5.8 Programmable Safety Systems ASISH GHOSH (2005) Partial List of Programmable Safety System Suppliers for Process Industries: ABB (Elsag-Bailey Controls) (www.ABB.com) G.E. Fanuc Automation (www.GEIndustrial.com) HIMA-Americas Inc. (www.hima-americas.com) Honeywell ACS Service (honey well.com/acs) ICS Triplex (www.icstriplex.com) Rockwell Automation (www.rockwellautomation.com) Siemens (www.sea.siemens.com) Yokogawa Corp. of America (www.yca.com) Triconex/Invensys (www.Triconex.com) Partial List of PLC Suppliers: ABB (Elsag-Bailey Controls) (www.ABB.com) Allen-Bradley/Rockwell Automation (www.AB.com) Automation Direct (www.Automationdirect.com) Danaher (Eagle Signal Controls) (www.Dancon.com) Eaton (Cutler-Hammer) (www.EatonElectrical.com) Emerson (Westinghouse) (www.EmersonProcess.com) Fuji Electric Corp. (www.FujiElectric.com) G.E. Fanuc Automation (www.GEIndustrial.com) Giddings & Lewis (www.GLControls.com) Idec Corp. (www.Idec.com) International Parallel Machines Inc. (www.ipmiplc.com) Mitsubishi Electric (www.meau.com) Modicon/Schneider Electric (www.Modicon.com) Moeller Corp. (www.Moeller.net) Omega Engineering (www.Omega.com) Omron Electronics Inc. (www.Omron.com) Reliance Electric Co./Rockwell Automation (www.Reliance.com) Siemens (www.sea.siemens.com) Toshiba Inc. (www.Toshiba.com) Triconex/Invensys (www.Triconex.com) Uticor Technology Inc. (www.Uticor.com) INTRODUCTION on orderly shutdown procedures in case of an emergency. The major trends in safety systems are 1 Since the publication of the IEC 61508 safety standard and more 2 recently the IEC 61511 standard for process safety, the interest in rigorous safety analysis and in certified safety instrumented systems (SISs) has increased considerably among the users. As users are becoming more knowledgeable about safety issues, they are increasingly focusing on the goal of overall safety. Users want their safety systems to be cost-effective and to provide closer integration of the safety and control systems. They are looking for flexible architecture with more scalability. They are also looking for increased functionality for modifying alarm limits based on process conditions and • • • • Increased focus on overall safety Closer integration with control systems Increased flexibility and scalability Increased function block capabilities Both IEC 61508 and 61511 standards are performancebased; as such, they do not mandate any specific safety system architecture or risk assessment procedures. However, they do provide guidance on the analysis of safety life cycle, hazards, and risks, and on methods for determining safety requirements. 993 © 2006 by Béla Lipták 994 PLCs and Other Logic Devices TABLE 5.8a Factors that Increase Risk • Operating plant and machinery closer to their limits • Transient operation states • Use of hazardous raw materials • Manufacture of hazardous intermediates • Presence of untrained personnel • Absence of safety culture Transient operations include startup, shutdown, shift change, and workforce transitions Safety system certifications should objectively assess the reliability and availability of critical control and safety shutdown systems and related equipment. Technical Inspection Associations (in German, Technischer Uberwachungs Verin, or TUVs) in Germany have been in the forefront of inspection and certification of safety-related systems worldwide. In choosing a safety system, users should take into account not only all the features of that system but also the specified restrictions, which are spelled out by the certification authority. This information is often found in the product safety manual. In choosing a system supplier, users should take into account the supplier’s knowledge and experience in safety analysis, their application knowledge, and local support. Risk Reduction Risk is usually defined as a combination of the severity and probability of an unplanned event. Risk depends on how often that event can happen and how bad it will be when it does. In manufacturing operations, the type of events and their associated Risk with safety protections risks include loss of life or limb, environmental impact, loss of capital equipment, and loss of production. For many manufacturers, loss of company image can also be a significant risk factor. With increased environmental awareness, regulatory concerns, and threat of litigation, risk reduction is becoming more and more important to most manufacturers (Table 5.8a). The best way to reduce risk in a manufacturing plant is to design inherently safe processes. However, inherent safety is rarely achievable in today’s manufacturing environments. Risks prevail wherever there are hazardous or toxic materials stored, processed, or handled (Figure 5.8b). Because it is impossible to eliminate all risks, a manufacturer must agree on a level of risk that is considered to be acceptable. After identifying the hazards, a study should therefore be performed to evaluate each risk situation by considering likelihood and severity. Site-specific conditions, such as population density, in-plant traffic patterns, and meteorological conditions, should also be taken into consideration during risk evaluation. The risk levels that are determined by the safety studies can be used to decide if the risks are within acceptable levels. Basic process control systems, including process alarms and the means of manual intervention, provide the first level of risk reduction in a manufacturing facility. Additional protection measures are needed where a basic control system does not reduce the risk to an acceptable level. They include safetyinstrumented systems along with hardware interlocks, relief valves, and containment dikes. To be effective, each protection subsystem should act independently of the others (Table 