EFCOG Best Practice #178 Best Practice Title: Adoption of NFPA 70 2014 in place of NFPA 70 2011 Facility: DOE Complex Point of Contact: Andrew Drutel, PE, Savannah River Site, 803-952-9380, andrew.drutel@srs.gov (Primary contact) Michael Hicks NE-Idaho, 208-526-3724, hicksmd@id.doe.gov John McAlhaney, PE, Savannah River Site, 803-557-9002, jackie.mcalhaney@srs.gov Brief Description of Best Practice: NFPA 70 2014 is recommended for approval across the DOE Complex as an upgrade to NFPA 70 2011 in 10 CFR 851 Worker Safety and Health Plans (WSHP). Why the best practice was used: 10 CFR 851 lists safety and health consensus standards with which the contractor must comply when applicable with site hazards (851.23). Only the versions of consensus standards that were in effect on February 9, 2006 were promulgated pursuant to rulemaking therefore only those specifically cited versions are required by the Rule. Contractors may include successor versions of the consensus standards that provide equal or greater worker protection if included in their DOE-approved worker safety and health program. What are the benefits of the best practice: The use of NFPA 70 2014 is at least as protective as the 2011 edition, and even more protective in some areas, such that the new edition should be considered for DOE Complex wide acceptance. NFPA 70 2014 is recommended for approval across the DOE Complex as an upgrade to NFPA 70 2011. What problems/issues were associated with the best practice: There were no issues associated with this gap analysis. Adoption of the 2014 Edition of NFPA 70 provides a level of protection “As Safe or Safer” than the 2011 version. How the success of the Best Practice was measured: N/A Description of process experience using the Best Practice: At the time this analysis was performed, process experience did not exist. . Page 1 of 203 Attachment to EFCOG Best Practice #178 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Date 08/18/2014 Code/Standard Title: NFPA 70® – National Electrical Code® 10CFR851 UPGRADE EVALUATION TITLE: Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Note: National Fire Protection Association ®, NFPA ®, NFPA 70®, National Electrical Code ®, NEC ®, National Electrical Safety Code®, NESC® are registered trademarks of the National Fire Protection Association, Quincy, MA. Page 2 of 203 Attachment to EFCOG Best Practice #178 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions 1. DESCRIPTION 10 CFR 851 - “DOE Worker Health and Safety Program” requires that the 2005 edition of NFPA 70 - “National Electrical Code” (NEC) be utilized. The purpose of this evaluation is to document the acceptability of the changes introduced in 2014 edition of NFPA 70 as compared to the 2011 edition and to identify and evaluate the impact of the changes to the safety and health of workers. 2008 and 2011 editions of NFPA 70 were reviewed separately. The sections of the NEC that deal strictly with residential systems or systems not in use at in industrial applications are not included in this evaluation. Furthermore, a majority of editorial changes, clarifications, additions of definitions, rearrangement of sections and related crossreference revisions, or changes related to bringing the code in alignment with the NEC Style Manual are not considered to have an impact on safety and, therefore, are in most cases not included in this evaluation. No Informational Notes and no Informative Annexes were evaluated as they are not part of the Code text and have no enforceable meaning. 2. TECHNICAL JUSTIFICATION The attached comparison was prepared by Andrew Drutel and reviewed by Jackie McAlhaney. The review identified no detrimental impacts to worker safety and health and concluded that the use of the 2014 edition of NFPA 70 is as protective to the worker as the 2008 and 2011 editions. Attachment #4 provides comparisons of changes that were made to 2011 Edition of NEC in 2014 Edition of the code. Each line item listed in the “Comparison Table” has been reviewed and rated for the impact on worker safety. A rating of “1” (editorial), “2” (technical improvement), or “3” (potential safety consequence) has been assigned for each item. Any item with a ranking of “3” requires additional justification. Examples of the three ratings are provided below. 1. Editorial Change – No impact to worker health or safety Example: Adding a metrication reference. 2. Technical Improvement – Addition, enhancement, or change in methodology or acceptance criteria that does not degrade worker safety when compared to the previous edition. Example: Adding requirements for equipment grounding for lighting switches supplied by a general purpose branch circuit. 3. Potential Safety Consequence – Changes or revisions that potentially make the electrical installation less robust and could affect personnel safety. A ranking of “3” requires additional justification or further action. Example: Change in an overcurrent protection of a conductor or equipment which could result in reduced margin of safety. In some cases text of a particular revised section was truncated, capturing only portion of the text relevant to a particular change. The changes are depicted as follows: Text shown in strikethrough font represents portions of the code which were deleted, Page 3 of 203 Attachment to EFCOG Best Practice #178 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Underlined font represents new text being added to the code. 3. CONCLUSION As demonstrated in Attachment #4, there have been no changes made to the NFPA 70, National Electrical Code in the 2014 Edition that could present adverse impact to worker health or safety (rated “3”, as described above). Furthermore, the provisions of the 2014 edition are at least as protective as the edition specified in 10 CFR 851 (NFPA 70-2005) , NFPA 70-2008, and NFPA 70-2011. 4. COST IMPACT The provisions of the NFPA 70, National Electrical Code are not retroactive; therefore, no cost impact related to implementation of the new editions of the code is anticipated. Some of the changes may affect future installations; however, the costs of design, construction, and startup testing will be factored in during the project development stage. Cost of implementing the requirement for sealing certain types of engineering documents by a Professional Engineer, addressed in 5. Notes, Items 1 and 2, below, is considered to be negligible. 5. NOTES 1. Additional code sections now require that the design documentation be prepared by a qualified licensed professional engineer engaged primarily in the subject design (e.g. Article 490, Equipment Over 1000 V, Nominal, Section 490.48). 2. In Sections 620.62, 700.28, 701.27, and 708.54 a new requirement was added for selective coordination studies of overcurrent-protection devices to be prepared by a licensed professional engineer or other qualified persons. 3. Article 590, Temporary Installations, Section 590.4(J) no longer allows cable assemblies and flexible cords and cables used as branch circuits or feeders to be installed on the floor or on the ground (this restriction does not apply to extension cables). Procedures applicable to temporary installations will need to be reviewed to ensure compliance with this requirement. 4. This document, along with NFPA 70-2011 evaluation, shall be considered when adopting 2014 edition of the National Electrical Code. 6. REFERENCES 1. 10 CFR 851, Worker Safety and Health Program Page 4 of 203 Attachment to EFCOG Best Practice #178 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. ANSI/ISA 12.27.01 – 2011, Requirements for Process Sealing Between Electrical Systems and Flammable or Combustible Process Fluids ANSI/ISA 60079-31– 2013, Explosive Atmospheres – Part 31: Equipment Dust Ignition Protection by Enclosure “t” ANSI/ISA 61241-1 – 2006, Electrical Apparatus for Use in Zone 21 and Zone 22 Hazardous (Classified) Locations − Protection by Enclosures “tD” ANSI/UL 508 – 1999, UL Standard for Safety Industrial Control Equipment ANSI/UL 2225 – 2013, UL Standard for Safety Cables and Cable-Fittings For Use In Hazardous (Classified) Locations ASTM E 11 – 2009, Standard Specification for Wire Cloth and Sieves for Testing Purposes IEEE 80 – 2000, Guide for Safety In AC Substation Grounding. NFPA 20 – 2013, Standard for Installation of Stationary Pumps for Fire Protection NFPA 33 – 2011, Standard for Spray Application Using Flammable or Combustible Materials NFPA 34 – 2011, Standard for Dipping, Coating, and Printing Processes Using Flammable or Combustible Liquids NFPA 70, National Electrical Code (2005, 2008, 2011, and 2014 editions) NFPA 70E – 2004, Standard for Electrical Safety in the Workplace NFPA 72 – 2013, National Fire Alarm and Signaling Code NFPA 79 – 2015, Electrical Standard for Industrial Machinery NFPA 90A – 2015, Standard for the Installation of Air-Conditioning and Ventilating Systems NFPA 499 – 2013 Recommended Practice for the Classification of Combustible Dusts and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas 7. ATTACHMENTS 1. 2. 3. 4. Email, Drutel to NFPA Licensing, dated March 13, 2014 Letter, Berry (NFPA) to Drutel, dated March 21, 2014 Evaluation Sample Comparison Table Page 5 of 203 Attachment to EFCOG Best Practice #178 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #1 Page 6 of 203 Attachment to EFCOG Best Practice #178 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #2 Page 7 of 203 Attachment to EFCOG Best Practice #178 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #3 Page 8 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Note: Reprinted with permission from NFPA 70®-2014 Redline, National Electrical Code®, Copyright © 2013, National Fire Protection Association, Quincy, MA. The reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. CODE-WIDE CHANGES Note: Changes listed under this heading are common to one or more articles and multiple sections of the NEC, and are addressed here in lieu of specific articles/sections they appear in. 2014 NEC (with changes) 110.21 Marking. (B) Field-Applied Hazard Markings. Where caution, warning, or danger signs or labels are required by this Code, the labels shall meet the following requirements: (1) The marking shall adequately warn of the hazard using effective words and/or colors and/or symbols. (2) The label shall be permanently affixed to the equipment or wiring method and shall not be hand written. Exception to (2): Portions of labels or markings that are variable, or that could be subject to changes, shall be permitted to be hand written and shall be legible. (3) The label shall be of sufficient durability to withstand the environment involved. 110.25 Lockable Disconnecting Means. Where a disconnecting means is required to be lockable open elsewhere in this Code, it shall be capable of being locked in the open position. The provisions for locking shall remain in place with or without the lock installed. Exception: Cord-and-plug connection locking provisions shall not be required to remain in place without the lock installed. 200.6 Means Conductors. of Identifying Grounded (A) Sizes 6 AWG or Smaller. An insulated grounded con- Change Description and Impact Change Description: Removed hazard marking requirements repeated throughout the code and replaced with a reference to Section 110.21(B), covering hazard marking requirements generically. Editorial change, simplifying use of the NEC. Rank 1 Impact(s) : No negative impact. Change Description: Removed lockable disconnecting means requirements repeated throughout the code and replaced with a reference to Section 110.25, covering these requirements generically. Editorial change, simplifying use of the NEC. 1 Impact(s) : No negative impact. Change Description: This change offers more choices to the installer and allows identification of grounded conductor by system if multiple systems Page 9 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ductor of 6 AWG or smaller shall be identified by one of are installed. the following means: (3) Three continuous white or gray stripes along the con- Impact(s) : ductor’s entire length on other than green insulation. No negative impact. Raised the 600V threshold in the NEC to 1000 V, based on the proposals submitted by the High Voltage Task Group appointed by the NEC Correlating Committee. Previously used reference to the National Electrical Safety Code (NESC) for voltages above 600V created confusion for personnel responsible for design of such systems. Change Description: The change is related to introduction of emerging technologies (e.g., wind power generating systems, photovoltaic systems) operating over 600V. To ensure safety the equipment must first be tested and found acceptable for use at the higher voltage. In addition, NEC must include prescriptive requirements to permit installations at these higher operating voltages. This change was made in majority cases where the previous code limited the installation voltage to 600V. Also, as a consequence of this change, the articles and sections referring to installations “over 600V” in the previous edition of the code were revised accordingly to “over 1000V”. 2 Impact(s) : This change is deemed to be acceptable and safe as long as the above criteria are applied (i.e. equipment tested/approved and NEC requirements exist for installation at up to 1000V). Revised text of several sections to expand applicability from “Buildings” to “Buildings and Other Structures”. Change Description: This change clarifies the intent of the NEC addressing applicability of the code to structures which cannot be classified as “buildings”. 2 Impact(s) : No negative impact. The title of the definition of the term “metalenclosed switchgear” has been changed to Change Description: As revised, the definition now applies to all switchgear types, Page 10 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table simply “switchgear,” resulting in more expanded application of this term. The revised definition also allows for inclusion of the term “switchgear” in existing rules that only include the term “switchboards,” but that requirement covers both types of equipment. The last sentence of the existing definition is more informative than descriptive and, accordingly, has been crafted into an informational note to this definition. All switchgear covered by the NEC rules are intended to be metal-enclosed types. As revised, the definition now applies to all switchgear types, such as metal-clad switchgear, metal-enclosed switchgear and low-voltage power circuit breaker switchgear as indicated in the new informational note. Action by Code-Making Panel 9 on Proposal 9104a results in a change in the title of Article 408 from “Switchboards and Panelboards” to “Switchboards, Switchgear, and Panelboards,” and the scope was revised to include switchgear. Article 490 was also revised to incorporate the term “switchgear” in place of the term “metal-enclosed switchgear.” Other NEC revisions have been made to replace the term “metal-enclosed switchgear” with “switchgear.” such as metal-clad switchgear, metal-enclosed switchgear and low-voltage power circuit breaker switchgear as indicated in the new informational note. Action by Code-Making Panel 9 on Proposal 9-104a results in a change in the title of Article 408 from “Switchboards and Panelboards” to “Switchboards, Switchgear, and Panelboards,” and the scope was revised to include switchgear. Article 490 was also revised to incorporate the term “switchgear” in place of the term “metal-enclosed switchgear.” Other NEC revisions have been made to replace the term “metalenclosed switchgear” with “switchgear.” Multiple definitions moved to Article 100 Change Description: This change is consistent with the NEC Style Manual which requires that definitions appearing in two or more articles be located in Article 100. Impact(s) No negative impact. Page 11 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Impact(s) : No negative impact. 2011 NEC added definitions for Overhead Service Conductors and Underground Service Conductors in Article 100, but these additional terms were not added to Article 250 and other applicable articles of the code discussing services. Change Description: The terms Overhead Service Conductors and/or Underground Service Conductors were added in Article 250 for clarity and to reflect changes to service definitions and terminology made in the 2011 NEC. 1 Impact(s) : No negative impact. I. General Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections without requiring those to whom ready access is requisite to actions such as to use tools, to climb over or remove obstacles, or to resort to portable ladders, and so forth. ARTICLE 100 Definitions Change Description: This change is further clarifying the intent of the code regarding accessibility by ensuring that for an equipment to be considered readily accessible no actions such as use of tools shall be necessary to access it. 2 Impact(s) Improves safety - no negative impact. ARTICLE 110 Requirements for Electrical Installations 110.16 Arc-Flash Hazard Warning. Electrical equipment, Change Description: such as switchboards, switchgear, panelboards, industrial Included factory marking as an acceptable method for warning control panels, meter socket enclosures, and motor control about a potential arc-flash hazard. This change eliminates a need centers, that are in other than dwelling units, and are likely for adding a redundant arc-flash hazard warning label in the field to require examination, adjustment, servicing, or maintefor equipment already marked by the manufacturer. nance while energized, shall be field or factory marked to warn qualified persons of potential electric arc flash hazards. The marking shall meet the requirements in 110.21(B) and shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or Impact(s) : No negative impact. Page 12 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table maintenance of the equipment. 110.26 Spaces About Electrical Equipment. (3) Personnel Doors. Where equipment rated 1200800 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 7.6 m (25 ft) from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with listed panic bars, pressure plates, or other devices that are normally latched but open under simple pressure.hardware. Change Description: Lowered the ampacity of equipment from 1200A to 800A for which the specific requirements for the personnel door apply. This lowers the exposure of a worker in case of an arc flash in the equipment. Also, added requirements for dedicated equipment space in outdoor applications, which was missing from the code. This change allows enforcement of safe installation of equipment, regardless of its location. 2 Impact(s) : Improves safety - no negative impact. (E) Dedicated Equipment Space. (2) Outdoor. (b) Dedicated Equipment Space. The space equal to the width and depth of the equipment, and extending from grade to a height of 1.8 m (6 ft) above the equipment, shall be dedicated to the electrical installation. No piping or other equipment foreign to the electrical installation shall be located in this zone. 110.27 Guarding of Live Parts. Change Description: Increased elevation of live parts of equipment operating at (A) Live Parts Guarded Against Accidental Contact. voltages between 301 V and 600V. This coordinates the (4) By elevation above the floor or other working surface as clearance requirements with the National Electrical Safety Code, shown in 110.27(A)(4)(a) or (b) below: 124A3 and Table 124-1. a. A minimum of 2.5 m (8 ft) or more above the floor or other working surface.for 50 to 300 volts b. A minimum of 2.6 m (81⁄2 ft) for 301 to 600 volts Impact(s) : Improves safety - no negative impact. ARTICLE 200 Use and Identification of Grounded Conductors Page 13 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 200.4 Neutral Conductors. Neutral conductors shall be installed in accordance with 200.4(A) and (B) (A) Installation. Neutral conductors shall not be used for more than one branch circuit, for more than one multiwire branch circuit, or for more than one set of ungrounded feeder conductors unless specifically permitted elsewhere in this Code. (B) Multiple Circuits. Where more than one neutral conductor associated with different circuits is in an enclosure, grounded circuit conductors of each circuit shall be identified or grouped to correspond with the ungrounded circuit conductor(s) by wire markers, cable ties, or similar means in at least one location within the enclosure. Change Description: This new provision in the code requires identification and grouping of the neutral conductor with ungrounded conductor of each circuit in an enclosure, following similar requirement in Section 210.4(D), but expanding it to all enclosures. 2 Impact(s) : Improves safety – no negative impact. Exception No. 1: The requirement for grouping or identifying shall not apply if the branch-circuit or feeder conductors enter from a cable or a raceway unique to the circuit that makes the grouping obvious. Exception No. 2: The requirement for grouping or identifying shall not apply where branch-circuit conductors pass though a box or conduit body without a loop as described in 314.16(B)(1) or without a splice or termination. 210.4 Multiwire Branch Circuits. (A) General. (D) Grouping. The ungrounded and grounded circuit conductors of each multiwire branch circuit shall be grouped by cable ties or similar means in at least one location within the panelboard or other point of origination. Exception: The requirement for grouping shall not apply if the circuit enters from a cable or raceway unique to the circuit that makes the grouping obvious or if the conductors ARTICLE 210 Branch Circuits Change Description: This change further clarifies the intent that the grounded and ungrounded conductors shall be identifiable and allows an exception to the grouping rule for conductors identified at the terminations. Impact(s) : No negative impact. are identified at their terminations with numbered wire Page 14 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table markers corresponding to the appropriate circuit number . 210.5 Identification for Branch Circuits (C) Identification of Ungrounded Conductors. (2) Branch Circuits Supplied From Direct-Current Systems. Where a branch circuit is supplied from a dc system operating at more than 50 volts, each ungrounded conductor of 4 AWG or larger shall be identified by polarity at all termination, connection, and splice points by marking tape, tagging, or other approved means; each ungrounded conductor of 6 AWG or smaller shall be identified by polarity at all termination, connection, and splice points in compliance with 210.5(C)(2)(a) and (b). The identification methods utilized for conductors originating within each branchcircuit panelboard or similar branch-circuit distribution equipment shall be documented in a manner that is readily available or shall be permanently posted at each branchcircuit panelboard or similar branch-circuit distribution equipment. Change Description: This change was triggered by the re-emergence of direct current (DC) applications. This new section provides criteria for identification of conductors in DC applications. Impact(s) : No negative impact. (a) Positive Polarity, Sizes 6 AWG or Smaller. Where the positive polarity of a dc system does not serve as the connection point for the grounded conductor, each positive ungrounded conductor shall be identified by one of the following means: (1) A continuous red outer finish (2) A continuous red stripe durably marked along the conductor’s entire length on insulation of a color other than green, white, gray, or black (3) Imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color other than green, white, gray, or black, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with 310.120(B) (b) Negative Polarity, Sizes 6 AWG or Smaller. Where the negative polarity of a dc system does not serve as the connection point for the grounded conductor, each negative ungrounded conductor shall be identified by one of the following means: Page 15 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (1) A continuous black outer finish (2) A continuous black stripe durably marked along the conductor’s entire length on insulation of a color other than green, white, gray, or red (3) Imprinted minus signs (–) or the word NEGATIVE or NEG durably marked on insulation of a color other than green, white, gray, or red, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with 310.120(B) 210.8 Ground-Fault Circuit-Interrupter Protection for Personnel. (B) Other Than Dwelling Units. Change Description: Clarifies the intent that ground-fault circuit-interrupter type receptacles installed on rooftops need to be readily accessible only from the roof top. 1 (3) Rooftops Impact(s) : Exception No. 1 to (3):Receptacles on rooftops shall not be No negative impact. required to be readily accessible other than from the rooftop. 210.13 Ground-Fault Protection of Equipment. Each branch-circuit disconnect rated 1000 A or more and installed on solidly grounded wye electrical systems of more than 150 volts to ground, but not exceeding 600 volts phase-to-phase, shall be provided with ground-fault protection of equipment in accordance with the provisions of 230.95. Change Description: This change expands the ground-fault protection (GFP) for equipment for branch circuits meeting the criteria of Section 230.95. This change is similar to an earlier change which introduced GFP for feeders (Section 215.10). 2 Impact(s) : Improves safety – no negative impact. 210.17 Electric Vehicle Branch Circuit. An outlet(s) installed for the purpose of charging electric vehicles shall be supplied by a separate branch circuit. This circuit shall have no other outlets. Change Description: New provision requiring vehicle charging station to be fed from a dedicated circuit, with no other outlets on it. Impact(s) : No negative impact. Page 16 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table II. Branch-Circuit Ratings 210.19 Conductors — Minimum Ampacity and Size. (A) Branch Circuits Not More Than 600 Volts. (1) General. Branch-circuit conductors shall have an ampacity not less than the maximum load to be served. Conductors shall be sized to carry not less than the larger of 210.19(A)(1)(a) or (b). (a) Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size, before the application of any adjustment or correction factors,size shall have an allowable ampacity not less than the noncontinuous load plus 125 percent of the continuous load. (b) The minimum branch-circuit conductor size shall have an allowable ampacity not less than the maximum load to be served after the application of any adjustment or correction factors. 210.22 Permissible Loads, Individual Branch Circuits. An individual branch circuit shall be permitted to supply any load for which it is rated, but in no case shall the load exceed the branch-circuit ampere rating. Change Description: The new wording clarifies that there are two conditions for determining the minimum conductor size and that the conductor is selected to carry not less than the larger of both conditions. Impact(s) : Improves clarity of the code – no negative impact. 1 Change Description: Separated Section 210.23 into two sections by adding Section 210.22, covering individual branch circuits. 1 Impact(s) : No negative impact. 210.64 Electrical Service Areas. At least one 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed within 15 m (50 ft) of the electrical service equipment. Change Description: New section added, requiring a receptacle (120V, 15A or 20A) outlet within 50’ of the service area. Impact(s) : Improves safety – no negative impact. ARTICLE 215 Feeders Page 17 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 215.2 Minimum Rating and Size. (A) Feeders Not More Than 600 Volts. (1) General. Feeder conductors shall have an ampacity not less than required to supply the load as calculated in Parts III, IV, and V of Article 220. Conductors shall be sized to carry not less than the larger of 215.2(A)(1)(a) or (b). Change Description: The new wording clarifies that there are two conditions for determining the minimum conductor size and that the conductor is selected to carry not less than the larger of both conditions. Impact(s) : Improves clarity of the code – no negative impact. 1 Change Description: This change was triggered by the re-emergence of direct current (DC) applications. This new section provides criteria for identification of conductors in DC applications. 2 (a) Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, The minimum feeder circuit conductor size, before the application of any adjustment or correction factors, the minimum feeder conductor size shall have an allowable ampacity not less than the noncontinuous load plus 125 percent of the continuous load. (b) The minimum feeder conductor size shall have an allowable ampacity not less than the maximum load to be served after the application of any adjustment or correction factors. 215.12 Identification for Feeders. (C) Identification of Ungrounded Conductors. Ungrounded conductors shall be identified in accordance with 215.12(C)(1) or (C)(2), as applicable. 2) Feeders Supplied from Direct-Current Systems. Where a feeder is supplied from a dc system operating at more than 50 volts, each ungrounded conductor of 4 AWG or larger shall be identified by polarity at all termination, connection, and splice points by marking tape, tagging, or other approved means; each ungrounded conductor of 6 AWG or smaller shall be identified by polarity at all termination, connection, and splice points in compliance with 215.12(C)(2)(a) and (b). The identification methods utilized for conductors originating within each feeder panelboard or similar feeder distribution equipment shall be documented in a manner that is readily available or shall be Impact(s) : No negative impact. Page 18 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table permanently posted at each feeder panelboard or similar feeder distribution equipment. (a) Positive Polarity, Sizes 6 AWG or Smaller. Where the positive polarity of a dc system does not serve as the connection for the grounded conductor, each positive ungrounded conductor shall be identified by one of the following means: (1) A continuous red outer finish (2) A continuous red stripe durably marked along the conductor’s entire length on insulation of a color other than green, white, gray, or black (3) Imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color other than green, white, gray, or black, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with 310.120(B) (b) Negative Polarity, Sizes 6 AWG or Smaller. Where the negative polarity of a dc system does not serve as the connection for the grounded conductor, each negative ungrounded conductor shall be identified by one of the following means: (1) A continuous black outer finish (2) A continuous black stripe durably marked along the conductor’s entire length on insulation of a color other than green, white, gray, or red (3) Imprinted minus signs (–) or the word NEGATIVE or NEG durably marked on insulation of a color other than green, white, gray, or red, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with 310.120(B) ARTICLE 220 Branch-Circuit, Feeder, and Service Calculations 220.12 Lighting Load for Specified Occupancies. A unit Change Description: load of not less than that specified in Table 220.12 for The new exception to calculating lighting loads was added to occupancies specified therein shall constitute the minimum allow lighting loads to be calculated in accordance with local lighting load. The floor area for each floor shall be calcucodes where power monitoring systems are in place. lated from the outside dimensions of the building, dwelling unit, or other area involved. For dwelling units, the calcu- Page 19 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table lated floor area shall not include open porches, garages, or unused or unfinished spaces not adaptable for future use. Impact(s) : No negative impact. Exception: Where the building is designed and constructed to comply with an energy code adopted by the local authority, the lighting load shall be permitted to be calculated at the values specified in the energy code where the following conditions are met: (1) A power monitoring system is installed that will provide continuous information regarding the total general lighting load of the building. (2) The power monitoring system will be set with alarm values to alert the building owner or manager if the lighting load exceeds the values set by the energy code. (3) The demand factors specified in 220.42 are not applied to the general lighting load. ARTICLE 225 Outside Branch Circuits and Feeders 225.4 Conductor Covering. Where within 3.0 m (10 ft) of Change Description: any building or structure other than supporting poles or towers, This change prohibits the use of bare conductors within 10’ from open individual (aerial) overhead conductors shall be insulated any building or structure, except poles or towers. or covered. for the nominal voltage. 2 Impact(s) : Improves safety – no negative impact. 225.11 Circuit Exits and Entrances. Where outside branch and feeder circuits leave or enter a building, the requirements of 230.52 and 230.54 shall apply. 225.11 Feeder and Branch-Circuit Conductors Entering, Exiting, or Attached to Buildings or Structures. Feeder and branch-circuit conductors entering or exiting buildings or structures shall be in installed in accordance with the requirements of 230.52. Overhead branch circuits and feeders attached to buildings or structures shall be in- Change Description: Change the title and the text of this section to improve the clarity. Also, expanded this requirement to include other structures. Impact(s) : No negative impact. Page 20 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table stalled in accordance with the requirements of 230.54. 225.17 Masts as Supports. Where a mast is Only feeder or branch-circuit conductors specified within this section shall be permitted to be attached to the feeder and/or branchcircuit mast. Masts used for the support of final spans of feeders or branch circuits, circuits shall be in- stalled in accordance with 225.17(A) and (B). Change Description: Text revised for clarity. Also, included a requirement for all components of a mast to be identified for use with a mast. In addition, put some restrictions on attaching conductors to a mast to ensure its structural integrity. 2 A) Strength. itThe mast shall be of adequate strength or be Impact(s) : supported by braces or guys to withstand safely the strain Improves safety – no negative impact. imposed by the overhead drop. Where raceway-type masts are used, all raceway fittings shall be identified for use with masts. Only the feeder or branch-circuit conduc- tors. Hubs intended for use with a conduit that serves as a mast for support of feeder or branch-circuit conductors specified within this section shall be permitted to be attached to the feeder and/or branch-circuit identified for use with a mast. (B) Attachment. Feeder and/or branch-circuit conductors shall not be attached to a mast between a weatherhead or the end of the conduit and a coupling where the coupling is located above the last point of securement to the building or other structure or is located above the building or other structure. 225.27 Raceway Seal. Where a raceway enters a building or structure from an underground distribution system, it shall be sealed in accordance with 300.5(G). Spare or unused raceways shall also be sealed. Sealants shall be identified for use with the cable insulation, conductor insulation, bare conductor, shield, or other components. Change Description: Expanded the scope of this section to require compatibility of sealants with conductor insulation and with bare conductor material. 2 Impact(s) : No negative impact. 225.36 Suitable for Service Equipment. Type. The disconnecting means specified in 225.31 shall be comprised of a Change Description: Revised to specifically identify acceptable disconnecting means Page 21 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table circuit breaker, molded case switch, general-use switch, snap switch, or other approved means. Where applied in accordance with 250.32(B), Exception No. 1, the disconnecting means shall be suitable for use as service equipment. and to clarify when a disconnecting means must be suitable for use as a service equipment. Also, eliminated exception allowing 3- and 4-way switches as disconnecting means because they would not provide a positive indication that a circuit was disconnected. Impact(s) : Improves safety - no negative impact. II. Over 6001000 Volts. 225.52 Disconnecting Means. (A) Location. A building or structure disconnecting means shall be located in accordance with 225.32, or, if not readily accessible, it shall be operable by mechanical linkage from a readily accessible point. For multibuilding industrial installations under single management, it shall be permitted to be electrically operated by a similarly locatedreadily accessible, remote-control device in a separate building or structure. Change Description: This change allows operation of disconnecting means over 1000V using remote-control device from a readily accessible location. 2 Impact(s) : No negative impact. (B) Type. Each building or structure disconnect shall simultaneously disconnect all ungrounded supply conductors it controls and shall have a fault-closing rating not less than the maximum available short-circuit current available at its supply terminals. Exception: Where the individual disconnecting means consists of fused cutouts, the simultaneous disconnection of all ungrounded supply conductors shall not be required if there is a means to disconnect the load before opening the cutouts. A permanent legible sign shall be installed adjacent to the fused cutouts indicating the above requirement. and shall read DISCONNECT LOAD BEFORE OPENING CUTOUTS. 225.56 Inspections and Tests. (A) Pre-Energization and Operating Tests. The complete electrical system design, including settings for protec- Change Description: Defined in more detail the required pre-energization and Page 22 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table tive, switching, and control circuits, shall be prepared in advance and made available on request to the authority having jurisdiction and shall be performance tested when first installed on-site. Each protective, switching, and control circuit shall be adjusted in accordance with the recommendations of the protective device studysystem design and tested by actual operation using current injection or equivalent methods as necessary to ensure that each and every such circuit operates correctly to the satisfaction of the authority having jurisdiction. (B) Type. Each building or structure disconnect shall simultaneously disconnect all ungrounded supply conductors it controls and shall have a fault-closing rating not less than the maximum available short-circuit current available at its supply terminals. operating tests for systems over 1000 V. Also, clarified what wording is to be provided for the warning sign to be located adjacent to a fuse cutout. Impact(s) : No negative impact. Exception: Where the individual disconnecting means consists of fused cutouts, the simultaneous disconnection of all ungrounded supply conductors shall not be required if there is a means to disconnect the load before opening the cutouts. A permanent legible sign shall be installed adjacent to the fused cutouts indicating the above requirement. and shall read DISCONNECT LOAD BEFORE OPENING CUTOUTS. 225.70 Substations. Change Description: Relocated requirements to Article 490, covering equipment over 1000 V. Impact(s) : No negative impact. ARTICLE 230 Services Page 23 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 230.6 Conductors Considered Outside the Building. Conductors shall be considered outside of a building or other structure under any of the following conditions: (5) Where installed in overhead service masts on the outside surface of the building traveling through the cave of that building within rigid metal conduit (Type RMC) or intermediate metal conduit (Type IMC) to meet the requirements of 230.24. used to accommodate the clearance requirements in 230.24 and routed directly through an eave but not a wall of a building. 230.28 Service Masts as Supports. Where a service mast is used for the support of service-drop conductors, it shall be of adequate strength or be supported by braces or guys to withstand safely the strain imposed by the service drop. Where raceway-type service masts are used, all raceway fittings shall be identified for use with service masts. Only power service-drop conductors shall be permitted to be attached to a service mast. Only power service-drop or overhead service conductors shall be permitted to be attached to a service mast. Service masts used for the support of service-drop or overhead service conductors shall be installed in accordance with 230.28(A) and (B). Change Description: The change defines as outside the building RMC or IMC raceways passing through an eave but not a wall of a building. This limits this provision of the code to heavy wall steel raceways. 2 Impact(s) : Improves safety - no negative impact. Change Description: Text revised for clarity. Also, included a requirement for all components of a mast to be identified for use with service equipment. In addition, put some restrictions on attaching conductors to a mast to ensure its structural integrity. Impact(s) : Improves safety – no negative impact. (A) Strength. The service mast shall be of adequate strength or be supported by braces or guys to withstand safely the strain imposed by the service-drop or overhead service conductors. Hubs intended for use with a conduit that serves as a service mast shall be identified for use with service-entrance equipment. (B) Attachment. Service-drop or overhead service conductors shall not be attached to a service mast between a weatherhead or the end of the conduit and a coupling, where the coupling is located above the last point of securement to the building or other structure or is located above the building or other structure. Page 24 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 230.42 Minimum Size and Rating. A) General. The ampacity of the service-entrance conductors before the application of any adjustment or correction factors shall not be less than either 230.42(A)(1), (A)(2), or (A)(23). Loads shall be determined in accordance with Part III, IV, or V of Article 220 as applicable. Ampacity shall be determined from 310.15. The maximum allow- able current of busways shall be that value for which the busway has been listed or labeled. (1) The sum of the noncontinuous loads plus 125 percent of continuous loads Change Description: Companion to changes to Sections 210.19(A)(1) and 215.2(A)(1). The new wording clarifies that there are two conditions for determining the minimum conductor size and that the conductor is selected to carry not less than the larger of both conditions. Impact(s) : Improves clarity – no negative impact. 1 Change Description: This change provides label spacing requirements, consistent with Section 392.18(H) for cable trays containing high voltage conductors. 2 Exception: Grounded conductors that are not connected to an overcurrent device shall be permitted to be sized at 100 percent of the continuous and noncontinuous load. (2) The sum of the noncontinuous load plus the continuous load after the application of any adjustment or correction factors. (2)(3)The sum of the noncontinuous load plus the continuous load if the service-entrance conductors terminate in an overcurrent device where both the overcurrent device and its assembly are listed for operation at 100 percent of their rating. 230.44 Cable Trays. Cable tray systems shall be permitted to support service-entrance conductors. Cable trays used to support service-entrance conductors shall contain only service-entrance conductors and shall be limited to the following methods: (1) Type SE cable (2) Type MC cable (3) Type MI cable (4) Type IGS cable Impact(s) : Provides consistency – no negative impact. (5) Single thermoplastic-insulated conductors 1/0 and larger with CT rating. Page 25 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Such cable trays shall be identified with permanently affixed labels with the wording “Service-Entrance Conductors.” The labels shall be located so as to be visible after installation and placedwith a spacing not to exceed 3 m (10 ft) so that the service-entrance conductors are able to be readily traced through the entire length of the cable tray. 230.82 Equipment Connected to the Supply Side of Service Disconnect. (3) Meter disconnect switches nominally rated not in excess of 600 volts1000 V that have a short-circuit current rating equal to or greater than the available short- circuit current, provided that all metal housings and service enclosures are grounded in accordance with Part VII and bonded in accordance with Part V of Ar- ticle 250. A meter disconnect switch shall be capable of interrupting the load served. A meter disconnect shall be legibly field marked on its exterior in a manner suitable for the environment as follows: METER DISCONNECT NOT SERVICE EQUIPMENT Change Description: Added a labeling requirement for meter disconnect to ensure a clear understanding that this particular disconnect is not a service disconnect. Impact(s) : Improves safety - no negative impact. ARTICLE 240 Overcurrent Protection 240.21 Location in Circuit. Change Description: (B) Feeder Taps. This new exception allows use of manufacturer specified wire (1) Taps Not over 3 m (10 ft) Long. If the length of the tap size in lieu of applying a tap rule for conductors supplying listed conductors does not exceed 3 m (10 ft) and the tap conductors equipment, such as surge protective device. comply with all of the following: (1) The ampacity of the tap conductors is a. Not less than the combined calculated loads on the circuits supplied by the tap conductors, and Impact(s) : No negative impact. b. Not less than the rating of the equipment containing an overcurrent device(s) supplied by the tap conductors or not less than the rating of the overcurrent protective device at the termination of the tap conductors. Page 26 of 203 2 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Exception to b: Where listed equipment, such as a surge protective device(s) [SPD(s)], is provided with specific instructions on minimum conductor sizing, the ampacity of the tap conductors supplying that equipment shall be permitted to be determined based on the manufacturer’s instructions. (C) Transformer Secondary Conductors. (10 ft) Long. If the length of secondary conductor does not exceed 3 m (10 ft) and complies with all of the following: (1) The ampacity of the secondary conductors is a. Not less than the combined calculated loads on the circuits supplied by the secondary conductors, and b. Not less than the rating of the equipment containing an overcurrent device(s) supplied by the secondary conductors or not less than the rating of the overcurrent protective device at the termination of the secondary conductors. Exception: Where listed equipment, such as a surge protective device(s) [SPD(s)], is provided with specific instructions on minimum conductor sizing, the ampacity of the tap conductors supplying that equipment shall be permitted to be determined based on the manufacturer’s instructions. 240.87 Noninstantaneous Trip.Arc Energy Reduction. Where the highest continuous current trip setting for which the actual overcurrent device installed in a circuit breaker is used without an instantaneous trip,rated or can be adjusted is 1200 A or higher, 240.87(A) and (B) shall apply. Change Description: This change provides more clarity and usability to this requirement and adds energy-reducing active arc flash mitigation system as one of the methods of reducing arc flash energy. (B) Method to Reduce Clearing Time. Where a circuit breaker is utilized without an instantaneous trip, oneOne of the following or approved equivalent means shall be provided: Impact(s) : No negative impact. Page 27 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (4) Energy-reducing active arc flash mitigation system (5) An approved equivalent means 250.10 Protection of Ground Clamps and Fittings. Ground clamps or other fittings shall be approved for general use without protection or shall be protected from exposed to physical damage as indicated in (1) or (2) as follows: (1) In installations where they are not likely to be damaged (2) Where shall be enclosed in metal, wood, or equivalent protective coveringcovering. ARTICLE 250 Grounding and Bonding Change Description: Change to the wording provides more clarity. Impact(s) : No negative impact. 250.21 Alternating-Current Systems of 50 Volts to Less Than 1000 Volts Not Required to Be Grounded. C) Marking. Ungrounded systems shall be legibly marked “Caution: Ungrounded System Operating — Volts Between Conductors” at the source or first disconnecting means of the system. The marking shall be of sufficient durability to withstand the environment involved. Change Description: Added a requirement for labeling of ungrounded systems to include operating voltage between conductors, consistent with requirement in 408.3(F)(2). 250.24 Grounding Service-Supplied AlternatingCurrent Systems. Change Description: A new Table 250.102(C)(1) was added for sizing grounded conductors and bonding jumpers rather than Table 250.66. References to this new table and the existing Table 250.66 were revised throughout Article 250. (C) Grounded Conductor Brought to Service Equipment. (1) Sizing for a Single Raceway. The grounded conductor shall not be smaller than the required grounding electrode conductor specified in Table 250.66250.102(C)(1). but shall not be required to be larger than the largest ungrounded service-entrance conductor(s). In addition, for sets of ungrounded service-entrance conductors larger than 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor shall not be smaller than 121⁄2 percent of the circular mil area of the largest set of service-entrance ungrounded con- 1 2 Impact(s) : Improves safety – no negative impact. Impact(s) : No negative impact. Page 28 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ductor(s). 250.28 Main Bonding Jumper and System Bonding Jumper. (D) Size. 1) General. Main bonding jumpers and system bonding jumpers shall not be smaller than the sizes shown in Table 250.66. Where the supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the bonding jumper shall have an area that is not less than 121⁄2 percent of the area of the largest phase conductor except that, where the phase conductors and the bonding jumper are of different materials (copper or aluminum), the minimum size of the bonding jumper shall be based on the assumed use of phase conductors of the same material as the bonding jumper and with an ampacity equivalent to that of the installed phase conductors. Main bonding jumpers and system bonding jumpers shall not be smaller than specified in Table 250.102(C)(1). 250.30 Grounding Separately Derived AlternatingCurrent Systems. In addition to complying with 250.30(A) for grounded systems, or as provided in 250.30(B) for ungrounded systems, separately derived systems shall comply with 250.20, 250.21, 250.22, and 250.26.250.22, or 250.26, as applicable. Multiple separately derived systems that are connected in parallel shall be installed in accordance with 250.30. 