air temperature lower than 10℃.
(4) I f superlink I (previous superlink) is selected, all the range of usage and limitations, not only the limitations of connectable indoor capacity
and connectable number of indoor unit but also of the piping length, operating temperature range and etc., become same as those of KX4 (See
technical manual ’07·KX·KXR-T-114). In addition to above limitations, all of new functions for KX6 and KXZ such as automatic address
setting function for multiple refrigerant systems and etc. will be cancelled.
(5)When it is required to install in a range of 50 to 70 m, the limitation of use, etc. are different from those described here. For details, refer to
page 20.
(6)When it is required to install in the difference between the longest and shortest piping more than 40m, refer to page 21.
-
16 -
'14 • KX-DB-201
System
Item
Indoor air temperature
(Upper, lower limits)
FDC1300KXZE1 FDC1350KXZE1 FDC1425KXZE1
FDC1200KXZE1
FDC1250KXZE1
FDCS1200KXZE1 FDCS1250KXZE1 FDCS1300KXZE1 FDCS1350KXZE1 FDCS1425KXZE1
Refer to page 19
Outdoor air temperature
(Upper, lower limits)
Indoor units
that can be
used in
combination
Number of connected units
Connectable capacity
(1)
3 to 80 units
3 to 80 units
600 - 1560
625 - 1625
Total piping length (2)
3 to 80 units
3 to 80 units
650 - 1690
675 - 1755
713 - 1852
1000m or less
Single direction piping length
Actual length : 160m or less, Equivalent length : 185m or less
130m or less
Main pipe length
Allowable pipe length from the first branching
90m or less (However, difference between the longest and shortest piping : 40m or less (6) )
18m or less
Elevation difference between the first branching point and the indoor unit
Difference in
height between
indoor and outdoor
units
3 to 80 units
Outdoor unit is higher
50m or less (Max.70m or less) (5)
Outdoor unit is lower
40m or less (3)
Difference in the elevation of indoor units in a system
18m or less
Difference in height between outdoor units
(Same system)
MAX. 0.4m
Difference between an outdoor unit and
on outdoor unit side branch pipe
MAX. 5m
Length of oil equalization piping
MAX. 10m
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
Compressor
1 cycle time
stop/start
Stop time
frequency
Power source
voltage
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU,FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
5 min or more (from stop to stop or from start to start)
3 min or more
Voltage fluctuation
Within
10% of rated voltage
Voltage drop during start
Within
15% of rated voltage
Within 3%
Phase unbalance
System FDC1450KXZE1
FDC1500KXZE1
FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE1
FDCS1450KXZE1 FDCS1500KXZE1 FDCS1560KXZE1 FDCS1620KXZE1 FDCS1680KXZE1
Item
Indoor air temperature (Upper, lower limits)
Refer to page 19
Outdoor air temperature (Upper, lower limits)
Indoor units
that can be
used in
combination
Number of connected units
3 to 80 units
3 to 80 units
Connectable capacity
725 - 1885
750 - 1950
Total piping length (2)
3 to 80 units
3 to 80 units
780 - 2080
810 - 2106
840 - 2184
1000m or less
Single direction piping length
Main pipe length
Allowable pipe length from the first branching
Actual length : 160m or less, Equivalent length : 185m or less
130m or less
90m or less (However, difference between the longest and shortest piping : 40m or less (6) )
18m or less
Elevation difference between the first branching point and the indoor unit
Difference in
height between
indoor and outdoor
units
3 to 80 units
Outdoor unit is higher
50m or less (Max.70m or less) (5)
Outdoor unit is lower
40m or less (3)
Difference in the elevation of indoor units in a system
18m or less
Difference in height between outdoor units
(Same system)
MAX. 0.4m
Difference between an outdoor unit and
on outdoor unit side branch pipe
MAX. 5m
Length of oil equalization piping
MAX. 10m
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models FDT, FDTC, FDTW, FDTS, FDTQ,
FDU, FDUM, FDUT, FDUH, FDU-F
Compressor
1 cycle time
stop/start
Stop time
frequency
Power source
voltage
Dew point temperature 28 or less, relative humidity 80% or less
(FDE, FDK, FDFL, FDFU,FDFW : Dew point temperature 23 or less, relative humidity 80% or less)
5 min or more (from stop to stop or from start to start)
3 min or more
Voltage fluctuation
Within
10% of rated voltage
Voltage drop during start
Within
15% of rated voltage
Within 3%
Phase unbalance
Note (1) When connecting the indoor unit type FDK, FDFL, FDFU or FDFW Series, limit the connectable capacity not higher than 130%.
(2) When the pipe extension length exceeds 510 m, additional refrigerant oil must be charged (1,000 cc).
(3) It must be less than 30 m when conducting the cooling operation with the outdoor air temperature lower than 10℃.
(4) I f superlink I (previous superlink) is selected, all the range of usage and limitations, not only the limitations of connectable indoor capacity
and connectable number of indoor unit but also of the piping length, operating temperature range and etc., become same as those of KX4 (See
technical manual ’07·KX·KXR-T-114). In addition to above limitations, all of new functions for KX6 and KXZ such as automatic address
setting function for multiple refrigerant systems and etc. will be cancelled.
(5)When it is required to install in a range of 50 to 70 m, the limitation of use, etc. are different from those described here. For details, refer to
page 20.
(6)When it is required to install in the difference between the longest and shortest piping more than 40m, refer to page 21.
-
17 -
'14 • KX-DB-201
gs+8$"
Allowable length of refrigerant piping, height difference between indoor and outdoor unit
(1) Branch pipe System (Branch piping used)
Outdoor unit
Indoor unit
denotes
MAX. 90m (2)
MAX. 130m
MAX. 5m
MAX. 40m (3)
MAX. 18m
Outdoor
unit 2
MAX. 5m
Outdoor unit
side branch
(DOS-2A-3)
MAX. 18m
MAX. 10m
First branch
MAX. 90m (2)
(Lowest indoor unit)
(2) Header System (Header used)
Outdoor unit
Outdoor
unit 1
Indoor unit
MAX. 40m (3)
MAX. 130m
MAX. 5m
(Highest indoor unit)
MAX. 18m
Outdoor
unit 2
MAX. 5m
MAX. 10m
Outdoor unit
side branch
(DOS-2A-3)
First branch
MAX. 18m
MAX. 0.4m
50m (Max.70m)
(Outdoor unit is lower : 40m)
Oil equalization
piping
MAX. 18m
(Highest indoor unit)
(Header)
MAX. 18m
Outdoor
unit 1
MAX. 0.4m
50m (Max.70m)
(Outdoor unit is lower : 40m)
Oil equalization
piping
(Lowest indoor unit)
MAX. 90m (2)
(3) Mixed System (Branch piping and Header used)
Outdoor unit
Indoor unit
MAX.90m(2)
MAX.18m
Ⅰ
MAX.130m
Ⅱ
(Header)
Ⅴ
MAX.90m(2)
Ⅳ
MAX.18m
Ⅲ
First branch
MAX.18m
(Outdoor unit is lower: 40m)
50m (Max.70m)
(Highest indoor unit)
MAX.40m(3)
Ⅵ
(Lowest indoor unit)
(4) Pipe system for combination of 3 outdoor units (Displaying only outdoor units)
Oil equalization
piping
Outdoor
unit 3
MAX. 130m
L1 ≦ 5m
L2 + L4 ≦ 5m
L3 + L4 ≦ 5m
MAX. 0.4m
L3
Outdoor
unit 2
L2
Lc
L4
La + Lb ≦ 10m
Lb + Lc ≦ 10m
Lc + La ≦ 10m
Outdoor
unit 1
L1
Lb
La
Outdoor unit
side branch
(DOS-3A-3)
First branch
Note (1) A branch piping system cannot be connected after a header system.