5.8c). History In the early days of process control, commonly used alarming and safety interlocking devices included pressure, flow, level, Risk with process control system Tolerable risk Risk without protective measures Increased risk Necessary minimum risk reduction Actual risk reduction Risk reduction achieved by all control and safety related systems and external risk reduction facilities FIG. 5.8b Reducing risk. © 2006 by Béla Lipták 5.8 Programmable Safety Systems TABLE 5.8c Driving Forces for Lowering Risks Input circuit 995 Output circuit Processor • Higher environmental awareness Diagnostic circuit • Increased regulatory considerations • Emergence of safety standards Input circuit • Maintaining company image and temperature switches. These switches were simple mechanical or electromechanical devices that, upon detection of hazardous conditions, activated valves, motors, and other plant equipment to bring a process to a safe state. Other mechanical devices, which are also still used today, include such physical devices as electrical fuses, safety valves, and rupture disks. While the electromechanical and solid-state relays could be used to design more sophisticated safety systems, they were difficult to program or to interface with digital computers. Hence, programmable safety systems were developed in the early 1970s. Programmable safety systems provide scalability, flexibility, and ease of configuration (Table 5.8d). Duplex and Triplex Designs In the late 1970s, August Systems pioneered the development of the programmable safety system, which was followed by systems from Triconex and Triplex. These three suppliers developed the triple modular redundant (TMR) systems, in which three independent, parallel TABLE 5.8d Typical Applications of Safety Systems • Emergency shutdown (ESD) • Fire and gas monitoring and protection • Critical process control • Turbine and compressor control • Unmanned installations Input leg A Input leg B Input leg C FIG. 5.8e Typical TMR system. © 2006 by Béla Lipták Diagnostic circuit FIG. 5.8f Typical duplex system. processors with extensive diagnostics are integrated into a single system (2oo3). At each decision point within the system, a twoout-of-three vote is taken to determine failures and guarantee correct operations. Other suppliers of TMR systems for process industries include GE Fanuc and Yokogawa (Figure 5.8e). A dual redundant system with extensive diagnostics (duplex) is another common safety system design. Here, two identical processors are configured as a married pair to check the health of the system (1oo2D). In this arrangement, two identical processors operate in parallel. They use the same inputs, while only one processor controls the output modules at any given time. The outputs of both processors are always compared to ensure that they are synchronized and identical. If they disagree, a diagnostic evaluation is initiated to determine which of the two is still reliable, and that the one used will continue the process in a safe state or shut it down. At the same time, messages are to fix the failed processor (Figure 5.8f). Major suppliers of duplex systems include ABB, Honeywell, Siemens, and Yokogawa. Quadruple Redundant Systems Another safety system design is the quadruple modular redundant (quad) system. The quad architecture provides four processors — two per channel (2oo4) — which may be viewed as a pair of duplex • Burner management and control Input Output circuit Processor Processor A Processor B Output leg A Output leg B Processor C Output leg C Voter Output 996 PLCs and Other Logic Devices IEC 61508: General Safety Standard 1oo2D The IEC 61508 standard is in seven parts: I/O bus 2 I/O bus 1 µP1 DPR Diagnostic DPR Diagnostic µP2 CM 1 µP1 1oo2 1oo2 µP2 CM 2 2oo4 1oo2D Actuator Actuator FIG. 5.8g Typical quad system. • • • • • • • Part 1: General requirements Part 2: Requirements for safety-related systems Part 3: Software requirements Part 4: Definitions and abbreviations Part 5: Examples of methods for the determination of safety integrity levels (SILs) Part 6: Guidelines on the applications Part 7: Overview of techniques and measures The standard is generic and can be used directly by industry, as a standalone standard, and by international standards organizations as a basis for the development of industryspecific standards, such as for the machinery sector, the process sector, or the nuclear sector. The IEC 61511 standard is more specific to the process industries. IEC 61511: Safety Standard for Process Industries systems with diagnostics. Both pairs of active processors operate synchronously with the same user program. A hardware comparator and a separate fail-safe watchdog monitor the operation of each pair of processors to diagnose and resolve anomalies (Figure 5.8g). At present HIMA and Honeywell are the two major suppliers of quad systems. The safety and availability of quad, TMR, and duplex systems are comparable. It is the quality of diagnostics and the system implementation that determines their relative performance. In recent years, the increased awareness of safety, the impact of various regulatory agencies, and the publication of safety standards have led to the rapid growth in demand for safety systems. Many DCS- and PLC-based control system suppliers are competing for a share of this market. SAFETY STANDARDS The IEC 61508 safety standard published by the International Electrotechnical Commission (IEC) is applicable to a wide range of industries and applications. The standard is intended both as the basis for the preparation of more specific standards and for standalone use. A more specific international safety standard for process industries (IEC 61511) has also been published. Since the publication of IEC 61508 and IEC 61511 standards, interest