250.30 Grounding Separately Derived AlternatingCurrent Systems. (A) Grounded Systems. (1) System Bonding Jumper. Exception No. 2: A If a building or structure is supplied by a feeder from an outdoor transformer, a system bonding Change Description: A new Table 250.102(C)(1) was added for sizing grounded conductors and bonding jumpers rather than Table 250.66. References to this new table and the existing Table 250.66 were revised throughout Article 250. 1 Impact(s) : No negative impact. Change Description: The added text provides requirements for multiple separately derived systems operating in parallel. 2 Impact(s) : No negative impact. Change Description: The revised text provides for the limited case where the grounded conductor can be bonded at the source of a separately derived system and in a building or structure served and continues to prohibit parallel paths. This limits the application of this exception to buildings and structures supplied by a feeder from an outdoor transformer. Page 29 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table jumper at both the source and the first disconnecting means shall be permitted if doing so does not establish a parallel path for the grounded conductor. If a grounded conductor is used in this manner, it shall not be smaller than the size specified for the system bonding jumper but shall not be required to be larger than the ungrounded conductor(s). For the purposes of this exception, connection through the earth shall not be considered as providing a parallel path. 250.30 Grounding Separately Derived AlternatingCurrent Systems. (A) Grounded Systems. (2) Supply-Side Bonding Jumper. Impact(s) : No negative impact. Change Description: A companion change to Section 250.30(A)(1), Exception No.2, allowing grounded conductor as a means of bonding enclosures. 2 Impact(s) : No negative impact. Exception: A supply-side bonding jumper shall not be required between enclosures for installations made in compliance with 250.30(A)(1), Exception No. 2. 250.30 Grounding Separately Derived AlternatingCurrent Systems. (A) Grounded Systems. (3) Grounded Conductor. a) Sizing for a Single Raceway. The grounded conductor shall not be smaller than the required grounding electrode conductor specified in Table 250.66250.102(C)(1). but shall not be required to be larger than the largest derived ungrounded conductor(s). In addition, for sets of derived ungrounded conductors larger than 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor shall not be smaller than 121⁄2 percent of the circular mil area of the largest set of derived ungrounded conductors. 250.32 Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s). Change Description: A new Table 250.102(C)(1) was added for sizing grounded conductors and bonding jumpers rather than Table 250.66. References to this new table and the existing Table 250.66 were revised throughout Article 250. 1 Impact(s) : No negative impact. Change Description: Page 30 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (B) Grounded Systems. (1) Supplied by a Feeder or Branch Circuit. Exception No. 2: If system bonding jumpers are installed in accordance with 250.30(A)(1), Exception No. 2, the feeder grounded circuit conductor at the building or structure served shall be connected to the equipment grounding conductors, grounding electrode conductor, and the enclsure for the first disconnecting means. 250.36 High-Impedance Grounded Neutral Systems. (F) Grounding Electrode Conductor Connection Location. The For services or separately derived systems, the grounding electrode conductor shall be connected at any point from the grounded side of the grounding impedance to the equipment grounding connection at the service equipment or the first system disconnecting means of a separately derived system. The added exception provides requirements for the grounded conductor in a building or structure served by a feeder from an outdoor transformer separately derived system installed in accordance with 250.30(A)(1) Exception No. 2. Impact(s) : No negative impact. Change Description: The change clarifies the intent of this section which requires establishing of the fault-current path from the system back to the source of the separately derived system. Impact(s) : No negative impact. 250.62 Grounding Electrode Conductor Material. The grounding electrode conductor shall be of copper, aluminum, copper-clad aluminum, or copper-clad aluminum. the items as permitted in 250.68(C). The material selected shall be resistant to any corrosive condition existing at the installation or shall be protected against corrosion. The conductorConductors of the wire type shall be solid or stranded, insulated, covered, or bare. Change Description: Clarified the intent that materials identified in Section 250.68(C) are acceptable as grounding electrode conductors (e.g. water piping, metal structural frame). 250.64 Grounding Electrode Conductor Installation. Change Description: The added sentence clarifies that grounding electrode conductors or grounding electrode bonding jumpers are not subject to the burial depth requirements found in Section 300.5. (B) Securing and Protection Against Physical Damage. Grounding electrode conductors and grounding electrode bonding jumpers shall not be required to comply with 300.5. 1 2 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 31 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 250.64 Grounding Electrode Conductor Installation. (D) Service Building or Structure with Multiple Disconnecting Means in Separate Enclosures. IfFor a service consists of more than a single enclosure as permitted in 230.71(A),or feeder with two or more disconnecting means in separate enclosures supplying a building or structure, the grounding electrode connections shall be made in accordance with 250.64(D)(1), (D)(2), or (D)(3). Change Description: This revised language incorporates clarification to ensure that this section can be applied to both, building services and buildings fed by one or more feeders. Impact(s) : No negative impact. (2) Individual Grounding Electrode Conductors. A grounding electrode conductor shall be connected between the grounded conductor in each service equipment disconnecting means enclosure and the grounding electrode system.grounding electrode system and one or more of the following, as applicable: (1) Grounded conductor in each service equipment disconnecting means enclosure (2) Equipment grounding conductor installed with the feeder (3) Supply-side bonding jumper Each grounding electrode conductor shall be sized in accordance with 250.66 based on the service-entrance or feeder conductor(s) supplying the individual service disconnecting means. (3) Common Location. A grounding electrode conductor shall be connected to the grounded service conductor(s) in a wireway or other accessible enclosure on the supply side of the service disconnecting means.means to one or more of the following, as applicable: (1) Grounded service conductor(s) (2) Equipment grounding conductor installed with the feeder (3) Supply-side bonding jumper Page 32 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 250.64 Grounding Electrode Conductor Installation. (E) Raceways and Enclosures for Grounding Electrode Conductors. (1) General. Ferrous metal raceways and enclosures for grounding electrode conductors shall be electrically continuous from the point of attachment to cabinets or equipment to the grounding electrode and shall be securely fastened to the ground clamp or fitting. NonferrousFerrous metal raceways and enclosures shall not be required to be electrically continuous. Ferrous metal enclosures that are not physically continuous from cabinets or equipmentbonded at each end of the raceway or enclosure to the grounding electrode shall be made electrically continuous by bonding each end of the raceway or enclosure to the grounding electrode conductor. or grounding electrode conductor. Nonferrous metal raceways and enclosures shall not be required to be electrically continuous. Change Description: This change affirms that nonferrous metal enclosures are not required to be electrically continuous or bonded. 1 Impact(s) : No negative impact. (2) Methods. Bonding methods shall be in compliance with 250.92(B) for installations at service equipment locations and with and ensured by one of the methods in 250.92(B)(2) through (B)(4) for other than service equipment locations shall apply at each end and to all intervening ferrous raceways, boxes, and enclosures between the cabinets or equipment and the grounding electrode.(B)(4). 250.66 Size of Alternating-Current Grounding Electrode Conductor. A) Connections to a Rod, Pipe, or Plate Electrode(s). Where the grounding electrode conductor is connected to a single or multiple rod, pipe, or plate electrode(s), or any combination thereof, as permitted in 250.52(A)(5) or (A)(7), that portion of the conductor that is the sole connection to the grounding electrode(s) shall not be required to be larger than 6 AWG copper wire or 4 AWG aluminum wire. Change Description: Clarification added for the “sole connection” provisions. Impact(s) : No negative impact. B) Connections to Concrete-Encased Electrodes. Where the Page 33 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table grounding electrode conductor is connected to a single or multiple concrete-encased electrode(s) as permitted in 250.52(A)(3), that portion of the conductor that is the sole connection to the grounding electrode(s) shall not be required to be larger than 4 AWG copper wire. 250.68 Grounding Electrode Conductor and Bonding Jumper Connection to Grounding Electrodes. (C) Metallic Water Pipe and Structural Metal.Grounding Electrode Connections. Grounding electrode conductors and bonding jumpers shall be permitted to be connected at the following locations and used to extend the connection to an electrode(s): (2) The metal structural frame of a building that is directly connected to a grounding electrode as specified in 250.52(A)(2) or 250.68(C)(2)(a), (b), or (c) shall be permitted to be used as a bonding conductor to interconnect electrodes that are part of the grounding electrode system, or as a grounding electrode conductor. Change Description: Removed prescriptive language limiting the use of metal structural frame as a bonding conductor. Also, recognized a common practice of extending rebar outside the concrete as an allowable grounding electrode conductor connection point. 2 Impact(s) : No negative impact. a. By connecting the structural metal frame to the reinforcing bars of a concrete-encased electrode, as provided in 250.52(A)(3), or ground ring as provided in 250.52(A)(4) b. By bonding the structural metal frame to one or more of the grounding electrodes, as specified in 250.52(A)(5) or (A)(7), that comply with 250.53(A)(2) c. By other approved means of establishing a connection to earth (3) A concrete-encased electrode of either the conductor type, reinforcing rod or bar installed in accordance with 250.52(A)(3) extended from its location within the concrete to an accessible location above the concrete shall be permitted. 250.102 Bonding Conductors and Jumpers. Change Description: Page 34 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (C) Size — Supply-Side Bonding Jumper. (1) Size for Supply Conductors in a Single Raceway or Cable. The supply-side bonding jumper shall not be smaller than the sizes shown specified in Table 250.66250.102(C)(1). for grounding electrode conductors. Where the ungrounded supply conductors are larger than 1100 kcmil copper or 1750 kcmil aluminum, the supplyside bonding jumper shall have an area not less than 121⁄2 percent of the area of the largest set of ungrounded supply conductors. (2) Size for Parallel Conductor Installations in Two or More Raceways. Where the ungrounded supply conductors are paralleled in two or more raceways or cables, and an individual supply-side bonding jumper is used for bonding these raceways or cables, the size of the supply-side bonding jumper for each raceway or cable shall be selected from Table 250.66250.102(C)(1) based on the size of the ungrounded supply conductors in each raceway or cable. A single supply-side bonding jumper installed for bonding two or more raceways or cables shall be sized in accordance with 250.102(C)(1). (3) Different Materials. Where the ungrounded supply conductors and the supply-side bonding jumper are of different materials (copper or aluminum), the minimum size of the supply-side bonding jumper shall be based on the assumed use of ungrounded conductors of the same material as the supply-side bonding jumper and with an ampacity equivalent to that of the installed ungrounded supply conductors. Table 250.102(C) Grounded Conductor, Main Bonding Jumper, System Bonding Jumper, and Supply-Side Bonding Jumper for Alternating-Current Systems The full Table not included for brevity. A new Table 250.102(C)(1) was added for sizing grounded conductors and bonding jumpers rather than Table 250.66. References to this new table and the existing Table 250.66 were revised throughout Article 250. Impact(s) : No negative impact. Change Description: This new table and corresponding changes to related sections are provided to simplify the sizing requirements for fault carrying conductors that are not sized using Table 250.122. Presently, multiple sections such as for main bonding jumpers, system Page 35 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table bonding jumpers, supply side bonding jumpers and grounded conductors refer to Table 250.66 for sizing the conductor or jumper. Impact(s) : No negative impact. 250.104 Bonding of Piping Systems and Exposed Structural Steel.Metal. (B) Other Metal Piping. The bonding conductor(s) or jumper(s) shall be sized in accordance with 250.122, using the rating of the circuit that is likely to energize the piping system(s). The equipment grounding conductor for the circuit that is likely to energize the piping shall be permitted to serve as the bonding means. The points of attachment of the bonding jumper(s) shall be accessible. Change Description: Editorial change clarifying the intent. 1 Impact(s) : No negative impact. 250.119 Identification of Equipment Grounding Conductors. Change Description: Editorial change clarifying the intent. Exception No. 2: Flexible cords having an integral insulation and jacket without an equipment grounding conductor shall be permitted to have a continuous outer finish that is green. Impact(s) : No negative impact. Exception No. 3: Conductors with green insulation shall be permitted to be used as ungrounded signal conductors where installed between the output terminations of traffıc signal control and traffıc signal indicating heads. Signaling circuits installed in accordance with this exception shall include an equipment grounding conductor in accordance with 250.118. Wire-type equipment grounding conductors shall be bare or have insulation or covering that is green with one or more yellow stripes. Page 36 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 250.121 Use of Equipment Grounding Conductors. An equipment grounding conductor shall not be used as a grounding electrode conductor. Exception: A wire-type equipment grounding conductor installed in compliance with 250.6(A) and the applicable requirements for both the equipment grounding conductor and the grounding electrode conductor in Parts II, III, and VI of this article shall be permitted to serve as both an equipment grounding conductor and a grounding electrode conductor. Change Description: The code making panel recognized that restricting the use of a wire-type equipment grounding conductor for both the equipment grounding conductor and grounding electrode conductor was not justified when it was introduced in 2011 edition of NEC. However, this restriction remains in effect for all types of equipment grounding conductors identified in Section 250.118 other than wire-type conductor. 2 Impact(s) : No negative impact. 250.130 Equipment Grounding Conductor Connections. (C) Nongrounding Receptacle Replacement or Branch Circuit Extensions. Change Description: This addition improves the grounding of nongrounding receptacle replacement or circuit extensions by allowing the most direct path back to the enclosure where the branch circuit originates. (4) An equipment grounding conductor that is part of another branch circuit that originates from the enclosure where the branch circuit for the receptacle or branch circuit originates Impact(s) : Improves safety - no negative impact. VIII. Direct-Current Systems Change Description: This change is related to the re-emergence of direct current applications with 50 V storage batteries and takes into account differences in the battery chemistries, with voltages potentially slightly exceeding 50 V threshold. It also aligns this voltage level with Chapter 9, Table 11(B) 60 V break point. 250.162 Direct-Current Circuits and Systems to Be Grounded. (A) Two-Wire, Direct-Current Systems. A 2-wire, dc system supplying premises wiring and operating at greater than 5060 volts but not greater than 300 volts shall be grounded. Exception No. 1: A system equipped with a ground detector and supplying only industrial equipment in limited areas shall not be required to be grounded where installed adjacent to or integral with the source of supply. Impact(s) : No negative impact. Page 37 of 203 2 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 250.166 Size of the Direct-Current Grounding Electrode Conductor. The size of the grounding electrode conductor for a dc system shall be as specified in 250.166(A) and (B), except as permitted by through 250.166(C) through (E). The grounding electrode conductor for a dc system shall meet the sizing requirements in this section but shall not be required to be larger than 3/0 copper or 250 kcmil aluminum. Change Description: This change fills the gap regarding the required maximum size of a grounding electrode conductor in a DC system. It brings this section into alignment with the similar requirements which exist for AC systems. 250.167 Direct-Current Ground-Fault Detection. Change Description: This new section provides details for ground-fault detection and aligns the requirements with the requirements found in NFPA 70E. (A) Ungrounded Systems. Ground-fault detection systems shall be required for ungrounded systems. (B) Grounded Systems. Ground-fault detection shall be permitted for grounded systems. 2 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. (C) Marking. Direct-current systems shall be legibly marked to indicate the grounding type at the dc source or the first disconnecting means of the system. The marking shall be of sufficient durability to withstand the environment involved. 250.186 Ground-Fault Circuit Conductor Brought to Service Equipment. (A) Systems with a Grounded Conductor at the Service Point. Where an ac system operating at over 1000 volts is grounded at any point and is provided with a grounded conductor at the service point, a grounded conductor(s) shall be installed and routed with the ungrounded conductors to each service disconnecting means and shall be connected to each disconnecting means grounded conductor(s) terminal or bus. A main bonding jumper shall connect the grounded conductor(s) to each service disconnecting means enclosure. The grounded conductor(s) shall be installed in accordance with 250.186(A)(1) through (A)(4). The size of Change Description: This new section provides requirements for a conductor providing a low impedance path for ground fault currents to return to the source on systems over 1000 V. It aligns the requirements for over 1000 V with requirements found in Section 250.24(C) for 1000 V and below systems regarding ground fault return path. Impact(s) : No negative impact. Page 38 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table the solidly grounded circuit conductor(s) shall be the larger of that determined by 250.184 or 250.186(A)(1) or (A)(2). Exception: Where two or more service disconnecting means are located in a single assembly listed for use as service equipment, it shall be permitted to connect the grounded conductor(s) to the assembly common grounded conductor(s) terminal or bus. The assembly shall include a main bonding jumper for connecting the grounded conductor(s) to the assembly enclosure. (1) Sizing for a Single Raceway or Overhead Conductor. The grounded conductor shall not be smaller than the required grounding electrode conductor specified in Table 250.66 but shall not be required to be larger than the largest ungrounded service-entrance conductor(s). In addition, for sets of ungrounded service-entrance conductors larger than 1100 kcmil copper or 1750 kcmil aluminum, the grounded conductor shall not be smaller than 121⁄2 percent of the circular mil area of the largest set of service-entrance ungrounded conductor(s). (2) Parallel Conductors in Two or More Raceways or Overhead Conductors. If the ungrounded service-entrance conductors are installed in parallel in two or more raceways or as overhead parallel conductors, the grounded conductors shall also be installed in parallel. The size of the grounded conductor in each raceway or overhead shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway or overhead, as indicated in 250.186(A)(1), but not smaller than 1/0 AWG. Informational Note: See 310.10(H) for grounded conduc- tors connected in parallel. (3) Delta-Connected Service. The grounded conductor of a 3-phase, 3-wire delta service shall have an ampacity not less than that of the ungrounded conductors. (4) Impedance Grounded Neutral Systems. Impedance grounded neutral systems shall be installed in accordance with 250.187. Page 39 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (B) Systems Without a Grounded Conductor at the Service Point. Where an ac system operating at greater than 1000 volts is grounded at any point and is not provided with a grounded conductor at the service point, a supplyside bonding jumper shall be installed and routed with the ungrounded conductors to each service disconnecting means and shall be connected to each disconnecting means equipment grounding conductor terminal or bus. The supply-side bonding jumper shall be installed in accordance with 250.186(B)(1) through (B)(3). Exception: Where two or more service disconnecting means are located in a single assembly listed for use as service equipment, it shall be permitted to connect the supply-side bonding jumper to the assembly common equipment grounding terminal or bus. (1) Sizing for a Single Raceway or Overhead Conductor. The supply-side bonding jumper shall not be smaller than the required grounding electrode conductor specified in Table 250.66 but shall not be required to be larger than the largest ungrounded service-entrance conductor(s). In addition, for sets of ungrounded service-entrance conductors larger than 1100 kcmil copper or 1750 kcmil aluminum, the supply-side bonding jumper shall not be smaller than 121⁄2 percent of the circular mil area of the largest set of service-entrance ungrounded conductor(s). (2) Parallel Conductors in Two or More Raceways or Overhead Conductors. If the ungrounded service-entrance conductors are installed in parallel in two or more raceways or overhead conductors, the supply-side bonding jumper shall also be installed in parallel. The size of the supplyside bonding jumper in each raceway or overhead shall be based on the total circular mil area of the parallel ungrounded conductors in the raceway or overhead, as indicated in 250.186(A)(1), but not smaller than 1/0 AWG. (3) Impedance Grounded Neutral Systems. Impedance Page 40 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table grounded neutral systems shall be installed in accordance with 250.187. 250.194 Grounding and Bonding of Fences and Other Metal Structures. Metallic fences enclosing, and other metal structures in or surrounding, a substation with exposed electrical conductors and equipment shall be grounded and bonded to limit step, touch, and transfer voltages. (A) Metal Fences. Where metal fences are located within 5 m (16 ft) of the exposed electrical conductors or equipment, the fence shall be bonded to the grounding electrode system with wire-type bonding jumpers as follows: (1) Bonding jumpers shall be installed at each fence corner and at maximum 50 m (160 ft) intervals along the fence. (2) Where bare overhead conductors cross the fence, bonding jumpers shall be installed on each side of the crossing. (3) Gates shall be bonded to the gate support post, and each gate support post shall be bonded to the grounding electrode system. (4) Any gate or other opening in the fence shall be bonded across the opening by a buried bonding jumper. (5) The grounding grid or grounding electrode systems shall be extended to cover the swing of all gates. (6) The barbed wire strands above the fence shall be bonded to the grounding electrode system. Change Description: This proposal is meant to establish basic prescriptive requirements for grounding and bonding of metal fences built in and around substations. For situations where step and touch potential considerations indicate additional grounding and bonding design is required, alternate designs performed under engineering supervision are allowed. Designers are also referred to the industry standard on the grounding of fences in and around substations, which is IEEE 80 Guide for Safety In AC Substation Grounding. Impact(s) : No negative impact – Typically IEEE 80 is followed in design of substation fence grounding. Alternate designs performed under engineering supervision shall be permitted for grounding or bonding of metal fences. Informational Note No. 1: A nonconducting fence or sec- tion may provide isolation for transfer of voltage to other areas. Informational Note No. 2: See IEEE 80-2000, IEEE Guide for Safety In AC Substation Grounding, for design and installation of fence grounding. Page 41 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (B) Metal Structures. All exposed conductive metal structures, including guy wires within 2.5 m (8 ft) vertically or 5 m (16 ft) horizontally of exposed conductors or equipment and subject to contact by persons, shall be bonded to the grounding electrode systems in the area. ARTICLE 285 Surge-Protective Devices (SPDs), 1000 Volts or less 285.13 Type 4 and Other Component Type SPDs. Type Change Description: 4 component assemblies and other component type SPDs Type 4 and 5 SPDs are not standalone devices and are only shall only be installed by the equipment manufacturer. acceptable if provided as a part of listed equipment. This new section makes it into a requirement. 2 Impact(s) : No negative impact. ARTICLE 300 General Requirements for Wiring Methods and Materials 300.22 Wiring in Ducts Not Used for Air Handling, Change Description: Fabricated Ducts for Environmental Air, and Other Section updated to allow MI cable without an overall nonmetallic Spaces for Environmental Air (Plenums). covering for use in Ducts Not Used for Air Handling, Fabricated Ducts for Environmental Air, and Other Spaces for Environmental (B) Ducts Specifically Fabricated for Environmental Air (Plenums). This aligns this section with the wiring methods Air. Equipment, devices, and devices the wiring methods specified in this section shall be permitted within such described in NFPA 90A. ducts only if necessary for the direct action upon, or sensing of, the contained air. Where equipment or devices are installed and illumination is necessary to facilitate maintenance and repair, enclosed gasketed-type luminaires shall be permitted. Impact(s) : No negative impact – Typically NFPA 90A requirements are followed in design. Only wiring methods consisting of Type MI cable without an overall nonmetallic covering, Type MC cable employing a smooth or corrugated impervious metal sheath without an overall nonmetallic covering, electrical metallic Page 42 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table tubing, flexible metallic tubing, intermediate metal conduit, or rigid metal conduit without an overall nonmetallic covering shall be installed in ducts specifically fabricated to transport environmental air. Flexible metal conduit shall be permitted, in lengths not to exceed 1.2 m (4 ft), to connect physically adjustable equipment and devices permitted to be in these fabricated ducts. The connectors used with flexible metal conduit shall effectively close any openings in the connection. 300.22 Wiring in Ducts Not Used for Air Handling, Fabricated Ducts for Environmental Air, and Other Spaces for Environmental Air (Plenums). (C) Other Spaces Used for Environmental Air (Plenums). This section shall apply to spaces not specifically fabricated for environmental air-handling purposes but used for air-handling purposes as a plenum. This section shall not apply to habitable rooms or areas of buildings, the prime purpose of which is not air handling. (1) Wiring Methods. The wiring methods for such other space shall be limited to totally enclosed, nonventilated, insulated busway having no provisions for plug-in connections, Type MI cable without an overall nonmetallic covering, Type MC cable without an overall nonmetallic covering, Type AC cable, or other factory-assembled multiconductor control or power cable that is specifically listed for use within an air-handling space, or listed prefabricated cable assemblies of metallic manufactured wiring systems without nonmetallic sheath. Other types of cables, conductors, and raceways shall be permitted to be installed in electrical metallic tubing, flexible metallic tubing, intermediate metal conduit, rigid metal conduit without an overall nonmetallic covering, flexible metal conduit, or, where accessible, surface metal raceway or metal wireway with metal covers. Nonmetallic cable ties and other nonmetallic cable accessories used to secure and support cables shall be listed as having low smoke and heat release properties. Change Description: Section updated to allow MI cable without an overall nonmetallic covering for use in Ducts Not Used for Air Handling, Fabricated Ducts for Environmental Air, and Other Spaces for Environmental Air (Plenums). This aligns this section with the wiring methods described in NFPA 90A. In addition, this section now requires that cable ties and other cable accessories be listed as having low smoke and low heat generation characteristics. Impact(s) : No negative impact – Typically NFPA 90A requirements are followed in design. Page 43 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 300.38 Raceways in Wet Locations Above Grade. Where raceways are installed in wet locations above grade, the interior of these raceways shall be considered to be a wet location. Insulated conductors and cables installed in raceways in wet locations above grade shall comply with 310.10(C). Change Description: This section applies to systems with voltages over 1000 V and addresses requirements for raceways in wet locations, above ground, aligning it with Section 300.9 for voltages below 1000 V. 2 Impact(s) : No negative impact. 300.45 Warning Signs. Warning signs shall be conspicuously posted at points of access to conductors in all conduit systems and cable systems. The warning sign(s) shall be legible and permanent and shall carry the following wording: DANGER—HIGH VOLTAGE—KEEP OUT Change Description: Added new section to address warning signs at the points of access to conductors operating at voltages above 1000 V. This requirement already exists in articles 314 and 490 (previously in 225). 2 Impact(s) : No negative impact. 300.50 Underground Installations. (A) General. Underground conductors shall be identified for the voltage and conditions under which they are installed. Direct-burial cables shall comply with the provisions of 310.10(F). Underground cables shall be installed in accordance with 300.50(A)(1) ,(A)(2), or (A)(23), and the installation shall meet the depth requirements of Table 300.50. (2) Industrial Establishments. In industrial establishments, where conditions of maintenance and supervision ensure that only qualified persons service the installed cable, nonshielded single-conductor cables with insulation types up to 2000 volts that are listed for direct burial shall be permitted to be directly buried. Change Description: It is a common practice in large utility-scale solar installations to direct bury 2000V rated conductors used to carry power from combiner boxes to the inverter. Since these installations are not accessible to the public and maintenance is controlled by the facility owner, direct buried single conductor installations are appropriate. There are already Listed PV wire products rated at 2000 volts and listed for direct burial, and placing this language in Article 300 ensures that the NEC is ready for other nonPV installations and similarly listed cable types that may be developed in the future. Having the language in 300.50 makes it easy for the code user to reference and apply the appropriate installation requirements, such as depth of burial and warning tape. Impact(s) : Page 44 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table No negative impact. ARTICLE 310 Conductors for General Wiring 310.15 Ampacities for Conductors Rated 0–2000 Volts. Change Description: Exception was added recognizing that cross-linked synthetic (B) Tables. polymer insulation (XHHW-2) is not subject to the melting when exposed to higher temperatures expected on the roof tops. The (3) Adjustment Factors. failure temperature of this type of insulation is in temperatures (c) Circular Raceways and Cables Exposed to Sunlight over 300°C and installations using XHHW-2 type conductors on Rooftops. Where conductorsraceways or cables are inshow no signs of failure even when fully loaded and installed in stalled in circular raceways exposed to direct sunlight on or the hottest regions of the country. above rooftops, the adjustments shown in Table 310.15(B)(3)(c) shall be added to the outdoor temperature to determine the applicable ambient temperature for application of the correction factors in Table 310.15(B)(2)(a) or Table 310.15(B)(2)(b). 2 Impact(s) : No negative impact. Exception: Type XHHW-2 insulated conductors shall not be subject to this ampacity adjustment. ARTICLE 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies: Fittings, and Handholes 314.15 Damp or Wet Locations. In damp or wet locaChange Description: tions, boxes, conduit bodies, outlet box hoods, and fittings The Code now recognizes a common practice of adding weep shall be placed or equipped so as to prevent moisture from holes in the field to prevent accumulation of condensed moisture entering or accumulating within the box, conduit body, or in boxes. This change will improve durability and safety of the fitting. Boxes, conduit bodies, outlet box hoods, and installations. fittings installed in wet locations shall be listed for use in wet locations. Approved drainage openings not larger than 6 mm (1⁄4 in.) shall be permitted to be installed in the field in boxes or conduit bodies listed for use in damp or wet locations. For installa- tion of listed drain fittings, larger openings are permitted to be installed in the field in accordance with manufacturer’s instructions. 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. 2 Impact(s) : No negative impact. Change Description: This change adds a clarity regarding box fill calculation and Page 45 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table considering clamp assemblies in determining a box volume. (B) Box Fill Calculations. (2) Clamp Fill. Where one or more internal cable clamps, whether factory or field supplied, are present in the box, a single volume allowance in accordance with Table 314.16(B) shall be made based on the largest conductor present in the box. No allowance shall be required for a cable connector with its clamping mechanism outside the box. A clamp assembly that incorporates a cable termination for the cable conductors shall be listed and marked for use with specific nonmetallic boxes. Conductors that originate within the clamp assembly shall be included in conductor fill calculations covered in 314.16(B)(1) as though they entered from outside the box. The clamp assembly shall not require a fill allowance, but the volume of the portion of the assembly that remains within the box after installation shall be excluded from the box volume as marked in 314.16(A)(2). 314.25 Covers and Canopies. In completed installations, each box shall have a cover, faceplate, lampholder, or luminaire canopy, except where the installation complies with 410.24(B). Screws used for the purpose of attaching covers, or other equipment, to the box shall be either machine screws matching the thread gauge or size that is integral to the box or shall be in accordance with the manufacturer’s instruction. Impact(s) : No negative impact. Change Description: This change ensures that only screws appropriate for the box are used to attach covers and other equipment. This will prevent use of screws not matching the thread gauge or size and minimize chances for damaging the box in the process of attaching covers or other equipment to the boxes. 2 Impact(s) : No negative impact. 314.28 Pull and Junction Boxes and Conduit Bodies. (A) Minimum Size. (3) Smaller Dimensions. Boxes Listed boxes or listed Change Description: This change allows use of Table 1 (Chapter 9) in establishing number of conductors to be installed in listed conduit bodies meeting conditions described in this section. Page 46 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table conduit bodies of dimensions less than those required in 314.28(A)(1) and (A)(2) shall be permitted for installations of combinations of conductors that are less than the maximum conduit or tubing fill (of conduits or tubing being used) permitted by Table 1 of Chapter 9, provided the box or conduit body has been listed for, and is permanently marked with, the maximum number and maximum size of conductors permitted. Listed conduit bodies of dimensions less than those required in 314.28(A)(2), and having a radius of the curve to the centerline not less than that indicated in Table 2 of Chapter 9 for one-shot and full-shoe benders, shall be permitted for installations of combinations of conductors permitted by Table 1 of Chapter 9. These conduit bodies shall be marked to show they have been specifically evaluated in accordance with this provision. Where the permitted combinations of conductors for which the box or conduit body has been listed are less than the maximum conduit or tubing fill permitted by Table 1 of Chapter 9, the box or conduit body shall be permanently marked with the maximum number and maximum size of conductors permitted. 330.10 Uses Permitted. (A) General Uses. Type MC cable shall be permitted as follows: (11) In wet locations where a corrosion-resistant jacket is provided over the metallic covering and any of the following conditions are met: a. The metallic covering is impervious to moisture. b. A moisture-impervious jacket resistant to moisture is provided under the metal covering. c. The insulated conductors under the metallic cover- ing are listed for use in wet locations, and a corrosion- Impact(s) : No negative impact. ARTICLE 330 Metal-Clad Cable: Type MC Change Description: The revised wording is consistent with the requirements for jackets in UL 1569, which contains the performance requirements that define resistance to moisture. Impact(s) : No negative impact. Page 47 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table resistant jacket is provided over the metallic sheath.locations. 330.30 Securing and Supporting. (B) Securing. Unless otherwise provided, cables shall be secured at intervals not exceeding 1.8 m (6 ft). Cables containing four or fewer conductors sized no larger than 10 AWG shall be secured within 300 mm (12 in.) of every box, cabinet, fitting, or other cable termination. In vertical installations, listed cables with ungrounded conductors 250 kcmil and larger shall be permitted to be secured at intervals not exceeding 3 m (10 ft) 330.30 Securing and Supporting. (D) Unsupported Cables. Type MC cable shall be permitted to be unsupported where the cable: (3) Is Type MC of the interlocked armor type in lengths not exceeding 900 mm (3 ft) from the last point where it is securely fastened and is used to connect equipment where flexibility is necessary to minimize the transmission of vibration from equipment or to provide flexibility for equipment that requires movement after installation. Change Description: Increased support spacing requirements for MC cables with conductors 250 kcmil and larger in vertical installations based on UL Report 12ME07391 demonstrating acceptability of this change. Impact(s) : No negative impact. Change Description: This change allows the use of a MC cable of the interlocked armor type in applications requiring flexibility at terminations with the last support 3 ft or less from the termination point. 2 Impact(s) : No negative impact. ARTICLE 334 Nonmetallic-Sheathed Cable: Types NM, NMC, and NMS 334.40 Boxes and Fittings. Change Description: Clarified the language in this section by changing term “rewiring” (B) Devices of Insulating Material. Switch,Self(typically associated with pulling new wires) to “repair”. This contained switches,outlet, self-contained receptacles, and change also makes it acceptable to install listed self-contained tap nonmetallic-sheathed cable interconnector devices of devices without boxes in exposed or concealed wiring in existing insulating material that are listed shall be permitted to be used without boxes in exposed cable wiring and for rewirbuildings. ingrepair wiring in existing buildings where the cable is concealed and fished.concealed. Openings in such devices shall form a close fit around the outer covering of the cable, and the device shall fully enclose the part of the cable from which any part of the covering has been removed. Where 2 Impact(s) : No negative impact. Page 48 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table connections to conductors are by binding-screw terminals, there shall be available as many terminals as conductors. ARTICLE 338 Service-Entrance Cable: Types SE and USE 338.10 Uses Permitted. Change Description: This new exception removes the requirement to apply 60°C (B) Branch Circuits or Feeders. ampacity rating limitation per 340.80 to USE type cables, which have higher than 60°C temperature rating. (4) Installation Methods for Branch Circuits and Feed- 2 ers. (b) Exterior Installations. In addition to the provisions of this article, service-entrance cable used for feeders or branch circuits, where installed as exterior wiring, shall be installed in accordance with Part I of Article 225. The cable shall be supported in accordance with 334.30. Type USE cable installed as underground feeder and branch circuit cable shall comply with Part II of Article 340. Exception: Single-conductor Type USE and multi-rated USE conductors shall not be subject to the ampacity limitations of Part II of Article 340. Impact(s) : No negative impact. ARTICLE 348 Flexible Metal Conduit: Type FMC 348.30 Securing and Supporting. Change Description: This change allows considering listed flexible metal conduit (A) Securely Fastened. fittings as means of support for the purpose of complying with the code, similar to the provisions for AC and MC type cables (320.30 Exception No. 4: Lengths not exceeding 1.8 m (6 ft) from and 330.30, respectively). the last point where the raceway is securely fastened for Impact(s) : connections within an accessible ceiling to a luminaire(s) or other equipment. For the purposes of this exception, No negative impact. listed flexible metal conduit fittings shall be permitted as a means of support. ARTICLE 350 Page 49 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Liquidtight Flexible Metal Conduit: Type LFMC 350.30 Securing and Supporting. Change Description: Companion change to 348.30 - this change allows considering (A) Securely Fastened. listed liquidtight flexible metal conduit fittings as means of support for the purpose of complying with the code, similar to the Exception No. 4: Lengths not exceeding 1.8 m (6 ft) from provisions for AC and MC type cables (320.30 and 330.30, the last point where the raceway is securely fastened for respectively). connections within an accessible ceiling to a luminaire(s) or other equipment. For the purposes of this exception, listed LFMC fittings shall be permitted as a means of support. 350.42 Couplings and Connectors. Only fittings listed for use with LFMC shall be used. Angle connectors shall not be concealed. Straight LFMC fittings shall be permitted for direct burial where marked. 2 Impact(s) : No negative impact. Change Description: This change identifies limitations for LFMC fittings. It also harmonizes these provisions with the same provisions for LFNC in Section 356.42. 2 Impact(s) : No negative impact. ARTICLE 356 Liquidtight Flexible Nonmetallic Conduit: Type LFNC 356.12 Uses Not Permitted. LFNC shall not be used as Change Description: follows: This change removes the application limitation for LFNC to below 600 V installations. This change is based on the listing for LFNC (4) Where the operating voltage of the contained conduc(UL 1660 and UL White Book, DXOQ) which do not limit LFNC to tors is in excess of 600 volts, nominal, except as per- mitted 600 V. in 600.32(A). Impact(s) : No negative impact. 356.30 Securing and Supporting. Type LFNC-B shall Change Description: be securely fastened and supported in accordance with Companion change to 348.30 - this change allows considering one of the following: listed liquidtight flexible nonmetallic conduit fittings as means of support for the purpose of complying with the code, similar to the 4) Securing or supporting of LFNC-B shall not be reprovisions for AC and MC type cables (320.30 and 330.30, quired where installed in lengths not exceeding 1.8 m (6 Page 50 of 203 2 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ft) from the last point where the raceway is securely fastened for connections within an accessible ceiling to a luminaire(s) or other equipment. For the purpose of 356.30, listed liquidtight flexible nonmetallic conduit fittings shall be permitted as a means of support. respectively). 356.60 Grounding and Bonding.Grounding. Where used to connect equipment where flexibility grounding is required, an a separate equipment grounding conductor shall be installed in the conduit. Where required or installed, equipment grounding conductors shall be installed in accordance with 250.134(B). Where required or installed, equipment bonding jumpers shall be installed in accordance with 250.102. Change Description: This change provides more clarity and harmonizes equipment grounding requirements applicable to LFNC with requirements for other nonmetallic raceways. Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Exception No. 1: As permitted in 250.134(B), Exception No. 2, for dc circuits and 250.134(B), Exception No. 1, for separately run equipment grounding conductors. Exception No. 2: Where the grounded conductor is used to ground equipment as permitted in 250.142. The text of this reorganized article not included for brevity. ARTICLE 370 Cablebus Change Description: Article 370 was reorganized in its entirety to more closely follow Chapter 3 numbering system. 1 Impact(s) : No negative impact. 376.56 Splices, Taps, and Power Distribution Blocks. (B) Power Distribution Blocks. (1) Installation. Power distribution blocks installed in metal wireways shall be listed. Power distribution blocks ARTICLE 376 Metal Wireways Change Description: Added language clarifies the expectation that the power distribution blocks installed on the line side of the service equipment shall be listed for that purpose. In (5) the added text Page 51 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table installed on the line side of the service equipment shall be listed for the purpose. ensures that the conductors do not obstruct block terminals – this requirement is consistent with 314.28(E) applicable to boxes. (5) Conductors. Conductors shall be arranged so the power distribution block terminals are unobstructed following installation. Impact(s) : No negative impact. 386.120 Marking. Each length of surface metal raceway shall be clearly and durably identified as required in the first sentence of 110.21(A). ARTICLE 386 Surface Metal Raceways Change Description: This addition of the clause covering marking to bring consistency with the requirements in other articles for similar products. 2 Impact(s) : No negative impact. ARTICLE 388 Surface Nonmetallic Raceways 388.120 Marking. Surface nonmetallic raceways that have Change Description: limited smoke-producing characteristics shall be permitted to This addition of the clause covering marking to bring consistency be so identified. Each length of surface nonmetallic race- way with the requirements in other articles for similar products. shall be clearly and durably identified as required in the 2 first sentence of 110.21(A). Impact(s) : No negative impact. 392.18 Cable Tray Installation. (H) Marking. Cable trays containing conductors rated over 600 volts shall have a permanent, legible warning notice carrying the wording “DANGER — HIGH VOLTAGE — KEEP AWAY” placed in a readily visible position on all cable trays, with the spacing of warning notices not to exceed 3 m (10 ft). The danger marking(s) or labels shall ARTICLE 392 Cable Trays Change Description: The added exception for industrial applications eliminates the requirement for marking cable trays containing conductors rated over 600V, if the cable tray is not accessible. Impact(s) : Improves safety - no negative impact. Page 52 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table comply with 110.21(B). Exception: Where not accessible (as applied to equipment), in industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, cable tray system warning notices shall be located where necessary for the installation to ensure safe maintenance and operation. 392.20 Cable and Conductor Installation. (A) Multiconductor Cables RatedOperating at 600Volts or Less. Multiconductor cables rated operating at 600 volts or less shall be permitted to be installed in the same cable tray. (B) Cables RatedOperating at Over 600 Volts. Cables rated operating at over 600 volts and those ratedoperating at 600 volts or less installed in the same cable tray shall comply with either of the following: (1) The cables ratedoperating at over 600 volts are Type MC. (2) The cables rated operating at over 600 volts are separated from the cables ratedoperating at 600 volts or less by a solid fixed barrier of a material compatible with the cable tray. Change Description: Replaced term “rated” with “operating at” within the subsection to allow selection of conductor insulation level based on maximum circuit voltage applied to any conductor within the enclosure or raceway, rather than the insulation rating itself. 2 Impact(s) : No negative impact. ARTICLE 393 Low-Voltage Suspended Ceiling Power Distribution Systems The text of this new article not included for Change Description: Added a new Article covering the installation of low-voltage Class brevity. 