ATTENTION February, 2012 MARK YOUR CALENDAR TO ATTEND OUR NEXT CODE SEMINAR ON MAY 26, TO UPDATE YOU ON THE MANY, MANY CHANGES TO THE 2012 ELECTRICAL CODE Inside in this Issue EIA Code Article by Ted Simmons 1 Christmas thank you list 6 Installation of Fire Pumps , a bit new information by Ark Tsisserev 8 BCEA Outstanding Individual Award 13 Membership Form & Meeting Information 14 EIA NEW Code Article by Ted Simmons . I n the November newsletter we reviewed the Code requirements for Commercial garages and Residential storage garages. In this article we will review the requirements pertaining to fin- Electrical Inspectors Association of British Columbia Suite 201, 3989 Henning Drive Burnaby, B.C., V5C 6N5 Phone: 604-294-4123 Fax: 604-294-4120 E-mail: info@eiabc.org ishing processes and will complete our review of Section 20. Rule 20-400 indicates that Rules 20-402 to 20-414 cover finishing processes such as regular or frequent application of paints, lacquers, or other flammable finishes by spraying, dipping, brushing or by other means. It also pertains to areas where volatile flammable solvents or thinners are used or where readily ignitable deposits or (Continued on page 2) INSPECTOR NEWSLETTER— February and Diagram 5 indicate that the entire space within 6m horizontally, in any direcresidues from such paints, lacquers, or fin- tion to a height of 1m above the goods to be ishes may occur. painted, shall be considered a Class I, Zone 1 location. Rule 20-402 – Hazardous locations In addition, Rule 20-402(4) indicates that When spray painting operations are perthe remaining space within the room that is formed within a ventilated spray booth the beyond the limits of the Class I, Zone 1 interior of the spray booth and associated area previously noted, shall be considered exhaust ducts will contain ignitable conto be a class I, Zone 2 location. The followcentrations of vapours, and as noted in ing illustration identifies the extent of the Rule 20-402(1), shall be considered Class hazardous locations for spraying operations I, Zone 1 locations. not performed in spray booths. For operations where paint spraying is not performed in a spray booth, Rule 20-402 (1)(b) (Continued from page 1) (Continued on page 3) 2 In Rule 20-402(7)(b) and as noted in Diagram 6, the extent of the Class I, Zone 2 It should be noted that Rule 20-402(7) re- classification is also reduced from the prelaxes the requirements of Rule 20-402(1) vious requirement to encompass the entire (b) for installations where adequate ventila- area within the room beyond the limits for tion with effective interlocks is provided at the Class I, Zone 1 areas, to include only floor level. the space between a 1m and 1.5m distance above the goods to be painted and all space For example, Rule 20-402(7)(a) reduces within 6m horizontally in any direction bethe extent of the Class I, Zone 1 classificayond the limits for the Class I, Zone 1 location from the previous 6m horizontal distion. The following illustration identifies tance in any direction from the goods to be the extent of the hazardous location for painted to a distance of 1m provided there spraying operations that are not performed is adequate ventilation with effective interin a spray booth and adequate ventilation locks. with effective interlocks is provided at floor level. (Continued from page 2) (Continued on page 4) 3 INSPECTOR NEWSLETTER— February baffle of sheet metal of not less than No.18 MSG is installed vertically above the front face In situations where paint spraying operations of an open-face spray booth to a height of 1m, are performed within an open faced spray or to ceiling, whichever is less, and extending booth; it is possible that the flammable vapours back on the side edges for a distance of 1.5m, will migrate outside of the spray booth, conse- the space behind the baffle shall be classified quently, Rule 20-402(2) indicates the Class I, as non-hazardous. Zone 2 location shall extend not less than 1.5m Rule 20-404 - Ventilation and spraying horizontally from the open face of the spray equipment interlock booth and will extend from floor level to 1m above the booth. Diagram 4 should be conThis rule requires the spraying equipment for a sulted for further information pertaining to the spray booth to be interlocked with the spray extent of the