in rigorous safety analysis and in applying certified safety instrumented systems has increased. These standards give guidance on good practice and offer recommendations, but do not absolve its users of responsibility for safety. The standards not only deal with technical issues but also include planning, documentation, and assessment of all activities. Thus, the standards deal with the management of safety throughout the entire life of a system. © 2006 by Béla Lipták While IEC 61508 has seven parts, the IEC 61511 standard has only three parts: • • • Part 1: Framework, definitions, system, hardware, and software requirements Part 2: Guidelines on the application Part 3: Guidance for the determination of the required safety integrity levels IEC 61511 Part 1 is primarily normative, while Parts 2 and 3 are informative. Part 1 is structured to adhere to a safety life cycle model similar to that in the IEC 61508 standard. The hazard and risk analysis utilizes the notion of protection layers and specifies the safety integrity level concept developed by the IEC 61508 standard. It also lists key issues that need to be addressed when developing a safety requirement specification. Issues like separation, common cause, response to fault detection, hardware reliability, and proven-in-use are also addressed in this part (Table 5.8h). In this part of the standard, software safety requirement specifications are included, addressing such items as TABLE 5.8h Main Differences Between IEC 61508 and IEC 61511 Standards IEC 61508 IEC 61511 Generic safety standard for broad range of applications Sector-specific safety standard for the process industries Applies to all safety-related systems and external risk reduction facilities Applies only to safety-instrumented systems Primarily for manufacturers and suppliers of safety systems and devices Primarily for system designers, integrators, and users of safety systems 5.8 Programmable Safety Systems architecture, relationship to hardware, safety instrument functions, safety integrity level, software validation planning, support tools, testing, integration, and modification. In addition, a section is dedicated to factory acceptance testing requirements, and another section lists the installation and commissioning requirements. Part 2 of the standard provides “how to” guidance on the specification, design, installation, operation, and maintenance of safety instrumented functions and related safety instrumented system as defined in Part 1 of the standard. Part 3 of the standard provides guidance for development of process hazard and risk analysis. It provides information on: • • • The underlying concepts of risk and the relationship of risk to safety integrity The determination of tolerable risk A number of different methods that enable the safety integrity levels for the safety instrumented functions to be determined It also illustrates methods from different countries that have been proven-in-use. It further illustrates good engineering practices across cultural and technological differences, providing the end user with effective methods from which to select. ANSI/ISA-84.01 Standard The original ANSI/ISA-84.01 standard was published in 1966; as such, it predates the IEC 61508 safety standard. However, it is being abandoned in favor of the IEC 61511 international standard. A new ISA standard was released in 2004, which was nearly identical to the IEC 61511 safety standard. There is, however, a grandfather clause in the new version that allows the continued use of safety systems following the original version of the standard. The safety standards give guidance on good practice and offer recommendations, but do not absolve its users of responsibility for safety. The standard recognizes that safety cannot be based on retrospective proof, but must be demonstrated in advance, and there cannot be a perfectly safe system. Therefore, the standards not only deal with technical issues, but also include planning, documentation, and assessment of all activities. Thus, the standard deals with the management of safety throughout the entire life of a system. The standards bring safety management to system management and safety engineering to software engineering. Safety Integrity Levels Safety integrity is defined as the likelihood of a safety instrumented system satisfactorily performing the required safety functions under all stated conditions, within a stated period. A safety integrity level (SIL) is defined as a discrete level for specifying the safety integrity requirements of safety functions. Whereas a safety integrity level is derived from an assessment of risk, it is not a measure of risk. It is a © 2006 by Béla Lipták 997 TABLE 5.8i Safety Integrity Levels (SIL) Safety Integrity Level (SIL) Probability of Failure on Demand Mode of Operation 1 ≥10 to <10 2 >10 to <10 −2 −1 −3 −2 −4 −3 −5 −4 3 >10 to <10 4 ≥10 to <10 Probability of Failure on Continuous Mode of Operation −6 −5 −7 −6 −8 −7 −9 −8 ≥10 to <10 >10 to <10 >10 to <10 ≥10 to <10 Notes: 1. Demand Mode: Where actions are taken in response to process or other conditions (no more than once per year) 2. Continuous Mode: Functions, which implement continuous control to maintain functional safety measure of the intended reliability of a system or function (Table 5.8i). Safety Life Cycle Safety life cycle is a method or procedure that provides the way to specify, design, implement, and maintain safety systems in order to achieve overall safety in a documented and verified way. All major safety standards, such as ANSI/ISA-84-01-1996, IEC 61508, and IEC 61511, have specified safety life cycles, which show considerable similarities, differing only in the details. The safety life cycle specified by the IEC 61511 standard shows a systematic approach