2 ac and dc suspended ceiling power distribution systems. Impact(s) : No negative impact – improves safety by providing specific requirements for the systems until now not addressed by the code. ARTICLE 400 Page 53 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 400.4 Types. Flexible cords and flexible cables shall conform to the description in Table 400.4. Types 400.4. The use of flexible cords and flexible cables other than those listed in the tableTable 400.4 shall be the subject of special investigation.require permission by the authority having jurisdiction. 400.5 Ampacities for Flexible Cords and Cables. (A) Ampacity Tables. Table 400.5(A)(1) provides the allowable ampacities, and Table 400.5(A)(2) provides the ampacities for flexible cords and cables with not more than three current-carrying conductors. These tables shall be used in conjunction with applicable end-use product standards to ensure selection of the proper size and type. Where cords and cables are used in ambient temperatures other than 30°C (86°F), the temperature correction factors from Table 310.15(B)(2)(a) that correspond to the temperature rating of the cord or cable shall be applied to the ampacity in Table 400.5(A)(1) and Table 400.5(A)(2). Cords and cables rated 105°C shall use correction factors in the 90°C column of Table 310.15(B)(2)(a) for temperature correc- tion. Where the number of current-carrying conductors ex- ceeds three, the allowable ampacity or the ampacity of each conductor shall be reduced from the 3three-conductor rating as shown in Table 400.5(A)(3). Flexible Cords and Cables Change Description: This change requires that flexible cords not listed in Table 400.4 be approved by AHJ prior to application. 2 Impact(s) : Any NEC unlisted flexible cords will require evaluation. Change Description: This change corrects an omission in the 2011 edition of the code which did not require application of temperature correction factors to cables listed in Table 400.5(A)(1). 2 Impact(s) : No negative impact. Change Description: Expanded marking requirements for flexible cords and cables to (A) Standard Markings. Flexible cords and cables shall be include maximum operating temperature. 400.6 Markings. marked by means of a printed tag attached to the coil reel or carton. The tag shall contain the information required in 310.120(A). Types S, SC, SCE, SCT, SE, SEO, SEOO, SJ, Impact(s) : SJE, SJEO, SJEOO, SJO, SJT, SJTO, SJTOO, SO, SOO, ST, No negative impact. STO, STOO, SEW, SEOW, SEOOW, SJEW, SJEOW, SJEOOW, SJOW, SJTW, SJTOW, SJTOOW, SOW, SOOW, STW, STOW, and STOOW flexible cords and G, G- Page 54 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table GC, PPE, and W flexible cables shall be durably marked on the surface at intervals not exceeding 610 mm (24 in.) with the type designation, size, and number of conductors. Required markings on tags, cords, and cables shall also include the maximum operating temperature of the flexible cord or cable. 400.7 Uses Permitted. (A) Uses. Flexible cords and cables shall be used only for the following: (11) Between an existing receptacle outlet and an inlet, where the inlet provides power to an additional single receptacle outlet. The wiring interconnecting the inlet to the single receptacle outlet shall be a Chapter 3 wiring method. The inlet, receptacle outlet, and Chapter 3 wiring method, including the flexible cord and fittings, shall be a listed assembly specific for this application. Change Description: This new provision expands the use of flexible cords and cables to allow new listed products primarily used for flat-screen TV mounted on the wall. 2 Impact(s) : No negative impact. 400.23 Equipment Grounding Conductor Identification. A conductor intended to be used as an equipment grounding conductor shall have a continuous identifying marker readily distinguishing it from the other conductor or conductors. Conductors having a continuous green color or a continuous green color with one or more yellow stripes shall not be used for other than equipment grounding conductors. Cords or cables consisting of integral insulation and a jacket without a nonintegral grounding conductor shall be permitted to be green. The identifying marker shall consist of one of the methods in 400.23(A) or (B). Change Description: This change allows the use of green color for cords or cables with integral insulation and jacket and without a nonintegral grounding conductor. III. Portable Cables Over 600 Volts, Nominal 400.31 Construction. (B) Equipment Grounding Conductor(s). An equipment grounding conductor(s) shall be provided in cables with three or more conductors. The total area shall not be less than that of the size of the equipment grounding conductor required in 250.122. Change Description: Clarifies that two conductor cables are acceptable without a grounding conductor. Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Page 55 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 404.2 Switch Connections. (C) Switches Controlling Lighting Loads. Where switches control lighting loads supplied by a general purpose branch circuit, the The grounded circuit conductor for the controlled lighting circuit shall be provided at the switch location.location where switches control lighting loads that are supplied by a grounded general-purpose branch circuit for other than the following: Exception: The grounded circuit conductor shall be permitted to be omitted from the switch enclosure where either of the following conditions in (1) or (2) apply: ARTICLE 404 Switches Change Description: This change rearranges the Section for clarity and adds five new conditions for which a grounded conductor does not have to be provided at the lighting switch location to accommodate common situation where bringing the grounded conductor would not improve safety or serve other purposes. Impact(s) : No negative impact. (1) Conductors for switches controlling lighting loads enter the box through a raceway. The raceway shall have suffıcient cross-sectional area to accommodate the extension of the grounded circuit conductor of the lighting circuit to the switch location whether or not the conductors in the raceway are required to be increased in size to comply with 310.15(B)(3)(a). Where conductors enter the box enclosing the switch through a raceway, provided that the raceway is large enough for all contained conductors, including a grounded conductor. (2) Cable assemblies for switches controlling lighting loads enter the box through a framing cavity that is open at the top or bottom on the same floor level, or through a wall, floor, or ceiling that is unfinished on one side.Where the box enclosing the switch is accessible for the installation of an additional or replacement cable without removing finish materials (3) Where snap switches with integral enclosures comply with 300.15(E) (4) Where a switch does not serve a habitable room or Page 56 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table bathroom (5) Where multiple switch locations control the same lighting load such that the entire floor area of the room or space is visible from the single or combined switch locations (6) Where lighting in the area is controlled by automatic means (7) Where a switch controls a receptacle load 404.8 Accessibility and Grouping. (C) Multipole Snap Switches. A multipole, general-use snap switch shall not be permitted to be fed from more than a single circuit unless it is listed and marked as a twocircuit or three-circuit switch, or unless its voltage rating is not less than the nominal line-to-line voltage of the system supplying the circuits.switch. 404.10 Mounting of Snap Switches. (B) Box Mounted. Flush-type snap switches mounted in boxes that are set back of the finished surface as permitted in 314.20 shall be installed so that the extension plaster ears are seated against the surface. Flush-type snap switches mounted in boxes that are flush with the finished surface or project from it shall be installed so that the mounting yoke or strap of the switch is seated against the box. Screws used for the purpose of attaching a snap switch to a box shall be of the type provided with a listed snap switch, or shall be machine screws having 32 threads per inch or part of listed assemblies or systems, in accordance with the manufacturer’s instructions. Change Description: The language added in 2008 NEC allowing use of snap switches on more than a single branch circuit is removed from this edition of the code for switches not specifically listed for such an application. 2 Impact(s) : No negative impact. Change Description: This change provides specific requirements for screws used in mounting snap switches to ensure that inappropriate screws which could potentially damage the switch are not being utilized. 2 Impact(s) : No negative impact. ARTICLE 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) 406.3 Receptacle Rating and Type. Change Description: This change introduces a requirement for marking automatically Page 57 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (E) Controlled Receptacle Marking. All nonlockingtype, 125-volt, 15- and 20-ampere receptacles that are controlled by an automatic control device, or that incorporate control features that remove power from the outlet for the purpose of energy management or building automation, shall be marked with the symbol shown in Figure 406.3(E) and located on the controlled receptacle outlet where visible after installation. controlled receptacles. Impact(s) : No negative impact. Exception: The marking is not required for receptacles controlled by a wall switch that provide the required room lighting outlets as permitted by 210.70. 406.4 General Installation Requirements. (A) Grounding Type. Except as provided in 406.4(D), Rreceptacles installed on 15- and 20-ampere branch circuits shall be of the grounding type. Grounding-type receptacles shall be installed only on circuits of the voltage class and current for which they are rated, except as provided in Table 210.21(B)(2) and Table 210.21(B)(3). Exception: Nongrounding-type receptacles installed in accordance with 406.4(D). Change Description: This requirement expands the accessibility of receptacles requiring testing (GFCI, AFCI) to replacement receptacles. Also, a new exception allows replacement of a receptacle which would otherwise be required to be of a GFCI type with the existing type (not GFCI) if the receptacle is protected by an upstream GFCI device. Impact(s) : No negative impact. D) Replacements. Replacement of receptacles shall comply with 406.4(D)(1) through (D)(6), as applicable. Arcfault circuit-interrupter type and ground-fault circuitinterrupter type receptacles shall be installed in a readily accessible location. (3) Ground-Fault Circuit Interrupters. Ground-fault circuit-interrupter protected receptacles shall be provided where replacements are made at receptacle outlets that are required to be so protected elsewhere in this Code. Exception: Where replacement of the receptacle type is impracticable, such as where the outlet box size will not permit the installation of the GFCI receptacle, the recep- Page 58 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table tacle shall be permitted to be replaced with a new receptacle of the existing type, where GFCI protection is provided and the receptacle is marked “GFCI protected” and “no equipment ground,” in accordance with 406.4(D)(2) (a), (b), or (c). 406.5 Receptacle Mounting. Receptacles shall be mounted in identified boxes or assemblies designed for the purpose, and suchassemblies. The boxes or assemblies shall be securely fastened in place unless otherwise permitted elsewhere in this Code. Screws used for the purpose of attaching receptacles to a box shall be of the type provided with a listed receptacle, or shall be machine screws having 32 threads per inch or part of listed assemblies or systems, in accordance with the manufacturer’s instructions. Change Description: This change provides specific requirements for screws used in mounting receptacles to ensure that inappropriate screws which could potentially damage the receptacle are not being utilized. 406.5 Receptacle Mounting. Change Description: This change expands requirements for receptacles mounted in countertops (face-up) to all occupancies and provides criteria for GFCI protection. It also adds specific criteria for receptacles in seating areas in a face-up position. (E) Receptacles in Countertops and Similar Work Surfaces in Dwelling Units.Surfaces. Receptacles, unless listed as receptacle assemblies for countertop applications, shall not be installed in a face-up position in countertops or similar work surfaces. Where receptacle assemblies for countertop applications are required to provide ground-fault circuit-interrupter protection for personnel in accordance with 210.8, such assemblies shall be permitted to be listed as GFCI receptacle assemblies for countertop applications. Impact(s) : No negative impact. Impact(s) : No negative impact. (F) Receptacles in Seating Areas and Other Similar Surfaces. In seating areas or similar surfaces, receptacles shall not be installed in a face-up position unless the receptacle is any of the following: (1) Part of an assembly listed as a furniture power distribution unit, if cord-and plug-connected 2) Part of an assembly listed either as household furnishings or as commercial furnishings (3) Listed either as a receptacle assembly for countertop applications or as a GFCI receptacle assembly for Page 59 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table countertop applications (4) Installed in a listed floor box 406.9 Receptacles in Damp or Wet Locations. (B) Wet Locations. (1) Receptacles of 15 and 20-Amperes Receptacles in a Wet Location. 15- and 20-ampere, 125- Receptacles of 15 and 250-volt receptacles20 amperes, 125 and 250 volts installed in a wet loca- tion shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. For other than one- or two-family dwellings, an An outlet box hood installed for this purpose shall be listed and where installed on an enclosure supported from grade as described in 314.23(B) or as described in 314.23(F) shall be identified as “extra duty.” All 15and 20-ampere, 125- and 250-volt nonlocking-type receptacles shall be listed weather- resistant type. 406.15 Dimmer-Controlled Receptacles. A receptacle supplying lighting loads shall not be connected to a dimmer unless the plug/receptacle combination is a nonstandard configuration type that is specifically listed and identified for each such unique combination. Change Description: Revision to this section expands requirements for an “extra duty” outlet box hood in wet locations, regardless of occupancy and enclosure mounting method. 2 Impact(s) : No negative impact. Change Description: New section added restricting regarding dimmer control of receptacles. 2 Impact(s) : No negative impact. ARTICLE 408 Switchboards, Switchgear, and Panelboards 408.3 Support and Arrangement of Busbars and ConChange Description: ductors. This new subsection provides criteria for DC bus arrangement. (E) Bus Arrangement. Impact(s) : (2) DC Bus Arrangement. Direct-current ungrounded buses No negative impact. shall be permitted to be in any order. Arrangement of dc buses shall be field marked as to polarity, grounding system, and Page 60 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table nominal voltage. 408.3 Support and Arrangement of Busbars and Conductors. (F) Switchboard, Switchgear, or Panelboard Identification. (3) High-Impedance Grounded Neutral AC System. A switchboard, switchgear, or panelboard containing a highimpedance grounded neutral ac system in accordance with 250.36 shall be legibly and permanently field marked as follows: Change Description: This new subsection requires permanent marking of electrical distribution equipment fed from a high-impedance grounded, ungrounded DC, and resistively grounded DC systems. Impact(s) : No negative impact. CAUTION: HIGH-IMPEDANCE GROUNDED NEUTRAL AC SYSTEM OPERATING — VOLTS BETWEEN CONDUCTORS AND MAY OPERATE --VOLTS TO GROUND FOR INDEFINITE PERIODS UNDER FAULT CONDITIONS (4) Ungrounded DC Systems. A switchboard, switchgear, or panelboard containing an ungrounded dc electrical system in accordance with 250.169 shall be legibly and permanently field marked as follows: CAUTION: UNGROUNDED DC SYSTEM OPERATING — VOLTS BETWEEN CONDUCTORS (5)) Resistively Grounded DC Systems. A switchboard, switchgear, or panelboard containing a resistive connection between current-carrying conductors and the grounding system to stabilize voltage to ground shall be legibly and permanently field marked as follows: CAUTION: DC SYSTEM OPERATING --VOLTS BETWEEN CONDUCTORS AND MAY OPERATE — VOLTS TO GROUND FOR INDEFINITE PERIODS UNDER FAULT CONDITIONS Page 61 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 408.55 Wire-Bending Space Within an Enclosure Containing a Panelboard. (A) Top and Bottom Wire-Bending Space. The enclosure for a panelboard shall have the top and bottom wirebending space sized in accordance with Table 312.6(B) for the largest conductor entering or leaving the enclosure. Side wire-bending space shall be in accordance with Table 312.6(A) for the largest conductor to be terminated in that space. Change Description: The revision expands the wire bending criteria to include back wire-bending space. 2 Impact(s) : No negative impact. (B) Side Wire-Bending Space. Side wire-bending space shall be in accordance with Table 312.6(A) for the largest conductor to be terminated in that space. (C) Back Wire-Bending Space. Where a raceway or cable entry is in the wall of the enclosure opposite a removable cover, the distance from that wall to the cover shall be permitted to comply with the distance required for one wire per terminal in Table 312.6(A). The distance between the center of the rear entry and the nearest termination for the entering conductors shall not be less than the distance given in Table 312.6(B). ARTICLE 410 Luminaires, Lampholders, and Lamps 410.10 Luminaires in Specific Locations. Change Description: This new subsection provides specific requirements for a (F) Luminaires Installed in or Under Roof Decking. Ludistance of luminaires from a metal corrugated roof decking. It minaires installed in exposed or concealed locations under minimizes a chance for damage of electrical components by roof metal-corrugated sheet roof decking shall be installed and material fasteners. supported so there is not less than 38 mm (11⁄2 in.) meaImpact(s) : sured from the lowest surface of the roof decking to the top of the luminaire. No negative impact. 410.23 Covering of Combustible Material at Outlet Boxes. Any combustible wall or ceiling finish exposed be- Change Description: Page 62 of 203 2 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table tween the edge of a luminaire canopy or pan and an outlet box having a surface area of 1160 mm2 (180 in.2) or more shall be covered with noncombustible material. This revision aligns Section 410.23 with UL 1598, ensuring that larger boxes (not covered by UL 1598) do not overheat adjacent combustible wall and ceiling materials. Impact(s) : No negative impact. XII. Special Provisions for Electric-Discharge Lighting Systems of 1000 Volts or Less 410.130 General. Change Description: This revision eliminates an exception for installation of disconnect switches for electric-discharge lighting over 1000 V in industrial establishments. 2 (G) Disconnecting Means. (1) General. In indoor locations other than dwellings and associated accessory structures, fluorescent luminaires that utilize double-ended lamps and contain ballast(s) that can be serviced in place shall have a disconnecting means either internal or external to each luminaire. For existing installed luminaires without disconnecting means, at the time a ballast is replaced, a disconnecting means shall be installed. The line side terminals of the disconnecting means shall be guarded. Impact(s) : Elimination of this exception improves safety of personnel performing maintenance/repair work on electric-discharge lighting over 1000 V in industrial establishments. Exception No. 4: A disconnecting means shall not be required in industrial establishments with restricted public access where conditions of maintenance and supervision ensure that only qualified persons service the installation by written procedures. ARTICLE 411 Lighting Systems Operating at 30 Volts or Less and Lighting Equipment Connected to Class 2 Power Sources 411.1 Scope. This article covers lighting systems operating Change Description: 1 at 30 volts or less and their associated components. This This revision provides clarification that the scope of the section article also covers lighting equipment connected to a Class Page 63 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 2 power source includes lighting equipment connected to a Class 2 power source. Impact(s) : No negative impact. 411.2411.3 Definition.Low-Voltage Lighting Systems. (A) General. Lighting Ssystems Ooperating at 30 Voltsvolts or Less. A lighting system consisting less shall consist of an isolating power supply, the low-voltage luminaires, and associated equipment that are all identified for the use. The output circuits of the power supply are shall be rated for not more than 25 amperes and operate at 30 volts (42.4 volts peak) or lessmaximum under all load conditions. Change Description: This revision better correlates this section with Article 725 and Chapter 9 Tables for Class 2 listed lighting systems. 2 Impact(s) : No negative impact. (B) Class 2. Listed Class 2 lighting equipment shall be rated in conformance with Chapter 9, Table 11(A) or Table 11(B). 411.3411.4 Listing Required. Lighting systems operating at 30 volts or less shall comply with 411.3(A)411.4(A) or 411.3(B).411.4(B). Class 2 power sources and lighting equipment connected to Class 2 power sources shall be listed. 422.5 Ground-Fault Circuit-Interrupter (GFCI) Protection. The device providing GFCI protection required in this article shall be readily accessible. 422.11 Overcurrent Protection. Appliances shall be protected against overcurrent in accordance with 422.11(A) through (G) and 422.10. (F) Electric Heating Appliances Employing Resistance- ARTICLE 422 Appliances Change Description: This added section aligns requirements for accessibility of GFCI protection device with Section 210.8. Impact(s) : No negative impact. Change Description: Rearranged this section for better clarity and added low-pressure water heater tanks and open outlet water heater vessels to the scope. Page 64 of 203 2 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Type Heating Elements Rated More Than 48 Amperes. (3) Water Heaters and Steam Boilers. Water heaters and steam boilers employing resistance-type Resistance-type immersion electric heating elements contained in an ASME-rated and stamped vessel or listed instantaneous water heaters shall be permitted to be subdivided into circuits not exceeding 120 amperes and protected at not more than 150 amperes. as follows: (1) Where contained in ASME-rated and stamped vessels (2) Where included in listed instantaneous water heaters (3) Where installed in low-pressure water heater tanks or open-outlet water heater vessels 422.19 Space for Conductors. Canopies of ceilingsuspended (paddle) fans and outlet boxes taken together shall provide sufficient space so that conductors and their connecting devices are capable of being installed in accordance with 314.16. 422.20 Outlet Boxes to Be Covered. In a completed installation, each outlet box shall be provided with a cover unless covered by means of a ceiling-suspended (paddle) fan canopy. Impact(s) : No negative impact. Change Description: Added three new sections addressing criteria for ceiling fan outlet boxes and their installation. 2 Impact(s) : No negative impact. 422.21 Covering of Combustible Material at Outlet Boxes. Any combustible ceiling finish exposed between the edge of a ceiling-suspended (paddle) fan canopy or pan and an outlet box shall be covered with noncombustible material. 422.23 Tire Inflation and Automotive Vacuum Machines. Tire inflation machines and automotive vacuum machines provided for public use shall be protected by a ground-fault circuit interrupter. Change Description: Added a requirement for GFCI protection for tire inflation and automotive vacuum machines provided for public use. Impact(s) : No negative impact. Page 65 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 422.31 Disconnection of Permanently Connected Appliances. C) Motor-Operated Appliances Rated over 1⁄8 Horsepower. For permanently connected motor-operated appliances with motors rated over 1⁄8 horse power, the branchcircuit switch or circuit breaker shall be permitted to serve as the disconnecting means where the switch or circuit breaker is within sight from the appliance. The disconnecting means shall comply with 430.109 and 430.110. For permanently connected motor-operated appliances with motors rated over 1⁄8 hp, the disconnecting means shall meet 422.31(C)(1) or (2). (1) The branch-circuit switch or circuit breaker shall be permitted to serve as the disconnecting means where the switch or circuit breaker is within sight from the appliance. (2) The disconnecting means shall be installed within sight of the appliance. 422.51 Cord-and-Plug-Connected Vending Machines. B) Other Than Cord-and Plug-Connected. Vending machines not utilizing a cord and plug connection shall be connected to a ground-fault circuit-interrupter protected circuit. Change Description: Section rearranged for clarity. Impact(s) : No negative impact. Change Description: This new subsection expands GFCI protection to hard-wired vending machines. 2 Impact(s) : No negative impact. ARTICLE 424 Fixed Electric Space-Heating Equipment 424.66 Installation. Change Description: (A) General. Duct heaters shall be installed in accordance The addition to this section provides specific criteria for electric with the manufacturer’s instructions in such a manner that space heaters that are mounted on duct systems. operation does not create a hazard to persons or property. Furthermore, duct heaters shall be located with respect to building construction and other equipment so as to permit access to the heater. Sufficient clearance shall be maintained to permit replacement of controls and heating ele- 1 Impact(s) : No negative impact. Page 66 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ments and for adjusting and cleaning of controls and other parts requiring such attention. See 110.26. Working space about electrical enclosures for resistance heating element–type duct heaters that are mounted on duct systems and contain equipment that requires examination, adjustment, servicing, or maintenance while energized shall comply with 424.66(B). (B) Limited Access. Where the enclosure is located in a space above a ceiling, all of the following shall apply: (1) The enclosure shall be accessible through a lay-in type ceiling or an access panel(s). (2) The width of the working space shall be the width of the enclosure or a minimum of 762 mm (30 in.), whichever is greater. (3) All doors or hinged panels shall open to at least 90 degrees. (4) The space in front of the enclosure shall comply with the depth requirements of Table 110.26(A)(1). A horizontal ceiling T-bar shall be permitted in this space. ARTICLE 430 Motors, Motor Circuits, and Controllers 430.52 Rating or Setting for Individual Motor Circuit. Change Description: (C) Rating or Setting. Clarified language addressing fusing for protection of electronic (5) Power Electronic Devices. SuitableSemiconductor devices and expanded protection coverage to include associated fuses intended for the protection of electronic devices shall electromechanical devices and conductors. be permitted in lieu of devices listed in Table 430.52 for power electronic devices, associated electromechanical devices (such as bypass contactors and isolation contactors), and conductors in a solid-state motor controller system, provided that the marking for replacement fuses is provided adjacent to the fuses. Impact(s) : No negative impact. 430.53 Several Motors or Loads on One Branch Circuit. (D) Single Motor Taps. For group installations described above, the conductors of any tap supplying a single motor shall not be required to have an individual branch-circuit short-circuit and ground-fault protective device, provided Change Description: The revised language in (2) clarifies where the 25 ft measurement is intended to reference, and improves readability. The revised language in (3) clarifies that the 10ft tap rule applies Page 67 of 203 2 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table they comply with one of the following: (2) No conductor to the motor shall have an ampacity less than one-third that of the branch-circuit conductors, with a minimum in accordance with 430.22, the. The conductors from the point of the tap to the motor overload device being shall be not more than 7.5 m (25 ft) long and beingbe protected from physical damage by being enclosed in an approved raceway or by use of other approved means. (3) Conductors from the branch-circuit short-circuit and ground-fault protective device to a listed manual motor controller additionally marked “Suitable for Tap Conductor Protection in Group Installations,” or to a branch-circuit protective device, shall be permitted to have an ampacity not less than one-tenth the rating or setting of the branch-circuit short-circuit and ground- fault protective device. The conductors from the controller to the motor shall have an ampacity in accordance with 430.22. The conductors from the branch-circuit shortcircuit and ground-fault protective device point of the tap to the controller(s) shall (1) be suitably protected from physical damage and enclosed either by an enclosed controller or by a raceway and be not more than 3 m (10 ft) long or (2) have an ampacity not less than that of the branch-circuit conductors to the tap conductors and is consistent with (2). 430.130 Branch-Circuit Short-Circuit and GroundFault Protection for Single Motor Circuits Containing Power Conversion Equipment. (A) Circuits Containing Power Conversion Equipment. Circuits containing power conversion equipment shall be protected by a branch-circuit short-circuit and ground-fault protective device in accordance with the following: (1) The rating and type of protection shall be determined by 430.52(C)(1), (C)(3), (C)(5), or (C)(6), using the full-load current rating of the motor load as determined by 430.6. (2) Where maximum branch-circuit short-circuit and ground-fault protective ratings are stipulated for specific Change Description: New sections 430.130 and 430.131 are proposed to deal with the special requirements of the adjustable speed drive controller overcurrent protection functions. Impact(s) : No negative impact. Impact(s) : No negative impact. Page 68 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table device types in the manufacturer’s instructions for the power conversion equipment or are otherwise marked on the equipment, they shall not be exceeded even if higher values are permitted by 430.130(A)(1). (3) A self-protected combination controller shall only be permitted where specifically identified in the manufacturer’s instructions for the power conversion equipment or if otherwise marked on the equipment. (B) Bypass Circuit/Device. Branch-circuit short-circuit and ground-fault protection shall also be provided for a bypass circuit/device(s). Where a single branch-circuit short-circuit and ground-fault protective device is provided for circuits containing both power conversion equipment and a bypass circuit, the branch-circuit protective device type and its rating or setting shall be in accordance with those determined for the power conversion equipment and for the bypass circuit/device(s) equipment. 430.131 Several Motors or Loads on One Branch Circuit Including Power Conversion Equipment. For installations meeting all the requirements of 430.53 that include one or more power converters, the branch-circuit shortcircuit and ground-fault protective fuses or inverse time circuit breakers shall be of a type and rating or setting permitted for use with the power conversion equipment using the full-load current rating of the connected motor load in accordance with 430.53. For the purposes of 430.53 and 430.131, power conversion equipment shall be considered to be a motor controller. 445.11 Marking. Each generator shall be provided with a nameplate giving the manufacturer’s name, the rated fre- ARTICLE 445 Generators Change Description: This revision expands the requirements for marking generators Page 69 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table quency, power factor, the number of phases if of alternating current, ac, the subtransient and transient impedances, the rating in kilowatts or kilovolt-amperes, the normal volts and amperes corresponding to the rating, the rated revolutions per minute, insulation system class and the rated ambient temperature or rated temperature rise, and time rating. rise. Nameplates for all stationary generators and portable generators rated more than 15 kW shall also give the power factor, the subtransient and transient impedances, the insulation system class, and the time rating. Marking shall be provided by the manufacturer to indicate whether or not the generator neutral is bonded to the generator frame. Where the bonding of a generator is modified in the field, additional marking shall be required to indicate whether the generator neutral is bonded to the generator frame. rated above 15 kW to include additional information required for the supplemental power system designer and the end user. Some of the information to be provided on the nameplate is no longer required for generators rated 15kW and below. 445.16 Bushings. Where wires passfield-installed wiring passes through an opening in an enclosure, a conduit box, or a barrier, a bushing shall be used to protect the conduc- tors from the edges of an opening having sharp edges. The bushing shall have smooth, well-rounded surfaces where it may be in contact with the conductors. If used where oils, grease, or other contaminants may be present, the bushing shall be made of a material not deleteriously affected. Change Description: Revised for better clarity. 445.17 Generator Terminal Housings. Generator terminal housings shall comply with 430.12. Where a horsepower rating is required to determine the required minimum size of the generator terminal housing, the full-load current of the generator shall be compared with comparable motors in Table 430.247 through Table 430.250. The higher horsepower rating of Table 430.247 and Table 430.250 shall be used whenever the generator selection is between two ratings. Exception: This section shall not apply to generators rated over 600 volts. Change Description: Table 430.12 only applies to generators rated less than 600 volts. The sizes shown are too small for 15 kV conductors. See Article 430 Part XI for over 600 volts. Impact(s) : No negative impact. 1 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 70 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 445.18 Disconnecting Means Required for Generators. Generators shall be equipped with a disconnect(s), lockable in the open position by means of which the generator and all protective devices and control apparatus are able to be disconnected entirely from the circuits supplied by the generator except where both of the following conditions apply: (1) The driving means for the generator can be readily shut down.Portable generators are cord- and plug- connected, or (2) Both of the following conditions apply: a. The driving means for the generator can be readily shut down, is rendered incapable of restarting, and is lockable in the OFF position in accordance with 110.25. (2)b. The generator is not arranged to operate in parallel with another generator or other source of voltage. Change Description: This change is partially based on the requirements found in UL 2200 which mandates a means to stop the driving means, prevent restarting, and requires the means to be lockable in OFF position. 445.19 Generators Supplying Multiple Loads. A single generator supplying more than one load, or multiple generators operating in parallel, shall be permitted to supply either of the following: (1) A vertical switchboard with separate sections (2) Individual enclosures with overcurrent protection tapped from a single feeder for load separation and distribution if a generator(s) is provided with overcur- rent protection meeting the requirements of 240.15(A). Change Description: This section has been deleted recognizing because the Article covering generators should not place restrictions on, or otherwise address, what a generator can supply. 445.20 Ground-Fault Circuit-Interrupter Protection for Receptacles on 15-kW or Smaller Portable Generators. All 125-volt, single-phase, 15- and 20-ampere receptacle outlets that are a part of a 15-kW or smaller portable generator either shall have ground-fault circuit-interrupter protection for personnel integral to the generator or receptacle or shall not be available for use when the 125/250-volt locking-type receptacle is in use. If the generator was manufactured or remanufactured prior to January 1, 2015, listed cord sets or devices incorporating listed Change Description: This new section adds a requirement for GFCI protection for 15and 20-ampere receptacles mounted on portable generators, rated 15 kW or less, used frequently in camping, construction, and loss of power situations). This addition provides better protection to personnel utilizing portable equipment fed from such a generator. 2 Impact(s) : Improves safety – no negative impact. 1 Impact(s) : No negative impact. Page 71 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ground-fault circuit-interrupter protection for personnel identified for portable use shall be permitted. If the generator does not have a 125/250-volt locking-type receptacle, this requirement shall not apply. Impact(s) : No negative impact. ARTICLE 450 Transformers and Transformer Vaults (including Secondary Ties) 450.5 Grounding Autotransformers. Grounding auChange Description: totransformers covered in this section are zigzag or Added new exception which allows the use of a special grounding T-connected transformers connected to 3-phase, 3-wire unautotransformer which does not permit neutral or ground-fault grounded systems for the purpose of creating a 3-phase, current to return over the line connection to be installed on the 4-wire distribution system or providing a neutral point for load side of the system grounding connection. This change grounding purposes. Such transformers shall have a conallows the use of a device which provides equally safe installation tinuous per-phase current rating and a continuous neutral current rating. Zigzag-connected transformers shall not be but is less expensive, smaller, and more energy efficient. installed on the load side of any system grounding connection, including those made in accordance with 250.24(B), 250.30(A)(1), or 250.32(B), Exception No. 1. Exception: An auto transformer with a wye configuration on its line side and a zigzag configuration on its load side that does not permit neutral or ground-fault current to return over the line connection shall be permitted on the load side of a system grounding connection. This exception shall not apply to a connection made from a high-resistance grounded system applied in accordance with 250.36 450.10 Grounding. (A) Dry-Type Transformer Enclosures. Where separate equipment grounding conductors and supply-side bonding jumpers are installed, a terminal bar for all grounding and bonding conductor connections shall be secured inside the transformer enclosure. The terminal bar shall be bonded to the enclosure in accordance with 250.12 and shall not be installed on or over any vented portion of the enclosure. Exception: Where a dry-type transformer is equipped with wire-type connections (leads), the grounding and bonding connections shall be permitted to be connected together using any of the methods in 250.8 and shall be bonded to 2 Impact(s) : No negative impact. Change Description: This new subsection eliminates a common practice of connecting grounding and bonding conductors at or over the venting openings resulting in less effective connection. The requirement for a terminal bar eliminates inconsistencies in installation and provides more effective connection. Impact(s) : Improves safety – no negative impact. Page 72 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table the enclosure if of metal. (B) Other Metal Parts. Where grounded, exposed non– current-carrying metal parts of transformer installations, including fences, guards, and so forth, shall be grounded and bonded under the conditions and in the manner specified for electrical equipment and other exposed metal parts in Parts V, VI, and VII of Article 250. 450.11 Marking. (B) Source Marking. A transformer shall be permitted to be supplied at the marked secondary voltage, provided that the installation is in accordance with the manufacturer’s instructions. Change Description: This added subsection clarifies that connecting a transformer in reverse (i.e., supply connected to the secondary winding) is only allowed if in accordance with manufacturer’s instructions. 2 Impact(s) : Improves safety – no negative impact. 480.3 Battery and Cell Terminations. (A) Dissimilar Metals. Where mating dissimilar metals, antioxidant material suitable for the battery connection shall be used. (B) Intercell and Intertier Conductors and Connections. The ampacity of field-assembled intercell and intertier connectors and conductors shall be of such crosssectional area that the temperature rise under maximum load conditions and at maximum ambient temperature shall not exceed the safe operating temperature of the conductor insulation or of the material of the conductor supports. (C) Battery Terminals. Electrical connections to the battery, and the cable(s) between cells on separate levels or racks, shall not put mechanical strain on the battery terminals. Terminal plates shall be used where practicable. 480.6 DC Disconnect Methods. (B) Remote Actuation. Where controls to activate the disconnecting means of a battery are not located within sight of a stationary battery system, the disconnecting means ARTICLE 480 Storage Batteries Change Description: New Section provides requirements for antioxidant material used on battery terminals, correlates this section with Section 668.12(B), and addresses strain put on terminals by weight of cables. 2 Impact(s) : No negative impact. Change Description: New subsections address requirements for remotely actuated DC disconnecting means, disconnect incorporated into a busway, Page 73 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table shall be capable of being locked in the open position, in accordance with 110.25, and the location of the controls shall be field marked on the disconnecting means. (C) Busway. Where a DC busway system is installed, the disconnecting means shall be permitted to be incorporated into the busway. and marking of the disconnecting means. Impact(s) : No negative impact. (D) Notification. The disconnecting means shall be legibly marked in the field. A label with the marking shall be placed in a conspicuous location near the battery if a disconnecting means is not provided. The marking shall be of sufficient durability to withstand the environment involved and shall include the following: (1) Nominal battery voltage (2) Maximum available short-circuit current derived from the stationary battery system (3) Date the calculation was performed 480.7 Insulation of Batteries of over 250 Volts. The provisions of 480.6 shall apply to storage batteries having the cells connected so as to operate at a nominal voltage exceeding 250 volts, and, in addition, the provisions of this section shall also apply to such batteries. Cells shall be installed in groups having a total nominal voltage of not over 250 volts. Insulation, which can be air, shall be provided between groups and shall have a minimum separation between live battery parts of opposite polarity of 50 mm (2 in.) for battery voltages not exceeding 600 volts. Change Description: This section was deleted due to its lack of clarity. In addition, it did not improve safety but was reducing the reliability of the battery systems. 480.8 Racks and Trays. (C) Accessibility. The terminals of all cells or multi-cell units shall be readily accessible for readings, inspection, and cleaning where required by the equipment design. One side of transparent battery containers shall be readily accessible for inspection of the internal components. Change Description: Added definition clarifies expectations regarding accessibility of battery racks and trays for inspections. 2 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 74 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 480.9 Battery Locations. Battery locations shall conform to 480.9(A), (B), and (C). (A) Ventilation. Provisions appropriate to the battery technology shall be made for sufficient diffusion and ventilation of the gases from the battery, if present, to prevent the accumulation of an explosive mixture. (C) Working Space.Spaces About Battery Systems. Working space Spaces about the battery systems shall comply with 110.26. Working clearancespace shall be measured from the edge of the batteryrack cabinet, racks, or trays. For battery racks, there shall be a minimum clearance of 25 mm (1 in.) between a cell container and any wall or structure on the side not requiring access for maintenance. Battery stands shall be permitted to contact adjacent walls or structures, provided that the battery shelf has a free air space for not less than 90 percent of its length. Change Description: This added language covers installation aspects which were originally addressed in NFPA 70E and deleted in 2009 edition of that code. This change was developed as a joint effort of the NEC DC Task Force and IEEE Stationary Battery Code Working Group. Impact(s) : No negative impact – improves safety. Informational Note: Additional space is often needed to accommodate battery hoisting equipment, tray removal, or spill containment. (D) Top Terminal Batteries. Where top terminal batteries are installed on tiered racks, working space in accordance with the battery manufacturer’s instructions shall be pro- vided between the highest point on a cell and the row or ceiling above that point. Informational Note: Battery manufacturer’s installation in- structions typically define how much top working space is necessary for a particular battery model. (E) Egress. A personnel door(s) intended for entrance to, and egress from, rooms designated as battery rooms shall open in the direction of egress and shall be equipped with listed panic hardware. (F) Piping in Battery Rooms. Gas piping shall not be Page 75 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table permitted in dedicated battery rooms. (G) Illumination. Illumination shall be provided for work- ing spaces containing battery systems. The lighting outlets shall not be controlled by automatic means only. Additional lighting outlets shall not be required where the work space is illuminated by an adjacent light source. The location of luminaires shall not: (1) Expose personnel to energized battery components while performing maintenance on the luminaires in the battery space; or (2) Create a hazard to the battery upon failure of the luminaire. ARTICLE 490 Equipment Over 6001000 Volts, Nominal 490.21 Circuit-Interrupting Devices. Change Description: (B) Power Fuses and Fuseholders. Change associated with deletion of Section 225.70(A). Added (6) Fuseholders. Fuseholders shall be designed or inrequirement for a field label alerting the worker to the danger stalled so that they are de-energized while a fuse is being associated with replacing fuses. replaced. A field-applied permanent and legible sign, in accordance with 110.21(B), shall be installed immediately adjacent to the fuseholders and shall be worded as follows: DANGER — DISCONNECT CIRCUIT BEFORE REPLACING FUSES. Exception: Fuses and fuseholders designed to permit fuse replacement by qualified persons using equipment designed for the purposeidentified equipment without de-energizing the fuseholder shall be permitted. 490.25 Backfeed. Installations where the possibility of backfeed exists shall comply with (a) and (b), which follow. 2 Impact(s) : No negative impact – improves safety. Change Description: Modified the requirement originally provided in Section 225.70(A)(4) which was deleted in this edition of the code. (a) A permanent sign in accordance with 110.21(B) Page 76 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table shall be installed on the disconnecting means enclosure or immediately adjacent to open disconnecting means with the following words or equivalent: DANGER — CONTACTS ON EITHER SIDE OF THIS DEVICE MAY BE ENERGIZED BY BACKFEED. (b) A permanent and legible single-line diagram of the local switching arrangement, clearly identifying each point of connection to the high-voltage section, shall be provided within sight of each point of connection. Impact(s) : No negative impact. 490.35 Accessibility of Energized Parts. (A) High-Voltage Equipment. Doors that would provide unqualified persons access to high-voltage energized parts shall be locked. Permanent signs in accordance with 110.21(B) shall be installed on panels or doors that provide access to live parts over 1000 volts and shall read DANGER — HIGH VOLTAGE — KEEP OUT Change Description: Added the requirement originally provided in Section 225.70(A)(5) which was deleted in this edition of the code. 490.47 Metal-Enclosed and Metal-CladSwitchgear Used as Service Equipment. Metal-enclosed and metalclad switchgear Switchgear installed as high-voltage service equipment shall include a ground bus for the connection of service cable shields and to facilitate the attachment of safety grounds for personnel protection. This bus shall be extended into the compartment where the service conductors are terminated. Where the compartment door or panel provides access to parts that can only be de-energized and visibly isolated by the serving utility, the warning sign required by 490.35(A) shall include a notice that access is limited to the serving utility or is permitted only following an authorization of the serving utility. 