Manual No. '14 • KX-DB-201 DATA BOOK VRF INVERTER MULTI-SYSTEM AIR-CONDITIONERS (OUTDOOR UNIT) KXZ series (Heat pump type) Standard series Single use (Used also for combination) FDC280KXZE1, 335KXZE1, 400KXZE1, 450KXZE1, 475KXZE1, 500KXZE1, 560KXZE1 Combination use FDC615KXZE1, 670KXZE1, 735KXZE1, 800KXZE1, 850KXZE1, 900KXZE1, 950KXZE1, 1000KXZE1, 1060KXZE1, 1120KXZE1, 1200KXZE1, 1250KXZE1, 1300KXZE1, 1350KXZE1,1425KXZE1, 1450KXZE1, 1500KXZE1, 1560KXZE1, 1620KXZE1, 1680KXZE1 Corrosion protection treatment series (Non-CE Marking models) Single use (Used also for combination) FDCS280KXZE1, 335KXZE1, 400KXZE1, 450KXZE1, 475KXZE1, 500KXZE1, 560KXZE1 Combination use FDCS615KXZE1, 670KXZE1, 735KXZE1, 800KXZE1, 850KXZE1, 900KXZE1, 950KXZE1, 1000KXZE1, 1060KXZE1, 1120KXZE1, 1200KXZE1, 1250KXZE1, 1300KXZE1, 1350KXZE1,1425KXZE1, 1450KXZE1, 1500KXZE1, 1560KXZE1, 1620KXZE1, 1680KXZE1 • Note: (1) Regarding the Indoor unit series, refer to the No.'14 • KX-DB-206 (2) Regarding the Duct Connected-High static Pressure-type Outdoor Air Processing Unit Series (FDU500∼1800FKXE6), refer to the DATA BOOK No.'08 • KX-DB-122 '14• •KX-DB-201 KX-DB-201 '14 PREFACE PREFACE Combination table for KX4, KX6 and KXZE1 series Connectable remote control 3-wire type Category Outdoor unit Indoor unit Same or Same series Same series Mixed series Mixed series Mixed series Mixed series Mixed series Same series RC-E1 3-wire type RC-E1R 2-wire type RC-E3 RC-E4 RC-E5 RC-EX1A KXE4 KXE4(A) KXE4A KXE4A KXE4A KXE4R KXE4BR KXE5R KXE4R KXE4BR KXE5R KXE4A KXE4R KXE4BR KXE5R KXE4R KXE4BR KXE5R KXE6 KXE6A KXE6B KXE6D KXE6F KXE6 KXE6A KXE6B KXE6D KXE6F KXE6 KXE6A KXE6B KXE6D KXE6F KXE6 KXE6A KXE6B KXE6D KXE6F FDCA-HKXE4 5HP YES[D] YES[D] NO NO NO NO NO NO FDCA-HKXE4 8-48HP NO YES[D] NO NO NO NO NO NO FDCA-HKXE4A FDCA-HKXE4R 5HP 5,6HP NO YES[D] YES[D] 1 NO NO YES[D] NO NO 8-48HP 8-48HP 8-48HP 8-48HP NO YES[D] YES[D] YES[D] YES[D] YES[D] YES[D] FDC-KXE6 4,5,6HP NO NO NO NO NO NO NO YES[B] 6 FDC-KXE6 8-48HP NO NO NO NO NO YES[C] YES[C] YES[B] FDC-KXZE1 10-60HP NO NO NO NO NO NO NO YES[A] FDCA-HKXE4A Heat pump FDCA-HKXE4R (2-pipe) FDCA-HKXE4BR systems FDCA-HKXE4D 1 YES[D] 1 Except FDKA71KXE5R Note (1) YES: Connectable (See following table in detail), NO: Not connectable Connected indoor unit Outdoor unit Dip switch setting of outdoor unit Same series Mixed series KXZE1/KXE6 Superlink protocol Limitation YES[A] 2 KXZE1 KXE6 Ⅱ(New) New (for New (for KXZE1/KXE6) KXZE1/KXE6) YES[B] 2 KXE6 KXE6 Ⅱ(New) New (for New (for KXZE1/KXE6) KXZE1/KXE6) YES[C] KXE6 KXE4 series YES[D] KXE4 series KXE4 series KXE4 series KXE6 & KXE4 Ⅰ(Previous) series Previous (for KXE4) Previous (for KXE4) Previous (for KXE4) Previous (for KXE4) 2 If outdoor unit system (YES [A] or YES [B]) is connected to other outdoor unit systems (YES [C] and/or YES [D]) in one superlink network, the dip switch of outdoor unit KXZE1 (YES [A]) or KXE6 of (YES [B]) should be set from (New) to (Previous). In this case the superlink protocol and limitation of outdoor unit system (YES [A] or YES [B]) are switched to Previous (for KX4). (2) Combination with new Central control, PC windows central control and BMS interface unit YES[A] & YES[B] YES[C] & YES[D] Connectable I/U Superlink protocol Connectable network Connectable I/U Superlink 5 protocol Connectable network Central control, PC windows central control and BMS interface unit SC-SL1N-E SC-SL2NA-E SC-SL4-AE/BE SC-WGWNB-A/B SC-LGWNA-A SC-BGWNA-A/B 128 128 96 128 16 64 (128x1) (64x2) 3 (48x2) (64x2) 3 New New New New 2 New 2 New 1 1 1 16 48 144 (48x3) 96 4 (48x2) Previous Previous Previous Previous Previous Previous 1 1 3 2 2 2 96 4 (48x2) 2 96 4 (48x2) 3 Maximum number of AC Cell is limited up to 96. In case the number of connected indoor units are more than 96, some AC Cells should hold 2 or more indoor units. 4 In case of other Central control like SC-SLxN-E is connected in the same network, the connectable indoor unit is limited up to 64(32x2). 5 In case of previous superlink protocol, the superlink mode of new central control should be set "Previous". 6 In case of (YES[A] or YES[B]), previous central control is available to use. But the limitation of connectable indoor unit and so on is complied with the rule of previous superlink. gs+8$" '14 • KX-DB-201 CONTENTS 1. GENERAL INFORMATION ............................................................................... 1 1.1 Specific features............................................................................................ 1 1.2 How to read the model name ........................................................................ 1 1.3 Table of models ............................................................................................. 2 1.4 Outdoor units combination table ................................................................... 3 2. OUTDOOR UNIT ................................................................................................ 4 2.1 Specifications ................................................................................................ 4 2.2 Exterior dimensions....................................................................................... 7 2.3 Electrical wiring ............................................................................................. 9 2.4 Noise level................................................................................................... 12 2.5 Corrosion protection treatment series ......................................................... 13 3. RANGE OF USAGE & LIMITATIONS .............................................................. 14 4. PIPING SYSTEM ............................................................................................. 22 5. SELECTION CHART........................................................................................ 25 6. WARNINGS ON REFRIGERANT LEAKAGE ................................................ 48 '14 • KX-DB-201 1. GENERAL INFORMATION 1.1 Specific features Connectable indoor capacity Capacity from 50% to 130% is possible. Item Number of connectable units Model 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 FDC(S)280KXZE1 FDC(S)335KXZE1 FDC(S)400KXZE1 FDC(S)450KXZE1 FDC(S)475KXZE1 FDC(S)500KXZE1 FDC(S)560KXZE1 FDC(S)615KXZE1 FDC(S)670KXZE1 FDC(S)735KXZE1 FDC(S)800KXZE1 FDC(S)850KXZE1 FDC(S)900KXZE1 FDC(S)950KXZE1 FDC(S)1000KXZE1 FDC(S)1060KXZE1 FDC(S)1120KXZE1 FDC(S)1200KXZE1 FDC(S)1250KXZE1 FDC(S)1300KXZE1 FDC(S)1350KXZE1 FDC(S)1425KXZE1 FDC(S)1450KXZE1 FDC(S)1500KXZE1 FDC(S)1560KXZE1 FDC(S)1620KXZE1 FDC(S)1680KXZE1 to to to to to to to to to to to to to to to to to to to to to to to to to to to 24 29 34 39 41 43 48 53 58 63 69 73 78 80 80 80 80 80 80 80 80 80 80 80 80 80 80 Connectable capacity 140 168 200 225 238 250 280 308 335 368 400 425 450 475 500 530 560 600 625 650 675 713 725 750 780 810 840 - - - - - - - - - - - - - - - - - - - - - - - - - - - 364 435 520 585 617 650 728 799 871 955 1040 1105 1170 1235 1300 1378 1456 1560 1625 1690 1755 1852 1885 1950 2028 2106 2184 Note For outdoor unit, EN61000-3-2 and EN61000-3-12 are not applicable as consent by the utility company or notification to the utility company is given before usage. 1.2 How to read the model name (1) Outdoor unit Example: FDC S 735 KXZ E 1 Series No. Application power source...See the specifications Multi KXZ series Nominal capacity (nominal cooling capacity : 73.5kW) Corrosion protection treatment models (Nothing : Standard models) Model name (Outdoor unit) - - '14 • KX-DB-201 (2) Indoor unit Example: FDT 28 KX E 6F Series No. Application power source...See the specifications Multi KX series Nominal capacity (nominal cooling capacity : 2.8 kW) Model name Indoor unit :FDT, FDTC, FDTW, FDTS, FDTQ, FDU, FDUM, FDUT, FDK, FDE, FDFL, FDFU, FDFW, FDUH, FDU-F 1.3 Table of models Capacity Model Ceiling cassette-4 way type (FDT) Ceiling cassette-4 way compact type (FDTC) Ceiling cassette-2 way type (FDTW) Ceiling cassette-1 way type (FDTS) Ceiling cassette-1 way compact type (FDTQ) Duct connected-High static pressure type (FDU) Duct connected-Low/Middle static pressure type (FDUM) Duct connected (thin)-Low static pressure type (FDUT) Wall mounted type (FDK) Ceiling suspended type (FDE) Floor standing (with casing) type (FDFL) Floor standing (without casing) type (FDFU) Floor standing-2 way type (FDFW) Duct connected-compact and Flexible type (FDUH) Outdoor air processing unit (FDU-F) Outdoor units to be combined (FDC) 15 ○ 22 ○ 28 36 45 56 71 90 112 140 160 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ 224 280 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ FDC280KXZE1-FDC1680KXZE1 Note (1) Reference No. of data book : ’14·KX-DB-206 - - ○ '14 • KX-DB-201 1.4 Outdoor units combination table Combination Outdoor unit models Item Indoor unit Number of connectable units 2 to 53 units - Connectable capacity 308 _ 799 335 _ 871 - 368 2 to 63 units - - 400 - - - 425 2 - - - 450 - - 2 - - 475 - - - - 2 - 500 - - - - - 1 1 530 FDC(S)1120KXZE1 - - - - - - 2 560 FDC(S)1200KXZE1 - - 3 - - - - 600 FDC(S)1250KXZE1 - - 2 1 - - - 625 FDC(S)1300KXZE1 - - 1 2 - - - 650 FDC(S)1350KXZE1 - - - 3 - - - 675 FDC(S)1425KXZE1 - - - - 3 - - 713 FDC(S)1450KXZE1 - - - - 2 1 725 FDC(S)1500KXZE1 - - - - - 3 - FDC(S)1560KXZE1 - - - - - 2 1 780 FDC(S)1620KXZE1 - - - - - 1 2 810 FDC(S)1680KXZE1 - - - - - - 3 840 FDC(S)615KXZE1 FDC280 KXZE1 1 FDC335 KXZE1 1 FDC400 KXZE1 - FDC450 KXZE1 - FDC475 KXZE1 - FDC500 KXZE1 - FDC560 KXZE1 - FDC(S)670KXZE1 - 2 - - - - FDC(S)735KXZE1 - 1 1 - - - FDC(S)800KXZE1 - - 2 - - FDC(S)850KXZE1 - - 1 1 FDC(S)900KXZE1 - - - FDC(S)950KXZE1 - - FDC(S)1000KXZE1 - FDC(S)1060KXZE1 Models 750 _ 955 _ 1040 _ 1105 _ 1170 _ 1235 _ 1300 _ 1378 _ 1456 _ 1560 _ 1625 _ 1690 _ 1755 _ 1852 _ 1885 _ 1950 _ 2028 _ 2106 _ 2184 2 to 58 units 2 to 69 units 2 to 73 units 2 to 78 units 2 to 80 units 2 to 80 units 2 to 80 units 2 to 80 units 3 to 80 units 3 to 80 units 3 to 80 units 3 to 80 units 3 to 80 units 3 to 80 units 3 to 80 units 3 to 80 units 3 to 80 units 3 to 80 units (a) Outdoor unit side branch pipe set (Option) Outdoor unit Branch pipe set For two units (for FDC615KXZE1-1120KXZE1) DOS-2A-3 For three units (for FDC1200KXZE1-1680KXZE1) DOS-3A-3 Note (1) Be sure to use this when combining units. (b) Branch pipe set (Option) Total capacity downstream Branching pipe set Less than 180 DIS-22-1G 180 or more but less than 371 DIS-180-1G 371 or more but less than 540 DIS-371-1G 540 or more DIS-540-3 (c) Header pipe set (Option) Total capacity downstream Header set model type Number of branches Less than 180 HEAD4-22-1G 4 branches at the most 180 or more but less than 371 HEAD6-180-1G 6 branches at the most 371 or more but less than 540 HEAD8-371-2 8 branches at the most 540 or more HEAD8-540-3 8 branches at the most - - - - Cooling Heating Cooling Heating Cooling Heating MPa mm (in) CMM Pa PCB003Z817 PCB003Z819 Gas line : φ22.22 (7/8") Liquid line : φ9.52 (3/8") 220 / 200 20˚C Heating*2 - 19˚C 7.32×1 Propeller fan×2 2.9 (M-MA32R) Microcomputer controlled De-Icer Electronic expansion valve R410A M fin & inner grooved tubing 40x1 9.32×1 Direct line starting 11.5 4.64×2 7˚C 35˚C DB 6˚C 24˚C WB Outdoor air temperature PCB003Z817 PCB003Z819 ISO-T1 Standards Adapted to RoHS directive Gas line : Brazing / Liquid line : Flare High 4.15 Low 2.21 Hole for drain ( φ20×10pcs, φ45×3pcs) Necessary (both Liquid & Gas lines) PCB003Z818 PCB003Z818 PCB003Z818 PCB003Z820 PCB003Z820 PCB003Z821 (2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1"UNITARY AIR-CONDITIONERS" (3) Refrigerant piping size applicable to European installations are shown in parentheses. 