to safety starting from hazard and risk analysis to implementation of safety system and finally to its decommissioning (Figure 5.8j). Perform Hazard and Risk Analysis: Determine hazards and hazardous events, the sequence of events leading to hazardous condition, the associated process risks, the requirements of risk reduction, and the safety functions required. Allocate Safety Functions to Protection Layers: Allocate safety functions to protection layers and safety systems. Specify Requirements for Safety System: Specify the requirements for each safety system and their safety integrity levels. Design and Engineer Safety System: Design system to meet the safety requirements. Design and Develop Other Means of Risk Reduction: Means of protection other than programmable safety systems include mechanical systems, process control systems, and manual systems. They are not specified in any detail in the standard (Figure 5.8k). Install, Commission, and Validate the Safety Protections: Install and validate that the safety system meets all the safety requirements of the safety integrity levels. Operate and Maintain: Ensure that the safety system functions are maintained during operation and maintenance. Modify and Update: Make corrections, enhancements, and adaptations to the safety system to ensure that the safety requirements are maintained. PLCs and Other Logic Devices Perform hazard and risk analysis Allocate safety functions to protection layers Specify requirements for safety system Design and engineer safety system Design and develop other means of risk reduction Install comission and validate the safety protections Verify safety system Plan and structure safety life cycle Manage functional safety, safety assessment, and safety audit 998 Operate and maintain Modify and update Perform decommissioning of safety system FIG. 5.8j The safety life cycle. Perform Decommissioning of Safety System: Conduct review and obtain required authorization before decommissioning of a safety system. Ensure that the required safety functions remain operational during decommissioning. Manage Functional Safety, Safety Assessment, and Safety Audit: Identify the management activities that are required to ensure the functional safety objectives are met. Plan and Structure Safety Life Cycle: Define safety life cycle in terms of inputs, outputs, and verification activities. Verify Safety System: Demonstrate by review, analysis, or testing that the required outputs satisfy the defined requirements for each phase of the safety life cycle. Like all models, the safety life cycle is also an approximation. While the life cycle phases are listed sequentially, in reality, there are significant iterations between these phases. Requirements of some of the functions, such as hazard and risk analysis, allocation of safety functions to protection layers, and designing and developing other means of risk Community Emergency Response Emergency broadcasting Medical alert Plant Emergency Response Evacuation procedures Mitigation Mechanical mitigation system Safety system for mitigation Prevention Mechanical protection system Safety system Control and Monitoring Basic process control system Monitoring system Operator supervision Process FIG. 5.8k The protection layers. © 2006 by Béla Lipták 5.8 Programmable Safety Systems reduction, are not specified in any detail in the standard. Certain functions, such as managing functional safety, planning and structuring safety life cycle, and verifying safety requirements at each phase, are carried out continuously during the whole life cycle and are shown as vertical boxes in the figure. MANAGEMENT CONSIDERATIONS The standards should be recognized as defining requirements for safety management rather than merely for system development. Not all safety life cycle phases will be relevant to every application, and it is the responsibility of management to define what requirements are applicable in each case. The standards do not prescribe exactly what should be done in any particular case, but only offer advice and guidance to the management. Therefore, management is still responsible for taking appropriate actions and for justifying them. Management responsibilities include rigorous safety planning, which includes the choice of safety life cycle phases to be used and the activities to be carried out within those phases. However, the users should realize that safety systems by themselves do not achieve safety. People working within a strong safety culture achieve greater safety, and it is management’s responsibility to foster and maintain such a culture (Table 5.8l). HAZARD AND RISK ANALYSIS The standard requires that safety requirements should be determined by analyzing the risks posed by the totality of a manufacturing system and its control system. The analysis consists of three stages: hazard identification, hazard analysis, and risk assessment. A hazard is defined as a potential source of harm. A manufacturing system and its control system may pose many hazards, each carrying its own risk. In determining the necessary overall risk reduction, the risk posed by each hazard must be considered. The importance of hazard identification cannot be overemphasized, because the risks associated with unidentified hazards cannot be reduced. Hazard identification is unlikely to be effective if carried out by an individual; therefore, it is preferable to have a team whose members are chosen to bring complementary viewpoints to the process. A well-managed team with defined objectives is more effective in performing hazard analysis than a single individual. TABLE 5.8l Management Responsibilities • Put organization structure with necessary authority • Define applicable requirements • Provide documentation infrastructure • Foster safety