490.48 Substation Design, Documentation, and Required Diagram. (A) Design and Documentation. Substations shall be designed by a qualified licensed professional engineer. Where components or the entirety of the substation are listed by a 1 Impact(s) : No negative impact. Change Description: Added and expanded the requirement originally provided in Section 225.70(A)(5) which was deleted in this edition of the code. 2 Impact(s) : No negative impact. Change Description: Added and made editorial changes to the requirement originally provided in Section 225.70(A)(5) which was deleted in this edition of the code. Page 77 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table qualified electrical testing laboratory, documentation of internal design features subject to the listing investigation shall not be required. The design shall address but not be limited to the following topics and the documentation of this design shall be made available to the authority having jurisdiction. (1) Clearances and exits (2) Electrical enclosures (3) Securing and support of electrical equipment (4) Fire protection (5) Safety ground connection provisions (6) Guarding live parts (7) Transformers and voltage regulation equipment (8) Conductor insulation, electrical and mechanical protection, isolation, and terminations (9) Application, arrangement, and disconnection of circuit breakers, switches, and fuses (10) Provisions for oil filled equipment (11) Switchgear (12) Surge arrestors (B) Diagram. A permanent, single-line diagram of the switchgear shall be provided in a readily visible location within the same room or enclosed area with the switchgear, and this diagram shall clearly identify interlocks, isolation means, and all possible sources of voltage to the installation under normal or emergency conditions, and the marking on the switchgear shall cross-reference the diagram. Exception: Where the equipment consists solely of a single cubicle or metal-enclosed unit substation containing only one set of high-voltage switching devices, diagrams shall not be required. Impact(s) : No negative impact. ARTICLE 500 Hazardous (Classified) Locations, Classes I, II, and III, Division 1 and 2 500.2 Definitions. Change Description: Combustible Dust. Any finely divided solid material that Revised to align with the changed definition found in NFPA 499. is 420 microns (0.017 in.) or smaller in diameter (material Page 78 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table passing a U.S. No. 40 Standard Sieve) and presents a fire or explosion hazard when dispersed and ignited in air. [499, 2008] Impact(s) : No negative impact. Combustible Dust. Dust particles that are 500 microns or smaller (material passing a U.S. No. 35 Standard Sieve as defined in ASTM E 11-09, Standard Specification for Wire Cloth and Sieves for Testing Purposes) and present a fire or explosion hazard when dispersed and ignited in air. 500.5 Classifications of Locations. (A) Classifications of Locations. Locations shall be classified depending on the properties of the flammable gas, flammable liquid-–produced vapor, combustible liquid– produced vapors, combustible dusts, or fibers/flyings that may be present, and the likelihood that a flammable or combustible concentration or quantity is present. Each room, section, or area shall be considered individually in determining its classification. Where pyrophoric materials are the only materials used or handled, these locations shall not be classified. Each room, section, or area shall be considered individually in determining its classification.are outside the scope of this article. 500.8 Equipment. Articles 500 through 504 require equipment construction and installation that ensure safe performance under conditions of proper use and maintenance. (C) Marking. Equipment shall be marked to show the environment for which it has been evaluated. Unless otherwise specified or allowed in (C)(6), the marking shall include the information specified in (C)(1) through (C)(5). (4) Equipment Temperature. The marking shall specify the temperature class or operating temperature at a 40°C ambient temperature, or at the higher ambient temperature if the equipment is rated and marked for an ambient temperature of greater than 40°C. For equipment installed in a Class II, Division 1 location, the temperature class or operating temperature shall be based on operation of the equip- Change Description: Clarified the original intent of this section. 1 Impact(s) : No negative impact. Change Description: Clarified the requirements for defining temperature class as referring to operating temperature when blanketed with dust. Impact(s) : No negative impact. Page 79 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ment when blanketed with the maximum amount of dust that can accumulate on the equipment. The temperature class, if provided, shall be indicated using the temperature class (T Codes)codes) shown in Table 500.8(C). Equipment for Class I and Class II shall be marked with the maximum safe operating temperature, as determined by simultaneous exposure to the combinations of Class I and Class II conditions. 501.10 Wiring Methods. Wiring methods shall comply with 501.10(A) or (B). (A) Class I, Division 1. (1) General. In Class I, Division 1 locations, the wiring methods in (a) through (d)(e) shall be permitted. e) Optical fiber cable Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in raceways in accordance with 501.10(A). These optical fiber cables shall be sealed in accordance with 501.15. (2) Flexible Connections. Where necessary to employ flexible connections, as at motor terminals, the following shall be permitted: (1) fFlexible fittings listed for the location, or (2) fFlexible cord in accordance with the provisions of 501.140, terminated with cord connectors listed for the location, shall be permitted. or ARTICLE 501 Class I Locations Change Description: Added a requirement for correlation with Chapter 7 which allows the listed optical fiber cables in classified locations if sealed per Chapter 5 requirements. In addition, the new subsection adds TC-ER-HL cable as an acceptable wiring method for industrial applications where flexibility is required. This cable is approved for use in classified locations per UL 2225. Impact(s) : No negative impact. (3) In industrial establishments with restricted public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation, for applications limited to 600 volts, nominal, or less, and where protected from damage by location or a suitable guard, listed Type TC-ER-HL cable with an overall jacket and a separate equipment grounding conductor(s) in accordance with 250.122 that is terminated with fittings listed for the location Page 80 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 501.10 Wiring Methods. Wiring methods shall comply with 501.10(A) or (B). (B) Class I, Division 2. (1) General. In Class I, Division 2 locations, the following wiring methods shall be permitted: (7) Optical fiber cable Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in cable trays or any other raceway in accor- dance with 501.10(B). Optical fiber cables shall be sealed in accordance with 501.15. (2) Flexible Connections. Where provision must be made for limited flexibility, one or more of the following shall be permitted: Change Description: Added a requirement for correlation with Chapter 7 which allows the listed optical fiber cables in classified locations if sealed per Chapter 5 requirements. The added subsection 501.10(B)(2)(3) adds to the acceptable wiring methods the MC cable already listed in 510.(A)(1). Also, the change under subsection 501.10(B)(2)(7) correlates the requirements with Chapter 4. 2 Impact(s) : No negative impact. (3) Interlocked armor Type MC cable with listed fittings. (7) For elevator use, an identified elevator cable of Type EO, ETP, or ETT, shown under the “use” column in Table 400.4 for “hazardous (classified) locations” and terminated with listed fittings. 501.15 Sealing and Drainage. Seals in conduit and cable systems shall comply with 501.15(A) through (F). Sealing compound shall be used in Type MI cable termination fittings to exclude moisture and other fluids from the cable insulation. (A) Conduit Seals, Class I, Division 1. In Class I, Division 1 locations, conduit seals shall be located in accordance with 501.15(A)(1) through (A)(4). (1) Entering Enclosures. In each Each conduit entry into an explosionproof enclosure shall have a conduit seal where either of the following apply: conditions applies: (1) The enclosure contains apparatus, such as switches, circuit breakers, fuses, relays, or resistors, that may pro-duce arcs, sparks, or high temperatures that are considered to be an ignition sourceexceed 80 percent of the autoignition Change Description: Revised to clarify language and for consistency with the NEC Style Manual. Impact(s) : No negative impact. Page 81 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table temperature, in degrees Celsius, of the gas or vapor involved in normal operation. Exception: Seals shall not be required for conduit entering an enclosure under any one of the following conditions: a. The switch, circuit breaker, fuse, relay, or resistor is enclosed within a chamber hermetically sealed against the entrance of gases or vapors. b. The switch, circuit breaker, fuse, relay, or resistor is immersed in oil in accordance with 501.115(B)(1)(2). c. The switch, circuit breaker, fuse, relay, or resistor is enclosed within a factory-sealed explosionproof chamber located within the enclosure, identified for the location, and marked “factory sealed” or equivalent. d. The switch, circuit breaker, fuse, relay, or resistor is part of a nonincendive circuit. (2) The entry is metric designator 53 (trade size 2) or larger, and the enclosure contains terminals, splices, or taps. For the purposes of this section, high temperatures shall be considered to be any temperatures exceeding 80 percent of the autoignition temperature in degrees Celsius of the gas or vapor involved. Exception to 501.15(A)(1)(1): Seals shall not be required for conduit entering an enclosure where such switches, circuit breakers, fuses, relays, or resistors comply with one of the following: (1) Are enclosed within a chamber hermetically sealed against the entrance of gases or vapors (2) Are immersed in oil in accordance with 501.115(B)(1)(2) (3) Are enclosed within a factory-sealed explosionproof chamber located within the enclosure, identified for the ocation, and marked “factory sealed” or equivalent, unless the enclosure entry is metric designator 53 Page 82 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (trade size 2) or larger (4) Are in nonincendive circuits 501.15 Sealing and Drainage. Seals in conduit and cable systems shall comply with 501.15(A) through (F). Sealing compound shall be used in Type MI cable termination fittings to exclude moisture and other fluids from the cable insulation. (A) Conduit Seals, Class I, Division 1. In Class I, Division 1 locations, conduit seals shall be located in accordance with 501.15(A)(1) through (A)(4). 4) Class I, Division 1 Boundary. In A conduit seal shall be required in each conduit run leaving a Class I, Division 1 location. The sealing fitting shall be permitted to be installed on either side of the boundary and it shall be dewithin 3.05 m (10 ft) of the boundary, and it shall be designed and installed so as to minimize the amount of gas or vapor within the Division 1 portion of the conduit from being communicated to the conduit installed in the Division1 location that can be communicated beyond the seal. Except for listed explosionproof reducers The conduit run between the conduit seal and the point at which at the conduit seal, there leaves the Division 1 location shall becontain no union, coupling, box, or other fitting between the conduit seal and the pointexcept for a listed explosionproof reducer installed at which the conduit leaves the Division 1 location.seal. Change Description: Revised to clarify language and for consistency with the NEC Style Manual. Impact(s) : No negative impact. 1 501.15 Sealing and Drainage. Seals in conduit and cable systems shall comply with 501.15(A) through (F). Sealing compound shall be used in Type MI cable termination fittings to exclude moisture and other fluids from the cable insulation. Change Description: Revised to clarify language and for consistency with the NEC Style Manual. 1 (B) Conduit Seals, Class I, Division 2. In Class I, Division 2 locations, conduit seals shall be located in accordance with 501.15(B)(1) and (B)(2). (2) Class I, Division 2 Boundary. In A conduit seal shall Impact(s) : No negative impact. Page 83 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table be required in each conduit run passing from leaving a Class I, Division 2 location into an unclassified location. The sealing fitting shall be permitted to be installed on either side of the boundary of such location within 3.05 m (10 ft) of the boundary and it shall be designed and installed to minimize the amount of gas or vapor within the portion of the conduit installed in the Division 2 location that can be communicated beyond the seal. Rigid metal conduit or threaded steel intermediate metal conduit shall be used between the sealing fitting and the point at which the conduit leaves the Division 2 location, and a threaded connection shall be used at the sealing fitting. Except for listed reducers at the conduit seal, there shall be no union, coupling, box, or fitting The conduit run between the conduit seal and the point at which the conduit leaves the Division 2 location. Conduits shall be sealed to minimize the amount of gas or vapor within the Division 2 portion of the conduit from being communicated to location shall contain no union, coupling, box, or other fitting except for a listed explosionproof reducer installed at the conduit beyond the seal. Such seals shall not be required to be explosionproof but shall be identified for the purpose of minimizing the passage of gases permitted under normal operating conditions and shall be accessible. 501.15 Sealing and Drainage. Seals in conduit and cable systems shall comply with 501.15(A) through (F). Sealing compound shall be used in Type MI cable termination fittings to exclude moisture and other fluids from the cable insulation. (D) Cable Seals, Class I, Division 1. In Class I, Division 1 locations, cable seals shall be located according to 501.15(D)(1) through (D)(3). 2) Cables Capable of Transmitting Gases or Vapors. Cables in conduit with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core, installed in conduit, shall be sealed in the Class 1, Division 1 location after removing the jacket and any other coverings have been removed so that the sealing compound Change Description: Revised to clarify language and for consistency with the NEC Style Manual. Impact(s) : No negative impact. Page 84 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table willcan surround each individual insulated conductor or optical fiber tube and the outer jacket. Exception: Multiconductor cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core shall be permitted to be considered as a single conductor by sealing the cable in the conduit within 450 mm (18 in.) of the enclosure and the cable end within the enclosure by an approved means to minimize the entrance of gases or vapors and prevent the propagation of flame into the cable core, or by other approved methods. For shielded cables and twisted pair cables, it It shall not be required to remove the shielding material or separate the twisted pairs of shielded cables and twisted pair cables. 501.15 Sealing and Drainage. Seals in conduit and cable Change Description: systems shall comply with 501.15(A) through (F). Sealing Revised to clarify language and for consistency with the NEC compound shall be used in Type MI cable termination fitStyle Manual. Also, added an exception allowing cables with tings to exclude moisture and other fluids from the cable unbroken gas/vaportight continuous sheath to pass through Div. insulation. (E) Cable Seals, Class I, Division 2. In Class I, Division 2 2 location without seals and expanded to include seals of fiber optic cables. locations, cable seals shall be located in accordance with 501.15(E)(1) through (E)(4). Exception: Cables with an unbroken gas/vaportight conImpact(s) : tinuous sheath shall be permitted to pass through a DiviNo negative impact. sion 2 location without seals. (1) Terminations. Cables entering enclosures that are required to be explosionproof shall be sealed at the point of entrance. The sealing fitting shall comply with 01.15(B)(1) or be explosionproof. Multiconductor or optical multifiber cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core shall be sealedthat are installed in a listed fitting in the Division 2 location after removing Division 2 location shall be sealed with a listed fitting after the jacket and any other coverings have been removed so that the sealing compound can surrounds each individual insulated conductor or optical fiber tube in such a manner as to minimize the passage of gases and vapors. Multiconductor or optical Page 85 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table multifiber cables installed in conduit shall be sealed as described in 501.15(D). 2) Cables That Do Not Transmit Gases or Vapors. Cables that have a gas/vaportight continuous sheath and do not transmit gases or vapors through the cable core in excess of the quantity permitted for seal fittings shall not be required to be sealed except as required in 501.15(E)(1). The minimum length of such a cable run shall not be less than thatthe length that limits needed to limit gas or vapor flow through the cable core, excluding the interstices of the conductor strands, to the rate permitted for seal fittings [200 cm3/hr (0.007 ft3/hr) of air at a pressure of 1500 pascals (6 in. of water)]. 501.15 Sealing and Drainage. Seals in conduit and cable systems shall comply with 501.15(A) through (F). Sealing compound shall be used in Type MI cable termination fittings to exclude moisture and other fluids from the cable insulation. (F) Drainage. (2) Motors and Generators. Where the authority having jurisdiction judges that there is a probability that liquid or condensed vapor may accumulate within motors or generators, joints and conduit systems shall be arranged to minimize the entrance of liquid. If means to prevent accumulation or to permit periodic draining are judged necessary, such means shall be provided at the time of manufacture and shall be considered an integral part of the machine. Change Description: This change removed ambiguity of the language in this section. 501.17 Process Sealing. This section shall apply to process-connected equipment, which includes, but is not limited to, canned pumps, submersible pumps, flow, pressure, temperature, or analysis measurement instruments. A process seal is a device to prevent the migration of process fluids from the designed containment into the external electrical system. Process-connected electrical equipment that incorporates a single process seal, such as a single compression seal, diaphragm, or tube to prevent flammable or Change Description: This change correlates the requirements with ANSI/ISA-12.27.01. 2 Impact(s) : No negative impact – improves safety. Impact(s) : No negative impact. Page 86 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table combustible fluids from entering a conduit or cable system capable of transmitting fluids, shall be provided with an additional means to mitigate a single process seal failure, The additional means may include, but is not limited to, the following: (4) An add-on secondary seal marked “secondary seal” and rated for the pressure and temperature conditions to which it will be subjected upon failure of the single process seal. 501.30 Grounding and Bonding, Class I, Divisions 1 and 2. Wiring Regardless of the voltage of the electrical system, wiring and equipment in Class I, Division 1 and 2 locations shall be grounded as specified in Article 250 and in accordance with the requirements of 501.30(A) and (B). Change Description: This change clarifies the applicability of this section. 501.40 Multiwire Branch Circuits. In a Class I, Division 1 location, a multiwire branch circuit shall not be permitted. Change Description: The requirements found in this deleted section are already included in 210.4(B) and do not need to be repeated here. Exception: Where the disconnect device(s) for the circuit opens all ungrounded conductors of the multiwire circuit simultaneously. 501.105 Meters, Instruments, and Relays. (B) Class I, Division 2. In Class I, Division 2 locations, meters, instruments, and relays shall comply with 501.105(B)(1) through (B)(6). (6) Connections. To facilitate replacements, process control instruments shall be permitted to be connected through flexible cord, attachment plug, and receptacle, provided all of the following conditions apply: (1) A switch complying with 501.105(B)(1) is provided so that the attachment plug is not depended on to interrupt current. Exception: The switch is not required if the circuit is nonincendive field wiring. 1 Impact(s) : No negative impact. 1 Impact(s) : No negative impact. Change Description: The added exception eliminates the requirement for a switch in a circuit with a connection plug for nonincendive field wiring. Nonincendive wiring is not capable of igniting flammable mixtures and a switch in this case is not required. Impact(s) : No negative impact. Page 87 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 501.130 Luminaires. Luminaires shall comply with 501.130(A) or (B). (B) Class I, Division 2. In Class I, Division 2 locations, luminaires shall comply with 501.130(B)(1) through (B)(6). (4) Portable Lighting Equipment. Portable lighting equipment shall comply with 501.130(A)(1). Exception: Where portable lighting equipment is mounted on movable stands and is connected by flexible cords, as covered in 501.140, it shall be permitted to comply with 501.130(B)(1), where mounted in any position, if provided that it conforms to also complies with 501.130(B)(2). 501.140 Flexible Cords, Class I, Divisions 1 and 2. (A) Permitted Uses. Flexible cord shall be permitted: (1) For connection between portable lighting equipment or other portable utilization equipment and the fixed portion of their supply circuit. The flexible cord shall be attached to the utilization equipment with a cord connector listed for the protection technique of the equipment wiring compartment. An attachment plug in accordance with 501.140(B)(4) shall be employed. 501.145 Receptacles and Attachment Plugs, Class I, Divisions 1 and 2. Receptacles and attachment plugs shall be of the type providing for connection to the equipment grounding conductor of a flexible cord and shall be identi- fied for the location. (A) Receptacles. Receptacles shall be part of the premises wiring, except as permitted by 501.140(A). (B) Attachment Plugs. Attachment plugs shall be of the type providing for connection to the equipment grounding conductor of a flexible cord and shall be identified for the location. Change Description: The change clarifies the language of this exception. 1 Impact(s) : No negative impact. Change Description: Revised to make clear that 501.140(A)(1) covers power cords that attach to the utilization equipment with a cord connector and have an attachment plug for connection to premises wiring. 1 Impact(s) : No negative impact. Change Description: Revised to make clear that the receptacle is part of the premises wiring and that the attachment plug is part of the utilization equipment. Impact(s) : No negative impact. ARTICLE 502 Page 88 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Class II Locations 502.10 Wiring Methods. Wiring methods shall comply Change Description: with 502.10(A) or (B). Added a requirement for correlation with Chapter 7 which allows the listed optical fiber cables in classified locations if sealed per (A) Class II, Division 1. (1) General. In Class II, Division 1 locations, the wiring Chapter 5 requirements. methods in (1) through (4) shall be permitted: Also, the change under subsection 502.10(A)(1)(6) correlates the (4) Fittings and boxes shall be provided with threaded requirements with Chapter 4. bosses for connection to conduit or cable terminations and shall be dusttight. Fittings and boxes in which taps, joints, or terminal connections are made, or that are used in Group E locations, shall be identified for Class II locations. (4) Optical fiber cables Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in raceways in accordance with 502.10(A). Optical fiber cables shall be sealed in accordance with 502.15. 6) For elevator use, an identified elevator cable of Type EO, ETP, or ETT, shown under the “use” column in Table 400.4 for “hazardous (classified) locations” and terminated with listed dusttight fittings. 502.10 Wiring Methods. Wiring methods shall comply with 502.10(A) or (B). (A) Class II, Division 1. (3) Boxes and Fittings. Boxes and fittings shall be provided with threaded bosses for connection to conduit or cable terminations and shall be dusttight. Boxes and fittings in which taps, joints, or terminal connections are made, or that are used in Group E locations, shall be identified for Class II locations. 502.10 Wiring Methods. Wiring methods shall comply with 502.10(A) or (B). (B) Class II, Division 2. 2 Impact(s) : No negative impact. Change Description: Editorial change – relocated from 502.10(A)(1)(4). 1 Impact(s) : No negative impact. Change Description: Added a requirement for correlation with Chapter 7 which allows the listed optical fiber cables in classified locations if sealed per Page 89 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (1) General. In Class II, Division 2 locations, the following wiring methods shall be permitted: (6) Type MC, MI, or TC cable installed in ladder, ventilated trough, or ventilated channel cable trays in a single layer, with a space not less than the larger cable diameter between the two adjacent cables, shall be the wiring method employed. Exception to (6): Type MC cable listed for use in Class II, Division 1 locations shall be permitted to be installed without the spacings required by (6). 8) Optical fiber cable Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in cable trays or any other raceway in accordance with 502.10(B). Optical fiber cables shall be sealed in accordance with 502.15. Chapter 5 requirements. Impact(s) : No negative impact. Exception to (6): Type MC cable listed for use in Class II, Division 1 locations shall be permitted to be installed without the spacings required by (6). 502.30 Grounding and Bonding, Class II, Divisions 1 and 2. Wiring Regardless of the voltage of the electrical system, wiring and equipment in Class II, Division 1 and 2 locations shall be grounded as specified in Article 250 and in accordance with the requirements of 502.30(A) and (B). Change Description: This change clarifies the applicability of this section. 502.40 Multiwire Branch Circuits. In a Class II, Division 1 location, a multiwire branch circuit shall not be permitted. Change Description: The requirements found in this deleted section are already included in 210.4(B) and do not need to be repeated here. Exception: Where the disconnect device(s) for the circuit opens all ungrounded conductors of the multiwire circuit simultaneously. Impact(s) : No negative impact. 502.125 Motors and Generators. (A) Class II, Division 1. In Class II, Division 1 locations, motors, generators, and other rotating electrical machinery 1 Impact(s) : No negative impact. Change Description: Editorial change. Page 90 of 203 1 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table shall be in conformance with either of the following: (1) Identified for the location (2) Totally enclosed pipe-ventilated, meeting temperature limitations in 502.5pipe-ventilated 502.140 Flexible Cords — Class II, Divisions 1 and 2. (A) Permitted Uses. Flexible cords used in Class II locations shall comply with all of the following: (1) Be of a type listed for extra-hard usage For connection between portable lighting equipment or other portable utilization equipment and the fixed portion of its supply circuit. The flexible cord shall be attached to the utilization equipment with a cord connector listed for the protection technique of the equipment wiring compartment. An attachment plug in accordance with 502.145 shall be employed. (2) Where flexible cord is permitted by 502.10(A)(2) for fixed and mobile electrical utilization equipment; where the flexible cord is protected by location or by a suitable guard from damage; and only in an industrial establishment where conditions of maintenance and engineering supervision ensure that only qualified persons install and service the installation. (3) For electric submersible pumps with means for removal without entering the wet-pit. The extension of the flexible cord within a suitable raceway between the wet-pit and the power source shall be permitted. (4) For electric mixers intended for travel into and out of open-type mixing tanks or vats. (5) For temporary portable assemblies consisting of receptacles, switches, and other devices that are not considered portable utilization equipment but are individually listed for the location. Impact(s) : No negative impact. Change Description: Revised to make clear that 502.140(A) covers power cords that attach to the utilization equipment with a cord connector and have an attachment plug for connection to premises wiring. It mirrors changes to Section 501.140. Impact(s) : No negative impact. (B) Installation. Where flexible cords are used, the cords shall comply with all of the following: (1) Be of a type listed for extra-hard usage. Page 91 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 5) Be of continuous length. Where 502.140(A)(5) is applied, cords shall be of continuous length from the power source to the temporary portable assembly and from the temporary portable assembly to the utilization equipment. 502.145 Receptacles and Attachment Plugs. Receptacles and attachment plugs shall be identified for the location. (A) Class II, Division 1. (1) Receptacles. In Class II, Division 1 locations, receptacles and attachment plugs shall be of the type providing for connection to the equipment grounding conductor of the flexible cord and shall be identified for Class II locations. part of the premises wiring. (2) Attachment Plugs. Attachment plugs shall be of the type that provides for connection to the equipment grounding conductor of the flexible cord. (B) Class II, Division 2. (1) Receptacles. In Class II, Division 2 locations, receptacles and attachment plugs shall be of the type that provides for connection to the equipment grounding conductor of the flexible cord and shall be designed so that connection to the supply circuit cannot be made or broken while live parts are exposed.part of the premises wiring. Change Description: Revised to make clear that the receptacle is part of the premises wiring and that the attachment plug is part of the utilization equipment. 1 Impact(s) : No negative impact. (2) Attachment Plugs. Attachment plugs shall be of the type that provides for connection to the equipment grounding conductor of the flexible cord. 503.5 General. Equipment installed in Class III locations shall be able to function at full rating without developing surface temperatures high enough to cause excessive dehydration or gradual carbonization of accumulated fibers/flyings. Organic material that is carbonized or exces- ARTICLE 503 Class III Locations Change Description: Clarified the requirements for defining temperature class as referring to operating temperature when blanketed with dust (simulating fibers/flyings). Page 92 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table sively dry is highly susceptible to spontaneous ignition. The maximum surface temperatures under operating conditions shall not exceed 165°C (329°F) for equipment that is not subject to overloading, and 120°C (248°F) for equipment (such as motors or power transformers) that may be overloaded. In a Class III, Division 1 location, the operating temperature shall be the temperature of the equipment when blanketed with the maximum amount of dust (simulating fibers/flyings) that can accumulate on the equipment. Impact(s) : No negative impact. 503.10 Wiring Methods. Wiring methods shall comply with 503.10(A) or (B). (A) Class III, Division 1. Change Description: The change under subsection 503.10(A)(3)(6) correlates the requirements with Chapter 4. (1) General. In Class III, Division 1 locations, the wiring method shall be in accordance with (1) through (4): (4) Type MC, MI, TC, or TC-ER cable installed in ladder, ventilated trough, or ventilated channel cable trays in a single layer, with a space not less than the larger cable diameter between the two adjacent cables, shall be the wiring method employed. The cable shall be terminated with listed fittings. Impact(s) : No negative impact. 1 (3) Flexible Connections. Where necessary to employ flexible connections, one or more of the following shall be permitted: (6) For elevator use, an identified elevator cable of Type EO, ETP, or ETT, shown under the “use” column in Table 400.4 for “hazardous (classified) locations” and terminated with listed dusttight fittings. 503.30 Grounding and Bonding — Class III, Divisions 1 and 2. Wiring Regardless of the voltage of the electrical system, wiring and equipment in Class III, Division 1 and 2 locations shall be grounded as specified in Article 250 and with the following additional requirements in 503.30(A) and (B). Change Description: This change clarifies the applicability of this section. Impact(s) : No negative impact. Page 93 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ARTICLE 504 Intrinsically Safe Systems 504.30 Separation of Intrinsically Safe Conductors. Change Description: (A) From Nonintrinsically Safe Circuit Conductors. Expanded separation requirement between nonintrinsically safe (2) Within Enclosures. Conductors of intrinsically safe and intrinsically safe circuits to include specific dimensions for the circuits shall be secured so that any conductor that might partition. come loose from a terminal is unlikely to come into contact 2 with another terminal. The conductors shall be separated from conductors of nonintrinsically safe circuits by one of the Impact(s) : methods in (1) through (4). No negative impact. (3) Separation from conductors of nonintrinsically safe circuits by use of an approved insulating partition. that extends to within 1.5 mm (0.0625 in.) of the enclosure walls C) From Grounded Metal. The clearance between the uninsulated parts of field wiring conductors connected to terminals and grounded metal or other conducting parts shall be at least 3 mm (0.125 in.). 505.5 Classifications of Locations. (A) Classification of Locations. Locations shall be classified depending on the properties of the flammable vapors, liquids, or gases flammable gases, flammable liquid– produced vapors, combustible liquid–produced vapors, combustible dusts, or fibers/flyings that may be present and the likelihood that a flammable or combustible concentration or quantity is present. Each room, section, or area shall be considered individually in determining its classification. Where pyrophoric materials are the only materials used or handled, these locations shall not be classified. Each room, ARTICLE 505 Zone 0, 1, and 2 Locations Change Description: Clarified the original intent of this section. Impact(s) : No negative impact. Page 94 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table section, or area shall be considered individually in determining its classification.are outside the scope of this article. 505.6 Material Groups. For purposes of testing, approval, and area classification, various air mixtures (not oxygen enriched) shall be grouped as required in 505.6(A), (B), and (C). Group II shall be subdivided into IIC, IIB, and IIA, as noted in 505.6(A), (B), and (C), according to the nature of the gas or vapor, for protection techniques “d,” “ia,” “ib,” “[ia],” and “[ib],” and, where applicable, “n” and “o.” Change Description: The second paragraph was redundant and was deleted from this section. 505.7 Special Precaution. Article 505 requires equipment construction and installation that ensures safe performance under conditions of proper use and maintenance. (F) Available Short-Circuit Current for Type of Protection “e”. The available short-circuit current for electrical equipment using type of protection “e” for the field wiring connections in Zone 1 locations shall be limited to 10,000 rms symmetrical amperes to reduce the likelihood of ignition of a flammable atmosphere by an arc during a shortcircuit event. Change Description: Added short circuit current requirements to correlate this subsection with ANSI/UL 508A, Standard for Industrial Control Panels. 505.9 Equipment. (C) Marking. Equipment shall be marked in accordance with 505.9(C)(1) or (C)(2). (2) Zone Equipment. Equipment meeting one or more of the protection techniques described in 505.8 shall be marked with all of the following in the order shown: (5) Applicable gas classification group(s) material group in accordance with Table 505.9(C)(1)(2) or a specific gas or vapor Exception No. 3: Fittings for the termination of cables shall not be required to have a marked operating temperature or temperature class. Electrical equipment of types of protection “e,” “m,” “ma,” “mb,” “px,” “py,” “pz,” or “q” shall be marked Group Change Description: Modified language for consistency in used terms. Cable fittings are not required by ANSI/UL 2225 to be marked with a temperature class. Also, since product standards have been revised such that the marking of the Group subdivision is always required, text covering marking was no longer necessary. 1 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 95 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table II. Electrical equipment of types of protection “d,” “ia,” “ib,” “ic,” [ia],” “[ib],” or “[ic]” shall be marked Group IIA, IIB, or IIC, or for a specific gas or vapor. Electrical equipment of types of protection “n” shall be marked Group II unless it contains enclosed-break devices, nonincendive components, or energy-limited equipment or circuits, in which case it shall be marked Group IIA, IIB, or IIC, or a specific gas or vapor. Electrical equipment of other types of protection shall be marked Group II unless the type of protection utilized by the equipment requires that it be marked Group IIA, IIB, or IIC, or a specific gas or vapor. 505.15 Wiring Methods. Wiring methods shall maintain the integrity of protection techniques and shall comply with 505.15(A) through (C). (B) Class I, Zone 1. (1) General. In Class I, Zone 1 locations, the wiring methods in (B)(1)(a) through (B)(1)(fi) shall be permitted. (g) Intrinsic safety type of protection “ib” shall be permitted using the wiring methods specified in Article 504. (h) Optical fiber cable Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in raceways in accordance with 505.15(B). Optical fiber cable shall be sealed in accordance with 505.16. (i) In industrial establishments with restricted public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation, for applications limited to 600 volts nominal or less, for cable diameters 25 mm (1 in.) or less, and where the cable is not subject to physical damage, Type TC-ER-HL cable listed for use in Class I, Zone 1 locations, with an overall jacket and a separate equipment grounding conductor(s) in accordance with 250.122, and terminated with fittings listed for the location, Type TC-ER-HL cable shall be installed in accordance with the provisions of Article 336, Change Description: Added a requirement for correlation with Chapter 7 which allows the listed optical fiber cables in classified locations if sealed per Chapter 5 requirements. In addition, the new subsection adds TC-ER-HL cable as an acceptable wiring method for industrial applications where flexibility is required. This cable is approved for use in classified locations per UL 2225. Impact(s) : No negative impact. Page 96 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table including the restrictions of 336.10(7). 505.15 Wiring Methods. Wiring methods shall maintain the integrity of protection techniques and shall comply with 505.15(A) through (C). (C) Class I, Zone 2. (1) General. In Class I, Zone 2 locations, the following wiring methods shall be permitted. (h) Optical fiber cable of Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in cable trays or any other raceway in accordance with 505.15(C). Optical fiber cable shall be sealed in accordance with 505.16. Change Description: Added a requirement for correlation with Chapter 7 which allows the listed optical fiber cables in classified locations if sealed per Chapter 5 requirements. 505.15 Wiring Methods. Wiring methods shall maintain the integrity of protection techniques and shall comply with 505.15(A) through (C). (C) Class I, Zone 2. (2) Flexible Connections. Where provision must be made for limited flexibility, flexible metal fittings, flexible metal conduit with listed fittings, liquidtight flexible metal conduit with listed fittings, liquidtight flexible nonmetallic conduit with listed fittings, or flexible cord in accordance with the provisions of 505.17 terminated with a listed cord connector that maintains the type of protection of the terminal compartment shall be permitted. Exception: For elevator use, an identified elevator cable of Type EO, ETP, or ETT, shown under the “use” column in Table 400.4 for “hazardous (classified) locations,” that is terminated with listed connectors that maintain the type of protection of the terminal compartment, shall be permitted. Change Description: The change under subsection 505.15(C)(2) correlates the requirements with Chapter 4. 505.16 Sealing and Drainage. Seals in conduit and cable systems shall comply with 505.16(A) through (E). Sealing compound shall be used in Type MI cable termination fittings to exclude moisture and other fluids from the cable insulation. (B) Zone 1. In Class I, Zone 1 locations, seals shall be located Change Description: Expanded language to include seals of fiber optic cables. 2 Impact(s) : No negative impact. 1 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 97 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table in accordance with 505.16(B)(1) through (B)(8). (5) Cables Capable of Transmitting Gases or Vapors. Conduits containing cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core shall be sealed in the Zone 1 location after removing the jacket and any other coverings so that the sealing compound surrounds each individual insulated conductor or optical fiber tube and the outer jacket. (6) Cables Incapable of Transmitting Gases or Vapors. Each multiconductor or optical multifiber cable in conduit shall be considered as a single conductor or single optical fiber tube if the cable is incapable of transmitting gases or vapors through the cable core. These cables shall be sealed in accordance with 505.16(D). 505.16 Sealing and Drainage. Seals in conduit and cable systems shall comply with 505.16(A) through (E). Sealing compound shall be used in Type MI cable termination fittings to exclude moisture and other fluids from the cable insulation. (C) Zone 2. In Class I, Zone 2 locations, seals shall be located in accordance with 505.16(C)(1) and (C)(2). (2) Cable Seals. Cable seals shall be located in accordance with (C)(2)(a), (C)(2)(b), and (C)(2)(c). (a) Explosionproof and Flameproof Enclosures. Cables entering enclosures required to be flameproof or explosionproof shall be sealed at the point of entrance. The seal shall comply with 505.16(D). Multiconductor or optical multifiber cables with a gas/vaportight continuous sheath capable of transmitting gases or vapors through the cable core shall be sealed in the Zone 2 location after re- moving the jacket and any other coverings so that the seal- ing compound surrounds each individual insulated conduc- tor or optical fiber tube in such a manner as to minimize the passage of gases and vapors. Multiconductor or optical multifiber cables in conduit shall be sealed as described in Change Description: Expanded language to include seals of fiber optic cables. Impact(s) : No negative impact. Page 98 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 505.16(B)(4). 505.16 Sealing and Drainage. Seals in conduit and cable systems shall comply with 505.16(A) through (E). Sealing compound shall be used in Type MI cable termination fittings to exclude moisture and other fluids from the cable insulation. (D) Class I, Zones 0, 1, and 2. Where required, seals in Class I, Zones 0, 1, and 2 locations shall comply with 505.16(D)(1) through (D)(5). (5) Conductor or Optical Fiber Fill. The cross-sectional area of the conductors or optical fiber tubes (metallic or nonmetallic) permitted in a seal shall not exceed 25 percent of the cross-sectional area of a rigid metal conduit of the same trade size unless it is specifically listed for a higher percentage of fill. Change Description: Expanded language to include seals of fiber optic cables. 505.17 Flexible Cords and Connections. B) Instrumentation Connections for Zone 2. To facilitate replacements, process control instruments shall be permitted to be connected through flexible cords, attachment plugs, and receptacles, provided that all of the following conditions apply: (1) A switch listed for Zone 2 is provided so that the attachment plug is not depended on to interrupt current, unless the circuit is type “ia,” “ib,” or “ic” protection, in which case the switch is not required. (2) The current does not exceed 3 amperes at 120 volts, nominal. (3) The power-supply cord does not exceed 900 mm (3 ft), is of a type listed for extra-hard usage or for hard usage if protected by location, and is supplied through an ttachment plug and receptacle of the locking and grounding type. (4) Only necessary receptacles are provided. (5) The receptacle carries a label warning against unplugging under load. Change Description: This added subsection provides requirements for instrumentation connections, applicable to Zone 2 locations. 2 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 99 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 505.20 Equipment Requirements. (D) Materials. Equipment marked Group IIC shall be permitted for applications requiring Group IIA or Group IIB equipment. Similarly, equipment marked Group IIB shall be permitted for applications requiring Group IIA equipment. Equipment marked for a specific gas or vapor shall be permitted for applications where the specific gas or vapor may be encountered. Change Description: This change addresses the suitability of equipment marked with the chemical formula of a specific material. Although clear in the product standards, it is not clear in Article 505 that IIC equipment is suitable for applications requiring IIA or IIB equipment. Similarly, it is not clear that IIB equipment is suitable for applications requiring IIA equipment. 1 Impact(s) : No negative impact. 505.21 Multiwire Branch Circuits. In a Class I, Zone 1 location, a multiwire branch circuit shall not be permitted. Exception: Where the disconnect device(s) for the circuit opens all ungrounded conductors of the multiwire circuit simultaneously. Change Description: The requirements found in this deleted section are already included in 210.4(B) and do not need to be repeated here. 1 Impact(s) : No negative impact. 505.25 Grounding and Bonding. Regardless of the volt- Change Description: age of the electrical system, Ggrounding and bonding shall This change clarifies the applicability of this section. comply with Article 250 and the requirements in 505.25(A) and (B). 1 505.26 Process Sealing. This section shall apply to process-connected equipment, which includes, but is not limited to, canned pumps, submersible pumps, flow, pressure, temperature, or analysis measurement instruments. A process seal is a device to prevent the migration of process fluids from the designed containment into the external electrical system. Process connected electrical equipment that incorporates a single process seal, such as a single compression seal, diaphragm, or tube to prevent flammable or 2 Impact(s) : No negative impact. Change Description: This change correlates the requirements with ANSI/ISA-12.27.01. Impact(s) : No negative impact. Page 100 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table combustible fluids from entering a conduit or cable system capable of transmitting fluids, shall be provided with an additional means to mitigate a single process seal failure. The additional means may include, but is not limited to the following: (4) An add-on secondary seal marked “secondary seal” and rated for the pressure and temperature conditions to which it will be subjected upon failure of the single process seal. ARTICLE 506 Zone 20, 21, and 22 Locations for Combustible Dusts or Ignitible Fibers/Flyings 506.1 Scope. This article covers the requirements for the Change Description: zone classification system as an alternative to the division This change clarifies the applicability of this section. classification system covered in Article 500, Article 502, and Article 503 for electrical and electronic equipment and wiring for all voltages in Zone 20, Zone 21, and Zone 22 hazardous (classified) locations where fire and explosion hazards may exist due to combustible dusts or ignitible fibers/flyings. Combustible metallic dusts are not covered by the requirements of this article. 1 Impact(s) : No negative impact. Combustible Dust. Any finely divided solid material Dust particles that is 420are 500 microns (0.017 in.) or smaller in diameter (material passing a U.S. No. 4035 Standard Sieve) Sieve as defined in ASTM E 11-09, Standard Specification for Wire Cloth and Sieves for Testing Purposes) and presents a fire or explosion hazard when dispersed and ignited in air. [499:3.3.3] Change Description: Revised to align with the changed definition found in NFPA 499. 506.3 Other Articles. All other applicable rules contained in this Code shall apply to electrical equipment and wiring installed in hazardous (classified) locations. Change Description: Added clarification regarding applicability of other articles in the Code to this article. 2 Impact(s) : No negative impact. Exception: As modified by Article 504 and this article. Impact(s) : No negative impact. Page 101 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 506.6 Material Groups. For the purposes of testing, approval, and area classification, various air mixtures (not oxygen enriched) shall be grouped as required in 506.6(A), (B), and (C). A) Group IIIC. Combustible metal dust. (B) Group IIIB. Combustible dust other than combustible metal dust. (C) Group IIIA. Solid particles, including fibers, greater than 500 µm in nominal size, which may be suspended in air and could settle out of the atmosphere under their own weight. 506.8 Protection Techniques. Acceptable protection techniques for electrical and electronic equipment in hazardous (classified) locations shall be as described in 506.8(A) through (J). (C) Intrinsic Safety. This protection technique shall be permitted for equipment in Zone 20, Zone 21, and Zone 22 locations for which it is identified. Installation of intrinsically safe apparatus and wiring shall be in accordance with the requirements of Article 504. (HG) Protection by Enclosure “tD”.“t”. This protection technique shall be permitted for equipment in Zone 2120, Zone 21, and Zone 22 locations for which it is identified. 506.9 Equipment Requirements. (C) Marking. (1) Division Equipment. Equipment identified for Class II, Division 1 or Class II, Division 2 shall, in addition to being marked in accordance with 500.8(C), be permitted to be marked with bothall of the following: (2) Temperature classificationMaterial group in accordance with 506.9(D)506.6 (3) Maximum surface temperature in accordance with 506.9(D), marked as a temperature value in degrees C, preceded by “T” and followed by the symbol “°C” Change Description: Added dust groups to properly provide criteria for selection and application of the currently manufactured equipment. 2 Impact(s) : No negative impact. Change Description: Relocated requirements for intrinsically safe apparatus to Section 506.15. Also, revised enclosure marking to correlate with ANSI/ISA-60079-31 and ANSI/ISA-61241-1. 