(2) 90m or less (However, difference between the longest and shortest piping : 40m or less (3))
(3) When it is required to install the difference between the longest and shortest piping more than 40m, refer to page 21.
Important
When the Additional refrigerant quantity (P+I) is over the following table, please separate the refrigerant line.
Outdoor unit
280-670
735-1350
1425-1680
P +I (kg)
40
80
100
P: Additional refrigerant quantity for piping (kg)
I : Additional refrigerant quantity for indoor units (kg)
- 18 -
'14 • KX-DB-201
Operating temperature range
50
Outdoor air D.B.
temperature
°CDB
Cooling operation
46℃DB
43℃DB
40
30
20
10
0
-10
-20
10
-15℃DB
12
14
16
18
20
22
24
26
Indoor air W.B. temperature °CWB
*In case it is the promised installation location that the outdoor unit is used on conditions with
the ambient temperature of 43℃ or more, refer to page 7 (2.2 Exterior dimensions).
35
Indoor air D.B.
temperature
°CDB
Heating operation
30
27℃DB
25
20
15
10
5
-20
-15
-10
-5
0
5
10
15
20
25
Outdoor air W.B. temperature °CWB
“CAUTION” Cooling operation under low outdoor air temperature conditions
KXZ models can be operated in cooling mode at low outdoor air temperature condition within above temperature range. However in
case of severely low temperature conditions if the following precaution is not observed, it may not be operated in spite of operable
temperature range mentioned above and cooling capacity may not be established under certain conditions.
[Precaution]
In case of severely low temperature condition
1) Install the outdoor unit at the place where strong wind cannot blow directly into the outdoor unit.
2) If there is no installation place where can prevent strong wind from directly blowing into the outdoor unit, prepare a windbreak
fence or something like that locally in order to divert the strong wind from the outdoor unit.
[Reason]
Under the low outdoor air temperature conditions of -5˚C or lower, if strong wind directly blow into the outdoor unit, the outdoor
heat exchanger temperature will drop, even though the outdoor fan is stopped by outdoor fan control. This makes high and low pressures to drop as well. This low pressure drop makes the indoor heat exchanger temperature to drop and will activate anti-frost control
at indoor heat exchanger at frequent intervals, that cooling operation may not be established for any given time.
-
19 -
'14 • KX-DB-201
Specification for installation with large head difference (Applicable to: FDC280 - 1680KXZE1)
In case when the outdoor unit is installed at a higher place and the difference in the elevation between the indoor and the outdoor
units is larger than 50 m and smaller than 70 m, the limitation on application differs partially from ordinary applications and, instead,
the following specification applies. The pipe size, refrigerant amount and way of switch setting become also different.
In the range of use, the outdoor air temperature (lower limit), indoor units allowed to combine, total piping length and difference in
the elevation between indoor units in the same system are different from ordinary applications.
Table 1 Range of use
FDC280-1680KXZE1
FDCS280-1680KXZE1
Item
Indoor air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor units that can be
used in combination
Total piping length
Refer to Table 2
Number of connected units
Connectable capacity
Refer to Table 3
510m or less
130m or less
Actual length:160m or less, Equivalent length:185m or less
90m or less
(However, difference between the longest and shortest piping:40m or less)
Main pipe length
Single direction piping length
Allowable pipe length from the first branching
Elevation difference between
the first branching point and
Allowable difference in the the indoor unit
Outdoor unit is higher
elevation
Outdoor unit is lower
Difference in the elevation of
indoor units in a system
18m or less
50m or more-70m or less
40m or less
15m or less
0.4m or less
Difference in the elevation
Elevation from outdoor unit to
Limitation on piping from
branching pipe at outdoor unit side
outdoor unit to branching
Oil equalizing pipe length
pipe at outdoor unit side
Length between outdoor branching
pipes for a combination of 3 units
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Only models
FDT,FDTC,FDTW,FDTQ,FDTS,FDU,FDUM,FDUH,FDUT
Compressor stop/start
frequency
Power source voltage
5m or less
10m or less
5m or less
。
Dew point temperature 28 C or less, relative humidity 80% or less
。
(FDT,FDK,FDFL,FDFU,FDFW:Dew point temperature 28 C or less, relative humidity
80% or less)
5 min or less (from stop to stop or from start to start)
3 min or more
Within ±10% of rated voltage
Within –15% of rated voltage
Within 3%
1 cycle time
Stop time
Voltage fluctuation
Voltage drop during start
Phase unbalance
Table 3 Number of connectable indoor units and capacity range
Table 2 Indoor air temperature/Out door air t e mpe rat ure
Outdoor air D.B.
temperature
°CDB
Cooling operation
Model/Item
50
43℃DB
40
30
20
10
0
-5℃DB
-10
-20
10
12
14
16
18
20
22
24
Indoor air W.B. temperature °CWB
Indoor air D.B.
temperature
°CDB
Heating operation
35
30
27℃DB
25
20
15
10
5
-10
-5
0
5
10
15
20
25
Outdoor air W.B. temperature °CWB
-
20 -
26
FDC(S)280KXZE1
FDC(S)335KXZE1
FDC(S)400KXZE1
FDC(S)450KXZE1
FDC(S)475KXZE1
FDC(S)500KXZE1
FDC(S)560KXZE1
FDC(S)615KXZE1
FDC(S)670KXZE1
FDC(S)735KXZE1
FDC(S)800KXZE1
FDC(S)850KXZE1
FDC(S)900KXZE1
FDC(S)950KXZE1
FDC(S)1000KXZE1
FDC(S)1060KXZE1
FDC(S)1120KXZE1
FDC(S)1200KXZE1
FDC(S)1250KXZE1
FDC(S)1300KXZE1
FDC(S)1350KXZE1
FDC(S)1425KXZE1
FDC(S)1450KXZE1
FDC(S)1500KXZE1
FDC(S)1560KXZE1
FDC(S)1620KXZE1
FDC(S)1680KXZE1
Number of
connectable
units
1 to 1 8
1 to 2 2
1 to 2 6
1 to 3 0
1 to 3 1
1 to 3 3
1 to 3 7
2 to 4 1
2 to 4 4
2 to 4 9
2 to 5 3
2 to 5 6
2 to 6 0
2 to 6 3
2 to 6 6
2 to 7 0
2 to 7 4
3 to 8 0
3 to 8 0
3 to 8 0
3 to 8 0
3 to 8 0
3 to 8 0
3 to 8 0
3 to 8 0
3 to 8 0
3 to 8 0
Connectable
capacity
140 - 280
168 - 335
200 - 400
225 - 450
238 - 475
250 - 500
280 - 560
308 - 615
335 - 670
368 - 735
400 - 800
425 - 850
450 - 900
475 - 950
500 - 1000
530 - 1060
560 - 1120
600 - 1200
625 - 1250
650 - 1300
675 - 1350
713 - 1425
725 - 1450
750 - 1500
780 - 1560
810 - 1620
840 - 1680
'14 • KX-DB-201
<Pipe size selection>
In the figure for pipe selection, sizes of main pipe and the pipe between the branch at the indoor side and the indoor unit are selected
on the basis different from normal practice.
(1) Main pipe (branch of the outdoor unit – first branch at the indoor side)
Size of liquid pipe is different. Change the size of main pipe according to Table 4.
When the maximum length (from the outdoor unit to the furthest indoor unit) is larger than 90 m (actual length), change the size
of main pipe according to Table 4.