27˚C Cooling*1 WB Indoor air temperature DB ltem Operation 5.94×1 2048×1350×720 4.2 (M-MA32R) 33×2 4.91×2 GTC5150NC47LF×2 370 13.97 13.49 22.6 / 20.7 21.8 / 20.0 94 / 94 94 / 94 61 / 62 FDC500KXZE1 FDCS500KXZE1 50.0 56.0 PCB003Z818 PCB003Z821 386×2 Direct start 280 / 200 280 / 260 280 / 260 280 / 260 280 / 260 Max.50 Rubber mount (for compressor) Compressor overheat protection / overcurrent protection / power transistor overheating protection / abnormal high pressure protection Liquid line : φ12.7 (1/2") Gas line : φ25.4 (1") Gas line : φ25.4 (1") Gas line : φ28.58 (11/8") ( φ22.22 (7/8") ) ( φ28.58 (11/8") ) 11.0 2.25 (M-MA32R) kg l W 33×1 W 4.76×1 GUC5185ND47V×1 GTC5150NC47LF×1 kW 317 272 10.96 10.69 17.5 / 16.2 17.5 / 16.2 95 / 94 93 / 92 60 / 62 FDC450KXZE1 FDC475KXZE1 FDCS450KXZE1 FDCS475KXZE1 45.0 47.5 50.0 53.0 3 Phase 380-415V 50Hz / 380V 60Hz 13.98 13.98 12.50 13.00 22.4 / 20.5 22.6 / 20.7 20.4 / 18.7 21.0 / 19.2 95 / 95 94 / 94 93 / 93 94 / 94 61 / 62 61 / 61 1690×1350×720 8.96 9.04 14.6 / 13.4 14.8 / 13.5 93 / 93 93 / 93 61 / 58 FDC400KXZE1 FDCS400KXZE1 40.0 45.0 kg 7.24 7.28 11.9 / 10.9 12.0 / 11.0 92 / 92 92 / 92 55 / 57 FDC335KXZE1 FDCS335KXZE1 33.5 37.5 mm dB (A) % A kW kW FDC280KXZE1 FDCS280KXZE1 28.0 31.5 Notes (1) The data are measured at the following conditions. Connecting method MAX. Pressure Drain Insulation for piping Accessories Exterior dimensions Electrical wiring Installation data Refrigerant piping size Safety equipment Sound Pressure Level Exterior dimensions Height × Width × Depth Net weight Refrigerant equipment compressor type & Q'ty Motor Starting method Crankcase heater Refrigerant equipment Heat exchanger Refrigerant control Refrigerant Quantity Refrigerant oil Defrost control Air handling equipment fan type & Q'ty Motor Starting method Air flow (Standard) Static pressure Shock & vibration absorber Power factor Running current Power consumption Nominal cooling capacity*1 Nominal heating capacity*2 Power source Models PCB003Z818 PCB003Z821 310 / 290 5.36×2 16.62 15.95 26.9 / 24.6 25.8 / 23.6 94 / 94 94 / 94 64 / 66 FDC560KXZE1 FDCS560KXZE1 56.0 63.0 '14 • KX-DB-201 2. OUTDOOR UNIT 2.1 Specifications • Single use (Used also for combination) PCB003Z816 - - Models Liquid line Gas line Oil equalization Cooling Heating Cooling Heating Cooling Heating φmm kg % A kW kW φmm kg % A kW kW 27˚C 20˚C Cooling*1 Heating*2 - 19˚C WB 95.0 106.0 27.96 26.00 45.2 / 41.4 42.0 / 38.4 94 / 94 94 / 94 740 φ15.88 7˚C 35˚C DB 6˚C 24˚C WB ISO-T1 Standards FDC950KXZE1 FDCS950KXZE1 FDC475KXZE1 FDCS475KXZE1 FDC475KXZE1 FDCS475KXZE1 Outdoor air temperature φ31.75 ( φ34.92) φ12.7 φ28.58 67.0 75.0 17.92 18.08 29.2 / 26.8 29.6 / 27.0 93 / 93 93 / 93 544 FDC670KXZE1 FDCS670KXZE1 FDC335KXZE1 FDCS335KXZE1 FDC335KXZE1 FDCS335KXZE1 (2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1"UNITARY AIR-CONDITIONERS" (3) Refrigerant piping size applicable to European installations are shown in parentheses. DB Indoor air temperature Operation ltem 90.0 100.0 27.96 25.00 44.8 / 41.0 40.8 / 37.4 95 / 95 93 / 93 634 FDC900KXZE1 FDCS900KXZE1 FDC450KXZE1 FDCS450KXZE1 FDC450KXZE1 FDCS450KXZE1 61.5 69.0 16.20 16.32 26.5 / 24.3 26.8 / 24.5 93 / 93 93 / 93 544 FDC615KXZE1 FDCS615KXZE1 FDC280KXZE1 FDCS280KXZE1 FDC335KXZE1 FDCS335KXZE1 Notes (1) The data are measured at the following conditions. Refrigerant piping size Net weight Power factor Running current Power consumption Cooling Heating Cooling Heating Cooling Heating Liquid line Gas line Oil equalization Power source Nominal cooling capacity*1 Nominal heating capacity*2 Combination unit Refrigerant piping size Net weight Power factor Running current Power consumption Power source Nominal cooling capacity*1 Nominal heating capacity*2 Combination unit Models Adapted to RoHS directive φ9.52 FDC1000KXZE1 FDCS1000KXZE1 FDC500KXZE1 FDCS500KXZE1 FDC500KXZE1 FDCS500KXZE1 3 Phase 380-415V 50Hz / 380V 60Hz 100.0 112.0 27.94 26.98 45.2 / 41.4 43.6 / 40.0 94 / 94 94 / 94 740 φ9.52 FDC735KXZE1 FDCS735KXZE1 FDC335KXZE1 FDCS335KXZE1 FDC400KXZE1 FDCS400KXZE1 3 Phase 380-415V 50Hz / 380V 60Hz 73.5 82.5 19.92 19.73 32.1 / 29.6 32.3 / 29.7 94 / 94 93 / 92 589 φ38.1 ( φ34.92) 106.0 119.0 30.59 29.44 49.5 / 45.3 47.6 / 43.6 94 / 94 94 / 94 740 FDC1060KXZE1 FDCS1060KXZE1 FDC500KXZE1 FDCS500KXZE1 FDC560KXZE1 FDCS560KXZE1 80.0 90.0 21.92 21.38 35.0 / 32.4 35.0 / 32.4 95 / 94 93 / 92 634 φ15.88 φ31.75 ( φ34.92) FDC800KXZE1 FDCS800KXZE1 FDC400KXZE1 FDCS400KXZE1 FDC400KXZE1 FDCS400KXZE1 φ19.05 112.0 126.0 33.24 31.90 53.8 / 49.2 51.6 / 47.2 94 / 94 94 / 94 740 FDC1120KXZE1 FDCS1120KXZE1 FDC560KXZE1 FDCS560KXZE1 FDC560KXZE1 FDCS560KXZE1 85.0 95.0 24.94 23.19 39.9 / 36.7 37.9 / 34.9 95 / 95 93 / 92 634 FDC850KXZE1 FDCS850KXZE1 FDC400KXZE1 FDCS400KXZE1 FDC450KXZE1 FDCS450KXZE1 '14 • KX-DB-201 • Combination use PCB003Z816 - - Models Liquid line Gas line Oil equalization Cooling Heating Cooling Heating Cooling Heating φmm kg % A kW kW φmm kg % A kW kW 19˚C 27˚C 20˚C Cooling*1 Heating*2 7˚C 35˚C DB 6˚C 24˚C WB Outdoor air temperature 150.0 168.0 41.91 40.47 67.8 / 62.1 65.4 / 60.0 94 / 94 94 / 94 1110 ISO-T1 Standards FDC1500KXZE1 FDCS1500KXZE1 FDC500KXZE1 FDCS500KXZE1 FDC500KXZE1 FDCS500KXZE1 FDC500KXZE1 FDCS500KXZE1 125.0 140.0 35.90 33.88 57.4 / 52.9 55.4 / 51.1 95 / 94 93 / 92 951 FDC1250KXZE1 FDCS1250KXZE1 FDC400KXZE1 FDCS400KXZE1 FDC400KXZE1 FDCS400KXZE1 FDC450KXZE1 FDCS450KXZE1 (2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1"UNITARY AIR-CONDITIONERS" (3) Refrigerant piping size applicable to European installations are shown in parentheses. - WB Indoor air temperature DB ltem Operation 145.0 162.0 41.93 39.49 67.8 / 62.1 63.8 / 58.4 94 / 94 94 / 94 1110 FDC1450KXZE1 FDCS1450KXZE1 FDC475KXZE1 FDCS475KXZE1 FDC475KXZE1 FDCS475KXZE1 FDC500KXZE1 FDCS500KXZE1 120.0 135.0 32.88 32.07 52.5 / 48.6 52.5 / 48.6 95 / 94 93 / 92 951 FDC1200KXZE1 FDCS1200KXZE1 FDC400KXZE1 FDCS400KXZE1 FDC400KXZE1 FDCS400KXZE1 FDC400KXZE1 FDCS400KXZE1 Notes (1) The data are measured at the following conditions. Refrigerant piping size Net weight Power factor Running current Power consumption Cooling Heating Cooling Heating Cooling Heating Liquid line Gas line Oil equalization Power source Nominal cooling capacity*1 Nominal heating capacity*2 Combination unit Refrigerant piping size Net weight Power factor Running current Power consumption Power source Nominal cooling capacity*1 Nominal heating capacity*2 Combination unit Models Adapted to RoHS directive FDC1560KXZE1 FDCS1560KXZE1 FDC500KXZE1 FDCS500KXZE1 FDC500KXZE1 FDCS500KXZE1 FDC560KXZE1 FDCS560KXZE1 3 Phase 380-415V 50Hz / 380V 60Hz 156.0 175.0 44.56 42.93 72.1 / 66.0 69.4 / 63.6 94 / 94 94 / 94 1110 φ19.05 φ38.1 ( φ34.92) φ9.52 FDC1300KXZE1 FDCS1300KXZE1 FDC400KXZE1 FDCS400KXZE1 FDC450KXZE1 FDCS450KXZE1 FDC450KXZE1 FDCS450KXZE1 3 Phase 380-415V 50Hz / 380V 60Hz 130.0 145.0 38.92 35.69 62.3 / 57.2 58.3 / 53.6 95 / 95 93 / 93 951 φ19.05 φ38.1 ( φ34.92) φ9.52 162.0 182.0 47.21 45.39 76.4 / 69.9 73.4 / 67.2 94 / 94 94 / 94 1110 FDC1620KXZE1 FDCS1620KXZE1 FDC500KXZE1 FDCS500KXZE1 FDC560KXZE1 FDCS560KXZE1 FDC560KXZE1 FDCS560KXZE1 135.0 150.0 41.94 37.50 67.2 / 61.5 61.2 / 56.1 95 / 95 93 / 93 951 FDC1350KXZE1 FDCS1350KXZE1 FDC450KXZE1 FDCS450KXZE1 FDC450KXZE1 FDCS450KXZE1 FDC450KXZE1 FDCS450KXZE1 168.0 189.0 49.86 47.85 80.7 / 73.8 77.4 / 70.8 94 / 94 94 / 94 1110 FDC1680KXZE1 FDCS1680KXZE1 FDC560KXZE1 FDCS560KXZE1 FDC560KXZE1 FDCS560KXZE1 FDC560KXZE1 FDCS560KXZE1 142.5 159.0 41.94 39.00 67.8 / 62.1 63.0 / 57.6 94 / 94 94 / 94 1110 FDC1425KXZE1 FDCS1425KXZE1 FDC475KXZE1 FDCS475KXZE1 FDC475KXZE1 FDCS475KXZE1 FDC475KXZE1 FDCS475KXZE1 '14 • KX-DB-201 • Combination use PCB003Z816 '14 • KX-DB-201 2.2 Exterior dimensions Models FDC280KXZE1, 335KXZE1 FDCS280KXZE1, 335KXZE1 PCB003Z817 - - '14 • KX-DB-201 Models FDC400KXZE1, 450KXZE1, 475KXZE1, 500KXZE1, 560KXZE1 FDCS400KXZE1, 450KXZE1, 475KXZE1, 500KXZE1, 560KXZE1 PCB003Z818 - - - Mark CH1 CM1 CNA-Z CT1 C1-1,2 DM1 EEVH1,2 EEVSC F FMC1 FMo1,2 IPM J11,12 J13 J14 J15 J16 LED1 LED1(INV) LED2 LED3 L1-1,2 L3 RD 52X1-4 52X1-3 DM1 CNR WH CNI2 WH Inverter PWB2-1 52X1-1 PWB3-1 - CT1 BK WH RD GN CNI3 BK LED1 (INV) L3 Inspection(Red) Normal(Yellow)-Flashing Normal(Green) Service(green for service) D.C.reactor D.C.reactor Mark PSH PSL PWB1∼3 R1-1∼1-4 SV1 SV6 SV11 SW1 SW2 SW3-1 SW3-2 ON OFF SW3-3 SW3-4 ON OFF SW3-5 ON OFF SW3-6 SW3-7 ON OFF SW3-8 CNI1 WH A2 B2 A1 B1 BK RD CNX1 YE CNW RD CNFAN1 WH CNR1 WH CNFAN2 RD CNM1 GY BK CH1 BR FMo1 M FMo2 Parts name High pressure sensor Low pressure sensor Printed wiring board(PCB) Rush current suppression resistor Solenoid valve(CM1:bypass) Solenoid valve(oil separator CM1) Solenoid valve(gas bypass) Address setting SW outdoor unit No.(2 digits) Address setting SW outdoor unit No.(1 digit) inspection LED reset Auto backup operation Regular operation Spare Refrigerant quantity check Regular operation Check operation Regular operation Spare Forced cooling/heating Regular operation Spare BETWEEN INDOOR UNIT AND OUTDOOR UNIT,BETWEEN OUTDOOR UNITS ON THE SAME REFRIGERANT LINE. BETWEEN OUTDOOR UNITS ON THE DIFFERENT REFRIGERANT LINES. MS 3∼ V Parts name Crankcase heater Compressor motor Connector Current sensor Electrolytic capacitor Diode module Expansion valve for heating Expansion valve for SC Fuse Fan for IPM Blower motor Intelligent power module Set up model(volt) External input select level/pulse Defrost recover temp Defrost start temp Spare E CNA WH W P IPM1 U V W N R1-4 + C1-2 R1-3 + C1-1 + AC1 AC2 AC3 U CM1 BL CNSL1,2 BK NETWORK CONNECTOR WH WH BL BK WH Meaning of marks TB2 A1 B1 A2 B2 Power source 3 Phase 380-415V 50Hz /380V 60Hz R1-1 R1-2 RD RD RD 52X1-3 Circuit breaker Earth leakage breaker (Impulse withstanding type) Signal line RD BL BL YE L1-2 WH RD WH GY 52X1-2 RD WH BL 52X1-4 RD WH BL WH YE L1-1 WH RD BL GY RD WH BL BK Noise filter M SW2 CNN1 RD CNA3 CNA1 WH WH Mark SW4-1∼4 SW4-5 SW4-6 SW4-7 SW4-8 SW5-1 ON OFF SW5-2 ON OFF SW5-3 ON OFF SW5-4 SW5-5 ON OFF SW5-6 8 SW6-1 3 SW6-4 ON OFF SW7 SW8 SW9 CNEEV1 RD 1 2 3 4 5 6 7 8 SW3 SW1 CONTROL PWB1 ON OFF RD F(4A) L1i L2i L3i Ni CNEEV2 BL EEVSC M J11 J13 CNEEV3 WH J12 EEVH2 M Parts name Model setting Spare Spare Address setting switch(master・slave) Address setting switch(master・slave) Trial operation Regular operation Trial operation mode/cooling Trial operation mode/heating Pump down operation Regular operation Spare Super Link communication Super Link communication Spare Spare High Head Standard Data clear/insert 7-segment indicate(unit's place) 7-segment indicate(ten's place) EEVH1 M SW7 SW8 SW9 LED1 J14 J15 CNV t° t° Mark TB1,2 Tho-A Tho-C1 Tho-D1 Tho-H Tho-P1 Tho-R1 Tho-R2 Tho-R3 Tho-R4 Tho-S Tho-SC 20S 52X1-1∼1-4 63H1-1 7SEG1 7SEG2 FMC1 t° t° t° t° t° Color Black Blue Brown Green Gray Orange Red White Yellow Pink Yellow YE/GN /Green Mark BK BL BR GN GY OR RD WH YE PK t° Demand input External input Silent mode input Color mark t° CNU1 BL CNP1 YE CNF2 GN WH CNS2 RD CNF1 WH WH CNS1 GN CNB4 RD WH CNG2 WH Cooling/Heating forced input WH Reserve output Operation output Trouble output RD WH BK PSH RD WH BK PSL CNG1 BL CNY WH CNH BL CNZ1 RD CNL1 BL CNL2 WH CNB3 BK CNN8 PK CNB2 RD CNQ1 WH High pressure switch(for protection) 7-segment L.E.D.(function indication) 7-segment L.E.D.(data indication) 4way valve Solenoid for CM 63H1-1 Parts name Terminal block External air thermistor Under-dome thermistor Discharge pipe thermistor Sub-cooling coil thermistor 2 Power transistor thermistor Heat exchanger thermistor(exhaust) Heat exchanger thermistor(exhaust) Heat exchanger thermistor(inlet) Heat exchanger thermistor(inlet) Suction pipe thermistor Sub-cooling coil thermistor 1 Compressor Terminal block V(White) t° CNTH WH PC (RS232C) U(Red) t° LED3 1 2 3 4 5 6 7 8 SW6 LED2 W(Blue) J16 1 2 3 4 5 6 7 8 SW5 CNN6 PK CNN9 BK 7SEG2 SV1 SV11 1 2 3 4 5 6 7 8 SW4 7SEG1 CNN2 GN RD L1o L2o L3o No BL OR YE WH YE/GN RD F(4A) BL RD BL BL OR YE WH BL BL OR YE WH BK WH OR YE BL GN PK WH OR YE BL GN PK BK RD BK RD RD BL SV6 BK Tho-R1 BK Tho-R2 20S BK Tho-D1 BK BK Tho-R3 BK Tho-R4 BK Tho-SC 52X1-2 BK Tho-S BK BK 52X1-1 YE Tho-A BK BK Tho-H BK Tho-P1 - Tho-C1 TB1 L1 L2 L3 N '14 • KX-DB-201 2.3 Electrical wiring Models FDC280KXZE1, 335KXZE1 FDCS280KXZE1 335KXZE1 PCB003Z819 Power source 3 Phase 380-415V 50Hz /380V 60Hz 10 - 52X1-4 52X1-3 DM1 CNR WH Mark CH1 CM1 CNA-Z CT1 C1-1,2 DM1 EEVH1,2 EEVSC F FMC1 FMo1,2 IPM J11,12 J13 J14 J15 J16 LED1 LED1(INV) LED2 LED3 L1-1∼3 L3 R1-4 + C1-2 R1-3 + C1-1 LED1 (INV) CNI3 BK Inspection(Red) Normal(Yellow)-Flashing Normal(Green) Service(green for service) D.C.reactor D.C.reactor Defrost recover temp Defrost start temp Spare BK BK WH RD RD GN RD WH BL L1o L2o L3o No L1i L2i L3i Ni GN E Noise filter PWB3-2 CN1 RD WH BL BK L3 Mark PSH PSL PWB1∼3 R1-1∼1-5 SV1 SV6 SW1 SW2 SW3-1 SW3-2 ON OFF SW3-3 SW3-4 ON OFF SW3-5 ON OFF SW3-6 SW3-7 ON OFF SW3-8 BK GN CNI1 WH A2 B2 A1 B1 BK RD CNX1 YE CNW RD CNFAN1 WH CNR1 WH BK CNFAN2 RD CNM1 GY BK CH1 BR FMo1 M FMo2 Parts name High pressure sensor Low pressure sensor Printed wiring board(PCB) Rush current suppression resistor Solenoid valve(CM1:bypass) Solenoid valve(oil separator CM1) Address setting SW outdoor unit No.(2 digits) Address setting SW outdoor unit No.