1 Impact(s) : No negative impact. Change Description: This change adds requirements for marking dust groups, necessary for proper selection of equipment. Also, revised Table 506.9(C)(2)(3) to add new designations per ISA 60079-11. Added exception for associated intrinsically safe apparatus not exposed to combustible dust, not requiring a temperature classification. This is already addressed for gases in 505.9(B)(2) Exception 1. Impact(s) : Page 102 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (2) Zone Equipment. Equipment meeting one or more of the protection techniques described in 506.8 shall be marked with the following in the order shown: (1) Zone (2) Symbol “AEx” (3) Protection technique(s) in accordance with Table 506.9(C)(2)(3) (4) Temperature classification, marked as a temperature value, in degrees C, preceded by TMaterial group in accordance with 506.6 (5) Maximum surface temperature in accordance with 506.9(D), marked as a temperature value in degrees C, preceded by “T” and followed by the symbol “°C” (56)Ambient temperature marking in accordance with 506.9(D) No negative impact. Exception: Associated apparatus NOT suitable for installation in a hazardous (classified) location shall be required to be marked only with 506.9(C)(2)(2), (3), and (5), but BOTH the symbol AEx in 506.9(C)(2)(2) and the symbol for the type of protection in 506.9(C)(2)(3) shall be enclosed within the same square brackets; for example, [AEx iaD] or [AEx ia] IIIC. 506.9 Equipment Requirements. (D) Temperature Classifications. Equipment shall be marked to show the operating maximum surface temperature referenced to a 40°C (104°F) ambient. ambient, or at the higher marked ambient temperature if the equipment is rated and marked for an ambient temperature of greater than 40°C. For equipment installed in a Zone 20 or Zone 21 location, the operating temperature shall be based on operation of the equipment when blanketed with the maximum amount of dust (or with dust-simulating fibers/flyings) that can accumulate on the equipment. Electrical equipment designed for use in the ambient temperature range between −20°C and +40°C shall require no additional ambient tem- Change Description: Clarified the requirements for defining temperature class as referring to operating temperature when blanketed with dust. Also, removed informational text in this section. Impact(s) : No negative impact. Page 103 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table perature marking. Electrical equipment that is designed for use in a range of ambient temperatures other than −20°C and +40°C is considered to be special; and the ambient temperature range shall then be marked on the equipment, including either the symbol “Ta” or “Tamb” together with the special range of ambient temperatures. As an example, such a marking might be “–30°C ≤ Ta ≤ +40°C.” Electrical equipment suitable for ambient temperatures exceeding 40°C (104°F) shall be marked with both the maximum ambient temperature and the operating temperature at that ambient temperature. 506.15 Wiring Methods. Wiring methods shall maintain the integrity of the protection techniques and shall comply with 506.15(A), (B), or (C). (A) Zone 20. In Zone 20 locations, the following wiring methods shall be permitted. (1) Threaded rigid metal conduit or threaded steel intermediate metal conduit. (2) Type MI cable terminated with fittings listed for the location. Type MI cable shall be installed and sup- ported in a manner to avoid tensile stress at the termi- nation fittings. Change Description: The wiring methods permitted for intrinsically safe apparatus in explosive dust atmospheres classified under the zone scheme are different from those permitted under the Division scheme. The wiring methods for intrinsically safe apparatus were previously addressed in Section 506.8 – Protection techniques. 1 Impact(s) : No negative impact. Exception No. 2: Equipment identified as intrinsically safe “iaD” or “ia” shall be permitted to be connected using the wiring methods identified in 504.20. 506.15 Wiring Methods. Wiring methods shall maintain the integrity of the protection techniques and shall comply with 506.15(A), (B), or (C). (A) Zone 20. In Zone 20 locations, the following wiring methods shall be permitted. (6) Where necessary to employ flexible connections, liquidtight flexible metal conduit with listed fittings, liquidtight flexible nonmetallic conduit with listed fittings, or flexible cord listed for extra-hard usage and provided with listed fittings shall be used. Where flexible cords Change Description: The change under subsection 506.15(A)(6) correlates the requirements with Chapter 4. Impact(s) : No negative impact. Page 104 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table are used, they shall also comply with 506.17 and shall be terminated with a listed cord connector that maintains the type of protection of the terminal compartment. Where flexible connections are subject to oil or other corrosive conditions, the insulation of the conductors shall be of a type listed for the condition or shall be protected by means of a suitable sheath. Exception No. 2: For elevator use, an identified elevator cable of Type EO, ETP, or ETT, shown under the “use” column in Table 400.4 for “hazardous (classified) locations,” and terminated with listed connectors that maintain the type of protection of the terminal compartment shall be permitted. 506.15 Wiring Methods. Wiring methods shall maintain the integrity of the protection techniques and shall comply with 506.15(A), (B), or (C). (A) Zone 20. In Zone 20 locations, the following wiring methods shall be permitted. (7) Optical fiber cable Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in raceways in accordance with 506.15(A). Optical fiber cables shall be sealed in accordance with 506.16. 506.15 Wiring Methods. Wiring methods shall maintain the integrity of the protection techniques and shall comply with 506.15(A), (B), or (C). (B) Zone 21. In Zone 21 locations, the wiring methods in (B)(1) and (B)(2) shall be permitted. (1) All wiring methods permitted in 506.15(A). (2) Fittings and boxes that are dusttight, provided with threaded bosses for connection to conduit, in which taps, joints, or terminal connections are not made, and are not used in locations where metal dust is present, may be used. Change Description: Added a requirement for correlation with Chapter 7 which allows the listed optical fiber cables in classified locations if sealed per Chapter 5 requirements. 2 Impact(s) : No negative impact. Change Description: The wiring methods permitted for intrinsically safe apparatus in explosive dust atmospheres classified under the zone scheme are different from those permitted under the Division scheme. The wiring methods for intrinsically safe apparatus were previously addressed in Section 506.8 – Protection techniques. Impact(s) : No negative impact. Exception: Equipment identified as intrinsically safe “ibD” or Page 105 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table “ib” shall be permitted to be connected using the wiring methods identified in 504.20. 506.15 Wiring Methods. Wiring methods shall maintain the integrity of the protection techniques and shall comply with 506.15(A), (B), or (C). (C) Zone 22. In Zone 22 locations, the following wiring methods shall be permitted. (7) Nonincendive field wiring Intrinsic safety type of protection “ic” shall be permitted using any of the wiring methods permitted for unclassified locations. Nonincendive field wiring Intrinsic safety type of protection “ic” systems shall be installed in accordance with the control drawing(s). Simple Simple apparatus, not shown on the control drawing, shall be permitted in a nonincendive field wiring circuit, circuit of intrinsic safety type of protection “ic”, provided that the simple apparatus does not interconnect the nonincendive field wiringintrinsic safety type of protection “ic” circuit to any other circuit. Separation of nonincendive field wiring circuitscircuits of intrinsic safety type of protection “ic” shall be in accordance with one of the following: Change Description: The wiring methods permitted for intrinsically safe apparatus in explosive dust atmospheres classified under the zone scheme are different from those permitted under the Division scheme. The wiring methods for intrinsically safe apparatus were previously addressed in Section 506.8 – Protection techniques. 506.15 Wiring Methods. Wiring methods shall maintain the integrity of the protection techniques and shall comply with 506.15(A), (B), or (C). (C) Zone 22. In Zone 22 locations, the following wiring methods shall be permitted. (9) Optical fiber cable Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC shall be permitted to be installed in cable trays or any raceway in accordance with 506.15(C). Optical fiber cables shall be sealed in accordance with 506.16. Change Description: Added a requirement for correlation with Chapter 7 which allows the listed optical fiber cables in classified locations if sealed per Chapter 5 requirements. 506.20 Equipment Installation. (D) Material Group. Equipment marked Group IIIC shall be permitted for applications requiring IIIA or IIIB equipment. Similarly, equipment marked Group IIIB shall be Change Description: This change addresses the suitability of equipment marked with the chemical formula of a specific material. Although clear in the 1 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Page 106 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table permitted for applications requiring IIIA equipment. product standards, it is not clear in Article 506 that IIIC equipment is suitable for applications requiring IIIA or IIIB equipment. Similarly, it is not clear that IIIB equipment is suitable for applications requiring IIIA equipment. Impact(s) : No negative impact. 506.21 Multiwire Branch Circuits. In Zone 20 and Zone 21 locations, a multiwire branch circuit shall not be permitted. Exception: Where the disconnect device(s) for the circuit opens all ungrounded conductors of the multiwire circuit simultaneously. 506.25 Grounding and Bonding. Regardless of the voltage of the electrical system, Ggrounding and bonding shall comply with Article 250 and the requirements in 506.25(A) and (B). Change Description: The requirements found in this deleted section are already included in 210.4(B) and do not need to be repeated here. Impact(s) : No negative impact. Change Description: This change clarifies the applicability of this section. 1 Impact(s) : No negative impact. ARTICLE 514 Motor Fuel Dispensing Facilities 514.3 Classification of Locations. [See Figure 514.3.] Change Description: (C) Motor Fuel Dispensing Stations in Boatyards and Relocated the area classification requirements from 555.21(B) Marinas. into a new 514.3(C ). Area classification requirements for motor (1) General. Electrical wiring and equipment located at or fuel dispensing are not appropriate for Section 555.21. serving motor fuel dispensing locations shall be installed on the side of the wharf, pier, or dock opposite from the liquid piping system. (2) Classification of Class I, Division 1 and 2 Areas. The following criteria shall be used for the purposes of applying 1 Impact(s) : No negative impact. Page 107 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Table 514.3(B)(1) and Table 514.3(B)(2) to motor fuel dispensing equipment on floating or fixed piers, wharfs, or docks. (D) Closed Construction. Where the construction of floating docks, piers, or wharfs is closed so that there is no space between the bottom of the dock, pier, or wharf and the water, as in the case of concrete-enclosed expanded foam or similar construction, and the construction includes integral service boxes with supply chases, the following shall apply: (1) The space above the surface of the floating dock, pier, or wharf shall be a Class I, Division 2 location with distances as specified in Table 514.3(B)(1) for dispenser and outdoor locations. (2) Spaces below the surface of the floating dock, pier, or wharf that have areas or enclosures, such as tubs, voids, pits, vaults, boxes, depressions, fuel piping chases, or similar spaces, where flammable liquid or vapor can accumulate shall be a Class I, Division 1 location. Exception No. 1: Dock, pier, or wharf sections that do not support fuel dispensers and abut, but are located 6.0 m (20 ft) or more from, dock sections that support a fuel dispenser(s) shall be permitted to be Class I, Division 2 locations where documented air space is provided between dock sections to allow flammable liquids or vapors to dissipate without traveling to such dock sections. The documentation shall comply with 500.4(A). Exception No. 2: Dock, pier, or wharf sections that do not support fuel dispensers and do not directly abut sections that support fuel dispensers shall be permitted to be unclassified where documented air space is provided and where flammable liquids or vapors cannot travel to such dock sections. The documentation shall comply with 500.4(A). (E) Open Construction. Where the construction of piers, wharfs, or docks is open, as in the case of decks built on stringers supported by pilings, floats, pontoons, or similar Page 108 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table construction, the following shall apply: (1) The area 450 mm (18 in.) above the surface of the dock, pier, or wharf and extending 6.0 m (20 ft) hori- zontally in all directions from the outside edge of the dispenser and down to the water level shall be a Class 1, Division 2 location. (2) Enclosures such as tubs, voids, pits, vaults, boxes, depressions, piping chases, or similar spaces where flammable liquids or vapors can accumulate within 6.0 m (20 ft) of the dispenser shall be a Class I, Division 1 location. ARTICLE 514 Spray Application, Dipping, Coating, and CoatingPrinting Processes Using Flammable or Combustible Materials Flash-Off Area. An open or enclosed area after a spray Change Description: 1 application process where vapors are released due to expoAdded new definitions to Article 514 per NFPA 33. sure to ambient air or a heated atmosphere. [33:3.3.1.1] Limited Finishing Workstation. An apparatus that is capable of confining the vapors, mists, residues, dusts, or deposits that are generated by a spray application process and that meets the requirements of Section 14.3 of NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials, but does not meet the requirements of a spray booth or spray room, as herein defined. [33:3.3.15.1] Impact(s) : No negative impact. Resin Application Area. Any area in which polyester resins or gelcoats are spray applied. [33:3.3.1.2] Spray Area. Normally, locations outside of buildings or localized operations within a larger room or space. Such are normally provided with some local vapor extraction/ventilation system. In automated operations, the area limits shall be the maximum area in the direct path of spray operations. In manual operations, the area limits shall be the maximum area of spray when aimed at 180 degrees Change Description: Revised Spray Area definition per NFPA 33. Impact(s) : No negative impact. Page 109 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table to the application surface. Any fully enclosed, partly enclosed, or unenclosed area in which ignitible quantities of flammable or combustible vapors, mists, residues, dusts, or deposits are present due to the operation of spray processes, including (1) any area in the direct path of a spray application process; (2) the interior of a spray booth or spray room or limited finishing workstation, as herein defined; (3) the interior of any exhaust plenum, eliminator section, or scrubber section; (4) the interior of any exhaust duct or exhaust stack leading from a spray application process; (5) the interior of any air recirculation filter house or enclosure, including secondary recirculation particulate filters; (6) any solvent concentrator (pollution abatement) unit or solvent recovery (distillation) unit. The following are not considered to be a part of the spray area: (1) fresh air make-up units; (2) air supply ducts and air supply plenums; (3) recirculation air supply ducts downstream of secondary filters; (4) exhaust ducts from solvent concentrator (pollution abatement) units. [33:3.3.2.3] Spray Booth. An enclosure or insert within a larger room used for spray/coating/dipping applications. A spray booth may be fully enclosed or have open front or face and may include separate conveyor entrance and exit. The spray booth is provided with a dedicated ventilation exhaust but may draw supply air from the larger room or have a dedicated air supply. A power-ventilated enclosure for a spray application operation or process that confines and limits the escape of the material being sprayed, including vapors, mists, dusts, and residues that are produced by the spraying operation and conducts or directs these materials to an exhaust system. [33:3.3.14] Change Description: Revised Spray Booth definition per NFPA 33. Spray Room. A power-ventilated fully enclosed room used exclusively for open spraying of flammable or combustible materials. A spray room is a purposefully enclosed room built Change Description: Revised Spray Room definition per NFPA 33. 1 Impact(s) : No negative impact. Page 110 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table for spray/coating/dipping applications provided with dedicated ventilation supply and exhaust. Normally the room is configured to house the item to be painted, providing reasonable access around the item/process. Depending on the size of the item being painted, such rooms may actually be the entire building or the major portion thereof. [33:3.3.15] Unenclosed Spray Area. Any spray area that is not confined by a limited finishing workstation, spray booth, or spray room, as herein defined. [33:3.3.2.3.2] Impact(s) : No negative impact. Change Description: Revised Unenclosed Spray Area definition per NFPA 33. 1 Impact(s) : No negative impact. 516.3 Classification of Locations. Classification is based on dangerous quantities of flammable vapors, combustible mists, residues, dusts, or deposits that are present or might be present in quantities sufficient to produce ignitible or explosive mixtures with air. (A) Zone Classification of Locations. (1) For the purposes of this article, the zone system of electrical area classification shall be applied as follows: a. The inside of open or closed containers or vessels shall be considered a Class I, Zone 0 location. b. A Class I, Division 1 location shall be permitted to be alternatively classified as a Class I, Zone 1 location. c. A Class I, Division 2 location shall be permitted to be alternatively classified as a Class I, Zone 2 location. d. A Class II, Division 1 location shall be permitted to be alternatively classified as a Zone 21 location. e. A Class II, Division 2 location shall be permitted to be alternatively classified as a Zone 22 location. [33: 6.2.2] (2) For the purposes of electrical area classification, the division system and the zone system shall not be intermixed for any given source of release. [33:6.2.3] (3) In instances of areas within the same facility classified separately, Class I, Zone 2 locations shall be permitted Change Description: Revised to correlate this section with NFPA 33. Impact(s) : No negative impact. Page 111 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table to abut, but not overlap, Class I, Division 2 locations. Class I, Zone 0 or Zone 1 locations shall not abut Class I, Division 1 or Division 2 locations. [33:6.2.4] (4) Open flames, spark-producing equipment or processes, and equipment whose exposed surfaces exceed the autoignition temperature of the material being sprayed shall not be located in a spray area or in any surrounding area that is classified as Division 2, Zone 2, or Zone 22. Exception: This requirement shall not apply to drying, curing, or fusing apparatus. [33:6.2.5] (5) Any utilization equipment or apparatus that is capable of producing sparks or particles of hot metal and that is located above or adjacent to either the spray area or the urrounding Division 2, Zone 2, or Zone 22 areas shall be of the totally enclosed type or shall be constructed to prevent the escape of sparks or particles of hot metal. [33: 6.2.6] 516.3 Classification of Locations. Classification is based on dangerous quantities of flammable vapors, combustible mists, residues, dusts, or deposits that are present or might be present in quantities sufficient to produce ignitible or explosive mixtures with air. (AB) Class I, Division 1 or Class I, Zone 0 Locations. The following spaces shall be considered Class I, Division 1, or Class I, Zone 0, as applicable: (3) The interior of any ink fountain, ink reservoir, or ink tank Change Description: Replaced unenforceable language and clarified the requirement. Revised to correlate this section with NFPA 34. 516.3 Classification of Locations. Classification is based on dangerous quantities of flammable vapors, combustible mists, residues, dusts, or deposits that are present or might be present in quantities sufficient to produce ignitible or explosive mixtures with air. Change Description: Replaced unenforceable language and clarified the requirement. Revised to correlate this section with NFPA 34. (BC) Class Ior I, Division 1; Class I, Zone 1; Class II, Division 1; or Zone 21 Locations. The following spaces shall be considered Class I, Division 1, or Class I, Zone 1, or Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Page 112 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Class II, Division 1, or Zone 21 locations, as applicable: (7) For limited finishing workstations, the area inside the curtains or partitions. See Figure 516.3(D)(5). 516.3 Classification of Locations. Classification is based on dangerous quantities of flammable vapors, combustible mists, residues, dusts, or deposits that are present or might be present in quantities sufficient to produce ignitible or explosive mixtures with air. (CD) Class Ior I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 Locations. The following spaces shall be considered Class I, Division 2, or 2; Class I, Zone 2, or 2; Class II, Division 2; or Zone 22, as applicable. (1) Open Spraying.Unenclosed Spray Processes. For openunenclosed spraying, all space outside of but within 6 m (20 ft) horizontally and 3 m (10 ft) vertically of the Class I, Division 1 or Class I, Zone 1 location as defined in 516.3(A), and not separated from it by partitions. See Figure 16.3(CD)(1). [33:6.5.1] (2) Closed-Top, Open-Face, and Open-Front Spraying. Spray Booths and Spray Rooms. If spray application operations are conducted within a closed-top, open-face, or open-front booth or room, as shown in Figure 516.3(D)(2) , any electrical wiring or utilization equipment located outside of the booth or room but within the boundaries designated as Division 2 or Zone 2 in Figure 516.3(C)(2) 915 mm (3 ft) of any opening shall be suitable for Class I, Division 2; Class I, Zone 2, or 2; Class II, Division 2;or Zone 22 locations, whichever is applicable. The Class I, Division 2; Class I, Zone 2, or 2; Class II, Division 2;or Zone 22 locations shown in Figure 516.3(CD)(2) shall extend from the edges of the open face or open front of the booth or room in accordance with the following: Change Description: Replaced unenforceable language and clarified the requirement. Revised to correlate this section with NFPA 33 and 34. Impact(s) : No negative impact. (a) If the exhaust ventilation system is interlocked with the spray application equipment, the Division 2 or Zone 2 location shall extend 1.5 m (5 ft) horizontally and 900 mm (3 ft) vertically from the open face or open front of the booth or room, as shown in Figure 516.3(C)(2), top. Page 113 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (b) If the exhaust ventilation system is not interlocked with the spray application equipment, the Division 2 or Zone 2 location shall extend 3 m (10 ft) horizontally and 900 mm (3 ft) vertically from the open face or open front of the booth or room, as shown in Figure 516.3(C)(2), bottom. For the purposes of this subsection, interlocked shall mean that the spray application equipment cannot be oper- ated unless the exhaust ventilation system is operating and functioning properly and spray application is automatically stopped if the exhaust ventilation system fails. [33:6.5.2.2] Figure 516.3(D)(2) Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 Locations Adjacent to a Closed Top, Open Face, or Open Front Spray Booth or Room. (3) Open-Top Spraying.Spray Booths. For spraying operations conducted within an open top spray booth, the space 900915 mm (3 ft) vertically above the booth and within 900915 mm (3 ft) of other booth openings shall be considered Class I, Division 2; Class I, Zone 2; or Class II, Division 2; or Zone 22. [33:6.5.3] (4) Enclosed Spray Booths and Spray Rooms. For spraying operations confined to an enclosed spray booth or room, the space within 900 mm (3 ft) in all directions from any openings considered Class I, Division 2; or Class I, Zone 2; or Class II, Division 2 as shown in Figure 516.3(C)(4).electrical area classification shall be as follows: [33:6.5.4] (5) Dip Tanks and Drain Boards — Surrounding Space. For dip tanks and drain boards, the 914-mm (3-ft) space surrounding the Class I, Division 1 or Class I, Zone 1 location as defined in 516.3(A)(4) and as shown in Figure 516.3(C)(5). [34:6.4.4] (6) Dip Tanks and Drain Boards — Space Above Floor. For dip tanks and drain boards, the space 900 mm (3 ft) above the floor and extending 6 m (20 ft) horizontally in all directions from the Class I, Division 1 or Class I, Zone 1 location. Exception: This space shall not be required to be considered a hazardous (classified) location where the vapor Page 114 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table source area is 0.46 m2 (5 ft2) or less and where the contents of the open tank trough or container do not exceed 19 L (5 gal). In addition, the vapor concentration during operation and shutdown periods shall not exceed 25 percent of the lower flammable limit outside the Class I location specified in 516.3(B)(4). [34:6.4.4 Exception] (1) The area within 915 mm (3 ft) of any opening shall be classified as Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 locations, whichever is applicable, as shown in Figure 516.3(D)(4)(1). (2) Where exhaust air is recirculated, both of the following shall apply: a. The interior of any recirculation path from the secondary particulate filters up to and including the air supply plenum shall be classified as Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 locations, whichever is applicable. b. The interior of fresh air supply ducts shall be unclassified. (3) Where exhaust air is not recirculated, the interior of fresh air supply ducts and fresh air supply plenums shall be unclassified. (5) Limited Finishing Workstations. For limited finishing workstations, the area inside the 915-mm (3-ft) space horizontally and vertically beyond the volume enclosed by the outside surface of the curtains or partitions shall be classified as Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22, as shown in Figure 516.3(D)(5). 6) Areas Adjacent to Open Dipping and Coating Processes. Electrical wiring and electrical utilization equip- ment located adjacent to open processes shall meet the requirements of 516(D)(6)(1) through (4) and Figure 516.3(D)(6)(a), Figure 516.3(D)(6)(b), Figure 516.3(D)(6)(c), Figure 516.3(D)(6)(d), or Figure 516.3(D)(6)(e), whichever is applicable. [34:6.4] (1) Electrical wiring and electrical utilization equipment located in any sump, pit, or below grade channel that is Page 115 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table within 7620 mm (25 ft) horizontally of a vapor source, as defined by this standard, shall be suitable for Class I, Division 1 or Class I, Zone 1 locations. If the sump, pit, or channel extends beyond 7620 mm (25 ft) of the vapor source, it shall be provided with a vapor stop, or it shall be classified as Class I, Division 1 or Class I, Zone 1 for its entire length. [34:6.4.1] (2) Electrical wiring and electrical utilization equipment located within 1525 mm (5 ft) of a vapor source shall be suitable for Class I, Division 1 or Class I, Zone 1 locations. The space inside a dip tank, ink fountain, ink reservoir, or ink tank shall be classified as Class I, Division 1 or Class I, Zone 0, whichever is applicable. [34:6.4.2] (3) Electrical wiring and electrical utilization equipment located within 915 mm (3 ft) of the Class I, Division 1 or Class I, Zone 1 location described in 516.3(D)(6)(2) shall be suitable for Class I, Division 2 or Class I, Zone 2 locations, whichever is applicable. [34:6.4.3] (4) The space 915 mm (3 ft) above the floor and extending 6100 mm (20 ft) horizontally in all directions from the Class I, Division 1 or Class I, Zone 1 location described in 6.4.3 shall be classified as Class I, Division 2 or Class I, Zone 2, and electrical wiring and electrical utilization equipment located within this space shall be suitable for Class I, Division 2 or Class I, Zone 2 locations, whichever is applicable. [34:6.4.4] Exception: This space shall be permitted to be unclassified for purposes of electrical installations if the surface area of the vapor source does not exceed 0.5 m2 (5 ft2), the contents of the dip tank, ink fountain, ink reservoir, or ink tank do not exceed 19 L (5 gal), and the vapor concentration during operating and shutdown periods does not exceed 25 percent of the lower flammable limit. (D7) Enclosed Coating and Dipping Operations. Areas adjacent to enclosed dipping and coating processes shall be Page 116 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table classified in accordance with 516.3(D)(7) and Figure 516.3(D)(7). The space adjacent to an enclosed dipping or coating process or apparatus shall be considered unclassified. [34:6.5.3] Exception: The space within 900915 mm (3 ft) in all direc- tions from any opening in the enclosures shall be classified as Class I, Division 2 or Class I, Zone 2, as applicable. [34:6.5.2] The interior of any enclosed dipping or coating process or apparatus shall be a Class I, Division 1 or Class I, Zone 1 location, and electrical wiring and electrical utilization equipment located within this space shall be suitable for Class I, Division 1 or Class I, Zone 1 locations, whichever is applicable. The area inside the dip tank shall be classified as Class I, Division 1 or Class I, Zone 0, whichever is applicable. [34:6.5.1] 516.4 Wiring and Equipment in Class I Locations. (B) Wiring and Equipment — Vapors and Residues. Unless specifically listed for locations containing deposits of dangerous quantities of flammable or combustible vapors, mists, residues, dusts, or deposits (as applicable), there shall be no electrical equipment in any spray area as herein defined whereon deposits of combustible residue may readily accumulate, except wiring in rigid metal conduit, intermediate metal conduit, Type MI cable, or in metal boxes or fittings containing no taps, splices, or terminal connections. [33:6.4.2]accumulate. All electrical wiring shall be comply with 516.4(A). (C) Illumination. Illumination of readily ignitible areas through panels of glass or other transparent or translucent material shall be permitted only if it complies with the following: (1) Fixed lighting units are used as the source of illumination.Luminaires, like that shown in Figure 516.4(C)(1), that are attached to the walls or ceiling of a spray area but that are outside any classified area and are separated from the spray area by glass panels shall Change Description: Revised to correlate this section with NFPA 33 and 34. Impact(s) : No negative impact. Page 117 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table be suitable for use in unclassified locations. Such fix[33:6.6.1] (2) The panel effectively isolates the Class I location from the area in which the lighting unit is located.Luminaires, like that shown in Figure 516.4(C)(1), that are attached to the walls or ceiling of a spray area; that are separated from the spray area by glass panels and that are located within a Class I, Division 2; a Class I, Zone 2; a Class II, Division 2; or a Zone 22 location shall be suitable for such location. Such fixtures shall be serviced from outside the spray area. [33:6.6.2] (3) The lighting unit is identified for its specific location. Luminaires, like that shown in Figure 516.4(C)(3), that are an integral part of the walls or ceiling of a spray area shall be permitted to be separated from the spray area by glass panels that are an integral part of the fixture. Such fixtures shall be listed for use in Class I, Division 2; Class I, Zone 2; Class II, Division 2; or Zone 22 locations, whichever is applicable, and also shall be listed for accumulations of deposits of combustible residues. Such fixtures shall be permitted to be serviced from inside the spray area. [33:6.6.3] (4) The panel is of a material or is protected so that break-age is unlikely.Glass panels used to separate luminaires from the spray area or that are an integral part of the luminaire shall meet the following requirements. a. Panels for light fixtures or for observation shall be of heat-treated glass, laminated glass, wired glass, or hammered-wired glass and shall be sealed to confine vapors, mists, residues, dusts, and deposits to the spray area. [33:5.5.1] Exception: Listed spray booth assemblies that have vision panels constructed of other materials shall be permitted. (5) b. The arrangement is such that normal accumulations of hazardous residue on the surface of the panel will not be raised to a dangerous temperature by radiation or conduction from the source of illumination. Page 118 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Panels for light fixtures shall be separated from the fixture to prevent the surface temperature of the panel from exceeding 93°C (200°F). [33:5.5.2] c. The panel frame and method of attachment shall be designed to not fail under fire exposure before the vision panel fails. [33:5.5.3] (F) Static Electric Discharges. (1) All persons and all electrically conductive objects, including any metal parts of the process equipment or apparatus, containers of material, exhaust ducts, and piping systems that convey flammable or combustible liquids, shall be electrically grounded. [34:6.8.1] (2) Provision shall be made to dissipate static electric charges from all nonconductive substrates in printing processes. 516.10 Special Equipment. (A) Fixed Electrostatic Equipment. This section shall apply to any equipment using electrostatically charged elements for the atomization, charging, and/or precipitation of hazardous materials for coatings on articles or for other similar purposes in which the charging or atomizing device is attached to a mechanical support or manipulator. This shall include robotic devices. This section shall not apply to devices that are held or manipulated by hand. Where robot or programming procedures involve manual manipulation of the robot arm while spraying with the high voltage on, the provisions of 516.10(B) shall apply. The installation of electrostatic spraying equipment shall comply with 516.10(A)(1) through (A)(10). Spray equipment shall be listed except as otherwise permitted. All automatic electrostatic equipment systems shall comply with 516.4(A)(1) through (A)(9). [33:11.5] (10) Other Than Nonincendive Equipment. Spray equipment that cannot be classified as nonincendive shall comply with (A)(10)(a) and (A)(10)(b). (a) Conveyors or, hangers, and application equipment shall be arranged so as to maintain that a safe distanceminimum separation of at least twice the sparking distance is Change Description: Revised to correlate this section with NFPA 33 and made editorial changes to clarify the language. Impact(s) : No negative impact. Page 119 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table maintained between goods the workpiece or material being paintedsprayed and electrodes, electrostatic atomizing heads, or charged conductors. Warnings defining this safe distance shall be posted. [33:11.4.1] (B) Electrostatic Hand-Spraying Equipment. This section shall apply to any equipment using electrostatically charged elements for the atomization, charging, and/oror precipitation of flammable and combustible materials for coatings on articles, or for other similar purposes in which the charging or atomizing device is hand-held orand manipulated during the spraying operation. Electrostatic handspraying equipment and devices used in connection with paint-spraying operations shall be of listed types and shall comply with 516.10(B)(1) through (B)(5). (3) Handle. The handle of the spraying gun shall be electrically connected to ground by a metallic connectionconductive material and be constructed so that the operator in normal operating position is in intimatedirect electrical contact with the grounded handle with a resistance of not more than 1 megohm to prevent buildup of a static charge on the operator’s body. Signs indicating the necessity for grounding other persons entering the spray area shall be conspicuously posted. (4) Electrostatic Equipment. All electrically conductive objects in the spraying area, except those objects required by the process to be at high voltage, shall be adequately grounded.electrically connected to ground with a resistance of not more than 1 megohm. This requirement shall apply to paint containers, wash cans, and any other electrical conductive objects or devices in the area. The equipment shall carry a prominent, permanently installed warning regarding the necessity for this grounding feature. ARTICLE 517 Health Care Facilities (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 520 Page 120 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Theaters, Audience Areas of Motion Picture and Television Studios, Performance Areas, and Similar Locations (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 522 Control Systems for Permanent Amusement Attractions (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 525 Carnivals, Circuses, Fairs, and Similar Events (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 530 Motion Picture and Television Studios, and Similar Locations (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 540 Motion Picture Projection Rooms (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 547 Agricultural Buildings (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 550 Mobile Homes, Manufactured Homes, and Mobile Home Parks 550.15 Wiring Methods and Materials. Except as speChange Description: cifically limited in this section, the wiring methods and Editorial change, clarifying requirements. materials included in this Code shall be used in mobile homes. Aluminum conductors, aluminum alloy conductors, and aluminum core conductors such as copper-clad aluminum shall not be acceptable for use as branch-circuit wiring. (H) Under-Chassis Wiring (Exposed to Weather). Where outdoor or under-chassis line-voltage (120 volts, nominal, or higher) wiring is exposed to moisture or physical damage, it shall be protected by rigid metal conduit or intermediate metal conduit, except as provided in (1) or (2). a conduit or raceway approved for use in wet locations or where subject to physical damage. The conductors shall be suitablelisted for use in wet locations. Impact(s) : No negative impact. Page 121 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (1) Where closely routed against frames and equipment enclosures, reinforced thermosetting resin conduit (RTRC) listed for aboveground use, Type MI cable, electrical metallic tubing, or rigid polyvinyl chloride conduit (PVC) shall be permitted. (2) Where extending vertically from a direct-burial depth of at least 457 mm (18 in.) below grade and terminated to a factory-installed conduit or enclosure, Schedule 80 PVC or RTRC listed for exposure to physical damage. ARTICLE 551 Recreational Vehicles and Recreational Vehicle Parks (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 552 Park Trailers (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 553 Floating Buildings (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 555 Marinas and Boatyards (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) 590.4 General. (J) Support. Cable assemblies and flexible cords and cables shall be supported in place at intervals that ensure that they will be protected from physical damage. Support shall be in the form of staples, cable ties, straps, or similar type fittings installed so as not to cause damage. Cable assemblies and flexible cords and cables installed as branch circuits or feeders shall not be installed on the floor or on the ground. Extension cords shall not be required to comply with 590.4(J). Vegetation shall not be used for support of overhead spans of branch circuits or feeders. ARTICLE 590 Temporary Installations Change Description: Restricted temporary installation requirements by not allowing cable assemblies and flexible cords to be installed on the floor or on the ground. This restriction does not include extension cords. Impact(s) : Improves safety - no negative impact. Procedures addressing temporary wiring may need to be reviewed to ensure compliance with this new requirement. Page 122 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 590.6 Ground-Fault Protection for Personnel. Groundfault protection for personnel for all temporary wiring installations shall be provided to comply with 590.6(A) and (B). This section shall apply only to temporary wiring installations used to supply temporary power to equipment used by personnel during construction, remodeling, maintenance, repair, or demolition of buildings, structures, equipment, or similar activities. This section shall apply to power derived from an electric utility company or from an on-site-generated power source. (A) Receptacle Outlets. Temporary receptacle installations used to supply temporary power to equipment used by personnel during construction, remodeling, maintenance, repair, or demolition of buildings, structures, equipment, or similar activities shall comply with the requirements of 590.6(A)(1) through (A)(3), as applicable. Change Description: This change clarifies the requirement for GFI protection of personnel, allowing use of listed cord sets or devices with GFI protection, in addition to GFI protected outlets. 2 Impact(s) : No negative impact. Exception: In industrial establishments only, where conditions of maintenance and supervision ensure that only qualified personnel are involved, an assured equipment grounding conductor program as specified in 590.6(B)(2) shall be permitted for only those receptacle outlets used to supply equipment that would create a greater hazard if power were interrupted or having a design that is not compatible with GFCI protection. (1) Receptacle Outlets Not Part of Permanent Wiring. All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that are not a part of the permanent wiring of the building or structure and that are in use by personnel shall have ground-fault circuit-interrupter protection for personnel. Listed cord sets or devices incorporating listed ground-fault circuit-interrupter protection for personnel identified for portable use shall be permitted. ARTICLE 600 Electric Signs and Outline Lighting 600.6 Disconnects. Each sign and outline lighting system, Change Description: feeder circuit or branch circuit supplying a sign, outline Page 123 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table lighting system, or skeleton tubing shall be controlled by an externally operable switch or circuit breaker that opens all ungrounded conductors and controls no other load. The switch or circuit breaker shall open all ungrounded conductors simultaneously on multi-wire branch circuits in accordance with 210.4(B). Signs and outline lighting systems located within fountains shall have the disconnect located in accordance with 680.12. (A) Location. (1) At Point of Entry to a Sign Enclosure. The disconnect shall be located at the point the feeder circuit or branch circuit(s) supplying a sign or outline lighting system enters a sign enclosure or a pole in accordance with 600.5(C)(3) and shall disconnect all wiring where it enters the enclosure of the sign or pole. Exception: A disconnect shall not be required for branch or feeder circuits passing through the sign where enclosed in a Chapter 3 listed raceway. (12) Within Sight of the Sign. The disconnecting means shall be within sight of the sign or outline lighting system that it controls. Where the disconnecting means is out of the line of sight from any section that is able to be energized, the disconnecting means shall be capable of being locked in the open position. lockable in accordance with 110.25. The provision for locking or adding a lock to the disconnecting means must remain in place at the switch or circuit breaker whether the lock is installed or not. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. (23) Within Sight of the Controller. The following shall apply for signs or outline lighting systems operated by electronic or electromechanical controllers located external to the sign or outline lighting system: Added a requirement for a sign disconnecting means to be installed at the supply circuit point of entry. Removed lockable disconnecting means requirements repeated throughout the code and replaced with a reference to Section 110.25, covering these requirements generically. Editorial change, simplifying use of the NEC. Impact(s) : No negative impact. (1) The disconnecting means shall be permitted to be located within sight of the controller or in the same enclosure with the controller. (2) The disconnecting means shall disconnect the sign or Page 124 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table outline lighting system and the controller from all ungrounded supply conductors. (3) The disconnecting means shall be designed such that no pole can be operated independently and shall be capable of being locked in the open position. lockable in accordance with 110.25.The provisions for locking or adding a lock to the disconnecting means must remain in place at the switch or circuit breaker whether the lock is installed or not. Portable means for adding a lock to the switch or circuit breaker shall not be permitted. 600.21 Ballasts, Transformers, Electronic Power Supplies, and Electronic Class 2 Power Supplies.Sources. Ballasts, transformers, electronic power supplies, and Class 2 power sources shall be of the self-contained type or be enclosed by placement in a listed sign body or listed separate enclosure. (A) Accessibility. Ballasts, transformers, electronic power supplies, and electronic Class 2 power suppliessources shall be located where accessible and shall be securely fastened in place. (B) Location. Ballasts, transformers, electronic power supplies, and electronic Class 2 power suppliessources shall be installed as near to the lamps or neon tubing as practicable to keep the secondary conductors as short as possible. (C) Wet Location. Ballasts, transformers, electronic power supplies, and electronic Class 2 power supplies sources used in wet locations shall be of the weatherproof type or be of the outdoor type and protected from the weather by placement in a sign body or separate enclosure. (D) Working Space. A working space at least 900 mm (3 ft) high,high × 900 mm (3 ft) wide, bywide × 900 mm (3 ft) deep shall be provided at each ballast, transformer, electronic power supply, and electronic Class 2 power supplysource or at its enclosure where not installed in a sign. Change Description: Added Class 2 power supplies which are used in LED sign, to ensure that the installation requirements are applied to these power supply sources. Impact(s) : No negative impact. Page 125 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (E) Attic and Soffit Locations. Ballasts, transformers, electronic power supplies, and electronic Class 2 power suppliessources shall be permitted to be located in attics and soffits, provided there is an access door at least 900 mm by× 562.5 mm (36 in. by× 221⁄2 in.) and a passageway of at least 900 mm (3 ft) high by× 600 mm (2 ft) wide with a suitable permanent walkway at least 300 mm (12 in.) wide extending from the point of entry to each component. At least one lighting outlet containing a switch or controlled by a wall switch shall be installed in such spaces. At least one point of control shall be at the usual point of entry to these spaces. The lighting outlet shall be provided at or near the equipment requiring servicing. (F) Suspended Ceilings. Ballasts, transformers, electronic power supplies, and electronic Class 2 power supplies sources shall be permitted to be located above suspended ceilings, provided that their enclosures are securely fastened in place and not dependent on the suspended-ceiling grid for support. Ballasts, transformers, and electronic power supplies installed in suspended ceilings shall not be connected to the branch circuit by flexible cord. 600.32 Neon Secondary-Circuit Wiring, over 1000 Volts, Nominal (A) Wiring Methods. (1) Installation. Conductors shall be installed in rigid metal conduit, intermediate metal conduit, PVC conduit, RTRC, liquidtight flexible nonmetallic conduit, flexible metal conduit, liquidtight flexible metal conduit, electrical metallic tubing, metal enclosures; on insulators in metal raceways; or in other equipment listed for use with neon secondary circuits over 1000 volts. Change Description: Removed PVC and RTRC conduits from the list of acceptable wiring methods for neon secondary –circuit wiring over 1000 V, which were inadvertently inserted in the 2008 version. 1 Impact(s) : No negative impact. ARTICLE 605 Office Furnishings(Consisting of Lighting Accessories and Wired Partitions) 605.5605.6 Lighting Accessories. Lighting equipment Change Description: shall be listed and identified for use with wired partitions Modified language of this article and added clarifications Page 126 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table office furnishings and shall comply with 605.5(A)605.6(A), (B), and (C). (B) Connection. Where cord and plug connection is provided, it shall comply with all of the following: (1) theThe cord length shall be suitable for the intended application but shall not exceed 2.7 m (9 ft) in length. (2) The cord shall not be smaller than 18 AWG, AWG. (3) The cord shall contain an equipment grounding conductor, andexcept as specified in 605.6(B)(4). (4) Cords on the load side of a listed Class 2 power source shall not be required to contain an equipment grounding conductor. (5) The cord shall be of the hard usage type, except as specified in 605.6(B)(6). (6) A cord provided on a listed Class 2 power source shall be of the type provided with the listed luminaire assembly or of the type specified in 725.130 and 725.127. 