Table 4 Main pipe size
Pipe size for an actual length of 90m or longer
Gas pipe
Liquid pipe
φ12.7 × t 0.8
φ25.4 (φ22.22) × t 1.0
Main pipe size (normal)
Gas pipe
Liquid pipe
φ12.7 × t 0.8
φ22.22 × t 1.0
φ25.4 (φ22.22) × t 1.0
φ25.4 (φ28.58) × t 1.0
Outdoor unit
280
335
400
450
475
500
560
615
670
735
800
850
900
950
1000
1060
1120
1200
1250
1300
1350
1425
1450
1500
1560
1620
1680
φ28.58 × t 1.0
φ15.88 × t 1.0
φ15.88 × t 1.0
φ28.58 × t 1.0
φ31.8 × t 1.1
(φ34.92 × t 1.2)
φ31.8 × t 1.1
(φ28.58 × t 1.0)
φ19.05 × t 1.0
φ19.05 × t 1.0
φ38.1 × t 1.35
(φ34.92 × t 1.2)
φ38.1 × t 1.35
(φ34.92 × t 1.2)
φ22.22 × t 1.0
φ22.22 × t 1.0
(2) Between branch at the indoor side and indoor unit
Size of gas pipe for indoor unit with capacity larger than 112 is different. Change the size of pipe
connected to indoor unit according to Table 5.
Table 5 Indoor unit connecting pipe size
Capacity
Indoor unit
Gas pipe
15,22,28
36,45,56
71,90
112,140,160
224
280
Liquid pipe
φ 9.52 × t0.8
φ 12.7 × t0.8
φ15.88 × t1.0
φ19.05 × t1.0
φ22.22 × t1.0
φ 25.4 × t1.0
φ 6.35 × t0.8
φ 9.52 × t0.8
(3) Refrigerant quantity
In addition to normal charge quantity for refrigerant pipes, charge quantity for the difference in capacity between the indoor and
the outdoor units, and standard additional refrigerant quantity, measure and charge the additional refrigerant quantity for the
installation with the difference in the elevation being over 50 m and less than 70 m.
Table 6 Additional refrigerant quantity for the installation with the difference in the elevation being over 50 m and less than 70 m
Outdoor unit
280
335
400
450
475
500
560
(kg)
0.3
0.5
0.6
0.7
0.8
0.8
0.9
Outdoor unit
615
670
735
800
850
900
950
(kg)
0.8
1.0
1.1
1.2
1.3
1.4
1.6
Outdoor unit
1000
1060
1120
1200
1250
1300
1350
(kg)
1.6
1.7
1.8
1.8
1.9
2.0
2.1
Outdoor unit
1425
1450
1500
1560
1600
1680
(kg)
2.4
2.4
2.4
2.5
2.6
2.7
(4) Microcomputer control
Setting of microcomputer control needs to be changed when the outdoor unit is installed upwards and the difference in elevation is larger
than 50 m and less than 70 m. Make sure to set SW6-4 at ON position on both the master and slave units, before turning the power on.
When the difference between the longest and shortest piping is longer
than 40 m, adjust the difference in the elevation of indoor units in a
system such that it will fall in the OK range on the following graph.
When the difference in the elevation between the indoor and the outdoor
units is 50 m – 70 m, the difference between the longest and shortest
piping cannot exceed 40 m. Reduce it to less than 40 m.
If the refrigerant quantity over occurs when the difference between the
ongest and shortest piping is longer than 40 m, there is a risk that the
heating capacity becomes insufficient. Take sufficient care to adjust
the additional refrigerant quantity at correct value.
Difference between the longest
and shortest piping (m)
Specification for installation with the difference between the longest and shortest piping more than 40m
85
80
75
70
NO
65
60
55
OK
50
45
40
0
2
4
6
8
10
12
14
16
18
Difference in the elevation of indoor units in a system (m)
-
21 -
-
Thermistor(Entrance)
(Thi-R2)
Thermistor
(Thi-A)
Thermistor(Exit)
(Thi-R3)
Thermistor(Entrance)
(Thi-R2)
Thermistor
(Thi-A)
22 -
Strainer
Electronic
expansion valve
Indoor unit
Strainer
Thermistor(Bend)
(Thi-R1)
Electronic
expansion valve
Indoor unit
To next indoor units
Liquid line
For outdoor
unit 2
Strainer
Oil
separator
Thermistor
(Tho-C1)
Service valve
Thermistor
(Tho-D1)
Muffler
High pressure
switch(63H1-1)
4way valve
Strainer
Receiver
Solenoid
valve
(SV11)
Strainer
Accumlator
Thermistor
(Tho-S)
Low pressure
sensor(PSL)
Check joint
Heat
exchanger
Strainer
Sub-cooling
coil
(Tho-R4)
(Thermistor,Entrance・Back)
Thi-R1, R2 : Heating operation : Indoor fan control.
Cooling operation : Frost prevention control.
Super heat control.
Thi-R3 :
For super heat control of cooling operation.
Tho-D :
For control of discharge pipe temperature.
Tho-C :
For control of temperature under the dome.
Tho-S :
For control of suction pipe temperature.
Tho-R1, R2 : For control of defrosting.
Tho-A :
For control of defrosting.
Tho-R3, R4 : Electronic expansion valve (EEVH1, 2) control of heating operation
Tho-SC :
Electronic expansion valve (EEVSC) control of cooling operation.
Tho-H :
For super heat control of sub-cooling coil.
Electronic
Strainer
expansion valve
(EEVSC)
Sub-cooling coil
Capillary tube
Check joint
High pressure
sensor(PSH)
Strainer Sub-cooling coil
Thermistor
(Tho-SC)
Strainer
Compressor 1
CM1
Check valve
Service valve
(Oil equalization line)
Notes (1) Preset point of protective devices
63H1-1 : Open 4.15MPa, Close 3.15MPa
(For protection)
(2) Function of thermistor
PSH :
For compressor control
3.70 ON (MPa)
PSL :
ON 0.18MPa, OFF 0.20MPa
(For compressor control)
ON 0.134MPa, OFF 0.18MPa
(For protection)
Strainer
Heat
exchanger
Strainer
Heat
exchanger
Solenoid
valve(SV6)
Capillary tube
Thermistor(Bend)
(Thi-R1)
Service valve
Capillary tube
(Tho-R3)
(Thermistor,Entrance・Front)
Sub-cooling coil
Thermistor
(Tho-H)
Thermistor(Exit)
(Thi-R3)
Gas line
Capillary tube
Solenoid
valve
(SV1)
(Tho-R1)
(Thermistor,Exit・Front)
Electronic
expansion valve
(EEVH1)
Heat
exchanger
Strainer
Sub-cooling
coil
Thermistor
(Tho-A)
Strainer
(Tho-R2)
(Thermistor,Exit・Back)
Electronic
expansion valve
(EEVH2)
Outdoor unit
'14 • KX-DB-201
4. PIPING SYSTEM
Models FDC280KXZE1, 335KXZE1
FDCS280KXZE1, 335KXZE1
PCB003Z822
-
Thermistor(Entrance)
(Thi-R2)
Thermistor
(Thi-A)
Thermistor(Exit)
(Thi-R3)
Thermistor(Entrance)
(Thi-R2)
Thermistor
(Thi-A)
23 -
Strainer
Electronic
expansion valve
Indoor unit
Strainer
Thermistor(Bend)
(Thi-R1)
Electronic
expansion valve
To next indoor units
Liquid line
For outdoor
unit 2
Strainer
Oil
separator
Check valve
Service valve
Electronic
Strainer
expansion valve
(EEVSC)
Receiver
Strainer
Accumlator
Thermistor
(Tho-S)
Low pressure
sensor(PSL)
Check joint
Strainer
Sub-cooling
coil
(Tho-R4)
(Thermistor,Entrance・Back)
(Tho-R3)
Sub-cooling coil
(Thermistor,Entrance・Front)
Thermistor
(Tho-H)
Electronic
expansion valve
Heat exchanger
(EEVH1)
(Tho-R1)
(Thermistor,Exit・Front)
Thi-R1, R2 : Heating operation : Indoor fan control.