hazardous location. booth ventilation system so that the spraying (Continued from page 3) equipment is made inoperable when the ventilation system is not in operation. In other words, the spraying equipment cannot be operated unless the ventilation system is functioning properly and the operation of the spray equipment is automatically stopped if the ventilation system fails. Where spraying operations are confined within a closed spray booth and for other areas where hazardous concentrations of flammable vapours are likely to be present, such as paint mixing rooms, there is the possibility that flammable vapours may be present in the vicinity of the openings to these areas. In order to address this problem Rule 20-402(3) indicates Rule 20-406 - Wiring and equipment in hazardous locations With innovative planning and careful layout, it is generally possible to locate most of the wiring and equipment associated with finishing processes outside of hazardous locations. However, where this is not possible, Rule 20-406(1) requires all electrical wiring and equipment installed within the hazardous areas as defined in Rule 20-402 to be installed in accordance with the requirements of Section 18. the space within 1m in all directions from any openings in the booth or room shall be considered a Class I, Zone 2 location. The extent of the Class I, Zone 2 location is shown in Diagram 10. In areas or rooms containing drip tanks or drain boards, or in areas where open spraying is conducted, it is possible that from time to time the flammable vapours may travel beyond the limits for the Class I, Zone 1 areas noted in Subrule (1) and as a result, Rule 20-402(4) requires the remainder of the room to be classified as a Class I, Zone 2 location. In addition to satisfying the requirements for Class I, Zone 1 and Zone 2 hazardous locations, Rule 20-406(2) requires equipment that is installed or used where it may be subject to a hazardous accumulation of readily ignitable In order to limit the extent of the hazardous lo- deposits or residue to be specifically approved cation surrounding the openings on open and for the gas group and have a maximum exterclosed spray booths, Subrules 20-402 (8) & (9) nal temperature that is less than the ignition permit the use of sheet metal baffles to prevent (Continued on page 5) the migration of the flammable vapour. For example, as noted in Rule 20-402(8) where a 4 other hot particles do not fall into the hazardous area and create a possible ignition source, Rule 20-412(2) requires equipment such as lamps, cutouts, switches, etc. installed above a hazardous area or above an area where freshly finished goods are handled to be of the totally enclosed type or constructed to prevent the escape of sparks or hot metal particles. (Continued from page 4) temperature of the vapours or deposits encountered in that area. As noted, it is generally advisable to locate equipment outside of hazardous locations. As a result, it is not uncommon for the lighting fixtures for spray booths and similar areas to be located outside of the booth with illumination of the area within the booth provided through panels of glass or other transparent or translucent material. This type of installation is permitted provided the requirements outlined in Rule 20-406(3) are satisfied. Rule 20-414 – Bonding In order to eliminate shock hazards and possible sparking which could create a source of ignition, this rule requires that all metal raceways and all non-current carrying metal portions of fixed or portable equipment, regardless of the voltage, be bonded to ground. It should be noted that Rule 20-406(5)(a) permits totally enclosed and gasketted lighting to be used on the ceiling of a spray booth where adequate ventilation is provided. More on Section 20 in future articles. Rule 20-406(5)(b) also permits infrared drying units to be used in a spray room if the controls are interlocked with those of the spraying equipment to ensure that both operations cannot be performed simultaneously. Ted Simmons, is Chief Instructor, Electrical Apprenticeship Program at the British Columbia Institute of Technology, Ted can he reached by e-mail at Ted_Simmons@bcit.ca. With regards to portable lamps, Rule 20406(4)(a) does not permit their use within a hazardous area during operation of the finishing process. Rule 