610.31 Runway Conductor Disconnecting Means. A disconnecting means that has a continuous ampere rating not less than that calculated in 610.14(E) and (F) shall be provided between the runway contact conductors and the power supply. SuchThe disconnecting means shall consist of a motor-circuit switch, circuit breaker, or molded-case switch.comply with 430.109. This disconnecting means shall be as follows: (1) Readily accessible and operable from the ground or floor level (2) Capable of being locked in the open position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. Por table means for adding a lock to the switch or circuit breaker shall not be permitted as the means required to regarding application of Class 2 power sources in office furnishings. Impact(s) : No negative impact. ARTICLE 610 Cranes and Hoists Change Description: Removed lockable disconnecting means requirements repeated throughout the code and replaced with a reference to Section 110.25, covering these requirements generically. In addition, referred to 430.109 for supplemental requirements. Included exception addressing disconnecting means for electrolytic cell lines. Impact(s) : No negative impact. Page 127 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table be installed at and remain with the equipment.Lockable open in accordance with 110.25 Exception: The runway conductor disconnecting means for electrolytic cell lines shall be permitted to be placed out of view of the runway contact conductors where either of the following conditions are met: (1) Where a location in view of the contact conductors is impracticable or introduces additional or increased hazards to persons or property (2) In industrial installations, with written safety procedures, where conditions of maintenance and supervision ensure that only qualified persons service the equipment ARTICLE 620 Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts 620.21 Wiring Methods. Conductors and optical fibers loChange Description: cated in hoistways, in escalator and moving walk wellways, Added exception for cords and cables allowing their installation in platform lifts, stairway chairlift runways, machinery without a raceway, recognizing that some equipment utilized in spaces, control spaces, in or on cars, in machine rooms and hoistways, moving walkways, etc. use cords for power supply control rooms, not including the traveling cables connect(computer displays, power supplies, etc.). The wiring typically ing the car or counterweight and hoistway wiring, shall be installed in rigid metal conduit, intermediate metal conduit, applied for this type of equipment is not meant to be installed in electrical metallic tubing, rigid nonmetallic conduit, or raceways. wireways, or shall be Type MC, MI, or AC cable unless otherwise permitted in 620.21(A) through (C). Exception: Cords and cables of listed cord- and plugconnected equipment shall not be required to be installed in a raceway. 620.22 Branch Circuits for Car Lighting, Receptacle(s), Ventilation, Heating, and Air-Conditioning. (B) Air-Conditioning and Heating Source. A dedicatedseparate branch circuit shall supply the air-conditioning and 2 Impact(s) : No negative impact. Revised to correlate this section with NFPA 33 and 34. Change Description: Editorial change clarifying language. Page 128 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table heating units on each elevator car. The overcurrent device protecting the branch circuit shall be located in the elevator machine room or control room/machinery space or control space. Impact(s) : No negative impact. 620.41 Suspension of Traveling Cables. Traveling cables shall be suspended at the car and hoistways’ ends, or counterweight end where applicable, so as to reduce the strain on the individual copper conductors to a minimum. Traveling cables shall be supported by one of the following means: (1) By their steel supporting member(s) (2) By looping the cables around supports for unsupported lengths less than 30 m (100 ft) (3) By suspending from the supports by a means that automatically tightens around the cable when tension is increased for unsupported lengths up to 60 m (200 ft) Informational Note: Unsupported length for the hoistway suspension means is shall be that length of cable as measured from the point of suspension in the hoistway to the bottom of the loop, with the elevator car located at the bottom landing. Unsupported length for the car suspension means is shall be that length of cable as measured from the point of suspension on the car to the bottom of the loop, with the elevator car located at the top landing. Change Description: Converted the text of the Informational Note to 620.41 into 620.41 as permissive language to clarify the intent of this section. 620.62 Selective Coordination. Where more than one driving machine disconnecting means is supplied by a single feeder, the overcurrent protective devices in each disconnecting means shall be selectively coordinated with any other supply side overcurrent protective devices. Selective coordination shall be selected by a licensed professional engineer or other qualified person engaged primarily in the design, installation, or maintenance of electri- Change Description: Added a requirement to have selective coordination developed by a licensed professional engineer or other qualified person and be made available to AHJ. 1 Impact(s) : No negative impact. Impact(s) : No safety impact. May have an impact on design agencies to Page 129 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table cal systems. The selection shall be documented and made available to those authorized to design, install, inspect, maintain, and operate the system. have documentation from licensed professional engineer to meet the requirement. ARTICLE 625 Electric Vehicle Charging System 625.4 Voltages. Unless other voltages are specified, the Change Description: nominal ac system voltages of 120, 120/240, 208Y/120, Revised to include dc system voltage criteria for supply 240, 480Y/277, 480, 600Y/347, and 600 volts and dc sysequipment covered by Article 625. tem voltages of up to 600 volts shall be used to supply equipment covered by this article. 625.17 Cable.Cords and Cables. The electric vehicle supply equipment cable shall be Type EV, EVJ, EVE, EVJE, EVT, or EVJT flexible cable as specified in Article 400 and Table 400.4. Ampacities shall be as specified in Table 400.5(A)(1) for 10 AWG and smaller, and in Table 400.5(A)(2) for 8 AWG and larger. The overall length of the cable shall not exceed 7.5 m (25 ft) unless equipped with a cable management system that is listed as suitable for the purpose. Other cable types and assemblies listed as being suitable for the purpose, including optional hybrid communications, signal, and composite optical fiber cables, shall be permitted. (A) Power-Supply Cord. The cable for cord-connected equipment shall comply with all of the following: (1) Be any of the types specified in 625.17(B) or hard service cord, junior hard service cord, or portable power cable types in accordance with Table 400.4. Hard service cord, junior hard service cord, or portable power cable types shall be listed, as applicable, for exposure to oil and damp and wet locations. (2) Have an ampacity as specified in Table 400.5(A)(1) or, for 8 AWG and larger, in the 60°C columns of Table 400.5(A)(2). (3) Have an overall length as specified in 625.17(A)(3)a or 2 Impact(s) : No negative impact. Change Description: Part of the renumbering of sections and reorganization of this article into three parts. The changes also address evolving EV technology. Impact(s) : No negative impact. Page 130 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table b as follows: a. When the interrupting device of the personnel protection system specified in 625.22 is located within the enclosure of the supply equipment or charging system, the power-supply cord shall be not more than 300 mm (12 in.) long, b. When the interrupting device of the personnel protection system specified in 625.22 is located at the attachment plug, or within the first 300 mm (12 in.) of the power-supply cord, the overall cord length shall be a minimum of 1.8 m (6 ft) and shall be not greater than 4.6 m (15 ft). (B) Output Cable to the Electric Vehicle. The output cable to the electric vehicle shall be Type EV, EVJ, EVE, EVJE, EVT, or EVJT flexible cable as specified in Table 400.4. (C) Overall Cord and Cable Length. The overall usable length shall not exceed 7.5 m (25 ft) unless equipped with a cable management system that is part of the listed electric vehicle supply equipment. (1) Not Fastened in Place. Where the electric vehicle supply equipment or charging system is not fastened in place, the cord-exposed usable length shall be measured from the face of the attachment plug to the face of the electric vehicle connector. (2) Fastened in Place. Where the electric vehicle supply equipment or charging system is fastened in place, the usable length of the output cable shall be measured from the cable exit of the electric vehicle supply equipment or charging system to the face of the electric vehicle connector. 625.18 Interlock. Electric vehicle supply equipment shall be provided with an interlock that de-energizes the electric vehicle connector and its cable whenever the electrical connector is uncoupled from the electric vehicle. An interlock shall not be required for portable cord-and-plug-connected Change Description: Part of the renumbering of sections and reorganization of this article into three parts. The changes also address evolving EV technology. Page 131 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table electric vehicle supply equipment intended for connection to receptacle outlets rated at 125 volts, single phase, 15 and 20 amperes. An interlock shall not be required for dc supplies less than 50 volts dc. Impact(s) : No negative impact. 625.19 Automatic De-Energization of Cable. The electric vehicle supply equipment or the cable-connector combination of the equipment shall be provided with an automatic means to de-energize the cable conductors and electric vehicle connector upon exposure to strain that could result in either cable rupture or separation of the cable from the electric connector and exposure of live parts. Automatic means to de-energize the cable conductors and electric vehicle connector shall not be required for portable cord-and-plug-connected electric vehicle supply equipment intended for connection to receptacle outlets rated at 125 volts, single phase, 15 and 20 amperes. An interlock shall not be required for dc supplies less than 50 volts dc. Change Description: This change eliminates a need for an interlock for dc supplies less than 50 V dc. 625.14625.41 Rating. Electric vehicle supply equipment shall have sufficient rating to supply the load served. For Electric vehicle charging loads shall be considered to be continuous loads for the purposes of this article. Where an automatic load management system is used, the maximum electric vehicle charging loads supply equipment load on a service and feeder shall be considered to be continuous loads.the maximum load permitted by the automatic load management system. Change Description: Part of the renumbering of sections and reorganization of this article into three parts. The changes also address evolving EV technology. 625.44 Electric Vehicle Supply Equipment Connection. Electric vehicle supply equipment shall be permitted to be cord- and plug-connected to the premises wiring system in accordance with one of the following: Change Description: Part of the renumbering of sections and reorganization of this article into three parts. The changes also address evolving EV technology. (A) Connections to 125-Volt, Single-Phase, 15- and 20-Ampere Receptacle Outlets. Electric vehicle supply equipment intended for connection to nonlocking, 2-pole, 2 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 132 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 2-wire grounding-type receptacle outlets rated at 125 V, single phase, 15 and 20 amperes or from a supply of less than 50 volts dc. (B) Connections to Other Receptacle Outlets. Electric vehicle supply equipment that is rated 250 V maximum and complying with all of the following: (1) It is intended for connection to nonlocking, 2-pole, 3-wire and 3-pole, 4-wire, grounding-type receptacle outlets rated not more than 50 amperes. (2) EVSE is fastened in place to facilitate any of the following: a. Ready removal for interchange b. Facilitation of maintenance and repair c. Repositioning of portable, movable, or EVSE fas- tened in place (3) Power-supply cord length for electric vehicle supply equipment fastened in place is limited to 1.8 m (6 ft). (4) Receptacles are located to avoid physical damage to the flexible cord. All other electric vehicle supply equipment shall be permanently wired and fastened in place to the supporting surface, a wall, a pole, or other structure. The electric vehicle supply equipment shall have no exposed live parts. (A)625.50Location. The electric vehicle supply equipment shall be located to permit for direct connection electrical coupling of the EV connector (conductive or inductive) to the electric vehicle. Unless specifically listed and marked for the location, the coupling means of the electric vehicle supply equipment shall be stored or located at a height of not less than 450 mm (18 in.) above the floor level for indoor locations and 600 mm (24 in.) above the grade level for outdoor locations. (B) Height. Unless specifically listed for the purpose and location, the coupling means of the electric vehicle supply equipment shall be stored or located at a height of not less than 450 mm (18 in.) and not more than 1.2 m (4 ft) above Change Description: Part of the renumbering of sections and reorganization of this article into three parts. The changes also address evolving EV technology. Impact(s) : No negative impact. Page 133 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table the floor level. 625.52 Ventilation. The ventilation requirement for charging an electric vehicle in an indoor enclosed space shall be determined by 625.52(A) or (B). (DB) Ventilation Required. Where the electric vehicle supply equipment is listed or labeled as suitable for charging electric vehicles that require ventilation for indoor charging, and is marked in accordance with 625.15(C), mechanical ventilation, such as a fan, shall be provided. The ventilation shall include both supply and exhaust equipment and shall be permanently installed and located to intake from, and vent directly to, the outdoors. Positivepressure ventilation systems shall be permitted only in vehicle charging buildings or areas that have been specifically designed and approved for that application. Mechanical ventilation requirements shall be determined by one of the methods specified in 625.29(D)625.52(B)(1) through (DB)(4). (4) Supply Circuits. The supply circuit to the mechanical ventilation equipment shall be electrically interlocked with the electric vehicle supply equipment and shall remain energized during the entire electric vehicle charging cycle. Electric vehicle supply equipment shall be marked in accordance with 625.15. Electric vehicle supply equipment receptacles rated at 125 volts, single phase, 15 and 20 amperes shall be marked in accordance with 625.15(C)625.15 and shall be switched, and the mechanical ventilation system shall be electrically interlocked through the switch supply power to the receptacle. Electric vehicle supply equipment supplied from less than 50 volts dc shall be marked in accordance with 625.15(C) and shall be switched, and the mechanical ventilation system shall be electrically interlocked through the switch supply power to the electric vehicle supply 625.30 Outdoor Sites. Outdoor sites shall include but not be limited to residential carports and driveways, curbside, Change Description: Part of the renumbering of sections and reorganization of this article into three parts. The changes also address evolving EV technology. 2 Impact(s) : No negative impact. Change Description: Part of the renumbering of sections and reorganization of this Page 134 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table open parking structures, parking lots, and commercial charging facilities. (A) Location. The electric vehicle supply equipment shall be located to permit direct connection to the electric vehicle. article into three parts. Impact(s) : No negative impact. (B) Height. Unless specifically listed for the purpose and location, the coupling means of electric vehicle supply equipment shall be stored or located at a height of not less than 600 mm (24 in.) and not more than 1.2 m (4 ft) above the parking surface. ARTICLE 645 Information Technology Equipment 645.4 Special Requirements for Information TechnolChange Description: ogy Equipment Room. This article shall be permitted to Section rewritten for better clarity. provide alternate wiring methods to the provisions of Chapters 1 through 4 Chapter 3 and Article 708 for power wirImpact(s) : ing, 725.154Parts I and III of Article 725 for signaling No negative impact. wiring, and 770.113(C) Parts I and Table 770.154(a) Vof Article 770 for optical fiber cabling whenwhere all of the Article 770 for optical fiber cabling whenwhere all of the following conditions are met: (1) Disconnecting means complying with 645.10 are provided. (2) A separate heating/ventilating/air-conditioning (HVAC system is provided in one of the methods identified in 645.4(2) a or b. a. A separate HVAC system that is dedicated for information technology equipment use and is separated from other areas of occupancy.;or b. Any HVAC system that serves other occupancies and meets all of the following: i. shall be permitted to also serve Also serves the information technology equipment room if ii. Provides fire/smoke dampers are provided at the Page 135 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table point of penetration of the room boundary. boundary iii. Such dampers shall operate on activation of Activates the damper operation upon initiation by smoke detectors anddetector alarms, by operation of the disconnecting means required by 645.10. , or by both 645.5 Supply Circuits and Interconnecting Cables. (E) Under Raised Floors. Power cables, communications cables, connecting cables, interconnecting cables, cord-andplug connections, and receptacles associated with the information technology equipment shall be permitted under a raised floor, provided the following conditions are met: (4) Ventilation in the underfloor area is used for the information technology equipment room only, except as provided in 645.4(2). The ventilation system shall be so arranged, with approved smoke detection devices, that upon the detection of fire or products of combustion in the underfloor space, the circulation of air will cease. 6) Cables, other than those covered in 645.5(E)(2) and (E)(3), and those complying with (E)(6)(a) or (E)(6)(b), shall be listed as Type DP cable having adequate fire- resistant characteristics suitable for use under raised floors of an information technology equipment room. are one of the following: Change Description: Section rewritten for better clarity. Impact(s) : No negative impact. a. Listed Type DP cable having adequate fire-resistant characteristics suitable for use under raised floors of an information technology equipment room a. b. Interconnecting cables enclosed in a raceway b. c. Cable type designations shown in Table 645.5 645.5(E)(6) shall be permitted. Green, or green with one or more yellow stripes, insulated single- conductor cables, 4 AWG and larger, marked “for use in cable trays” or “for CT use” shall be permitted for equipment grounding. d. Equipment grounding conductors Page 136 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 645.14 System Grounding. Separately derived power systems shall be installed in accordance with the provisions of Parts I and II of Article 250. Power systems derived within listed information technology equipment that supply information technology systems through receptacles or cable assemblies supplied as part of this equipment shall not be considered separately derived for the purpose of applying 250.30 Change Description: This revision divides the grounding requirements into two different sections: one for equipment grounding and bonding, and one for system grounding. 645.15 Grounding.Equipment Grounding and Bonding. All exposed non–current-carrying metal parts of an information technology system shall be bonded to the equipment grounding conductor in accordance with Parts I, V, VI, VII, and VIII of Article 250 or shall be double insulated. Power systems derived within listed information technology equipment that supply information technology systems through receptacles or cable assemblies supplied as part of this equipment shall not be considered separately derived for the purpose of applying 250.30. Where signal reference structures are installed, they shall be bonded to the equipment grounding conductor provided for the information technology equipment. Any auxiliary grounding electrode(s) installed for information technology equipment shall be installed in accordance with 250.54. Change Description: This revision divides the grounding requirements into two different sections: one for equipment grounding and bonding, and one for system grounding. 645.27 Selective Coordination. Critical operations data system(s) overcurrent protective devices shall be selectively coordinated with all supply-side overcurrent protective devices. Change Description: Added a requirement for a selective coordination of overcurrent protection devices in power supply systems of critical operations data systems. 1 Impact(s) : No negative impact. 1 Impact(s) : No negative impact. Impact(s) : No negative impact. ARTICLE 646 Modular Data Center Page 137 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Added a new Article. The text of this new article not included for brevity. Change Description: Added a new article addressing requirements for modular data centers. 2 Impact(s) : No negative impact. ARTICLE 650 Pipe Organs (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 675 Electrically Driven or Controlled Irrigation Machines (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 680 Swimming Pools, Fountains, and Similar Installations (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) ARTICLE 690 Solar Photovoltaic (PV) Systems 690.4 Installation.General Requirements. Change Description: A) Photovoltaic Systems. Photovoltaic systems shall be Article 690 was rearranged in this edition of the code. Portions of permitted to supply a building or other structure in addition Section 690.4 were moved to Section 690.31. Also, added a to any other electricityelectrical supply system(s). subsection requiring that the personnel installing PV systems (B) Identification and Grouping. Photovoltaic source cirshall be qualified. cuits and PV output circuits shall not be contained in the same raceway, cable tray, cable, outlet box, junction box, or similar fitting as conductors, feeders, or branch circuits of other non-PV systems, unless the conductors of the different systems are separated by a partition. Photovoltaic system conductors shall be identified and grouped as required by 690.4(B)(1) through (4). The means of identification shall be permitted by separate color coding, marking tape, tagging, or other approved means. Impact(s) : No negative impact. (1) Photovoltaic Source Circuits. Photovoltaic source circuits shall be identified at all points of termination, connection, and splices. Page 138 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (2) Photovoltaic Output and Inverter Circuits. The conductors of PV output circuits and inverter input and output circuits shall be identified at all points of termination, connection, and splices. (3) Conductors of Multiple Systems. Where the conductors of more than one PV system occupy the same junction box, raceway, or equipment, the conductors of each system shall be identified at all termination, connection, and splice points. Exception: Where the identification of the conductors is evident by spacing or arrangement, further identification is not required. (4) Grouping. Where the conductors of more than one PV system occupy the same junction box or raceway with a removable cover(s), the ac and dc conductors of each system shall be grouped separately by wire ties or similar means at least once, and then shall be grouped at intervals not to exceed 1.8 m (6 ft). Exception: The requirement for grouping shall not apply if the circuit enters from a cable or raceway unique to the circuit that makes the grouping obvious. (C) Module Connection Arrangement. The connection to a module or panel shall be arranged so that removal of a module or panel from a photovoltaic source circuit does not interrupt a grounded conductor to other PV source circuits. (DB) Equipment. Inverters, motor generators, photovoltaicPV modules, photovoltaicPV panels, ac photovoltaicPV modules, source-circuitdc combiners, dc-to-dc converters, and charge controllers intended for use in photovoltaicPV power systems shall be identified and listed for the PV application. (E) Wiring and Connections. The equipment and systems in 690.4(A) through (D) and all associated wiring and interconnections shall be installed only by qualified persons. Informational Note: See Article 100 for the definition of qualified person. Page 139 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (F) Circuit Routing. Photovoltaic source and PV output conductors, in and out of conduit, and inside of a building or structure, shall be routed along building structural members such as beams, rafters, trusses, and columns where the location of those structural members can be determined by observation. Where circuits are imbedded in built-up, laminate, or membrane roofing materials in roof areas not covered by PV modules and associated equipment, the location of circuits shall be clearly marked. (G) Bipolar Photovoltaic Systems. Where the sum, without consideration of polarity, of the PV system voltages of the two monopole subarrays exceeds the rating of the conductors and connected equipment, monopole subarrays in a bipolar PV system shall be physically separated, and the electrical output circuits from each monopole subarray shall be installed in separate raceways until connected to the inverter. The disconnecting means and overcurrent protective devices for each monopole subarray output shall be in separate enclosures. All conductors from each separate monopole subarray shall be routed in the same raceway. Exception: Listed switchgear rated for the maximum voltage between circuits and containing a physical barrier separating the disconnecting means for each monopole subarray shall be permitted to be used instead of disconnecting means in separate enclosures. (C) Qualified Personnel. The installation of equipment and all associated wiring and interconnections shall be performed only by qualified persons. 690.5 Ground-Fault Protection. Grounded dc photovoltaicPV arrays shall be provided with dc ground-fault protection meeting the requirements of 690.5(A) through (C) to reduce fire hazards. Ungrounded dc photovoltaicPV arrays shall comply with 690.35. Change Description: Exception 2 was deleted because research and actual fires due to ground faults indicated that oversizing the equipmentgrounding conductors in lieu of providing a ground fault protection Page 140 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Exception No. 2: Photovoltaic arrays installed at other than dwelling units shall be permitted without ground-fault protection if each equipment grounding conductor is sized in accordance with 690.45. (A) Ground-Fault Detection and Interruption. The ground fault protection device or system shall: 1) beBe capable of detecting a ground-fault current, ground fault in the PV array dc current-carrying conductors and components, including any intentionally grounded conductors, (2) interruptingInterrupt the flow of fault current, and current (3) providingProvide an indication of the fault.fault, and (4) Be listed for providing PV ground-fault protection Automatically opening the grounded conductor of the faulted circuitfor measurement purposes or to interrupt the ground-fault current path shall be permitted. If a grounded conductor is opened to interrupt the ground-fault current path, all conductors of the faulted circuit shall be automatically and simultaneously opened. Manual operation of the main PV dc disconnect shall not activate the ground-fault protection device or result in grounded conductors becoming ungrounded. would not reduce the potential for fire. Also, expanded the text to better define ground-fault detection requirements. 690.6 Alternating-Current (ac) Modules. (D) Ground-Fault Detection. Alternating-current module systems shall be permitted to use a single detection device to detect only ac ground faults and to disable the array by removing ac power to the ac module(s). Change Description: The text was deleted because there is no readily available equipment that can perform this function. There are no exposed receptacles connected to this system and ground fault detection is not necessary. Impact(s) : No negative impact. Change Description: Reworded and reorganized section to better define the requirements and to clarify expectations. 690.8 Circuit Sizing and Current. (A) Calculation of Maximum Circuit Current. The maximum current for the specific circuit shall be calculated in accordance with 690.8(A)(1) through (A)(45). (5) DC-to-DC Converter Output Current. The maxi- Impact(s) : No negative impact. Page 141 of 203 2 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table mum current shall be the dc-to-dc converter continuous output current rating. (B) Ampacity and Overcurrent Device Ratings.Conductor Ampacity. PhotovoltaicPV system currents shall be considered to be continuous.(2) Conductor Ampacity. Circuit conductors shall be sized to carry not less than the larger of 690.8(B)(2)(a)690.8(B)(1) or (2)(b). (2). (1) Overcurrent Devices. Overcurrent devices, where required, shall be rated as required by 690.8(B)(1)(a) through (1)(d). (a) To carry not less than 125 percent of the maximum currents calculated in 690.8(A). (a)(1) One hundred and twenty-five percent of the maximum currents calculated in 690.8(A) without any additional correction factors for conditions of use. before the application of adjustment and correction factors. (b) Terminal temperature limits shall be in accordance with 110.3(B) and 110.14(C). (c) Where operated at temperatures greater than 40°C (104°F), the manufacturer’s temperature correction factors shall apply. (d) The rating or setting of overcurrent devices shall be permitted in accordance with 240.4(B), (C), and (D). b)(2) The maximum currents calculated in 690.8(A) after conditions of use have been applied.application of adjustment and correction factors. (c) The conductor selected, after application of conditions of use, shall be protected by the overcurrent protective device, where required. Impact(s) : No negative impact. 690.9 Overcurrent Protection. (A) Circuits and Equipment. PhotovoltaicPV source circuit, photovoltaicPV output circuit, inverter output circuit, and storage battery circuit conductors and equipment shall be protected in accordance with the requirements of Article 240. Protection devices for PV source circuits and PV output circuits shall be in accordance with the requirements of 690.9(B) through (E). Circuits, either ac or dc, connected to Change Description: This section was revised for clarity. Also, language was added to insure that listed equipment be used to provide overcurrent protection. Impact(s) : No negative impact. Page 142 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table more than one electrical source shall have overcurrent devices located so as current-limited supplies (e.g., PV modules ac output of utility-interactive inverters) and also connected to provide overcurrent protection from all sources.sources having significantly higher current availability (e.g., parallel strings of modules, utility power), shall be protected at the source from overcurrent. B) Overcurrent Device Ratings. Overcurrent device ratings shall be not less than 125 percent of the maximum currents calculated in 690.8(A). Exception: Circuits containing an assembly, together with its overcurrent device(s), that is listed for continuous operation at 100 percent of its rating shall be permitted to be used at 100 percent of its rating. CD) Photovoltaic Source and Output Circuits. Branchcircuit or supplementary-type Listed PV overcurrent devices shall be permittedrequired to provide overcurrent protection in photovoltaicPV source and output circuits. The overcurrent devices shall be accessible but shall not be required to be readily accessible. Standard values of supplementary overcurrent devices allowed by this section shall be in one ampere size increments, starting at one ampere up to and including 15 amperes. Higher standard values above 15 amperes for supplementary overcurrent devices shall be based on the standard sizes provided in 240.6(A). E) Series Overcurrent Protection. In grounded PV source circuits, a single overcurrent protection device, where required, shall be permitted to protect the PV modules and the interconnecting conductors. In ungrounded PV source circuits complying with 690.35, an overcurrent protection device, where required, shall be installed in each ungrounded circuit conductor and shall be permitted to protect the PV modules and the interconnecting cables. 690.11 Arc-Fault Circuit Protection (Direct Current). Photovoltaic systems with dc source circuits, dc output circuits, or both, on or penetrating a building operating at a Change Description: This section was revised for clarity. Also, prescriptive methods were removed, thereby allowing alternate methods. Page 143 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table PV system maximum system voltage of 80 volts or greater, shall be protected by a listed (dc) arc-fault circuit interrupter, PV type, or other system components listed to provide equivalent protection. The PV arc-fault protection means shall comply with the following requirements: (1) The system shall detect and interrupt arcing faults resulting from a failure in the intended continuity of a conductor, connection, module, or other system component in the dc PV source and dc PV output circuits. 2) The system shall disable or disconnect one of the following: a. Inverters or charge controllers connected to the fault circuit when the fault is detected b. System components within the arcing circuit Impact(s) : No negative impact. 690.12 Rapid Shutdown of PV Systems on Buildings. PV system circuits installed on or in buildings shall include a rapid shutdown function that controls specific conductors in accordance with 690.12(1) through (5) as follows. (1) Requirements for controlled conductors shall apply only to PV system conductors of more than 1.5 m (5 ft) in length inside a building, or more than 3 m (10 ft) from a PV array. (2) Controlled conductors shall be limited to not more than 30 volts and 240 volt-amperes within 10 seconds of rapid shutdown initiation. (3) Voltage and power shall be measured between any two conductors and between any conductor and ground. (4) The rapid shutdown initiation methods shall be labeled in accordance with 690.56(B). (5) Equipment that performs the rapid shutdown shall be listed and identified. Change Description: This new section requires that PV systems installed on building roofs should be equipped with rapid shutdown equipment, deenergizing specific conductors of the system within 10 seconds of rapid shutdown initiation to minimize hazards to firefighters. 690.13 All Conductors.Building or Other Structure Supplied by a Photovoltaic System. Means shall be provided to disconnect all current-carryingungrounded dc conductors of a photovoltaicPV system from all other conduc- Change Description: Section 690.13 was reorganized and rewritten to address various wiring methods previously covered in 690.4 and 690.14 and to improve clarity. Also, moved disconnect construction 2 Impact(s) : Improves safety - no negative impact Page 144 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table tors in a building or other structure. A switch, circuit breaker, requirements to Section 690.17. or other device shall not be installed in a grounded conductor if operation of that switch, circuit breaker, or other device leaves the marked, grounded conductor in an ungrounded and Impact(s) : No negative impact. energized state. Exception No. 1: A switch or circuit breaker that is part of a ground-fault detection system required by 690.5, or that is part of an arc-fault detection/interruption system re- quired by 690.11, shall be permitted to open the grounded conductor when that switch or circuit breaker is automatically opened as a normal function of the device in responding to ground faults. Exception No. 2: A disconnecting switch shall be permitted in a grounded conductor if all of the following conditions are met: (1) The switch is used only for PV array maintenance. (2) The switch is accessible only by qualified persons. (3) The switch is rated for the maximum dc voltage and current that could be present during any operation, including ground-fault conditions. 690.14 Additional Provisions. Photovoltaic disconnecting means shall comply with 690.14(A) through (D). (A) Disconnecting Means. The disconnecting means shall not be required to be suitable as service equipment and shall comply with 690.17. (B) Equipment. Equipment such as photovoltaic source circuit isolating switches, overcurrent devices, and blocking diodes shall be permitted on the photovoltaic side of the photovoltaic disconnecting means. (C) Requirements for Disconnecting Means. Means shall be provided to disconnect all conductors in a building or other structure from the photovoltaic system conductors. (3C) Suitable for Use. Each photovoltaicPV system disconnecting means shall not be suitable for the prevailing Page 145 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table conditions. required to be suitable as service equipment. Equipment installed in hazardous (classified) locations shall comply with the requirements of Articles 500 through 517. 690.15 Disconnection of Photovoltaic Equipment. Means shall be provided to disconnect equipment, such as inverters, batteries, charge controllers, and the like,charge controllers, from all ungrounded conductors of all sources. If the equipment is energized from more than one source, the disconnecting means shall be grouped and identified. A single disconnecting means in accordance with 690.17 shall be permitted for the combined ac output of one or more inverters or ac modules in an interactive system. (B) Equipment. Equipment such as PV source circuit isolating switches, overcurrent devices, dc-to-dc converters, and blocking diodes shall be permitted on the PV side of the PV disconnecting means. (C) Direct-Current Combiner Disconnects. The dc output of dc combiners mounted on roofs of dwellings or other buildings shall have a load break disconnecting means located in the combiner or w i t h i n 1.8 m (6 ft) of the com- biner. The disconnecting means shall be permitted to be remotely controlled but shall be manually operable locally when control power is not available. Change Description: Part of series of changes, reorganizing Article 690 and adding disconnect requirements, aimed at improving firefighters safety in case of an emergency. 690.17 Switch or Circuit Breaker.Disconnect Type. Change Description: Part of series of changes, reorganizing Article 690 and including disconnect requirements, previously covered in other sections of this article. (A) Manually Operable. The disconnecting means for ungrounded PV conductors shall consist of a manually operable switch(es) or circuit breaker(s) breaker(s). The disconnecting means shall be permitted to be power operable with provisions for manual operation in the event of a powersupply failure. complying with all of the following requirements: The disconnecting means shall be one of the following listed devices: (1) Located where readily accessibleA PV industrial control switch marked for use in PV systems (2) Externally operable without exposing the operator to 2 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 146 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table contact with live partsA PV molded-case circuit breaker marked for use in PV systems (3) Plainly indicating whether in the open or closed positionA PV molded-case switch marked for use in PV systems (4) Having an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipmentA PV enclosed switch marked for use in PV systems (5) A PV open-type switch marked for use in PV systems (6) A dc-rated molded-case circuit breaker suitable for backfeed operation (7) A dc-rated molded-case switch suitable for backfeed operation (8) A dc-rated enclosed switch (9) A dc-rated open-type switch (10) A dc-rated rated low-voltage power circuit breaker Where all terminals of the disconnecting means may be energized in the open position, a warning sign shall be ounted on or adjacent to the disconnecting means. The sign shall be clearly legible and have the following words or equivalent: (B) Simultaneous Opening of Poles. The PV disconnecting means shall simultaneously disconnect all ungrounded supply conductors. C) Externally Operable and Indicating. The PV disconnecting means shall be externally operable without exposing the operator to contact with live parts and shall indicate whether in the open or closed position. (D) Disconnection of Grounded Conductor. A switch, circuit breaker, or other device shall not be installed in a grounded conductor if operation of that switch, circuit breaker, or other device leaves the marked, grounded conductor in an ungrounded and energized state. Exception No. 1: A switch or circuit breaker that is part of a ground-fault detection system required by 690.5, or that Page 147 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table is part of an arc-fault detection/interruption system required by 690.11, shall be permitted to open the grounded conductor when that switch or circuit breaker is automatically opened as a normal function of the device in responding to ground faults. Exception No. 2: A disconnecting switch shall be permitted in a grounded conductor if all of the following conditions are met: (1) The switch is used only for PV array maintenance. (2) The switch is accessible only by qualified persons. (3) The switch is rated for the maximum dc voltage and current that could be present during any operation, including ground-fault conditions. (E) Interrupting Rating. The building or structure disconnecting means shall have an interrupting rating sufficient for the maximum circuit voltage and current that is available at the line terminals of the equipment. Where all terminals of the disconnecting means may be energized in the open position, a warning sign shall be mounted on or adjacent to the disconnecting means. The sign shall be clearly legible and have the following words or equivalent: WARNING ELECTRIC SHOCK HAZARD DO NOT TOUCH TERMINALS. TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. The warning sign(s) or label(s) shall comply with 110.21(B). Exception: A connector shall be permitted to be used as an ac or a dc disconnecting means, provided that it complies with the requirements of 690.33 and is listed and identified for the use with specific equipment. Page 148 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 690.31 Methods Permitted. (A) Wiring Systems. All raceway and cable wiring methods included in this Code and , other wiring systems and fittings specifically intended and identified listed for use on photovoltaic arraysPV arrays, and wiring as part of a listed system shall be permitted. Where wiring devices with integral enclosures are used, sufficient length of cable shall be provided to facilitate replacement. Where photovoltaicPV source and output circuits operating at maximum system voltages greater than 30 volts are installed in readily accessible locations, circuit conductors shall be guarded or installed in a raceway. B) Identification and Grouping. PV source circuits and PV output circuits shall not be contained in the same raceway, cable tray, cable, outlet box, junction box, or similar fitting as conductors, feeders, branch circuits of other non-PV systems, or inverter output circuits, unless the conductors of the different systems are separated by a partition. PV system conductors shall be identified and grouped as required by 690.31(B)(1) through (4). The means of identification shall be permitted by separate color coding, marking tape, tagging, or other approved means. Change Description: Part of series of changes, reorganizing Article 690 and addressing various wiring methods, previously covered in other sections of this article. Impact(s) : No negative impact. (1) PV Source Circuits. PV source circuits shall be identified at all points of termination, connection, and splices. (2) PV Output and Inverter Circuits. The conductors of PV output circuits and inverter input and output circuits shall be identified at all points of termination, connection, and splices. 3) Conductors of Multiple Systems. Where the conductors of more than one PV system occupy the same junction box, raceway, or equipment, the conductors of each system shall be identified at all termination, connection, and splice points. Exception: Where the identification of the conductors is evident by spacing or arrangement, further identification shall not be required. Page 149 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (4) Grouping. Where the conductors of more than one PV system occupy the same junction box or raceway with a removable cover(s), the ac and dc conductors of each system shall be grouped separately by cable ties or similar means at least once and shall then be grouped at intervals not to exceed 1.8 m (6 ft). Exception: The requirement for grouping shall not apply if the circuit enters from a cable or raceway unique to the circuit that makes the grouping obvious. 690.31 Methods Permitted. (BC) Single-Conductor Cable. (2) Cable Tray. PV source circuits and PV output circuits using single-conductor cable listed and labeled as photovoltaic (PV) wire of all sizes, with or without a cable tray marking/rating, shall be permitted in cable trays installed in outdoor locations, provided that the cables are supported at intervals not to exceed 300 mm (12 in.) and secured at intervals not to exceed 1.4 m (4.5 ft). Change Description: Part of series of changes, reorganizing Article 690 and addressing various wiring methods, previously covered in other sections of this article. 690.31 Methods Permitted. (D) Multiconductor Cable. Multiconductor cable Type TC-ER or Type USE-2 shall be permitted in outdoor locations in PV inverter output circuits where used with utilityinteractive inverters mounted in locations that are not readily accessible. The cable shall be secured at intervals not exceeding 1.8 m (6 ft). Equipment grounding for the utilization equipment shall be provided by an equipment grounding conductor within the cable. Change Description: Part of series of changes, reorganizing Article 690 and addressing various wiring methods, previously covered in other sections of this article. 690.31 Methods Permitted. (EG) Direct-Current Photovoltaic Source and DirectCurrent Output Circuits on or Inside a Building. Where dc photovoltaicPV source or dc PV output circuits from a building-integrated systems or other photovoltaic systemPV systems are run inside a building or structure, they shall be contained in metal raceways, Type MC metal-clad Change Description: Part of series of changes, reorganizing Article 690 and addressing various wiring methods, previously covered in other sections of this article. 1 Impact(s) : No negative impact. 1 Impact(s) : No negative impact. Impact(s) : Page 150 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table cable that complies with 250.118(10), or metal enclosures from the point of penetration of the surface of the building or structure to the first readily accessible disconnecting means. The disconnecting means shall comply with 690.14(A)690.13(B), (B), and (C) and (D). 690.15(A) and (B). The wiring methods shall comply with the additional installation requirements in 690.31(G)(1) through (4). No negative impact. (1) Beneath Roofs.Embedded in Building Surfaces. Wiring methods shall not be installed within 25 cm (10 in.) of the roof decking or sheathing except where directly below the Where circuits are embedded in built-up, laminate, or membrane roofing materials in roof surface areas not covered by PV modules and associated equipment., the location of circuits Circuits shall be run perpendicular to the roof penetration point to supports a minimum of 25 cm (10 in.) below the roof decking.clearly marked using a marking protocol that is approved as being suitable for continuous exposure to sunlight and weather. (4) Marking and Labeling Methods and Locations. The labels or markings shall be visible after installation. The labels shall be reflective, and all letters shall be capitalized and shall be a minimum height of 9.5 mm (3⁄8 in.) in white on a red background. Photovoltaic PV power circuit labels shall appear on every section of the wiring system that is separated by enclosures, walls, partitions, ceilings, or floors. Spacing between labels or markings, or between a label and a marking, shall not be more than 3 m (10 ft). Labels required by this section shall be suitable for the environment where they are installed. 690.31 Methods Permitted. (I) Bipolar Photovoltaic Systems. Where the sum, without consideration of polarity, of the PV system voltages of the two monopole subarrays exceeds the rating of the conductors and connected equipment, monopole subarrays in a bipolar PV system shall be physically separated, and the electrical output circuits from each monopole subarray shall be installed in separate raceways until connected to Change Description: Part of series of changes, reorganizing Article 690 and addressing various wiring methods, previously covered in other sections of this article. Impact(s) : No negative impact. Page 151 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table the inverter. The disconnecting means and overcurrent protective devices for each monopole subarray output shall be in separate enclosures. All conductors from each separate monopole subarray shall be routed in the same raceway. Bipolar PV systems shall be clearly marked with a permanent, legible warning notice indicating that the disconnecException: Listed switchgear rated for the maximum voltage between circuits and containing a physical barrier separating the disconnecting means for each monopole subarray shall be permitted to be used instead of disconnecting means in separate enclosures. 690.31 Methods Permitted. (J) Module Connection Arrangement. The connection to a module or panel shall be arranged so that removal of a module or panel from a PV source circuit does not interrupt a grounded conductor connection to other PV source circuits. Change Description: Part of series of changes, reorganizing Article 690 and addressing various wiring methods, previously covered in other sections of this article. 1 Impact(s) : No negative impact. 