Cooling operation : Frost prevention control.
Super heat control.
Thi-R3 :
For super heat control of cooling operation.
Tho-D :
For control of discharge pipe temperature.
Tho-C :
For control of temperature under the dome.
Tho-S :
For control of suction pipe temperature.
Tho-R1, R2 : For control of defrosting.
Tho-A :
For control of defrosting.
Tho-R3, R4 : Electronic expansion valve (EEVH1, 2) control of heating operation
Tho-SC :
Electronic expansion valve (EEVSC) control of cooling operation.
Tho-H :
For super heat control of sub-cooling coil.
Strainer Sub-cooling coil
Thermistor
(Tho-SC)
Capillary tube
Sub-cooling coil
Thermistor
(Tho-D1)
Muffler
High pressure
switch(63H1-1)
CM1
Strainer
4way valve
Check joint
High pressure
sensor(PSH)
Compressor 1
Thermistor
(Tho-C1)
Service valve
(Oil equalization line)
Notes (1) Preset point of protective devices
63H1-1 : Open 4.15MPa, Close 3.15MPa
(For protection)
(2) Function of thermistor
PSH :
For compressor control
3.70 ON (MPa)
PSL :
ON 0.18MPa, OFF 0.20MPa
(For compressor control)
ON 0.134MPa, OFF 0.18MPa
(For protection)
Strainer
Heat
exchanger
Strainer
Indoor unit
Solenoid
valve(SV6)
Capillary tube
Heat
exchanger
Capillary tube
Thermistor(Bend)
(Thi-R1)
Service valve
Solenoid
valve(20UF)
Thermistor(Exit)
(Thi-R3)
Gas line
Capillary tube
Solenoid
valve
(SV1)
Strainer
Strainer
Sub-cooling
coil
Thermistor
(Tho-A)
(Tho-R2)
(Thermistor,Exit・Back)
Heat exchanger
Electronic
expansion valve
(EEVH2)
Outdoor unit
'14 • KX-DB-201
Models FDC400KXZE1, 450KXZE1
FDCS400KXZE1, 450KXZE1
PCB003Z823
-
Thermistor(Entrance)
(Thi-R2)
Thermistor
(Thi-A)
Thermistor(Exit)
(Thi-R3)
Thermistor(Entrance)
(Thi-R2)
Thermistor
(Thi-A)
24 -
Strainer
Electronic
expansion valve
Indoor unit
Strainer
Thermistor(Bend)
(Thi-R1)
Electronic
expansion valve
To next indoor units
Liquid line
For outdoor
unit 2
Strainer
Oil
separator
Service valve
Strainer
Oil
separator
Electronic
Strainer
expansion valve
(EEVSC)
Sub-cooling coil
Thermistor
(Tho-C2)
Capillary tube
Receiver
Compressor 2
CM2
Thermistor
(Tho-D2)
Check valve
High pressure
switch(63H1-2)
Strainer
Solenoid
valve
(SV11)
Strainer
Accumlator
Thermistor
(Tho-S)
Low pressure
sensor(PSL)
Check joint
Strainer
Sub-cooling
coil
(Tho-R4)
(Thermistor,Entrance・Back)
(Tho-R3)
(Thermistor,Entrance・Front)
Thi-R1, R2 : Heating operation : Indoor fan control.
Cooling operation : Frost prevention control.
Super heat control.
Thi-R3 :
For super heat control of cooling operation.
Tho-D1, D2 : For control of discharge pipe temperature.
Tho-C1, C2 : For control of temperature under the dome.
Tho-S :
For control of suction pipe temperature.
Tho-R1, R2 : For control of defrosting.
Tho-A :
For control of defrosting.
Tho-R3, R4 : Electronic expansion valve (EEVH1, 2) control of heating operation
Tho-SC :
Electronic expansion valve (EEVSC) control of cooling operation.
Tho-H :
For super heat control of sub-cooling coil.
Strainer Sub-cooling coil
Thermistor
(Tho-SC)
Service valve
(Oil equalization line)
Strainer
Compressor 1
CM1
Muffler
High pressure
switch(63H1-1)
Thermistor
(Tho-D1)
Check valve
Thermistor
(Tho-C1)
Notes (1) Preset point of protective devices
63H1-1, 2 : Open 4.15MPa, Close 3.15MPa
(For protection)
(2) Function of thermistor
PSH :
For compressor control
3.70 ON (MPa)
PSL :
ON 0.18MPa, OFF 0.20MPa
(For compressor control)
ON 0.134MPa, OFF 0.18MPa
(For protection)
Strainer
Heat
exchanger
Strainer
Indoor unit
Solenoid
valve(SV6)
Capillary tube
Check joint
High pressure
sensor(PSH)
Solenoid
valve
Capillary tube(SV7)
Heat
exchanger
Capillary tube
4way valve
Capillary tube
Thermistor(Bend)
(Thi-R1)
Capillary tube
Service valve
Capillary tube
Solenoid
valve
(SV1)
Thermistor(Exit)
(Thi-R3)
Gas line
Solenoid
valve(SV2) Capillary tube
(Tho-R1)
(Thermistor,Exit・Front)
Heat exchanger
Sub-cooling coil
Thermistor
(Tho-H)
Electronic
expansion valve
(EEVH1)
Strainer
Strainer
Sub-cooling
coil
Thermistor
(Tho-A)
(Tho-R2)
(Thermistor,Exit・Back)
Heat exchanger
Electronic
expansion valve
(EEVH2)
Outdoor unit
'14 • KX-DB-201
Models FDC475KXZE1, 500KXZE1, 560KXZE1
FDCS475KXZE1, 500KXZE1, 560KXZE1
PCB003Z824
'14 • KX-DB-201
5. SELECTION CHART
(1) Equipment selection flow
Calculate the load for each room separately, then determine the indoor load.
Select an indoor unit that matches the indoor load (tentative).
Calculate the temperature compensation,
then calculate the indoor unit capacity.
(See item () (a) for the calculation method.)
Indoor unit
capacity (tentative)
Indoor Load
Change the indoor unit.
Select the outdoor unit (tentative).
NO
Calculate temperature compensation and piping
compensation, etc., then calculate the outdoor unit
capacity. (See item () (b) for the calculation method.)
YES
Calculate the total indoor unit capacity.
Calculate the system capacity
(See item () (c) for the calculation method.)
NO
Total indoor unit
capacity System Capacity
Change the outdoor unit.
YES
Calculate the indoor unit capacity.
(See item () (d) for the calculation method.)
Indoor unit
capacity Indoor Load
YES
Equipment selection complete.
-
25 -
NO
'14 • KX-DB-201
(2) Capacity calculation method
(a) Calculating the indoor unit capacity compensation
Indoor unit capacity (cooling, heating) = Indoor unit total rated capacity
× Capacity compensation coefficient according to temperature conditions
See item (3) (a) concerning the capacity compensation coefficient according to temperature conditions.
(b) Calculating the outdoor unit capacity compensation
Outdoor Unit Capacity (Cooling, Heating) = Outdoor unit rated capacity (rated capacity when 100% connected)
× Capacity compensation coefficient according to temperature conditions
× Capacity compensation coefficient according to piping length
× Capacity compensation coefficient according to height difference
× Correction of heating capacity in relation to the frost on the outdoor unit
heat exchanger
× Capacity compensation coefficient according to indoor unit connection
capacity
See item (3) (a) concerning the capacity compensation coefficient according to temperature conditions.
See item (3) (b) concerning the capacity compensation coefficient according to piping length.