culture © 2006 by Béla Lipták 999 IEC 61508 and 61511 are performance-based standards; as such, they do not mandate any specific safety system architecture or risk assessment procedures. However, they provide guidance in the areas of risk assessment and risk reduction. Following are some of the risk assessment and SIL determination concepts as outlined in the IEC 61511 standard Part 3. Detailed descriptions of these techniques are beyond the scope of this section. Readers are advised to refer to the IEC 61511 standard or the textbooks listed in the References section. As Low as Reasonably Practicable (ALARP) The ALARP principle may be applied during the determination of tolerable risk and safety integrity levels. However, it is not in itself a method for determining safety integrity levels. Tolerable risk implies that it is not possible to achieve absolute safety. A level of risk may be considered tolerable, in the light of the benefit gained in taking the risk, provided it is as low as reasonably practicable. The ALARP triangle is divided into three regions with the width at any point indicating the magnitude of the risk (Figure 5.8m). Risk class I represent risks that cannot be justified except in extraordinary circumstances. Risk class III represents risk that is so low as to be negligible and is thus acceptable without any further risk avoidance measures. Risk class II in the middle represents risk that can only be tolerated if measures have been taken to reduce it to as low as reasonably practicable. This means that the cost of mitigating the risk is disproportionate to the benefits gained. The concept of ALARP can be used when qualitative or quantitative risk targets are adopted. In order to apply the ALARP principle, it is necessary to define the three regions in terms of the probability and consequence of an incident. This definition would take place by discussion and agreement between the interested parties, such as those producing the risks, those exposed to the risks, and safety regulatory authorities. Table 5.8n is an example of the three risk classes for a number of consequences and frequencies. After determining the tolerable risk target, it is then possible to determine the safety integrity levels of safety-instrumented functions. Required Safety Integrity Level The IEC 61511 standard Part 3 specifies a number of ways of establishing the required safety integrity levels for a specific application. The methods selected for a specific application depends on many factors, such as: • • • • • Application complexity Guidelines from regulatory authorities Nature of the risk and the risk reduction requirements Experience and skills of the persons available to undertake the work Information available on the parameters relevant to the risk 1000 PLCs and Other Logic Devices Unacceptable region Risk class I Tolerable region Risk class II Broadly acceptable region Risk class III Risk class I: Risk cannot be justified except in extraordinary circumstances Risk class II: Risk is tolerable only if: —Further risk reduction is impracticable or its cost is grossly disproportionate to the improvements gained —Society desires the benefit of the activity given the associated risk Risk class III: Level of residual risk regarded as negligible and further measures to reduce not usually required Note: There is no relationship between risk class and SIL FIG. 5.8m Tolerable risk and ALARP. More than one method may be used in an application. A qualitative method may be used first, followed by a more rigorous quantitative method, if needed. Qualitative methods outlined in the standard include: • • • • • • Failure mode and effects analysis Cause-consequence analysis Hazard and operability analysis is one of the more widely used techniques. It identifies and evaluates hazards in process plants and nonhazardous operability problems that compromise its ability to achieve design productivity. Table 5.8o is an example of the results of a HAZOP analysis. Safety reviews Checklists What if analysis Hazard and operability (HAZOP) TABLE 5.8n Example of Risk Classification of Incidents Probability Catastrophic Critical Marginal Negligible Frequent I Probable I I I II I II II Occasional Remote I II II II II II II III Improbable Incredible II III III III II III III III The probability of occurrence are defined as: Frequent: Many times in the system’s lifetime Probable: Several times in the system’s lifetime Occasional: Once in the system’s lifetime Remote: Unlikely during the system’s lifetime Improbable: Very unlikely Incredible: Absolutely improbable © 2006 by Béla Lipták The consequences are defined as: Catastrophic: Multiple loss of life Critical: Loss of a single life Marginal: Major injuries to one or more person Negligible: Minor injuries Note: The risk classes are application dependent 5.8 Programmable Safety Systems 1001 TABLE 5.8o Example of a HAZOP Report Item Reactor Deviation Cause Consequence Safeguards Recommendations High level Failure of control system High pressure Operator High pressure • High level • External fire Release to environment – Alarm, protection layer – Fire deluge system Evaluate conditions for release to environment Low flow Failure of control system Excess pressure Operator Open pressure release valve manually Semi-Quantitative Risk Analysis Techniques SAFETY SYSTEM CERTIFICATION An estimate of the process risk can be made by a semiquantitative risk analysis procedure that identifies and quantifies the risks associated with potential process accidents or hazardous events. The results can be used to identify necessary safety functions and their associated SIL in order to reduce the process risk to an accepted level. Following are the main steps of this technique, where the first four steps can be performed during