690.35 Ungrounded Photovoltaic Power Systems. Photovoltaic power systems shall be permitted to operate with ungrounded photovoltaicPV source and output circuits where the system complies with 690.35(A) through (G). (C) Ground-Fault Protection. All photovoltaicPV source and output circuits shall be provided with a ground-fault protection device or system that complies with 690.35(1) through (3):(4): (1) Detects a ground fault.fault(s) in the PV array dc current-carrying conductors and components (2) Indicates that a ground fault has occurred (3) Automatically disconnects all conductors or causes the inverter or charge controller connected to the faulted circuit to automatically cease supplying power to out- put circuits. (4) Is listed for providing PV ground-fault protection Change Description: This change provides clarification regarding ground-fault protection devices installed in the ungrounded PV systems. Impact(s) : No negative impact. Page 152 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 690.35 Ungrounded Photovoltaic Power Systems. Photovoltaic power systems shall be permitted to operate with ungrounded photovoltaicPV source and output circuits where the system complies with 690.35(A) through (G). (D) Conductors. The photovoltaicPV source conductors shall consist of the following: (1) Nonmetallic Metallic or nonmetallic jacketed multiconductor cables (2) Conductors installed in raceways, orraceways (3) Conductors listed and identified as Photovoltaic (PV) Wire PV wire installed as exposed, single conductors., or (4) Conductors that are direct-buried and identified for direct-burial use Change Description: This change provides clarification regarding ground-fault protection devices installed in the ungrounded PV systems. 690.41 System Grounding. For a photovoltaic power source, one conductor of a 2-wire system with a photovoltaic system voltage over 50 volts and the reference (center tap) conductor of a bipolar system shall be solidly grounded or shall use other methods that accomplish equivalent system protection in accordance with 250.4(A) and that utilize equipment listed and identified for the use. Change Description: Section revised for clarity into a list format. Also, removed reference to “over 50 volts” since the section now covers all voltage levels of PV systems. Exception: Systems complying with 690.35. Photovoltaic systems shall comply with one of the following: (1) Ungrounded systems shall comply with 690.35. (2) Grounded two-wire systems shall have one conductor grounded or be impedance grounded, and the system shall comply with 690.5. (3) Grounded bipolar systems shall have the reference (center tap) conductor grounded or be impedance grounded, and the system shall comply with 690.5. (4) Other methods that accomplish equivalent system protection in accordance with 250.4(A) with equipment listed and identified for the use shall be permitted to be used. 690.45 Size of Equipment Grounding Conductors. 2 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Change Description: Page 153 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Equipment grounding conductors for photovoltaicPV source and photovoltaicPV output circuits shall be sized in accordance with 690.45(A)250.122 or (B).. Where no overcurrent protective device is used in the circuit, an assumed overcurrent device rated at the PV maximum circuit current shall be used when applying Table 250.122. Increases in equipment grounding conductor size to address voltage drop considerations shall not be required. An equipment grounding conductor shall not be smaller than 14 AWG. A) General. Equipment grounding conductors in photovoltaic source and photovoltaic output circuits shall be sized in accordance with Table 250.122. Where no overcurrent protective device is used in the circuit, an assumed overcurrent device rated at the photovoltaic rated shortcircuit current shall be used in Table 250.122. Increases in equipment grounding conductor size to address voltage drop considerations shall not be required. The equipment grounding conductors shall be no smaller than 14 AWG. Revised section to move text from a subsection to the main body and removed portions no longer valid as a result of changes to other sections in this article. Impact(s) : No negative impact. (B) Ground-Fault Protection Not Provided. For other than dwelling units where ground-fault protection is not provided in accordance with 690.5(A) through (C), each equipment grounding conductor shall have an ampacity of at least two (2) times the temperature and conduit fill corrected circuit conductor ampacity. 690.46 Array Equipment Grounding Conductors. Equipment grounding conductors for photovoltaic modulesFor PV modules, equipment grounding conductors smaller than 6 AWG shall comply with 250.120(C). Where installed in raceways, equipment grounding conductors and grounding electrode conductors not larger than 6 AWG shall be permitted to be solid. Change Description: This change addresses a concern related to migration of water in strands of a conductor and subsequent degradation of the conductor and connections of conductors smaller than #6 AWG. 690.47 Grounding Electrode System. (B) Direct-Current Systems. If installing a dc system, a grounding electrode system shall be provided in accordance with 250.166 for grounded systems or 250.169 for un- Change Description: This added text addresses equipment grounding requirements in ungrounded PV arrays connected to utility-interactive inverters, 2 Impact(s) : No negative impact. Page 154 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table grounded systems. The grounding electrode conductor shall be installed in accordance with 250.64. A common dc grounding-electrode conductor shall be permitted to serve multiple inverters. The size of the common grounding electrode and the tap conductors shall be in accordance with 250.166. The tap conductors shall be connected to the common grounding-electrode conductor by exothermic welding or with connectors listed as grounding and bonding equipment in such a manner that the common grounding electrode conductor remains without a splice or joint. An ac equipment grounding system shall be permitted to be used for equipment grounding of inverters and other equipment and for the ground-fault detection reference for ungrounded PV systems. as allowed by 690.35. 690.47 Grounding Electrode System. (C) Systems with Alternating-Current and DirectCurrent Grounding Requirements. Photovoltaic systems having dc circuits and ac circuits with no direct connection between the dc grounded conductor and ac grounded conductor shall have a dc grounding system. The dc grounding system shall be bonded to the ac grounding system by one of the methods in (1), (2), or (3). This section shall not apply to ac PV modules. When using the methods of (C)(2) or (C)(3), the existing ac grounding electrode system shall meet the applicable requirements of Article 250, Part III. (3) Combined Direct-Current Grounding Electrode Conductor and Alternating-Current Equipment Grounding Conductor. An unspliced, or irreversibly spliced, combined grounding conductor shall be run from the marked dc grounding electrode conductor connection point along with the ac circuit conductors to the grounding busbar in the associated ac equipment. This combined grounding conductor shall be the larger of the sizes specified by 250.122 or 250.166 and shall be installed in accordance with 250.64(E). For ungrounded systems, this con- Change Description: Added wording addresses equipment grounding requirements in ungrounded PV systems. Impact(s) : No negative impact. Impact(s) : No negative impact. Page 155 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ductor shall be sized in accordance with 250.122 and shall not be required to be larger than the largest ungrounded phase conductor. 690.47 Grounding Electrode System. (D) Additional Auxiliary Electrodes for Array Grounding. A grounding electrode shall be installed in accordance with 250.52 and 250.54 at the location of all ground- and pole-mounted PV arrays and as close as practicable to the location of roof-mounted PV arrays. The electrodes shall be connected directly to the array frame(s) or structure. The dc grounding electrode conductor shall be sized according to 250.166. Additional electrodes are not permitted to be used as a substitute for equipment bonding or equipment grounding conductor requirements. The structure of a ground- or pole-mounted PV array shall be permitted to be considered a grounding electrode if it meets the requirements of 250.52. Roof-mounted PV arrays shall be permitted to use the metal frame of a building or structure if the requirements of 250.52(A)(2) are met. Change Description: Re-inserted subsection 690.47(D), inadvertently removed from the code in 2011. 2 Impact(s) : No negative impact. Exception No. 1: An array grounding electrode(s) shall not be required where the load served by the array is integral with the array. Exception No. 2: An additional array grounding electrode(s) shall not be required if located within 1.8 m (6 ft) of the premises wiring electrode. 690.53 Direct-Current Photovoltaic Power Source. A permanent label for the direct-current photovoltaicPV power source indicating items the information specified in (1) through (5) shall be provided by the installer at the photovoltaicPV disconnecting means: (1) Rated maximum power-point current. (2) Rated maximum power-point voltage. (3) Maximum system voltage. (4) Short-circuit current Maximum circuit current. Where the PV power source has multiple outputs, 690.53(1) and (4) shall be specified for each output. Change Description: Clarified the expectations regarding labeling of PV power sources and removed a conflict in terminology between “maximum circuit current” and “short-circuit current”, as they are used in other sections of this article. Impact(s) : No negative impact. Page 156 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 690.56 Identification of Power Sources. (C) Facilities with Rapid Shutdown. Buildings or structures with both utility service and a PV system, complying with 690.12, shall have a permanent plaque or directory including the following wording: PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN The plaque or directory shall be reflective, with all letters capitalized and having a minimum height of 9.5 mm (3⁄8 in.), in white on red background. Change Description: Added requirements for labeling facilities equipped with a rapid shutdown. VIII. Storage Batteries Change Description: Added a new subsection addressing installation of disconnects and overcurrent protection for storage batteries. 690.71 Installation. (H) Disconnects and Overcurrent Protection. Where energy storage device input and output terminals are more than 1.5 m (5 ft) from connected equipment, or where the circuits from these terminals pass through a wall or partition, the installation shall comply with the following: (1) A disconnecting means and overcurrent protection shall be provided at the energy storage device end of the circuit. Fused disconnecting means or circuit breakers shall be permitted to be used. (2) Where fused disconnecting means are used, the line terminals of the disconnecting means shall be connected toward the energy storage device terminals. (3) Overcurrent devices or disconnecting means shall not be installed in energy storage device enclosures where explosive atmospheres can exist. (4) A second disconnecting means located at the connected equipment shall be installed where the disconnecting means required by 690.71(H)(1) is not within sight of the connected equipment. (5) Where the energy storage device disconnecting means is not within sight of the PV system ac and dc disconnecting means, placards or directories shall be installed at the locations of all disconnecting means indicating the location of all disconnecting means. 2 Impact(s) : No negative impact. Impact(s) : Improves safety – no negative impact. Page 157 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table IX. Systems over 6001000 Volts 690.81 Listing. Products listed for PV systems shall be permitted to be used and installed in accordance with their listing. PV wire that is listed for direct burial at voltages above 600 volts, but not exceeding 2000 volts, shall be installed in accordance with Table 300.50, column 1. Change Description: This change addresses listing requirements for PV systems over 1000 V. X. Electric Vehicle Charging 690.90 General. Photovoltaic systems used directly to charge electric vehicles shall comply with Article 625 in addition to the requirements of this article. Change Description: Added references to Article 625, Electric Vehicle Charging Systems, for PV systems used directly to charge electric vehicles. 690.91 Charging Equipment. Electric vehicle couplers shall comply with 625.10. Personnel protection systems in accordance with 625.22 and automatic de-energization of cables in accordance with 625.19 are not required for PV systems with maximum system voltages of less than 2 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. ARTICLE 694 Wind Electric Systems (Note: Changes to this Article in general are not applicable and are not addressed in this evaluation) 695.3 Power Source(s) for Electric Motor-Driven Fire Pumps. Electric motor-driven fire pumps shall have a reliable source of power. (F) Transfer of Power. Transfer of power to the fire pump controller between the individual source and one alternate source shall take place within the pump room. [20:9.6.4] (1) Power Source Selection. Selection of power source shall be performed by a transfer switch listed for fire pump service. [20:10.8.1.3.1] ARTICLE 695 Fire Pumps Change Description: This change correlates Section 695.3 with NFPA 20. Also, it adds text allowing overcurrent protection device for the fire pump to be provided as a part of transfer switch assembly. Impact(s) : No negative impact. (2) Overcurrent Device Selection. An instantaneous trip circuit breaker shall be permitted in lieu of the overcurrent Page 158 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table devices specified in 695.4(B)(2)(a)(1), provided that it is part of a transfer switch assembly listed for fire pump service that complies with 695.4(B)(2)(a)(2). 695.4 Continuity of Power. Circuits that supply electric motor-–driven fire pumps shall be supervised from inadvertent disconnection as covered in 695.4(A) or (B). (A) Direct Connection. The supply conductors shall directly connect the power source to either a listed fire pump controller orcontroller, a listed combination fire pump controller and power transfer switch, or a listed fire pump power transfer switch. (B) Connection Through Disconnecting Means and Overcurrent Device. (a) Individual Sources. Overcurrent protection for individual sources shall comply with 695.4(B)(2)(a)(1) or (2). (1) The oOvercurrent protective device(s) shall be rated to carry indefinitely the sum of the locked-rotor current of largest fire pump motor(s)motor and the pressure maintenance pump motor(s) and the full-load current of all of the other pump motors and the associated fire pump accessory equipment when connected to this power supply. (…) (2) Overcurrent protection shall be provided by an assembly listed for fire pump service and complying with the following: Change Description: This change correlates Section 695.4 with NFPA 20. Also, clarifies requirements regarding locking provisions for disconnecting means, consistent with the rest of the code. Impact(s) : No negative impact. a. The overcurrent protective device shall not open within 2 minutes at 600 percent of the full-load current of the fire pump motor(s). b. The overcurrent protective device shall not open with a re-start transient of 24 times the full-load current of the fire pump motor(s). c. The overcurrent protective device shall not open within 10 minutes at 300 percent of the full-load current of the fire pump motor(s). d. The trip point for circuit breakers shall not be field adjustable. [20:9.2.3.4.1] Page 159 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (3) Disconnecting Means. All disconnecting devices that are unique to the fire pump loads shall comply with items (a) through (e). (a) Features and Location — Normal Power Source. The disconnecting means for the normal power source shall comply with all of the following: [20:9.2.3.1] (2) Be lockable in the closed position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place w i t h or without the lock installed. (3) Not be located within equipment the same enclosure, panelboard, switchboard, switchgear, or motor control center, with or without common bus, that feedssupplies loads other than the fire pump. (b) Features and Location — On-Site Standby Generator. The disconnecting means for an on-site standby generator(s) used as the alternate power source shall be installed in accordance with 700.10(B)(5) for emergency circuits and shall be lockable in the closed position. The provision for locking or adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker used as the disconnecting means and shall remain in place with or without the lock installed. 695.6 Power Wiring. Power circuits and wiring methods shall comply with the requirements in 695.6(A) through (J), and as permitted in 230.90(A), Exception No. 4; 230.94, Exception No. 4; 240.13; 230.208; 240.4(A); and 430.31. (D) Pump Wiring. All wiring from the controllers to the pump motors shall be in rigid metal conduit, intermediate metal conduit, electrical metallic tubing, liquidtight flexible metal conduit, or liquidtight flexible nonmetallic conduit Type LFNC-B, listed Type MC cable with an impervious covering, or Type MI cable. Electrical connections at motor Change Description: Connections in motor terminal boxes made with twist-on, insulation-piercing and soldered connectors have been shown to compromise from motor vibration and thus become a source of failures such as disconnection, overheating, ground fault, and short circuit. Para. 13.5.9.2 of NFPA 79 (Industrial Machinery) already prohibits their use. Impact(s) : Page 160 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table terminal boxes shall be made with a listed means of connection. Twist-on, insulation-piercing–type, and soldered wire connectors shall not be permitted to be used for this purpose. Relay, Automatic Load Control. A device used to energize switched set normally dimmed or normally-off switched emergency lighting equipment from an emergency supply to full power illumination levels in the event of a loss of the normal supply, and to de-energize or supply by bypassing the dimming/switching controls, and to return the emergency lighting equipment to normal status when the device senses the normal supply ishas been restored. 700.8 Surge Protection. A listed SPD shall be installed in or on all emergency systems switchboards and panelboards. Improves safety - no negative impact. ARTICLE 700 Emergency Systems Change Description: Added dimming devices to be overridden by an automatic load control relay. 2 Impact(s) : No negative impact. Change Description: Added a requirement for a listed surge protection devices to be added in or on all emergency system switchboards and panelboards. 2 Impact(s) : Improves safety - no negative impact. 700.10 Wiring, Emergency System. (D) Fire Protection. Emergency systems shall meet the additional requirements in (D)(1) through (D)(3) in assembly occupancies for not less than 1000 persons or in buildings above 23 m (75 ft) in height with any of the following occupancy classes: assembly, educational, residential, detention and correctional, business, and mercantile. 700.12 General Requirements. (B) Generator Set. (6) Outdoor Generator Sets. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means in accordance with 445.18, and the discon- Change Description: The need for fire protection of emergency systems is the same regardless of the occupancy classification. This change eliminates potential exclusion of some of the assembly occupancies from the requirements of this section. Impact(s) : No negative impact. Change Description: This change clarifies the expectations regarding disconnecting means for outdoor generator sets and provides reference to Section 445.18. Page 161 of 203 2 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table necting means is located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. Where the generator supply conductors terminate at a disconnecting means in or on a building or structure, Tthe disconnecting means shall meet the requirements of 225.36. Impact(s) : No negative impact. 700.16 Emergency Illumination. Emergency illumination shall include all required means of egress lighting, illuminated exit signs, and all other lights specified as necessary to provide required illumination. Emergency lighting systems shall be designed and installed so that the failure of any individual lighting element, such as the burning out of a lamp, cannot leave in total darkness any space that requires emergency illumination. Where high-intensity discharge lighting such as highand low-pressure sodium, mercury vapor, and metal halide is used as the sole source of normal illumination, the emergency lighting system shall be required to operate until normal illumination has been restored. Where an emergency system is installed, emergency illumination shall be provided in the area of the disconnecting means required by 225.31 and 230.70, as applicable, where the disconnecting means are installed indoors. Change Description: Added a requirement for emergency illumination in the indoor areas of the disconnecting means installed per 225.31 and 230.70. 700.19 Multiwire Branch Circuits. The branch circuit serving emergency lighting and power circuits shall not be part of a multiwire branch circuit. Change Description: This requirement was added to prevent unnecessary opening of one or two poles of a multi-wire branch circuit because of an overload or short circuit on one pole of a multi-wire circuit overcurrent protection. This change is consistent with similar requirement covered in Article 517. 2 Impact(s) : No negative impact. 2 Impact(s) : Improves safety - no negative impact. 700.24 Directly Controlled Luminaires. Where emer- Change Description: Page 162 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table gency illumination is provided by one or more directly controlled luminaires that respond to an external control input to bypass normal control upon loss of normal power, such luminaires and external bypass controls shall be individually listed for use in emergency systems. This change expands bypass requirements for dimmed luminaires to luminaires with internal onboard dimming capability. 700.26700.27 Ground-Fault Protection of Equipment. The alternate source for emergency systems shall not be required to have ground-fault protection of equipment with automatic disconnecting means. Ground-fault indication of the emergency source shall be provided in accordance with 700.6(D).700.6(D) if ground-fault protection of equipment with automatic disconnecting means is not provided. Change Description: Reworded section for clarity of intent. 700.27700.28 Selective Coordination. Emergency system(s) overcurrent devices shall be selectively coordinated with all supply-side overcurrent protective devices. Selective coordination shall be selected by a licensed professional engineer or other qualified persons engaged primarily in the design, installation, or maintenance of electrical systems. The selection shall be documented and made available to those authorized to design, install, inspect, maintain, and operate the system. Change Description: The additional language adds a requirement and identifies who is responsible for ensuring selective coordination of an emergency system’s overcurrent devices. Impact(s) : Improves safety - no negative impact. 1 Impact(s) : No negative impact. 2 Impact(s) : May have an impact on design agencies to have documentation from licensed professional engineer or other qualified person to meet the requirement. No negative impact. ARTICLE 701 Legally Required Standby Systems 701.12 General Requirements. Change Description: (B) Generator Set. This change clarifies the expectations regarding disconnecting (5) Outdoor Generator Sets. Where an outdoor housed means for outdoor generator sets and provides reference to generator set is equipped with a readily accessible disconSection 445.18. necting means in accordance with 445.18, and the disconImpact(s) : necting means is located within sight of the building or structure supplied, an additional disconnecting means shall No negative impact. not be required where ungrounded conductors serve or pass through the building or structure. Where the generator supply conductors terminate at a disconnecting means in or on Page 163 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table a building or structure, Tthe disconnecting means shall meet the requirements of 225.36. 701.26 Ground-Fault Protection of Equipment. The alternate source for legally required standby systems shall not be required to have ground-fault protection of equipment with automatic disconnecting means. Ground-fault indica- tion of the legally required standby source shall be pro- vided in accordance with 701.6(D).701.6(D) if ground-fault protection of equipment with automatic disconnecting means is not provided. Change Description: Reworded section for clarity of intent. 701.27 Selective Coordination. Legally required standby system(s) overcurrent devices shall be selectively coordinated with all supply-side overcurrent protective devices. Selective coordination shall be selected by a licensed professional engineer or other qualified persons engaged primarily in the design, installation, or maintenance of electrical systems. The selection shall be documented and made available to those authorized to design, install, inspect, maintain, and operate the system. Change Description: The additional language adds a requirement and identifies who is responsible for ensuring selective coordination of an emergency system’s overcurrent devices. 702.7 Signs. (C) Power Inlet. Where a power inlet is used for a temporary connection to a portable generator, a warning sign shall be placed near the inlet to indicate the type of derived system that the system is capable of based on the wiring of the transfer equipment. The sign shall display one of the following warnings: WARNING: FOR CONNECTION OF A SEPARATELY DERIVED (BONDED NEUTRAL) SYSTEM ONLY or 1 Impact(s) : No negative impact. 2 Impact(s) : May have an impact on design agencies to have documentation from licensed professional engineer or other qualified person to meet the requirement. No negative impact. ARTICLE 702 Optional Standby Systems Change Description: A new provision was added requiring a warning sign at the power inlet for temporary connection to a portable generator, indicating type of derived system. Impact(s) : Improves safety - no negative impact. Page 164 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table WARNING: FOR CONNECTION OF A NONSEPARATELY DERIVED (FLOATING NEUTRAL) SYSTEM ONLY 702.12 Outdoor Generator Sets. (A) Permanently Installed Generators and Portable Generators Greater Than 15 kW. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means in accordance with 445.18, and the disconnecting means is located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. Where the generator supply conductors terminate at a disconnecting means in or on a building or structure, Tthe disconnecting means shall meet the requirements of 225.36. B) Portable Generators 15 kW or Less. Where a portable generator, rated 15 kW or less, is installed using a flanged inlet or other cord- and plug-type connection, a disconnecting means shall not be required where ungrounded conductors serve or pass through a building or structure. Change Description: This change clarifies the expectations regarding disconnecting means for outdoor generator sets and provides reference to Section 445.18. Also, the section is now divided into two subsections, for generators greater than 15 kW and generators 15 kW or less. For generators 15 kW or less this new subsection allows omitting disconnecting means for flanged inlet and cordand plug-type connection where ungrounded conductors serve or pass through a building or structure. This provision correlates the requirements with revised section 445.18. Impact(s) : No negative impact. ARTICLE 705 Interconnected Electric Power Production Sources 705.12 Point of Connection. The output of an interconChange Description: nected electric power source shall be connected as specified in Section 705.12(D) was rearranged and reorganized for better 705.12(A), (B), (C), or (D). clarity. Also, deleted redundant ground-fault protection (D) Utility-Interactive Inverters. requirements which are already covered in Section 705.32. (2) Bus or Conductor Ampere Rating. The sum of the ampere ratings of overcurrent devices in circuits supplying power to a busbar or conductor shall not exceed 120 per- cent of the rating of the busbar or conductor. 2 Impact(s) : No negative impact. Exception: Where the photovoltaic system has an energy storage device to allow stand-alone operation of loads, the value used in the calculation of bus or conductor loading shall be 125 percent of the rated utility-interactive current from the inverter instead of the rating of the overcurrent device Page 165 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table between the inverter and the bus or conductor. One hundred twenty-five percent of the inverter output circuit current shall be used in ampacity calculations for the following: (1) Feeders. Where the inverter output connection is made to a feeder at a location other than the opposite end of the feeder from the primary source overcurrent device, that portion of the feeder on the load side of the in- verter output connection shall be protected by one of the following: (a) The feeder ampacity shall be not less than the sum of the primary source overcurrent device and 125 percent of the inverter output circuit current. (b) An overcurrent device on the load side of the inverter connection shall be rated not greater than the ampacity of the feeder. (2) Taps.In systems where inverter output connections are made at feeders, any taps shall be sized based on the sum of 125 percent of the inverter(s) output circuit current and the rating of the overcurrent device protect- ing the feeder conductors as calculated in 240.21(B). 3) Busbars. One of the methods that follows shall be used to determine the ratings of busbars in panelboards. (a) The sum of 125 percent of the inverter(s) output circuit current and the rating of the overcurrent device protecting the busbar shall not exceed the ampacity of the busbar. (b) Where two sources, one a utility and the other an inverter, are located at opposite ends of a busbar that contains loads, the sum of 125 percent of the inverter(s) output circuit current and the rating of the overcurrent device protecting the busbar shall not exceed 120 percent of the ampacity of the busbar. The busbar shall be sized for the loads connected in accordance with Article 220. A permanent warning label shall be applied to the distribution equipment adjacent to the back-fed Page 166 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table breaker from the inverter that displays the following or equivalent wording: WARNING: INVERTER OUTPUT CONNECTION; DO NOT RELOCATE THIS OVERCURRENT DEVICE. The warning sign(s) or label (s) shall comply with 110.21(B). (c) The sum of the ampere ratings of all overcurrent devices on panelboards, both load and supply devices, excluding the rating of the overcurrent device protecting the busbar, shall not exceed the ampacity of the busbar. The rating of the overcurrent device protecting the busbar shall not exceed the rating of the busbar. Permanent warning labels shall be applied to distribution equipment that displays the following or equivalent wording: WARNING: THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT DEVICES, EXCLUDING MAIN SUPPLY OVERCURRENT DEVICE, SHALL NOT EXCEED AMPACITY OF BUSBAR. The warning sign(s) or label (s) shall comply with 110.21(B). (d) Connections shall be permitted on multipleampacity busbars or center-fed panelboards where designed under engineering supervision that includes fault studies and busbar load calculations. (3) Ground-Fault Protection. The interconnection point shall be on the line side of all ground-fault protection equipment. Page 167 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Exception: Connection shall be permitted to be made to the load side of ground-fault protection, provided that there is ground-fault protection for equipment from all ground- fault current sources. Ground-fault protection devices used with supplies connected to the load-side terminals shall be identified and listed as suitable for backfeeding. (7) Inverter Output Connection. Unless the panelboard is rated not less than the sum of the ampere ratings of all overcurrent devices supplying it, a connection in a panelboard shall be positioned at the opposite (load) end from the input feeder location or main circuit location. The bus or conductor rating shall be sized for the loads connected in accordance with Article 220. In systems with panelboards connected in series, the rating of the first overcurrent device directly connected to the output of a utility-interactive inverter(s) shall be used in the calculations for all busbars and conductors. A permanent warning label shall be applied to the distribution equipment with the following or equivalent wording: WARNING INVERTER OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE (6) Wire Harness and Exposed Cable Arc-Fault Protection. A utility-interactive inverter(s) that has a wire harness or cable output circuit rated 240 V, 30 amperes, or less, that is not installed within an enclosed raceway, shall be provided with listed ac AFCI protection. 705.31 Location of Overcurrent Protection. Overcurrent protection for electric power production source conductors, connected to the supply side of the service disconnecting means in accordance with 705.12(A), shall be located within 3 m (10 ft) of the point where the electric power production source conductors are connected to the service. Exception: Where the overcurrent protection for the power Change Description: This new section provides requirements for placing overcurrent protection within three meters from the point where the electric power production source conductors are connected to the service. If the distance from the connection point to the overcurrent protection device exceeds 3 meters, the new exception allows using cable limiters or current-limited circuit Page 168 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table production source is located more than 3 m (10 ft) from the point of connection for the electric power production source to the service, cable limiters or current-limited circuit breakers for each ungrounded conductor shall be installed at the point where the electric power production conductors are connected to the service. breakers at the connection point as a protection for the otherwise unprotected conductors. 705.100 Unbalanced Interconnections. (A) Single Phase. Single-phase inverters for hybrid systems and ac modules in interactive hybrid systems shall not be connected to 3three-phase power systems unless the interconnected system is designed so that significant unbalanced voltages cannot result.in order to limit unbalanced voltages to not more than 3 percent. Change Description: Removed unenforceable language (i.e., “significant”) and replaced it with a specific value of an acceptable voltage unbalance. Impact(s) : Improves safety - no negative impact. Impact(s) : No negative impact. ARTICLE 708 Critical Operations Power Systems (COPS) 708.14 Wiring of HVAC, Fire Alarm, Security, EmerChange Description: gency Communications, and Signaling Systems. All conReworded section for clarity of intent and added a riser-rated ductors or cables shall be installed using any of the metal cable as an acceptable emergency communication cable. wiring methods permitted by 708.10(C)(1) and, in addition, shall comply with 708.14(1) through (8), as applicable. (1) All cables for fire alarm, security, signaling systems, and emergency communications shall be shielded twisted pair cables or installed to comply with the performance requirements of the system. (2) Shields of cables for fire alarm, s e c u r i t y , signaling systems, and emergency communications shall be continuous. arranged in accordance with the manufacturer’s published installation instructions. 2 Impact(s) : No negative impact. (7) All cables for fire a l a r m , security, and signaling sys- tems shall be riser-rated and shall be a listed 2hour electrical circuit protective system. Riser emergency Emergency communication cables shall be Type CMR-CI or shall be riser-rated and shall Page 169 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table be a listed 2-hour electrical circuit protective system. 708.20 Sources of Power. (F) Generator Set. (5) Outdoor Generator Sets. (a) Permanently Installed Generators and Portable Generators Greater Than 15 kW. Where an outdoor housed generator set is equipped with a readily accessible disconnecting means in accordance with 445.18, and the disconnecting means is located within sight of the building or structure supplied, an additional disconnecting means shall not be required where ungrounded conductors serve or pass through the building or structure. Where the generator supply conductors terminate at a disconnecting means in or on a building or structure, the disconnecting means shall meet the requirements of 225.36. (b) Portable Generators 15 kW or Less. Where a portable generator, rated 15 kW or less, is installed using a flanged inlet or other cord-and plug-type connection, a disconnecting means shall not be required where ungrounded conductors serve or pass through a building or structure. Change Description: Revised to correlate with changes in Articles 700, 701, and 702. This change clarifies the expectations regarding disconnecting means for outdoor generator sets and provides reference to Section 445.18. Also, the section is now divided into two subsections, for generators greater than 15 kW and generators 15 kW or less. For generators 15 kW or less this new subsection allows omitting disconnecting means for flanged inlet and cordand plug-type connection where ungrounded conductors serve or pass through a building or structure. This provision correlates the requirements with revised Section 445.18. 708.52 Ground-Fault Protection of Equipment. (D) Selectivity. Ground-fault protection for operation of the service and feeder disconnecting means shall be fully selective such that the feeder device, but not the service device, shall open on ground faults on the load side of the feeder device. A six-cycle minimum separation between the service and feeder Separation of ground-fault tripping bands protection time-current characteristics shall be provided. conform to the manufacturer’s recommendations Operating time of the disconnecting devices shall be considered in selecting the time spread between these two bands and shall consider all required tolerances and disconnect operating time to achieve 100 percent selectivity. 708.54 Selective Coordination. Critical operations power system(s) overcurrent devices shall be selectively coordinated with all supply-side overcurrent protective devices. Selective coordination shall be selected by a licensed Change Description: Revised to reflect changes to Section 517.17(C), introduced in 2008 edition of the Code. This change improves selective coordination for COPS. 2 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Change Description: The additional language adds a requirement and identifies who is responsible for ensuring selective coordination of a COPS’ Page 170 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table professional engineer or other qualified persons engaged primarily in the design, installation, or maintenance of electrical systems. The selection shall be documented and made available to those authorized to design, install, inspect, maintain, and operate the system. Exception: Selective coordination shall not be required between two overcurrent devices located in series if no loads are connected in parallel with the downstream device. overcurrent devices. Impact(s) : May have an impact on design agencies to have documentation from licensed professional engineer or other qualified person to meet the requirement. No negative impact. ARTICLE 725 Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits Power-Limited Tray Cable (PLTC). A factory assembly of Change Description: two or more insulated conductors rated at 300 V, with or Added definition for Power-Limited Tray Cable. without associated bare or insulated equipment grounding conductors, under a nonmetallic jacket. 725.49 Class 1 Circuit Conductors. (B) Insulation. Insulation on conductors shall be rated for the system voltage and not less than 600 volts. 1 Impact(s) : No negative impact. Change Description: Clarified the language regarding applicability of this Article regarding Class 1 circuit conductor insulation. 1 Impact(s) : No negative impact. 725.135 Installation of Class 2, Class 3, and PLTC Cables. Installation of Class 2, Class 3, and PLTC cables shall comply with 725.135(A) through (M). (A) Listing. Class 2, Class 3, and PLTC cables installed in buildings shall be listed. (B) Fabricated Ducts Used for Environmental Air. The Change Description: Added new section addressing installation of Class 2, Class 3, and PLTC cables, similar to Section 800.13, covering communication circuits, including plenum grade cable routing assemblies. This is a companion change to the revision of Section 725.154, separating application and installation rules in to two sections. Page 171 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table following wires and cables shall be permitted in ducts used for environmental air as described in 300.22(B) if they are directly associated with the air distribution system: (1) Types CL2P and CL3P cables in lengths as short as practicable to perform the required function (2) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables installed in raceways that are installed in compliance with 300.22(B) Impact(s) : No negative impact. (C) Other Spaces Used for Environmental Air (Plenums). The following cables shall be permitted in other spaces used for environmental air as described in 300.22(C): (1) Types CL2P and CL3 cables (2) Types CL2P and CL3P cables installed in plenum communications raceways (3) Types CL2P and CL3P cables and plenum communications raceways supported by open metallic cable trays or cable tray systems (4) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables installed in raceways that are installed in compliance with 300.22(C) (5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables supported by solid bottom metal cable trays with solid metal covers in other spaces used for environmental air (plenums) as described in 300.22(C) (6) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables installed in plenum communications raceways, riser communications raceways, and general-purpose communications raceways supported by solid bottom metal cable trays with solid metal covers in other spaces used for environmental air (plenums) as described in 300.22(C) (D) Risers — Cables in Vertical Runs. The following cables shall be permitted in vertical runs penetrating one or more floors and in vertical runs in a shaft: Page 172 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (1) Types CL2P, CL3P, CL2R, and CL3R cables (2) Types CL2P, CL3P, CL2R, and CL3R cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies (E) Risers — Cables in Metal Raceways. The following cables shall be permitted in metal raceways in a riser having firestops at each floor: (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables (2) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables installed in the following: a. Plenum communications raceways b. Riser communications raceways c. General-purpose communications raceways (F) Risers — Cables in Fireproof Shafts. The following shall be permitted to be installed in fireproof riser shafts having firestops at each floor: (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables (2) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies e. General-purpose communications raceways f. General-purpose cable routing assemblies (G) Risers — One- and Two-Family Dwellings. The following cables shall be permitted in one- and two-family dwellings: Page 173 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables (2) Types CL2X and CL3X cables less than 6 mm (0.25 in.) in diameter (3) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies e. General-purpose communications raceways f. General-purpose cable routing assemblies (H) Cable Trays. Cables installed in cable trays outdoors shall be Type PLTC. The following cables shall be permitted to be supported by cable trays in buildings: (1) Types CM CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables (2) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in the following: a. Plenum communications raceways b. Riser communications raceways c. General-purpose communications raceways (I) Cross-Connect Arrays. The following cables shall be permitted to be installed in cross-connect arrays: (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables (2) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies Page 174 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table e. General-purpose communications raceways f. General-purpose cable routing assemblies (J) Industrial Establishments. In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation, Type PLTC cable shall be permitted in accordance with either (1) or (2) as follows: (1) Where the cable is not subject to physical damage, Type PLTC cable that complies with the crush and impact requirements of Type MC cable and is identified as LTC-ER for such use shall be permitted to be exposed between the cable tray and the utilization equipment or device. The cable shall be continuously supported and protected against physical damage using mechanical protection such as dedicated struts, angles, or channels. The cable shall be supported and secured at intervals not exceeding 1.8 m (6 ft). (2) Type PLTC cable, with a metallic sheath or armor in accordance with 725.179(E), shall be permitted to be installed exposed. The cable shall be continuously sup- ported and protected against physical damage using mechanical protection such as dedicated struts, angles, or channels. The cable shall be secured at intervals not exceeding 1.8 m (6 ft). (K) Other Building Locations. The following wires and cables shall be permitted to be installed in building locations other than the locations covered in 725.135(B) through (I): (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables (2) A maximum of 3 m (10 ft) of exposed Type CL2X wires and cables in nonconcealed spaces (3) A maximum of 3 m (10 ft) of exposed Type CL3X wires and cables in nonconcealed spaces (4) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in the following: Page 175 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies e. General-purpose communications raceways f. General-purpose cable routing assemblies (5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC cables installed in raceways recognized in Chapter 3 (6) Type CMUC undercarpet communications wires and cables installed under carpet (L) Multifamily Dwellings. The following wires and cables shall be permitted to be installed in multifamily dwellings in locations other than the locations covered in 725.135(B) through (I): (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables (2) Type CL2X wires and cables less than 6 mm (0.25 in.) in diameter in nonconcealed spaces (3) Type CL3X wires and cables less than 6 mm (0.25 in.) in diameter in nonconcealed spaces (4) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies e. General-purpose communications raceways f. General-purpose cable routing assemblies (5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC wires and cables installed in race- ways recognized in Chapter 3 (6) Type CMUC undercarpet communications wires and cables installed under carpet Page 176 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (M) One- and Two-Family Dwellings. The following wires and cables shall be permitted to be installed in oneand two-family dwellings in locations other than the locations covered in 725.135(B) through (I): (1) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC wires and cables (2) Type CL2X wires and cables less than 6 mm (0.25 in.) in diameter (3) Type CL3X wires and cables less than 6 mm (0.25 in.) in diameter (4) Communications wires and Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, and PLTC cables installed in the following: a. Plenum communications raceways b. Plenum cable routing assemblies c. Riser communications raceways d. Riser cable routing assemblies e. General-purpose communications raceways f. General-purpose cable routing assemblies (5) Types CL2P, CL3P, CL2R, CL3R, CL2, CL3, CL2X, CL3X, and PLTC wires and cables installed in raceways recognized in Chapter 3 (6) Type CMUC undercarpet communications wires and cables installed under carpet 725.154 Applications of Listed Class 2, Class 3, and PLTC Cables. Class 2, Class 3, and PLTC cables shall comply with any of the requirements described in 25.154(A) through (I). (C) and as indicated in Table 725.154. (GA) Class 2 and Class 3 Cable Substitutions. The substitutions for Class 2 and Class 3 cables listed in Table 725.154(GA) and illustrated in Figure 725.154(GA) shall be permitted. Where substitute cables are installed, the wiring requirements of Article 725, Parts I and III, shall Change Description: Converted descriptive portion of this section to a table format (Table 725.154). This is a companion change to the added Section 725.135, separating application and installation rules in to two sections. Impact(s) : No negative impact. Page 177 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table apply. 725.179 Listing and Marking of Class 2, Class 3, and Type PLTC Cables; Communications Raceways; and Cable Routing Assemblies. Class 2, Class 3, and Type PLTC cables and cables, nonmetallic signaling raceways and cable routing assemblies installed as wiring methods within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with 725.179(A) through (K)(J) and shall be marked in accordance with 725.179(L).725.179 (K). (F) Circuit Integrity (CI) Cable or Electrical Circuit Protective System. Cables that are used for survivability of critical circuits under fire conditions shall be listed as circuit integrity (CI) cable.meet either 725.179(F)(1) or (F)(2) as follows: (1) Circuit Integrity (CI) Cables. Circuit Integrity (CI) cables, specified in 725.154(A), and (B), used for survivability of critical circuits, shall have the additional classification using the suffix “CI.” Circuit integrity (CI) cables shall only be permitted to be installed in a raceway where specifically listed and marked as part of an electrical circuit protective system as covered in 725.179(F)(2). Change Description: This change separates the two methods of establishing cable survivability. Cable are either tested as a CI cable or tested as part of an electrical circuit protective system. The new text clarifies the two cable options and marking requirements. 