See item (3) (c) concerning the capacity compensation coefficient according to height difference. This compensation
should be carried out only in cases where the outdoor unit is lower during cooling and higher during heating.
See item (3) (d) correction of heating capacity in relation to the frost on the outdoor unit heat exchanger. This compensation should be carried out only when calculating the heating capacity.
See item (3) (e) concerning the capacity compensation coefficient according to indoor unit connected capacity. This
compensation should be carried out only in cases where the indoor unit total capacity is 100% or higher.
(c) Calculating system capacity
Compare the capacities determined in items (a) and (b) above and let the smaller value be the system capacity (cooling,
heating).
In cases where indoor unit total capacity (cooling, heating) > outdoor unit capacity (cooling, heating)
System capacity (cooling, heating) = Outdoor unit capacity (cooling, heating)
In cases where indoor unit total capacity (cooling, heating) < outdoor unit capacity (cooling, heating)
System capacity (cooling, heating) = Indoor unit capacity (cooling, heating)
(d) Calculating indoor unit capacity [item (c) 1 only]
Indoor unit capacity (cooling, heating) = System capacity (cooling, heating)
× [(Indoor unit capacity) / (Indoor unit total capacity)]
Capacity calculation examples
Example 1
Cooling (when the indoor unit connected total capacity is less than 100%)
• Outdoor unit FDC450KXZE1...................................................... 1 Unit
• Indoor unit FDT56KXE6F........................................................... 7 Units
• Piping length ............................................................................... 60 m (Equivalent length)
• Indoor, outdoor unit height difference......................................... 15 m (Outdoor unit is lower)
• Temperature conditions ............................................................... Outdoor temperature: 33˚C DB
• Temperature conditions................................................................ Indoor temperature: 19˚C WB
<Indoor unit total cooling capacity>: Item (2) (a) calculation.
• Indoor unit rated cooling capacity: 5.6 kW
• Capacity compensation coefficient according to temperature conditions:
1.02 (Calculated according to Indoor 19˚C WB / Outdoor 33˚C DB); (See page 28)
.
Indoor unit cooling capacity: 5.6 kW × 1.02 =. 5.7 kW
• Indoor unit total cooling capacity calculation;
indoor unit total cooling capacity: 5.7 kW × 7 units = 39.9 kW
<Outdoor unit maximum cooling capacity> : Item (2) (b) calculation
• Outdoor unit rated cooling capacity: 45.0 kW
• Capacity compensation coefficient according to temperature conditions:
1.02 (Calculated according to Indoor 19˚C WB / Outdoor 33˚C DB); (See page 28)
.
Outdoor unit cooling capacity: 45.0 kW × 1.02 =. 45.9 kW
• Capacity compensation coefficient according to piping length: 0.94 (calculated according to 60 m length); (See page 30)
.
45.9 kW × 0.94 =. 43.1 kW
-
26 -
'14 • KX-DB-201
• Capacity compensation coefficient according to height difference: 0.97 (calculated according to 15 m difference); (See page 34)
.
43.1 kW × 0.97 =. 41.8 kW
• Capacity compensation coefficient according to indoor unit connected total capacity: 1.0 , (56 × 7) / 450 < 100%)
No compensation
<System cooling capacity>: Item (2) (c) calculation
Compare the indoor unit total cooling capacity and the outdoor unit maximum cooling capacity. The smaller value is the actual
system cooling capacity.
• Indoor unit total cooling capacity: 39.9 kW
e System cooling capacity: 39.9 kW
• Outdoor unit maximum cooling capacity: 41.8 kW
<Indoor unit capacity compensation> No compensation (5.7 kW)
Example 2
Cooling (when the indoor unit connected total capacity is 100% or higher)
• Outdoor unit FDC450KXZE1...................................................... 1 Unit
• Indoor unit FDT56KXE6F........................................................... 10 Units
• Piping length ............................................................................... 60 m (Equivalent length)
• Indoor, outdoor unit height difference......................................... 15 m (Outdoor unit is higher)
• Temperature conditions ............................................................... Outdoor temperature: 35˚C DB
• Temperature conditions................................................................ Indoor temperature: 18˚C WB
<Indoor unit total cooling capacity>: Item (2) (a) calculation.
• Indoor unit rated cooling capacity: 5.6 kW
• Capacity compensation coefficient according to temperature conditions:
0.95 (Calculated according to Indoor 18˚C WB / Outdoor 35˚C DB); (See page 28)
.
Indoor unit cooling capacity: 5.6 kW × 0.95 =. 5.3 kW
• Indoor unit total cooling capacity calculation;
indoor unit total cooling capacity: 5.3 kW × 10 units .=. 53.0 kW
<Outdoor unit maximum cooling capacity> : Item (2) (b) calculation
• Outdoor unit rated cooling capacity: 45.0 kW
• Capacity compensation coefficient according to temperature conditions:
0.95 (Calculated according to Indoor 18˚C WB / Outdoor 35˚C DB); (See page 28)
.
Outdoor unit cooling capacity: 45.0 kW × 0.95 =. 42.8 kW
• Capacity compensation coefficient according to piping length: 0.94 (calculated according to 60 m length); (See page 30)
.
42.8 kW × 0.94 =. 40.2 kW
• Capacity compensation coefficient according to height difference: 1.0 (the outdoor unit is higher during cooling)
No compensation
.
• Capacity compensation coefficient according to indoor unit connected total capacity: 1.04 , (56 × 10) / 450 =. 124%) (See page 36)
..
40.2 kW × 1.04 = 41.8 kW
<System cooling capacity>: Item (2) (c) calculation
Compare the indoor unit total cooling capacity and the outdoor unit maximum cooling capacity. The smaller value is the actual
system cooling capacity.
• Indoor unit total cooling capacity
: 53.0 kW e System cooling capacity: 41.8 kW
• Outdoor unit maximum cooling capacity: 41.8 kW
<Indoor unit cooling capacity Compensation>: Item (2) (d) calculation.
41.8 kW × 5.3 kW .
=. 4.2 kW
53.0 kW
Example 3
Heating (when the indoor unit connected total capacity is 100% or higher)
• Outdoor unit FDC450KXZE1...................................................... 1 Unit
• Indoor unit FDT56KXE6F........................................................... 10 Units
• Piping length ............................................................................... 60 m (Equivalent length)
• Indoor, outdoor unit height difference......................................... 20 m (Outdoor unit is higher)
• Temperature conditions ............................................................... Outdoor temperature: 6˚C WB
• Temperature conditions................................................................ Indoor temperature: 19˚C DB
<Indoor unit total heating capacity>: Item (2) (a) calculation.
• Indoor unit rated heating capacity:6.3 kW
• Capacity compensation coefficient according to temprature conditions:
1.04 (Calculated according to Outdoor 6˚C WB / Indoor 19˚C DB); (See page 29)
Indoor unit heating capacity: 6.3 kW × 1.04 .=. 6.6 kW
• Indoor unit total heating capacity calculation;
.
indoor unit total heating capacity: 6.6 kW × 10 units =. 66.0 kW
-
27 -
'14 • KX-DB-201
<Outdoor unit maximum heating capacity> : Item (2) (b) calculation
• Outdoor unit rated heating capacity: 50.0 kW
• Capacity compensation coefficient according to temperature conditions:
1.04 (Calculated according to Outdoor 6˚C WB / Indoor 19˚C DB); (See page 29)
Outdoor unit heating capacity: 50.0 kW x 1.04 = 52.0 kW
• Capacity compensation coefficient according to piping length: 0.982 (calculated according to 60 m length); (See page 33)
.
52.0 kW x 0.982 =. 51.0 kW
• Capacity compensation coefficient according to height difference: 0.96 (calculated according to 20 m difference); (See page 34)
.