20-406(4)(b) does however, permit the use of portable electric lamps for cleaning and repairing operations provided they are of a type specifically approved for use in Class I locations. Fixed electrostatic equipment and electrostatic hand spraying equipment shall be installed in accordance with the requirements of Rules 20-408 and 20-410. What’s New Do you have any technical information or letters to the editor, please mail or email : info@eiabc.org Rule 20-412 – Wiring and equipment above hazardous areas This rule indicates the fixed wiring installed above hazardous areas shall conform to Section 12. However, to ensure that sparks or 5 INSPECTOR NEWSLETTER— February The Merry Membership For the nineteenth year the Electrical Inspector’s Association once again had a great Christmas dinner meeting, and gave away lots of door prizes. Ninety three people attended the dinner. The prizes were donated by many contractors, businesses and individual members. This article has been written to show the Electrical Inspector’s Associations appreciation to the following people and organizations for their generous support making the meeting another grand success. City of Vancouver Electrical Inspectors, Keiller Gowans, Dwayne Askins, Moerman Electric, Berts Electric, The Safety Authority, An anonymous donor, Paul Kelly, Lab Test Services, Warren Hancock, Indy Electric, Elworthy Electric, Alf Lam, Elec Tech, John Evans, Nightingale Electric, Joe Fata Electric, CM and sons Electric, Jack Ball, Dave Harper, David Wrisht of BOA Constuction, Mike Cupit, Cypress Mountain, T&B Geor GE Foreman, Jim Cupit, Efficient Electric, International Cellars, Lions Electric, Norgate Electric, Rimrow Developements, Mike McAndrew, Trolls Restaurant, The West Van. Care Center, 6 Metro Electric, Cam Duncan, WBI Home Warranty Service, Abharham, The Mystery Santa, The City of Surrey Inspectors, Dave Broadbent of Gescan, Bill Strain of Villa Electric, Rick Porcina, Sabb Electric, GPR Electric, Ted Simmons, United Power, Onkar Singh Hundal of Ojay Electric, Betty-Lou Pacey of the BCEA, Dave Thorne of CSA, Ark Tsisserev, Gurmit Rooprai of Roop Electric, Len Rhodes, The Park Royal White Spot, Ed Ballard, Mike Wpit, Calvins Cafe, Kim Davies of Ready Lite, Deltec Electric, Genuine Electric, Kuban Electric, Andy Moerman, John and Daniel Morse, Wespac Electric, Westburne Electric, Gescan N. Van., Andrew and Vicky Collins, (Continued from page 6) Armeh Construction, Siba Homes, Chris Simpkins of CSC Construction, Quality Electric, Derek Page, Westrade Electric, Les Shaw, Bellex Construction, Park Royal Shopping Center, Home Line Projects, Mitre Electric, Ron Osterman, Zpiegniew of Zolt Electric, Lorne Benson, Barry Hill of Sylvania. G&M Electronics, Bruce Moss, Go-on Construction, FX 40 Design, Duncan McFarlane, Jennine Waldern of Intertek, White Croze Electric, Nu-way Electric, Paul Sampson, Rick Alexander, Ron Cemett, Jason Maros, Eccol Electric, Eric Voitech, The generosity of the group came to light when the money for the 50/50 draw for the Canuck Place Children’s hospice fund raising was counted. $300.00 dollars was raised through the sale of 50/50 tickets. One of the most generous people at the meeting was Gurmit Rooprai of Roop Electric. He won the 50 draw and said he was going to donate his winnings to the Childrens Hospital. What a great guy! In closing the executive would like to say a especial thanks to Santa Len for obtaining many of the door prizes himself and organizing them all to be given away. We would also like to thank all those who attended the meeting and those who could not, but made a donation never the less. Ho, ho, ho! President Jack Ball Renewal Time Application Form and Renewal Form on the last Page of this News Letter 7 INSPECTOR NEWSLETTER— February Installation of fire pumps - a bit of new information. by Ark Tsisserev P.Eng. This subject is not new. There have been numerous articles written about the CE Code requirements for fire pump installations and about the selection of the conductors and overcurrent protection for fire pump feeders. instantaneous/magnetic trip setting of the circuit breaker in a fire pump controller at not more than 20 times of the full load current of the fire pump and a thermal trip setting of the value that will allow a fire pump controller to carry locked