(1 digit) inspection LED reset Auto backup operation Regular operation Spare Refrigerant quantity check Regular operation Check operation Regular operation Spare Forced cooling/heating Regular operation Spare BETWEEN INDOOR UNIT AND OUTDOOR UNIT,BETWEEN OUTDOOR UNITS ON THE SAME REFRIGERANT LINE. BETWEEN OUTDOOR UNITS ON THE DIFFERENT REFRIGERANT LINES. Parts name Crankcase heater Compressor motor Connector Current sensor Electrolytic capacitor Diode module Expansion valve for heating Expansion valve for SC Fuse Fan for IPM Blower motor Intelligent power module Set up model(volt) External input select level/pulse MS 3∼ V CT1 BK CNA WH W P IPM1 U V W N CNSL1,2 BK NETWORK CONNECTOR WH WH BL BK WH CNI2 WH + - AC1 AC2 AC3 U CM1 BL Inverter PWB2-1 Meaning of marks TB2 A1 B1 A2 B2 RD RD R1-5 R1-1 RD WH BL RD 52X1-1 RD 52X1-3 YE Circuit breaker Earth leakage breaker (Impulse withstanding type) Signal line YE L1-2 WH R1-2 GY 52X1-2 RD WH BL GY RD WH BL BK L1-1 RD WH BL 52X1-4 RD WH BL YE L1-3 WH WH RD RD BL M SW2 CNA3 CNA1 WH WH Mark SW4-1∼4 SW4-5 SW4-6 SW4-7 SW4-8 SW5-1 ON OFF SW5-2 ON OFF SW5-3 ON OFF SW5-4 SW5-5 ON OFF SW5-6 8 SW6-1 3 SW6-4 ON OFF SW7 SW8 SW9 CNEEV1 RD 1 2 3 4 5 6 7 8 SW3 CONTROL PWB1 ON OFF SW1 CNN1 RD BL SW7 SW8 SW9 CNEEV2 BL EEVSC M J11 J13 EEVH2 M J14 J15 CNV t° t° Mark TB1,2 Tho-A Tho-C1 Tho-D1 Tho-H Tho-P1 Tho-R1 Tho-R2 Tho-R3 Tho-R4 Tho-S Tho-SC 20S 20UF 52X1-1∼1-4 63H1-1 7SEG1 7SEG2 FMC1 t° t° t° t° t° Color Black Blue Brown Green Gray Orange Red White Yellow Pink Yellow YE/GN /Green Mark BK BL BR GN GY OR RD WH YE PK t° Demand input External input Color mark t° CNU1 BL CNP1 YE CNF2 GN WH CNS2 RD CNF1 WH WH CNS1 GN CNB4 RD WH CNG2 WH Silent mode input WH Cooling/Heating forced input Reserve output Operation output Trouble output RD WH BK PSH RD WH BK PSL CNG1 BL CNY WH CNH BL CNZ1 RD CNL1 BL CNL2 WH CNB3 BK CNN8 PK CNB2 RD CNQ1 WH High pressure switch(for protection) 7-segment L.E.D.(function indication) 7-segment L.E.D.(data indication) 4way valve Capacity control Solenoid for CM1 63H1-1 Parts name Terminal block External air thermistor Under-dome thermistor Discharge pipe thermistor Sub-cooling coil thermistor 2 Power transistor thermistor Heat exchanger thermistor(exhaust) Heat exchanger thermistor(exhaust) Heat exchanger thermistor(inlet) Heat exchanger thermistor(inlet) Suction pipe thermistor Sub-cooling coil thermistor 1 Compressor Terminal block V(White) t° CNTH WH PC (RS232C) U(Red) t° LED3 1 2 3 4 5 6 7 8 SW6 LED2 W(Blue) J16 1 2 3 4 5 6 7 8 CNEEV3 WH J12 CNN7 GN CNN6 PK LED1 20UF SV1 BL SW5 Parts name Model setting Spare Spare Address setting switch(master・slave) Address setting switch(master・slave) Trial operation Regular operation Trial operation mode/cooling Trial operation mode/heating Pump down operation Regular operation Spare Super Link communication Super Link communication Spare Spare High Head Standard Data clear/insert 7-segment indicate(unit's place) 7-segment indicate(ten's place) EEVH1 M 7SEG2 1 2 3 4 5 6 7 8 SW4 7SEG1 CNN2 GN BL OR YE WH L1i L2i L3i Ni RD L1o L2o L3o No RD F(4A) BL OR YE WH GN E Noise filter PWB3-1 CN1 RD BL BL OR YE WH YE/GN RD F(4A) WH OR YE BL GN PK WH OR YE BL GN PK BK RD BK RD RD BL SV6 BK Tho-R1 BK Tho-R2 20S BK Tho-D1 BK BK Tho-R3 BK Tho-R4 BK Tho-SC 52X1-2 BK Tho-S BK BK 52X1-1 YE Tho-A BK BK Tho-H BK Tho-P1 - Tho-C1 TB1 L1 L2 L3 N '14 • KX-DB-201 Models FDC400KXZE1, 450KXZE1 FDCS400KXZE1, 450KXZE1 PCB003Z820 Mark CH1,2 CM1,2 CNA-Z CT1,CT2 C1-1,2,C2-1,2 DM1,2 EEVH1,2 EEVSC F FMC1,2 FMo1,2 IPM J11,12 J13 J14 J15 J16 LED1 LED1(INV) LED2 LED3 L1-1,2,L2-1,2 L3 R1-1 RD 52X1-4 52X1-3 DM1 CNI2 WH Inverter PWB2-1 CNR WH CNSL1,2 BK NETWORK CONNECTOR WH WH BL BK WH PWB3-1 Noise filter - U MS 3∼ V Inspection(Red) Normal(Yellow)-Flashing Normal(Green) Service(green for service) D.C.reactor D.C.reactor Defrost recover temp Defrost start temp Spare CNI3 BK LED1 (INV) RD 52X2-4 52X2-3 DM2 Inverter PWB2-2 CNR WH CNI3 BK BK BK WH RD GN L3 L1i L2i L3i Ni U N U CM2 MS 3∼ V CNI2 WH LED1 (INV) CNA WH W P IPM2 V W R2-4 + C2-2 R2-3 + C2-1 + AC1 AC2 AC3 - Mark PSH PSL PWB1∼3 R1-1∼2-4 SV1 SV2 SV6 SV7 SV11 SW1 SW2 SW3-1 SW3-2 ON OFF SW3-3 SW3-4 ON OFF SW3-5 ON OFF SW3-6 SW3-7 ON OFF CT2 L1o L2o L3o No GN E Noise filter PWB3-2 CNI1 WH A2 B2 A1 B1 BK RD CNX1 YE CNW RD CNFAN1 WH CNR2 BL CH1 BR CNR1 WH CH2 BR FMo1 M BK CNM1 GY BK CNFAN2 RD FMo2 Parts name High pressure sensor Low pressure sensor Printed wiring board(PCB) Rush current suppression resistor Solenoid valve(CM1:bypass) Solenoid valve(CM2:bypass) Solenoid valve(oil separator CM1) Solenoid valve(oil separator CM2) Solenoid valve(gas bypass) Address setting SW outdoor unit No.(2 digits) Address setting SW outdoor unit No.(1 digit) inspection LED reset Auto backup operation Regular operation Spare Refrigerant quantity check Regular operation Check operation Regular operation Spare Forced cooling/heating Regular operation BETWEEN INDOOR UNIT AND OUTDOOR UNIT,BETWEEN OUTDOOR UNITS ON THE SAME REFRIGERANT LINE. BETWEEN OUTDOOR UNITS ON THE DIFFERENT REFRIGERANT LINES. U CM1 CT1 CNA WH W P IPM1 V W R1-4 + C1-2 R1-3 + C1-1 + AC1 AC2 AC3 N E L1i L2i L3i Ni L1o L2o L3o No Parts name Crankcase heater Compressor motor Connector Current sensor Electrolytic capacitor Diode module Expansion valve for heating Expansion valve for SC Fuse Fan for IPM Blower motor Intelligent power module Set up model(volt) External input select level/pulse Meaning of marks TB2 A1 B1 A2 B2 Power source 3 Phase 380-415V 50Hz /380V 60Hz Circuit breaker Earth leakage breaker (Impulse withstanding type) Signal line RD RD 52X1-1 RD 52X1-3 BL YE L1-2 WH R1-2 GY BL GY RD WH BL BK 52X1-2 RD WH BL 52X1-4 RD WH BL WH 52X2-2 YE/GN GY YE L1-1 WH RD RD WH BL RD BL R2-1 R2-2 RD RD 52X2-1 RD WH GY RD 52X2-3 BL YE L2-2 WH BL BL RD WH BL BK RD WH BL 52X2-4 RD WH BL WH M SW2 CNN1 RD CNA3 CNA1 WH WH Mark SW3-8 SW4-1∼4 SW4-5 SW4-6 SW4-7 SW4-8 SW5-1 ON OFF SW5-2 ON OFF SW5-3 ON OFF SW5-4 SW5-5 ON OFF SW5-6 8 SW6-1 3 SW6-4 ON OFF SW7 SW8 SW9 CNEEV1 RD 1 2 3 4 5 6 7 8 SW3 CONTROL PWB1 ON OFF SW1 CNM2 RD BL 20S CNN3 BL CNN2 GN SW7 SW8 SW9 CNEEV2 BL EEVSC EEVH1 J13 CNEEV3 WH J12 EEVH2 M Parts name Spare Model setting Spare Spare Address setting switch(master・slave) Address setting switch(master・slave) Trial operation Regular operation Trial operation mode/cooling Trial operation mode/heating Pump down operation Regular operation Spare Super Link communication Super Link communication Spare Spare High Head Standard Data clear/insert 7-segment indicate(unit's place) 7-segment indicate(ten's place) M M J11 J14 J15 CNV t° t° Mark TB1,2 Tho-A Tho-C1,2 Tho-D1,2 Tho-H Tho-P1,2 Tho-R1 Tho-R2 Tho-R3 Tho-R4 Tho-S Tho-SC 20S 52X1-1∼2-4 63H1-1,2 7SEG1 7SEG2 BK BK CNP2 YE CNU2 BK t° t° t° t° t° Color Black Blue Brown Green Gray Orange Red White Yellow Pink Yellow YE/GN /Green Mark BK BL BR GN GY OR RD WH YE PK t° t° Tho-C2 t° Tho-P2 t° Tho-D2 Demand input External input Silent mode input Color mark t° CNU1 BL BK CNC2 GN CNP1 YE WH CNS2 RD CNF2 GN WH CNS1 GN CNF1 WH WH CNG2 WH Cooling/Heating forced input WH Reserve output Operation output Trouble output RD WH BK PSH RD WH BK PSL CNG1 BL CNY WH CNH BL CNZ1 RD CNL1 BL CNL2 WH CNB4 RD CNN8 PK FMC2 CNB3 BK CNQ2 WH FMC1 CNB2 RD CNQ1 WH 63H1-2 High pressure switch(for protection) 7-segment L.E.D.(function indication) 7-segment L.E.D.(data indication) 4way valve Solenoid for CM 63H1-1 Parts name Terminal block External air thermistor Under-dome thermistor Discharge pipe thermistor Sub-cooling coil thermistor 2 Power transistor thermistor Heat exchanger thermistor(exhaust) Heat exchanger thermistor(exhaust) Heat exchanger thermistor(inlet) Heat exchanger thermistor(inlet) Suction pipe thermistor Sub-cooling coil thermistor 1 Compressor Terminal block V(White) t° CNTH WH PC (RS232C) U(Red) t° LED3 1 2 3 4 5 6 7 8 SW6 LED2 W(Blue) J16 1 2 3 4 5 6 7 8 SW5 LED1 CNN7 GN CNN6 PK CNN9 BK 7SEG2 SV2 SV1 SV11 BL 1 2 3 4 5 6 7 8 SW4 7SEG1 SV7 SV6 RD YE L2-1 WH RD BL BL OR YE WH RD BL BL RD BK F(4A) BL BL OR YE WH BL BL OR YE WH BK F(4A) WH OR YE BL GN PK WH OR YE BL GN PK BK RD BK RD RD RD 11 RD BK Tho-R2 52X2-2 BK Tho-R1 BK BK Tho-R3 52X2-1 BK Tho-D1 BK BK Tho-R4 BK Tho-SC 52X1-2 BK Tho-S BK BK 52X1-1 YE Tho-A BK BK Tho-H BK Tho-P1 - Tho-C1 TB1 L1 L2 L3 N '14 • KX-DB-201 Models FDC475KXZE1, 500KXZE1, 560KXZE1 FDCS475KXZE1, 500KXZE1, 560KXZE1 PCB003Z821 '14 • KX-DB-201 2.4 Noise level Measured based on JIS B 8616 Mike position as highest noise level in position as below Distance from front side 1m Height 1m N80 70 N70 60 N60 50 N50 40 30 80 70 60 50 40 N40 N3 0 63 125 250 500 1000 2000 4000 30 8000 Cooling 80 N80 70 N70 60 N60 50 N50 40 30 N70 N60 50 N50 40 30 80 70 60 50 40 N40 N3 0 63 125 250 500 1000 2000 4000 30 8000 Mid Octave Band Frequency (Hz) Sound Pressure Level (dB) (Standard 2 x 10 -5 Pa) Sound Pressure Level (dB) (Standard 2 x 10 -5 Pa) N80 60 Sound Pressure Level (dB) (Standard 2 x 10 -5 Pa) Cooling 63 125 250 500 1000 N80 N70 60 N60 50 N50 40 Cooling 80 250 500 1000 2000 N80 N70 60 N60 50 N50 40 N50 40 30 4000 80 70 60 50 40 N40 N3 0 63 125 250 500 1000 2000 80 70 60 50 30 8000 Mid Octave Band Frequency (Hz) - 9- - 12 - 70 60 50 40 N40 N3 0 63 125 250 500 1000 2000 4000 30 8000 Model FDC500KXZE1 FDCS500KXZE1 Noise level 61 dB (A) at cooling 62 dB (A) at heating N60 50 80 Mid Octave Band Frequency (Hz) N70 60 Heating 70 30 30 8000 Heating 70 40 0 125 4000 N80 N40 N3 63 2000 4000 Mid Octave Band Frequency (Hz) Heating 70 30 50 40 0 Model FDC560KXZE1 FDCS560KXZE1 Noise level 64 dB (A) at cooling 66 dB (A) at heating 80 60 Model FDC475KXZE1 FDCS475KXZE1 Noise level 61 dB (A) at cooling 61 dB (A) at heating Heating 70 70 Cooling 80 Mid Octave Band Frequency (Hz) Model FDC450KXZE1 FDCS450KXZE1 Noise level 61 dB (A) at cooling 62 dB (A) at heating Cooling 80 N40 N3 Mid Octave Band Frequency (Hz) 80 Heating Sound Pressure Level (dB) (Standard 2 x 10 -5 Pa) Heating Model FDC400KXZE1 FDCS400KXZE1 Noise level 60 dB (A) at cooling 62 dB (A) at heating 30 8000 Sound Pressure Level (dB) (Standard 2 x 10 -5 Pa) Cooling 80 Model FDC335KXZE1 FDCS335KXZE1 Noise level 61 dB (A) at cooling 58 dB (A) at heating Sound Pressure Level (dB) (Standard 2 x 10 -5 Pa) Sound Pressure Level (dB) (Standard 2 x 10 -5 Pa) Model FDC280KXZE1 FDCS280KXZE1 Noise level 55 dB (A) at cooling 57 dB (A) at heating Cooling 80 Heating N80 70 N70 60 N60 50 N50 40 30 80 70 60 50 40 N40 N3 0 63 125 250 500 1000 2000 4000 Mid Octave Band Frequency (Hz) 30 8000 '14 • KX-DB-201 2.5 Corrosion protection treatment series Production by order KXZ outdoor series are available with special coating applied for not only sheet metals but also small parts in order to prevent salt corrosion caused by sea breeze in area along coast line (Within approximately 500m from coast line). Model No. FDCS280KXZE1 FDCS335KXZE1 FDCS400KXZE1 FDCS450KXZE1 FDCS475KXZE1 FDCS500KXZE1 FDCS560KXZE1 Nominal Cooling Capacity 28.0kW 33.5kW 40.0kW 45.0kW 47.5kW 50.0kW 56.0kW Sea breeze Sea Additional treatment from the standard series Parts Description Exterior panel undercoat: Cation electrodeposition coating topcoat: acrylic baked coating Base plate undercoat: Cation electrodeposition coating topcoat: acrylic baked coating Drain pan undercoat: Cation electrodeposition coating topcoat: acrylic baked coating Fan motor application of anticorrosion compound application of anticorrosion compound Fan motor base Fin Precoated Aluminum Blue Fins in high anticorrosion specification pipe application of anticorrosion compound Side plate application of anticorrosion compound Heat exchanger Compressor application of anticorrosion compound Accumulator application of anticorrosion compound Receiver application of anticorrosion compound Control box galvanized steel sheet + undercoat: Cation electrodeposition coating + topcoat: acrylic baked finish Baffle plate Service valve bracket galvanized steel sheet + undercoat: Cation electrodeposition coating + topcoat: acrylic baked finish Screw tap for exterior panel zinc coating + chromate treatment + fluorine coating Screw tap for inside of exterior panel zinc coating + chromate treatment + fluorine coating Corrosion protection treatment complies with regulation of The Japan Refrigeration and Air Conditioning Industry Association Caution Even if the outdoor unit is protected with the anti-salt damage treatment, it cannot be perfectly free from rusting. The following points should be kept in mind during installation and maintenance of the outdoor units. Installation (1) When installing the outdoor unit close to the coastal area, provide a windbreak to protect it from direct sea breeze and salt water splash. (2) Select a well-drained place to install. (3) If any scratch or damages occurred on the outdoor unit during installation, repair it carefully. Maintenance (1) Clean salt grains on the outdoor unit with fresh water periodically. (2) Apply rust preventive at regular intervals for maintenance depending on the conditions at the installation place (consulting with the withstanding capacity). (3) Confirm reset of screw tap after maintenance, if missing it may cause corrosion occurred from the hole of screw tap. (4) During prolonged non operation periods, protect the unit with covering. - 13 - '14 • KX-DB-201 3. RANGE OF USAGE & LIMITATIONS • Single use (also for combined use) System Item Indoor air temperature (Upper, lower limits) FDC280KXZE1 FDCS280KXZE1 FDC335KXZE1 FDCS335KXZE1 Refer to page 19 Outdoor air temperature (Upper, lower limits) Indoor units that can be used in combination Number of connected units Connectable capacity (1) Total piping length 1 to 24 units 1 to 29 units 1 to 34 units 140 - 364 168 - 435 200 - 520 (2) 1000m or less Main pipe length 130m or less Single direction piping length Actual length : 