51.0 kW x 0.96 =. 49.0 kW
• Correction of heating capacity in relation to the frost on the outdoor unit heat exchanger:
1.0 (calculated according to 6˚C WB); (See page 34)
.
49.0 kW x 1.0 =. 49.0 kW.
.
• Capacity compensation coefficient according to indoor unit connected total capacity: 1.0 ← (56 x 10) / 450 =. 124%) (See page 36)
.
49.0 kW x 1.0 =. 49.0 kW.
<System heating capacity> : Item (2) (c) calculation
Compare the indoor unit total heating capacity and the outdoor unit maximum heating capacity. The smaller value is the actual
system heating capacity.
• Indoor unit total heating capacity
: 66.0 kW ⇨ System heating capacity: 49.0 kW
• Outdoor unit maximum heating capacity : 49.0 kW
<Indoor unit heating capacity compensation> : Item (2) (d) calculation
49.0 kW x 6.6 kW .
=. 4.9 kW
66.0 kW
(3) Capacity compensation coefficient
(a) Capacity compensation coefficient and power consumption compensation coefficient according to indoor and outdoor temperature conditions.
1) Capacity compensation coefficient
1.40
◆ Cooling
Indoor air W.B. temperature 24˚CWB
1.35
Indoor air W.B. temperature 26˚CWB
Capacity compensation coefficient
1.30
1.25
Indoor air W.B. temperature 22˚CWB
1.20
Indoor air W.B. temperature 21˚CWB
1.15
1.10
Indoor air W.B. temperature 20˚CWB
1.05
Indoor air W.B. temperature 19˚CWB
1.00
0.95
Indoor air W.B. temperature 18˚CWB
0.90
Indoor air W.B. temperature 17˚CWB
0.85
0.80
Indoor air W.B. temperature 16˚CWB
Indoor air W.B. temperature 15˚CWB
0.75
0.70
Indoor air W.B. temperature 14˚CWB
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
Outdoor air D.B. temperature (˚CDB)
32
34
36
38
40
42
44
46
Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment.
(2) When performing the cooling operation with the outdoor air temperature being -5°C or under, a windbreak fence must be
installed.
--140 28 -
'14 • KX-DB-201
◆ Heating
1.20
1.15
Outdoor air W.B. temperature 18˚CWB
Capacity compensation coefficient
1.10
Outdoor air W.B. temperature 10˚CWB
1.05
Outdoor air W.B. temperature 14˚CWB
1.00
Outdoor air W.B. temperature 6˚CWB
0.95
Outdoor air W.B. temperature 2˚CWB
0.90
Outdoor air W.B. temperature -2˚CWB
0.85
Outdoor air W.B. temperature -6˚CWB
0.80
0.75
Outdoor air W.B. temperature -10˚CWB
0.70
0.65
Outdoor air W.B. temperature -15˚CWB
0.60
0.55
17
16
18
Outdoor air W.B. temperature -20˚CWB
19
20
21
22
23
24
Indoor air D.B. temperature(˚CDB)
Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment.
2) Power consumption correction factor
1.30
◆ Cooling
Power consumption compensation coefficient
1.25
1.20
1.15
Indoor air W.B. temperature 26˚CWB
1.10
Indoor air W.B. temperature 24˚CWB
1.05
1.00
Indoor air W.B. temperature 22˚CWB
0.95
Indoor air W.B. temperature 21˚CWB
0.90
0.85
Indoor air W.B. temperature 20˚CWB
0.80
Indoor air W.B. temperature 19˚CWB
0.75
Indoor air W.B. temperature 18˚CWB
0.70
0.65
Indoor air W.B. temperature 17˚CWB
0.60
Indoor air W.B. temperature 16˚CWB
0.55
0.50
Indoor air W.B. temperature 15˚CWB
0
2
4
6
8
Indoor air W.B. temperature 14˚CWB
10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
Outdoor air D.B. temperature(˚CDB)
Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment.
-141
29 --
'14 • KX-DB-201
1.25
◆ Heating
Power consumption compensation coefficient
Outdoor air W.B. temperature 6˚CWB
1.20
Outdoor air W.B. temperature -2˚CWB
Outdoor air W.B. temperature 2˚CWB
Outdoor air W.B. temperature -6˚CWB
1.15
1.10
Outdoor air W.B.
temperature 10˚CWB
1.05
1.00
0.95
Outdoor air W.B.
temperature -15˚CWB
0.90
0.85
Outdoor air W.B. temperature -10˚CWB
0.80
Outdoor air W.B. temperature -20˚CWB
Outdoor air W.B. temperature 14˚CWB
0.75
Outdoorair W.B. temperature 18˚CWB
0.70
16
17
18
19
20
21
22
23
24
Indoor air D.B. temperature(˚CDB)
Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment.
(b) Correction of cooling and heating capacity in relation to one way length of refrigerant piping.
(Note) This table is for reference only. If the refrigerant piping one way equivalent after the first branch is extended longer than 40 m, it could
drop further by about 10% in the worst case.
1) Cooling
Model FDC(S)280KXZE1
Model FDC(S)335KXZE1
1.00
Gas pipe: ø25.4
0.95
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
Gas pipe: ø22.22
0.90
0.85
0.80
0
20
40
60
0.95
Gas pipe: ø25.4
0.90
0.85
Gas pipe: ø22.22*
0.80
80 90100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Capacity compensation
coefficient
Capacity compensation
coefficient
0.95
Gas pipe: ø25.4
0.85
20
40
60
80
100
60
80
100 120 140 160 180
Model FDC(S)450KXZE1
*
0
40
1.00
Gas pipe: ø28.58
0.80
20
Refrigerant piping one way equivalent length (m)
Model FDC(S)400KXZE1
1.00
0.90
0
120
140
160
180
Refrigerant piping one way equivalent length (m)
Note (1) Parts with the * mark show the piping size in case used in Europe.
- 142
30 --
Gas pipe: ø31.8
0.95
Gas pipe: ø28.58
0.90
0.85
0.80
0
20
40
60
80 90 100
120
140
160
180
Refrigerant piping one way equivalent length (m)
'14 • KX-DB-201
Model FDC(S)475KXZE1
1.00
Gas pipe: ø31.8
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
Model FDC(S)500KXZE1
0.95
Gas pipe: ø28.58
0.90
0.85
0.80
0
20
40
60
0.95
Gas pipe: ø28.58
0.90
0.85
0.80
80 90100 120 140 160 180
Gas pipe: ø31.8
0
Model FDC(S)560KXZE1
1.00
Gas pipe: ø31.8
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
0.95
Gas pipe: ø28.58
0.90
0.85
0.80
0
20
40
60
Gas pipe: ø31.8
Gas pipe: ø28.58
0.90
0.85
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
Gas pipe: ø28.58
0.90
0.85
0.80
0
20
40
60
Capacity compensation
coefficient
Capacity compensation
coefficient
Gas pipe: ø34.92*
0.85
0.80
0
20
40
60
80 90 100
120
140
160
80 90100 120 140 160 180
Model FDC(S)735KXZE1
(FDC(S)335KXZE1 + FDC(S)400KXZE1)
Gas pipe: ø31.8
0.90
Gas pipe: ø34.92*
0.85
1.00
Gas pipe: ø31.8
0.90
60
0
20
40
60
80 90100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Model FDC(S)800KXZE1
(FDC(S)400KXZE1 + FDC(S)400KXZE1)
0.95
40
0.95
0.80
80 90 100 120 140 160 180
Gas pipe: ø38.1
20
Gas pipe: ø38.1
Refrigerant piping one way equivalent length (m)
1.00
80 90100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Model FDC(S)670KXZE1
(FDC(S)335KXZE1 + FDC(S)335KXZE1)
0.95
60
Model FDC(S)615KXZE1
(FDC(S)280KXZE1 + FDC(S)335KXZE1)
0.80
0
80 90100 120 140 160 180
Gas pipe: ø31.8
40
0.95
Refrigerant piping one way equivalent length (m)
1.00
20
Refrigerant piping one way equivalent length (m)
Refrigerant piping one way equivalent length (m)
180
Refrigerant piping one way equivalent length (m)
Note (1) Parts with the * mark show the piping size in case used in Europe.