rotor current for a period between 8 and 20 So, what's the reason to revisit this issue? sec. NFPA 20 also specifies that locked roThe answer is: changes to the NFPA 20. tor overcurrent protection in the fire pump controller must be “calibrated and set at Let's elaborate. This article is intended to a minimum of 300 percent of motor fullclarify the requirements of Rule 32-206 of load current”. Rule 32-206(4) requires the Canadian Electrical Code, Part I – that if a circuit breaker is installed in an 2009 and to correlate these requirements emergency power supply circuit, upstream with the NFPA 20-2010 (the latest pubof the fire pump transfer switch, then the lished edition of the standard). rating or setting of this circuit breaker Background: must comply with Rule 28-200 (i.e. it must be selected in accordance with Table D16 of 1. Rule 32-206(5) of the CE Code requires the CE Code). This requirement is based on that the rating or setting of a circuit the exception provided in previous editions breaker installed in a normal power supply of NFPA 20 – which was allowing to bypass circuit, upstream of the fire pump controlovercurrent protection within the fire pump ler shall be not less than that the overcurcontroller when the power is derived from rent protection that is provided integral an emergency generator. This CE Code rewith the fire pump controller. Appendix B quirement reflects the fact that a coordinaNote on this Rule clarifies the Code requiretion of the O/C protection settings at the ment by stating that this circuit breaker circuit breaker installed in the emergency should have setting of its overcurrent depower supply circuit with the O/C settings vices coordinated with the setting of the at the fire pump controller circuit breaker overcurrent devices of the circuit breaker is no longer necessary, as the fire pump that is provided integrally with the fire controller circuit breaker is bypassed when pump controller, and this coordination the power is derived from an emergency should be established “in such a manner generator (see Diagram 1). that the upstream overcurrent device does not disconnect the circuit prior to 2. Rule 32-200 of the CE Code mandates the operation of the fire pump controlthat conductors from an emergency power ler overcurrent protection” Additional supply to the fire pump must have an amNote in Appendix B on this Rule advises (Continued on page 11) the Code users that NFPA 20 mandates an 8 9 INSPECTOR NEWSLETTER— February 10 NFPA 20. Clause 10.8.2.1.3. of NFPA 20 (that covers requirements for a transfer switch) states the following: “10.8.2.1.3 Circuit Breaker. The transfer switch emergency side shall be provided with a circuit breaker complying with 10.4.3 and 10.4.4”. This means that a fire pump transfer (Continued from page 8) pacity not less than 125% of the full load current rating of the fire pump motor. It should be noted that this Code requirement is no different than the provisions of Rule 28-106 for branch circuit conductors supplying all other types of individual motors. As this Rule does not specify require2. switch arranged in a “listed combinaments for selection of the ampacity of fire tion Fire Pump Controller and Power pump conductors from a normal power Transfer Switch” as described in supply circuit, the ampacity of these conClause 10.8.2.1 of NFPA 20 must now ductors would have to be selected based on be provided with a circuit breaker identhe requirements of Rule 28-106. (i.e. they tical to the circuit breaker in the fire would have to be also not less than 125% pump controller. This also means that of the full load current rating of the fire the electrical characteristics of the cirpump motor) cuit breaker selected by the electrical It looks like issues addressed by items 1 designers upstream of: and 2 above might be intertwined by the (a) the fire pump controller – in the normal rules of the current edition of the CE power supply circuit, and (b) the fire pump Code. transfer switch – in the emergency power Let's discuss these issues. supply circuit Discussion: must be also identical. This means that the setting requirements described in Rule 321. Clauses 10.4.3.3. and 10.4.4 of the cur- 206(5) of the CEC for the circuit breaker in rent (2010) edition of NFPA 20 provide the normal power supply circuit and coorsimilar