PUMP OPERATOR Note Taking Guide PILOT Spring 2012 Maryland Fire and Rescue Institute University of Maryland Steven T. Edwards, Director The Maryland Fire and Rescue Institute of the University of Maryland is the State’s comprehensive training and education system for all emergency services. The Institute plans, researches, develops, and delivers quality programs to enhance the ability of emergency service providers to protect life, the environment, and property. Lesson 1-2 The Role of the Driver/Operator Student Performance Objective Given information from discussion, handouts, and reading materials, describe the history of the fire service driver/operator. FIRE 113-PPT-1-2-1 Overview The Safe Operation of Fire Apparatus The History and Evolution of Fire Apparatus Safety Considerations and NFPA 1500 Types and Specifications of Modern Fire Apparatus FIRE 113-PPT-1-2-2 The Safe Operation of Fire Apparatus The proper operation of the fire apparatus and equipment is critical Driving to and from the scene can be as dangerous as operating on the fireground itself Failure of equipment on the fireground can be disastrous FIRE 113-PPT-1-2-3 The Safe Operation of Fire Apparatus The driver/operator has a tremendous responsibility for the success and safety of the company Preparing and inspecting fire apparatus and equipment for a safe response Driving the fire apparatus in emergency response mode to a call Placing the fire apparatus at the scene to ensure maximum effectiveness of the equipment FIRE 113-PPT-1-2-4 The Safe Operation of Fire Apparatus The responsibility of the driver/operator (continued) Operating the equipment to support operations on the fireground Securing equipment Returning the fire apparatus and company members to the station FIRE 113-PPT-1-2-5 The History and Evolution of Fire Apparatus The introduction of hand pumps and hose carts Hand pumps were the first equipment to replace the bucket brigade FIRE 113-PPT-1-2-6 The History and Evolution of Fire Apparatus Hand pumps are piston-driven, positive-displacement pumps pushed up and down by firefighters manning poles on either side of the pump FIRE 113-PPT-1-2-7 The History and Evolution of Fire Apparatus The fire apparatus evolution The first mechanized fire pumps The introduction of gasoline-powered fire apparatus The addition of a pump to apparatus FIRE 113-PPT-1-2-8 The History and Evolution of Fire Apparatus The addition of a pump to apparatus Booster pumps were added as trucks became larger and stronger A booster line was attached to the pump FIRE 113-PPT-1-2-9 The History and Evolution of Fire Apparatus The addition of diesel-powered fire apparatus Larger-capacity pumps that required greater horsepower meant larger vehicles The diesel engine started to replace the gasoline engine Diesel engines replaced the gasoline engine as the power system of choice for the fire service FIRE 113-PPT-1-2-10 Safety Considerations and NFPA 1500 NFPA 1500 Emerged from a growing concern for firefighter safety during the movement of fire apparatus FIRE 113-PPT-1-2-11 Safety Considerations and NFPA 1500 NFPA 1500 required that new fire apparatus be designed so that all members riding on the apparatus would have a seating area inside an enclosed cab The adoption of this standard resulted in the near elimination of rear steps on fire apparatus FIRE 113-PPT-1-2-12 Types and Specifications of Modern Fire Apparatus The fire apparatus used by departments today are larger, heavier, and taller with a higher center of gravity, and thus are more difficult to maneuver through traffic Th capacities The iti off fire fi apparatus t continue ti to t increase The water delivery rate of many pumps exceeds 1500 GPM FIRE 113-PPT-1-2-13 Types and Specifications of Modern Fire Apparatus The use of computers on fire apparatus has increased ABS systems prevent the vehicle brakes from locking up Electrical load management systems make sure the electrical load does not exceed the ability of the fire apparatus to produce electricity FIRE 113-PPT-1-2-14 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the history of the fire service driver/operator. FIRE 113-PPT-1-2-15 Review The Safe Operation of Fire Apparatus The History and Evolution of Fire Apparatus Safety Considerations and NFPA 1500 Types and Specifications of Modern Fire Apparatus FIRE 113-PPT-1-2-16 Lesson 1-3 Types of Fire Apparatus Pumps Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of water on the fire apparatus, the elements of a pumper, and the elements of various fire apparatus including initial attack,, mobile water supply, pp y, aerial,, q quint,, special service, and mobile foam. FIRE FIRE113-PPT-2-1-1 113-PPT-1-3-1 Overview Water on the Fire Apparatus Pumpers Mobile Water Supply Apparatus Other Types of Fire Apparatus FIRE FIRE113-PPT-2-1-2 113-PPT-1-3-2 Water on the Fire Apparatus Water is the major component of fire attack Water must be pressurized by a fire pump NFPA 1901 defines a fire pump as a water pump mounted on an apparatus and used for firefighting FIRE FIRE113-PPT-2-1-3 113-PPT-1-3-3 Water on the Fire Apparatus A fire pump of any size must meet certain requirements As a pump's psi rate is increased, the amount of water that can be delivered decreases The size and number of suction lines required vary according to the fire pump size FIRE FIRE113-PPT-2-1-4 113-PPT-1-3-4 Water on the Fire Apparatus All fire pumps are rated from draft so no added water pressure from an external source is used to offset the fire pump capacity The pump certification test is conducted at the manufacturer by a third party FIRE FIRE113-PPT-2-1-5 113-PPT-1-3-5 Water on the Fire Apparatus NFPA 1901 defines the requirements of a fire apparatus equipped with water tanks Depending on the type of fire apparatus, a water tank may hold several hundred or several thousand gallons of water NFPA 1901 covers other aspects of the water tank FIRE FIRE113-PPT-2-1-6 113-PPT-1-3-6 Pumpers The pumper Is the "bread and butter" of the fire service Is the most common type of fire apparatus and is part of almost every department FIRE FIRE113-PPT-2-1-7 113-PPT-1-3-7 Pumpers Per NFPA 1901, the pumper shall be equipped with a permanently mounted pump at a minimum rating of 750 GPM FIRE FIRE113-PPT-2-1-8 113-PPT-1-3-8 Pumpers NFPA 1901 requires the pumper to carry certain fire hoses and nozzles FIRE FIRE113-PPT-2-1-9 113-PPT-1-3-9 Pumpers The pumper must be designed with at least 40 ft3 of enclosed weather-resistant compartments to store equipment FIRE FIRE113-PPT-2-1-10 113-PPT-1-3-10 Mobile Water Supply Apparatus Many rural communities do not have hydrants or readily accessible water Firefighters need fire apparatus with large-capacity water tanks Tenders are mobile water supply fire apparatus that provide water For larger fires needing more water, a water shuttle operation may be used to establish a sustained water supply FIRE FIRE113-PPT-2-1-11 113-PPT-1-3-11 Mobile Water Supply Apparatus FIRE FIRE113-PPT-2-1-12 113-PPT-1-3-12 Mobile Water Supply Apparatus The mobile water supply apparatus May be designed with or without a fire pump Is designed to carry a large capacity of water to the fire scene Is equipped with one or more water tanks that meet requirements of NFPA 1901 and have a minimum certified capacity of 1000 gallons FIRE FIRE113-PPT-2-1-13 113-PPT-1-3-13 Mobile Water Supply Apparatus If the mobile water supply apparatus is equipped with a fire pump, then it must carry at least 15' of soft suction hose or 20' of hard suction hose with a strainer Soft suction hose includes couplings compatible with local hydrants The fire department specifies to the manufacturer whether hard or soft suction hose is needed FIRE FIRE113-PPT-2-1-14 113-PPT-1-3-14 Mobile Water Supply Apparatus Equipment storage is very important At least 20 ft3 of enclosed weather-resistant compartment space must be provided for equipment storage Minor equipment is organized and mounted in brackets or in compartments FIRE FIRE113-PPT-2-1-15 113-PPT-1-3-15 Other Types of Fire Apparatus Aerial Fire Apparatus FIRE FIRE113-PPT-2-1-16 113-PPT-1-3-16 Other Types of Fire Apparatus Quint Fire Apparatus FIRE FIRE113-PPT-2-1-17 113-PPT-1-3-17 Other Types of Fire Apparatus Special Service Fire Apparatus FIRE FIRE113-PPT-2-1-18 113-PPT-1-3-18 Other Types of Fire Apparatus Mobile Foam Fire Apparatus FIRE FIRE113-PPT-2-1-19 113-PPT-1-3-19 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of water on the fire apparatus, the elements of a pumper, and the elements of various fire apparatus including initial attack,, mobile water supply, pp y, aerial,, q quint,, special service, and mobile foam. FIRE FIRE113-PPT-2-1-20 113-PPT-1-3-20 Review Water on the Fire Apparatus Pumpers Mobile Water Supply Apparatus Other Types of Fire Apparatus FIRE FIRE113-PPT-2-1-21 113-PPT-1-3-21 Lesson 2-1 Water Supplies and Pressure Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of water supplies, the chemical properties of water, and characteristics of a municipal and rural water supply. pp y Describe the concepts p of water flow and pressure; the characteristics, operation and location of fire hydrants; and the proper steps for maintenance and testing of fire hydrants. FIRE 113-PPT-2-1-1 Overview The Importance of Water Supply Municipal Water Systems Flow and Pressure Fire Hydrants Inspecting and Maintaining Fire Hydrants Testing Fire Hydrants Rural Water Supplies FIRE 113-PPT-2-1-2 The Importance of Water Supply The hoseline is the primary weapon for fighting fire Fighting fires requires an adequate supply of water to confine, control, and extinguish fire A water supply that is interrupted while crews are working inside a building could cause firefighters to become trapped, injured, or killed FIRE 113-PPT-2-1-3 The Importance of Water Supply Ensuring a dependable water supply is a critical operation to be accomplished as quickly as possible Water is obtained from three sources Static sources (lakes and streams) Pressurized sources Water carried to the fire scene in a tanker FIRE 113-PPT-2-1-4 The Importance of Water Supply Water exists in all three states on earth: liquid, gas, and solid The property states affect the use of water in firefighting operations Water is the primary substance used to extinguish fire because it turns to vapor (steam) when it comes in contact with fire FIRE 113-PPT-2-1-5 Municipal Water Systems Municipal water systems make clean water available to people in populated areas 78 8% 78.8% FIRE 113-PPT-2-1-6 Municipal Water Systems Water sources Municipal water systems can draw water from wells, rivers, streams, lakes, and reservoirs The source depends on p geographic and hydrologic features of the area Many systems draw water from several sources to ensure a sufficient supply Underground pipelines or open canals supply some cities with water from sources that are many miles away FIRE 113-PPT-2-1-7 Municipal Water Systems A water source needs to be large enough to meet the demands of its service area Most systems include large storage facilities to ensure they will be able to meet the community's demands if the primary water source is interrupted The backup supply for some systems can provide water for several months or years FIRE 113-PPT-2-1-8 Municipal Water Systems The water distribution system The distribution system delivers water from the treatment facility to end users and hydrants through water mains The distribution center also includes pumps pumps, storage tanks, reservoirs, and other components to ensure that the required water can be delivered where and when it is needed at the required pressure FIRE 113-PPT-2-1-9 Municipal Water Systems Systems may rely on pumps to provide required pressure directly or indirectly A pure gravity-feed system has the water source treatment plant source, plant, and storage facilities located on high ground while the end users live in lower-lying areas FIRE 113-PPT-2-1-10 Municipal Water Systems Most systems use pumps and gravity to deliver water A combination pump-and-gravity-fed system must maintain enough water in the elevated storage t tanks t k and d reservoirs i to t meett anticipated demands FIRE 113-PPT-2-1-11 Municipal Water Systems The size of the water mains required depends on the water needed for normal consumption and fire protection Water mains in a well well-designed designed system will follow a grid pattern which can: Help ensure an adequate flow of water for firefighting Minimize downtime Divert water flow FIRE 113-PPT-2-1-12 Municipal Water Systems Older distribution systems may have deadend water mains that supply water from only one direction FIRE 113-PPT-2-1-13 Flow and Pressure To understand the procedures for testing hydrants, firefighters must understand the terminology The flow or quantity of water moving through a pipe, hose, or nozzle is measured by the volume Static pressure is the pressure in a system when the water is not moving FIRE 113-PPT-2-1-14 Flow and Pressure Normal operating pressure is the amount of pressure in a system during a period of normal consumption Residual pressure is the amount of pressure in a system when water is flowing Knowing static pressure, flow in gallons per minute, and residual pressure enables a firefighter to calculate the water that can be obtained from a hydrant or group of hydrants on the same water main FIRE 113-PPT-2-1-15 Flow and Pressure Gravity continues to exert its effects on flowing water based on the stream's elevation and altitude Water hammer is a pressure surge or wave caused by kinetic energy of fluid in motion when it is forced to stop or change direction suddenly FIRE 113-PPT-2-1-16 Fire Hydrants Hydrants are equipped with one or more valves to control water flow through the hydrant One or more outlets are provided to connect fire department hoses to the hydrant FIRE 113-PPT-2-1-17 Fire Hydrants Dry-barrel hydrants are used where temperatures can fall below freezing A partially opened valve means the drain is also p partially y open p and pressurized p water can flow out FIRE 113-PPT-2-1-18 Inspecting and Maintaining Fire Hydrants Understand how to inspect and maintain hydrants Check for visibility and accessibility ibilit Check the hydrant exterior for damage Ensure that the hydrant is working properly FIRE 113-PPT-2-1-19 Testing Fire Hydrants The amount of water available to fight fire at its location is crucial in planning an attack Fire companies often are assigned to test hydrant flow to better plan water supply for future incidents FIRE 113-PPT-2-1-20 Testing Fire Hydrants FIRE 113-PPT-2-1-21 Testing Fire Hydrants FIRE 113-PPT-2-1-22 Rural Water Supplies Protecting areas that are not serviced by municipal water systems Residents depend on individual wells or