160m or less, Equivalent length : 185m or less Allowable pipe length from the first branching 90m or less (However, difference between the longest and shortest piping : 40m or less(6)) 18m or less Elevation difference between the first branching point and the indoor unit Difference in height between indoor and outdoor units 50m or less (Max. 70m or less) (5) Outdoor unit is higher Indoor unit atmosphere (behind ceiling) temperature and humidity Only models FDT, FDTC, FDTW, FDTS, FDTQ, FDU, FDUM, FDUT, FDUH, FDU-F 18m or less Dew point temperature 28 or less, relative humidity 80% or less (FDE, FDK, FDFL, FDFU, FDFW : Dew point temperature 23 or less, relative humidity 80% or less) 5 min or more (from stop to stop or from start to start) 1 cycle time 3 min or more Stop time Voltage fluctuation Within 10% of rated voltage Voltage drop during start Within 15% of rated voltage Phase unbalance Within 3% Indoor units that can be used in combination FDC475KXZE1 FDCS475KXZE1 Connectable capacity (1) MAX. 90m 1 to 39 units 225 - 585 1 to (Highest 41 units indoor unit) 238 - 617 Single direction piping length Allowable pipe length from the first First branching branch 18m or less 50m or less (Max. 70m or less) (5) (Lowest indoor unit) 40m or less (3) Indoor unit 18m or less (Highest indoor unit) Dew point temperature 28 or less, relative humidity 80% or less (FDE, FDK, FDFL, FDFU, FDFW : Dew point temperature 23 or less, relative humidity 80% or less) MAX. 18m Stop time MAX. 130m 5 min or more (from stop to stop or from start to start) (Header) 3 min or more Voltage fluctuation Within 10% of rated voltage Voltage drop Firstduring branch start Within 15% of rated voltage MAX. 18m 50m (Outdoor unit is lower : 40m) Power source voltage MAX. 90m Outdoor unit is lower 1 cycle time 280 - 728 90m or less (However, difference between the longest and shortest piping : 40m or less(6)) Outdoor unit is higher Indoor unit atmosphere (behind ceiling) temperature and humidity Only models FDT, FDTC, FDTW, FDTS, FDTQ, FDU, FDUM, FDUT, FDUH, FDU-F Compressor stop/start frequency 250 - 650 130m or less Actual length : 160m or less, Equivalent length : 185m or less Elevation difference between the first branching point and the indoor unit Outdoor unit Difference in the elevation of indoor units in a system denotes 1 to 48 units 1000m or less MAX. 130m FDC560KXZE1 FDCS560KXZE1 1 to 43 units MAX. 18m 50m Total piping length (2) Difference in height between indoor and outdoor units FDC500KXZE1 FDCS500KXZE1 Refer to page 19 Indoor unit Number of connected units (Outdoor unit is lower : 40m) FDC450KXZE1 FDCS450KXZE1 MAX. 18m System Item Indoor air temperature (Upper, lower limits) Outdoor unit Outdoor air temperature (Upper, lower limits) MAX. 18m Power source voltage MAX. 18m Compressor stop/start frequency (3) 40m or less Outdoor unit is lower Difference in the elevation of indoor units in a system Main pipe length FDC400KXZE1 FDCS400KXZE1 Phase unbalance (Lowest indoor unit) Within 3% MAX. 130m 14 - X. 18m - MAX. 18m 50m nit is lower : 40m) Note (1) When connecting the indoor unit type FDK, FDFL, FDFU or FDFW Series, limit the connectable capacity not higher than 130%. (2) When the pipe extension length exceeds 510 m, additional refrigerant MAX. 90m oil must be charged (1,000 cc). (3) It must be less than 30 m when conducting the cooling operation with the outdoor air temperature lower than 10℃. (4) I f superlink I (previous superlink) is selected, all the range of usage and limitations, not only the limitations of connectable indoor capacity and connectable number of indoor unit but also of the piping length, operating temperature range and etc., become same as those of KX4 (See technical manual ’07·KX·KXR-T-114). In addition to above limitations, all of new functions for KX6 and KXZ such as automatic address unitrefrigerant systems and etc. will be Indoor unit denotes setting functionOutdoor for multiple cancelled. (5)When it is required to install in a range of 50 to 70 m, the limitation of use, etc. are different from those described here. For details, refer to (2) MAX. 40m page 20. MAX. 90m (2) (6)When it is required to install in the difference between the longest and shortest(Highest piping more indoor unit)than 40m, refer to page 21. '14 • KX-DB-201 '14 • KX-DB-201 Allowable length of refrigerant piping, height difference between indoor and outdoor unit (1) Branch pipe System (Branch piping used) Outdoor unit Indoor unit MAX. denotes 90m (2) MAX. 40m (3) Ⅳ First branch Ⅴ Ⅵ MAX. 90m (2) (Lowest indoor unit) (2) Header System (Header used) Outdoor unit MAX. 18m Ⅲ MAX. 18m Ⅱ MAX. 130m MAX. 18m (Outdoor unit is lower : 40m) 50m (Max.70m) (Highest indoor unit) Ⅰ Indoor unit MAX. 40m (3) Ⅲ First branch Ⅳ (Lowest indoor unit) MAX. 18m Ⅱ (Header) MAX. 18m MAX. 130m 50m (Max.70m) (Outdoor unit is lower : 40m) Ⅰ MAX. 18m (Highest indoor unit) MAX. 90m (2) (3) Mixed System (Branch piping and Header used) Outdoor unit Indoor unit MAX.90m(2) Ⅱ Ⅲ First branch (Header) Ⅴ MAX.90m(2) Ⅳ MAX.18m MAX.18m Ⅰ MAX.130m MAX.18m 50m (Max.70m) (Outdoor unit is lower: 40m) (Highest indoor unit) (3) MAX.40m Ⅵ (Lowest indoor unit) Note (1) A branch piping system cannot be connected after a header system. (2) 90m or less (However, difference between the longest and shortest piping : 40m or less (3)) (3) When it is required to install the difference between the longest and shortest piping more than 40m, refer to page 21. Important When the Additional refrigerant quantity (P+I) is over the following table, please separate the refrigerant line. Outdoor unit 280-670 735-1350 1425-1680 P +I (kg) 40 80 100 P: Additional refrigerant quantity for piping (kg) I : Additional refrigerant quantity for indoor units (kg) - 15 - '14 • KX-DB-201 • Combination use System Item Indoor air temperature (Upper, lower limits) FDC670KXZE1 FDCS670KXZE1 FDC615KXZE1 FDCS615KXZE1 FDC735KXZE1 FDCS735KXZE1 Number of connected units Connectable capacity (1) 2 to 53 units 2 to 58 units 308 - 799 335 - 871 Total piping length (2) 2 to 63 units 2 to 69 units 2 to 73 units 368 - 955 400 - 1040 425 - 1105 1000m or less Single direction piping length Actual length : 160m or less, Equivalent length : 185m or less 130m or less Main pipe length Allowable pipe length from the first branching 90m or less (However, difference between the longest and shortest piping : 40m or less (6) ) 18m or less Elevation difference between the first branching point and the indoor unit Difference in height between indoor and outdoor units Outdoor unit is higher 50m or less (Max.70m or less) (5) Outdoor unit is lower 40m or less (3) Difference in the elevation of indoor units in a system 18m or less Difference in height between outdoor units (Same system) MAX. 0.4m Difference between an outdoor unit and on outdoor unit side branch pipe MAX. 5m Length of oil equalization piping MAX. 10m Indoor unit atmosphere (behind ceiling) temperature and humidity Only models FDT, FDTC, FDTW, FDTS, FDTQ, FDU, FDUM, FDUT, FDUH, FDU-F Compressor 1 cycle time stop/start Stop time frequency Power source voltage Dew point temperature 28 or less, relative humidity 80% or less (FDE, FDK, FDFL, FDFU, FDFW : Dew point temperature 23 or less, relative humidity 80% or less) 5 min or more (from stop to stop or from start to start) 3 min or more Voltage fluctuation Within Voltage drop during start Within System Item Indoor air temperature (Upper, lower limits) FDC900KXZE1 FDCS900KXZE1 FDC950KXZE1 FDCS950KXZE1 15% of rated voltage FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE1 FDCS1000KXZE1 FDCS1060KXZE1 FDCS1120KXZE1 Refer to page 19 Outdoor air temperature (Upper, lower limits) Number of connected units 2 to 78 units 2 to 80 units Connectable capacity 450 - 1170 475 - 1235 Total piping length (2) 2 to 80 units 2 to 80 units 2 to 80 units 500 - 1300 530 - 1378 560 - 1456 1000m or less Single direction piping length Main pipe length Allowable pipe length from the first branching Actual length : 160m or less, Equivalent length : 185m or less 130m or less 90m or less (However, difference between the longest and shortest piping : 40m or less (6) ) 18m or less Elevation difference between the first branching point and the indoor unit Difference in height between indoor and outdoor units 10% of rated voltage Within 3% Phase unbalance Indoor units that can be used in combination Outdoor unit is higher 50m or less (Max.70m or less) (5) Outdoor unit is lower 40m or less (3) Difference in the elevation of indoor units in a system 18m or less Difference in height between outdoor units (Same system) MAX. 0.4m Difference between an outdoor unit and on outdoor unit side branch pipe MAX. 5m Length of oil equalization piping MAX. 10m Indoor unit atmosphere (behind ceiling) temperature and humidity Only models FDT, FDTC, FDTW, FDTS, FDTQ, FDU, FDUM, FDUT, FDUH, FDU-F Compressor 1 cycle time stop/start Stop time frequency Power source voltage FDC850KXZE1 FDCS850KXZE1 Refer to page 19 Outdoor air temperature (Upper, lower limits) Indoor units that can be used in combination FDC800KXZE1 FDCS800KXZE1 Dew point temperature 28 or less, relative humidity 80% or less (FDE, FDK, FDFL, FDFU,FDFW : Dew point temperature 23 or less, relative humidity 80% or less) 5 min or more (from stop to stop or from start to start) 3 min or more Voltage fluctuation Within Voltage drop during start Within 10% of rated voltage 15% of rated voltage Within 3% Phase unbalance Note (1) When connecting the indoor unit type FDK, FDFL, FDFU or FDFW Series, limit the connectable capacity not higher than 130%. (2) When the pipe extension length exceeds 510 m, additional refrigerant oil must be charged (1,000 cc). (3) It must be less than 30 m when conducting the cooling operation with the outdoor air temperature lower than 10℃. (4) I f superlink I (previous superlink) is selected, all the range of usage and limitations, not only the limitations of connectable indoor capacity and connectable number of indoor unit but also of the piping length, operating temperature range and etc., become same as those of KX4 (See technical manual ’07·KX·KXR-T-114). In addition to above limitations, all of new functions for KX6 and KXZ such as automatic address setting function for multiple refrigerant systems and etc. will be cancelled. (5)When it is required to install in a range of 50 to 70 m, the limitation of use, etc. are different from those described here. For details, refer to page 20. (6)When it is required to install in the difference between the longest and shortest piping more than 40m, refer to page 21. - 16 - '14 • KX-DB-201 System Item Indoor air temperature (Upper, lower limits) FDC1300KXZE1 FDC1350KXZE1 FDC1425KXZE1 FDC1200KXZE1 FDC1250KXZE1 FDCS1200KXZE1 FDCS1250KXZE1 FDCS1300KXZE1 FDCS1350KXZE1 FDCS1425KXZE1 Refer to page 19 Outdoor air temperature (Upper, lower limits) Indoor units that can be used in combination Number of connected units Connectable capacity (1) 3 to 80 units 3 to 80 units 600 - 1560 625 - 1625 Total piping length (2) 3 to 80 units 3 to 80 units 650 - 1690 675 - 1755 713 - 1852 1000m or less Single direction piping length Actual length : 160m or less, Equivalent length : 185m or less 130m or less Main pipe length Allowable pipe length from the first branching 90m or less (However, difference between the longest and shortest piping : 40m or less (6) ) 18m or less Elevation difference between the first branching point and the indoor unit Difference in height between indoor and outdoor units 3 to 80 units Outdoor unit is higher 50m or less (Max.70m or less) (5) Outdoor unit is lower 40m or less (3) Difference in the elevation of indoor units in a system 18m or less Difference in height between outdoor units (Same system) MAX. 0.4m Difference between an outdoor unit and on outdoor unit side branch pipe MAX. 5m Length of oil equalization piping MAX. 10m Indoor unit atmosphere (behind ceiling) temperature and humidity Only models FDT, FDTC, FDTW, FDTS, FDTQ, FDU, FDUM, FDUT, FDUH, FDU-F Compressor 1 cycle time stop/start Stop time frequency Power source voltage Dew point temperature 28 or less, relative humidity 80% or less (FDE, FDK, FDFL, FDFU,FDFW : Dew point temperature 23 or less, relative humidity 80% or less) 5 min or more (from stop to stop or from start to start) 3 min or more Voltage fluctuation Within 10% of rated voltage Voltage drop during start Within 15% of rated voltage Within 3% Phase unbalance System FDC1450KXZE1 FDC1500KXZE1 FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE1 FDCS1450KXZE1 FDCS1500KXZE1 FDCS1560KXZE1 FDCS1620KXZE1 FDCS1680KXZE1 Item Indoor air temperature (Upper, lower limits) Refer to page 19 Outdoor air temperature (Upper, lower limits) Indoor units that can be used in combination Number of connected units 3 to 80 units 3 to 80 units Connectable capacity 725 - 1885 750 - 