requirements for the circuit dination of these settings with the circuit breaker in a fire pump transfer switch breaker of the fire pump controller must be as the requirements that are currently extended to the circuit breaker installed in referenced in Appendix B Note on Rule an emergency power supply circuit (see 32-206 of the CEC (i.e. instantaneous/ Diagram 2). magnetic trip setting of the circuit breaker in a fire pump controller at 2. Rule 32-200 of the CE Code requires not more than 20 times of the full load that conductors from an emergency power current of the fire pump and a thermal supply to the fire pump must have an amtrip setting/locked rotor overcurrent pacity not less than 125% of the full load protection setting at a minimum of 300 current rating of the fire pump motor. It percent of motor full-load current - to should be noted that this Code requirement allow a fire pump controller to carry is no different than the provisions of Rule locked rotor current for a pe28-106 for branch circuit conductors supriod between 8 and 20 sec). However, plying all other types of individual motors. the exception that was permitted in Rule 32-200 appears to be conspicuously 1999 edition of NFPA 20 (in the edition silent on selection of the ampacity of conthat is referenced in Appendix B Note on ductors that connect a fire pump to a norRule 32-206 of the CEC) has been re(Continued on page 12) moved from the current edition of the 11 INSPECTOR NEWSLETTER— February the motor full-load current. (Continued from page 11) mal power supply circuit. Perhaps, this Rule reflects the fact that in the emergency power supply circuit, the O/C protection of the circuit breaker would not have to be coordinated with the circuit breaker in the fire pump controller, as the overcurrent protection in the fire pump controller was allowed to be bypassed in accordance with the 1999 edition of the NFPA (1999 edition of the NFPA 20 is currently referenced in Appendix B Note on Rule 32-206). If this is the case, then 125% of the full load current rating of the fire pump motor supplied from an emergency power source is the logical ampacity . It should be also noted that ampacity of branch circuit conductors based on 125% of the full load current rating of any motor is shown in Table D16 of the CE Code, and such ampacity values are correlated with the O/C devices protecting these conductors - as also prescribed by Table D16. Thus, provision of Rule 32-200 for the conductors of the emergency power supply circuit made perfect sense, since the O/C protection of the controller downstream from the circuit breaker installed in the emergency supply circuit, was permitted to be bypassed. However, in light of the fact that in accordance with NFPA 2010, the trip settings of the circuit breaker in the emergency power supply circuit will have to be coordinated with the settings of the circuit breaker in the transfer switch, the conductor ampacity currently mandated by Rule 32-200 (125% of the full load current) may not be now sufficient - to prevent insulation damage without being subjected to damage , as these conductors would have to carry a fault current in excess of 20 times of the full load current. 2. If a transfer switch “approved for fire pump service” in accordance with Rule 32-208 (1)(c)of the CE Code meets provisions of the current edition of the NFPA 20 (i.e. is provided with an integral circuit breaker), then the circuit breaker designed for installation in the emergency power supply circuit, upstream of the circuit breaker in the transfer switch (see Diagram 2) should also be selected with an instantaneous trip setting at 21 times of the full-load current and with thermal/locked rotor overcurrent protection setting at 350% of the motor full-load current. 3. If a transfer switch “approved for fire pump service” in accordance with Rule 32-208 (1)(c) of the CE Code does not meet provisions of the current edition of the NFPA 20 (i.e. integral overcurrent protection is bypassed in the fire pump controller/fire pump transfer switch arrangements, as shown in Diagram 1), then current provision of Rule 32-206(4) of the CE Code could be met. Note: Proposal to amend Rule 32-206 has been submitted to the Section 32 S/C of the CE Code – to reflect the conclusion 2 above. 