cisterns to supply their water There are no hydrants so firefighters must depend on water from other sources FIRE 113-PPT-2-1-23 Rural Water Supplies Static sources of water Several potential static water sources can be used for fighting fires in rural areas Water from a static source can be used to fight fire directly if it is close enough to the fire scene Static water sources must be accessible to a fire engine or portable pump FIRE 113-PPT-2-1-24 Rural Water Supplies Dry hydrants provide quick, reliable access to static water sources A dry hydrant is a pipe with a strainer on one end and a connection for a hard suction hose on the other end D h Dry hydrants d t often ft are iinstalled t ll d iin llakes, k rivers, i and close to clusters of buildings where there is a recognized need for fire protection The portable pump is an alternative means of obtaining water in areas that are inaccessible to fire apparatus FIRE 113-PPT-2-1-25 Rural Water Supplies Dry Hydrant FIRE 113-PPT-2-1-26 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of water supplies, the chemical properties of water, and characteristics of a municipal and rural water supply. pp y Describe the concepts p of water flow and pressure; the characteristics, operation and location of fire hydrants; and the proper steps for maintenance and testing of fire hydrants. FIRE 113-PPT-2-1-27 Review The Importance of Water Supply Municipal Water Systems Flow and Pressure Fire Hydrants Inspecting and Maintaining Fire Hydrants Testing Fire Hydrants Rural Water Supplies FIRE 113-PPT-2-1-28 Lesson 2-2 Hydraulic Calculations I Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations; pump discharge pressure; friction loss; calculating friction loss; and the different types yp of connections. FIRE 113-PPT-2-2-1 Overview The Importance of Hydraulic Calculations Pump Discharge Pressure Friction Loss Calculating Friction Loss Using the Coefficient Method Estimating Friction Loss by Hose Size Examples FIRE 113-PPT-2-2-2 The Importance of Hydraulic Calculations Fire service hydraulic calculations are used to determine the required pump discharge pressure (PDP) for fireground operations Fire service hydraulics is the study of the characteristics and movement of water pertaining to calculations for fire streams and fireground operations FIRE 113-PPT-2-2-3 The Importance of Hydraulic Calculations Theoretical hydraulics is the scientific or more exact calculation Fireground hydraulics is a less exact but more user-friendly calculation method used on the fireground FIRE 113-PPT-2-2-4 The Importance of Hydraulic Calculations Calculations will be affected by nozzles, appliances, and hoses Use the manufacturer's recommended nozzle pressure specific to an actual nozzle on a hose or appliance with the apparatus, under the guidelines of a specific fire department Use flow tests with department equipment to confirm the pressures to use on the fireground FIRE 113-PPT-2-2-5 Pump Discharge Pressure Fighting fire with water: determining the water flow (GPM) versus heat generation (BTU) FIRE 113-PPT-2-2-6 Pump Discharge Pressure The critical rate of flow is the flow required to overcome the heat generated by the fire The proper selection of hose and nozzle is one of the most important attack decisions after securing the water supply to produce an adequate flow to extinguish the fire Strategically placed hoseline or lines using correct tactics protect lives and confine and extinguish the fire FIRE 113-PPT-2-2-7 Pump Discharge Pressure FIRE 113-PPT-2-2-8 Pump Discharge Pressure Supplying hoselines with optimal PDP If the pressure is too great, it will cause the stream to break up, lessening its effectiveness Inadequate q p pressure will p produce insufficient flow to overcome the fire, possibly endangering the safety of the attack team FIRE 113-PPT-2-2-9 Pump Discharge Pressure PDP: the total pressure needed to overcome all friction, appliance, and elevation loss while maintaining an adequate nozzle pressure to deliver effective fire streams FIRE 113-PPT-2-2-10 Pump Discharge Pressure PDP FORMULA PDP = NP + FL + AL ± EP NP = Nozzle Pressure FL = Friction Loss AL = Appliance loss EP = Elevation Pressure FIRE 113-PPT-2-2-11 Pump Discharge Pressure Nozzle Pressures Nozzle pressure is the pressure required at the nozzle to deliver the fire stream and flow rate for that nozzle's design The manufacturer's specifications for maximum water flow from an aerial device are listed with the nozzle specifications Broken-stream nozzles are available in fog and smooth-bore varieties FIRE 113-PPT-2-2-12 Pump Discharge Pressure There are three standard nozzle pressures (SNPs) for sufficient fireground operations 100 psi NP for all fog nozzles 50 psi NP for smooth-bore handline nozzles 80 p psi NP for smooth-bore master stream nozzles FIRE 113-PPT-2-2-13 Pump Discharge Pressure FIRE 113-PPT-2-2-14 Pump Discharge Pressure Determining Nozzle Flow Flow rate is the volume of water moving through a nozzle and measured in GPM Flow and p pressure differ by y the design g and the purchaser's options Fog nozzles are designed with pre-determined flow rates based on a set NP Smoothbore nozzles commonly are rated at 50 psi Nozzle flow from an orifice is 29.7 x d² × √NP FIRE 113-PPT-2-2-15 Examples Calculate the flow rate for a 1¼” smooth bore tip used on a 2½” handline GPM = 29.7 × d² × √NP GPM = 29.7 29 7 × (1¼ )² ) × √50 GPM = 29.7 × (1.25)² × √50 GPM = 29.7 × 1.56 × 7.07 GPM = 327.567 GPM (Round to 300 GPM) FIRE 113-PPT-2-2-16 Examples Calculate the flow rate for a 1½” smooth bore master stream nozzle GPM = 29.7 × d² × √NP GPM = 29.7 29 7 × (1.5) (1 5)² × √80 GPM = 29.7 × 2.25 × 8.94 GPM = 597.415 GPM (Round to 600 GPM) FIRE 113-PPT-2-2-17 Friction Loss Friction loss is the pressure lost from turbulence as water passes through pipes, hoses, fittings, adapters, and appliances Friction loss must be determined after determining the NP Exceeding 50 psi of FL per 100' of hose may decrease the flow because of increased turbulence in the hose FIRE 113-PPT-2-2-18 Calculating Friction Loss Using the Coefficient Method The friction loss equation: FL = C × Q2 × L FL = friction loss C = th the coefficient, ffi i t a numerical i l measure constant for each specific hose diameter Q = the quantity of water flowing (GPM ) divided by 100 L = the length of hose in feet, divided by 100 FIRE 113-PPT-2-2-19 Estimating Friction Loss By Hose Size This method estimates friction loss per 100 ft of hose as follows 30 psi × 100 ft of 1¾” 60 psi × 100 ft of 1½” 1½ 15 psi × 100 ft of 2½” FIRE 113-PPT-2-2-20 Examples What is the PDP for 300’ of 2½” hose with a 11/8” smooth bore nozzle? Smooth bore nozzle on a handline has a NP of 50 psi PDP = NP + FL + AL ± EP PDP = 50 + FL + AL ± EP FIRE 113-PPT-2-2-21 Examples Now we need to calculate FL: For a 2½” hose the coefficient is 2 (C=2) The nozzle has a 11/8” tip, which we know flows 250 GPM ((rounded)) We know the nozzle flow from table 4-1 or by the formula GPM = 29.7 × d² × √NP The flow is 250 GPM so 250/100 = 2.5 so Q = 2.5 FIRE 113-PPT-2-2-22 Examples Now we insert the values into the formulas: FL = C × Q2 × L FL = 2 × (2.5)² × 300/100 FL = 2 × 6.25 6 25 × 3 FL = 37.5 psi FIRE 113-PPT-2-2-23 Examples Now we return to the PDP formula and insert FL PDP = NP + FL + AL ± EP PDP = 50 +37.5 +37 5 + AL ± EP PDP = 87.5 psi FIRE 113-PPT-2-2-24 Examples Calculate the FL in 200’ of 1¾” hose with a 7/ ” smooth bore nozzle 8 FIRE 113-PPT-2-2-25 Examples A smooth bore handline has a NP of 50 psi, so NP =50. A 7/8” tip flows 161 GPM, so Q = 1.6 PDP = NP + FL + AL ± EP PDP = 50 + FL + AL ± EP FL = C × Q2 × L FL = 15.5 × (1.6)² × 200/100 FL = 15.5 × 2.56 × 2 FL = 79.36 psi (Round to 80 psi) FIRE 113-PPT-2-2-26 Examples Now we return to the PDP formula and insert FL PDP = NP + FL+ AL ± EP PDP = 50 + 80 + AL ± EP PDP = 130 psi FIRE 113-PPT-2-2-27 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations; pump discharge pressure; friction loss; calculating friction loss; and the different types yp of connections. FIRE 113-PPT-2-2-28 Review The Importance of Hydraulic Calculations Pump Discharge Pressure Friction Loss Calculating Friction Loss Using the Coefficient Method Estimating Friction Loss by Hose Size Examples FIRE 113-PPT-2-2-29 Lesson 3-1 Apparatus and Pump Panel Overview Student Performance Objective Given information from discussion, handouts, and reading materials, the student will describe the characteristics and parts of pumper apparatus. FIRE 113-PPT-3-1-1 Overview Pumps Types of Fire Pumps Types of Priming Systems FIRE 113-PPT-3-1-2 Pumps Fires are extinguished when the proper amount of water (GPM rate) is applied Water is directed through the nozzle at the required pressure to give the fire stream enough reach to penetrate to the seat of the fire FIRE 113-PPT-3-1-3 Pumps The pump pressurizes the water used to attack the fire A fire pump is a mechanical device used to move fluids Firefighters want the pump to move the water from the source to the fire through attack lines Pumps displace the fluid, which causes the fluid to move or flow The resistance to flow creates the pressure FIRE 113-PPT-3-1-4 Pumps Pumps cannot provide high pressure and high volume at the same time There are two sides of all pumps: intake and discharge The intake side is referred to as the "supply side" because it is where the water is supplied to the pump Pipes and connections for the intake are set lower than the discharge piping and connections FIRE 113-PPT-3-1-5 Types of Fire Pumps Positive-displacement pumps The pump traps a fixed amount of fluid and forces it into a discharge stream during every revolution of the pumping element The pump displaces the liquid by creating a space between the pumping elements, trapping the liquid in space The pumping element moves and reduces the size of the space, forcing the fluid out of the pump FIRE 113-PPT-3-1-6 Types of Fire Pumps Positive-displacement pumps Rely on tightly fitting parts to function properly Come in models that are self-priming p g but require the proper conditions to function properly Can move air or water during every revolution because the parts fit together so closely FIRE 113-PPT-3-1-7 Types of Fire Pumps Positive Displacement Pumps Are ideal for use as priming pumps for centrifugal pumps As p priming gp pumps p are connected to the top p of the centrifugal pump Are used as high-pressure auxiliary pumps or portable pumps FIRE 113-PPT-3-1-8 Types of Fire Pumps There are two classifications of positivedisplacement pumps: piston pumps and rotary pumps Rotary pumps exhibit a circular motion FIRE 113-PPT-3-1-9 Types of Fire Pumps Piston pumps have an up-and-down action FIRE 113-PPT-3-1-10 Types of Fire Pumps Rotary pumps are used as priming pumps for centrifugal pumps Rotary pumps operate in a circular motion, the discharge a constant flow of water with each revolution The pumping element rotates, expanding the volume inside to allow the water to enter the pump FIRE 113-PPT-3-1-11 Types of Fire Pumps The rotary gear pump uses two gears that are driven by a 12-volt electric motor The rotary vane pump uses small moveable vanes to freely move in and out of the rotor slots to maintain a tight seal against the pump casing FIRE 113-PPT-3-1-12 Types of Fire Pumps FIRE 113-PPT-3-1-13 Types of Fire Pumps FIRE 113-PPT-3-1-14 Types of Fire Pumps The centrifugal pump The centrifugal pump is the most common fire pump in use today Water flow is discharged g based on p pressures at the discharge side of the pump At higher flow rates (rpm), the pump flows less volume but creates higher pressures The pump spinning more slowly creates less pressure on the discharge side but flows greater water volume FIRE 113-PPT-3-1-15 Types of Fire Pumps The pump operates on the principle of centrifugal force: outward force from the center of rotation A metal pump impeller transfers energy from the vehicle's vehicle s motor to discharge incoming water Inside the impeller are impeller vanes, which divide the impeller The spinning impeller accelerates the water movement between the vanes and discharges the fluid radially outward into the volute FIRE 113-PPT-3-1-16 Types of Fire Pumps FIRE 113-PPT-3-1-17 Types of Fire Pumps The centrifugal pump can pump only water or other liquids The pump has no valves from the intake to discharge side The water can move between either side of the impeller when it is not spinning When the impeller is spinning, the water is taken from the intake side and flows out the discharge side If the discharge valves are closed, the water inside the pump will churn around inside FIRE 113-PPT-3-1-18 Types of Fire Pumps The centrifugal pump Relies on water movement from the intake side to the discharge side to operate effectively Is not self-priming Can take advantage of the incoming pressure on the intake side to increase the discharge pressure FIRE 113-PPT-3-1-19 Types of Fire Pumps Waterous Pump Training FIRE 113-PPT-3-1-20 Types of Fire Pumps Centrifugal pumps are single stage (one impeller) or multistage (two or more impellers within one pump housing turning on the same shaft) Single-stage pumps have one impeller that takes in and discharges water out of the pump FIRE 113-PPT-3-1-21 Types of Fire Pumps FIRE 113-PPT-3-1-22 Types of Fire Pumps The two-stage pump is the most common type of multistage pump The transfer valve determines whether the pump will be operated in series/pressure mode or parallel/volume mode p – Never use transfer valve when PSI is over 50 psi When in parallel/volume mode, the water enters each impeller from the common intake side and is discharged into the common discharge header When in the series/pressure mode, the water travels through one impeller in series FIRE 113-PPT-3-1-23 Types of Fire Pumps FIRE 113-PPT-3-1-24 Types of Fire Pumps A fire pump is rated by and tested to Underwriters Laboratories (UL) specifications During annual service testing the pump must produce at: 100 percent of rated capability at 150 psi for 20 minutes 70 percent of rated capability at 200 psi for 10 minutes 50 percent of rated capability at 250 psi for 10 minutes No rating is provided for pressures greater than 250 psi FIRE 113-PPT-3-1-25 Types of Fire Pumps Special multistage pumps are built to produce extraordinarily high pressures for special pumping requirements Some departments p want the ability y to use high-pressure booster lines while still having volume pumping capabilities of 500 GPM or more FIRE 113-PPT-3-1-26 Types of Fire Pumps The pump capacity is increased significantly with the development of larger pumps with larger impellers In the 1950s, p pumps p delivered flows of 500 or 750 GPM Today, pumps can flow at 2000 GPM or larger Pump capacity also increased