1950 Total piping length (2) 3 to 80 units 3 to 80 units 780 - 2080 810 - 2106 840 - 2184 1000m or less Single direction piping length Main pipe length Allowable pipe length from the first branching Actual length : 160m or less, Equivalent length : 185m or less 130m or less 90m or less (However, difference between the longest and shortest piping : 40m or less (6) ) 18m or less Elevation difference between the first branching point and the indoor unit Difference in height between indoor and outdoor units 3 to 80 units Outdoor unit is higher 50m or less (Max.70m or less) (5) Outdoor unit is lower 40m or less (3) Difference in the elevation of indoor units in a system 18m or less Difference in height between outdoor units (Same system) MAX. 0.4m Difference between an outdoor unit and on outdoor unit side branch pipe MAX. 5m Length of oil equalization piping MAX. 10m Indoor unit atmosphere (behind ceiling) temperature and humidity Only models FDT, FDTC, FDTW, FDTS, FDTQ, FDU, FDUM, FDUT, FDUH, FDU-F Compressor 1 cycle time stop/start Stop time frequency Power source voltage Dew point temperature 28 or less, relative humidity 80% or less (FDE, FDK, FDFL, FDFU,FDFW : Dew point temperature 23 or less, relative humidity 80% or less) 5 min or more (from stop to stop or from start to start) 3 min or more Voltage fluctuation Within 10% of rated voltage Voltage drop during start Within 15% of rated voltage Within 3% Phase unbalance Note (1) When connecting the indoor unit type FDK, FDFL, FDFU or FDFW Series, limit the connectable capacity not higher than 130%. (2) When the pipe extension length exceeds 510 m, additional refrigerant oil must be charged (1,000 cc). (3) It must be less than 30 m when conducting the cooling operation with the outdoor air temperature lower than 10℃. (4) I f superlink I (previous superlink) is selected, all the range of usage and limitations, not only the limitations of connectable indoor capacity and connectable number of indoor unit but also of the piping length, operating temperature range and etc., become same as those of KX4 (See technical manual ’07·KX·KXR-T-114). In addition to above limitations, all of new functions for KX6 and KXZ such as automatic address setting function for multiple refrigerant systems and etc. will be cancelled. (5)When it is required to install in a range of 50 to 70 m, the limitation of use, etc. are different from those described here. For details, refer to page 20. (6)When it is required to install in the difference between the longest and shortest piping more than 40m, refer to page 21. - 17 - '14 • KX-DB-201 gs+8$" Allowable length of refrigerant piping, height difference between indoor and outdoor unit (1) Branch pipe System (Branch piping used) Outdoor unit Indoor unit denotes MAX. 90m (2) MAX. 130m MAX. 5m MAX. 40m (3) MAX. 18m Outdoor unit 2 MAX. 5m Outdoor unit side branch (DOS-2A-3) MAX. 18m MAX. 10m First branch MAX. 90m (2) (Lowest indoor unit) (2) Header System (Header used) Outdoor unit Outdoor unit 1 Indoor unit MAX. 40m (3) MAX. 130m MAX. 5m (Highest indoor unit) MAX. 18m Outdoor unit 2 MAX. 5m MAX. 10m Outdoor unit side branch (DOS-2A-3) First branch MAX. 18m MAX. 0.4m 50m (Max.70m) (Outdoor unit is lower : 40m) Oil equalization piping MAX. 18m (Highest indoor unit) (Header) MAX. 18m Outdoor unit 1 MAX. 0.4m 50m (Max.70m) (Outdoor unit is lower : 40m) Oil equalization piping (Lowest indoor unit) MAX. 90m (2) (3) Mixed System (Branch piping and Header used) Outdoor unit Indoor unit MAX.90m(2) MAX.18m Ⅰ MAX.130m Ⅱ (Header) Ⅴ MAX.90m(2) Ⅳ MAX.18m Ⅲ First branch MAX.18m (Outdoor unit is lower: 40m) 50m (Max.70m) (Highest indoor unit) MAX.40m(3) Ⅵ (Lowest indoor unit) (4) Pipe system for combination of 3 outdoor units (Displaying only outdoor units) Oil equalization piping Outdoor unit 3 MAX. 130m L1 ≦ 5m L2 + L4 ≦ 5m L3 + L4 ≦ 5m MAX. 0.4m L3 Outdoor unit 2 L2 Lc L4 La + Lb ≦ 10m Lb + Lc ≦ 10m Lc + La ≦ 10m Outdoor unit 1 L1 Lb La Outdoor unit side branch (DOS-3A-3) First branch Note (1) A branch piping system cannot be connected after a header system. (2) 90m or less (However, difference between the longest and shortest piping : 40m or less (3)) (3) When it is required to install the difference between the longest and shortest piping more than 40m, refer to page 21. Important When the Additional refrigerant quantity (P+I) is over the following table, please separate the refrigerant line. Outdoor unit 280-670 735-1350 1425-1680 P +I (kg) 40 80 100 P: Additional refrigerant quantity for piping (kg) I : Additional refrigerant quantity for indoor units (kg) - 18 - '14 • KX-DB-201 Operating temperature range 50 Outdoor air D.B. temperature °CDB Cooling operation 46℃DB 43℃DB 40 30 20 10 0 -10 -20 10 -15℃DB 12 14 16 18 20 22 24 26 Indoor air W.B. temperature °CWB *In case it is the promised installation location that the outdoor unit is used on conditions with the ambient temperature of 43℃ or more, refer to page 7 (2.2 Exterior dimensions). 35 Indoor air D.B. temperature °CDB Heating operation 30 27℃DB 25 20 15 10 5 -20 -15 -10 -5 0 5 10 15 20 25 Outdoor air W.B. temperature °CWB “CAUTION” Cooling operation under low outdoor air temperature conditions KXZ models can be operated in cooling mode at low outdoor air temperature condition within above temperature range. However in case of severely low temperature conditions if the following precaution is not observed, it may not be operated in spite of operable temperature range mentioned above and cooling capacity may not be established under certain conditions. [Precaution] In case of severely low temperature condition 1) Install the outdoor unit at the place where strong wind cannot blow directly into the outdoor unit. 2) If there is no installation place where can prevent strong wind from directly blowing into the outdoor unit, prepare a windbreak fence or something like that locally in order to divert the strong wind from the outdoor unit. [Reason] Under the low outdoor air temperature conditions of -5˚C or lower, if strong wind directly blow into the outdoor unit, the outdoor heat exchanger temperature will drop, even though the outdoor fan is stopped by outdoor fan control. This makes high and low pressures to drop as well. This low pressure drop makes the indoor heat exchanger temperature to drop and will activate anti-frost control at indoor heat exchanger at frequent intervals, that cooling operation may not be established for any given time. - 19 - '14 • KX-DB-201 Specification for installation with large head difference (Applicable to: FDC280 - 1680KXZE1) In case when the outdoor unit is installed at a higher place and the difference in the elevation between the indoor and the outdoor units is larger than 50 m and smaller than 70 m, the limitation on application differs partially from ordinary applications and, instead, the following specification applies. The pipe size, refrigerant amount and way of switch setting become also different. In the range of use, the outdoor air temperature (lower limit), indoor units allowed to combine, total piping length and difference in the elevation between indoor units in the same system are different from ordinary applications. Table 1 Range of use FDC280-1680KXZE1 FDCS280-1680KXZE1 Item Indoor air temperature (Upper, lower limits) Outdoor air temperature (Upper, lower limits) Indoor units that can be used in combination Total piping length Refer to Table 2 Number of connected units Connectable capacity Refer to Table 3 510m or less 130m or less Actual length:160m or less, Equivalent length:185m or less 90m or less (However, difference between the longest and shortest piping:40m or less) Main pipe length Single direction piping length Allowable pipe length from the first branching Elevation difference between the first branching point and Allowable difference in the the indoor unit Outdoor unit is higher elevation Outdoor unit is lower Difference in the elevation of indoor units in a system 18m or less 50m or more-70m or less 40m or less 15m or less 0.4m or less Difference in the elevation Elevation from outdoor unit to Limitation on piping from branching pipe at outdoor unit side outdoor unit to branching Oil equalizing pipe length pipe at outdoor unit side Length between outdoor branching pipes for a combination of 3 units Indoor unit atmosphere (behind ceiling) temperature and humidity Only models FDT,FDTC,FDTW,FDTQ,FDTS,FDU,FDUM,FDUH,FDUT Compressor stop/start frequency Power source voltage 5m or less 10m or less 5m or less 。 Dew point temperature 28 C or less, relative humidity 80% or less 。 (FDT,FDK,FDFL,FDFU,FDFW:Dew point temperature 28 C or less, relative humidity 80% or less) 5 min or less (from stop to stop or from start to start) 3 min or more Within ±10% of rated voltage Within –15% of rated voltage Within 3% 1 cycle time Stop time Voltage fluctuation Voltage drop during start Phase unbalance Table 3 Number of connectable indoor units and capacity range Table 2 Indoor air temperature/Out door air t e mpe rat ure Outdoor air D.B. temperature °CDB Cooling operation Model/Item 50 43℃DB 40 30 20 10 0 -5℃DB -10 -20 10 12 14 16 18 20 22 24 Indoor air W.B. temperature °CWB Indoor air D.B. temperature °CDB Heating operation 35 30 27℃DB 25 20 15 10 5 -10 -5 0 5 10 15 20 25 Outdoor air W.B. temperature °CWB - 20 - 26 FDC(S)280KXZE1 FDC(S)335KXZE1 FDC(S)400KXZE1 FDC(S)450KXZE1 FDC(S)475KXZE1 FDC(S)500KXZE1 FDC(S)560KXZE1 FDC(S)615KXZE1 FDC(S)670KXZE1 FDC(S)735KXZE1 FDC(S)800KXZE1 FDC(S)850KXZE1 FDC(S)900KXZE1 FDC(S)950KXZE1 FDC(S)1000KXZE1 FDC(S)1060KXZE1 FDC(S)1120KXZE1 FDC(S)1200KXZE1 FDC(S)1250KXZE1 FDC(S)1300KXZE1 FDC(S)1350KXZE1 FDC(S)1425KXZE1 FDC(S)1450KXZE1 FDC(S)1500KXZE1 FDC(S)1560KXZE1 FDC(S)1620KXZE1 FDC(S)1680KXZE1 Number of connectable units 1 to 1 8 1 to 2 2 1 to 2 6 1 to 3 0 1 to 3 1 1 to 3 3 1 to 3 7 2 to 4 1 2 to 4 4 2 to 4 9 2 to 5 3 2 to 5 6 2 to 6 0 2 to 6 3 2 to 6 6 2 to 7 0 2 to 7 4 3 to 8 0 3 to 8 0 3 to 8 0 3 to 8 0 3 to 8 0 3 to 8 0 3 to 8 0 3 to 8 0 3 to 8 0 3 to 8 0 Connectable capacity 140 - 280 168 - 335 200 - 400 225 - 450 238 - 475 250 - 500 280 - 560 308 - 615 335 - 670 368 - 735 400 - 800 425 - 850 450 - 900 475 - 950 500 - 1000 530 - 1060 560 - 1120 600 - 1200 625 - 1250 650 - 1300 675 - 1350 713 - 1425 725 - 1450 750 - 1500 780 - 1560 810 - 1620 840 - 1680 '14 • KX-DB-201 <Pipe size selection> In the figure for pipe selection, sizes of main pipe and the pipe between the branch at the indoor side and the indoor unit are selected on the basis different from normal practice. (1) Main pipe (branch of the outdoor unit – first branch at the indoor side) Size of liquid pipe is different. Change the size of main pipe according to Table 4. When the maximum length (from the outdoor unit to the furthest indoor unit) is larger than 90 m (actual length), change the size of main pipe according to Table 4. Table 4 Main pipe size Pipe size for an actual length of 90m or longer Gas pipe Liquid pipe φ12.7 × t 0.8 φ25.4 (φ22.22) × t 1.0 Main pipe size (normal) Gas pipe Liquid pipe φ12.7 × t 0.8 φ22.22 × t 1.0 φ25.4 (φ22.22) × t 1.0 φ25.4 (φ28.58) × t 1.0 Outdoor unit 280 335 400 450 475 500 560 615 670 735 800 850 900 950 1000 1060 1120 1200 1250 1300 1350 1425 1450 1500 1560 1620 1680 φ28.58 × t 1.0 φ15.88 × t 1.0 φ15.88 × t 1.0 φ28.58 × t 1.0 φ31.8 × t 1.1 (φ34.92 × t 1.2) φ31.8 × t 1.1 (φ28.58 × t 1.0) φ19.05 × t 1.0 φ19.05 × t 1.0 φ38.1 × t 1.35 (φ34.92 × t 1.2) φ38.1 × t 1.35 (φ34.92 × t 1.2) φ22.22 × t 1.0 φ22.22 × t 1.0 (2) Between branch at the indoor side and indoor unit Size of gas pipe for indoor unit with capacity larger than 112 is different. Change the size of pipe connected to indoor unit according to Table 5. Table 5 Indoor unit connecting pipe size Capacity Indoor unit Gas pipe 15,22,28 36,45,56 71,90 112,140,160 224 280 Liquid pipe φ 9.52 × t0.8 φ 12.7 × t0.8 φ15.88 × t1.0 φ19.05 × t1.0 φ22.22 × t1.0 φ 25.4 × t1.0 φ 6.35 × t0.8 φ 9.52 × t0.8 (3) Refrigerant quantity In addition to normal charge quantity for refrigerant pipes, charge quantity for the difference in capacity between the indoor and the outdoor units, and standard additional refrigerant quantity, measure and charge the additional refrigerant quantity for the installation with the difference in the elevation being over 50 m and less than 70 m. Table 6 Additional refrigerant quantity for the installation with the difference in the elevation being over 50 m and less than 70 m Outdoor unit 280 335 400 450 475 500 560 (kg) 0.3 0.5 0.6 0.7 0.8 0.8 0.9 Outdoor unit 615 670 735 800 850 900 950 (kg) 0.8 1.0 1.1 1.2 1.3 1.4 1.6 Outdoor unit 1000 1060 1120 1200 1250 1300 1350 (kg) 1.6 1.7 1.8 1.8 1.9 2.0 2.1 Outdoor unit 1425 1450 1500 1560 1600 1680 (kg) 2.4 2.4 2.4 2.5 2.6 2.7 (4) Microcomputer control Setting of microcomputer control needs to be changed when the outdoor unit is installed upwards and the