- 143
31 --
Model FDC(S)850KXZE1
(FDC(S)400KXZE1 + FDC(S)450KXZE1)
Gas pipe: ø38.1
0.95
Gas pipe: ø31.8
0.90
0.85
0.80
Gas pipe: ø34.92*
0
20
40
60
80 90 100 120 140 160 180
Refrigerant piping one way equivalent length (m)
'14 • KX-DB-201
Model FDC900(S)KXZE1
(FDC450(S)KXZE1 + FDC(S)450KXZE1)
Capacity compensation
coefficient
Gas pipe: ø38.1
0.95
0.90
Gas pipe: ø31.8
0.85
0.80
Gas pipe: ø34.92*
0
1.00
Capacity compensation
coefficient
1.00
20
40
60
80 90 100
120
140
160
Gas pipe: ø38.1
0.85
1.00
80 90100 120 140 160 180
*
Gas pipe: ø34.92
0.85
20
40
60
80
0.95
Gas pipe: ø38.1
0.90
*
Gas pipe: ø34.92
0.85
0.80
100 120 140 160 180
0
Refrigerant piping one way equivalent length (m)
Model FDC(S)1120KXZE1
(FDC(S)560KXZE1+FDC(S)560KXZE1)
Gas pipe: ø38.1
0.90
*
Gas pipe: ø34.92
0.85
0.80
0
20
40
60
80
Capacity compensation
coefficient
Model FDC(S)1250KXZE1
(FDC(S)400KXZE1+FDC(S)400KXZE1+FDC(S)450KXZE1)
Gas pipe: ø38.1
*
Gas pipe: ø34.92
0.85
0
20
40
60
80
80
100 120 140 160 180
Gas pipe: ø38.1
0.90
*
Gas pipe: ø34.92
0.85
0
20
40
60
80
100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Refrigerant piping one way equivalent length (m)
0.90
60
0.95
0.80
100 120 140 160 180
0.95
40
Model FDC(S)1200KXZE1
(FDC(S)400KXZE1+FDC(S)400KXZE1+FDC(S)400KXZE1)
1.00
0.95
20
Refrigerant piping one way equivalent length (m)
Capacity compensation
coefficient
Capacity compensation
coefficient
60
Model FDC(S)1060KXZE1
(FDC(S)500KXZE1+FDC(S)560KXZE1)
0.80
0
Capacity compensation
coefficient
40
Model FDC(S)1000KXZE1
(FDC(S)500KXZE1+FDC(S)500KXZE1)
0.90
0.80
20
Refrigerant piping one way equivalent length (m)
Gas pipe: ø38.1
1.00
Gas pipe: ø31.8
0.90
Refrigerant piping one way equivalent length (m)
0.95
1.00
*
Gas pipe: ø34.92
0.95
0.80
0
180
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
Model FDC(S)950KXZE1
(FDC(S)475KXZE1-K+FDC(S)475KXZE1)
100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Note (1) Parts with the * mark show the piping size in case used in Europe.
- 32
- 144
--
1.00
Model FDC(S)1300KXZE1
(FDC(S)400KXZE1+FDC(S)450KXZE1+FDC(S)450KXZE1)
0.95
Gas pipe: ø38.1
0.90
*
Gas pipe: ø34.92
0.85
0.80
0
20
40
60
80
100 120 140 160 180
Refrigerant piping one way equivalent length (m)
'14 • KX-DB-201
Model FDC(S)1350KXZE1
(FDC(S)450KXZE1+FDC(S)450KXZE1+FDC(S)450KXZE1)
1.00
Capacity compensation
coefficient
Capacity compensation
coefficient
1.00
0.95
Gas pipe: ø38.1
0.90
*
Gas pipe: ø34.92
0.85
0.80
0
20
40
60
80
0.90
0.75
1.00
Capacity compensation
coefficient
Gas pipe: ø38.1
*
Gas pipe: ø34.92
0.80
0.75
0.70
0
20
40
60
80
Capacity compensation
coefficient
Capacity compensation
coefficient
Gas pipe: ø38.1
*
Gas pipe: ø34.92
0.75
0.75
*
Gas pipe: ø34.92
0.75
0.70
Model FDC(S)1620KXZE1
(FDC(S)500KXZE1+FDC(S)560KXZE1+FDC(S)560KXZE1)
0.95
0.90
Gas pipe: ø38.1
0.85
*
Gas pipe: ø34.92
0.80
0.75
0
20
40
60
80
100 120 140 160 180
2) Heating
Model FDC(S)1680KXZE1
(FDC(S)560KXZE1+FDC(S)560KXZE1+FDC(S)560KXZE1)
Gas pipe: ø38.1
0
20 40 60 80 100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Refrigerant piping one way equivalent length (m)
1.00
0.95
0.80
100 120 140 160 180
*
Gas pipe: ø34.92
0.80
0.70
0
20 40 60 80 100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Capacity compensation
coefficient
Capacity compensation
coefficient
0.95
0.85
80
Gas pipe: ø38.1
0.85
1.00
1.00
0.90
60
0.90
0.70
100 120 140 160 180
Model FDC(S)1560KXZE1
(FDC(S)500KXZE1+FDC(S)500KXZE1+FDC(S)560KXZE1)
1.00
40
0.95
Refrigerant piping one way equivalent length (m)
0.70
20
Model FDC(S)1500KXZE1
(FDC(S)500KXZE1+FDC(S)500KXZE1+FDC(S)500KXZE1)
0.85
0.80
0
Model FDC(S)1450KXZE1
(FDC(S)475KXZE1+FDC(S)475KXZE1+FDC(S)500KXZE1)
0.90
0.85
*
Gas pipe: ø34.92
0.80
Refrigerant piping one way equivalent length (m)
0.95
0.90
Gas pipe: ø38.1
0.85
Refrigerant piping one way equivalent length (m)
1.00
Capacity compensation
coefficient
0.95
0.70
100 120 140 160 180
Model FDC(S)1425KXZE1
(FDC(S)475KXZE1+FDC(S)475KXZE1+FDC(S)475KXZE1)
0
20 40 60 80 100 120 140 160 180
Refrigerant piping one way equivalent length (m)
Note (1) Parts with the * mark show the piping size in case used in Europe.
- 144
- 33--
0.98
0.96
0.94
0.92
0.90
0
20
40
60
80
100
120
140
160
180
Refrigerant piping one way equivalent length (m)
'14 • KX-DB-201
Note (1) Equivalent piping length can be obtained by calculating as follows.
Equivalent piping length = Real gas piping length + Number of bends in gas piping × Equivalent piping length of bends.
Unit : m/one part
Equivalent length of each joint
Gas piping size
Joint (90˚ elbow)
φ15.88
0.25
φ19.05
0.30
φ22.22
0.35
φ25.4
0.40
φ28.58
0.45
φ31.8
0.55
φ34.92
0.60
φ38.1
0.65
(c) When the outdoor unit is located at alower height than the indoor unit in cooling operation and when the
outdoor unit is located at a higher height than the indoor unit in heating operation, the following values
should be subtracted from the values in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
Adjustment coefficient
Height difference between the indoor unit and
outdoor unit in the vertical height difference
Adjustment coefficient
5m
10 m
15 m
20 m
25 m
30 m
35 m
0.99
0.98
0.97
0.96
0.95
0.94
0.93
40 m
45 m
50 m
55 m
60 m
65 m
70 m
0.92
0.91
0.90
0.89
0.88
0.87
0.86
(d) Correction of heating capacity in relation to the frost on the outdoor unit heat exchanger
Air inlet temperature of
outdoor unit in ˚C WB
Adjustment coefficient
-20
-15
-13
-11
-9
-7
-5
-3
-1
1
3
5 or more
0.96
0.96
0.96
0.95
0.94
0.93
0.91
0.88
0.86
0.87
0.92
1
The correction factors will change drastically according to weather conditions. So necessary adjustment should be
made empirically according to the weather data of the particular area.