because of the increase in diesel engines' horsepower FIRE 113-PPT-3-1-27 Types of Fire Pumps Power supplies for pumps The driver/operator must be familiar with how various pumps receive power The simplest form of a power supply is available with a portable pump The pump is carried by two or more firefighters to a water source to pump the water from the source The pump has a small engine attached directly to the pump There are no gear boxes, clutches, shifting levers, or other devices FIRE 113-PPT-3-1-28 Types of Fire Pumps Some apparatus have a pump mounted on the front bumper Power take-off (PTO) units are commonly used for small pumps like those on tankers or tenders The PTO unit is mounted to the side of the transmission, through the shaft directed to the gear case on the pump PTO provides a less-expensive method of developing pump power, especially when the pump has a limited capacity PTO allows a pump-and-roll capability for certain apparatus FIRE 113-PPT-3-1-29 Types of Fire Pumps Transfer case is the most common power system found in pumps The gearbox is mounted to the apparatus frame between the transmission and rear axle The drive shaft is connected from the apparatus transmission to the transfer case so the transfer case can direct power to the rear axle or pump FIRE 113-PPT-3-1-30 Types of Fire Pumps Power supplies for pumps Placing the pump into the pump gear in the cab transfers power from the rear axle to the pump The pump speed is directly related to transmission speed Automatic transmissions are made for pumping operations that will lock into the intended gear once the apparatus is placed in the pumping mode FIRE 113-PPT-3-1-31 Types of Fire Pumps FIRE 113-PPT-3-1-32 Types of Fire Pumps Electronic Pump Governors Come in different styles made by the different apparatus builders Control the p pump pp pressures via electronic throttle control and a pump casing transducer Allow pump pressure to remain at a set pressure Can be operated in RPM or pressure mode Will not control pressure until a discharge pressure of 70 psi is reached FIRE 113-PPT-3-1-33 Types of Fire Pumps When drafting with an EPG: It is recommended you draft in RPM mode After draft is successful and water flow established switch to pressure mode FIRE 113-PPT-3-1-34 Types of Fire Pumps Safety Considerations EPGs have several safety features that can prevent damage to the pump EPGs have an Electronic Control Module or ECM If the water supply is not sufficient and discharge pressure drops below 45 psi the EPG will limit engine speed to 1100 RPM’s If the pressure drops below 15 psi the engine will reset to idle FIRE 113-PPT-3-1-35 Types of Fire Pumps Should any of the above conditions exist on an attack engine the operator should: Place the EPG in the RPM mode and throttle back up to the desired pump pressure Stay in RPM until all danger to attack crews has passed Try to figure out the problem after the incident is over FIRE 113-PPT-3-1-36 Types of Priming Systems Positive Displacement primers The Rotary Vane Primer Requires higher RPM Can be powered mechanically by the pump transfer case or by an electric motor Consists of a rotary vane pump, primary vane and oil reservoir FIRE 113-PPT-3-1-37 Types of Priming Systems FIRE 113-PPT-3-1-38 Types of Priming Systems Positive displacement primers use an oil supply for two reasons: Oil helps seal the gaps between gears and the case Oil acts as a preservative and minimizes part deterioration FIRE 113-PPT-3-1-39 Types of Priming Systems Rotary Gear Primers Have a larger capacity than a rotary vane primer Can tolerate larger air leaks than smaller pumps Enable priming action to take place under adverse conditions Consist of a pump, priming valve and oil reservoir Can be driven by electric motor or mechanically by the transfer case FIRE 113-PPT-3-1-40 Types of Priming Systems FIRE 113-PPT-3-1-41 Types of Priming Systems Manual Controls Some primers have the option of being operated electronically or manually Manual operating p g controls are p placed on the pump panel When manual control is used: The mechanical drive to the pump should be energized and the pump turning before opening the priming valve After the pump is primed, the priming valve must be closed before the priming pump stops turning FIRE 113-PPT-3-1-42 Types of Priming Systems Exhaust Primers (EPs) In EPs the exhaust gases are stopped by the exhaust gas deflector and diverted to a chamber to create a venturi effect and a vacuum The chamber is connected though a line and a priming valve to the intake of the pump An exhaust primer requires a lot of maintenance since exhaust gases moving through the primer leave deposits and can reduce efficiency FIRE 113-PPT-3-1-43 Types of Priming Systems FIRE 113-PPT-3-1-44 Types of Priming Systems Exhaust Primers Exhaust primers require high RPM’s Exhaust primers are primarily used on portable pumps p p FIRE 113-PPT-3-1-45 Types of Priming Systems Vacuum Primers (VPs) VPs are the simplest type of primer VPs make use of the vacuum already present in the intake manifold of anyy g gasoline engine g As air enters the line from the intake side of the pump, the pump is primed and fills with water Vacuum primers work best at low RPM With the advent of diesel engines this type of primer is seldom used FIRE 113-PPT-3-1-46 Types of Priming Systems FIRE 113-PPT-3-1-47 Types of Priming Systems Operation of a Primer In order to operate a primer it is necessary to follow these generall steps: t Create an airtight waterway from the pump to the water Set the engine RPM as required by your manufacturer’s specifications FIRE 113-PPT-3-1-48 Types of Priming Systems Operate the primer until the pump is primed and: The hard suction hose drops and fills with water There is a vacuum reading on compound gauge Water discharges on the ground from the priming pump or exhaust ejector Pressure is indicated on pressure gauge FIRE 113-PPT-3-1-49 Student Performance Objective Given information from discussion, handouts, and reading materials, the student will describe the characteristics and parts of pumper apparatus. FIRE 113-PPT-3-1-50 Review Pumps Types of Fire Pumps Types of Priming Systems FIRE 113-PPT-3-1-51 Lesson 3-2 Hydraulic Calculations II Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations for attack lines and wyed connections. FIRE 113-PPT-3-2-1 Overview Hydraulic Calculations for Attack Lines Connections and Appliances FIRE 113-PPT-3-2-2 Hydraulic Calculations for Attack Lines Using multiple hoselines of different sizes and lengths On the fireground, a scenario may arise where multiple water pressures are needed from one fire pumper Only one pressure (the highest) can be created by a pumper The driver/operator needs to know how to control the water pressures on discharges requiring less pressure – Two identical lines – Operating lines of unequal size and length FIRE 113-PPT-3-2-3 Hydraulic Calculations for Attack Lines Under normal conditions, the valve should be fully opened to prevent excess turbulence and FL through the valve FIRE 113-PPT-3-2-4 Hydraulic Calculations for Attack Lines Calculating friction loss using the Q² method The basic formula for this calculation is FL = Q² The formula has a conversion factor depending on hose diameter For 3” hose FL = Q² For 2½” hose FL = Q² × 2 For 4” hose FL = Q² ÷ 5 For 5” hose FL = Q² ÷ 15 For 6” hose FL = Q² ÷ 30 FIRE 113-PPT-3-2-5 Examples A pumper is supplying two attack lines. The first is 150’ of 1¾” hose flowing 150 GPM with a fog nozzle. The second line is 200’ of 2½” hose flowing 250 GPM with a smooth bore nozzle. Using the Coefficient method, what is the PDP? The PDP for the FIRST line is: FL =C × Q² × L FL = 15.5 × (1.5)² × 1.5 FL = 15.5 × 2.25 × 1.5 FL = 52.3 for FIRST line FIRE 113-PPT-3-2-6 Examples Insert the FL into the PDP formula: PDP = NP + FL+ AL ± EP PDP = 100 + 52.3 + AL ± EP PDP = 152.3 psi The PDP for the SECOND line is: FL =C × Q² × L FL = 2 × (2.5)² × 2 FL = 2 × 6.25 × 2 FL = 25 for the SECOND line FIRE 113-PPT-3-2-7 Examples Insert the FL into the PDP formula PDP = NP + FL + AL ± EP PDP = 50 +25 + AL ± EP PDP = 75 psi The answer for this scenario is the higher pressure which was 152 psi on the FIRST line FIRE 113-PPT-3-2-8 Examples The same scenario calculated with the Q² method: The PDP for the FIRST line according to chart in SM 2-2 is 140 PSI The PDP for the SECOND line is: FL = Q² × 2 FL = 2.5² × 2 FL = 6.25 × 2 FL = 12.5 psi per 100 feet of hose × 2 FL = 25 psi for the SECOND line FIRE 113-PPT-3-2-9 Examples Insert the FL into the PDP formula PDP = NP + FL+ AL ± EP PDP = 50 +25 + AL ± EP PDP = 75 psi The answer for this scenario is the higher pressure which was 140 psi on the FIRST line FIRE 113-PPT-3-2-10 Examples A pumper is supplying two hoselines. The first attack line is 300’of 2½” hose flowing 300 GPM with a smooth bore nozzle. The second line is 200’ of 1¾” hose flowing 150 GPM with a fog nozzle. What is the PDP? The PDP for the first line is: FL = C × Q² Q ×L FL =2 × (3)² × 3 FL = 54 Insert the FL into the PDP formula PDP = NP + FL + AL ± EP PDP = 50 + 54 + AL ± EP PDP = 104 FIRE 113-PPT-3-2-11 Examples The PDP for the second line is: FL =C × Q² × L FL = 15.5 × (1.5)² × 2 FL = 69.75 Insert the FL into the PDP formula PDP = NP + FL + AL ± EP PDP = 100 + 69.75 + AL ± EP PDP = 169.75 The answer for this scenario is the higher pressure which was 169.75 psi (round to 170 psi) on the second line FIRE 113-PPT-3-2-12 Examples The same scenario calculated with the Q² method: The PDP for the FIRST line is: FL = Q² × 2 FL = 3.0² × 2 FL = 9 × 2 FL = 18 psi per 100 feet of hose × 3 FL = 54 psi for the FIRST line FIRE 113-PPT-3-2-13 Examples Insert the FL into the PDP formula PDP = NP + FL + AL ± EP PDP = 50 + 54 + AL ± EP PDP = 104 psi The PDP for the SECOND line according to chart in SM 2-2 is 155 PSI The answer for this scenario is the higher pressure which was 155 psi on the second line FIRE 113-PPT-3-2-14 Hydraulic Calculations for Attack Lines Elevation Pressure Adjust the calculations for elevation pressure, which is the distance the nozzle is above or below the pump Elevation loss is the pressure lost when the nozzle is above the pump Elevation gain is the pressure gained when a nozzle is below the pump FIRE 113-PPT-3-2-15 Hydraulic Calculations for Attack Lines Elevation Pressure Add or subtract the EP from the PDP after calculating the EP Elevation loss requires added pressure to discharge to compensate for the loss Elevation gain requires the subtraction of pressure from the discharge pressure Adjust for elevation considering grade and altitude relative to sea level FIRE 113-PPT-3-2-16 Hydraulic Calculations for Attack Lines There are many situations where the water has to be discharged at an elevation that is higher or lower than the pumper A change in elevation affects the PDP because water has weight that must be compensated for FIRE 113-PPT-3-2-17 Hydraulic Calculations for Attack Lines When calculating EP, remember water exerts a pressure of 0.434 psi per 1' of water column When doing calculations simplify by multiplying by 0.5 per foot To speed the calculation process further, determine the elevation change in 10' increments and multiply by 5 psi FIRE 113-PPT-3-2-18 Hydraulic Calculations for Attack Lines Elevation Pressure Use a variance of ±5 psi per floor when calculating the elevation gain/loss on multi-story buildings For multi-story buildings, use EP = 5 psi × (number of stories - 1) To calculate the EP for a grade, use EP = 0.5 H 0.5 is constant H = height FIRE 113-PPT-3-2-19 Examples Determine EP when the nozzle is on the eleventh floor of a building EP = (Number of stories -1) × 5 psi EP = (11-1) × 5 psi EP = 10 × 5 psi EP = 50 psi FIRE 113-PPT-3-2-20 Examples Determine the EP when the nozzle is 30’ below the pump EP = 0.5 × height EP = 0.5 × -30 EP = -15 PSI FIRE 113-PPT-3-2-21 Hydraulic Calculations for Attack Lines Appliance Loss Appliances are the devices used to connect and adapt the hoses and direct and control the water flow in various hose layouts Appliances include adapters, reducers, gated wyes, Siamese connections, water thieves, monitors, manifolds, and elevated master stream devices FIRE 113-PPT-3-2-22 Hydraulic Calculations for Attack Lines Like any other water supply device, appliances may add to FL As in the fire hose, the FL in an appliance is directly proportional to the water volume (GPM) flowing through the system An appliance FL is considered insignificant when the water flows are less than 350 GPM Assign 10 psi in AL for handlines with a flow of 350 GPM or greater FIRE 113-PPT-3-2-23 Hydraulic Calculations for Attack Lines Appliance Loss Friction in appliances will not be calculated in flows of less than 350 GPM Fire streams of 350 GPM or greater are considered master streams Assign 25 psi in AL for master streams FIRE 113-PPT-3-2-24 Hydraulic Calculations for Attack Lines When determining friction loss in appliances: Check the department appliances for FL at the water flows most likely to be encountered on the fireground Student will need the hose or appliance to be tested and two in-line in line pressure gauges for testing hose Also needed are a nozzle appropriately sized for the hose to control the water discharged, the hose to make the connections, and the adapters and fittings to make the connections FIRE 113-PPT-3-2-25 Hydraulic Calculations for Attack Lines Choose the method to use and document the results Conduct the tests on level ground and complete the process at various flows to see how the FL changes FIRE 113-PPT-3-2-26 Connections and Appliances Wyed Hoselines The wye is used to split a single line into two lines The use of a wye requires an additional calculation to find the final FL FIRE 113-PPT-3-2-27 Examples A pumper is supplying 100’ of 2½” hose to a wye that has two 1¾” lines 200’ long flowing 150 GPM each through fog nozzles. What is the PDP? FIRE 113-PPT-3-2-28 Examples PDP = NP + FL + AL ± EP FL =C × Q² × L FL for the 2½” line = 2 × (3)² × 1 FL = 18 psi FL for the 1¾” line = 15.5 × (1.5)² × 2 FL = 15.5 × 2.25 × 2 FL = 69.75 psi (round to 70 psi) It takes 70 psi to flow the 1¾” line, the second line is identical, both lines experience the same FL and have the same NP. FIRE 113-PPT-3-2-29 Examples Insert values into the formula: PDP = NP + FL + AL ± EP PDP = 100 (NP) + 36 (for the 2½” line) + 70 (for the 1¾” lines) + 10 for friction loss PDP = 100 + 18 + 70 + 10 + EP PDP = 198 psi FIRE 113-PPT-3-2-30 Examples The same scenario calculated with the Q² method: The PDP for the 2½” line is: FL = Q² × 2 FL = 3.0² × 2 FL = 9 × 2 FL = 18 psi per 100 feet of hose × 1 FL = 18 psi for the 2½” line FIRE 113-PPT-3-2-31 Examples Insert values in the formula: PDP = NP + FL + AL ± EP