the HAZOP study: Safety system certifications objectively assess the reliability and availability of critical control and safety shutdown systems and related products. Following are some of its advantages: • • • • • • • Identify process hazards Identify safety layer composition Identify initiating events Develop hazardous event scenarios for every initiating event Ascertain the frequency of occurrence of the initiating events and the reliability of existing safety systems Quantify the frequency of occurrence of significant hazardous events Integrate the results for risks associated with each hazardous event The above exercise leads to a better understanding of hazards and risks associated with a process and leads to the identification of safety functions needed to reduce risks to acceptable levels. Risk Graphs The use of a risk graph is a method for evaluating safety integrity levels, which is illustrated in Figure 5.8p. This method focuses on the evaluation of risk from the point of view of a person being exposed to the incident impact zone. In a risk graph there are four parameters to characterize a potential hazardous event: consequence, frequency of exposure, possibility of escape, and likelihood of events. In assessing the consequence severity, the following are considered: • • • Potential for injury or fatality Possibility of the exposed person recovering and returning to normal activities The effects of injury: acute or chronic The resulting safety integrity levels are shown in vertical columns. © 2006 by Béla Lipták • • • • • Allows making informed decisions when choosing a product for a specific application Allows products and systems certified against standards Allows installing certified products and achieves recognized levels of process safety Gives the manufacturers of safety systems the opportunity to improve their products Gives suppliers of safety systems competitive advantage through documented product quality and reliability Safety regulations came after the start of industrialization when steam engines and boiler explosions caused many deaths. For over 127 years, TUVs have been in the forefront of inspection and certification of safety related systems in Germany. The TUV certification process is very exhaustive and covers everything from the formulation and documentation of the original design concepts to the manufactured product and its suitability for a defined application. TUV is not a single entity, but consists of a number of independent regional organizations. Among them, TUV Rheinland, TUV Product Services (a part of TUV Suddeutschland), and TUVIT (part of RWTUV) are most active in certifying safety-related systems. A research project started in the early 1980s by the TUVs on computer-based safety systems resulted in a document that led to the German safety standard DIN/VDE 0801. Until recently, the TUVs certified systems were based on the DIN standard (AK Class 1 to 7). They are now certifying systems based on IEC 61508 standards. Every supplier that pursues this market has systems certified by one of the TUVs. This condition has been viewed favorably by both users and suppliers of safety systems, where users wanted reassurance of having a system certified by a qualified agency, and suppliers were willing to pay the necessary fees in order to differentiate themselves from competitors. It should be emphasized, however, that some of the certified equipment has extensive restrictions. These restrictions effectively represent requirements not met by the manufacturer. When this happens, the user must compensate by adding externally wired equipment or user-programmed logic. 1002 PLCs and Other Logic Devices W3 W2 W1 a a a P1 1 a a P2 1 1 a P1 2 1 1 P2 3 2 1 3 3 2 4 3 3 b b b C1 F1 C2 Potential hazardous event F2 C3 F1 F2 C4 a = No special safety requirement b = A single safety system is not sufficient 1, 2, 3, 4 = Safety integrity level Consequence of event: C1 = Minor injury C2 = Serious permanent injury to one or more persons, death to one person C3 = Death of several people C4 = Very many people killed Frequency of exposure: F1 = Rare to more often exposure in the hazardous zone F2 = Frequent to permanent exposure Possibility of escape: P1 = Possible under certain conditions P2 = Almost impossible Probability of occurrence: W1 = Slight probability (less than 0.3 pa) W2 = Medium probability (greater than 0.3 pa but below 3 pa) W3 = High probability (3 pa or above) FIG. 5.8p Example of a risk graph. This extra work and extra expense should be estimated before selecting the equipment. Other organizations involved in safety system certification include INERIS, Factory Mutual, UL, BASEEFA, and many other national organizations. INERIS is a French research organization with close links with French Ministries of the Environment and Industry. It has been involved in safety system certification since its inception in 1992. INERIS has little presence outside France, and its clients are predominantly French manufacturers. Factory Mutual, whose headquarters are in Norwood, MA, has a long history in product testing and approval. The company services its clients through offices around the globe and interlaboratory agreements with testing facilities in North America, Europe, Asia, Australia, and Latin America. In late 1997, Factory Mutual and TUV Product Services signed a collaborative agreement enabling safety system © 2006 by Béla Lipták manufacturers to obtain global certification of their products at either laboratory. The two labs are also working together to develop common interpretation and certification procedures for the IEC 61508 standard. As the two organizations have name recognition in the different regions of the world, safety certification from either organization will be more widely accepted than before. The two organizations will be able to work in parallel, when required, to reduce the time required for the certification process and time to market. Users with manufacturing facilities around the world will be able to install safety systems in more countries without recertification. It is essential that users consider only those systems that have been certified by a TUV or a similar organization for safety applications. To get full details of specific restrictions a user should demand a copy of the safety certification report and safety manual from its prospective supplier. 