COSUMNES FIRE DEPARTMENT 10573 E Stockton Blvd. Elk Grove, CA 95624 (916) 405-7100 Fax (916) 685-6622 www.yourcsd.com COSUMNES FIRE DEPARTMENT FIRE CONTROL ROOM DESIGN STANDARD A fire control room shall be provided for all commercial buildings and apartment buildings. The exterior access door shall be full size and clearly marked “Fire Control Room” with a minimum of 3” letters contrasting in color to their background. Rooms shall be provided with permanent and emergency lighting. Two keys of each of the following shall be located in an approved Knox box mounted directly adjacent to each fire control room: fire control room, manual pull stations, fire alarm control panel, breakaway lock for PIV and building entrance keys. Knox Box applications can be obtained at the Cosumnes Fire Department. All dimensions are minimum sizes unless otherwise approved. Rooms may be enlarged to share with other equipment such as electrical or mechanical. However rooms may not be used as storage areas and a minimum of three feet of clearance shall be maintained around all fire protection equipment. Fire control rooms housing fire pumps shall be a dedicated room which is large enough to house the fire pump, fire pump equipment, fire risers, fire alarm control panel, etc. and be provided with enough room to conduct maintenance and testing operations. Doors to fire control rooms shall be labeled “Fire Control Room” and “Fire Pump.” Fire pump rooms shall be equipped with a test header. Commercial Building and Apartment Clubhouse Fire Control Room 7 feet DACP Provide contact information for the responsible party and for the Fire Alarm Company FACP Riser 12” SPARE HEADS ALARM PLANS AND FLOOR PLAN ZONE MAP 5 feet Keypad required in this room 12” Bell Knox Box 6 feet high Full size man door open to the exterior. Label “Fire Control Room” Minimum 3” letters contrasting in color to the background POST “NO-STORAGE” SIGNS IN EACH FIRE CONTROL ROOM. STORAGE IS NOT ALLOWED IN FIRE CONTROL ROOMS OR RISER CLOSETS. COSUMNES FIRE DEPARTMENT FIRE CONTROL ROOM STANDARD CONTINUED Townhome, Condominium, and Apartment Building Riser Closet 4 feet 12” 3 feet Riser 12” Valve Bell Full size man door open to the exterior. Label “Fire Control Room” Minimum 4” letters contrasting in color to the background Revised 10.4.13 aa