PDP = 50 + 18 + AL ± EP PDP = 68 psi The PDP for the 1¾” line according to chart in SM 2-2 is 155 PSI The answer for this scenario is the higher pressure which was 155 psi on the 1¾” line FIRE 113-PPT-3-2-32 Examples A pumper is supplying 100’ of 3” (with 2½” couplings) to a wye with two equal lines of 2½” hose, each 200’ flowing 250 GPM through smooth bore nozzles. What is the PDP? PDP = NP + FL + AL ± EP For the 3” line: FL =C × Q² × L FL = 0.8 × (5)² × 1 FL = 0.8 × 25 FL = 20 FIRE 113-PPT-3-2-33 Examples For the 2½” lines: FL =C × Q² × L FL = 2 × (2.5)² × 2 FL = 2 × 6.25 × 2 FL = 25 PDP = NP + FL + AL ± EP PDP = 50 + 20 + 25 + 10 (for appliance loss) PDP = 105 psi FIRE 113-PPT-3-2-34 Examples The same scenario calculated with the Q² method: For the 3” line is FL = Q² FL = 5² FL = 25 FIRE 113-PPT-3-2-35 Examples For the 2½” line FL = Q² × 2 FL = 2.5² × 2 FL = 6.25 × 2 FL = 12.5 × 2 (for 200 feet of hose) FL = 25 PDP = NP + FL + AL ± EP PDP = 50 + 25 + 25 + 10 (for appliance loss) PDP = 110 psi FIRE 113-PPT-3-2-36 Connections and Appliances Siamese Hoselines A Siamese connection is a device allowing multiple hoselines to converge into one and is often used on the intake side of a pump, allowing multiple lines to supply the pumper Used by departments that do not have a large-diameter hose Used to supply large amounts of water at a reasonable amount of pump pressure FIRE 113-PPT-3-2-37 Connections and Appliances A Siamese connection May be used on the discharge side of the pump to bring two or three lines into one attack line, reducing the FL in long reach Is found on fire department connections on buildings with standpipe sprinkler systems FIRE 113-PPT-3-2-38 Connections and Appliances There are three methods to calculate the FL in the lines to the Siamese connection when the lines are of equal size and length Split flow method C ffi i t method Coefficient th d Percentage method FIRE 113-PPT-3-2-39 Examples A pumper is supplying 1200 GPM through three 2½” lines that are 300 ft long to a Siamese line. What is the FL to the Siamese connection as calculated using the Siamese coefficient? FL = C × Q Q² × L C= 0.22 Q = 1200/100 = 12 L = 300’/100 = 3 FL = 0.22 × 12² × 3 FL = 95 psi FIRE 113-PPT-3-2-40 Examples The same scenario calculated with the Q² method: For the 2½” line FL = Q² × 2 FL = 4² × 2 FL = 16 × 2 FL = 32 × 3 (for 300 ft of hose) FL = 96 psi FIRE 113-PPT-3-2-41 Split Method Examples A pumper is supplying 1200 GPM through three 2½” lines that are 300’ long to a Siamese connection. What is the FL to the Siamese connection as calculated with the split flow method? 1200 GPM/3 hoselines = 400 GPM each FL =C × Q² × L C=2 Q = 400/100 = 4 L = 300’/100 = 3 FL =2 × 4² × 3 FL = 96 psi FIRE 113-PPT-3-2-42 Split Method Examples The same scenario calculated with the Q² method: For the 2½” hose FL = Q² × 2 FL = 4² × 2 FL = 16 × 2 FL = 32 × 3 (for 3 hose lines) FL = 96 psi FIRE 113-PPT-3-2-43 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations for attack lines and wyed connections. FIRE 113-PPT-3-2-44 Review Hydraulic Calculations for Attack Lines Connections and Appliances FIRE 113-PPT-3-2-45 Lesson 4-1 Static Water Supply Sources and Water Shuttle Operations Student Performance Objective Given information from discussion, handouts, and reading materials, the student will describe the process of priming, pumping, maintaining a flow of water from a draft and establishing water shuttle and dump p site operations. p FIRE 113-PPT-4-1-1 Overview Selecting a Drafting Site Pumping from a Draft Preparing to Operate at Draft by Priming the Pump Drafting Operations Producing a Flow of Water Preventing Complications during Drafting Operations Water Shuttle Operations Establishing Dump Site Operations FIRE 113-PPT-4-1-2 Selecting a Drafting Site Ensuring that an incident has a steady water supply Selecting the appropriate drafting site involves determining the reliability of the static water source including: g Accessibility Purpose of site Positioning of apparatus Once the reliability is established, operational requirements may influence the site selection FIRE 113-PPT-4-1-3 Selecting a Drafting Site Determining the reliability of static water sources Evaluate the reliability of a static water source before committing to draft from it Consider the following factors when determining the reliability of a static water source: Accessibility Quantity of water available Quality of water Remember that failure to determine the reliability can affect the ability to support fireground operations FIRE 113-PPT-4-1-4 Selecting a Drafting Site FIRE 113-PPT-4-1-5 Selecting a Drafting Site Estimating the quantity of water available Considering lakes or large rivers There is no question that an adequate supply will be available Smaller static sources require careful evaluation Evaluating water quality of a static source Water from a static source should be free of aquatic weeds, moss, algae, and other trash or debris Clean water is preferred over muddy or murky water FIRE 113-PPT-4-1-6 Selecting a Drafting Site FIRE 113-PPT-4-1-7 Selecting a Drafting Site Accessing the static water source Safely position the apparatus close enough to the water source to submerge the strainer of the hard-sided supply hose completely in water once it is connected to the fire pump Check the soil near the edges of the water source to make sure it is dry and solid enough to support the weight of the apparatus, especially for extended wet operations FIRE 113-PPT-4-1-8 Selecting a Drafting Site Identify a drafting site that is level and free of trees, bushes, rocks, fences, and other obstructions that may limit access to the source Obstructions can limit one's ability to access the site and can serve as safety concerns Rocks and other ground debris can cause trip hazards Too steep of a slope can make the apparatus shift or roll FIRE 113-PPT-4-1-9 Selecting a Drafting Site FIRE 113-PPT-4-1-10 Selecting a Drafting Site Remember that access to static water sources can be difficult during the winter Snow can hide hazards Ice covering the water presents an access problem and a potential life safety situation Chop a hole in the ice to gain access to the water source if necessary Firmly and carefully tap the ice to determine if it is safe to walk on FIRE 113-PPT-4-1-11 Selecting a Drafting Site Special accessibility considerations Draft from a bridge if needed Be sure the bridge is designed to support the weight of the apparatus Evaluate the height of the lift Consider the effects of restricting or blocking traffic Consider safety hazards for personnel and equipment when operating near moving traffic FIRE 113-PPT-4-1-12 Selecting a Drafting Site Identify drafting sites during preplanning rather than waiting for a fire Perform calculations for water availability from static and moving sources when you are not under pressure from an emergency g y incident Identify and note problem areas before an emergency operation and locate predetermined drafting sites FIRE 113-PPT-4-1-13 Selecting a Drafting Site FIRE 113-PPT-4-1-14 Selecting a Drafting Site Consider placing portable pumps near static water sources when accessibility with the fire pumper is not possible Portable pumps deliver water, through a hose, to a spot with better accessibility for the apparatus Drafting options using portable pumps are not ideal but multiple pumps may be used to supply larger volumes of water when needed Consider using floating pumps with ports and strainers that go below the water's surface and do not draw air into the pump FIRE 113-PPT-4-1-15 Selecting a Drafting Site Consider placing a dam in a streambed as an option for drafting from shallow flowing water sources Use anything that blocks the water flow in a stream FIRE 113-PPT-4-1-16 Selecting a Drafting Site If damming, ensure that: The water source, once dammed, will provide an adequate water supply Creating the dam will not have a negative effect downstream The dam is strong enough to stay in place for the duration of the operation Once the operation is completed, releasing the water will not have a negative effect downstream FIRE 113-PPT-4-1-17 Selecting a Drafting Site If drafting to supply a water shuttle or to be the source pumper in a relay operation, remember that operational and other considerations will apply to the site selection FIRE 113-PPT-4-1-18 Pumping from a Draft Setting up the pump to draft Setting up the pump to draft requires teamwork of two or more firefighters A hard-sided supply hose is heavy and can be awkward to handle with fewer than two firefighters FIRE 113-PPT-4-1-19 Pumping from a Draft Making the connection Determine when to connect the hard suction hose to the pump If the location allows, place the apparatus in its final position before making connections while ensuring an adequate space to work around the pump panel and to connect the hose to the pump intake valve If space is limited, connect the hard suction hose away from the final position and slowly move the apparatus with firefighters carrying the hose while advancing toward the final position FIRE 113-PPT-4-1-20 Pumping from a Draft Before the connections are made, inspect the gaskets for proper placement and the absence of cracks and debris that might affect their ability to create a vacuum and obtain draft Using a rubber mallet to tighten connections provides a strong seal and ensures they will not loosen when moved during placement A hard suction hose must be connected to the pump intake connection FIRE 113-PPT-4-1-21 Pumping from a Draft FIRE 113-PPT-4-1-22 Pumping from a Draft Once the needed length of hose is determined, place the strainer on the end The strainer prevents large debris and animals or fish from entering the pump and causing pump failure or damage The connection between the strainer and hose should be as tight as the connection between the hard suction hose and pump intake valve FIRE 113-PPT-4-1-23 Pumping from a Draft FIRE 113-PPT-4-1-24 Pumping from a Draft Strainer Use Barrel strainers are most commonly used for deep water sources in which strainers will not be able to contact the bottom of the source or large debris fields Low-level Low level strainers are designed for clean clean, shallow water sources The square-shaped, flat strainer has an opening between two flat plates of aluminum There is a 2" wide gap between 16" plates on the top and bottom of the strainer FIRE 113-PPT-4-1-25 Pumping from a Draft FIRE 113-PPT-4-1-26 Pumping from a Draft Low-level strainers are considered lower-flow strainers because their intake openings are slightly smaller than the hose diameter to avoid creating a strong draft that draws in debris Low-level strainers are used when drafting from portable t bl ttanks k b because th the water t iis d debris-free bi f and d the strainer can touch the bottom without dirt or silt entering the pump FIRE 113-PPT-4-1-27 Pumping from a Draft Floating strainers are designed to operate below the surface scum, but above the weeds, dirt, or silt in a water source Are ideal for water sources in which the depth or bottom quality is unknown Can be large and will take up significant space in the apparatus cabinets May be made of aluminum or polyethylene Contain large, hollow chambers, allowing them to float Have an intake port equipped with a strainer that is placed below the water surface and will not draw air into the pump FIRE 113-PPT-4-1-28 Pumping from a Draft FIRE 113-PPT-4-1-29 Pumping from a Draft Once all connections are made, the hard suction hose and strainer should be placed into the water Tie rope to the strainer to help move the hose once it is in the water Ensure that the strainer is completely immersed so air is not drawn into the pump FIRE 113-PPT-4-1-30 Pumping from a Draft When using a barrel strainer, ensure that there is at least 24" of water in all directions around the strainer Remember that low-level, floating strainers are designed to operate in shallow conditions and require only 24" of water depth With connections made and the strainer securely placed, begin drafting FIRE 113-PPT-4-1-31 Preparing to Operate at Draft by Priming the Pump Ensure that all drains and valves including the tank to pump valve are closed Firmly pull the priming pump handle out until it stops, hold it out and increase RPM’s to manufacturers f t specifications ifi ti Observe that water and air are discharged under the apparatus FIRE 113-PPT-4-1-32 Preparing to Operate at Draft by Priming the Pump FIRE 113-PPT-4-1-33 Preparing to Operate at Draft by Priming the Pump Look for a vacuum reading to appear on the supply master gauge while pulling the handle out Priming should not take more than 45 to 60 seconds if everything is working correctly N t th Note thatt more water t flows fl outt off th the priming i i pump and is discharged under the apparatus when the air is pumped out Do not stop operating the priming pump until you note pressure on the discharge side Slightly advance the throttle FIRE 113-PPT-4-1-34 Preparing to Operate at Draft by Priming the Pump FIRE 113-PPT-4-1-35 Drafting Operations Before supplying water to the handlines, master streams, or relay pumping operation, establish a dump line Slowly open the discharge valve for the dump line and begin flowing water If the valve is opened too fast, it may cause a loss of vacuum, breaking the pump draft Slightly increase the engine rpm to maintain the draft FIRE 113-PPT-4-1-36 Drafting Operations FIRE 113-PPT-4-1-37 Drafting Operations Discharge water from the dump line back into the water source, away from the strainer, to avoid introducing air into the hard suction hose An air inflow may lead to a loss of vacuum, ending the pump's pump s draft If the dump line cannot be discharged back into the source, discharge the water onto the ground away from the drafting site FIRE 113-PPT-4-1-38 Drafting Operations Once you sustain a flow of water through the dump line, attach the hoselines that you will be supplying The lines may differ depending on the purpose of the drafting operation The operation can be sped up if other crew members make the connections while the driver/operator establishes the draft and dump lines Once the water is flowing from the dump line and the lines being supplied are attached, increase the amount of water that will flow FIRE 113-PPT-4-1-39 Producing a Flow of Water Whether supplying attack lines or water for an attack pumper, make sure the crews know that water flow is ready to start before opening the discharge valve Slowly open the corresponding discharge valve for the hoseline and begin flowing water Increase the engine rpm by increasing the throttle to maintain the draft and provide an adequate discharge pressure FIRE 113-PPT-4-1-40 