4. Fire pump feeder conductors in both - normal and emergency power supply circuit should have an ampacity not less than 200% of the full load current of the fire pump motor or not less than 200% of the sum of the full load currents of the fire pump, jockey pump and the fire pump auxiliary loads, where two or more motors are provided with the fire pump. Note: Proposal to amend Rule 32-200 has also been submitted to the Section 32 S/C of the CE Code – to reflect this conclusion. 5. Fire pump feeder conductors from both – the normal and the emergency power supply sources to the fire pump should be pro1. A circuit breaker designed for installation in tected against fire exposure to provide contina normal power supply circuit, upstream of ued operation for not less than 1 h in accorthe circuit breaker in a fire pump controller dance with sentence 3.2.7.10.(2) of the (see Diagram 2) should be selected with NBCC 2010. (i.e. conductors shall have circuit an instantaneous trip setting at 21 times of the integrity rating not less than 1 h in accorfull-load current and with thermal/locked rodance with the ULC S139 “Fire Test for tor overcurrent protection setting at 350% of Conclusion: (Continued on page 13) 12 (Continued from page 12) Evaluation of Integrity of Electrical Cables” or be located in a service space that is separated from the remainder of the building by a fire separation that has a fire resistance rating not less than 1 h). However, it should be noted that the above conclusions only represent observations of the author on this subject, and until these conclusions are incorporated into the CE Code as the result of the submitted proposals, compliance with them is not legally required, as these conclusions simply describe a good engineering practice. consulted on this subject during the design and installation of the fire pumps circuits. Ark is a registered professional engineer with a master’s degree in Electrical Engineering. He is currently the Chair of the Technical Committee for the Canadian Electrical Code and is representing the CE Code Committee on the CMP-1 of the National Electrical Code. Ark Tsisserev P.Eng. And as usual, the appropriate AHJ should be Ted Simmons, being recognized for his — Outstanding Individual of the Year Award, Presented by the BCEA. The purpose of this award is to recognize a company or individual who has given back to the community. A person well recognized in our community who is always willing to help the industry grow. He is a respected individual in our industry and was nominated by many individuals. He was also a nominee last year for this same award; Congratulations Ted well done! Photo L—R Ark Tsisserev P.Eng., Barbette Ishii, Ted Simmons (the man himself) , Jack Ball 13 INSPECTOR NEWSLETTER— February EIA Executive President—Jack Ball, jackmball@shaw.ca Vice President— Nick LeForte City of Surrey nleforte@surrey.ca Treasurer—Brian Esau, City of Burnaby Brian.Esau@burnaby.ca Monday, February 27 th , 2012 125—East 2nd Street, North Vancouver, B.C. (just off Lonsdale Avenue) Membership Secretary George Razzo, BC Safety Authority, Chilliwack leachtown@shaw.ca Recording Secretary Ted Simmons, BCIT tsimmons@bcit.ca Social Hour 5:15—6:00 Dinner 6:00—7:00 Meeting 7:00— 9:00 Presention from EATON’s electric vehicle equipment and associated installation requirements. They will have a number of knowledgeable presenters to make it a very interesting update. Followed by the Election of Officers. Directors Kerry Peterson, CSA International kerry.peterson@csa-international.org Paul Stevens, Retired stev0851@telus.net Vince Pietracupa Intertek vince.pietracupa@intertek.com Len Rhodes, District of West Vancouver lrhodes@westvancouver.ca Bill Strain, ECA of B.C. billvilla@telus.net Past President Roger Tuttle, City of Vancouver roger.tuttle@vancouver.ca Editor: Rick Porcina, Email: info@eiabc.org Dinner: $35 Most Important for Reservations: Please Phone Dwayne Askin (778) 396-2050 or Email: Dwayne.Askin@safetyauthority.ca Membership Application & Renewal Form For 1 year (Jan 1, 2012—Dec. 31, 2012) $ 75.00 For 2 years (Jan 1, 2012—Dec. 31, 2013) $ 150.00 For 3 years (Jan 1, 2012—Dec. 31, 2014) $ 225.00 New Membership Name (Please Print) Address Renewal City Postal Code Inspector Company Title Associate Email Mail to: The EIA of BC, Suite 201— 3989 Henning Drive, Burnaby, B.C., V5C 6N5 14