difference in elevation is larger than 50 m and less than 70 m. Make sure to set SW6-4 at ON position on both the master and slave units, before turning the power on. When the difference between the longest and shortest piping is longer than 40 m, adjust the difference in the elevation of indoor units in a system such that it will fall in the OK range on the following graph. When the difference in the elevation between the indoor and the outdoor units is 50 m – 70 m, the difference between the longest and shortest piping cannot exceed 40 m. Reduce it to less than 40 m. If the refrigerant quantity over occurs when the difference between the ongest and shortest piping is longer than 40 m, there is a risk that the heating capacity becomes insufficient. Take sufficient care to adjust the additional refrigerant quantity at correct value. Difference between the longest and shortest piping (m) Specification for installation with the difference between the longest and shortest piping more than 40m 85 80 75 70 NO 65 60 55 OK 50 45 40 0 2 4 6 8 10 12 14 16 18 Difference in the elevation of indoor units in a system (m) - 21 - - Thermistor(Entrance) (Thi-R2) Thermistor (Thi-A) Thermistor(Exit) (Thi-R3) Thermistor(Entrance) (Thi-R2) Thermistor (Thi-A) 22 - Strainer Electronic expansion valve Indoor unit Strainer Thermistor(Bend) (Thi-R1) Electronic expansion valve Indoor unit To next indoor units Liquid line For outdoor unit 2 Strainer Oil separator Thermistor (Tho-C1) Service valve Thermistor (Tho-D1) Muffler High pressure switch(63H1-1) 4way valve Strainer Receiver Solenoid valve (SV11) Strainer Accumlator Thermistor (Tho-S) Low pressure sensor(PSL) Check joint Heat exchanger Strainer Sub-cooling coil (Tho-R4) (Thermistor,Entrance・Back) Thi-R1, R2 : Heating operation : Indoor fan control. Cooling operation : Frost prevention control. Super heat control. Thi-R3 : For super heat control of cooling operation. Tho-D : For control of discharge pipe temperature. Tho-C : For control of temperature under the dome. Tho-S : For control of suction pipe temperature. Tho-R1, R2 : For control of defrosting. Tho-A : For control of defrosting. Tho-R3, R4 : Electronic expansion valve (EEVH1, 2) control of heating operation Tho-SC : Electronic expansion valve (EEVSC) control of cooling operation. Tho-H : For super heat control of sub-cooling coil. Electronic Strainer expansion valve (EEVSC) Sub-cooling coil Capillary tube Check joint High pressure sensor(PSH) Strainer Sub-cooling coil Thermistor (Tho-SC) Strainer Compressor 1 CM1 Check valve Service valve (Oil equalization line) Notes (1) Preset point of protective devices 63H1-1 : Open 4.15MPa, Close 3.15MPa (For protection) (2) Function of thermistor PSH : For compressor control 3.70 ON (MPa) PSL : ON 0.18MPa, OFF 0.20MPa (For compressor control) ON 0.134MPa, OFF 0.18MPa (For protection) Strainer Heat exchanger Strainer Heat exchanger Solenoid valve(SV6) Capillary tube Thermistor(Bend) (Thi-R1) Service valve Capillary tube (Tho-R3) (Thermistor,Entrance・Front) Sub-cooling coil Thermistor (Tho-H) Thermistor(Exit) (Thi-R3) Gas line Capillary tube Solenoid valve (SV1) (Tho-R1) (Thermistor,Exit・Front) Electronic expansion valve (EEVH1) Heat exchanger Strainer Sub-cooling coil Thermistor (Tho-A) Strainer (Tho-R2) (Thermistor,Exit・Back) Electronic expansion valve (EEVH2) Outdoor unit '14 • KX-DB-201 4. PIPING SYSTEM Models FDC280KXZE1, 335KXZE1 FDCS280KXZE1, 335KXZE1 PCB003Z822 - Thermistor(Entrance) (Thi-R2) Thermistor (Thi-A) Thermistor(Exit) (Thi-R3) Thermistor(Entrance) (Thi-R2) Thermistor (Thi-A) 23 - Strainer Electronic expansion valve Indoor unit Strainer Thermistor(Bend) (Thi-R1) Electronic expansion valve To next indoor units Liquid line For outdoor unit 2 Strainer Oil separator Check valve Service valve Electronic Strainer expansion valve (EEVSC) Receiver Strainer Accumlator Thermistor (Tho-S) Low pressure sensor(PSL) Check joint Strainer Sub-cooling coil (Tho-R4) (Thermistor,Entrance・Back) (Tho-R3) Sub-cooling coil (Thermistor,Entrance・Front) Thermistor (Tho-H) Electronic expansion valve Heat exchanger (EEVH1) (Tho-R1) (Thermistor,Exit・Front) Thi-R1, R2 : Heating operation : Indoor fan control. Cooling operation : Frost prevention control. Super heat control. Thi-R3 : For super heat control of cooling operation. Tho-D : For control of discharge pipe temperature. Tho-C : For control of temperature under the dome. Tho-S : For control of suction pipe temperature. Tho-R1, R2 : For control of defrosting. Tho-A : For control of defrosting. Tho-R3, R4 : Electronic expansion valve (EEVH1, 2) control of heating operation Tho-SC : Electronic expansion valve (EEVSC) control of cooling operation. Tho-H : For super heat control of sub-cooling coil. Strainer Sub-cooling coil Thermistor (Tho-SC) Capillary tube Sub-cooling coil Thermistor (Tho-D1) Muffler High pressure switch(63H1-1) CM1 Strainer 4way valve Check joint High pressure sensor(PSH) Compressor 1 Thermistor (Tho-C1) Service valve (Oil equalization line) Notes (1) Preset point of protective devices 63H1-1 : Open 4.15MPa, Close 3.15MPa (For protection) (2) Function of thermistor PSH : For compressor control 3.70 ON (MPa) PSL : ON 0.18MPa, OFF 0.20MPa (For compressor control) ON 0.134MPa, OFF 0.18MPa (For protection) Strainer Heat exchanger Strainer Indoor unit Solenoid valve(SV6) Capillary tube Heat exchanger Capillary tube Thermistor(Bend) (Thi-R1) Service valve Solenoid valve(20UF) Thermistor(Exit) (Thi-R3) Gas line Capillary tube Solenoid valve (SV1) Strainer Strainer Sub-cooling coil Thermistor (Tho-A) (Tho-R2) (Thermistor,Exit・Back) Heat exchanger Electronic expansion valve (EEVH2) Outdoor unit '14 • KX-DB-201 Models FDC400KXZE1, 450KXZE1 FDCS400KXZE1, 450KXZE1 PCB003Z823 - Thermistor(Entrance) (Thi-R2) Thermistor (Thi-A) Thermistor(Exit) (Thi-R3) Thermistor(Entrance) (Thi-R2) Thermistor (Thi-A) 24 - Strainer Electronic expansion valve Indoor unit Strainer Thermistor(Bend) (Thi-R1) Electronic expansion valve To next indoor units Liquid line For outdoor unit 2 Strainer Oil separator Service valve Strainer Oil separator Electronic Strainer expansion valve (EEVSC) Sub-cooling coil Thermistor (Tho-C2) Capillary tube Receiver Compressor 2 CM2 Thermistor (Tho-D2) Check valve High pressure switch(63H1-2) Strainer Solenoid valve (SV11) Strainer Accumlator Thermistor (Tho-S) Low pressure sensor(PSL) Check joint Strainer Sub-cooling coil (Tho-R4) (Thermistor,Entrance・Back) (Tho-R3) (Thermistor,Entrance・Front) Thi-R1, R2 : Heating operation : Indoor fan control. Cooling operation : Frost prevention control. Super heat control. Thi-R3 : For super heat control of cooling operation. Tho-D1, D2 : For control of discharge pipe temperature. Tho-C1, C2 : For control of temperature under the dome. Tho-S : For control of suction pipe temperature. Tho-R1, R2 : For control of defrosting. Tho-A : For control of defrosting. Tho-R3, R4 : Electronic expansion valve (EEVH1, 2) control of heating operation Tho-SC : Electronic expansion valve (EEVSC) control of cooling operation. Tho-H : For super heat control of sub-cooling coil. Strainer Sub-cooling coil Thermistor (Tho-SC) Service valve (Oil equalization line) Strainer Compressor 1 CM1 Muffler High pressure switch(63H1-1) Thermistor (Tho-D1) Check valve Thermistor (Tho-C1) Notes (1) Preset point of protective devices 63H1-1, 2 : Open 4.15MPa, Close 3.15MPa (For protection) (2) Function of thermistor PSH : For compressor control 3.70 ON (MPa) PSL : ON 0.18MPa, OFF 0.20MPa (For compressor control) ON 0.134MPa, OFF 0.18MPa (For protection) Strainer Heat exchanger Strainer Indoor unit Solenoid valve(SV6) Capillary tube Check joint High pressure sensor(PSH) Solenoid valve Capillary tube(SV7) Heat exchanger Capillary tube 4way valve Capillary tube Thermistor(Bend) (Thi-R1) Capillary tube Service valve Capillary tube Solenoid valve (SV1) Thermistor(Exit) (Thi-R3) Gas line Solenoid valve(SV2) Capillary tube (Tho-R1) (Thermistor,Exit・Front) Heat exchanger Sub-cooling coil Thermistor (Tho-H) Electronic expansion valve (EEVH1) Strainer Strainer Sub-cooling coil Thermistor (Tho-A) (Tho-R2) (Thermistor,Exit・Back) Heat exchanger Electronic expansion valve (EEVH2) Outdoor unit '14 • KX-DB-201 Models FDC475KXZE1, 500KXZE1, 560KXZE1 FDCS475KXZE1, 500KXZE1, 560KXZE1 PCB003Z824 '14 • KX-DB-201 5. SELECTION CHART (1) Equipment selection flow Calculate the load for each room separately, then determine the indoor load. Select an indoor unit that matches the indoor load (tentative). Calculate the temperature compensation, then calculate the indoor unit capacity. (See item () (a) for the calculation method.) Indoor unit capacity (tentative) Indoor Load Change the indoor unit. Select the outdoor unit (tentative). NO Calculate temperature compensation and piping compensation, etc., then calculate the outdoor unit capacity. (See item () (b) for the calculation method.) YES Calculate the total indoor unit capacity. Calculate the system capacity (See item () (c) for the calculation method.) NO Total indoor unit capacity System Capacity Change the outdoor unit. YES Calculate the indoor unit capacity. (See item () (d) for the calculation method.) Indoor unit capacity Indoor Load YES Equipment selection complete. - 25 - NO '14 • KX-DB-201 (2) Capacity calculation method (a) Calculating the indoor unit capacity compensation Indoor unit capacity (cooling, heating) = Indoor unit total rated capacity × Capacity compensation coefficient according to temperature conditions See item (3) (a) concerning the capacity compensation coefficient according to temperature conditions. (b) Calculating the outdoor unit capacity compensation Outdoor Unit Capacity (Cooling, Heating) = Outdoor unit rated capacity (rated capacity when 100% connected) × Capacity compensation coefficient according to temperature conditions × Capacity compensation coefficient according to piping length × Capacity compensation coefficient according to height difference × Correction of heating capacity in relation to the frost on the outdoor unit heat exchanger × Capacity compensation coefficient according to indoor unit connection capacity See item (3) (a) concerning the capacity compensation coefficient according to temperature conditions. See item (3) (b) concerning the capacity compensation coefficient according to piping length. See item (3) (c) concerning the capacity compensation coefficient according to height difference. This compensation should be carried out only in cases where the outdoor unit is lower during cooling and higher during heating. See item (3) (d) correction of heating capacity in relation to the frost on the outdoor unit heat exchanger. This compensation should be carried out only when calculating the heating capacity. See item (3) (e) concerning the capacity compensation coefficient according to indoor unit connected capacity. This compensation should be carried out only in cases where the indoor unit total capacity is 100% or higher. (c) Calculating system capacity Compare the capacities determined in items (a) and (b) above and let the smaller value be the system capacity (cooling, heating). In cases where indoor unit total capacity (cooling, heating) > outdoor unit capacity (cooling, heating) System capacity (cooling, heating) = Outdoor unit capacity (cooling, heating) In cases where indoor unit total capacity (cooling, heating) < outdoor unit capacity (cooling, heating) System capacity (cooling, heating) = Indoor unit capacity (cooling, heating) (d) Calculating indoor unit capacity [item (c) 1 only] Indoor unit capacity (cooling, heating) = System capacity (cooling, heating) × [(Indoor unit capacity) / (Indoor unit total capacity)] Capacity calculation examples Example 1 Cooling (when the indoor unit connected total capacity is less than 100%) • Outdoor unit FDC450KXZE1...................................................... 1 Unit • Indoor unit FDT56KXE6F........................................................... 7 Units • Piping length ............................................................................... 60 m (Equivalent length) • Indoor, outdoor unit height difference......................................... 15 m (Outdoor unit is lower) • Temperature conditions ............................................................... Outdoor temperature: 33˚C DB • Temperature conditions................................................................ Indoor temperature: 19˚C WB <Indoor unit total cooling capacity>: Item (2) (a) calculation. • Indoor unit rated cooling capacity: 5.6 kW • Capacity compensation coefficient according to temperature conditions: 1.02 (Calculated according to Indoor 19˚C WB / Outdoor 33˚C DB); (See page 28) . Indoor unit cooling capacity: 5.6 kW × 1.02 =. 