Producing a Flow of Water FIRE 113-PPT-4-1-41 Producing a Flow of Water Observe that the water flow into the pump usually is slower than the discharge flow because the energy required to create a vacuum is greater than the energy required to discharge water Continue to increase the throttle until the desired discharge pressure is reached Set the pressure relief valve to prevent spikes Once the draft has been accomplished, do not drop the draft until the operation is completed and either the water supply officer or the IC gives the order to do so FIRE 113-PPT-4-1-42 Preventing Complications during Drafting Operations Continuously observe the intake gauge reading (compound gauge) while drafting Continuously observe the temperature gauges Drafting operations require components to work hard; sometimes, ti nott enough h water t flows fl tto kkeep th them cooll If you are supplying a dump line while waiting to fill the tanker shuttle operation, your flow will be less than 100 GPM FIRE 113-PPT-4-1-43 Preventing Complications during Drafting Operations FIRE 113-PPT-4-1-44 Preventing Complications during Drafting Operations Open and close the cooling lines as recommended by the apparatus manufacturer to prevent the engine or pump from overheating Listen for cavitation Cavitation occurs when attempting to flow water faster than it is supplied to the pump FIRE 113-PPT-4-1-45 Preventing Complications during Drafting Operations Remember that cavitation affects the fire pump's ability to deliver water and can damage the pump The problem is easy to diagnose because it causes the discharge pressure reading on the pump panel to fluctuate significantly g y The firefighter will hear a rattling that sounds like the pump is pumping gravel When the pump is cavitating, the discharge pressure does not respond to the throttle (rpm) increase as under normal operations The firefighter may hear a sputtering or popping from the nozzles on the discharge lines FIRE 113-PPT-4-1-46 Preventing Complications during Drafting Operations If cavitation is suspected during drafting, notify the IC, throttle down and reduce discharge and/or flow Check the vacuum reading on the master supply gauge The reading should indicate 1 in. Hg of pressure for each foot of lift under normal operating conditions If the reading is significantly higher than normal, suspect cavitation due to supply restrictions FIRE 113-PPT-4-1-47 Preventing Complications during Drafting Operations FIRE 113-PPT-4-1-48 Preventing Complications during Drafting Operations If there is a higher than normal vacuum reading, check the intake screen If the screen is clean but the supply vacuum reading is still high, confirm that the suction valve is fully open (if one is being g used)) If everything checks out but the vacuum reading is still high, reduce the throttle slightly or gate down discharges slightly; you probably are trying to pump water faster than it can be supplied to the pump FIRE 113-PPT-4-1-49 Preventing Complications during Drafting Operations Remember that a pump's failure to prime is one of the most common problems that occurs during drafting operations Double-check the steps required for priming the pump E Ensure th the fi fire pump on th the apparatus t primes i iin th the time ti specified in the manufacturer’s specifications Follow the diagnostic steps to identify the problem and find a solution: Note the vacuum reading on the supply master gauge after holding the primer valve fully open for 20 to 30 seconds FIRE 113-PPT-4-1-50 Preventing Complications during Drafting Operations If you cannot create a vacuum, recheck all the valves on the pump control panel to verify they are closed Recheck the couplings on the hard suction line to make sure they are tight Make sure the suction strainer is completely submerged Try priming the pump again If it is still not working and the booster tank is empty, add one or two 5-gal buckets of water to the booster tank Make sure the primer is operating within manufacturer’s specifications FIRE 113-PPT-4-1-51 Preventing Complications during Drafting Operations If you cannot create a vacuum make sure the intake screen is clean and water is not being lifted too high Reposition the fire pump so the lift is 10-15’ Make sure the suction valve is open (if one is being used) Try to prime the pump again If you are still unsuccessful and the vacuum reading is high, remove the suction hose from the pump and check the inlet strainer on the fire pump and the inside of the suction hose for an obstruction FIRE 113-PPT-4-1-52 Preventing Complications during Drafting Operations Reconnect the hard suction hose and try to prime the pump again If you are still unsuccessful and the vacuum reading is high, replace the hard suction hose with another hose and try again FIRE 113-PPT-4-1-53 The Water Shuttle Using a water shuttle in rural and remote areas Elements of a water shuttle A fill site is where tankers get their water tanks filled A dump p site is where the tanker offloads water Water shuttles can become large and complex operations A water supply officer is assigned to coordinate required activities If the incident is small or quickly mitigated, the water shuttle may be simple and short FIRE 113-PPT-4-1-54 The Water Shuttle FIRE 113-PPT-4-1-55 The Water Shuttle Establishing a fill site at a static water source Remember the formula PDP = 35 + FL + AL ± EP Establish a fill site from a static source following the same procedures as discussed earlier Choose a location after considering if it affects how other apparatus will access the incident Select a site that will not block egress to the scene When the tanker is full, slowly throttle down and close the discharge valves, keeping the dump line open during the operation FIRE 113-PPT-4-1-56 The Water Shuttle FIRE 113-PPT-4-1-57 The Water Shuttle When utilizing fill sites in inaccessible areas, consider Using portable pumps to get the water to the tankers if you cannot get a pumper close to a static water source Using portable floating pumps for obtaining water in inaccessible areas FIRE 113-PPT-4-1-58 The Water Shuttle Safety for water shuttle operations Steps to improve incident safety include: Preplanning locations for obtaining water Being trained in the use and operation of the equipment Knowing which equipment to use Communication between tankers and the fill sites may require a separate radio frequency FIRE 113-PPT-4-1-59 The Water Shuttle Sites should be well lit and personnel should wear high visibility PPE Extreme caution must be emphasized while driving tankers because they handle differently from standard pumpers The maneuverability is greatly reduced with tankers due to their size and weight Vehicles should never be operated beyond the posted speed limit FIRE 113-PPT-4-1-60 The Water Shuttle FIRE 113-PPT-4-1-61 Establishing Dump Site Operations Choosing and establishing a dump site location The site should be on firm, level ground that is not susceptible to significant changes from apparatus movement or getting wet from water The location must be large and strong enough to support the weight of the water and incoming tankers The location should provide enough room for the movement of tankers in and out Large parking lots and fields that are flat and smooth make excellent dump sites FIRE 113-PPT-4-1-62 Establishing Dump Site Operations Taking care not to obstruct the flow of additional responding apparatus or the tanker shuttle Consider which way a tanker will offload water Once a good site is determined, set up the portable tanks and create a static source for the source pumper FIRE 113-PPT-4-1-63 Establishing Dump Site Operations Using portable tanks Fill the portable tanks with as much water as the capacity of the tanker allows When using portable tanks, an expanding operation should be considered The portable tanks provide water that is free from debris and not subjected to stream currents and unknown shore soil conditions FIRE 113-PPT-4-1-64 Establishing Dump Site Operations Ensure portable tank is set in an area free of debris that could puncture the tank Initially fill the portable tank from a tanker before it enters the water shuttle operation When tanks are in place, the tanker positions itself to offload water and moves to fill site The portable tank should not overflow while being filled, so fill the tank slowly FIRE 113-PPT-4-1-65 Establishing Dump Site Operations FIRE 113-PPT-4-1-66 Establishing Dump Site Operations Offloading tankers A method of offloading a tanker when large dump valves are not installed on apparatus is to attach medium-size lines (2½" to 3") to the tanker pump and place the other end of the lines into the portable tank The hose must be held in place or a commercially made device must be attached to the tank The tanker driver/operator should pump water through the hoselines at a maximum of 50 psi FIRE 113-PPT-4-1-67 Establishing Dump Site Operations Use of multiple portable tanks The use of multiple portable tanks is standard practice in rural firefighting Jet siphon adapters use a hard suction hose as a pathway for flowing water forced through the hose by Venturi forces The jet siphon has a connection for a 1½" or 1¾" hose to flow water, creating Venturi forces and drawing water from the tank up through the hose to be discharged into the second tank A jet siphon is connected to one end of a loose hard suction hose in the tank from which the water is being removed FIRE 113-PPT-4-1-68 Establishing Dump Site Operations A 1½" or 1¾" hose is attached to the jet siphon device and placed into the tank once it is full The source pumper connects a hose to the discharge port and pumps at 100 to 125 psi Dump p lines should not be used to supply pp y jjet siphons p You can use multiple jet siphons to move water between the tanks depending on how many tanks are in the operation FIRE 113-PPT-4-1-69 Establishing Dump Site Operations Source pumper considerations for portable tank operations Keep the main portable tank full when moving water from one tank to another After the source pumper establishes a draft from a static water supply, make an effort to prevent air from being introduced into the pump When one tank is used, the tanker operator must not dump water on or near the strainer, creating air turbulence Using a blow-up ball is important in portable tank operations because the size of the water "container" is much smaller and whirlpools can easily be created in shallow water FIRE 113-PPT-4-1-70 Establishing Dump Site Operations FIRE 113-PPT-4-1-71 Establishing Dump Site Operations Note that the main tank should not run low on water during an operation if the tanker shuttle is working as designed If the main tank runs out of water, the incident loses its water supply, putting firefighters at risk if they are in interior positions If the main tank keeps running low, ask the IC or water supply officer to consider adding more tankers to the shuttle operation to keep up with the water demands FIRE 113-PPT-4-1-72 Establishing Dump Site Operations Traffic flow within a dump site Ensure efficient movement of tankers to prevent congestions Place the portable tanks in as open an area as possible to allow easy maneuverability around the site Offload two tankers at the same time if both sides of the tanks are accessible and offloading into two tanks will not disrupt the source pumpers' drafting operation FIRE 113-PPT-4-1-73 Student Performance Objective Given information from discussion, handouts, and reading materials, the student will describe the process of priming, pumping, maintaining a flow of water from a draft and establishing water shuttle and dump p site operations. p FIRE 113-PPT-4-1-74 Review Selecting a Drafting Site Pumping from a Draft Preparing to Operate at Draft by Priming the Pump Drafting Operations Producing a Flow of Water Preventing Complications during Drafting Operations Water Shuttle Operations Establishing Dump Site Operations FIRE 113-PPT-4-1-75 Lesson 4-2 Relay Pump Operations Student Performance Objective Given information from discussion, handouts, and reading materials, the student will describe the process of establishing a relay pump operation. FIRE 113-PPT-4-2-1 Overview The Complexity of Relay Operations Components of a Relay Pumping Operation Personnel for Relay Pumping Operations Preparing for a Relay Pumping Operation Types of Relay Pumping Operations FIRE 113-PPT-4-2-2 Overview Operating the Source Pumper Operating the Attack Pumper Operating the Relay Pumper Joining an Existing Relay Pumping Operation Pressure Fluctuations in a Relay Pumping Operation Shutting Down a Relay Pumping Operation Safety for Relay Pumping Operations FIRE 113-PPT-4-2-3 The Complexity of Relay Operations The relay can be as simple as one pumper at a source and another pumper at the scene The relay can be as complex as multiple pumpers to supply water over a long distance to the fire operation FIRE 113-PPT-4-2-4 Components of a Relay Pumping Operation A minimum of two fire pumpers with hoselines and personnel are needed to establish a relay Two supply or LDH lines supply the water The fire hose can consist of a single LDH 4” or 5” in diameter The fire hose can consist of multiple medium-size hoses 2½” or 3” in diameter FIRE 113-PPT-4-2-5 Components of a Relay Pumping Operation FIRE 113-PPT-4-2-6 Components of a Relay Pumping Operation The source pumper Is the most important pumper in a relay because it is located at the water source and supplies water to the incident Should be the largest fire pump assigned to a relay operation ensuring it can provide the maximum amount of operation, water FIRE 113-PPT-4-2-7 Components of a Relay Pumping Operation The attack pumper Is the first unit on the scene and its operation dictates how much water is needed based on how many GPM are required for the fire attack May lay a dry supply line into the scene to be filled by the source pumper or relay pumper if it cannot establish its own water supply Should have the supply line laid down from an open area to the limited access point if positioned in an area with limited access Starts supplying the hoselines while operating from a water tank on arrival at the incident FIRE 113-PPT-4-2-8 Components of a Relay Pumping Operation Can support additional hoselines only if the incoming water supply from a relay operation will support them Is the "workhorse," providing the water to all hoselines attacking the fire Relay pumpers Are apparatus placed in the middle of the relay pumping operation Obtain water from the source pumper and increase the pressure to the next pumper in the relay Cannot increase the water volume (GPM) being pumped FIRE 113-PPT-4-2-9 Components of a Relay Pumping Operation FIRE 113-PPT-4-2-10 