5.8 Programmable Safety Systems MAJOR TRENDS As users are getting more knowledgeable about safety issues, they are performing more thorough safety analysis to determine their needs for each application more accurately. They are looking for reduction of risks by increasing their focus on overall safety. They would like their safety systems to satisfy their needs in a more cost-effective way by closer integration of safety with control systems. They are looking for a flexible architecture and with more scalability; increased functionality for modifying alarm limits based on process conditions; and orderly shutdown procedures in case of emergency. Overall Safety The main cause of an SIS failure is not the failure of logic, but the failure of field devices. There has been a significant advance in the development of the architecture of logic solvers with voting circuits and advanced diagnostics. However, they do not address over 90% of the causes for failure, which are due to the failure of field devices. What is needed is an integrated safety approach, where field devices are well integrated with the programmable safety systems. Today, a protective system should be able to check the health of the process inputs and outputs (I/O). In fact, it needs to incorporate the I/O components in its overall design. They include: • • • Sensor validation Environment condition monitoring, such as temperature and humidity that can cause sensor degradation Impulse line blockage monitoring Failures of electronic components are frequently due to environmental conditions. Many electronic device failures are due to elevated humidity and temperature, which need to be monitored closely. Sensor calibration is also becoming an integral part of a safety system. Use of protocols, such as HART, Profibus, and Foundation Fieldbus, allows for remote monitoring, diagnostics, and validation. Intelligent valves and digital valve positioners can also contribute to improved safety. With valves, the most frequent safety problems is when the valve does not respond to the trip demand, which is often caused by stem seizure or packing failure. The newer control valve designs, such as TUV certified valves, have reduced the probability of these and are available on the marketplace. The SIS-based valve design includes the feature of testing for limited valve movement during normal operation. Separation from the Control System It has long been the practice of many users to keep controllers used for safety completely independent of those used for control and optimization. In the past, controllers used for safety came from specialized manufacturers that added extensive diagnostics and received TUV safety certification. There © 2006 by Béla Lipták 1003 was no choice but to use completely different systems for control and safety. Some users even mandated the purchase of control and safety systems from different manufacturers. There are many other reasons to place the safety and control functions in different control systems. They include • • • Independent failures: Minimizing the risk of simultaneous failure of a control system along with the SIS Security: Changes in a control system not causing any change or corruption in the associated SIS Special requirements for safety controllers: Special features, like diagnostics, certified fail-safe response, special software error checking, protected data storage, and fault tolerance The IEC 61508 safety standard is somewhat ambiguous on this issue; it generally recommends separation but does not mandate it. In contrast, the IEC 61513 standard for the nuclear industries mandates physical separation of control and safety functions. Today, a number of users in process industries are finding logical reasons for using the same systems for control and safety functions, because that will reduce the integration problems caused by the different programming procedures, languages, installation requirements, and maintenance. There is always the risk caused by communication problems resulting from integration of different software languages and procedures. It is preferred by the users to have the same service and support requirements for both the control and safety functions. Control system and SIS suppliers now offer similar systems for both functions, including their HMI, configuration procedures, programming languages, and maintenance procedures. The systems may be physically separate but are similar and are provided with a common operator interface. They may communicate with each other, but are provided with adequate protection from corruption of one by the other (Table 5.8q). Flexibility and Scalability The installed base of systems for critical control or safety shutdown is largely either TMR (2oo3) or duplex (1oo2D) systems. However, other architectures, such as quad (2oo4D), hybrid 2oo4/1oo2, and other combinations, are also available. Increasingly, suppliers are offering configuration flexibility, where the user has the choice of combining two or more safety controllers to reduce failure rate and increase availability. TABLE 5.8q Advantages of Closer Integration with Control Systems • Common data mapping • Increased security • Similar engineering