5.7 kW • Indoor unit total cooling capacity calculation; indoor unit total cooling capacity: 5.7 kW × 7 units = 39.9 kW <Outdoor unit maximum cooling capacity> : Item (2) (b) calculation • Outdoor unit rated cooling capacity: 45.0 kW • Capacity compensation coefficient according to temperature conditions: 1.02 (Calculated according to Indoor 19˚C WB / Outdoor 33˚C DB); (See page 28) . Outdoor unit cooling capacity: 45.0 kW × 1.02 =. 45.9 kW • Capacity compensation coefficient according to piping length: 0.94 (calculated according to 60 m length); (See page 30) . 45.9 kW × 0.94 =. 43.1 kW - 26 - '14 • KX-DB-201 • Capacity compensation coefficient according to height difference: 0.97 (calculated according to 15 m difference); (See page 34) . 43.1 kW × 0.97 =. 41.8 kW • Capacity compensation coefficient according to indoor unit connected total capacity: 1.0 , (56 × 7) / 450 < 100%) No compensation <System cooling capacity>: Item (2) (c) calculation Compare the indoor unit total cooling capacity and the outdoor unit maximum cooling capacity. The smaller value is the actual system cooling capacity. • Indoor unit total cooling capacity: 39.9 kW e System cooling capacity: 39.9 kW • Outdoor unit maximum cooling capacity: 41.8 kW <Indoor unit capacity compensation> No compensation (5.7 kW) Example 2 Cooling (when the indoor unit connected total capacity is 100% or higher) • Outdoor unit FDC450KXZE1...................................................... 1 Unit • Indoor unit FDT56KXE6F........................................................... 10 Units • Piping length ............................................................................... 60 m (Equivalent length) • Indoor, outdoor unit height difference......................................... 15 m (Outdoor unit is higher) • Temperature conditions ............................................................... Outdoor temperature: 35˚C DB • Temperature conditions................................................................ Indoor temperature: 18˚C WB <Indoor unit total cooling capacity>: Item (2) (a) calculation. • Indoor unit rated cooling capacity: 5.6 kW • Capacity compensation coefficient according to temperature conditions: 0.95 (Calculated according to Indoor 18˚C WB / Outdoor 35˚C DB); (See page 28) . Indoor unit cooling capacity: 5.6 kW × 0.95 =. 5.3 kW • Indoor unit total cooling capacity calculation; indoor unit total cooling capacity: 5.3 kW × 10 units .=. 53.0 kW <Outdoor unit maximum cooling capacity> : Item (2) (b) calculation • Outdoor unit rated cooling capacity: 45.0 kW • Capacity compensation coefficient according to temperature conditions: 0.95 (Calculated according to Indoor 18˚C WB / Outdoor 35˚C DB); (See page 28) . Outdoor unit cooling capacity: 45.0 kW × 0.95 =. 42.8 kW • Capacity compensation coefficient according to piping length: 0.94 (calculated according to 60 m length); (See page 30) . 42.8 kW × 0.94 =. 40.2 kW • Capacity compensation coefficient according to height difference: 1.0 (the outdoor unit is higher during cooling) No compensation . • Capacity compensation coefficient according to indoor unit connected total capacity: 1.04 , (56 × 10) / 450 =. 124%) (See page 36) .. 40.2 kW × 1.04 = 41.8 kW <System cooling capacity>: Item (2) (c) calculation Compare the indoor unit total cooling capacity and the outdoor unit maximum cooling capacity. The smaller value is the actual system cooling capacity. • Indoor unit total cooling capacity : 53.0 kW e System cooling capacity: 41.8 kW • Outdoor unit maximum cooling capacity: 41.8 kW <Indoor unit cooling capacity Compensation>: Item (2) (d) calculation. 41.8 kW × 5.3 kW . =. 4.2 kW 53.0 kW Example 3 Heating (when the indoor unit connected total capacity is 100% or higher) • Outdoor unit FDC450KXZE1...................................................... 1 Unit • Indoor unit FDT56KXE6F........................................................... 10 Units • Piping length ............................................................................... 60 m (Equivalent length) • Indoor, outdoor unit height difference......................................... 20 m (Outdoor unit is higher) • Temperature conditions ............................................................... Outdoor temperature: 6˚C WB • Temperature conditions................................................................ Indoor temperature: 19˚C DB <Indoor unit total heating capacity>: Item (2) (a) calculation. • Indoor unit rated heating capacity:6.3 kW • Capacity compensation coefficient according to temprature conditions: 1.04 (Calculated according to Outdoor 6˚C WB / Indoor 19˚C DB); (See page 29) Indoor unit heating capacity: 6.3 kW × 1.04 .=. 6.6 kW • Indoor unit total heating capacity calculation; . indoor unit total heating capacity: 6.6 kW × 10 units =. 66.0 kW - 27 - '14 • KX-DB-201 <Outdoor unit maximum heating capacity> : Item (2) (b) calculation • Outdoor unit rated heating capacity: 50.0 kW • Capacity compensation coefficient according to temperature conditions: 1.04 (Calculated according to Outdoor 6˚C WB / Indoor 19˚C DB); (See page 29) Outdoor unit heating capacity: 50.0 kW x 1.04 = 52.0 kW • Capacity compensation coefficient according to piping length: 0.982 (calculated according to 60 m length); (See page 33) . 52.0 kW x 0.982 =. 51.0 kW • Capacity compensation coefficient according to height difference: 0.96 (calculated according to 20 m difference); (See page 34) . 51.0 kW x 0.96 =. 49.0 kW • Correction of heating capacity in relation to the frost on the outdoor unit heat exchanger: 1.0 (calculated according to 6˚C WB); (See page 34) . 49.0 kW x 1.0 =. 49.0 kW. . • Capacity compensation coefficient according to indoor unit connected total capacity: 1.0 ← (56 x 10) / 450 =. 124%) (See page 36) . 49.0 kW x 1.0 =. 49.0 kW. <System heating capacity> : Item (2) (c) calculation Compare the indoor unit total heating capacity and the outdoor unit maximum heating capacity. The smaller value is the actual system heating capacity. • Indoor unit total heating capacity : 66.0 kW ⇨ System heating capacity: 49.0 kW • Outdoor unit maximum heating capacity : 49.0 kW <Indoor unit heating capacity compensation> : Item (2) (d) calculation 49.0 kW x 6.6 kW . =. 4.9 kW 66.0 kW (3) Capacity compensation coefficient (a) Capacity compensation coefficient and power consumption compensation coefficient according to indoor and outdoor temperature conditions. 1) Capacity compensation coefficient 1.40 ◆ Cooling Indoor air W.B. temperature 24˚CWB 1.35 Indoor air W.B. temperature 26˚CWB Capacity compensation coefficient 1.30 1.25 Indoor air W.B. temperature 22˚CWB 1.20 Indoor air W.B. temperature 21˚CWB 1.15 1.10 Indoor air W.B. temperature 20˚CWB 1.05 Indoor air W.B. temperature 19˚CWB 1.00 0.95 Indoor air W.B. temperature 18˚CWB 0.90 Indoor air W.B. temperature 17˚CWB 0.85 0.80 Indoor air W.B. temperature 16˚CWB Indoor air W.B. temperature 15˚CWB 0.75 0.70 Indoor air W.B. temperature 14˚CWB 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Outdoor air D.B. temperature (˚CDB) 32 34 36 38 40 42 44 46 Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment. (2) When performing the cooling operation with the outdoor air temperature being -5°C or under, a windbreak fence must be installed. --140 28 - '14 • KX-DB-201 ◆ Heating 1.20 1.15 Outdoor air W.B. temperature 18˚CWB Capacity compensation coefficient 1.10 Outdoor air W.B. temperature 10˚CWB 1.05 Outdoor air W.B. temperature 14˚CWB 1.00 Outdoor air W.B. temperature 6˚CWB 0.95 Outdoor air W.B. temperature 2˚CWB 0.90 Outdoor air W.B. temperature -2˚CWB 0.85 Outdoor air W.B. temperature -6˚CWB 0.80 0.75 Outdoor air W.B. temperature -10˚CWB 0.70 0.65 Outdoor air W.B. temperature -15˚CWB 0.60 0.55 17 16 18 Outdoor air W.B. temperature -20˚CWB 19 20 21 22 23 24 Indoor air D.B. temperature(˚CDB) Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment. 2) Power consumption correction factor 1.30 ◆ Cooling Power consumption compensation coefficient 1.25 1.20 1.15 Indoor air W.B. temperature 26˚CWB 1.10 Indoor air W.B. temperature 24˚CWB 1.05 1.00 Indoor air W.B. temperature 22˚CWB 0.95 Indoor air W.B. temperature 21˚CWB 0.90 0.85 Indoor air W.B. temperature 20˚CWB 0.80 Indoor air W.B. temperature 19˚CWB 0.75 Indoor air W.B. temperature 18˚CWB 0.70 0.65 Indoor air W.B. temperature 17˚CWB 0.60 Indoor air W.B. temperature 16˚CWB 0.55 0.50 Indoor air W.B. temperature 15˚CWB 0 2 4 6 8 Indoor air W.B. temperature 14˚CWB 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 Outdoor air D.B. temperature(˚CDB) Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment. -141 29 -- '14 • KX-DB-201 1.25 ◆ Heating Power consumption compensation coefficient Outdoor air W.B. temperature 6˚CWB 1.20 Outdoor air W.B. temperature -2˚CWB Outdoor air W.B. temperature 2˚CWB Outdoor air W.B. temperature -6˚CWB 1.15 1.10 Outdoor air W.B. temperature 10˚CWB 1.05 1.00 0.95 Outdoor air W.B. temperature -15˚CWB 0.90 0.85 Outdoor air W.B. temperature -10˚CWB 0.80 Outdoor air W.B. temperature -20˚CWB Outdoor air W.B. temperature 14˚CWB 0.75 Outdoorair W.B. temperature 18˚CWB 0.70 16 17 18 19 20 21 22 23 24 Indoor air D.B. temperature(˚CDB) Note (1) The above-mentioned table shows a typical condition among conditions to occur via controlling an air-conditioning equipment. (b) Correction of cooling and heating capacity in relation to one way length of refrigerant piping. (Note) This table is for reference only. If the refrigerant piping one way equivalent after the first branch is extended longer than 40 m, it could drop further by about 10% in the worst case. 1) Cooling Model FDC(S)280KXZE1 Model FDC(S)335KXZE1 1.00 Gas pipe: ø25.4 0.95 Capacity compensation coefficient Capacity compensation coefficient 1.00 Gas pipe: ø22.22 0.90 0.85 0.80 0 20 40 60 0.95 Gas pipe: ø25.4 0.90 0.85 Gas pipe: ø22.22* 0.80 80 90100 120 140 160 180 Refrigerant piping one way equivalent length (m) Capacity compensation coefficient Capacity compensation coefficient 0.95 Gas pipe: ø25.4 0.85 20 40 60 80 100 60 80 100 120 140 160 180 Model FDC(S)450KXZE1 * 0 40 1.00 Gas pipe: ø28.58 0.80 20 Refrigerant piping one way equivalent length (m) Model FDC(S)400KXZE1 1.00 0.90 0 120 140 160 180 Refrigerant piping one way equivalent length (m) Note (1) Parts with the * mark show the piping size in case used in Europe. - 142 30 -- Gas pipe: ø31.8 0.95 Gas pipe: ø28.58 0.90 0.85 0.80 0 20 40 60 80 90 100 120 140 160 180 Refrigerant piping one way equivalent length (m) '14 • KX-DB-201 Model FDC(S)475KXZE1 1.00 Gas pipe: ø31.8 Capacity compensation coefficient Capacity compensation coefficient 1.00 Model FDC(S)500KXZE1 0.95 Gas pipe: ø28.58 0.90 0.85 0.80 0 20 40 60 0.95 Gas pipe: ø28.58 0.90 0.85 0.80 80 90100 120 140 160 180 Gas pipe: ø31.8 0 Model FDC(S)560KXZE1 1.00 Gas pipe: ø31.8 Capacity compensation coefficient Capacity compensation coefficient 1.00 0.95 Gas pipe: ø28.58 0.90 0.85 0.80 0 20 40 60 Gas pipe: ø31.8 Gas pipe: ø28.58 0.90 0.85 Capacity compensation coefficient Capacity compensation coefficient 1.00 Gas pipe: ø28.58 0.90 0.85 0.80 0 20 40 60 Capacity compensation coefficient Capacity compensation coefficient Gas pipe: ø34.92* 0.85 0.80 0 20 40 60 80 90 100 120 140 160 80 90100 120 140 160 180 Model FDC(S)735KXZE1 (FDC(S)335KXZE1 + FDC(S)400KXZE1) Gas pipe: ø31.8 0.90 Gas pipe: ø34.92* 0.85 1.00 Gas pipe: ø31.8 0.90 60 0 20 40 60 80 90100 120 140 160 180 Refrigerant piping one way equivalent length (m) Model FDC(S)800KXZE1 (FDC(S)400KXZE1 + FDC(S)400KXZE1) 0.95 40 0.95 0.80 80 90 100 120 140 160 180 Gas pipe: ø38.1 20 Gas pipe: ø38.1 Refrigerant piping one way equivalent length (m) 1.00 80 90100 120 140 160 180 Refrigerant piping one way equivalent length (m) Model FDC(S)670KXZE1 (FDC(S)335KXZE1 + FDC(S)335KXZE1) 0.95 60 Model FDC(S)615KXZE1 (FDC(S)280KXZE1 + FDC(S)335KXZE1) 0.80 0 80 90100 120 140 160 180 Gas pipe: ø31.8 40 0.95 Refrigerant piping one way equivalent length (m) 1.00 20 Refrigerant piping one way equivalent length (m) Refrigerant piping one way equivalent length (m) 180 Refrigerant piping one way equivalent length (m) Note (1) Parts with the * mark show the piping size in case used in Europe. - 143 31 -- Model FDC(S)850KXZE1 (FDC(S)400KXZE1 + FDC(S)450KXZE1) Gas pipe: ø38.1 0.95 Gas pipe: ø31.8 0.90 0.85 0.80 Gas pipe: ø34.92* 0 20 40 60 80 90 100 120 140 160 180 Refrigerant piping one way equivalent length (m) '14 • KX-DB-201 Model FDC900(S)KXZE1 (FDC450(S)KXZE1 + FDC(S)450KXZE1) Capacity compensation coefficient Gas pipe: ø38.1 0.95 0.90 Gas pipe: ø31.8 0.85 0.80 Gas pipe: ø34.92* 0 1.00 Capacity compensation coefficient 1.00 20 40 60 80 90 100 120 140 160 Gas pipe: ø38.1 0.85 1.00 80 90100 120 140 160 180 * Gas pipe: ø34.92 0.85 20 40 60 80 0.95 Gas pipe: ø38.1 0.90 * Gas pipe: ø34.92 0.85 0.80 100 120 140 160 180 0 Refrigerant piping one way equivalent length (m) Model FDC(S)1120KXZE1 (FDC(S)560KXZE1+FDC(S)560KXZE1) Gas pipe: ø38.1 0.90 * Gas pipe: ø34.92 0.85 0.80 0 20 