Components of a Relay Pumping Operation Single lines of LDH have a low friction loss variable Medium size hose has significantly higher friction loss than LDH; therefore, if medium hoselines are used for water supply, it will require 2+ lines to provide the same GPM as an LDH To avoid the issue, use LDH when possible Calculate the friction loss for your part of the operation and adjust the discharge pressure FIRE 113-PPT-4-2-11 Components of a Relay Pumping Operation No matter which hose is used to supply water from the source pumper, each pumper in a relay operation and the attack pumper must be equipped with an intake relief valve The intake relief valve prevents the incoming water supply from reaching an excessively high pressure, damaging the pump and interrupting relay operation Relief valves discharge excessive pressure through a port on the valve FIRE 113-PPT-4-2-12 Personnel for Relay Pumping Operations It is the driver/operator's responsibility to operate the pump and manage the intake and discharge pressures The second firefighter is responsible for managing the area around the apparatus to ensure the safety of the members by monitoring vehicle movement and warning the driver of possible dangers FIRE 113-PPT-4-2-13 Preparing for a Relay Pumping Operation The length of the relay operation is determined by the distance from a water source to the incident The amount of water required by the attack pumper and the size of the supply line affect whether relay pumpers are required and how many are needed Once the hose is in place for a relay, the need for a relay pumper can be determined by calculating the amount of friction loss for that length of hose lay FIRE 113-PPT-4-2-14 Preparing for a Relay Pumping Operation FIRE 113-PPT-4-2-15 Types of Relay Pumping Operations The most common type of relay uses actual flow calculations to determine the water quantity required The attack pumper's needs drive the relay operation The attack pumper's driver/operator must communicate to the source pumper's pumper s driver/operator how much water (GPM) is flowing now or is planned to flow The attack pumper driver/operator determines the flow quickly by adding the flow of each handline or master stream that the attack pumper is discharging FIRE 113-PPT-4-2-16 Types of Relay Pumping Operations The driver/operator of the source pumper calculates the distance between the two pumpers in hose lengths To calculate the friction loss, divide the flow in GPM by the number of hoselines used Multiply the friction loss factor by the number of feet in hundreds for the total friction loss Once the friction loss is calculated, add the residual pressure (20psi) to prevent cavitation for a total discharge pressure FIRE 113-PPT-4-2-17 Types of Relay Pumping Operations In a constant pressure relay, the source pumper and relay pumpers supply a constant pressure and flow for the operation regardless of the flow (GPM) being discharged by the attack pumper Many departments have standardized supply pressures used for constant pressure relays based on experience The use of constant pressure relay eliminates the need for pump calculations unless there are excessive elevation changes FIRE 113-PPT-4-2-18 Types of Relay Pumping Operations The pumper driver/operator sets the pump discharge pressure depending on the size of the supply line and maintains the pressure for the duration of the operation Setting the pressure relief valve or pressure governor maintains the desired pressure in the event of changes at th attack the tt k pumper FIRE 113-PPT-4-2-19 Operating the Source Pumper The relay pumping operation starts at the source pumper, where the largest fire pump should be located When setting up the source pumper at a static water source consider the maximum water available for source, the operation Establish a water source and, once water is flowing through the dump line, connect the hoselines and notify the receiving driver/operator that the water is ready to start flowing FIRE 113-PPT-4-2-20 Operating the Source Pumper FIRE 113-PPT-4-2-21 Operating the Source Pumper Determine the flow rate by calculating the friction loss for the supply hose based on the GPM to be supplied, the relay length, and the hose size, plus residual pressure of 20 psi Contact the receiving driver/operator that the supply is ready Open the discharge valve and slowly flow the water while advancing the throttle as the discharge valve is opened When the desired pressure is reached, set the pressure relief valve or governor to prevent pump damage if the flow is stopped or interrupted by the relay or attack pumper FIRE 113-PPT-4-2-22 Operating the Attack Pumper The attack pumper establishes the hoselines that determine the flow If the attack pumper starts and continues flowing water from the pumper tank until the relay is set up, monitor the tank level to ensure the interior crews do not run out of water Getting the water from the source pumper is critical to continued operations and firefighter safety Once the supply lines are charged, bleed the air in the hoseline from the bleeder valve on the pumper's intake valve until a steady water stream comes out of the bleeder Always bleed the supply lines to prevent the air from entering the pump FIRE 113-PPT-4-2-23 Operating the Attack Pumper Pressure from the incoming water supply increases the discharge pressure to the hoselines unless the throttle rate is decreased Close the tank-to-pump valve and slightly open the tank fill valve Fill the tank on the attack pumper When full, close the tank fill valve FIRE 113-PPT-4-2-24 Operating the Attack Pumper The source pumper should be advised how much water is needed and indicate whether the incoming pressure is sufficient to maintain at least 20 psi of residual pressure If more flow is needed needed, contact the supply crew but do not try to get more water than the source pumper is supplying Until receiving the required pressure/ flow, decrease the pressure to the handlines supported by the attack pumper Notify the crews operating the lines so they can make adjustments or retreat until the water supply issue is resolved FIRE 113-PPT-4-2-25 Operating the Relay Pumper Lay out the hose between the next pumper and your location and supply the required pressure and volume to the next pumper or the attack pumper When water fills the supply hose, bleed off any air in the hoseline from a bleeder valve on the pumper's pumper s intake valve until a steady stream of water comes out of the bleeder FIRE 113-PPT-4-2-26 Operating the Relay Pumper FIRE 113-PPT-4-2-27 Operating the Relay Pumper Have the driver/operator of the relay pumper monitor incoming residual pressure from the source or other relay pumper Once the flow is stabilized, set the pressure relief valve or governor to prevent damage to the fire pump if the flow is stopped or interrupted by the supply or discharge side of the pump FIRE 113-PPT-4-2-28 Joining an Existing Relay Pumping Operation Most relay operations are set up all at once from the beginning of an incident Adding a pumper to an existing operation requires stopping the water flow If called to assist with the relay operation already in progress, the driver/operator needs to hook up the pumper to the hoselines already in use Pumpers generally are added to an existing operation because of an insufficient pressure or flow to meet the demands of the attack pumper FIRE 113-PPT-4-2-29 Pressure Fluctuations in a Relay Pumping Operation The needs and capacity of the attack pumper affect all other pumpers in the relay operation The driver/operator of the attack pumper determines the GPM needed and notifies the driver/operators of the relay and/or source p pumpers p of their requirements q Mechanical failures or an increase or decrease in hoseline flows can cause pressure fluctuations Sometimes the driver/operator must man-ually adjust the pump pressures The driver/operator of the attack pumper and all relay pumpers must decrease the pump discharge pressure FIRE 113-PPT-4-2-30 Pressure Fluctuations in a Relay Pumping Operation If the attack pumper opens an additional line causing an increased flow (GPM), all the relay pumpers need to ensure they do not drop below 20 psi residual pressure to avoid pump cavitation The intake relief valve can compensate for increased intake pressure FIRE 113-PPT-4-2-31 Shutting Down a Relay Pumping Operation The order to terminate a relay pumping operation is given by the IC or the water supply officer only after careful consideration Shutting down the operation is simple, but all pumpers must be coordinated When shutting down an operation, the attack pumper acts first The driver/operator of the attack pumper ensures that the apparatus tank is full, then slowly throttles down The hoselines continue flowing water while shutting down the relay to prevent fluctuations in water pressure throughout the operation FIRE 113-PPT-4-2-32 Shutting Down a Relay Pumping Operation The next pumper in the relay makes sure that its tank is full, and slowly throttles down, while still flowing water The source pumper contacts the attack pumper to begin closing the intake valve FIRE 113-PPT-4-2-33 Shutting Down a Relay Pumping Operation All pumpers in the relay close the intake and discharge lines until all pumpers are no longer flowing water, including the dump line from the source pumper The hoselines are disconnected and drained before reloading or rolling up A systematic approach prevents pump damage by keeping the water flowing at low levels before being shut down completely FIRE 113-PPT-4-2-34 Shutting Down a Relay Pumping Operation The source pumper shuts down the water source to stop the water flow into the pump If providing water from a static source, stop the flow through the pump to break the vacuum and draft FIRE 113-PPT-4-2-35 Safety for Relay Pumping Operations Remember that communication is an integral part of a relay pumping operation Contact the IC for a channel to which all pump operators can be assigned Remember that constant communication between the pump driver/operators helps prevent situations that might cause safety hazards FIRE 113-PPT-4-2-36 Safety for Relay Pumping Operations Exercise caution when using fire hose during relay pumping operations Identify any defects and replace the hose section before it is used to save time later and have a safer operation If the defect is spotted after an operation began began, get a replacement hose in place and follow the shutdown procedures used for entering an existing relay pumping operation FIRE 113-PPT-4-2-37 Safety for Relay Pumping Operations Exercise caution when personnel work around relay pumping operations Turnout pants and boots, helmet, and gloves will protect the driver/operator's hands, feet, and head from falling equipment q p or hoseline failure Crew members in or around the street and moving traffic should wear reflective vests, even during daytime operations Know that NFPA standards are moving towards requiring the placement of discharges on opposite side of pump for safer pump operations FIRE 113-PPT-4-2-38 Student Performance Objective Given information from discussion, handouts, and reading materials, the student will describe the process of establishing a relay pump operation. FIRE 113-PPT-4-2-39 Review The Complexity of Relay Operations Components of a Relay Pumping Operation Personnel for Relay Pumping Operations Preparing for a Relay Pumping Operation Types of Relay Pumping Operations FIRE 113-PPT-4-2-40 Review Operating the Source Pumper Operating the Attack Pumper Operating the Relay Pumper Joining an Existing Relay Pumping Operation Pressure Fluctuations in a Relay Pumping Operation Shutting Down a Relay Pumping Operation Safety for Relay Pumping Operations FIRE 113-PPT-4-2-41 Lesson 4-3 Hydraulic Calculations III Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations on a relay operation. FIRE 113-PPT-4-3-1 Overview Hydraulic Calculations for Relay Operations FIRE 113-PPT-4-3-2 Hydraulic Calculations for Relay Operations Relay Pumpers Fire departments may have to establish a water supply with inadequate hoselines One solution to this problem is to insert relay pumpers into the line to compensate for friction loss Adding a relay pumper in the middle of the supply line will help reduce engine pressure of the supply pumper FIRE 113-PPT-4-3-3 Examples A supply pumper is delivering water for an attack pumper through 1000’ of 3” hose. The attack pumper is flowing 500 GPM through nozzle. What is the PDP for the supply pumper? PDP = NP + FL + AL ± EP FL =C × Q² × L FL = 0.8 × (500/100)² × (1000’/100) FL = 0.8 × 5² × 10 FL = 0.8 × 25 × 10 FL = 200 psi FIRE 113-PPT-4-3-4 Examples PDP = NP + FL + AL + EP PDP = 50 + 200 PDP = 250 psi FIRE 113-PPT-4-3-5 Examples The same scenario calculated with the Q² method would go as follows For the 3” hoseline FL = Q² FL = 5² FL = 25 × 10 (for 1000’ of hose) FL = 250 PDP = NP + FL + AL + EP PDP = 50 + 250 PDP = 300 psi FIRE 113-PPT-4-3-6 Examples However, if a relay pumper is introduced into the system halfway between the source pumper and the attack pumper (500’) and flows the same 500 GPM through 500’ of 3” hose with a fog nozzle, the PDP is reduced. PDP = NP + FL + AL ± EP PDP = 50 + FL + AL ± EP FL =C × Q² × L FL = 0.8 × (500/100)² × (500’/100) FL = 0.8 × 5² × 5 FL = 100 FIRE 113-PPT-4-3-7 Examples PDP = NP + FL + AL + EP PDP = 50 + 100 + AL + EP PDP = 150 psi FIRE 113-PPT-4-3-8 Examples The same scenario calculated with the Q² method would go as follows – For the 3” hoseline – FL = Q² – FL = 5² – FL = 25 × 5 (for 500’ of hose) – FL = 125 – PDP = NP + FL + AL + EP – PDP = 50 + 125 – PDP = 175 psi FIRE 113-PPT-4-3-9 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations on a relay operation. FIRE 113-PPT-4-3-10 Review Hydraulic Calculations for Relay Operations FIRE 113-PPT-4-3-11 Lesson 6-1 Foam Equipment Systems Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of foam systems and foam proportioning methods. FIRE 113-PPT-6-1-1 Overview Introduction to Foam Foam Proportioning Foam Supplies FIRE 113-PPT-6-1-2 Introduction to Foam Foam Creation Foam is created through the application of four components: water, foam concentrate, mechanical agitation, and air Water mixes with the foam concentrate in various ratios to produce a foam solution FIRE 113-PPT-6-1-3 Introduction to Foam The solution mixes with air by mechanical agitation In firefighting, this mechanical agitation usually takes the form of a nozzle that mixes the air and foam solution to form the final product: finished foam Too little foam concentrate in the water produces a lean solution l ti th thatt may dissipate di i t into i t th the ffuell Too much concentrate produces a rich