2 Impact(s) : No negative impact. (2) Electrical Circuit Protective System. Cables specified in 725.154(A), and (B), (D)(1), and (E), and used for circuit integrity that are part of an electrical circuit protective system shall have the additional classification using the suffix “-CI”. Cables that are part of a listed electrical circuit protective system shall be considered to meet the requirements of survivability. be identified with the protective system number and hourly rating printed on the outer jacket of the cable and installed in accordance with the listing of the protective system. 725.179 Listing and Marking of Class 2, Class 3, and Type PLTC Cables; Communications Raceways; and Cable Routing Assemblies. Class 2, Class 3, and Type PLTC cables and cables, nonmetallic signaling raceways Change Description: Revised to reflect nomenclature change from “signaling raceway” to “communication raceway”. Page 178 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table and cable routing assemblies installed as wiring methods within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with 725.179(A) through (K)(J) and shall be marked in accordance with 725.179(L).725.179 (K). (I) Plenum Signaling Raceways. Plenum signaling raceways shall be listed as having adequate fire-resistant and low smoke-producing characteristics. Impact(s) : No negative impact. 725.179 Listing and Marking of Class 2, Class 3, and Type PLTC Cables; Communications Raceways; and Cable Routing Assemblies. Class 2, Class 3, and Type PLTC cables and cables, nonmetallic signaling raceways and cable routing assemblies installed as wiring methods within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with 725.179(A) through (K)(J) and shall be marked in accordance with 725.179(L).725.179 (K). (JI) Riser Signaling Raceways.Cable Routing Assemblies. Riser signaling raceways cable routing assemblies shall be listed as having adequate fire-resistant characteristics capable of preventing the carrying of fire from floor to floor. Change Description: Revised to reflect nomenclature change from “signaling raceway” to “communication raceway” and addition of cable routing assemblies. 725.179 Listing and Marking of Class 2, Class 3, and Type PLTC Cables; Communications Raceways; and Cable Routing Assemblies. Class 2, Class 3, and Type PLTC cables and cables, nonmetallic signaling raceways and cable routing assemblies installed as wiring methods within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with 725.179(A) through (K)(J) and shall be marked in accordance with 725.179(L).725.179 (K). (KJ) General-Purpose Signaling Raceways.GeneralUse Cable Routing Assemblies. General-purpose signaling racewaysGeneral-use cable routing assemblies shall be listed as being resistant to the spread of fire. Change Description: Revised to reflect nomenclature change from “signaling raceway” to “communication raceway” and addition of cable routing assemblies. 2 Impact(s) : No negative impact. Impact(s) : No negative impact. Page 179 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ARTICLE 728 Fire-Resistive Cable Systems Added a new Article. The text of this new article not Change Description: included for brevity. This new articles provides installation requirements for fireresistive cable systems. 2 Impact(s) : No negative impact. ARTICLE 750 Energy Management System Added a new Article. The text of this new article not included Change Description: for brevity. This new article provides requirements for installation and operation of energy management systems. 2 Impact(s) : No negative impact. 760.24 Mechanical Execution of Work. (B) Circuit Integrity (CI) Cable. Circuit in tegr ity (CI) cables shall be supported at a distance not exceeding 610 mm (24 in.). Where located within 2.1 m (7 ft) of the floor, as covered in 760.53(A)(1) and 760.130(1), as appli- cable, the cable shall be fastened in an approved manner at intervals of not more than 450 mm (18 in.). Cable supports and fasteners shall be steel. 760.32 Fire Alarm Circuits Extending Beyond One Building. PowerNon–power-limited fire alarm circuits and power-limited fire alarm circuits that extend beyond one building and run outdoors either shall meet the installation ARTICLE 760 Fire Alarm Systems Change Description: This change correlates the installation requirements for CI cables with UL 2196 testing for the cable. 2 Impact(s) : No negative impact. Change Description: As a result of this change all non-power-limited and power-limited signaling system circuits entering a building must be now Page 180 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table requirements of Parts II, III, and IV of Article 800 or shall meet the installation requirements of Part I of Article 300. Non–power-limited fire alarm circuits that extend beyond one building and run outdoors and shall meet the installation requirements of Part I of Article 300 and the applicable sections of Part I of Article 225. provided with transient protection. This change is consistent with the changes to NFPA 72. Impact(s) : Improves safety of fire alarm circuits – no negative impact. 760.51 Number of Conductors in Cable Trays and Raceways, and Ampacity Adjustment Factors. (B) Power-Supply Conductors and Fire AlarmNPLFA Circuit Conductors. Where power-supply conductors and non–power-limited fire alarm circuit conductors are permitted in a raceway in accordance with 760.48, the number of conductors shall be determined in accordance with 300.17. The ampacity adjustment factors given in 310.15(B)(3)(a) shall apply as follows: Change Description: Revised to clarify that this section applies only to non-power limited circuits. 760.135 Installation of PLFA Cables in Buildings. Installation of power-limited fire alarm cables in buildings shall comply with 760.135(A) through (J). (The full text of the article is not included) Change Description: Added new section addressing installation of PLFA cables. This is a companion change to the revision of Section 760.154, separating application and installation rules in to two sections. 1 Impact(s) : No negative impact. 1 Impact(s) : No negative impact. 760.154 Applications of Listed PLFA Cables. PLFA cables shall comply with the requirements described in either 760.154(A), (B), or (C) Table 760.154 or where cable substitutions are made as shown in 760.154(D)760.154(A). Where substitute cables are installed, the wiring requirements of Article 760, Parts I and III, shall apply. Types FPLP-CI, FPLR-CI, and FPL-CI cables shall be permitted to be installed to provide 2-hour circuit integrity rated cables. (A) Plenum. Cables installed in ducts, plenums, and other spaces used for environmental air shall be Type FPLP. Types FPLP, FPLR, and FPL cables installed in compliance Change Description: Converted descriptive portion of this section to a table format (Table 760.154). This is a companion change to the added Section 760.135, separating application and installation rules in to two sections. Impact(s) : No negative impact. Page 181 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table with 300.22 shall be permitted. Type FPLP-CI cable shall be permitted to be installed to provide a 2-hour circuit integrity rated cable. (B) Riser. Cables installed in risers shall be as described in either (1), (2), or (3): (1) Cables installed in vertical runs and penetrating more than one floor, or cables installed in vertical runs in a shaft, shall be Type FPLR. Floor penetrations requiring Type FPLR shall contain only cables suitable for riser or plenum use. Type FPLR-CI cable shall be permitted to be installed to provide a 2-hour circuit integrity rated cable. (2) Other cables shall be installed in metal raceways or located in a fireproof shaft having firestops at each floor. (3) Type FPL cable shall be permitted in one- and twofamily dwellings. Informational Note: See 300.21 for firestop requirements for floor penetrations. (C) Other Wiring Within Buildings. Cables installed in building locations other than those covered in 760.154(A) or (B) shall be as described in either (C)(1), (C)(2), (C)(3), or (C)(4). Type FPL-CI cable shall be permitted to be installed as described in either (C)(1), (C)(2), (C)(3), or (C)(4) to provide a 2-hour circuit integrity rated cable. (1) General. Type FPL shall be permitted. (2) In Raceways. Cables shall be permitted to be installed in raceways. (3) Nonconcealed Spaces. Cables specified in Chapter 3 and meeting the requirements of 760.179(A) and (B) shall be permitted to be installed in nonconcealed spaces where the exposed length of cable does not exceed 3 m (10 ft). (4) Portable Fire Alarm System. A portable fire alarm Page 182 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table system provided to protect a stage or set when not in use shall be permitted to use wiring methods in accordance with 530.12. 760.176 Listing and Marking of NPLFA Cables. Non– power-limited fire alarm cables installed as wiring within buildings shall be listed in accordance with 760.176(A) and (B) and as being resistant to the spread of fire in accordance with 760.176(C) through (F), and shall be marked in accordance with 760.176(G). Cable used in a wet location shall be listed for use in wet locations or have a moistureimpervious metal sheath. (F) Fire Alarm Circuit Integrity (CI) Cable or Electrical Circuit Protective System. Cables that are used for survivability of critical circuits shall be listed as circuit integrity (CI) cable. Cables specified in 760.176(C), (D), and (E), and used for circuit integrity shall have the additional classification using the suffix “-CI.” Cables that are part of a listed electrical circuit protective system shall be considered to meet the requirements of survivability.under fire conditions shall meet either 760.176(F)(1) or (F)(2) as follows: Change Description: This change separates the two methods of establishing cable survivability. Cable are either tested as a CI cable or tested as part of an electrical circuit protective system. The new text clarifies the two cable options and marking requirements. 2 Impact(s) : No negative impact. (1) Circuit Integrity (CI) Cables. Circuit integrity (CI) cables, specified in 760.176(C), (D), and (E), and used for survivability of critical circuits, shall have an additional classification using the suffix “CI.” Circuit integrity (CI) cables shall only be permitted to be installed in a raceway where specifically listed and marked as part of an electrical circuit protective system as covered in 760.176(F)(2). (2) Electrical Circuit Protective System. Cables specified in 760.176(C), (D), (E), and (F)(1), that are part of an electrical circuit protective system, shall be identified with the protective system number and hourly rating printed on the outer jacket of the cable and installed in accordance with the listing of the protective system. 760.179 Listing and Marking of PLFA Cables and In- Change Description: Page 183 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table sulated Continuous Line-Type Fire Detectors. PLFA cables installed as wiring within buildings shall be listed as being resistant to the spread of fire and other criteria in accordance with 760.179(A) through (H) and shall be marked in accordance with 760.179(I). Insulated continuous line-type fire detectors shall be listed in accordance with 760.179(J). Cable used in a wet location shall be listed for use in wet locations or have a moisture-impervious metal sheath. (G) Fire Alarm Circuit Integrity (CI) Cable or Electrical Circuit Protective System. Cables that are used for survivability of critical circuits shall be listed as circuit integrity (CI) cable. Cables specified in 760.179(D), (E), (F), and (H) and used for circuit integrity shall have the additional classification using the suffix “-CI.” Cables that are part of a listed electrical circuit protective system shall be considered to meet the requirements of survivability.under fire conditions shall meet either 760.179(G)(1) or (G)(2) as follows: (1) Circuit Integrity (CI) Cables. Circuit integrity (CI) cables specified in 760.179(D), (E), (F), and (H), and used for survivability of critical circuits, shall have an additional classification using the suffix “CI.” Circuit integrity (CI) cables shall only be permitted to be installed in a raceway where specifically listed and marked as part of an electrical circuit protective system as covered in 760.179(G)(2). (2) Electrical Circuit Protective System. Cables specified in 760.179(D), (E), (F), (H), and (G)(1), that are part of an electrical circuit protective system, shall be identified with the protective system number and hourly rating printed on the outer jacket of the cable and installed in accordance with the listing of the protective system. This change separates the two methods of establishing cable survivability. Cable are either tested as a CI cable or tested as part of an electrical circuit protective system. The new text clarifies the two cable options and marking requirements. Impact(s) : No negative impact. ARTICLE 770 Optical Fiber Cables and Raceways 770.3 Other Articles. Installations of optical fiber cables Change Description: Page 184 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table and raceways shall comply with 770.3(A) and (B). Only those sections of Chapter 2 and Article 300 referenced in this article shall apply to optical fiber cables and raceways. (B) Cables in Ducts for Dust, Loose Stock, or Vapor Removal. The requirements of 300.22(A) for wiring systems shall apply to conductive optical fiber cables. Added new subsection to provide requirements for optical fiber cables, similar to Section 800.3. 770.24 Mechanical Execution of Work. Optical fiber cables shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by hardware including straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform with 300.4(D) and 300.11.300.4(D) through (G) and 300.11. Nonmetallic cable ties and other nonmetallic cable accessories used to secure and support cables in other spaces used for environmental air (plenums) shall be listed as having low smoke and heat release properties. Change Description: Revised to correlate with requirements in NFPA 90A, providing criteria for cable ties and accessories installed in plenums. 770.47 Underground Optical Fiber Cables Entering Buildings. Underground optical fiber cables entering buildings shall comply with 770.47(A) and (B). Change Description: Added new section addressing underground optical fiber cables entering buildings, similar to the sections in Articles 800, 820, 830, and 840. (A) Underground Systems with Electric Light, Power, Class 1, or Non–Power-Limited Fire Alarm Circuit Conductors. Underground conductive optical fiber cables entering buildings with electric light, power, Class 1, or non– power-limited fire alarm circuit conductors in a raceway, handhole enclosure, or manhole shall be located in a section separated from such conductors by means of brick, concrete, or tile partitions or by means of a suitable barrier. Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Impact(s) : No negative impact. (B) Direct-Buried Cables and Raceways. Direct-buried conductive optical fiber cables shall be separated by at least 300 mm (12 in.) from conductors of any electric light, power, or non–power-limited fire alarm circuit conductors Page 185 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table or Class 1 circuit. Exception No. 1: Direct-buried conductive optical fiber cables shall not be required to be separated by at least 300 mm (12 in.) from electric service conductors where electric service conductors are installed in raceways or have metal cable armor. Exception No. 2: Direct-buried conductive optical fiber cables shall not be required to be separated b y at least 300 mm (12 in.) from electric light or power branchcircuit or feeder conductors, non–power-limited fire alarm circuit conductors, or Class 1 circuit conductors where electric light or power branch-circuit or feeder conductors, non– power-limited fire alarm circuit conductors, or Class 1 cir- cuit conductors are installed in a raceway or in metal- sheathed, metal-clad, or Type UF or Type USE cables. 770.49 Metallic Entrance Conduit Grounding. Rigid metal conduit (RMC) or intermediate metal conduit (IMC) containing optical fiber entrance cable shall be connected by a bonding conductor or grounding electrode conductor to a grounding electrode in accordance with 770.100(B). Change Description: Moved the definition containing a requirement to a new section to comply with NEC Style Manual. 770.100 Entrance Cable Bonding and Grounding. Where required, the non–current-carrying metallic members of optical fiber cables entering buildings shall be bonded or grounded as specified in 770.100(A) through (D). Change Description: Added new subsection, providing bonding and grounding conductor length and protection requirements, similar to Articles 800, 820, and 830. (A) Bonding Conductor or Grounding Electrode Conductor. (4) Length. The bonding conductor or grounding electrode conductor shall be as short as practicable. In one- and twofamily dwellings, the bonding conductor or grounding electrode conductor shall be as short as practicable not to exceed 6.0 m (20 ft) in length. Impact(s) : No negative impact. 1 Impact(s) : No negative impact. Page 186 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Exception: In one- and two-family dwellings where it is not practicable to achieve an overall maximum bonding conductor or grounding electrode conductor length of 6.0 m (20 ft), a separate ground rod meeting the minimum dimensional criteria of 770.100(B)(3)(2) shall be driven, the grounding electrode conductor shall be connected to the separate ground rod in accordance with 770.100(C), and the separate ground rod shall be bonded to the power grounding electrode system in accordance with 770.100(D). (56) Physical Damage.Protection. Where necessary, the bonding conductor Bonding conductors and grounding electrode conductors shall be guarded from protected where exposed to physical damage. Where these conductors are the bonding conductor or grounding electrode conductor is installed in a metal raceway, both ends of the raceway shall be bonded to the contained conductors or to the same terminal or electrode to which the conductor(s) is (are)bonding conductor or grounding electrode conductor is connected. 770.110 Raceways and Cable Routing Assemblies for Optical Fiber Cables. (A) Types of Raceways. Optical fiber cables shall be permitted to be installed in any raceway that complies with either 770.110(A)(1) or (A)(2) and in cable routing assemblies installed in compliance with 770.110(C). (2) Other PermittedCommunications Raceways. Optical fiber cables shall be permitted to be installed in listed plenum optical fiber raceway, listed plenum communications raceways, listed riser optical fiber raceway, listed riser communications raceway, listed general-purpose optical fiber raceway, or raceways, and listed general-purpose communications raceways selected in accordance with the provisions of 770.113, 800.110, and 800.113, and installed in accordance with 362.24 through 362.56, where the requirements applicable to electrical nonmetallic tubing (ENT) apply. 770.110 Raceways and Cable Routing Assemblies for Optical Fiber Cables. Change Description: This change is one of a series of changes simplifying types of raceways specified in Articles 770, 800, and 820. 1 Impact(s) : No negative impact. Change Description: This added subsection provides installation rules for cable routing Page 187 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (C) Cable Routing Assemblies. Optical fiber cables shall be permitted to be installed in plenum cable routing assemlies, riser cable routing assemblies, and general-purpose cable routing assemblies selected in accordance with the provisions of 800.113 and Table 800.154(c) and installed in accordance with 770.110(C)(1) and (C)(2). assemblies. Impact(s) : No negative impact. (1) Horizontal Support. Cable routing assemblies shall be supported where run horizontally at intervals not to exceed 900 mm (3 ft), and at each end or joint, unless listed for other support intervals. In no case shall the distance between supports exceed 3 m (10 ft). (2) Vertical Support. Vertical runs of cable routing assemblies shall be supported at intervals not exceeding 1.2 m (4 ft), unless listed for other support intervals, and shall not have more than one joint between supports. 770.113 Installation of Optical Fiber Cables and Raceways, and Cable Routing Assemblies.Cables. Installation of optical fiber cables and raceways, and cable routing assemblies shall comply with 770.113(A) through (J). Installation of raceways shall also comply with 770.12 and 770.110. Change Description: This change is one of a series of changes simplifying types of raceways specified in Articles 770, 800, and 820. This includes deletion of Section 770.182. (A) Listing. Optical fiber cables and raceways, and cable routing assemblies installed in buildings shall be listed. (C) Other Spaces Used For Environmental Air (Plenums). The following cables and raceways shall be permitted in other spaces used for environmental air as described in 300.22(C): (1) Types OFNP and OFCP cables (2) Plenum optical fiber racewayTypes OFNP and OFCP cables installed in plenum communications raceways (3) Types OFNP and OFCP cables installed in plenum optical fiber racewaysupported by open metallic cable trays or plenum communications raceway cable tray systems (4) Types OFNP and OFCP cables and plenum optical fiber raceways supported by open metallic cable trays or cable tray systemsOFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC cables installed in raceways that are Impact(s) : No negative impact. Page 188 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table installed in compliance with 300.22(C) (5) Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC cables installed in raceways that are installed supported by solid bottom metal cable trays with solid metal covers in other spaces used for environmental air (plenums), in compliance with as described in 300.22(C) (6) Types OFNP, OFCP, OFNR, OFCR, OFNG, OFCG, OFN, and OFC cables and installed in plenum optical fiber communications raceways, riser optical fiber raceways and communications raceways, or generalpurpose optical fiber communications raceways supported by solid bottom metal cable trays with solid metal covers in other spaces used for environmental air (plenums), as described in 300.22(C) 770.179 Optical Fiber Cables. Optical fiber cables shall be listed in accordance with 770.179(A) through (E)(F) and shall be marked in accordance with Table 770.179. Optical fiber cables shall have a temperature rating of not less than 60°C (140°F). (E) Optical Fiber Circuit Integrity (CI) Cables or Electrical Circuit Protective System. Cables suitable for use in systems to ensure that are used for survivability of critical circuits and pathways during a specified time under fire conditions shall be additionally listed as circuit integrity (CI) cable. Cables identified in 770.179(A) through (D) that meet the requirements for circuit integrity shall have the additional classification using the suffix “CI.”and meet either 770.179(E)(1) or (E)(2). Change Description: This change separates the two methods of establishing cable survivability. Cable are either tested as a CI cable or tested as part of an electrical circuit protective system. The new text clarifies the two cable options and marking requirements. The added subsection (F) covers marking and listing requirements for field-assembled optical fiber cables. Impact(s) : No negative impact. 770.182 Optical Fiber Raceways and Cable Routing Assemblies.(1) Circuit Integrity (CI) Cables. Optical fiber raceways and cable routing assemblies shall be listed in accordance with 770.182(A) through (C). Circuit integrity (CI) cables specified in 770.179(A) through (D), and used for survivability of critical circuits, shall have an additional classification using the suffix “CI.” In order to Page 189 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table maintain its listed fire rating, circuit integrity (CI) cable shall only be installed in free air. (A) Plenum Optical Fiber Raceway. Plenum optical fiber raceways shall be listed as having adequate fire-resistant and low smoke-producing characteristics. (B2) Riser Optical Fiber Raceways and Cable Routing Assemblies. Fire-Resistive Cables. Riser optical fiber raceways and riser cable routing assemblies shall be listed as having fire-resistant characteristics capable of preventing the carrying of fire from floor to floor. Cables specified in 770.179(A) through (D) and 770.179(E)(1), that are part of an electrical circuit protective system, shall be fire-resistive cable and identified with the protective system number on the product or on the smallest unit container in which the product is packaged and installed in accordance with the listing of the protective system. (C) General-Purpose Optical Fiber Cable Raceways and Cable Routing Assemblies. General-purpose optical fiber cable raceways and cable routing assemblies shall be listed as being resistant to the spread of fire. (F) Field-Assembled Optical Fiber Cables. Fieldassembled optical fiber cable shall comply with 770.179(F)(1) through (4). (1) The specific combination of jacket and optical fibers intended to be installed as a field- assembled optical fiber cable shall be listed in accordance with 770.179(A), (B), or (D) and shall be marked in accordance with Table 770.179. (2) The jacket of a field-assembled optical fiber cable shall have a surface marking indicating the specific optical fibers with which it is listed for use. (3) The optical fibers shall have a permanent marking, such as a marker tape, indicating the jacket with which they are listed for use. (4) The jacket without fibers shall meet the listing requirements for communications raceways in 800.182(A), (B), or (C) in accordance with the cable marking. Page 190 of 203 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 770.180 Grounding Devices. Where bonding or grounding is required, devices used to connect a shield, a sheath, or non–current-carrying metallic members of a cable to a bonding conductor or grounding electrode conductor shall be listed or be part of listed equipment. Change Description: New section added to address requirements for optical fiber cable grounding devices to be listed or part of listed equipment. 2 Impact(s) : No negative impact. ARTICLE 800 Communication Systems 800.12 Innerduct. Listed plenum communications raceway, listed riser communications raceway, and listed general-purpose communications raceway selected in accordance with the provisions of Table 800.154(b) shall be permitted to be installed as innerduct in any type of listed raceway permitted in Chapter 3. Change Description: Added a new definition addressing use of raceways as an innerduct in communication systems. 800.24 Mechanical Execution of Work. Communications circuits and equipment shall be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by hardware, including straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform to 300.4(D) and 300.11. Nonmetallic cable ties and other nonmetallic cable accessories used to secure and support cables in other spaces used for environmental air (plenums) shall be listed as having low smoke and heat release properties. 800.49 Metallic Entrance Conduit Grounding. Rigid metal conduit (RMC) or intermediate metal conduit (IMC) containing communications entrance wire or cable shall be connected by a bonding conductor or grounding electrode Change Description: Revised to correlate with requirements in NFPA 90A, providing criteria for cable ties and accessories installed in plenums. 2 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Change Description: Moved the definition containing a requirement to a new section to comply with NEC Style Manual. Page 191 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table conductor to a grounding electrode in accordance with 800.100(B). 800.110 Raceways and Cable Routing Assemblies for Communications Wires and Cables. (A) Types of Raceways. Communications wires and cables shall be permitted to be installed in any raceway that complies with either (A)(1) or (A)(2) and in cable routing assemblies installed in compliance with 800.110(C). (C) Cable Routing Assemblies. Communications wires and cables shall be permitted to be installed in plenum cable routing assemblies, riser cable routing assemblies, and general-purpose cable routing assemblies selected in accordance with the provisions of 800.113 and installed in accordance with 800.110(C)(1) and (2). Impact(s) : No negative impact. Change Description: This added subsection provides installation rules for cable routing assemblies. 2 Impact(s) : No negative impact. (1) Horizontal Support. Cable routing assemblies shall be supported where run horizontally at intervals not to exceed 900 mm (3 ft), and at each end or joint, unless listed for other support intervals. In no case shall the distance between supports exceed 3 m (10 ft). (2) Vertical Support. Vertical runs of cable routing assemblies shall be supported at intervals not exceeding 1.2 m (4 ft), unless listed for other support intervals, and shall not have more than one joint between supports. 800.113 Installation of Communications Wires, Cables and Raceways, and Cable Routing Assemblies. Installation of communications wires, cables and raceways, and cable routing assemblies shall comply with 800.113(A) through (L). Installation of raceways and cable routing assemblies shall also comply with 800.110. (A) Listing. Communications wires, communications cables, communications raceways, and racewayscable routing assemblies installed in buildings shall be listed. (C) Other Spaces Used for Environmental Air (Plenums). The following wires, cables, and raceways shall be Change Description: Expanded scope of the section to include cable routing assemblies. Impact(s) : No negative impact. Page 192 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table permitted in other spaces used for environmental air as described in 300.22(C): (7) Types CMP, CMR, CMG, CM, and CMX cables installed in plenum communications raceways, riser communications raceways, and general-purpose communications raceways supported by solid bottom metal cable trays with solid metal covers in other spaces used for environmental air (plenums) as described in 300.22(C) (D) Risers — Cables and Raceways in Vertical Runs. The following cables, raceways, and raceways cable routing assemblies shall be permitted in vertical runs penetrating one or more floors and in vertical runs in a shaft: (3) Plenum and riser cable routing assemblies (F) Risers — Cables, Raceways, and RacewaysCable Routing Assemblies in Fireproof Shafts. The following cables, raceways, and raceways cable routing assemblies shall be permitted to be installed in fireproof riser shafts having firestops at each floor: (3) Plenum, riser, and general-purpose cable routing assemblies 800.154 Applications of Listed Communications Wires, Cables and Raceways, and Listed Cable Routing Assemblies. Permitted and nonpermitted applications of listed communications wires, cables, and raceways, and listed cable routing assemblies, shall be in accordance with one of the following: (1) Listed communications wires and cables as indicated in Table 800.154(a). (2) Listed communications raceways as indicated in Table 800.154(b) (3) Listed cable routing assemblies as indicated in Table 800.154(c) Change Description: Expanded scope of the section to include cable routing assemblies. 800.170 Equipment. Communications equipment shall be listed as being suitable for electrical connection to a communications network. (C) Plenum Grade Cable Ties. Cable ties intended for Change Description: Revised to correlate with requirements in NFPA 90A, providing criteria for cable ties and accessories installed in plenums. 2 Impact(s) : No negative impact. Page 193 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table use in other space used for environmental air (plenums) shall be listed as having low smoke and heat release properties. G) Communications Circuit Integrity (CI) Cables or Electrical Circuit Protective System. Cables suitable for use in communications systems to ensure that are used for survivability of critical circuits during a specified time under fire conditions shall be listed as circuit integrity (CI) cable. Cables identified in 800.179(A) through (E) that and meet the requirements for circuit integrity shall have the additional classification using the suffix “CI.”either 800.179(G)(1) or (2) as follows: (1) Circuit Integrity (CI) Cables. Circuit integrity (CI) cables specified in 800.179(A) through (E), and used for survivability of critical circuits, shall have an additional classification using the suffix “CI.” In order to maintain its listed fire rating, circuit integrity (CI) cable shall only be installed in free air. (2) Fire-Resistive Cables. Cables specified in 800.179(A) through (E) and 800.179(G)(1), that are part of an electrical circuit protective system, shall be fire-resistive cable identified with the protective system number on the product, or on the smallest unit container in which the product is packaged, and shall be installed in accordance with the listing of the protective system. Also, the change in subsection (G) separates the two methods of establishing cable survivability. Cable are either tested as a CI cable or tested as part of an electrical circuit protective system. The new text clarifies the two cable options and marking requirements. 800.180 Grounding Devices. Where bonding or grounding is required, devices used to connect a shield, a sheath, or non–current-carrying metallic members of a cable to a bonding conductor or grounding electrode conductor shall be listed or be part of listed equipment. (A) Plenum Communications Raceways and Plenum Cable Routing Assemblies. Plenum communications raceways and plenum cable routing assemblies listed as plenum optical fiber raceways shall be permitted for use in ducts, plenums, and other spaces used for environmental air and shall also be listed as having adequate fire-resistant and low smoke-producing characteristics. Change Description: New section added to address requirements for communication circuits grounding devices to be listed or part of listed equipment. Impact(s) : No negative impact. Impact(s) : No negative impact. Page 194 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table ARTICLE 810 Radio and Television Equipment 810.6 Antenna Lead-In Protectors. Where an antenna Change Description: lead-in surge protector is installed, it shall be listed as being Antenna lead-in protectors may be subject to high energy suitable for limiting surges on the cable that connects the lightning surges in the range of 5-50 kA or higher. Listing and antenna to the receiver/transmitter electronics and shall be compliance with appropriate requirements ensure that the connected between the conductors and the grounded shield protector can withstand these surges without introducing a risk of or other ground connection. The antenna lead-in protector shall be grounded using a bonding conductor or grounding fire or personal injury (from explosions) and also that the electrode conductor installed in accordance with 810.21(F). protector will continue to provide surge protection after being subjected to various environmental and surge conditions that may be expected in an typical installation. 2 Impact(s) : Improves safety - no negative impact. 810.7 Grounding Devices. Where bonding or grounding is required, devices used to connect a shield, a sheath, non– current-carrying metallic members of a cable, or metal parts of equipment or antennas to a bonding conductor or grounding electrode conductor shall be listed or be part of listed equipment. Change Description: New section added to address requirements for Radio and television equipment grounding devices to be listed or part of listed equipment. 2 Impact(s) : No negative impact. ARTICLE 820 Community Antenna Television and Radio Distribution Systems 820.3 Other Articles. Circuits and equipment shall comChange Description: ply with 820.3(A) through (G).(J). Added references to Section 300.22 for community antenna (B) Wiring in Ducts for Dust, Loose Stock, or Vapor television and radio distribution wiring systems installed in ducts Removal. The requirements of 300.22(A) shall apply. and other spaces used for environmental air. (C) Equipment in Other Space Used for Environmental Air. The requirements of 300.22(C)(3) shall apply. Impact(s) : No negative impact. Page 195 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table 820.24 Mechanical Execution of Work. Community television and radio distribution systems shall be installed in a neat and workmanlike manner. Coaxial cables installed exposed on the surface of ceiling and sidewalls shall be supported by the building structure in such a manner that the cables will not be damaged by normal building use. Such cables shall be secured by hardware including straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform to 300.4(D) and 300.11. Nonmetallic cable ties and other nonmetallic cable accessories used to secure and support cables in other spaces used for environmental air (plenums) shall be listed as having low smoke and heat release properties. Change Description: Revised to correlate with requirements in NFPA 90A, providing criteria for cable ties and accessories installed in plenums. 820.47 Underground Coaxial Cables Entering Buildings. Underground coaxial cables entering buildings shall comply with 820.47(A) and (B). (A) Underground Systems with Electric Light and Power, Power, Class 1, or Non–Power-Limited Fire Alarm Circuit Conductors. Underground coaxial cables in a duct, pedestal, handhole enclosure, or manhole that contains electric light, power, or power conductorsClass 1 or Class 1 circuitsnon–power-limited fire alarm circuit conductors shall be in a section permanently separated from such conductors by means of a suitable barrier. Change Description: This change addresses non-power-limited fire alarm circuits missing from this section. 820.49 Metallic Entrance Conduit Grounding. Rigid metal conduit (RMC) or intermediate metal conduit (IMC) containing entrance coaxial cable shall be connected by a bonding conductor or grounding electrode conductor to a grounding electrode in accordance with 820.100(B). Change Description: Moved the definition containing a requirement to a new section to comply with NEC Style Manual. 820.100 Cable Bonding and Grounding. The shield of the coaxial cable shall be bonded or grounded as specified in 820.100(A) through (D). Change Description: Correlates with similar requirements in Articles 770, 800, and 830, not allowing the use of steam or hot water pipes as 2 Impact(s) : No negative impact. 2 Impact(s) : No negative impact. 1 Impact(s) : No negative impact. Page 196 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table (3) In Buildings or Structures Without an Intersystem Bonding Termination or Grounding Means. If the building or structure served has no intersystem bonding termination or grounding means, as described in 820.100(B)(2), the grounding electrode conductor shall be connected to either of the following: (2) If the building or structure served has no intersystem bonding termination or grounding means, as described in 820.100(B)(2) or (B)(3)(1), to any one of the individual grounding electrodes described in 250.52(A)(5), (A)(7), and (A)(8). Steam or hot water pipes or air terminal conductors (lightning-rod conductors) shall not be employed as grounding electrodes for bonding conductors or grounding electrode conductors. grounding electrodes. 820.110 Raceways and Cable Routing Assemblies for Coaxial Cables. (C) Cable Routing Assemblies. Coaxial cables shall be permitted to be installed in plenum cable routing assemblies, riser cable routing assemblies, and general-purpose cable routing assemblies selected in accordance with the provisions of 800.113 and installed in accordance with 820.110(C)(1) and (2). (1) Horizontal Support. Cable routing assemblies shall be supported where run horizontally at intervals not to exceed 900 mm (3 ft), and at each end or joint, unless listed for other support intervals. In no case shall the distance between supports exceed 3 m (10 ft) (2) Vertical Support. Vertical runs of cable routing assemblies shall be supported at intervals not exceeding 1.2 m (4 ft), unless listed for other support intervals, and shall not have more than one joint between supports. Change Description: This added subsection provides installation rules for cable routing assemblies. 820.113 Installation of Coaxial Cables. Installation of coaxial cables shall comply with 820.113(A) through (K). Installation of raceways shall comply with 820.110. (C) Other Spaces Used For Environmental Air (Plenums). The following cables shall be permitted in other Change Description: This change establishes listing requirements for community antenna television and radio distribution system cables installed in other spaces used for environmental air (plenums). Impact(s) : No negative impact. 2 Impact(s) : No negative impact. Page 197 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table spaces used for environmental air as described in 300.22(C): (6) Types CATVP, CATVR, CATV, and CATVX cables installed in plenum communications raceways, riser communications raceways, or general-purpose communications raceways supported by solid bottom metal cable trays with solid metal covers in other spaces used for environmental air (plenums) as described in 300.22(C) 820.180 Grounding Devices. Where bonding or grounding is required, devices used to connect a shield, a sheath, or non–current-carrying metallic members of a cable to a bonding conductor, or grounding electrode conductor, shall be listed or be part of listed equipment. Impact(s) : No negative impact. Change Description: New section added to address requirements for community antenna television and radio distribution system equipment grounding devices to be listed or part of listed equipment. 2 Impact(s) : No negative impact. ARTICLE 830 Network-Powered Broadband Communications Systems 830.3 Other Articles. Circuits and equipment shall comChange Description: ply with 830.3(A) through (F).(G). Added references to Section 300.22 for network-powered B) Wiring in Ducts for Dust, Loose Stock, or Vapor broadband communication wiring systems installed in ducts for Removal. The requirements of 300.22(A) shall apply. dust, loose stock, or vapor removal. Impact(s) : No negative impact. 830.24 Mechanical Execution of Work. NetworkChange Description: powered broadband communications circuits and equipRevised to correlate with requirements in NFPA 90A, providing ment shall be installed in a neat and workmanlike manner. criteria for cable ties and accessories installed in plenums. Cables installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be secured by hardware including straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also conform to 300.4(D) and 300.11. Nonmetallic cable ties and other nonmetallic cable acces- Impact(s) : No negative impact. Page 198 of 203 2 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table sories used to secure and support cables in other spaces used for environmental air (plenums) shall be listed as having low smoke and heat release properties. 830.49 Metallic Entrance Conduit Grounding. Rigid metal conduit (RMC) or intermediate metal conduit (IMC) containing network-powered broadband communications entrance cable shall be connected by a bonding conductor or grounding electrode conductor to a grounding electrode in accordance with 830.100(B). Change Description: Moved the definition containing a requirement to a new section to comply with NEC Style Manual. 830.110 Raceways for Low- and Medium-Powerand Cable Routing Assemblies for Network-Powered Broadband Communications Cables. (A) Types of Raceways. Low-power network-powered broadband communications cables shall be permitted to be installed in any raceway that complies with either 830.110(A)(1) or (A)(2) and in cable routing assemblies installed in compliance with 830.110(C). Medium-power network-powered broadband communications cables shall be permitted to be installed in any raceway that complies with 830.110(A)(1). Change Description: The change corrects an oversight in the 2011 NEC. Table 830.154(a) and 830.113 permit low-power networkpowered communications cables to be installed in communications raceways, but communications raceways were omitted from this section. 1 Impact(s) : No negative impact. 1 Impact(s) : No negative impact. (2) Communications Raceways. Low-power networkpowered broadband communications cables shall be permitted to be installed in listed plenum communications raceways, listed riser communications raceways, and listed general-purpose communications raceways, selected in accordance with the provisions of 800.113 and 830.113 and installed in accordance with 362.24 through 362.56, where the requirements applicable to electrical nonmetallic tubing apply. 830.110 Raceways for Low- and Medium-Powerand Cable Routing Assemblies for Network-Powered Broadband Communications Cables. (C) Cable Routing Assemblies. Network-powered broad- Change Description: This added subsection provides installation rules for cable routing assemblies. Page 199 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table band communications cables shall be permitted to be installed in plenum cable routing assemblies, riser cable routing assemblies, and general-purpose cable routing assemblies selected in accordance with the provisions of 800.113 and installed in accordance with 830.110(C)(1) and (2). (1) Horizontal Support. Cable routing assemblies shall be supported where run horizontally at intervals not to exceed 900 mm (3 ft), and at each end or joint, unless listed for other support intervals. In no case shall the distance between supports exceed 3 m (10 ft). (2) Vertical Support. Vertical runs of cable routing assemblies shall be supported at intervals not exceeding 1.2 m (4 ft), unless listed for other support intervals, and shall not have more than one joint between supports. Impact(s) : No negative impact. 830.113 Installation of Network-Powered Broadband Communications Cables. Installation of network-powered broadband communications cables shall comply with 830.113(A) through (H). (C) Other Spaces Used For Environmental Air (Plenums). The following cables shall be permitted in other spaces used for environmental air as described in 300.22(C): (6) Types BLP, BMR, BLR, BM, BL, and BLX cables installed in plenum communications raceways, riser communications raceways, or general-purpose communications raceways supported by solid bottom metal cable trays with solid metal covers in other spaces used for environmental air (plenums) as described in 300.22(C) Change Description: This change establishes listing requirements for network-powered broadband communication cables installed in other spaces used for environmental air (plenums). 830.180 Grounding Devices. Where bonding or grounding is required, devices used to connect a shield, a sheath, or non–current-carrying metallic members of a cable to a bonding conductor, or grounding electrode conductor, shall be listed or be part of listed equipment. Change Description: New section added to address requirements for network-powered broadband communication cables grounding devices to be listed or part of listed equipment. 2 Impact(s) : No negative impact. Impact(s) : Page 200 of 203 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table No negative impact. ARTICLE 840 Premises-Powered Broadband Communications Systems 840.3 Other Articles. Change Description: (B) Cables in Ducts for Dust, Loose Stock, or Vapor Added new subsection to provide requirements for optical fiber Removal. The requirements of 300.22(A) for wiring syscables, similar to Section 800.3. tems shall apply to conductive optical fiber cables. (D) Installation and Use. The requirements of 110.3(B) shall apply. 840.49 Metallic Entrance Conduit Grounding. The requirements of 770.49 shall apply. 2 Impact(s) : No negative impact. Change Description: Added reference to Section 770.49 for metallic entrance conduit grounding. 2 Impact(s) : No negative impact. 840.93 Grounding or Interruption. Non–current-carrying metallic members of optical fiber cables, communications cables, or coaxial cables entering buildings or attaching to buildings shall comply with 840.93(A), (B), or (C), respectively. Change Description: Editorial change, consistent with NEC Style Manual. 840.103 Equipment Grounding. The grounding of the ONT shall be as required by the equipment listing. Change Description: Deleted redundant section – grounding requirements are covered 840.101(C). Impact(s) : No negative impact. Change Description: New section added to address requirements for premisespowered broadband communication cables grounding devices to be listed or part of listed equipment. 840.180 Grounding Devices. Where bonding or grounding is required, devices used to connect a shield, a sheath, or non–current-carrying metallic members of a cable to a bonding conductor, or grounding electrode conductor, shall be listed or be part of listed equipment. 1 Impact(s) : No negative impact. Page 201 of 203 1 2 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table Impact(s) : No negative impact. Table 1 Percent of Cross Section of Conduit and Tubing for Conductors and Cables Notes to Tables (6) For combinations of conductors of different sizes, use actual dimensions or Table 5 and Table 5A for dimensions of conductors and Table 4 for the applicable conduit or tubing dimensions. Table 1 Percent of Cross Section of Conduit and Tubing for Conductors and Cables Notes to Tables (7) When calculating the maximum number of conductors or cables permitted in a conduit or tubing, all of the same size (total cross-sectional area including insulation), the next higher whole number shall be used to determine the maximum number of conductors permitted when the calculation results in a decimal of 0.8 or larger.greater than or equal to 0.8. When calculating the size for conduit or tubing permitted for a single conductor, one conductor shall be permitted when the calculation results in a decimal greater than or equal to 0.8. Table 1 Percent of Cross Section of Conduit and Tubing for Conductors and Cables Notes to Tables (10) The values for approximate conductor diameter and area shown in Table 5 are based on worst-case scenario and indicate round concentric-lay-stranded conductors. Solid and round concentric-lay-stranded conductor values are grouped together for the purpose of Table 5. Round compact-stranded conductor values are shown in Table 5A. If the actual values of the conductor diameter and CHAPTER 9 Tables Change Description: Since not all conductor sizes are covered in the referenced tables, the code was changed to allow use of actual dimensions of the conductors in calculating conduit and tubing fill. 2 Impact(s) : No negative impact. Change Description: Editorial change. 1 Impact(s) : No negative impact. Change Description: Added a new note clarifying the data provided in Tables 5 and 5A. Impact(s) : No negative impact. Page 202 of 203 1 Technical Evaluation of the Changes in NFPA 70 between 2011 and 2014 Editions Attachment #4 - Comparison Table area are known, they shall be permitted to be used. Page 203 of 203