40 60 80 Capacity compensation coefficient Model FDC(S)1250KXZE1 (FDC(S)400KXZE1+FDC(S)400KXZE1+FDC(S)450KXZE1) Gas pipe: ø38.1 * Gas pipe: ø34.92 0.85 0 20 40 60 80 80 100 120 140 160 180 Gas pipe: ø38.1 0.90 * Gas pipe: ø34.92 0.85 0 20 40 60 80 100 120 140 160 180 Refrigerant piping one way equivalent length (m) Refrigerant piping one way equivalent length (m) 0.90 60 0.95 0.80 100 120 140 160 180 0.95 40 Model FDC(S)1200KXZE1 (FDC(S)400KXZE1+FDC(S)400KXZE1+FDC(S)400KXZE1) 1.00 0.95 20 Refrigerant piping one way equivalent length (m) Capacity compensation coefficient Capacity compensation coefficient 60 Model FDC(S)1060KXZE1 (FDC(S)500KXZE1+FDC(S)560KXZE1) 0.80 0 Capacity compensation coefficient 40 Model FDC(S)1000KXZE1 (FDC(S)500KXZE1+FDC(S)500KXZE1) 0.90 0.80 20 Refrigerant piping one way equivalent length (m) Gas pipe: ø38.1 1.00 Gas pipe: ø31.8 0.90 Refrigerant piping one way equivalent length (m) 0.95 1.00 * Gas pipe: ø34.92 0.95 0.80 0 180 Capacity compensation coefficient Capacity compensation coefficient 1.00 Model FDC(S)950KXZE1 (FDC(S)475KXZE1-K+FDC(S)475KXZE1) 100 120 140 160 180 Refrigerant piping one way equivalent length (m) Note (1) Parts with the * mark show the piping size in case used in Europe. - 32 - 144 -- 1.00 Model FDC(S)1300KXZE1 (FDC(S)400KXZE1+FDC(S)450KXZE1+FDC(S)450KXZE1) 0.95 Gas pipe: ø38.1 0.90 * Gas pipe: ø34.92 0.85 0.80 0 20 40 60 80 100 120 140 160 180 Refrigerant piping one way equivalent length (m) '14 • KX-DB-201 Model FDC(S)1350KXZE1 (FDC(S)450KXZE1+FDC(S)450KXZE1+FDC(S)450KXZE1) 1.00 Capacity compensation coefficient Capacity compensation coefficient 1.00 0.95 Gas pipe: ø38.1 0.90 * Gas pipe: ø34.92 0.85 0.80 0 20 40 60 80 0.90 0.75 1.00 Capacity compensation coefficient Gas pipe: ø38.1 * Gas pipe: ø34.92 0.80 0.75 0.70 0 20 40 60 80 Capacity compensation coefficient Capacity compensation coefficient Gas pipe: ø38.1 * Gas pipe: ø34.92 0.75 0.75 * Gas pipe: ø34.92 0.75 0.70 Model FDC(S)1620KXZE1 (FDC(S)500KXZE1+FDC(S)560KXZE1+FDC(S)560KXZE1) 0.95 0.90 Gas pipe: ø38.1 0.85 * Gas pipe: ø34.92 0.80 0.75 0 20 40 60 80 100 120 140 160 180 2) Heating Model FDC(S)1680KXZE1 (FDC(S)560KXZE1+FDC(S)560KXZE1+FDC(S)560KXZE1) Gas pipe: ø38.1 0 20 40 60 80 100 120 140 160 180 Refrigerant piping one way equivalent length (m) Refrigerant piping one way equivalent length (m) 1.00 0.95 0.80 100 120 140 160 180 * Gas pipe: ø34.92 0.80 0.70 0 20 40 60 80 100 120 140 160 180 Refrigerant piping one way equivalent length (m) Capacity compensation coefficient Capacity compensation coefficient 0.95 0.85 80 Gas pipe: ø38.1 0.85 1.00 1.00 0.90 60 0.90 0.70 100 120 140 160 180 Model FDC(S)1560KXZE1 (FDC(S)500KXZE1+FDC(S)500KXZE1+FDC(S)560KXZE1) 1.00 40 0.95 Refrigerant piping one way equivalent length (m) 0.70 20 Model FDC(S)1500KXZE1 (FDC(S)500KXZE1+FDC(S)500KXZE1+FDC(S)500KXZE1) 0.85 0.80 0 Model FDC(S)1450KXZE1 (FDC(S)475KXZE1+FDC(S)475KXZE1+FDC(S)500KXZE1) 0.90 0.85 * Gas pipe: ø34.92 0.80 Refrigerant piping one way equivalent length (m) 0.95 0.90 Gas pipe: ø38.1 0.85 Refrigerant piping one way equivalent length (m) 1.00 Capacity compensation coefficient 0.95 0.70 100 120 140 160 180 Model FDC(S)1425KXZE1 (FDC(S)475KXZE1+FDC(S)475KXZE1+FDC(S)475KXZE1) 0 20 40 60 80 100 120 140 160 180 Refrigerant piping one way equivalent length (m) Note (1) Parts with the * mark show the piping size in case used in Europe. - 144 - 33-- 0.98 0.96 0.94 0.92 0.90 0 20 40 60 80 100 120 140 160 180 Refrigerant piping one way equivalent length (m) '14 • KX-DB-201 Note (1) Equivalent piping length can be obtained by calculating as follows. Equivalent piping length = Real gas piping length + Number of bends in gas piping × Equivalent piping length of bends. Unit : m/one part Equivalent length of each joint Gas piping size Joint (90˚ elbow) φ15.88 0.25 φ19.05 0.30 φ22.22 0.35 φ25.4 0.40 φ28.58 0.45 φ31.8 0.55 φ34.92 0.60 φ38.1 0.65 (c) When the outdoor unit is located at alower height than the indoor unit in cooling operation and when the outdoor unit is located at a higher height than the indoor unit in heating operation, the following values should be subtracted from the values in the above table. Height difference between the indoor unit and outdoor unit in the vertical height difference Adjustment coefficient Height difference between the indoor unit and outdoor unit in the vertical height difference Adjustment coefficient 5m 10 m 15 m 20 m 25 m 30 m 35 m 0.99 0.98 0.97 0.96 0.95 0.94 0.93 40 m 45 m 50 m 55 m 60 m 65 m 70 m 0.92 0.91 0.90 0.89 0.88 0.87 0.86 (d) Correction of heating capacity in relation to the frost on the outdoor unit heat exchanger Air inlet temperature of outdoor unit in ˚C WB Adjustment coefficient -20 -15 -13 -11 -9 -7 -5 -3 -1 1 3 5 or more 0.96 0.96 0.96 0.95 0.94 0.93 0.91 0.88 0.86 0.87 0.92 1 The correction factors will change drastically according to weather conditions. So necessary adjustment should be made empirically according to the weather data of the particular area. (e) The capacity compensation coefficient and power consumption compensation coefficient vary according to the total capacity of concurrently operating indoor units, as shown below. (Note) This table shows typical values. Model FDC(S)280KXZE1 ◆ Capability compensation coefficient Cooling 1.2 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient Capability compensation coefficient 1.0 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 - - 0.8 0.6 0.4 0.2 1.2 145 - 34 - 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) '14 • KX-DB-201 Model FDC(S)335KXZE1 ◆ Capability compensation coefficient Cooling 1.2 Capability compensation coefficient Capability compensation coefficient 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)400KXZE1 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 146 - - 35 - '14 • KX-DB-201 Model FDC(S)450KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)475KXZE1 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 147 - - 36 - '14 • KX-DB-201 Model FDC(S)500KXZE1 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)560KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) - 37 - 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) '14 • KX-DB-201 Model FDC(S)615KXZE1 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)670KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) - 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) 38 - '14 • KX-DB-201 Model FDC(S)735KXZE1 ◆ Capability compensation coefficient Cooling Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient 1.2 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)800KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) - 39 - 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) '14 • KX-DB-201 Model FDC(S)850KXZE1 ◆ Capability compensation coefficient Cooling 1.2 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient Capability compensation coefficient 1.0 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient 1.2 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)900KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 151 - - 40 - '14 • KX-DB-201 Model FDC(S)950KXZE1 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)1000KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 0.6 0.4 0.2 0 Power consumption compensation coefficient Power consumption compensation coefficient 0.8 0.6 0.4 0.2 0 0.8 1.2 1.0 0 1.0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) ◆ Power consumption compensation coefficient Cooling 1.2 20 40 60 80 100 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 152 - - 41 - '14 • KX-DB-201 Model FDC(S)1060KXZE1 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 1.0 0.8 0.6 0.4 0.2 0 0 0.8 0.6 0.4 0.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 20 40 60 80 100 Heating 1.0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 0 Total capacity of concurrently operating indoor units (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)1120KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 153 - - 42 - '14 • KX-DB-201 Model FDC(S)1200KXZE1 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 Heating 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)1250KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 153 - - 43 - '14 • KX-DB-201 Model FDC(S)1300KXZE1 ◆ Capability compensation coefficient Cooling 1.2 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 Power consumption compensation coefficient 0 0 1.0 0.8 0.6 0.4 0.2 0 0 0.8 0.6 0.4 0.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 20 40 60 80 100 Heating 1.0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient 1.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)1350KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 153 - - 44 - '14 • KX-DB-201 Model FDC(S)1425KXZE1 ◆ Capability compensation coefficient Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 0 Power consumption compensation coefficient 1.2 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 Heating 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient 1.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)1450KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 153 - - 45 - '14 • KX-DB-201 Model FDC(S)1500KXZE1 ◆ Capability compensation coefficient Cooling 1.2 Capability compensation coefficient 1.0 0.8 0.6 0.4 0.2 Power consumption compensation coefficient 0 0 ◆ Power consumption compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 Heating 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Capability compensation coefficient 1.2 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)1560KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 153 - - 46 - '14 • KX-DB-201 Model FDC(S)1620KXZE1 ◆ Capability compensation coefficient Cooling 1.2 Capability compensation coefficient Capability compensation coefficient 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient 1.2 1.0 0.8 0.6 0.4 0.2 0 0 20 40 60 80 100 1.2 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 Total capacity of concurrently operating indoor unit (%) 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Model FDC(S)1680KXZE1 1.2 Capability compensation coefficient Capability compensation coefficient ◆ Capability compensation coefficient Cooling 1.2 1.0 0.8 0.6 0.4 0.2 0 0 1.0 0.8 0.6 0.4 0.2 0 20 40 60 80 100 0.8 0.6 0.4 0.2 1.2 Power consumption compensation coefficient Power consumption compensation coefficient ◆ Power consumption compensation coefficient Cooling 1.2 0 1.0 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Total capacity of concurrently operating indoor unit (%) 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) Heating 1.0 0.8 0.6 0.4 0.2 0 120 Heating 0 20 40 60 80 100 120 Total capacity of concurrently operating indoor unit (%) - 154 - - 47 - '14 • KX-DB-201 6. ON REFRIGERANT LEAKAGE WARNINGS ON REFRIGERANT LEAKAGE 6.WARNINGS Check of concentration limit Important The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe,without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost nonexistent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration dose not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below. Note(2) The standards for minimum room volume are as follows. ① No partition (shaded portion) ② When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door,or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door). Outdoor unit Refrigerant piping Indoor unit ③ If an indoor unit is installed in each partitioned room and the refrigerant tubing is interconnected, the smallest of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object. Total amount of refrigerant (kg) Min. volume of the indoor unit installed room (m3) Refrigerant piping ≤ Concentration limit (kg/m3) Outdoor unit The concentration limit of R410A which is used in multi air conditioners is 0.42kg/m3. (ISO5149) Note(1) If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device. Small room Room C Room D Room E Min. indoor floor area (m2) 40 Room B Large room Note(3) The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high) e.g., Charged amount (15kg) Indoor unit Room A Medium room Mechanical ventilation device - Gas leak detector Outdoor unit e.g., Charged amount (10kg) Indoor unit Very small room Room F For the amount of charge in this example: The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg. 35 30 Range below the density limit of 0.42kg/m3 (countermeasures not needed) 25 20 15 Range above the density limit of 0.42kg/m3 (countermeasures needed) 10 5 0 10 20 30 Total amount of refrigerant (kg) - 48 - VRF INVERTER MULTI-SYSTEM AIR-CONDITIONERS Air-Conditioning & Refrigeration Division 16-5, Konan 2-chome, Minato-ku, Tokyo, 108-8215 Japan http://www.mhi.co.jp Because of our policy of continuous improvement, we reserve the right to make changes in all specifications without notice. c Copyright MITSUBISHI HEAVY INDUSTRIES, LTD.