tools • Significant reduction in integration efforts 1004 PLCs and Other Logic Devices Safety controllers are also becoming more scalable. They are getting smaller, where one controller handles a limited number of I/O, but a number of these controllers working together can handle a much larger application. This is a saving for the users, as they no longer have to purchase large and expensive systems for their smaller applications. TABLE 5.8s Supplier Selection Criteria • Knowledge & Experience in HAZOP Analysis • Knowledge of Regulatory Requirements • Industry Application Expertise • Local Support Function Blocks A state-of-the-art safety system provides facilities for simple sequencing (usually without looping) to allow orderly shutdown of a process on detection of a failure condition. Although orderly shutdown in case of some alarm conditions is often controlled by the basic control system, also incorporating it in the safety system reduces the risks. Rich function blocks make it easier to configure functions, such as trip levels, deviation percentage, pretrip alarm, and degradation behavior. They make it easier to bypass specified alarms during start-up. Traditionally, cause-andeffect matrices (CEMs) are implemented in ladder logic. Rich functions blocks make their applications easier and support more intuitive presentations at run time. SAFETY SYSTEM SELECTION Before embarking on the selection procedure, a user should do a study to determine the safety protection requirements for the application. The requirements should conform to safety standards and meet the guidelines of regulatory agencies such as OSHA and EPA. Outside help from a third-party consultant or an established safety system supplier is strongly recommended if the necessary experience in safety study and risk reduction procedures does not exist in-house. Conventional control systems provide the first line of defense against hazardous conditions. Incorporating alarming and effective shutdown procedures in the basic control systems can considerably reduce the risks. Further reduction or elimination of a number of risks is possible by adding protection measures such as hardware interlocks, relief valves, and improved operator access for manual intervention. In many situations, containment systems such as dikes and firewalls can considerably reduce the effects of an accident. Programmable safety systems are needed if these actions do not reduce the risks to an acceptable level. Once the need for a programmable safety system is established, the user should also take into account the requirements of the certifying organization. These requirements specify the TABLE 5.8r System Selection Criteria • TUV Certification and Restrictions • Required Speed of Response • Product Maturity and Installed Base • Ease of Integration to Your Control System © 2006 by Béla Lipták allowable operating conditions and requirements for redundant I/O and for initiating shutdowns in case of a processor failure. Speed of response can also be an important consideration for some applications, and it must be considered along with the response time of all the field instruments (Table 5.8r). In making a safety system evaluation, the user should take into account its installed base and product maturity. The ease of integration of the safety system with the control system is also an important consideration. Providing the same interface and the same configuration software for the two systems is also recommended, because it will help reduce the learning efforts of engineers and operators. The control system should be able to monitor the status of the safety system and to monitor real-time data in order for the two systems to work in a unified fashion. When selecting suppliers, their knowledge and experience in safety analysis and regulatory requirements should be considered, including experience in applying safety systems to similar applications. Finally, one should also consider the availability of local support and of spare parts (Table 5.8s). ACKNOWLEDGMENTS The help and suggestions made by Dr. William M. Goble of Exida are acknowledged. ACRONYMS ALARP ANSI CEM DCS DIN EPA HAZOP IEC I/O ISA OSHA SIL SIS TMR TUV As Low As Reasonably Practicable American National Standards Institute Cause-and-Effect Matrix Distributed Control System Deutsches Institut Normung (German Standards Institute) Environmental Protection Agency Hazard and Operability International Electrotechnical Commission Input/output Instrumentation, Systems, and Automation Society Occupational Safety and Health Administration Safety Integrity Level Safety Instrumented System Triple Modular Redundant Technischer Uberwachungs Verin (Technical Inspection Association) 5.8 Programmable Safety Systems 1005 References Bibliography 1. ARC Report, Critical Control and Safety Shutdown System Strategies, Dedham, MA: ARC Advisory Group, 1999. Goble, W. M., Control System Safety Evaluation and Reliability, Research Triangle Park, NC: ISA, 1998. Gruhn, P. and Cheddie, H. L., Safety Shutdown Systems: Design, Analysis, and Justification, Research Triangle Park, NC: ISA, 1998. Marzal, E. M. and Schrapf, E. W., Safety Integrity Level Selection, Research Triangle Park, NC: ISA, 2002. 2. 3. IEC 61508 Parts 1 to 7, “International Standard, Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems,” Geneva, Switzerland: International Electrotechnical Commission, 2000. IEC 61511 Parts 1, 2, and 3, “International Standard, Functional Safety: Safety Instrumented Systems for the Process Industry Sector,” Geneva, Switzerland: International Electrotechnical Commission, 2003. ANSI/ISA-84.00.01—2004, “Standard, Functional Safety: Safety Instrumented System for the Process Industry Sector,” Research Triangle Park, NC: ISA, 2003. © 2006 by Béla Lipták