solution that cannot properly expand or aspirate when mixed with air FIRE 113-PPT-6-1-4 Introduction to Foam The expansion of the foam solution depends on the process of introducing air into the foam solution Good mechanical agitation gives an effective aeration When iinsufficient Wh ffi i t air i iis iintroduced t d d iinto t th the solution l ti stream, the solution is poorly aerated The foam has few bubbles, causing the foam to break down quickly so it does not suppress vapors effectively FIRE 113-PPT-6-1-5 Introduction to Foam FIRE 113-PPT-6-1-6 Introduction to Foam Foam Compatibility Mixing the different classes of concentrate may make the concentrate gel, hindering the operation of foam proportioning equipment Class B foam concentrates are not compatible with each other Class A and Class B concentrates are not compatible FIRE 113-PPT-6-1-7 Introduction to Foam Make sure onboard tanks on the apparatus are properly marked Many apparatus carry onboard water, Class A foam concentrate, and Class B foam concentrate tanks The concentrate can be poured into the wrong tank with undesirable results FIRE 113-PPT-6-1-8 Foam Proportioning Proportioning foam properly Applying foams at the proper percentage depends on the foam concentrate being mixed at the proper percentage with water The percentage of concentrate is introduced into the water stream The driver/operator must be familiar with the equipment used in the department's foam operations FIRE 113-PPT-6-1-9 Foam Proportioning FIRE 113-PPT-6-1-10 Foam Proportioning The driver/operator has the responsibility to produce effective foam streams He or she must have the knowledge of all aspects of foam operations so the foam will work as intended Foam not mixed at the proper percentage or not used as intended will be ineffective and could put firefighters in danger FIRE 113-PPT-6-1-11 Foam Proportioning To produce a finished foam, the water, air, and foam concentrate must be mixed at the proper ratio The foam concentrate must be added to the water flowing from the discharge line to form the proper mixture The mixture or percentage is based on the foam concentrate used, material involved in the incident, and the equipment used to produce the finished foam FIRE 113-PPT-6-1-12 Foam Proportioning Foam proportioning systems A foam proportioner: a device that mixes the foam concentrate into the fire stream in the proper percentage There are two types: eductors and injectors The foam solution can also be produced by batch mixing or premixing FIRE 113-PPT-6-1-13 Foam Proportioning FIRE 113-PPT-6-1-14 Foam Proportioning Batch mixing Batch mixing is the process of pouring a foam concentrate directly into the apparatus tank and mixing a large amount of foam at once The proper amount of the foam concentrate is poured into the onboard tank to produce the desired percentage in finished foam FIRE 113-PPT-6-1-15 Foam Proportioning Batch mixing requires no special appliances but there are some problems: The foam solution is corrosive to the apparatus's pipes, pump, and water tank It is difficult to adjust j and maintain the correct application rate, especially if additional water is supplied from an external source Adding the foam solution causes the gauges to be inaccurate and overflows the water tank with foam when the pump re-circulates the mixture When the water tank is empty, there is no foam available; a new batch must be mixed FIRE 113-PPT-6-1-16 Foam Proportioning Premixing: a technique reserved for portable fire extinguishers Foam eductors Induction involves the use of an eductor to introduce the appropriate i t amountt off foam f concentrate t t into i t a water t stream flowing from the discharge An eductor is an appliance that uses the Venturi principle to induce a foam concentrate into a water stream Eductors can be built into the plumbing of the engine or a portable eductor can be inserted in the attack hoseline FIRE 113-PPT-6-1-17 Foam Proportioning The foam eductor is designed to work at a predetermined pressure and flow rate A foam eductor has a small pick-up tube submerged in the foam concentrate Water traveling g through g the in-line eductor draws the foam concentrate into the water at the desired percentage using the Venturi principle – Suction is created at the narrow inlet to the eductor – The foam concentrate is introduced into the eductor using a metering valve, which lets the driver/operator adjust the foam concentrate percentage educted into the water stream FIRE 113-PPT-6-1-18 Foam Proportioning There are two types of eductors in the fire service: inline and bypass In-line eductors Have long been used to proportion foam Are simple to operate and found in many departments May be mounted permanently on the apparatus or can be portable and connected anywhere along the hose lay FIRE 113-PPT-6-1-19 Foam Proportioning FIRE 113-PPT-6-1-20 Foam Proportioning In-line eductors Are used only for applying foam Mounted permanently to the fire pump are dedicated to one foam discharge Bypass eductors are appliances that can be used for water or foam application, depending on incident requirements FIRE 113-PPT-6-1-21 Foam Proportioning Most eductors are calibrated to flow a rated capacity at a specified inlet pressure Eductors deliver various flow rates The nozzle used must match the flow rating of the eductor The manufacturer's recommendations must be followed when selecting nozzles FIRE 113-PPT-6-1-22 Foam Proportioning Metering valve The metering valve will be adjusted to control the amount of foam concentrate introduced into the water stream Metering valves have adjustable settings: 0 (closed) to 6 percent FIRE 113-PPT-6-1-23 Foam Proportioning The percentage on the metering valve is achieved only if the inlet pressure at the eductor matches the manufacturer's recommended inlet pressure If the eductor is operated at less than the recommended inlet pressure, a lower flow of water goes through the eductor If the inlet pressure to the eductor exceeds the pressure recommended by the manufacturer, this causes the foam solution to have a lower percentage of concentrate, thus affecting the company's ability to handle the situation FIRE 113-PPT-6-1-24 Foam Proportioning FIRE 113-PPT-6-1-25 Foam Proportioning The around-the-pump proportioning system The around-the-pump proportioning (AP) system operates on the same principle as an in-line or bypass eductor system An around-the-pump around the pump proportioning system diverts part of a water pump's output from the discharge side through the eductor A vacuum is created at the eductor's foam concentrate inlet, which draws the foam concentrate through the metering valve and into the eductor The foam solution is sent to the suction side of the water pump, where it mixes with the incoming water and is distributed throughout the discharge piping FIRE 113-PPT-6-1-26 Foam Proportioning FIRE 113-PPT-6-1-27 Foam Proportioning The AP system has several advantages over other foam-creation methods: The variable flow discharge rate allows for the adjustment of foam depending on the application Variable pressure operations are possible, possible usually within 125 psi to 250 psi There are no backpressure restrictions because the system is not affected by the hose length or elevation loss There are no nozzle restrictions because the system operates with any size or type of fixed-gallon nozzle FIRE 113-PPT-6-1-28 Foam Proportioning AP systems have certain limitations The maximum inlet pressure to the water pump cannot be more than 10 psi Anything greater affects the eductor's operation Some systems are designed to operate with an inlet pressure as much as 40 psi FIRE 113-PPT-6-1-29 Foam Proportioning AP systems operate properly when the water is supplied from the onboard tank or draft A pressurized source affects the system operation Most apparatus with AP systems have a direct tank fill that does not go through the pump Flush all discharges after the foam operation has ended, even if not all of the foam was used FIRE 113-PPT-6-1-30 Foam Proportioning Balanced-pressure proportioning system The balanced-pressure proportioning system is a versatile and accurate means to deliver foam and water The foam concentrate pump is a separate pump that supplies the foam concentrate to the pressure control valve and ratio controller Many balanced-pressure systems are equipped with a foam heat exchanger FIRE 113-PPT-6-1-31 Foam Proportioning FIRE 113-PPT-6-1-32 Foam Proportioning Injection systems Injection systems use an electrically operated, variable-speed foam concentrate pump to directly inject the foam concentrate into the discharge side of the pump manifold Injection systems are unaffected by changes in suction and discharge pressure FIRE 113-PPT-6-1-33 Foam Proportioning The compressed-air foam system (CAFS) Combines compressed air and foam solution to create a finished foam Is designed for quick and effective fire attack and exposure protection Generates a Class A foam: a high-quality finished foam that clings to vertical surfaces FIRE 113-PPT-6-1-34 Foam Proportioning FIRE 113-PPT-6-1-35 Foam Proportioning Master stream foam nozzles Master stream foam nozzles let operators deal with large incidents where handline nozzles cannot handle the demands for foam suppression Master stream nozzles are supplied from the apparatus's apparatus s onboard systems or can have an eductor A pick-up tube draws foam into the master stream nozzle Master stream foam nozzles can be mounted permanently on the apparatus, can be removable for use as a portable unit, or can be portable devices FIRE 113-PPT-6-1-36 Foam Proportioning FIRE 113-PPT-6-1-37 Foam Proportioning Air-aspirating foam nozzles Are designed to mix air with a foam solution while being discharged Are designed to aspirate the foam solution to produce a good-quality good quality finished foam FIRE 113-PPT-6-1-38 Foam Proportioning Smooth-bore nozzles The aeration of foam solution occurs in the piping and hose, so the finished foam is discharged at the nozzle The application is the major concern at the discharge of the nozzle using CAFS FIRE 113-PPT-6-1-39 Foam Proportioning Fog nozzles The problem with fog nozzles is that they do not provide the best aeration of the foam solution For an incident involving polar solvent fuels, the fog nozzles may not deliver foam able to extinguish the fire Foam aeration tubes are available to clamp onto the fog nozzle to aerate the foam solution more efficiently FIRE 113-PPT-6-1-40 Foam Supplies Foam concentrate is stored in containers from 5gallon pails to 55-gallon drums The shelf life varies depending on the type of concentrate The environmental impact when using foam has been a concern FIRE 113-PPT-6-1-41 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of foam systems and foam proportioning methods. FIRE 113-PPT-6-1-42 Review Introduction to Foam Foam Proportioning Foam Supplies FIRE 113-PPT-6-1-43 Lesson 6-2 Hydraulic Calculations IV Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations on master streams. FIRE 113-PPT-6-2-1 Overview Hydraulic Calculations for Master Streams FIRE 113-PPT-6-2-2 Hydraulic Calculations for Master Streams Master streams A pre-piped elevated master stream is an aerial fire apparatus (ladder truck) with a fixed waterway attached to the underside of the ladder with a water inlet at the base supplying the master stream device at the end Figure 4-11 shows that the master stream device has a locking mechanism that places the nozzle on the bed section for rescue or on a fly section for water tower operations No single FL amount can adequately encompass all prepiped elevated master stream devices FIRE 113-PPT-6-2-3 Hydraulic Calculations for Master Streams The Rule of 8’s Is a method to calculate the flow through a master stream smooth bore nozzle Convert the fraction part of the tip size into 8ths Take the top number of the fraction and add 2 The result is the FL in 100’s of GPM FIRE 113-PPT-6-2-4 Hydraulic Calculations for Master Streams Example: A master stream with a 1½” tip ½ converts to 4/8 4+2=6 6 × 100 = 600 GPM FIRE 113-PPT-6-2-5 Examples A pumper supplying an elevated master stream is on the hydrant, supplying one 5” line that is 200’ long to the inlet of the ladder truck, which has a ladder extended 80’ vertically; it is equipped with a 1½” smooth bore master stream tip p ((600 GPM). ) There is 30 psi of FL in the fixed waterway of this particular truck. Assign 25 psi FL for the master stream appliance. What is the PDP? FIRE 113-PPT-6-2-6 Examples PDP = NP + FL + AL + EP PDP = 80 + FL + AL + EP FL =C × Q² × L FL = 0.08 × 6² × 2 FL = 5.76 (round to 6) FL = 6 + AL FL = 6 + 30 (specific to the waterway) FL = 36 psi PDP = 80 + 36 + 25 + 40 PDP = 181 psi FIRE 113-PPT-6-2-7 Examples The same scenario calculated with the Q² method: For the 5” line FL = Q² ÷ 15 FL = 6² ÷ 15 FL = 36 ÷ 15 FL = 2.4 x 2 (for 200 ft of hose) FL = 4.8 psi (round to 5) FIRE 113-PPT-6-2-8 Examples FL = 5 + AL FL = 5 + 30 FL = 35 PDP = 80 + 35 + 25 + 40 PDP = 180 psi FIRE 113-PPT-6-2-9 Examples Determine the PDP for supplying a non-prepiped elevated master stream that is raised 60’ and is flowing 600 GPM to a 1½” tip rated at 80 psi through 300’ of 3” hose with 2½” couplings. The aerial and master streams have 25 p psi of FL each. PDP = NP + FL + AL + EP PDP = 80 + FL + AL + EP FIRE 113-PPT-6-2-10 Examples FL =C × Q² × L FL = 0.8 × (600/100)² × (300/100) FL = 0.8 × 6² x 3 FL = 0.8 × 36 x 3 FL = 86 psi AL = 20 psi EP = 30 psi PDP = NP + FL + AL + EP PDP = 80 + 86 + 20 + 30 PDP = 216 psi FIRE 113-PPT-6-2-11 Examples The same scenario calculated with the Q² method: For the 3” line FL = Q² FL = 6² FL = 36 FL = 36 x 3 (for 300 ft of hose) FL = 108 PDP = 80 + 108 + 20 + 30 PDP = 238 psi FIRE 113-PPT-6-2-12 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations on master streams. FIRE 113-PPT-6-2-13 Review Hydraulic Calculations for Master Streams FIRE 113-PPT-6-2-14 Lesson 7-1 Standpipe and Sprinkler Connections Student Performance Objective Given information from discussion, handouts, and reading materials, describe the procedures for connecting and flowing water through a standpipe/sprinkler system. FIRE 113-PPT-7-1-1 Overview Standpipe/Sprinkler Connections FIRE 113-PPT-7-1-2 Standpipe/Sprinkler Connections Connecting supply hoselines to standpipe and sprinkler systems Fire department connections on buildings are provided so the department can pump water into the standpipe and/or sprinkler p systems y The hoseline's function is to provide a primary or secondary water supply for the sprinkler or standpipe system FIRE 113-PPT-7-1-3 Standpipe/Sprinkler Connections FIRE 113-PPT-7-1-4 Standpipe/Sprinkler Connections Standpipe systems Standpipe systems provide a water supply