(e) The capacity compensation coefficient and power consumption compensation coefficient vary
according to the total capacity of concurrently operating indoor units, as shown below.
(Note) This table shows typical values.
Model FDC(S)280KXZE1
◆ Capability compensation coefficient
Cooling
1.2
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Capability compensation
coefficient
1.0
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
-
-
0.8
0.6
0.4
0.2
1.2
145 -
34 -
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
'14 • KX-DB-201
Model FDC(S)335KXZE1
◆ Capability compensation coefficient
Cooling
1.2
Capability compensation
coefficient
Capability compensation
coefficient
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)400KXZE1
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
146 -
-
35 -
'14 • KX-DB-201
Model FDC(S)450KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)475KXZE1
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
147 -
-
36 -
'14 • KX-DB-201
Model FDC(S)500KXZE1
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)560KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
-
37 -
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
'14 • KX-DB-201
Model FDC(S)615KXZE1
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)670KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
-
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
38 -
'14 • KX-DB-201
Model FDC(S)735KXZE1
◆ Capability compensation coefficient
Cooling
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
1.2
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)800KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
-
39 -
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
'14 • KX-DB-201
Model FDC(S)850KXZE1
◆ Capability compensation coefficient
Cooling
1.2
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Capability compensation
coefficient
1.0
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
1.2
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)900KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
151 -
-
40 -
'14 • KX-DB-201
Model FDC(S)950KXZE1
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)1000KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
0.6
0.4
0.2
0
Power consumption
compensation coefficient
Power consumption
compensation coefficient
0.8
0.6
0.4
0.2
0
0.8
1.2
1.0
0
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
◆ Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
152 -
-
41 -
'14 • KX-DB-201
Model FDC(S)1060KXZE1
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
1.0
0.8
0.6
0.4
0.2
0
0
0.8
0.6
0.4
0.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor units (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)1120KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
153 -
-
42 -
'14 • KX-DB-201
Model FDC(S)1200KXZE1
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
Heating
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)1250KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
153 -
-
43 -
'14 • KX-DB-201
Model FDC(S)1300KXZE1
◆ Capability compensation coefficient
Cooling
1.2
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
Power consumption
compensation coefficient
0
0
1.0
0.8
0.6
0.4
0.2
0
0
0.8
0.6
0.4
0.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
20
40
60
80
100
Heating
1.0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
1.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)1350KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
153 -
-
44 -
'14 • KX-DB-201
Model FDC(S)1425KXZE1
◆ Capability compensation coefficient
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
0
Power consumption
compensation coefficient
1.2
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
Heating
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
1.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)1450KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
153 -
-
45 -
'14 • KX-DB-201
Model FDC(S)1500KXZE1
◆ Capability compensation coefficient
Cooling
1.2
Capability compensation
coefficient
1.0
0.8
0.6
0.4
0.2
Power consumption
compensation coefficient
0
0
◆ Power consumption compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
Heating
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Capability compensation
coefficient
1.2
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)1560KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
153 -
-
46 -
'14 • KX-DB-201
Model FDC(S)1620KXZE1
◆ Capability compensation coefficient
Cooling
1.2
Capability compensation
coefficient
Capability compensation
coefficient
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
1.2
1.0
0.8
0.6
0.4
0.2
0
0
20
40
60
80
100
1.2
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
Total capacity of concurrently operating indoor unit (%)
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Model FDC(S)1680KXZE1
1.2
Capability compensation
coefficient
Capability compensation
coefficient
◆ Capability compensation coefficient
Cooling
1.2
1.0
0.8
0.6
0.4
0.2
0
0
1.0
0.8
0.6
0.4
0.2
0
20
40
60
80
100
0.8
0.6
0.4
0.2
1.2
Power consumption
compensation coefficient
Power consumption
compensation coefficient
◆ Power consumption compensation coefficient
Cooling
1.2
0
1.0
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Total capacity of concurrently operating indoor unit (%)
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
Heating
1.0
0.8
0.6
0.4
0.2
0
120
Heating
0
20
40
60
80
100
120
Total capacity of concurrently operating indoor unit (%)
-
154 -
-
47 -
'14 • KX-DB-201
6.
ON REFRIGERANT
LEAKAGE
WARNINGS
ON REFRIGERANT
LEAKAGE
6.WARNINGS
Check of concentration limit
Important
The room in which the air conditioner is to be installed requires
a design that in the event of refrigerant gas leaking out, its
concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is
safe,without the toxicity or combustibility of ammonia, and is
not restricted by laws to be imposed which protect the ozone
layer. However, since it contains more than air, it poses the risk
of suffocation if its concentration should rise excessively.
Suffocation from leakage of R410A is almost nonexistent. With
the recent increase in the number of high concentration buildings,
however, the installation of multi air conditioner systems is on
the increase because of the need for effective use of floor space,
individual control, energy conservation by curtailing heat and
carrying power etc.
Most importantly, the multi air conditioner system is able to
replenish a large amount of refrigerant compared with conventional
individual air conditioners. If a single unit of the multi conditioner
system is to be installed in a small room, select a suitable model
and installation procedure so that if the refrigerant accidentally
leaks out, its concentration dose not reach the limit (and in the
event of an emergency, measures can be made before injury
can occur).
In a room where the concentration may exceed the limit, create
an opening with adjacent rooms, or install mechanical ventilation
combined with a gas leak detection device.
The concentration is as given below.
Note(2) The standards for minimum room volume are as
follows.
① No partition (shaded portion)
② When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening
without a door,or an opening 0.15% or larger than
the respective floor spaces at the top or bottom of
the door).
Outdoor unit
Refrigerant piping
Indoor unit
③ If an indoor unit is installed in each partitioned room and
the refrigerant tubing is interconnected, the smallest
of course becomes the object.
But when a mechanical ventilation is installed interlocked
with a gas leakage detector in the smallest room where
the density limit is exceeded, the volume of the next
smallest room becomes the object.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m3)
Refrigerant piping
≤ Concentration limit (kg/m3)
Outdoor unit
The concentration limit of R410A which is used in multi air
conditioners is 0.42kg/m3. (ISO5149)
Note(1) If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
Small
room
Room C
Room D
Room E
Min. indoor floor area (m2)
40
Room B
Large room
Note(3) The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows: (When
the ceiling is 2.7m high)
e.g.,
Charged amount (15kg)
Indoor unit
Room A
Medium
room
Mechanical ventilation device - Gas leak detector
Outdoor unit
e.g., Charged
amount (10kg)
Indoor unit
Very
small
room
Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms
A, B and C is 10kg.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15kg.
35
30
Range below the
density limit of
0.42kg/m3
(countermeasures
not needed)
25
20
15
Range above
the density limit
of 0.42kg/m3
(countermeasures
needed)
10
5
0
10
20
30
Total amount of refrigerant (kg)
-
48 -
VRF INVERTER MULTI-SYSTEM AIR-CONDITIONERS
Air-Conditioning & Refrigeration Division
16-5, Konan 2-chome, Minato-ku, Tokyo, 108-8215 Japan
http://www.mhi.co.jp
Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice.
c Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.
Download