for the attack lines that will be operated inside the building Outlets are provided in the building where firefighters can connect the attack lines Firefighters in the building depend on firefighters outside to supply the water to the fire department connection FIRE 113-PPT-7-1-5 Standpipe/Sprinkler Connections FIRE 113-PPT-7-1-6 Standpipe/Sprinkler Connections Types of standpipe systems are the Dry standpipe system: depends on the department to provide all the water Wet standpipe system: has a built-in water supply, p connection is p provided to deliver but the department a higher flow or to boost pressure If the exterior FDC connection is damaged so the connection cannot be accomplished, hook up to the standpipe on the building's first floor FIRE 113-PPT-7-1-7 Standpipe/Sprinkler Connections After connecting the engine to the sprinkler/standpipe, the department's SOP may specify when to supply the standpipe A wet system has water under pressure in the pipe at all times A dry system has no water in the pipe and depends on the department to supply water Regardless of the system present, a supply line must be established FIRE 113-PPT-7-1-8 Standpipe/Sprinkler Connections Sprinkler systems Private fire protection systems may be present in the building due to building characteristics within a response area as well as the height and construction materials used in the building FIRE 113-PPT-7-1-9 Standpipe/Sprinkler Connections Pre-incident planning and a familiarization with the response area help to identify buildings with sprinkler systems and standpipes When planning or driving through your response area, look for fire department connections (FDCs), hydrant l locations, ti and d sprinkler i kl valves l associated i t d with ith th the building Look for signs indicating a FDC location FIRE 113-PPT-7-1-10 Standpipe/Sprinkler Connections Typically free standing or wall mounted FDCs consist of a Siamese connection with two 2½" female connections The building's occupancy may require multipleconnection standpipes to be present Local codes may dictate the number and the size of the standpipes provided FIRE 113-PPT-7-1-11 Standpipe/Sprinkler Connections Each female connection should have a clapper valve inside the Siamese connection that swings closed when the connection is not in use This allows one side of the Siamese connection to be charged without water discharging from the other open intake i t k Depending on your department's SOP, both and/or all connections to the FDC should be used when supplying the standpipe FIRE 113-PPT-7-1-12 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the procedures for connecting and flowing water through a standpipe/sprinkler system. FIRE 113-PPT-7-1-13 Review Standpipe/Sprinkler Connections FIRE 113-PPT-7-1-14 Lesson 7-2 Hydraulic Calculations V Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations on a standpipe system. FIRE 113-PPT-7-2-1 Overview Standpipe Hydraulic Calculations FIRE 113-PPT-7-2-2 Standpipe Hydraulic Calculations Standpipe systems Standpipe operations can pose a challenge since firefighters must know the buildings, occupancy, fire load, special hazards, and hydrant locations Be familiar with the fire department connection (FDC) and standpipe locations Know whether there are pressure-regulating valves and what types, if present Know whether a pump is available in the building Have an established pre-incident plan for hazard targets FIRE 113-PPT-7-2-3 Standpipe Hydraulic Calculations For buildings with standpipe supply systems, the water supply is critical When the FDC has two connections, advance a hoseline to the FDC and charge it before attaching the second hoseline Get the water into the standpipe system as soon as possible FIRE 113-PPT-7-2-4 Standpipe Hydraulic Calculations For buildings with standpipe supply systems, the water supply is critical Have different pumpers supply each FDC on buildings with multiple FDCs – High-risk g buildings g should have one p pumper p on the hydrant supplying another on the standpipe connection – A water supply independent of the building supply should be available FIRE 113-PPT-7-2-5 Standpipe Hydraulic Calculations Standpipe systems require the greatest number of calculations; they have very demanding pump pressures Calculate standpipe pump pressures from markings on or at the FDC or as determined by depart-mental SOPs Predetermine pump discharge pressures for highrise structures to limit the calculations needed on the fireground during the actual incident FIRE 113-PPT-7-2-6 Standpipe Hydraulic Calculations The driver/operator controls only one pressure to the standpipe: the highest pressure needed at any one discharge The operator must pump to the highest pressure required not necessarily the highest in elevation The operator must calculate the PDP for each line being supplied FIRE 113-PPT-7-2-7 Standpipe Hydraulic Calculations The firefighter needs to know the required operating pressure of the attack hoselines to adequately control the pressure from the outlet Ensure that the attack hoseline is flowing water so that the crew member can obtain an accurate gauge reading Increase the pressure to the desired pressure for the outlet being used Using an in-line gauge is preferred for standpipe operations FIRE 113-PPT-7-2-8 Standpipe Hydraulic Calculations The PDP for standpipe operations requires that calculations be made for supply lines to standpipe, the FL within a standpipe system, the FL for attack handlines, and the pressure loss due to an increase in elevation If no pre-incident i id t plan l h has b been made d and d th the riser i size i is unknown, add 25 psi to account for the standpipe riser FIRE 113-PPT-7-2-9 Standpipe Hydraulic Calculations Pressure-regulating valves (PRVs) PRVs are installed on standpipe risers where static pressures exceed 175 psi If the pressures while flowing exceed 100 psi, NFPA 14 requires the installation of a device at the outlet to restrict or reduce the flow pressure to a maximum of 100 psi FIRE 113-PPT-7-2-10 Examples You have been assigned to develop a pre-incident plan for the use of a standpipe system for fire attack on the top floor of a 17-story building. The attack hose will consist of two 200’ of 2½” hose with a smooth bore 11/8” tip p nozzle. A third 2½” line with 1¼” tip is the backup line. The total flow is 858 GPM. The FDC is supplied with two 100’ lengths of 2½” hose. The building is equipped with a 5” riser (the coefficient is 0.126). What is the PDP to operate these three lines on the 10th floor? FIRE 113-PPT-7-2-11 Examples Supply FL = C × Q² × L Supply FL = 2 × (4.29)² × 1 Supply FL = 36.8 (round to 37 psi) FDC = 10 psi AL when flowing 350 GPM or greater and calculating for standpipe FL Riser FL = C × Q² × L Riser FL = 0.126 × (8.58)² × 0.9 Riser FL = 14.84 (round to 14 psi) FIRE 113-PPT-7-2-12 Examples Two attack lines with 200’ of 2½” hose with 11/8” smooth bore nozzles: FL =C × Q² × L FL = 2 × (2.66)² × 2 FL = 28 psi PDP = 50 + 28 PDP = 78 psi for these two lines (round to 80 psi) FIRE 113-PPT-7-2-13 Examples One attack line with 200’ of 2½” hose with a 1¼” smooth bore nozzle FL =C × Q² × L FL = 2 × (3.26)² × 2 FL = 42.5 psi (round to 43 psi) PDP = 50 + 43 PDP = 93 psi We add elevation for 9 floors (5 psi times 9) PDP = 93 + 45 PDP = 138 FIRE 113-PPT-7-2-14 Examples Pump to the line requiring the highest pressure (138 psi) and add it all together: 138 is highest pressure attack line 14 for the riser 10 for FDC 37 supply to the FDC Add 45 psi for elevation loss Total PDP = 93 + 13 + 10 + 37 + 45 Total PDP = 199 psi (round to 200 psi) FIRE 113-PPT-7-2-15 Examples The same scenario calculated with the Q² method: For the Supply 2½” line Supply FL = Q² x 2 Supply FL = 4.29² x 2 Supply FL = 18.4 (round to 18) x 2 Supply FL = 36 x 1 (for 100 ft of hose) Supply FL = 36 psi FIRE 113-PPT-7-2-16 Examples Two attack lines with 200’ of 2½” hose with 1½” smooth bore nozzle FL = Q² x 2 FL = 2.66² x 2 FL = 7.07 (round to 7) x 2 FL = 14 x 2 (for 200’ of hose) FL = 28 PDP = NP + FL +AL ± EP PDP = 50 + 28 PDP = 78 psi FIRE 113-PPT-7-2-17 Examples One attack line with 200’ of 2½” hose with 1¼” smooth bore nozzle FL = Q² x 2 FL = 3.26² x 2 FL = 10.6 (round to 11) x 2 FL = 22 x 2 (for 200’ of hose) FL = 44 PDP = NP + FL +AL ± EP PDP = 50 + 44 PDP = 94 psi FIRE 113-PPT-7-2-18 Examples Pump to the line requiring the highest pressure (94 psi) and add it all together 94 is the highest pressure attack line 14 for the riser 10 for the FDC 36 supply to the FDC 45 psi for elevation loss Total PDP = 94 + 14 + 10 + 36 + 45 Total PDP = 199 psi (Round to 200) FIRE 113-PPT-7-2-19 Student Performance Objective Given information from discussion, handouts, and reading materials, describe the importance of hydraulic calculations on a standpipe system. FIRE 113-PPT-7-2-20 Review Standpipe Hydraulic Calculations FIRE 113-PPT-7-2-21 Lesson 8-1 Hydraulic Calculations VI Student Performance Objective Given information from discussion, handouts, and reading materials, demonstrate proficiency in fireground hydraulic calculations and describe the importance and use of flow meters and electronic pump p p controllers. FIRE 113-PPT-8-1-1 Overview Fireground Hydraulic Calculations Flow Meters and Electronic Pump Controllers Calculations for Lines of Unequal Diameter and/or Length FIRE 113-PPT-8-1-2 Fireground Hydraulic Calculations Charts Charts list the most commonly used or reasonably expected hose lays The chart lists the common pressures for the attack hose and nozzle combinations at different lengths Charts may be homemade or purchased, pocket-size or larger When using the charts, do not allow pressures to exceed the hose test pressures Charts may be prepared for complex fire problems Chart Sample FIRE 113-PPT-8-1-3 FIRE 113-PPT-8-1-4 Coefficients for Friction Loss (psi/100ft) gpm 3/4" 1" 10 20 30 40 60 90 100 120 150 175 200 220 240 250 260 280 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1200 1300 1400 1500 2000 11.00 44.00 99.00 176.00 1.50 6.00 13.50 24.00 54.00 1 1/2" 0.96 2.16 3.84 8.64 19.44 24.00 34.56 54.00 73.50 96.00 116.16 138.24 1 3/4" 2" 2 1/2" 5.58 12.56 15.50 22.32 34.88 47.47 62.00 75.02 89.28 96.88 2.88 6.48 8.00 11.52 18.00 24.50 32.00 38.72 46.08 50.00 0.72 1.62 2.00 2.88 4.50 6.13 8.00 9.68 11.52 12.50 13.52 15.68 18 00 18.00 24.50 32.00 3" (2 1/2") 3" 3 1/2" 3.20 3.87 4.61 5.00 5.41 6.27 7 20 7.20 9.80 12.80 16.20 20.00 24.20 28.80 33.80 39.20 2.72 3.29 3.92 4.25 4.60 5.33 6 12 6.12 8.33 10.88 13.77 17.00 20.57 24.48 28.73 33.32 38.25 43.52 49.13 55.08 61.37 68.00 1.36 1.65 1.96 2.13 2.30 2.67 3 06 3.06 4.17 5.44 6.89 8.50 10.29 12.24 14.37 16.66 19.13 21.76 24.57 27.54 30.69 34.00 48.96 57.46 66.64 76.50 4" 5" 4.05 5.00 6.05 7.20 8.45 9.80 11.25 12.80 14.45 16.20 18.05 20.00 28.80 33.80 39.20 45.00 80.00 4.50 5.12 5.78 6.48 7.22 8.00 11.52 13.52 15.68 18.00 32.00 FIRE 113-PPT-8-1-5 Fireground Hydraulic Calculations Hydraulic calculators Hydraulic calculators: may be manual (mechanical) or electronic Manual hydraulic calculators may consist of a sliding card or slide rule Slide rule hydraulic calculators offer fire stream calculators (GPM) and FL calculators Electronic calculators: may be mounted, hand held or applications in a smart phone FIRE 113-PPT-8-1-6 Fireground Hydraulic Calculations FIRE 113-PPT-8-1-7 Flow Meters and Electronic Pump Controllers The sensing device on top of the meter is designed to measure the flow (GPM) through the discharge A flow meter can deliver the desired GPM without the operator knowing the length of the hoselines (L), FL, or EP FIRE 113-PPT-8-1-8 Flow Meters and Electronic Pump Controllers The technological innovation assists the driver/operator but raises the possibility of an electrical failure, disabling apparatus The threat of an electrical malfunction increased because of the absence of manual overrides on fire apparatus with these features The driver/operator must have a thorough understanding of the apparatus and pumping procedures should problems occur FIRE 113-PPT-8-1-9 Calculations for Lines of Unequal Diameter and/or Length Parallel lines of unequal diameter In some cases a combination of 2½” and 3” hose may be used in parallel In this case, the 3” line will carry about 60% and the 2½” 2½ will carry the other 40% Friction loss calculations are done for the 3” hose FIRE 113-PPT-8-1-10 Example If 500 GPM are moving through parallel lines of 3” and 2½”, 300 GPM would be carried by the 3” for 200’ of hose FL =C × Q² × L FL = 2 × 3² × 2 FL =2 × 9 × 2 FL = 36 FIRE 113-PPT-8-1-11 Example The same scenario using the Q² method: FL = Q² × 2 FL = 3² × 2 FL = 9 × 2 FL = 18 (per 100’ of hose) FL = 18 × 2 (for 200 ft of hose) FL = 36 FIRE 113-PPT-8-1-12 Calculations for Lines of Unequal Diameter and/or Length Parallel Lines of unequal length When using parallel lines of the same diameter but different lengths you average the length of all items Example p Two parallel lines are supplying water, one is 1000’ long and the other 800’ Average of both lengths is 900’ Calculate FL as if they were two 900’ lines FIRE 113-PPT-8-1-13 Calculations for Lines of Unequal Diameter and/or Length Estimating Hydrant Capacities An estimate of the remaining capacity of a hydrant can be made by comparing the static pressure at the initial connection with the residual pressure while water is flowing If the residual pressure is 10% less than the static pressure only one third of available water is being used and two thirds are still available If the difference is 15% or less two thirds of the water is being used FIRE 113-PPT-8-1-14 Calculations for Lines of Unequal Diameter and/or Length Estimating Hydrant Capacities (continued) If the difference is 25% or less half the water is being used If the difference is more than 25% additional flow would be limited to less than the amount being used FIRE 113-PPT-8-1-15 Example A static pressure on the compound gauge of 60 psi was measured when the hydrant was opened. When the first 3” line flowing 400 GPM is put in service, residual pressure decreased to 54 psi, a drop p of 6 p psi. The remaining g available flow is: 60 (static) – 54 (residual) ÷ 60 (static) 6 ÷ 60 = 10% drop This indicates that one third of the water is being used and supply for two more lines (or 800 GPM) is available FIRE 113-PPT-8-1-16 Student Performance Objective Given information from discussion, handouts, and reading materials, demonstrate proficiency in fireground hydraulic calculations and describe the importance and use of flow meters and electronic pump p p controllers. FIRE 113-PPT-8-1-17 Review Fireground Hydraulic Calculations Flow Meters and Electronic Pump Controllers Calculations for Lines of Unequal Diameter and/or Length FIRE 113-PPT-8-1-18